Global Engineering Guideline OEM Electrical & Control Guideline OEM Electrical and Control Guideline The OEM Electrical and Control Standard provides standard design and implementation details for all General Mills Incorporated (GMI) equipment purchased from original equipment manufacturers (OEMs). It communicates electrical expectations for equipment and systems to both internal and external resources and equipment manufacturers. Table of Contents 1. Summary 2. Contacts 3. General Requirements 4. Definitions 5. Component, Control Panel, and Construction Requirements 6. PLC and HMI Control Equipment and Software 7. Safety 8. Documentation and Deliverables 9. Revision Summaries 1. Summary This document is a unified electrical specification for all OEM equipment purchased for GMI. The document has several purposes: • Provide a guideline and communicates electrical expectations for OEM equipment or systems to both internal and external resources and equipment manufacturers. • Create a common machine specification that maximizes capital efficiencies by conforming, wherever possible, to accepted industry machinery standards. • Affirm GMI’s commitment to the safety and regulatory considerations of electrical systems covered by this document. • Create a future framework for equipment redeployment by making the equipment electrically compatible and similar at all locations. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 1 Global Engineering Guideline OEM Electrical & Control Guideline 2. Contacts Document owner: Daniel Migliori Subject matter experts: Daniel Migliori David Otis Mark Chatterton Mark Daily David Fulmer 763-764-2217 763-764-2217 763-764-2668 763-764-3490 615-849-1504 763-293-3659 3. General Requirements 3.1 Scope This document applies to: • New or remanufactured machinery, and/or multiple machines or systems (unit of operations) that are purchased by GMI. (Remanufacture does not include overhaul, repair, reconditioning, or refurbishment to original specification.) • Other equipment or businesses deemed applicable by GMI. • Equipment intended for US sites. Be aware that some details apply to specific functional areas (processing, utilities, or packaging), and some apply specifically to area classifications (such as outdoors, dusty, wet wash, and dry warehouse). 3.2 Approval Required for Variance Consider all standards described in this document mandatory unless otherwise identified as optional or preferred. Any variance from GMI requirements or preferences requires prior GMI Engineering approval. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 2 Global Engineering Guideline OEM Electrical & Control Guideline Obtain approval from the engineer that issued this document (“GMI engineer”) or has been designated as responsible for project deliverables. GMI will provide and document specific project requirements and approvals. Always inform the GMI engineer of any mandated components or designs that might compromise the equipment’s performance. 3.3 Project-Specific Requirements Additional project-specific requirements will be included in the General Mills purchase order and in GMI Global Engineering document 40_67_00.02 known as Schedule Z1. Schedule Z usually includes: 3.4 • Conformance checklist • Project-specific electrical requirements and equipment • Device code identifiers, if specified • Control and other system requirements • Integration requirements Panel Certification All electrical control panels consisting of eight or more components, whether supplied in a complete enclosure or as an open back plate, must be built, certified, and labeled by a national recognized testing laboratory (NRTL), such as Underwriters Laboratory (UL). An electrical control panel, wiring, equipment or materials for which a NRTL certification does not exist may be approved upon certification by an electrical engineer licensed in the state for which the control panel will be installed. Such a certification will not be valid unless based on a verification of the manufacturer’s component safety and performance test data for the product. Variance from this requires prior GMI Engineering approval. 1 40_67_00.02_Schedule_Z_Electrical_Control_Requirements 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 3 Global Engineering Guideline OEM Electrical & Control Guideline 3.5 Hazard Identification, Risk Assessment, and Safety Requirements The vendor’s Risk Assessment and Safeguarding System for Process Machinery must follow published ANSI, PMMI, ISO, IEC, and EN safety guidelines for process equipment, unless conflicts exist with higher level regulations. 3.6 Electrical and Safety Codes 3.6.1 General All supplied equipment, wiring, and controls shall comply with the current edition of the following electrical and safety codes and specifications at the time of purchase. These codes and specifications are listed in order of precedence. If a conflict exists, apply the code with the higher precedence. • Local regulatory authority having jurisdiction. • NFPA 70 (National Electrical Code) • NFPA 79 (Electrical Standard for Industrial Machinery) • CIS_314_OEM Electrical and Control Standard. (This document) • General Mills Program for Control of Hazardous Energy (See Section 5 in this document) • OSHA 1910.Subpart S - Electrical (1910.301 to 1910.399) • OSHA 1910.147 - The Control of Hazardous Energy (Lockout/Tagout) 3.6.2 Packaging Machinery The following codes apply to packaging machinery only. • ANSI/RIA R15.06 Safety Requirements for Industrial Robots and Robot Systems • ISO/IEC/EN Published guidelines for hazard identification and risk assessment of packaging equipment. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 4 Global Engineering Guideline OEM Electrical & Control Guideline • ANSI/PMMI B155.1 for Packaging Machines 3.6.3 Utility Equipment The following standards apply to utility equipment only. 3.7 • NFPA 85 – Boilers • NFPA 86 – Ovens, Furnaces Other GMI Standards and Guidelines The following GMI Engineering standards and guidelines also apply. • CIS_301_Electric Motor Design Standard • CIS_302_Variable Frequency Drive Design Standard • CIS_303_Servo_Drive_Design_Standard • CIS_304_Safety_Controls_Standard • CIS_308_Portable Cord and Connector Standard • CIS_314_OEM Electrical and Control Standard (this document) • CIS_401_ControlLogix Programming Guidelines • CIS_402_Wonderware_Framework • CIS_403_HMI Application Standard • CIS_409_ControlLogix Configuration Guidelines 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 5 Global Engineering Guideline OEM Electrical & Control Guideline 4. Definitions Term Definition HMI (Human Machine Interface) Computer-based devices that communicate to the processor through a network or over the computer backplane. Sometimes called Operator Interface Terminal (OIT). LOTO (Lockout/Tagout) The safety practice of locking out equipment with a padlock and tag to render a piece of equipment safe at rest. Each plant has a specific, detailed policy that meets OSHA requirements. MQIS Manufacturing Quality Information System. MQIS is GMI’s proprietary MES layer of information systems. It includes various computer- and network-based modules for processing and storing plant floor manufacturing information. NEC National Electrical Code (NFPA-70) Qualified person General Mills employees or contractors who have been trained in electrical safety. Personnel must also possess the correct tools and PPE (personnel protection equipment) approved for the voltage levels and arc flash hazard. (NFPA 70E) Schedule Z A companion MS Excel file to this document. Schedule Z is found in GMI Global Engineering document 40_67_00.02 and contains a checklist to ensure detailed compliance with this standard. Additionally, Schedule Z contains specific requirements for the designated plant, project, or machine. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 6 Global Engineering Guideline OEM Electrical & Control Guideline 5. Component, Control Panel, and Construction Requirements 5.1 Products and Materials 5.1.1 Area Classification Use the following table to determine minimum panel construction and minimum rating for individual components on the equipment. Area Classification Packaging Process & Utilities Dry—warehouse NEMA 12 (IP 54) Painted white epoxy, match equipment, or STEELIT NEMA 12 (IP 54) Painted white epoxy or match equipment Dry clean, dusty (possible wet splash) NEMA 12 (IP 54) Painted white epoxy, match equipment, or STEELIT NEMA 12 (IP 54) Painted white epoxy or match equipment Dry dusty with possible wet wipe only NEMA 12 (IP 65) Stainless steel NEMA 12 (IP 65) Stainless steel Wet wash NEMA 4x (IP 66) Stainless steel. NEMA 4x (IP 66, IP67, IP69K) Stainless steel. Outdoors Not applicable NEMA 3, 3R, (IP 33) 4 or 4X (IP 66). 5.1.2 Preferred Components Preferred electrical components are listed in Schedule Z. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 7 Global Engineering Guideline OEM Electrical & Control Guideline 5.1.3 Device Selection For equipment purchased for facilities in North America, use only devices manufactured in North America or from manufacturers with a substantial presence in North America, including substantial North American stock. 