SHOP DRAWING REVIEW
REVIEWED
FURNISH AS CORRECTED
REVISE AND RESUBMIT
REJECTED
SUBMIT SPECIFIED ITEM
This review is only for general conformance with (1) the design concept and (2) the information
given in the construction documents. Corrections or comments made on a shop drawing during
this review do not relieve the contractor from compliance with the requirements of the plans and
specifications. Approval of a specific item does not include approval of an assembly of which
the item is a component. The contractor remains responsible for: dimensions to be confirmed and
correlated at the job site; information that pertains solely to the fabrication process or to the
means, methods, techniques, sequences and procedures of construction; coordination of the
Work with that of all other trades; and performing all Work in a safe and satisfactory manner.
By: Scott Dickson
Date: May 29, 2012
Comments:
1.)Exact Quantities of all devices, components etc, are the responsibility of the contractor.
2.)Basic outline programming shall be as per MKC published relay schedules, the contractor shall be responsible for all
final programming.
3.)Factory start-up, check out and programming must be provided.
4.)All field components requiring 120v power is the responsibility of the contractor to provide.
5.)These shop drawings were reviewed for design intent only, the contractor shall provide & install all components
necessary for a complete system and as per the manufacturer's recommendations.
6.)The contractor shall provide detailed as-builts including all component addresses & programming output
nomenclature.
7.)All wall switches shall have brushed stainless steel finish (PST) coverplates, and gray push buttons (BGY)
6-4-2012 Revised - All buttons shall be
Ivory (BIV)
File Name:
26 09 43 Low Voltage lighting control system
26 09 43 submittal review comments:
Relay R22 in Bus #1 shall be programmed to control room C30 – outside lamps
emergency – Circuit EL3-1
Relay R25 in Bus #2 shall be listed to control room lights on circuit L1-9
Relay R37 in Bus #2 shall be listed to control room lights on circuit E14A
emergency – EL1-5
Relay R12 in Bus #3 shall be listed to control room lights on circuit L1-20
Provide relays for the following rooms as per the low voltage lighting system relay
schedules 26 09 43:
Relay #209 D16 inside lamps emergency – EL1-5
Relay #210 D16 inside lamps emergency – EL1-5
Westlake City Schools
Submittal Cover Sheet
(To be filled out and submitted with each submittal)
School:Lee Burneson Middle School Contractor: Lake Erie Electric ____ Date: __4/20/12 ________
Item:__Low Voltage Lighting Controls__________________________________________________
Specification Section: _260943_______
Sub Specification Section: ___1.2___________________
Contractor’s Submittal # ___11___________Revision # __0____ Submittal Type ___PD___________
Lead Time After Approval (wks) ______ Manufacturer/Supplier: Lighting Controls, Sensor Switch
Intended Area of Use, Drawing # and Detail Reference: _Interior of building _ ___________________
Contractor Stamp
CM Stamp
TURNER/RESOURCE
LAKE ERIE
ELECTRIC, INC.
APPROVED
Ron Levine 4/20/12
Reviewed for general acceptance only. This review does
not relieve the Contractor of the responsibility for making
the work conform to the requirements of the contract. The
Contractor is responsible for all dimensions, correct
fabrication and accurate fit with the work of other trades.
SUBJECT TO ARCHITECT’S APPROVAL
Kyle Richardson Date: _____________
4/25/12
Signed: ____________________
260943-1
CM Submittal #: ________________________________
Architect Stamp
Engineer Stamp
LAKE ERIE ELECTRIC, INC.
CONTRACTORS & ENGINEERS
25730 First Street
P.O. Box 450859
Westlake, Ohio 44145
Established 1952
Phone (440) 835-5565
Fax
(440) 835-5688
TRANSMITTAL LETTER
To
Turner
Date
4/20/12
2282 Dover Center Rd
Our Job No.
11121010
Westlake, Oh
Our Purch. No.
Attention Kyle Richardson
Customer's No.
Project
LEE Submittal No.
New Lee Burneson Middle School
11
Location Westlake, Oh
X
1 Elect.
Please Find
Sheet/Dwg. No.
Date
4/20
260943.11
Attached Herewith
Our Drawings or Sketches
Under Separate Cover
Specifications
Copy Of The Following
Submittal
Rev.
0
DESCRIPTION
Spec. Section: 260943 Low Voltage Lighting Controls
Supplier: Jack Duffy & Assoc.
Manufacturer: Lighting Contols, Sensor Switch
Remarks
Preliminary
X For Approval
Approved for Construction
For Your Use
Resubmit
Copies For Approval
Approved As Noted
Resubmit
Copies For Distribution
For Files and Distribution
For Bids Due
Revised Copies - Destroy Originals or Place in Superseded File
For Record Only
Acknowledge Receipt Of Above By Returning One Signed Copy Of Transmittal
As Requested
X Return
1
Copies, With Approval Or Comment Not Later Than
5/4/2012
DISTRIBUTION
CC:
PRINTS:
X
(1) Job/Engineering File 11121010
X
(1) Ron Levine/Project Manager
X
(1) Dave Klicman/Foreman
Very truly yours,
David Hutter for Ron Levine
LAKE ERIE ELECTRIC, INC.
LE 128-1
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
Lighting Control & Design
Submittal Package
LEE BURNESON MIDDLE SCHOOL
WEST LAKE, OH
ABC PROJECT # 15768
PO# 615106054AA
April 18, 2012
The following information is included in this submittal package:
General:
Approval Worksheet
Notes
Bill of Material
Single Line Diagram
Warranty Information
New Construction Planning Guide
Final Activation Checklist
Commissioning Request Form
Schedules:
Panel Schedules
Clock Schedule
Switch Schedules
Digilink Schedules
Photocell Schedules
Data / Specifications:
GR 2400 Lighting Control Single Line, GR2400 Micro Panel
GR 2400 Relay Panel, Chelsea Digital Switch, GR Unity Software
Outdoor Photocell, Metaserver and Uplink. Digilink
Bus Booster, Key Digital and Key Enable Switch, Link to BACNET IP
1
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
Table of Contents
April 18, 2012
Project Name: LEE BURNESON MIDDLE SCHOOL
Location:
WEST LAKE, OH
Approval Worksheet
...3
Notes
...4
Bill of Materials
...5
Bus 1
...7
Bus 2
. . . 31
Bus 3
. . . 79
Single Line
. . . 111
Warranty Information
. . . 112
GR2400 New Construction Planning Guide
. . . 113
GR2400 Final Activation Checklist
. . . 125
Commissioning Request Form
. . . 130
Product Tech Sheets
. . . 131
2
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
Approval Worksheet
April 18, 2012
Enclosed is the LC&D submittal data for
LEE BURNESON MIDDLE SCHOOL
WEST LAKE, OH
1
2
3
4
5
A
B
C
D
E
Bill Of Material
LCP Panel Schedules
Switch Schedule
Clock Schedule
Single Line Drawing
Typical
Job Specific
X
Verify the accuracy of each sheet.
Enter all missing data in spaces indicated
If RFI is attached, please supply requested data
Correct or change data as required
If you have any questions or require assistance with completing
this submittal, contact the LC&D submittal manager at 800.345.4448
*Please check the appropriate box below. If no selection is made, Submittal is assumed to be "Approved as Submitted".
Waiver of Submittal, signature required*
Note: LC&D will manufacture the lighting control system to the specifications detailed in the attached sheets.
LC&D is not responsible for any changes, errors or omissions of any kind unless noted by correction to
the data attached, signed and dated.
Approved with Corrections Noted*
Note: LC&D will manufacture the lighting control system to the specifications detailed in the attached sheets,
with noted corrections. LC&D is not responsible for any changes, errors or omissions of any kind unless noted
by correction to the data attached, signed and dated.
Approved as Submitted*
Note: LC&D will manufacture the lighting control system to the specifications detailed in the attached sheets.
LC&D is not responsible for any changes, errors or omissions of any kind unless noted by correction to
the data attached, signed and dated.
LC&D will furnish only the equipment detailed in this submittal with noted corrections, if any. LC&D is
not responsible for the Contractor's compliance with the Contract Documents. Any material, parts,
labor, software, training or any other requirements not detailed in this approved submittal shall be the
sole responsibility of the contractor.
Signature:
Date:
Printed Name:
Company:
3
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
Notes
*** Important ***
April 18, 2012
Project Name:
Location:
LEE BURNESON MIDDLE SCHOOL
WEST LAKE, OH
Note 1:
THIS DESIGN INCLUDES ONE INTEGRATED SYSTEM, CONSISTS OF THREE BUSES. DESIGN IS BASED ON E-SHEETS E101-E110 AND E-501 DATED 11-28-11 PROVIDED BY CLIENT. PLEASE VERIFY/CORRECT ALL EQUIPMENT TYPE AND
PROGRAMMING.
Note 2:
LC&D recommends use of Stranded Cat 5 cable over Solid Cat 5 cable for its flexible properties and ease of installation.
Either type shall work as long as they are properly crimped/terminated and routed by qualified installers. Maximum Cat 5
cable length per bus is 4000ft. Exceeding this parameter requires additional equipment and a revised quote.
PLEASE NOTE: Cable routing and distance shall be verified by EC/Installer prior to release and installation. LC&D is NOT
responsible for systems exceeding cabling parameters.
Note 3:
Occupancy sensors and Power Pack to be provided by Sensor Switch, Inc. Dry contact inputs to tie occupancy
sensorswith lighting control system included. ONLY occupancy sensors with relay option can interface with LC&D
lighting control panels. All others will be stand-alone.
Note 4:
This design provides on-site start-up. Contractor is to schedule the on-site visit with LC&D. Please fill out the
Commissioning Request Form included in this submittal and return with the signed approval.
Note 5:
This system provides (1) outdoor photocell to control exterior lighting. The outdoor photocell has 14 trigger points. If
additional photocell is required, please request for a revised quote.
Note 6:
Metaserver and Uplinks are provided to integrate (3) buses, Computers and peripherals are to be provided by others.
Note 7:
Self contained transformer/relay and contactors are to be provided by others.
Note 8:
This design includes BMS/BAS interface. Protocol use is BACnet IP. Protocols available are: BACNet IP, N2, Dry Contacts,
or ModBus
Note 9:
A Digilink is capable of accepting up to 14 dry contact inputs. If more inputs are required, please request for a revised
quote.
Note 10:
GR2400 Bus Booster is provided to prevent voltage drop within the GR2400 bus.
Note 11:
0-10V, 4 wire dimming provided. Client shall verify dimming ballast compatibility prior to release.
Low Voltage dimming provided in specified areas, all other dimming is provided by others.
Low Voltage Panel
Schedule:
Please verify/correct the attached panel schedules.
Low Voltage Switch Please verify/correct the attached switch schedules, by specifying the correct location, programming and engraving information
Schedule:
for each button. For each button we can engrave 2 lines, 8 characters per line.
PLEASE NOTE: If this submittal is waived or accepted "as is" these switches will be shipped as noted in the BUS file.
Photocell Schedule: Please verify/correct the attached photocell schedule.
Time Clock
Schedule:
Please verify/correct the attached time schedule. Times and Loads can be programmed during the start-up process with our Tech
Support Department at (800) 345-4448 x391.
LEED Certification:
Is this project designed to LEED standards? If yes, is it certified Silver, Gold or Platinum?
Sincerely,
EMMANUEL RONQUILLO
Applications Engineer
4
Job Name:
BOM REF #:
Quote Label:
Job Location:
Issue Date:
Good Through:
BOM
Lee Burneson Middle School, Base Bid
11-13637-2
ER_041812
Westlake, Ohio
4/18/2012
AB CONTROLS REGION 1
ONE LITHONIA WAY
CONYERS, GA 30012-3957
Type
Qty
Manufacturer/Brand
Catalog #
Line Comment
BUS 1
1
ABL-Acuity Brands Controls
GR2448 INT 48NCL DTC DV
RP2 (A)
1
ABL-Acuity Brands Controls
GR2448 INT 44NCL REMOTE DV D6 1VB
RP2 (B)
1
ABL-Acuity Brands Controls
GR2448 INT 48NCL REMOTE DV 1VB
3
ABL-Acuity Brands Controls
GR2448 ENC SM NE1
3
ABL-Acuity Brands Controls
GR2400 DIGILINK DV D14 SM NE1
13
ABL-Acuity Brands Controls
CH1 BWH PST
4
ABL-Acuity Brands Controls
CH2 BWH PST
7
ABL-Acuity Brands Controls
CH4 BWH PST
2
ABL-Acuity Brands Controls
KE PST
2
ABL-Acuity Brands Controls
KS PST
1
ABL-Acuity Brands Controls
GR2400 L2 BACNETIP DV SM NE1
1
ABL-Acuity Brands Controls
GR2400 UH4 DV SM NE1
1
ABL-Acuity Brands Controls
GR2448 INT 48NCL DTC DV
RP1 (D)
1
ABL-Acuity Brands Controls
GR2432 INT 32NCL REMOTE DV
RP1 (E)
1
ABL-Acuity Brands Controls
GR2448 INT 48NCL REMOTE DV 1VB
RP1 (D&E EMER)
1
ABL-Acuity Brands Controls
GR2448 INT 48NCL REMOTE DV9%
RP1 (F)
3
ABL-Acuity Brands Controls
GR2448 ENC SM NE1
1
ABL-Acuity Brands Controls
GR2432 ENC SM NE1
1
ABL-Acuity Brands Controls
GR2408 INT 6NCL IDIM8 DV 1VB
1
ABL-Acuity Brands Controls
GR2408 ENC SM NE1
1
ABL-Acuity Brands Controls
GR2400 PCC1 2WO SM NE1
5
ABL-Acuity Brands Controls
GR2400 DIGILINK DV D14 SM NE1
17
ABL-Acuity Brands Controls
CH1 BWH PST
1
ABL-Acuity Brands Controls
CH1 WP BWH PST
23
ABL-Acuity Brands Controls
CH2 BWH PST
3
ABL-Acuity Brands Controls
CH3 BWH PST
8
ABL-Acuity Brands Controls
CH4 BWH PST
BUS 2
5
Job Name:
BOM REF #:
Quote Label:
Job Location:
Issue Date:
Good Through:
BOM
Type
Qty
Manufacturer/Brand
Catalog #
1
ABL-Acuity Brands Controls
KE PST
6
ABL-Acuity Brands Controls
KS PST
1
ABL-Acuity Brands Controls
GR2400 L2 BACNETIP DV SM NE1
1
ABL-Acuity Brands Controls
GR2400 UH4 DV SM NE1
2
ABL-Acuity Brands Controls
GR2400 BOOSTER DV SM NE1
Line Comment
BUS 3
1
ABL-Acuity Brands Controls
GR2448 INT 48NCL DTC DV
RP1 (G)
1
ABL-Acuity Brands Controls
GR2448 INT 4NCL REMOTE DV D6 1VB
RP1 (G EMER)
2
ABL-Acuity Brands Controls
GR2448 ENC SM NE1
3
ABL-Acuity Brands Controls
GR2400 DIGILINK DV D14 SM NE1
24
ABL-Acuity Brands Controls
CH1 BWH PST
2
ABL-Acuity Brands Controls
CH1 WP BWH PST
5
ABL-Acuity Brands Controls
CH2 BWH PST
12
ABL-Acuity Brands Controls
CH4 BWH PST
4
ABL-Acuity Brands Controls
KE PST
1
ABL-Acuity Brands Controls
GR2400 UH4 DV SM NE1
1
ABL-Acuity Brands Controls
GR2400 L2 BACNETIP DV SM NE1
2
ABL-Acuity Brands Controls
GR2400 BOOSTER DV SM NE1
1
ABL-Acuity Brands Controls
GR2400 SH4MOD DV SM NE1
1
ABL-Acuity Brands Controls
FACTORY ONSITE SERVICE
1
ABL-Acuity Brands Controls
FACTORY ENGSRV
1
ABL-Acuity Brands Controls
UNITY VCLOCK
MISCELLANEOUS
6
Lee Burneson Middle School, Base Bid
11-13637-2
ER_041812
Westlake, Ohio
4/18/2012
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
BUS 1
7
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
LCP Location:
Model #: GR2448 INT 48NCL DTC DV SM NE1
LCP Name: RP2 (A) (LCP 1)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
L2 2
NC
R3
L2 1
NC
R5
L2 1
R7
R9
Relay
Line Feed
277V-N A10, A27
R2
EL2 2
NC
277V-E A10, A27
277V-N A15
R4
EL2 1
NC
277V-E A15
NC
277V-N A16 BOARDS
R6
NC
277V-E SPARE
L2 1
NC
277V-N A16 INSIDE LAMP
R8
NC
277V-E SPARE
L2 1
NC
277V-N A16 OUTSIDE LAMP
R10
NC
277V-E A16 OUTSIDE LAMP
R11
L2 1
NC
277V-N A16A
R12
NC
277V-E SPARE
R13
L2 3
NC
277V-N A18
R14
EL2 1
NC
277V-E A18
R15
L2 3
NC
277V-N A19
R16
EL2 1
NC
277V-E A19
R17
L2 3
NC
277V-N A20
R18
EL2 1
NC
277V-E A20
R19
L2 3
NC
277V-N A21
R20
EL2 1
NC
277V-E A21
R21
L2 5
NC
277V-N A22
R22
NC
277V-E SPARE
R23
L2 5
NC
277V-N A23
R24
EL2 1
NC
277V-E A23
R25
L2 5
NC
277V-N A24
R26
EL2 1
NC
277V-E A24
R27
L2 4
NC
277V-N A28
R28
EL2 1
NC
277V-E A28
R29
L2 4
NC
277V-N A30 BOARDS
R30
NC
277V-E SPARE
R31
L2 4
NC
277V-N A30 INSIDE LAMP
R32
NC
277V-E SPARE
R33
L2 4
NC
277V-N A30 OUTSIDE LAMP
R34
EL2 1
NC
277V-E A30 OUTSIDE LAMP
R35
L2 8
NC
277V-N A31, B10,B11,C31
R36
EL2 2
NC
277V-E A31, B10,B11,C31
R37 P2A59 41
NC
120V-N DISPLAY CASE
R38
NC
277V-E SPARE
R39
NC
277V-N SPARE
R40
NC
277V-E SPARE
R41
NC
277V-N SPARE
R42
NC
277V-E SPARE
R43
NC
277V-N SPARE
R44
NC
277V-E SPARE
R45
NC
277V-N SPARE
R46
NC
277V-E SPARE
R47
NC
277V-N SPARE
R48
NC
277V-E SPARE
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Load Name
Accessories:
EL2 1
Relay Summary:
DTC Clock
Active Relays: 31
Mounting: Surface
Zone Type Voltage
Load Name
Relay Types:
Single Pole (NC): 48
Spare Relays: 17
NEMA Rating: 1
Total Relays: 48
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 1-6
8
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
LCP Location:
Model #: GR2448 INT 44NCL REMOTE DV D6 SM NE1 1VB
LCP Name: RP2 (B) (LCP 2)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
L2 7
NC
277V-N B12 INSIDE LAMP
R2
NC
277V-E SPARE
R3
L2 7
NC
277V-N B12 OUTSIDE LAMP
R4
NC
277V-E SPARE
R5
L2 7
NC
277V-N B13 INSIDE LAMP
R6
NC
277V-E SPARE
R7
L2 7
NC
277V-N B13 OUTSIDE LAMP
R8
NC
277V-E SPARE
R9
L2 10
NC
277V-N B14
R10
NC
277V-E SPARE
R11
L2 10
NC
277V-N B15 BOARD LIGHTS
R12
NC
277V-E SPARE
R13
L2 10
NC
277V-N B15 INSIDE LAMP
R14
NC
277V-E SPARE
R15
L2 10
NC
277V-N B15 OUTSIDE LAMP
R16
NC
277V-E B15 OUTSIDE LAMP
R17
L2 7
NC
277V-N B18 BOARD LIGHTS
R18
NC
277V-E SPARE
R19
L2 7
NC
277V-N B18 INSIDE LAMP
R20
NC
277V-E SPARE
R21
L2 7
NC
277V-N B18 OUTSIDE LAMP
R22
NC
277V-E B18 OUTSIDE LAMP
R23
L2 7
NC
277V-N B19
R24
NC
277V-E SPARE
R25
L2 12
NC
277V-N B25
R26
EL2 2
NC
277V-E B25
R27
L2 12
NC
277V-N B25A/V
R28
EL2 2
NC
277V-E B24
R29
L2 8
NC
277V-N B24
R30
EL2 4
NC
277V-E EXTERIOR LTG
R31
L2 12
NC
277V-N B27
R32
EL2 2
NC
277V-E B27
R33
L2 12
NC
277V-N B27 A/V
R34
L2 22
NC
277V-N BARRIER GATE #1
R35
L2 11
NC
277V-N PARKING LOT LTG
R36
L2 18
NC
277V-N BARRIER GATE #2
R37
L2 13
NC
277V-N PARKING LOT LTG
R38
L2 20
NC
277V-N BARRIER GATE #3
R39
L2 15
NC
277V-N EXTERIOR LTG
R40
NC
277V-N SPARE
R41
P2A 81
NC
277V-N EXHAUSTFAN EF-6
R42
Space 277V-N BARRIER GATE #1
R43
L2 17
NC
277V-N PARKING LOT LTG
R44
Space 277V-N BARRIER GATE #2
R45
L2 19
NC
277V-N PARKING LOT LTG
R46
Space 277V-N BARRIER GATE #3
NC
277V-N SPARE
R48
Space 277V-N BARRIER GATE #4
R47
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Load Name
Accessories:
Relay
Line Feed
EL2 2
EL2 2
Relay Summary:
DigiLink ID#13
Active Relays: 32
Mounting: Surface
Zone Type Voltage
Load Name
Relay Types:
Single Pole (NC): 44
Spare Relays: 12
NEMA Rating: 1
Total Relays: 44
Door Type: Hinged, Locking
Spaces: 4
Comments:
RELAY 42,44,46&48 TO BE WIRE TO DIGILINK INPUTS 1-4 CONSECUTIVELY.
