PQn Celsa_Datasheet.cdr

advertisement
BIQ..n - Maximum Demand Ammeter with Bimetallic Movement,
BOQ..n - Combined Bimetallic & Moving Iron Ammeter
Description
The Maximum Demand Ammeter BIQ/BOQ 72/96n are used for measurement and indication of maximum demand current (BIQ) & maximum
demand current with instantaneous current (BOQ).
These instruments are used in thermal loading in power distribution Systems, Networks, Machines etc
The thermal bimetallic movement indicates the mean RMS value over 15 min. (optional 8min or 20min.), high torque of thermal movement
drives a maximum demand current pointer which is associated with instrument pointer. The maximum demand current pointer will remain at
the maximum value reached for consequent reading until reset by manually by sealable reset knob.
Bimetallic instruments have a specific inertia due to their thermal time lag making these instruments suitable to instruments maximum
demands.
For measurement of instantaneous RMS values a moving iron movement with pivot suspension spring loaded shock absorbing jewel bearing
and silicon oil damping is in corporated.
The moving iron movement has response time of approx 1 second.
BOQ 72/96n combines thermal bimetallic & moving iron movements paced diagonally in same case.
Features
1. House in glass filed polycarbonate cases.
2. Measurement of RMS values of maximum currents & true RMS measurements for instantaneous current for BOQ..n
3. Most economical solution for measurements of thermal or time characteristics of the load.
4. Rugged Movement
5. Having 20% overload capacity
6. Simultaneously measurement of maximum demand current & instantaneous current.
7. Standard terminal covers IP 10. Complete protection cover on request.
Applicable Standards
Nominal case & cutout dimensions for DIN 43700
indicating Electrical instruments
Scale & pointer for electrical
measuring instruments
DIN 43802
Connections and Terminal markings
for panel meters
DIN 43807
Terminal bolts / leads.
DIN 46200/46282
Safety requirements and protective
measures for Electrical indicating.
instruments and their accessories.
DIN 40050/8-70,
VDE 0110/ 11-72
VDE 0410/ 10-76
IEC 529 , IEC 1010
Performance specifications for direct
acting indicating analogue electrical
measuring instruments & their
accessories
IEC51/DINEN60051
DIN 43701
Environmental conditions
VDE / VDI 3540
Front frames for indicating measuring
instruments Principle dimensions
DIN 43718
UL Combustibility Class
UL 94 V-0
Mechanical strength ( vibration,
free fall test)
IEC 51, VDE 0411, Part 14
sec 43/44, IEC 1010
Comply with following European
directives
89 / 336 / EEC
(EMC Directive),
73/23/EEC
(low voltage directive)
& 93/68/EEC, for
CE Marking.
BIQ..n
BOQ..n
Scale and Pointer
Pointer
Scale characteristics
Over Range
Scale Division
Scale Length
Knife - edge pointer & 0...900 Deflection .
Bimetallic - Quadratic
Moving Iron - near to linear
Bimetallic - 1.2 times rated current.
Moving Iron - 2 times rated current.
Coarse - fine
BOQ 72n - Bimetallic
- Moving Iron
BOQ 96n - Bimetallic
- Moving Iron
BIQ 72n - Bimetallic
BIQ 96n - Bimetallic
52mm
61mm
71mm
90mm
61mm
97mm
Barthelsmühlring, 16, D - 76870 Kandel, GERMANY.
Tel. : + 49 7275-9883-0
Fax: +497275-9883-33
E-mail : info@celsagermany.com
Web : www.celsagermany.com
BIQ..n - Maximum Demand Ammeter with Bimetallic Movement,
BOQ..n - Combined Bimetallic & Moving Iron Ammeter
Environmental Conditions
Accuracy at Reference Conditions
Accuracy class
3 (bimetallic movement)
1.5 (moving -iron movement)
Acc to IEC 51/DIN EN 60051
Climatic suitability
Climatic class 3 according to
VDE/VDI 3540
Operating temperature
- 10... + 55 C
o
Reference conditions
Ambient temperature
230 C ±
20 C
Position of use
Nomial position ±
5
%
Storage temperature
- 25... + 65 C
Input
External magnetic field
Frequency:
Rated value of current
0.5 mT
Relative humidity
15..400 Hz
Other conditions
IEC 51/ DIN EN 60051
Shock resistance
Vibration resistance
< 75% annual average,
non-condensing
15g. 11 ms
1.5 g at about 50 Hz
Position of use
Frequency
Mechanical Specification
Case details
Moulded square case suitable for
mounting in Control/ Switchgear
panels, Machinery consoles.
