Selection and ordering data 3NP4 standard series 3NP4 standard series – Accessories Accessories Basic versions For surface mounting and switchboard install. Connection in mm2 160 A1) 160 A Size 000 Size 00 250 A 400 A 630 A Size Size Size 1.5 – 50 up to 2 x 70 (M8) 2.5 – 70 up to 150 (M10) up to 240 (M12) up to 2 x 240 (M12) 1 2 3 SIGUT terminal Flat pad connection SIGUT terminal Flat pad connection Flat pad connection Flat pad connection For 40 mm busbars2) 160 A1) 160 A Size 000 Size 00 Flat pad connection SIGUT terminal 250 A Size 1 Flat pad connection For 60 mm busbars 160 A1) 160 A Size 000 Size 00 400 A 630 A Size Size Size 1 2 3 With fuse monitoring 1.5 – 50 Connection, top Connection, bottom up to 2 x 70 (M8) Connection, top Connection, bottom 2.5 – 70 Connection, top Connection, bottom up to 150 (M10) top or bottom3) 3NP4015 – 1CK01 3NP4015 – 1CJ01 3NP4075 – 1CE01 3NP4075 – 1CF01 3NP4075 – 1CK01 3NP4075 – 1CJ01 3NP4275– 1CG01 Connection in mm2 SIGUT terminal Flat pad connection SIGUT terminal 250 A 3NP4010 – 0CH10 3NP4070 – 0CA01 3NP4070 – 0CH01 3NP4270 – 0CA01 3NP4370 – 0CA10 3NP4470 – 0CA01 Connection in mm2 SIGUT terminal Flat pad connection Flat pad connection Flat pad connection By simply snapping onto the busbars from the top, the disconnectors can also be mounted onto T or double T profiles as well as onto Power-Line systems from the Rittal company, without the horizontal parts of the busbars preventing this. 1.5 – 50 Connection, top Connection, bottom 3NP4016 – 1CK01 3NP4016 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4076 – 1CE01 3NP4076 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4076 – 1CK01 3NP4076 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4276 – 1CG01 up to 240 (M12) top or bottom3) 3NP4376 – 1CG01 up to 2 x 240 (M12) top or bottom3) 3NP4476 – 1CG01 400 – 690 V AC, 220 V DC all of the versions specified above (except size 000) are also available with mounted fuse monitoring; Order No. supplement: 3NP4…–.F.01 1) 125 and 160 A only with special, 21-mm-wide fuses 3NY1822 and 3NY1824, refer to Accessories 2) Adapter depth, 28 mm; for disconnectors with deeper adapters (49 mm), refer to Catalog NSK, Section 12 3) Connection modules can be replaced, refer to the Instruction Manual for 3NP401 Size 000 for 3NP407 Size 00 for 3NP42 Size 1 for 3NP43 Size 2 Connection terminals (1 set = 3 units) connection: integrated integrated 3NY7120 70 – 150 mm2 3NY7130 3NY7140 120 – 240 mm2 150 – 300 mm2 Cable lug cover (1 set = 3 units) safe from finger touch cover of the flat pad connection acc. to VBG4 not required 3NY7101 3NY7121 3NY7131 Auxiliary contact, 1 changeover contact normal version electronics-compatible Quick retaining plate to mount the disconnectors between two mounting rails (125 mm clearance) 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY1995 3NY1995 3NY7322 – – 3-phase busbars for 2 disconnectors for 3 disconnectors for 4 disconnectors connecting buses for > 4 disconnectors cap for empty location (20x units): Incoming supply terminal (1 set = 3 units) for conductors e/m: up to 95 mm2 finely stranded with end sleeves: up to 70 mm2 Masking frames for mounting in general distribution systems for disconnectors with SIGUT terminal for disconnectors with flat pad connection Dimensions (H x W): Overreach protection (10 units) The circuit-breaker is connected in parallel to the three main disconnector phases, and is tripped as soon as at least one of three fuses blows. The voltage is tapped at the handle lugs of the fuses which means that only fuses with live grip lugs can be used. not required break-off 3NY7381 not required 3NY7381 not required not possible not required 3NY7102 3NY7102 – – – – 3NY7105 – – – 3NY1237 3NY1238 3NY1438 – – – – – – – – – – – – 3NY1263 3NY1265 – – – – – – – – 3NY1236 – – – – integrated – – – – – – – – integrated 3NY7482 3NY7482 3NY7482 3NY1251 3NY7200 – – – – 215 x 130 3NY7201 215 x 130 3NY7220 375 x 220 3NY7230 375 x 245 3NY7240 375 x 290 integrated integrated 3NY7481 3NY7481 3NY7481 for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog E20001-8ZX1012-OHP54-5AB1 This button prevents the shock protection from being inserted as long as the latching mechanism hasn’t correctly latched into place. Allaround safety With the cable lug covers correctly mounted, the enclosed disconnectors offer a high IP 30 degree of protection, even after a voltage test using the 6 test holes in the withdrawable fuse carrier. The versions with SIGUT terminals are completely safe from finger touch without any additional covers. The large clear inspection window allows the type and the operating statuses of the fuse links to be quickly and reliably identified. Overreach and reacharound touch protection is already integrated into the withdrawable fuse carrier up to 160 A; from Size 1 shock protection is available as accessory. At home on all busbars All 3NP4 sizes are available for 40 mm or 60 mm busbar center clearance. Busbars can either be 5 or 10 mm wide. For 10 mm busbars, for sizes 000 and 00, two lugs must be broken off at the three rear busbar clamps. Busbar compensation is available as accessory for mounting sizes 1 and 2 onto 5 mm busbars (size 3 disconnectors cannot only be snapped onto 5 mm busbars). Quickly mounted … All of these features reduce valuable mounting and installation time. It also means that the correct tightening torque of the screws doesn’t have to be checked and adjusted. The mounting rail latching mechanisms, integrated into the basic size 000 and 00 devices, also provide a clear financial benefit, especially, where up to 160 A disconnectors are used in larger unit quantities: additional screws, hooks, intermediate plates or a second mounting rail are not required. Smart accessories for every application The auxiliary contacts, which fit all sizes, can be subsequently retrofitted without taking up any extra space. The three-way terminal makes it easy to connect up to 3 cables (e. g. for capacitor protection). Several disconnectors can be fed in parallel using the 3-phase busbars, connecting buses and feeder terminals up to 225 A. Numerous masking frames and mounting sets for SIKUS distribution boards or the 8HP distribution system guarantee simple engineering and fast mounting and installation. 3NP Fuse Switch Disconnector – the Optimum Handle on Every Application 1NO/1NC signal outputs are used as standard. For size 00, they are brought out to a connector socket at the front, and for sizes 1 to 3, as double AMP flat connector at the shock protection in the lower section of the disconnector. Either pre-assembled 1- or 3-m cables with strain relief can be used as connecting cable for size 00. These can then be easily inserted at the fuse monitoring using the mounted connectors. There are also connector mounting sets for crimping (short-circuit proof) cables. 3NP4 – quickly mounted onto all busbars Fuse links, size 000 21 mm wide, Duty class gL/gC 400 V/125 A 3NY1822 400 V/160 A 3NY1824 Sealing pin can be retrofitted (1 pkg. = 10 units) can frequently occur, e. g. in line supplies with AC drive converters and inverters. Intelligent latching mechanism This automatically adapts itself to busbar widths between 5 and 30 mm, and it reliably latches into place. This eliminates numerous versions and complicated adjustments before mounting. There is a small red button inside the switch, which, especially from size 1, ensures that the disconnector is really mounted onto the busbar to its endstop. 3NY7141 3NY3035 3NY3030 Busbar width compensation only for 5 mm busbars not required for 10 mm busbars break-off Three-way terminal (1 set = 3 units) to connect 3 x 2.5 – 16 mm2 (e/m) or 3 x 2.5 – 10 mm2 (finely stranded with end sleeves) for mounting onto a SIGUT terminal for mounting onto a flat pad connection for 3NP44 Size 3 Fuse monitoring for 3NP4 From size NH00 onwards, all of the 3NP4 versions are also available with fuse monitoring. This is realized using 3RV SIRIUS circuit-breakers which are mounted at the front in the center of the fuse carrier. Flat connectors are always used for sizes 1–3. The disconnector can then be fed as required from either the top or the bottom, whereby voltages up to 690 V AC/220 V DC are possible. Furthermore, this type of fuse monitoring is completely insensitive to EMC disturbances and harmonics. These disturbances The function of the 3RV can be tested at any time using the test button provided. Technical data Type Rated operational voltage Ue 3NP401 AC 50/60 Hz V DC V 3NP40 7 3NP42 3NP43 3NP44 690 690 220 (3 phases in series) 440 (2 phases in series) with mounted fuse monitoring upt to 220 V DC max. Rated conditional short-circuit current with fuses (for fast closing) With fuse links rated current Size/A For 400 V AC (690 V) kA (RMS value) Permissible fuse cut-off current kA (peak value) 000/100 (35) 00/160 50 (50) 50 11 (5) 15 1/250 50 25 2/400 50 35 3/630 50 55 Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A Up to 690 V kA (RMS value) Permissible fuse cut-off current kA (peak value) 000/100 100 15 00/160 50 15 1/250 50 25 2/400 50 35 3/630 50 55 Rated operational current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 000 800 160 100 00 800 160 100 1 2,000 250 250 2 3,200 400 400 3 5,040 630 630 For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B A AC-22B A AC-23B A 000 240 160 50 25 00 240 160 50 25 1 375 250 – – 2 600 400 – – 3 945 630 – – for additional values, refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, ...) sentric can also be safely handled, favorably-priced backup protection, simple selectivity calculations and absolute reliability, even when short-circuits occur. The fuse 3NP5 – the rugged types for the toughest applications melts completely so that there is no residual risk as a result of contacts which may have welded together. When the disconnector is in the open position, Furthermore, 3NP5 have an extremely high AC-23 switching capacity. The switching gases which are formed are deflected into the disconnector using a sophisticated arc chamber design, instead of being discharged upwards and to the side. This means that operating personnel and plant sections and components in the vicinity are reliably protected. there is a visible isolating gap, which is often demanded, e. g. for maintenance purposes. And the optional mounted fuse monitoring offers additional security – fuse switch disconnectors 3NP for the highest plant availability and safety. Fuse monitoring: To allow monitoring of the fuses in the disconnectors, a permanently wired 3RV1 circuit-breaker is mounted on the fuse carrier. Fuses for your safety – 3NP4 and 3NP5 switch disconnectors ble to use other disconnectors available on the market. But the fast closing and arc deflection chambers of the 3NP5 come through with flying colors. 