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 7-12
9
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments: USED FOR BARRIER GATE CONTROLS
DigiLink Location: RP2 (B)
DigiLink Name: BARRIER GATE
Model #: GR400 DIGILINK D6
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
GROUP22
INPUT 1
2
Maintain
GROUP23
INPUT 2
3
Maintain
GROUP24
INPUT 3
4
Maintain
GROUP25
INPUT 4
5
Maintain
INPUT 5
6
Maintain
INPUT 6
Programming Section Only
Serial #:
Control Card Address: 13
10
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments: WIRE NORMALLY CLOSED OCCUPANCY
DigiLink Location: A30
SENSOR RELAY TO THE INPUT AND GND.
DigiLink Name: OCC INPUT 1 #21
Model #: GR2400 DIGILINK DV D14 SM NE1
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Off Mode
LCP 1:11
A16A
2
Off Mode
LCP 1:23-24
A23
3
Off Mode
LCP 1:29,31,33-34
A30
4
Off Mode
LCP 2:17,19,21-22
B18
5
Off Mode
LCP 2:1,3
B12
6
Off Mode
LCP 2:5,7
B13
7
Maintain
8
Off Mode
LCP 2:11,13,15-16
B15
9
Off Mode
LCP 2:9
B14
10
Off Mode
LCP 2:23
B19
11
Off Mode
LCP 2:25-27
B25
12
Off Mode
LCP 2:31-33
B27
13
Maintain
INPUT 13
14
Maintain
INPUT 14
INPUT 7
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 21
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
11
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments: WIRE NORMALLY OPEN OCCUPANCY
DigiLink Location: A30
SENSOR RELAY TO THE INPUT AND GND.
DigiLink Name: OCC INPUT 2 #22
Model #: GR2400 DIGILINK DV D14 SM NE1
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
LCP 1:1-2
A10, A27
2
Maintain
LCP 1:13-14
A18
3
Maintain
LCP 1:15-16
A19
4
Maintain
LCP 1:17-18
A20
5
Maintain
LCP 1:19-20
A21
6
Maintain
LCP 1:21
A22
7
Maintain
8
Maintain
LCP 1:25-26
A24
9
Maintain
LCP 1:35-36
A31, B10,B11,C31
10
Maintain
LCP 2:28-29
B24
11
Maintain
INPUT 11
12
Maintain
INPUT 12
13
Maintain
INPUT 13
14
Maintain
INPUT 14
INPUT 7
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 22
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
12
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments: WIRE NORMALLY OPEN OCCUPANCY
DigiLink Location: C20
SENSOR RELAY TO THE INPUT 1-6 AND GND.
DigiLink Name: OCC INPUT 3 #35
WIRE NORMALLY CLOSED OCCUPANCY
Model #: GR2400 DIGILINK DV D14 SM NE1
SENSOR RELAY TO THE INPUT 8-13 AND GND.
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
LCP 3:1-2
C10, C27
2
Maintain
LCP 3:13-14
C18
3
Maintain
LCP 3:15-16
C19
4
Maintain
LCP 3:17-18
C20
5
Maintain
LCP 3:19-20
C21
6
Maintain
LCP 3:21
C22
7
Maintain
INPUT 7
8
Maintain
LCP 3:25-26
C24
9
Off Mode
LCP 3:29,31,33
C30
10
Off Mode
LCP 3:5,7,9-10
C16
11
Off Mode
LCP 3:11
C16A
12
Off Mode
LCP 3:3-4
C15
13
Off Mode
LCP 3:23-24
C23
14
Maintain
INPUT 14
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 35
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
13
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
LCP Location:
Model #: GR2448 INT 48NCL REMOTE DV SM NE1 1VB
LCP Name: RP3 (C) (LCP 3)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
L3 1
NC
R3
L3 2
NC
R5
L3 2
R7
R9
Relay
Line Feed
277V-N C10, C27
R2
EL3 1
NC
277V-E C10, C27
277V-N C15
R4
EL3 1
NC
277V-E C15
NC
277V-N C16 BOARD LIGHTS
R6
NC
277V-E SPARE
L3 2
NC
277V-N C16 INSIDE LAMP
R8
NC
277V-E SPARE
L3 2
NC
277V-N C16 OUTSIDE LAMP
R10
NC
277V-E C16 OUTSIDE LAMP
R11
L3 2
NC
277V-N C16A
R12
NC
277V-E SPARE
R13
L3 3
NC
277V-N C18
R14
EL3 1
NC
277V-E C18
R15
L3 3
NC
277V-N C19
R16
EL3 1
NC
277V-E C19
R17
L3 3
NC
277V-N C20
R18
EL3 1
NC
277V-E C20
R19
L3 3
NC
277V-N C21
R20
EL3 1
NC
277V-E C21
R21
L3 3
NC
277V-N C22
R22
EL3 1
NC
277V-E SPARE
R23
L3 3
NC
277V-N C23
R24
EL3 1
NC
277V-E C23
R25
L3 8
NC
277V-N C24
R26
EL3 1
NC
277V-E C24
R27
L3 3
NC
277V-N C28
R28
EL3 1
NC
277V-E C28
R29
L3 4
NC
277V-N C30 BOARD LIGHTS
R30
EL3 2
NC
277V-E EXTERIOR LIGHTNG
R31
L3 4
NC
277V-N C30 INSIDE LAMP
R32
EL3 4
NC
277V-E COURTYARD
R33
L3 4
NC
277V-N C30 OUTSIDE LAMP
R34
NC
277V-N SPARE
R35
P3A 61
NC
120V-N DISPLAY CASE
R36
NC
277V-N SPARE
R37
L3 6
NC
277V-N PARKING LOT
R38
NC
277V-N SPARE
R39
L3 8
NC
277V-N PARKING LOT
R40
NC
277V-N SPARE
R41
L3 7
NC
277V-N EXTERIOR LIGHTNG
R42
NC
277V-N SPARE
R43
L3 10
NC
277V-N COURTYARD
R44
NC
277V-N SPARE
R45
L3 12
NC
277V-N BARRIER GATE 4
R46
NC
277V-N SPARE
NC
277V-N SPARE
R48
NC
277V-N SPARE
R47
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Accessories:
Load Name
EL3 1
Relay Summary:
None
Active Relays: 35
Mounting: Surface
Zone Type Voltage
Load Name
Relay Types:
Single Pole (NC): 48
Spare Relays: 13
NEMA Rating: 1
Total Relays: 48
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 38-43
14
CommLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
CommLink Location:
CommLink Name:
Interface to: GR2400 UH4 DV SM NE1
Supply Circuit:
Comments:
Enclosure:
Programming Section Only
Dimensions: 8.4"H x 8.4"W x 3.125"D
Serial #:
Mounting: Surface
Control Card Address: 120
NEMA Rating: 1
Door Type: Screw Cover
15
CommLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
CommLink Location:
CommLink Name:
Interface to: GR2400 L2 BACNETIP DV SM NE1
Supply Circuit:
Comments:
Enclosure:
Programming Section Only
Dimensions: 8.4"H x 8.4"W x 3.125"D
Serial #:
Mounting: Surface
Control Card Address: 126
NEMA Rating: 1
Door Type: Screw Cover
16
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A15 (ADD #14)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:3-4
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 14
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A16A (ADD #15)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:11
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 15
17
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A16 (ADD #16)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:7
A
White
2
Toggle
LCP 1:9-10
B
White
3
Toggle
LCP 1:5
4
Mix Mode
Line 1
On:LCP 1:7 Off:LCP 1:9-10
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 16
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A DISPLAY #17
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 1:37
2
Off Mode
LCP 1:37
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 17
18
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A23 (ADD #18)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:23-24
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 18
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A28 (ADD #19)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:27-28
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 19
19
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: A30 (ADD #20)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:31
A
White
2
Toggle
LCP 1:33-34
B
White
3
Toggle
LCP 1:29
4
Mix Mode
Line 1
On:LCP 1:31 Off:LCP 1:29,33-34
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 20
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B19 (ADD #23)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 2:23
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 23
20
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B19 (ADD #24)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 2:23
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 24
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B18 (ADD #25)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:19
A
White
2
Toggle
LCP 2:21-22
B
White
3
Toggle
LCP 2:17
4
Mix Mode
On:LCP 2:19 Off:LCP 2:17,21-22
Line 1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 25
21
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B12 (ADD #26)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:1
A
White
2
Toggle
LCP 2:3
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 26
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B13 (ADD #27)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:5
A
White
2
Toggle
LCP 2:7
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 27
22
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B15 (ADD #28)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:13
A
White
2
Toggle
LCP 2:15-16
B
White
3
Toggle
LCP 2:11
4
Mix Mode
Line 1
On:LCP 2:13 Off:LCP 2:11,15-16
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 28
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B14 (ADD #29)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 2:9
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 29
23
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B14 (ADD #30)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 2:9
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 30
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B25 (ADD #31)
Switch Type: Chelsea
Model #: CH2 BWH PST
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:25-26
2
Toggle
LCP 2:27
Engraving
Line 1
Line 2
Color
A
White
A/V
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 31
24
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: B27 (ADD #32)
Switch Type: Chelsea
Model #: CH2 BWH PST
Button #
Function
1
Toggle
LCP 2:31-32
2
Toggle
LCP 2:33
Engraving
Zones or Relays Controlled
Line 1
Line 2
Color
A
White
A/V
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 32
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C30 (ADD #33)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 3:31
A
White
2
Toggle
LCP 3:33
B
White
3
Toggle
LCP 3:29
BOARD
LIGHTS
White
4
Mix Mode
A/V
MODE
White
On:LCP 3:31 Off:LCP 3:29,33
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 33
25
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C DISPLAY #34
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 3:35
2
Off Mode
LCP 3:35
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 34
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C16 (ADD #36)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 3:7
A
White
2
Toggle
LCP 3:9-10
B
White
3
Toggle
LCP 3:5
4
Mix Mode
On:LCP 3:7 Off:LCP 3:5,9-10
Line 1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 36
26
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C16A (ADD #37)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 3:11
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 37
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C15 (ADD #44)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 3:3-4
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 44
27
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C28 (ADD #45)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 3:27-28
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 45
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: C23 (ADD #46)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 3:23-24
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 46
28
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments:
Switch Location:
Switch Name: GATE (ADD #47)
Switch Type: Chelsea w/ KeyEnable
Model #: CH4 BWH PST
KE PST
Button #
Function
1
Toggle
2
Toggle
3
4
Engraving
Zones or Relays Controlled
Color
Line 1
Line 2
LCP 2:42
#1
BARRIER
White
LCP 2:44
#1
BARRIER
White
Toggle
LCP 2:46
#2
BARRIER
White
Toggle
LCP 2:48
#2
BARRIER
White
Options: KeyEnable Switch
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 47
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 1
Comments: BTN7=1-6 >9-14= LCP 2:47=ON
BTN 9 = GROUP 27
Switch Location:
Switch Name: PARKING (ADD#48)
Switch Type: Chelsea w/ KeyEnable
Model #: CH1 BWH PST
KE PST
Button #
Function
1
Mntry On
Zones or Relays Controlled
GROUP26
Options: KeyEnable Switch
Engraving
Line 1
Line 2
PARKING
LOT
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 48
29
Group Schedule
By Lighting Control & Design
Job Name : LEE BURNESON MIDDLE SCHOOL-BUS 1
Job Location : WEST LAKE, OH
Group #
Group Name
Function
Auto On
Timer Out
Blink Warning
No
2:00:00
05 min.
GROUP 1 -- 16 are not used
17
18
19
20
21
22
23
24
25
26
27
GLOBAL 4AM/11PM
LCP 2
35,43
LCP 3
37
SCHED DUSK-DAWN
LCP 2
37,45
LCP 3
39
PCELL DUSK-DAWN
LCP 2
30,35,39,43
LCP 3
30,37,41
DUSK-11PM
LCP 3
32,43
11PM OFF
LCP 1
27-28,37
LCP 3
27-28,35
BARRIER GATE 1
LCP 2
34
BARRIER GATE 2
LCP 2
36
BARRIER GATE 3
LCP 2
38
BARRIER GATE 4
LCP 3
45
PARKING LOT
LCP 2
35,37,43,45,47
LCP 3
37,39
PARKING LOT OFF
LCP 2
35,37,43,45,47
LCP 3
37,39
Maintain
Maintain
Maintain
Maintain
Maintain+Offsweep
Maintain
Maintain
Maintain
Maintain
Momentary On
Momentary Off
GROUP 28 -- 32 are not used
30
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
BUS 2
31
Time Clock Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Job Location: WEST LAKE, OH
Schedule#:1 Type: 7 Day
On Time:
Schedule Name: Schedule 1
Off Time:
Monday: 4:00:00 AM
11:00:00 PM
Tuesday: 4:00:00 AM
11:00:00 PM
Wednesday: 4:00:00 AM
11:00:00 PM
Group Name: GLOBAL 4AM/11PM
Thursday: 4:00:00 AM
11:00:00 PM
Friday: 4:00:00 AM
11:00:00 PM
From: Jan 1
Saturday: 4:00:00 AM
11:00:00 PM
Sunday: 4:00:00 AM
11:00:00 PM
Holiday 1: Not Omitted
Not Omitted
Holiday 2: Not Omitted
Not Omitted
Group#: 17
Type: MDLQWDLQ
To: Dec 31
Zones or Relays Controlled:
Comments:
LCP 2:28
Schedule#:2 Type: 7 Day
On Time:
Schedule Name: Schedule 2
Group#: 18
Type: Maintain
Group Name: SCHED DUSK-DAWN
From: Jan 1
To: Dec 31
Zones or Relays Controlled:
Off Time:
Monday: Dusk-0min
Dawn-0min
Tuesday: Dusk-0min
Dawn-0min
Wednesday: Dusk-0min
Dawn-0min
Thursday: Dusk-0min
Dawn-0min
Friday: Dusk-0min
Dawn-0min
Saturday: Dusk-0min
Dawn-0min
Sunday: Dusk-0min
Dawn-0min
Holiday 1: Not Omitted
Not Omitted
Holiday 2: Not Omitted
Not Omitted
Comments:
LCP 2:30
Schedule#:3 Type: 7 Day
On Time:
Schedule Name: Schedule 3
Group#: 20
Type: Maintain
Group Name: SCHED DUSK-11PM
From: Jan 1
To: Dec 31
Zones or Relays Controlled:
Monday: Dusk-0min
11:00:00 PM
Tuesday: Dusk-0min
11:00:00 PM
Wednesday: Dusk-0min
11:00:00 PM
Thursday: Dusk-0min
11:00:00 PM
Friday: Dusk-0min
11:00:00 PM
Saturday: Dusk-0min
11:00:00 PM
Sunday: Dusk-0min
11:00:00 PM
Holiday 1: Not Omitted
Not Omitted
Holiday 2: Not Omitted
Not Omitted
Comments:
32
Off Time:
Time Clock Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Job Location: WEST LAKE, OH
Schedule#:4 Type: 7 Day
On Time:
Schedule Name: Schedule 4
Off Time:
Monday: 5:30:00 AM
11:00:00 PM
Tuesday: 5:30:00 AM
11:00:00 PM
Wednesday: 5:30:00 AM
11:00:00 PM
Group Name: 11PM OFF
Thursday: 5:30:00 AM
11:00:00 PM
Friday: 5:30:00 AM
11:00:00 PM
From: Jan 1
Saturday: 5:30:00 AM
11:00:00 PM
Sunday: 5:30:00 AM
11:00:00 PM
No Automatic On Timer Out: 2:00:00
Holiday 1: Not Omitted
Not Omitted
Blink Warning: 5 Min
Holiday 2: Not Omitted
Not Omitted
Group#: 21
Type: Maintain+Offsweep
To: Dec 31
Zones or Relays Controlled:
Comments:
LCP 1:12-14,33,48; LCP 2:10,22; LCP 3:24,37,
45; LCP 4:16,26,31,33,44-46,48
Schedule#:6 Type: 7 Day
On Time:
Schedule Name: Schedule 6
Group#: 21
Type: Maintain+Offsweep
Group Name: 11PM OFF
From: Jan 1
To: Dec 31
No Automatic On Timer Out: 2:00:00
Blink Warning: 5 Min
Zones or Relays Controlled:
Off Time:
Monday: 5:30:00 AM
7:00:00 PM
Tuesday: 5:30:00 AM
7:00:00 PM
Wednesday: 5:30:00 AM
7:00:00 PM
Thursday: 5:30:00 AM
7:00:00 PM
Friday: 5:30:00 AM
7:00:00 PM
Saturday: 5:30:00 AM
7:00:00 PM
Sunday: 5:30:00 AM
7:00:00 PM
Holiday 1: Not Omitted
Not Omitted
Holiday 2: Not Omitted
Not Omitted
Comments:
LCP 1:12-14,33,48; LCP 2:10,22; LCP 3:24,37,
45; LCP 4:16,26,31,33,44-46,48
Schedule#:7 Type: 7 Day
On Time:
Schedule Name: Schedule 7
Group#: 24
Type: Maintain
Group Name: BARRIER GATE 3
From: Jan 1
To: Dec 31
Zones or Relays Controlled:
Monday: 5:30:00 AM
7:30:00 PM
Tuesday: 5:30:00 AM
7:30:00 PM
Wednesday: 5:30:00 AM
7:30:00 PM
Thursday: 5:30:00 AM
7:30:00 PM
Friday: 5:30:00 AM
7:30:00 PM
Saturday: 5:30:00 AM
7:30:00 PM
Sunday: 5:30:00 AM
7:30:00 PM
Holiday 1: Not Omitted
Not Omitted
Holiday 2: Not Omitted
Not Omitted
Comments:
33
Off Time:
Time Clock Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Job Location: WEST LAKE, OH
Schedule#:8 Type: 7 Day
On Time:
Schedule Name: Schedule 8
Off Time:
Monday: 5:30:00 AM
7:30:00 PM
Tuesday: 5:30:00 AM
7:30:00 PM
Wednesday: 5:30:00 AM
7:30:00 PM
Group Name: BARRIER GATE 4
Thursday: 5:30:00 AM
7:30:00 PM
Friday: 5:30:00 AM
7:30:00 PM
From: Jan 1
Saturday: 5:30:00 AM
7:30:00 PM
Sunday: 5:30:00 AM
7:30:00 PM
Holiday 1: Not Omitted
Not Omitted
Holiday 2: Not Omitted
Not Omitted
Group#: 25
Type: Maintain
To: Dec 31
Zones or Relays Controlled:
Comments:
34
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: WIRE NORMALLY OPEN OCCUPANCY
DigiLink Location: F21
SENSOR RELAY TO THE INPUT 1-6 AND GND.
DigiLink Name: OCC INPUT 1 #13
WIRE NORMALLY CLOSED OCCUPANCY
Model #: GR2400 DIGILINK DV D14 SM NE1
SENSOR RELAY TO THE INPUT 8-14 AND GND.