5.1.4 Disallowed Materials Glass, mercury, wood, or asbestos shall not be used for any part of the machine, including panels. Additionally, no material considered harmful for food contact shall be permitted over or in the vicinity of an open food area. Any variance, such as glass photoelectric devices, requires prior GMI Engineering approval. Exceptions: • GMI glass, fluorescent lighting bulbs in panels protected by a shatterproof plastic lens shall be permitted. • Small, glass fuses shall be permitted. 5.1.5 Heat-ups Where designated, equipment and electrical components must withstand, in a non-powered state, occasional system heat-ups to a temperature of 150 degrees Fahrenheit for a 24-hour period. 5.2 Device Labels 5.2.1 Component Labels Each component in the panel (such as terminal blocks and relays) as well as each component on the machine (such as motors, solenoids, and photoeyes) shall have an identification label. Provide white with black letter, plastic laminate tags with a minimum 1/8-inch letter height. Tags inside the panel may be attached with an adhesive and tags on the machine components shall be attached to the machine frame mechanically or with an adhesive. It is preferred that external machine component device labels be metal detectable. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 8 Global Engineering Guideline OEM Electrical & Control Guideline 5.2.2 Device Labels All devices shall be labeled. The label shall include the device’s electrical schematic identifier (e.g. XV13), common name, and I/O address (e.g. 01001) where applicable. Such labels shall not be fastened to a removable panel or directly on the device. The Vendor shall be permitted to use their standard device code identifier system unless otherwise specified in Schedule Z. Some plants may allow labels made with Brady HandiMark material. GMI will specify the labeling method in Schedule Z. 5.3 Power Source 5.3.1 Main Power Source The main power supply shall be nominal 480VAC, 3Ph, 60Hz. Alternate voltages require prior GMI Engineering approval. The current and voltage levels shall be indicated in the formal quotation. Power for all devices other than PLCs, HMIs, servo control axis modules, and network devices (see 5.3.2) shall be connected to the load side of the main, lockable disconnect for this power source. 5.3.2 PLC, HMI, PC, Servos Axis Control Module, and Network Devices Power for PLC, HMI, PC, servo axis control modules, and network devices shall be maintained at all times and supplied either from a separate power source to the machine’s main control panel or derived from the line side of the control panel’s 480VAC main supply. The choice as to which option is used will be determined per project. When derived from the line side of the control panel’s 480VAC main supply, this power source shall have its own lockable disconnect. Below is an illustration of an acceptable method for deriving the separate power for the PLC, HMI, PC, servo axis control modules, and network devices from the 480VAC supply. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 9 Global Engineering Guideline OEM Electrical & Control Guideline 5.3.3 Derived Power for Other Voltages Except where allowed in 5.3.2, all other required voltages shall be derived from the main source. Power supplies shall have a capacity of 25 percent over maximum inrush. 5.3.4 Device Voltages 5.3.4.1 Panel devices requiring a power source, such as PLC chassis and HMIs, shall be 120VAC, 60Hz, if available; 24VDC is also acceptable. 5.3.4.2 Motor VFDs and servo amplifiers shall be 480VAC, 3Ph, 60Hz. 5.3.4.3 Field devices requiring a separate power connection from their signal connection shall use 120VAC, 60Hz, if available; 24VDC is also acceptable. 5.3.5 Disconnecting Means 5.3.5.1 Main disconnect 5.3.5.1.1 All electrical control panels greater than 50 Volts shall have a lockable means—suitable as a LOTO point—for 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 10 Global Engineering Guideline OEM Electrical & Control Guideline disconnecting all power to the machine. Control panels with an integral lock and key are not acceptable. It is preferred that auxiliary contacts indicating the status of the disconnect be wired as a PLC input. 5.3.5.1.2 Panel doors shall be mechanically interlocked to the main disconnect and include a defeater requiring only a common electrician’s screwdriver to open the door while the panel is energized. 5.3.5.1.3 For safety and reliability reasons, the mechanical connection from the main disconnect operator/handle to the disconnecting means shall be permanent. Throughthe-door style disconnects shall not be used. Acceptable styles include but are not limited to: • Flange mounted disconnect • Cable operated disconnect • Side mounted disconnect • Remote mounted disconnect 5.3.5.2 Hot glue disconnect. For equipment that includes a hot-glue system, include a separate disconnect for the glue system independent from the main machine. 5.3.5.3 Other subsystem disconnects. Clearly labeled subsystem disconnects shall be considered in situations where subsystem lockout is desired with portions of the machine remaining energized. Plant safety management approval shall be obtained for subsystem disconnects. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 11 Global Engineering Guideline OEM Electrical & Control Guideline 5.3.6 Short Circuit Current Rating (SCCR) Equipment shall be designed and labeled with the SCCR rating. The NEC requires that the SCCR rating of the industrial control panel must meet or exceed the available fault current at the point of application. If the fault current is unknown at the time of purchase, use the table provided below. 460V, 3ø I, amp rating 30 60 100 150 200 300 400 500 600 SCCR, ka 5 10 14 18 22 26 32 34 42 230V, 200V, 3ø, 230V, 115V 1ø I, amp rating SCCR, ka 150 5 200 10 5.3.7 Loss of Power Toleration The machine shall be designed to tolerate a sudden, random loss of power (such as a power failure) at any time without damage to the machine. Recovery procedures from such a power loss shall be provided. 5.4 Designs Requirements for Control and Power Panels 5.4.1 Enclosure Design 5.4.1.1 Panel access. Panels shall be designed to be accessible to qualified personnel only. For panels with voltages greater than 50 volts, a defeater/tool shall be required to allow access. The panel door shall automatically re-latch when the door is closed. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 12 Global Engineering Guideline OEM Electrical & Control Guideline 5.4.1.2 Door locks and latches. GMI prefers a single-handle latch mechanism on each door in accordance with the enclosure rating. Obtain GMI Engineering approval before using cabinet latching systems that have more than one latch and/or requires a tool (i.e. common screwdriver) to open or close. Do NOT fit control panel latches with locks or keys. 5.4.1.3 Panel labeling. A NFPA 79 compliant machine nameplate including the supplier’s name, model and/or serial number, rated volts, number of phases and frequency, full load amps, nominal KVA load, SCCR rating, and electrical diagram number(s) is required. Panels or machines requiring more than one disconnecting means to disconnect all power shall be marked to indicate that more than one disconnecting means is required to de-energize the equipment. Control panels and junction boxes not rated for washdown/hosedown conditions shall be carry a label stating “Warning: No Wash Down.” 5.4.1.4 Finger-safe design. Finger-safe electrical components prevent fingers from easily or inadvertently contacting live parts. Devices rated IP20 are considered finger-safe. Finger-safe components shall be used wherever possible. Exposed, non-finger-safe parts operating at greater than 50 volts shall be covered with clear Lexan labeled “Live Voltage Present.” The Lexan covers shall be removable or hinged to allow access to components when needed. Holes for test probes in compliance with IP20 shall be permitted. 5.4.1.5 Light fixture Panels 14-inches or deeper shall be provided with an LED light fixture inside the panel with a door switch or IR motion sensor so the light fixture will turn off when the panel door is closed. 5.4.1.6 NEC working clearance 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 13 Global Engineering Guideline OEM Electrical & Control Guideline Electrical panels mounted on or near the equipment shall comply with NEC working clearance requirements. Generally, the NEC requires that electrical panels be positioned to provide a safe working space at least 30-inches wide, 78-inches high, and with appropriate frontal clearance based on the in-cabinet voltage. If the voltage in the cabinet is 150 volts or less, the frontal clearance requirement is 36-inches from the front plane of the cabinet to any object. For cabinet voltages greater than 150 Volts, the NEC requires 42-inches from a grounded surface, or 48-inches from the access point of another electrical panel of any voltage. 