NHPV-8 Series 8" Vertical Architectural Frame-In

advertisement
NHPV-8 Series
8" Vertical Architectural Frame-In
with Lensed Trim
Type
Project
Lamp: 13-26W Electronic 4-Pin Quad
13-42W Electronic 4-Pin Triple Biax
Catalog No.
Lamp/Wattage
NHPV-8 -Series
NHPV-8 -Series
PRODUCT DESCRIPTION
New construction eight inch vertical compact fluorescent down light, for use with one quad or
triple tube lamp. Use in non insulated ceilings, where insulation can be kept 3" from fixture,
and 1/2” from adjacent building components. Adheres to the minimum lumens to watts ratio
that qualifies to Energy Star.
CONSTRUCTION
Plaster Ring
Pre-wired architectural quality .050 galvanized steel ring, riveted to an elevated junction box.
DIMENSIONS
Mounting
Plaster ring has two universal mounting brackets that adjusts 3-1/8" vertically. Accepts flat
bar hangers (ordered separately), C-Channel or 1/2" EMT conduit pipe. Accommodates up to
a 5/8" thick ceiling.
Socket Cup
Galvanized steel socket cup with one, 4-pin socket. The socket cup attaches to the finishing
trim easily. Three positions are available to move the lamp up or down into the reflector
enabling the user to orient the lamp at the optical focal plane of the reflector for precise
optics and optimum performance.
Lamp
- One 13-26W Electronic 4-Pin Quad ordered separately.
- One 13-42W Electronic 4-Pin Triple Biax ordered separately.
BALLAST
Electronic - Universal
Thermally protected, electronic high power factor, single tap input voltage ranging from 110V
– 277V, 0.358Ampere - 0.1552Ampere,50/60Hz with end of life protection. Class P, 42Watts
maximum.
Starting Temperature
0˚ F – 18˚C
Operating Ambient Temperature
75˚C (Max)
Start Rating
>50,000
Power Factor
HPF
Flicker
<3%
THD
<10%
(For magnetic ballast consult factory.)
Trim
Precision spun .050 aluminum reflector, high grade specular finish. Choice of glass lenses,
Clear, Frosted or decorative. Three clips hold trim in frame. Decorative glass (ordered
separately) see accessories.
Labels and Listings
UL Listed for Damp Location w/ Feed Through
Energy Star Rated (Electronic ballast only)
Housing - select one box from each column
Catalog No.
NHPV-8
Lamps
1
Wattage
13
18
26-42
Ballast
EL
Example: N H P V - 8 2 6 4 2 M 7 E M
Options
Cut out: 8-3/8"
ID:
7-1/4"
OD:
9"
Housing Length: 13-3/8"
Housing Width: 13-3/8"
Height:
10-1/8"
Optional Dimming
A variety of dimming ballast option are available in 13-42W. Each option
requires a controller that is compatible. Specify suffix.
DAS Advance Mark X, AMBI Star 120V (2Wire), Residential
D10 Universal Technologies 0-10V (4Wire), Universal
MX1 Advance Mark X 120V (2Wire), (Specify Wattage)
MX2 Advance Mark X 277V (2Wire), (Specify Wattage)
M7 Advance Mark 7 (4Wire), Universal
L51 Lutron SE 5% 120V (3Wire), (Specify Wattage & Voltage)
L52 Lutron SE 5% 277V (3Wire). (Specify Wattage & Voltage)
Optional Emergency
Emergency back-up operates one lamp for a minimum of 90 minutes. Unit
includes battery, charger and test plate with indicator light. Emergency
ballasts are for dry locations.
For one lamp operation:
Add: (EM) Emergency ballast 650 Lumen,
(EMI) Emergency ballast 650 Lumen with Internal Switch.
(EM2) Emergency ballast up to 1300 Lumen.