Case material
Glass filled polycarbonate , with non drip
flame retardant property as per UL 94 V-0
Front facia
Glass
Colour of bezel
Black
Position of use
Vertical
Panel fixing
Side clamp
Panel thickness
< 40 mm
Terminals
Hexagon studs, M4 screws and
wire clamps E3 (DIN 46282)
o
Vertical +- 5
15...400Hz
o
Standard Measuring Ranges
BIQ
BOQ
For Use On C.T.
1A
1A
...../ 1A
5A
5A
...../ 5A
Options
Electrical Specification
Front facia
Antiglare glass
Position of use
On request 15 ....165
Colour of pointer
Blank dial
Special markings
Black and Red
With initial and end values marked.
Numbering / Lettering.
o
Division dials
Basic divisions without numbering.
Measured quantity
Thermal time delay:
(Bimetallic)
Power consumption:
AC Current.
15 minutes
( 8 min. or 20 min. on request)
for rated current 1A
for 5A
Colour markings/bands
Red or green
BIQ
BOQ
< 1.6VA
< 2.5VA
Overload capacity
(acc. to IEC 51)
Accuracy class
Thermal time delay
Calibration
1 on request
8min. or 20 min.
for other frequency 15Hz...400Hz
Continuously
:1.2 times rated voltage /current
:10 times rated current, 1 sec max.
Short duration
Enclosure code
(IEC 529)
Insulation class
< 2.5VA
< 3.4VA
IP 40 case
Accessories
Group A according to VDE 0110
Rated insulation voltage
1000V
Proof voltage
3kV
Installation category
300 V CAT III according to IEC 1010.
Insulation resistance
> 50 M W
at 500 V d.c
Safety Terminal Protection
Protection back cover to provide protection against accidental
contact (hand and fingers) acc. to VDE 0410.
Saturating current transformer
Saturating transformer accuracy class 3, 50Hz to protect the
movement against continuous overloads.
Barthelsmühlring, 16, D - 76870 Kandel, GERMANY.
Tel. : + 49 7275-9883-0
Fax: +497275-9883-33
E-mail : info@celsagermany.com
Web : www.celsagermany.com
BIQ..n - Maximum Demand Ammeter with Bimetallic Movement,
BOQ..n - Combined Bimetallic & Moving Iron Ammeter
Connections
Ordering Information
AC Current (for use on current
Transformer)
AC Voltage (Direct connected)
17
17
18
k
L1
N(L2)
18
X
L1
N(L2)
k
Type BIQ..n
BOQ..n
MDI with Bimetallic movement.
MDI meter with Moving Iron ammeter.
Front dimension
96 mm x 96 mm
Measuring Ranges
1A
5A
---/1 A for use on Current transformer
---/5A for use on Current transformer
l
L
X
Dimensions
Over range
Bimetal Movement
Bimetal & Moving Iron
Moving Iron
1.2 times rated current *1
1.2 times rated current *3
2 times rated current *1
Terminal protection
Terminal cover/Backcover
Panel Fixing
Side clamp
Calibration
50 Hz*1 For frequency 15- 400Hz *3
Thermal Time Delay
15 min*1
8 min*3
20 min*3
Front facia
Normal glass *1
Antiglare glass*3
Colour of bezel
Black *1
Red, Blue, Yellow, White *3
Position of use
Vertical *1
0 *3
On request 15 .... 165
Dial
Standard scale same as measuring range
Blank dial with division *3
*3
Additional lettering on request
*3
Additional numbering on request
Coloured marking red or green *3
Coloured sector red or green *3
Logo
CELSA
Saturating current
BOQ/BIQ72n
72 mm x 72 mm
BOQ/BIQ96n
*1
*3
Without *1
ESW 1/5A 4.25VA
ESW 5/5A 4.25VA
Standard
Please clearly add the desired specifications while ordering
Ordering example
BIQ72n for use C.T. of range 1000/1A Thermal time delay 15 min.
Barthelsmühlring, 16, D - 76870 Kandel, GERMANY.
Tel. : + 49 7275-9883-0
Fax: +497275-9883-33
E-mail : info@celsagermany.com
Web : www.celsagermany.com
Download