5.4.1.7 Panel penetration Control panels shall be designed with no top penetration and no penetrations on the upper 1/3 of the sides. This requirement applies to all area classifications. Exception: Panel mounted devices, such as stack lights, may penetrate the upper 1/3 of the sides upon GMI Engineering approval. Top No Enclosure Penetration Top 1/3 or Side Top 1/3 of Side Figure 1: Electrical Panel Penetrations 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 14 Global Engineering Guideline OEM Electrical & Control Guideline 5.4.1.8 Windows in enclosures. Windows in enclosures shall use clear polycarbonate (Lexan) that maintains the rating classification of the enclosure. 5.4.2 Component Mounting Requirements 5.4.2.1 Side and bottom. It is preferred that all components be mounted ONLY on the back panel. Components shall not be mounted on the bottom of the panel or on the lower 1/3 of the sides. 5.4.2.2 Penetration rating. All equipment that penetrates an enclosure shall maintain the classification rating of that enclosure. 5.4.2.3 Terminal strips. All field wiring shall connect to terminal strips. It is preferred that only a single level of terminal strips be used. Use of multi-level terminal strips requires prior GMI Engineering approval. Exception: Special-purpose, sensitive signals (such as thermocouple, servo feedback, and load cells), which must be connected directly to a PLC input card or instrument. 5.4.2.4 Component temperature and spacing Component manufacturers’ recommendations on spacing requirements and operational temperature range shall be followed. The electrical panel shall be designed and built such that the temperature inside the enclosure does not exceed the operating temperatures of the components it contains—typically 40°C under ambient operating conditions of 30°C (85°F). Panels shall not be vented to achieve temperature ratings. If an air conditioner is used, it shall be designed so that outside air does not enter the enclosure. Additionally, air drawn into a heat exchange section shall be filtered with an easily-maintained filter. For systems with air conditioners, a method to prevent condensation from spilling directly onto the floor shall be included 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 15 Global Engineering Guideline OEM Electrical & Control Guideline For systems with panel cooling devices, such as an air conditioner or heat exchanger, a method of de-energizing the cooling device when one or more of the control panel doors are open shall be included. 5.4.2.5 Programming connections All panels with voltages above 50 volts and which contain programmable devices shall be provided with an exterior, 120VAC duplex, GFI receptacle, protected at 5A, and labeled “For computer use only.” If the machine is connected to a plant Ethernet LAN, an Ethernet outlet shall be included. Programming plug receptacles needed to connect to any other required device programming port without opening the panel shall be provided. Only NEMA 4X-rated receptacles shall be used regardless of the panel rating. Refer to Schedule Z for specific plant requirements. 5.4.2.6 Plastic wiring duct. For interior wiring, plastic wiring duct shall be used to maintain neat and workmanlike construction (such as Panduit®). Note that GMI requires special, high-temperature rated material for heat-ups. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 16 Global Engineering Guideline OEM Electrical & Control Guideline 5.4.3 Spare and Space Requirements for Future The following table lists space for future requirements. Variance requires prior GMI Engineering approval. The proposal shall indicate the portion of the space to be populated with spares. Spare and Space Requirements Category 5.5 Main Cabinet(s) Machine Mounted Enclosure Back panel 15 to 30% area 10% Terminal strip 25-40% I/O points 10% PLC I/O 25% spare slots or space 10% Power Components 1 spare space for each similar Starter, VFD or Axis Module GMI Engineer’s discretion Internal Components 5.5.1 FVNR Motor Starter Full-Voltage Non-Reversing (FVNR) starters are the common across-theline starter. Allen Bradley IEC starters with Type II protection shall be used for fixed-speed drives. NEMA type starters shall be accepted with prior GMI Engineering approval. 5.5.2 Variable Frequency Drive Guidelines Refer to CIS_302_Variable Frequency Drive Design Guidelines. Key requirements: • Minimum VFD size is 1HP, 480VAC, 3 Ph. • Power line reactors shall be installed on the line side of ac drives (i.e. PF525) that do not have built-in reactors. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 17 Global Engineering Guideline OEM Electrical & Control Guideline • Configured range of the VFD shall not exceed the turndown specification of the motor, gearbox of other drivetrain components. Note: Typical VFD frequency range is 30Hz to 90Hz. • All VFD applications should utilize the “Safe Torque Off” safety feature of the drives. • Provide full HIM with keypad and display. • Provide VFD parameters documented in the schematics. 5.5.3 Branch Circuit Protection Individual branch circuit protection for all drives and starters shall be provided. Circuit breakers shall be used unless otherwise prohibited. 5.5.4 Control Relays DIN rail-mounted relays shall be used and shall have a means to indicate when the relay is energized. 5.5.5 Solenoid-Operated Pneumatic Valves Solenoid-operated pneumatic valves shall not be installed in the same enclosure as other electrical components unless external exhausts are provided. GMI prefers solenoid-operated pneumatic valves be either free-standing and rated for the area classification OR mounted in a separate, dedicated panel. For panel-mounted valves, a Hoffman Concept® or equivalent NEMA 4X or 12 stainless steel enclosure shall be used. The number of enclosures and valves per enclosure shall be dictated by the overall design, geographic physical location, and concentration of pneumatic devices. The panel shall be permitted to contain a remote I/O rack to support the valves but shall contain no other electronic equipment. Pneumatic tubing from a valve to its end device shall not exceed 10 feet (3m). 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 18 Global Engineering Guideline OEM Electrical & Control Guideline Compressed air requirements (PSI and CFM) for the system shall be documented on the pneumatic schematic as well as labeled on the equipment. 5.5.6 Power-Conditioning Filter A power-conditioning filter (Islatrol® or equivalent) shall be used for all computer-controlled electrical components, such as PLC processors and servo-drive controllers. 5.5.7 LED Requirement Panel indicators—pilot lights, illuminated pushbuttons, etc.—shall be of the LED type. 5.6 PLC I/O 5.6.1 Prewired I/O Cables With prior GMI Engineering approval, GMI will accept 1492 Series prewired cables and interface modules cards with 16 or more point I/O. 5.6.2 Digital Input Modules Digital input components connected to chassis-based I/O systems located inside a control panel and connected to an input module shall be fused with at least one fuse per 16 input points. Digital input components connected to an on-machine I/O system shall have a separate fuse or circuit breaker for each input module or block. In either case, fusing inputs based on sub-groups determined by common location or function is recommended. Variance requires prior GMI Engineering approval. 5.6.3 Digital Output Modules Individually fused outputs shall be used: either fused wiring arms or other output fusing designs as approved by GMI Engineering. Blown fuse indicators shall be provided for all applications. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 19 Global Engineering Guideline OEM Electrical & Control Guideline Digital outputs components connected to an on-machine I/O system shall use a separate fuse or circuit breaker for each output module or block. Exception: GMI permits electronically fused PLC output cards (such as 1756-OB16E and/or Point I/O) provided that the HMI indicates and resets blown fuses. 5.6.4 Digital I/O and Field Device Voltage Requirements Use the following table to determine voltage requirements. Function Process Voltage Level 120VAC or 24VDC Process where time critical 24VDC Packaging 24VDC Safety Circuits 24VDC Utility 120VAC or 24VDC 5.6.5 24VDC Digital I/O Wiring Use the following table to determine module and component wiring requirements. 24 VDC I/O Module Input Output Wiring Field Component Sinking PNP Sourcing 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 20 Global Engineering Guideline OEM Electrical & Control Guideline 5.6.6 Analog I/O Function Signal Typical 100ohm Pt RTD 1756-IR6I,1769-IR6, 1734IR2 Hardy ControlLogix card using C2 HI-1756-WS Frequency 1756-CFM 4—20mA 1756-IF8H,1756-IF16 (Use differential configuration),1769-IF4I, 1734-IR4, Temperature Weight Flow Pressure, Level, Conductivity, Other 5.7 Fieldbus GMI requires review and approval for all fieldbus use. A fieldbus is a control network such as DeviceNet, Ethernet I/P, and CIPMotion that connects the PLC or main processor to remote I/O, drives, and other field devices. 