Optional
FS
NRA-28
NRA-38
Accessories
Fuse 2A
27" Flat Bar Hanger
C-Channel
Decorative
NTG-8B/167
NTG-8B/80
NTG-8CF
NTS-8FC
/
Glass Options for NT-638C
Tempered Blue Ring, 3" Open Center (120mm)
Tempered Blue Ring, 6-1/2" Open Center (80mm)
Tempered Ring, 7-7/8" Frosted Center, 1-1/8" Clear Outer
Tempered Ring, 7-7/8" Clear Center, -1/81" Frosted Outer
NTS-935G
Lensed Trim
Dimming
Emergency
DAS
M7
EM
D10
L51
EMI*
MX1
13-3/8"
13-3/8"
8-3/8"
8-3/8"Cutout: 8-3/8"
Ceiling
Ceiling Cutout: 8-3/8"
Junction Box
Prewired 25 cubic inch .064" thick galvanized steel, with seven 7/8" knockout, four Romex®
pryouts, and snap on covers. All leads are #18AWG wire, the ground wire is connected to the
bottom, and quick connectors are supplied on all leads. Through branch circuit wiring, (4-in,
4-out).
Create a complete fixture/trim catalog number:
13-3/8"
13-3/8"
10-1/8"
10-1/8"
L52
Fuse
Catalog No.
FS
EM2
NTS-935
Reflector
C
Flange
W
Glass
CL
Emergency
Decorative Glass
EMI
NTG-8B/167
NTS-936
FL
NTG-8B/80
NTS-938
G
NTG-8CF
L
NTG-8FC
Finishes: C =Chrome, CL =Clear Lens, FL =Frost Lens, G =Glass, L =Lexan, W =White
MX2
* When selecting EMI add EMI to the trim for test switch aperture.
6505 Gayhart St., Commerce, CA 90040
Phone: 800.686.6672 • FAX 800.500.9955
www.noralighting.com • e-mail: nora@noralighting.com
Specifications subject to change without notice. © 2008
LENSED TRIM
NHPV-8 -Series
NTS-935
NHPV-8 -Series
NTS-938C
Chrome Reflector w/Lens
Chrome Reflector for Decorative Glass
42 Watts Max. Quad/Triple Biax CFL
13-3/8"
10-1/8"
13-3/8"
8-3/8"
Ceiling Cutout: 8-3/8"
13-3/8"
10-1/8"
13-3/8"
8-3/8"
Ceiling Cutout: 8-3/8"
Ring:
1/2"
Trim OD: 9"
Trim OD: 9"
NHPV-8 -Series
Decorative Glass Options for NT-938C
NTS-936
Chrome Reflector w/Flush Mounted Lens
NTG-8B/167
NTG-8B/80
NTG-8CF
NTS-8FC
Tempered Blue Ring, 3" Open Center (120mm)
Tempered Blue Ring, 6-1/2" Open Center (80mm)
Tempered Ring, 7-7/8" Frosted Center, 1-1/8" Clear Outer
Tempered Ring, 7-7/8" Clear Center, 1-1/8" Frosted Outer
13-3/8"
10-1/8"
13-3/8"
8-3/8"
Ceiling Cutout: 8-3/8"
Lens:
Ring:
Trim OD:
More than one glass may be used by adding NRA-103 sland-offs between lenses.
Clear (CL), Frosted (FL)
1/2"
9"
Lens is mounted in a chrome ring that twists and locks for easy relamping
6505 Gayhart St., Commerce, CA 90040
Phone: 800.686.6672 • FAX 800.500.9955
www.noralighting.com • e-mail: nora@noralighting.com
Specifications subject to change without notice. © 2008
NHPV-8 Series
8" Vertical Architectural Frame-In
with Baffle Trim
Type
Project
Lamp: 13-26W Electronic 4-Pin Quad
13-42W Electronic 4-Pin Triple Biax
Catalog No.
Lamp/Wattage
NHPV-8 -Series
NHPV-8 -Series
PRODUCT DESCRIPTION
New construction eight inch vertical compact fluorescent down light, for use with one quad or
triple tube lamp. Use in non insulated ceilings, where insulation can be kept 3" from fixture,
and 1/2” from adjacent building components. Adheres to the minimum lumens to watts ratio
that qualifies to Energy Star.
CONSTRUCTION
Plaster Ring
Pre-wired architectural quality .050 galvanized steel ring, riveted to an elevated junction box.
DIMENSIONS
Mounting
Plaster ring has two universal mounting brackets that adjusts 3-1/8" vertically. Accepts flat
bar hangers (ordered separately), C-Channel or 1/2" EMT conduit pipe. Accommodates up to
a 5/8" thick ceiling.
Socket Cup
Galvanized steel socket cup with one, 4-pin socket. The socket cup attaches to the finishing
trim easily. Three positions are available to move the lamp up or down into the reflector
enabling the user to orient the lamp at the optical focal plane of the reflector for precise
optics and optimum performance.
