Application Guide

advertisement
AL602ULADA(J)
AL802ULADA(J)
AL1002ULADA(J)
NAC Power Extenders
Application Guide
(See Installation Guide for additional information)
Altronix Corp.
140 58th St. Brooklyn, NY
Rev. 042010
1. General Information (Use this in conjunction with respective Installation Guide):
Altronix AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA and
AL1002ULADAJ are very versatile devices. They can be used with or without specific synchronization modules
provided by some manufacturers. Multiple units can be synchronized by using either the built-in sync mode or a external
synchronization module. Please note, that only notification appliances with synchronization capabilities can be
synchronized. Contact signal manufacturer for more detailed information. Units can operate with either one (1)
or two (2) outputs from the FACP.
2.­Class A, Style Z and Class B, Style W, Y Hookups:
Units can be used with the outputs configured for:
• Two (2) Class A, Style Z (Fig. 2a­­­­).
• Two (2) Class B, Style W, Y and one (1) Class A, Style Z NAC
• Up to Four (4) Class B, Style W, Y circuits (Fig. 2b).
Fig. 2a
SW2 SW1
+ OUT1 --
+ OUT2 --
+ OUT3 --
+ OUT4 --
NAC Loop 1 starts on Output 1 and terminates on Output 3.
Switch
SW1,
when
closed, provides proper termination for this
UPPER TERMINALS
IN1+ IN1-- IN2+ IN2-C "DRY1" NC
RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS
loop. NAC Loop 2 starts on Output 2 and terminates on Output 4,
SW2 must be closed for proper termination.
Please make sure that all the dip switches for corresponding outputs are set the same way.
From
FACP
NAC1
From
Return FACP
to FACP NAC2
Two (2) Class A, StyleZ
Hookups
Fig. 2b
Return
to FACP
SW2 SW1
+ OUT1 --
+ OUT2 --
2.2K
EOL
+ OUT3 --
+ OUT4 --
For combination of two (2) Class B, Style W, Y and one (1) Class
A, Style Z circuit, only one (1) switch (SW1 or SW2) must be
UPPER TERMINALS
IN1+ IN1-- IN2+ IN2-- C "DRY1" NC
closed,
terminating
Class A circuit only.
RET1+ RET1-- RET2+ RET2-C "DRY2" NC LOWER TERMINALS
2.2K
EOL
One (1) Class A, StyleZ
two (2) Class B, Style W, Y
Hookups
- 2 -­
02ULADA Application Notes
When using NAC appliances not designed to support synchronization feature, it is recommended to use separate output circuits for audible notification appliances (horns) and visual notification appliances (strobes). Set dip switches for
the visual notification appliances to follow Input 1 [IN1] and for audible notification appliances to follow Input 2 [IN2].
This will allow, when using two (2) outputs from the FACP, to support silencing of audible notification appliances.
When using only one (1) FACP output, set all dip switches to follow Input 1 [IN1]. The units outputs can each be set
for the desired NAC drive signal, such as Code 3 or march time sequence (Output Programming Selection Table, pg. 6).
Non-synchronizable Audible Appliances will follow the sequence, when feature is selected.
4. Using Multiple NAC Power Extenders from an FACP:
AL602/AL802/1002ULADA(J) units are designed to follow (replicate) the coded sequence, generated by a manufacturer’s
sync module. One (1) or more units can be triggered. Connect the output of the FACP module to Input 1 and Input 2
Terminate the input circuit with the EOL or FACP, connecting it to terminals marked [RET+ and RET-], or continue the
input circuit, connecting to terminals marked [RET+ and RET-] to [INP+ and INP-] of the next unit, when multiple units
need to be triggered.
In case FACP does not have any synchronization capabilities and the sync mode is not used,
the notification appliance synchronization will not be provided.
Fig. 4a
FACP with Sync Output
NAC Power Extender:
DIP switches set to Input to Output follower mode.
NAC Power Extender:
DIP switches set to Input to Output follower mode.
FACP
(Fire Alarm
Control Panel
with sync
capabilities)
Memory
Reset
Memory
Reset
Or
Sync Module
POWER
IN ---
ZONE 2
POWER
IN ---
ZONE 1
+ NAC 2 ---
POWER
IN +
ZONE 1
POWER
IN +
HORN
CONTROL
+ NAC 1 ---
3. Non-synchronizable NAC Appliances:
POWER
OUT +
POWER
OUT --POWER
OUT +
To FACP EOL or
next NAC power extender
Control
Circuit
POWER
OUT ---
2.2K 2.2K
EOL EOL
2.2K 2.2K
EOL EOL
2.2K 2.2K
EOL EOL
2.2K 2.2K
EOL EOL
Control Circuit
No Notification Appliances Allowed
Caution: Do not connect any notification appliances on the control circuit interconnecting FACP
outputs (sync module outputs) and inputs of NAC Power Extenders. Applications that do not employ
synchronization module or FACP with synchronization protocol will not provide NAC sycnchronization
between NAC Power Extenders.