5.8 Wiring Methods 5.8.1 Voltage Separation Conductors shall be grouped and separated by voltage and insulation class throughout the machine (for example, via wiring channels such as Panduit® or rigid conduit). All conductors in a group shall have an insulation voltage rating at least as great as the maximum voltage level of the highest voltage conductor in that group. The following groupings shall be observed: • Nominal 240 and 480 RMS voltage (includes 700VDC) • Nominal 120 RMS voltage (includes 90 and 180VDC) • 50 volt RMS and less (includes 24VDC) 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 21 Global Engineering Guideline OEM Electrical & Control Guideline • TTL and Communications signals 5.8.2 Wire Size For single conductors, stranded copper shall be used. Insulation type and minimum size are specified below. • For panel wiring—18 Gauge TFFN or MTW (MTW is more flexible and easier for the cabinet builder to route and connect). • For field control device wiring—16 Gauge TFFN. • For motor wiring—14 Gauge THHN and larger (sized for amperage). Note: Use of conductors with an insulation class less than the maximum circuit voltage applied to any other conductor within an enclosure is discouraged. Doing so requires grouping and physical separation in accordance with NFPA-79 and sec. 3.8.1 of this document. GMI permits smaller size wires (no smaller than 20 AWG) when using multi-conductor cable provided ampacity and voltage drop considerations are satisfied. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 22 Global Engineering Guideline OEM Electrical & Control Guideline 5.8.3 Wire Colors Use the wire colors as described in the following table (refer to NFPA 79, and IEC). Wire Color Use Green or green with yellow stripes Grounding Conductor Black Ungrounded conductor at line voltage Red Ungrounded AC control conductor at less than line voltage including PLC I/O Blue Ungrounded DC control conductor Orange Ungrounded control circuit conductors that remain energized when the disconnect is off (such as external interlocks) Note: this is a recent NFPA 79 change from yellow White Grounded circuit conductor White w/ blue stripe Grounded (current-carrying) DC circuit conductors White w/ orange stripe to match the ungrounded conductor. Grounded (current-carrying) AC control circuit conductors that remain energized when the disconnect is off (such as external interlocks). Striping and tracer colors Requires prior GMI Engineering approval if different from above. Pre-manufactured wiring systems Requires prior GMI Engineering approval NOTE: For multi-conductor cables, GMI allows deviation from these color requirements, providing that each conductor has its own unique identifier. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 23 Global Engineering Guideline OEM Electrical & Control Guideline 5.8.4 Wire and Terminal Labeling All terminal points and both ends of all wires shall be labeled with machine-printed labels. Hand-written labels shall not be used. For wires, A-B sleeve or Brady wrap-type wire markers shall be used. Refer to CIS_401_ControlLogix Programming Frameworks for the preferred labeling scheme for Logix processors. Other wire numbers are derived from the page and line number or the number of the control schematic drawing. Terminal strip labels shall match the wire number. Wires connecting a field device may include an additional label with the device tag number. All spare wires shall be terminated and labeled as spare. 5.8.5 Shielded cables 5.8.5.1 Analog Signal Cables Analog cables shall be shielded and the shield bonded to ground at the I/O connection end only. The shield shall be trimmed and shrink tubing applied to cover the exposed shield at both ends. 5.8.5.2 VFD Motor Leads Motor lead shields shall be grounded at the motor junction box and on the VFD ground terminal strip point as per the manufacturer’s recommendation. 5.9 Raceway and Wiring Requirements Raceway is an enclosed channel designed expressly for holding wire and cable. It includes conduit and wireway. It does not include cable tray utilized in the interior of control enclosures. The wiring of devices on the machine to the control panel can be accomplished by various methods: wire and cable in conduit, wires and cables in sealed wireway, exposed cable in wire basket, and exposed cable supported on the machine. The methods selected shall be determined by considering the ruggedness and 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 24 Global Engineering Guideline OEM Electrical & Control Guideline duty for the environment and to meet the GMI sanitary requirements. All raceway materials shall be NRTL approved. See Schedule Z for methods allowed and forbidden for a particular application. 5.9.1 Conduit Rigid conduit is allowed for all applications. Determination of the specific type of conduit (aluminum, galvanized steel, PVC-coated) shall be based on the application or plant requirements. Electrical metallic tubing (EMT) shall not be used. GMI requires sanitary construction for all conduit and supports. Acceptable methods of conduit support include Mineralac® clamps with spacers and inverted angle with U-bolts. GMI prohibits the use of allthread threaded rod and Unistrut®. 5.9.2 Wireway Wireway or troughs require prior GMI Engineering approval. Typically, GMI only accepts wireway when installing several multi-conductor preterminated cables (such as servo motor cables). Use Hoffman® or an approved equivalent is preferred. GMI prefers that the wireway be rotated 45 degrees so there are no flat top surfaces. The wireway must maintain separation of conductors by voltage and insulation class. The wireway must have the access door mounted so that it opens upward with the hinge at the highest part of the enclosure. 5.9.3 Flexible Connections GMI permits flexible equipment connections only as follows. • Liquidtight Flexible Metal Conduit (LFMC) or Liquidtight Flexible Nonmetallic Conduit (LFNC) o A properly sized equipment grounding conductor wire shall be run with the phase conductors and used to ground metallic parts of the equipment. o Flexible conduit length shall not exceed 36 inches. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 25 Global Engineering Guideline OEM Electrical & Control Guideline • Power & Control Tray Cable (TC-ER) • SO or other flexible cord/cable listed in National Electrical Code Article 400 is permitted only in the following cases: o Noise or vibration cannot be abated using flexible conduit. o The connection is made to a moving part. o The motor is interchanged frequently—portable equipment or equipment that must be frequently interchanged for reasons other than breakdown. o On OEM equipment in accordance with Chapter 13 of NFPA-79. 5.9.4 Exposed Cable Exposed cable shall have a jacket rated for the application and environment. Unsupported exposed cable shall not exceed 36 inches. 5.9.4.1 Wire Basket Construction Where exposed cable is permitted, cables shall be rated as Power & Control Tray Cable (TC-ER) and spaced with a minimum of ¼ inch between cables and equipment framework. Wire basket construction shall be permitted in order to achieve this spacing. When using wire basket, cables are shall be secured with metal-impregnated wire ties every 16 inches to 2 feet. 5.9.4.2 Quick Disconnect Connectors GMI prefers quick disconnect connectors (such as Brad Harrison type) for device connections when exposed cable (SO type) is used. Any modular or quick-disconnect connectors on all field devices shall be mounted facing down or otherwise positioned to avoid collecting water or dust. In wet locations, connectors shall have a rating of IP69K. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 26 Global Engineering Guideline OEM Electrical & Control Guideline 5.9.4.3 Plug Connections Supplying Electric Power For plug connections, load-breaking receptacles shall be used for voltages greater than 50V AC or DC. 5.9.4.4 Long Cords Long cords needed for portable equipment require GMI engineering approval. See CIS_308_Portable Cord and Connector Standard for additional information. 5.9.5 Cable and Raceway Routing Routing cable or raceways over open product areas shall not be permitted. 5.10 Wire Ties Only metal impregnated or metal wire ties are permitted, with the exception of inside control panels and where the potential for open product does not exist. 5.11 Motors Guidelines Refer to CIS_301_Electric Motor Design Guidelines Key requirements: • NEMA Frame, 480VAC, Efficiency > 85.5% • Motors driven with inverters shall meet the requirements of NEMA MG1 (Motors & Generators) part 31.4.4.2. 5.11.1 Field Disconnect All induction and servo motors shall have a local, lockable field disconnect close to the motor and in conformance to GMI LOTO requirements. The field disconnect shall include an auxiliary contact that provides an input to the PLC. It is preferred that the lockable field disconnect be within 3 ft. of the device and within line of sight. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 27 Global Engineering Guideline OEM Electrical & Control Guideline Exception: With prior GMI Engineering approval, a motor within the safety-guarded envelope of a machine does not require an individual disconnect, if the motor is an integral part of the machine’s operation and the main disconnect for the machine satisfies the requirement for locking out the equipment. 