3NP5 provides the highest degree of safety for operating personnel and the plant, as main switch with high switching frequency and good AC-23 characteristics, e.g. for motor loads. Both of these ranges are climate-proof and correspond to IEC 60 947-3 and VDE 0660, Part 107. The fuses can be clearly identified through the large clear inspection window. Matching masking frames and complete, TSK-tested mounting sets are available both for the moldedplastic 8HP distribution system as well as for the various SIKUS distribution boards. 2 series in the range – the optimum handle on every application The 3NP4 series (sizes NH000 to NH3) offer the optimum solution for most applications. These range from power distribution in residential and commercial buildings, through flexible distribution stations up to power distribution systems in large industrial plants.They are also admirably suited as main and incoming feeder breakers in industry, for control systems, as well as in motor feeders or as backup protection for circuit-breakers. They have an integrated lug for sealing which is integrated as standard. This means that they can be used, without any restrictions, in meter cabinets and incoming main feeder boxes for buildings. The rugged 3NP5 series (sizes NH00 to NH3) provide reliable protection for all of the “tougher” applications. This is especially true in mining, in the steel industry, and also in the chemical industry, where sulphur-laden, or aggressive ambient conditions or hazardous locations make it almost impossi- The values for switching capacitors (e.g. for reactive power compensation) were also tested (refer to Catalog NSK, Section 12), and when used with SITOR semiconductor or 3NE1 double-protection fuses, 3NP disconnectors can be used to protect soft starters, AC drive converters and similar devices (tables with tested device-fuse combinations are provided in the NSK). Shock and vibration testing as well as special earthquake tests guarantee that the 3NP can be used in marine applications, nuclear power stations and similar safety-critical plants. high switching frequency for devices such as these. The erosion electrodes additionally extend the lifetime of the main contacts. The lateral spring mechanism (= fast switching) eliminates any danger as a result of incorrect operation, e.g. briefly actuating the disconnector or switching which is too slow. When the switch disconnector is in the ON position, the circuit-braker poles are connected in parallel with the fuses to be monitored. When the switch is in the OFF position, the poles of the circuit-breaker are dead. The 3NP5 disconnector series (sizes NH00 to NH3) for fixed installation can be quickly hung onto preinstalled mounting bolts. They can also be mounted on the front of switchgear panels using the matching mounting sets or they can be mounted onto 60 mm busbar systems using 8US1 adapters. The especially rugged design of this series (plastic with a high resistance to heat, metal parts which can be mechanically stressed), permits an unusually The internal resistance of the circuit-breaker is so high that it does not affect the protection given by the monitored fuses. Rated operational voltage Ue Electronic fuse monitoring (EFM): The electronic fuse monitoring system is also mounted on the fuse carrier of the 3NP5. It works whether or not a load is present. Fuse blowing can be signalled to a switch control room by means of a group indication (2NO contacts + 1NC contact). 2 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC 250 A Size 00 Size 1 Flat pad connection 2.5 – 120 Clamp connection 2.5 – 50 Flat pad connection Clamp connection Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) Rated operating current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B up to AC-23B A For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 35 – 120 400 A Size 2 Flat pad connection 6 – 240 630 A Size 3 Flat pad connection 6 – 2 x 240 160 A Size 00 in mm2 Auxiliary contacts Flat pad connection at the bottom 2.5 – 120 Clamp connection at the bottom 2.5 – 50 without 1NO/1NC without 1NO/1NC 3NP5065 – 1CF00 3NP5065 – 1CF10 3NP5065 – 1CG00 3NP5065 – 1CG10 400 – 690 V AC, 220 V DC For surface mounting and switchboard install. in mm2 Auxiliary contacts2) 160 A Size 00 Flat pad connection Clamp connection 2.5 – 120 2.5 – 50 1NO/1NC 1NO/1NC 3NP5060 – 0EA86 3NP5060 – 0EB86 3NP54 250 A Size 1 Flat pad connection Clamp connection 6 – 150 35 – 120 1NO/1NC 1NO/1NC 3NP5260 – 0EA86 3NP5260 – 0EB86 690 440 (3 phases in series) 220 (2 phases in series with mounted fuse monitoring) 400 A 630 A Size 2 Size 3 Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 3NP5360 – 0EA86 3NP5460 – 0EA86 3NP52 3NP53 1) Rated conditional short-circuit current with fuses With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) 6 – 150 3NP5060 – 0CA00 3NP5060 – 0CA00 3NP5060 – 0CB00 3NP5060 – 0CB10 3NP5260 – 0CA00 3NP5260 – 0CA10 3NP5260 – 0CB00 3NP5260 – 0CB10 3NP5360 – 0CA00 3NP5360 – 0CA10 3NP5460 – 0CA00 3NP5460 – 0CA10 With fuse monitoring 3NP50 50/60 Hz V AC V DC Basic versions For 40 mm busbars1) Technical data Type Selection and ordering data 3NP5 high end series 2 For 40 mm busbars 00/160 50 15 00/160 100 23 00 1,600 160 00 800 160 100 1/250 2/400 3/630 50 50 50 25 40 50 160 A for additional values refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, …) 0 1,600 160 0 1,000 160 125 2 4,000 400 2 2,520 400 315 Flat pad connection at the bottom Clamp connection at the bottom Auxiliary contacts 2.5 –120 1NO/1NC 3NP5065 – 1EF86 2.5 – 50 1NO/1NC 3NP5065 – 1EG86 400/500 V AC 2 1 2,500 250 1 1,600 250 200 3 5,040 630 3 3,200 630 400 2 4,000 400 2 2,520 400 315 2) in mm With electronic fuse monitoring 1/250 2/400 3/630 100 50 50 32 40 60 1 2,500 250 1 1,280 250 160 Size 00 6 – 240 6 – 2 x 240 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A Size 00 Flat pad connection Clamp connection 1NO/1NC 1NO/1NC 3NP5060 – 0HA13 3NP5060 – 0HB13 250 A 400 A 630 A Size 1 Size 2 Size 3 Flat pad connection Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 1NO/1NC 3NP5260 – 0HA13 3NP5360 – 0HA13 3NP5460 – 0HA13 For 40 mm busbars1) 160 A Size 00 at Flat pad connection the bottom 2.5 –120 2.5 – 50 6 – 150 6 – 240 6 – 2 x 240 in mm2 Auxiliary contacts 2.5 – 120 1NO/1NC 3NP5065 – 1HF13 1) for mounting on 60 mm busbars, use devices “for surface mounting and installation” and 8US1 busbar adapters 2) optionally, 2 NO as signal outputs: Order No. 3NP5…–.E.26 3NP5 high end series – Accessories Accessories for 3NP50 Size 00 for 3NP52 Size 1 for 3NP53 Size 2 for 3NP54 Size 3 Clamp connection (1 set = 3 units) 3NY1903 2.5 – 50 mm2 3NY1907 35 – 120 mm2 – – Quick retaining plate between 2 mounting rails 3NY1995 – – – Adapter for mounting on 60 mm busbars 8US1291-4SB00 8US1210-4AG00 8US1210-4AG00 8US1210-4AG00 3NY1105 215 x 135 – – – 3NY1115 215 x 135 – – – 3NY1107 265 x 135 – – – 3NY1208 250 x 149 3NY1210 300 x 220 3NY1211 300 x 245 3NY1212 300 x 290 3NY1106 290 x 135 – – – 3NY1116 290 x 135 – – – 3NY1108 – – – – 3NY1241 3NY1245 3NY1245 Auxiliary contacts 1NO/1NC (= mounting set) 3NY3033 3NY3034 3NY3034 3NY3034 Sealing lug can be retrofitted (1 pkg. = 10 units) 3NY1940 – – – Molded-plastic masking frames Dimensions (H x W): for disconnectors without/with auxiliary contacts Dimensions (H x W): for disconnectors with auxiliary contacts Dimensions (H x W): Masking frame mounting set Dimensions (H x W): for mounting the disconnector in the front of the switchgear panel (masking frame and mounting parts) Cable lug cover Masking frame (H x W) for disconnectors without/ with auxiliary contacts Masking frame (H x W) for disconnectors with auxiliary contacts 2 separate covers for top/bottom 6 individual covers (L = 120 mm) for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog 8ZX1012-OHP54-5AB1 for masking frames and mounting sets for SIKUS installation distribution panels, refer to Catalogs I2.34 and 12.35 Subject to change without prior notice 08/02 | Bestell-Nr. EXXXXX-A190-PXXX | DISPO XXXXX | XXXXXXXXX PDWL.XX.X.XX WS 0802X.X | Printed in Germany Fuses for overload and short-circuit protection means: high short-circuit currents Siemens AG Automation and Drives Low Voltage Controls and Distribution P. O. Box 32 40, D-91050 Erlangen www.siemens.com/sentric can also be safely handled, favorably-priced backup protection, simple selectivity calculations and absolute reliability, even when short-circuits occur. The fuse 3NP5 – the rugged types for the toughest applications melts completely so that there is no residual risk as a result of contacts which may have welded together. When the disconnector is in the open position, Furthermore, 3NP5 have an extremely high AC-23 switching capacity. The switching gases which are formed are deflected into the disconnector using a sophisticated arc chamber design, instead of being discharged upwards and to the side. This means that operating personnel and plant sections and components in the vicinity are reliably protected. there is a visible isolating gap, which is often demanded, e. g. for maintenance purposes. And the optional mounted fuse monitoring offers additional security – fuse switch disconnectors 3NP for the highest plant availability and safety. Fuse monitoring: To allow monitoring of the fuses in the disconnectors, a permanently wired 3RV1 circuit-breaker is mounted on the fuse carrier. Fuses for your safety – 3NP4 and 3NP5 switch disconnectors ble to use other disconnectors available on the market. But the fast closing and arc deflection chambers of the 3NP5 come through with flying colors. 3NP5 provides the highest degree of safety for operating personnel and the plant, as main switch with high switching frequency and good AC-23 characteristics, e.g. for motor loads. Both of these ranges are climate-proof and correspond to IEC 60 947-3 and VDE 0660, Part 107. The fuses can be clearly identified through the large clear inspection window. Matching masking frames and complete, TSK-tested mounting sets are available both for the moldedplastic 8HP distribution system as well as for the various SIKUS distribution boards. 