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
LCP 4:22,41
F22C
2
Maintain
LCP 4:24,43
F22F
3
Maintain
LCP 4:1-2
F10, F10A
4
Maintain
LCP 4:3-4
F11, C10
5
Maintain
LCP 4:5-6
F12
6
Maintain
LCP 4:7-8
F13
7
Maintain
INPUT 7
8
Maintain
LCP 4:28,47
F14
9
Off Mode
LCP 4:10,13,15
F17
10
Off Mode
LCP 4:17,19
F18
11
Off Mode
LCP 4:21,23
F19
12
Off Mode
LCP 4:12,14,25,27,29
F21
13
Off Mode
LCP 4:18,35,37
F22A
14
Maintain
LCP 4:20,39
F22B
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 13
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
35
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
LCP Location:
Model #: GR2448 INT 48NCL DTC DV SM NE1
LCP Name: RP1 (D) (LCP 1)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
L1 1
NC
R3
L1 3
NC
R5
L1 3
R7
R9
Load Name
Relay
Line Feed
Zone Type Voltage
Load Name
277V-N D10, D10A
R2
L1 1
NC
277V-N D11, D12, D24
277V-N D13 INSIDE LAMP
R4
L1 3
NC
277V-N D13 OUTSIDE LAMP
NC
277V-N D14 INSIDE LAMP
R6
L1 3
NC
277V-N D14 OUTSIDE LAMP
L1 3
NC
277V-N D15 INSIDE LAMP
R8
L1 3
NC
277V-N D15 OUTSIDE LAMP
L1 3
NC
277V-N D17 INSIDE LAMP
R10
L1 3
NC
277V-N D17 OUTSIDE LAMP
R11
L1 3
NC
277V-N D17A
R12
L1 3
NC
277V-N D17 CLNC BED "A"
R13
L1 3
NC
277V-N D17 CLNC BED "B"
R14
L1 3
NC
277V-N D17 CLNC BED "C"
R15
L1 3
NC
277V-N D18
R16
L1 2
NC
277V-N SPARE
R17
L1 3
NC
277V-N D19 INSIDE LAMP
R18
L1 3
NC
277V-N D19 OUTSIDE LAMP
R19
L1 5
NC
277V-N D20 INSIDE LAMP
R20
L1 5
NC
277V-N D20 OUTSIDE LAMP
R21
L1 5
NC
277V-N D21 INSIDE LAMP
R22
L1 5
NC
277V-N D21 OUTSIDE LAMP
R23
L1 5
NC
277V-N D22 INSIDE LAMP
R24
L1 5
NC
277V-N D22 OUTSIDE LAMP
R25
L1 5
NC
277V-N D23 INSIDE LAMP
R26
L1 5
NC
277V-N D23 OUTSIDE LAMP
R27
L1 5
NC
277V-N D25
R28
L1 5
NC
277V-N D26
R29
L1 5
NC
277V-N D27
R30
L1 1
NC
277V-N D28A,D29, E10
R31
L1 5
NC
277V-N D28 INSIDE LAMP
R32
L1 5
NC
277V-N D28 OUTSIDE LAMP
R33
L1 5
NC
277V-N D30
R34
L1 5
NC
277V-N D31
R35
L1 5
NC
277V-N D32
R36
L1 5
NC
277V-N D33
R37
L1 5
NC
277V-N D34 INSIDE LAMP
R38
L1 5
NC
277V-N D34 OUTSIDE LAMP
R39
L1 2
NC
277V-N D35
R40
L1 2
NC
277V-N D36
R41
L1 2
L1 2
NC
277V-N D37
R42
NC
277V-N D38A
R43
NC
277V-N SPARE
R44
NC
277V-N SPARE
R45
NC
277V-N SPARE
R46
NC
277V-N SPARE
R47
NC
277V-N SPARE
R48
NC
120V-N D10 DISPLAY CASE
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Accessories:
P1B 14
Relay Summary:
DTC Clock
Active Relays: 42
Mounting: Surface
Relay Types:
Single Pole (NC): 48
Spare Relays: 6
NEMA Rating: 1
Total Relays: 48
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 21-26
36
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
LCP Location:
Model #: GR2432 INT 32NCL REMOTE DV SM NE1
LCP Name: RP1 (E) (LCP 2)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
Load Name
Relay
Line Feed
Zone Type Voltage
Load Name
R1
L1 18
NC
277V-N E11 INSIDE LAMP
R2
L1 18
NC
277V-N E11 OUTSIDE LAMP
R3
L1 18
NC
277V-N E11 BOARD LIGHTS
R4
L1 18
NC
277V-N E11A
R5
L1 18
NC
277V-N E12 BOARD LIGHT
R6
L1 18
NC
277V-N E11B
R7
L1 18
NC
277V-N E12 INSIDE LAMP
R8
L1 18
NC
277V-N E12 OUTSIDE LAMP
R9
L1 21
NC
277V-N E15 BOARD LIGHT
R10
L1 2
NC
277V-N E14A
R11
L1 21
NC
277V-N E15 INSIDE LAMP
R12
L1 21
NC
277V-N E15 OUTSIDE LAMP
R13
L1 19
NC
277V-N E16 INSIDE LAMP
R14
L1 19
NC
277V-N E16 OUTSIDE LAMP
R15
L1 19
NC
277V-N E16A
R16
L1 19
NC
277V-N E16B
R17
L1 19
NC
277V-N E16C INSIDE LAMP
R18
L1 19
NC
277V-N E16C OUTSDE LAMP
R19
L1 17
NC
277V-N E17 INSIDE LAMP
R20
L1 17
NC
277V-N E17 OUTSIDE LAMP
R21
L1 17
NC
277V-N E17 BOARD LIGHT
R22
L1 18
NC
277V-N E18
R23
L1 19
NC
277V-N E16 CIRC DESKCAN
R24
NC
277V-N SPARE
R25
NC
277V-N SPARE
R26
NC
277V-N SPARE
R27
NC
277V-N SPARE
R28
L1 22
NC
277V-N PARKING LOT LTG
R29
NC
277V-N SPARE
R30
L1 24
NC
277V-N PARKING LOT LTG
NC
120V-N E10 DISPLAY CASE
R32
L1 23
NC
277V-N EXTERIOR LIGHTNG
R31
P1A 64
Enclosure:
Dimensions: 25.5"H x 20"W x 6"D
Accessories:
Relay Summary:
None
Active Relays: 27
Mounting: Surface
Relay Types:
Single Pole (NC): 32
Spare Relays: 5
NEMA Rating: 1
Total Relays: 32
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 27-30
37
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
LCP Location:
Model #: GR2448 INT 48NCL REMOTE DV SM NE1 1VB
LCP Name: RP1 (D&E EMER) (LCP 3)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
EL1 1
NC
R3
EL1 5
NC
R5
EL1 5
R7
R9
Relay
Line Feed
277V-E D10, D10A
R2
EL1 1
NC
277V-E D11, D12,D24
277V-E D13 INSIDE LAMP
R4
EL1 5
NC
277V-E D13 OUTSIDE LAMP
NC
277V-E D14 INSIDE LAMP
R6
EL1 5
NC
277V-E D14 OUTSIDE LAMP
EL1 5
NC
277V-E D15 INSIDE LAMP
R8
EL1 5
NC
277V-E D15 OUTSIDE LAMP
EL1 1
NC
277V-E D17 INSIDE LAMP
R10
EL1 1
NC
277V-E D17 OUTSIDE LAMP
R11
EL1 1
NC
277V-E D17A
R12
EL1 3
NC
277V-E D18
R13
EL1 5
NC
277V-E D20 INSIDE LAMP
R14
EL1 5
NC
277V-E D20 OUTSIDE LAMP
R15
EL1 5
NC
277V-E D21 INSIDE LAMP
R16
EL1 5
NC
277V-E D21 OUTSIDE LAMP
R17
EL1 5
NC
277V-E D22 INSIDE LAMP
R18
EL1 5
NC
277V-E D22 OUTSIDE LAMP
R19
EL1 5
NC
277V-E D23 INSIDE LAMP
R20
EL1 5
NC
277V-E D23 OUTSIDE LAMP
R21
EL1 1
NC
277V-E D28 INSIDE LAMP
R22
EL1 1
NC
277V-E D28 OUTSIDE LAMP
R23
EL1 1
NC
277V-E D28A, D29, E10
R24
EL1 1
NC
277V-E D30
R25
EL1 1
NC
277V-E D31
R26
EL1 1
NC
277V-E D32
R27
EL1 4
NC
277V-E D34 INSIDE LAMP
R28
EL1 4
NC
277V-E D34 OUTSIDE LAMP
R29
EL1 1
NC
277V-E D33
R30
EL1 1
NC
277V-E D36
R31
EL1 1
NC
277V-E D37
R32
EL1 5
NC
277V-E D38A
R33
EL1 4
NC
277V-E E11 OUTSIDE LAMP
R34
NC
277V-E SPARE
NC
277V-E SPARE
R36
NC
277V-E E12 OUTSIDE LAMP
NC
277V-E E14A
R38
NC
277V-E SPARE
NC
277V-E SPARE
R40
EL1 4
NC
277V-E E15 OUTSIDE LAMP
NC
277V-E E16 INSIDE LAMP
R42
EL1 4
NC
277V-E E16 OUTSIDE LAMP
NC
277V-E SPARE
R44
EL1 4
NC
277V-E E17 OUTSIDE LAMP
NC
277V-E E18
R46
NC
277V-E SPARE
NC
277V-E SPARE
R48
NC
277V-E EXTERIOR LIGHTNG
R35
R37
EL1 5
R39
R41
EL1 4
R43
R45
EL1 4
R47
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Accessories:
Load Name
EL1 4
EL1 6
Relay Summary:
None
Active Relays: 41
Mounting: Surface
Zone Type Voltage
Load Name
Relay Types:
Single Pole (NC): 48
Spare Relays: 7
NEMA Rating: 1
Total Relays: 48
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 31-36
38
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
LCP Location:
Model #: GR2448 INT 48NCL REMOTE DV SM NE1 1VB
LCP Name: RP1 (F) (LCP 4)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
L1 4
NC
R3
L1 4
NC
R5
L1 4
R7
R9
Relay
Line Feed
277V-N F10, F10A
R2
EL1 3
NC
277V-E F10, F10A
277V-N F11, C10
R4
EL1 3
NC
277V-E F11, C10
NC
277V-N F12
R6
EL1 4
NC
277V-E F12
L1 4
NC
277V-N F13
R8
EL1 4
NC
277V-E F13
L1 6
NC
277V-N F15
R10
EL1 3
NC
277V-E F17 OUTSIDE LAMP
R11
L1 6
NC
277V-N F16
R12
EL1 3
NC
277V-E F21 "A" LAMPS
R13
L1 4
NC
277V-N F17 INSIDE LAMP
R14
EL1 3
NC
277V-E F21 "B" LAMPS
R15
L1 4
NC
277V-N F17 OUTSIDE LAMP
R16
EL1 5
NC
277V-E F22
R17
L1 4
NC
277V-N F18 INSIDE LAMP
R18
EL1 5
NC
277V-E F22A OUTSDE LAMP
R19
L1 4
NC
277V-N F18 OUTSIDE LAMP
R20
EL1 5
NC
277V-E F22B
R21
L1 4
NC
277V-N F19 INSIDE LAMP
R22
EL1 5
NC
277V-E F22C
R23
L1 4
NC
277V-N F19 OUTSIDE LAMP
R24
EL1 5
NC
277V-E F22F
R25
L1 7
NC
277V-N F21 "A" LAMPS
R26
EL1 5
NC
277V-E F22G
R27
L1 7
NC
277V-N F21 "B" LAMPS
R28
EL1 4
NC
277V-E F14
R29
L1 7
NC
277V-N F21 "C" LAMPS
R30
P1C 1
NC
120V-N EXHAUST FAN EF23
R31
L1 7
NC
277V-N F21 CANS "C"
R32
P1C 1
NC
120V-N EXHAUST FAN EF22
R33
L1 12
NC
277V-N F22
R34
P1C 16
NC
120V-N EXHAUST FAN EF13
R35
L1 12
NC
277V-N F22A INSIDE LAMP
R36
P1C 16
NC
120V-N EXHAUST FAN EF12
R37
L1 12
NC
277V-N F22A OUTSDE LAMP
R38
P1C 18
NC
120V-N EXHAUST FAN EF14
R39
L1 12
NC
277V-N F22B
R40
P1C 18
NC
120V-N EXHAUST FAN EF15
R41
L1 12
NC
277V-N F22C
R42
P1C 18
NC
120V-N EXHAUST FAN EF16
R43
L1 12
NC
277V-N F22F
R44
P1C 40
NC
120V-N EXHAUST FAN EF17
R45
L1 12
NC
277V-N F22G
R46
P1A 62
NC
120V-N F11 DISPLAY CASE
R47
L1 4
NC
277V-N F14
R48
P1A 64
NC
120V-N F21 DISPLAY CASE
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Accessories:
Load Name
Relay Summary:
None
Active Relays: 48
Mounting: Surface
Zone Type Voltage
Load Name
Relay Types:
Single Pole (NC): 48
Spare Relays: 0
NEMA Rating: 1
Total Relays: 48
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 37-42
39
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: WIRE NORMALLY OPEN OCCUPANCY
DigiLink Location: E16B
SENSOR RELAY TO THE INPUT 1-2 AND GND.
DigiLink Name: OCC INPUT 2 #55
WIRE NORMALLY CLOSED OCCUPANCY
Model #: GR2400 DIGILINK DV D14 SM NE1
SENSOR RELAY TO THE INPUT 3-14 AND GND.
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
LCP 2:4
E11A
2
Maintain
LCP 2:10; LCP 3:37
E14A
3
Off Mode
LCP 2:1-3; LCP 3:33
E11
4
Off Mode
LCP 2:6
E11B
5
Off Mode
LCP 2:5,7-8; LCP 3:36
E12
6
Off Mode
LCP 2:11-12; LCP 3:40
E15
7
Maintain
8
Off Mode
LCP 2:13-14; LCP 3:41-42
E16
9
Off Mode
LCP 2:15
E16A
10
Off Mode
LCP 2:16
E16B
11
Off Mode
LCP 2:17-18
E16C
12
Off Mode
LCP 2:19-21; LCP 3:44
E17
13
Off Mode
LCP 4:9
F15
14
Off Mode
LCP 4:11
F16
INPUT 7
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 55
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
40
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: WIRE NORMALLY OPEN OCCUPANCY
DigiLink Location: D27
SENSOR RELAY TO THE INPUT AND GND.
DigiLink Name: OCC INPUT 3 #68
Model #: GR2400 DIGILINK DV D14 SM NE1
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
LCP 1:1; LCP 3:1
D10, D10A
2
Maintain
LCP 1:2; LCP 3:2
D11, D12, D24
3
Maintain
LCP 1:11; LCP 3:11
D17A
4
Maintain
LCP 1:15; LCP 3:12
D18
5
Maintain
LCP 1:27
D25
6
Maintain
LCP 1:29
D27
7
Maintain
8
Maintain
LCP 1:30; LCP 3:23
D28A, D29,E10
9
Maintain
LCP 1:34; LCP 3:25
D31
10
Maintain
LCP 1:35; LCP 3:26
D32
11
Maintain
LCP 1:36; LCP 3:29
D33
12
Maintain
LCP 1:40; LCP 3:30
D36
13
Maintain
LCP 1:41; LCP 3:31
D37
14
Maintain
INPUT 7
INPUT 14
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 68
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
41
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: WIRE NORMALLY CLOSED OCCUPANCY
DigiLink Location: D27
SENSOR RELAY TO THE INPUT AND GND.
DigiLink Name: OCC INPUT 4 #69
Model #: GR2400 DIGILINK DV D14 SM NE1
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Off Mode
LCP 1:3-4; LCP 3:3-4
D13
2
Off Mode
LCP 1:5-6; LCP 3:5-6
D14
3
Off Mode
LCP 1:7-8; LCP 3:7-8
D15
4
Off Mode
LCP 1:9-10,12-14; LCP 3:9-10
D17
5
Off Mode
LCP 1:17-18
D19
6
Off Mode
LCP 1:19-20; LCP 3:13-14
D20
7
Maintain
8
Off Mode
LCP 1:21-22; LCP 3:15-16
D21
9
Off Mode
LCP 1:23-24; LCP 3:17-18
D22
10
Off Mode
LCP 1:25-26; LCP 3:19-20
D23
11
Off Mode
LCP 1:28
D26
12
Off Mode
LCP 1:31-32; LCP 3:21-22
D28
13
Off Mode
LCP 1:37-38; LCP 3:27-28
D34
14
Off Mode
LCP 1:39
D35
INPUT 7
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 69
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
42
Dimmer Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: WIRE NORMALLY CLOSED OCCUPANCY
SENSOR RELAY TO THE SCENE 5 AND GND.
LCP Location:
Model #: GR2408 INT 6NCL IDIM8 DV SM 1VB
LCP Name: D16 (LCP 50)
Voltage: 120V Normal
Supply Circuit:
Board Address: 75-76
Serial #:
D16 MOUNTED IN ENCLOSURE WITH D16b
Dimmer Line Feed
Zone Type Voltage
NC
277V-N D16
D2
NC
277V-N SPARE
D3
NC
277V-N SPARE
D4
NC
277V-N SPARE
D1
L1 3
Load Name
Scene5 - OFF : Scene, Fade=00M:03S
D1 : 0%
D2 : 0%
D3 : 0%
Scene6 - ON : Scene, Fade=00M:03S
D4 : 0%
R5 : N/A
R6 : N/A
R7 : N/A
R8 : N/A
R5 : N/A
R6 : N/A
R7 : N/A
R8 : N/A
D1 : Raise
D2 : Raise
D3 : Raise
D4 : Raise
R5 : N/A
Scene8 - LOWER : Lower, Minimum:Off, Fade=00M:03S, Fade=00M:03S
R6 : N/A
R7 : N/A
R8 : N/A
D1 : Lower
R6 : N/A
R7 : N/A
R8 : N/A
D1 : 70%
D2 : 70%
D3 : 70%
D4 : 70%
Scene7 - RAISE : Raise, Fade=00M:03S, Fade=00M:03S
D2 : Lower
D3 : Lower
D4 : Lower
R5 : N/A
Scene 9 to 16 do not have loads.
43
Dimmer Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: SCENE 5 CONNECTED TO SCENE 5 OF CARD 1.
LCP Location:
D16b MOUNTED IN ENCLOSURE WITH D16
LCP Name: D16b (LCP 51)
Voltage: 120V Normal
Supply Circuit:
Board Address: 77-78
Serial #:
Accessories:
Dimmer Line Feed
D1
Zone Type Voltage
EL1 5
D2
NC
277V-E D16
NC
277V-E SPARE
D3
Space 277V-E /// SPACE ///
D4
Space 277V-E /// SPACE ///
Scene5 - OFF : Scene, Fade=00M:03S
CONNECTED TO CARD 1
D1 : 0%
D2 : 0%
D3 : N/A
Scene6 - ON : Scene, Fade=00M:03S
None
Load Name
D4 : N/A
R5 : N/A
R6 : N/A
R7 : N/A
R8 : N/A
D1 : 70%
D2 : 70%
D3 : N/A
D4 : N/A
Scene7 - RAISE : Raise, Fade=00M:03S, Fade=00M:03S
R5 : N/A
R6 : N/A
R7 : N/A
R8 : N/A
D1 : Raise
D2 : Raise
D3 : N/A
D4 : N/A
R5 : N/A
Scene8 - LOWER : Lower, Minimum:Off, Fade=00M:03S, Fade=00M:03S
R6 : N/A
R7 : N/A
R8 : N/A
D1 : Lower
R6 : N/A
R7 : N/A
R8 : N/A
D2 : Lower
D3 : N/A
D4 : N/A
R5 : N/A
Scene 9 to 16 do not have loads.
44
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments: WIRE NORMALLY OPEN OCCUPANCY
SENSOR RELAY TO THE INPUT AND GND.
DigiLink Location:
DigiLink Name: EXHAUST FANS #89
Model #: GR2400 DIGILINK DV D14 SM NE1
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
LCP 4:36
EXHAUST FANS EF-12
2
Maintain
LCP 4:34
EXHAUST FANS EF-13
3
Maintain
LCP 4:38
EXHAUST FANS EF-14
4
Maintain
LCP 4:40
EXHAUST FANS EF-15
5
Maintain
LCP 4:42
EXHAUST FANS EF-16
6
Maintain
LCP 4:44
EXHAUST FANS EF-17
7
Maintain
8
Maintain
LCP 4:32
EXHAUST FANS EF-22
9
Maintain
LCP 4:30
EXHAUST FANS EF-23
10
Maintain
INPUT 10
11
Maintain
INPUT 11
12
Maintain
INPUT 12
13
Maintain
INPUT 13
14
Maintain
INPUT 14
INPUT 7
Enclosure:
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 89
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
45
PCC1 Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Ext. Location:
Card Name:
Model #: GR2400 PCC1 2WO SM NE1
Trigger #
Function
1
Maintain
Zones or Relays Controlled
Trigger Name
GROUP19
TRIGGER 1
Input
Time Triggering when light level
Delay
Analog1 03 min.
