D Journal of Energy and Power Engineering 6 (2012) 240-249 DAVID PUBLISHING A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks Mohamed F. Abdel-Fattah1,2 and Matti Lehtonen1 1. Department of Electrical Engineering, School of Electrical Engineering, Aalto University, Espoo 00076, Finland 2. Department of Electrical Power and Machines Engineering, Faculty of Engineering, Zagazig University, Zagazig, Sharqia, PO Box 44519, Egypt Received: August 05, 2010 / Accepted: April 28, 2011 / Published: February 29, 2012. Abstract: This paper presents a new earth-fault detection algorithm for unearthed (isolated) and compensated neutral medium voltage (MV) networks. The proposed algorithm is based on capacitance calculation from transient impedance and dominant transient frequency. The Discrete Fourier Transform (DFT) method is used to determine the dominant transient frequency. The values of voltage and current earth modes are calculated in the period of the dominant transient frequency, then the transient impedance can be determined, from which we can calculate the earth capacitance. The calculated capacitance gives an indication about if the feeder is faulted or not. The algorithm is less dependent on the fault resistance and the faulted feeder parameters; it mainly depends on the background network. The network is simulated by ATP/EMTP program. Several different fault conditions are covered in the simulation process, different fault inception angles, fault locations and fault resistances. Key words: Earth faults, earth capacitance, transient impedance, transient frequency, unearthed and compensated MV networks. 1. Introduction In networks with an unearthed (isolated) neutral, the currents of single phase to ground faults depend mostly on the phase to ground capacitances of the lines. When the fault happens, the capacitance of the faulty phase is bypassed, leading to unsymmetrical system. The fault current is composed of the currents flowing through the earth capacitances of the two sound phases as shown in Fig. 1. Therefore, the capacitance measurement gives an indication if the feeder is faulted or healthy. The main advantage of unearthed neutral in power systems is small fault currents which does not require to shut down immediately, but the main problem is the over-voltage that resulted by charging of the system Corresponding author: Mohamed F. Abdel-Fattah, postdoctoral researcher/lecturer, research fields: earth-faults detection, diagnosis and location using transient and fast transient-based algorithms and the intelligent protection systems for self-healing capability of the smart grids. E-mail: mohamed.abdel-fattah@aalto.fi. capacitance of the sound phases, which may lead to flashover or breakdown. Also, it may establish a double line to earth fault. In earth faults, the transient components include charge and discharge of the network capacitance and consist of different frequencies. The voltage of the faulty phase falls suddenly, giving rise to the discharge transient while the charge transient is generated by the E1 E2 E3 ~ ~ ~ Z L1 Z L2 Z L3 Ce Fig. 1 Earth fault in unearthed neutral network. RF A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks voltage rise in sound phases during a single-phase to ground fault. This means that a charge transient is always a side effect of the ground fault. Moreover, the charge component dominates the amplitude of the composite transient and therefore it is reasonable to be used for single-phase to ground fault detection. The charge component has to flow through the transformer winding and consequently its frequencies are substantially lower than those of discharge component. According to practical experience, the frequencies of discharge and charge components vary in the range 500-2500 Hz and 100-800 Hz respectively. The amplitude of the discharge component is relatively small, typically only about 5%-10% of the amplitude of the charge component [1, 2]. The small fault currents may reduce the sensitivity of conventional relays that normally are based on the fundamental components of the current and voltage at power frequency. The high fault generated high frequencies should be filtered out in the conventional protective schemes which only use the power frequency, however, these high frequency components contain more information about the fault than power frequency that should be utilized, with the rapid developments in microprocessor technology, in new developed techniques called transient based techniques. In contrast to present protection techniques based on fault transient detection, such as traveling wave based protection techniques, the transient based techniques are not limited by the bandwidth of the conventional transducers, and are able to accurately separate and extract the high frequency information required from the dominant power frequency signals [3]. Transient-based protective schemes can detect high impedance as well as intermittent arcing faults, leading to improvement in the power system reliability. However, there are the hidden faults which involve developing and self extinguished/arcing faults which may not be detected by the conventional protection system. In particular, high resistance arcing faults are highly random as viewed from their current waveforms. 