ADDENDUM FIVE SECTION 16418 LOW HARMONIC VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 Description ADDENDUM FIVE A. This specification describes an AC variable speed/torque Direct Torque Control™ (DTC™) Drive used to control the speed/torque of a NEMA design B induction motor. The drive must also provide an optional operational mode for scalar or V/Hz operation. B. The Drive shall be manufactured by a firm with at least ten (10) years experience in the production of this type of equipment. C. Refer to Section 17300 for control scenarios. 1.2 Quality Assurance A. The Drive manufacturing facility shall be ISO 9001 and 14001 certified. B. The Drive shall be UL listed, or Canadian UL listed, or CSA listed and comply with EMC Directive 89/336 EEC, Low Voltage Directive 73/23 EEC and Machinery Directive 98/37 EC in accordance with the European Union’s CE directive. C. All printed circuit boards shall be completely tested and burned-in before being assembled into the completed Drive. The Drive shall then be subjected to a preliminary functional test, minimum one (1) hour burn-in and computerized final test. The burn-in shall be at 104F (40C), at full rated load, or cycled load. Drive input power shall be continuously cycled for maximum stress and thermal variation. D. The Drive shall utilize efficient IGBT technology throughout the entire Drive manufacturer’s Power and Voltage range. E. The Drive shall utilize the same communications architecture, utilizing plug-in communications cards, for high-speed noise immune connectivity throughout the entire Drive manufacturer’s Power range. F. The Drive manufacturer shall have an analysis laboratory to evaluate the failure of any component. The failure analysis lab shall allow the manufacturer to perform complete electrical testing, x-ray components, and decap or delaminate components and analyze failures within the component. G. The Drive shall utilize surface mount technology in the manufacturing of internal printed circuit boards and electronics, for maximum reliability. 1.3 Submittals A. The Submittals shall include the following information. 1. Outline Dimensions. 2. Weight. 3. Compliance to IEEE 519 - Harmonic analysis for particular jobsite including total voltage harmonic distortion and total current distortion. The Drive manufacturer shall 5-12-dp 16418 – Low Voltage VFD - 1 of 10 provide calculations, specific to this installation, showing total harmonic current distortion (TDD), at the Point of Common Coupling (PCC), is less than required. PART 2 - PRODUCTS 2.1 Manufacturer A. 2.2 The Drive shall be manufactured by ABB, Model ACS-800-37-0210-5-C129-H350-H352K466; no equals allowed. Adjustable Frequency Drives A. The Drive shall be solid state, with a Pulse Width Modulated (PWM) output. The drive shall be a Direct Torque Control (DTC) AC to AC converter utilizing the latest isolated gate bipolar transistor (IGBT) technology. The Drive shall employ Direct Torque Control (DTC) inner loop torque control strategy that mathematically determines motor torque and flux every 25 microseconds (s) (40,000 times per second). The drive must also provide an optional operational mode for scalar or V/Hz operation. The drive shall eliminate low order harmonics with an active converter controlled with DTC and high order harmonics with an LCL line filter. B. Ratings 1. The Drive shall be rated to operate from 3-phase power at 230VAC to 500VAC +10/10%, 48Hz to 63Hz. The Drive shall employ a full wave rectifier to prevent input line notching and operate at a fundamental (displacement) input power factor of 0.97 at all speeds and loads. The Drive efficiency shall be 98% or better at full speed and load. An internally mounted AC line reactor or DC choke shall be provided to reduce input current harmonic content, provide protection from power line transients such as utility power factor correction capacitor switching transients and reduce RFI emissions. 2. The overvoltage trip level shall be a minimum of 30% over nominal, and the undervoltage trip level shall be a minimum 35% under the nominal voltage. 3. Output voltage and current ratings shall match the adjustable frequency operating requirements of standard 460VAC, 3ph, 60Hz, NEMA design A or NEMA design B motors. The overload current capacity shall be 110% of rated current for one (1) minute out of five (5). Output frequency shall be adjustable between 0Hz and 300Hz. Operation above motor nameplate shall require programming changes to prevent inadvertent high-speed operation. The drive’s switching pattern shall be continually adjusted to provide optimum motor flux and avoid the high-pitched audible noise produced by motors energized by conventional PWM drives. The drive shall be furnished in a UL Type 1 listed enclosure rated for operation at ambient temperatures between 0 and 40C at an altitude not exceeding 3300 feet, with relative humidity less than 95% and no condensation allowed. The drive shall be protected from atmospheric contamination by chemical gasses and solid particles pre IEC 721-3-3, classes 3C2 and 3S2. The drive shall be protected from vibration per IEC 68-2-6 (max. sinusoidal displacement 1 mm, 5Hz to 13.2Hz and max. acceleration 7m/s2, 13.2Hz to 100Hz). C. Control Functions and Adjustments 1. An intelligent start-up assistant shall be provided as standard. The Start-up assistant will guide the user through all necessary adjustments to optimize operation and will 5-12-dp 16418 – Low Voltage VFD - 2 of 10 include “plug and produce” operation, which recognizes the addition options/fieldbus adapters and provides the necessary adjustment assistance. of 2. Start-up data entries shall include motor nameplate power, speed, voltage, frequency and current. 3. A motor parameter ID function shall automatically define the motor equivalent circuit used by the sensorless vector torque controller. 4. A PID speed/torque loop regulator shall be provided with an autotune function as well as manual adjustments. 5. A selection of six (6) preprogrammed application macro parameter sets shall be provided to minimize the number of different parameters to be set during start-up. Macros included as standard are as follows: Factory Default, Hand/Auto, PID Control, Sequential Control, and Torque Control. A selection of two (2) user defined macros shall are also be available. 6. Start/Stop control functions shall include two (2) or three-(3) wire start/stop, coast/ramp stop selections, optional dynamic braking and flux braking. 7. The drive shall be capable of starting into a rotating load (forward or reverse) and accelerate or decelerate to reference without safety tripping or component damage (flying start). The drive shall also be capable of flux braking at start to stop a reverse spinning motor prior to ramp. 8. The drive shall have the ability to automatically restart after an overcurrent, overvoltage, undervoltage, or loss of input signal protective trip. The number of restart attempts, trial time, and time between reset attempts shall be programmable. 9. Accel/Decel control functions shall include two (2) sets of ramp time adjustments with linear and three (3) s-curve ramp selections. 10. Speed/Torque control functions shall include: a. Adjustable min./max. speed and/or torque limits. b. Selection of up to 15 preset speed settings or external speed control. c. Three (3) sets of critical speed lockout adjustments. d. A built-in PID controller to control a process variable such as pressure, flow or fluid level. e. Reference signal processing shall include increase/decrease floating point control and control of both speed/torque and direction using a “joystick” reference signal. Two (2) analog inputs shall be programmable to form a reference by addition, subtraction, multiplication, minimum selection or maximum selection. 11. Output control functions shall include. a. Flux optimization to limit the audible noise produced by the motor and to maximize efficiency by providing the optimum magnetic flux for any given speed/torque operating point. 5-12-dp 16418 – Low Voltage VFD - 3 of 10 b. Current and torque limit adjustments to limit the maximum Drive output current and the maximum torque produced by the motor. These limits shall govern the inner loop torque regulator to provide tight conformance with the limits with minimum overshoot. c. A torque regulated operating mode with adjustable torque ramp up/down and speed/torque limits. 12. The Drive shall be capable of sensing a loss of load (broken belt / broken coupling) and signal the loss of load condition. The drive shall be programmable to signal this condition via a keypad warning, relay output and/or over the serial communications bus. Relay output shall include programmable time delays that will allow for drive acceleration from zero speed without signaling a false underload condition. 13. The Drive shall have programmable “Sleep” and “Wake up” functions to allow the drive to be started and stopped from the level of a process feedback signal. 14. Two (3) programmable critical frequency lockout ranges to prevent the AFD from operating the load continuously at an unstable speed. D. Static and Dynamic Performance 1. Open loop static speed regulation shall be 0.1% to 0.3% (10% of motor slip). When motor speed feedback is provided from a suitable encoder, closed loop speed regulation shall be 0.01% or better. Dynamic speed accuracy shall be 0.3-0.4 %-sec or better open loop and 0.1-0.2 %-sec or better-closed loop. E. Operator Control Panel (Keypad) 1. Each Drive shall be equipped with a front mounted operator control panel (keypad) consisting of a four- (4-) line by 20-character back-lit alphanumeric display and a keypad with keys for Run/Stop, Local/Remote, Increase/Decrease, reset, menu navigation and parameter select/save. 2. All parameter names, fault messages, warnings and other information shall be displayed in complete English words or standard English abbreviations to allow the user to understand what is being displayed without the use of a manual or crossreference table. 3. The Display shall have contrast adjustment provisions to optimize viewing at any angle. 4. The control panel shall include a feature for uploading parameter settings to control panel memory and downloading from the control panel to the same drive or to another drive. 5. All Drives throughout the entire power range shall have the same customer interface, including digital display, and keypad, regardless of horsepower rating. 6. The keypad is to be used for local control, for setting all parameters, and for stepping through the displays and menus. 7. The keypad shall be removable and insertable under drive power, capable of remote mounting, and shall have its own non-volatile memory. 5-12-dp 16418 – Low Voltage VFD - 4 of 10 8. During normal operation, one (1) line of the control panel shall display the speed reference, and run/stop forward/reverse and local/remote status. The remaining three (3) lines of the display shall be programmable to display the values of any three (3) operating parameters. At least 26 selections shall be available including the following: a. Speed/torque in percent (%), RPM or user-scaled units. b. Output frequency, voltage, current and torque. c. Input voltage, power and kilowatt hours. d. Heatsink temperature and DC bus voltage e. Status of discrete inputs and outputs f. Values of analog input and output signals g. Values of PID controller reference, feedback and error signals h. Control interface inputs and outputs shall include: F. I/O Capabilities 1. Six (6) discrete inputs, all independently programmable with at least 25 input function selections. Inputs shall be designed for “dry contact” inputs used with either an internal or external 24 VDC source. 2. Three (3) form C relay contact outputs, all independently programmable with at least 30 output function selections. Relay contacts shall be rated to switch 2 Amps at 24VDC or 115/230VAC. Function selections shall include indications that the drive is ready, running, reversed and at set speed/torque. General and specific warning and fault indications shall be available. Adjustable supervision limit indications shall be available to indicate programmed values of operating speed, speed reference, current, torque and PID feedback. 