falls below
rises above
0020
0030
Programming Section Only
Serial #:
Control Card Address: 100
PhotoCell-1 Name: EXTERIOR
PhotoCell-1 Type: 2WO
46
PhotoCell-1 Location: ROOF FACING NORTH
CommLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
CommLink Location:
CommLink Name:
Interface to: GR2400 UH4 DV SM NE1
Supply Circuit:
Comments:
Enclosure:
Programming Section Only
Dimensions: 8.4"H x 8.4"W x 3.125"D
Serial #:
Mounting: Surface
Control Card Address: 120
NEMA Rating: 1
Door Type: Screw Cover
47
CommLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
CommLink Location:
CommLink Name:
Interface to: GR2400 L2 BACNETIP DV SM NE1
Supply Circuit:
Comments:
Enclosure:
Programming Section Only
Dimensions: 8.4"H x 8.4"W x 3.125"D
Serial #:
Mounting: Surface
Control Card Address: 126
NEMA Rating: 1
Door Type: Screw Cover
48
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F22A (ADD #1)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 4:35
A
White
2
Toggle
LCP 4:20,37
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 1
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F22B (ADD #2)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 4:20,39
Engraving
Line 1
Line 2
LIGHTS
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 2
49
Color
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F22 (ADD #3)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 4:16,33
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 3
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F22 (ADD #4)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 4:16,33
Engraving
Line 1
Line 2
LIGHTS
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 4
50
Color
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F22 (ADD #5)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 4:16,33
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 5
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F22G (ADD #6)
Switch Type: Chelsea
Model #: CH1 WP BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 4:26,45
Engraving
Line 1
Line 2
LIGHTS
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 6
51
Color
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F21 (ADD #7)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 4:12,25
A
White
2
Toggle
LCP 4:14,27
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 7
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F21 (ADD #8)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 4:12,25
A
White
2
Toggle
LCP 4:14,27
B
White
Line 1
Line 2
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 8
52
Color
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F21 (ADD #9)
Switch Type: Chelsea
Model #: CH3 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 4:12,25
A
White
2
Toggle
LCP 4:14,27
B
White
3
Toggle
LCP 4:29
C
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 9
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F21 (ADD #10)
Switch Type: Chelsea
Model #: CH3 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 4:12,25
A
White
2
Toggle
LCP 4:14,27
B
White
3
Toggle
LCP 4:29
C
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 10
53
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F21 DISPLAY #11
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 4:48
2
Off Mode
LCP 4:48
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 11
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F21B (ADD #12)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 4:31
Engraving
Line 1
Line 2
C
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 12
54
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F17 (ADD #14)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 4:13
A
White
2
Toggle
LCP 4:10,15
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 14
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F17 (ADD #15)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 4:13
A
White
2
Toggle
LCP 4:10,15
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 15
55
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F19 (ADD #16)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 4:21
A
White
2
Toggle
LCP 4:23
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 16
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F18 (ADD #17)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 4:17
A
White
2
Toggle
LCP 4:19
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 17
56
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F11 DISPLAY #18
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 4:46
2
Off Mode
LCP 4:46
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 18
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F15 (ADD #19)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 4:9
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 19
57
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: F16 (ADD #20)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 4:11
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 20
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E18 (ADD #43)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 2:22; LCP 3:45
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 43
58
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E18 (ADD #44)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 2:22; LCP 3:45
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 44
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E18 (ADD #45)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 2:22; LCP 3:45
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 45
59
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E11 (ADD #46)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:1
A
White
2
Toggle
LCP 2:2; LCP 3:33
B
White
3
Toggle
LCP 2:3
4
Mix Mode
Line 1
On:LCP 2:1 Off:LCP 3:33
Line 2
Color
BOARD
LIGHTS
White
AV
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 46
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E11B (ADD #47)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 2:6
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 47
60
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E12 (ADD #48)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:7
A
White
2
Toggle
LCP 2:8; LCP 3:36
B
White
3
Toggle
LCP 2:5
4
Mix Mode
Line 1
On:LCP 2:7 Off:LCP 2:5,8; LCP 3:36
Line 2
Color
BOARD
LIGHTS
White
AV
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 48
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E17 (ADD #49)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:19
A
White
2
Toggle
LCP 2:20; LCP 3:44
B
White
3
Toggle
LCP 2:21
4
Mix Mode
On:LCP 2:19 Off:LCP 2:20-21; LCP 3:44
Line 1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 49
61
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E17 (ADD #50)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:19
A
White
2
Toggle
LCP 2:20; LCP 3:44
B
White
3
Toggle
LCP 2:21
4
Mix Mode
Line 1
On:LCP 2:19 Off:LCP 2:20-21; LCP 3:44
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 50
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E16 (ADD #51)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:13; LCP 3:41
A
White
2
Toggle
LCP 2:14; LCP 3:42
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 51
62
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E16C (ADD #52)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:17
A
White
2
Toggle
LCP 2:18
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 52
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E16 (ADD #53)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:13; LCP 3:41
A
White
2
Toggle
LCP 2:14; LCP 3:42
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 53
63
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E16B (ADD #54)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 2:16
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 54
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E10 DISPLAY #56
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 2:31
2
Off Mode
LCP 2:31
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 56
64
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E16A (ADD #57)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 2:15
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 57
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E16 (ADD #58)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:13; LCP 3:41
A
White
2
Toggle
LCP 2:14; LCP 3:42
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 58
65
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E15 (ADD #59)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 2:11
A
White
2
Toggle
LCP 2:12; LCP 3:40
B
White
3
Toggle
LCP 2:9
4
Mix Mode
Line 1
On:LCP 2:11 Off:LCP 2:9,12; LCP 3:40
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 59
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E15 (ADD #60)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 2:11
A
White
2
Toggle
LCP 2:12; LCP 3:40
B
White
3
Toggle
LCP 2:9
4
Mix Mode
On:LCP 2:11 Off:LCP 2:9,12; LCP 3:40
Line 1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 60
66
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: E14A (ADD #61)
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 2:10; LCP 3:37
2
Off Mode
LCP 2:10; LCP 3:37
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 61
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D38A (ADD #62)
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 1:16
2
Off Mode
LCP 1:16
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 62
67
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D35 (ADD #63)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:39
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 63
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D35 (ADD #64)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:39
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 64
68
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D34 (ADD #65)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:37; LCP 3:27
A
White
2
Toggle
LCP 1:38; LCP 3:28
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 65
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D30 (ADD #66)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:33; LCP 3:24
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 66
69
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D28 (ADD #67)
Switch Type: Chelsea w/ KeyEnable
Model #: CH2 BWH PST
KE PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:31; LCP 3:21
A
White
2
Toggle
LCP 1:32; LCP 3:22
B
White
Line 1
Options: KeyEnable Switch
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 67
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D26 (ADD #70)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:28
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 70
70
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D23 (ADD #71)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:25; LCP 3:19
A
White
2
Toggle
LCP 1:26; LCP 3:20
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 71
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D22 (ADD #72)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:23; LCP 3:17
A
White
2
Toggle
LCP 1:24; LCP 3:18
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 72
71
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D21 (ADD #73)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:21; LCP 3:15
A
White
2
Toggle
LCP 1:22; LCP 3:16
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 73
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D20 (ADD #74)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:19; LCP 3:13
A
White
2
Toggle
LCP 1:20; LCP 3:14
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 74
72
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D16 (ADD #79)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 50:6; LCP 51:6
ON
White
2
Maintain
LCP 50:7; LCP 51:7
RAISE
White
3
On Mode
LCP 50:5; LCP 51:5
OFF
White
4
Maintain
LCP 50:8; LCP 51:8
LOWER
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 79
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D16 (ADD #80)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
On Mode
LCP 50:6; LCP 51:6
ON
White
2
Maintain
LCP 50:7; LCP 51:7
RAISE
White
3
On Mode
LCP 50:5; LCP 51:5
OFF
White
4
Maintain
LCP 50:8; LCP 51:8
LOWER
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 80
73
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D19 (ADD #81)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:17
A
White
2
Toggle
LCP 1:18
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 81
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D19 (ADD #82)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:17
A
White
2
Toggle
LCP 1:18
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 82
74
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D15 (ADD #83)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:7; LCP 3:7
A
White
2
Toggle
LCP 1:8; LCP 3:8
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 83
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D14 (ADD #84)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:5; LCP 3:5
A
White
2
Toggle
LCP 1:6; LCP 3:6
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 84
75
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D13 (ADD #85)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:3; LCP 3:3
A
White
2
Toggle
LCP 1:4; LCP 3:4
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 85
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D17 (ADD #86)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:9; LCP 3:9
A
White
2
Toggle
LCP 1:10; LCP 3:10
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 86
76
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D17 (ADD #87)
Switch Type: Chelsea
Model #: CH3 BWH PST
Button #
Function
1
Toggle
2
Toggle
3
Toggle
Engraving
Zones or Relays Controlled
Color
Line 1
Line 2
LCP 1:12
A
BED
White
LCP 1:13
B
BED
White
LCP 1:14
C
BED
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 87
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 2
Comments:
Switch Location:
Switch Name: D10 DISPLAY #88
Switch Type: Key Switch
Model #: KS PST
Button #
Function
Zones or Relays Controlled
1
On Mode
LCP 1:48
2
Off Mode
LCP 1:47
Programming Section Only
Pilot Light Color: Red
Serial #:
Control Card Address: 88
77
Group Schedule
By Lighting Control & Design
Job Name : LEE BURNESON MIDDLE SCHOOL-BUS 2
Job Location : WEST LAKE, OH
Group #
Group Name
Function
Auto On
Timer Out
Blink Warning
No
2:00:00
05 min.
GROUP 1 -- 16 are not used
17
18
19
20
21
22
23
24
25
26
27
GLOBAL 4AM/11PM
0DLQWDLQ
LCP 2
28
SCHED DUSK-DAWN
Maintain
LCP 2
30
PCELL DUSK-DAWN
Maintain
LCP 2
28,32
LCP 3
48
SCHED DUSK-11PM
Maintain
No load assigned
11PM OFF
Maintain+Offsweep
LCP 1
12-14,33,48
LCP 2
10,22
LCP 3
24,37,45
LCP 4
16,26,31,33,44-46,48
BARRIER GATE 1
Maintain
No load assigned
BARRIER GATE 2
Maintain
No load assigned
BARRIER GATE 3
Maintain
No load assigned
BARRIER GATE 4
Maintain
No load assigned
PARKING LOT
Momentary On
LCP 2
28,30
GROUP 27
Momentary Off
LCP 2
28,30
GROUP 28 -- 32 are not used
78
905 Allen Avenue • Glendale, CA 91201 • 800.345.4448 • 323.226.1000-Fax
BUS 3
79
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: WIRE NORMALLY OPEN OCCUPANCY
DigiLink Location: G28
SENSOR RELAY TO THE INPUT 1-6 AND GND.
DigiLink Name: OCC INPUT 1 #6
WIRE NORMALLY CLOSED OCCUPANCY
Model #: GR2400 DIGILINK DV D14 SM NE1
Supply Circuit:
Input #
Function
Zones or Relays Controlled
1
Maintain
LCP 1:40; LCP 2:24
G23
2
Maintain
LCP 1:39
G24
3
Maintain
LCP 1:42; LCP 2:26
G25
4
Maintain
LCP 1:41
G26
5
Maintain
INPUT 5
6
Maintain
INPUT 6
7
Maintain
INPUT 7
8
Off Mode
LCP 1:43,46; LCP 2:27-28
G27
9
Off Mode
LCP 1:46
G28
10
Off Mode
INPUT 10
11
Off Mode
INPUT 11
12
Off Mode
INPUT 12
13
Off Mode
INPUT 13
14
Off Mode
INPUT 14
Enclosure:
Input Name
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 6
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
80
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
LCP Location:
Model #: GR2448 INT 48NCL DTC DV SM NE1
LCP Name: RP1 (G) (LCP 1)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
L1 8
NC
R3
L1 8
NC
R5
L1 6
R7
R9
Relay
Line Feed
277V-N G11 INSIDE LAMP
R2
L1 8
NC
277V-N G11 OUTSIDE LAMP
277V-N G11 BOARD LIGHT
R4
L1 6
NC
277V-N G12
NC
277V-N G11A INSIDE LAMP
R6
L1 6
NC
277V-N G11A OUTSDE LAMP
L1 6
NC
277V-N G13 INSIDE LAMP
R8
L1 6
NC
277V-N G13 OUTSIDE LAMP
L1 6
NC
277V-N G13 BOARD LIGHT
R10
L1 6
NC
277V-N G13A OUTSDE LAMP
R11
L1 6
NC
277V-N G13A INSIDE LAMP
R12
L1
NC
277V-N G30
R13
L1 6
NC
277V-N G13B INSIDE LAMP
R14
L1 6
NC
277V-N G14
R15
L1 6
NC
277V-N G15
R16
L1 6
NC
277V-N G16
R17
L1 16
NC
277V-N G17 "A" LAMP
R18
L1 16
NC
277V-N G17 "B" LAMP
R19
L1 14
NC
277V-N G17 "C" LAMP
R20
L1 14
NC
277V-N G17 "D" LAMP
R21
L1 11
NC
277V-N G17 "E" LAMP
R22
L1 11
NC
277V-N G17 "F" LAMP
R23
L1 11
NC
277V-N G17 "G" LAMP
R24
L1 11
NC
277V-N G17 "H" LAMP
R25
L1 8
NC
277V-N G18
R26
L1 8
NC
277V-N G19
R27
L1 8
NC
277V-N G19A INSIDE LAMP
R28
L1 8
NC
277V-N G19A OUTSDE LAMP
R29
L1 8
NC
277V-N G19C
R30
L1 8
NC
277V-N G19B
R31
L1 10
NC
277V-N G21
R32
L1 10
NC
277V-N G20
R33
L1 10
NC
277V-N G21A INSIDE LAMP
R34
L1 10
NC
277V-N G21A OUTSDE LAMP
R35
L1 10
NC
277V-N G21C
R36
L1 10
NC
277V-N G21B
R37
L1 10
NC
277V-N G22
R38
L1 10
NC
277V-N G21D
R39
L1 10
NC
277V-N G24
R40
L1 10
NC
277V-N G23
R41
L1 10
NC
277V-N G26
R42
L1 10
NC
277V-N G25
R43
L1 10
NC
277V-N G27 INSIDE LAMP
R44
L1 10
NC
277V-N G27 OUTSIDE LAMP
R45
L1 15
NC
277V-N G29,G29A,G29B
R46
L1 10
NC
277V-N G28
R47
L1 15
NC
277V-N G29 "B"
R48
L1 10
NC
277V-N G19D
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Load Name
Accessories:
Relay Summary:
DTC Clock
Active Relays: 48
Mounting: Surface
Zone Type Voltage
Load Name
Relay Types:
Single Pole (NC): 48
Spare Relays: 0
NEMA Rating: 1
Total Relays: 48
Door Type: Hinged, Locking
Spaces: 0
Comments:
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 17-22
81
Relay Panel Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
LCP Location:
Model #: GR2448 INT 40NCL REMOTE DV D6 SM NE1
LCP Name: RP1 (G EMER) (LCP 2)
Voltage: 277V Normal
Supply Circuit:
Relay
Line Feed
Zone Type Voltage
R1
EL1 2
NC
R3
EL1 2
NC
R5
EL1 2
R7
R9
Relay
Line Feed
277V-E G11 OUTSIDE LAMP
R2
EL1 2
NC
277V-E G13 OUTSIDE LAMP
277V-E G13B INSIDE LAMP
R4
EL1 2
NC
277V-E G14
NC
277V-E G15
R6
EL1 2
NC
277V-E G16
EL1 2
NC
277V-E G17 "A" LAMPS
R8
EL1 2
NC
277V-E G17 "B" LAMPS
EL1 2
NC
277V-E G17 "C" LAMPS
R10
EL1 2
NC
277V-E G17 "D" LAMPS
R11
EL1 2
NC
277V-E G17 "E" LAMPS
R12
EL1 2
NC
277V-E G17 "F" LAMPS
R13
EL1 2
NC
277V-E G17 "G" LAMPS
R14
EL1 2
NC
277V-E G17 "H" LAMPS
R15
EL1 2
NC
277V-E G18
R16
EL1 2
NC
277V-E G19
R17
EL1 1
NC
277V-E G19B
R18
EL1 2
NC
277V-E G19C
R19
EL1 2
NC
277V-E G19D
R20
EL1 2
NC
277V-E G21
R21
EL1 2
NC
277V-E G21B
R22
EL1 2
NC
277V-E G21C
R23
EL1 2
NC
277V-E G22
R24
EL1 2
NC
277V-E G23
NC
277V-E SPARE
R26
EL1 2
NC
277V-E G25
R25
Load Name
Zone Type Voltage
Load Name
R27
EL1 2
NC
277V-E G27 INSIDE LAMP
R28
EL1 2
NC
277V-E G27 OUTSIDE LAMP
R29
EL1 2
NC
277V-E G29,G291,G29B A
R30
EL1 2
NC
277V-E G29 "B"
R31
EL1 2
EL1 2
NC
277V-E G21D
NC
277V-E G30
R32
R33
NC
277V-E SPARE
R34
Space 277V-E /// SPACE ///
R35
NC
277V-E SPARE
R36
Space 277V-E /// SPACE ///
R37
NC
277V-E SPARE
R38
Space 277V-E /// SPACE ///
R39
NC
277V-E SPARE
R40
Space 277V-E /// SPACE ///
R41
NC
277V-E SPARE
R42
Space 277V-E BARRIER GATE #1
R43
NC
277V-E SPARE
R44
Space 277V-E BARRIER GATE #2
R45
NC
277V-E SPARE
R46
Space 277V-E BARRIER GATE #3
R47
NC
277V-E SPARE
R48
Space 277V-E BARRIER GATE #4
Enclosure:
Dimensions: 37.5"H x 20"W x 6"D
Accessories:
Relay Summary:
DigiLink ID#29
Active Relays: 31
Mounting: Surface
Relay Types:
Single Pole (NC): 40
Spare Relays: 9
NEMA Rating: 1
Total Relays: 40
Door Type: Hinged, Locking
Spaces: 8
Comments:
RELAY 42,44,46&48 TO BE WIRE TO DIGILINK INPUTS 1-4 CONSECUTIVELY.
Programming Section Only
Card Mode: Discrete
Serial #:
Control Card Address: 23-28
82
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: USED FOR BARRIER GATE CONTROLS
DigiLink Location: RP1 (G EMER)
DigiLink Name: BARRIER GATE
Model #: GR400 DIGILINK D6
Supply Circuit:
Input #
Function
Zones or Relays Controlled
Input Name
1
Maintain
GROUP22
INPUT 1
2
Maintain
GROUP23
INPUT 2
3
Maintain
GROUP24
INPUT 3
4
Maintain
GROUP25
INPUT 4
5
Maintain
INPUT 5
6
Maintain
INPUT 6
Programming Section Only
Serial #:
Control Card Address: 29
83
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: WIRE NORMALLY OPEN OCCUPANCY
SENSOR RELAY TO THE INPUT 1-6 AND GND.
DigiLink Location:
DigiLink Name: OCC INPUT 2 #35
WIRE NORMALLY CLOSED OCCUPANCY
Model #: GR2400 DIGILINK DV D14 SM NE1
SENSOR RELAY TO THE INPUT 8-14 AND GND.
Supply Circuit:
Input #
Function
Zones or Relays Controlled
1
Maintain
LCP 1:15; LCP 2:5
G15
2
Maintain
LCP 1:16; LCP 2:6
G16
3
Maintain
LCP 1:4
G12
4
Maintain
INPUT 4
5
Maintain
INPUT 5
6
Maintain
INPUT 6
7
Maintain
INPUT 7
8
Off Mode
LCP 1:1-3; LCP 2:1
G11
9
Off Mode
LCP 1:5-6
G11a
10
Off Mode
LCP 1:7-9; LCP 2:2
G13
11
Off Mode
LCP 1:10-11
G13A
12
Maintain
INPUT 12
13
Maintain
INPUT 13
14
Maintain
INPUT 14
Enclosure:
Input Name
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 35
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
84
DigiLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: WIRE NORMALLY OPEN OCCUPANCY
SENSOR RELAY TO THE INPUT 1-6 AND GND.
DigiLink Location:
DigiLink Name: OCC INPUT 3 #44
WIRE NORMALLY CLOSED OCCUPANCY
Model #: GR2400 DIGILINK DV D14 SM NE1
SENSOR RELAY TO THE INPUT 8-14 AND GND.
Supply Circuit:
Input #
Function
Zones or Relays Controlled
1
Maintain
LCP 1:25; LCP 2:15
G18
2
Maintain
LCP 1:35; LCP 2:22
G19C
3
Maintain
LCP 1:35; LCP 2:22
G21C
4
Maintain
INPUT 4
5
Maintain
INPUT 5
6
Maintain
INPUT 6
7
Maintain
INPUT 7
8
Off Mode
LCP 1:27-28
G19A
9
Off Mode
LCP 1:30; LCP 2:30
G19B
10
Off Mode
LCP 1:32
G20
11
Maintain
LCP 1:31; LCP 2:20
G21
12
Maintain
LCP 1:33-34
G21A
13
Maintain
LCP 1:36; LCP 2:21
G21B
14
Maintain
LCP 1:37; LCP 2:23
G22
Enclosure:
Input Name
Programming Section Only
Dimensions: 8"H x 9"W x 4"D
Serial #:
Mounting: Surface
Control Card Address: 44
NEMA Rating: 1
Door Type: Screw Cover
Power Supply: 120/277 Volts
85
CommLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
CommLink Location:
CommLink Name:
Interface to: GR2400 UH4 DV SM NE1
Supply Circuit:
Comments:
Enclosure:
Programming Section Only
Dimensions: 8.4"H x 8.4"W x 3.125"D
Serial #:
Mounting: Surface
Control Card Address: 120
NEMA Rating: 1
Door Type: Screw Cover
86
CommLink Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
CommLink Location:
CommLink Name:
Interface to: GR2400 L2 BACNETIP DV SM NE1
Supply Circuit:
Comments:
Enclosure:
Programming Section Only
Dimensions: 8.4"H x 8.4"W x 3.125"D
Serial #:
Mounting: Surface
Control Card Address: 126
NEMA Rating: 1
Door Type: Screw Cover
87
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: GATE (ADD #1)
Switch Type: Chelsea w/ KeyEnable
Model #: CH4 BWH PST
KE PST
Button #
Function
1
Toggle
2
Toggle
3
4
Engraving
Zones or Relays Controlled
Color
Line 1
Line 2
LCP 2:42
#1
BARRIER
White
LCP 2:44
#1
BARRIER
White
Toggle
LCP 2:46
#2
BARRIER
White
Toggle
LCP 2:48
#2
BARRIER
White
Options: KeyEnable Switch
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 1
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: BTN7=1-6 >9-14= LCP 2:47=ON
BTN 9 = GROUP 27
Switch Location:
Switch Name: PARKING (ADD#2)
Switch Type: Chelsea w/ KeyEnable
Model #: CH1 BWH PST
KE PST
Button #
Function
1
Mntry On
Zones or Relays Controlled
GROUP26
Options: KeyEnable Switch
Engraving
Line 1
Line 2
PARKING
LOT
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 2
88
Color
White
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G29B (ADD #3)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:47; LCP 2:30
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 3
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G27 (ADD #4)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:43; LCP 2:27
A
White
2
Toggle
LCP 1:44; LCP 2:28
B
White
Line 1
Line 2
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 4
89
Color
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G28 (ADD #5)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:46
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 5
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location: G28
Switch Name: GATE (ADD #7)
Switch Type: Chelsea w/ KeyEnable
Model #: CH4 BWH PST
KE PST
Button #
Function
1
Toggle
2
Toggle
3
4
Zones or Relays Controlled
Engraving
Color
Line 1
Line 2
LCP 2:41
#1
BARRIER
White
LCP 2:43
#1
BARRIER
White
Toggle
LCP 2:45
#2
BARRIER
White
Toggle
LCP 2:47
#2
BARRIER
White
Options: KeyEnable Switch
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 7
90
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: BTN7=1-6 >9-14= LCP 2:47=ON
BTN 9 = GROUP 27
Switch Location:
Switch Name: MS PARKING LOT#8
Switch Type: Chelsea w/ KeyEnable
Model #: CH1 BWH PST
KE PST
Button #
Function
1
Mntry On
Engraving
Zones or Relays Controlled
GROUP26
Options: KeyEnable Switch
Line 1
Line 2
PARKING
LOT
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 8
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G28 (ADD #9)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:44
Engraving
Line 1
Line 2
LIGHTS
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 9
91
Color
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G29A (ADD #10)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:45; LCP 2:29
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 10
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: GANG WITH SWITCH G17B
Switch Location:
Switch Name: G17A (ADD #11)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:17; LCP 2:7
BLEACHER
White
2
Toggle
LCP 1:18; LCP 2:8
BLEACHER
White
3
Toggle
LCP 1:19; LCP 2:9
CENTER
COURT
White
4
Toggle
LCP 1:20; LCP 2:10
CENTER
COURT
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 11
92
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: GANG WITH SWITCH G17A
Switch Location:
Switch Name: G17B (ADD #12)
Switch Type: Chelsea
Model #: CH4 BWH PST
Button #
Function
1
Toggle
2
Toggle
3
4
Engraving
Zones or Relays Controlled
Color
Line 1
Line 2
LCP 1:21; LCP 2:11
RIGHT
SIDE
White
LCP 1:22; LCP 2:12
RIGHT
SIDE
White
Toggle
LCP 1:23; LCP 2:13
LEFT
SIDE
White
Toggle
LCP 1:24; LCP 2:14
LEFT
SIDE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 12
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: GANG WITH SWITCH G17B
Switch Location:
Switch Name: G17A (ADD #13)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:17; LCP 2:7
BLEACHER
White
2
Toggle
LCP 1:18; LCP 2:8
BLEACHER
White
3
Toggle
LCP 1:19; LCP 2:9
CENTER
COURT
White
4
Toggle
LCP 1:20; LCP 2:10
CENTER
COURT
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 13
93
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: GANG WITH SWITCH G17A
Switch Location:
Switch Name: G17B (ADD #14)
Switch Type: Chelsea
Model #: CH4 BWH PST
Button #
Function
1
Toggle
2
Toggle
3
4
Engraving
Zones or Relays Controlled
Color
Line 1
Line 2
LCP 1:21; LCP 2:11
RIGHT
SIDE
White
LCP 1:22; LCP 2:12
RIGHT
SIDE
White
Toggle
LCP 1:23; LCP 2:13
LEFT
SIDE
White
Toggle
LCP 1:24; LCP 2:14
LEFT
SIDE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 14
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G14 (ADD #15)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:14; LCP 2:4
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 15
94
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G14 (ADD #16)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:14; LCP 2:4
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 16
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G16 (ADD #30)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:16; LCP 2:6
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 30
95
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G13 (ADD #31)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:7
A
White
2
Toggle
LCP 1:8; LCP 2:2
B
White
3
Toggle
LCP 1:9
4
Mix Mode
Line 1
On:LCP 1:7 Off:LCP 1:8-9; LCP 2:2
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 31
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G11A (ADD #32)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:5
A
White
2
Toggle
LCP 1:5-6
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 32
96
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G13A (ADD #33)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:11
A
White
2
Toggle
LCP 1:10
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 33
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G13 (ADD #34)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:7
A
White
2
Toggle
LCP 1:8; LCP 2:2
B
White
3
Toggle
LCP 1:9
4
Mix Mode
On:LCP 1:7 Off:LCP 1:8-9; LCP 2:2
Line 1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 34
97
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G11 (ADD #36)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:1
A
White
2
Toggle
LCP 1:2; LCP 2:1
B
White
3
Toggle
LCP 1:3
4
Mix Mode
Line 1
On:LCP 1:1 Off:LCP 1:2-3; LCP 2:1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 36
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G11 (ADD #37)
Switch Type: Chelsea
Model #: CH4 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:1
A
White
2
Toggle
LCP 1:2; LCP 2:1
B
White
3
Toggle
LCP 1:3
4
Mix Mode
On:LCP 1:1 Off:LCP 1:2-3; LCP 2:1
Line 1
Line 2
Color
BOARD
LIGHTS
White
A/V
MODE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 37
98
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: GANG WITH SWITCH G17B
Switch Location:
Switch Name: G17A (ADD #38)
Switch Type: Chelsea
Model #: CH4 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:17; LCP 2:7
BLEACHER
White
2
Toggle
LCP 1:18; LCP 2:8
BLEACHER
White
3
Toggle
LCP 1:19; LCP 2:9
CENTER
COURT
White
4
Toggle
LCP 1:20; LCP 2:10
CENTER
COURT
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 38
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments: GANG WITH SWITCH G17A
Switch Location:
Switch Name: G17B (ADD #39)
Switch Type: Chelsea
Model #: CH4 BWH PST
Button #
Function
1
Toggle
2
Toggle
3
4
Zones or Relays Controlled
Engraving
Color
Line 1
Line 2
LCP 1:21; LCP 2:11
RIGHT
SIDE
White
LCP 1:22; LCP 2:12
RIGHT
SIDE
White
Toggle
LCP 1:23; LCP 2:13
LEFT
SIDE
White
Toggle
LCP 1:24; LCP 2:14
LEFT
SIDE
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 39
99
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G19 (ADD #40)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:26; LCP 2:16
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 40
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G19A (ADD #41)
Switch Type: Chelsea
Model #: CH2 BWH PST
Zones or Relays Controlled
Engraving
Button #
Function
1
Toggle
LCP 1:27
A
White
2
Toggle
LCP 1:28
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 41
100
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G19B (ADD #42)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:30; LCP 2:17
Line 2
A
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 42
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G20 (ADD #43)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:32
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 43
101
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G19 (ADD #45)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:26; LCP 2:16
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 45
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G13B (ADD #46)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:13; LCP 2:3
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 46
102
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G19D (ADD #47)
Switch Type: Chelsea
Model #: CH1 WP BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:48; LCP 2:19
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 47
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G21 (ADD #48)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:31; LCP 2:20
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 48
103
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G21D (ADD #49)
Switch Type: Chelsea
Model #: CH1 WP BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:38; LCP 2:32
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 49
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G21B (ADD #50)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:36; LCP 2:21
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 50
104
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G21A (ADD #51)
Switch Type: Chelsea
Model #: CH2 BWH PST
Engraving
Button #
Function
Zones or Relays Controlled
1
Toggle
LCP 1:33
A
White
2
Toggle
LCP 1:34
B
White
Line 1
Line 2
Color
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 51
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G21 (ADD #52)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:31; LCP 2:20
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 52
105
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G22 (ADD #53)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:37; LCP 2:23
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 53
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G30 (ADD #54)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:12; LCP 2:31
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 54
106
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G30 (ADD #55)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:12; LCP 2:31
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 55
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G29A (ADD #56)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:45; LCP 2:29
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 56
107
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G29A (ADD #57)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Engraving
Zones or Relays Controlled
Line 1
LCP 1:45; LCP 2:29
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 57
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G29A (ADD #58)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:45; LCP 2:29
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 58
108
Switch Schedule
By Lighting Control & Design
Job Name: LEE BURNESON MIDDLE SCHOOL-BUS 3
Comments:
Switch Location:
Switch Name: G29A (ADD #59)
Switch Type: Chelsea
Model #: CH1 BWH PST
Button #
Function
1
Toggle
Zones or Relays Controlled
LCP 1:45; LCP 2:29
Engraving
Line 1
Line 2
LIGHTS
Color
White
Programming Section Only
Pilot Light Color: Red
Serial #:
Locator Light Color: Green
Control Card Address: 59
109
Group Schedule
By Lighting Control & Design
Job Name : LEE BURNESON MIDDLE SCHOOL-BUS 3
Job Location : WEST LAKE, OH
Group #
Group Name
Function
Auto On
Timer Out
Blink Warning
No
2:00:00
05 min.