5.12 Servo Motion Refer to CIS_303_Servo_Drive_Design_Guidelines. Key requirements: • Allen Bradley Kinetix Motion Control or Bosch Rexroth Motion control (req. approval) • Servo system 480VAC 3Ph • Servo motors sized with Motion Analyzer software. • Each axis homing to a switch or a hard stop, where applicable. • Homing initiated from HMI, where applicable. • Servo diagnostics displayed on HMI. • Absolute multi-turn encoders are preferred. • High-flex servo cables on axis requiring cable movement. • Use servo cables of the proper length to minimize excess and eliminate coiling. • Disconnects are not permitted on the load side of the drive. • Wet Wash rated motors for use in wet wash areas (e.g. Allen Bradley Food Grade MPF motors). 5.13 Field Devices 5.13.1 Quick disconnect Use field devices with quick disconnect connection. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 28 Global Engineering Guideline OEM Electrical & Control Guideline 5.13.2 Device Area Classification Rating Select field devices for the area classification specified in the request for proposal. 5.13.3 Solid State 24V DC Sensors 24VDC sensors must be PNP to supply a signal to a sinking input card. 6. PLC and HMI Control Equipment and Software 6.1 Processor 6.1.1 Rockwell PLC Systems Rockwell ControlLogix or CompactLogix processor shall be used for new machines. Use of non-Rockwell PLC machine controllers requires approval by the Engineering Global Technical Services (GTS) Director. Refer to CIS_409_ControlLogix Configuration Guidelines for more information. 6.2 Control Network 6.2.1 PLC LAN Connection All programmable controllers shall have a dedicated Ethernet connection to the GMI PLC LAN. Programmable controllers with a single Ethernet port (i.e. CompactLogix) will require a NAT (Network Address Translation) device to provide its connection to the PLC LAN (figure 4.2). Only the programmable controller or a single Ethernet module used by the controller shall be connected directly to the PLC LAN. These components shall not be connected to the PLC LAN: VFDs, HMIs, instrumentation, vision systems, scanners, etc. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 29 Global Engineering Guideline OEM Electrical & Control Guideline 6.2.2 HMI LAN Connection HMI terminals requiring connection to GMI’s network shall be connected to the plant’s HMI LAN. Such connections may be made directly to a GMI HMI LAN switch or indirectly through an OEM-provided switch. (See Figures 4.3A, B, or C below). The Ethernet addresses for HMI terminals connected to the GMI HMI LAN shall be supplied by General Mills. 6.2.3 Fieldbus Network HMI terminals not requiring connection to GMI’s network may be connected to the Fieldbus network. Ethernet I/P is the standard Fieldbus network, and all advanced components shall be connected to this network (i.e. servos, VFD, flow meters, scanners, etc.). Fieldbus Ethernet addressing must remain separate from all other networks. Use addresses 10.10.xx.xx or 192.168.1.X for this segment (figures 4.3A, B, or C). Other industrial control networks, like DeviceNet and ControlNet, require GMI approval. 6.2.4 Fieldbus Network Topologies Star and Ring topologies are acceptable. Ring topologies can be a mixture of technologies providing there are not more than 25 devices on a segment. It is preferred to have the motion control device level ring on a dedicated segment (figure 4.3C). Linear topology is only acceptable on motion control systems with 4 or less axes (figure 4.3B). 6.2.5 Motion Control Networks Ethernet I/P CIP motion is the preferred motion control network. The Logix Time Synchronization or CIP Sync GrandMaster clock owner shall be contained within the motion control domain. The network design shall have a non-PTP (Precision Time Protocol) device at the network connection points to other networks. Non-PTP devices could be a 1783E-Tap, 9300-ENA (NAT) or non-PTP switch. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 30 Global Engineering Guideline OEM Electrical & Control Guideline 6.3 Fieldbus Ethernet Switches Ethernet switches that connect directly to the PLC LAN shall be of the managed type. A switch separated from the PLC LAN by a NAT device shall be permitted to be a non-managed type. Unmanaged switches shall be limited to 8 ports or less. Reference Schedule Z for the preferred managed and unmanaged switch selection. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 31 Global Engineering Guideline OEM Electrical & Control Guideline Figure 4.3A Controls Ethernet 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 32 Global Engineering Guideline OEM Electrical & Control Guideline Figure 4.3B Controls Ethernet 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 33 Global Engineering Guideline OEM Electrical & Control Guideline Figure 4.3C Controls Ethernet 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 34 Global Engineering Guideline OEM Electrical & Control Guideline 6.4 Software and Software Documentation 6.4.1 Ownership All software developed for GMI becomes the property of GMI upon completion of the project unless stated otherwise in the GMI-issued purchase order. 6.4.2 Protected Code Password protected or “locked down" source code that is unavailable to GMI shall not be used. If the vendor refuses and is not willing to provide unprotected code, then the OEM Vendor shall agree to provide lifetime support for the protected code at their cost. 6.5 Allen-Bradley PLC Documentation For ControlLogix applications, refer to CIS_401_ControlLogix Programming Frameworks. 6.5.1 Language Relay ladder logic shall be the language used exclusively. Structured text and function block programming shall not be. Deviations must be approved by a GMI Engineer. 6.6 Program Documentation Use the following guidelines to ensure that the PLC and all programmable devices are correctly documented: 6.6.1 Documented Source Code Fully documented source code for all programmable systems shall be provided in electronic format. All development software programming packages and support licenses shall be provided. (Supplying the software license is optional if the software already exists at the site.) 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 35 Global Engineering Guideline OEM Electrical & Control Guideline Back-up and restore capability shall be provided. Step-by-step instructions for backing up and restoring non-Rockwell software controlled equipment shall be provided. 6.6.2 Documentation for PLC Ladder Logic 6.6.2.1 Rung Comments GMI requires extensive use of rung comments and device descriptors. At a minimum, a rung comment shall appear at the beginning of each subroutine and each sub-grouping within a subroutine explaining the control strategy for that program. Uncommon logic schemes also require explanatory rung comments. 6.6.2.2 Device Descriptors All I/O device descriptors shall be labeled with a common name and a tag name included in the descriptor fields. The identical description shall be used on the control schematics, device location drawings, and labels on the devices. 6.6.3 ControlLogix Documentation For Logix PLC applications, refer to CIS_401_ControlLogix Programming Frameworks. 6.7 Operator Controls The location, height, and identity of all operator controls (HMI and manual) shall be provided in the vendor’s proposals. Plan to discuss these at machine design review meetings. 6.7.1 Safety Controls Refer to Section 7 (Safety) for detailed requirements on safety-related controls including emergency stops, secondary safety devices, column lights, and audible alarms. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 36 Global Engineering Guideline OEM Electrical & Control Guideline 6.7.2 Human Machine Interface This section covers HMI hardware that is software-based and includes a graphical screen. 6.7.2.1 HMI Screen Height The centerline of the screen shall be approximately 60-inches (152 cm) from the floor. 6.7.2.2 HMI Selection GMI prefers Wonderware as the HMI software if the following conditions apply: • Wonderware is already developed and offered as a standard option. • Wonderware is needed for high level system control, as required by the plant or project. Stand-alone Wonderware applications shall use remote tag referencing. For all other applications, Rockwell HMIs with a 7” minimum screen size shall be used. The specific sizes shall be dictated by the vendor, machine, or project requirements. 6.7.2.3 HMI Communication Network GMI prefers Ethernet for the communication network. 