02ULADA Application Notes
-3-
5. Synchronizing NAC Power Extender Using Built-in Sync Protocol:
AL602/AL802/1002ULADA(J) have built-in protocols to support Amseco, Faraday, Gentex® and System Sensor®,
Wheelock® two-wire synchronizable devices, therefore an external sync module is not required (Output Programming
Selection Table, pg. 6). In these modes, Input 1 is always used to activate visual notification appliances (strobes), and
Input 2 is used to activate and silence audible notification appliances (strobes).
Note: Input 1 has to be activated in all the configurations.
Fig. 5a
NAC Power Extender:
Dip Switches set for desired Sync Protocol (ex. Gentex®,
System Sensor®, Faraday or Amseco, CooperWheelock®).
SW2 SW1
NAC Power Extender:
Dip Switches set for Input to Output Follower Mode
SW2 SW1
+ OUT1 --
+ OUT2 --
+ OUT3 --
+ OUT1 --
+ OUT4 --
+ OUT2 --
+ OUT3 --
UPPER TERMINALS
IN1+ IN1-- IN2+ IN2-- C "DRY1" NC
RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS
UPPER TERMINALS
IN1+ IN1-- IN2+ IN2-- C "DRY1" NC
RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS
To EOL or next
NAC Power Extender
Control Circuit
No Notification Appliances
Allowed
2.2K
EOL
2.2K
EOL
2.2K
EOL
FACP
(Fire Alarm
Control Panel)
FACP
EOL
+ OUT4 --
For continuous loop
circuit use 2.2K EOL,
(Altronix Model #
AL-EOL22).
2.2K
EOL
2.2K
EOL
2.2K
EOL
FACP
EOL
When connecting, keep wires on different sides of the screws in order to maintain loop integrity supervision.
DO NOT LOOP CONTINUOUS WIRE AROUND THE SCREW.
- 4 -­
02ULADA Application Notes
6. Using a Single FACP Output:
When only one FACP output is available, you may connect both Input1 and Input2 to it. Wire [RET1+ and RET1-]
to [INP2+ and INP2-]. Both visual and audible notification appliances will be activated simultaneously (Fig. 6a).
Fig. 6a
IN1+ IN1-- IN2+ IN2-- C "DRY1" NC
RET1+ RET1-- RET2+ RET2-- C "DRY2" NC
UPPER TERMINALS
LOWER TERMINALS
FACP
02ULADA Application Notes
Control Circuit
NO Notification
Appliances allowed
EOL
or
Next Device
-5-
Output Programming Selection Table:
Outputs must be programmed independently [OUT1 - OUT4]
Switch Position
Function
Description
ON
OFF
Input to Output
Output follows signal it receives from the corresponding input (i.e. FACP
1
2, 3
Follower Mode
Sync module - maintains synchronization of notification appliance circuit.
Temporal Code 3
Enables Temporal Code 3 signal generation output.
3
1, 2
Mode
This mode is activated by a steady or a pulsing input.
A steady output signal will be generated. This mode is activated by
Steady Mode
N/A 1, 2, 3
a steady or pulsing input.
March Time Mode
Enables a March Time output which will sound 60 beats
2, 3
1
(60 beats per minute)
per minute. This mode is activated by a steady or pulsing input.
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
(AL800LGK9E Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
Sync Mode Selection Table:
Switch Position
Function
Description
ON
OFF
This mode is designed to work with the Amseco series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
Amseco
1, 3, 4
2
synchronizing the flash timing of the strobe, and silencing the horns of the
Sync Mode*
horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
Faraday
2, 4
1, 3
synchronizing the flash timing of the strobe, and silencing the horns of the
Sync Mode*
horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Gentex® Commander GOS and ST/HS
Gentex
series of horns, strobes, and horn/strobes to provide a means of synchronizing
1, 2,
Sync Mode*
N/A the Temporal-coded horns, synchronizing the flash timing of the strobe, and
3, 4
Gentex is a registered
silencing the horns of the horn/strobe combination over a two (2)-wire circuit
trademark of Gentex Corporation.
while leaving strobes active.
This mode is designed to work with the SpectrAlertTM series of horns, strobes,
System Sensor
and horn/strobes to provide a means of synchronizing the Temporal-coded
Sync Mode*
horns, synchronizing the one-second flash timing of the strobe, and silencing
1, 2, 4
3
System Sensor is a registered
the horns of the horn/strobe combination over a two-wire circuit while leaving
trademark of Honeywell.
strobes active.
This mode is designed to work with the Wheelock series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded
CooperWheelock®
2, 3, 4
1
horns, synchronizing the one-second flash timing of the strobe, and silencing
Sync Mode*
the horns of the horn/strobe combination over a two-wire circuit while leaving
strobes active.
Note: The AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA and AL1002ULADAJ
will only synchronize horns, horn strobes and strobes that contain synchronization capability. Contact signal manufacturer
for more detailed info. The same synchronization mode must be selected for all outputs.
- 6 -­
02ULADA Application Notes
Notes:
02ULADA Application Notes
-7-
Notes:
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIAL602,AL802,1002ULADA(J)