Stanpro - Emergency Lighting Catalog

advertisement
02/2009/19
2:37 PM
Page 249
EMERGENCY SERIES
07- emergency
249
07- emergency
02/2009/19
2:37 PM
Page 250
Codes & Standards
Extracts from the National Building Code of Canada - 1995
3.2.6.
Additional Requirements for High Buildings
(See Appendix B.)
3.2.6.1. Application
1) This Subsection applies to a building
a) Of Group A. D. E or F major occupancy classification that is more than
(I) 36 m high, measured between grade and the floor level of the top
storey or
(II) 18 m high, measured between grade and the floor level of the top
storey, and in which the cumulative or total occupant load on or above
any storey above grade, other than the first storey, divided by
1.8 times the width in metres of all exit stairs at that storey,
exceeds 300.
(b) Containing a Group B major occupancy in which the floor level of the
highest storey of that major occupancy is more than 18 m above grade(c)
containing a floor area or part of a floor area located above the third storey
designed or intended as a Group B, Division 2 occupancy, and
(d) Containing a Group C major occupancy whose floor level is more than
18 m above grade.
EMERGENCY SERIES
250
250
3.2.7. Lighting and Emergency Power Systems
3.2.7.3. Emergency Lighting
1) Emergency lighting shall be provided to an average level of illumination
not less than 10 Ix at floor or tread level in
(a) exits,
(b) principal routes providing access to exit in an open floor area,
(c) corridors used by the public,
(d) corridors serving patients’ sleeping rooms,
(e) corridors serving classrooms,
(f) underground walkways,
(g) public corridors, and
(h) floor areas or parts thereof where the public may congregate in
(I) Group A, Division 1 occupancies, or
(II) Group A, Division 2 and 3 occupancies having anoccupant load
of 60 or more.
2) Emergency lighting to provide an average level of illumination of not less
than 10 Ix at floor or catwalk level shall be included in a service space
referred to in Sentence 3.2.1.1.(7).
3) The minimum value of the illumination required by Sentences (1) and (2)
shall be not less than 1 Ix.
3.2.7.4. Emergency Power for Lighting
1) An emergency power supply shall be
(a) provided to maintain the emergency lighting required by this Subsection
from a power source such as batteries or generators that will continue to
supply power in the event that the regular power supply to the buildings
is interrupted and
(b) so designed and installed that upon failure of the regular power it will
assume the electrical load automatically for a period of
(I) 2 h for a building within the scope of Subsection 3.2.6,
(II) 1 h for a building of Group B major occupancy classification that is not
within the scope of Subsection 3.2.6. and
(III) 30 min for a building of any other occupancy. (See appendix A).
2) If self-contained emergency lighting units are used, they shall conform to
CSA C22.2 No. 141-M, ‘Unit Equipment for Emergency Lighting.”
3.4.5.Exit Signs
3.4.5.1.Exit Signage
1) Every exit door other than the main entrance to a room or building
shall have an exit sign placed over or adjacent to it if the exit serves
(a) a building more than 2 storeys in building height,
(b) a building having an occupant load more than 150, or
(c) a room or floor area that has a fire escape as part of a required means of
egress.
2) Every exit sign shall
(a) be visible from the exit approach.
(b) have the word EXIT or SORTIE displayed in plain legible letters, and
(c) be illuminated continuously while the building is occupied
3) Exit signs shall consist of
(a) red letters on a contrasting background or contrasting letters on a red
background, with the letters not less than 114 mm high and having a
19 mm stroke, if the sign in internally illuminated, and
(b) white letters on a red background or red letters on a contrasting
background that is white or light tint, with letters not less than 150 mm
high and having a 19 mm stroke, if the sign is externally illuminated.
4) If illumination of an exit sign is provided from an electrical circuit,
that circuit shall
(a) serve no equipment other than emergency equipment, and
(b) be connected to an emergency power supply as described in
Sentence 3.2.7.4.(1).
5) If necessary, the direction of egress in public corridors and passage ways
shall be indicated by a sign conforming to sentence (3) with a suitable
arrow or pointer indicating the direction of egress.
6) Except for egress doorways described in Sentence 3.3.2.3(4) and
except for the main entrance door, an Exit sign conforming to
Sentences (2), (3) and shall be placed over adjacent to every egress
doorway from rooms with an occupant load more than 60 in Group A,
Division 1 occupancies, dance halls, licensed beverage establishments
and other similar occupancies that, when occupied, have lighting levels
below that which would provide easy identification of the egress doorway.
3.4.5.2 Signs for Basement Stairs and Ramps.
1) In a building more than 2 storeys in building height, any part of an exit
ramp or stair that continues past an exterior exit door down to a basement shall be clearly marked.
9.9.10. Signage
9.9.10.1. Application.
1) This Subsection applies to all exits except those serving not more than
one dwelling unit.
9.9.10.2. Visibility of Exits.
1) Exits shall be located so as to be clearly visible or their locations shall be
clearly indicated.
9.9.10.3. Required Exit Signs.
1) Except for the main entrance door to a building, every exit door in a
building 3 storeys in building height or in a building having an occupant
load greater than 150 shall have an exit sign over adjacent to it.
9.9.10.4. Exit Direction Signs.
1) Exit direction signs shall be placed in corridors and passageways where
necessary to indicate the direction of exit travel.
9.9.10.5. Visibility of Exit Signs.
1) Exit signs shall be installed so as to be visible from the exit approach and
shall be illuminated continuously while the building is occupied.
9.9.10.6. Lettering
1) Exit signs shall have the word EXIT or SORTIE in red letters on a
contrasting background or a red background with contrasting letters
when the sign is internally lighted, and white letters on a red background
or red letters on a white background when the sign is externally lighted.
2) Lettering referred to in Sentence (1) shall be made with not less than
19 mm wide strokes and be not less than 150 mm high when the sign is
externally lighted, and not less than 114 mm high when the sign is
internally lighted.
9.9.10.7 Illumination
1) Illumination of exit signs required in Article 9.9.1 0.3. shall conform to
sentences 9.9.11.3. (2) and (3).
2) Where illumination of exit signs required in article 9.9.10.3. is provided by
an electrical circuit, that circuit shall serve no equipment other than
emergency equipment.
9.9.10.7. Exits Continuing to a basement.
1) In buildings 3 storeys in building height any part of an exit ramp or stair
that continues down to a basement past an exterior exit door shall be
clearly marked to indicate that it does not lead to an exit where the
portion below ground level may be mistaken as the direction of exit
travel.
9.9.11. Lighting
9.9.11.3. Emergency Lighting
1) Emergency lighting shall be provided in
(a) exits
(b) principal routes providing access to exit in an open floor area.
(c) corridors used by the public
(d) underground walkways and
(e) public corridors
2) Emergency lighting required in Sentence (1) shall be provided from a
source of energy separate from the electrical supply for the building.
3) Lighting required in Sentence (1) shall be designed to be automatically
actuated for a period of at least 30 min. when the electric lighting in the
affected is interrupted.
4) Illumination from lighting required in Sentence (1) shall be provided to
average levels of not less than10 LX at floor or tread level.
5) Where incandescent lighting is provided, lighting equal to 1 W/m2 of floor
area shall be considered to meet the requirement in Sentence (4).
6) Where self-contained emergency lighting units are used, they shall
conform to CSA C22.2 No.141-M," Unit Equipment for Emergency
Lighting ".
07- emergency
02/2009/19
2:37 PM
Page 251
Codes & Standards
9.9.10.7. Exits Continuing to a basement.
1) In buildings 3 storeys in building height any part of an exit ramp or stair
that continues down to a basement past an exterior exit door shall be
clearly marked to indicate that it does not lead to an exit where the
portion below ground level may be mistaken as the direction of exit
travel.
9.9.11. Lighting
9.9.11.3. Emergency Lighting
1) Emergency lighting shall be provided in
(a) exits
(b) principal routes providing access to exit in an open floor area.
(c) corridors used by the public
(d) underground walkways and
(e) public corridors
2) Emergency lighting required in Sentence (1) shall be provided from a
source of energy separate from the electrical supply for the building.
3) Lighting required in Sentence (1) shall be designed to be automatically
actuated for a period of at least 30 min. when the electric lighting in the
affected is interrupted.
4) Illumination from lighting required in Sentence (1) shall be provided to
average levels of not less than10 LX at floor or tread level.
5) Where incandescent lighting is provided, lighting equal to 1 W/m2 of floor
area shall be considered to meet the requirement in Sentence (4).
6) Where self-contained emergency lighting units are used, they shall
conform to CSA C22.2 No.141-M," Unit Equipment for Emergency
Lighting ".
Examples
Motion picture theatres
Television studios admitting a viewing audience
Art galleries
Auditoria
Bowling alleys
Churches and similar places of worship
Club, nonresidential
Community halls
Court rooms
Dance halls
Exhibition halls (other than classified in Group E)
Gymnasia
Arenas
Rinks
Amusement park structures
(not elsewhere classified)
Bleachers
Jails
Penitentiaries
Police stations with detention quarters
Children's custodial homes
Convalescent homes
Hospitals
Infirmaries
Orphanages
Apartments
Boarding houses
Clubs, residential
Colleges, residential
Convents
Dormitories
Banks
Barber and hairdressing shops
Beauty parlours
Dental offices
Dry cleaning establishments
Self-service, not using flammable or explosive solvents or cleaners
Department stores
Exhibition halls
Markets
Bulk plants for flammable liquids
Bulk storage warehouses for hazardous substances
Lacquer factories
Mattress factories
Chemicals manufacturing or processing plants
Distilleries
Dry cleaning plants
Feed mills
Aircraft hangars
Box factories
Candy plants
Cold storage plants
Dry cleaning establishments not using flammable or explosive
solvents or cleaners
Storage rooms
Television studios not admitting a viewing audience
Warehouses
Wholesale rooms
Woodworking factories
Workshops
Creameries
Factoriesparking garages
Storage rooms
Power plants
Workshops
Opera houses
Theatres, including experimental theatres
Lecture halls
Libraries
Licensed beverage establishments
Museums
Passenger stations and depots
Recreational piers
Restaurants
Schools and colleges, non-residential
Undertaking premises
Indoor swimming pools with or without spectator seating
Grandstands
Reviewing stands
Stadia
Psychiatric hospitals with detention quarters
Reformatories with detention quarters
Prisons
Psychiatric hospitals without detention quarters
Reformatories without detention quarters
Sanitoria without detention quarters
Nursing homes
Hotels
Houses
Loading houses
Monasteries
Motels
Schools, residential
Laundries, self-service
Medical offices
Offices
Police stations without detention quarters
Radio stations
Small tool and appliance rental and service establishments
Shops
Stores
Supermarkets
Flour mills
Grain elevators
Cereal mills
Paint, varnish and pyroxylin product factories
Rubber processing plants
Spray painting operations
Waste paper processing plants
Mattress factories
Planning mills
Printing plants
Repair garages
Salesrooms
Services stations
Electrical substations
Factories
Freight depots
Helicopter landing areas on roofs
Laboratories
Laundries except self-service
Storage garages including open air
Laboratories
Warehouses
Salesrooms
Samples display rooms
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
Group
Group
A
1
A
2
A
3
A
4
B
1
B
2
EMERGENCY SERIES
Classification by Group
C
D
251
E
F
1
F
2
F
3
07- emergency
EMERGENCY SERIES
252
02/2009/19
2:37 PM
Page 252
07- emergency
02/2009/19
2:37 PM
Page 253
ATD options
Auto test &
self diagnostic
Description
Visual indication
The Stanpro Auto-Test and Self-Diagnostics option incorporates an
advanced microprocessor based controller to accurately perform
fully automated monitoring and testing. The system continuously
monitors normal unit status and automatically performs battery discharge tests at scheduled intervals. The testing improves unit reliability by exercising the batteries and einsuring functional emergency
operation. The self-diagnostic logic circuits monitor for battery and
charger malfunctions, transfer circuit problems and emergency lamp
circuit failure. Failure of these functions is signalled by a dedicated,
tri-colour LED indicator. The fault indication remains latched in the
system until cleared by either correcting the problem or resetting the
system.
The Stanpro Auto-Test and Self-Diagnostics option utilizes a tricolour LED indicator to visually signal the operational condition of the
unit. By combining this function into a single LED, Stanpro has greatly simplified the process of determining unit status. Additionally, the
3 colour system is highly intuitive and simple to understand: red for
critical faults, yellow for functional faults and green for normal operation. Indication is further enhanced by appropriately flashing the
indicated colour versus a steady state illumination. This “RED-YELLOW-GREEN” stoplight approach greatly simplifies trouble recognition by maintenance staff, thereby speeding repairs and enhancing
equipment reliability.
Electrical
NORMAL OPERATION
• 120/347VAC 60Hz Input, field selectable
• 6VDC, 12VDC or 24VDC emergency power output
versions (as specified)
• Fully automated, microprocessor based controller
• Momentary push button test switch
• Pilot LED for CHARGE
• Tri-colour, flashing and steady state indicator LED for
system STATUS
• 10 Minute time delay of transfer back to AC power once power is
restored (allows for HID lighting to warm-up and restrike)
• High efficiency, rapid recovery, precision control charging system
• Fully automatic, current limited charger
• Line latched, low voltage protection
• Solid state design and construction
• Brownout and short circuit protection
• Temperature compensated
• Large magnum terminal screw type connectors for remote load
connection
• CSA C22.2 No 141 Performance Certified
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Status indicator is steady green.
• Unit is functioning normally and successfully
completed the most recent battery
discharge test.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
LAMP FAULT
Status indicator is steady yellow.
• The lamp circuit has been disconnected or the
lamps have burnt out.
BATTERY OR CHARGER FAULT
Status indicator is either steady red or flashing red.
• The batteries are disconnected or the charger
has failed (flashing)
• The unit failed the most recent battery
discharge test (steady)
Continued on next page...
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
253253
07- emergency
02/2009/19
2:37 PM
Page 254
ATD options
Auto test &
self diagnostic
Approvals:
CSA Certified to
C22.2 #141
EMERGENCY SERIES
254
Operation
Diagnostic
Initialization
1) The Auto-Test can be reset or initialized by first disconnecting the
batteries and then turning off the AC power supply. Reconnect the
batteries and turn on AC power to complete the reset.
2) Upon power-up, all automated timers are reset to zero and all status indicators will clear.
3) A unit operational status test will be initiated. The STATUS indicator may flash green during this test.
4) After successfully completing the test, the STATUS indicator will
light steady green.
5) Any operational faults will result in the STATUS indicator
lighting/flashing in another colour.
Battery Condition
Should the batteries become disconnected, the STATUS indicator will
flash red. If the batteries fail to provide the required power during a
discharge test, the STATUS indicator will light steady red.
Automated Test
1) The internal timer will initiate the appropriate discharge test once
every 30 days.
2) The test will be delayed by 24 hours if a manual test or power interruption had occurred in the previous 24 hours.
3) The CHARGE indicator will turn off and any connected load/lamps
will illuminate for 5 or 30 minutes depending on the test scheduled.
4) After successfully completing the test, the STATUS indicator will
light steady green.
5) Any operational faults will result in the STATUS indicator
lighting/flashing in another colour.
Lamps/Connected Load
Should the lamp heads become disconnected or lamps burn out, the
STATUS indicator will flash yellow.
Manual Test
1) To manually initiate an operational test, press and release the TEST
push-button.
2) The CHARGE indicator will turn off and any connected load/lamps
will illuminate.
3) The STATUS indicator may briefly flash then become a steady
green.
4) The connected load will remain on for 10 mins. (automatic re-transfer delay) and then turn off.
5) The CHARGE LED will illuminate steady or flash depending on the
required battery recharge.
6) After successfully completing the test, the STATUS indicator will
light steady green.
7) Any operational faults will result in the STATUS indicator
lighting/flashing in another colour.
Battery Charger
Charger output is continuously monitored. Should output fail to meet
the design parameters, the STATUS indicator will flash red.
Battery Transfer
Should the system fail to transfer to battery power during an AC
power failure, the STATUS indicator will flash red.
Code compliance
The automated testing performed by the Stanpro Auto-Test system
has been designed to comply with all of the requirements of the
National Fire Code. Every month, a 5 minute discharge and diagnostic test checks the operational status of the unit. Every 6 months, this
test is extended to the full 30 minute, Code required duration.
Additionally, following every other 6 month test (or once a year), the
unit will repeat the same test 24 hours following the first test. This
insures that the battery charger is recharging the battery in accordance with Code requirements as follows:
National Fire Code of Canada - 1995
Section 6.7 Emergency Power Systems and
Unit Equipment for Emergency Lighting
6.7.1.6. Inspection of Equipment
...3) After completion of the test required in Clause (2)(b), the
charging conditions for voltage and current and the recovery
period shall be tested to ensure that the charging system is
functioning in accordance with the manufacturer’s specifications.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 255
SLA
11.6250”
10.3750”
5.8750”
2.9750”
Compact
Emergency
Light Series
12.2500”
Head Types
4.7500
2.2500
2.2500
2.6250
5.7500
3.7500
3.7500
Type N
Type S
Type M
Type L
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
MR 16
Die Cast
Max 50 watts
PAR 36
Thermoplastic
Max 55 watts
Approvals:
CSA Certified to
C22.2 #141
Description
Circuitry
The Stanpro SLA series provides an economical, compact and attractive solution
for typical emergency lighting needs. The low profile, all steel housing is
designed for simple installation and long lasting durability. The SLA is available
in 6V and 12V versions and will provide up to 72W of emergency power for 30
minutes duration. A variety of heads and lamp combinations can be fitted to
either the top, sides or front of the unit, providing great flexibility in meeting specific lighting requirements. Large magnum terminals allow for the connection of
various remote load(s).
The SLA units come complete with high quality, pulse action chargers which are
up to 70% more efficient than constant voltage chargers. The chargers are solid
state and are complete with low voltage disconnect, brownout, and short circuit
protections. Standard dual input of either 120VAC or 347VAC is field selectable.
A dual LED display indicates AC-ON and High charge, and all chargers are complete with a quick test, push-button switch for easy maintenance and testing.
Recharge time is 24 hours. Optional automatic self-diagnostic/test control
boards are also available.
Features
Warranty
The SLA unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits; a 120 volt line cord is installed on standard models. A
maintenance free, sealed lead acid battery is included with the unit, which will
provide the specified wattage for 30 minutes duration. A universal key hole
mounting pattern is stamped into the back of the unit as well as conduit knockouts. White finish is standard, and custom colours are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
4.5000
Ordering Guide
—
Series
Voltage
Wattage
Battery
Heads
SLA
06-6 volt
12-12 volt
see rating
chart
below
(eg. 036)
Blank - regular
HP - high power
factor
Lamp Watts
00-no heads
(eg. 09)
1N-1 PAR 18(standard)
see lamp
2N-2 PAR 18(standard) selection chart
1S-1 MR 16
below
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16, 2M-2 MR16
3M-3 MR16, 4M-4 MR16
Lamp
Options
Q-Quartz Halogen
T-Tungsten
SBQ-Quartz
sealed beam
SBT-Tungsten
sealed beam
AT, OBM, FD5,
FD6, TD*, TP,
TPB, BD, IRT*,
LD, RFS*, TLP*,
ACTB, DCTB, SP,
A, CPS, CT, SMH,
TFC, TPX, V, FD2,
FD3, FD4
Wireguard
* Specify voltage
Lamp Selection
Model Ratings
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
SLA06018
6
18
9
NA
NA
SLA06036
6
36
18
9
NA
SLA06050
6
50
25
12
NA
6 Volts
12 Volts
PAR18 - Small Heads
Model
SLA12036
SLA12050
SLA12072
12
12
12
36
50
72
18
25
36
9
12
18
NA
NA
9
Q
T
8W, 10W, 12W
8W, 10W, 12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
PAR36 - Large Heads
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W, 35W
Q
5.4W, 9W, 18W, 25W
T 5.4W, 7.2W, 9W, 18W, 25W
10W, 8W, 12W, 20W
8W, 12W, 30W, 35W, 55W
SB Q
9W, 18W
25W
SB T
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
See options
descriptions on
page 334
255
07- emergency
02/2009/19
2:37 PM
Page 256
SLB
14.7500”
13.5000”
9.0000”
Commercial
Emergency
Light Series
3.2870”
10.0000”
Head Types
4.7500
2.2500
2.2500
2.6250
5.7500
Approvals:
CSA Certified to
C22.2 #141
4.5000
3.7500
3.7500
Type N
Type S
Type M
Type L
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
MR 16
Die Cast
Max 50 watts
PAR 36
Thermoplastic
Max 55 watts
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLB series is designed to provide dependable and efficient emergency lighting in a modern, low profile design. The SLB utilizes a sturdy, all steel
housing that facilitates quick and simple installation. The SLB is available in 6V
and 12V versions and will provide up to 100W of emergency power for 30 minutes duration. A variety of heads and lamp combinations can be fitted to either
the top, sides or front of the unit, providing great flexibility in meeting specific
lighting requirements. Large magnum terminals allow for the connection of
various remote load(s).
The SLB units come complete with high quality, pulse action chargers which are
up to 70% more efficient than constant voltage chargers. The chargers are solid
state and are complete with low voltage disconnect, brownout, and short circuit
protections. Standard dual input of either 120VAC or 347VAC is field selectable.
A dual LED display indicates AC-ON and High charge, and all chargers are complete with a quick test, push-button switch for easy maintenance and testing.
Recharge time is 24 hours. Optional automatic self-diagnostic/test control
boards are also available.
Features
Warranty
The SLB unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits. A maintenance free, sealed lead acid battery is included with the unit, which will provide the specified wattage for 30 minutes duration. A universal key hole mounting pattern is stamped into the back of the unit
as well as conduit knockouts. White finish is standard, and custom colours are
optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
Series
Voltage
Wattage
Battery
SLB
06-6 volt
12-12 volt
see rating
chart
below
(eg. 036)
Blank - regular
HP - high power
factor
256
Voltage
SLB06072
SLB06100
6
6
SLB12100
12
Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 min.
72
36
18
9
100
50
25
12
100
Lamp Watts
Lamp
Q-Quartz Halogen
T-Tungsten
SBQ-Quartz
sealed beam
SBT-Tungsten
sealed beam
Lamp Selection
Model Ratings
Model
Heads
00-no heads
(eg. 09)
1N-1 PAR 18(standard)
see lamp
2N-2 PAR 18(standard) selection chart
1S-1 MR 16
below
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16, 2M-2 MR16
3M-3 MR16, 4M-4 MR16
50
25
* Specify voltage
6 Volts
12 Volts
PAR18 - Small Heads
Q
T
Options
AT, OBM, FD5,
FD6, TD*, TP,
TPB, BD, IRT*,
LD, RFS*, TLP*,
ACTB, DCTB, SP,
A, CPS, CT, SMH,
TFC, TPX, V, FD2,
FD3, FD4
Wireguard
Mounting shelf
8W, 10W, 12W
8W, 10W, 12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
See options
descriptions on
page 334
MR16 - Small Heads c/w MR16 Lamp
12
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
PAR36 - Large Heads
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W, 35W
Q
5.4W, 9W, 18W, 25W
T 5.4W, 7.2W, 9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
SB Q
9W, 18W
25W
SB T
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 257
SLC
A=15.8750”
B=15.8750”
A=14.6250”
B=14.6250”
A=10.1250”
B=10.1250”
A=4.2620”
B=8.5238”
Head Types
Specification
Emergency
Light Series
A=14.2500”
B=12.9000”
4.7500
2.2500
2.2500
2.6250
5.7500
3.7500
Approvals:
CSA Certified to
C22.2 #141
3.7500
Type N
Type S
Type M
Type L
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
MR 16
Die Cast
Max 50 watts
PAR 36
Thermoplastic
Max 55 watts
Description
Circuitry
The Stanpro SLC series is designed to provide dependable and efficient emergency lighting in a modern, low profile design. The SLC utilizes a sturdy, all steel
housing that facilitates quick and simple installation. The SLC is available in 6V,
12V and 24V versions and will provide up to 360W of emergency power for 30
minutes duration. A variety of heads and lamp combinations can be fitted to
either the top, sides or front of the unit, providing great flexibility in meeting specific lighting requirements. Large magnum terminals allow for the connection of
various remote load(s).
The SLC units come complete with high quality, pulse action chargers which are
up to 70% more efficient than constant voltage chargers. The chargers are solid
state and are complete with low voltage disconnect, brownout, and short circuit
protections. Standard dual input of either 120VAC or 347VAC is field selectable.
A dual LED display indicates AC-ON and High charge, and all chargers are complete with a quick test, push-button switch for easy maintenance and testing.
Recharge time is 24 hours. Optional automatic self-diagnostic/test control
boards are also available.
