8/6/2008 Motor Calcs 2005 NEC Motor Circuit Requirements and Calculations Copyright 1999-2007 Dan Dudley Motor Calcs NEC Motor Calculations Basic Information • 430.6(a)(1) Basic Calc information – Name Plate Values (430.6(a)(2) are only used to size overloads) – Otherwise use T.430.247, 248, 249, & 250 • 430.22(a) Single motor 125% cont. duty (3 hrs or more) • T.430.22(e) Note Cont. Duty unless nature of apparatus is otherwise. Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs NEC Motor Calculations Basic Information • 430.52(c)(1) exception – Next higher standard size overcurrent protective device. • 430.62 Feeder O.C. Protection – Largest S.C. – G.F. Protective device plus the sum of the F.L.C. of all other motors supplied by the same feeder • No provision for going UP to next standard size must go down to next standard size Copyright 1999-2007 Dan Dudley Motor Calcs Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Hp Phases Voltage FLC Hz Temp Rise Service Factor Insulation Class Locked Rotor Letter Copyright 1999-2007 Dan Dudley Motor Calcs Line side Nameplate Data Actuating Coil Overload Relays Load Side Overload Reset Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs For all other calculations use Table values Copyright 1999-2007 Dan Dudley Motor Calcs Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley ¾ @120 5 @208 Motor Calcs 25 HP 208 Volts 50 HP Synchronous 200 HP 440 Volts 480 Volts 25-208 50 sync – 440 200 - 480 Copyright 2000-2007 Dan Dudley Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs C.B. 3-phase Std. Fuse Copyright 1999-2007 Dan Dudley Motor Calcs 10HP 240V 1Φ FLI 44 What minimum size THHN conductors are required for this motor ? Name Plate Not used 430.248: 430.248: 10hp @ 240v = 50 amps 430.22(a): 430.22(a): 50 X 125% = 62.5 amps 310.16: 310.16: 62.5 amps = #4 THHN T.310.16 Copyright 2000-2007 Dan Dudley T.430.248 110.14 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs 25HP 480V 3Φ FLI 32.5 What is the minimum ampacity of the branch circuit conductors for a 25 HP , 480-volt, 3 phase, squirrel cage motor with nameplate FLI of 32.5 amps ? Name Plate value not used 430.250: 430.250: 25hp @480v = 34 amps 430.22(a): 430.22(a): 34 X 125% = 42.5 amps 310.16 : # 6 THHN @60º @60ºC and 55 amps T.310.16 T.430.250 Copyright 1999-2007 Dan Dudley 110.14 Circuits with more than one Motor • Step 1. • Decide which motor has largest FLI rating (This may not be the largest HP) • Step 2. • Largest FLI of one motor X 125% (only increase one) • • Step 3. Add FLI rating of all other motors (straight from tables) Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs 5HP 3Φ 208V 5HP 3Φ 208V What is the minimum ampacity of the branch circuit conductors for the two motors as shown ? 3∅, 208V 430.250: 430.250: 5 hp @ 208v = 16.7 amps 430.24: 430.24: Ampacity = FLI 1st motor X 125% + FLI 2nd motor Ampacity = 16.7 X 125% + 16.7 = 37.575 amps T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley Motor Calcs 5HP 1Φ 230V 2HP 1Φ 230V What is the minimum ampacity of the branch circuit conductors supplying the two motors as shown ? 1∅, 230V 430.248: 2hp @ 230v = 12 amps 430.248: 5hp @ 230v = 28 amps Ampacity = Largest FLI X 125% + Second FLI 28 X 125% + 12 = 47 amps T.310.16 Copyright 2000-2007 Dan Dudley T.430.248 110.14 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs 10HP 3Φ 480V Squirrel Cage 25HP 3Φ 480V Squirrel Cage 30HP 3Φ 480V Synchronous What is the minimum ampacity of the branch circuit conductor serving the three motors as shown above? T.310.16 T.430.250 Copyright 1999-2007 Dan Dudley 110.14 Motor Calcs 10HP 3Φ 480V Squirrel Cage 25HP 3Φ 480V Squirrel Cage 30HP 3Φ 480V Synchronous 430.250: FLI’s, 3-phase, 480v 10hp Squirrel cage = 14 FLI 25hp Squirrel cage = 34 FLI 30hp Synchronous = 32 FLI 34 X 125% + 14 + 32 = 88.5 amps T.310.16 Copyright 2000-2007 Dan Dudley T.430.250 110.14 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs 88.5A 10HP 3Φ 480V Squirrel Cage 25HP 3Φ 480V Squirrel Cage 30HP 3Φ 480V Synchronous What Size THWN conductors are required for: 1: Ungrounded Conductors Design A 2: Grounded Conductor 3: Grounding Conductor T.310.16 & 110.14(c) = #2 THWN Ungrounded (60°C) No Grounded Conductor Required T.250.122 Grounding Conductor (EGC) = #8 Cu or #6 Al T.310.16 T.250.122 110.14 T.430.250 Copyright 1999-2007 Dan Dudley Motor Calcs 6000 watts Incandescent Lighting 1HP 1Φ 120V FLI 12.4 What is the minimum size branch circuit conductors supplying the motor and incandescent lighting above ? 