RM6
Components
Motorization
Switch, circuit breaker
and fuse-switch combination
Motor mechanism
PE57772
Switch operating mechanism
• The switch operating mechanism includes a space that is reserved for the
installation of a geared motor. This can be installed at the factory, but it can also
be installed on-site, by the customer, without de-energizing the unit, and without
dismantling the operating mechanism.
• An electrical interlocking assembly prohibits any false operations.
PE57773
Once motorized, the RM6 integrates perfectly into a telecontrol system
Circuit breaker and fuse-switch combination
operating mechanism
PE57776
• Circuit breaker or fuse protection functions can be motorized.
Functional units of circuit breaker or fuse-switch protection can be equipped.
The motorization can be installed at the factory, but it can also be installed on-site,
by the customer, without de-energizing the unit, and without dismantling the
operating mechanism.
• Electrical locking prohibits any false operations. This functionality is an option
for circuit breaker and is by default for fuse-switch function. Once motorized, the
RM6 integrates perfectly into a telecontrol system.
This option becomes particularly useful in the context of the protection
of a secondary ring, with supervision by a telecontrol system.
Unit applications
Operating mechanism types
CIT
CI1
CI1
Switch
Circuit breaker
Fuse switch combination
Main circuit switch
Closing
Opening
Closing
Opening
Closing
Opening
Manual operating mode
Remote control option
Operating time
Earthing switch
Manual operating mode
Hand lever
Motor
1 to 2 s
Closing
Hand lever
Hand lever
Motor
1 to 2 s
Opening
Hand lever
Hand lever
Motor
max. 13 s
Closing
Hand lever
Push button
Coil
65 to 75 ms
Opening
Hand lever
Hand lever
Motor
11 to 13 s
Closing
Hand lever
Push button
Coil
60 to 85 ms
Opening
Hand lever
Motor option for switch-units and circuit breakers
The operating mechanism I, D, B and Q functions may be motorized
DCw
Un power
supply
Power
(V) **
24
AC (50 Hz) *
48
60
110
125
220
120
230
(W)
240
(VA)
280
(*) Please consult us for other frequencies.
(**) At least a 20 A power supply is necessary when starting the motor.