3. Three (3) analog inputs, one (1) +/- 0VAC - 10VAC and two (2) 4mA - 20mA, all independently programmable with at least ten (10) input function selections. A differential input isolation amplifier shall be provided for each input. Analog input signal processing functions shall including scaling adjustments, adjustable filtering and signal inversion. If the input reference (4-20mA or 2-10V) is lost, the AFD shall give the user the option of the following: (1) stopping and displaying a fault, (2) running at a programmable preset speed, (3) hold the AFD speed based on the last good reference received, or (4) cause a warning to be issued, as selected by the user. The drive shall be programmable to signal this condition via a keypad warning, relay output and/or over the serial communications bus. 4. Two (2) analog outputs providing 4mA to 20mA signals. Outputs shall be independently programmable to provide signals proportional to at least 12 output function selections including output speed, frequency, voltage, current and power. G. Ethernet communications 1. Provide Ethernet communication capability for remote monitoring of the VFD. 5-12-dp 16418 – Low Voltage VFD - 5 of 10 H. Microsoft Windows-based software shall be available for drive setup, diagnostic analysis, monitoring and control. The software shall provide real time graphical displays of drive performance. I. Protective Functions 1. For each programmed warning and fault protection function, the drive shall display a message in complete English words or Standard English abbreviations. The five (5) most recent fault messages and times shall be stored in the drive’s fault history. 2. The drive shall include internal MOV’s for phase to phase and phase to ground line voltage transient protection. 3. Output short circuit and ground fault protection rated for 65,000 amps shall be provided per UL508C without relying on line fuses. Motor phase loss protection shall be provided. 4. The drive shall provide electronic motor overload protection qualified per UL508C. 5. Protection shall be provided for AC line or DC bus overvoltage at 130% of maximum rated voltage or undervoltage at 65% of min. rated voltage and input phase loss. 6. A power loss ride through feature will allow the drive to remain fully operational after losing power as long as kinetic energy can be recovered from the rotating mass of the motor and load. 7. Stall protection shall be programmable to provide a warning or stop the drive after the motor has operated above a programmed torque level for a programmed time limit. 8. Underload protection shall be programmable to provide a warning or stop the drive after the motor has operated below a selected underload curve for a programmed time limit. 9. Over-temperature protection shall provide a warning if the power module temperature is less than 5C below the over-temperature trip level. 10. Input terminals shall be provided for connecting a motor thermistor (PTC type) to the drive’s protective monitoring circuitry. An input shall also be programmable to monitor an external relay or switch contact (klixon). J. Motor Protection Relay with Temperature Monitoring and Alarm System 1. The motor protection relay shall have 10 RTD inputs and Ethernet communications. Provide SEL Part #071001B0X9X0X850200; no equals allowed. K. Harmonics and EMC 1. The AFD shall have an active line supply unit which controls the low order harmonic current drawn from the power line. 2. The AFD shall have an internal LCL line filter to eliminate high order harmonic current, provide voltage boost when the line is low and provide Power Factor control. 3. The input current to the AFD shall have a total harmonic content less than 5% of the AFD’s rated input on any power system and under all operating conditions. The input 5-12-dp 16418 – Low Voltage VFD - 6 of 10 Power Factor shall be approximately unity under all conditions. AFD’s which use filters or multi-pulse transformers external to the AFD shall not be allowed. 4. The AFD shall have an EMC filter which meets requirements for 2nd environment, unrestricted distribution according to EN 61800-3. L. Enclosure 1. Enclosure shall be UL Type 1 filtered. 2. Enclosure shall have bottom entry and exit of cables. PART 3 - EXECUTION 3.1 Harmonic Distortion A. The variable frequency drive manufacturer shall perform a comprehensive pre-equipmentselection harmonic study to determine harmonic voltage and current distortion and the ratings and characteristics of individual tuned filters or other attenuation equipment if these are necessary to achieve the required distortion limits. In conducting the study, the manufacturer shall calculate the total harmonic voltage distortion at the point of common coupling which will be the 480 volt bus supplying the VFDs using an assumed source impedance of 3.5 percent unless stated otherwise in the specifications or drawings. B. The harmonic distortion values contributed by operation of all variable frequency drive motor-loads operating at full load shall be: 1. Maximum Allowable Total Harmonic Voltage Distortion (THVD) Contribution: 3 percent of the fundamental. 2. Maximum Allowable Total Harmonic Current Demand Distortion (THID) Contribution: 8 percent of the combined load current of the main feeder supplying all 480 volt loads. C. The Owner shall review and approve in writing, the harmonic study before equipment manufacturing is begun. 3.2 Source Quality Control A. Testing and Test Reports: 1. Testing shall be per manufacturer’s standard. 2. A copy of the test reports shall be provided as part of the Closeout documentation. B. Verification of Performance: 1. A representative of the Owner may witness tests. Variable frequency drive manufacturer shall notify the Owner 2 weeks in advance and shall provide testing procedures to the Owner 4 weeks prior to actual testing. Failure of a test shall result in rejection of the equipment until performance is in compliance with these specifications. 5-12-dp 16418 – Low Voltage VFD - 7 of 10 2. Certification on materials and records of shop tests necessary for the inspector to verity that the requirements of these specifications are met shall be made available to the inspector. 3. Submit signed and dated certification that all of the factory inspection and testing procedures described herein have been successfully performed by the Contractor prior to shipment. 3.3 Field Quality Control A. Provide the services on an experienced, factory trained technician or service engineer of the variable frequency drive manufacturer at the jobsite for a minimum of 2 days for startup of each VFD beginning at a date mutually agreeable to the Contractor and the Owner. One additional day shall be provided for training. The technician shall be on duty at the site for at least 8 hours per day and shall be available 24 hours per day when required to advise concerning special problems with equipment and systems. B. Include in the bid an allowance for factory-trained service personnel to supervise field installation, inspect, make final adjustments and operational checks, make functional checks of spare parts, and prepare a final report for record purposes. Adjust control and the Owner has accepted instrument equipment until this equipment has been field tested by the Contractor and the results of these tests. C. Include in the bid the training of personnel in the operation and maintenance of each furnished variable frequency drive control system. For the purpose of this training section of the Specifications, a system is by definition a group of driven equipment which all serve a common function (e.g., filter influent pumps, chlorine mixers, flocculators). 3.4 Maintenance A. Spare Parts: As a minimum, furnish and list the following spare parts in the Bill of Material: 1. One set of all power and control fuses and indicating lamps for each variable frequency drive. 2. One fully functional main control circuit board. 3. One of each inverter power semiconductor for each rating supplied for each variable frequency drive. B. Tools and Equipment: Variable frequency drive manufacturer shall identify and supply special tools or test equipment necessary to perform maintenance or repair tasks. C. Field Services: Manufacturer shall describe the field service system available to support the proposed variable frequency drive system. As a minimum describe: 1. Type of technical support available (e.g. system engineering and technician). 2. Location of field service personnel (maximum 100 miles). 3. Field service daily rates in dollars per hour and dollars per day. 4. Guaranteed response time to service requests. 3.5 5-12-dp Acceptance Tests 16418 – Low Voltage VFD - 8 of 10 A. Final Inspection: The Contractor to perform and submit the results of a final comprehensive field performance survey after equipment installation. B. Performance Verification. 1. The Contractor shall field measure actual harmonic distortion and verify with tests acceptable to the Owner after satisfactory full-load operation. Test methods shall be acceptable to the Owner. 2. As part of the specified harmonic studies and measurement for this project, use frequency scan analysis to identify and correct resonance conditions in the electrical distribution system at no additional cost to the Owner. 3. Measurements shall include harmonic voltage and current spectra and individual and total harmonic distortions. C. System Performance: 1. During the three-week period between final inspection and delivery of the test and as-built documentation, City of Santa Ana shall validate operation of the variable frequency drive system by regular inspection during workdays. 2. Completion of the installation, final inspection, receipt of the test and as-built documentation, and successful performance of the system for three-week period shall constitute acceptance of the system. 3.6 Warranty A. With a certified start-up, warranty shall be 60 months from the date of start-up. warranty shall include all parts, labor, travel time, and expenses. The END OF SECTION 5-12-dp 16418 – Low Voltage VFD - 9 of 10 THIS PAGE INTENTIONALLY BLANK 5-12-dp 16418 – Low Voltage VFD - 10 of 10 SECTION 16620 STANDBY GENERATOR ADDENDUM FIVE PART 1 - GENERAL 1.1 Work Included A. This specification outlines the requirements for installing and acceptance testing for a complete and operable prototype tested standby diesel generator set as furnished by the CITY. Generator shall be outdoors. B. The manufacturer will have available prototype test results for the assembled enginegenerator set. Individual component tests for the major components are not acceptable as a substitute for prototype testing of the complete and assembled engine generator set. All the equipment shall be new, and of current design and shall be constructed in accordance with the applicable requirements of the IEEE, NEMA, NEC, UL, and ANSI standards. C. Equipment and materials will be new and delivered to the job site factory tested and ready for installation. The work includes the following: 1. Install City furnished engine-generator set with mounted and loose accessories as described herein and shown on the drawings. 2. Furnish tests, documents and services as specified. 3. Furnish fuel, oil and antifreeze for testing and final fill. D. The specifications and drawings describe the system, but do not purport to cover all required details. Provide all appurtenances required, whether specifically noted herein or not. It shall be the Contractor’s responsibility to coordinate with the generator supplier to determine what field installation requirements will be necessary to make the equipment complete and operable. E. The engine generator will be equipped with the necessary devices to meet current SCAQMD regulations for the operation of the submitted diesel generator. Documentation will list current Tier requirements and particulate filter. Contractor shall obtain a general permit registration number to submit application, pay for, and obtain a South Coast Air Quality Management District (SCAQMD) permit to construct and operate the standby generator for the first year of operation. The generator fuel fill system shall meet the requirements of the local fire department. 1. Air Emissions: a. The CITY shall be solely responsible for providing a system that complies with BACT standards at the time of equipment purchase. At a minimum, the engines will be a minimum of Tier 3 Certified. b. CITY will provide a particulate filter system as required by AQMD to maintain pollutants below permitted value to allow operation in a “Sensitive Receptor’ location. Particulate filter shall be capable of reduction of pollutants level by at least 70%. c. CITY will submit certificate or “Source Test Report” for engine demonstrating compliance with the BACT standards at the time of equipment purchase with the draft permit applications. 5-12-dp 16620 – Standby Generator - 1 of 12 F. 1.2 Factory Engineer: CITY will coordinate services of factory-trained Service Engineer, specifically trained on type of equipment specified. Contractor is responsible for the installation, commissioning, startup, and acceptance testing for the diesel generator. The Contractor is also responsible for providing generator fuel and coolant. Submittal A. The following submittal and shop drawing information will be provided for CONTRACTOR reference. 