Features
Warranty
The SLC unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits. A maintenance free, sealed lead acid battery is included with the unit, which will provide the specified wattage for 30 minutes duration. A universal key hole mounting pattern is stamped into the back of the unit
as well as conduit knockouts. White finish is standard, and custom colours are
optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
4.5000
Ordering Guide
—
Series
Voltage
Wattage
Battery
SLC
06-6 volt
12-12 volt
see rating
chart
below
(eg. 036)
Blank - regular
HP - high power
factor
Model Ratings
Heads
Lamp Watts
00-no heads
(eg. 09)
1N-1 PAR 18(standard)
see lamp
2N-2 PAR 18(standard) selection chart
1S-1 MR 16
below
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16, 2M-2 MR16
3M-3 MR16, 4M-4 MR16
Lamp
Options
Q-Quartz Halogen
T-Tungsten
SBQ-Quartz
sealed beam
SBT-Tungsten
sealed beam
AT, OBM, FD5,
FD6, TD*, TP,
TPB, BD, IRT*,
LD, RFS*, TLP*,
ACTB, DCTB, SP,
A, CPS, CT, SMH,
TFC, TPX, V, FD2,
FD3, FD4
Wireguard
Mounting shelf
Lamp Selection
6 Volts
Q
T
* Specify voltage
12 Volts
PAR18 - Small Heads
24 Volts
8W, 10W, 12W
8W, 10W, 12W
12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
9W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
12W, 20W,
35W, 50W, 70W
PAR36 - Large Heads
Q
T
SB Q
SB T
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W, 35W
12W, 20W
5.4W, 7.2W, 9W, 18W, 25W
5.4W, 9W, 18W, 25W
9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
55W, 70W
9W, 18W
25W
N/A
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
See options
descriptions on
page 334
257
07- emergency
02/2009/19
2:37 PM
Page 258
SLD
15.88”
14.63”
10.13”
High Capacity
Emergency
Light Series
8.52”
Head Types
18.13”
4.7500
2.2500
2.2500
2.6250
5.7500
Approvals:
CSA Certified to
C22.2 #141
4.5000
3.7500
3.7500
Type N
Type S
Type M
Type L
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
MR 16
Die Cast
Max 50 watts
PAR 36
Thermoplastic
Max 55 watts
EMERGENCY SERIES
Description
Circuitry
The SLD series from Stanpro is designed to deliver the power needed to supply
the most demanding emergency lighting requirements. By utilizing an all steel
design, the SLD provides a sturdy housing that facilitates a quick and simple
installation. The SLD is available in high capacity 24V versions that provide up to
720W of emergency power for 30 minutes duration. A variety of heads and lamp
combinations can be fitted to either the top, sides or front of the unit, providing
great flexibility in meeting specific lighting requirements. Large magnum terminals allow for the connection of various remote load(s).
The SLD units come complete with high quality, pulse action chargers which are
up to 70% more efficient than constant voltage chargers. The chargers are solid
state and are complete with low voltage disconnect, brownout, and short circuit
protections. Standard dual input of either 120VAC or 347VAC is field selectable.
A dual LED display indicates AC-ON and High charge, and all chargers are complete with a quick test, push-button switch for easy maintenance and testing.
Recharge time is 24 hours. Optional automatic self-diagnostic/test control
boards are also available.
Features
Warranty
The SLD unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits. A maintenance free, sealed lead acid battery is
included with the unit, which will provide the specified wattage for 30 minutes
duration. A universal key hole mounting pattern is stamped into the back of the
unit as well as conduit knockouts. White finish is standard, and custom colours
are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
258
Series
Voltage
Wattage
Battery
SLD
06-6 volt
12-12 volt
see rating
chart
below
(eg. 036)
Blank - regular
HP - high power
factor
Voltage
SLD24350
SLD24550
SLD24720
24
24
24
Lamp Watts
00-no heads
(eg. 09)
1N-1 PAR 18(standard)
see lamp
2N-2 PAR 18(standard) selection chart
1S-1 MR 16
below
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16, 2M-2 MR16
3M-3 MR16, 4M-4 MR16
Lamp
Q-Quartz Halogen
T-Tungsten
SBQ-Quartz
sealed beam
SBT-Tungsten
sealed beam
Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 min.
350
175
87
43
550
275
137
68
720
360
180
90
24 Volts
PAR18 - Small Heads
AT, OBM, FD5,
FD6, TD*, TP,
TPB, BD, IRT*,
LD, RFS*, TLP*,
ACTB, DCTB, SP,
A, CPS, CT, SMH,
TFC, TPX, V, FD2,
FD3, FD4
Wireguard
Mounting shelf
See options
descriptions on
page 334
12W
Q
9W, 18W
T
MR16 - Small Heads c/w MR16 Lamp
Q
Options
* Specify voltage
Lamp Selection
Model Ratings
Model
Heads
10W, 12W, 20W, 35W, 50W
PAR36 - Large Heads
Q
T
SB Q
Q = Quartz Halogen
12W, 20W
9W, 18W, 25W
55W, 70W
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 259
SLY-2
5-1/2’’
Decorative
Thermoplastic
Emergency
Light Series
11’’
5’’
Description
Circuitry
The Stanpro SLY-2 series is a decorative emergency light which will fit well in
any commercial application. The SLY-2 comes with two EMR16 base, integral
lamps which will provide superior lighting in the event of a power outage. The
housing and lens is made of impact, heat and scratch resistant, UV stabilized
thermoplastic. Mounting is made easy with the universal mounting plate in the
back.
The Stanpro SLY-2 emergency lighting units come complete with high quality,
pulse action chargers which are up to 70% more efficient than constant voltage
chargers. The chargers are solid state and are complete with low voltage disconnect, brownout, and short circuit protections. A LED display indicates AC-ON status and all chargers are complete with a quick test, push-button and optional
laser test switch for easy maintenance and testing. Recharge time is 24 hours.
Features
Warranty
The SLY-2 unit is a completely self-contained emergency light which is made for
use on 120 or 347 volt circuits. A 6V maintenance free, sealed lead acid battery
is included with the SLY-2 which will provide 30 watts for 30 minutes of emergency lighting. The universal mounting plate is made to fit over a standard octagon box for simple, low cost installation. Once the plate is pre-mounted and all
wiring connections terminated, the unit is snapped onto the plate, completing
installation. White finish is standard.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
Ordering Guide
Series
Lamp
Options
SLY-2
Q - see lamp selection
/LT - laser test
/TP - tamper resistant screws
Lamp Selection
6 Volts
EMR16*
Q
8W, 10W
Q = Quartz Halogen
* Come with specialty emergency lighting MR16
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
259
07- emergency
EMERGENCY SERIES
260
02/2009/19
2:37 PM
Page 260
07- emergency
02/2009/19
2:37 PM
Page 261
SLG-2
Thermoplastic
Emergency
Light Series
7.2500”
2.7500”
4.8750”
8.7500”
Description
Circuitry
The SLG-2 series from Stanpro provides a compact and economical solution to
suit a variety of emergency lighting needs. The entire unit has been designed to
install quickly and easily to electrical junction boxes (not supplied) by utilizing a
snap-on base plate. The SLG-2 is a stand alone unit available in 6V capable of
providing up to 30w of emergency power for 30 minutes duration. A variety of
head and lamp combinations can be fitted to the unit to suit specific requirements.
The Stanpro SLG-2 units come complete with high quality chargers. The chargers are solid state and are complete with low voltage disconnect, brownout, and
short circuit protections. Standard dual input of either 120VAC or 347VAC is field
selectable. An LED display indicates AC-ON, and all chargers are complete with
a quick test, push-button switch for easy maintenance and testing. Recharge
time is 24 hours.
Features
The SLG-2 unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits. The housing is made of durable, UV stabilized
thermoplastic. A maintenance free, sealed lead acid battery is included with the
unit which will provide the specified wattage for 30 minutes duration. All snapon base plates are complete with a universal knock out pattern. Once the plate
is pre-mounted and all wiring connections terminated, the unit is snapped onto
the plate, completing installation. White finish is standard.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
Ordering Guide
261
Series
Heads
Options
SLG-2
00 - no head
1N-1 PAR 18(standard)
2N-2 PAR 18(standard)
Line cord available with 120V unit
Lamp Selection
6 Volts
EMR16*
SLG-2
Q
8W, 10W, 12W
T
5.4W, 7.2W, 9W
Q = Quartz Halogen T = Tungsten
* Come with specialty emergency lighting MR16
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 262
11.7500”
SLE-2
2.3750”
Decorative
Thermoplastic
Emergency
Light Series
5.0000”
Approvals:
CSA Certified to
C22.2 #141
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLE-2 series is a slim line decorative emergency light which will fit
well in any commercial application. The SLE-2 comes with two wedge base,
integral lamps which will provide uniform lighting in the event of a power outage. Contact factory for optional lamps. The housing and lenses are made of
impact, heat and scratch resistant, UV stabilized thermoplastic. Mounting is
made easy with the universal mounting plate in the back, and conduit knockouts
on the sides of the unit.
The Stanpro SLE-2 emergency lighting units come complete with high quality,
pulse action chargers which are up to 70% more efficient than constant voltage
chargers. The chargers are solid state and are complete with low voltage disconnect, brownout, and short circuit protections. A LED display indicates AC-ON status and all chargers are complete with a quick test, push-button switch for easy
maintenance and testing. Recharge time is 24 hours.
Features
The SLE-2 unit is a completely self-contained emergency light which is made for
use on 120 or 347 volt circuits. A 6V maintenance free, sealed lead acid battery
is included with the SLE-2, which will provide 30 watts for 30 minutes of emergency lighting. The universal mounting plate is made to fit over a standard octagon box for simple, low cost installation. Once the plate is pre-mounted and all
wiring connections terminated, the unit is snapped onto the plate, completing
installation. White finish is standard.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
262
SLE-2
SLE-2
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 263
16.5000”
SLP-2
Polycarbonate
Emergency Light
Series
4.6500”
5.0000”
Description
Circuitry
The SLP-2 series from Stanpro offers a decorative, yet economical solution for
your emergency lighting needs. The housing is made of thermoplastic and the
lens are made of injection moulded, high impact polycarbonate, corrosion and
flame resistant. The SLP-2 is a stand alone unit available in 6V and will provide
30 watts for 30 minutes of emergency lighting. The 2 square heads use 9w
wedge base incandescent lamps which are fully adjustable and have an impact
and heat resistant polystyrene lens. Polished specular reflectors insure maximum photometric distribution. Contact factory for optional lamps.
The Stanpro SLP-2 emergency lighting units come complete with high quality,
pulse action chargers which are up to 70% more efficient than constant voltage
chargers. The chargers are solid state and are complete with low voltage disconnect, brownout, and short circuit protections. An LED display indicates ACON, and all chargers are complete with a quick test, push-button switch for easy
maintenance and testing. Recharge time is 24 hours.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Features
The SLP-2 unit is a completely self-contained emergency light which is made for
use on 120 or 347 volt circuits. A 6V maintenance free, sealed lead acid battery
is included with the SLP-2 which will provide up to 30 watts for 30 minutes of
emergency lighting. The universal mounting plate is made to fit over a standard
octagon box for simple, low cost installation. Once the plate is pre-mounted and
all wiring connections terminated, the unit is snapped onto the plate, completing installation. White finish is standard.
EMERGENCY SERIES
A
=11.7500”
Approvals:
CSA Certified to
C22.2 #141
Ordering Guide
Series
Options
SLP-2
/K5 - 1/2’’ knockout for pendant mount
/LT - Laser remote test
SLP-2
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
263
07- emergency
02/2009/19
2:37 PM
Page 264
SLW
Specter Series
12 Volt, 36 Watt Virtually
Invisible Emergency Light
Approvals:
CSA Certified to
C22.2 #141
EMERGENCY SERIES
264
Description
Suggested Specifications
Stanpro introduces a virtually invisible emergency light luminaire that is easily
recessed inside the wall or ceiling space. Without compromising the aesthetic
appeal of the interior design, Stanpro provides the architectural community with
an innovative solution that meets emergency lighting codes. When AC power loss
occurs, the lens housing simply extends outward from behind the cover plate.
Instantly energized, the dual-lamp light source provides bright, even illumination
along the path of egress. When AC power is restored, the lamps are extinguished
and the lens housing returns to the closed position… hidden from sight. This
essentially vandal proof luminaire is designed for a wide range of commercial
and residential applications. The Stanpro series luminaire was inspired by the
belief that emergency lighting can be both beautiful and functional. Stanpro’s
revolutionary design offers easy light adjustments, all with a simple turn of the
lens. By directing the light where its needed most, dark areas are minimized,
enabling safe egress in residential and commercial spaces.
Charging Circuitry
Unit shall utilize a solid state, fully automatic, voltage regulated charging system
which will maintain the battery at full capacity without the need for periodic
exercising or equalization. The following features shall be standard: Low voltage
disconnect (LVD), brownout protection and AC lockout.
Battery
The battery shall be maintenance free, sealed lead calcium type. The battery
shall provide trouble-free operation in temperatures up to 85oF (30oC) and is supplied with a one year full, three year pro-rata warranty.
Illumination
Illumination shall be provided by two internally mounted T-5 style 15 watt Xenon
lamps. When mounted on 24’ centers, at 7’ AFF, the unit shall provide an average of 1.10 footcandles between luminaires from base of wall to 5’ from wall.
Housing
Backbox shall be compatible for mechanical fastening to stud or drywall via
screws and/or hanger bars and be supplied with a knockout pattern to facilitate
mounting and wire connections. Screw covers and dry wall screws shall be provided with each unit.
Dust Covers
To protect the units during installation, all Stanpro luminaires will be supplied
with a protective cover to be removed and discarded prior to final electrical connection.
Features
• Compact, recessed luminaire that blends with wall or ceiling
• Entirely self-contained battery unit
• Recessed AC on/push to test LED
• Essentially vandal proof for high-abuse areas
• High-impact polycarbonate coverplate and lens
• Durable, corrosion resistant metal back box
• Adjustable flanges for easy installation in new construction or retrofits (field
selectable)
• Precision lens drive featuring a 30-year rated DC motor
• 2 powerful Xenon lamps with 10,000 hour life
• Innovative optics provide bright, even illumination along the path of Egress
• 120 or 347 VAC 60 Hz input (field selectable)
• Solid state charger with automatic low-voltage disconnect and brownout
protection
• 3 year limited warranty on all units
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
SLW
Voltage
12-12 volt
Lamp Power (W)
011-11W
Lamp
2-Double
Watts
5.5
Lamp
T - Tungsten
Options
NC, AT, RF
See options descriptions
on page 334
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 265
9.5000”
SLSR
8.8750”
Recessed PAR 36
Emergency
Light Series
8.7500”
11.0000”
9.0000”
Description
Circuitry
The Stanpro SLSR recessed ceiling mount emergency light provides an unobtrusive emergency lighting solution for modern design needs. The entire unit is
designed to blend into the decor with only the lamp and trimplate viewable. The
housing that contains the battery and circuitry, fits up and into the ceiling for a
secure mounting, completely out of sight. The SLSR is available in 6VDC supplying 36W of emergency power for 30 minutes duration. A variety of lamps can be
fitted into the unit to meet specific emergency lighting needs.
The Stanpro SLSR recessed emergency lighting units come complete with high
quality, pulse action chargers which are up to 70% more efficient than constant
voltage chargers. The chargers are solid state and are complete with low voltage disconnect, brownout, and short circuit protections. A LED display indicates
AC-ON status and all chargers are complete with a quick test, push-button
switch for easy maintenance and testing. Recharge time is 24 hours.
Features
The SLSR unit is a completely self-contained emergency light, made for use on
120 or 347V circuits. A 6V maintenance free, sealed lead acid battery is included
with the SLSR unit which will provide 36 watts for 30 minutes of emergency lighting. A standard type octagon box is mounted to the top of the unit with all connection wires pre-pulled in to it for simple, low cost installation. White finish trimplate is standard (for special colours consult factory).
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
Ordering Guide
—
Series
Voltage
Wattage
Lamp
SLSR
06-6 volt
036-36W
See Lamp
selection chart
Options
/BK Black trim
Lamp Selection
6 Volts
PAR36 - Large Heads
8W, 10W, 12W, 20W
Q
7.2W, 9W, 18W, 25W
T
8W, 12W, 20W
SB Q
SB T 8W, 9W, 12W, 18W, 30W
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
265
07- emergency
02/2009/19
2:37 PM
Page 266
SLSOR
4.7500”
Recessed T-Bar
Emergency
Light Series
11.6250”
12.8750”
7.1250”
23.6250”
3.2500”
Approvals:
CSA Certified to
C22.2 #141
EMERGENCY SERIES
Description
Circuitry
The SLSOR series from Stanpro provides an unobtrusive emergency lighting
solution for modern design needs. The entire unit is designed to fit into typical Tbar type grid ceilings; simplifying installation while blending into the decor. The
entire steel battery and circuitry housing is located above the ceiling, out of sight
with only the steel cover trim exposed. The SLSOR is available in 6V, 12V and 24V
versions and will provide up to 200W of emergency power for 30 minutes duration. A variety of head and lamp combinations can be fitted to the cover trim and
large magnum terminals allow for the connection of various remote load(s).
The Stanpro SLSOR units come complete with high quality, pulse action chargers which are up to 70% more efficient than constant voltage chargers. The
chargers are solid state and are complete with low voltage disconnect,
brownout, and short circuit protections. Standard dual input of either 120VAC
or 347VAC is field selectable. A dual LED display indicates AC-ON and High
charge, and all chargers are complete with a quick test, push-button switch for
easy maintenance and testing. Recharge time is 24 hours. Optional automatic
self-diagnostic/test control boards are also available.
Features
Warranty
The SLSOR unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits. A maintenance free, sealed lead acid battery is
included with the unit which will provide the specified wattage for 30 minutes
duration. Multiple conduit knockouts are stamped into the unit and chain/cable
mounting holes are provided for secure mounting (cable/chain not included).
White finish is standard, and custom colours are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
266
Series
Voltage
Wattage
Battery
SLSOR
06-6 volt
12-12 volt
24-24 volt
see rating
chart
below
(eg. 036)
Blank - regular
HP - high power
factor
Heads
Lamp Watts
Lamp
00-no heads
(eg. 09)
1N-1 PAR 18(standard)
see lamp
2N-2 PAR 18(standard) selection chart
1S-1 MR 16
below
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16, 2M-2 MR16
3M-3 MR16, 4M-4 MR16
Q-Quartz Halogen
T-Tungsten
SBQ-Quartz
sealed beam
SBT-Tungsten
sealed beam
Options
AT, OBM, FD5,
FD6, TD*, TP,
TPB, BD, IRT*,
LD, RFS*, TLP*,
ACTB, DCTB, SP,
A, CPS, CT, SMH,
TFC, TPX, V, FD2,
FD3, FD4
Wireguard
* Specify voltage
Lamp Selection
Model Ratings
Model
Voltage
Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 min.
72
36
18
9
100
50
25
12
160
80
40
20
180
90
45
23
SLSOR06072
SLSOR06100
SLSOR06160
SLSOR06180
6
6
6
6
SLSOR12072
SLSOR12100
SLSOR12160
SLSOR12200
SLSOR12250
12
12
12
12
12
72
100
160
200
250
36
50
80
100
125
18
25
40
50
62
9
12
20
25
31
SLSOR24144
SLSOR24200
SLSOR24288
24
24
24
144
200
280
72
100
100
36
50
50
18
25
25
6 Volts
Q
T
12 Volts
PAR18 - Small Heads
24 Volts
8W, 10W, 12W
8W, 10W, 12W
12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
9W, 18W
See options
descriptions on
page 334
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
10W, 12W, 20W,
35W, 50W
PAR36 - Large Heads
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W, 35W
12W, 20W
Q
5.4W, 7.2W, 9W, 18W, 25W
5.4W, 9W, 18W, 25W
9W, 18W, 25W
T
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
55W, 70W
SB Q
9W, 18W
25W
N/A
SB T
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 267
A = 21.2500” (sm.)
B = 27.2500” (lg.)
SLMC
5.0000”
5.7500”
5.0000”
Vandal Resistant
Emergency
Light Series
Approvals:
CSA Certified to
C22.2 #141
A = 12.0000” (sm.)
B = 18.0000” (lg.)
Description
Circuitry
The Stanpro SLMC series is designed to withstand exceptional levels of abuse
while providing superior light output. The chassis is constructed from18 gauge
steel, utilizing an interlocking, two piece design that builds additional strength.
Each lamp assembly is fully adjustable and protected from tampering with a
moulded, high impact polycarbonate shield. Both tungsten and quartz lamps can
be utilized for greater layout flexibility. Knockouts for surface mounted conduit
and a stamped universal mounting backplate provide a wide variety of mounting options.
The Stanpro SLMC emergency lighting units come complete with high quality,
pulse action chargers which are up to 70% more efficient than constant voltage
chargers. The chargers are solid state and are complete with low voltage disconnect, brownout, and short circuit protections. Standard dual input of either
120VAC or 347VAC is field selectable. A dual LED display indicates AC-ON and
High charge, and all chargers are complete with a quick test, push-button switch
for easy maintenance and testing. Recharge time is 24 hours.
Features
The SLMC unit is a completely self-contained emergency light, made for use on
120 or 347 volt circuits. A maintenance free, sealed lead acid battery is
included with the unit which will provide the specified wattage for 30 minutes
duration. The universal mounting plate is made to fit over a standard octagon
box for simple installation. White finish is standard, and custom colours are
optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
5.7500”
Ordering Guide
—
Series
Voltage
Wattage
Lamps/Heads
Lamp Watts
Lamp
SLMC
06-6 volt
12-12 volt
24-24 volt
see rating
chart
below
(eg. 160)
10-single lamp
20-double lamps
1M-1 MR16
2M-2 MR16
(eg. 09)
see lamp
selection chart
below
Q-Quartz Halogen
T-Tungsten
Model
SLMC06036
SLMC06050
SLMC06072
SLMC06100
SLMC06160
SLMC12100
SLMC12160
SLMC12200
SLMC12250
SLMC24144
SLMC24200
SLMC24320
SLMC12036
SLMC12050
SLMC12072
Voltage Size
6
6
6
6
6
12
12
12
12
24
24
24
12
12
12
A
A
A
A
A
A
A
A
B
A
A
B
A
A
A
Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 min.
36
18
NA
NA
50
25
NA
NA
72
36
18
NA
100
50
25
NA
160
80
40
20
100
50
25
NA
160
80
40
20
200
100
50
25
250
125
62
31
144
72
36
18
200
100
50
25
320
160
80
40
36
18
9
NA
50
25
NA
NA
72
36
18
9
6 Volts
Q
T
AT, ACTB, DCTB, TD, SP,
FD2, FD3, FD4, FD5, FD6,
TP, TPX, RFS*
* Specify voltage
See options
descriptions on
page 334
Lamp Selection
Model Ratings
Options
12 Volts
PAR18 - Small Heads
24 Volts
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
12W, 20W
7.2W, 9W, 18W
5.4W, 9W, 18W
9W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W, 20W
Q = Quartz Halogen
T = Tungsten
8W, 10W, 12W, 20W, 35W (1 lamp only) 12W, 20W, 35W
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
267
07- emergency
EMERGENCY SERIES
268
02/2009/19
2:37 PM
Page 268
07- emergency
02/2009/19
2:37 PM
Page 269
5.6250”
4.3750”
0.3750”
SLEXS & SLSRS
7.7500”
Commercial Steel
Exit Series
12.0000”
5.6250”
2.2500”
4.37500”
0.3750”
7.7500”
2.2500”
Description
Circuitry
The Stanpro SLEXS & SLSRS series of commercial, slim line steel signs are
designed with a clean, contemporary appearance that is perfectly suited to
todays’ modern interiors. Available in long-life, high brightness LED versions with
energy efficient consumption as low as
All standard LED models are 120/347VAC dual input voltage, available in AC only,
AC/DC and self-powered models. AC/DC models feature universal emergency
backup DC voltages: 6, 12 or 24VDC, each field selectable. Emergency power
wattages for EXIT LED models are as follows:
VDC
EXIT
SORTIE
120V
1.2
1.4
IB
347V
1.4
1.5
120V
4.7
4.0
347V
4.7
4.0
Each sign is designed with a simple slide-out face/backplate for quick and easy
installation and all backplates are stamped with a universal mounting pattern.
Multiple conduit knockouts and a universal mounting canopy kit complete each
model.
Features
The Stanpro SLEXS & SLSRS series are designed with 20 gauge steel construction that wraps and interlocks completely, eliminating annoying light leaks. All
faceplates are designed with field removable knock out chevron/arrows. The
standard SLEXS is finished with a durable white baked powder coat finish. Other
colours are available, including custom colour matching.