GROUP 1 -- 16 are not used
17
18
19
20
21
22
23
24
25
26
27
GLOBAL 4AM/11PM
Maintain
No load assigned
SCHED DUSK-DAWN
Maintain
No load assigned
PCELL DUSK-DAWN
Maintain
No load assigned
SCHED DUSK-11PM
Maintain
No load assigned
11PM OFF
Maintain+Offsweep
LCP 1
14,17-24,38,45,47-48
LCP 2
4,7-14,19,29-30,32
BARRIER GATE #1
Maintain
No load assigned
BARRIER GATE #2
Maintain
No load assigned
BARRIER GATE #3
Maintain
No load assigned
BARRIER GATE #4
Maintain
No load assigned
PARKING LOT
Momentary On
LCP 2
47
PARKING LOT OFF
Momentary Off
LCP 2
47
GROUP 28 -- 32 are not used
110
111
905 Allen Ave. • Glendale, CA 91201-2019
Ph. (323) 226-0000 • Fax (323) 226-1000 • Support (800) 345-4448
www.lightingcontrols.com
Project Name: LEE BURNESON MIDDLE SCHOOL
Location: WEST LAKE, OH
ABC Project Web #: 15768
Today’s Date: 04/18/12
SPECIAL WARRANTY
Lighting Control & Design Inc. (LC&D) warrants this system for three years from shipment to be free of
defects in material and workmanship and damages from transient voltage surges under conditions of
normal use and specified ambient temperature when installed and operated under LC&D’s product
specifications and in accordance with the National Electrical Code.
LC&D warrants this system for ten years from shipment due to damages from transient voltage surges
under conditions of normal use and specified ambient temperature when installed and operated under
LC&D’s product specifications and in accordance with the National Electrical Code.
LC&D warrants the relays for ten years from shipment to be free of defects in material and workmanship
and damages from transient voltage surges under conditions of normal use and specified ambient
temperature when installed and operated under LC&D’s product specifications and in accordance with the
National Electrical Code.
LC&D shall at its option, repair or replace any defective unit which in its opinion, has not been improperly
installed, wired, insulated, used or maintained, provided however that LC&D shall not be required to
remove, install or re-install any defective unit and provided that LC&D is properly notified of said defect
within the aforementioned warranty period. This warranty in no way covers any labor required to effect
changes.
The foregoing warranty and optional remedies are exclusive and, except for the foregoing warranties
THERE ARE NO OTHER WARRANTIES OF MERCHANTABILITY OR OF ANY OTHER TYPE. In no
event shall LC & D or any other seller be liable for consequential or special damages, nor for any repair
work, undertaken without its prior written consent, nor shall LC&D’s liability on any claim for damages
arising out of or connected with the manufacture, sale, installation, delivery or use of said unit ever
exceed the price paid therefore.
112
®
GR 2400 PLANNING GUIDE
[ NEW CONSTRUCTION ]
Planning Guide Index
The Bus File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Single Line Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Multi-Bus Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Digital Cabling Basics . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Eliminate Low Voltage Interference . . . . . . . . . . . . . 5
Planning Your Cabling Route . . . . . . . . . . . . . . . . . . . 6
Eliminate Voltage Drops . . . . . . . . . . . . . . . . . . . . . . . . 7
The Bus Booster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Crimping Kits & Pre-Made Cables . . . . . . . . . . . . . . . 9
Photosensor Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cabling Non-Digital Devices . . . . . . . . . . . . . . . . . . . 11
Graphical Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
On-Site Training and Commissioning . . . . . . . . . . 12
Important Note:
This supplement to the Quick Start Guide should be read by the project foreman before any cables are pulled. It
should also be read by those who are involved with the submittal process to ensure a successful installation. The
Quick Start Guide is a colorful overview of the steps necessary to install and start up the GR 2400 system. Please
also refer to our Product Installation Guides for installation and start-up details for each GR 2400 product.
113
Following the Approved Submittal
Documentation
The documentation specific to your project (excepting systems not factory programmed) consists of
the Bus File and the Single Line Drawings—both of which have been carefully engineered for your site.
Please adhere carefully to these customer-approved construction documents.
In some cases, the approved submittals don’t accurately represent the as-built devices or
programming due to requirements per production specification, quality control, and superseding
changes by the customer made after the approved submittals. In every case, as-built bus files and
single line documentation are provided with every system (located with the door sheets in the main
panel). Upon request, the dated record-only drawings can be provided via email or fax.
The Bus File
The Bus File consists of schedules for each control panel and digital device. The device schedule
indicates device location, programming details, and the line-feed for each relay or dimmer. Refer to
Figure 2. It clearly shows where the panel is located, the line-feed for each relay, and load names.
The approved submittal amends any relay numbering indicated on the original plans. Varying from the
approved submittal, by swapping relays or loads, will result in unnecessary re-programming in the field
and may violate NEC or UL requirements particularly if controlling both normal and emergency power
loads. If you consider it absolutely necessary to vary from the schedules, please try to address this during
the submittal phase, or if during the installation phase, notify Tech Support prior to making changes.
Figure 2
Relay Panel Schedule by Lighting Control & Design
[
[ ] [
Relay:
Relay 1
]
]
[
]
LCP Location:
Location of panel
Line Feed:
Breaker H1
Load Name:
Corridor Lighting
To Load
Pg. 2
www.lightingcontrols.com
114
Following the Approved Submittal
Single Line Drawings
Devices may be connected in any order on the same bus. The single line drawing shows all digital devices
on one bus. Though devices are usually shown on the bus in an order similar to the physical location, it is
not necessary to wire them in the order shown. Devices may be placed in any order on the bus.
Single-Bus Systems
Figure 3.1
A single-bus system only has one DTC clock
located on the bus.
DTC Clock
Remote
Panel
Multi-Bus Systems
When a system exceeds the length of a single bus,
it becomes a multi-bus system. The multiple buses
are connected by a “back bone bus” headed by
an “UpLink” Card. Moving a device to a bus other
than the bus indicated for that item on the single
line drawing can result in the device not being able
to control the circuits it was specified for.
Figure 3.2
MetaServer
Card
The UpLink Card is used to
link multiple buses. Digital
devices can be daisy-chained
in any order but may not
be moved to another bus,
otherwise they might not
control the correct circuits.
UpLink
Card
MicroPanel
DTC Clock
Remote
Panel
UpLink
Card
DTC Clock
UpLink
Card
DTC Clock
LC&D 800.345.4448
MicroPanel
Remote
Panel
MicroPanel
Remote
Panel
MicroPanel
Pg. 3
115
Digital Cabling Basics
Digital Cabling Basics
With a few exceptions, GR 2400 System devices are digital and therefore can be daisy-chained using
Cat. 5 cable with RJ45 connectors. Do not “home run” any of the digital devices on the bus back to a
panel. When cabling digital devices, no spurs or T-Taps are allowed. Cabling for photosensors and the
peripherals are covered in their respective manuals.
Figure 4.1
If the above illustration was converted to a single line drawing, similar to those supplied with your project, it would
look like this. The saw-tooth pattern is a drawing standard which indicates a daisy-chain style network (RS-485).
Figure 4.2
DTC 2400
MicroPanel iDH
Chelsea Digital Switches
Powered DigiLink
Chelsea Digital Switches
Modem
Cat. 5 Cable (4,000 ft. - up to 127 addresses)
No Spurs
No T-Taps
DTC 2400
Figure 4.3
Modem
Pg. 4
www.lightingcontrols.com
116
OS OS
Occupancy Sensor
MicroPanel or
DigiLink
MicroPanel or
DigiLink
3#18AWG up to 200 ft.
3#18 shielded 200 - 1,000 ft.
3#18AWG up to 200 ft.
3#18 shielded 200 - 1,000 ft.
Eliminating Low Voltage Interference
Momentary or Maintained Contact from Security or Building Automation
Momentary or Maintained Contact from Security or Building Automation
R
MicroPanel or
DigiLink
MicroPanel or
DigiLink
R
2#18AWG up to 200 ft.
2#18 shielded 200 - 1,000 ft.
2#18AWG up to 200 ft.
2#18 shielded 200 - 1,000 ft.
Eliminate Low Voltage Interference
Cat. 5 cable must be at least 12 inches from all line voltage conductors except to cross or make
terminations. Cat. 5 cable must be kept away from all EMF devices such as ballasts or transformers.
photosensor
Low voltage cabling
must not be run in parallel with line voltage cable, and must not share the same conduit, whether
digital cable (Cat. 5) or just low voltage cable (3#18 from a photosensor).
photosensor
Figure 5.1
Isolate Line Voltage Cable
Low Voltage Cable
Low Voltage Cable
PS PS
photosensor
input
photosensor
input
relay
Line Voltage Cable
relay
MicroPanel
Line Voltage Cable
MicroPanel
Low voltage cabling must avoid EMF or RF from ballasts or other “noisy” loads. EMF or RF interference can create an
unstable bus and can eventually ruin digital devices.
photosensor
Figure 5.2
photosensor
Isolate Line Voltage Devices
Low Voltage Cable
Low Voltage Cable
Ballast
Ballast
Ballast
Ballast
PS PS
photosensor
input
photosensor
input
relay
relay
MicroPanel
MicroPanel
Line Voltage Cable
Line Voltage Cable
LC&D 800.345.4448
Pg. 5
117
Planning Your Cabling Route
Plan Your Cabling Route
As already stated, you may vary from the single line drawing as long as the devices remain within a
specific bus.
There are two extremely important issues to think about when planning your low voltage cabling
route: voltage drop and the current-draw of bus-powered devices. If too many bus-powered devices
are added contiguously, particularly over long cabling lengths, they may not receive enough current
to operate from the active devices.
Use the Bus-Powered Devices chart (Figure 6) to help plan your cabling route by avoiding too many
contiguous bus-powered devices. The active devices shipped with your order will supply enough
current for all the bus-powered devices if cabled properly. Never try to support more than 21 items on
the bus from a large relay panel (such as a GR 2400 or The Blue Box LT), or nine items from a MicroPanel.
Figure 6
Definitions:
Bus-Powered Device: Any
device that relies on the
12V supplied by the GR
2400 bus for its power.
Example: digital switches
and photosensor cards.
Maxiumum Bus-Powered Devices allowed
for each Active Device
Allowed
Not Allowed
1000 ft
900 ft
Total Feet of Cabling from One Active Device
Active Device: Any device
with a power supply (a
transformer). It acts as a
source of electrical energy
for the GR 2400 bus.
Examples: Control Panels,
powered DigiLinks and
Bus Boosters.
800 ft
700 ft
600 ft
500 ft
400 ft
300 ft
200 ft
30
27
24
21
18
15
12
9
6
3
100 ft
Number of Bus-Powered Devices
Pg. 6
www.lightingcontrols.com
118
Eliminating Voltage Drops
Up to 3 bus-powered devices @ 1,000 ft.
Up to 3 bus-powered devices @ 1,000 ft.
Eliminate Voltage
Drops$
$
$
$
$
$
Per the Bus-Powered
Devices
chart
(Figure
6),
up
to
3
bus-powered
devices
may
be
powered
across
bus-powered devices
active device
anywhere within the 1,000 foot region.
1,000 feet of Cat. 5 cable. The active device may be located
anywhere
in the 1,000 ft. zone
Cat. 5 Cable
Up to 3 bus-powered devices @ 1,000 ft.
Up
to 3 bus-powered devices @ 1,000 ft.
power
active device
$
$
$
$
$
$
bus-powered devices
bus-powered devices
power
power
active device
active device
$
$
$
$
$
$
$
$
bus-powered devices
insufficient power power
active device
power
$ active device
$
$
bus-powered devices
Cat. 5 Cable
active device
$
active device anywhere
in the
1,000device
ft. zone
active
anywhere
in the 1,000 ft. zone
Cat. 5 Cable
Cat. 5 Cable
1,000 ft.
power
A second panel
does not help. power
active device
Figure 7.1
Up to 3 bus-powered devices @ 1,000 ft.
Up to 3 bus-powered devices @power
1,000 ft.
active device
1,000 ft.
1,000 ft.
insufficient power
insufficient power
Figure 7.2
$
$
$
$
$
$
$
$
$
$
$
bus-powered devices
bus-powered devices $
ft.
sufficient power
power
power 1,000bus-powered
devices
bus-powered devices
power
power
$
$
$
$
$
Cat. 5 Cable $
active device
active device
Cat. 5 Cable
bus-powered
devices
active device
active device
power
power
5 Cable
Multiple panels do not increase the distance. For the above scenario, the correctCat.
solution
would be to
shown below:
route the Cat. 5 properly so as to spread the
active
1,000
ft. devices out. This issufficient
power
1,000 ft.
$
$
$
$
$
bus-powered
devices
1,000 $
ft.
bus-powered devices
power
$
$
$
power
bus-powered devices
power
power
active device
LC&D 800.345.4448 power
power
1,000 ft.
$
$
$
$devices
$
bus-powered
bus-powered devices
insufficient
power power for these devices
power
119
$
$
$
$
bus-powered devices
active device
active
$
$ device $
$
$
sufficient power
$
$
$Figure 7.3
$
power
$
$ 5 Cable$
Cat.
power
bus-poweredCat.
devices
5 Cable
power
1,000 ft.
1,000 ft.
$
sufficient power
sufficient power
sufficient power
$
$
$
$
$devices
$
bus-powered
bus-powered devicesPg. 7
1,000 ft.
power
power
$
$
$
power
active device
power
$
$
bus-powered devices
$
1,000 ft.
sufficient power
active device
$
$
$
bus-powered devices
Boosting the Bus
power
$
$
bus-powered devices
Cat. 5 Cable
$
$
$
power
Cat. 5 Cable
sufficient power
1,000 ft.
$
$
$
bus-powered devices
$
1,000 ft.
$
$
sufficient power
power
power
Cat. 5 Cable
$
$
$
$
$
$
The Bus Booster
bus-powered devices
bus-powered devices
In instances where there
are simply not enough regular active devices to supply power to the passive
power
devices, use a Bus Booster (1 amp @ 12V).
power
power
ft.
sufficientwas
power
active
device
LC&D may have
determined
during the1,000
submittal
phase that a bus booster
required, which then
would have been included with the shipment and mentioned on the submittal documents.
$
$
$
bus-powered devices
power
power
insufficient power for these devices
1,000device
ft.
active
$
$
$
$
bus-powered devices
power
active device1,000 ft.
$
$
$
$
$
$
bus-powered devices
$
$
$
$
$
bus-powered devices
$
$
$
power
active device
$
sufficient power
1,000 ft.
$
$
insufficient power for these devices Cat. 5 Cable1,000 ft.
power
The Bus Booster
adds current to the bus; it does not amplify the digital signal.
Cat. 5 Cable
active device
Figure 8.1
power
1,000 ft.
$
$
$
$
$
$
$
1,000 ft.
$
$
power
active device
Figure 8.2
power
1,000 ft.
active device
$
$
$
power
active device
power
sufficient
power
active device
(bus booster)
$
$
$
power
active device
(bus booster)
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
power
active device
Cat. 5 Cable
1,000 ft.
$
$
$
power
active device
Cat. 5 Cable
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
If you need to order a Bus Booster, contact Customer Support: 800-345-4448.
CAT 5 CABLE WITH RJ45 CONNECTORS
4000 FT - 127 DEVICES MAX
GR 2400 MASTER RELAY PANEL
WITH DTC CLOCK AND MODEM
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
GR 2400 MASTER RELAY PANEL
WITH DTC CLOCK AND MODEM
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CAT 5 CABLE WITH RJ45 CONNECTORS
4000 FT - 127 DEVICES MAX
CHELSEA
DIGITALSWITCH
POWERED
DIGILINK
Pg. 8
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
120
POWERED
MICROPANEL-IDH
CHELSEA
DIGITALSWITCH
MICROPANEL-IDH
CHELSEA
DIGITALSWITCH
www.lightingcontrols.com
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
Making Up Cat. 5 Cable
Crimping Kits
All systems with three panels or more are shipped with a factory crimping kit.
This kit contains an approved crimper and approved crimps sufficient for the job. More importantly, it
contains a manual that goes over all the ways that a crimp can be badly made and cause failure.
Since 90% of failed system start ups are due to bad Cat. 5 connections or crimping, it can save a lot of
time and money to both read and apply the data in this kit.
Additional kits will be shipped for a small fee to jobs that need more than one or have less panels.
Pre-Made Cables
In some applications where the cable lengths are standard, it is well worth ordering pre-made factory
cables. One website that has very attractive prices is: https://www.cablesforless.com.
Factory-provided crimping kit.