1. Outline drawing for engine generator showing overall dimensions, power and control wiring entrance locations, fuel connections, anchor points, weight, breaker location and control panel. 2. Manufacturer data sheets for major components including engine, generator, protective controls, voltage regulator, fuel tank, batteries, charger, exhaust components, jacket water heater, load bank, and circuit breakers. 3. AC and DC wiring diagrams. 4. Vibration isolation certified calculations for Zone 4 installations. 5. Warranty and Prototype test documents. 6. Specification review noting compliance. 7. Computerized generator sizing report indicating steps. B. The CITY will furnish, at time of startup, four (4) Operating and Maintenance Manuals in three ring notebooks containing graphic diagrams, equipment data, spare parts lists, maintenance instructions and operator and service instructions. C. The following documents shall apply to the specified equipment. 1. IEEE 587 Surge Testing 2. NEMA MG1 Motors and Generators 3. NFPA 110 Emergency/Standby 4. NFPA 37 Installation and Use 5. UL 142 Fuel Tanks 6. UL 2200 Stationary Engine Generator Assemblies D. CONTRACTOR shall prepare on behalf of the CITY permit applications for “Authority to Construct” and “Permit to Operate” for the South Coast Air Quality Management District (SCAQMD). The permit applications shall include all necessary documentation required by SCAQMD including, but not limited to, shop drawings, source test requirements, etc. The CONTRACTOR shall submit these applications to the CITY within 90 days from the date of the Notice to Proceed. The CITY will then submit the permit applications to the SCAQMD within 5 working days from when received from the CONTRACTOR. If the application is deemed incomplete or not acceptable by the SCAQMD, the CONTRACTOR shall be responsible for responding to any comments or requests for information from SCAQMD and 5-12-dp 16620 – Standby Generator - 2 of 12 for preparing any and all revised permit applications for resubmittal to SCAQMD. Obtaining approved permits from SCAQMD shall be the sole responsibility of the CONTRACTOR. Any changes to equipment and/or emission requirements that occur after the initial submittal to SCAQMD shall be made at the CITY’s sole expense. PART 2 - EQUIPMENT 2.1 Acceptable Manufacturers A. Subject to compliance with requirements, provide diesel generators, documents, tests, and services by the supplier and the authorized distributor. Provide UL 2200 labeling. B. Authorized manufacturer's distributor shall be capable of providing equipment as specified, maintaining parts inventory; performing initial start-up, warranty and 24 hour emergency service. C. Warranty for all products against defects in material and workmanship shall be provided by the CITY for a period of 5 years from the date of Owner’s final acceptance. Warranty coverage shall include parts, labor, travel expenses, and labor to remove/re-install equipment. Engage supplier capable of administering the warranty service on all components of the emergency system specified herein. Refer to Division 1 for Warranty requirements. D. Manufacturer shall be Caterpillar, Onan, Generac, or Kohler. No substitutions allowed. 2.2 Ratings A. The generator set shall be diesel powered, 1800 RPM, minimum rated for continuous standby operation at ratings of 500 kw, 0.80 P.F., 277/480 volt, 3 phase 4 wire. Site conditions: 110 degrees F, 1500 Ft. Generator shall be minimally sized as shown with a maximum 20% voltage dip and 10% frequency dip. Provide generator sizing reports for submitted generator. 1. Step 1: eleven 1 hp FVNR motor; one 13.4 kw single phase linear miscellaneous load; two 3 hp FVNR motor; one 10 hp FVNR motor; one 3.3 kw single phase miscellaneous linear load; one 7.5 ton air conditioner; one 1.5 hp FVNR motor. 2. Step 2: one 200 hp VFD (125%CL) non-loaded pump. 3. Step 3: one 200 hp SSRV (300%CL) non-loaded pump. B. 2.3 The generator set shall be capable of picking up 100% load in one step in accordance with NFPA Standard 110. Engine and Equipment A. Engine shall be four cycle only, turbocharged/aftercooled as required. powered by #2 diesel, water cooled and B. Positive displacement, full pressure, lubrication oil pump. Full flow lubrication oil filters with replaceable spin-on canister elements and dipstick. C. Engine Oil Drain Extension. Provide 2-inch stainless steel oil pan drain extension with a 2inch stainless steel ball valve. The valve shall extend to the side of the frame for ease of maintenance during oil changes. 5-12-dp 16620 – Standby Generator - 3 of 12 D. Engine driven positive displacement fuel pump. Fuel filter with replaceable spin-on canister element. Replaceable dry element air cleaner with restriction indicator. E. Provide a filter/water separator on the engine, Raycor filter, DAHL, or equivalent, just ahead of the fuel filters to prevent condensation, or other water, present in the fuel from reaching the engine filters, pumps, or injectors. Construct of heat-resistant glass, with an aluminumperforated baffle, for easy viewing of the amount of water contained. F. Engine mounted battery charging alternator, 45 ampere minimum, and solid-state voltage regulator. Battery charger and fill control panel will be fed with a single 120 vac circuit. G. Jacket water heater, UL Listed, 120 volt, single phase dedicated circuit. H. Electronic governor with adjustable control. Frequency regulation shall be isochronous under varying loads from no load to full load. Frequency variation shall be + 0.25 percent of rated speed. 2.4 I. Provide engine mounted radiator including belt-driven pusher fan, water pump and thermostat. Cooling system shall be rated for full rated load operation in 122 degree F ambient conditions. Include a duct adaptor flange for attachment of an air duct. Guard rotating parts against accidental contact. J. The engine and generator shall be mounted on a heavy duty steel base with a battery tray with battery holddown clamps within the base. Electrical and fuel stub up shall be within the base rails. K. Provide a closed crankcase ventilation system by Racor CCV or equal. Engine Starting A. Electric starter. B. Control cranking with three crank attempts with rest periods, 75 second minimum. Lock out controls after third attempt. C. Battery, 12 VDC, lead acid type. Battery shall provide sufficient capacity to provide 100 seconds cranking. Provide insulated stranded copper conductors to connect batteries to generator starter. Mount batteries inside generator baserails. Provide battery tray and seismic straps. D. Battery charger, 120 VAC, 10 amp 12 VDC, voltage regulated on the skid. Equip with adjustable float and manual equalize charge settings, and DC voltmeter and ammeter. Provide contact and wiring for indication of low battery voltage on control panel. Charger voltage regulator shall be temperature compensated to prevent thermal damage to batteries. Provide Stored Energy Systems (SENS) NRG charger. 2.5 5-12-dp Generator A. The generator shall be single bearing, four pole, two-thirds pitch, dripproof, and air cooled. The rotor shall have amortisseur windings and be dynamically balanced. B. THD shall not exceed 5% of rated voltage at full load and no single harmonic shall exceed 3% of rated voltage at full load. 16620 – Standby Generator - 4 of 12 C. The exciter shall be brushless, three phase, with full wave silicon diodes, surge suppressor and exciter circuit breaker. D. Provide permanent magnet generator (PMG) for isolation and sustained 300% short circuit current for 10 seconds. Electronic current boost methods or CT boost methods are not acceptable. E. The insulation system for rotor, stator, exciter and PMG shall be Class H. Temperature rise shall not exceed 125 degrees C at full rating. F. The voltage regulator shall be 3 phase RMS sensing, temperature compensated, pulse width modulated and + 0.5% regulation with overvoltage and overexcitation protection. Overvoltage protection shall shut down regulator output on a sustained overvoltage of one (1) second; overexcitation protection shall shutdown regulator output if overloads exceed ten (10) seconds. The regulator shall allow frequency to decline to 58 Hz before correcting the output voltage in a linear volts/hertz manner. G. Shield generator, exciter and regulator to prevent radio frequency interference per provisions of BS.800 and VDE Class G and N. 2.6 Generator Control A. The CITY will provide a NEMA 1 enclosed control panel mounted on the generator with vibration isolators. Solid state components shall have surge suppression for protection. Provide panel lighting with ON/OFF switch. Indicating meters (2%) and devices shall include: 1. AC ammeter 2. AC voltmeter 3. Frequency meter 4. Phase selector switch with OFF position for meter display of current and voltage in each generator phase. 5. Voltage adjustment 5% 6. Running time meter 7. Oil pressure gauge 8. Water temperature gauge 9. DC voltmeter B. Controls shall shut down and lock out the engine upon: 1. Overcrank 2. Overspeed 3. Low oil pressure 4. High engine temperature 5-12-dp 16620 – Standby Generator - 5 of 12 C. Provide DC powered engine monitor with the following lights on the control panel: 1. Run green 2. Low oil pressure (prealarm) amber 3. High engine temp (prealarm) amber 4. Low engine temp (prealarm) amber 5. Low fuel (prealarm) amber 6. Fuel leak (alarm) red 7. Low oil pressure (shutdown) red 8. High engine temp (shutdown) red 9. Overcrank (shutdown) red 10. Overspeed (shutdown) red 11. Not in Automatic (flashing) red 12. Low coolant level (alarm) red D. Provide the following SCADA dry contacts: 1. Run 2. Fail 3. Low fuel 4. Low battery 5. Breaker Open E. Operation of shut down circuits shall be independent of pre-alarm circuits. Panel mounted switches shall reset the engine monitor and test all the lamps. F. Provide three position panel mounted switch (RUN-STOP-AUTO) to stop the engine in the STOP position, start and run the engine in the RUN position, and allow the engine to start and run by closing a remote contact, and stop by opening the remote contact when in the AUTO position. G. Provide two-position load bank control marked “on” and “off”. H. Provide cranking cycle function, consisting of three crank attempts followed by rest periods. Failure to start after three attempts (75 seconds) shall shut down and lockout engine. Two means of cranking termination after engine start shall be provided, one as a backup to the other. I. 5-12-dp Provide distribution circuit breaker as shown on drawings. Breaker shall U.L. listed molded case, with overload and overcurrent trip. Breaker shall be rated for service entrance. Provide auxiliary contact for breaker open position. 16620 – Standby Generator - 6 of 12 J. 2.7 The generator control panel shall have Ethernet communications. Load Bank A. The generator unit set shall have a resistive load bank, which will operate only under exercising function of the generator. The total rating of the load resistors shall be not less than 50 percent of the full load kW rating of the generator to which it is connected, or larger, as required by engine generator manufacturer to maintain by unit warranty. The load shall be provided with a minimum of four load steps. B. The load bank shall be housed in a NEMA 1 enclosure, mounted integrally to the engine on the front radiator. The load bank's load chamber shall have the physical dimensions coordinated with the radiators duct flange. The radiator fans cooling capacity shall be increased as necessary to prevent excessive static pressure build-up caused by the load bank. C. Resisters shall be constructed of high temperature alloy capable of continuous operation at 1920 deg., and designed to operate at an average of 750°F. The resisters shall be assembled in a three-phase array with the phase-to-phase resister current balanced within 2%, and an overall kW tolerance within 5% of its normal rating. D. A circuit breaker shall be provided in the engine generator supplying the load bank, sized at 125% of the full load bank. Provide fuse protection for the individual load bank section. E. Provide automatic electric contactors, as required, to activate load bank, in the exercising mode. Provide all control interlocks with the automatic transfer switch for the unit, as required, to provide the following functions: 1. Transfer switch exercising time lock starts generator and brings load bank on-line. 2. Exercising function operates for pre-selected period of time with the load bank connected at 100% of load bank capacity. 