EXIT
SORTIE
6V
0.5
0.5
12V
1.5
1.5
24V
3.5
3.5
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
18.5000”
Approvals:
CSA Certified to
C22.2 #141
269
Ordering Guide
Series
Approval
Faces #
Colour
SLEXS
SLSRS
C-C860 Certified
1-Single Face
2-Double Face
0-Universal Faces
WH-White (standard)
GY-Grey
BK-Black
SP-Custom colour
Options
TP, TPB, PM, IB, IB2, RW*, PG•,
120VDC*•, OP, BO, WO, NDC, G*, UB
Wireguard
See options descriptions on page 334
* For 120VAC only.
• Specify mounting.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 270
SLESS & SLSES
5.6250”
Commercial
Steel C860
Bilingual Series
5.6250”
5.6250”
4.3750”
0.3750”
7.7500”
28.0000”
2.2500”
Approvals:
CSA Certified to
C22.2 #141
EMERGENCY SERIES
270
Description
Circuitry
The Stanpro SLESS & SLSES series of commercial, slim line steel exit and
sortie bilingual signs are designed to meet the requirements of the C860 standard while maintaining a clean, contemporary appearance. The SLESS & SLSES
series is supplied standard with long-life, high brightness energy efficient LEDs.
Each sign is designed with a simple slide-out face/backplate for quick and easy
installation and all backplates are stamped with a universal mounting pattern.
Multiple conduit knockouts and a universal mounting canopy kit complete each
model.
The SLESS & SLSES series of C860 compliant bilingual signs utilize a
120/347VAC dual input voltage LED light source, available in AC only, AC/DC and
self-powered models. AC/DC models feature universal emergency backup DC
voltages: 6, 12 or 24VDC, each field selectable. Emergency power wattages are
as follows:
6V
12V
24V
EXIT SORTIE
1.0
3.3
6.7
Features
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
The Stanpro SLESS & SLSES bilingual sign series are designed with 20 gauge
steel construction that wraps and interlocks completely, eliminating annoying
light leaks. All faceplates are designed with field removable knock out
chevron/arrows. The standard SLSES is finished with a durable white baked powder coat finish. Other colours are available, including custom colour matching.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
Approval
Faces #
Colour
SLESS
or
SLSES
C-C860 Certified
1-Single Face
2-Double Faces
WH-White (standard)
GY-Grey
BK-Black
SP-Custom colour
Options
TP, TPB, PM, IB, IB2, PG•, BO,
WO, OP, NDC, UB
Wireguard
See options descriptions
on page 334
• Specify mounting.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
0.3750”
2:37 PM
4.3750”
Page 271
5.6250”
5.6250”
4.8750”
SPEXS & SPSRS
7.7500”
2.2500”
12.0000”
Commercial Steel
Combination
Head Types
Exit Series
18.5000”
4.7500
2.2500
2.2500
2.6250
5.7500
3.7500
3.7500
Type N
Type S
Type M
Type L
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
MR 16
Die Cast
Max 50 watts
PAR 36
Thermoplastic
Max 55 watts
Approvals:
CSA Certified to
C22.2 #141
Description
Circuitry
The Stanpro SPEXS & SPSRS series of C860 certified commercial, slim line steel
combination signs are designed to provide the greatest flexibility in meeting emergency lighting needs. The clean, contemporary appearance of the sign is combined with the reliability and performance of an emergency lighting unit.
Available with long-life, high brightness LEDs with energy efficient consumption
as low as just 4.7w AC. Each sign is designed with a simple slide-out face/backplate for quick and easy installation and all backplates are stamped with a universal mounting pattern. Multiple conduit knockouts and a universal mounting
canopy kit complete each model.
The Stanpro SPEXS & SPSRS units come complete with high quality, pulse action
chargers which are up to 70% more efficient than constant voltage chargers. The
solid state chargers are complete with low voltage disconnect, brownout, and
short circuit protections. All models are standard 120VAC or 347VAC dual input,
field selectable. A dual LED display indicates AC-ON and High charge, and all
chargers are complete with a quick test, push-button switch for easy maintenance and testing. Recharge time is 24 hours.
Features
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Warranty
The SPEXS & SPSRS are a series of completely self-contained, combination
emergency light and sign, made for use on 120 or 347 volt circuits. The SPEXS
& SPSRS series are designed with 20 gauge steel construction and all faceplates
have field removable knock out chevron/ arrows. A maintenance free, sealed
lead acid battery is included with the unit that will provide the specified wattage
for 30 minutes duration. Multiple conduit knockouts and a universal mounting
pattern are stamped into the unit. White baked finish is standard and custom
colours are optional.
EMERGENCY SERIES
4.5000
Ordering Guide
—
Series
Voltage
Wattage
Faces #
Heads
SPEXS
SPSRS
C680
Certified
06-6 volt
12-12 volt
see rating
chart
below
(eg. 036)
1-Single
Face
2-Double
Face
0-Universal
Faces
00-no heads
1N-1 PAR 18(standard)
2N-2 PAR 18(standard)
1S-1 MR 16
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16
2M-2 MR16
s
SPEXS6036
SPEXS6050
SPEXS1036
SPEXS1050
SPEXS1072
Lamp
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
6
36
18
9
NA
6
50
25
12
NA
12
36
18
9
NA
12
50
25
12
NA
12
72
36
18
9
Q
T
AT, LD, BD
TP, TPB, TD**,
PM, OP*, G*,
UB, PG•, SP
Wireguard
* For Exit signs only.
** Specify voltage.
• Specify mounting.
See options
descriptions on
page 334
6 Volts
12 Volts
PAR18 - Small Heads
8W, 10W, 12W
8W, 10W, 12W
5.4W, 7.2W, 9W
5.4W, 9W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
For SORTIE, replace “EX” by “SR” i.e. SPSRS6036.
8W, 10W, 12W,
20W
8W, 10W, 12W,
20W, 35W
PAR36 - Large Heads
Q
T
SB Q
SB T
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
5.4W, 7.2W, 9W, 18W, 25W
5.4W, 9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W
9W, 18W
Q = Quartz Halogen
Options
(eg. 09)
Q-Quartz Halogen
see lamp
T-Tungsten
selection chart
below
Lamp Selection
Model Ratings
Model
Lamp Watts
25W
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
271
07- emergency
02/2009/19
2:37 PM
Page 272
7.0000”
SLEXP
4.6250”
0.6250”
Commercial
Thermoplastic
Exit Series
7.25
8.5000”
Approvals:
CSA Certified to
C22.2 #141
12.2500”
1.8
2.5000”
EMERGENCY SERIES
Description
Circuitry
By combining value with a modern design, the Stanpro SLEXP series of high
impact thermoplastic commercial exit signs provide ideal exit signage solutions.
Supplied standard with long-life, high brightness LEDs, the SLEXP series are also
energy efficient with energy consumption as low as just 1.8W AC! Installation is
quick and easy since each sign is designed and supplied with quick-snap faceplates, backplate and universal canopy. All backplates are stamped with a universal mounting pattern for even greater installation ease and flexibility.
All SLEXP exit signs are supplied with 120/347VAC dual input voltage, available
in AC only, AC/DC and self-powered models. AC/DC models feature universal
emergency backup DC voltages: 6, 12 or 24VDC, each field selectable.
Emergency power wattages are as follows: 0.9 watts @ 6VDC, 1.0 watts @
12VDC and 1.8watts @ 24VDC. Self-powered models utilize an internal, solid
state charger and come complete with a high-performance Ni-Cad battery, supplying 90 minutes of emergency power. Up to 180 minute, extended duration
batteries are optional.
Features
The Stanpro SLEXP exit series are designed utilizing an all thermoplastic construction.The plastic is UV stabilized, lightweight, impact and scratch resistant.
All faceplates are designed with field removable snap out chevron/arrows. The
standard SLEXP is white in colour.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
Approval
Faces #
Colour
SLEXP
C-C860 Certified
0-Universal Faces
WH-White (standard)
Options
PG*, G, Wireguard
See options descriptions on page 334
* Specify mounting.
272
15.000”
7.000”
SPEXP60362SQ09T
4.625”
0.625”
4.500”
Commercial
Thermoplastic combination
Exit Series
Approvals:
CSA Certified to
C22.2 #141
12.125”
12.250”
2.000”
Ordering Guide
Series
SPEXP60362SQ09T
C680 Certified
Model Ratings
Model
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 120 m.
SPEXP60362SQ09T
6
30
15
7.5
NA
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 273
13-3/8’’
SLEXB
2’’
8-1/4’’
Die Cast Aluminum
self-powered
Thin Exit Series
Description
Circuitry
The Stanpro SLEXB series of commercial decorative die cast aluminum exit signs
are the perfect match of aesthetics and durability. The die cast construction produces an extremely rigid housing while the highly machined brushed housinglends a high-end look. The series has been designed to meet the C860 standard using energy efficient LEDs, with energy consumption as low as 1.8W AC!
Faceplates are hinged and snap into place for ease of installation.
The SLEXB series of die cast aluminum exit signs utilize a 120/277VAC dual input
voltage LED light source, available in self-powered models utilize an internal,
solid state charger and come complete with a high-performance Ni-Cad battery,
supplying 90 minutes of emergency power.
Features
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Warranty
The Stanpro SLEXB exit sign series are designed with all die cast aluminum
construction. The aluminum faceplates are designed with field removable knockout chevron/arrows. The SLEXB is supplied standard with a durable powdercoat
finish on the entire body. Other colours are available, including custom colour
matching and brushed aluminum.
EMERGENCY SERIES
Pending:
CSA to C22.2 #141
UL924 approved
Ordering Guide
—
—
Series
Approval
Face #
Frame Colour
Face Colour
Voltage
Options
SLEXB
C-C680
Certified
1-Single Face
2-Double Face
BK-Black
BA-Brushed Aluminum
WH-White (standard)
BK-Black
BA-Brushed Aluminum
WH-White (standard)
W
AT, TP, TPB, PM, IB,
IB2, 120VDC, HVC,
HVE, VS, OP,
G, SP, NDC, UB
See options descriptions on
page 334
Line voltage Identifier:
W - 120/277V
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
273
07- emergency
02/2009/19
2:37 PM
Page 274
SLESX & SLSEX
Extruded Aluminum
Bilingual Series
5.6250”
5.6250”
5.6250”
4.3750”
0.3750”
7.5000”
28.5000”
2.0000”
Approvals:
CSA Certified to
C22.2 #141
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLESX & SLSEX series of commercial extruded aluminum bilingual exit
and sortie signs have been designed to meet the requirements of the C860 standard with superior construction and clean lines. Supplied standard with long-life,
high brightness energy efficient LEDs, with energy consumption as low as
The SLESX & SLSEX series of extruded aluminum bilingual signs utilize a
120/347VAC dual input voltage LED light source, available in AC only, AC/DC and
self-powered models. AC/DC models feature universal emergency backup DC
voltages: 6, 12 or 24VDC, each field selectable. Emergency power wattages are
as follows:
6V
12V
24V
EXIT SORTIE
1.0
3.3
6.7
VDC
EXIT SORTIE
120V
2.5
IB
347V
2.9
120V
7.9
347V
7.9
Faceplates and backplates can slide along a formed channel for quick installation and all backplates are stamped with a universal mounting pattern. Multiple
conduit knockouts and a variety of canopy mounting options complete each
model.
Features
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
The Stanpro SLESX & SLSEX exit sign series are designed with a one piece, lightweight, extruded aluminum frame. The extruded aluminum faceplates are
designed with field removable snap out chevron/arrows. The SLESX & SLSEX are
supplied standard with a durable white baked powder coat finish. Other colours
are available, including custom colour matching.
274
Ordering Guide
Series
Approval
Faces #
Colour
SLESX
or
SLSEX
C-C860 Certified
1-Single Face
2-Double Faces
WH-White (standard)
BA-Brushed aluminum
BK-Black
SP-Custom colour
Options
TP, TPB, PM, IB
IB2, PG*, OP, BO,
WO, AZ, NDC, UB
Wireguard
See options
descriptions on
page 334
* Specify mounting.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 275
5.6250”
4.3750”
0.3750”
7.5000”
SLEXX & SLSRX
13.0000”
Extruded
Aluminum
Series
2.0000”
5.6250”
4.3750”
0.3750”
7.5000”
Approvals:
CSA Certified to
C22.2 #141
2.0000”
Description
Circuitry
The Stanpro SLEXX & SLSRX series of commercial extruded aluminum signs
have been designed to meet the requirements of the C860 standard with superior construction and clean lines. Supplied standard with long-life, high brightness energy efficient LEDs, with energy consumption as low as
The SLEXX & SLSRX series of extruded aluminum signs utilize a 120/347VAC dual
input voltage LED light source, available in AC only, AC/DC or self-powered models. AC/DC models feature universal emergency backup DC voltages: 6, 12 or
24VDC, each field selectable. Emergency power wattages for EXIT are as follows:
VDC
EXIT
SORTIE
120V
1.2
1.4
IB
347V
1.4
1.5
120V
4.7
4.0
347V
4.7
4.0
Faceplates and backplates can slide along a formed channel for quick installation and all backplates are stamped with a universal key hole mounting pattern.
Multiple conduit knockouts and a universal mounting canopy kit complete each
model.
Features
The Stanpro SLEXX & SLSRX sign series are designed with a one piece, lightweight, extruded aluminum frame. The extruded aluminum faceplates are
designed with field removable knock out chevron/arrows. The SLEXX & SLSRX
are supplied standard with a durable white baked powder coat finish. Other
colours are available, including custom colour matching.
EXIT
SORTIE
6V
0.5
1.3
12V
1.5
1.7
24V
3.5
3.2
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
18.5000”
275
Ordering Guide
Series
Approval
Face #
Frame Colour
SLEXX
SLSRX
C-C860
Certified
1-Single Face
2-Double Face
WH-White (standard)
BA-Brushed Aluminum
BK-Black
SP-Custom colour
Options
TP, TPB, PM, IB, IB2, 120VDC*•, RW**, PG•, OP,
G*, BO, WO, AZ, NDC, UB
Wireguard
See options descriptions on page 334
* For EXIT signs only.
** For single face EXIT signs only.
• Specify mounting.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 276
Head Types
2.2500
2.6250
4.5000
3.7500
SPSLESX &
SPSLSEX
Type N
Type S
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
2.2500
Extruded Aluminum
combination
Bilingual Series
3.7500
Type M
MR 16
Die Cast
Max 50 watts
4.7500
5.7500
Type L
PAR 36
Thermoplastic
Max 55 watts
Approvals:
CSA Certified to C22.2 #141
EMERGENCY SERIES
Description
Circuitry
The Stanpro SPSLESX/SPSLSEX series of commercial, extruded aluminum combination exit signs are designed to provide the greatest flexibility in meeting emergency
lighting needs. The clean, contemporary appearance of the exit is combined with
there liability and performance of an emergency lighting unit. Available with long-life,
high brightness LEDs with energy efficient consumption as low as just 4.7w AC!
Faceplates and backplates can slide along a formed channel for quick installation
and all backplates are stamped with a universal mounting pattern. Multiple conduit
knockouts and a universal mounting canopy kit complete each model.
The Stanpro SPSLESX/SPSLSEX units come complete with high quality, pulse action
chargers which are up to 70% more efficient than constant voltage chargers. The
solid state chargers are complete with low voltage disconnect, brownout, and shortcircuit protection. All models are standard 120VAC or 347VAC dual input, field selectable. A dual LED display indicates AC-ON and High charge, and all chargers are complete with a quick test, push-button switch for easy maintenance and testing. A longlife, maintenance free sealed lead acid battery provides the emergency backup
power during AC failure. Recharge time is 24 hours.
Features
Warranty
The SPSLESX/SPSLSEX is a series of completely self-contained, combination emergency
light and exit sign, made for use on 120 or 347 volt circuits. The SPSLESX/SPSLSEX
series are designed with light weight aluminum and all faceplates have field removable
knockout chevron/arrows. A maintenance free, sealed lead acid battery is included with
the unit that will provide up to 72 watts of emergency power for 30 minutes duration.
Multiple conduit knockouts and a universal key hole mounting pattern are stamped into
the unit. White baked finish is standard and custom colours are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
276
Series
Voltage
SPSLESX
or
SPSLSEX
C680
Certified
06-6 volt
10-12 volt
Wattage
SPSLESX6036
SPSLESX6050
SPSLESX1036
SPSLESX1050
SPSLESX1072
SPSLSEX6036
SPSLSEX6050
SPSLSEX1036
SPSLSEX1050
SPSLSEX1072
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
6
36
18
9
NA
6
50
25
12
NA
12
36
18
9
NA
12
50
25
12
NA
12
72
36
18
9
6
6
12
12
12
Heads
Lamp Watts
Lamp
00-no heads
(eg. 09)
Q-Quartz Halogen
1N-1 PAR 18(standard)
see lamp
T-Tungsten
2N-2 PAR 18(standard) selection chart
1S-1 MR 16
below
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
* Specify AC voltage.
1M-1 MR16
2M-2 MR16 • Specify mounting.
Options
AT, LD, BD, TP,
TPB, TD*, PM,
OP, IRT*, G,
PG•,
BK, SP
Wireguard
See options
descriptions on
page 334
Lamp Selection
Model Ratings
Model
Faces #
see rating 1-Single
chart
Face
below
2-Double
(eg. 036)
Face
36
50
36
50
72
18
25
18
25
36
9
12
9
12
18
NA
NA
NA
NA
9
6 Volts
12 Volts
PAR18 - Small Heads
Q
T
8W, 10W, 12W
8W, 10W, 12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W
8W, 10W, 12W,
20W, 35W
PAR36 - Large Heads
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
Q
5.4W, 9W, 18W, 25W
T 5.4W, 7.2W, 9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W
SB Q
9W, 18W
25W
SB T
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
0.3750”
4.3750”
2:37 PM
Page 277
5.6250”
SPSRX & SPEXX
4.8750”
Extruded Aluminum
Combination
Exit & Sortie Series
7.5000”
13.0000”
2.0000”
Head Types
4.7500
2.2500
2.2500
2.6250
5.7500
3.7500
3.7500
Type N
Type S
Type M
Type L
PAR 18
Thermoplastic
Max 18 watts
MR 16
Die Cast
Max 50 watt
MR 16
Die Cast
Max 50 watts
PAR 36
Thermoplastic
Max 55 watts
Approvals:
CSA Certified to
C22.2 #141
Description
Circuitry
The Stanpro SPSRX/SPEXX series of commercial, extruded aluminum combination
exit signs are designed to provide the greatest flexibility in meeting emergency lighting needs. The clean, contemporary appearance of the exit is combined with there
liability and performance of an emergency lighting unit. Available with long-life, high
brightness LEDs with energy efficient consumption as low as just 4.7W AC!
Faceplates and backplates can slide along a formed channel for quick installation
and all backplates are stamped with a universal mounting pattern. Multiple conduit
knockouts and a universal mounting canopy kit complete each model.
The Stanpro SPSRX/SPEXX units come complete with high quality, pulse action
chargers which are up to 70% more efficient than constant voltage chargers. The
solid state chargers are complete with low voltage disconnect, brownout, and shortcircuit protection. All models are standard 120VAC or 347VAC dual input, field selectable. A dual LED display indicates AC-ON and High charge, and all chargers are
complete with a quick test, push-button switch for easy maintenance and testing. A
long-life, maintenance free sealed lead acid battery provides the emergency backup
power during AC failure. Recharge time is 24 hours.
Features
Warranty
The SPSRX/SPEXX is a series of completely self-contained, combination emergency
light and exit sign, made for use on 120 or 347 volt circuits. The SPSRX/SPEXX series
are designed with light weight aluminum and all faceplates have field removable
knockout chevron/arrows. A maintenance free, sealed lead acid battery is included
with the unit that will provide up to 72 watts of emergency power for 30 minutes duration. Multiple conduit knockouts and a universal key hole mounting pattern are
stamped into the unit. White baked finish is standard and custom colours are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
4.5000
Ordering Guide
—
Series
Voltage
Wattage
Faces #
Heads
SPEXX
SPSRX
C680
Certified
06-6 volt
10-12 volt
see rating
chart
below
(eg. 036)
1-Single
Face
2-Double
Face
00-no heads
1N-1 PAR 18(standard)
2N-2 PAR 18(standard)
1S-1 MR 16
2S-2 MR 16
1L-1 PAR 36
2L-2 PAR 36
1M-1 MR16
2M-2 MR16
SPEXX6036
SPEXX6050
SPEXX1036
SPEXX1050
SPEXX1072
SPSRX6036
SPSRX6050
SPSRX1036
SPSRX1050
SPSRX1072
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
6
36
18
9
NA
6
50
25
12
NA
12
36
18
9
NA
12
50
25
12
NA
12
72
36
18
9
6
6
12
12
12
Lamp
(eg. 09)
Q-Quartz Halogen
see lamp
T-Tungsten
selection chart
below
* Specify AC voltage.
• Specify mounting.
Lamp Selection
Model Ratings
Model
Lamp Watts
36
50
36
50
72
18
25
18
25
36
9
12
9
12
18
NA
NA
NA
NA
9
6 Volts
12 Volts
PAR18 - Small Heads
Q
T
8W, 10W, 12W
8W, 10W, 12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W
8W, 10W, 12W,
20W, 35W
PAR36 - Large Heads
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
Q
5.4W, 9W, 18W, 25W
T 5.4W, 7.2W, 9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
SB Q
9W, 18W
25W
SB T
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
Options
AT, LD, BD, TP,
TPB, TD*, PM,
OP, IRT*, G,
PG•,
BK, SP
Wireguard
See options
descriptions on
page 334
277
07- emergency
02/2009/19
2:37 PM
Page 278
1.875’’
19.5’’
1.875’’
SLEXO & SLSRO
7’’
Universal wall or
ceiling mount
19’’
12.5’’
7’’
Approvals:
CSA Certified to
C22.2 #141 and UL924 (SLEXO only)
12’’
EMERGENCY SERIES
Description
Features
The SLEXO/SLSRO series of architectural edgelit exit and sortie signs provide
interiors with a clean, distinguished appearance. Ideal for use in facilities
required to meet current building code requirements such as airports or government buildings and institutions. Mounting is available as a universal wall, ceiling
or end mount. The SLEXO/SLSRO series is available in AC only, AC/DC and internally Self-Powered versions.
• High clarity, clear acrylic faceplates with a choice of backings: clear (single
face), white or mirrored
• Screened on exit lettering/stencil
• Field installable peel on/off universal directional chevrons/arrows
• Housing is made of high end extruded aluminum.
• All electronics and faceplate are factory installed for rapid and simple installation
• White powder coat finish or brushed aluminum are standard, other
finishes and colours optional
Electrical
• LED Ultra-bright light source
• 120/347VAC Input, field selectable
• 6/12/24VDC Input, field selectable
• 90 Minutes emergency duration is optional
• 180 Minutes emergency duration is optional
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
VDC
IB
8 in. VDC
6V
12V
24V
120V
347V
120V
347V
120V
277V
EXIT
0.5
1.4
3.2
1.8
1.9
2.2
2.4
1.9
1.9
SORTIE
0.6
2.0
4.5
1.9
2.1
2.6
2.9
8 in. IB
120V
6 in. VDC
277V
120V
277V
6 in. IB
120V
277V
HEAVY DUTY END MOUNT
278
UNIVERSAL WALL OR CEILING
simply slide the canopy to position
Ordering Guide
Series
Approval
Face #
Mounting
Housing Colour Faceplate color
Ac voltage
Dc voltage
SLEXO
(Exit)
SLSRO
(Sortie)
C-C860
1- single
face
2- double
face
SC-surface
ceiling
SW-surface
wall
SE-surface end
PM - pendant
mount
WH-white
BA-brushed
Aluminum
BK-black
SP-custom
colour
Z - 120/347
N - no ac
UDC - (6,12,24V)
NDC - AC only
IB - Internal Batteries
provide 90 min. of
emergency duration
IB2 - Internal Batteries
provide 180 min. of
emergency duration
CR- clear on red
(single face only)
WR - white on red
MR - mirror on red
CG - clear on green
WG - white on green
MG - mirror on green
Options
OP
See options
descriptions on
page 334
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 279
1.875’’
34.875’’
1.875’
SLESO &
SLSEO
7’’
Universal wall or
ceiling mount
34.375’’
End Mount
Ceiling Mount
Wall Mount
Description
Features
The SLESO/SLSEO series of architectural edgelit exit and sortie signs provide
interiors with a clean, distinguished appearance. Ideal for use in facilities
required to meet current building code requirements such as airports or government buildings and institutions. Mounting is available as a universal wall, ceiling
or end mount. The SLESO/SLSEO series is available in AC only, AC/DC and internally Self-Powered versions.
• High clarity, clear acrylic faceplates with a choice of backings: clear (single
face), white or mirrored
• Screened on exit lettering/stencil
• Field installable peel on/off universal directional chevrons/arrows
• Housing is made of high end extruded aluminum.