241 Many research works have been done in this area in the last few years, for earth fault detection in unearthed and compensated neutral networks, but the goal is still not fulfilled. It is very important to validate the results from the simulation process and to be satisfied that it can represent the actual realistic conditions. In Ref. [4], comparative investigations between real earth fault field tests and the equivalent simulation data have been presented. A simple powerful technique in Ref. [5] is proposed to utilize the peak values of the superimposed waveforms. In the same time, these peaks can be used to synchronize the waveforms, supported by a suitable secure manipulation within the algorithm. Another efficient way is to use the probabilistic analysis as proposed in Ref. [6]. The earth fault characteristics, analysis and comparison, in medium voltage distribution networks, 20 kV with high impedance earthing, were presented in Ref. [7]; the presented results are based on the evaluation of 465 real case data recording, obtained from substations of distribution networks with an unearthed or a compensated neutral during the observations period of 3 years; continued investigations were presented in Ref. [8]. The earth fault location for different fault conditions, in these networks, were also investigated in Refs. [9-14] and a probabilistic-based method is proposed in Ref. [15]. Some work have been done to investigate the intermittent earth fault; in Ref. [16] using the zero sequence voltage and a sum current of phase currents, the intermittent fault is identified if the amplitude of the voltage and current exceed corresponding set values and the phase difference is within preset set values, in Ref. [17] the features of the intermittent fault were identified to using wavelet analysis and in Ref. [18] the wavelet analysis were applied using the phase comparison between wavelet coefficients of zero sequence voltage and currents. A residual equivalent circuit for Peterson coil grounded distribution systems have been presented in Ref. [19] and an extended zero sequence equivalent circuit for compensated medium voltage systems, with load current contribution 242 A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks accounted, is presented in Ref. [20] and the detection of single line-to-ground fault in compensated networks has been investigated in Refs. [21, 22]. The transient period features have been investigated in Ref. [23], an algorithm for high impedance fault is detected in compensated neutral grounded medium voltage power systems, the calculation of the influence of feeder admittance unbalance in neutral voltage is presented in Ref. [24]. The three-phase line can be decomposed into three separate and independent modal equivalent circuits. The modal components are the transform of the instantaneous (or time domain) phase quantities, using transformation matrices, into zero, first and second modes. The zero mode is also termed the “earth mode”, while the second and third modes are termed “aerial modes”. In protection applications, there are three modal transformation matrices that have been widely used. They are Wedepohl, Karrenbauer and Clark transformations [25]. For all of these transformations, the earth mode is the same; it is equal to one-third of the summation of the instantaneous phase values (voltages or currents) as given by Eqs. (1) and (2). The values of the voltage and current earth modes are equal to zero in normal operation and become meaningful in fault condition. They are very sensitive for earth faults; hence they are suggested to be used for fault detection. The voltage and current earth modes are given by Eqs. (1) and (2). v (t ) 0 13 [v a (t ) v b (t ) v c (t )] i (t ) 0 13 [ia (t ) ib (t ) ic (t )] (1) (2) In this paper, a new earth-fault detection algorithm for unearthed and compensated neutral medium voltage networks is presented. The algorithm is proposed to calculate the earth capacitance that can be used as fault indication for the faulted feeder. The capacitance can be calculated using the dominant transient frequency and the transient impedance. Different fault inception angles, fault locations and resistances were simulated to check the validity of the algorithm. 