Lamp
- One 13-26W Electronic 4-Pin Quad ordered separately.
- One 13-42W Electronic 4-Pin Triple Biax ordered separately.
BALLAST
Electronic - Universal
Thermally protected, electronic high power factor, single tap input voltage ranging from 110V
– 277V, 0.358Ampere - 0.1552Ampere,50/60Hz with end of life protection. Class P, 42Watts
maximum.
Starting Temperature
0˚ F – 18˚C
Operating Ambient Temperature
75˚C (Max)
Start Rating
>50,000
Power Factor
HPF
Flicker
<3%
THD
<10%
(For magnetic ballast consult factory.)
Trim
Baffle is precision spun .050 aluminum with deep grooves to reduce aperture glare. Baffle
has a non-reflective matte black or white painted finishes. Open reflector precision spun .050
aluminum high grade specular finishes white self flange or low iridescent Alzak® with white
or matching self flanged. Three slots at the top of the reflector allow for lamp positioning.
Available in a variety of designer colors.
Housing - select one box from each column
Catalog No.
NHPV-8
Lamps
1
Wattage
13
Ballast
EL
Example: N H P V - 8 2 6 4 2 M 7 E M
Options
Cut out: 8-3/8"
ID:
7-1/4"
OD:
9"
26-42
Optional Emergency
Emergency back-up operates one lamp for a minimum of 90 minutes. Unit
includes battery, charger and test plate with indicator light. Emergency
ballasts are for dry locations.
For one lamp operation:
Add: (EM) Emergency ballast 650 Lumen,
(EMI) Emergency ballast 650 Lumen with Internal Switch.
(EM2) Emergency ballast up to 1300 Lumen.
Optional
FS
NRA-28
NRA-38
Accessories
Fuse 2A
27" Flat Bar Hanger
C-Channel
Labels and Listings
UL Listed for Damp Location w/ Feed Through
Energy Star Rated (Electronic ballast only)
/
NTS-932BLISF
Baffle Trim
Dimming
Emergency
DAS
M7
EM
D10
L51
EMI*
MX1
Housing Length: 13-3/8"
Housing Width: 13-3/8"
Height:
10-1/8"
Optional Dimming
A variety of dimming ballast option are available in 13-42W. Each option
requires a controller that is compatible. Specify suffix.
DAS Advance Mark X, AMBI Star 120V (2Wire), Residential
D10 Universal Technologies 0-10V (4Wire), Universal
MX1 Advance Mark X 120V (2Wire), (Specify Wattage)
MX2 Advance Mark X 277V (2Wire), (Specify Wattage)
M7 Advance Mark 7 (4Wire), Universal
L51 Lutron SE 5% 120V (3Wire), (Specify Wattage & Voltage)
L52 Lutron SE 5% 277V (3Wire). (Specify Wattage & Voltage)
Fuse
Catalog No.
FS
NTS-932
Baffle Finish
B
W
18
13-3/8"
13-3/8"
8-3/8"
8-3/8"Cutout: 8-3/8"
Ceiling
Ceiling Cutout: 8-3/8"
Junction Box
Prewired 25 cubic inch .064" thick galvanized steel, with seven 7/8" knockout, four Romex®
pryouts, and snap on covers. All leads are #18AWG wire, the ground wire is connected to the
bottom, and quick connectors are supplied on all leads. Through branch circuit wiring, (4-in,
4-out).
Create a complete fixture/trim catalog number:
13-3/8"
13-3/8"
10-1/8"
10-1/8"
L52
EM2
Reflector Finish
Flange
C
BZ
SF
WF
G
HZ
LI
PE
ST
WH
Emergency
EMI
Finishes: B = Black, BZ = Bronze, C =Chrome, G =Gold, HZ =Haze, LI =Clear, PE = Pewter,
SF = Self Flanged, ST = Straw, W = White, WF =White Flanged
MX2
* When selecting EMI add EMI to the trim for test switch aperture.