• All electronics and faceplate are factory installed for rapid and simple installation
• White powder coat finish or brushed aluminum are standard, other
finishes and colours optional
Electrical
• LED Ultra-bright light source
• 120/347VAC Input, field selectable
• 6/12/24VDC Input, field selectable
• 90 Minutes emergency duration is optional
• 80 Minutes emergency duration is optional
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
VDC
EXIT SORTIE
IB
6V
12V
24V
120V
347V
120V
347V
1.1
3.4
7.7
2.3
2.5
4.8
5.2
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
HEAVY DUTY END MOUNT
279
UNIVERSAL WALL OR CEILING
simply slide the canopy to position
Ordering Guide
Series
# Face
Mounting
Colour
Letter/Face Colour
SLESO
Exit-Sortie
SLSEO
Sortie-Exit
C860
certified
1 - single
face
2 - double
face
SC - surface
ceiling
SW - surface
wall
SE - surface end
PM - pendant
mount
WH - white
BK - black
BA - brushed
aluminum
SP - custom
colour
(please specify)
CR - red on clear
Z - 120/347
WR - red on white
N - No AC
MR - red on mirror
CG - green on clear
WG - green on white
MG - green on mirror
AC voltage
DC voltage
Options
UDC - 6, 12, 24
universal DC
IB - self powered
for 90 min.
IB2 - self powered
for 180 min.
PDK12 - 12" pendant kit
(matching colour)
NDC - AC only
OP
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
See options
descriptions on
page 334
07- emergency
02/2009/19
2:37 PM
Page 280
15.0000”
5.1250”
14.2500”
4.0000”
4.0000”
0.2500”
SLEXE & SLSRE
Edge Lit
Exit Series
7.0000”
12.0000”
5.0000”
21.0000”
5.1250”
20.1250”
4.0000”
4.0000”
0.2500”
7.0000”
Approvals:
CSA Certified to
C22.2 #141 (SLEXE only)
19.0000”
5.0000”
EMERGENCY SERIES
Description
Features
The SLEXE & SLSRE series of commercial edge lit signs lend style and prestige
to any application. These series have been designed to meet the C860 standard
while providing an elegant, high-end look. Standard with long-life, high brightness energy efficient LEDs, with energy consumption as low as
The Stanpro SLEXE & SLSRE sign series utilize a high clarity, clear acrylic faceplate. Stencils are screened onto the faceplate with 6” letter height. A universal,
field selectable, chevron/arrow kit is included with every sign. These series are
supplied standard with a durable white baked powder coat finish integral trim.
Other colours and finishes are available, including custom colour matching.
VDC
EXIT
SORTIE
120V
4.7
-
IB
347V
4.7
-
120V
3.8
-
347V
4.0
-
SLEXE & SLSRE series signs can be specified recessed or surface mount for
either walls or ceilings. Recessed ceiling model backboxes come complete with
hanger bars for T-bar type ceilings. Surface mount backboxes include conduit
knockouts and a universal mounting pattern.
Circuitry
The SLEXE & SLSRE series of edge lit signs utilize a 120/347VAC dual input voltage LED light source, available in AC only, AC/DC and self-powered models.
AC/DC models feature emergency backup DC voltages: 6, 12 or 24VDC, specify
upon ordering. Emergency power wattages are as follows: 2.0 watts @ 6VDC,
3.5 watts @ 12VDC and 8.5 watts @ 24VDC. Self-powered models utilize an
internal, solid state charger and come complete with a high-performance Ni-Cad
battery, supplying 90 minutes of emergency power. Up to 180 minute, extended
duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
280
Ordering Guide
Series
Approval
Face #
Mounting
Faceplate color
Colour
SLEXE
SLSRE
C-C680
Certified
1-Single Face
2-Double Face
RC-Recessed ceiling
SC-Surface ceiling
SW-Surface wall
SE-Surface end
SWU - surface wallup
PM - pendant mount
CR - red on clear
WR - white on red
MR - mirror on red
CG - clear on green
WG - white on green
MG - mirror on green
WH-White
BA-Brushed Aluminum
BK-Black
SP-Custom colour
Options
PM, OP, CR,
WR, MR, 6V,
12V, 24V, G*, IB,
IB2, NDC
See options
descriptions
on page 334
* For EXIT signs only.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:37 PM
Page 281
36.0000”
5.1250”
34.3750”
4.0000”
SLESE & SLSEE
4.0000”
0.2500”
7.0000”
31.0000”
Bilingual Edge Lit
Series
5.0000”
Description
Circuitry
The SLESE and SLSEE series of commercial edge lit bilingual exit and sortie
signs lend style and prestige to any application. The SLESE and SLSEE series
have been designed to meet the C860 standard while providing an elegant, highend look. They come standard with long-life, high brightness energy efficient
LEDs, with energy consumption as low as 7.8w AC. SLESE and SLSEE series
signs are available in recessed ceiling models only. The recessed ceiling backboxes come complete with hanger bars for T-bar type ceilings.
The SLESE and SLSEE series of edge lit C860 approved bilingual exit and
sortie signs utilize a 120/347VAC dual input voltage LED light source, available
in AC only, AC/DC and self-powered models. AC/DC models feature emergency
backup DC voltages: 6, 12 or 24VDC, specify upon ordering. Emergency power
wattages areas follows: 4.0 watts @ 6VDC, 7.0 watts @ 12VDC and 17.0 watts
@ 24VDC. Self-powered models utilize an internal, solid state charger and come
complete with a high-performance Ni-Cad battery, supplying 90 minutes of
emergency power. Up to180 minute, extended duration batteries are optional.
Features
The Stanpro SLESE and SLSEE bilingual exit and sortie sign series utilize a high
clarity, clear acrylic faceplate. Stencils are screened onto the faceplate with 6”
letter height. A universal, field selectable, chevron/arrow kit is included with
every sign. The SLESE and SLSEE series are supplied standard with a durable
white baked powder coat finish integral trim. Other trim colours and finishes are
available, including custom colour matching.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
Ordering Guide
Series
SLESE
or
SLSEE
Approval
C-C860
Certified
Faces #
1-Single Face
2-Double Faces
Mounting
RC-Recessed
Ceiling
Faceplate color
CR - red on clear
WR - white on red
MR - mirror on red
CG - clear on green
WG - white on green
MG - mirror on green
Colour
Options
WH-White (standard)
BA-Brushed aluminum
BK-Black
SP-Custom colour
OP, CR, WR,
MR, 6V, 12V,
24V, IB, IB2,
NDC
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
See options
descriptions
on page 334
281
07- emergency
02/2009/19
2:38 PM
Page 282
SLEXV & SLSRV
Vandal Resistant
Exit Series
Approvals:
CSA Certified to
C22.2 #141 (SLEXV only)
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLEXV & SLSRV series of vandal resistant signs were designed to
withstand the kind of abuse that a regular sign could not. In applications such as
schools, institutional buildings and apartment complexes. These series will continue to frustrate the efforts of even the most violent vandals. Supplied standard
with long-life, high brightness LEDs the SLEXV & SLSRV are energy efficient with
energy consumption as low as just 1W AC (2.5W AC for sortie)!Each sign is
designed with multiple vandal resistant features to help protect them against
intentional damage.
The SLEXV & SLSRV series of vandal resistant signs utilize a 120/347VAC dual
input voltage LED light source, available in AC only, AC/DC and selfpowered models. AC/DC models feature universal emergency backup DC voltages: 6, 12 or 24VDC, each field selectable. Emergency power wattages for EXIT
are as follows:
Features
The Stanpro SLEXV & SLSRV series are designed around a 16 gauge steel frame.
The frame forms a solid housing for all electronics and sign face stencils. The
face(s) are then covered with a high impact, polycarbonate shield. The faceplate
and shield assembly is held in place with a 16 gauge steel collar that wraps
completely around the sign frame. The entire assembly is then secured together
using stainless steel tamperproof screws. A full length, heavy-duty steel canopy
is factory installed for ceiling or end mount versions. All faceplates are designed
with field removable peel out chevron/arrows. Standard colour is white, other
colours available including custom colour matching.
VDC
IB
6V
12V
24V
120V
347V
120V
347V
EXIT
1.1
3.0
7.0
2.3
2.7
4.7
4.7
SORTIE
2.5
3.5
6.3
2.7
3.0
4.0
4.0
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
282
Ordering Guide
Series
Approval
Face #
Mounting
Colour
AC voltage
DC voltage
SLEXV
SLSRV
C-C680
Certified
1-Single Face
2-Double Face
CM - ceiling mount
WM - wall mount
EM - end mount
WH-White (std)
GY-Grey
BK-Black
SP-Custom
colour
A - 120
Z - 120/347
H - 347
UDC - 6, 12, 24
universal DC
IB - self powered
for 90 min.
IB2 - self powered
for 180 min.
Options
TPB, IB, IB2,
120VDC*, OP, G*,
BO, WO, WM,
HVC, UB
Wireguard
See options
descriptions
on page 334
* For EXIT signs only.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 283
SLESV & SLSEV
4.5000”
Vandal Resistant
Bilingual Series
0.7500”
8.5000”
Approvals:
CSA Certified to
C22.2 #141
3.0000”
Description
Circuitry
The Stanpro SLESV series of vandal resistant bilingual signs were designed to
withstand the kind of abuse that a regular exit sign could not. In applications
such as schools, institutional buildings and apartment complexes. The SLESV
series will continue to frustrate the efforts of even the most violent vandals.
Supplied standard with long-life, high brightness LEDs the SLESV is energy efficient with energy consumption as low as just 5W AC! Each sign is designed with
multiple vandal resistant features to help protect them against intentional damage.
The SLESV series of vandal resistant bilingual signs utilize a 120/347VAC dual
input voltage LED light source, available in AC only, AC/DC and self-powered
models. AC/DC models feature universal emergency backup DC voltages: 6, 12
or 24VDC, each field selectable. Emergency power wattages are as follows:
VDC
EXIT SORTIE
IB
6V
12V
24V
120V
347V
120V
347V
3.5
6.5
13.3
5.0
5.8
7.9
7.9
Features
The Stanpro SLESV bilingual series are designed around a 16 gauge steel frame.
The frame forms a solid housing for all electronics and exit face stencils. The
face(s) are then covered with a high impact, polycarbonate shield. The faceplate
and shield assembly is held in place with a 16 gauge steel collar that wraps
completely around the exit frame. The entire assembly is secured together using
stainless steel tamperproof screws. A full length, heavy-duty steel canopy is factory installed for ceiling or end mount versions. All faceplates are designed with
field removable peel out chevron/arrows. Standard colour is white, other colours
available including custom colour matching.
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
28.0000”
283
Ordering Guide
Series
Approval
Face #
Mounting
Colour
AC voltage
DC voltage
SLESV
C-C680
Certified
1-Single Face
2-Double Face
CM - ceiling mount
WM - wall mount
WH-White (std)
GY-Grey
BK-Black
SP-Custom
colour
A - 120
Z - 120/347
H - 347
UDC - 6, 12, 24
universal DC
IB - self powered
for 90 min.
IB2 - self powered
for 180 min.
NDC - AC only
SLSEV
* For EXIT signs only.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
Options
PM, OP, BO, WO,
WM, HVC, HVE,
UB
Wireguard
See options
descriptions on
page 334
07- emergency
02/2009/19
2:38 PM
Page 284
SLEXA
12.1250”
Triangular
Exit Series
7.8750”
Approvals:
CSA Certified to
C22.2 #141
14.0000”
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLEXA provides an advanced solution to unique exit design applications. Double face wall or triple face pendant mounted (pendant not included),
the SLEXA design insures that the exit stencil is visible from the widest possible
field of vision. The modern SLEXA design includes provisions for the mounting of
auxiliary equipment, such as security TV cameras (contact Stanpro for details).
Standard with long-life, high brightness LEDs the SLEXA is energy efficient with
energy consumption at a low 2.3W AC per sign!
The SLEXA series of triangular exit signs utilize a 120/377VAC dual input voltage
LED light source. The EXA is available in AC only, AC/DC and self-powered models. AC/DC models feature emergency backup DC voltages in 6VDC, 12VDC or
24VDC, specify when ordering. Emergency power wattages are as follows:
Features
The Stanpro SLEXA exit is designed with extruded aluminum, utilizing an unique
three sided, triangular frame. The LED light source employs an advanced parallel lamp design that ensures the failure of one LED will not extinguish the
remaining ones. All faceplates are designed with field removable knock out
chevron/arrows. Standard colour is white, other colours available including custom colour matching.
VDC
6V
12V
24V
120V
347V
SLEXAC2
1.0
3.0
7.0
2.3
2.7
SLEXAC3
1.5
4.5
10.5
3.5
4.1
Self-powered models utilize an internal, solid state charger and transfer (no
relay). Self-powered models also include a charge indicator light, push button
test switch and a high-performance Ni-Cad battery, supplying 90 minutes of
emergency power. A 180 minute, extended duration battery is optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
284
Ordering Guide
Series
Approval
Face #
AC voltage
DC voltage
Colour
SLEXA
C-C680
Certified
2-Double Face
3-Triple Face
A - 120
Z - 120/347
H - 347
UDC - 6, 12, 24
universal DC
IB - self powered
for 90 min.
IB2 - self powered
for 180 min.
NDC - AC only
WH-White (standard)
BA-Brushed Aluminum
BK-Black
SP-Custom colour
Options
PM, PG, G, OP
Wireguard
See options descriptions
on page 334
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 285
24.840
28.862
2.750
14.258
18.280
CUBEX
Length to suit.
Supplied by
contractor.
Pendant mount
6.346
Length to suit.
Supplied by
contractor.
7.757
Description
Circuitry
The Stanpro Cubex series is designed to provide dependable and efficient emergency lighting in a modern design. The Cubex utilizes a sturdy, all steel housing
that facilitates quick installation. This series is only available in 12V version and
provides 360W of emergency power.
Exit sign models available in AC only or AC/DC, 120 or 347V. AC/DC models feature emergency backup DC voltage of 6, 12 or 24V. The Cubex units come complete with high quality, pulse action chargers witch are up to 70% more efficient
than constant voltage chargers. The solid state chargers are complete with low
voltage disconnect, brownout and short circuit protections. All models are standard 120VAC or 347VAC field selectable. A long-life, maintenance free sealed
lead acid battery provides the emergency back-up power during AC failure.
Mounting
The Cubex is pendant mounted from the ceiling with conduit and threaded hook.
The hook is supplied with the battery unit, conduit supplied by others.
Mandatory options
Features
Infrared test receiver
The Cubex battery unit is a completely self-contained emergency light made for
use on 120 or 347 volt circuits. Maintenance free, sealed lead acid battery is
included with the unit which will provide the specified wattage for 30 minutes
duration. The signs portion is made with 20 gauge steel construction that wraps
and interlocks completely, eliminating annoying light leaks. All faceplates are
designed with field removable knock out chevron/arrows. The standard Cubex is
finished with a durable white baked powder coat finish. Other colours are available, including custom colour matching.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #141
16.850
12.828
Ordering Guide
285
Series
Voltage
Wattage
Face #
Heads
Lamp watts
AC voltage
Mandatory options
Options
CUBEX
(EXIT)
CUBSR
(SORTIE)
12 - 12V
360 - 360W
4 - 4 faces
8L - 8X PAR36
8N - 8X PAR18
8S - 8X MR16
die cast
8M - 8X MR16
die cast
(see lamp
selection
chart below)
A - 120V
H - 347V
IT - infrared test
receiver
TD10, TD15,
AT, NDC, 6V,
12V, 24V,
RFS
Lamp Selection
12 Volts
PAR18 - Small Heads
8W, 10W, 12W
Q
5.4W, 7.2W, 9W, 18W
T
MR16 - Small Heads c/w MR16 Lamp
8W, 10W, 12W, 20W, 35W
Q
PAR36 - Large Heads
8W, 10W, 12W, 20W, 35W
Q
5.4W, 7.2W, 9W, 18W, 25W
T
8W, 12W, 30W, 35W
SB Q
8W, 9W, 12W, 18W, 25W
SB T
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
See options
descriptions on
page 334
07- emergency
EMERGENCY SERIES
286
02/2009/19
2:38 PM
Page 286
07- emergency
02/2009/19
2:38 PM
Page 287
5.6250”
4.2500”
0.3750”
8.2500”
SLEXT & SLSRT
1.2500”
12.2500”
5.6250”
Non-Electrical
Self-Luminous
Series
Description
Light Source
The Stanpro SLEXT series of self-luminous exit signs provide reliable exit signage for applications where typical signs cannot be employed. The SLEXT series
are completely non-electrical so they can be installed in any location, including
glass entranceways/vestibules, greenhouses and outdoor applications. This also
insures that the SLEXT signs are non-sparking, making them ideal for explosionproof locations. Available with a 10, 15 or 20 year expected life, sealed tritiumphosphor light source are available in wall or ceiling mount (canopy included).
The SLEXT series self-luminous signs utilize a sealed tritium light source. The tritium is sealed within several silicate tubes fitted into the ABS thermoplastic
housing. The tubes are lined with phosphor which glows green in colour, in conjunction with the sealed tritium. The light output is unaffected by extremes of
temperature or moisture. As specified, the sign will continuously illuminate at
performance specifications for the rated duration of 10, 15 or 20 years. The light
source requires no maintenance or service throughout the lifespan of the sign
and all signs comply with the applicable codes and standards.
Features
Warranty
The SLEXT series from Stanpro are supplied standard with a white, low
profile thermoplastic frame, an optional extruded aluminum frame is available,
contact factory for details. The frame secures the thermoplastic face and stencil
and allows for simple wall mounting. An optional canopy easily attaches to the
exit to facilitate ceiling mounting. The letter colour is always phosphor green and
the stencil can be supplied in red (standard), green or black. Standard exit stencils incorporate peel out chevron/arrows. Custom wording or graphic stencils
can be ordered. Please note that SLEXT signs are not governed by the requirements of the C860 standard due to the non-electrical design of the light source.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
12.2500”
Ordering Guide
287
Series
Life Expectancy
Face #
SLEXT or
10Y-10 years
1-Single Face
SLSRT
15Y-15 years
2-Double Face
(sortie)
20Y-20 years*
or
SLEST (Exit/Sortie) letters 2-3/4’’
or
SLSET (Sortie/Exit) letters 2-3/4’’
Face Colour
Frame Colour
R-Red (standard)
G-Green
B-Black
WH-White (standard)
BK-Black
GY-Grey
* 20 years on EXIT only.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
Options
PG
Wireguard
See options
descriptions on
page 334
07- emergency
02/2009/19
2:38 PM
Page 288
Optional Signs
Overview
LED Exit Signage
The following special wording signs are available to replace any standard Exit
sign legend. Please add the suffix OP + the chosen sign number to the catalogue
number. Contact your Stanpro representative for any other special wording
requirement.
The special signage legends are available as either Red (RL) or Green (GL) stencil legends on opaque background colour either White (W) or Black (B). The letter colour and background colour should be added as a suffix to the legend number as follows:
ADA Signage
Signs are available in many colours, please specify when ordering.
No. OP005 - Area of Rescue assistance can be supplied with Red legend and
Blue wheelchair symbol, specify No. OP5RBW.
EMERGENCY SERIES
288
Red letters
Green letters
White Background
OP_RLW
OP_GLW
Black Background
OP_RLB
OP_GLB
Add legend number, colour and background colour to catalogue
number when ordering.
OP001
OP002
OP003
OP004
OP005
OP006
OP007
OP008
OP009
OP010
OP011
OP012
OP013
OP014
OP015
OP016
DARK
ROOM
OP017
OP018
OP019
OP020
OP021
OP022
OP023
OP024
OP025
OP026
OP027
OP028
OP029
OP030
OP031
OP032
OP033
OP034
OP035
OP036
OP037
OP038
OP039
OP040
OP041
OP042
OP043
OP044
OP045
OP046
OP047
OP048
OP050
OP051
OP052
OP053
OP054
OP055
OP056
OP058
OP059
OP060
OP061
OP062
OP063
OP064
OP049
OP057
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 289
OP065
OP066
OP067
OP068
OP069
OP070
OP071
OP072
OP073
OP074
OP075
OP076
OP077
OP078
OP079
OP080
OP081
OP082
OP083
OP084
OP085
OP086
OP087
OP088
OP089
OP090
OP091
OP092
OP093
OP094
OP095
OP096
OP097
OP098
OP099
OP100
OP101
OP102
OP103
OP104
OP106
OP107
OP108
OP109
OP110
OP111
OP112
OP113
OP114
OP115
OP116
OP117
OP118
OP119
OP120
OP121
OP122
OP123
OP124
OP125
OP126
OP127
OP128
OP105
EMERGENCY SERIES
Optional Signs
289
OP129
OP130
OP131
OP132
OP133
OP134
OP135
OP136
OP137
OP138
OP139
OP140
OP141
OP142
OP143
OP144
OP145
OP146
OP147
OP148
OP149
OP150
OP151
OP152
OP153
OP154
OP155
OP156
OP157
OP158
OP159
OP160
OP161
OP162
OP163
OP164
OP165
OP166
OP167
OP168
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
EMERGENCY SERIES
290
02/2009/19
2:38 PM
Page 290
07- emergency
02/2009/19
2:38 PM
Page 291
Hazardous
Environments
Classifications
The following Stanpro hazardous location emergency lighting and exit sign application procedure, is strictly for reference and is intended to be used for information purposes only. Please contact your local Stanpro representatives for the precise categorization of your specific application and the appropriate codes and standards to which it applies.
Class 1, Division 1 - locations where the hazardous gas atmosphere is expected to be present as a part of normal operations, maintenance or repair. The hazardous condition is always considered present.
Class 1, Division 2 - locations where the hazardous gas atmosphere is not expected to be present and is normally confined as a part of normal operations,
maintenance, break-down or repair. The hazardous condition is usually not present, hazard occurs due to abnormal or accidental
circumstances.
class 2, Division 2 - locations where the hazardous dust is not expected to be present and is normally confined as a part of normal operations, maintenance,
break-down or repair. The hazardous condition is usually not present, hazard occurs due to abnormal or accidental circumstances.
Examples of class 1 hazardous materials include:
Group A
Group B
Group C
Group D
Acetylene
Hydrogen
Butadien
Ethylene oxide
Propylene oxide
Manufactured gases
Acetaldehyde
Cycloproprane
Diethyl ether
Ethylene
Hydro sulfide
Naphtha
Unsymmetrical Dimethyl
Hydrazine (UDMH)
Other
Alcohol
Acetone
Acrylonitrile
Ammonia
Benzine
Benzol
Butane
Gasoline
Natural Gas
Propane
Naptha
Other
EMERGENCY SERIES
class 2, Division 1 - locations where the hazardous dust is in suspension in the environment under normal operations both continuously or periodically.
The hazardous condition is always considered present.
291
Examples of class 2 hazardous materials include:
Group E
Group F
Group G
Metal dust
Coal
Carbon black
Coke dust
Flour
Starch
Grain dust
Other
Examples of class 3 hazardous materials include:
• Ignitable fibres
• Other fibres
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 292
SLBIS
NEMA12/EEMAC12
Emergency Light
A=18.0000”
B=20.0000”
A=16.7500”
B=18.7500”
A=12.5000”
B=14.5000”
A=8.0000”
B=10.0000”
A=10.2500”
B=12.2500”
8.1250”
Head Types
4.7500
4.8750
4.8750
3.0000
5.7500
6.1250
4.5000
Approvals:
CSA Certified to
C22.2 #141
Type P
Type R
Type D
PAR 36
À lʼépreuve des intempéries
55 watts max.
PAR 36 Faisceau scellé
Caoutchouc
55 watts max.
MR 16
Moulé sous pression
50 watts max.
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLBIS series of NEMA12 and EEMAC12 rated emergency lighting
units provide the rugged dependability needed from a dust tight unit. The all steel
housing features integral mounting points and a simple screw lock hinged cover.
The SLBIS is available in 6V, 12V and 24V versions and will provide up to 360W
of emergency power for 30 minutes duration. A variety of heads and lamp combinations can be fitted to the unit, providing great flexibility in meeting specific
lighting requirements. Large magnum terminals allow for the connection of various remote load(s).
The SLBIS series dust tight units come complete with high quality, pulse action
chargers which are up to 70% more efficient than constant voltage chargers. The
chargers are solid state and are complete with low voltage disconnect,
brownout, and short circuit protections. Standard dual input of either 120VAC or
347VAC is field selectable. A dual LED display indicates AC-ON and High charge,
and all chargers are complete with a quick test, dust tight, push-button switch
for easy maintenance and testing. Recharge time is 24 hours. Optional automatic self-diagnostic/ test control boards are also available.
