Liebert TYPE SS Transient Voltage Surge Suppression

Surge Protection
For Business-Critical Continuity™
Liebert TYPE SS Transient Voltage Surge Suppression
Advanced Hybrid Surge Suppression Technology
Approved by Motorola R56 2005 Version, Standards and
Guidelines for Communication Sites — Type 1, Type 2 Devices
Utilizes advanced SAD/MOV array technology for
industry leading transient suppression voltages
Incorporates Liebert’s “state-of-the-art” Interceptor
technology for enhanced safety and performance
coordination of all surge and fuse components
Modular design for flexibility and ease of servicing
160 kA surge current capacity for increased
reliability
Real-time system monitoring
Product performance and safety standards —
UL1283, UL 1449 Second Edition 2005, (effective
Feb. 9, 2007), C22.2 No. 8 Bulletin 516 and NEMA
LS1-1992
Two Different Units Available:
Type 1 Hybrid TVSS — 20 kA of SAD protection and
160 kA of MOV protection
Type 2 MOV only TVSS — 160 kA of MOV protection
Warranty:
Covered 24x7 by Emerson Network Power Service
Business: 10-Years for Parts, 5-Years On-Site Labor
Typical Applications:
Cell Sites
Communication shelters
AC main and distribution panels and load centers
Transmitters
Base Stations
Liebert Corporation
Liebert TYPE SS Transient Voltage Surge Suppression
Surge Current (%)
MOV/SAD Current Sharing – Type 1 Model
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
The Liebert Answer:
MOV Module
SAD Module
0
5000
10000
15000
20000
25000
8/20 µs Surge Current (Amperes)
The Liebert TYPE SS Type I Model
offers a true, coordinated multi-stage
system of suppression. It integrates
the fast response time of the silicon
avalanche diode (SAD) with the highenergy capability of the metal oxide
varistor (MOV) for increased reliability
and performance. This unique circuitry
30000 does not sacrifice the sensitive SAD
module when subjected to a
damaging high-energy transient event.
120/240V and 120/208V
(Please consult factory for additional voltage configurations)
Maximum Continuous
Operating Voltage (MCOV)
≥125%
Fault Current Rating (AIC)
200 kAIC
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
Technical Specifications
Voltage Configurations
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
liebert.com
Operating Frequency Range
47 – 63 Hz
Technical Support
Connection
Parallel (4-6 AWG recommended and 14-1/0 AWG capable); wire lug or disconnect
Modes of Protection
Line to Neutral/standard
800 288 6169 Toll-Free
607 724 2484 Phone
607 722 8713 Fax
Surge Current Capacity
160 kA per mode
Response Time
<0.5 nanoseconds
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
Dimensions
15.32 in. x 13.32 in. x 6.60 in.
Weight
35 lbs.
Operating Temperature
-40°C to +60°C
Status Indication
LEDs, Form “C” contacts — 2 sets
Form “C” Contact Rating
120 VAC, 5.0 amps, pF of 1.0
Certifications
Product performance and safety standards — UL 1283, UL 1449 Second Edition 2005,
(effective Feb. 9, 2007), C22.2 No.8 Bulletin 516, NEMA LS1-1992
Technology
Type 1 Hybrid TVSS — 20 kA of SAD protection and 160 kA of MOV protection
© 2007 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
Type 2 MOV only TVSS — 160 kA of MOV protection
Enclosure
NEMA 4X; suitable for indoor or outdoor applications
Warranty
Covered 24x7 by Emerson Network Power Service Business 10-Years Parts and 5-Years
On-Site Labor
Typical NEMA LS1 Data
Type 1 Unit;
Line - Neutral
Type 2 Unit;
Line - Neutral
SL-22090 (R05/07)
Printed in USA
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
120/208V & 120/240V
120/208V & 120/240V
Clamping Voltage (Vpk)
Clamping Voltage (Vpk)
Category A Ringwave
(6 kV / 0.2 kA)
176
284
Category B Ringwave
(6 kV / 0.5 kA)
288
304
UL 1449 Combination Wave
(6 kV / 0.5 kA)
256
300
Category B Combination
Wave (6 kV / 3.0 kA)
304
336
Emerson Network Power.com
Category C Combination
Wave (20 kV / 10.0 kA)
440
408
Business-Critical Continuity™, Emerson Network
Power and the Emerson Network Power logo are
trademarks and service marks of Emerson
Electric Co. ©2007 Emerson Electric Co.