Mercy Hospital of Buffalo Catholic Health System nd 2 Floor Patient Holding Center rd 3 Floor Locker Rooms Shaflucas Architects, PC Project No. 0649 SECTION 22 64 00 MEDICAL GAS ALARMS PART 1 - GENERAL 1.1 A. RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 A. SUMMARY Section Includes: 1. 1.3 A. Area alarm panels. DEFINITIONS Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote-control, signaling powerlimited circuits. 1.4 A. 1.5 ACTION SUBMITTALS Product Data: For each type of product. INFORMATIONAL SUBMITTALS A. Qualification Data: For Installer and testing agency. B. Product Test Reports: For each alarm panel, for tests performed by a qualified testing agency. C. 1.6 A. Field quality-control reports. CLOSEOUT SUBMITTALS Operation and Maintenance Data: For alarm panels to include in emergency, operation, and maintenance manuals. 1.7 A. QUALITY ASSURANCE Installer Qualifications: Qualify Installers for vacuum and gas piping systems for healthcare facilities according to ASSE Standard #6010 for medical-gas-system installers. B. Testing Agency Qualifications: An independent testing agency, with the experience and capability to conduct the vacuum and gas piping testing indicated, that is a member of the Medical Gas Professional Healthcare 22 64 00 - 1 Mercy Hospital of Buffalo Catholic Health System nd 2 Floor Patient Holding Center rd 3 Floor Locker Rooms Shaflucas Architects, PC Project No. 0649 Organization or is an NRTL, and that is acceptable to authorities having jurisdiction. 1. Qualify testing personnel for vacuum and gas piping systems for healthcare facilities medical-gas-system according inspectors to and ASSE Standard #6020 ASSE Standard #6030 for for medical-gas-system verifiers. PART 2 - PRODUCTS 2.1 A. 2.2 A. SYSTEM DESCRIPTION Gas and Vacuum Systems Monitored: 1. Medical-surgical vacuum, designated "medical vacuum." 2. Oxygen, designated "medical oxygen." MANUFACTURERS Manufacturers: Subject to compliance with requirements, provide products by one of the following: B. 1. Allied Healthcare Products Inc. 2. Amico Corporation. 3. BeaconMedaes. 4. Ohio Medical Corporation. 5. Tri-Tech Medical. Source Limitations: Obtain medical alarm systems and components from single manufacturer. 2.3 A. GENERAL REQUIREMENTS FOR ALARM PANELS Description: Factory wired with audible and color-coded visible signals to indicate specified functions. 1. Mounting: Recessed installation. 2. Enclosures: Fabricated from minimum 0.047-inch- thick steel or minimum 0.05-inch- thick aluminum, with knockouts for electrical and piping connections. B. Components: Designed for continuous service and to operate on power supplied from 120-V ac power source to alarm panels and with connections for low-voltage wiring to remote sensing devices. Include step-down transformers if required. 22 64 00 - 2 Mercy Hospital of Buffalo Catholic Health System nd 2 Floor Patient Holding Center rd 3 Floor Locker Rooms Shaflucas Architects, PC Project No. 0649 C. Pressure Switches or Transducer Sensors: Continuous line monitoring with electrical connections for alarm system. 1. D. Low-Pressure Operating Range: 0 to 100 psig. Vacuum Switches or Pressure Transducer Sensors: Continuous line monitoring with electrical connections for alarm system. 1. 2.4 A. Vacuum Operating Range: 0 to 30 in. Hg. AREA ALARM PANELS Area Alarm Panel AAP-1: Separate trouble alarm signals and indicators for each system. 1. Standards: Comply with NFPA 99 and UL 544. 2. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 3. Include alarm signals when the following condition exists: a. Medical Vacuum: Vacuum drops below 12 in. Hg. b. Medical Oxygen: Pressure drops below 40 psig or rises above 60 psig. B. Area Alarm Panel AAP-2: Separate trouble alarm signals and indicators for each system. 1. Standards: Comply with NFPA 99 and UL 544. 2. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 3. Include alarm signals when the following condition exists: a. Medical Oxygen: Pressure drops below 40 psig or rises above 60 psig. PART 3 - EXECUTION 3.1 A. ALARM-PANEL INSTALLATION Install alarm panels in locations required by and according to NFPA 99. 3.2 A. CONNECTIONS Comply "Vacuum with requirements Piping for for Laboratory piping and 22 64 00 - 3 specified Healthcare in Section 226213 Facilities," and Mercy Hospital of Buffalo Catholic Health System nd 2 Floor Patient Holding Center rd 3 Floor Locker Rooms Shaflucas Architects, PC Project No. 0649 Section 226313 "Gas Piping for Laboratory and Healthcare Facilities." Drawings indicate general arrangement of piping, fittings, and specialties. B. Where installing piping adjacent to alarm panels, allow space for service and maintenance. 3.3 A. IDENTIFICATION Identify system identification components. specified in Comply with requirements Section 220553 "Identification for for Plumbing Piping and Equipment" and according to NFPA 99. 3.4 A. FIELD QUALITY CONTROL Testing Agency: Engage a qualified testing agency to perform tests and inspections. B. Manufacturer's Field representative to Service: test Engage and a inspect factory-authorized components, service assemblies, and equipment installations, including connections. C. Perform the following tests and inspections with the assistance of a factory-authorized service representative: 1. Perform each visual and mechanical inspection. 2. Operational Test: After electrical circuitry has been energized, start units to confirm proper unit operation. 3. Test and adjust controls and safeties. Replace damaged and malfunctioning panels and equipment. D. Alarm panels will be considered defective if they do not pass tests and inspections. E. 3.5 A. Prepare test and inspection reports. STARTUP SERVICE Engage a factory-authorized service representative to perform startup service. 1. Complete installation and startup checks according manufacturer's written instructions. 3.6 A. ADJUSTING Adjust initial alarm panel pressure and vacuum set points. 22 64 00 - 4 to Mercy Hospital of Buffalo Catholic Health System nd 2 Floor Patient Holding Center rd 3 Floor Locker Rooms Shaflucas Architects, PC Project No. 0649 3.7 A. DEMONSTRATION Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain alarm panels and computer-interface cabinet. - - - END - - - 22 64 00 - 5