430.248: 1hp @ 120v = 16 amps Lighting: I=W / E = 6000 / 120 = 50 amps 430.24(a): Ampacity = motor FLI X 125% + Lighting I 16 X 125% + 50 = 70 amps #4 THHN Cu (60°C) T.310.16 Copyright 2000-2007 Dan Dudley T.430.248 110.14 Copyright 1999-2007 Dan Dudley 8/6/2008 Copyright 1999-2007 Dan Dudley Motor Calcs T.310.16 Copyright 2000-2007 Dan Dudley T.430.250 110.14 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs 81.25 26.25 123.25 T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley Motor Calcs T.310.16 Copyright 2000-2007 Dan Dudley T.430.250 110.14 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley 430.52 Motor Calcs T.310.16 T.430.250 Copyright 2000-2007 Dan Dudley 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs Time Delay Fuses T.310.16 T.430.250 110.14 20HP 3Φ 480V FLI 29 430.52 240.6 Copyright 1999-2007 Dan Dudley Motor Calcs Time Delay Fuses 20HP 3Φ 480V FLI 29 T.430.250: 20hp = 27 amps T.430.52: Time Delay Fuse = 175% Max. O.C. device = 27 X 175% = 47.25 amps 430.52(c)(1) exception #1: Next Larger size permitted 240.6(a) Next Larger Std size = 50 amps Answer: 50 amp Time Delay Fuse T.310.16 T.430.250 Copyright 2000-2007 Dan Dudley 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs Non-Time Delay Fuses 20HP 3Φ 480V FLI 29 T.430.250: 20hp = 27 amps T.430.52: Non-Time Delay Fuse = 300% Max. O.C. device = 27 X 300% = 81 amps 430.52(c)(1) exception #1: Next Larger size permitted 240.6(a) Next Larger Std size = 90 amps Answer: 90 amp Non-Time Delay Fuse T.310.16 T.430.250 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley Motor Calcs Inverse Time Breaker 20HP 3Φ 480V FLI 29 T.430.250: 20hp = 27 amps T.430.52: Inverse Time Breaker = 250% Max. O.C. device = 27 X 250% = 67.5 amps 430.52(c)(1) exception 1: Next Larger size permitted 240.6(a) Next Larger Std size = 70 amps Answer: 70 amp Inverse Time Circuit Breaker T.310.16 T.430.250 Copyright 2000-2007 Dan Dudley 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley 8/6/2008 Selecting Minimum Size Overloads 430.32(A)(1) Service Factor Less than 1.15 use 115% Temperature Rise 1.15 or greater use 125% No Service Factor Listed use 115% 40°C or less use 125% Over 40°C use 115% No Temp Listed use 115% Copyright 1999-2007 Dan Dudley Selecting Maximum Size Overloads 430.32(C) Service Factor Less than 1.15 use 130% 1.15 or greater use 140% No Service Factor Listed use 130% Temperature Rise 40°C or less use 140% Over 40°C use 130% No Temp Listed use 130% Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motors with a Duty Cycle - Welders Solution: Welder No.1 630.11(a) Nonmotor Generator Duty cycle 30 Multiplier = 0.55 I=RPCXM I = 28 amps x 0.55 = 15.4 amps Welder No.2 630.11(a) Nonmotor Generator Duty cycle 80 Multiplier = 0.89 I=RPC xM I = 18 amps x 0.89 = 16.02 amps 630.11(b) Total = No.1+ No.2 RPC 28A Duty Cycle 30% RPC 18A Duty Cycle 80% Total = 15.4 + 16.02 = 31.42 amps Ans. 31.42 amps T.310.16 T.630.11 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley Motor Calcs 5HP 230V 1Φ FLI 24.5 Periodic Duty 15 Min Solution: Nameplate current rating is used. Table 430.22(e) FLI 15 min. periodic duty = 90% Ampacity -Nameplate FLI x 90% = 24.5 x 90% = 22.05 amps. Answer: 22.05 amperes T.310.16 T.430.22(e) Copyright 2000-2007 Dan Dudley 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley 8/6/2008 Motor Calcs 15HP 230V 3Φ FLI 16.5 Varying Duty Solution: Nameplate FLI is used. Table 430.22(e) Continuous use, varying duty= 200% Ampacity = nameplate FLI x 200 % Ampacity= 16.5 x 200 = 33 amps Answer: 33 amperes T.310.16 