LC&D 800.345.4448
Pg. 9
121
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITAL
SWITCH
C
D
S
MICROPANEL-IDH
CAT. 5 CABLE WITH RJ45 CONNECTORS
4,000 FT. - 127 ADDRESSES MAX
GR 2400 MASTER RELAY PANEL
WITH DTC CLOCK AND MODEM
Photosensor Basics
Photosensors
Indoor or outdoor photosensors can be wired to a photocell card (PCC1 or PCC3), The Blue Box LT, or
any MicroPanel. Refer to the photosensor card schedule in your bus file or the single line drawing to
determine where the specified photosensors are mounted and the location of the device they are
cabled to. You are strongly urged to review LC&D’s Photosensor Placement Guide for applications with
daylight harvesting. Photosensors may be located up to 1,000 feet away from the device they are
CHELSEA
CHELSEA
CHELSEA
CHELSEA
cabled to using 3#18 AWG.
DIGITALSWITCH
DIGITALSWITCH
DIGITALSWITCH
DIGITAL
SWITCH
GR 2400 MASTER RELAY PANEL
WITH DTC CLOCK AND MODEM
Indoor Photosensor
Outdoor Photosensor
photosensor
Figure 10.1
PS
NOTE: Some GR 2400 components
are not run with Cat. 5 cable. This
overview of those devices should
assist you in planning your cabling.
CHELSEA
DIGITAL SWIT
MicroPanel
Blue Box or
Photocell Card
3#18AWG up to 1,000 ft.
3-way wall
3-way wall switch
Photocell Schedule
byswitch
Lighting Control & Design
Job Name: Central Library Warehouse
[ Inp.Card Location:
LCP 1
]
$
Zones or Relays Controlled
Model #: P CC-3
$
Figure 10.2
MicroPanel or
DigiLink
Time
Triggering when light level
3#18AWG upInput
to 200 ft.
Delay
falls below
rises above
3#18 shielded 200 - 1,000 ft.
Trigger #
Function
1
Maintain
T R IG G E R 1
Analog 1
03 min.
00 01
00 02
2
Maintain
T R IG G E R 2
Analog 1
03 min.
00 01
00 02
3
Maintain
T R IG G E R 3
Analog 1
03 min.
00 01
00 02
4
Maintain
4
Analog 1
03 min.
00 01
00 02
5
Maintain
5
Analog 1
03 min.
00 01
00 02
6
Maintain
T R IG G E R 6
Analog 1
03 min.
00 01
00 02
7
Maintain
T R IG G E R 7
Analog 1
03 min.
00 01
00 02
8
Maintain
T R IG G E R 8
Analog 1
03 min.
00 01
00 02
9
Maintain
T R IG G E R 9
Analog 1
03 min.
00 01
00 02
10
Maintain
T R IGG E R 10
Analog 1
03 min.
00 01
MicroPanel or
00 02DigiLink
11
Maintain
T R IGG E R 11
Analog 1
03 min.
00 01
00 02
12
Maintain
T R IGG E R 12
00 01
00 02
13
Maintain
00 01
00 02
14
Maintain
00 01
00 02
Photocell-1 Name : North Warehouse
Photocell Card Location:
Inside LCP 1
Trigger Name
OS
T R IG G E R
Occupancy Sensor
T R IG G E R
3#18AWG up
to 200
ft. min.
Analog
1 03
T R IGG E R 13
Analog 1 03 min.
3#18
shielded
200
1,000 ft.
T R IGG E R 14
Analog 1 03 min.
[ Photocell-1 Type:
PCO
] [ Photocell-1 Location:
Roof Mounted Facing North
]
Momentary or Maintained Contact from Security or Building Automation
Photocell Type:
PCO
R - Outdoor Photocell
Pg. 10
Photocell Location:
Roof Mounted Facing North
2#18AWG up to 200 ft.
2#18 shielded 200 - 1,000 ft.
122
MicroPanel or
DigiLink
www.lightingcontrols.com
DIGILINK
MICROPANEL-IDH
CAT. 5 CABLE WITH RJ45 CONNECTORS
4,000 FT. - 127 ADDRESSES MAX
GR 2400 MASTER RELAY PANEL
WITH DTC CLOCK AND MODEM
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITAL
SWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITALSWITCH
CHELSEA
DIGITAL
SWITCH
Cabling Non-Digital Devices
GR 2400 MASTER RELAY PANEL
WITH DTC CLOCK AND MODEM
CHELSEA
DIGITAL SWITCH
PS
photosensor
Contact Closure Devices
Many manufacturers offer contact-closure based devices to provide external control of the GR 2400
CHELSEA
system, including: Building Automation,CHELSEA
Security, wall CHELSEA
switches, or momentary
pushCHELSEA
button switches.
DIGITALSWITCH
DIGITALSWITCH
DIGITALSWITCH
DIGITAL
GR 2400 MASTER RELAY PANEL
CHELSEA
See below for general
information
on running cables. Refer to specific product guide
for hook-up
SWITCH
WITH DTC
CLOCK AND MODEM
DIGITAL SWITCH
MicroPanel
details. Switches must be rated for low voltage use (made with gold-flashed contacts.)
photosensor
3#18AWG up to 1,000 ft.
Three-Way Switches
CHELSEA
DIGITAL SWITCH
PS
WITH DTC CLOCK AND MODEM
$
3-way wall switch
$
3#18AWG up to 1,000 ft.
PS
3#18AWG up to 200 ft.
3-way wall switch 3#18 shielded 200 - 1,000
3-wayft.wall switch
Occupancy Sensors
$
Occupancy
Sensor
3#18AWG up to 1,000 ft.
$
MicroPanel
Blue Box or
Photocell Card
Figure 11.1
MicroPanel or
DigiLink
MicroPanel
Blue Box or
Photocell Card
MicroPanel or
OS
LC&D can interface with most low voltage occupancy sensors with dry contact outputs.
In most cases the MicroPanel
DigiLink
MicroPanel or
3#18AWG
up to
ft.
replaces the power pack. Download hook-up
diagrams
for200
approved
sensors at www.lightingcontrols.com
if not
wall switch
3-wayft.wall switch
DigiLink
3#18 shielded 200 - 1,000
already included with your3-way
construction
documents.
3#18AWG up to 200 ft.
$
$
Occupancy Sensor 3#18 shielded 200 - 1,000 ft.
Figure 11.2
MicroPanel or
DigiLink
OS
3#18AWG up to 200 ft.
MicroPanel or
3#18 shielded
200
- 1,000
ft. or Building Automation
Momentary or Maintained
Contact
from
Security
DigiLink
OS
3#18AWG up to 200 ft.
R
Occupancy
Sensor 3#18 shielded 200 - 1,000 ft.
Dry Contact Relays
MicroPanel or
DigiLink
2#18AWG up to 200 ft.
MicroPanel or
2#18 shielded
- 1,000
ft. or Building Automation
DigiLink
Momentary or Maintained
Contact200
from
Security
Use shielded cable if the dry contact output3#18AWG
device exceeds
200
up to 200
ft.ft. in distance from the DigiLink, MicroPanel, or any
contact closure input. Proper
shielded
cable
shielded
200requires
- 1,000 ft.that the drain wire be landed on the ground input
R termination of3#18
MicroPanel
of the MicroPanel, DigiLink or The Blue Box LT—ground the shield at only one end of the
cable! or
DigiLink
2#18AWG up to 200 ft.
Momentary or Maintained
Contact200
from
Security
2#18 shielded
- 1,000
ft. or Building Automation
photosensor
R
Figure 11.3
MicroPanel or
DigiLink
2#18AWG up to 200 ft.
2#18
200 - 1,000 ft.
Lowshielded
Voltage Cable
photosensor
photosensor
Pg. 11
input
PS
LC&D 800.345.4448
123
Low Voltage Cable
photosensor
Line Voltage Cable
CHELSEA
DIGITAL SWITCH
Blue Box or
Photocell Card
GR 2400
MASTER RELAY
Three-way low-voltage
switches
mayPANEL
be used with the MicroPanel for local and override controls.
3-way wall switch
photosensor
CHELSEA
DIGITAL SWITCH
relay
CHELSEA
DIGITAL SWITCH
With You Every Step
Unity GX Programming
If we are developing Unity GX graphical pages, please ensure that the Unity GX preparation package is
completed and forwarded to your project manager in Tech Support.
On-Site Training and Commissioning
To schedule on-site start-ups or on-site training, contact your project manager in Technical Support.
Once Equipment is Received
1. Once you receive your shipment, call us to schedule over the phone training with your installation team.
2. We will also perform diagnostics once you have completed each low voltage bus to ensure that
everything is working properly.
3. We will also dial into your system just prior to owner-occupation for any final programming.
4. Two months after owner-occupation, we will contact the owner’s rep and verify that everything with
the programming is OK.
The Ideal Installation
Our goal is your success. Call us if you have questions or need assistance during the submittal phase.
Technical Support: 800-345-4448
Lighting Control & Design
905 Allen Avenue, Glendale, CA 91201
www.lightingcontrols.com
© 2007, 2010 Acuity Brands Lighting Inc., All Rights Reserved. • 1382.056
124
Complete the Quick-Start Guide before doing this checklist
GR 2400
FINAL ACTIVATION
CHECKLIST
System Installer Read This First
Follow the Release Package (provided with your
shipment) and cut your installation time in half.
For specific product manuals and installation guides,
visit www.lightingcontrols.com or call Tech Support at
800-345-4448 prior to equipment start-up and turn-over.
125
SYSTEM START-UP CHECKLIST
IMPORTANT NOTE:
Tools You Will Need
This checklist can save you many hours of work, if followed
carefully, by preventing common problems encountered in
networked installations.
Even if each cable length checks out with a Local Area
Network (LAN) cable tester, it is still possible for the entire
cable structure to become problematic once connected.
The following are just some of the scenarios that may cause
this problem:
You have been provided with
the following devices (located
in the master panel) to assist
with testing your system.
1
Have them on-hand along
with your meter:
2
1. GR 2400 Terminators
• Dirt/dust in the RJ45 socket
2. XPoint Terminators
(if applicable)
• Strain on the Cat. 5 cable
3. Data/Power Jumper
• D
amaged springs in the RJ45 sockets, caused by strain
on the cable
4. Bus Checker
5. Multi-Meter
• D
amaged conductors, caused by nicks while cable is
being stripped
• Bus length exceeding 4,000 feet
3
4
5
IMPORTANT NOTE:
Please refer to the inset diagrams to understand cable
structure and placement of bus terminators, as these vary
slightly for each bus type.
GR 2400 OR GR 1400 (SINGLE BUS)
XPOINT OR GR 2400 (MULTI-BUS)
126
HARDWARE ACTIVATION TESTS
Before starting, please note the approximate total bus cable
length for each bus:
Bus 1:
Bus 2:
Bus 3:
Bus 4:
4. All test values must be within 10% of the values in the
chart below to be considered valid.
12Ω to 20Ω
3,000 ft.
102Ω to 120Ω
1,000 ft.
34Ω to 40Ω
4,000 ft.
130Ω to 160Ω
Ground
_____ohms
A
_____ohms
+12
_____ohms
B
_____ohms
________ohms:
10. Remove the Bus Checker Card.
NOTE: For an XPoint bus, remove the Bus Checker Card and
plug the XPoint Terminator into the device.
Continuity Test Results Chart (Gnd to A & B to +12)
500 ft.
_____ohms
NOTE: For an XPoint bus, plug one terminator in at one end
of the bus and the Bus Checker Card at the other. Plug the
second terminator into one of the RJ45 ports on the Bus
Checker Card and measure the above.
_____ohms
68Ω to 80Ω
B to +12
A to B
3. At the other end, plug in the Bus Checker Card and
measure resistance across these terminals:
2,000 ft.
_____ohms
9. Measure the resistance across the following terminal on
the Bus Checker Card:
2. At one bus end, plug in the Data/Power Jumper.
3Ω to 6Ω
Gnd to +12
8. Add a terminator on the first and last device.
1. De-power every item on the bus and check the voltage
at both ends to ensure a reading of 0V. Remove any
terminators.
100 ft.
_____ohms
Purpose: To ensure that only two terminators exist; one at
each end of the bus. Readings out of range would indicate
a missing, misplaced or extra terminator on the bus.
Terminators are provided in a labeled bag inside the DTC
master panel.
Purpose: To verify bus length, continuity and detect crossed
data-pair wires. Do the following:
Ohms:
A to +12
Terminator Test
Continuity Test
Length:
_____ohms
NOTE: Readings between each terminal and earth ground
should be infinite or “open.”
Each test must be passed before moving onto the next. If
any readings obtained are out of range, refer to the Troubleshooting section (later in this checklist) or call Tech Support
at 800-345-4448.
Ohms:
Gnd to B
7. Measure resistance between the terminals below and earth
ground (metallic enclosure or conduit):
When doing this checklist, the Cat. 5 connecting the GR 2400
system to the XPoint Routers should be disconnected.
Length:
_____ohms
Purpose: to detect any pathways to earth ground:
For an XPoint system, this checklist would be completed for
each of the XPoint buses in addition to, but separate from,
the GR 2400 bus it’s connected to.
B to + 12
A to B
Earth Ground Test
For example, on a GR 2400 system these steps are followed
for each bus in addition to, but separate from, the backbone
bus (bus allowing all buses to communicate with each other).
_____ohms
_____ohms
NOTE: All test values should be greater than 1K ohms.
The following steps should be performed on each bus
separately:
Gnd to A
Gnd to A
11. Call Tech Support at 800-345-4448 with your results.
Bus Checker Card
Short Circuit Test
Purpose: to detect any short circuits along the bus. Please
use the 1K ohms or equivalent range setting on your
multi-meter. DO NOT use a “beep” test.
5. Remove the Data/Power Jumper.
6. Measure the resistance across the following terminals on
the Bus Checker Card:
127
Data/Power Jumper
TROUBLESHOOTING
!
!
!
Always re-check “failed” results. A meter that is
improperly set or connected can display unusual readings
and lead to failed testing.
1. An abraded or “folded” cable inside the conduit will cause
a short to earth ground.
2. Other low-/high-voltage wires touching devices on a bus
will cause continuity to earth ground.
T he Bus-Splitting Technique is the fastest way to find a
bad cable and/or damaged device. Be sure to document
the cable path.
Use the Bus-Splitting Technique to find the problem.
Terminator Troubleshooting
Cat. 5 cables that pass a Local Aera Network (LAN) cable
test can still short or break from stress and strain during
installation.
1. Ensure that the Data/Power Jumper is removed.
2. Visually inspect both terminators are present and properly
seated on each bus-end device.
If re-testing a suspected cable, wiggle and tug on the
conductors near the RJ45 connector while keeping an eye on
the LAN tester—conductors should remain engaged during
the testing.
NOTE: Refer to the Quick-Start Guide or the Making Up Cat. 5
Cable With RJ45 Connections Manual on running low-voltage
cables across, or parallel to, line-voltage cables or exposing
low-voltage cables to EMF or RF sources (e.g. welders,
ballasts, improperly grounded wireless devices, etc.); any of
which can interfere with the bus operation and stability.
Continuity Test Troubleshooting
1. Fluctuating resistance readings indicate one or more
active devices that are still “hot.” De-power all of the
devices and re-test.
A digital device can also become damaged and create signal
noise. An oscilloscope can also be used to locate the source
of the bus failure.
2. High resistance readings indicate broken or resistive
connections. The following are just some of the scenarios
that may cause this problem:
• R J45 connectors that are not properly seated with a
“click” in the sockets
• R J45 connectors improperly crimped (bowed, wires
extended beyond the end of the connector)
• C
able strain breaking or pulling conductors out of RJ45
contacts (visually inspect cable and connector)
• Damaged device
• Dirt or paint in RJ45 sockets or on connectors
• Bad Data/Power Jumper
For assistance in troubleshooting any of the above scenarios,
refer to the Bus-Splitting Technique later in this checklist.
NOTE: Complete the Continuity Test after the problem has
been resolved.
Short Circuit Test Troubleshooting
1. A low-resistance reading indicates a crossed or shorted
pair or a damaged device. Cable strain when pushing
switches into a wall can short circuit nicked conductors.
Use the Bus-Splitting Technique to find the bad cable,
crimp or device.
Important Note:
2. Resistance readings below 300Ω on A-B indicate an extra
terminator. Use the Bus-Splitting Technique to find the
short or extra terminator.
If you need help or if you get stuck,
contact Tech Support at 800-345-4448.
NOTE: After the problem has been resolved, please complete
the Continuity Test.
Earth Ground Troubleshooting
LAN-tested cables can still have paths to earth ground.
128
TROUBLESHOOTING (cont’d)
Bus-Splitting Technique
!
To speed up troubleshooting when readings are less than
200Ω on the Continuity Test or Short-Circuit Test, refer to
the Continuity Test Results Chart earlier in this checklist
before splitting the bus.
This can provide an approximate distance to a shorted pair or
extra terminator from the test point.
1. On the middle device of the bus, disconnect one Cat. 5
cable to create two smaller “half buses.”
2. Test each “half bus” to find the side with out-of-range values.
3. Repeat steps 1 and 2 on the out-of-range “half bus” to
create another “half bus” until the cable, crimp or device
creating the out-of-range measurement is located.
The idea is to split a bus in half and then half again—
over and over until the bad area has been located. Visual
inspection can also be used.
Full Bus
Half Bus
Half Bus
Lighting Control & Design
905 Allen Ave., Glendale, CA 91201
www.lightingcontrols.com
© 2010 Acuity Brands Lighting Inc., All Rights Reserved • Form No. 1382.069
129
COMMISSIONING REQUEST FORM
Factory Startup is a service included with the purchase of this system to field-test the lighting control system by
a factory technician. Factory Startup will be performed only after notification that the installation is complete.
Training for the system will be held the last day of the startup. The contractor is responsible for scheduling with
the owner and for providing any required recording materials upon the owner's request.
Job Information
Job Name:
LC&D Project ID #
Street Address:
City, State, Zip Code:
End User Contact Phone :
System Modem Number:
If LEED project, level? Circle one
Certified - Silver - Gold - Platinum
Electrical Contractor Information
Company Name:
Foreman/Electrician/Installer:
Foreman's email address:
Project Manager:
Project Manager's email address
Phone:
Phone:
Phone:
Billing Information
Name:
Billing Address:
Phone:
What is the targeted completion date of the project?
Special clearances
Special job site clearance or requirements technician needs to be aware of to have site access?
(if so please provide detailed information)
System Overview
Prior to a technician going onsite the Final Activation Checklist must be filled out and returned to LC&D (see
brochure). This checklist will provide the installing contractor with important check points for the installation of
the system. Completing this form will ensure that the installation of the system is done succesfully. Telephone
support is available to assist our clients with troubleshooting, wiring questions, programming questions and
other installation concerns. Please fill out and return this form along with the signed submittal approval.
130
GR 2400
™
Accessory
Bus Booster
Description: The Bus Booster is used on the GR 2400 System when the distance between switches and a relay panel
cause voltage drop.
Switches are supplied with power over the GR 2400 bus. While the data can travel 4,000 ft., the power to
a switch needs to be fed with a relay panel or a bus booster every few hundred feet. Features: • Provides up to 0.8 amp at 12 volts DC to the system bus
• Simply power up and plug in the bus
• Current limited
Enclosure rating: NEMA 1
Enclosure dimensions: 8.375" w x 8.375" h x 3.125" d
RJ45 Connectors: Sockets for Bus In & Out and Clock
Input: 120/277VAC, 347VAC
Output: 12VDC up to 800mA
Approvals: UL and cUL listed to UL 916
131
ACCESSORIES & LINK-TO CARDS
Specifications:
Layout
6.25" [15.9cm]
25UT
E226385
OS ANGELES
ALIFORNIA
JUNCTION AND
PULL BOX
7.25" [18.4cm]
®
LED
TYPE 1
+12
GND
CLOCK
LISTED
GND
+24
9.15" [23.3cm]
WITH COVER
UL
CAT. 5 CONNECTORS
LED POWER INDICATOR
BUS
LIGHTING CONTROL & DESIGN LC
BUS
This box is intended to be
used in an installation in
which equipment is grounded
by connection to metal raceway or metalic cable sheaths.
.25" [ .7cm]
MOUNTING HOLES
4 PLACES
1.125/.875 DOUBLE KNOCKOUT,
FOR 1/2" - 3/4" CONDUIT
8 PLACES
TERMINAL
STRIP
GROUNDING
LUG
277VAC
120VAC
Neutral
HIGH-VOLTAGE AREA
EQUIPMENT
GROUNDING
ONLY
LOW-VOLTAGE AREA
6.75" [17.2cm]
8.25" [21cm]
(8.4" [21.3cm] WITH COVER)
3.94" [10cm]
COVER NOT SHOWN IN VIEW
3 BUS-POWERED DEVICES
WITHIN 1000ft
Insufficient Power
Normally, up to 3 bus-powered
devices may be powered across
1000 feet of Cat. 5 cable. This
ensures that the power supplied
by the Master LCP is sufficient for
each device.
DEVICES WITHIN
ALLOWED LIMIT
ACTIVE
DEVICE
Specifying a Bus Booster allows
you to add more devices without
dropping voltage, because it
provides additional power to the bus.