2 series in the range – the optimum handle on every application The 3NP4 series (sizes NH000 to NH3) offer the optimum solution for most applications. These range from power distribution in residential and commercial buildings, through flexible distribution stations up to power distribution systems in large industrial plants.They are also admirably suited as main and incoming feeder breakers in industry, for control systems, as well as in motor feeders or as backup protection for circuit-breakers. They have an integrated lug for sealing which is integrated as standard. This means that they can be used, without any restrictions, in meter cabinets and incoming main feeder boxes for buildings. The rugged 3NP5 series (sizes NH00 to NH3) provide reliable protection for all of the “tougher” applications. This is especially true in mining, in the steel industry, and also in the chemical industry, where sulphur-laden, or aggressive ambient conditions or hazardous locations make it almost impossi- The values for switching capacitors (e.g. for reactive power compensation) were also tested (refer to Catalog NSK, Section 12), and when used with SITOR semiconductor or 3NE1 double-protection fuses, 3NP disconnectors can be used to protect soft starters, AC drive converters and similar devices (tables with tested device-fuse combinations are provided in the NSK). Shock and vibration testing as well as special earthquake tests guarantee that the 3NP can be used in marine applications, nuclear power stations and similar safety-critical plants. high switching frequency for devices such as these. The erosion electrodes additionally extend the lifetime of the main contacts. The lateral spring mechanism (= fast switching) eliminates any danger as a result of incorrect operation, e.g. briefly actuating the disconnector or switching which is too slow. When the switch disconnector is in the ON position, the circuit-braker poles are connected in parallel with the fuses to be monitored. When the switch is in the OFF position, the poles of the circuit-breaker are dead. The 3NP5 disconnector series (sizes NH00 to NH3) for fixed installation can be quickly hung onto preinstalled mounting bolts. They can also be mounted on the front of switchgear panels using the matching mounting sets or they can be mounted onto 60 mm busbar systems using 8US1 adapters. The especially rugged design of this series (plastic with a high resistance to heat, metal parts which can be mechanically stressed), permits an unusually The internal resistance of the circuit-breaker is so high that it does not affect the protection given by the monitored fuses. Rated operational voltage Ue Electronic fuse monitoring (EFM): The electronic fuse monitoring system is also mounted on the fuse carrier of the 3NP5. It works whether or not a load is present. Fuse blowing can be signalled to a switch control room by means of a group indication (2NO contacts + 1NC contact). 2 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC 250 A Size 00 Size 1 Flat pad connection 2.5 – 120 Clamp connection 2.5 – 50 Flat pad connection Clamp connection Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) Rated operating current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B up to AC-23B A For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 35 – 120 400 A Size 2 Flat pad connection 6 – 240 630 A Size 3 Flat pad connection 6 – 2 x 240 160 A Size 00 in mm2 Auxiliary contacts Flat pad connection at the bottom 2.5 – 120 Clamp connection at the bottom 2.5 – 50 without 1NO/1NC without 1NO/1NC 3NP5065 – 1CF00 3NP5065 – 1CF10 3NP5065 – 1CG00 3NP5065 – 1CG10 400 – 690 V AC, 220 V DC For surface mounting and switchboard install. in mm2 Auxiliary contacts2) 160 A Size 00 Flat pad connection Clamp connection 2.5 – 120 2.5 – 50 1NO/1NC 1NO/1NC 3NP5060 – 0EA86 3NP5060 – 0EB86 3NP54 250 A Size 1 Flat pad connection Clamp connection 6 – 150 35 – 120 1NO/1NC 1NO/1NC 3NP5260 – 0EA86 3NP5260 – 0EB86 690 440 (3 phases in series) 220 (2 phases in series with mounted fuse monitoring) 400 A 630 A Size 2 Size 3 Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 3NP5360 – 0EA86 3NP5460 – 0EA86 3NP52 3NP53 1) Rated conditional short-circuit current with fuses With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) 6 – 150 3NP5060 – 0CA00 3NP5060 – 0CA00 3NP5060 – 0CB00 3NP5060 – 0CB10 3NP5260 – 0CA00 3NP5260 – 0CA10 3NP5260 – 0CB00 3NP5260 – 0CB10 3NP5360 – 0CA00 3NP5360 – 0CA10 3NP5460 – 0CA00 3NP5460 – 0CA10 With fuse monitoring 3NP50 50/60 Hz V AC V DC Basic versions For 40 mm busbars1) Technical data Type Selection and ordering data 3NP5 high end series 2 For 40 mm busbars 00/160 50 15 00/160 100 23 00 1,600 160 00 800 160 100 1/250 2/400 3/630 50 50 50 25 40 50 160 A for additional values refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, …) 0 1,600 160 0 1,000 160 125 2 4,000 400 2 2,520 400 315 Flat pad connection at the bottom Clamp connection at the bottom Auxiliary contacts 2.5 –120 1NO/1NC 3NP5065 – 1EF86 2.5 – 50 1NO/1NC 3NP5065 – 1EG86 400/500 V AC 2 1 2,500 250 1 1,600 250 200 3 5,040 630 3 3,200 630 400 2 4,000 400 2 2,520 400 315 2) in mm With electronic fuse monitoring 1/250 2/400 3/630 100 50 50 32 40 60 1 2,500 250 1 1,280 250 160 Size 00 6 – 240 6 – 2 x 240 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A Size 00 Flat pad connection Clamp connection 1NO/1NC 1NO/1NC 3NP5060 – 0HA13 3NP5060 – 0HB13 250 A 400 A 630 A Size 1 Size 2 Size 3 Flat pad connection Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 1NO/1NC 3NP5260 – 0HA13 3NP5360 – 0HA13 3NP5460 – 0HA13 For 40 mm busbars1) 160 A Size 00 at Flat pad connection the bottom 2.5 –120 2.5 – 50 6 – 150 6 – 240 6 – 2 x 240 in mm2 Auxiliary contacts 2.5 – 120 1NO/1NC 3NP5065 – 1HF13 1) for mounting on 60 mm busbars, use devices “for surface mounting and installation” and 8US1 busbar adapters 2) optionally, 2 NO as signal outputs: Order No. 3NP5…–.E.26 3NP5 high end series – Accessories Accessories for 3NP50 Size 00 for 3NP52 Size 1 for 3NP53 Size 2 for 3NP54 Size 3 Clamp connection (1 set = 3 units) 3NY1903 2.5 – 50 mm2 3NY1907 35 – 120 mm2 – – Quick retaining plate between 2 mounting rails 3NY1995 – – – Adapter for mounting on 60 mm busbars 8US1291-4SB00 8US1210-4AG00 8US1210-4AG00 8US1210-4AG00 3NY1105 215 x 135 – – – 3NY1115 215 x 135 – – – 3NY1107 265 x 135 – – – 3NY1208 250 x 149 3NY1210 300 x 220 3NY1211 300 x 245 3NY1212 300 x 290 3NY1106 290 x 135 – – – 3NY1116 290 x 135 – – – 3NY1108 – – – – 3NY1241 3NY1245 3NY1245 Auxiliary contacts 1NO/1NC (= mounting set) 3NY3033 3NY3034 3NY3034 3NY3034 Sealing lug can be retrofitted (1 pkg. = 10 units) 3NY1940 – – – Molded-plastic masking frames Dimensions (H x W): for disconnectors without/with auxiliary contacts Dimensions (H x W): for disconnectors with auxiliary contacts Dimensions (H x W): Masking frame mounting set Dimensions (H x W): for mounting the disconnector in the front of the switchgear panel (masking frame and mounting parts) Cable lug cover Masking frame (H x W) for disconnectors without/ with auxiliary contacts Masking frame (H x W) for disconnectors with auxiliary contacts 2 separate covers for top/bottom 6 individual covers (L = 120 mm) for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog 8ZX1012-OHP54-5AB1 for masking frames and mounting sets for SIKUS installation distribution panels, refer to Catalogs I2.34 and 12.35 Subject to change without prior notice 08/02 | Bestell-Nr. EXXXXX-A190-PXXX | DISPO XXXXX | XXXXXXXXX PDWL.XX.X.XX WS 0802X.X | Printed in Germany Fuses for overload and short-circuit protection means: high short-circuit currents Siemens AG Automation and Drives Low Voltage Controls and Distribution P. O. Box 32 40, D-91050 Erlangen www.siemens.com/sentric can also be safely handled, favorably-priced backup protection, simple selectivity calculations and absolute reliability, even when short-circuits occur. The fuse 3NP5 – the rugged types for the toughest applications melts completely so that there is no residual risk as a result of contacts which may have welded together. When the disconnector is in the open position, Furthermore, 3NP5 have an extremely high AC-23 switching capacity. The switching gases which are formed are deflected into the disconnector using a sophisticated arc chamber design, instead of being discharged upwards and to the side. This means that operating personnel and plant sections and components in the vicinity are reliably protected. there is a visible isolating gap, which is often demanded, e. g. for maintenance purposes. And the optional mounted fuse monitoring offers additional security – fuse switch disconnectors 3NP for the highest plant availability and safety. Fuse monitoring: To allow monitoring of the fuses in the disconnectors, a permanently wired 3RV1 circuit-breaker is mounted on the fuse carrier. Fuses for your safety – 3NP4 and 3NP5 switch disconnectors ble to use other disconnectors available on the market. But the fast closing and arc deflection chambers of the 3NP5 come through with flying colors. 3NP5 provides the highest degree of safety for operating personnel and the plant, as main switch with high switching frequency and good AC-23 characteristics, e.g. for motor loads. Both of these ranges are climate-proof and correspond to IEC 60 947-3 and VDE 0660, Part 107. The fuses can be clearly identified through the large clear inspection window. Matching masking frames and complete, TSK-tested mounting sets are available both for the moldedplastic 8HP distribution system as well as for the various SIKUS distribution boards. 