3. At end of exercise period, load bank shall be automatically taken off line during engine cool-down. 4. If utility power outage occurs during the exercise period, the load bank shall immediately be de-energized before the emergency load automatic transfer switches change position; generator shall continue to run during the disconnect of the load bank. F. 2.8 5-12-dp Load bank systems shall be UL listed as manufactured by AVTRON, Simplex or equal. Sound Attenuated Enclosure and Exhaust System A. The CITY will provide a weather-protective and sound attenuated enclosure with removable or hinged doors to allow inspection and maintenance. Enclosure material shall be aluminum alloy or steel with a minimum thickness of 14 gauge. Lockable latches shall be of stainless steel. Doors shall have a common keyed latch. Provide two (2) sets of keys. B. Enclosure and engine exhaust system shall be sound attenuated to limit noise level when operating at full rated load to a maximum of 75 dB(A) at 23 feet in any horizontal direction from the center of the unit. Intake and discharge of cooling air shall be through top mounted openings that are covered for weather protection. Provide acoustical material on 16620 – Standby Generator - 7 of 12 internal walls and surfaces of the enclosure. External holes and opening in the enclosure shall be covered with galvanized or coated mesh to prevent entry of birds or rodents. C. A super-critical degree silencer shall be provided as part of the diesel particulate filter. Supplier shall furnish back pressure calculations for the installation, including the discharge piping, verifying that engine limitation is not exceeded. Silencer shall be arranged for horizontal mounting with bottom (side) inlet and end outlet. Provide a stainless steel bellows type flexible exhaust connector at the engine exhaust outlet. Provide suitable raincap or moisture drain. A "Critical Degree" silencer is considered to be one capable of attenuating engine exhaust noise component to 85 dba at 10 feet in a free-field environment. 2.9 Fuel Storage System A. The CITY will provide a sub-base mounted fuel storage tank capable of supporting the generator set at rated load for 20 hours. The tank shall not extend beyond the generator end of the base rails. Provide access for electrical conduit for the circuit breaker, battery charger and jacket water heater power, and control wiring from below. Tank shall be built and labeled in accordance with UL-142. Mounting feet shall provide clearance between bottom of tank and foundation. B. Tank features shall include: 1. 2 inch filler neck and locking cap 2. Engine supply and return openings and draw tubes 3. Emergency vents per UL for both primary and secondary containment with approved caps. Vents shall extend to outside of enclosure 12’ above generator pad. 4. Tank leak port 5. Fuel level indicator gauge, direct reading type 6. Low fuel level alarm switch, set at 4 remaining hour’s capacity 7. Secondary containment, totally closed design, by double wall construction. Provide alarm contact for liquid in containment basin. Wire contact to alarm light in the generator control panel. 8. 5 gallon Fill/Spill containment to contain fuel overfill spills that may occur during fillup. 2.10 Seismic Restraint A. 2.11 Provide an IBC seismically approved generator with mounting details. Spare Parts A. The CITY will provide spare parts as recommended by manufacturer for six months of operation for engine-generator set plus the following: 1. Three filters of each type for all services. 2. Three fuses of each type and rating used. 5-12-dp 16620 – Standby Generator - 8 of 12 3. Three indicator light bulbs of each type and rating used. B. Pack spare parts in suitable containers or boxes bearing labels clearly designating contents and piece of equipment for which they are intended. C. The CITY will deliver spare parts at same time as equipment to which they pertain. Properly store and safeguard spare parts until completion of the work at which time deliver them where directed by the Engineer. PART 3 - EXECUTION 3.1 Examination A. 3.2 Examine areas and conditions under which diesel generators are to be installed and notify of conditions detrimental to proper completion of the work. Do not proceed with the work until unsatisfactory conditions have been corrected. Delivery, Storage and Handling A. Deliver equipment properly packaged and mounted on skids to facilitate handling. Deliver with recommended oil and coolant installed. B. Store equipment to protect from weather and construction traffic. Wherever possible, store indoor; where necessary to store outdoors, store above grade with weather-protective enclosure or plastic wrapping. C. Handle equipment carefully to prevent physical damage. Do not install damaged equipment; remove from site and replace damaged equipment with new. 3.3 Installation of Diesel Generator Set A. Install diesel generator as indicated, in accordance with the equipment manufacturer's written instructions, and with recognized industry practices, to ensure that the unit fulfills requirements. Comply with NFPA and NEMA standards pertaining to installation of engine generator sets and accessories. B. Install generator suitable for Seismic Design Category’s D and F conditions. The CITY will furnish certified anchor calculations. C. Coordinate with other work, including raceways, electrical boxes and fittings, exhaust piping, and accessories, as necessary to interface installation of engine generator equipment work with other work. 3.4 Grounding A. 3.5 Provide equipment grounding connections for diesel generator as indicated. Tighten connections to comply with tightening torques specified in UL 486A to assure permanent and effective grounding. Ground neutral at the generator (separately derived source). Production Tests A. The CITY will provide certified factory production tests on the equipment performed at rated load and 0.8 PF. Tests shall include: 1. Steady-state voltage and frequency analysis 5-12-dp 16620 – Standby Generator - 9 of 12 2. Rated load at rated PF 3. Maximum power analysis 3.6 Field Test A. Engage the services of the supplier's factory trained technicians to perform testing including furnishing all test equipment. B. Submit notification of test schedule and procedure for approval by the Engineer not less than two (2) weeks prior to the scheduled date. Notify all interested parties of the time and date for the testing. C. All tests shall be made with the door to the enclosure in which the generator is located closed. 1. Verify all electrical, exhaust, fuel and water connections for proper size, continuity, phase rotation, and tightness of fittings. Check all fluids for appropriate levels. 2. Verify operation of jacket water heater, battery charger, automatic transfer switch and remote alarm connections. 3. Start up engine and make initial check of voltage, frequency, battery charging, oil pressure, water temperature and safety shutdowns. D. Connect a load bank at 100% of generator rating at unity power factor. 1. Generator set shall be run for 1 hour at 75% then 1 hour at 100%. Record every 15 minutes water temperature, oil pressure, ambient air temperature, voltage, current, frequency, and kilowatts. Test all safety devices using methods recommended by the manufacturer. At conclusion of test allow 10 minute unloaded cooldown before shutdown. E. Test generator controls in Remote position using the building load. Simulate failure of the normal power source by opening normal source breaker. Engine generator shall start and assume load within 10 seconds. 1. Run the generator for 30 minutes on building load. 2. Record starting step voltage and frequency drops and provide report. F. Any failure or malfunction of equipment or controls during any time of test procedure shall be corrected and retested at no additional cost to Owner. G. Production and field test results shall be documented and forwarded to the Engineer. Include test reports in O & M manuals. H. Training by the CITY: 1. Training session: The CITY will provide one 4 hour classroom session for operations and maintenance Provide one 4 hour field session for operations and maintenance. 2. Manufacturer shall submit a lesson plan to include operator training and maintenance training at least two weeks prior to the training sessions. 5-12-dp 16620 – Standby Generator - 10 of 12 3. Training shall include both classroom and field "hands-on" training. Both types of training shall provide full coverage of all techniques for the operators to fully understand the generator operation, and for the maintenance personnel to fully understand the requirements for preventive and corrective maintenance. 4. Acceptable operation and maintenance manuals must be onsite and available when training sessions are implemented. I. At the conclusion of field testing, Contractor shall, at his expense, fill the fuel tank with Diesel fuel. END OF SECTION 5-12-dp 16620 – Standby Generator - 11 of 12 THIS PAGE INTENTIONALLY BLANK 5-12-dp 16620 – Standby Generator - 12 of 12 SECTION 17000 GENERAL INSTRUMENTATION AND CONTROL PART 1 - GENERAL 1.1 ADDENDUM FIVE Description A. This section of the specifications includes the requirements for the materials, testing, installation, and configuration of the instrumentation and Process Control System (PCS), including the programmable logic control system and local operator interface, as specified herein and indicated on the drawings. B. Programming of the Central HMI system will be done by others under separate contract. C. The Contractor shall provide, configure, calibrate, test, and commission all components of the instrumentation, control, communications, and network systems supplied unless specifically noted otherwise (UNO). The Contractor shall place the completed systems in operation, including tuning loops and making final adjustments to instruments as required during facility start-up. The Contractor shall provide the services of instrument technicians for testing and adjustment activities. D. Division 17 is an extension of, and includes all of the requirements of Division 16, Electrical. All work performed under Division 17 shall also comply with the applicable sections of Division 16 as well as the general provisions of Division 1. E. Division 17 Organization: The requirements for the PCS are described in this Section, the drawings, and the following Division 17 Sections 1. Section 17100 - Instrumentation Cabinets and Enclosures 2. Section 17300 - Programmable Logic Controllers and Programmable Operator Interfaces. 3. Section 17350 – Telemetry System Equipment 4. Section 17600 – Testing and Commissioning 5. Section 17700 – Programming F. These specifications shall not be interpreted as permission or direction to violate any governing code or ordinance. Equipment, materials, and workmanship shall comply with the latest revisions of the following codes and standards: 1. Instrumentation: International Society of Automation (ISA). 2. Wiring: National Electrical Code (NEC), ISA S5.3 and S5.4, 1976. 3. Control Panels and Equipment: NEMA, UL, and ANSI. 4. Piping: ANSI B31.3 (instrumentation piping). 1.2 Related Work Specified Elsewhere A. 10-15-dp One-year Guarantee: General Provisions. 17000 – General Instrumentation and Control - 1 of 24 B. Permits and Licenses: General Provisions. C. General Electrical Requirements: 16010 1.3 Abbreviations A. General 1. ANSI: American National Standards Institute 2. ATS: Automatic Transfer Switch (associated with backup generator) 3. FAT: Factory Acceptance Test 4. FM: Factory Mutual 5. HMI: Human-Machine-Interface. The software providing the graphical user interface to the control system 6. GUI: Graphical User Interface. 7. IP: Internet Protocol 8. ISA: International Society of Automation 9. NEMA: National Electric Manufacturers Association 10. I/O : PLC Inputs and Outputs. 11. O&M: Operations and Maintenance. 12. P&ID: Piping and Instrumentation Diagram. 13. PCS: Process Control System 14. PLC: Programmable Logic Controller. 15. RAT: Reliability Acceptance Test 16. SAT: Site Acceptance Test 17. SCADA: Supervisory Control and Data Acquisition. 18. SHC: Sodium Hypochlorite 19. UPS: Uninterruptible Power Supply. 20. VAI, VAO: Virtual PLC analog input and analog output 21. VDI, VDO: Virtual PLC discrete input and discrete output B. Definitions 1. PCS Integrator: An Integrator meeting the experience qualifications detailed in 1.5 of this Section and having, as a minimum, responsibility for integrating, configuring, 10-15-dp 17000 – General Instrumentation and Control - 2 of 24 testing and documenting, the PLC, Local HMI, networks, devices connected to the network, and instruments. 2. Central: For this Contract whenever the term “Central” is used it means the City of San Ana’s Water Utility Operations Center at 220 Daisy Street, Santa Ana, California. 3. Virtual PLC I/O: PLC inputs and outputs that are read by the PLC or written by the PLC over a network connection such as Modbus, or Ethernet, via a PLC communications port. 1.4 Software Configuration A. The PCS subcontractor shall be responsible for software configuration, programming, and integration of the following as a minimum, to meet the requirements of these specifications: 1. The Modicon M580 series programmable logic controller (PLC). 