6505 Gayhart St., Commerce, CA 90040
Phone: 800.686.6672 • FAX 800.500.9955
www.noralighting.com • e-mail: nora@noralighting.com
Specifications subject to change without notice. © 2008
BAFFLE TRIM
NHPV-8 -Series
NTS-932
Reflector with Baffle
42 Watts Max. Quad/Triple Biax CFL
13-3/8"
10-1/8"
13-3/8"
8-3/8"
Ceiling Cutout: 8-3/8"
Baffle:
Trim ID:
Trim OD:
Baffle Depth:
8-1/2"
Black (B), White (W)
7-1/4"
9"
1"
9"
6505 Gayhart St., Commerce, CA 90040
Phone: 800.686.6672 • FAX 800.500.9955
www.noralighting.com • e-mail: nora@noralighting.com
Specifications subject to change without notice. © 2008
NHPV-813 / NTS-932BC
13W
Lab: LM-63-1995 Test No. LRL1099-1A (Test performed with 32W lamp in clear specular reflector; .27375 multiplier has been applied - .375 for 13W
results concurrent with .73 for black baffle insert) Spacing Criteria: 1.5 Lamp Position: 2 Efficiency: 44% Total Watts: 13 Lumens: 900
CANDELAS
OPTIONAL
MULTIPLIERS
Gold Finish = .92
White Finish = .71
Lens = .50
Louver = .60
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
0
0.5475
0. 8 2 12 5
1.6425
2.19
3.55875
1 6. 151 25
53.1075
8 4. 588 75
115.2488
14 1. 802 5
166.9875
17 4. 926 3
183.1387
17 6. 568 8
176.295
18 4. 233 7
176.8425
16 6. 987 5
COEFFICIENTS OF UTILIZATION*
RC
RW
80
70 50 30 10
70
70 50 30 10
0
52 52 52 52
51 51 51 51
1
49 48 46 45
48 47 45 44
2
46 43 41 39
45 42 40 38
3
42 39 36 34
41 38 36 33
4
39 35 32 29
39 35 32 29
5
37 32 28 26
36 31 28 26
6
34 29 26 23
33 29 25 23
7
32 26 23 21
31 26 23 21
8
30 24 21 19
29 24 21 19
9
28 22 19 17
27 22 19 17
10 26 21 17 15
25 20 17 15
* Effective Floor Cavity Reflectance = 20%
50
50 30 10
30
50 30 10
10
50 30 10
0
0
49
45
41
37
34
30
28
25
23
22
20
47
43
39
36
33
30
27
25
23
21
20
45
42
38
35
32
29
26
24
22
21
19
44
40
35
31
27
24
22
19
18
16
14
49
44
39
35
31
28
25
23
21
19
17
49
43
37
33
29
26
23
21
18
17
15
47
42
38
34
30
27
25
22
20
19
17
47
42
37
32
29
25
23
20
18
17
15
45
41
37
33
30
27
24
22
20
18
17
45
40
36
32
28
25
23
20
18
17
15
LUMINANCE VALUES
Angle in
Degrees
Average
0-Deg
Average
90-Deg
BEAM & CONE DATA
Mounting
Height
Maximum
Spacing
Circle
Diameter
F.C. at
Center
F.C. at
Edge
45
55
65
75
85
5719
3249
333
272
403
5719
3249
333
272
403
4
5.60
10.60
10.43
1.04
6
8.40
15.90
4.63
0.47
8
11.20
21.20
2.60
0.27
10
14.00
26.50
1.67
0.16
12
16.80
31.80
1.15
0.11
Beam Angle: 106˚
NHPV-818 / NTS-932BC
18W
Lab: LM-63-1995 Test No. LRL1099-1A (Test performed with 32W lamp in clear specular reflector; .365 multiplier has been applied - .5 for 18W
results concurrent with .73 for black baffle insert) Spacing Criteria: 1.5 Lamp Position: 2 Efficiency: 44% Total Watts: 18 Lumens: 1200
CANDELAS
OPTIONAL
MULTIPLIERS
Gold Finish = .92
White Finish = .71
Lens = .50
Louver = .60
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
0
0.73
1.095
2.19
2.92
4.745
21.535
70.81001
11 2 . 78 5
153.665
189.0 7
222.65
23 3 . 23 5
244.185
23 5 . 42 5
235.06
24 5 . 64 5
235.79
222.6 5
COEFFICIENTS OF UTILIZATION*