2 series in the range – the optimum handle on every application The 3NP4 series (sizes NH000 to NH3) offer the optimum solution for most applications. These range from power distribution in residential and commercial buildings, through flexible distribution stations up to power distribution systems in large industrial plants.They are also admirably suited as main and incoming feeder breakers in industry, for control systems, as well as in motor feeders or as backup protection for circuit-breakers. They have an integrated lug for sealing which is integrated as standard. This means that they can be used, without any restrictions, in meter cabinets and incoming main feeder boxes for buildings. The rugged 3NP5 series (sizes NH00 to NH3) provide reliable protection for all of the “tougher” applications. This is especially true in mining, in the steel industry, and also in the chemical industry, where sulphur-laden, or aggressive ambient conditions or hazardous locations make it almost impossi- The values for switching capacitors (e.g. for reactive power compensation) were also tested (refer to Catalog NSK, Section 12), and when used with SITOR semiconductor or 3NE1 double-protection fuses, 3NP disconnectors can be used to protect soft starters, AC drive converters and similar devices (tables with tested device-fuse combinations are provided in the NSK). Shock and vibration testing as well as special earthquake tests guarantee that the 3NP can be used in marine applications, nuclear power stations and similar safety-critical plants. high switching frequency for devices such as these. The erosion electrodes additionally extend the lifetime of the main contacts. The lateral spring mechanism (= fast switching) eliminates any danger as a result of incorrect operation, e.g. briefly actuating the disconnector or switching which is too slow. When the switch disconnector is in the ON position, the circuit-braker poles are connected in parallel with the fuses to be monitored. When the switch is in the OFF position, the poles of the circuit-breaker are dead. The 3NP5 disconnector series (sizes NH00 to NH3) for fixed installation can be quickly hung onto preinstalled mounting bolts. They can also be mounted on the front of switchgear panels using the matching mounting sets or they can be mounted onto 60 mm busbar systems using 8US1 adapters. The especially rugged design of this series (plastic with a high resistance to heat, metal parts which can be mechanically stressed), permits an unusually The internal resistance of the circuit-breaker is so high that it does not affect the protection given by the monitored fuses. Rated operational voltage Ue Electronic fuse monitoring (EFM): The electronic fuse monitoring system is also mounted on the fuse carrier of the 3NP5. It works whether or not a load is present. Fuse blowing can be signalled to a switch control room by means of a group indication (2NO contacts + 1NC contact). 2 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC 250 A Size 00 Size 1 Flat pad connection 2.5 – 120 Clamp connection 2.5 – 50 Flat pad connection Clamp connection Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) Rated operating current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B up to AC-23B A For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 35 – 120 400 A Size 2 Flat pad connection 6 – 240 630 A Size 3 Flat pad connection 6 – 2 x 240 160 A Size 00 in mm2 Auxiliary contacts Flat pad connection at the bottom 2.5 – 120 Clamp connection at the bottom 2.5 – 50 without 1NO/1NC without 1NO/1NC 3NP5065 – 1CF00 3NP5065 – 1CF10 3NP5065 – 1CG00 3NP5065 – 1CG10 400 – 690 V AC, 220 V DC For surface mounting and switchboard install. in mm2 Auxiliary contacts2) 160 A Size 00 Flat pad connection Clamp connection 2.5 – 120 2.5 – 50 1NO/1NC 1NO/1NC 3NP5060 – 0EA86 3NP5060 – 0EB86 3NP54 250 A Size 1 Flat pad connection Clamp connection 6 – 150 35 – 120 1NO/1NC 1NO/1NC 3NP5260 – 0EA86 3NP5260 – 0EB86 690 440 (3 phases in series) 220 (2 phases in series with mounted fuse monitoring) 400 A 630 A Size 2 Size 3 Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 3NP5360 – 0EA86 3NP5460 – 0EA86 3NP52 3NP53 1) Rated conditional short-circuit current with fuses With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) 6 – 150 3NP5060 – 0CA00 3NP5060 – 0CA00 3NP5060 – 0CB00 3NP5060 – 0CB10 3NP5260 – 0CA00 3NP5260 – 0CA10 3NP5260 – 0CB00 3NP5260 – 0CB10 3NP5360 – 0CA00 3NP5360 – 0CA10 3NP5460 – 0CA00 3NP5460 – 0CA10 With fuse monitoring 3NP50 50/60 Hz V AC V DC Basic versions For 40 mm busbars1) Technical data Type Selection and ordering data 3NP5 high end series 2 For 40 mm busbars 00/160 50 15 00/160 100 23 00 1,600 160 00 800 160 100 1/250 2/400 3/630 50 50 50 25 40 50 160 A for additional values refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, …) 0 1,600 160 0 1,000 160 125 2 4,000 400 2 2,520 400 315 Flat pad connection at the bottom Clamp connection at the bottom Auxiliary contacts 2.5 –120 1NO/1NC 3NP5065 – 1EF86 2.5 – 50 1NO/1NC 3NP5065 – 1EG86 400/500 V AC 2 1 2,500 250 1 1,600 250 200 3 5,040 630 3 3,200 630 400 2 4,000 400 2 2,520 400 315 2) in mm With electronic fuse monitoring 1/250 2/400 3/630 100 50 50 32 40 60 1 2,500 250 1 1,280 250 160 Size 00 6 – 240 6 – 2 x 240 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A Size 00 Flat pad connection Clamp connection 1NO/1NC 1NO/1NC 3NP5060 – 0HA13 3NP5060 – 0HB13 250 A 400 A 630 A Size 1 Size 2 Size 3 Flat pad connection Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 1NO/1NC 3NP5260 – 0HA13 3NP5360 – 0HA13 3NP5460 – 0HA13 For 40 mm busbars1) 160 A Size 00 at Flat pad connection the bottom 2.5 –120 2.5 – 50 6 – 150 6 – 240 6 – 2 x 240 in mm2 Auxiliary contacts 2.5 – 120 1NO/1NC 3NP5065 – 1HF13 1) for mounting on 60 mm busbars, use devices “for surface mounting and installation” and 8US1 busbar adapters 2) optionally, 2 NO as signal outputs: Order No. 3NP5…–.E.26 3NP5 high end series – Accessories Accessories for 3NP50 Size 00 for 3NP52 Size 1 for 3NP53 Size 2 for 3NP54 Size 3 Clamp connection (1 set = 3 units) 3NY1903 2.5 – 50 mm2 3NY1907 35 – 120 mm2 – – Quick retaining plate between 2 mounting rails 3NY1995 – – – Adapter for mounting on 60 mm busbars 8US1291-4SB00 8US1210-4AG00 8US1210-4AG00 8US1210-4AG00 3NY1105 215 x 135 – – – 3NY1115 215 x 135 – – – 3NY1107 265 x 135 – – – 3NY1208 250 x 149 3NY1210 300 x 220 3NY1211 300 x 245 3NY1212 300 x 290 3NY1106 290 x 135 – – – 3NY1116 290 x 135 – – – 3NY1108 – – – – 3NY1241 3NY1245 3NY1245 Auxiliary contacts 1NO/1NC (= mounting set) 3NY3033 3NY3034 3NY3034 3NY3034 Sealing lug can be retrofitted (1 pkg. = 10 units) 3NY1940 – – – Molded-plastic masking frames Dimensions (H x W): for disconnectors without/with auxiliary contacts Dimensions (H x W): for disconnectors with auxiliary contacts Dimensions (H x W): Masking frame mounting set Dimensions (H x W): for mounting the disconnector in the front of the switchgear panel (masking frame and mounting parts) Cable lug cover Masking frame (H x W) for disconnectors without/ with auxiliary contacts Masking frame (H x W) for disconnectors with auxiliary contacts 2 separate covers for top/bottom 6 individual covers (L = 120 mm) for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog 8ZX1012-OHP54-5AB1 for masking frames and mounting sets for SIKUS installation distribution panels, refer to Catalogs I2.34 and 12.35 Subject to change without prior notice 08/02 | Bestell-Nr. EXXXXX-A190-PXXX | DISPO XXXXX | XXXXXXXXX PDWL.XX.X.XX WS 0802X.X | Printed in Germany Fuses for overload and short-circuit protection means: high short-circuit currents Siemens AG Automation and Drives Low Voltage Controls and Distribution P. O. Box 32 40, D-91050 Erlangen www.siemens.com/sentric can also be safely handled, favorably-priced backup protection, simple selectivity calculations and absolute reliability, even when short-circuits occur. The fuse 3NP5 – the rugged types for the toughest applications melts completely so that there is no residual risk as a result of contacts which may have welded together. When the disconnector is in the open position, Furthermore, 3NP5 have an extremely high AC-23 switching capacity. The switching gases which are formed are deflected into the disconnector using a sophisticated arc chamber design, instead of being discharged upwards and to the side. This means that operating personnel and plant sections and components in the vicinity are reliably protected. there is a visible isolating gap, which is often demanded, e. g. for maintenance purposes. And the optional mounted fuse monitoring offers additional security – fuse switch disconnectors 3NP for the highest plant availability and safety. Fuse monitoring: To allow monitoring of the fuses in the disconnectors, a permanently wired 3RV1 circuit-breaker is mounted on the fuse carrier. Fuses for your safety – 3NP4 and 3NP5 switch disconnectors ble to use other disconnectors available on the market. But the fast closing and arc deflection chambers of the 3NP5 come through with flying colors. 3NP5 provides the highest degree of safety for operating personnel and the plant, as main switch with high switching frequency and good AC-23 characteristics, e.g. for motor loads. Both of these ranges are climate-proof and correspond to IEC 60 947-3 and VDE 0660, Part 107. The fuses can be clearly identified through the large clear inspection window. Matching masking frames and complete, TSK-tested mounting sets are available both for the moldedplastic 8HP distribution system as well as for the various SIKUS distribution boards. 2 series in the range – the optimum handle on every application The 3NP4 series (sizes NH000 to NH3) offer the optimum solution for most applications. These range from power distribution in residential and commercial buildings, through flexible distribution stations up to power distribution systems in large industrial plants.They are also admirably suited as main and incoming feeder breakers in industry, for control systems, as well as in motor feeders or as backup protection for circuit-breakers. They have an integrated lug for sealing which is integrated as standard. This means that they can be used, without any restrictions, in meter cabinets and incoming main feeder boxes for buildings. The rugged 3NP5 series (sizes NH00 to NH3) provide reliable protection for all of the “tougher” applications. This is especially true in mining, in the steel industry, and also in the chemical industry, where sulphur-laden, or aggressive ambient conditions or hazardous locations make it almost impossi- The values for switching capacitors (e.g. for reactive power compensation) were also tested (refer to Catalog NSK, Section 12), and when used with SITOR semiconductor or 3NE1 double-protection fuses, 3NP disconnectors can be used to protect soft starters, AC drive converters and similar devices (tables with tested device-fuse combinations are provided in the NSK). Shock and vibration testing as well as special earthquake tests guarantee that the 3NP can be used in marine applications, nuclear power stations and similar safety-critical plants. high switching frequency for devices such as these. The erosion electrodes additionally extend the lifetime of the main contacts. The lateral spring mechanism (= fast switching) eliminates any danger as a result of incorrect operation, e.g. briefly actuating the disconnector or switching which is too slow. When the switch disconnector is in the ON position, the circuit-braker poles are connected in parallel with the fuses to be monitored. When the switch is in the OFF position, the poles of the circuit-breaker are dead. The 3NP5 disconnector series (sizes NH00 to NH3) for fixed installation can be quickly hung onto preinstalled mounting bolts. They can also be mounted on the front of switchgear panels using the matching mounting sets or they can be mounted onto 60 mm busbar systems using 8US1 adapters. The especially rugged design of this series (plastic with a high resistance to heat, metal parts which can be mechanically stressed), permits an unusually The internal resistance of the circuit-breaker is so high that it does not affect the protection given by the monitored fuses. Rated operational voltage Ue Electronic fuse monitoring (EFM): The electronic fuse monitoring system is also mounted on the fuse carrier of the 3NP5. It works whether or not a load is present. Fuse blowing can be signalled to a switch control room by means of a group indication (2NO contacts + 1NC contact). 