POWER
INSUFFICIENT POWER
BUS-POWERED
DEVICES
CAT.5 CABLE
SUFFICIENTLY POWERED
DEVICES
SUFFICIENTLY POWERED
DEVICES
BUS-POWER
BOOSTER
BUS-POWERED
DEVICES
ACTIVE
DEVICE
POWER
CAT.5 CABLE
ADDED
EQUIPMENT
POWER
ordering logic
Bus Booster
GR2400 BOOSTER
System and Type
Transformer
Mount and Enclosure Type
DV = Dual voltage 120/277V
347 = 347 volt
SM NE1 = Surface mount, NEMA 1
FM NE1 = Flush mount, NEMA 1
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
132
GR 2400
™
Chelsea
Switch
Chelsea Digital Switch ™
Description: The Chelsea DigitalSwitch is a 100% digital switch which connects directly to the GR 2400 bus via
Cat. 5 patch cable with RJ45 connectors. Chelsea DigitalSwitches can be ordered with 1, 2, 3, 4 or 6
buttons per gang and can be mounted in any standard 2.25" deep switch box with a decorator style
switch plate. All Chelsea DigitalSwitches are 100% backwards compatible with all LC&D systems.
to control any relay,
Features: • May be programmed
™
SmartBreaker or dimmer in any panel
• Factory preprogrammed. May be reprogrammed
in the field using the DTC (Digital Time Clock)
• Custom button engraving at no cost
(2 lines 8 character/line)
• Link up to 127 digital addresses via Cat. 5 patch
cable with RJ45 connectors
• Available in a choice of plate and button colors
• Can be enabled/disabled by optional
KeyEnable™ switch
• All push buttons are annunciated with a pilot light
Advanced • A programmable green “Locator Light” at the top
Programming of each unit is always on, can be programmed
Features: to blink to show Horn Driver Mode or help locate
• Audible beep alert for warning or switch locating
• Programmable Status LED logic
• Alternate button programming to allow more
flexibility of use, for example the same button
can perform a different task at different times of
the day
• Adjustable debounce time to avoid
accidental trigger
• Capable of being digitally enabled/disabled over
the bus on a per button or per switch basis
a switch
Specifications:
Dimensions:
Switch plate:
Mounting:
Switch addresses
available:
Address per switch:
Function:
1.3" w x 4" h x 1.3" d
Decorator style
2.25" deep-switch box
1–119
1
ON, OFF, Mixed, Group
Control, Toggle, Scene Control
Programming:
Humidity:
Ambient temperature:
Power supply:
Bus connector:
Bus termination:
133
Via DTC
10– 90% non-condensing
32–105° F (0–41° C) Powered from GR 2400 bus
Two RJ45 connectors
Manual end-of-line termination
with jumper
SWITCHES / PHOTOSENSORS
Cover plate provided by contractor
Ordering Information
Chelsea DigitalSwitches™ are available in 1, 2, 3, 4 or 6 buttons. Center plates are available in white, ivory and brushed stainless steel.
Indicator light is red and locator light is green.
GR 2400™ Master
Relay Panel
GR 2400 Remote
Relay Panel
Chelsea
DigitalSwitch™
Chelsea
DigitalSwitch™
To phone line for
remote dial up
Example: Typical wiring
of a GR 2400 bus.
Cat. 5 patch cable with RJ45 connectors • Up to 127 digital addresses • Up to 4,000 ft.
ordering logic
Chelsea Digital
Number of Buttons
Single/Multicolor
Multicolor Button Colors
CH1 = 1 button Chelsea
CH2 = 2 button Chelsea
CH3 = 3 button Chelsea
CH4 = 4 button Chelsea
CH6 = 6 button Chelsea
BWH = All buttons white
BIV = All buttons ivory
BGY = All buttons gray
BBK = All buttons black
BRD = All buttons red
BGR = All buttons green
BBU = All buttons blue
BYL = All buttons yellow
BOR = All buttons orange
MC = Multicolored buttons
(please select quantities from
the multicolor button section)
Button Quantity
1B = 1 button
2B = 2 buttons
3B = 3 buttons
4B = 4 buttons
6B = 6 buttons
Examples:
Color
WH = White
IV = Ivory
GY = Gray
BK = Black
RD = Red
GR = Green
BU = Blue
YL = Yellow
OR = Orange
Plate Colors
Multicolor Examples:
CH6 MC 2BWH 4BBK PST
6 button Chelsea with 2 white and 4 black buttons and
a stainless steel faceplate PWH = White plate
PIV = Ivory plate
PST = Stainless steel plate
PBK = Black plate
CH4 MC 2BBU 1BGR 1BYL PWH
4 button Chelsea with 2 blue, 1 green, and 1 yellow
button and a white faceplate Button Quantity represents the number of buttons on
a switch that will be in the selected color— number may
not exceed total number of buttons on switch - total of
all button color quantities must equal total number of
buttons on switch (refer to examples).
CH6 BWH PWH = 6 button Chelsea with all white buttons and a white faceplate
CH3 MC 1BRD 2BBK PST = 3 button Chelsea with 1 red button, 2 black buttons, and a stainless steel faceplate
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
134
GR 2400
™
Switch
Chelsea Waterproof Digital Switch ™
Description: The Chelsea Waterproof DigitalSwitch is a 100% digital switch which connects directly to the GR
2400 bus via Cat. 5 patch cable. Chelsea Waterproof DigitalSwitches can be ordered with 1, 2, 3, 4 or
6 buttons per gang and can be mounted in any standard bell box with a decorator style switch plate.
Features: • May be programmed to control any relay, SmartBreaker™ or dimmer in any panel
• Factory preprogrammed. May be reprogrammed in the field using the DTC clock or remotely using
Unity™ Lighting Control Software
• Available in a choice of plate and button colors
• All push buttons are annunciated with a pilot light
• A “Locator Light” at the top of each unit is always on
• Custom button engraving at no cost (2 lines 8 CH/line)
• Link up to 127 digital addresses via Cat. 5 patch cable with RJ45 connectors
Optional: • Capable of being digitally enabled/disabled over the bus on a per button or per switch basis
Specifications:
Dimensions:
Switch plate:
Mounting:
Switch Addresses available:
Addresses per switch:
Function:
Programming:
Humidity:
Ambient temperature:
Power supply:
Bus protocol:
1.6" w x 4" h x 1" d
Decorator style
Waterproof bell box
1–119
1
Positive ON, Positive OFF, Group Control, Toggle,
Bypass or Scene Control
Via DTC clock, via PC with
Unity™ Lighting Control Software
100% rain proof
0–105° F
Accepts 12VDC from bus
RS 485 (GR 2400 bus)
135
SWITCHES/PHOTOSENSORS
Cover plate provided by contractor
Hookup Information
ordering logic
Chelsea Waterproof DigitalSwitch™
Number of Buttons
Single/Multicolor
Multicolor Button Colors
CH1 WP = 1 button Chelsea
CH2 WP = 2 button Chelsea
CH3 WP = 3 button Chelsea
CH4 WP = 4 button Chelsea
CH6 WP = 6 button Chelsea
BWH = All buttons white
BIV = All buttons ivory
BGY = All buttons gray
BBK = All buttons black
BRD = All buttons red
BGR = All buttons green
BBU = All buttons blue
BYL = All buttons yellow
BOR = All buttons orange
MC = Multicolored buttons
(please select quantities from
the multicolor button section)
Button Quantity
1B = 1 button
2B = 2 buttons
3B = 3 buttons
4B = 4 buttons
5B = 5 buttons
Examples:
Color
WH = White
IV = Ivory
GY = Gray
BK = Black
RD = Red
GR = Green
BU = Blue
YL = Yellow
OR = Orange
Plate Colors
Multicolor Examples:
CH6 MC 2BWH 4BBK PST = 6 button Chelsea with
2 white and 4 black buttons and a stainless steel
faceplate CH4 MC 2BBU 1BGR 1BYL PWH = 4 button
Chelsea with 2 blue, 1 green, and 1 yellow button
and a white faceplate PWH = White plate
PIV = Ivory plate
PST = Stainless steel plate
PBK = Black plate
Button Quantity represents the number of buttons
on a switch that will be in the selected color number may not exceed total number of buttons
on switch - total of all button color quantities must
equal total number of buttons on switch (refer to
examples).
CH6 WP BWH PBK = 6 button waterproof Chelsea with all white buttons and a black faceplate
CH4 WP MC 2BGR 2BWH PWH = 4 button waterproof Chelsea with 2 green buttons, 2 white buttons, and 1 white faceplate
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2009 Acuity Brands Lighting, All Rights Reserved.
136
GR 2400
™
Accessory
DigiLink™ Contact Closure Interface
Description: The DigiLink is a gateway for dry contact closure devices to the GR 2400 system. The DL 2400 is Features: Contact closure devices may be programmed to control any relays, SmartBreakers™ or dimmers in
typically mounted in a relay panel, but may be mounted in an optional external enclosure.
any panel. Control relays through time schedules of any Building Automation System.
Up to 14 contact closure inputs. Optional 6 input card allows for digital enable/disable over the bus.
Interface to:
• Building automation
• Occupancy sensors
• Security systems — life safety
• Contact closure low voltage switches
Specifications:
Enclosure type: NEMA 1, Flush mount optional
8.375" w x 8.375" h x 3.125" d with onboard Optional enclosure: NEMA 4, NEMA 12
Card dimensions: 3.45" x 2.75"
Power supply: Accepts 12VDC from bus
Optional power supply: Dual Voltage
Contact closure inputs: 14
Ambient temperature: 32–105° F (0–41° C) 137
Bus protocol: RS 485 (GR 2400 bus)
# of Addresses: 1
Programming: via DTC, via PC with Unity™
Lighting Control Software
Bus connectors: RJ45 connectors
Digilink with Supplies up to 500mA @
24VDC for occupancy sensor
power
ACCESSORIES & LINK-TO CARDS
• Link up to 127 digital addresses via Cat. 5 patch cable with RJ45 connectors
Hook Up / Wiring Details
DigiLink™
(shown with optional enclosure
and power supply)
(2) RJ45 Connectors
(1) Depluggable Screw Connector
14 Contact Closure Inputs
GR 2400 Bus Connectors
.7 amp power out for
occupant sensors
Maintained Contact Closure
Power Supply
Specify 120V, 277V
Momentary Contact Closure
Master
Relay Panel
Photosensor
Chelsea
DigitalSwitch™
Positive On/Off Contact Closure
Remote Relay Panel
Cat. 5 patch cable with RJ45 connectors • Up to 127 digital addresses • Up to 4,000 ft.
ordering logic
DigiLink Dry Contact Closure Gateway
GR2400 DIGILINK
System and Accessory Type
Transformer
Dry Contact Inputs
DV = Dual voltage 120/277V
347 = 347 volt
D6 = 6 inputs (with enable/disable)
D14 = 14 inputs (no enable/disable)
Lighting Control & Design • Glendale, CA
Enclosure Mounting, NEMA Rating,
Knockouts
SM NE1 = Surface Mount, NEMA 1
FM NE1 = Flush Mount, NEMA 1
SM NE4 = Surface Mount, NEMA 4
SM NE12 = Surface Mount, NEMA 12
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
138
GR 2400
CONTROL PANELS
™
C o n t ro l P a n e l
GR 2400™ Relay Panel
Description: The GR 2400 system is a 100% digital solution to lighting control. Panels and switches daisy-chain
together, using Cat. 5 patch cable with RJ45 connectors in any sequence.
Features: • 32-channel, 365-day/astronomical time clock. Large display (21 x 8 characters) acts as the programming interface for the entire system. Non-volatile memory holds all programming indefinitely. Ten-year battery back-up for time-of-day
• Modem includes free lifetime factory programming
• May control mixed voltages (i.e., 120V, 277V)
• May control normal or emergency power
• Ideal for all applications
• Manual override of individual relays, zones or entire panel
• Link up to 127 addresses of digital devices via Cat. 5 patch cable with RJ45 connectors
Specifications:
Enclosure dimensions: 20" w x 25.5" h x 6" d (32 relays)
20" w x 37.5" h x 6" d (48 relays)
Enclosure type: Surface mount, hinged locking door, NEMA 1
Optional enclosures: NEMA 4, NEMA 4X, NEMA 12, flush mount
Relay:
Optional relays:
Normally Closed (NCL)
30A @ 277VAC Ballast
20A @ 120VAC Tungsten
20A @ 347VAC Ballast
SCCR 18kA @ 277VAC Rated 250,000 Cycles
Addresses used: GR 2432 (4), GR 2448 (6)
Listings: UL and cUL 916 listed, ETL listed to UL 924 (for
emergency circuit use)
Programming: Via DTC, via PC with
Unity 2™ Lighting Control
Software
Max. humidity: 10 – 90% non-condensing
Ambient temperature: 32–105° F (0–41° C)
Normally Open, (NOL) Spec same as NCL,
Two Pole — NO or NC (480VAC);
Double Throw 20A 277VAC
139
Power supply voltage: 120/277VAC or 120/347VAC
Bus protocol: RS 485 (GR 2400 bus)
Bus connector: RJ45 connectors
Overview
Power Supply:
120/277V or 120/347V
DTC:
32-channel, 365-day astro clock
Access and program the entire system
Modem:
Remote programming and control, includes free
lifetime dial-up programming
Bus connectors
RJ45 connectors
Lighting Relays:
Normally Closed (NCL), 30A @ 277V Ballast,
20A @ 120V Tungsten, 20A @ 347V Ballast,
SCCR 18K A @ 277V, Rated 250,000 Cycles
Optional Relays:
Normally Open, (NOL) Spec same as NCL,
Two Pole — NO or NC (480V); Double Throw 20A 277V
High/Low Voltage Barrier:
(16 gauge steel)
Master Relay
Panel
Photosensor
PCELL 2WO
Chelsea
DigitalSwitch
Remote Relay Panel
w/PCC1 card
Chelsea
DigitalSwitch™
Relay Control Card
(manual control of zones
or individual relays)
Up to 127 digital addresses • Up to 4,000 ft.
Cat. 5 patch cable with RJ45 connectors
ordering logic
enclosure
Examples:
Enclosure Mounting, NEMA Rating, Knockouts
Relay Panel Enclosure
GR2448 ENC = 48 Relay Enclosure
GR2432 ENC = 32 Relay Enclosure
SM NE1 = Surface Mount, NEMA 1 with knockouts
FM NE1 = Flush Mount, NEMA 1 with knockouts
SM NE1 NKO = Surface Mount, NEMA 1 no knockouts
FM NE1 NKO = Flush Mount, NEMA 1 no knockouts
SM NE4 = Surface Mount, NEMA 4
SM NE12 = Surface Mount, NEMA 12
SM NE4X = Surface Mount, NEMA 4X
GR2448 ENC SM NE1
GR2448 INT 12NCL 12DPNC DTCMOD DV
48 relay, surface mount NEMA 1 enclosure with knockouts,
with 12 normally closed relays, 12 double pole normally
closed relays, with a digital time clock and modem (master
panel), and a 120/277V dual voltage transformer (also, no
voltage barriers).
interior
Relay Panel Interior
Relays
Clock Option
GR2448 INT = 48 Relay
Interior
GR2432 INT = 32 Relay
Interior
[qty]NCL = Normally Closed Latching
[qty]NOL = Normally Open Latching
[qty]DPNC = Double Pole Normally Closed
[qty]DPNO = Double Pole Normally Open
[qty]RRNO = Reed Relay Normally Open (pair)
[qty]SPDT = Single Pole Double Throw
[qty]SPDTC = Single Pole Double Throw Contactor
DTCMOD = Digital time clock
with modem
DTC = Digital time clock
without modem
REMOTE = Remote panel,
no clock
Transformer
Voltage Barrier1
DV = Dual voltage
120/277V
CNDV = 120/347V
[blank] = No barrier
1VB = 1 barrier
2VB = 2 barriers
3VB = 3 barriers
4VB = 4 barriers
Lighting Control & Design • Glendale, CA
1 = Check with NEC or
CEC, State or Province,
and local regulations as
well as your electrical
inspector about
allowances for voltage
barriers within panels.
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
140
GR 2400
™
Switch
Description: The Key DigitalSwitch™ is a 100% digital switch which connects directly to the GR 2400 bus via
Cat. 5 patch cable with RJ45 connectors. Key DigitalSwitches can be mounted in any 2.25" switch box
with a decorator style switch plate. This makes the Key DigitalSwitch ideal for schools, gymnasiums,
site-lighting and high-security applications.
Features: • Factory preprogrammed. May be reprogrammed in the field or remotely
• Key DigitalSwitch is available as momentary on/off or as “captive” (CT24 required captive key)
• Pilot LED indicates status of controlled loads (on or off)
• May be programmed to control any relay, SmartBreaker or dimmer in any panel
• Link up to 127 digital addresses via Cat. 5 patch cable with RJ45 connectors
• Use to enable/disable multiple Chelsea DE or Chelsea AD switches
Specifications:
Dimensions:
Switch plate:
Mounting:
Switch addresses available:
Addresses per switch:
Function:
Action:
Programming:
Humidity:
Ambient temperature:
Power supply:
Bus protocol:
Bus connector:
1.3" w x 4" h x 1.625" d
Decorator style
3" deep-switch box
1–119
1
Positive ON, Positive OFF, Group Control,
Toggle, Bypass or Scene Control
Center-off momentary (positive-on/positive-off)
Via DTC, via PC with Unity™ Lighting Control Software
10–90% non-condensing
32–105° F (0–41° C)
12VDC from bus
RS 485 (GR 2400 bus)
RJ45 connectors
141
SWITCHES / PHOTOSENSORS
Key Digital Switch™
Hook Up
Outdoor Photosensor
(facing north)
GR 2400™
Master Relay Panel
GR 2400 Remote
Relay Panel
Chelsea
DigitalSwitch™
Key
DigitalSwitch™
To phone
line for
remote
dial up
Controls Loads
directly
Cat. 5 patch cable with RJ45 connectors • Up to 127 digital addresses • Up to 4,000 ft.
ordering logic
Key DigitalSwitch
KS
Switch
Plate Color
Captive Key
PWH = White plate
PIV = Ivory plate
PST = Stainless steel plate
[blank] = No captive key
CK = Captive key
Examples:
KS PWH = Key DigitalSwitch with white plate
KS PST = Key DigitalSwitch with stainless steel plate
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
142
GR 2400
™
Switch
Decora plate provided by contractor
®
Description: The KeyEnable Switch replaces multiple-gang key switches. The KeyEnable may be mounted with
up to three Chelsea DigitalSwitches™, with up to six buttons each. The buttons of the Chelsea
DigitalSwitch are enabled and disabled by the KeyEnable Switch. This eliminates the requirement for
unwieldy multiple-gang key switches.
Features: • No programming required
• Ideal for site lighting, schools, theatres, gymnasiums, prisons and other high-security applications
• Pilot LED indicates status of controlled Chelsea DigitalSwitches (enabled or disabled)
• Captive key option available, so that the key can only be removed in the “disabled” position
• Push button switch LEDs function whether or not buttons are enabled
Specifications:
Dimensions:
Switch plate:
Mounting:
Action:
1.3" w x 2.6" h x 1.625" d
Decorator style
2.25" deep-switch box
Maintained
Function: Positive ON, Positive OFF, Group Control, Toggle, Bypass or Scene Control
Humidity: 10 –90% non-condensing
Ambient temperature: 32–105° F (0–41° C)
Power supply: Powered from adjacent 12VDC Chelsea DigitalSwitch
143
SWITCHES / PHOTOSENSORS
KeyEnable™ Switch
Hook Up
1. Starting with the topmost, connect a jumper from
the KeyEnable™ Switch to the disable pins on the
custom Chelsea DigitalSwitch™.
2. Using the second and third connectors, connect
jumpers to Chelsea DigitalSwitches 2 & 3 (if
needed).
3. Connect all switches to the bus. Program Chelsea
DigitalSwitches if not already done (see manual).
4. Mount switches in Decora plate (not supplied).
Note:
Factory prewired Key Enabled Chelsea
DigitalSwitches are available—please specify prior
to purchase.
ordering logic
KeyEnable Switch
KE
Switch
Plate Color
Captive Key
PWH = White plate
PIV = Ivory plate
PST = Stainless steel plate
[blank] = No captive key
CK = Captive key
Examples: KE PWH = KeyEnable Switch with white plate
KE PST = KeyEnable Switch with stainless steel plate
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
144
GR 2400
™
®
Link-to Building Automation (BACnet)
Link-To™ Building Automation
Description: LC&D offers two methods of building automation interfaces:
Specifications:
Enclosure rating: NEMA 1
Enclosure dimensions: 8.375" w x 8.375" h x 3.125" d
Optional mounting: In relay panel
Max. humidity: 10 – 90% non-condensing
Ambient temperature: 32–105° F (0–41° C) Power supply: 120/277VAC or 347VAC (specify)
Bus protocol: RS 485 (GR 2400 bus)
Interface protocol: Specific to building automation system
Approvals: UL and cUL listed
145
ACCESSORIES & LINK-TO CARDS
Features:
1)Gateway cards using DDC protocols such as BACnet™ and Metasys™ (N2) accept on/off commands,
time schedules and report status of all relays in all panels in real time.
2) The second method greatly simplifies interface to building automation through dry contact closure.
• Certified Connectivity Partner with Johnson Controls©, N2 protocol
• A number of building automation protocols are available as well as contact closure
• Program schedules from building automation package
• Expand any building automation package to include:
a) Communication-based Chelsea DigitalSwitches™
b) “Flick Warn” option for notifying room occupants of an impending lighting shut-off
c) Remotely adjustable multi-trip-point photosensor(s)
d) Gateway cards accept control and report real-time status of all relays
• Link up to 127 digital addresses via Cat. 5 patch cable with RJ45 connectors
Details
Link-To Building Automation
(DigiLink™)
Link-To Building Automation
(BACnet Gateway)
®
Power Supply:
Specify 120/277V or
347V
Ethernet Output
to BACnet
14 contact closure inputs
GR 2400 Bus Connectors
(2) RJ45 Connectors
(1) Depluggable Screw Connector
Low-Voltage Compartment
Access Door
Master Relay
Panel
Photosensor
Chelsea
DigitalSwitch
Remote
Relay
Panel
Link-To Building
Automation
(BACnet)
OR
Link-To Building Automation
(DigiLink)
Building Automation
Package using
BACnet
Contact Closure
from any Building
Automation Package
Ethernet Hub
Cat. 5 patch cable with RJ45 connectors • Up to 127 digital addresses • Up to 4,000 ft.
ordering logic
Link-To™ Building Automation
GR2400 L2
System and Type
Link-to Type
Transformer, Mount and Enclosure Type
MODB232 = ModBus RS2321
MODB485 = ModBus RS4851
BACNETIP = BacNet IP1
METN2 = N2 Metasys2
1=R
equired to choose a
transformer, mount and
enclosure type
2 = Transformer, mount and
enclosure optional (device
may be ordered as card only)
DV SM NE1 = Dual voltage 120/277V, surface mount, NEMA 1
DV FM NE1 = Dual voltage 120/277V, flush mount, NEMA 1
DV SM NE4 = Dual voltage 120/277V, surface mount, NEMA 4
347 SM NE1 = 347 volt, surface mount, NEMA 1
347 FM NE1 = 347 volt, flush mount, NEMA 1
347 SM NE4 = 347 volt, surface mount, NEMA 4
For
dry contact
inputs, see digilink
tech sheet
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
146
GR 2400
™
Accessory
UpLink
MetaServer™ and UpLink™
Description:
The UpLink™ network multiplex card links up to 99 digital buses together to create a system with over 12 thousand digital lighting
control devices.