Features
Warranty
The SLBIS unit is a completely self-contained emergency light, rated to NEMA
12/EEMAC 12 standards and made for use on 120 or 347 volt circuits. A 120 volt
line cord complete with dust tight connector is installed on standard models. A
maintenance free, sealed lead acid battery is included with the unit which will
provide the specified wattage for 30 minutes duration. Four integral mounting
holes are provided on the back of the unit. Grey industrial finish is standard, and
custom colours are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
292
Series
Voltage
Wattage
Heads
SLBIS
06-6 volt
12-12 volt
24-24 volt
see rating
chart
below
(eg. 100)
00-no heads
1P-1 PAR 36 (weatherproof)
2P-2 PAR 36 (weatherproof)
1R-1 PAR 36 (rubber)
2R-2 PAR 36 (rubber)
1D-1 MR16 (NEMA4)
2D-2 MR16 (NEMA4)
Lamp
Options
(eg. 09)
Q-Quartz Halogen
see lamp
T-Tungsten
selection chart
below
AT, OBM, FD5, FD6, V, A, TD*, TP,
TPB, BD, LD, IRT*, RFS*, CT, TLP*,
ACTB, DCTB, HTR*, WE, SP, PG
Wireguard
* Specify AC voltage.
See options descriptions on page 334
Lamp Selection
Model Ratings
Model
Lamp Watts
SLBIS06036
SLBIS06050
SLBIS06072
SLBIS06100
SLBIS06160
SLBIS06180
Volt. Cabinet Wattage Capacities in minutes
30min. 60min. 120min. 240m.
6
A
36
18
9
NA
6
A
50
25
12
6
6
A
72
36
18
9
6
A
100
50
25
12
6
A
160
80
40
20
6
A
180
90
45
23
SLBIS12036
SLBIS12050
SLBIS12072
SLBIS12100
SLBIS12160
SLBIS12200
SLBIS12250
SLBIS12360
12
12
12
12
12
12
12
12
A
A
A
A
A
A
B
B
36
50
72
100
160
200
250
360
18
25
36
50
80
100
125
180
9
12
18
25
40
50
60
90
NA
NA
NA
12
20
25
30
45
SLBIS24144 24
SLBIS24200 24
SLBIS24320 24
A
A
B
144
200
320
72
100
160
36
50
80
18
25
40
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
24 Volts
10W, 12W, 20W,
35W, 50W
PAR36 - Large Heads
Q
T
SB Q
SB T
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
12W, 20W
5.4W, 7.2W, 9W, 18W, 25W
5.4W, 9W, 18W, 25W
9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
55W, 70W
9W, 12W, 18W
25W
N/A
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 293
A=16.4500”
B=18.5100”
C=20.5000”
A=15.2000”
B=17.2600”
C=19.2500”
A=11.4500”
B=13.5100”
C=15.5000”
SLBIF
A=5.4300”
B=5.6000”
C=6.6000”
Head Types
NEMA4X/EEMAC4X
Emergency Light
A=9.3100”
B=11.3000”
C=13.3200”
4.7500
4.8750
4.8750
3.0000
5.7500
6.1250
4.5000
Type R
Type D
PAR 36 Sealed Beam
Rubber
Max 55 watt
MR 16
Die Cast
Max 50 watts
Approvals:
CSA Certified to
C22.2 #141
Description
Circuitry
The Stanpro SLBIF series of NEMA4X and EEMAC4X rated water tight
emergency lighting units provide exceptional protection from extreme environments. The fibreglass reinforced housing features integral mounting points, a
simple screw lock hinged cover and a moulded, one piece gasket seal. The BIF
is available in 6V, 12V and 24V versions and will provide up to 720W of emergency power for 30 minutes duration. A variety of heads and lamp combinations
can be fitted to the unit, providing great flexibility in meeting specific lighting
requirements. Large magnum terminals allow for the connection of various
remote load(s).
The SLBIF series of water tight units come complete with high quality, pulse
action chargers which are up to 70% more efficient than constant voltage chargers. The chargers are solid state and are complete with low voltage disconnect,
brownout, and short circuit protections. Standard dual input of either 120VAC or
347VAC is field selectable. A dual LED display indicates AC-ON and High charge,
and all chargers are complete with a quick test, sealed, push-button switch for
easy maintenance and testing. Recharge time is 24 hours. Optional automatic
self-diagnostic/test control boards are also available.
Warranty
Features
The SLBIF unit is a completely self-contained emergency light, rated to NEMA
4X/EEMAC 4X standards and made for use on 120 or 347 volt circuits. A 120 volt
line cord complete with a liquid tight connector is installed on standard models.
A rated, one-way, covered breather valve allows for the escape of any gases or
condensation. A maintenance free, sealed lead acid battery is included with the
unit which will provide the specified wattage for 30 minutes duration. Four integral mounting holes are provided in the back of the unit. Grey industrial finish is
standard, and custom colours are optional.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Type P
PAR 36
Weather-proof
Max 55 watts
Ordering Guide
—
Series
Voltage
Wattage
Heads
SLBIF
06-6 volt
12-12 volt
24-24 volt
see rating
chart
below
(eg. 100)
00-no heads
1P-1 PAR 36 (weatherproof)
2P-2 PAR 36 (weatherproof)
1R-1 PAR 36 (rubber)
2R-2 PAR 36 (rubber)
1D-1 MR16 (NEMA4)
2D-2 MR16 (NEMA4)
Lamp Watts
Lamp
Options
(eg. 09)
Q-Quartz Halogen
see lamp
T-Tungsten
selection chart
below
AT, OBM, FD5, FD6, TD*, TP, TPB,
BD, LD, IRT*, RFS*, CT, TLP*,
ACTB, DCTB, HTR*, WE, SP, PG
Wireguard
* Specify AC voltage
See options descriptions on page 334
Model Ratings
Model
SLBIF06036
SLBIF06050
SLBIF06072
SLBIF06100
SLBIF06160
SLBIF06180
SLBIF12036
SLBIF12050
SLBIF12072
SLBIF12100
SLBIF12160
SLBIF12200
SLBIF12250
SLBIF12360
Volt. Cabinet Wattage Capacities in minutes
30min. 60min. 120min. 240m.
6
A
36
18
9
NA
6
A
50
25
12
NA
6
A
72
36
18
9
6
A
100
50
25
12
6
B
160
80
40
20
6
B
180
90
45
23
12
A
36
18
9
NA
12
A
50
25
12
NA
12
A
72
36
18
NA
12
A
100
50
25
12
12
B
160
80
40
20
12
B
200
100
50
25
12
B
250
125
60
30
12
C
360
180
90
45
SLBIF24144
SLBIF24200
SLBIF24320
SLBIF24350
SLBIF24550
SLBIF24720
24
24
24
24
24
24
B
B
B
B
C
C
144
200
320
350
550
720
72
100
160
175
275
360
36
50
80
86
140
180
Lamp Selection
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
24 Volts
10W, 12W, 20W,
35W, 50W
PAR36 - Large Heads
Q
T
SB Q
SB T
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
12W, 20W
5.4W, 7.2W, 9W, 18W, 25W
5.4W, 9W, 18W, 25W
9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
55W, 70W
9W, 12W, 18W
25W
N/A
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
18
25
40
44
70
90
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
293
07- emergency
02/2009/19
2:38 PM
Page 294
SLEXR & SLSRR
12.1250”
“Rainstorm”
NEMA4X/EEMAC4X
Exit Series
12.1250”
SORTIE
Approvals:
CSA Certified to
C22.2 #141
6.8750”
11.880”
21.930”
6.580”
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLEXR & SLSRR series of NEMA4X and EEMAC4X rated water tight
exit signs provide exceptional protection from extreme environments. Suitable
for outdoor and wash-down locations, the SLEXR & SLSRR series are designed
using a fiberglass reinforced thermoplastic housing. The housing features four
enclosed, integral wall mounting points and a moulded gasket that completely
seals the housing from the elements. For other mounting configurations, see the
options section. The SLEXR & SLSRR are supplied standard long-life, high brightness LED versions with energy efficient consumption.
The SLEXR & SLSRR series of NEMA4X and EEMAC4X rated signs are supplied
standard with 120/347VAC dual input voltage, available in AC only, AC/DC and
self-powered models. AC/DC models feature universal emergency backup DC
voltages: 6, 12 or 24VDC, each field selectable. Emergency power wattages for
LED models are as follows:
Features
The SLEXR & SLSRR water tight signs utilize a heavy-duty fiberglass reinforced
thermoplastic housing. The faceplate is manufactured with a form moulded, one
piece gasket that seals the luminaire from dust and water. The faceplate(s) is
secured to the housing with four captive, oversized screws. A one-way breather
valve for the escape of any battery associated gases or condensation is installed
on self-powered models. The housing is supplied standard in a grey industrial
finish; the exit stencil is standard white background with red letters.
VDC
IB
6V
12V
24V
120V
347V
120V
347V
EXIT
1.5
3.0
7.0
2.3
2.7
-
-
SORTIE
1.3
1.7
3.2
1.4
1.5
4.0
4.0
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
294
Series
Approval
Face #
Frame Colour
Mounting
Options
SLEXR
SLSRR
C-C680
Certified
1-Single Face
2-Double Face
GY-Grey
CM - ceiling mount
WM - wall mount
EM - end mount
PM - pendant mount
(Exit only)
AT*, TP, TPB, IB, IB2, 120VDC**, PG,
OP, NDC, UB, G**, CM, EM, HTR,
Wireguard
See options descriptions on page 334
* 120V only.
** Exit signs only.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
02/2009/19
2:38 PM
Page 295
SORTIE
SLSRN & SLEXN
8.75’’
11.880”
21.930”
19.25’’
NEMA4X/EEMAC4X
Exit Series
2.75’’
6.580”
EXIT
8.75’’
11.880”
Approvals:
CSA Certified to
C22.2 #141
21.930”
19.25’’
Description
Circuitry
The Stanpro SLSRN/SLEXN series of NEMA4X and EEMAC4X rated water tight
sortie and exit signs provide exceptional protection from extreme environments.
Suitable for outdoor and wash-down locations, the SLSRN/SLEXN series are
designed using a polycarbonate housing. The housing features a moulded gasket
that completely seals the housing from the elements. For mounting configurations, see the ordering guide. SLSRN/SLEXN are supplied standard long-life, high
brightness LED with energy efficient consumption.
The SLSRN/SLEXN series of NEMA4X and EEMAC4X rated signs are supplied
standard with 120/347VAC dual input voltage, available in AC only, AC/DC and
self-powered models. AC/DC models feature universal emergency backup DC
voltages: 6, 12 or 24VDC, each field selectable. Emergency power wattages for
LED models are as follows:
Features
The SLSRN/SLEXN water tight signs utilize a heavy-duty reinforced polycarbonate housing. The faceplate is manufactured with a form moulded, one piece gasket that seals the luminaire from dust and water. The faceplate(s) is secured to
the housing with ten captive screws. The housing is supplied standard in a black
industrial finish; the sortie and exit stencisl are standard white background with
red letters.
VDC
IB
6V
12V
24V
120V
347V
120V
347V
EXIT
0.8
1.8
3.8
3.3
2.9
-
-
SORTIE
1.6
3.0
6.0
3.8
3.6
-
-
Self-powered models utilize an internal, solid state charger and come complete
with a high-performance Ni-Cad battery, supplying 90 minutes of emergency
power. Up to 180 minute, extended duration batteries are optional.
Warranty
EMERGENCY SERIES
07- emergency
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
295
Ordering Guide
Series
Approval
Face #
Mounting
Frame Colour
Voltage
SLSRN
(Sortie)
SLEXN
(Exit)
C-C860
Certified
1-Single Face
2-Double Face
CM - ceiling
WM - wall
PM - pendant
EM - end mount
BK-Black
N, Z
Line voltage Identifier:
Options
TP, TPB, OP, IB,
IB2, NDC,
UNVDC
See options
descriptions
on page 334
N - No AC
Z - 120/347V
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 296
SPEXR
17.8750”
16.6250”
NEMA4X/EEMAC4X
Combination
Exit Series
Head Types
6.8750”
12.1250”
4.7500
4.8750
3.0000
5.7500
6.1250
4.5000
Approvals:
CSA Certified to
C22.2 #141
Type P
Type R
Type D
PAR 36
Weather-proof
Max 55 watts
PAR 36 Sealed Beam
Rubber
Max 55 watt
MR 16
Die Cast
Max 50 watts
EMERGENCY SERIES
Description
Circuitry
The Stanpro SPEXR series of NEMA4X and EEMAC4X rated water tight combination exit signs provide exceptional protection from extreme environments.
Suitable for outdoor and wash-down locations, the SPEXR series are designed
using a thermoplastic housing. The housing features four enclosed, integral wall
mounting points and a moulded gasket that completely seals the housing from
the elements. For other mounting configurations, see the options section. The
SPEXR is supplied standard with long-life, high brightness LEDs with energy efficient consumption as low as just 3.6W AC. A variety of heads and lamp combinations can be fitted to the exit, providing great flexibility in meeting specific
lighting requirements.
The SPEXR series of NEMA4X and EEMAC4X rated combination exits utilize a
high quality, pulse action charger which is up to 70% more efficient than constant voltage chargers. The solid state charger is complete with low voltage disconnect, brownout and short circuit protections. Standard dual input of either
120VAC or 347VAC is field selectable on all models. An AC-ON LED indicator is
standard for all models along with a sealed, push-button, momentary test switch
for easy maintenance and testing. Recharge time is 24 hours.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Features
The SPEXR water tight combination exits utilize a heavy-duty, fiberglass reinforced thermoplastic housing. The faceplate is manufactured with a form moulded, one piece gasket that seals the luminaire from dust and water. The faceplate(s) then is secured to the housing with four captive, oversized screws. A
one-way breather valve for the escape of any battery associated gases or condensation is installed on all models. Emergency backup power is supplied from
a maintenance free, sealed lead acid battery which will provide the specified
wattage for 30 minutes duration. The housing is supplied standard in a grey
industrial finish; the exit stencil is standard white background with red letters.
Ordering Guide
296
—
Series
Voltage
SPEXR 06-6 volt
C680
12-12 volt
Certified
Wattage
Face #
see rating
chart
below
(eg. 036)
1-Single
Face
2-Double
Face
Heads
00-no heads
(eg. 09)
1P-1 PAR 36 (weatherproof)
see lamp
2P-2 PAR 36 (weatherproof)
selection
1R-1 PAR 36 (rubber)
chart below
2R-2 PAR 36 (rubber)
1D-1 MR16 (NEMA4)
2D-2 MR16 (NEMA4)
SPEXR6036
SPEXR6050
SPEXR6072*
SPEXR1036
SPEXR1050
SPEXR1072
SPEXR1108*
* Single face only
Lamp
Mounting
Q-Quartz WM - wall mount
Halogen CM - ceiling mount
T-Tungsten EM - end mount
Lamp Selection
Model Ratings
Model
Lamp Watts
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
6
36
18
9
NA
6
50
25
12
NA
6
72
36
18
9
12
36
18
9
NA
12
50
25
12
NA
12
72
36
18
9
12
108
54
26
12
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W
Options
AT, TP, TPB,
TD*, RFS*, OP,
PG, G, CM,
EM, HTR
Wireguard
* Specify AC
voltage
See options
descriptions on
page 334
8W, 10W, 12W,
20W, 35W, 50W
PAR36 - Large Heads
Q
T
SB Q
SB T
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
5.4W, 7.2W, 9W, 18W, 25W
5.4W, 9W, 18W, 25W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
9W, 12W, 18W
Q = Quartz Halogen
T = Tungsten
25W
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 297
14.5”
SPEXN &
SPSRN
14.5”
4.75”
19.5”
EMA4X/EEMAC4X
Combination
Series
19.5”
4.7500
Head Types
5.7500
Approvals:
CSA Certified to
C22.2 #141
Type P
PAR 36
Weather-proof
Max 55 watts
The Stanpro SPEXN/SPSRN series of NEMA4X and EEMAC4X rated water tight
combination exit signs provide exceptional protection from extreme environments. Suitable for outdoor and wash-down locations, the SPEXN/SPSRN series
are designed using a black polycarbonate housing. The housing features ten
enclosed, integral wall mounting points and a moulded gasket that completely
seals the housing from the elements. For other mounting configurations, see the
options section. The SPEXN/SPSRN are supplied with standard long-life, high
brightness LEDs with energy efficient consumption as low as just 3.6W AC. A
variety of heads and lamp combinations can be fitted to the exit, providing great
flexibility in meeting specific lighting requirements.
plied from a maintenance free, sealed lead acid battery which will provide the
specified wattage for 30 minutes duration. The housing is supplied standard in
a black finish; the exit stencil is standard white background with red letters.
Circuitry
The SPEXN/SPSRN series of NEMA4X and EEMAC4X rated combination utilize a
high quality, pulse action charger which is up to 70% more efficient than constant voltage chargers. The solid state charger is complete with low voltage disconnect, brownout and short circuit protections. Standard dual input of either
120VAC or 347VAC is field selectable on all models. An AC-ON LED indicator is
standard for all models along with a sealed, push-button, momentary test switch
for easy maintenance and testing. Recharge time is 24 hours.
Features
The SPEXN/SPSRN water tight combination utilize a heavy-duty, polycarbonate
housing. The faceplate is manufactured with a form moulded, one piece gasket
that seals the luminaire from dust and water. The faceplate(s) is secured to the
housing with ten captive, oversized screws. Emergency backup power is sup-
EMERGENCY SERIES
Description
Ordering Guide
Series
Voltage
Wattage
Face #
Mounting
Heads
Lamp Watts
Lamp
Options
SPEXN
(Exit)
SPSRN
(Sortie)
06-6 volt
12-12 volt
(sortie only)
see rating
chart
below
(eg. 036)
1-Single
Face
2-Double
Face
PM - pendant mount
WM - wall mount
EM - end mount
00-no heads
1P-1 PAR 36
(eg. 09)
see lamp
selection
chart below
Q-Quartz
Halogen
T-Tungsten
TP, TPB, OP, HL,
TD, HTR,
AT (sortie only)
(weatherproof)
2P-2 PAR 36
(weatherproof)
See options
descriptions on
page 334
Lamp Selection
Model Ratings
Voltage Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
SPEXN6036
6
36
18
9
N/A
SPEXN6050
6
50
25
12
N/A
SPEXN6072*
6
72
36
18
9
SPEXN1036
12
36
18
9
N/A
SPEXN1050
12
50
25
12
N/A
SPEXN1072
12
72
36
18
9
SPEXN1108*
12
108
54
26
12
SPSRN6036
6
36
18
9
N/A
SPSRN6050
6
50
25
12
N/A
SPSRN6072*
6
72
36
18
9
SPSRN1036
12
36
18
9
N/A
SPSRN1050
12
50
25
12
N/A
SPSRN1072
12
72
36
18
9
SPSRN1108*
12
108
54
26
12
6 Volts
12 Volts
PAR36 - Large Heads
Model
SB Q
SB T
8W, 12W
8W, 10W
8W, 9W, 12W, 18W
12W, 18W
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
* Single face only
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
297
07- emergency
02/2009/19
2:38 PM
Page 298
SPEXH
Class 1 Division 2
Combination
Exit Series
Head Types
16.88”
3.0000
11.88”
4.5000
12.14’’
Type D
MR 16
Die Cast
Max 50 watts
Approvals:
CSA Certified to
C22.2 #141 et #137
6.88”
11.88”
EMERGENCY SERIES
Description
Circuitry
The Stanpro SPEXH series of combination exits are designed to perform in the
demanding environments of Class 1, Division 2 rated hazardous locations. The
exits are rated for use in Class 1, Division 2 locations, contact Stanpro for exact
group and zone ratings. The SPEXH combination exit is available in 12V and will
provide up to 200W of emergency power for 30 minutes duration. A variety of
heads and lamp combinations can be fitted to the exit, providing great flexibility
in meeting specific lighting requirements.
The SPEXH series of hazardous location combination exit signs utilize a solid
state charger and transfer. The charger features solid state components and are
complete with low voltage disconnect, brownout, and short circuit protections.
Standard dual input of either 120VAC or 347VAC is field selectable on all models. An AC-ON LED indicator is standard for combination models and all chargers are complete with a quick test, rated, push-button switch for easy maintenance and testing. Recharge time is 24 hours.
Features
Warranty
All SPEXH models are made for use on 120 or 347 volt circuits. A one-way,
breather valve allows for the escape of any gases or condensation. All models
include include a maintenance free, sealed lead acid battery which will provide
the specified wattage for 30 minutes duration. Grey industrial finish is standard.
AC terminal block is standard.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
Series
Voltage
Wattage
Face #
Heads
Lamp Watts
SPEXH
12-12 volt
see rating
chart
below
1-Single
face
2-Double
face
00-no heads
1D-1 MR16
2D-2 MR16
(eg. 08)
see lamp
selection chart
below
298
SPEXH1036
SPEXH1050
SPEXH1072
SPEXH1100
SPEXH1160
SPEXH1200
Catalog Number
SPEXH1___-_D08Q
SPEXH1___-_D10Q
SPEXH1___-_D12Q
SPEXH1___-_D20Q
SPEXH1___-_D35Q
SPEXH1___-_D50Q
SPEXH1___-00
Options
* Specify AC voltage
See options descriptions
on page 334
Lamp Selection
Model Ratings
Model
Lamp
Q-Quartz Halogen AT, FD5, TD*, DCTB,
WG, PG
Voltage Wattage Capacities in minutes
30 min. 60 min. 120min.
12
36
18
9
12
50
25
12
12
72
36
18
12
100
50
25
12
160
80
40
12
200
100
50
Temperature Code
T3C
T3A
T3A
T2C
T2A
T1
T3C
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
Q = Quartz Halogen
Description
Combo pack, with 8W quartz halogen lamps
Combo pack, with 10W quartz halogen lamps
Combo pack, with 12W quartz halogen lamps
Combo pack, with 20W quartz halogen lamps
Combo pack, with 35W quartz halogen lamps
Combo pack, with 50W quartz halogen lamps
Combo pack, no integral-mounted lamps
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 299
SLEXH
Class 1 Division 2
Exit Series
11.8750”
12.1400
6.8750”
Approvals:
CSA Certified to
C22.2 #141 & #137
Description
Circuitry
The Stanpro SLEXH series of AC only exit signs are designed to perform in the
demanding environments of Class 1, Division 2 rated hazardous locations. The
exits are rated for use in Class 1, Division 2 locations, contact Stanpro for exact
group and zone ratings. The enclosure also meets the requirements for NEMA 4X
/ EEMAC 4X. The SLEXH self-powered version comes complete with an internal
battery that will automatically power the sign for 90 minutes duration upon regular AC failure.
The SLEXH series of hazardous location exits come in a variety of
versions. The self-powered versions utilize a solid state charger and transfer. An
AC-ON LED indicator is standard for self-powered models and all come complete with a quick test, hazardous location rated, push-button switch for easy
maintenance and testing. Recharge time is 24 hours.
Features
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Warranty
The SLEXH series of Class 1, Division 2 exits include AC only and completely
self-contained, self-powered exit models. All models are made for use on 120 or
347 volt circuits. A rated, one-way, breather valve allows for the escape of any
gases or condensation. Grey industrial finish is standard. AC terminal block is
standard.
Ordering Guide
Series
Face #
Colour
SLEXH
1-Single Face
GY-Grey (standard)
EMERGENCY SERIES
11.8750”
299
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 300
SLBXPII
Hazardous location
Battery unit
Head Types
1
2
3
3.0000
4.5000
Approvals:
CSA Certified to C22.2 #141
& C22.2 #137
Type D
MR 16
Die Cast
Max 50 watts
EMERGENCY SERIES
Description
Circuitry
The SLBXPII series of class 1, Division 2 / Zone 2 group C & D rated battery units
are designed to perform in demanding hazardous applications. The unit maintains its sealed interior with a continuous integral gasket. As well the LED pilot
light and test switch is sealed, hazardous location rated type. The breather, pilot
light and test switch shall be mounted into the bottom of the enclosure to allow
for quick and simple visual inspection and maintenance testing from below.
Heads are MR16. Available with 12VDC emergency backup power in a range of
battery capacities. NEMA 4X / EEMAC 4X with no head.