2 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC 250 A Size 00 Size 1 Flat pad connection 2.5 – 120 Clamp connection 2.5 – 50 Flat pad connection Clamp connection Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) Rated operating current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B up to AC-23B A For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 35 – 120 400 A Size 2 Flat pad connection 6 – 240 630 A Size 3 Flat pad connection 6 – 2 x 240 160 A Size 00 in mm2 Auxiliary contacts Flat pad connection at the bottom 2.5 – 120 Clamp connection at the bottom 2.5 – 50 without 1NO/1NC without 1NO/1NC 3NP5065 – 1CF00 3NP5065 – 1CF10 3NP5065 – 1CG00 3NP5065 – 1CG10 400 – 690 V AC, 220 V DC For surface mounting and switchboard install. in mm2 Auxiliary contacts2) 160 A Size 00 Flat pad connection Clamp connection 2.5 – 120 2.5 – 50 1NO/1NC 1NO/1NC 3NP5060 – 0EA86 3NP5060 – 0EB86 3NP54 250 A Size 1 Flat pad connection Clamp connection 6 – 150 35 – 120 1NO/1NC 1NO/1NC 3NP5260 – 0EA86 3NP5260 – 0EB86 690 440 (3 phases in series) 220 (2 phases in series with mounted fuse monitoring) 400 A 630 A Size 2 Size 3 Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 3NP5360 – 0EA86 3NP5460 – 0EA86 3NP52 3NP53 1) Rated conditional short-circuit current with fuses With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) 6 – 150 3NP5060 – 0CA00 3NP5060 – 0CA00 3NP5060 – 0CB00 3NP5060 – 0CB10 3NP5260 – 0CA00 3NP5260 – 0CA10 3NP5260 – 0CB00 3NP5260 – 0CB10 3NP5360 – 0CA00 3NP5360 – 0CA10 3NP5460 – 0CA00 3NP5460 – 0CA10 With fuse monitoring 3NP50 50/60 Hz V AC V DC Basic versions For 40 mm busbars1) Technical data Type Selection and ordering data 3NP5 high end series 2 For 40 mm busbars 00/160 50 15 00/160 100 23 00 1,600 160 00 800 160 100 1/250 2/400 3/630 50 50 50 25 40 50 160 A for additional values refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, …) 0 1,600 160 0 1,000 160 125 2 4,000 400 2 2,520 400 315 Flat pad connection at the bottom Clamp connection at the bottom Auxiliary contacts 2.5 –120 1NO/1NC 3NP5065 – 1EF86 2.5 – 50 1NO/1NC 3NP5065 – 1EG86 400/500 V AC 2 1 2,500 250 1 1,600 250 200 3 5,040 630 3 3,200 630 400 2 4,000 400 2 2,520 400 315 2) in mm With electronic fuse monitoring 1/250 2/400 3/630 100 50 50 32 40 60 1 2,500 250 1 1,280 250 160 Size 00 6 – 240 6 – 2 x 240 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A Size 00 Flat pad connection Clamp connection 1NO/1NC 1NO/1NC 3NP5060 – 0HA13 3NP5060 – 0HB13 250 A 400 A 630 A Size 1 Size 2 Size 3 Flat pad connection Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 1NO/1NC 3NP5260 – 0HA13 3NP5360 – 0HA13 3NP5460 – 0HA13 For 40 mm busbars1) 160 A Size 00 at Flat pad connection the bottom 2.5 –120 2.5 – 50 6 – 150 6 – 240 6 – 2 x 240 in mm2 Auxiliary contacts 2.5 – 120 1NO/1NC 3NP5065 – 1HF13 1) for mounting on 60 mm busbars, use devices “for surface mounting and installation” and 8US1 busbar adapters 2) optionally, 2 NO as signal outputs: Order No. 3NP5…–.E.26 3NP5 high end series – Accessories Accessories for 3NP50 Size 00 for 3NP52 Size 1 for 3NP53 Size 2 for 3NP54 Size 3 Clamp connection (1 set = 3 units) 3NY1903 2.5 – 50 mm2 3NY1907 35 – 120 mm2 – – Quick retaining plate between 2 mounting rails 3NY1995 – – – Adapter for mounting on 60 mm busbars 8US1291-4SB00 8US1210-4AG00 8US1210-4AG00 8US1210-4AG00 3NY1105 215 x 135 – – – 3NY1115 215 x 135 – – – 3NY1107 265 x 135 – – – 3NY1208 250 x 149 3NY1210 300 x 220 3NY1211 300 x 245 3NY1212 300 x 290 3NY1106 290 x 135 – – – 3NY1116 290 x 135 – – – 3NY1108 – – – – 3NY1241 3NY1245 3NY1245 Auxiliary contacts 1NO/1NC (= mounting set) 3NY3033 3NY3034 3NY3034 3NY3034 Sealing lug can be retrofitted (1 pkg. = 10 units) 3NY1940 – – – Molded-plastic masking frames Dimensions (H x W): for disconnectors without/with auxiliary contacts Dimensions (H x W): for disconnectors with auxiliary contacts Dimensions (H x W): Masking frame mounting set Dimensions (H x W): for mounting the disconnector in the front of the switchgear panel (masking frame and mounting parts) Cable lug cover Masking frame (H x W) for disconnectors without/ with auxiliary contacts Masking frame (H x W) for disconnectors with auxiliary contacts 2 separate covers for top/bottom 6 individual covers (L = 120 mm) for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog 8ZX1012-OHP54-5AB1 for masking frames and mounting sets for SIKUS installation distribution panels, refer to Catalogs I2.34 and 12.35 Subject to change without prior notice 08/02 | Bestell-Nr. EXXXXX-A190-PXXX | DISPO XXXXX | XXXXXXXXX PDWL.XX.X.XX WS 0802X.X | Printed in Germany Fuses for overload and short-circuit protection means: high short-circuit currents Siemens AG Automation and Drives Low Voltage Controls and Distribution P. O. Box 32 40, D-91050 Erlangen www.siemens.com/sentric Selection and ordering data 3NP4 standard series 3NP4 standard Accessories for 3 Size Basic versions For surface mounting and switchboard install. Connection in mm2 160 A1) 160 A Size 000 Size 00 250 A 400 A 630 A Size Size Size 1.5 – 50 up to 2 x 70 (M8) 2.5 – 70 up to 150 (M10) up to 240 (M12) up to 2 x 240 (M12) 1 2 3 SIGUT terminal Flat pad connection SIGUT terminal Flat pad connection Flat pad connection Flat pad connection For 40 mm busbars2) 160 A1) 160 A Size 000 Size 00 Connection in mm2 SIGUT terminal Flat pad connection SIGUT terminal 250 A Size 1 Flat pad connection For 60 mm busbars 160 A1) 160 A Size 000 Size 00 400 A 630 A Size Size Size 1 2 3 With fuse monitoring 1.5 – 50 Connection, top Connection, bottom 3NP4015 – 1CK01 3NP4015 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4075 – 1CE01 3NP4075 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4075 – 1CK01 3NP4075 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4275– 1CG01 Connection in mm 2 SIGUT terminal Flat pad connection SIGUT terminal 250 A 3NP4010 – 0CH10 3NP4070 – 0CA01 3NP4070 – 0CH01 3NP4270 – 0CA01 3NP4370 – 0CA10 3NP4470 – 0CA01 Flat pad connection Flat pad connection Flat pad connection 1.5 – 50 Connection, top Connection, bottom 3NP4016 – 1CK01 3NP4016 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4076 – 1CE01 3NP4076 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4076 – 1CK01 3NP4076 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4276 – 1CG01 up to 240 (M12) top or bottom3) 3NP4376 – 1CG01 up to 2 x 240 (M12) top or bottom3) 3NP4476 – 1CG01 400 – 690 V AC, 220 V DC all of the versions specified above (except size 000) are also available with mounted fuse monitoring; Order No. supplement: 3NP4…–.F.01 1) 125 and 160 A only with special, 21-mm-wide fuses 3NY1822 and 3NY1824, refer to Accessories 2) Adapter depth, 28 mm; for disconnectors with deeper adapters (49 mm), refer to Catalog NSK, Section 12 3) Connection modules can be replaced, refer to the Instruction Manual Connection terminals (1 set = 3 units) connection: inte Cable lug cover (1 set = 3 units) safe from finger touch cover of the flat pad connection acc. to VBG4 not Auxiliary contact, 1 changeover contact normal version electronics-compatible Quick retaining plate to mount the disconnectors between two mounting rails (125 mm clearance) 3NY 3NY 3NY Busbar width compensation only for 5 mm busbars not for 10 mm busbars brea Three-way terminal (1 set = 3 units) to connect 3 x 2.5 – 16 mm2 (e/m) or 3 x 2.5 – 10 mm2 (finely stranded with end sleeves) for mounting onto a SIGUT terminal for mounting onto a flat pad connection 3-phase busbars for 2 disconnectors for 3 disconnectors for 4 disconnectors connecting buses for > 4 disconnectors cap for empty location (20x units): Incoming supply terminal (1 set = 3 units) for conductors e/m: up to 95 mm2 finely stranded with end sleeves: up to 70 mm2 3NY – 3NY 3NY 3NY 3NY 3NY 3NY Fuse links, size 000 21 mm wide, Duty class gL/gC 400 V/125 A 3NY 400 V/160 A 3NY Sealing pin can be retrofitted (1 pkg. = 10 units) Masking frames for mounting in general distribution systems for disconnectors with SIGUT terminal for disconnectors with flat pad connection Dimensions (H x W): Overreach protection (10 units) inte 3NY – 215 inte for spare parts, refer to Catalog N for masking frames and mountin E20001-8ZX1012-OHP54-5AB1 Selection and ordering data 3NP4 standard series 3NP4 standard series – Accessories Accessories Basic versions For surface mounting and switchboard install. Connection in mm2 160 A1) 160 A Size 000 Size 00 250 A 400 A 630 A Size Size Size 1.5 – 50 up to 2 x 70 (M8) 2.5 – 70 up to 150 (M10) up to 240 (M12) up to 2 x 240 (M12) 1 2 3 SIGUT terminal Flat pad connection SIGUT terminal Flat pad connection Flat pad connection Flat pad connection For 40 mm busbars2) 160 A1) 160 A Size 000 Size 00 Connection in mm2 SIGUT terminal Flat pad connection SIGUT terminal 250 A Size 1 Flat pad connection For 60 mm busbars 160 A1) 160 A Size 000 Size 00 400 A 630 A Size Size Size 1 2 3 With fuse monitoring 1.5 – 50 Connection, top Connection, bottom 3NP4015 – 1CK01 3NP4015 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4075 – 1CE01 3NP4075 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4075 – 1CK01 3NP4075 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4275– 1CG01 Connection in mm 2 SIGUT terminal Flat pad connection SIGUT terminal 250 A 3NP4010 – 0CH10 3NP4070 – 0CA01 3NP4070 – 0CH01 3NP4270 – 0CA01 3NP4370 – 0CA10 3NP4470 – 0CA01 Flat pad connection Flat pad connection Flat pad connection 1.5 – 50 Connection, top Connection, bottom 3NP4016 – 1CK01 3NP4016 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4076 – 1CE01 3NP4076 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4076 – 1CK01 3NP4076 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4276 – 1CG01 up to 240 (M12) top or bottom3) 3NP4376 – 1CG01 up to 2 x 240 (M12) top or bottom3) 3NP4476 – 1CG01 400 – 690 V AC, 220 V DC all of the versions specified above (except size 000) are also available with mounted fuse monitoring; Order No. supplement: 3NP4…–.F.01 1) 125 and 160 A only with special, 21-mm-wide fuses 3NY1822 and 3NY1824, refer to Accessories 2) Adapter depth, 28 mm; for disconnectors with deeper adapters (49 mm), refer to Catalog NSK, Section 12 3) Connection modules can be replaced, refer to the Instruction