6.7.2.4 Functionality of a Graphical HMI Indicate on the Schedule Z which of the following features is included in the proposal: • Status of key machine elements • Guard door, emergency stop, and safety circuit status • Useful statistics for operator 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 37 Global Engineering Guideline OEM Electrical & Control Guideline • Abnormal machine conditions (including alarms) • Software adjustment parameters • Helpful diagnostics • Setup selection (recipes) 6.7.2.5 Keyboard, Touch screen Keypad, Size Indicate on the Schedule Z which of the following features is included in the proposal: • Terminal type: touch, keypad or both • Optional keyboard: keyboard, keyboard with pointing device or none. • Screen size • Communication method 6.7.2.6 HMI Program Style HMI software shall be written so that all machine logic and variables are contained in the PLC processor memory and do not reside in the HMI. Specifically, screen objects such as retained objects or initiated variables shall not reside within the HMI software. An HMI shall be able to shut down and restart while the machine is running without affecting the machine’s behavior. Likewise, an HMI shall be able to receive a new version of software while the machine is running without the machine’s behavior being affected. 6.7.2.7 HMI Standards Documents Refer to the following documents for additional information on HMI configuration and Wonderware standards. • CIS_402_Wonderware_Framework • CIS_403_HMI Application Standard 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 38 Global Engineering Guideline OEM Electrical & Control Guideline 6.7.2.8 Standard Colors The following table lists common machine functions and GMI’s standard colors for HMI screens. Deviations must be pre-approved by a GMI Engineer. Color Function Red Shutdown alarms Amber System alarms (up or down stream) Blue Material shortages Green Normal or Start White Reset White Text Operator prompts Yellow Text Dynamic data Green Text Static information Cyan Text Display headings Magenta Text Communication messages 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 39 Global Engineering Guideline OEM Electrical & Control Guideline 6.7.3 Illuminated (LED) Devices, including Column Lights If remote indicating lights are required, use full-size industrial components, such as the Allen Bradley Bulletin 855T series for column lights and 800T for pilot lights. All lighting elements must be LED. The standard GMI light colors are: Color Function Red Emergency stop or system alarm condition Amber Warning condition (up or down stream) Blue Material shortages Green Normal or Start White Safety/Reset indicator The order of the column lights from top to bottom shall be red, amber, blue and green. GMI discourages flashing indicators. Flashing indicators shall only be used to: • Attract attention • Requires immediate action • Indicate a discrepancy between command and the actual states • Indicate a change in process (flashing during transition) 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 40 Global Engineering Guideline OEM Electrical & Control Guideline 6.7.4 Hard-Wired Manual Controls Stop, cycle stop, emergency stop, reset, and start control devices shall be hardwired (NOT HMI or key controlled). Deviations shall be preapproved by a GMI Engineer. Use the following information to configure hard-wired control switches: • STOP Buttons—Use red, extended head pushbuttons with momentary contacts. Choose between a STOP or CYCLE STOP depending on the most desirable control strategy. Include both if the control strategy warrants it. • EMERGENCY STOP Buttons—Use a safety-rated, lighted (LED), red, mushroom-head, maintained pushbutton with a yellow background. Section 7 (Safety). • RESET Buttons—Use white, flush-head pushbuttons with momentary contacts. Reset buttons are required to reset all primary (emergency stop) and secondary (guards) safety devices. • START Buttons—Use green, flush-head pushbuttons with momentary contacts. A start button is any device that initiates machine motion when actuated. • SAFETY Indicator Light—Use a white panel light (LED) to indicate that the safety circuit is energized. • Combination devices—The above requirements can be satisfied by: • o Combining the START and the RESET button or; o Combining the RESET button with the SAFETY indicator light. For all other hard-wired pushbuttons, use black, flush-head push buttons with momentary contacts. Label the pushbuttons appropriately to clearly identify the button’s function. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 41 Global Engineering Guideline OEM Electrical & Control Guideline 6.8 Control Integration Requirements 6.8.1 Standard Integration Requirements All integration requirements listed in Schedule Z shall be met. These typically include: • Upstream Shutdown Interlock Output — Hardwired, dry, normallyopen output contact (closed permissive to run upstream equipment) or a software Ethernet I/P interlock. • Downstream Run Permissive Input — Hardwired, dry, normally-open contact from downstream equipment (closed permissive to run this equipment) or a software Ethernet I/P interlock. A protected method (password or location for hardwired jumper) shall be provided to bypass the Downstream Run Permissive for test purposes. • Machine speed signal — Analog signal representing a rate (such as feet per minute or other unit per time) over software Ethernet I/P. • Emergency Stop — Means shall be included to integrate emergency stop functions to support equipment furnished by others, including emergency stop interlock circuit(s) and status monitoring. See Section 7 (Safety). • Emergency Stop for Others — Emergency stop logic interlocks (safety circuit connection points and PLC inputs) for primary safety devices furnished by others shall be provided. See Section 7 (Safety). • Emergency Stop by Others — Means to allow an emergency stop zone furnished by others to control your equipment shall be provided. See Section 7 (Safety). Exception: Communication of the non-safety signals shall be permitted on a peer-to-peer network as stipulated by the GMI engineer. Loss-ofcommunication logic shall be included when using networks. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 42 Global Engineering Guideline OEM Electrical & Control Guideline 6.8.2 Sub-Unit Integration Additional integration requirements for sub-units typically include: • Feeders • Level sensors • Metal Detector • Checkweigher • Date Coder • Motor Aux Contact (e.g. conveyors) • Line-Backup Sensor • Other Unit Operations Sub-units shall be integrated with the main unit so the sub-unit stops, starts, faults, and safely stops with the parent equipment. In addition, controls shall be configured so the main unit’s HMI contains all operator interaction (such as parameter adjustment and fault status) for the subunit. 6.9 Software Features 6.9.1 Interlock For machines that have downstream and upstream interlocks, a means for the operator to operate the machine with the interlocks overridden shall be provided. Such an interlock override feature facilitates maintenance, sanitation, and product changeover. 6.9.2 Cleanout Mode For machines that have partial product or packages retained in the machine, operator control features to easily clean out products and packages shall be provided. Such a cleanout feature facilitates changeover and production shutdown. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 43 Global Engineering Guideline OEM Electrical & Control Guideline 6.9.3 Product Changeover Mode For machines that require product changeover, features that allow for quick and safe changeover procedures shall be provided. 6.9.4 Sanitation Mode For machines requiring sanitation, operator controls and operational modes to facilitate safe, thorough, and rapid sanitation of the equipment shall be included. 6.9.5 RMT Information Reliability Metrics Tracking is GMI’s proprietary module of MQIS that tracks downtime for the production lines. The module tracks downtime for each unit operation by cause. In addition, it measures time spent in each major state, and counts the units produced or rejected. Exclusive downtime assigns blame for each downtime event to the machine causing the downtime. Additionally if a machine only accounts for a fraction of the production, it assigns downtime proportionately. This data is used to calculate the mean time to recover (MTTR) and mean time to failure (MTBF) and system utilization (SU) for the machine and for the combined system according to a companywide, unified methodology. For machines designated as principal units of operation contributing to the production line’s productivity, logic and data structures to indicate the machine’s status as Running, Blocked, Starved, or Stopped condition shall be provided along with the fault condition(s) that caused the machine to stop. A separate proposal with specific requirements may be requested for systems requiring this feature. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 44 Global Engineering Guideline OEM Electrical & Control Guideline 7. Safety Safety controls may be implemented if reasonable means to design a hazard out of the machine are inadequate. Safety controls are required to monitor the access of a hazard area. Safety controls are not a replacement for Lockout/Tagout. Refer to CIS_304_Safety and Emergency Stop Circuit Design Guidelines for more details. 