• 120/347VAC 60Hz Input, field selectable
• High efficiency, rapid recovery, precision control charging system
• 12VDC emergency power output
• Wattage capacities from 36 to 200 watts
• 30 Minutes emergency power duration standard
• Sealed momentary push button test switch
• Diagnostic/pilot LED for AC ON
• Fully automatic, current limited charger
• Line latched, low voltage protection
• Solid state design and construction
• Brownout and short circuit protections
• Temperature compensated
• Large terminal strip connectors for all electrical connections - AC and DC
• Complete battery recharge in 24 hours
• Maintenance free, sealed lead acid battery
Features
• Heavy-duty non-metallic, reinforced construction
• One piece, molded and gasketed lens
• Four external mounting feet (one per corner)
• Bottom hinged cover, secured with two screws
• One-way breather valve for release of gases and/or moisture condensation
• All external metal hardware is stainless steel
• Wall mount construction
• Grey finish housing
• Optional heads include: Die cast metal rated MR16 type
• Top head mounting is standard
• AC terminal block
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
300
—
Series
SLBXPII
Voltage
12-12 volt
Wattage
Heads
see rating
chart
below
(eg. 100)
Lamp Watts
00-no heads
1D-1 MR16
2D-2 MR16
Model rating
Model
12VDC
12VDC
12VDC
12VDC
12VDC
12VDC
see lamp
selection chart
below (eg. 08)
GRY- Grey (std)
36
50
72
100
160
200
Wattage Capacities
60 min.
90 min.
18
25
36
50
80
100
12
16
24
33
53
66
120 min.
9
12
18
25
40
50
Options
AT, DCTB,
wireguard
See options
descriptions
on page 334
Lamp Selection
Voltage
30 min.
SLBXPII1236
SLBXPII1250
SLBXPII1272
SLBXPII12100
SLBXPII12160
SLBXPII12200
Colour
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
Q = Quartz Halogen
Catalog Number
SLBXPII___-_D08Q
SLBXPII___-_D10Q
SLBXPII___-_D12Q
SLBXPII___-_D20Q
SLBXPII___-_D35Q
SLBXPII___-_D50Q
SLBXPII___-00
Temperature
Code
T3C
T3A
T3A
T2C
T2A
T1
T3C
Description
Battery unit, with 8W quartz halogen lamps
Battery unit, with 10W quartz halogen lamps
Battery unit, with 12W quartz halogen lamps
Battery unit, with 20W quartz halogen lamps
Battery unit, with 35W quartz halogen lamps
Battery unit, with 50W quartz halogen lamps
Battery unit, no integral-mounted lamps
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
02/2009/19
2:38 PM
Page 301
EMERGENCY SERIES
07- emergency
301
07- emergency
02/2009/19
2:38 PM
Page 302
SLEXY
Hazardous Location
Exit Series
Approvals:
CSA Certified to
C22.2 #30
EMERGENCY SERIES
Description
Warranty
The Stanpro SLEXY series of hazardous location exit signs are designed to meet
and exceed the most stringent code requirements. The housings are made from
copper free, heavy-duty die cast aluminum. The exit frame and faceplate(s) are
manufactured in heavy gauge steel with a white, baked powder coat finish. The
signs can be specified to suit a variety of mounting options including ceiling, wall
and pendant mount.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Features
Both the wall and ceiling mount versions of the SLEXY series of hazardous location remote luminaires incorporate integral mounting points and junction box.
The mounting holes are sized to accommodate oversized lags or other mounting
hardware (not supplied) and are located for easy access during installation. The
integral junction box allows for a variety of conduit/rigid connection options with
multiple pretapped and plugged holes. For all mounting types, lamp circuit wires
are pre-pulled through the luminaire for rapid installation. Please note that C860
standard certification does not apply to hazardous location exit signs. High efficiency led lamp for normal operation on 120VAC only.
Ordering Guide
—
302
Series
Face #
Voltage
Class
Division
Group
Mounting
SLEXY
1-Single
face
2-Double
face
06-6VDC
12-12VDC
24-24VDC
1
1
C
D
CM-Ceiling Mount
PM-Pendant Mount
WM-Wall Mount
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 303
SPEXY/SPSXY
Hazardous Location
Combination
Exit Series
Description
Circuitry
The Stanpro SPEXY series of hazardous location combination exit signs are
designed to meet and exceed the most stringent code requirements. The housings are made from copper free, heavy-duty die cast aluminum. Units can be
specified with or without an attached emergency lighting head. The exit frame
and faceplate(s) are manufactured in heavy gauge steel with a white, baked
powder coat finish. A downlight is provided in the bottom of each exit for additional light at floor level.
The Stanpro SPEXY units come complete with a high quality, pulse action charger which is up to 70% more efficient than constant voltage chargers. The solid
state chargers are complete with low voltage disconnect, brownout, and short
circuit protections. Models are standard 120VAC or 347VAC input, specify when
ordering. A standard dual purpose AC ON pilot light and push button, momentary
test switch allow for easy maintenance and testing. Recharge time is 24 hours.
Features
The SPEXY series of hazardous location combination exit signs utilize a single,
die cast aluminum housing. The internal cavity of the housing is easily accessed
via a circular screw on/off cover. Four integral mounting feet are sized to accommodate oversized lugs or other mounting hardware (not supplied). A stainless
steel one way breather valve allows for the release of internal condensation. exit
and sortie signs are illuminated with high efficiency LED lamps in normal mode
for energy efficiency.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
Voltage
Wattage
SPEXY
(exit)
SPSXY
(sortie)
6-6VDC
1-12VDC
2-24VDC
See rating 1-Single
chart
face
below
2-Double
(eg. 036)
face
Face #
Class Div. Group
1
SPEXY6036
SPEXY6050
SPEXY6072
SPEXY6100
SPEXY1036
SPEXY1050
SPEXY1072
SPEXY1100
SPEXY1144
SPEXY1160
SPEXY1200
SPEXY2144
SPEXY2320
Voltage
6
6
6
6
12
12
12
12
24
24
24
24
24
C
D
Heads
0 - no heads
1R1L - one head
one lamp per head
1R2L - one head
two lamps per head
2R1L - two heads
one lamp per head
2R2L - two heads
two lamp per head
Lamp Watts Lamp Type
(eg. 12)
See lamp
selection
chart
below
Lamp Selection
Model Ratings
Model
1
Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
36
18
9
NA
50
25
12
NA
72
36
18
9
100
50
25
12
36
18
9
NA
50
25
12
NA
72
36
18
9
100
50
25
12
144
72
36
18
160
80
40
20
200
100
50
25
144
72
36
18
320
160
80
40
6 Volts
Q
12 Volts
PAR18 - Small Heads
8W, 10W, 12W
8W, 10W, 12W, 20W
24 Volts
12W, 20W
Q = Quartz Halogen
Maximum of two 20W quartz lamps per globe/head.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
Q-Quartz
Halogen
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #30
Options
TD, RFS, WG
See options
descriptions
on page 334
303
07- emergency
02/2009/19
2:38 PM
Page 304
SLBXP
Hazardous Location
Emergency Light
Approvals:
CSA Certified to
C22.2 #30
EMERGENCY SERIES
Description
Circuitry
The Stanpro SLBXP series of hazardous location emergency lights are designed
to meet and exceed the most stringent code requirements. The housings are
made from copper free, heavy-duty die cast aluminum. Units can be specified
with none, one or two attached emergency lighting heads and each head can
house one or two independently aimed PAR 18 lamp assemblies. Units are also
capable of supplying emergency lighting power to remote heads, as specified.
The Stanpro SLBXP units come complete with a high quality, pulse action
charger which is up to 70% more efficient than constant voltage chargers. The
solid state chargers are complete with low voltage disconnect, brownout, and
short circuit protections. Models are standard 120VAC/ 347VAC dual input, field
selectable. A standard dual purpose AC ON pilot light and push button, momentary test switch allow for easy maintenance and testing. Recharge time is 24
hours.
Features
The SLBXP series of hazardous location emergency lights utilize a single, die
cast aluminum housing. The internal cavity of the housing is easily accessed via
a circular screw on/off cover. Four integral mounting feet are sized to accommodate oversized lugs or other mounting hardware (not supplied). A stainless steel
one way breather valve allows for the release of internal condensation.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
304
Series
Voltage
Wattage
Face #
SLBXP
6-6VDC
1-12VDC
2-24VDC
See rating 1-Single
chart
face
below
2-Double
(eg. 036)
face
Class Div. Group
1
Model Ratings
Model
SLBXP06036
SLBXP06050
SLBXP06072
SLBXP06100
SLBXP12036
SLBXP12050
SLBXP12072
SLBXP12100
SLBXP12144
SLBXP12160
SLBXP12200
SLBXP24144
SLBXP24360
Voltage
6
6
6
6
12
12
12
12
24
24
24
24
24
1
C
D
Heads
Lamp Watts Lamp Type
0 - no heads
1R1L - one head
one lamp per head
1R2L - one head
two lamps per head
2R1L - two heads
one lamp per head
2R2L - two heads
two lamp per head
(eg. 12)
See lamp
selection
chart
below
Q-Quartz
Halogen
Options
TD, RFS, WG
See options
descriptions
on page 334
Lamp Selection
Wattage Capacities in minutes
30 min. 60 min. 120 min. 240 m.
36
18
9
s/o
50
25
12
s/o
72
36
18
9
100
50
25
12
36
18
9
s/o
50
25
12
s/o
72
36
18
9
100
50
25
12
144
72
36
18
160
80
40
20
200
100
50
25
144
72
36
18
360
180
90
45
6 Volts
Q
12 Volts
PAR18 - Small Heads
8W, 10W, 12W
8W, 10W, 12W, 20W
24 Volts
12W, 20W
Q = Quartz Halogen
Maximum of two 20W quartz lamps per globe/head.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 305
SLRXP
Hazardous Location
Remote Series
Description
Light Source
The Stanpro SLRXP series of hazardous location remote luminaires are designed
to meet and exceed the most stringent code requirements. The housings are
made from copper free, heavy-duty die cast aluminum and the lenses from
industrial grade Pyrex. The housings can be specified to suit a variety of mounting options including ceiling, wall and pendant mount. The remotes can also be
specified as one individual globe/head or a two individual globe/heads connected via a supplied junction box.
For applications specifying the use of low voltage lamps (24V and under), the
SLRXP hazardous remotes utilize a PAR 18 reflector assembly mounted inside
the Pyrex globe. The assembly is designed to use quartz halogen lamps and can
be fully rotated and swivelled to achieve the best lighting distribution. Class1 DIV2 only.
Features
Both the wall and ceiling mount versions of the SLRXP series of hazardous location remote luminaires incorporate integral mounting points and junction box.
The mounting holes are sized to accommodate oversized lugs or other mounting hardware (not supplied) and are located for easy access during installation.
The integral junction box allows for a variety of conduit/rigid connection options
with multiple pretapped and plugged holes. For all mounting types, lamp circuit
wires are pre-pulled through the luminaire for rapid installation.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
EMERGENCY SERIES
Approvals:
CSA Certified to
C22.2 #30
Ordering Guide
—
Series
Heads
No. of lamps
Voltage
SLRXP
1-Single
2-Double
(with J-Box)
1L-Single
lamp
2L-Double
lamp
06-6V
12-12V
24-24V
Lamp Watts Lamp Type
(eg. 12)
See lamp
chart
below
Q-Quartz
Halogen
—
Class
Div.
Group
Mounting
1
1
2
C
D
E
F
G
CM-Ceiling
mount
PM-Pendant
mount
WM-Wall
mount
Options
WG
Die cast aluminum head guard
Lamp Selection
6 Volts
12 Volts
DIV1 & 2 - PAR18 - Small Heads
Q
8W, 10W, 12W
8W, 10W, 12W, 20W
24 Volts
12W, 20W
DIV2 ONLY - PAR18 - Small Heads
T
9W
9W, 12W, 18W
9W, 18W
Q = Quartz Halogen
Maximum of two 20W quartz lamps per globe/head.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
305
07- emergency
02/2009/19
2:38 PM
Page 306
N Series
Thermoplastic PAR18
Emergency Remotes
Approvals:
CSA Certified to
C22.2 #141
Description
2.8000”
EMERGENCY SERIES
The Stanpro N series are thermoplastic remote heads featuring a fully
adjustable locking tilt and swivel. Available with tungsten or quartz lamps up to
18W, these remotes are designed for use with 6, 12 or 24V emergency lighting
circuits. The 5” canopy mounts directly to a standard electrical box (not supplied). Standard finish is white. Other colours are available, please consult
Stanpro for details.
5.7416”
5.0000” dia.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
9.3488”
2.8000”
4.4304”
5.0000” dia.
Ordering Guide
306
Series
Voltage
Lamp Watts
Lamp Type
Options
N1- Single Head
N2- Double Head
N3- Triple Head
N4- Quad Head
06-6VDC
12-12VDC
24-24VDC
(eg. 09w)
see lamp
selection chart
Q-Quartz
T-Tungsten
BK-Black
SP-Custom
colour
Lamp Selection
6 Volts
Q
T
12 Volts
PAR18 - Small Heads
24 Volts
8W, 10W, 12W
8W, 10W, 12W
12W
5.4W, 7.2W, 9W
5.4W, 9W, 12W, 18W
9W, 18W
Q = Quartz Halogen
T = Tungsten
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 307
L Series
PAR 36 Emergency
Remotes
Approvals:
CSA Certified to
C22.2 #141
Description
6.5500”
Warranty
5.0000” dia.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
9.5000”
4.7500”
EMERGENCY SERIES
4.7500
The Stanpro L series are thermoplastic remote heads featuring a fully
adjustable locking tilt and swivel. Available with tungsten or quartz lamps up to
18W, these remotes are designed for use with 6, 12 or 24V emergency lighting
circuits. The 5” canopy mounts directly to a standard electrical boxes (not supplied). Standard finish is white. Other colours are available, please consult
Stanpro for details.
6.1500”
5.0000” dia.
Ordering Guide
307
Series
Voltage
L1- Single Head
L2- Double Head
L3- Triple Head
L4- Quad Head
Lamp Watts
06-6VDC
(eg. 09w)
12-12VDC
see lamp
24-24VDC selection chart
120-120VDC
Lamp Type
Options
Q-Quartz
T-Tungsten
BK-Black
SP-Custom
colour
Lamp Selection
6 Volts
Q
T
SB Q
SB T
12 Volts
PAR36 - Large Heads
24 Volts
120 Volts
8W, 10W, 12W
8W, 10W, 12W
12W, 18W
-
5.4W, 7.2W, 9W, 18W
5.4W, 9W, 18W
9W, 18W, 25W
15W
8W, 10W, 12W
8W, 12W
55W, 70W
30W, 50W
9W,18W
-
-
-
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 308
R Series
PAR 36 Rubber
Emergency Remotes
Description
EMERGENCY SERIES
The Stanpro R series are PAR 36, single piece, molded rubber heads. Suitable
for outdoor and washdown area use. The heads have fully adjustable tilt and
swivel. Available with sealed beam tungsten or quartz lamps up to 55W, these
remotes are designed for use with 6 or 12V emergency lighting circuits. The 5”
canopy mounts directly to a standard electrical box (not supplied). Standard finish is black.
4.8750”
6.8750”
4.5000”
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
7.2500”
4.8750”
6.6750”
4.5000”
Ordering Guide
308
Series
Voltage
Lamp Watts
Lamp Type
R1- Single Head
R2- Double Head
06-6VDC
12-12VDC
(eg. 09w)
see lamp
selection chart
Q-Quartz
T-Tungsten
Lamp Selection
6 Volts
12 Volts
PAR36 - Large Heads
SB Q
SB T
Q = Quartz Halogen
8W, 12W, 20W
8W, 12W, 30W, 35W, 55W
9W, 18W, 25W
18W, 25W
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 309
SR Series
PAR 36 Recessed Emergency
Remotes
Approvals:
CSA Certified to
C22.2 #141
The Stanpro SR series are steel PAR 36 recessed ceiling remotes. The lamps
are mounted into an adjustable gimbal mounting. Available with tungsten or
quartz lamps up to 55W, these remotes are designed for use with 6, 12 or 24V
emergency lighting circuits. The 9” diameter trim plate attaches and conceals
the recessed 8” diameter housing. Standard finish is white. Other colours are
available, please consult Stanpro for details.
9.0000”
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
9.0000”
4.0000”
EMERGENCY SERIES
Description
Ordering Guide
Series
Voltage
SR- Recessed
Head
Lamp Watts
06-6VDC
(eg. 09w)
12-12VDC
see lamp
24-24VDC selection chart
32-32VDC
120-120VDC
Lamp Type
Options
Q-Quartz
T-Tungsten
BK-Black
SP-Custom
colour
SF-surface mount
309
Lamp Selection
6 Volts
Q
T
SB Q
SB T
12 Volts
PAR36 - Large Heads
24 Volts
32 Volts
120 Volts
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W, 35W, 55W
12W, 20W
-
-
5.4W, 7.2W, 9W, 18W
5.4W, 9W, 18W, 25W
9W, 18W, 25W
25W
15W, 30W, 50W
8W, 10W, 12W, 20W
8W, 12W, 30W, 35W, 55W
55W, 70W
-
30W, 50W
9W, 18W, 25W
25W
-
-
-
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 310
S Series
Die Cast MR16
Emergency Remotes
Approvals:
CSA Certified to
C22.2 #141
Description
2.2500”
SÉRIE URGENCE
The Stanpro S series are die cast MR16 remote heads featuring a twist lock
lens collar. The heads are fully adjustable in both tilt and swivel. Available with
MR16 quartz halogen lamps up to 50W, these remotes are designed for use
with 6, 12 or 24V emergency lighting circuits. The 5” canopy mounts directly to
a standard electrical box (not supplied). Standard finish is white. Other colours
are available, please consult Stanpro for details.
4.6500”
5.0000”
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
6.3750”
2.2500”
5.0000”
310
Ordering Guide
Series
Voltage
Lamp Watts
Lamp Type
Options
S1- Single Head
S2- Double Head
S3- Triple Head
S4- Quad Head
06-6VDC
12-12VDC
24-24VDC
(eg. 12w)
see lamp
selection chart
Q-Quartz
BK-Black
SP-Custom
colour
Lamp Selection
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
24 Volts
10W, 12W, 20W,
35W, 50W
Q = Quartz Halogen
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 311
M Series
Die Cast MR16
Emergency Remotes
Approvals:
CSA Certified to
C22.2 #141
Description
2.5000”
The Stanpro M series is a decorative die cast metal remote emergency light
which uses powerful MR16 lamps with glass cover. This series is available in
single, double, triple or quad head and is made for use with 6, 12 or 24V emergency lighting systems. The M series features fully adjustable locking swivels
and rotary collar. No tools are needed for lamp aiming or replacement, which
makes for easy installation and maintenance. The 5” canopy mounts directly to
a standard octagon box (not supplied). Standard finish is white. Other colours
are available, please consult Stanpro for details.
EMERGENCY SERIES
4.6500”
5.0000”
Warranty
6.4819”
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
2.2500”
5.0000”
311
Ordering Guide
Series
Voltage
Lamp Watts
Lamp Type
Options
M1- Single Head
M2- Double Head
M3- Triple Head
M4- Quad Head
06-6VDC
12-12VDC
24-24VDC
(eg. 12w)
see lamp
selection chart
Q-Quartz
BK-Black
SP-Custom
colour
Lamp Selection
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
24 Volts
10W, 12W, 20W,
35W, 50W
Q = Quartz Halogen
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 312
SMC
Vandal Cube
Emergency Remotes
Approvals:
CSA Certified to
C22.2 #141
Description
EMERGENCY SERIES
The Stanpro SMC series are polycarbonate vandal proof remote heads ideal for
locations where the luminaire is readily subject to abuse. The polycarbonate
cube is locked to the steel base plate with a formed steel pin and screw. One
or two fully adjustable PAR 18 reflector assemblies can be housed within the
cube. Available with tungsten or quartz lamps up to 40W, these remotes are
designed for use with 6, 12 or 24V emergency lighting circuits.
Warranty
5.3750”
4.6750”
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
5.3750”
Ordering Guide
—
312
Series
SMC1- Single Lamp
SMC2- Double Lamp
Voltage
Lamp Watts
Lamp Type
06-6VDC
12-12VDC
24-24VDC*
(eg. 12w)
see lamp
selection chart
Q-Quartz
T-Tungsten
*40W lamp total max
Lamp Selection
6 Volts
Q
T
12 Volts
PAR18 - Small Heads
24 Volts
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
12W, 20W
9W, 18W
9W, 12W, 18W
9W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W, 20W
Q = Quartz Halogen
8W, 10W, 12W, 20W, 35W
12W, 20W, 35W
T = Tungsten
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 313
SMC2W
Vandal Cube
Emergency Remotes
Approvals:
CSA Certified to
C22.2 #141
Description
5.0000”
6.5000”
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
5.5000”
5.6750”
EMERGENCY SERIES
14.6750”
The Stanpro SMC2W series are double polycarbonate vandal proof remote
heads ideal for locations where the luminaire is readily subject to abuse. Two
polycarbonate cubes are paired to a centre steel base plate. One or two fully
adjustable PAR 18 reflector assemblies can be housed within each cube.
Available with tungsten or quartz lamps up to 20W, these remotes are designed
for use with 6, 12 or 24V emergency lighting circuits.
Ordering Guide
—
313
Series
Voltage
Lamp Watts
Lamp Type
SMC2W- Single
Lamp
06-6VDC
12-12VDC
24-24VDC
(eg. 12w)
see lamp
selection chart
Q-Quartz
T-Tungsten
Lamp Selection
6 Volts
Q
T
12 Volts
PAR18 - Small Heads
24 Volts
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
12W, 20W
9W, 18W
9W, 12W, 18W
9W, 18W
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W, 20W
Q = Quartz Halogen
8W, 10W, 12W, 20W, 35W
12W, 20W, 35W
T = Tungsten
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 314
SRC
Recessed MR16
Emergency Remotes
Series
Approvals:
CSA Certified to
C22.2 #141
Description
EMERGENCY SERIES
The Stanpro SRC series are recessed ceiling remotes utilizing MR16 lamps
mounted into an adjustable steel gimbal mounting. Available with MR16 quartz
lamps up to 50W, these remotes are designed for use with 6, 12 or 24V emergency lighting circuits. The trim plate attaches and conceals the recessed
housing. Standard finish is white. Other colours are available, please consult
Stanpro for details.
8.7500
5.0000
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
5.7500
13.5000
(extends
(extend
up toto24’’)
24.0000)
314
Ordering Guide
Series
Voltage
Lamp Watts
Lamp Type
Options
SRC- Recessed
Head
06-6VDC
12-12VDC
24-24VDC
(eg. 09w)
see lamp
selection chart
Q-Quartz
T-Tungsten
BK-Black
SP-Custom
colour
Lamp Selection
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
Q = Quartz Halogen
8W, 10W, 12W,
20W, 35W, 50W
T = Tungsten
24 Volts
12W, 20W,
35W, 50W
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 315
SWP
Weather Proof
Emergency Remotes
Series
Approvals:
CSA Certified to
C22.2 #141
The Stanpro SWP series are EEMAC 4X rated weather proof remote heads ideal
for exterior or wash down areas. A clear polycarbonate cover with an integral
gasket seals the luminaire from the elements. One or two fully adjustable PAR
18 reflector assemblies can be installed within each housing. Available with
tungsten or quartz lamps up to 20W, these remotes are designed for use with
6, 12 or 24V emergency lighting circuits.
5.0300”
5.0300”
4.0200”
5.0300”
4.0200”
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
7.0000”
EMERGENCY SERIES
Description
315
Ordering Guide
—
Series
SWP1- Single Lamp
SWP2- Double Lamp
Voltage
Lamp Watts
Lamp Type
06-6VDC
12-12VDC
24-24VDC
(eg. 12w)
see lamp
selection chart
Q-Quartz
T-Tungsten
Lamp Selection
6 Volts
Q
T
12 Volts
PAR36 - Large Heads
24 Volts
8W, 10W, 12W, 20W
8W, 10W, 12W, 20W
12W, 20W
9W, 18W
9W, 18W
9W, 18W
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 316
D series
MR16 weatherproof die cast
Emergency
Remotes Series
Approvals:
CSA Certified to
C22.2 #141
Description
EMERGENCY SERIES
The D series by Stanpro is a fully enclosed die-cast remote emergency light.
The gasket seal, ensures that this series will be the perfect choice in an industrial application where water or other contaminants can affect the condition of
the unit. The MR16 lamps provide maximum lighting protection in case of power
failure. The series is available in single or double heads. The 5” canopy mounts
directly to a standard octagon box (not supplied). Standard finish is grey. Other
colours are available, please consult Stanpro for details.
3.0000”
7.6331”
4.8700”
5.0000”
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
9.0423”
3.0000”
7.0640”
4.3109”
5.0000”
316
Ordering Guide
Series
Voltage
Lamp Watts
Lamp Type
Options
D1- Single Head
D2- Double Head
D3- Triple Head
06-6VDC
12-12VDC
(eg. 12w)
see lamp
24-24VDC
Q-Quartz
Halogen
selection chart
SP-Custom
colour
BK-black
Lamp Selection
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
24 Volts
10W, 12W, 20W,
35W, 50W
Q = Quartz Halogen
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 317
P series
PAR 36 Emergency
Remotes Series
Approvals:
CSA Certified to
C22.2 #141
Description
4.7500”
The P series of weather proof thermoplastic remote heads from Stanpro are
designed for damp or exposed locations. The heads are fully adjustable with
locking tilt and swivel. Available with tungsten or quartz lamps up to 18W, these
remotes are designed for use with 6, 12 or 24V emergency lighting circuits. The
5” canopy mounts directly to a standard electrical box (not supplied). Standard
finish is black.