Manual for 3NP401 Size 000 for 3NP407 Size 00 for 3NP42 Size 1 for 3NP43 Size 2 Connection terminals (1 set = 3 units) connection: integrated integrated 3NY7120 70 – 150 mm2 3NY7130 3NY7140 120 – 240 mm2 150 – 300 mm2 Cable lug cover (1 set = 3 units) safe from finger touch cover of the flat pad connection acc. to VBG4 not required 3NY7101 3NY7121 3NY7131 3NY7141 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY1995 3NY1995 3NY7322 – – Auxiliary contact, 1 changeover contact normal version electronics-compatible Quick retaining plate to mount the disconnectors between two mounting rails (125 mm clearance) for 3NP44 Size 3 3NP4 – quickly mou Busbar width compensation only for 5 mm busbars not required for 10 mm busbars break-off not required break-off 3NY7381 not required 3NY7381 not required not possible not required 3NY7102 3NY7102 – – – – 3NY7105 – – – 3NY1237 3NY1238 3NY1438 – – – – – – – – – – – – 3NY1263 3NY1265 – – – – – – – – 3NY1236 – – – – Fuse links, size 000 21 mm wide, Duty class gL/gC 400 V/125 A 3NY1822 400 V/160 A 3NY1824 – – – – – – – – integrated integrated 3NY7482 3NY7482 3NY7482 3NY1251 3NY7200 – – – – 215 x 130 3NY7201 215 x 130 3NY7220 375 x 220 3NY7230 375 x 245 3NY7240 375 x 290 integrated integrated 3NY7481 3NY7481 3NY7481 Three-way terminal (1 set = 3 units) to connect 3 x 2.5 – 16 mm2 (e/m) or 3 x 2.5 – 10 mm2 (finely stranded with end sleeves) for mounting onto a SIGUT terminal for mounting onto a flat pad connection 3-phase busbars for 2 disconnectors for 3 disconnectors for 4 disconnectors connecting buses for > 4 disconnectors cap for empty location (20x units): Incoming supply terminal (1 set = 3 units) for conductors e/m: up to 95 mm2 finely stranded with end sleeves: up to 70 mm2 Sealing pin can be retrofitted (1 pkg. = 10 units) Masking frames for mounting in general distribution systems for disconnectors with SIGUT terminal for disconnectors with flat pad connection Dimensions (H x W): Overreach protection (10 units) for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog E20001-8ZX1012-OHP54-5AB1 All-around safety With the cable lug covers cor enclosed disconnectors offer protection, even after a volta holes in the withdrawable fus with SIGUT terminals are com touch without any additional The large clear inspection win and the operating statuses of quickly and reliably identified around touch protection is al the withdrawable fuse carrier Size 1 shock protection is ava At home on all busbars All 3NP4 sizes are available fo busbar center clearance. Busb 10 mm wide. For 10 mm bus 00, two lugs must be broken busbar clamps. Busbar compe as accessory for mounting siz busbars (size 3 disconnectors snapped onto 5 mm busbars) By simply snapping onto the the disconnectors can also be double T profiles as well as on from the Rittal company, with of the busbars preventing this Selection and ordering data 3NP4 standard series 3NP4 standard series – Accessories Accessories Basic versions For surface mounting and switchboard install. Connection in mm2 160 A1) 160 A Size 000 Size 00 250 A 400 A 630 A Size Size Size 1.5 – 50 up to 2 x 70 (M8) 2.5 – 70 up to 150 (M10) up to 240 (M12) up to 2 x 240 (M12) 1 2 3 SIGUT terminal Flat pad connection SIGUT terminal Flat pad connection Flat pad connection Flat pad connection For 40 mm busbars2) 160 A1) 160 A Size 000 Size 00 Flat pad connection SIGUT terminal 250 A Size 1 Flat pad connection For 60 mm busbars 160 A1) 160 A Size 000 Size 00 400 A 630 A Size Size Size 1 2 3 With fuse monitoring 1.5 – 50 Connection, top Connection, bottom up to 2 x 70 (M8) Connection, top Connection, bottom 2.5 – 70 Connection, top Connection, bottom up to 150 (M10) top or bottom3) 3NP4015 – 1CK01 3NP4015 – 1CJ01 3NP4075 – 1CE01 3NP4075 – 1CF01 3NP4075 – 1CK01 3NP4075 – 1CJ01 3NP4275– 1CG01 Connection in mm2 SIGUT terminal Flat pad connection SIGUT terminal 250 A 3NP4010 – 0CH10 3NP4070 – 0CA01 3NP4070 – 0CH01 3NP4270 – 0CA01 3NP4370 – 0CA10 3NP4470 – 0CA01 Connection in mm2 SIGUT terminal Flat pad connection Flat pad connection Flat pad connection By simply snapping onto the busbars from the top, the disconnectors can also be mounted onto T or double T profiles as well as onto Power-Line systems from the Rittal company, without the horizontal parts of the busbars preventing this. 1.5 – 50 Connection, top Connection, bottom 3NP4016 – 1CK01 3NP4016 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4076 – 1CE01 3NP4076 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4076 – 1CK01 3NP4076 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4276 – 1CG01 up to 240 (M12) top or bottom3) 3NP4376 – 1CG01 up to 2 x 240 (M12) top or bottom3) 3NP4476 – 1CG01 400 – 690 V AC, 220 V DC all of the versions specified above (except size 000) are also available with mounted fuse monitoring; Order No. supplement: 3NP4…–.F.01 1) 125 and 160 A only with special, 21-mm-wide fuses 3NY1822 and 3NY1824, refer to Accessories 2) Adapter depth, 28 mm; for disconnectors with deeper adapters (49 mm), refer to Catalog NSK, Section 12 3) Connection modules can be replaced, refer to the Instruction Manual for 3NP401 Size 000 for 3NP407 Size 00 for 3NP42 Size 1 for 3NP43 Size 2 Connection terminals (1 set = 3 units) connection: integrated integrated 3NY7120 70 – 150 mm2 3NY7130 3NY7140 120 – 240 mm2 150 – 300 mm2 Cable lug cover (1 set = 3 units) safe from finger touch cover of the flat pad connection acc. to VBG4 not required 3NY7101 3NY7121 3NY7131 Auxiliary contact, 1 changeover contact normal version electronics-compatible Quick retaining plate to mount the disconnectors between two mounting rails (125 mm clearance) 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY1995 3NY1995 3NY7322 – – 3-phase busbars for 2 disconnectors for 3 disconnectors for 4 disconnectors connecting buses for > 4 disconnectors cap for empty location (20x units): Incoming supply terminal (1 set = 3 units) for conductors e/m: up to 95 mm2 finely stranded with end sleeves: up to 70 mm2 Masking frames for mounting in general distribution systems for disconnectors with SIGUT terminal for disconnectors with flat pad connection Dimensions (H x W): Overreach protection (10 units) The circuit-breaker is connected in parallel to the three main disconnector phases, and is tripped as soon as at least one of three fuses blows. The voltage is tapped at the handle lugs of the fuses which means that only fuses with live grip lugs can be used. not required break-off 3NY7381 not required 3NY7381 not required not possible not required 3NY7102 3NY7102 – – – – 3NY7105 – – – 3NY1237 3NY1238 3NY1438 – – – – – – – – – – – – 3NY1263 3NY1265 – – – – – – – – 3NY1236 – – – – integrated – – – – – – – – integrated 3NY7482 3NY7482 3NY7482 3NY1251 3NY7200 – – – – 215 x 130 3NY7201 215 x 130 3NY7220 375 x 220 3NY7230 375 x 245 3NY7240 375 x 290 integrated integrated 3NY7481 3NY7481 3NY7481 for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog E20001-8ZX1012-OHP54-5AB1 This button prevents the shock protection from being inserted as long as the latching mechanism hasn’t correctly latched into place. Allaround safety With the cable lug covers correctly mounted, the enclosed disconnectors offer a high IP 30 degree of protection, even after a voltage test using the 6 test holes in the withdrawable fuse carrier. The versions with SIGUT terminals are completely safe from finger touch without any additional covers. The large clear inspection window allows the type and the operating statuses of the fuse links to be quickly and reliably identified. Overreach and reacharound touch protection is already integrated into the withdrawable fuse carrier up to 160 A; from Size 1 shock protection is available as accessory. At home on all busbars All 3NP4 sizes are available for 40 mm or 60 mm busbar center clearance. Busbars can either be 5 or 10 mm wide. For 10 mm busbars, for sizes 000 and 00, two lugs must be broken off at the three rear busbar clamps. Busbar compensation is available as accessory for mounting sizes 1 and 2 onto 5 mm busbars (size 3 disconnectors cannot only be snapped onto 5 mm busbars). Quickly mounted … All of these features reduce valuable mounting and installation time. It also means that the correct tightening torque of the screws doesn’t have to be checked and adjusted. The mounting rail latching mechanisms, integrated into the basic size 000 and 00 devices, also provide a clear financial benefit, especially, where up to 160 A disconnectors are used in larger unit quantities: additional screws, hooks, intermediate plates or a second mounting rail are not required. Smart accessories for every application The auxiliary contacts, which fit all sizes, can be subsequently retrofitted without taking up any extra space. The three-way terminal makes it easy to connect up to 3 cables (e. g. for capacitor protection). Several disconnectors can be fed in parallel using the 3-phase busbars, connecting buses and feeder terminals up to 225 A. Numerous masking frames and mounting sets for SIKUS distribution boards or the 8HP distribution system guarantee simple engineering and fast mounting and installation. 3NP Fuse Switch Disconnector – the Optimum Handle on Every Application 1NO/1NC signal outputs are used as standard. For size 00, they are brought out to a connector socket at the front, and for sizes 1 to 3, as double AMP flat connector at the shock protection in the lower section of the disconnector. Either pre-assembled 1- or 3-m cables with strain relief can be used as connecting cable for size 00. These can then be easily inserted at the fuse monitoring using the mounted connectors. There are also connector mounting sets for crimping (short-circuit proof) cables. 3NP4 – quickly mounted onto all busbars Fuse links, size 000 21 mm wide, Duty class gL/gC 400 V/125 A 3NY1822 400 V/160 A 3NY1824 Sealing pin can be retrofitted (1 pkg. = 10 units) can frequently occur, e. g. in line supplies with AC drive converters and inverters. Intelligent latching mechanism This automatically adapts itself to busbar widths between 5 and 30 mm, and it reliably latches into place. This eliminates numerous versions and complicated adjustments before mounting. There is a small red button inside the switch, which, especially from size 1, ensures that the disconnector is really mounted onto the busbar to its endstop. 