Problem 2-23 The following figure shows a power system consisting of a three-phase 480-V, 60-Hz generator supplying two loads through a transmission line with a pair of transformers at either end. a. Sketch the per-phase equivalent circuit of this power system. b. With the switch open, find the real power P, reactive power Q, and apparent power S supplied by the generator. What is the power factor of the generator? c. With the switch closed, find the real power P reactive power Q, and apparent power S supplied by the generator. What is the power factor of the generator? d. What are the transmission losses (transformer plus transmission line losses) in this system with the switch open? With the switch closed? What is the effect of adding load 2 to the system? Y ∆ ∆ Y G 480 V T1 480/13,800 V 1000 kVA R = 0.010 pu X = 0.040 pu T2 13,800/480 V 500 kVA R = 0.020 pu X = 0.085 pu Load 1 ZL=0.5∠36.87oΩ Y-connected Load 2 ZL=-j0.833Ω Y-connected ZL = 1.5 + j10 Region 1 Sbase1=1000 kVA VLbase1=480V Region 2 Sbase2=1000 kVA VL, base2= 13,800 V Region 3 Sbase3=1000 kVA VL, base3= 480 V Solution: This problem can best be solved using the per-unit system of measurements. The power system can be divided into three regions by the two transformers. If the perunit base quantities in Region 1 are chosen to be Sbase1 = 1000 kVA and VL,base1 = 480 V, then the base quantities in Region 2 and 3 will be as shown above. The base impedance of each region will be: Z base1 = 3(Vφ1 )2 3(277 )2 = = 0.238 Ω Sbase1 1000 kVA Z base 2 = 3(Vφ2 )2 3(7967 )2 = = 190.4 Ω Sbase 2 1000 kVA Z base3 = 3(Vφ3 )2 3(277 )2 = = 0.238 Ω Sbase3 1000 kVA a. To have the per-unit, per-phase equivalent circuit, we must convert each impedance in the system to per unit on the base of the region in which it is located. The impedance of transformer T1 is already in per unit to the proper base R1, pu = 0.010 X1, pu = 0.040 The impedance of transformer T2 is already in per unit, but it is per-unit to the base of transformer T2, so it must be converted to the base of the power system. 2 (R, X, Z)pu on base 2 = (R, X, Z)pu on base 1 (Vbase1 )2 (Sbase2 ) (Vbase2 ) (Sbase1 ) 2 (7967 V ) (1000 kVA ) = 0.040 R 2, pu = 0.02 (7967 )2 (500 kVA ) (7967 V )2 (1000 kVA ) = 0.170 X 2, pu = 0.085 (7967 )2 (500 kVA ) The per unit impedance of the transmission line is Zline, pu = Zline 1.5 + j10 = = 0.00788 + j 0.0525 Z base2 190.4 The per unit impedance of load 1 is Zload1,pu = Zload1 0.5∠36.87 o = = 1.681 + j1.261 Z base3 0.238 The per unit impedance of load 2 is Zload2,pu = - j 0.833 = − j 3.5 0.238 The per-unit, per-phase equivalent circuit is shown below T1 Line 0.01+j0.04 0.0078+j0.052 T2 0.04+j17 L1 1.68+j 1.26 1∠0o b. With the switch open, the equivalent impedance is ZT = 0.010 + j0.040 + 0.00788 + j0.0525 + 0.040 + j0.170 + 1.681 + j1.261 = 2.312∠41.2o The current is I= 1∠0o 2.312∠41.2o = 0.4325∠ − 41.2o A The load voltage is ( ) Vload, pu = I Zload = 0.4325∠ - 41.2o (1.681 + j1.261) = 0.909∠ − 4.3o The actual load voltage is 0.909×480=436 V. The power supplied to the load is Pload, pu = I 2 R load = (0.4325)2 (1.681) = 0.314 Pload == Pload, pu Sbase = (0.314)(1000 kVA ) = 314 kW The power supplied by the generator PG, pu = VI cos θ = (1)(0.4325) cos 41.2o = 0.325 Q G, pu = VIsinθ = (1)(0.4325) sin 41.2o = 0.285 SG, pu = VI = (1)(0.4325) = 0.4325 Actual values are: PG = 325 kW; QG = 285 kVAR; SG = 432.5 kVA L2 -j3.5 The power factor is: cos 41.2o = 0.752 lagging c. With the switch closed, the equivalent circuit is ZT = 0.010 + j0.040 + 0.00788 + j0.0525 + 0.040 + j0.170 + (1.681 + j1.26)(− j3.5) = 2.698∠5.6o 1.681 + j1.261 − j 3.5 The current is I= 1∠0o 2.698∠5.6o = 0.371∠ − 5.6o The load voltage is Vload,pu = I Zload = 0.371∠ - 5.6o (2.627 − j 0.011) = 0.975∠ − 5.6o Vload = (0.975)(480 ) = 468 V The power supplied to the two loads is Pload, pu = I 2 Rload = (0.371)2 (2.672) = 0.361 Pload = (0.361)(1000 kVA ) = 361 kW The power supplied by the generator PG, pu = VIcosθ = (1)(0.371) cos 5.6o = 0.369 QG,pu == VI sin θ = (1)(0.371) sin 5.6o = 0.0369 SG,pu = VI = 0.371 Multiply each value by 1000 kVA to get actual values: PG = 369 kW; QG = 36 kVAR; SG = 371 kVA. The power factor of the generator is cos 5.6o = 0.995 lagging. d. The transmission losses with the switch open are: Pline,pu = (0.4325)2 (0.00788) = 0.00147 Pline = (0.00147 )(1000) = 1.47 kW The transmission losses with the switch closed are Pline,pu = (0.371)2 (0.00788) = 0.00108 Pline = (0.00108)(1000) = 1.08 kW Load 2 improved the power factor of the system.