Warranty
5.0000”
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
9.5000”
4.7500”
6.1500”
5.0000” dia.
EMERGENCY SERIES
6.5500”
317
Ordering Guide
Series
Voltage
P1- Single Head
P2- Double Head
Lamp Watts
06-6VDC
(eg. 09w)
12-12VDC
see lamp
24-24VDC selection chart
120-120VDC
Lamp Type
Options
Q-Quartz
T-Tungsten
SP-Custom
colour
Lamp Selection
6 Volts
Q
T
SB Q
SB T
12 Volts
PAR36 - Large Heads
24 Volts
120 Volts
8W, 10W, 12W
8W, 10W, 12W
12W
-
5.4W, 7.2W, 9W, 18W
5.4W, 9W, 18W
9W, 18W, 25W
15W
8W, 10W, 12W
8W, 12W
55W, 70W
30W, 50W
9W, 18W
18W
N/A
-
Q = Quartz Halogen
T = Tungsten
SB = Sealed Beam
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 318
E2 Specter
6, 12 & 24V remote
Virtually Invisible
Emergency Light
Approvals:
cCULus Certified to CSA
C22.2 #141
EMERGENCY SERIES
318
Description
Suggested Specifications
Stanpro introduces a virtually invisible emergency light luminaire that is easily
recessed inside the wall or ceiling space. Without compromising the aesthetic
appeal of the interior design, Stanpro provides the architectural community
with an innovative solution that meets emergency lighting codes. When AC
power loss occurs, the lens housing simply extends outward from behind the
cover plate. Instantly energized, the dual-lamp light source provides bright,
even illumination along the path of egress. When AC power is restored, the
lamps are extinguished and the lens housing returns to the closed position…
hidden from sight. This essentially vandal proof luminaire is designed for a
wide range of commercial and residential applications. The Stanpro series
luminaire was inspired by the belief that emergency lighting can be both beautiful and functional. Stanpro’s revolutionary design offers easy light adjustments, all with a simple turn of the lens. By directing the light where its needed most, dark areas are minimized, enabling safe egress in residential and
commercial spaces.
Charging Circuitry (when using Stanpro unit equipment)
Central battery unit shall utilize a solid state, fully automatic, voltage
regulated charging system which will maintain the battery at full capacity without the need for periodic exercising or equalization. The following features shall
be standard: Low voltage disconnect (LVD), brownout protection and AC lockout.
The central battery unit shall utilize maintenance free, sealed lead calcium. The
batteries shall provide trouble free operation intemperatures up to 85F (30C).
Illumination
Illumination shall be provided by two internally mounted T-5 style 15 watt Xenon
lamps. When mounted on 24’ centers, at 7’ AFF, the unit shall provide an average of 1.10 footcandles between luminaires from base of wall to 3’ from wall.
Housing
Backbox shall be compatible for mechanical fastening to stud or drywall via
screws and/or hanger bars and be supplied with a knockout pattern to facilitate
mounting and wire connection. Screw covers and dry wall screws shall be provided with each unit.
Dust Covers
To protect the units during installation, all Stanpro luminaires will be supplied
with a protective cover to be removed and discarded prior to final electrical connection.
Features
• Compact, recessed luminaire that blends with wall or ceiling
• Essentially vandal proof for high-abuse areas
• High-impact polycarbonate coverplate and lens
• Coverplate customizable with paint
• Durable, corrosion resistant metal back box
• Adjustable flanges for easy installation in new construction or retrofits (field
selectable)
• Precision lens drive featuring a 30-year rated DC motor
• 2 powerful Xenon lamps with 10,000 hour life
• Innovative optics provide bright, even illumination along the path of Egress
• Available in 12 or 24V input voltage.
• 3 year limited warranty on all units
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
Voltage
Watts
Lamp
E2
Double
Lamp
12-12 volt
9
18
Tungsten
Lamp Selection
12 Volts
T
9W, 18W
T = Tungsten
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
02/2009/19
2:38 PM
Page 319
EMERGENCY SERIES
07- emergency
319
07- emergency
02/2009/19
2:38 PM
Page 320
H series
Decorative
Emergency
Remotes Series
B
5.3125”
(ceiling mount only)
Homologations:
Certification CSA C22.2 #141
5.1250”
Description
A
EMERGENCY SERIES
The H series is a recessed multi-spot remote emergency light which uses powerful MR16 lamps with glass cover. This series is available in single, double,
triple or quadruple lamp versions and is made for use with 6, 12 or 24V emergency lighting systems. The lamps are gimbal mounted for full adjustability and
each lamp can be individually aimed/positioned. Standard finish is matte grey.
Other colours are available, please consult Stanpro for details.
Num. of
lamps
1
2
3
Features
4
Dimensions
A
B
5-1/8” 4-1/2”
9”
8-1/4”
12-7/8” 12”
16”
15-1/4”
The aluminum lampholder(s) are secured in place with the matching
aluminum trim plate. The sturdy, all steel backbox is designed with an integral
electrical connection box for simplified installation. The backbox also features
multiple conduit knockouts and support wire/chain mounting holes. Standard
finish of the backbox is black and standard trim finish is matte grey.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
320
Series
Voltage
Lamp Watts
Lamp Type
Options
H1- Single Head
H2- Double Head
H3- Triple Head
H4- Quadruple Head
06-6VDC
12-12VDC
24-24VDC
(eg. 08w)
see lamp
selection chart
below
Q-Quartz Halogen
GY-Grey
BK-Black
SP-Custom colour
A-120VAC
Lamp Selection
6 Volts
12 Volts
MR16 - Small Heads c/w MR16 Lamp
Q
8W, 10W, 12W,
20W, 35W, 50W
8W, 10W, 12W,
20W, 35W, 50W
24 Volts
12W, 20W,
35W, 50W
Q = Quartz Halogen
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 321
Ceiling Mount
Pendant Mount
V series
2.3750
9.7500”
8.7500”
Vapour Proof Industrial
Emergency Remotes
4.2500”
4.2500”
Approvals:
CSA Certified to C22.2 #141
Wall Mount
The Stanpro V200 series are heavy-duty aluminum die cast remote heads ideal
for industrial or architectural specific applications. The luminaire is CSA listed for
use in wet locations and features a fully gasketed tempered glass lens. Available
with incandescent or compact fluorescent lamps up to 100w, these remotes are
designed for use with 6, 12 , 24 or 120v emergency lighting circuits. Standard
finish is grey, other colours available.
9.7500”
Features
The aluminum die cast housing of each V200 series remote includes a screw-on
cast guard. Lamps are protected behind a fully gasketed tempered glass lens,
supplied standard in clear. Frosted glass is optional. Integral mounting boxes
and/or pendant sockets can be specified with 1/2” or 3/4” NPT tapping. A variety of optional stainless steel shades can be mounted to the luminaires to suit
specific lighting and design requirements. Standard finish of all hardware is a
textured grey powder coat. Other colours are available, contact Stanpro for
details.
4.2500”
Warranty
EMERGENCY SERIES
Description
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
321
—
Series
Mounting
Tapping
Lens
Lamp
Options
V200
(compact)
CM-Ceiling Mount
WM-Wall Mount
PM-Pendant Mount
A-1/2” NPT
B-3/4” NPT
CL-Clear
FR-Frosted
See lamp
selection
guide below
SHS-Straight shade small
AHS-Angled shade small
WGS-Wireguard small
Lamp Selection
6 Volts
Q
12 Volts
PAR18 - Small Heads
8W, 10W, 12W
8W, 10W, 12W
24 Volts
12W
Q = Quartz Halogen
Maximumof two 20W quartz lamps per globe/head.
For 120V and 347V applications maximum 25W A19 lamp.
Compact Fluorescent Lamp
Code
Input Voltage
FLL6712-12V
12V
FLL6713-12V
12V
FLL6712-24V
24V
FLL6713-24V
24V
Wattage
11W
15W
11W
15W
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 322
Replacement Lamps
Order No.
EMERGENCY SERIES
322
Ref. No.
LIT006V3.6WW
909
LIT006V5.4WW
939
LIQ006V006WB
784
LI6006V006WB
H7556
LIT006V006WD
82
LIT006V7.2WW
927
LI6006V7.2WW
S7672
LIQ006V008WB
785
LI6006V008WB
H7551
LIT006V008WD
64
LIM006V008WB
LIT006V009WW
908
LI6006V009WW
S7631
LIQ06V010WB
787
LI6006V010WB
H7552
LIQ006V012WB
786
LI6006V012WW
S4042
LI6006V012WB
H7553
LIT006V012WD
88
LIM006V012WB
LI6006V018WW
S4014
LIT006V018WD
6
LIQ006V020WB
788
LI6006V020WB
H7554
LIM006V020WB
LI6006V025WW
4510
LI6006V030WW
S4515
LIQ012V008WB
774
LI6012V008WB
H7555
LIT012V008WD
90
LIM012V008WB
LIT012V009WW
915
LIT012V010WB
780
LIQ012V012WB
783
LI6012V012WW
S4044
LI6012V012WB
H7557
LIT012V012WD
94
LIM012V012WB
LIQ012V014WB
789
LIT012V14.4WW
917
LIT012V016WD
1005
LIT012V018WW
921
LI6012V018WW
S4414
LIT012V018WD
1142
LIQ012V020WB
782
LIM012V020WB
LIT012V022WD
1076
LIT012V023WD
1176
LI6012V025WW
S4446
LI6012V030WW
S4416
LIQ012V035WB
791
LIQ012V035WBG635
LIM012V035WB
LI6012V035WW
S4413
LIM012V050WB
LIQ012V055WBG635
LIQ012V055WBH3
31397
LIT024V004WD
302
LIT024V005WW
EMS2405W
LIT024V007WD
304
LIT024V009WW
EMS2409W
LIT024V009WD
624
LIT024V012WB
LIT024V012WD
306
LIM024V012WB
Volt
Watts
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
24
24
24
24
24
24
24
24
3.6
5.4
6
6
6
7.2
7.2
8
8
8
8
9
9
10
10
12
12
12
12
12
18
18
20
20
20
25
30
8
8
8
8
9
10
12
12
12
12
12
14
14.4
16
18
18
18
20
20
22
23
25
30
35
35
35
35
50
55
55
4
5
7
9
9
12
12
12
Lamp Type
Wedge Base
Wedge Base
Bi-Pin Halogen
Halogen Sealed Beam
Double Contact Bayonet
Wedge Base
PAR36 Sealed Beam
Bi-Pin Halogen
Halogen Sealed Beam
Double Contact Bayonet
MR16 Halogen
Wedge Base
PAR36 Sealed Beam
Bi-Pin Halogen
Sealed Beam Halogen
Bi-Pin Halogen
PAR36 Sealed Beam
Halogen Sealed Beam
Double Contact Bayonet
MR16 Halogen
PAR36 Sealed Beam
Double Contact Bayonet
Bi-Pin Halogen
Halogen Sealed Beam
MR16 Halogen
PAR36 Sealed Beam
PAR36 Sealed Beam
Bi-Pin Halogen
Halogen Sealed Beam
Double Contact Bayonet
MR16 Halogen
Wedge Base
Bi-Pin Halogen
Bi-Pin Halogen
PAR36 Sealed Beam
Sealed Beam Halogen
Double Contact Bayonet
MR16 Halogen
Bi-Pin Halogen
Wedge Base
Double Contact Bayonet
Wedge Base
PAR36 Sealed Beam
Double Contact Bayonet
Bi-Pin Halogen
MR16 Halogen
Double Contact Bayonet
Double Contact Bayonet
PAR36 Sealed Beam
PAR36 Sealed Beam
Bi-Pin Halogen
G6.35 Bi-Pin Halogen
MR16 Halogen
PAR36 Sealed Beam
MR16 Halogen
G6.35 Bi-Pin Halogen
H3 Bi-Pin Halogen
Double Contact Bayonet
Wedge Base
Double Contact Bayonet
Wedge Base
Double Contact Bayonet
Bi-Pin Halogen
Double Contact Bayonet
MR16 Halogen
Lumens
Beam CP
48
72
113
107
90
101
101
155
155
165
180
240
40
400
350
350
350
550
550
555
150
132
201
201
302
177
302
240
400
400
650
650
850
1100
850
855
243
245
457
457
1500
1505
1400
1400
385
155
155
80
800
55000
550
550
600
138
360
277
182
277
280
850
1100
850
853
302
1050
210
260
245
264
461
1440
975
1500
485
155
395
1500
2100
400
35000
395
1100
55
310
99
355
132
400
210
1100
1400
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 323
Replacement Lamps
Order No.
Ref. No.
Volt
Watts
24
24
24
24
24
24
24
24
24
18
20
20
24
35
35
50
55
70
LIT024V018WW
EMS2218W
LIQ024V020WB
JC24V20W
LIM024V020WB
LIT024V024WD
310
LIQ024V035WBG635
LIM024V035WB
LIM024V050WB
LIM024V055WBG635
LIM024V070WBH3
39707
Lamp Type
Lumens
Beam CP
402
855
Wedge Base
Bi-Pin Halogen
MR16 Halogen
Double Contact Bayonet
G6.35 Bi-Pin Halogen
MR16 Halogen
MR16 Halogen
G6.35 Bi-Pin Halogen
H3 Bi-Pin Halogen
Exit sign lamps
Order No.
LIT120V020WD
LIT120V020WI
LIT145V025WD
LIT145V015WCT6
Ref. No.
Volt
Watts
2218
2215
2058
2055B
120
120
145
145
20
20
25
15
Lamp Type
Double Contact Bayonet
Intermediate Screw Base
Double Contact Bayonet
T6 Mini Candelabra
120V Compact fluorescent lamps
FLL6712-12V
FLL6713-12V
FLL6712-24V
FLL6713-24V
Voltage Drop Tables
6 Volts Maximum Voltage Drop 5% per Canadian Electrical Code (Wiring Distance in Feet)
Wire
Size 4
#12 111
#10 177
#8 281
#6 447
6
89
141
225
358
8
67
106
169
268
10
53
85
135
215
12
45
71
113
179
13
41
65
110
165
16
33
53
84
134
18
30
47
75
120
20
27
42
68
107
Watts
24
22
35
56
89
25
21
32
54
86
28
19
30
48
77
35
15
24
39
62
44
12
19
31
49
50
11
17
27
43
75
8
11
18
29
100
6
9
14
22
150
4
6
9
15
200 250
7
11
9
EMERGENCY SERIES
Order No.
12 Volts Maximum Voltage Drop 5% per Canadian Electrical Code (Wiring Distance in Feet)
Wire
Size
4
8
#12 534 267
#10 849 425
#8 1351 675
#6 2148 1073
12
178
283
450
716
13
165
260
415
660
16
134
212
338
537
18
110
190
300
475
24
89
142
225
358
25
85
136
215
340
Watts
28
76
121
193
307
35
61
97
154
245
44
49
77
123
195
50
42
68
108
170
75
29
45
72
114
100
21
34
54
86
150
14
23
36
57
200
10
17
27
43
250
8
14
21
34
300
11
18
28
24 Volts Maximum Voltage Drop 5% per Canadian Electrical Code (Wiring Distance in Feet)
Wire
Size
#12
#10
#8
#6
13
660
1040
1668
2640
18
440
760
1200
1900
25
340
544
860
1360
28
305
485
772
1227
35
244
388
616
980
44
194
309
491
781
Watts
50
168
272
432
680
75
116
180
288
456
100
84
136
216
344
150
56
92
144
228
200
40
68
108
172
250
32
52
84
136
300
26
44
72
112
400
21
34
54
85
32 Volts Maximum Voltage Drop 5% per Canadian Electrical Code (Wiring Distance in Feet)
Wire
Size
#12
#10
#8
#6
13
1170
CM =
L
18
840
1340
22 x W x L
0.05 x E2
= CM x 0.05 x E2
22 x W
25
600
960
1540
44
345
549
873
1388
Watts
50
300
480
770
1220
28
543
863
1372
2180
35
435
690
1100
1740
75
200
320
510
815
100
150
240
385
610
CM =
W =
L
=
E
=
22 =
0.05 =
Wire size in circular mils
Emergency load in watts
Length of circuit in feet
Line voltage
Constant
Factor for maximum allowable voltage drop
150
100
160
255
405
AWG
12
10
8
6
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
200
75
120
192
305
250
60
86
154
240
300
50
80
128
200
Circular Mill Chart
AMP Capacity
C/M
20
6,530
25
10,380
30
16,510
50
26,250
400
42
63
100
163
323
07- emergency
02/2009/19
2:38 PM
Page 324
SLRET
0.8125”
Exit Sign Retrofit Kit
0.8750”
11.2500”
Approvals:
CSA Certified to C22.2 #141
EMERGENCY SERIES
Description
Circuitry
The SLRET from Stanpro is a complete exit sign retrofit solution. Providing substantial savings over traditional incandescent lamps, the LED technology
employed in the SLRET series operates at just 1.1 watts AC. Also, unlike incandescent lamps that burn out frequently, the SLRET is designed using long-life
LEDs with a 20 year life expectancy. The series is available with quick connect
lamp bases in candelabra, intermediate, D.C. bayonet or medium type bases.
Hardwired assemblies are also available.
The SLRET is constructed with a high-impact, UV stabilized thermoplastic
sleeve/housing. The LED circuit board is designed to slide into the sleeve providing a secure and electrically insulated mounting. Long-life, high-adhesion double sided tape provides a simplified mounting in any type of exit sign. Power is
filtered to the LED circuit board via a sealed capacitor assembly. The assemblies
can be supplied with a variety of quick connect bases in 120VAC or can be supplied for hardwire installations in 120/347VAC dual selectable input.
Features
Warranty
The SLRET utilizes long-life, ultra-bright LEDs. The LEDs have a 20 year lifeexpectancy and are completely maintenance free. The LED technology is also
unaffected by extreme temperatures or vibration. Larger 8mm red LEDs are
arranged linearly to provide crisp, even light. The linear arrangement eliminates
“hot spots” typically seen with LED bulb/lamp type retrofits.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Series
324
SLRET
Base Type
C-Candelabra- 120V only
I-Intermediate- 120V only
D-D.C. Bayonet- 120V only
M-Medium- 120V only
HW-Hardwire- 120/347V dual selectable
Options
UB-Ultra bright LEDs
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 325
LED
Exit Sign Lamp
Replacement Kit
Description
Features
The Stanpro LED exit sign lamp replacement kit provides exceptional energy and
maintenance savings over traditional incandescent type lamps. Each LED lamp
consumes just 1.1 watts of AC power and are designed utilizing long-life maintenance-free LEDs. The twenty-six high brightness LEDs are arranged in a “U”
shape in order to optimize the light distribution. The thin-line LED housing is
made from an advanced technopolymer that can be rotated to align with the
face-plate of the exit sign.
The exit sign LED lamp replacement kit is designed for use in exit signs utilizing
120 volt AC circuits. Light output is provided by 26 high brightness individual
LEDs arranged in a “U” shape. Integral current limiting and surge absorbing
capacitors insure flicker free, long-life operation. The technopolymer housing is
available with three bases: candelabra, intermediate and D.C. bayonet.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
—
Series
Order/Type Code
Base Type
LED
120V 1.1W
(120 volt AC input,
1.1 watt AC consumption)
U-Universal
EMERGENCY SERIES
Approvals:
CSA Certified to C22.2 #141
325
Energy Savings
Existing Lamp
15T6CC/145V
15T6NC/145V
25T6.5NC/145V
25T6.5DC/145V
(15W)
(15W)
(25W)
(25W)
Replacement Lamp
LED120V 1.1W - C
LED120V 1.1W - I
LED120V 1.1W - C
LED120V 1.1W - D
Watts Saved
-13.8W
-13.8W
-23.8W
-23.8W
*Annual Saving
per Lamp ($0.065/kwh)
$7.87
$7.87
$13.57
$13.57
% Saving
92%
92%
95%
95%
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 326
Wire Guards
Description
Length
Length
Width
Width
The Stanpro series of steel wire guards are designed to protect valuable emergency lighting equipment from damage and abuse. The welded steel construction provides an exceptional rigid cage and the integrated mounting loops ensure
a reliable installation. Standard finish is white baked powder coat finish. Custom
colours are available, please contact your Stanpro representative for details.
Depth
Depth
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Model
L
EMERGENCY SERIES
326
WGD510
WGD520
WGD540
WGD550
WGD560
WGD590
WGD600
WGD620
WGD630
WGD650
WGD660
17.25”
14.00”
14.50”
8.50”
25.50”
15.25”
20.25”
8.50”
12.00”
13.75”
29.50”
Dimension
x
W
x
x
x
x
x
x
x
x
x
x
x
x
17.25”
10.00”
6.25”
6.00”
8.50”
14.25”
17.25”
6.00”
9.00”
12.25”
8.50”
x
x
x
x
x
x
x
x
x
x
x
Application
D
7.00”
4.75”
10.50”
7.00”
8.00”
6.75”
8.50”
8.50”
9.00”
16.50”
10.00”
battery units 144W to 200W
battery units 18W to 72W; wall mount SLEXSC & SLEXXC
ceiling mount SLEXSC & SLEXXC
N1, N2, M1, M2, S1 and S2 remotes
wall mount SLSRSC & SLSRXC
battery units 80W to 100W; wall mount SPEXSC & SPEXXC
battery units 250W to 720W
L1, R1 & P1 remotes
L2, R2 & P2 remotes
end mount SLEXSC & SLEXXC; ceiling or end mount SPEXSC & SPEXXC
ceiling or wall mount SLESSC, SLSESC, SLESXC & SLSEXC
Mounting Shelves
Description
Warranty
The Stanpro series of steel mounting shelves provide a stable and durable platform for the installation of emergency lighting units. The shelves are made with
heavy gauge steel and finished standard with a white baked powder coat finish.
Custom colours are available, please contact your Stanpro representative for
details.
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
MS2- SLC series battery unit (200W and under)
MS1 - SLB series battery unit
10.5000”
9.0000”
10.1250”
9.0000”
10.6250”
14.0000”
3.87500”
MS3- SLC series battery unit (over 200W)
MS4- SLD series battery unit
15.0000”
10.5000”
10.1250”
10.1250”
14.0000”
5.0000”
9.0000”
18.5000”
9.0000”
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 327
BI
Fluorescent Inverter
Series
Cat. No
BI1400
BI0700
BI0600
BI0750
BI0450
Description
Features
The BI Fluorescent emergency ballast works in conjunction with an AC ballast to
convert new or existing fluorescent luminaires into emergency lighting. The
emergency ballast consists of a high-temperature nickel-cadmium battery,
charger and electronic circuitry in one compact case. Select from one of our BI
product categories as these can be used in most 12-215w (2’-8’) T8, T9, T10 or
T12 fluorescent lamps without integral starters, including U shaped, HO, VHO circline, energy saving and (4 pin) twin, quad and triple twin tube compacts. One
or two lamp operation may be selected. It is also compatible with most one-,
two-,three- and four-lamp electronic, standard, energy saving and dimming AC
ballasts. If used in an emergency-only luminaire, no AC ballast is necessary. The
BI is suitable for use in indoor applications. It is not suitable for air handling heated air outlets or wet, damp or harzadous locations.
• Self-contained in one housing for easy installation and maximum mounting
flexibility
• Can be wired to operate with switched, unswitched and normally off luminaires
• Fully compatible with energy saving and electronic dimmable ballasts
• Either 1 or 2 lamp operation
• Maintenance free nickel cadmium battery
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering Guide
Model cat no
Input voltage
Operating Time
Lumens
BI1400
blank 120/347v
90 minutes
1100-1400
BI0700
blank 120/347v
90 minutes
600-700
BI0600
blank 120/347v
90 minutes
500-600
BI0750
blank 120/347v
90 minutes
300-750
BI0450
blank 120/347v
90 minutes
350-450
Factory Recommended
Description
1X 17-2 15W (2’ to 8’) or 2X 17 to 40W
(2’ to 4’) T8, T9, T10 & T12 or (4 pin) long
compact fluorescent.
1X 17-215W (2’ to 8’) or 2X 17 to 40W
(2’ to 4’) T8, T9, & T12 or (4 pin) long
compact fluorescent.
1X 17 to 40W (2’ to 4’) T8, T9, T10 & T12
or (4 pin) long compact fluorescent.
1X 6 to 42W or 2x 6 to 39W (4 pin) twin, quad,
triple, quadruple, twin tube or long compact
fluorescent.