3NY7141 3NY3035 3NY3030 Busbar width compensation only for 5 mm busbars not required for 10 mm busbars break-off Three-way terminal (1 set = 3 units) to connect 3 x 2.5 – 16 mm2 (e/m) or 3 x 2.5 – 10 mm2 (finely stranded with end sleeves) for mounting onto a SIGUT terminal for mounting onto a flat pad connection for 3NP44 Size 3 Fuse monitoring for 3NP4 From size NH00 onwards, all of the 3NP4 versions are also available with fuse monitoring. This is realized using 3RV SIRIUS circuit-breakers which are mounted at the front in the center of the fuse carrier. Flat connectors are always used for sizes 1–3. The disconnector can then be fed as required from either the top or the bottom, whereby voltages up to 690 V AC/220 V DC are possible. Furthermore, this type of fuse monitoring is completely insensitive to EMC disturbances and harmonics. These disturbances The function of the 3RV can be tested at any time using the test button provided. Technical data Type Rated operational voltage Ue 3NP401 AC 50/60 Hz V DC V 3NP40 7 3NP42 3NP43 3NP44 690 690 220 (3 phases in series) 440 (2 phases in series) with mounted fuse monitoring upt to 220 V DC max. Rated conditional short-circuit current with fuses (for fast closing) With fuse links rated current Size/A For 400 V AC (690 V) kA (RMS value) Permissible fuse cut-off current kA (peak value) 000/100 (35) 00/160 50 (50) 50 11 (5) 15 1/250 50 25 2/400 50 35 3/630 50 55 Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A Up to 690 V kA (RMS value) Permissible fuse cut-off current kA (peak value) 000/100 100 15 00/160 50 15 1/250 50 25 2/400 50 35 3/630 50 55 Rated operational current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 000 800 160 100 00 800 160 100 1 2,000 250 250 2 3,200 400 400 3 5,040 630 630 For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B A AC-22B A AC-23B A 000 240 160 50 25 00 240 160 50 25 1 375 250 – – 2 600 400 – – 3 945 630 – – for additional values, refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, ...) sentric Selection and ordering data 3NP4 standard series 3NP4 standard series – Accessories Accessories Basic versions For surface mounting and switchboard install. Connection in mm2 160 A1) 160 A Size 000 Size 00 250 A 400 A 630 A Size Size Size 1.5 – 50 up to 2 x 70 (M8) 2.5 – 70 up to 150 (M10) up to 240 (M12) up to 2 x 240 (M12) 1 2 3 SIGUT terminal Flat pad connection SIGUT terminal Flat pad connection Flat pad connection Flat pad connection For 40 mm busbars2) 160 A1) 160 A Size 000 Size 00 Flat pad connection SIGUT terminal 250 A Size 1 Flat pad connection For 60 mm busbars 160 A1) 160 A Size 000 Size 00 400 A 630 A Size Size Size 1 2 3 With fuse monitoring 1.5 – 50 Connection, top Connection, bottom up to 2 x 70 (M8) Connection, top Connection, bottom 2.5 – 70 Connection, top Connection, bottom up to 150 (M10) top or bottom3) 3NP4015 – 1CK01 3NP4015 – 1CJ01 3NP4075 – 1CE01 3NP4075 – 1CF01 3NP4075 – 1CK01 3NP4075 – 1CJ01 3NP4275– 1CG01 Connection in mm2 SIGUT terminal Flat pad connection SIGUT terminal 250 A 3NP4010 – 0CH10 3NP4070 – 0CA01 3NP4070 – 0CH01 3NP4270 – 0CA01 3NP4370 – 0CA10 3NP4470 – 0CA01 Connection in mm2 SIGUT terminal Flat pad connection Flat pad connection Flat pad connection By simply snapping onto the busbars from the top, the disconnectors can also be mounted onto T or double T profiles as well as onto Power-Line systems from the Rittal company, without the horizontal parts of the busbars preventing this. 1.5 – 50 Connection, top Connection, bottom 3NP4016 – 1CK01 3NP4016 – 1CJ01 up to 2 x 70 (M8) Connection, top Connection, bottom 3NP4076 – 1CE01 3NP4076 – 1CF01 2.5 – 70 Connection, top Connection, bottom 3NP4076 – 1CK01 3NP4076 – 1CJ01 up to 150 (M10) top or bottom3) 3NP4276 – 1CG01 up to 240 (M12) top or bottom3) 3NP4376 – 1CG01 up to 2 x 240 (M12) top or bottom3) 3NP4476 – 1CG01 400 – 690 V AC, 220 V DC all of the versions specified above (except size 000) are also available with mounted fuse monitoring; Order No. supplement: 3NP4…–.F.01 1) 125 and 160 A only with special, 21-mm-wide fuses 3NY1822 and 3NY1824, refer to Accessories 2) Adapter depth, 28 mm; for disconnectors with deeper adapters (49 mm), refer to Catalog NSK, Section 12 3) Connection modules can be replaced, refer to the Instruction Manual for 3NP401 Size 000 for 3NP407 Size 00 for 3NP42 Size 1 for 3NP43 Size 2 Connection terminals (1 set = 3 units) connection: integrated integrated 3NY7120 70 – 150 mm2 3NY7130 3NY7140 120 – 240 mm2 150 – 300 mm2 Cable lug cover (1 set = 3 units) safe from finger touch cover of the flat pad connection acc. to VBG4 not required 3NY7101 3NY7121 3NY7131 Auxiliary contact, 1 changeover contact normal version electronics-compatible Quick retaining plate to mount the disconnectors between two mounting rails (125 mm clearance) 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY3035 3NY3030 3NY1995 3NY1995 3NY7322 – – 3-phase busbars for 2 disconnectors for 3 disconnectors for 4 disconnectors connecting buses for > 4 disconnectors cap for empty location (20x units): Incoming supply terminal (1 set = 3 units) for conductors e/m: up to 95 mm2 finely stranded with end sleeves: up to 70 mm2 Masking frames for mounting in general distribution systems for disconnectors with SIGUT terminal for disconnectors with flat pad connection Dimensions (H x W): Overreach protection (10 units) The circuit-breaker is connected in parallel to the three main disconnector phases, and is tripped as soon as at least one of three fuses blows. The voltage is tapped at the handle lugs of the fuses which means that only fuses with live grip lugs can be used. not required break-off 3NY7381 not required 3NY7381 not required not possible not required 3NY7102 3NY7102 – – – – 3NY7105 – – – 3NY1237 3NY1238 3NY1438 – – – – – – – – – – – – 3NY1263 3NY1265 – – – – – – – – 3NY1236 – – – – integrated – – – – – – – – integrated 3NY7482 3NY7482 3NY7482 3NY1251 3NY7200 – – – – 215 x 130 3NY7201 215 x 130 3NY7220 375 x 220 3NY7230 375 x 245 3NY7240 375 x 290 integrated integrated 3NY7481 3NY7481 3NY7481 for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog E20001-8ZX1012-OHP54-5AB1 This button prevents the shock protection from being inserted as long as the latching mechanism hasn’t correctly latched into place. Allaround safety With the cable lug covers correctly mounted, the enclosed disconnectors offer a high IP 30 degree of protection, even after a voltage test using the 6 test holes in the withdrawable fuse carrier. The versions with SIGUT terminals are completely safe from finger touch without any additional covers. The large clear inspection window allows the type and the operating statuses of the fuse links to be quickly and reliably identified. Overreach and reacharound touch protection is already integrated into the withdrawable fuse carrier up to 160 A; from Size 1 shock protection is available as accessory. At home on all busbars All 3NP4 sizes are available for 40 mm or 60 mm busbar center clearance. Busbars can either be 5 or 10 mm wide. For 10 mm busbars, for sizes 000 and 00, two lugs must be broken off at the three rear busbar clamps. Busbar compensation is available as accessory for mounting sizes 1 and 2 onto 5 mm busbars (size 3 disconnectors cannot only be snapped onto 5 mm busbars). Quickly mounted … All of these features reduce valuable mounting and installation time. It also means that the correct tightening torque of the screws doesn’t have to be checked and adjusted. The mounting rail latching mechanisms, integrated into the basic size 000 and 00 devices, also provide a clear financial benefit, especially, where up to 160 A disconnectors are used in larger unit quantities: additional screws, hooks, intermediate plates or a second mounting rail are not required. Smart accessories for every application The auxiliary contacts, which fit all sizes, can be subsequently retrofitted without taking up any extra space. The three-way terminal makes it easy to connect up to 3 cables (e. g. for capacitor protection). Several disconnectors can be fed in parallel using the 3-phase busbars, connecting buses and feeder terminals up to 225 A. Numerous masking frames and mounting sets for SIKUS distribution boards or the 8HP distribution system guarantee simple engineering and fast mounting and installation. 3NP Fuse Switch Disconnector – the Optimum Handle on Every Application 1NO/1NC signal outputs are used as standard. For size 00, they are brought out to a connector socket at the front, and for sizes 1 to 3, as double AMP flat connector at the shock protection in the lower section of the disconnector. Either pre-assembled 1- or 3-m cables with strain relief can be used as connecting cable for size 00. These can then be easily inserted at the fuse monitoring using the mounted connectors. There are also connector mounting sets for crimping (short-circuit proof) cables. 3NP4 – quickly mounted onto all busbars Fuse links, size 000 21 mm wide, Duty class gL/gC 400 V/125 A 3NY1822 400 V/160 A 3NY1824 Sealing pin can be retrofitted (1 pkg. = 10 units) can frequently occur, e. g. in line supplies with AC drive converters and inverters. Intelligent latching mechanism This automatically adapts itself to busbar widths between 5 and 30 mm, and it reliably latches into place. This eliminates numerous versions and complicated adjustments before mounting. There is a small red button inside the switch, which, especially from size 1, ensures that the disconnector is really mounted onto the busbar to its endstop. 