NFPA 70E COMPLIANCE GUIDE This guide shall only be used in conjunction with performing the necessary calculations in a flash hazard analysis to determine the proper cal/cm 2. If the results of the calculations exceed the cal/cm2 that correspond to the HRC found on this guide, you must use clothing that complies with the calculation. Panelboards or Other Equipment Rated 240V and Below - Note 1 Arc Flash Boundary = 19 in. Task (equipment is energized & work is done within the flash protection boundary) Perform infrared thermography and other noncontact inspection outside the restricted approach boundary V-Rated Gloves V-Rated Tools 600V Class Switchgear (with power circuit breakers or fused switches) and 600V Class Switchboards - Note 4 Arc Flash Boundary = 233 in. (19' 5") HRC Task (equipment is energized & work is done within the flash protection boundary) V-Rated Gloves V-Rated Tools Metal Clad Switchgear, 1 kV thru 38 kV - Note 5 Arc Flash Boundary = 422 in. (35' 2") HRC 0 CB or fused switch or starter operation with enclosure doors closed 0 Circuit Breaker (CB) or fused switch operation with covers on 0 0 CB or fused switch operation with covers off 0 Reading a panel meter while operating a meter switch Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed Open hinged covers (to exposed bare, energized electrical conductors and circuit parts) 0 Work on energized electrical conductors and circuit parts, including voltage testing Remove/install CBs or fused switches Y Y 1 Y Y 1 Y Y 0 Task (equipment is energized & work is done within the flash protection boundary) V-Rated Gloves V-Rated Tools Reading a panel meter while operating a meter switch CB operation with enclosure doors closed Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed Perform infrared thermography and other noncontact inspection outside the restricted approach boundary HRC 0 2 Y Y 2 CB or fused switch operation with enclosure doors open Perform infrared thermography and other noncontact inspection outside the restricted approach boundary 1 2 Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 Open hinged covers (to exposed bare, energized electrical conductors and circuit parts) 2 Removal of bolted cover (to expose bare, enenergized electrical conductors and circuit parts) 4 3 Removal of bolted covers (to exposed bare, 1 energized electrical conductors and circuit parts) Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a Y Y 1 branch circuit of the panelboard Panelboards or Other Equipment Rated >240V and up to 600V (with molded or insulated case circuit breakers) - Note 1 Arc Flash Boundary = 30 in. Work on energized electrical conductors and circuit parts, including voltage testing Y Y 2 Work on energized electrical conductors and circuit parts, including voltage testing Y Y 4 Work on control circuits with energized electrical conductor and circuit parts >120 V, exposed Y Y 2 Work on control circuits with energized electrical conductor and circuit parts >120 V, exposed Y Y 4 Application of temporary safety grounds, after voltage test Y 2 Insertion or removal (racking) of CBs from cubicles, doors open or closed Task (equipment is energized & work is done within the flash protection boundary) Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 Application of temporary safety grounds, after voltage test Removal of bolted covers (to exposed bare, energized electrical conductors and circuit parts) 4 Opening voltage transformer or control power transformer compartments V-Rated Gloves V-Rated Tools HRC Circuit Breaker (CB) or fused switch operation with covers on 0 Open hinged covers (to exposed bare, energized electrical conductors and circuit parts) 0 Removal of bolted covers (to exposed bare, energized electrical conductors and circuit parts) Perform infrared thermography and other noncontact inspection outside the restricted approach boundary 1 1 CB or fused switch operation with covers off Y Work on energized electrical conductors and circuit parts, including voltage testing Y Y 2 Y Y 2 Remove/install CBs or fused switches Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the panelboard or Switchboard 1 Y Y 2 600V Class Motor Control Center (MCCs) - Note 2 Arc Flash Boundary = 53 in Task (equipment is energized & work is done within the flash protection boundary) V-Rated Gloves V-Rated Tools HRC CB or fused switch or starter operation with enclosure doors closed 0 Reading a panel meter while operating a meter switch 0 Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed Perform infrared thermography and other noncontact inspection outside the restricted approach boundary Y Y CB or fused switch or starter operation with enclosure doors open Y Work on control circuits with energized