2. The Magelis iPC series local HMI on the Main Control Panel. 3. The Ethernet and Modbus communications networks and network devices. 4. The variable frequency drives (VFDs) and solid state starters. 5. The single loop pressure controller and PID controllers configured within the PLC. 6. The Eaton Power meter 7. Other microprocessor based devices provided as part of this project. B. The PCS subcontractor shall be responsible for software configuration, programming and/or integration of Owner supplied systems including: 1. Control Panel for SA-2 2. Control Panel for City Well 29 3. Backup generator/ATS 4. SHC System C. The Integrator is to configure the PCS system to meet the following requirements. 1. Operator setpoints and pump duties can be set and changed by an Operator at the the Local Station HMI. The local HMI shall be configured for both monitoring and control. The PLC is to accept the most recent Operator set value/ instructions entered from the local HMI. The PLC is to update the HMI such that it always displays the current operational values and setpoints. 2. Access to the local HMI for all functions except viewing, to be protected by a password. 3. If communications with Central is lost, the station is to maintain automatic operation, using the last entered operator setpoints. The functionality of the Local HMI is to be unaffected by this loss of communications. 10-15-dp 17000 – General Instrumentation and Control - 3 of 24 1.5 Responsibility of Contractor and PCS Integrator A. PCS Integrator 1. The Contractor shall employ an experienced and well qualified PCS Integrator for the design and software configuration of the PLC, local Operator Interface, and communication networks. All systems shall be the responsibility of the one system supplier for all PCS hardware. The programmable logic control system installation and wiring connections to peripheral equipment and instruments shall be the responsibility of the PCS Integrator using qualified personnel possessing the necessary equipment and having experience with similar installations. 2. All instrumentation and industrial electronic systems and functions shall be provided under the supervision of a single PCS Integrator, chosen by the Contractor, who is regularly engaged in the design, configuration, and installation of similar systems of equal or greater scope and complexity. The PCS Integrator shall be enjoined by the Contractor as a Subcontractor. The assignment of specific responsibilities herein to the PCS Integrator shall not, in any way or under any conditions, diminish the Contractor's full and complete responsibility for all work performed and all materials installed under the contract. The contract between the Contractor and the PCS Integrator shall specifically require that the PCS Integrator conform to and meet all requirements specified in the contract documents. The assignment of the PCS Integrator as an equipment supplier shall not be acceptable. Programming of the PLC and the SCADA system may be performed by others, but the associated hardware will be supplied by the PCS Integrator. All equipment in the instrument and control system including network systems, field equipment, panels, work stations, server racks, control panels, and instruments will be the responsibility of the PCS integrator. The PCS Integrator will work with PLC/SCADA programmers to test, commission and start up the plant. B. Acceptable PCS Integrators: 1. The Control System shall be designed, constructed, and commissioned by full time or contract employees with a minimum of 5 years of experience and a minimum of one year with Integrator. The PCS Integrator shall configure and program all devices and equipment supplied to perform the functions indicated in the contract documents unless specifically noted otherwise. Engineering and site integration services shall only be provided by staff members directly employed by the PCS Integrator. Contract labor is not acceptable for engineering and programming services. 2. Evidence of such qualification, as well as notification of the assuming unit responsibility, shall be furnished to the City in writing prior to commencement of the work. The qualification evidence shall include the following: i. The Contractor shall have had a minimum of five years experience with the installation of industrial control systems similar in type to those to be installed in this project. ii. A complete list of similar installations including names and address of Department, name of project, and date of completion. iii. The name and qualifications of supervisory personnel to be directly responsible for the installation of the control system. 10-15-dp 17000 – General Instrumentation and Control - 4 of 24 iv. WITHHOLDING OF APPROVAL: The Contractor and the proposed PCS Integrator shall anticipate that the Project Representative may withhold approval of a proposed PCS Integrator or employee if, in the opinion of the Project Representative, the PCS Integrator or employee does not have the experience, capability, or an acceptable performance and execution record of similar projects in the past. No Contractor, PCS Integrator, or employee denied approval by the Project Representative shall be entitled to any extension of time or to any claim for damages related to any consequences resulting from the withholding of approval for any reason whatsoever. Applicable consequences may include but are not limited to associated extra or unanticipated costs, hindrances, delays, or complications of any kind. v. Instrumentation systems and control panels, with the exception of Pressure Reducing Valve Vault Instrumentation Systems and control panels, shall be supplied, installed, calibrated, and tested by the following pre-qualified suppliers: 10-15-dp Mr. Greg Beebe Brithinee Electric 620 South Rancho Avenue Colton, CA 92324 Phone- 909-825-7971 FAX- 909-825-2044 greg_beebe@mail.brithinee.com Russ Cotton CC-Powertec 31441 Santa Margarita Pwky., A390 Rancho Santa Margarita, CA 92688 Phone- 949-702-2434 FAX- 949-858-8587 russcotton@cox.net Dave Stone Control Technologies 6780 Katella Ave. Cyprus, CA 90630 Phone- 714-901-3500 FAX- 714-527-3335 davids@control- technologies.com Mr. Brian Downing Delta System Eng., Inc. 3550 North Central Avenue, Suite 1900 Phoenix, AZ 85012 Phone 602-266-4658 FAX 602-266-4953 bdowning@deltaseinc.com Mr. Peter Matthews Morrow-Meadows Corp. 665 Brea Canyon Walnut, CA 91789 Phone- 909-772-5428 FAX- 909-468-0593 pmatthews@morrow-meadows.com Mr. Joe Engle Neal Electric 13250 Kirkham Way Poway, CA 92604 Phone- 858-513-2525 FAX- 858-513-9499 jengle@nealelectric.com Mr. Salib Mansour Soffa Electric 5901 Corvette Street Commerce, CA 90040 Phone- 323-728-0230 FAX- 323-887-8076 salib.mansour@soffaelectric.com Mr. Jerry Horst TESCO Controls, Inc. 3434 52nd Avenue Sacramento, CA 95823 Phone- 916-395-8800 FAX- 916-429-2817 rmartinez@tescocontrols.com 17000 – General Instrumentation and Control - 5 of 24 Mr. Dean McLaughlin Trimax Systems 565 Explorer Brea, CA 92821 Phone- 714-255-8590 FAX- 714-255-1922 deanm@trimaxsystems.com C. Under this section, the PCS Integrator shall furnish and be responsible for the following: 1. Detailed Design of Control Panels: The drawings shall depict the functional and operational requirements of the control system and are at times diagrammatic. The PCS Integrator shall provide detailed, scaled design of all components on and in control panels and determine specific physical, thermal, and electrical requirements. 2. Detailed Design of Control Circuitry: The drawings shall depict the functional and operational requirements of the control system and are at times diagrammatic. The PCS Integrator shall be responsible for the final selection of all control system components, except for components specified as “no equal”, and all detailed circuit design and component interconnection required to meet the general and functional requirements indicated in or implied by the Drawings and Specifications. Where components are specified as “no equal”, the PCS Integrator shall provide all detailed design, including specification of miscellaneous or interfacing components required to integrate the specified component into the PCS Integrator’s control system design. It is the responsibility of the PCS Integrator to ensure that all devices selected, and the proposed interconnection of those devices, perform as intended to provide a complete and operable system meeting the requirements of the anticipated environment and area classifications. The PCS Integrator shall define all requirements for all interfacing components and shall supply all appurtenances, accessories, and all such devices which may be required for proper functioning and interfacing of components as part of the control system. An example of such appurtenances would be interposing relays or analog isolators. All such aforementioned necessary ancillary components not specifically indicated in the Contract Documents shall be considered incidental to the contract and shall be required just as if they had been specifically indicated. 3. INTERCONNECTING WIRING: The design of all interconnecting wiring of control equipment, including remote control panels, packaged equipment panels, mechanical equipment with control components, etc. Provide PLC I/O schematics for each PLC slot and Motor Starter schematics for each starter unit in the MCCs showing all the external and internal wiring. 4. INTEGRATION TESTING: Integration testing of all system and related components simultaneously in the PCS Integrator’s facility. This testing shall include all panels, instruments, process switches, test fixtures, MCCs, motor controllers, available equipment packages, communications and networking equipment, SCADA system hardware and software (UNO), PLC system hardware and software (UNO), etc. Per Section 17600. 5. COORDINATION WITH GC: Coordinate with the Contractor for specific requirements and locations of raceway penetrations and field wiring in control panels. The PCS Integrator shall supply the Contractor with all necessary detailed installation drawings and/or written instruction for installation of all control components and sensing devices as required for proper system operation. 6. CALIBRATION: Calibration of all field instruments UNO. Per Section 17600. 10-15-dp 17000 – General Instrumentation and Control - 6 of 24 7. COMMUNICATIONS AND NETWORKS: Set up, configuration, test, and verification of all communications equipment, channels, and networks including new and reused communication circuits. Integration with the City’s existing Dynac SCADA system shall be coordinated with the City’s SCADA system service provider, Kapsch. Contractor shall solicit the services of Kapsch during control system development, configuration, testing, and validation tasks associated with integration with the City’s Dynac SCADA system. 8. STARTUP AND TESTING: System start up, commissioning, functional testing following installation. Per Section 17600. 9. INSTRUMENTS: Provide all instruments specified unless specifically noted otherwise. Some instruments shall be provided by packaged equipment vendors. The PCS Integrator shall integrate vendor provided instruments and equipment. 10. CONFIGURATION Configure all supplied devices, equipment, and software unless specifically noted otherwise. All computers are to be configured for application programming by others. Configuration and programming of devices and equipment supplied as a part of packaged systems shall be provided by the vendor of each packaged system. 11. EQUIPMENT SUBMITTAL REVIEW: Review all equipment and packaged system submittals which include Division 17 items. Notify the Contractor of any and all needed modifications to submitted equipment, package system scope of services or supply, or PCS Integrator supplied equipment required to accommodate and integrate submitted equipment into the PCS Integrator’s work. Specifically note how submittals which include variances from the contract documents will impact PCS Integrator provided control panels and MCC's if accepted by the contractor. 12. Spare parts. 13. Special tools and test equipment required by the supplier. 14. Operator training. 