The MetaServer™ digital web server is a gateway that provides Internet or computer access to these devices.
Here’s how they work: Up to 127 digital addresses (relay panels, digital switches, etc) may be linked together within a GR 2400 digital bus. Except for the largest projects, this proves to be more than enough capacity. For larger installations where multiple buses are
needed to accommodate the large number of digital devices, LC&D has developed a BackBone Bus using the UpLink™ card and
MetaServer™ to link up to 99 GR 2400 buses together.
At the head of the BackBone Bus is a MetaServer that does the duty of connecting the whole system via ethernet to a computer or
the internet. Connecting each digital bus to the BackBone Bus is an UpLink card. It captures packets meant for that particular bus
and routes the data correctly. The UpLink card has a large memory capacity which acts as a mirror of the status of the GR 2400 bus
for more rapid communication. It also keeps logs of the number of times a relay has been operated, the time it has been ON since
last reset and a log of each event (see DataLogger™ tech sheet for more information).
Features: •
•
•
•
•
An almost unlimited number of commands may move from one digital bus to another. Switches from one GR 2400 bus
may control all relays, dimmers, scenes, groups, or SmartBreakers in other downstream busses with full feedback.
Run-time and event-logging are stored in Flash memory until downloaded by an administrator (see tech sheet for
DataLogger software)
Connect as many as 99 UpLink cards to the internet
Access multiple buses using Unity GX Advanced Graphical Software
The MetaServer requires only a single IP and provides complete access to one or multiple buildings
Specifications:
Enclosure dimensions: 8.375" w x 8.375" h x 3.125" d
Ambient temperature: 32–105° F (0–41° C)
Enclosure type: Surface mount NEMA 1,
flush mount optional
Optional enclosure: NEMA 4
147
Power supply: 120/277VAC (DV) or 347VAC
Programming: via PC
(with administrator access)
Approvals: UL and cUL listed
ACCESSORIES & LINK-TO CARDS
Hook up / Programming
Hub
BackBone Bus
Server Card
Internet
GR 2400
Remote Panel
GR 2400
Master Panel
BackBone Bus
MicroPanel
Chelsea
DigitalSwitch
Uplink Card
GR 2400
Remote Panel
GR 2400
Master Panel
Chelsea
DigitalSwitch
Uplink Card
Smart Breaker
Panel
SmartBreaker
Panel
MicroPanel
Note: MetaServer • 1 per system, UpLink • 1 per bus
ordering logic
MetaServer™ and UpLink™
System and Type
Transformer
GR2400 UH4 = UpLink
GR2400 SH4MOD = MetaServer with modem
DV = Dual voltage 120/277V
347 = 347 volt
Mount and Enclosure Type
SM NE1 = Surface mount, NEMA 1
FM NE1 = Flush mount, NEMA 1
SM NE4 = Surface mount, NEMA 4
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
148
CONTROL PANELS
GR 2400-i
™
C o n t ro l P a n e l
Micro Panel™
Description: The MicroPanel™ comes standard equipped with four relays (MicroPanel-4) and provides integration features
simply not available anywhere else; particularly the advanced daylight harvesting properties. In its extended
version it is a compact lighting controller with up to eight switching (iDH) and four 0–10V dimming (iDim)
outputs that links every room into one digital, easy-to-use system.
The MicroPanel-8 (with eight relays) provides eight switched outputs, four of which can be dimmed outputs
using a single control card. It is the ideal solution for applications requiring more than four switch legs per
classroom. Example: “a, b, c” lighting with dimming, a leg for presentation lighting over a white board,
emergency lighting, and a contact closure for the thermostat. For applications that require more than four
(0–10V) dimming outputs, a second control card may be added.
Features: • Digital (global) or local wall switches
•
•
•
•
•
Digital (global) or local photosensors and occupant sensors
Integrates with the entire GR 2400™ system including centralized control panels
Time-of-day scheduling
Back plate mounting allows enclosure only to be shipped for rough-in
Rated for Normal or Emergency Power (mixed sources require an adjacent enclosure)
Specifications:
Enclosure dimensions:
Enclosure type:
Optional Enclosures:
Relays:
MicroPanel-4 - 8.375" w x 8.375" h x 3.125" d (2-4 relays) MicroPanel-8 - 12.875" w x 8.375" h x 3.125" d (5-8 relays)
Ambient temp:
Listings:
Surface mount, screw cover door, NEMA 1, EZ-Find™
yellow powdercoat
NEMA 4, NEMA 4X, NEMA 12
Normally Closed (NCL) 30A @ 277VAC Ballast,
Photosensor inputs:
20A @ 120VAC Tungsten, 20A @ 347VAC Ballast, Local switch inputs:
SCCR 18kA @ 277VAC, Rated 250,000 Cycles
0–10VDC outputs:
Optional Relays: Normally Open, (NOL) Spec same as NCL, Power for Occupant Sensor:
NO or NC; Two Pole — NO or NC (480VAC); Double Throw 20A, 277VAC
Power Supply Voltage:
Number of Addresses: MicroPanel 4 (2) addresses
MicroPanel 8 (4) addresses
149
32–105° F (0 – 41° C), non-condensing
UL and cUL to UL 916, available as UL
listed for mounting in an air plenum (with
suitable enclosure), ETL listed to UL 924
(for emergency circuit use) 4 (8 with optional 2nd control card)
8 (16 with optional 2nd control card)
4 (8 with optional 2nd control card, 15mA per channel)
24VDC/450mA
120/277VAC or 347VAC
Programming: Via DTC, via PC with Unity™ Lighting Control Software
The Digital Daylight Harvesting Solution
Because our competitor’s daylight
harvesting controls are not part of a
system, commissioning and any later
adjustments often require on-site or
hardwiring changes.
With proper installation, expensive
on-site commissioning can be eliminated.
Commissioning can be accomplished
remotely (via dial-up or internet) from the
factory.
The MicroPanel-iDH and -iDim solve
this with our 100% digital lighting control
system.
Any adjustments (e.g.,­­­ to adapt to
interior design changes) can be made
with a phone call.
Adjustments can
be made with a
phone call
Unprecedented Daylight Harvesting
Response Curve. Individually set three
points on the response curve, start dim
level, mid-point and turn off or end point.
This is a major breakthrough in daylight
harvesting, as almost any architectural
setting can be compensated for after
photosensor placement.
Fade Rates. Separate raise and lower
fade rates (0 seconds to 100 minutes)
in response to the photosensor helps
accommodate human eye response.
0v
Daylight Levels
Occupants offered a degree of control are
less likely to disable the system.
Trim. Individual trim
levels may be set for
each dimmer to compensate for
manufacturers’ ballast response (for
example, 2–8V instead of 0–10V).
Bright
12 Scenes. Accommodate daylight
harvesting presets for seasonal
changes or fixed level presets for
architectural dimming.
"Must Turn On" Level. A light level
below which electric lighting is switched
on with no time delay (but with the
proper fade rate). Sometimes required
when blinds are closed or dark clouds
pass overhead.
0v
Trim
Dimming Output
stop dim
10v
Night
Time Delay. Prevents
nuisance cycling. Adjust
from 0 seconds to 99
minutes.
0v
mid-point
5v
Baseline. If room occupants feel the
automatic settings are too bright or too
dim, they can adjust the baseline with
an optional slider switch. The adjustment
range of the slider can be set remotely.
Dimming Output
Dimming Output
start dim
Local Override. Room occupants may
temporarily override automatic lighting
levels. Even operates with
inexpensive (3-way) low
voltage wall switches.
Night
mid-point
start dim
Trim
10v
stop dim
10v
Daylight Levels
150
Bright
Night
Daylight Levels
Bright
Multi-Zone Dimming & Switching
The really big news is the ability of
the MicroPanel to control multiple
daylight harvesting zones (dimming or
switching) with a single (local or global)
photosensor.
Each dimmer (or relay) may have its own
dimming curve appropriate to its location
in the room. These multiple dimming
curves are ideal for open loop or closed
loop daylight harvesting.
No matter what the exposure may be
(north, south, east or west), the right
curve can be precisely set for any
architectural setting.
0v
-iPCPCELL 3WI TZ
photosensor
Row 1
Dimming Output
-iDim
Row 1
Row 2
Row 3
Row 2
5v
Row 3
10v
Glazing
Daylight Levels
Night
Bright
Local & Global Photosensors
LC&D clients are used to having local and
global switches, occupancy sensors and
programming. Now we also offer global
daylighting photosensors!
Local Photosensors
Daylit
dimming
zone
PCELL 3WI TZ
-iPC-L
Local photosensors are used when
separate responses are required for each
room to account for individual blinds or
window treatments.
Multiple rooms that share the same
exposure and window treatment can share
the same photosensor over the network.
Global photosensors are also used for toplit applications such as warehouses.
dim 4
General
lighting zone
dim 3
Hot
dim 2
dim 1
Daylit
dimming
zone
-iPC-L
PCELL 3WI TZ
Local
Photosensor
General lighting zone
MicroPanel-iDim
Digital Switch (local and global control)
Global Photosensor
Daylit
dimming
zone
Daylit
dimming
zone
-iPC-G
Daylit zone
“c” leg
Global
PCC1
PCELL 2WI
Photosensor
Daylit zone
“c” leg
dim 4
dim 3
Hot
dim 2
dim 1
General
lighting zone
General
lighting zone
“b” leg
“a” leg
MicroPanel-iDim
MicroPanel-iDH
Digital Switch (local and global control)
151
“b” leg
“a” leg
MicroPanel-iDH
Single Line Drawings
3-WAY LOW VOLTAGE WALL SWITCH
PCELL 3WI TZ
ordering logic
Enclosure
Relay Panel Enclosure
Enclosure Mounting, NEMA Rating, Knockouts
GR2404 ENC = 4 Relay Enclosure
GR2408 ENC = 8 Relay Enclosure
SM NE1 = Surface Mount, NEMA 1
FM NE1 = Flush Mount, NEMA 1
SM NE4 = Surface Mount, NEMA 4
SM NE12 = Surface Mount, NEMA 12
SM NE4X = Surface Mount, NEMA 4X
Emergency Enclosure
(optional)
EMSMDM
EMSMDH
If this is not being used for separating
normal and emergency circuits, then leave
this blank. Otherwise put EM for emergency,
SM for surface mount (flush mount is
not available in this configuration), then
depending on your control card choice for
the interior, put DM if you chose iDim, or DH
if you chose iDH.
Example: EMSMDH would be for a
MicroPanel iDH for emergency circuits in a
surface mount enclosure.
Interior
Relay Panel Interior
GR2404 INT =
4 Relay Interior
GR2408 INT =
8 Relay Interior
Relays
[qty]NCL = Normally Closed Latching
[qty]NOL = Normally Open Latching
[qty]DPNC = Double Pole Normally Closed
[qty]DPNO = Double Pole Normally Open
[qty]RRNO = Reed Relay Normally Open (pair)
[qty]SPDT = Single Pole Double Throw
[qty]SPDTC = Single Pole Double Throw Contactor
Control Card
IDH4 = iDH control card for GR 2404
IDH8 = iDH control card for GR 2408
IDIM4 = iDim control card for GR 2404
IDIM8 = iDim control card for GR 2408
Transformer
Input Card (optional)*
DV = Dual voltage 120/277V
347 = 347 volt
D6 = 6 inputs (enable/disable)
D14 = 14 inputs
(no enable/disable)
Example:
Where [qty] is in the nomenclature, replace with quantity of relays, and leave no space
between number and code (example: 8NOL = a quantity of 8 normally open, latching relays).
GR2408 ENC SM NE1 EMSMDM
GR2408 INT 8NCL IDIM4 DV D6
Total may not exceed 4 for GR2404, or 8 for GR2408 and quantity must be in pairs for single
relays (NCL, NOL, and SPDT) or each for any double relays (DPNC, DPNO, RRNO, and
SPDTC) as they count as two: example, a GR2408 may only have 2, 4, 6 or 8 NCL relays, or
1,2,3 or 4 DPNC relays).
8 relay MicroPanel iDim for emergency circuits, surface mount NEMA 1
enclosure, with 8 normally closed relays, iDim control card with 6 dry-contact
enable/disable inputs, and a 120/277V dual voltage transformer.
Lighting Control & Design • Glendale, CA
*Input card option for
GR2404 INT requires a
GR2408 ENC. Input card
option for GR2408 INT
requires an additional
GR2404 ENC to be
specified.
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
152
GR 2400
™
Photosensor
Outdoor Digital Photosensor
Description: The Outdoor Digital Photosensor is designed for single-zone or multi-zone outdoor lighting control
applications. Its global control ability makes it ideal for both simple and complex site-lighting
controls. The GR2400 PCC1 2WO is the 2-wire outdoor photosensor shipped with a photocell control
card which may be located anywhere on the GR 2400 Bus. The PCELL 2WO is shipped without a control card to be plugged directly into a Blue Box Master control card.
Features: • Readout of the photosensor is digitally displayed at the DTC and remotely at a PC operating Unity™
Lighting Control Software
• The GR2400 PCC1 2WO may be programmed with up to 14 different trigger points, each controlling
a unique relay group at different ON and OFF light levels in as many as 64 relay panels.
• The PCELL 2WO operates with a single schedule with a single trigger point to provide photocell ON,
timeclock OFF control to a GR 1400 system. This will operate on any relay on the bus.
• Totally sealed and suitable for wet locations
Specifications:
Operating range: 0–1000 fc
Programming at: DTC
PC (with Unity™
Lighting Control
Software)
Outdoor Photosensors
The hood protects the photosensor from
direct exposure to the sun. The Outdoor
Digital Photosensor is usually roofmounted and aimed North.
For daylight harvesting applications, refer
to the Indoor Digital Photosensor.
153
SWITCHES / PHOTOSENSORS
Outdoor Digital Photosensor
Single Line
Global Photosensor
PCELL 2WO
2 #18 AWG
GR2400 PCC1
Chelsea
DigitalSwitch™
GR 2400™ Relay
Panel
Cat. 5 patch cable • up to 4,000 ft. • up to 127 digital addresses
Global Photosensor
PCELL 2WO
Bell Box or
outdoor
rated
enclosure
PCELL 2WO
2 #18 AWG
8V (common)
Photosensor input
Lighting can be staggered on as outdoor
light levels decrease with a single
photosensor.
The Blue Box™
ordering logic
Outdoor Digital Photosensor
PCELL 2WO
Two-Wire Outdoor Photosensor for GR 1400 system
GR2400 PCC1 2WO
Two-Wire Outdoor Photosensor with PCC-1 control card for GR 2400 system
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
154
GR 2400
™
Photosensor
I n p u t C a rd s
Description: Photosensor input card which a) converts the signal of a photosensor into a digital stream, and b) stores
“global” switching triggers. Triggers are global “On” and “Off” commands programmed at a unique light
level, each with a unique group of relays, smart breakers or dimmers.
The PCC1 is used for outdoor photosensors (PCELL 2WO) and has a single photosensor input.
The PCC3 is used for indoor photosensors (PCELL 2WI) and has inputs for up to 3 separate
photosensors.
Features: • Light levels from each photosensor may be displayed or read at the DTC
• Light levels may also be displayed via Unity™ Lighting Control Software or Unity GX™ Advanced
Graphical Software
• Up to 14 switch-trigger points
• May be polled by GR2400 Dimmers over the bus
• Programming locally at the DTC, or remotely via Unity™ Lighting Control Software or Unity GX™
Advanced Graphical Software
• The inputs of a PCC-3 may be digitally enabled or disabled via time clock, or other controllers such
as digital switch, building automation, occupant sensors, etc.
• Advanced daylight harvesting features—please refer to Indoor Photosensor tech sheet for more
details
Specifications:
Enclosure: 6" w x 6" h x 4" d
NEMA 1 Screw Cover
# of Addresses: 1 (PCC1 and PCC3)
Power supply: From GR 2400 bus
Humidity: 10– 90% non-condensing
Ambient temperature: 32–105° F (0– 41° C)
155
Max wiring distance: 300 ft. to each photosensor
SWITCHES / PHOTOSENSORS
Photosensor Input Cards
Hook up / Programming
PCELL 2WO
PCELL 2WI
GR 2400
Relay Panel
GR 2400
Relay Panel
Chelsea
DigitalSwitch
2 #18
3 #18
PCC1
Laptop computer running
Unity™ Software
PCELL 3WI TZ
GR2408
Cat. 5 patch cable with RJ45 connectors • up to 127 digital addresses • up to 4,000 feet
Photosensors do not always require a photosensor card. The Blue Box Master Panel (not shown) has an onboard input for
one outdoor photosensor with 8 global triggers. The MicroPanel has onboard inputs for up to 4 local indoor photosensors.
ordering logic
Photosensor Control Cards
GR2400
System Type
Photosensor Card
(with or without Photosensor)1
PCC1 = Outdoor card, 1 input, no sensor
PCC1 2WO = Outdoor card, 1 input, one 2WO
PCC3 = Indoor card, 3 inputs, no sensor
PCC3 2WI= Indoor card, 3 inputs, one 2WI
PCC3 2WO = Indoor card, 3 inputs, one 2WO
Enclosure
[blank] = card only, no enclosure
SM NE1 = Surface Mount, NEMA 1
FM NE1 = Flush Mount, NEMA 1
SM NE4 = Surface Mount, NEMA 4
1 = Indoor Photosensor card PCC3 includes
digital enable/disable feature
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
156
PCC3
GR 2400
™
Lighting Control Software
TM
Download Unity2.2 at: www.lightingcontrols.com
S o f t w a re
Unity2.2™ Lighting Control Software
Unity2.2 Lighting Control Softwarebundlesdesign(specification),
programmingandmanagementofalightingcontrolsystemintoa
singlesoftwarepackage.It’sfree.Anditrequiresnoformaltraining.
SpecifiersuseourUnity2.2 Lighting Control Softwaretorapidly
designanewlightingcontrolsystem.Unityfilesmaybesaved
andoutputtoAUTOCADinafewseconds.Installersareassisted
byUnity2.2sinceiteliminatesfieldprogrammingrequirements.
LC&Dwillpreprogram(uploadthespecifier’sUnityfile)prior
toshipment—atnocost.
BuildingengineersmayuseUnity2.2tomonitorandcontrol
thelightingcontrolsinrealtimefromthedisplayofourclockor
fromadesktopPC.
Version2.2nowutilizesfullyupdatedproductcodesforallproducts.
Design
OneofthebestfeaturesofUnity2.2 Lighting Control Softwareisitseaseofuseandeasypointandclickfeatures.Quicklydesignacomplete
lightingcontrolsystemfromthegroundupinminutes.
Add relay panels, switches
Addrelaypanels,switchesoranyofour
of
manyaccessories.Simplypointyourmouse
totheleftwindowpaneandright-click.You
willseeapulldownboxwhichallowsyouto
selectwhateverdeviceyourequire.Youcan
dothisasmanytimesasneeded.
Submit
Submityourlightingcontrolsystemin
lighting control system in
AUTOCADformatoroutputyourdesignto
aUnityfile(.bus2)andemailittous.LC&D
canbuildyoursystemaccordingtoyour
specifications.
157
Exportyourlightingcontrolsystemdesignto
CAD(.DXFformat)inseconds.Unity2.2
willgenerateasingle-linedrawing,panel
schedules,switchschedulesand
specifications.
ACCESSORIES & LINK-TO CARDS
• Setuprelaypanels,switches,photosensors,timeschedules—anyaspectofasystem
• OutputadesigntoAUTOCADinafewseconds,includingjob-specificsingle-linedrawings,panelschedules,switchschedulesandspecs
• Whenready,theUnityfilecanbeemailedtoLightingControl&Designandwillbebuiltandprogrammedexactlyaslaidout
Program
Lighting Control & DesignusesourcarefullypreparedUnitysubmittaltopreprogrampanels,
switchesandtimeschedules—theentirelightingcontrolsystempriortoshipment.Newsettingsmay
beuploadedtothelightingcontrolsystemorprogrammedinrealtime.
AllthetoolsneededtoprogramyourlightingcontrolsystemareincorporatedinUnity.Programming
oradjustingswitches,photosensors,relaypanels,etc.,isfastandsimple.Easilyconnecttoyour
lightingsystemtomodifyyoursystemortosavesettingstodisk.
Uploadyournewsettingstoyourlightingcontrolsystemeitherthroughdial-uporanetworkLAN.
Thesesettingswillinstantlygointoeffect.
Manage
SimplifyyourlightingcontrolsystembymanagingitwiththeDTCinthemasterpanel
oradesktopcomputer,localorremote.Controlrelaysandgroups,modifyschedules
andmuchmore.
Unityismorethanjustagraphicaluserinterface.Unityisthefirmwareusedbythe
GR 2400™system.TheGR 2400systemsitsontheUnityplatform.
TheDigitalTimeClock(DTC)mountedinthemasterrelaypanelusesUnityto:
• Manuallycontrolallrelaysinrealtime
• Programswitchesandphotosensortrippoints
• Programtimeschedules
• Programallaspectsofthesystem
RemotelyaccesstheGR 2400buswithUnity Software.Connectionoptionsinclude:
• Dial-upconnection(builtinmodeminthemasterLCP)
• Directserialconnection(Link-To PC)
GXisanoptionalgraphical
softwarepackagewhich
complementsthebasicUnity
package.Learnmoreat:
www.lightingcontrols.com
orDeringlogic
Software
UNITY
Unity Software
Lighting Control & Design • Glendale, CA
Phone(323)226-0000•F(323)226-1000•SalesHotLine(800)345-4448•sales@lightingcontrols.com•www.lightingcontrols.com
©2010AcuityBrandsLighting,AllRightsReserved.
158