RC
RW
80
70 50 30 10
70
70 50 30 10
0
52 52 52 52
51 51 51 51
1
49 48 46 45
48 47 45 44
45 42 40 38
46 43 41 39
2
41 38 36 33
42 39 36 34
3
4
39 35 32 29
38 35 32 29
5
37 32 28 26
36 31 28 26
34 29 26 23
33 29 25 23
6
7
32 26 23 21
31 26 23 21
29 24 21 19
30 24 21 19
8
9
28 22 19 17
27 22 19 17
10 26 21 17 15
25 20 17 15
* Effective Floor Cavity Reflectance = 20%
LUMINANCE VALUES
50
50 30 10
30
50 30 10
10
50 30 10
0
0
49
45
41
37
34
30
28
25
23
22
20
47
43
39
36
33
30
27
25
23
21
20
45
42
38
35
32
29
26
24
22
21
19
44
40
35
31
27
24
22
19
18
16
14
49
44
39
35
31
28
25
23
21
19
17
49
43
37
33
29
26
23
21
18
17
15
47
42
38
34
30
27
25
22
20
19
17
BEAM & CONE DATA
47
42
37
32
29
25
23
20
18
17
15
45
41
37
33
30
27
24
22
20
18
17
45
40
36
32
28
25
23
20
18
17
15
Beam Angle: 106˚
Angle in
Degrees
Average
0-Deg
Average
90-Deg
Mounting
Height
Maximum
Spacing
Circle
Diameter
F.C. at
Center
F.C. at
Edge
45
55
65
75
85
7659
4353
416
272
403
7659
4353
416
272
403
4
5.60
10.60
13.91
1.39
6
8.40
15.90
6.17
0.62
8
11.20
21.20
3.47
0.37
10
14.00
26.50
2.23
0.22
12
16.80
31.80
1.53
0.15
Phone: 800.686.6672 • FAX 800.500.9955
6505 Gayhart St., Commerce, CA 90040
Specifications subject to change without notice. © 2008
www.noralighting.com • e-mail: nora@noralighting.com
NHPV-82642 / NTS-932BC
2642W
Lab: LM-63-1995 Test No. LRL1099-1A (.5475 Multiplier applied to 32W test results: .75 26W multiplier by .73 for black baffle insert)
Spacing Criteria: 1.5 Lamp Position: 2 Efficiency: 44% Total Watts: 26 Lumens: 1800
CANDELAS
OPTIONAL
MULTIPLIERS
Gold Finish = .92
White Finish = .71
Lens = .50
Louver = .60
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
0
1.095
1 .6425
3.285
4.38
7.1175
3 2. 3 0 25
106.215
169 .1 775
230.4975
28 3 . 60 5
333.975
349 .8 525
366.2775
353 .1 375
352.59
368 .4 675
353.685
33 3 . 97 5
COEFFICIENTS OF UTILIZATION*
RC
RW
80
70 50 30 10
70
70 50 30 10
52 52 52 52
51 51 51 51
0
1
49 47 46 45
48 47 45 44
2
46 43 41 39
45 42 40 38
3
42 39 36 34
41 38 35 33
4
39 35 32 29
38 34 32 29
5
37 32 28 26
36 31 28 26
6
34 29 26 23
33 29 25 23
7
32 26 23 21
31 26 23 21
8
30 24 21 19
29 24 21 19
9
28 22 19 17
27 22 19 17
10 26 21 17 15
25 20 17 15
* Effective Floor Cavity Reflectance = 20%
50
50 30 10
30
50 30 10
10
50 30 10
0
0
49
45
41
37
33
30
28
25
23
22
20
47
43
39
36
33
30
27
25
23
21
20
45
42
38
35
32
29
26
24
22
21
19
44
39
35
31
27
24
22
19
18
16
14
49
44
39
35
31
28
25
23
21
19
17
49
43
37
33
29
26
23
20
18
17
15
47
42
38
34
30
27
25
22
20
19
17
47
41
37
32
29
25
23
20
18
17
15
45
41
37
33
30
27
24
22
20
18
17
45
40
36
32
28
25
22
20
18
17
15
Angle in
Degrees
LUMINANCE VALUES
Average
0-Deg
Average
90-Deg
BEAM & CONE DATA
Mounting
Height
Maximum
Spacing
Circle
Diameter
F.C. at
Center
F.C. at
Edge
45
55
65
75
85
11438
6499
582
408
403
11438
6499
582
408
403
4
5.60
10.60
20.86
2.08
6
8.40
15.90
9.25
0.93
8
11.20
21.20
5.20
0.55
10
14.00
26.50
3.34
0.33
12
16.80
31.80
2.30
0.22
Beam Angle: 106˚
Download