Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 1 Fast and Practical Protection Coordination Strategy for Radial Distribution Systems with Distributed Generations Hadi Zayandehroodi Department of Electrical Engineering, Kerman Branch, Islamic Azad University, Kerman, Iran. Email: h.zayandehroodi@yahoo.com Abstract This paper presents a new protection method of coordinating the open/close states of the overcurrent relays in a power distribution system with DG units. A faulty line is initially identified, and all downstream and upstream paths leading to the DG units are determined using the backtracking algorithm. The main protection algorithm then determines the open/close states of relays, thereby isolating the faulty line. A backup protection algorithm is considered in completing the protection coordination scheme in case the primary protection scheme fails. The accuracy of the proposed protection coordination method has been tested on a 22-bus test system. Results illustrate that the proposed protection strategy can accurately coordinate the relays in a power distribution system with DG units. Keywords: Coordination, Distributed Generated, Fault Location, Overcurrent Relay, Protection, Radial Distribution Network, Introduction Conventional distribution systems are designed based on the assumption that power flow is unidirectional, from the generating stations to the transmission network and finally to the distribution network (Zayandehroodi, et al. 2013). When DG units are connected in a system, the distribution system is no longer radial, and the assumption of a unidirectional power flow no longer holds. Consequently, the system has to be analyzed as a mesh network (Ghosh, et al. 2010). Thus, Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 2 DG units may cause the loss of coordination among network protection devices (Brahma and Girgis 2004, Zayandehroodi, et al. 2010). Given that distribution systems typically have radial configurations with only one source, distribution systems have simple protection schemes, which are usually implemented using fuses, reclosers, and overcurrent (OC) relays (Quezada, et al. 2006). In OC relay coordination, a fault is sensed as soon as it occurs by both the primary and backup protection. However, finding a proper OC relay setting to meet this requirement is difficult using traditional distribution network methods with DG units (Zayandehroodi, et al. 2011). Previous literature has introduced several new approaches to solve the OC relay coordination problem. Checking the protection coordination of a system after connecting each DG unit to a distribution network is suggested in (Hadjsaid, et al. 1999). However, this approach is applicable only in systems with low DG penetration. In (Girgis and Brahma 2001), it was proven that protective devices in radial distribution systems can maintain coordination using the available margin in the curves of the protective devices. A study was performed to solve the fuse coordination problem, in which the suggested solution was to disconnect all DG units whenever a fault occurs (Brahma and Girgis 2002). The disadvantage of this solution is that it leads to the disconnection of all DG units even when transient faults occur. The recloser–fuse coordination with DG units using microprocessor-based reclosers was also addressed. An adaptive protection scheme based on network clustering into several zones was presented to solve the disconnection problem of all downstream DGs (Brahma and Girgis 2004). A new protection coordination strategy was developed to maximize generation in a distribution network and to avoid unacceptably high fault clearing times (Jager, et al. 2004). In this scheme, the OC principle and the time-dependent characteristics of the current were used. An adaptive OC pickup scheme that updates the OC relay minimum pickup current based on the fault Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 3 analysis of the distribution system was presented in (Zayandehroodi, et al. 2015) . However, this study focuses only on studying inverter-interfaced DG units. Another protection coordination scheme for radial distribution networks with DG units employs directional relays at the beginning of the feeders embedding the DG units (Zamani, et al. 2010). An expert system was previously applied for protective relay coordination in a radial distribution network with small DG units (Tuitemwong and Premrudeepreechacharn 2011). The expert system employs a knowledge base and an inference process to improve the coordination settings of relays, thereby accommodating DG penetration. Furthermore, some studies (Wan, et al. 2008) proposed a multi-agent-based protection scheme for distribution systems with DG units (Hui, et al. 2010). The coordination strategy is embedded in every relay agent. In the coordination strategy, relay settings and time are not the only parameters determining the relay coordination. Efforts are currently underway to improve the performance of multi-agent systems in coping with protection coordination within more complex systems. Backtracking Algorithm The backtracking algorithm is implemented by multi-stage confirmed step by step search method. At every stage, there are multi-selection branches necessary to pick out one branch from the available set of alternative branches. If no solution can be found, the algorithm must backtrack to the searched node and select another node. If no solution can be found after testing the entire set of branches at a particular node, the algorithm must backtrack to the quondam node which is called as the backtracking node which is satisfied by the backtracking condition (Wang, et al. 2002). In this paper, the backtracking algorithm is applied to determine the location of DG units when a fault occurs in a distribution network with DG units. Finding the feasible solution for a problem can be formulated by finding a solution path in an implicitly directed state-space tree from an initial bus to a goal bus. When the last