3NY7141 3NY3035 3NY3030 Busbar width compensation only for 5 mm busbars not required for 10 mm busbars break-off Three-way terminal (1 set = 3 units) to connect 3 x 2.5 – 16 mm2 (e/m) or 3 x 2.5 – 10 mm2 (finely stranded with end sleeves) for mounting onto a SIGUT terminal for mounting onto a flat pad connection for 3NP44 Size 3 Fuse monitoring for 3NP4 From size NH00 onwards, all of the 3NP4 versions are also available with fuse monitoring. This is realized using 3RV SIRIUS circuit-breakers which are mounted at the front in the center of the fuse carrier. Flat connectors are always used for sizes 1–3. The disconnector can then be fed as required from either the top or the bottom, whereby voltages up to 690 V AC/220 V DC are possible. Furthermore, this type of fuse monitoring is completely insensitive to EMC disturbances and harmonics. These disturbances The function of the 3RV can be tested at any time using the test button provided. Technical data Type Rated operational voltage Ue 3NP401 AC 50/60 Hz V DC V 3NP40 7 3NP42 3NP43 3NP44 690 690 220 (3 phases in series) 440 (2 phases in series) with mounted fuse monitoring upt to 220 V DC max. Rated conditional short-circuit current with fuses (for fast closing) With fuse links rated current Size/A For 400 V AC (690 V) kA (RMS value) Permissible fuse cut-off current kA (peak value) 000/100 (35) 00/160 50 (50) 50 11 (5) 15 1/250 50 25 2/400 50 35 3/630 50 55 Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A Up to 690 V kA (RMS value) Permissible fuse cut-off current kA (peak value) 000/100 100 15 00/160 50 15 1/250 50 25 2/400 50 35 3/630 50 55 Rated operational current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 000 800 160 100 00 800 160 100 1 2,000 250 250 2 3,200 400 400 3 5,040 630 630 For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B A AC-22B A AC-23B A 000 240 160 50 25 00 240 160 50 25 1 375 250 – – 2 600 400 – – 3 945 630 – – for additional values, refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, ...) sentric can also be safely handled, favorably-priced backup protection, simple selectivity calculations and absolute reliability, even when short-circuits occur. The fuse 3NP5 – the rugged types for the toughest applications melts completely so that there is no residual risk as a result of contacts which may have welded together. When the disconnector is in the open position, Furthermore, 3NP5 have an extremely high AC-23 switching capacity. The switching gases which are formed are deflected into the disconnector using a sophisticated arc chamber design, instead of being discharged upwards and to the side. This means that operating personnel and plant sections and components in the vicinity are reliably protected. there is a visible isolating gap, which is often demanded, e. g. for maintenance purposes. And the optional mounted fuse monitoring offers additional security – fuse switch disconnectors 3NP for the highest plant availability and safety. Fuse monitoring: To allow monitoring of the fuses in the disconnectors, a permanently wired 3RV1 circuit-breaker is mounted on the fuse carrier. Fuses for your safety – 3NP4 and 3NP5 switch disconnectors ble to use other disconnectors available on the market. But the fast closing and arc deflection chambers of the 3NP5 come through with flying colors. 3NP5 provides the highest degree of safety for operating personnel and the plant, as main switch with high switching frequency and good AC-23 characteristics, e.g. for motor loads. Both of these ranges are climate-proof and correspond to IEC 60 947-3 and VDE 0660, Part 107. The fuses can be clearly identified through the large clear inspection window. Matching masking frames and complete, TSK-tested mounting sets are available both for the moldedplastic 8HP distribution system as well as for the various SIKUS distribution boards. 2 series in the range – the optimum handle on every application The 3NP4 series (sizes NH000 to NH3) offer the optimum solution for most applications. These range from power distribution in residential and commercial buildings, through flexible distribution stations up to power distribution systems in large industrial plants.They are also admirably suited as main and incoming feeder breakers in industry, for control systems, as well as in motor feeders or as backup protection for circuit-breakers. They have an integrated lug for sealing which is integrated as standard. This means that they can be used, without any restrictions, in meter cabinets and incoming main feeder boxes for buildings. The rugged 3NP5 series (sizes NH00 to NH3) provide reliable protection for all of the “tougher” applications. This is especially true in mining, in the steel industry, and also in the chemical industry, where sulphur-laden, or aggressive ambient conditions or hazardous locations make it almost impossi- The values for switching capacitors (e.g. for reactive power compensation) were also tested (refer to Catalog NSK, Section 12), and when used with SITOR semiconductor or 3NE1 double-protection fuses, 3NP disconnectors can be used to protect soft starters, AC drive converters and similar devices (tables with tested device-fuse combinations are provided in the NSK). Shock and vibration testing as well as special earthquake tests guarantee that the 3NP can be used in marine applications, nuclear power stations and similar safety-critical plants. high switching frequency for devices such as these. The erosion electrodes additionally extend the lifetime of the main contacts. The lateral spring mechanism (= fast switching) eliminates any danger as a result of incorrect operation, e.g. briefly actuating the disconnector or switching which is too slow. When the switch disconnector is in the ON position, the circuit-braker poles are connected in parallel with the fuses to be monitored. When the switch is in the OFF position, the poles of the circuit-breaker are dead. The 3NP5 disconnector series (sizes NH00 to NH3) for fixed installation can be quickly hung onto preinstalled mounting bolts. They can also be mounted on the front of switchgear panels using the matching mounting sets or they can be mounted onto 60 mm busbar systems using 8US1 adapters. The especially rugged design of this series (plastic with a high resistance to heat, metal parts which can be mechanically stressed), permits an unusually The internal resistance of the circuit-breaker is so high that it does not affect the protection given by the monitored fuses. Rated operational voltage Ue Electronic fuse monitoring (EFM): The electronic fuse monitoring system is also mounted on the fuse carrier of the 3NP5. It works whether or not a load is present. Fuse blowing can be signalled to a switch control room by means of a group indication (2NO contacts + 1NC contact). 2 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC without 1NO/1NC 250 A Size 00 Size 1 Flat pad connection 2.5 – 120 Clamp connection 2.5 – 50 Flat pad connection Clamp connection Short-circuit strength with fuse (with the disconnector closed) With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) Rated operating current and switching capacity (supply from either the top or bottom) For 400 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B up to AC-23B A For 690 V AC, with fuse links or isolating links Size Rated breaking current Ic (cos p = 0.35) A (RMS value) Rated operating current Ie for AC-21B, AC-22B A AC-23B A 35 – 120 400 A Size 2 Flat pad connection 6 – 240 630 A Size 3 Flat pad connection 6 – 2 x 240 160 A Size 00 in mm2 Auxiliary contacts Flat pad connection at the bottom 2.5 – 120 Clamp connection at the bottom 2.5 – 50 without 1NO/1NC without 1NO/1NC 3NP5065 – 1CF00 3NP5065 – 1CF10 3NP5065 – 1CG00 3NP5065 – 1CG10 400 – 690 V AC, 220 V DC For surface mounting and switchboard install. in mm2 Auxiliary contacts2) 160 A Size 00 Flat pad connection Clamp connection 2.5 – 120 2.5 – 50 1NO/1NC 1NO/1NC 3NP5060 – 0EA86 3NP5060 – 0EB86 3NP54 250 A Size 1 Flat pad connection Clamp connection 6 – 150 35 – 120 1NO/1NC 1NO/1NC 3NP5260 – 0EA86 3NP5260 – 0EB86 690 440 (3 phases in series) 220 (2 phases in series with mounted fuse monitoring) 400 A 630 A Size 2 Size 3 Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 3NP5360 – 0EA86 3NP5460 – 0EA86 3NP52 3NP53 1) Rated conditional short-circuit current with fuses With fuse links rated current Size/A For 500 V AC kA (RMS value) Permissible fuse cut-off current kA (peak value) 6 – 150 3NP5060 – 0CA00 3NP5060 – 0CA00 3NP5060 – 0CB00 3NP5060 – 0CB10 3NP5260 – 0CA00 3NP5260 – 0CA10 3NP5260 – 0CB00 3NP5260 – 0CB10 3NP5360 – 0CA00 3NP5360 – 0CA10 3NP5460 – 0CA00 3NP5460 – 0CA10 With fuse monitoring 3NP50 50/60 Hz V AC V DC Basic versions For 40 mm busbars1) Technical data Type Selection and ordering data 3NP5 high end series 2 For 40 mm busbars 00/160 50 15 00/160 100 23 00 1,600 160 00 800 160 100 1/250 2/400 3/630 50 50 50 25 40 50 160 A for additional values refer to Catalog NSK, Section 12 (e. g. capacitor and DC switching capacity, switching capacity at 500 V AC, …) 0 1,600 160 0 1,000 160 125 2 4,000 400 2 2,520 400 315 Flat pad connection at the bottom Clamp connection at the bottom Auxiliary contacts 2.5 –120 1NO/1NC 3NP5065 – 1EF86 2.5 – 50 1NO/1NC 3NP5065 – 1EG86 400/500 V AC 2 1 2,500 250 1 1,600 250 200 3 5,040 630 3 3,200 630 400 2 4,000 400 2 2,520 400 315 2) in mm With electronic fuse monitoring 1/250 2/400 3/630 100 50 50 32 40 60 1 2,500 250 1 1,280 250 160 Size 00 6 – 240 6 – 2 x 240 For surface mounting and switchboard install. in mm Auxiliary contacts 160 A Size 00 Flat pad connection Clamp connection 1NO/1NC 1NO/1NC 3NP5060 – 0HA13 3NP5060 – 0HB13 250 A 400 A 630 A Size 1 Size 2 Size 3 Flat pad connection Flat pad connection Flat pad connection 1NO/1NC 1NO/1NC 1NO/1NC 3NP5260 – 0HA13 3NP5360 – 0HA13 3NP5460 – 0HA13 For 40 mm busbars1) 160 A Size 00 at Flat pad connection the bottom 2.5 –120 2.5 – 50 6 – 150 6 – 240 6 – 2 x 240 in mm2 Auxiliary contacts 2.5 – 120 1NO/1NC 3NP5065 – 1HF13 1) for mounting on 60 mm busbars, use devices “for surface mounting and installation” and 8US1 busbar adapters 2) optionally, 2 NO as signal outputs: Order No. 3NP5…–.E.26 3NP5 high end series – Accessories Accessories for 3NP50 Size 00 for 3NP52 Size 1 for 3NP53 Size 2 for 3NP54 Size 3 Clamp connection (1 set = 3 units) 3NY1903 2.5 – 50 mm2 3NY1907 35 – 120 mm2 – – Quick retaining plate between 2 mounting rails 3NY1995 – – – Adapter for mounting on 60 mm busbars 8US1291-4SB00 8US1210-4AG00 8US1210-4AG00 8US1210-4AG00 3NY1105 215 x 135 – – – 3NY1115 215 x 135 – – – 3NY1107 265 x 135 – – – 3NY1208 250 x 149 3NY1210 300 x 220 3NY1211 300 x 245 3NY1212 300 x 290 3NY1106 290 x 135 – – – 3NY1116 290 x 135 – – – 3NY1108 – – – – 3NY1241 3NY1245 3NY1245 Auxiliary contacts 1NO/1NC (= mounting set) 3NY3033 3NY3034 3NY3034 3NY3034 Sealing lug can be retrofitted (1 pkg. = 10 units) 3NY1940 – – – Molded-plastic masking frames Dimensions (H x W): for disconnectors without/with auxiliary contacts Dimensions (H x W): for disconnectors with auxiliary contacts Dimensions (H x W): Masking frame mounting set Dimensions (H x W): for mounting the disconnector in the front of the switchgear panel (masking frame and mounting parts) Cable lug cover Masking frame (H x W) for disconnectors without/ with auxiliary contacts Masking frame (H x W) for disconnectors with auxiliary contacts 2 separate covers for top/bottom 6 individual covers (L = 120 mm) for spare parts, refer to Catalog NSK, Section 12 for masking frames and mounting sets for 8HP molded-plastic distribution systems, refer to Catalog 8ZX1012-OHP54-5AB1 for masking frames and mounting sets for SIKUS installation distribution panels, refer to Catalogs I2.34 and 12.35 Subject to change without prior notice 08/02 | Bestell-Nr. EXXXXX-A190-PXXX | DISPO XXXXX | XXXXXXXXX PDWL.XX.X.XX WS 0802X.X | Printed in Germany Fuses for overload and short-circuit protection means: high short-circuit currents Siemens AG Automation and Drives Low Voltage Controls and Distribution P. O. Box 32 40, D-91050 Erlangen www.siemens.com/sentric