BUSSMANN Technical Data 10467 Effective November 2015 SERIES Bussmann series 10 x 38 mm gR cylindrical fuse links Product description Eaton’s Bussmann series 10 x 38 mm cylindrical class gR fuse links are used to protect AC/DC drives and semi conductors. Standard features • Compact design • Compatible with Eaton’s Bussmann series CH modular fuse holders (data sheet number 720147) Technical Data 10467 Bussmann series 10 x 38 mm gR cylindrical fuse links Effective November 2015 Catalogue symbol FWP-(amp)G10F • Fuse link size 10 x 38 mm • Technical data • Rated voltage: 690 V a.c. • Rated current: 4 to 32 A • Breaking capacity: 200 kA a.c. • Class of operation: gR Standards/Approvals • IEC 60269-4 • UL 248-13 Packaging MOQ: 10 • Table 1. Technical Data Catalogue number Rated current (A) Rated voltage (V a.c.) Prearcing I2t Total I2t at 690 V a.c. Power loss at 80% In (W) Power loss at In (W) FWP-4G10F 4 690 5.6 17 1.13 2.05 FWP-6G10F 6 690 16 48 1.56 3 FWP-8G10F 8 690 4.3 38 0.97 1.68 FWP-10G10F 10 690 6.6 59 1.20 2.09 FWP-12G10F 12 690 9.6 84 1.69 2.99 FWP-16G10F 16 690 17 150 2.31 4.27 FWP-20G10F 20 690 23.5 200 2.86 5.35 FWP-25G10F 25 690 60.2 512 2.94 5.52 FWP-32G10F 32 690 94 800 3.82 7.43 Correction curves Peak Arc Voltage UL I2t correction curve K 2300 0.9 0.9 2100 K factor 0.7 0.6 0.5 0.4 KP factor for Watt losses 1 1 UL Max Arc Voltage (peak) 2500 0.8 2A - 6A 1900 In ≥ 8A 1700 1500 1300 1100 0.8 0.7 0.6 0.5 0.4 900 0.3 0.3 700 0.2 0.2 500 100 200 300 400 500 600 Eg [V] RMS value of working votlage 2 Correction curve for Watt losses 1.1 EATON www.eaton.com 700 0.1 200 300 400 500 600 Eg [V] RMS value of working votlage 700 40 50 60 70 80 90 Ib RMS value of load current in [%] of IN 100 Bussmann series 10 x 38 mm gR cylindrical fuse links Technical Data 10467 Effective November 2015 Time-current curve 10000 1000 Pre-arcing Time (s) 100 10 1 0.1 0.01 0.001 1 10 100 1000 Prospective current (A) EATON www.eaton.com 3 Technical Data 10467 Bussmann series 10 x 38 mm gR cylindrical fuse links Effective November 2015 Cut-off characteristics Peak let through current (Ipeak) vs. Prospective Short Circuit Current in SYMM. RMS value, 50Hz / p.f. > 0.15 1000 √2 x Ip Peak CUrrent Ipeak [A] 2.5 x Ip 100 10 10 100 1000 10000 100000 Prospective current Ip (RMS. SYMM) [A] Kt factor Ambient temperature derating curve Kt 1.40 1.30 1.20 1.10 1.00 0.90 0.80 0.70 0.60 0.50 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 Ambient temperature °C Eaton EMEA Headquarters Route de la Longeraie 7 1110 Morges, Switzerland Changes to the products, to the information contained in this document, and to prices are reserved; so are errors and omissions. Only order confirmations and technical documentation by Eaton is binding. Photos and pictures also do not warrant a specific layout or functionality. Their use in whatever form is subject to prior approval by Eaton. The same applies to Trademarks (especially Eaton, Moeller, and Cutler-Hammer). The Terms and Conditions of Eaton apply, as referenced on Eaton Internet pages and Eaton order confirmations. Electrical Sector Eaton Melton road, Burton-on-the-Wolds LE12 5TH, United Kingdom Eaton.eu Eaton.com/bussmannseries © 2015 Eaton All Rights Reserved PDF only Publication No. 10467 November 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.