generated bus has a DG unit, the searching algorithm is completed in Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 4 that path. Figure 1 illustrates the backtracking search algorithm in a sample distribution network with two DG units. Figure 1: Backtracking search in a distribution network with several DG units Proposed Protection Coordination Strategy The proposed protection coordination strategy can be divided into two sub-strategies. In the first strategy, the main protection algorithm supervises the entire network to clear the fault at the time of occurrence. The second strategy, which is called backup protection algorithm, operates as a complement in standby mode to clear a fault when the main protection is misoperated. Main Protection Algorithm After identifying the faulty line number using the radial basis function neural network (RBFNN) method, as illustrated in (Zayandehroodi, et al. 2011), the main protection algorithm functions by determining all downstream paths leading to the DG units using the backtracking algorithm. When a DG is present in the downstream path, a signal is sent to the open relay at the faulty line, N, as well as all the relays attached to the immediate downstream bus leading to the DG units. Otherwise, the control signal is only sent to the relay at the faulty line. Figure 2 shows a flowchart of the implementation procedure of the proposed main protection algorithm. Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 5 Specify a faulty line, N Find all downstream paths leading to DG units using the Backtracking Aalgorithm Open the relay at line N No Is the number of DG paths > 0 Yes Open all the relays attached to immediate downstream bus leading to DG units and relay at line N End of Main protection Figure 2: Proposed main protection algorithm Backup Protection Algorithm In case the main protection system misoperated, the backup protection system is activated from its standby mode to protect the network. For this purpose, the location of the misoperated relay should be determined, which may be placed at either the immediate upstream or the downstream bus of the faulty line, N. If the relay is located at the immediate upstream bus of the faulty line, the main protection algorithm is implemented for the upstream line of the faulty line. Otherwise, the main protection algorithm is implemented for the downstream line where the misoperation has occurred. This process continues until the absolute isolation of the fault is achieved. Figure 3 shows the flowchart of the proposed backup protection algorithm. Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 6 Receive the main protection relays status Whether all relays operate during main protection Yes End of backup protection No Whether the misoperated relays connected to immediate Upstream bus of faulty line, N No Yes Consider the downstream line where misoperation occurred Consider the immediate line connected upstream to the faulty line Find all downstream paths leading to DG units using the Backtracking Algorithm Find all downstream and upstream paths leading to DG units and main source using the Backtracking Algorithm Is the number of DG paths in downstream > 0 No End of backup protection No Is the number of DG paths in upstream > 0 Yes Yes Open all the relays connected to the immediate downstream bus leading to DG units Open the relay at immediate line connected upstream to the faulty line Figure 3: Proposed backup protection algorithm Results and Discussion Figure 4 shows the 22-bus, 20 kV distribution network with two DG units used to verify the performance and accuracy of the proposed protection coordination strategy. The system data can be find in (Zayandehroodi, et al. 2010). Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 7 Figure 4: Single line diagram of a 22-bus test system In this study, DIgSILENT Power Factory 14.0.524 software is used to simulate the abovementioned test system; various types of faults are created in each line. The two-stage RBFNN method is applied and implemented using MATLAB software to estimate the fault distance from each source and from the faulty line number (Zayandehroodi, et al. 2012, Zayandehroodi, et al. 2010). The proposed main and backup protection schemes shown in Figures 2 and 3 are coded in MATLAB to determine the operation sequence of the main and backup relays, thus completing the protection scheme. Various fault types, including single phase to ground fault, phase to phase fault, two phases to ground fault, and three-phase fault, have been selected randomly for testing to confirm the accuracy and effectiveness of the proposed protection scheme at the time of fault occurrence. At first by creating a fault in line 8, the proposed method identifying two upstream paths and one downstream path using the backtracking algorithm. At this time, the opening signals are sent to relays R8 and R9 via the main protection algorithm to isolate the faulty line 8, as shown in Figure 5. Figure 6 illustrates that when the main protection operates accurately, the backup Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 8 protection does not operate and stays in the closed mode. The rest of the network will receive power from the main source S and DG units DG1 and DG2. Figure 5: Status of the circuit breakers of R8 and R9 as main protection with a fault at line 8 Figure 6: Status of R1, R2, and R10 with a fault at line 8 and the main protection operates In the case of relay misoperation in the main protection system, the backup protection is activated through the activation of the backup relays from standby mode, thus protecting the network. Figure 7 also illustrates the generated on/off command for the main protection relays and misoperation of relay R8. Figure 8 shows the on/off command for the backup protection relays to cover the misoperation of relay R8. Figure 7: Status of R8 and R9 as main protection with a fault at line 8 when R8 does not operate as the first backup protection Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 