15. Warranty (one year from City issuance of Notice of Completion) i. The PCS Integrator shall be solely and completely responsible for all maintenance of control systems they supply from time of installation to the date of substantial completion of all work under the contract. The PCS Integrator shall correct all deficiencies and defects and make any and all repairs, replacements, modifications, and adjustments as malfunctions or failures occur. The PCS shall perform all such work required or considered to be required by the owner to properly maintain the system. ii. The PCS Integrator shall make any and all repairs, replacements, modifications, and adjustments required to eliminate any and all defects in design, materials, and workmanship which are discovered within the one year guarantee period. The PCS Integrator shall begin all repairs, replacements, modifications and adjustments within twenty-four (24) hours of notification by telephone by the owner and shall complete such repairs, replacements, modifications and adjustments within forty-eight (48) hours of notification. 10-15-dp 17000 – General Instrumentation and Control - 7 of 24 iii. The PCS Integrator shall anticipate that the Owner may delay acceptance of all work under the contract if, in the judgment of the Owner, malfunctions or failures in operation of the supplied control system repeatedly occur after start-up to an unacceptable extent. The PCS Integrator shall not be entitled to an extension of time or to any claim for damages because of hindrances, delays, or complications caused by or resulting from delay by the owner in accepting the work because of malfunctions or failures in operation of the supplied control system. 16. Shipping and receiving. D. All calibration and final checkout of the instrumentation and programmable logic control system shall be witnessed by the City's Representative to determine if the system complies with the contract documents. Instrumentation calibration by the Contractor shall include both new and existing instruments, PCS equipment, and devices that are part of the system. E. The PCS Integrator shall be directly responsible for the coordination and integration of the control system with motor controls, packaged equipment controls, and other related equipment. The PCS Integrator shall be responsible to obtain submittal information on equipment specified or provided by other suppliers or disciplines and to integrate all the equipment into the control system to form a complete working system as outlined by the Contract Documents. F. The PCS Integrator shall communicate directly with the manufacturer(s) and supplier(s) of all related equipment to determine all details of the equipment that may influence or affect the control system. The PCS Integrator shall determine all requirements for and shall cause integration of the control system into a unified operating system. All correspondence shall include Carbon Copying (cc:) the General Contractor and City Project Manager. G. The system supplier will provide PLC programs as required by the contract documents. Descriptions of the system operation and PLC functions are provided in Sections 17300, 17700, and the Contract drawings, to help the Contractor understand the complete system and its operation. H. The PCS Integrator shall: 1. Provide a PLC and HMI system whose input and output configuration complies with the requirements of the contract documents, including specific I/O register assignments when applicable. 2. Notify the Owner of any changes to the input/output configurations described by the contract documents at the time of submittal of shop drawings. 3. Continue to notify the Owner after submittal review immediately of any PLC input/output changes which impact the configuration as defined in the contract documents. 4. Allow forty (40) hours every three (3 months) of on-site programming changes per the direction of the City of Santa Ana. These changes will reflect system control adjustments as necessary to fine tune the overall control strategy. This effort is to be responsive within three (3) days notice and includes changes desired by the City of Santa Ana at Walnut Pump Station. This requirement will be in effect for a period of one (1) year from the date of final acceptance at no additional cost to the City of Santa Ana. 10-15-dp 17000 – General Instrumentation and Control - 8 of 24 I. 1.6 The PCS has been designed to include operator interfaces for all system functions. All systems have been designed to be manually operable via discrete devices and via programmed Human Machine Interface devices. Systems have been designed to be monitored and controlled in a hierarchical manner. Basic functions have been designed to be provided at field stations, local panels, and MCC’s by discrete panel switches, indicator lights, and displays. The overall department wide SCADA system has been designed to provide monitoring and control of all systems and equipment at the facility. All programmable devices and systems have been designed to, and shall communicate over a TCP/IP plant Ethernet network. The PCS Integrator, the Contractor, and packaged equipment suppliers shall ensure that all components of supplied plant systems fully and seamlessly integrate into this system architecture. Submittals A. General 1. Submittals shall be in three-ring hardcover binders and arranged for convenient use including tab sheets, all indexed, and cross-referenced. Bill of materials, cut sheets, shop drawings, schematics, panel layouts, schedules, etc., shall be crossreferenced, indexed, or otherwise related by unique identifier for each item. The Engineer may reject improperly organized or notated submittals. 2. Provide pdf file with page numbers in table of contents as well as bookmark links to section coversheets in pdf file. 3. Suppliers shall provide re-submittals which include responses to all submittal review comments separately and at a level of detail commensurate with each comment. Supplier responses shall indicate how the supplier resolved the issue pertaining to each review comment. Responses that only indicate that the review comment was noted, will be looked into, etc., are not satisfactory. Re-submittals which do not comply with this requirement may be rejected and returned without review. Contractor shall be allowed no extensions of any kind to any part of their contract due to the rejection of non-compliant submittals. Submittal review comments not addressed by the contractor in re submittals shall continue to apply whether restated or not in subsequent reviews until adequately addressed by the contractor to the satisfaction of the reviewing and approving authority. 4. Labeling: Label submittal title sheet with Project title, submittal title, date, Specification Section number, submittal number, and version (re-submittal). 5. Submit catalog cut sheets for all products. Identify all cut sheets by unique bill of material item number, index, or key. Notate catalog cuts to indicate only those items, models, options, or series of equipment to be furnished. Cross out or otherwise obliterate all extraneous materials and information. Clearly identify all configuration options for the equipment to be furnished. 6. Submit copies of all Division 17 specification sections with each paragraph notated to indicate compliance. A check mark shall indicate complete compliance. Explanations shall be provided for all non-compliant items. 7. In the case of deviations from the contract documents, particularly related to the impact of the configuration of submitted packaged equipment supplied to the project, 10-15-dp 17000 – General Instrumentation and Control - 9 of 24 submit marked up copies of applicable Electrical and Instrumentation contract drawings notated to identify and explain all proposed deviations from the contract documents. Items not notated on the submitted marked up copies shall be assumed to be 100% compliant with the bid documents. This requirement applies to electrical one lines, MCCs, MCC control schematics, panel schedules, and control schematics. This requirement does not apply to plan drawings and conduit schedule which shall be marked up to reflect the as constructed project configuration and submitted as record drawings. 8. Submit operation and maintenance information as specified in any Division 17 specification section. O&M manuals shall include product data for all materials and items supplied in compliance with the submittal requirements of this section. 9. Submit all drawings described in this and other Division 17 sections including elementary, loop, single-line, schematic, fabrication, installation, field wiring, panel layout and assembly, etc., drawings. Drawings shall be updated following submittal review, factory test, and commissioning. Updates shall be provided to the Project Representative in a timely manner. Cross reference drawing elements with BOM and catalog cut sheet unique references. Drawings shall use project tag formats and numbers. Unique and separate drawings shall be provided for each item supplied including but not limited to all panels and all MCC units. Typical drawings that apply to multiple panels or multiple MCC motor control units are not acceptable. Individual I/O schematics diagrams are to be provided for each I/O slot based on the typicals in the design and the PLC I/O List. Individual motor starter schematics are to be provided for each starter unit including VFD and breaker units as well as spare or space units. 10. Submit dimensional, installation, and wiring diagrams and drawings for all supplied components. 11. Submit test plans, calibration forms, test forms, test results, and test reports required by any Division 17 specification section. 12. Provide to the Owner in a timely fashion. Contractor to plan and make submittals to avoid project delays or conflicts. Include sufficient time for the City to check and approve the document. 13. Variations from Contract Documents. Clearly list separately all proposed variations from the Contract Documents. Provide information which explains the advantages of the proposed alternative approach or alternative equipment. B. Design Submittals 1. Product Information a. Catalog product sheets shall include, but not be limited to: 1. Catalog cuts, data sheets, performance surveys, test reports, equipment lists, material list, diagrams, pictures, and descriptive material. 2. All items including PLCs, instruments, cabinets, mechanical devices, mounting components, wiring, terminal strips, connectors, accessories, and spare parts. b. Clearly identify proposed items and selected options, sizes and speeds, by highlighting or encircling. 10-15-dp 17000 – General Instrumentation and Control - 10 of 24 c. Cross out all extraneous catalog cut material. d. Include performance data and specifications for each item. e. List all proposed modifications or changes to standard items. f. Submit, for review prior to commencement of manufacture (or shipment for stock items). 2. Shop Drawings a. General 1. Include, block diagrams, panel schematics, scaled panel general arrangement drawings, loop diagrams and installation details. 2. For all drawings provide borders, title block, revision date, Contractor’s name, Owner’s names, and cross references to related drawings. 3. In the drawing revision block identify the changes made since the last revision. 4. Drawings shall be prepared utilizing a computer aided drafting program. CAD shop drawings shall be updated and provided to the Project Representative prior to factory testing, prior to system installation, and with the O&M manuals in hardcopy and electronic file formats. 5. Size drawings 22 inch by 34 inch, except loop drawings. Size loop drawings 11 inch by 17 inch. 6. Provide both hard and electronic copies (CAD and PDF) on a labeled CD/DVD/solid state drive. b. Block Diagram 1. Show major subsystems and interrelationships between them to provide an overview of the complete facility PCS system. 2. Provide a separate block diagram for each facility. c. Panel Fabrication and Layout Drawings: Show the placement, labeling and wiring of components within panels, cabinets and consoles. Include: 1. Front, back, and side panel elevations with dimensions. 2. A bill of materials with device tag, English narrative description, manufacturer, model, and quantities. 3. Sufficient detail to demonstrate material choices, outward appearance, construction methods, and seismic force resistance. 4. Neutral and earth bars where applicable. 5. Panel ventilation, heating and cooling systems. 10-15-dp 17000 – General Instrumentation and Control - 11 of 24 6. Paint color and dry film thickness. 7. Paint color and dry film thickness. 8. Conduit entry points. 9. Draw panel to a scale appropriate (architectural units) 10. Show all additions and deletions of devices and wires in existing enclosures. 11. Provide panduits within the panel for organizing wire bundles, with a minimum of 20 percent spare wire capacity. 12. Provide separate panduits for low voltage DC signal wires. 