2. The Simulated Network Based on a typical 20 kV medium voltage distribution network configuration, a suitable network model will be proposed for the required investigations. A realistic network of the arrangement shown in Fig. 2 is proposed for the study. A primary (110/20 kV) substation feeds a rural overhead network consisting of five feeders of many tens of kilometers length. The mathematical model of the network has been implemented using the alternative transient program. The alternative transient program ATP/EMTP is a popular simulation software package mainly intended for transient analysis applications [26, 27]. ATPDraw, a graphical pre-processor to ATP, has been used to construct the network elements using suitable graphical blocks/symbols, to plot the required figures and to write the required output data files in a suitable form for further advanced analysis in Matlab [28]. The transmission line frequency dependent model (JMarti) is used for feeders simulation with sampling time of 100 μs. The network data are given in the appendix. 3. The Proposed Algorithm For the simulated network shown in Fig. 2, the earth modes of the bus voltage and feeder currents are calculated at substation (measuring points). Fig. 3 shows the waveforms of the voltage earth mode at the bus and the current earth modes for each feeder. The waveforms for all healthy feeders are approximately the same but situation is different for faulted feeder as shown. The transient period is the first few milliseconds directly after fault incidence. From investigations of the simulation results it is found that a suitable transient window of 2.5 ms is adequate to extract the transient frequencies in all different fault conditions, different fault inception angles, fault locations and fault resistances, hence it will be used with DFT (Discrete Fourier Transform) method. A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks The enlarged view of the transient period is shown in Fig. 4. The DFT method will be used to extract the dominant transient frequency (of higher amplitude) from the charge transient component, from 0 to 1200 Hz. In Matlab, the discrete Fourier transform (DFT) is computed with a fast Fourier transform (FFT) algorithm. F5 F4 66/20 kV, ∆/Y Substation Transformer F3 F2 CB F1 Measuring Point Fault Point Fig. 2 The simulated medium voltage distribution network. 20 Healthy Current (A) 15 Faulted Current (A) 10 Voltage (kV) 5 0 -5 -10 -15 -20 0 4 8 12 16 20 24 28 Fig. 3 The waveforms of the voltage earth mode at the bus and the current earth modes of faulted and healthy feeders, for one period after the fault incidence at 8 ms incidence time, 10 Ω fault resistance and 80% fault distance. 20 15 Healthy Current (A) Faulted Current (A) 10 Voltage (kV) 5 0 -5 At the beginning of the research, a sampling frequency of 100 kHz (10 μs) is used for investigation. From the results, a practical low sampling frequency can be used without affecting the accuracy. This can be investigated from the frequency range of the transient period which is very effective from 200 Hz to 1000 Hz. Hence lower practical sampling frequencies around 10 kHz (100 μs) will be adequate hence the proposed algorithm will be suitable for microprocessor based relaying. The frequency domains for the currents are quite similar but the magnitudes are different; the higher magnitude is of course for the faulted feeder current. The frequency domain output from DFT of the faulted current waveform, presented in Fig. 3, is shown in Fig. 5. For this case, the dominant frequency is 318 Hz which is equivalent to about 3.15 ms period. Within the transient period, of 3.15 ms, the values of the voltage and current earth modes will be calculated, after that the impedance can be calculated as a ratio of the voltage to the current. All these values are at the same transient frequency, which in this case is equal to 318 Hz. As expected, the dominant transient frequency is different from case to another, depending up on the fault conditions, including the fault resistance, incidence angle and the fault distance. The flow of the fault current is presented in Fig. 6. The average value of a sinusoidal waveform over the period is equal to zero; hence it is suggested to use the average value of the waveforms to eliminate the