9 Figure 8: Status of R1, R2, and R10 with a fault at line 8 when R8 does not operate as the first backup protection. In case of the misoperation of relay R9 in the main protection system, the backup protection system is activated from its standby mode to protect the network. Relay R10 operates with a 247 ms delay as a backup for relay R9. The operation performances of the related relays are shown in Figures 9 and 10. As shown in the figures, the calculated implementation times of the proposed protection coordination method in the main and backup protection for various fault types are around 111 and 247 ms, respectively, which are quite fast and meet the Institute of Electrical and Electronics Engineers Standard 242-2001 requirements (IEEE 2001). Figure 9: Status of R8 and R9 as main protection with a fault at line 8 when R9 does not operate as the first backup protection Figure 10: Status of R1, R2, and R10 with fault in Line 8 when R9 does not operate as the first backup protection. Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 10 Conclusion A new protection coordination strategy for a distribution network with DG units has been presented. In the proposed approach, all downstream paths leading to DG units are determined using the backtracking algorithm after determining the location of the faulty line. The faulty line number is then sent to the main protection system to determine the open/close states of the relays for isolating the faulty line. A backup protection system is also considered to complete the protection scheme in case the main protection system misoperates. References Brahma, S. M. and A. A. Girgis, "Microprocessor-based reclosing to coordinate fuse and recloser in a system with high penetration of distributed generation," in IEEE Power Engineering Society Winter Meeting. . vol. 1, ed., p.^pp. 453-458 (2002). Brahma, S. M. and A. A. Girgis, "Development of adaptive protection scheme for distribution systems with high penetration of distributed generation," IEEE Transactions on Power Delivery, 19, 56-63 (2004). Ghosh, S., S. P. Ghoshal and S. Ghosh, "Optimal sizing and placement of distributed generation in a network system," International Journal of Electrical Power & Energy Systems, 32, 849-856 (2010). Girgis, A. and S. Brahma, "Effect of distributed generation on protective device coordination in distribution system," in Large Engineering Systems Conference on Power Engineering, (LESCOPE '01) ed., p.^pp. 115-119 (2001). Hadjsaid, N., J. F. Canard and F. Dumas, "Dispersed generation impact on distribution networks," IEEE Computer Applications in Power, 12, 22-28 (1999). Hui, W., K. K. Li and K. P. Wong, "An Adaptive Multiagent Approach to Protection Relay Coordination With Distributed Generators in Industrial Power Distribution System," IEEE Transactions on Industry Applications, 46, 2118-2124 (2010). IEEE, "IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems," in IEEE Std 242-2001 (Revision of IEEE Std 242-1986) ed., p.^pp. i-740 (2001). Jager, J., T. Keil, L. Shang and R. Krebs, "New protection coordination methods in the presence of distributed generation," in Eighth IEE International Conference on Developments in Power System Protection vol. 1, ed., p.^pp. 319-322 (2004). Quezada, V. H. M., J. R. Abbad and T. G. S. Roman, "Assessment of energy distribution losses for increasing penetration of distributed generation," IEEE Transactions on Power Systems 21, 533540 (2006). Journal of Engineering and Economic Development, 2(2), 1-11, July 2015 11 Tuitemwong, K. and S. Premrudeepreechacharn, "Expert system for protection coordination of distribution system with distributed generators," International Journal of Electrical Power & Energy Systems, 33, 466-471 (2011). Wan, H., K. P. Wong and C. Y. Chung, "Multi-agent application in protection coordination of power system with distributed generations," in Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE, ed., p.^pp. 1-6 (2008). Wang, H., S. Liao and L. Liao, "Modeling constraint-based negotiating agents," Decision Support Systems, 33, 201-217 (2002). Zamani, A., T. Sidhu and A. Yazdani, "A strategy for protection coordination in radial distribution networks with distributed generators," in IEEE Power and Energy Society General Meeting ed., p.^pp. 1-8 (2010). Zayandehroodi, H., A. Mohamed, M. Farhoodnea and M. Mohammadjafari, "An Optimal Radial Basis Function Neural Network for Fault Location in a Distribution Network with High Penetration of DG Units," Measurement, 46, 3319–3327 (2013). Zayandehroodi, H., A. Mohamed, H. Shareef and M. Farhoodnea, "A novel neural network and backtracking based protection coordination scheme for distribution system with distributed generation," International Journal of Electrical Power & Energy Systems, 43, 868-879 (2012). Zayandehroodi, H., A. Mohamed, H. Shareef and M. Mohammadjafari, "Automated Fault Location in a Power System with Distributed Generations Using Radial Basis Function Neural Networks," Journal of Applied Sciences, 10, 3032-3041 (2010). Zayandehroodi, H., A. Mohamed, H. Shareef and M. Mohammadjafari, "A New Protection Scheme for Distribution Network with Distributed Generations Using Radial Basis Function Neural Network," International Journal of Emerging Electric Power Systems, 11, 1–19 (2010). Zayandehroodi, H., A. Mohamed, H. Shareef and M. Mohammadjafari, "A Comprehensive review of protection coordination methods in power distribution systems in the presence of DG," Przeglad Elektrotechniczny, 87, 142-148 (2011). Zayandehroodi, H., A. Mohamed, H. Shareef and M. Mohammadjafari, "Determining exact fault location in a distribution network in presence of DGs using RBF neural networks," in IEEE International Conference on Information Reuse and Integration (IRI), ed., p.^pp. 434-438, Las Vegas, Nevada, USA (2011). Zayandehroodi, H., S. E. Shahgholi, M. Sharifi and M. Shabanipour, "A new method for adaptive protection and optimal co-ordination of overcurrent relays," WALIA journal, 31, 8-12 (2015).