BIQ..n - Maximum Demand Ammeter with Bimetallic Movement, BOQ..n - Combined Bimetallic & Moving Iron Ammeter Description The Maximum Demand Ammeter BIQ/BOQ 72/96n are used for measurement and indication of maximum demand current (BIQ) & maximum demand current with instantaneous current (BOQ). These instruments are used in thermal loading in power distribution Systems, Networks, Machines etc The thermal bimetallic movement indicates the mean RMS value over 15 min. (optional 8min or 20min.), high torque of thermal movement drives a maximum demand current pointer which is associated with instrument pointer. The maximum demand current pointer will remain at the maximum value reached for consequent reading until reset by manually by sealable reset knob. Bimetallic instruments have a specific inertia due to their thermal time lag making these instruments suitable to instruments maximum demands. For measurement of instantaneous RMS values a moving iron movement with pivot suspension spring loaded shock absorbing jewel bearing and silicon oil damping is in corporated. The moving iron movement has response time of approx 1 second. BOQ 72/96n combines thermal bimetallic & moving iron movements paced diagonally in same case. Features 1. House in glass filed polycarbonate cases. 2. Measurement of RMS values of maximum currents & true RMS measurements for instantaneous current for BOQ..n 3. Most economical solution for measurements of thermal or time characteristics of the load. 4. Rugged Movement 5. Having 20% overload capacity 6. Simultaneously measurement of maximum demand current & instantaneous current. 7. Standard terminal covers IP 10. Complete protection cover on request. Applicable Standards Nominal case & cutout dimensions for DIN 43700 indicating Electrical instruments Scale & pointer for electrical measuring instruments DIN 43802 Connections and Terminal markings for panel meters DIN 43807 Terminal bolts / leads. DIN 46200/46282 Safety requirements and protective measures for Electrical indicating. instruments and their accessories. DIN 40050/8-70, VDE 0110/ 11-72 VDE 0410/ 10-76 IEC 529 , IEC 1010 Performance specifications for direct acting indicating analogue electrical measuring instruments & their accessories IEC51/DINEN60051 DIN 43701 Environmental conditions VDE / VDI 3540 Front frames for indicating measuring instruments Principle dimensions DIN 43718 UL Combustibility Class UL 94 V-0 Mechanical strength ( vibration, free fall test) IEC 51, VDE 0411, Part 14 sec 43/44, IEC 1010 Comply with following European directives 89 / 336 / EEC (EMC Directive), 73/23/EEC (low voltage directive) & 93/68/EEC, for CE Marking. BIQ..n BOQ..n Scale and Pointer Pointer Scale characteristics Over Range Scale Division Scale Length Knife - edge pointer & 0...900 Deflection . Bimetallic - Quadratic Moving Iron - near to linear Bimetallic - 1.2 times rated current. Moving Iron - 2 times rated current. Coarse - fine BOQ 72n - Bimetallic - Moving Iron BOQ 96n - Bimetallic - Moving Iron BIQ 72n - Bimetallic BIQ 96n - Bimetallic 52mm 61mm 71mm 90mm 61mm 97mm Barthelsmühlring, 16, D - 76870 Kandel, GERMANY. Tel. : + 49 7275-9883-0 Fax: +497275-9883-33 E-mail : info@celsagermany.com Web : www.celsagermany.com BIQ..n - Maximum Demand Ammeter with Bimetallic Movement, BOQ..n - Combined Bimetallic & Moving Iron Ammeter Environmental Conditions Accuracy at Reference Conditions Accuracy class 3 (bimetallic movement) 1.5 (moving -iron movement) Acc to IEC 51/DIN EN 60051 Climatic suitability Climatic class 3 according to VDE/VDI 3540 Operating temperature - 10... + 55 C o Reference conditions Ambient temperature 230 C ± 20 C Position of use Nomial position ± 5 % Storage temperature - 25... + 65 C Input External