values of higher frequencies contained as possible. For the fundamental transient frequency, the average values will be calculated in the first half of the period to ensure the same polarity, as in Ref. [23], and can be calculated using Eqs. (3)-(5). N -10 The average voltage is V0 -15 -20 243 7 8 9 10 11 12 Fig. 4 The transient period (the first few milliseconds directly after the fault incidence), for the waveforms shown in Fig. 3. v 0, k k 1 N (3) N The average current is I 0 i 0,k k 1 N (4) 244 A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks 14 the earth capacitance and can hence be neglected. The earth capacitance of the network depends on the Magnitude 12 10 types and lengths of the lines connected in the same 8 part of the galvanic connected network. In practice, for 6 radial medium voltage distribution networks, it is the 4 area supplied by one HV/MV substation transformer. Therefore, for faulted feeder, the calculated 2 0 0 300 600 900 1200 1500 1800 Frequency (Hz) 2100 2400 2700 3000 Fig. 5 The frequency domain output from DFT of the faulted current. impedance will be the capacitive impedance of the background network while for healthy feeder, it is the capacitive impedance of the feeder itself, both defined at the dominating transient frequencies. Also, from Healthy Feeder Fig. 6, the calculated capacitance for the faulted feeder will be negative because its direction is opposite to the measurement direction which verifies the 66/20 kV ∆/Y 66 kV Supply directionality technique. In Ref. [5], the technique is based on the transient impedance which highly Faulted Feeder dependends on the transient frequency band, in the Measuring Point (V0, I0) transient period. The proposed algorithm here is based Fault Point on earth capacitance estimation which improves the performance. The earth capacitance of the feeder Fig. 6 The flow of the earth fault currents, during a single-phase to ground fault, through the earth capacitance of the healthy feeders of the network. The average impedance is Z 0 V0 I0 (5) where v0,k is the instantaneous voltage earth mode at sample k, calculated from Eq. (1), i0,k is the instantaneous current earth mode at sample k, calculated from Eq. (2) and N is the number of samples in the window. The rms and average values are related to peak value by constant factors, 0.707 and 0.636 respectively, and then the rms value is related to the average value by a constant factor of 1.111. The impedance is calculated as a ratio of the voltage to the current, hence, no need for other factors to be considered. The fault current is composed of the currents flowing through the earth capacitances of the sound lines (background network) as presented in Fig. 6, and hence the calculated impedance will depend mostly on the earth capacitance of background network. The other impedances of the network components are small compared to those of depends on the type and length. From the dominant transient frequency and calculated transient impedance, the earth capacitance can be calculated from Eq. (6), as follows: Ce 1 2 f tr Z 0 (6) where ftr is the dominant transient frequency that determined the frequency domain output from DFT and Z0 is the average impedance calculated from Eq. (5). For the case shown in Fig. 3, the calculated values are: The voltage Vo= -6.5251 kV The dominant transient frequency ftr = 318.004 Hz The faulted feeder current I0f = 7.9679 A The faulted feeder impedance Z0f = -0.8184 kΩ The faulted feeder capacitance Cef= -0.6113 μF The healthy feeder current I0h = -1.9271 A The healthy feeder impedance Z0h= 3.3840 kΩ The healthy feeder capacitance Ceh= 0.1478 μF It is found that the calculated capacitance is not accurate due to the sources of error in this technique, A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks that are the error from the DFT method which is highly effected by the sampling frequency, the error due to neglecting the network impedances which effect increases with higher frequencies and the error due to the effect of frequencies of higher magnitudes around the dominant frequency, including the discharge transient frequency. To overcome these errors, it is proposed to use the ratio (Kc) of the calculated capacitances (Ce,calc.) to the total network capacitance (Ce,total) as a fault indicator as given by Eq. (7). C K c e , calc. (7) Ce , total The capacitance is directly proportional to the lengths of the feeders which are 41, 35, 30, 33 and 45 km, total length of 184 km, hence we can determine the values of these ratios in healthy and faulty conditions for all feeders as follows: For healthy condition: For