T.430.22(e) 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley Motor Calcs Motor Efficiency No motor is 100% efficient • Efficiency = Output / Input Efficiency = Output / Input • 5HP, 240V, 1∅ = 28A F.L.C. T.430.248 • W = E X I = 240V X 28A = 6720 VA • 6720 VA input and 5712 VA output • 5712/6720 = .85 • 6720 VA X .85 = 5712 VA output • 85% efficiency Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Motor Duty Rating Intermittent Duty = T.430.22(e) Nameplate F.L.C. used 50HP,480V,3∅, 15 minute rated elevator motor, Name Plate FLC =61.2A T.430.22(e) = 85% Name Plate FLC = 61.2 X 85% = 52.02A Branch Circuit Ampacity Conductor Required = #6 (60°C column) Copyright 1999-2007 Dan Dudley Motor Calcs Motor Calculations Practice Questions 10 Questions 30 Minutes Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs Motor Calculations Answers 1. (a) 33A 13.2 X 250% = 33A KW 2. (a) 38.5A 30.8 X 125% = 38.5A KW 3. (b) #3/0 THHN 2 – 7.5 hp 1Ø = 44 A each 2 – 5 hp 1Ø = 30.8 A 1 – 2 hp 1Ø = 13.2 A 1 - 1 HP 1Ø = 8.8 A 56 X 125% + 44 + 30.8 + 24 + 13.2 + 11 70 + 44 + 30.8 + 13.2 + 13.2 + 8.8 Answer: 193 amps *Note #2 T. 430.248: 5hp, 208v, 1∅ = 30.8 amps 30.8 X 125% = 38.5 amps T.310.16 T.430.248 Copyright 2000-2007 Dan Dudley T.430.250 T.430.250 1999-2007 Dan Dudley 110.14Copyright 430.52 240.6 8/6/2008 Motor Calcs Motor Calculations Answers 4. (c) #3 TW 65 X 125% = 81.25 amps required. T. 310.16 5. (b) 9152 va Power(va) = E X I W= 208v X 44 = 9152 va 6. (d) 15.18 A 13.2 X 115% = 15.8 amps 7. (b) 80 amp 44 A FLC X 175% = 77 A 8. (a) 250 amp 175 A + 44 A + 30.8 A +24 A + 13.2A + 11 A = 298 amps 240.6 = 250 amp Can’t go up on FEEDER T.310.16 T.430.248 T.430.250 T.430.250 1999-2007 Dan Dudley 110.14Copyright 430.52 240.6 Motor Calcs Motor Calculations Answers 9. 10. (d) 200 amps 1. 175 + 21 + 21 = 217 2. Can’t go up on feeder - drop down to 200 amp (240.6) (d) #4 41 amps X 1.25 = 51.25a Be careful of TYPE of MOTOR, in this case SYNCHRONOUS Also be careful of type of CONDUCTOR Look in Right side – aluminum conductors in the middle column since design “D” is stated ** For motors marked with design letters B, C, or D conductors having an insulation rating of 75°C (167°F) or higher shall be permitted to be used provided the ampacity of such conductors does not exceed the 75°C (167°F) ampacity. T.310.16 T.430.248 Copyright 2000-2007 Dan Dudley T.430.250 T.430.250 1999-2007 Dan Dudley 110.14Copyright 430.52 240.6 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs 25-208 50 sync – 440 200 - 480 Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Copyright 1999-2007 Dan Dudley Motor Calcs Question 1 Keywords What size short circuit/ground fault protection is required for the branch circuit serving motor #1 in motor diagram #1? What size short circuit/ground fault protection is required for the branch circuit serving motor #1 in motor diagram #1? We are looking for the smallest fuse or circuit breaker required to protect motor #1 on Motor Diagram #1. Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley 8/6/2008 Motor Calcs Question 2 Keywords What is the minimum size overloads required for motor #2 on motor diagram #1 ? What is the minimum size overloads required for motor #2 on motor diagram #1 ? We are looking for the smallest heater/overload size allowed for motor #2 on motor diagram #1. Overloads = name plate full load current times either 115% or 125% depending on S.F. and/or Temp Rise. Copyright 1999-2007 Dan Dudley Motor Calcs Question 3 Keywords What is the minimum size THHN feeder required for the six motors as shown on Motor Diagram #1 ? What is the minimum size THHN feeder required for the six motors as shown on Motor Diagram #1 ? We are looking for the smallest legally allowed THHN copper conductor to feed these 6 motors. Feeder conductor = three steps: 1 find largest FLA motor and multiply by 1.25 (125%) 2. Add FLA of all other motors on same feeder 3. Can’t go up in size = drop down to standard at 240.6 Copyright 1999-2007 Dan Dudley Copyright 2000-2007 Dan Dudley