7.1 Safety Design A safety risk assessment shall be completed on each machine. A taskbased risk assessment is preferred over a hazard-based risk assessment. Each task performed by an operator, sanitation worker, or maintenance person shall be evaluated for hazards. The preferred risk assessment standard is ANSI B11.TR3, Risk Assessment and Safeguarding of Machinery Package. If a safety risk assessment cannot be completed prior to the design of the control safety system, a default ISO 13849-1 PLd (Performance Level) shall be used for the safety design. 7.1.1 Safety Zones Safety equipment in machines zones shall be designed to bring all hazardous motion to a safe state within the zone. A machine might have one or several zones. Equipment in upstream safety zones shall automatically perform a cycle stop. Safety zones shall be designed so operators can clearly and intuitively understand which controls apply to each zone and can easily understand equipment behavior in every situation. 7.1.2 Circuit Approval Required. Safety circuits shall be submitted to GMI Engineering for approval 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 45 Global Engineering Guideline OEM Electrical & Control Guideline 7.1.3 Safety Interlock Sensors Safety interlock sensors shall be used to safeguard any safety barrier that provides easy access to a hazardous area. Only safety-rated sensors with TÜV safety certification (or equivalent) shall be used. If a guard is permanently mounted or requires a tool to access, no safety interlock sensor is required. In cases where hazardous motion may be present after the activation of the safety circuit, latching-type devices designed so the latch is only released when the machine is in a safe state shall be used. Delay through a safety monitoring relay, a zero motion switch, or other means consistent with the ISO 13949-1 PLd safety rating shall be used. Safety interlock sensors that are most suitable for the need of the application shall be selected. GMI prefers Rockwell Automation’s safety sensors unless an application requires special form factors or functionality. Safety interlock sensors requiring separate interfacing devices or converters shall be selected. 7.1.3.1 Safety Device Monitoring The status of every safety input device shall be communicated to the PLC and displayed on the operator interface. 7.1.4 Safety Controllers Safety controllers shall be selected based upon the complexity of the safety needs. For less complex safety systems (10 or fewer safety input devices and one safety zone), a general safety controller (see 7.1.3.1) shall be permitted. For complex safety applications (>10 input devices or multiple safety zones), an advanced safety controller (see 7.1.3.2) shall be used. All safety controllers shall be a product of Rockwell Automation. Refer to CIS_304_Safety_Controls_Design_Standard for more safety controller specification and safety circuit examples. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 46 Global Engineering Guideline OEM Electrical & Control Guideline 7.1.4.1 General Safety Controllers • A Rockwell GuardMaster Safety Relay shall be permitted in single zone applications with 10 or fewer safety input devices. • Utilize as many safety outputs as required. • Status of each channel of every safety device shall be communicated via Ethernet I/P to the PLC for display on the operation interface. 7.1.4.2 Advanced Safety Controllers • Programmable safety controllers shall be use for applications with more than 10 safety devices or more than one safety zone. • Programmable safety controllers shall be Rockwell GuardLogix. • Safety programming shall be limited to the safety function blocks available in the GuardLogix Safety controller. • Status of each channel of each safety device or component shall be displayed on the operator interface. • GuardLogix processors shall have a Safety Signature generated, and the safety processor must be locked prior to utilization of any safety function of a system. Safety signatures shall be recorded in the GMI Safety Signature Vault web portal. 7.1.5 Safety Power Outputs Safety output devices shall be utilized whenever a safety function requires power be removed from a motor or compressed air removed from a pneumatic system. All safety power devices shall have a TÜV safety certification (or equivalent). Power and pneumatic components participating in safety functions shall be selected with safety features integrated into the components themselves when available (i.e. safetorque off). 7.2 Safety Override and Bypassing 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 47 Global Engineering Guideline OEM Electrical & Control Guideline Overriding, bypassing or defeating a safety system is prohibited. 7.3 Heat Seal Systems With pre-approval by a GMI engineer, machine heat seal systems shall be permitted to be left unaffected by safety circuits. 7.4 Startup Warning Audible Alarm Sequence If a machine has hazards that are guarded using doors that can be opened without a tool or guards that can be removed without a tool, a startup warning sequence shall be implemented: • Operator pushes the start button for a specified prestart time (generally a minimum of three seconds, per plant practice) during which a startup warning alarm sounds. This gives other workers in the area notification that the machine is about to start. • If the operator releases the start button before the end of the prestart period, the equipment will not start and the prestart timer will reset. • If the operator keeps the start button pushed for the entire prestart time, the machine starts, and the operator can release the start button. The start button shall be permitted to be used for both reset and start as long as the safety circuit resets the safety devices and sounds the startup warning alarm. Exception: For equipment that is integrated as a subsystem to a larger group, it shall be permitted that start of the larger group provides the start, audible warning alarm, and delay (as well as emergency stop and normal stop functions). If the subsystem equipment has a start function independent of the start for the larger group, this exception does not apply for the independent start. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 48 Global Engineering Guideline OEM Electrical & Control Guideline 7.5 Minor Servicing Exception (MSE) Minor tasks which take place during normal production that are routine, repetitive, and integral to the use of the equipment for production shall be permitted to use the MSE (Minor Servicing Exception) instead of a full Lockout Tagout provided the task meets the requirements of the MSE Decision Tree listed below. In general, minor servicing includes simple adjustments or inspections that enable the equipment to continue to make good product, clearing jams involving the product or packaging materials, and cleaning product/material build-up during production. Minor servicing tasks would commonly be completed by only one employee and would not require component removal or equipment disassembly. 7.5.1 MSE Decision Tree If a task is MSE eligible according to the MSE decision tree, control safeties must be installed to protect the operator during the MSE task. The performance level (PL) of these safeties shall be determined using the MSE Performance Level Grid listed below. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 49 Global Engineering Guideline OEM Electrical & Control Guideline Are all the following true about the task? It is minor servicing. (see definitions) It will occur during normal production. (see definitions) It is routine. (see definitions) It is repetitive.”(see definitions) It is integral to normal production. (see definitions) No Yes Are any of the following true about the task? Fastened-in-place guards will be removed. Tools will be used to add or replace components. There is potential to accidentally trigger a hazardous machine motion or action. There is potential contact with a moving part. Workers will be exposed to live electrical parts operating at 50 volts or higher. Yes No Are all of the following true? The only source of energy is a single, cord & plug connected electrical cord. No stored or residual energy is present after unplugging the equipment The employee can maintain exclusive control of the electrical plug for the duration of the task. (see definitions) No Yes Complete a DesignSafe risk assessment for the task. Does the risk assessment place the task in one of the red boxes on the Risk Assessment Grid on the back of this sheet? MSE allowed under single electrical energy source rules. The employee will maintain exclusive control of the electrical plug for the duration of the task. Yes No MSE allowed. All equipment: Worker can maintain exclusive control of at least one of the safety devices while conducting the task. (see definitions) There is an equipment startup signaling system and startup delay OR multiple startup steps sufficient to alert employees in time to vacate areas of hazard. (see definitions) MSE not allowed. Use LOTO. New equipment: Electrical/controls safety components & circuits meet the Performance Level required by the result of the DesignSafe risk assessment. (see MSE Performance Level grid) If the Performance Level of the controls design is less than PL-d, a maintained e-stop button is provided. Legacy equipment: Use of a maintained e-stop button plus an additional safety measure (e-stop+1) is allowed. Except: Convert to LOTO if the assessed risk is catastrophic and likely or very likely. If upgrades are performed, bring MSE safeties up to current standards (above). 