feeder (1), Kc1 = 0.22 For feeder (2), Kc2 = 0.19 For feeder (3), Kc3 = 0.16 For feeder (4), Kc4 = 0.18 For feeder (5), Kc5 = 0.25 For faulty condition: For feeder (1), Kc1 = -0.78 For feeder (2), Kc2 = -0.81 For feeder (3), Kc3 = -0.84 For feeder (4), Kc4 = -0.82 For feeder (5), Kc5 = -0.75 For the same feeder, the summation of the ratio magnitudes, or the magnitude of the difference, in healthy and in faulty conditions, is equal to one. It must be noted that the total earth capacitance must be scaled to include the error in the calculated values. From the calculated values, the average scaled value of the total earth capacitance of the network is equal to 0.7818 μF. By this technique, for the case shown in Fig. 3, the ratio of the healthy feeder is equal to 0.1891 and the ratio of the faulted feeder is equal to 0.78187, which is comparable to the calculated values. From the calculated values of the ratios, the average value of the 245 healthy condition is 0.20 and the average value of the faulty condition is -0.80. For compensated networks (Peterson coil/ resonance grounded/earthing networks), the impedance of the compensation coil is relatively high at transient frequencies. Consequently, the transients are about similar in both of unearthed and compensated neutral networks. This is clearly investigated from the simulation data that will be presented in the following section, also the setting of the algorithm will be proposed. 4. Results and Setting Fig. 7 shows the variation of the ratios for healthy and faulty conditions with the fault incidence time, over the power frequency period (0-20 ms), Fig. 8 shows its variation with the fault distance and Fig. 9 shows its variation with the fault resistance. The values of the ratios for healthy and faulty conditions for unearthed network are presented by solid lines and for compensated network are presented by dash lines. The setting value of the ratio will be chosen at the middle between the average ratio values of healthy and faulty conditions to achieve maximum performance of the algorithm operation. These values are 0.2 and -0.8, and then the setting value will be -0.3. The limits of the setting value will be from 0.0 (for network with two feeders) to -0.5 (for network with very high number of feeders), so its value always negative. In this section, some discussion about Figs. 7-9 will be presented. It is found that there is an adequate gap between the healthy and faulty condition, and no overlapping between the two conditions. This gap covers any sources of error in the measurements, that may give incorrect higher or lower ratios, and the proposed algorithm will operate effectively. For the simulated system, the magnitude of the average ratio of the faulty condition is equal to four times the average value of the healthy condition; this related to the number of the feeders and its lengths. At faulted condition we have four healthy feeders and one faulted feeder, hence, we can find the 246 A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks 0.4 the healthy condition will be 0.10, the average value of the faulty condition will be -0.90. By choosing a suitable value of the setting, the performance of the proposed algorithm will not be affected by number of feeders in the network. Healthy condition 0.2 0.0 Ratio -0.2 Setting Value = -0.3 -0.4 -0.6 From the practical point of view the required Faulty condition sampling rate is an important factor. From the results of -0.8 -1.0 different analysis at different frequencies, it shows that 0 2 4 6 8 10 12 14 Incidence time (ms) 16 18 20 Fig. 7 The variation of the ratios for healthy and faulty conditions with the fault incidence time, over the power frequency period (0-20 ms) at 80 Ω fault resistance and 80% fault distance for unearthed (—) and compensated (---) neutral networks. 0.4 Ratio definitely the sensitivity is increased with higher sampling rate. Therefore, the simulations were after using a sub-sampling factor of 16. -0.2 The lower sampling frequency of the proposed Setting Value = -0.3 algorithm indicates the applicability and the suitability -0.4 for microprocessor based relaying. -0.6 Faulty condition 5. Conclusions -0.8 0 10 20 30 40 50 60 70 Fault distance (%) 80 90 100 Fig. 8 The variation of the ratios for healthy and faulty conditions with the fault distance at 8 ms incidence time and 80 Ω fault resistance. A new transient-based algorithm for earth fault detection for unearthed (isolated) and compensated neutral medium voltage networks is proposed. It is based on determining the dominant transient frequency by using DFT method. 