magnetic field Frequency: Rated value of current 0.5 mT Relative humidity 15..400 Hz Other conditions IEC 51/ DIN EN 60051 Shock resistance Vibration resistance < 75% annual average, non-condensing 15g. 11 ms 1.5 g at about 50 Hz Position of use Frequency Mechanical Specification Case details Moulded square case suitable for mounting in Control/ Switchgear panels, Machinery consoles. Case material Glass filled polycarbonate , with non drip flame retardant property as per UL 94 V-0 Front facia Glass Colour of bezel Black Position of use Vertical Panel fixing Side clamp Panel thickness < 40 mm Terminals Hexagon studs, M4 screws and wire clamps E3 (DIN 46282) o Vertical +- 5 15...400Hz o Standard Measuring Ranges BIQ BOQ For Use On C.T. 1A 1A ...../ 1A 5A 5A ...../ 5A Options Electrical Specification Front facia Antiglare glass Position of use On request 15 ....165 Colour of pointer Blank dial Special markings Black and Red With initial and end values marked. Numbering / Lettering. o Division dials Basic divisions without numbering. Measured quantity Thermal time delay: (Bimetallic) Power consumption: AC Current. 15 minutes ( 8 min. or 20 min. on request) for rated current 1A for 5A Colour markings/bands Red or green BIQ BOQ < 1.6VA < 2.5VA Overload capacity (acc. to IEC 51) Accuracy class Thermal time delay Calibration 1 on request 8min. or 20 min. for other frequency 15Hz...400Hz Continuously :1.2 times rated voltage /current :10 times rated current, 1 sec max. Short duration Enclosure code (IEC 529) Insulation class < 2.5VA < 3.4VA IP 40 case Accessories Group A according to VDE 0110 Rated insulation voltage 1000V Proof voltage 3kV Installation category 300 V CAT III according to IEC 1010. Insulation resistance > 50 M W at 500 V d.c Safety Terminal Protection Protection back cover to provide protection against accidental contact (hand and fingers) acc. to VDE 0410. Saturating current transformer Saturating transformer accuracy class 3, 50Hz to protect the movement against continuous overloads. Barthelsmühlring, 16, D - 76870 Kandel, GERMANY. Tel. : + 49 7275-9883-0 Fax: +497275-9883-33 E-mail : info@celsagermany.com Web : www.celsagermany.com BIQ..n - Maximum Demand Ammeter with Bimetallic Movement, BOQ..n - Combined Bimetallic & Moving Iron Ammeter Connections Ordering Information AC Current (for use on current Transformer) AC Voltage (Direct connected) 17 17 18 k L1 N(L2) 18 X L1 N(L2) k Type BIQ..n BOQ..n MDI with Bimetallic movement. MDI meter with Moving Iron ammeter. Front dimension 96 mm x 96 mm Measuring Ranges 1A 5A ---/1 A for use on Current transformer ---/5A for use on Current transformer l L X Dimensions Over range Bimetal Movement Bimetal & Moving Iron Moving Iron 1.2 times rated current *1 1.2 times rated current *3 2 times rated current *1 Terminal protection Terminal cover/Backcover Panel Fixing Side clamp Calibration 50 Hz*1 For frequency 15- 400Hz *3 Thermal Time Delay 15 min*1 8 min*3 20 min*3 Front facia Normal glass *1 Antiglare glass*3 Colour of bezel Black *1 Red, Blue, Yellow, White *3 Position of use Vertical *1 0 *3 On request 15 .... 165 Dial Standard scale same as measuring range Blank dial with division *3 *3 Additional lettering on request *3 Additional numbering on request Coloured marking red or green *3 Coloured sector red or green *3 Logo CELSA Saturating current BOQ/BIQ72n 72 mm x 72 mm BOQ/BIQ96n *1 *3 Without *1 ESW 1/5A 4.25VA ESW 5/5A 4.25VA Standard Please clearly add the desired specifications while ordering Ordering example BIQ72n for use C.T. of range 1000/1A Thermal time delay 15 min. Barthelsmühlring, 16, D - 76870 Kandel, GERMANY. Tel. : + 49 7275-9883-0 Fax: +497275-9883-33 E-mail : info@celsagermany.com Web : www.celsagermany.com