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 50 Global Engineering Guideline OEM Electrical & Control Guideline MSE Performance Level Grid 7.5.2 MSE (Minor Servicing Exception) Procedure Below is listed the required procedure to perform tasks eligible for the minor servicing exception (as determined using the MSE decision tree) and for which control safeties have been installed that need the performance level (PL) specified in the MSE Performance Level Grid: 1. Actuate the cycle or system stop switch, if so equipped. 2. Verify that the machine has come to a complete stop. 3. Access the safeguarded area, by opening a guard door, breaking a light-curtain beam or using a tool. 4. Perform the minor servicing or unjam the equipment. 5. When the work is complete, clear all obstructions, remove any tools, and close all guard doors (or reset light curtains). 6. Press the RESET to reset the safety circuits. The SAFETY indicator confirms that the reset is successful. 7. Press and hold the start button for the specified prestart time system enabled. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 51 Global Engineering Guideline OEM Electrical & Control Guideline 8. Documentation and Deliverables 8.1 Documentation Format Both electronic and hard-copy versions of all documentation as specified in the machine purchase order shall be provided. For engineering drawings, both AutoCAD drawing (.dwg) and Adobe Acrobat (.pdf) files shall be provided. A summary list of all the documentation provided shall also be included. 8.2 Approval Documentation Approval documentation, also referred as “shop drawings”, (bill of materials, panel layout, and control schematics) shall be submitted prior to fabrication. Any variance requires prior GMI Engineering approval. 8.3 Text in English Text on drawings and all machine documentation (manuals, drawings, procedures) shall be in English. Variance requires prior GMI Engineering approval. 8.4 Electrical Symbols GMI prefers the use of electrical symbols in accordance with IEEE 315. Other symbols (such as pneumatic and hydraulic) shall follow IEC standards. Variance requires prior GMI Engineering approval. 8.5 Deliverables 8.5.1 Bill of Materials Parts List A parts list that includes functional descriptions, manufacturer’s name, and part number, and quantities for each component shall be provided. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 52 Global Engineering Guideline OEM Electrical & Control Guideline 8.5.2 Recommended Spare Parts List When compiling a recommended spare parts list, it shall be assumed that the equipment will operate 24 hours-per-day and 365 days-per-year. Functional descriptions and OEM ordering information (such as functional descriptions, manufacturer’s name, and part number, and quantities) shall be included. A spare parts list shall be submitted in a specific format to be provided by GMI. The spare parts list shall be submitted 60 days prior to shipment. 8.5.3 Manufacturers’ Literature At least one copy, in both electronic and hard-copy forms, of all relevant literature for all major purchased components shall be provided. 8.5.4 Software and Software Documentation The following software and software documentation shall be provided: • RSLogix programming and documentation in electronic format. • Fully-documented source code for all non-PLC and HMI programmable systems in both electronic and hard-copy formats. • Rockwell HMI programs and documentation in electronic format. • Step-by-step back-up and recovery instructions to restore software for each programmable device. An exception for equipment commonly supported by the plant may be made by the plant engineer. 8.5.5 User and Service Manuals User and service manuals for all equipment to support operator training and ongoing equipment operation and maintenance shall be provided. Service manuals shall include a sequence of operation, recommended preventative maintenance schedule, and troubleshooting guide. User and service manuals shall be provided in both printed and electronic format. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 53 Global Engineering Guideline OEM Electrical & Control Guideline 8.5.6 Field Installation Electrical Drawings A preliminary drawing (labeled “Approved for Bidding”) shall be submitted 60 days prior to shipping that summarizes field electrical installation requirements. The preliminary drawing shall contain conductor and termination counts and enough detail to allow installation contractors to accurately bid the installation. The Vendor shall inform GMI immediately of any significant changes to these drawings once they have been issued. A fully developed field installation drawing (labeled “Approved for Construction”) 30 days prior to shipment shall be submitted. The Approved for Construction drawings shall include; 8.6 • List of disconnect sizes and estimated FLA (Full Load Amps) for each external power source • Details for wiring harnesses for re-termination between shipping splits • Detailed schedules for additional field conduit and wire quantities listed by color and size required for installation • On the summary drawing, sufficient termination details to allow a contractor to accurately bid the installation Software Support after Installation After installation, PLC software will be uploaded to the Plant PLC software server. Manufacturer’s field support personal will then use either a GMI plant terminal to access software through the system or have the client application installed on their PC. Use of non-GMI PCs requires approval by the plant I.S. department. Obtain current requirements and approval from the plant before using. To be approved, PCs require an operating system with current patches and the latest virus protection software. When the PLC is in production, any PC support connections shall be made through a programming port so that the PLC never loses connection to the GMI network. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 54 Global Engineering Guideline OEM Electrical & Control Guideline 8.7 Drawing Requirements The following is a listing of drawing titles for specific functional areas. The drawings can be separate or combined as separate layers of the same drawing. All drawings are required. Variance requires prior GMI Engineering approval. GMI prefers that the OEM vendor use the GMI AutoCAD border. • Drawing Index or Table of Contents—List all drawings and diagrams included in the electrical drawing set. • Legends Page—Include a separate drawing or a legends section on a drawing where symbols are defined. • Equipment Layout and Footprint—Show equipment outline, belt outline, main centerlines, control panels, operator stations, junction boxes, utility connections, door swings, and guard door swings. • Panel Layout Drawings—Show internal and external electrical panel layouts. • Device Location Drawings—Provide for packaging applications. Use the assembly drawing as the background for this drawing. • Electrical Schematic Drawings—Show wiring (including all wire numbers) for all devices. Include wiring diagrams for all controller I/O and safety circuits. • Network Drawings—Show the wiring of any data communication, fieldbus network, or other networks associated with the equipment. • Related diagrams—Where appropriate, provide the following diagrams for reference: block diagram, electronic schematic, lubrication diagram, pneumatic diagram, hydraulic diagram, and coolant or refrigerant diagram. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 55 Global Engineering Guideline OEM Electrical & Control Guideline 9. Revision Summaries Revision Number Revision Date Revision Owner Revision Summary (Brief description of major changes) 0 1 9-Feb-06 5-Sep-08 Jack Janzen Jack Janzen Original Development Minor Error Correction 2 5-Nov-09 Jack Janzen Major Revision and Update 3 20-Mar-15 David Otis 4 25-Sep-15 Mark Chatterton Major Revision and Update • Prohibit thru-the-door disconnects • Renumber from old CIS_314 to MasterFormat numbering scheme; change to document format. 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 56 Global Engineering Guideline OEM Electrical & Control Guideline 9.1 Plant Customization Tracking Enter information in these tables to track revisions to plant customized documents. NOTE: In the Entry column, enter your information between the dashes. The entries automatically update document properties. Document Property Entry Plant Code -XXX- Plant Owner -Enter Name- Plant Revision Number -0.0- Plant Revision Date -xx/xx/xx- Revision Revision Number Date Revision Owner Use the following format for the Plant Revision Number: <Master Revision Number>.<Plant Revision Number> Revision Summary (Brief description of major changes) 0 40_67_00.01_OEM_Electrical_and_Control_Guideline.doc Revised Oct. 2015 57