13. Arrange panel to provide the maximum spare panel space to accommodate mounting future equipment. Provide a minimum of 20 percent spare panel mounting area. 14. The City has the right to make modifications to the interior and exterior layouts of panels as part of the shop drawing review. Provide in the bid price at least one panel redesign for incorporating the requested City modifications. d. Panel Schematics: Provide schematic drawings showing all control panel components, the interconnection of all control panel components, all field devices, and the connection of all field devices to control panels. Schematic diagrams shall also show all communications components, their interconnection, and their interface with other control panel components. Provide wire and terminal block numbers. e. Interconnection Diagrams: Prepare and submit panel interconnection diagrams. Loop diagrams are not acceptable as a substitute for connection diagrams. 1. Show the external wiring between terminals of associated equipment, control panels, motor control centers, terminal boxes, field instruments, and any other device, panel, or enclosure. 2. Show wiring and cable numbers and device tags. Number wiring and cables in conformance with the City’s standards. 3. Reference related drawings by drawing number. f. Loop Diagrams: Provide elementary loop diagrams for all discrete loops in compliance with ISA S5.4. Elementary diagrams and loop diagrams shall show circuits and devices of a system and include identification of power source. These diagrams shall be arranged to emphasize device elements and their functions as an aid to understanding the operation of a system and maintaining or troubleshooting that system. 1. Show both discrete and analog devices and signals. 2. Do not combine multiple loops on a single drawing. 10-15-dp 17000 – General Instrumentation and Control - 12 of 24 3. Show wire numbers, color codes, signal polarities, and terminal block numbers. Tables for wire numbers, signal polarity, and terminal block numbers are not acceptable. 4. Show all field wiring, field junction boxes, instruments, cabinet terminals and associated PLC inputs/outputs. 5. Reference related drawings by drawing number. g. Cabinet Cooling Calculations 1. Provide cooling calculations for all cabinets and panels containing electronic equipment. 2. Provide cabinet fans or alternative cooling to maintain equipment within the manufacturer’s recommended operating range. h. Record Drawings: 1. Also referred to as as-built drawings. 2. SHOP DRAWINGS: All submitted drawings shall be updated over the course of the construction project to reflect the installations and equipment as-built. A full set of record drawings shall be provided to the Project Representative upon completion of the project and shall be included in the O&M manuals. Record drawing requirements shall be the same as submittal drawing requirements. 3. CONTRACT DRAWINGS: The contractor shall maintain a set of record plan markup drawings on site during construction. The contractor shall mark up the record drawing set to indicate any and all deviations of the installed systems from the contract documents. The marked-up drawings shall be provided to the project representative at project close out. C. Testing Submittals 1. Test Plans: Also see requirements in Section 17300 and 17600. Provide: a. Submit test plans for the following tests: b. HMI Communications Test c. Factory Demonstration Test d. HMI Demonstration Test e. Functional Acceptance Test f. Radio Communications Test D. Training submittals: As specified in Section 1.10. E. 10-15-dp Preliminary O&M Submittal: A preliminary copy of the Final O&M, delivered prior to the Site Acceptance Test. 17000 – General Instrumentation and Control - 13 of 24 F. Final O&M Submittal: Detailed Systems Drawings and Data: The submittal shall consist of six sets of detailed drawings and data prepared and organized by the Contractor who was designated at the time of bidding. These drawings and data shall be submitted as a complete package at one time. 1. Detailed JIC-style schematic diagrams of each discrete I/O point. 2. Detailed instrumentation diagrams of each analog I/O instrumentation and control loop, per ISA S5.3 and S5.4 standards. 3. Detailed programmable logic controller (PLC) connection loop diagrams. 4. Data sheets for each component, together with a technical product brochure or bulletin. The data sheets shall show: a. Component name. b. Manufacturer’s model number. c. Project tag number. d. Project location. e. Input and output characteristics. 5. The data sheets shall be grouped together in the submittal by systems or loops as a separate group for each system or loop. If within a single system or loop, a single component is employed more than once, one data sheet with one brochure or bulletin may cover all identical uses of that component in that system. 6. Component interconnect drawings showing the interconnecting wiring between each component including equipment supplied under other sections requiring interfacing with the control system. 7. Arrangement and construction drawings for consoles, control panels, and for other special enclosed assemblies for field installation. These drawings shall include dimensions, identification of all components, preparation and finish data, nameplates, and the like. These drawings also include enough other details to define the style and overall appearance of the assembly; a finish color sample shall be included. Drawings shall include: a. Electrical drawings as required by Section 16010, General Electrical Diagrams. b. Loop diagrams to ISA 5.4 standards. One loop per sheet, in a 11” x 17” format. 8. Installation, mounting, and anchoring detail for all components or entry details. 9. Electronic Files of Shop Drawings: Submit electronic files of all shop drawings in CAD and PDF format. 10. Complete detailed bills of material. 11. Fully annotated PLC logic diagrams as described in Section 17300. 12. Record “as built” drawings and corresponding CAD files. 10-15-dp 17000 – General Instrumentation and Control - 14 of 24 13. Calibration sheets for instruments and other devices requiring field adjustment. Includes as a minimum: a. All field instruments including analog instruments (4 -20mA), pressure, flow, level, and analytical instrument switches. b. PLC analog inputs and outputs. c. Valve end-of-travel switches. 14. Proposed acceptance test methodology and record sheets submitted for approval by the Owner, prior to acceptance testing beginning. 15. Final Site Acceptance Test record sheets, signed by the Owner. 16. “As built” equipment configuration sheets for all equipment with user configurable parameters including PID configuration/set points. This includes VFDs, SSTs, controllers, and network devices. 17. Updated English control strategy narratives. 1.7 Instruments A. The Contractor shall: 1. Remove any existing instruments mounted on process equipment or pipes that are being removed. 2. Remount the instruments on the new equipment or pipe. 3. Recalibrate all instruments, and automatic valves, and check they are in good order. 4. Provide and install new instruments where shown on the contract documents. 5. Submit all calibration sheets to the Owner for approval as required under paragraph “Submittals” B. 1.8 In cases where an instrument not supplied by the Contractor, cannot be properly calibrated because of its condition or is judged by the PCS Integrator to be unreliable, the Contractor shall inform the Owner in writing within 24 hours of the failed calibration attempt or negative evaluation. The Owner will direct the Contractor on the action to be taken. Workshop A. The PCS Integrator shall attend a 3 hour workshop no later than 3 weeks after the Notice to Proceed, to review the PCS specifications requirements, and discuss the PCS integrators proposed architecture. The PCS Integrator shall present a draft systems architecture at the workshop. B. Workshop purpose: To clarify the requirements for the PCS and discuss the initial approach proposed by the PCS integrator. The following topics will be covered. 1. Review of the PCS requirements and goals. Led by the City. 2. Presentation of PCS Integrator’s approach. Led by PCS Integrator. 10-15-dp 17000 – General Instrumentation and Control - 15 of 24 3. Review and discussion of submittal and testing requirements. Led by City. 4. Other topics. C. The City will prepare the workshop minutes. 1.9 Testing A. 1.10 As specified in section 17600 Training A. General 1. The PCS Integrator shall conduct specifically organized training sessions to educate and train the owner's personnel in the maintenance and operation of all aspects and components of the control system they supply. Training on all system components shall include, but not be limited to, the following subjects: a. All O&M manual items b. All system users’ manual items c. Local HMI programming training: For City maintenance staff. d. Pump Station controls training: For Operator and maintenance staff. 2. Schedule all training courses Tuesday through Thursday between 8:00am and 3:30 PM. 3. Obtain approval from the Owner for the proposed training schedule. 4. Pump station controls training: The PCS Integrator shall provide a minimum of 16 hours of on-site instruction to the owner's employees after start-up and commissioning of the system. The owner shall be allowed to video tape all or any part of the training sessions. The PCS Integrator shall prepare and assemble specific instruction materials for each training session and shall supply such materials to the Project Representative at least two (2) weeks prior to the time of the training. The O&M manuals and the system users’ manual shall be complete and shall be used in the training sessions. a. Provider: PCS Integrator. b. Class length: 4 hour sessions. c. Audience: City operations and maintenance staff (up to 10 attendees). d. Location: Part classroom (Utility Administration Building), part at Walnut Pump Station site. e. Content: 1. Overview of new controls. 10-15-dp 17000 – General Instrumentation and Control - 16 of 24 2. Control strategies 3. Communications 4. Local HMI screens 5. Control modes, control options and operation. 6. Power failure and recovery f. 1.11 Handouts: Provide attendee’s understanding of the system. with handout material which assist Guarantee A. The Contractor shall repair or replace defective components, rectify malfunctions, correct software problems (for any software supplied by the Contractor), and correct faulty workmanship, all at no additional cost to the Owner during the guarantee period. To fulfill this obligation, he shall utilize technical service personnel designated by the Contractor who was originally assigned project responsibility. Services shall be performed within five calendar days after notification by the Owner's Representative. PART 2 - MATERIALS 2.1 Designation of Components A. Component and Equipment naming 1. In these specifications and on the plans, all systems, and other elements are represented schematically and are designated by numbers, as derived from criteria in International Society of Automation (ISA) Standards. 2. The nomenclature and numbers designated on the Contact Documents shall be employed exclusively throughout shop drawings, data sheets, and the like. Any other symbols, designations, and nomenclature unique to a manufacturer' standard methods shall not replace those prescribed above without prior Owner authorization. 2.2 2.3 Instrument Tagging A. Attach a stainless-steel tag to the instrument at the factory. stainless-steel tag with the instrument tag number. B. The manufacturer’s standard metal nameplate as a minimum shall denote model number, serial number, operating electrical voltage and amperage (when applicable), date of manufacturer, and where applicable, operational range and output signal range. Matching Style, Appearance, and Type A. 10-15-dp Permanently mark the Power provided for the instrument system shall be 24Vdc, from a single source. This system will supply 100% of the control power for the PLC and instruments. Provide battery backup system for all components in the Main Control Panel, and for instruments and network devices on the project. 17000 – General Instrumentation and Control - 17 of 24 B. Where d-c power supplies are not furnished integral with any one instrument system loop, provide separate solid-state power supplies. C. All display instruments of each type shall represent the same outward appearance, having the same physical size and shape and the same size and style of numbers and pointers. 2.4 Analog Signal Isolator/Repeater – Dual Output A. 2.5 Manufacturer: WAGO JumpFlex 857-423, no equal Level Indicating Transmitter A. The level transmitter shall use hydrostatic pressure to measure level. It shall include a sensor/cable assembly 35 feet long and a NEMA 4X housing to mount at the well head or tank. The housing shall contain an electronics module with zero and span adjustments. It shall include a 3 1/2 digit LCD, and the output shall be 4-20 mA isolated. Supply power shall be 24 VDC loop powered. The sensor housing shall be 316 SS. B. Manufacturer: Level indicating transmitter shall be manufactured by Delta Controls, Model 592Y-CN-G4Y-4X-35V-328; no-equals allowed. Tag No. LIT-201 2.6 Service Reservoir Level Probe Length 35 feet Dwg. E-2 Level Switches – Conductance Probe Sensor A. General: Units shall activate isolated contacts when a conductive liquid completes a circuit between electrodes. Units shall consist of electrode holder, electrode(s), and control relays. 