0.4 The dominant transient frequency will be used to Healthy condition 0.2 calculate the transient impedance, in the transient 0.0 Ratio selectivity and security of the proposed algorithm, data were analyzed at sampling frequency of 6.25 kHz 0.0 -1.0 analysis is around 6 kHz without affecting much in the performed at sampling frequency of 100 kHz and the Healthy condition 0.2 the minimum sampling frequency that can be used for period, from which the earth capacitance can be -0.2 calculated. The earth capacitance gives a good Setting Value = -0.3 -0.4 indication about the earth fault, as it equals to all the -0.6 background network earth capacitance in faulty condition but equal to line earth capacitance in healthy -0.8 -1.0 Faulty condition 1 10 condition. To overcome the sources of errors in the 100 1000 10000 Fault Resistance (Ω) 100000 1000000 calculation, it is proposed to use the ratio of the Fig. 9 The variation of the ratios for healthy and faulty conditions with the fault resistance at 8 ms incidence time and 80% fault distance. calculated capacitances to the total network factor four. This is for comparable length feeders, as an example if we have ten feeders network and then we will find a factor nine. In this case, the average value of method) has been done to investigate and validate the capacitance as a fault indicator. Extensive simulations by ATP/EMTP program and analysis by Matlab (DFT performance of the proposed algorithm for different fault conditions including different values of incidence A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks time, fault resistance and fault location. There is an adequate gap between the healthy and faulty condition, and no overlapping between the two conditions. This [8] gap can cover any source of errors in the measurements that may give incorrect higher or lower ratios. An average setting value of -0.25 can be used as the default [9] setting value that can be used for different network configuration. The performance of the proposed algorithm is promising and it can be more enhanced by choosing the ratio setting value from 0.0 to -0.5, at the middle between the average ratio values of healthy and faulty conditions, depending on the network configuration. The proposed algorithm is applicable with a lower sampling frequency of 6.25 kHz and hence suitable for microprocessor based relaying. [10] [11] [12] References [1] [2] [3] [4] [5] [6] [7] M. Lehtonen, T. Hakola, Neutral Earthing and Power System Protection, Earthing Solutions and Protective Relaying in Medium Voltage Distribution Networks, Vassa, Finland, 1996. S. Hänninen, M. Lehtonen, T. Hakola, E. Antila, J. Ström, S. Ingman, Characteristics of earth faults in power systems with a compensated or an unearthed neutral, in: 14th International Conference and Exhibition on Electricity Distribution (CIRED 97), Birmingham, UK, 1997. Z.Q. Bo, F. Jiang, Z. Chen, X.Z. Dong, G. Weller, M.A. Redfern, Transient based protection for power transmission systems, in: IEEE Power Engineering Society Winter Meeting, Vol. 3, 2000, pp. 1832-1837. M.F. Abdel-Fattah, M. Lehtonen, EMTP-ATP investigations of earth-fault transient simulation in realistic finnish 21 kV overhead line medium voltage network, in: EEUG Meeting 2009: European EMTP-ATP Conference, Delft, The Netherlands, 2009. M.F. Abdel-Fattah, M. Lehtonen, A novel earth fault detection technique based on extraction of transient superimposed components from the phase currents, in: EEUG Meeting 2009: European EMTP-ATP Conference, Delft, The Netherlands, 2009. M.F. Abdel-Fattah, M. Lehtonen, A probabilistic-based technique using transient rms currents for earth fault detection in medium voltage distribution networks, in: The 10th International Conference on Developments in Power System Protection (DPSP 2010), Manchester, UK, 2010. S. Hänninen, M. Lehtonen, Characteristics of earth faults in electrical distribution networks with high impedance [13] [14] [15] [16] [17] [18] [19] 247 earthing, EPSR (Electric Power Systems Research) 44 (3) (1998) 155-161. S. Hänninen, M. Lehtonen, T. Hakola, Earth faults and related disturbances in distribution networks, in: Proceedings of IEEE PES SM 2001, Vancouver, Canada, 2001 [CD-ROM] p. 6. G. Achleitner, C. Obkircher, L. Fickert, M. Sakulin, C. Raunig, An earth fault distance location algorithm in compensated networks with additional estimation of the fault impedance and fault current, in: Power Quality and Supply Reliability Conference (PQ 2008), 2008, pp. 193-198. S. Hänninen, M. Lehtonen, Method for detection and location of very high resistive earth faults, European Transactions on Electrical Power 