Technical data Danfoss DHP-S ! A building heat pump in power outputs from 20 to 42 kW. ! Filled with R407C (60¡C) Main parts.......................................... 2 Control and safety devices................ 3 Dimensions and connections.............4 Technical data....................................5 VFGFA102 Main parts 1 Compressor • Scroll compressor 2 Circulation pumps • Condenser circulation • Brine circulation 3 3 Heat exchanger • Condenser • Evaporator • De-superheater 1 2 VFGFA102 Dimensions and connections 1 Coolant out (from HP) 2 Heat return (return line) 3 Return line hot-gas exchanger 4 Supply line hot-gas exchanger 5 Heat supply (supply line) 6 Coolant in (to HP) 7 Lead-in for communication cable 8 Lead-in for incoming power supply and sensors VFGFA102 Control and safety devices To ensure a correct function of the heat pump there are a number of control and safety devices. The figure below shows the heat pump’s three liquid circuits with respective safety function. Compressor The compressor is equipped with a thermal overload relay which protects the compressor from over current. Thermal overload relay Figure 2: The thermal overload relay on the electrical panel. 1. 2. 3. 4. 5. 6. 7. 8. If the thermal overload relay is tripped the alarm indicator on the front panel is flashing and an alarm text is displayed. The thermal overload relay must cool down and it is automatically reset. The alarm is acknowledged by setting the operational mode to OFF and then back to previous mode (AUTO/HEATPUMP/ADD. HEAT/HOT WATER). The compressor is also equipped with an internal protection which stops the compressor’s operation if it risks being overheated. The internal protection cannot be reset manually, the compressor must cool down before it can start operation. Brine circut Evaporator Compressor Hot gas exchanger Condensor Expansion valve Refrigerant circut Heat transfer circuit Heat transfer circuit If the pressure in this circuit exceeds the opening pressure of the safety valve , the valve opens to release the overflow and then shuts again. The safety valve overflow pipe must have an open connection to the drain and visibly flow into this in a frost-free environment. Refrigerant circuit The refrigerant circuit’s high pressure side is equipped with a high pressure switch and one operational pressure switches . The connected operational pressure switch stops the compressor when the switching point is reached, that is, when sufficient amount of heat is produced. If the operational pressure switch should fail and the pressure continue to rise, the compressor is stopped by the high pressure switch when its switching point is reached. The operation of theheat pump is blocked. When the problem with the abnormally high pressure is solved, the pressure switch is automatically reset. If the high pressure switch is tripped the alarm indicator on thefront panel is flashing and an alarm text is displayed.Restart the heat pump by first setting the operational mode to OFF and then back to previous mode (AUTO/HEATPUMP/ADD.HEAT/HOT WATER). The low pressure switch stops the compressor if the pressure is too low on the low pressure side. The operation of the heat pump is blocked. When the problem with the abnormally low pressure is solved, the pressure switch is automatically reset. If the low pressure switch is tripped the alarm indicator on the front panel is flashing and an alarm text is displayed. Restart the heat pump by first setting the operational mode to OFF and then back to previous mode (AUTO/HEATPUMP/ADD.HEAT/HOT WATER). Brine circuit If the pressure in this circuit exceeds the opening pressure of the safety valve, the valve opens to release the overflow and then shuts again. The safety valve overflow pipe must have an open connection to the drain and visibly flow into this in a VFGFA102 Circulation pumps A circulation pump has an internal overload protection. It is reset automatically when the pump has cooled down. However, a pump in a 20 to 42kW heat pump has an internal overload relay that trips the motor protection alarm. The indication and reset are the same as for the compressor. Specifications Please see the technical data tables at the end of this manual fordetailed specifications. Technical data DHP-S 20 26 8.8 11.8 R407C T brine °C 20 5 -5 -10 5 20 VFGFA102 35 15.7 T water °C 55 60 60 20 20 30 42 19.9