1. Electrode holders shall be cast iron pressure-tight assemblies and shall mount with 2 1/2-inch NPT. Unit shall include the number and length of electrodes as required to accommodate the noted set points. Electrode material shall be Type 316 stainless steel. Electrodes shall be manufactured by Charles F. Warrick Company, Type 3RXC4 (with PVC sheathing) or 3RXC0 (without PVC sheathing for common probe only); no-equals. Electrode holder shall be manufactured by Charles F. Warrick Company, Type 3E2A; no-equals. 2. Induction relay contacts shall be rated for 8 amperes at 120 Vac. Units shall be powered by 120 volt, 50/60 Hertz. The sensitivity shall be field adjustable by use of external resistors. Manufacturer shall be Gems, Series 26; no-equals. B. Manufacturer: Units shall be conductance-activated liquid level control systems manufactured by Charles F. Warrick Company; no-equals allowed. Tag No. Common LSL-110 2.7 Probe Length TBD TBD Dwg. E-4 E-4 Electronic Pressure Indicating Switch/Transmitter A. 10-15-dp Service Low Water Cutoff Low Water Cutoff The electronic pressure indicating switch/transmitter shall provide continuous pressure monitoring. Pressure switch shall include an 8-digit 14-segment LED display with bargraph and trend indication. 17000 – General Instrumentation and Control - 18 of 24 B. All parameters shall be configured by keypad. Display units shall be selectable from: Bar, psi, psi x 10, hPa, and mbar. The options for pressure measuring ranges are (PSIG): 0150, 0-1500, 0-3000, 0-6000, and 0-9000. C. Unit shall provide 4 relay outputs and 1 analog output. The analog output shall have an accuracy of 0.5% full scale. The SPDT relay output contacts shall be rated for 5 amps at 250 VAC. Unit shall be Barksdale Model UDS3-05-N-5; no equals allowed. D. The following units shall be provided: Tag No. PSH/PSL-120 PSH/PSL-130 PSH/PSL-140 PSH/PSL-150 PSH/PSL-160 2.8 10-15-dp Dwg. E-4 E-4 E-4 E-4 E-4 A. Intrusion switches shall be mounted and wired in series such that upon opening any exterior door shall provide an alarm to the PLC. Intrusion switch shall be NEMA 4X. Provide Allen Bradley 802MC-AY5; or equal. B. The following intrusion switches shall be provided: Service Workshop Electrical Room Pump Station Pump Station Pump Station Utility Closet Hatch Sodium Hypochlorite Storage Room POL Storage Room Valve Vault 1 Intrusion Valve Vault 2 Intrusion Meter Vault Intrusion Reservoir Access Hatch Intrusion Butterfly Valve Vault Hatch Intrusion Dwg. E-4 E-4 E-4 E-4 E-4 E-4 E-4 E-4 E-7 E-4 E-4 E-8 E-8 Flood Switch A. Switch shall be a stem mounted float device with 304 stainless steel stem, Buna N Float Material, Lucite Slosh Shield, IMO/GEMS Model LS-270 or approved equal. B. The following flood switches shall be provided: Tag No. LS-107 LS-117 LS-197 LS-200 2.10 High/Low Setpoints TBD TBD TBD TBD TBD Lever Arm Intrusion Switch Tag No. ZS-168A ZS-168B ZS-168C ZS-168D ZS-168E ZS-168F ZS-171A ZS-171B ZS-108 ZS-118 ZS-198 ZS-199 ZS-200 2.9 Service Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Service Valve Vault 1 Flood Valve Vault 2 Flood Meter Vault Flood Butterfly Valve Vault Flood Dwg. E-7 E-4 E-4 E-8 Chlorine Analyzer 17000 – General Instrumentation and Control - 19 of 24 A. General: Unit shall monitor water continuously for total residual chlorine. B. Manufacturer: ProMinent Total Chlorine Analyzer; no-equals allowed. Tag No. AIT-170 Service CL2 Residual Range TBD Dwg. E-4 PART 3 - EXECUTION 3.1 Installation A. The drawings indicate connections for typical equipment only. If the equipment furnished is different from what is shown, provide the modifications necessary for a safe and properly operating installation in accordance with the equipment manufacturer's recommendations. B. The drawings indicate diagrammatically the desired location and arrangement of equipment. Field determine exact location based on physical size and arrangement of equipment, finished elevations, and obstructions. C. Work or equipment not indicated or specified which is necessary for the complete and proper operation of the instrumentation and control systems shall be accomplished without additional cost to the Owner. D. The PCS Integrator shall determine all requirements for and shall cause integration of the supplied control systems, MCCs, and any supplied packaged equipment control systems into a complete and unified system. The PCS Integrator shall be responsible for the coordination and integration of the supplied control system with motor controls and other related equipment such as VFDs, powermeter, SHC, and back-up generator/ATS. E. INSTALLATION BY CONTRACTOR: The control system and associated instruments and connections shall be installed by the contractor. F. INSTALLATION INSTRUCTIONS: The control system shall be installed in accordance with the installation drawings and instructions provided by the PCS Integrator, packaged system suppliers, and other equipment suppliers. G. SUPERVISION: The PCS Integrator's instrumentation and controls project engineer shall supervise and coordinate all activities related to the installation of Division 17 requirements. H. EXPERTISE OF INSTALLER: Installation shall be performed by the workers who are skilled and experienced in the installation of electrical instrumentation and control systems. Installation shall include all elements and components of the control systems and all conduit and interconnecting wiring between all elements, components, sensors, valve operators, etc. 10-15-dp I. LOCATION: Equipment shall be located so that it is readily accessible for operation and maintenance. J. INSTRUMENT TECHNICIAN: The PCS Integrator shall provide the services of skilled instrument technicians for testing, calibration, and adjustment activities. 17000 – General Instrumentation and Control - 20 of 24 3.2 Mounting of Equipment and Accessories A. Mount equipment in accordance with the installation detail drawings as prepared by the Contractor and reviewed by the Owner. Mount equipment so that they are rigidly supported, level and plumb, and in such a manner as to provide accessibility; protection from damage; isolation from heat, shock, and vibration; and freedom from interference with other equipment, piping, and electrical work. Do not install consoles, cabinets, and panels until heavy construction work adjacent to computer and telemetry equipment has been completed to the extent that there shall be no damage to the equipment. B. Locate devices, including accessories, where they shall be accessible from grade, except as shown otherwise. C. Mount local equipment in cabinets or existing panels as specified. Mount associated I/O terminals on a common panel or rack; mounting panels and rack shall be baked enamel. D. Provide cooling for all cabinets containing electronic equipment. Maintain temperatures inside the cabinet to within the recommended manufacturer’s limits for the equipment mounted in the cabinet, and not greater than 8 degrees C above ambient. Submit calculations to Owner for approval prior to manufacturing. 3.3 E. Coordinate the installation of the electrical service to components related to the system to assure a compatible and functionally correct system. All accessories shall be coordinated and installation supervised by the Contractor. F. Test the complete system after installation to assure that all components are operating with the specified range and all interlocks are functioning properly. Testing A. The Contractor shall perform testing and start-up of the instrumentation and control equipment following the PCS written test procedures, submitted and pre-approved by the Owner, per Section 17600. B. Testing results shall be fully documented by the PCS Integrator. Each step of the test shall be witnessed and signed off by the Owner or his representative per section 17600. C. The PCS Integrator shall pre-test the system following the pre-approved test procedures, prior to the start of witnessed test by the Owner. All problems discovered during the pretest shall be resolved prior to the witnessed test, per section 17600. 3.4 10-15-dp Maintenance and Repair Manuals A. Maintenance manuals shall be prepared and submitted to the City's Representative for preliminary review in six copies. When the City's Representative is satisfied that these are complete and properly prepared, six final sets shall be delivered to the City's Representative. These manuals shall be submitted two weeks prior to City staff training. B. The complete Maintenance manual shall contain all the information included in the preliminary equipment submittal, the detailed installation submittal, programming instructions, and the additional information required herein, all bound in hard-cover binders and arranged for convenient use including tab sheets, all indexed and cross referenced, and all final As-Built drawings. 17000 – General Instrumentation and Control - 21 of 24 C. The maintenance manuals shall contain: 1. Calibration and maintenance instructions. 2. Trouble-shooting instructions 3. Component replacement procedures. 4. Preventative maintenance procedures. 5. Listing of recommended spare parts. 6. Instructions for ordering replacement parts. 7. Listing of recommended maintenance tools and equipment. 8. Catalog data for all equipment and devices supplied, organized per submittal requirements. 9. Complete set of “as built” drawings. 10. PLC logic diagrams, comprehensively annotated. 11. “As-built” configuration sheets for all devices with user set parameters, including VFDs, SSTs, controllers, network devices, and PID tuning parameters. D. At the time of submittal of the Operations and Maintenance Manuals, the Contractor shall provide “as-built” versions of submittal drawings, and equipment manufacturers shop drawings. All contract drawings and control strategy specification sections and all submittal drawings shall be revised to reflect as-built conditions at the end of the project. Record drawings and documents shall be submitted with the O&M manuals. E. Electronic Files Of Shop Drawings and O&M manuals: In addition to hard copies of manuals, provide two sets of electronic files on labeled CDs/DVD/solid state drives containing all: 1. “As-built” shop drawings (CAD files). 2. O&M manuals. Include electronic (pdf) files of all. a. Manufacturer’s manuals (user and installation) b. Manufacturer’s data sheets c. Manufacturer’s drawings d. Maintenance procedures e. Equipment List f. 10-15-dp Instrument List 17000 – General Instrumentation and Control - 22 of 24 F. SYSTEM USERS MANUAL 1. The PCS Integrator shall develop and submit a detailed user manual covering all aspects of the operation and use of the components and systems they supply. The manual shall cover the following: a. OVERVIEW: An overview of the architecture of the control system including control panels, MCC's, field devices, PLC, HMI, SCADA, remote alarm notification, communications, networks, remote access, etc. b. FUNCTIONS: All hardware/hardwired, programmed, manual, automatic, display, control, alarming, timer, communications, networking, etc. features and functions of the systems and components they supply. c. HARDWIRED ELEMENTS: Descriptions of the meaning and function of all hardwired panel, MCC, and field mounted discrete operator interface monitoring and control devices. Correlate functions to the control strategies. d. TAG LISTS: PLC, HMI, SCADA, remote alarm notification system, tag data base lists, and register listings. e. CONFIGURATION SETUP: Configuration screens for all PLC, HMI, SCADA, PIDs, timers, remote alarm notification, communications, and network system components. f. Network schema: Provide IP address listing g. SECURITY: System, application, data base, remote access, etc., security. Provide all configured user and administrator user names and passwords. h. START UP: System start up procedures for SCADA systems supplied and configured by the contractor for the project. 2. USED IN TRAINING: The system users manual shall be completed prior to and shall be used for required training. The manual shall be updated to incorporate comments received during training and re submitted for inclusion in the Final O&M manual. Submit 2 weeks prior to training. END OF SECTION 10-15-dp 17000 – General Instrumentation and Control - 23 of 24 THIS PAGE INTENTIONALLY BLANK 10-15-dp 17000 – General Instrumentation and Control - 24 of 24