9 (5) (1999) 285-291. J.B. Roberts, D. Hou, H. Altuve-Ferrer, Sensitive ground fault detection system for use in compensated electric power distribution networks, United States Patent, No. 6573726 B1 (2003). L.V. Bogdashova, V.E. Kachesov, Parametric on-line fault location methods for distribution MV networks, in: IEEE Power Tech 2005, Russia, 2005, pp. 1-7. E. Bjerkan, T. Venseth, Locating earth-faults in compensated distribution networks by means of fault indicators, in: International Conference in Power System Transients (IPST’05), Montreal, Canada, 2005, pp. 1-6. W. Cong, Z.C. Pan, G. Zheng, J. Hou, F. Zhang, Q.L. Zhang, Study on single phase to ground fault site location method based on injection signal and gsm short message, in: IET 9th International Conference on Developments in Power System Protection (DPSP 2008), 2008, pp. 365-369. S. Hänninen, M. Lehtonen, U. Pulkkinen, A probabilistic method for detection and location of very high resistive earth faults, in: Electric Power Systems Research 54 (3) (2000) 199-206. O. Mäkinen. Method and Apparatus for Identifying Intermittent Earth Fault, World International Property Organization (WIPO), International Publication No. WO 2005/038474 A1, 2005. J. Lorenc, K. Musierowicz, A. Kwapisz, Detection of the intermittent earth faults in compensated MV network, in: IEEE Power Tech 2003 Conference Proceedings, Bologna, Vol. 2, 2003, pp. 1-6. H. Belka, M. Michalik, Application of the continuous wavelet transform to intermittent high impedance ground fault detection in MV networks, in: Eighth IEE International Conference on Developments in Power System Protection, Vol. 2, 2004, pp. 473-476. R. Kaczmarek, W.Y. Huang, P. Bastard, Equivalent circuit application to a phase to ground fault detection in distribution networks without MV voltage measurements, 248 [20] [21] [22] [23] A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks in: Eighth IEE International Conference on Developments in Power System Protection, Vol. 2, 2004, pp. 481-485. W.Y. Huang, R. Kaczmarek, Equivalent circuits for an SLG fault distance evaluation by curve fitting in compensated distribution systems, IEEE Transactions on Power Delivery 23 (2) (2008) 601-608. W.Y. Huang, R. Kaczmarek, SLG fault detection in presence of strong capacitive currents in compensated networks, IEEE Transactions on Power Delivery 22 (4) (2007) 2132-2135. W.Y. Huang, R. Kaczmarek, Symmetric components for transient regime application in MV systems, in: International Conference in Power System Transients (IPST’07), Lyon, France, 2007, pp. 1-4. M.F. Abdel-Fattah, M. Lehtonen, A transient fault detection technique with varying fault detection window [24] [25] [26] [27] [28] [29] of earth modes in unearthed MV systems, in: 6th International Conference on Power Quality and Supply Reliability, (PQ2008), Pärnu, Estonia, 2008, pp. 181-186. F. Ruz, A. Quijano, E. Gómez, DSTRP: A new algorithm for high impedance fault detection in compensated neutral grounded M.V. power systems, European Transactions on Electrical Power (ETEP)13 (1) (2003) 23-28. A.T. Johns, S.K. Salman, Digital Protection for Power Systems, Peter Peregrinus Ltd., London, United Kingdom, 1995. EMTP Home Page: http://www.emtp.org/. L. Prikler, H. Høidalen, ATPDraw User’s Manual, SINTEF Energy Research, TR A4790, 1998. Mathworks Home Page: http://www.mathworks.com/. Prysmian Cables & Systems Finland Home Page: http://www.prysmian.fi/index.html. Appendix The simulated network data: Substation transformer: U1/U2 = 66/20 kV Delta/Star connection S = 10 MVA, x = 10.0% Network: Five 20 kV overhead line feeders Total length = 184 km Feeder 1 length = 41 km Feeder 2 length = 35 km Feeder 3 length = 30 km Feeder 4 length = 33 km Feeder 5 length = 45 km Network positive sequence capacitance: 5.1 μF Network zero sequence capacitance: 9.6 μF Line average positive sequence inductance: 0.9 mH/km Distribution transformers: Five step-down transformers U1/U2 = 20/0.4 kV Delta/Star-earthed connection Loads: Five 0.4 kV loads Total load = 5.5 MW Load 1 rating = 1.5 MW Load 2 rating = 1.5 MW Load 3 rating = 0.5 MW Load 4 rating = 1.5 MW A New Transient Impedance-Based Algorithm for Earth Fault Detection in Medium Voltage Networks Load 5 rating = 0.5 MW Overhead line configuration [29]: MV wooden pole with steel cross-arm Bare conductors ACSR 54/9 Raven Aluminum Conductor Steel Reinforced (ACSR) Current rating (in air at 80 oC) = 280 A Number of wires = 7 (6 Aluminum & 1 Steel) Complete conductor diameter = 10.1 mm Total cross-section area = 62.4 mm2 DC resistance (at 20 oC) = 0.536 /km Conductor spacing = 1.1 m and 8.1 m height 249