1X 20 to 40W (2’ to 4’) T8, T10 & T12
or (4 pin) compact fluorescent.
Factory Recommended
BI1400
BI0750
LAMP
LUMENS
1 LAMP 2 LAMPS
FO25, FBO24 T8
FO32, FBO31 T8
FO96 T8
FO17, FBO16
F40T12, F40/U
F48T12/HO
1250
1350
1400
1050
1100
1200
F96T12, HO, VHO
F39BX, PL36, DULUX L 39W
4-PIN 28W 2D
4-PIN 38W 2D
F27BX, PL24, DULUX L 27W
F40T12/ES (34W)
PL40, F40BX, F50BX, DULUX L 55W
1100
1100
1100
1000*
Partial listing of lamps operated.
* indicates light output lower than 1100 lumens.
975*
900*
1100
1350
950*
1100
1100
1100
1100
1000*
975*
LAMP TYPE (4-PIN)
LUMENS
1 LAMP 2 LAMPS
PL-T 42 W/4P, DULUX T/E 42 W
PL-T 32 W/4P, DULUX T/E 32 W
750
575
PL-T 26 W/4P, DULUX T/E 26 W, F26TBX/4P
PL-T 18 W/4P, DULUX T/E 18 W, F18TBX/4P
PL-C 26 W/4P, DULUX D/E 26 W, F26DBX/4P
PL-C 18 W/4P, DULUX D/E 18 W, F18DBX/4P
PL-C 13 W/4P, DULUX D/E 13 W, F13DBX/4P
PL-L 40 W, DULUX L 40 W, F40/30BX/4P
PL-L 36 W, DULUX L 39 W, F39/36BX/4P
450
300
600
475
350
650
575
750
PL-L 24 W, DULUX L 27 W, F27/24BX/4P
PL-L 18 W, DULUX L 18 W, F18 BX
F382D/4F
FO26, FBO24 T8
475
300
525
625
550
400
650
700
FQL 28
FO17, FBO16 T8
600
425
700
500
750
725
525
700
575
425
Partial listing of lamps operated.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
EMERGENCY SERIES
Approvals:
CSA Certified to C22.2 #141
327
07- emergency
02/2009/19
2:38 PM
Page 328
CENTRAL
INVERTER
SYSTEM
UL924
CCMC
BMEC
UL1778
38.0
33.0
BATTERY CABINETS
"S" Cabinet = 17"W x 21"D x 7"H
"M" Cabinet = 22"W x 32"D x 44"H
"L" Cabinet = 33"W x 36"D x 52"H
"B2B" Cabinet = 15"W x 33"D x 22.4"H
"C" Cabinet = 22"W x 33"D x 44"H
"H" Cabinet = 34"W x 38"D x 53"H
EMERGENCY SERIES
• "No break" power
• Pulse width modulated (PWM) technology
• 100% load compatibility
• Maximized reliability
• Reduced maintenance expense
• Enhanced security
• Improved building aesthetics
• Minimized space requirements
• Communication capability
• Variety of input & output voltages
• Scalable runtimes
• Modular design
Reduced Maintenance
The STANPRO Central Inverter system encompasses a single inverter unit
installed in a centralized location. This greatly simplifies maintenance, testing
and service. The included System Power Analyzer incorporates a suite of diagnostic functions, including auto battery testing at user defined intervals. Should
the analyzer detect an element of the system that has exceeded the design
parameters, programmed alarm functions automatically indicate and identify the
component requiring service.
Tested to the most current and stringent requirements, the STANPRO Central
Inverter is listed to CCMC for 30 minutes, UL 924 for 90 minutes and UL UPS
1778 standards. STANPRO Central Inverter's advanced design technology meets
the demands of the "real world". The STANPRO Central Inverter is designed with
a 100,000 hours MTBF for the entire system and 200,000 hours MTBF for the
primary transformer. Combined with the included System Power Analyzer diagnostic, the STANPRO Central Inverter will deliver trouble-free operation.
BATTERY CABINET
INVERTER CABINETS
Centrally located in a utility area, STANPRO Central Inverter is secure and safe.
Traditional solutions for life safety egress lighting include unit equipment on
walls or ceilings. This approach detracts from interior design aesthetics. The
STANPRO Central Inverter supplies power to existing lighting luminaires, elimina-ting the need for special emergency lighting luminaires.
53.0
INVERTER CABINET
Features
Aesthetics
34.0
52.0
Security
Enhanced Reliability
328
36.0
PWM Technology
Pulse width modulated (PWM) inverter control is designed to produce the output
wave form by switching battery current at a high switching response time, many
compatibility problems with loads such as power factor-corrected ballasts, HID
lighting and microprocessor-controlled equipment are eliminated.
PWM Design Advantages: High efficiency
Lower operating cost
Smaller design
Quiet operation
Improved reliability
Wider load compatibility
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 329
CENTRAL
INVERTER
SYSTEM
System Features
System Operation
• True "no-break" power to loads
• Digitally generated sine wave output
• Low input current distortion
• 90% efficiency on line
• Up to 125% for ten minutes overload capacity
• Surge and transient protection: 150% of rated output without need of
static bypass
• Inverter load versatility – lighting (including fluorescent, incandescent,
HID luminaires with self-ballasted lamps, electronic or power-factor corrected
ballasts), fire, security, communication systems and other critical loads.
• Microprocessor control allows for automatic self-diagnostic operation
(standard) to warn of potential problems
• Standard 30 minute battery runtime – Extended runtimes as specified
• Load flexibility and reliability – use of a building's existing lighting elements
for emergency reduces the likelihood of unknown lamp failure
• No additional backup systems to maintain or test
• Intelligent,easy-to-use system
• Display panel monitors and controls all parameters
• One-year electronics warranty
• Batteries carry additional pro-rata warranty
• The incoming AC utility voltage is split and fed to the battery charger (to
maintain the batteries at full charge) and also to the output power controller
• Microprocessor controlled pulse width modulated inverter transforms
the power supply into low-distortion, clean sine wave AC voltage to supply the
connected load
• On AC utility voltage failure the inverter transforms the DC battery power
into the same low-distortion, clean sine wave AC voltage to supply the
connected load.
Voltage Regulation
STANPRO Central Inverters voltage regulation protects your loads from
"brownouts" and recurrent low-voltage transients by sensing any drop in voltage and regulating the voltage back up to nominal. Regulation is accomplished
without switching to or relying on the batteries and thereby shortening battery life
expectancy.
Batteries
STANPRO Central Inverters are designed to utilize a maintenance free, valve regulated, gas recombinant, suspended electrolyte batteries with no gel contaminant. The batteries are individually contained within shock absorbent, thick wall
polypropylene cases. The entire battery set is factory pre-tested and pre-packaged with the system to ensure smooth start-up. External battery cabinets come
complete with a fused disconnect for additional safety.
Extended Runtimes
The standard STANPRO Central Inverters are rated to provide 30 minutes of
emergency power (UP-AC30). Extended runtimes (as required) may be specified
as outlined in the Ordering Information section.
Interruption-free Power
STANPRO Central Inverter provides continuous power to all of the connected load
including any life safety or other secondary systems.The no-break switching
between regular utility AC and battery-to-inverter power means that all
connected equipment will continue to operate normally under emergency conditions.
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
VOLTAGE REGULATION
INPUT
POWER PURIFICATION
OUTPUT
EMERGENCY SERIES
System Operation
INPUT
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
OUTPUT
329
07- emergency
02/2009/19
2:38 PM
Page 330
CENTRAL
INVERTER
SYSTEM
Electrical Specifications
EMERGENCY SERIES
Input:
Battery
•
•
•
•
•
•
• Recharge time: 24 hours. Meets UL 924 & CCMC requirements
• Standard battery: Sealed, maintenance free, gas recombinant, self
venting, suspended electrolyte with no gel contaminant
• Bus Voltage: Float 2.27 VPC, final 1.75 VPC. Factory tested with
specific inverter before shipping
• Runtimes: 30 minutes standard. Other runtimes available as specified
• Operating temperature: 0ºC to 40ºC (32ºF to 104ºF)
• Relative humidity: 95% non-condensing
Note
Battery performance: Batteries will deliver 30 minutes of run-time between
18ºC – 40ºC. Battery's life of 15 years is rated at 18ºC.
Input voltage: 120, 208, 240, 277, 347 or 600 VAC
Input Frequency: Capture 57.5 Hz to 62.5 Hz.
Operating Range: + 10% to – 15%
Power factor: Self correcting to >0.95 (approaching unity)
Input Harmonics: < 5% THD (total harmonic distortion)
Spike Attenuation: 3000:1, exceeds ANSI/IEE C62.41 cat.B3 waveform
Output:
• Output voltage: 120, 120/208, 120/240, 277, 347 or 600 VAC
Other voltages available upon request
• Sine Wave Voltage: Maximum 3% harmonic distortion, any single
harmonic.
• Crest Factor: 3.0:1
• K Factor: 30 or better
• Power Factor: Unity rated
• Harmonic Attenuation: Reflected load generated harmonics are
attenuated 23dB at the input.
• Line Regulation: Typically better than +3%
• Load Regulation: Typically better than +3%
• Time to transfer to inverter after a utility power failure: No break
Warranty
330
The system is guaranteed against defects in workmanship and materials for a
period of one year from star-up, under normal and proper use. Batteries supplied
with the system are covered under a separate pro-rata warranty as described
below. Warranty of the system commences on the start-up date.
Batteries – One (1) year complete replacement
Plus pro-rata period
Pro-Rata period – Lead – Calcium – 14 years
Capacity
Rating
(kVA)
021 = 2.1Kva
029 = 2.9Kva
036 = 3.6Kva
043= 4.3Kva
050= 5.0Kva
075 = 7.5Kva
080 = 8.0kVA
090 = 9.0kVA
105 = 10.5kVA
115 = 11.5kVA
130 = 13.0kVA
140 = 14.0kVA
160 = 16.0kVA
170 = 17.0kVA
180= 18.0kVA
200 = 20.0kVA
Inverter
Cabinet
(INV)
S
S
S
S
S
M
M
M
M
M
M
L
L
L
L
L
Battery
Cabinet
(BAT-30 min.)
B2B
B2B
B2B
C
C
C
C
C
C
C
C
INTERNAL
H
H
H
H
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 331
CENTRAL
INVERTER
SYSTEM
How to order
The optional System Power Analyzer is a user friendly, precision, metering and data acquisition system. It provides true RMS metering, power analysis and display
of all electrical parameters of the STANPRO Inverter. An intuitive touch panel and LCD display allows maintenance personnel to easily retrieve alarm messages, operating status and logged events.
Metered Parameters:
Log Functions:
Alarm Messages:
AC Input Voltage
Number of outages
Number of alarms
AC Output Voltage L1-N
Time and date of occurances
Output overloads
AC Output Voltage L1-L2
Elapsed days
Output under voltage
AC Output Current L1
Inverter hours
Low battery voltage
Ac Output Current L2
Cleared logs
Transformer high temp.
Percent Load
Automatic battery test
Frequency fault
Crest Factor L1
- Programmable auto battery test
Heat sink high temp.
Crest Factor L2
- Proprietary manual test
DC battery charger fail
DC Charging Voltage
- Select alarm
Alarm silence
DC Charging Current
SPA (System power analyzer)
Battery Bus Voltage
GA (General alarm)
Output Frequency
Back-Up Time Remaining
Time/Date
pf = kW/kVA
Load kW
EMERGENCY SERIES
System Power Analyzer
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please see our terms and conditions.
331
Ordering Guide
Series +
Run Time
(in mins.)
Input
Voltage
(VAC)
Capacity
Rating
(kVA)
Output
Voltage
(VAC)
Optional Output
Circuit Breakers
(Amps)
Quantity
Output
Breakers
Options
SNV-30
(30 mins.)
SNV-60
(60 mins.)
SNV-120
(120 mins.)
120
208
240
277
347
600
021 = 2.1kVA
029 = 2.9kVA
036 = 3.6kVA
043 = 4.3kVA
050 = 5.0kVA
075 = 7.5kVA
080 = 8.0kVA
090 = 9.0kVA
105 = 10.5kVA
115 = 11.5kVA
130 = 13.0kVA
140 = 14.0kVA
160 = 16.0kVA
170 = 17.0kVA
180= 18.0kVA
200 = 20.0kVA
120
120/208
120/240
277
347
600
120/347
Normally On
ON15A
ON20A
ON25A
ON30A
ON35A
ON40A
Normally Off
OFF15A
OFF20A
OFF25A
OFF30A
OFF35A
OFF40A
01 (One)
02 (Two)
03 (Three)
04 (Four)
05 (Five)
Internal MBS
(maintenance bypass switch)
RAP (Remote annunciator panel)
AMD (Automatic message dialer)
SGS (Sprinkler guard shield)
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 332
L
D
SLZC
Zone sensing
control pannel
H
For cabinet dimensions see the ordering guide
Description
EMERGENCY SERIES
The SLZC series zone sensing controls are designed to be either
integral inside the battery unit or external outside the battery unit and
to automatically trigger emergency lighting operation in conjunction
with local/zone normal lighting circuit failure. The SLZC panel is
installed with zone monitoring circuits connected to regular, localized
lighting circuits. Should one of these circuits loose power, the SLZC
panel will cause the emergency lighting unit to supply power to the
luminaires it supports. The localized area where the power failed is
now illuminated by emergency lighting. Without the SLZC panel, this
area would be exposed to the potential dangers of total darkness.
Code requirement
The requirement for zone sensing controls originates from the applicable sections of both the Building and Electrical codes. Both of
these documents refer to the automatic actuation of emergency
lighting in the “area” where the normal lighting has failed.
NATIONAL BUILDING CODE OF CANADA - 1995:
9.9.11. Lighting
9.9.11.3. Emergency Lighting
...3) Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min. when the electric lighting in the affected area is interrupted.
CANADIAN ELECTRICAL CODE:
Section 46 - Emergency Systems, Unit Equipment,
and Exit Signs
46-304 Supply Connections
…4) Unit equipment shall be installed in such a manner that it will be
automatically actuated upon failure of the power supply to the
normal lighting in the area covered by that unit equipment.
Features
• 20 Gauge steel construction
• Universal spider knockout pattern and keyhole mounting slots
stamped into back of cabinet
• Multiple conduit entry knockouts
• White powder coat finish standard, other finishes and colours
optional
• Heavy duty, large gauge terminal blocks for all wiring
connections
Electrical
• Various monitoring voltages available
• Unlimited number of monitored zones/circuits can be
specified (consult Stanpro for details)
• Optional zone testing/disconnect switch available (single switch
per zone)
Warranty
As always, Stanpro is Focused on Quality. For complete warranty details, please
see our terms and conditions.
Ordering guide
332
Series
SLZCIBU
(integral
inside
battery
unti)
DC
Voltage
DC
Wattage
Zone Monitoring
Voltage
# of Monitored Circuits / Zones
Options
12V
160
200
250
360
A - 120V
1 - N/A
2 - d cabinet 18.0"L x 10.12" H x 8.52'' D
3 - d cabinet 18.0"L x 10.12" H x 8.52'' D
4 - d cabinet 18.0"L x 10.12" H x 8.52'' D
5 - h cabinet 20'' L x 16'' H x 8'' D
6 - h cabinet 20'' L x 16'' H x 8'' D
7 - h cabinet 20'' L x 16'' H x 8'' D
8 - h cabinet 20'' L x 16'' H x 8'' D
9 - h cabinet 20'' L x 16'' H x 8'' D
10 - h cabinet 20'' L x 16'' H x 8'' D
BD - Battery disconnect
ZTS - zone test switch
ZPL - zone pilot light
LC - 120V line cord
TLP347 - 347V twist lock plug c/w cord
AT - Auto test
TD - Time delay
WPC - Weather-Proof Cabinet
(EEMAC 4) available on H cabinets only
LD - Lamp disconnect
ACTB - AC terminal block
24V
144
200
320
550
720
12V
160
200
250
360
H- 347V
1
2
3
4
5
6
24V
144
200
320
550
720
-
N/A
d cabinet 18.0"L x 10.12" H x 8.52'' D
h cabinet 20'' L x 16'' H x 8'' D
h cabinet 20'' L x 16'' H x 8'' D
h cabinet 20'' L x 16'' H x 8'' D
h cabinet 20'' L x 16'' H x 8'' D
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
07- emergency
02/2009/19
2:38 PM
Page 333
ZONE SENSING CONTROL PANEL
Typical Emergency Lighting Installation: Residential Building, 4 Stories plus Basement
NOT CODE COMPLIANT • CODE COMPLIANT WITH SLZC SERIES ZONE SENSING
C860
1) A power failure of a lighting circuit or panel on a particular given
floor will result in a failure of the regular lighting on that floor only.
2) Since the emergency lighting unit is supplied power from a different circuit (in the basement) it will not be activated and not illuminate the connected remote luminaires.
3) RESULT : Darkness on the affected floor(s).
Ordering guide
Series
Zone Monitoring
Voltage
SLZCEBU A - 120v
H - 347v
1) A power failure of a lighting circuit or panel on a particular given
floor will result in a failure of the regular lighting on that floor only.
2) The zone sensing circuit connected to that lighting panel or circuit
senses the failure and triggers the emergency lighting unit to provide power to the connected luminaires.
3) RESULT : Automatically actuating emergency lighting illuminates
the affected zone/floor.
# of Monitored Circuits / Zones
1 - N/A
2 - b cabinet 10.0"L x 9.0" H x 3.3'' D
3 - b cabinet 10.0"L x 9.0" H x 3.3'' D
4 - b cabinet 10.0"L x 9.0" H x 3.3'' D
5 - c cabinet 12.9"L x 10.12" H x 8.52'' D
6 - c cabinet 12.9"L x 10.12" H x 8.52'' D
7 - c cabinet 12.9"L x 10.12" H x 8.52'' D
8 - c cabinet 12.9"L x 10.12" H x 8.52'' D
9 - c cabinet 12.9"L x 10.12" H x 8.52'' D
10 - c cabinet 12.9"L x 10.12" H x 8.52'' D
11 - d cabinet 18.0"L x 10.12" H x 8.52'' D
12 - d cabinet 18.0"L x 10.12" H x 8.52'' D
13 - d cabinet 18.0"L x 10.12" H x 8.52'' D
14 - d cabinet 18.0"L x 10.12" H x 8.52'' D
15 - d cabinet 18.0"L x 10.12" H x 8.52'' D
16 - d cabinet 18.0"L x 10.12" H x 8.52'' D
17 - d cabinet 18.0"L x 10.12" H x 8.52'' D
18 - d cabinet 18.0"L x 10.12" H x 8.52'' D
19 - d cabinet 18.0"L x 10.12" H x 8.52'' D
20 - d cabinet 18.0"L x 10.12" H x 8.52'' D
Relay control
output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1 - N/A
2 - b cabinet 12.9"L x 10.12" H x 8.52'' D
3 - c cabinet 12.9"L x 10.12" H x 8.52'' D
4 - c cabinet 12.9"L x 10.12" H x 8.52'' D
5 - c cabinet 12.9"L x 10.12" H x 8.52'' D
6 - c cabinet 12.9"L x 10.12" H x 8.52'' D
7 - d cabinet 18.0"L x 10.12" H x 8.52'' D
8 - d cabinet 18.0"L x 10.12" H x 8.52'' D
9 - d cabinet 18.0"L x 10.12" H x 8.52'' D
10 - d cabinet 18.0"L x 10.12" H x 8.52'' D
11 - d cabinet 18.0"L x 10.12" H x 8.52'' D
12 - d cabinet 18.0"L x 10.12" H x 8.52'' D
13 - d cabinet 18.0"L x 10.12" H x 8.52'' D
14 - d cabinet 18.0"L x 10.12" H x 8.52'' D
15 - d cabinet 18.0"L x 10.12" H x 8.52'' D
16 - d cabinet 18.0"L x 10.12" H x 8.52'' D
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
EMERGENCY SERIES
Approved
Options
ZTS - zone test switch
ZPL - zone pilot light
WPC - Weather-Proof
Cabinet (EEMAC 4)
available on H cabinets only
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
333
07- emergency
02/2009/19
2:38 PM
Page 334
Options descriptions
EMERGENCY SERIES
334
AT
Auto-test self diagnostics
120VDC Emergency backup 120VDC LED - DC only sign
12V
Emergency backup 12VDC
220/50
220 VAC, 50Hz input
24V
Emergency backup 24VDC
6V
Emergency backup 6VDC
AZ
Anodized aluminum
BD
Battery Disconnect
BK
Black
BO
Black out
CG
Green letters on clear background (single face only)
CM
Ceiling mount - heads mounted on side of unit
CPS
Constant power supply
CT
Cabtire DC output
CR
Red letters on clear background (single face only)
DL
Damp location rated
EM
End mount - heads mounted on top of unit
FD1 to FD6 Circuit internally fused distribution panel used for large remote applications
FP12B
12’’ Pendant mount kit - black
FP12W
12’’ Pendant mount kit - white
G
Green lettering
H
347 VAC input (contact factory for availability)
HVC
Heavy-duty full width ceiling mount canopy
HVE
Heavy-duty full width end mount canopy
IB
90 minute internally self-powered
IB2
180 minute internally self-powered
IT
Infrared test receiver
K5
1/2’’ knockout for pendant mount
LC
120V line cord
LD
Lamp disconnect
LG
Lexan guard
LT
Remote laser test sensor (consult factory)
LTP
Laser test pen
MG
Green letters on mirrored background
MIP
Mini inverter
MR
Red letters on mirrored background
MC
Metal canopy
NDC
AC only (no DC)
NF
No face plate
OP
Special wording or graphic - see special wording page
P
Suspension 12’’
PG
Polycarbonate guard (consult factory)
PM
12’’ Pendant mount kit
RW
Recessed wall mount
SP
Custom colours available upon request
SMH
Side mount head
TFC
Teflon coated lenses
TPX
Vandal resist screws torx
TPB
Vandal resistant screw bit
UB
Ultra-bright LED’s - 3.9W 120/347VAC dual input voltage
Vandal resistant wraparound polycarbonate shield (specify mounting)
VS
WE
Wire entry holes complete with liquid tight connectors
WG
Green letters on white background
WG
Wireguard
WM
Wall mount - no canopy (single face only)
WO
White out
WR
Red letters on white background
VSR
Zone sensing
OBM
Octagon Box Mount
Universal keyhole mounting pattern stamped into the back of the
unit as well as conduit knockouts. Line cord not supplied.
TD
Time Delay
Time delay option leaves the backup lights illuminated for up to
10 to 15 minutes after the AC power is restored. Brownout conditions, complete power failure or manual testing activates the
time delay.
TP
Tamper Proof
Tamper proof screws avoid unauthorized entry to the battery cabinet. Special tamper proof bits are required to open and close the
cabinet. (Bit sold separately. Specify "TPB" and the quantity
required.)
LD
Lamp Disconnect
A switch used to disconnect the lamp load during extended
power outages once the building has been cleared or for maintainence purposes. When re-entering the area, the switch should
be turned back on to reconnect the lamp heads. Lamps will
remain on until the battery reaches low voltage disconnect level
or AC power is restored.
RFS
Radio Frequency Suppression
A capacitor based voltage noise suppression module wired in
conjunction with the input voltage.
TLP
Twist Lock Plug
NEMA configuration twist lock plug and 3' cab tire standard. 120V
uses a type L15L NEMA configuration, and 347V uses type L2420 NEMA configuration. For other requirements, please contact
your Stanpro representative.
ACTB AC Voltage Terminal Block
AC input terminal block for direct hard wire installation.
DCTB DC Voltage Terminal Block
DC input terminal block for direct hard wire installation.
A
Ammeter
An Ammeter is an analog meter which displays the current going
to the battery during normal AC charge conditions.
V
Voltmeter
A Voltmeter is an analog meter which displays the voltage being
delivered to the battery during normal AC charge conditions, as
well as the voltage capacity of the battery during power failure
(DC mode).
CT
Cab Tire
16/3 SOW Cab tire supplied for installations where a line cord is
required and the unit will not be directly mounted on a junction
box. (Plug not included).
HTR
Heater and Thermostat
To be used in applications where the temperature will reach
0 degrees Celsius and below. Consists of a 50 watt heating pad
or coil and thermostat programmed to turn on at 0 degrees and
turn off at 15 degrees.
5905 Chemin de la Côte de Liesse, Saint-Laurent, Quebec, H4T 1C3
Tel.: (514) 739-9984 • Toll Free:1-866-280-2332 • Fax: (514) 739-9912 • www.stanprols.com
The information in this brochure is typical and must not be interpreted as a guarantee of individual product performance and/or characteristics.
Stanpro Lighting Systems Inc. follows a policy of continuous advancements in development. For this reason specifications may change without notice.
Download