electrical conductor and circuit parts >120 V, exposed Y Application of safety grounds, after voltage test Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the motor control center Y Y Y Y V-Rated Gloves V-Rated Tools Insertion or removal of individual starter “buckets” from MCC Y Removal of bolted covers (to exposed bare, energized electrical conductors and circuit parts) Miscellaneous Equipment cover removal or installation Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) - Lighting or small power transformer (600v max) Work on energized electrical conductors and circuit parts, including voltage testing - Lighting or small power transformer (600v max) Y Y 2 2 2 4 2 Work on energized electrical conductors and circuit parts, including voltage testing Y Work on control circuits with energized electrical conductor - and circuit parts >120 V, exposed 2 2 2 V-Rated Tools HRC Y Y Y * If the notes cannot be satisfied, work must be performed de-energized Note 1 Maximum of 25 kA short circuit current available, maximum of 0.03 second (2 cycle) fault clearing time. Work on energized electrical conductors and circuit parts, including voltage testing Insertion or removal (racking) of CBs from cubicles, doors open or closed Removal of bolted cover (to expose bare, energized electrical-cal conductors and circuit parts) Y Y 2 4 Insertion or removal of CBs from cubicles, doors open Other Equipment Including Metal-Enclosed Interrupter Switchgear, Fused or Unfused 1 kV Thru 38 kV - Note 5 Arc Flash Boundary = 422 in. (35' 2") Task (equipment is energized & work is done within the flash protection boundary) V-Rated Gloves V-Rated Tools Metal -enclosed Interupter Switchgear, Fused or Unfused Switch operation of arc-resistant-type construction, tested in accordance with IEEE C37.20.7, doors closed only HRC 0 2 Switch operation , doors closed Y Y 4 Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 0 Outdoor disconnect switch operation (hookstick operated) Y 0 Outdoor disconnect switch operation (gangoperated, from grade) Y 2 0 Insulated cable examination, in manhole or other confined space Y 4 Y 2 Insulated cable examination, in open area Task (equipment is energized & work is done within the flash protection boundary) 3 Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >1 kA and <4 kA. - Potential arc flash boundary using above parameters at 4 kA: 36 in. 4 4 4 Y 3 Storage Batteries, Direct-Currenty Switchboards and Other Direct-Curent Supply Sources >100 v < 250 V Maximum Arc Duration and Working Distance 2 sec @ 18 in. 3 3 Y Y 0 Application of temporary safety grounds, after voltage test NOTES 0 4 3 Y Insertion or removal (racking) of CBs from cubicles, doors closed Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed Removal of bolted cover (to expose bare, energized electrical conductors and circuit parts) 2 Y HRC 0 CB operation with enclosure doors closed Work on energized electrical conductors and circuit parts, including voltage testing V-Rated Gloves Opening hinged covers (to expose bare, energized electrical-cal conductors and circuit parts) Perform infrared thermography and other noncontact inspection outside the restricted approach boundary V-Rated Tools 0 2 Contactor operation with enclosure doors open V-Rated Gloves Insertion or removal (racking) voltage trans-former on or off the bus door closed 2 HRC Task (equipment is energized & work is done within the flash protection boundary) 1 Y Contactor operation with enclosure doors closed Insertion or removal (racking) of starters from cubicles of arc-resistant construction, tested in accordance with IEEE C37.20.7, doors closed only CB operation with enclosure doors open Arc-Resistant Switchgear Type 1 or 2 (for clearing times of <0.5 sec with a perspective fault current not exceed the arc resistant rating of equipment)Note 5 Arc Flash Boundary = 422 in. (35' 2") 0 Revenue meters (kW-hour, at primary voltage and current) Insertion or removal Removal of bolted cover (to expose bare, energized electrical conductors and circuit parts) Lighting or small power transformer (600v max) Task (equipment is energized & work is done within the flash protection boundary) Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 4 Insertion or removal (racking) of ground and test device with doors closed 2 Y 4 1 Y Reading a panel meter while operating a meter switch 4 HRC Application of safety grounds, after voltage test Lighting or small power transformer (600v max) Y Y 4 1 Cable trough or tray cover removal or installation Insertion or removal of plug-in devices into or from Y busways NEMA E2 (fused contactor) Motor Starters, 2.3kV thru 7.2kV Note 5 Arc Flash Boundary = 422 in. (35' 2") 1 Open hinged covers (to exposed bare, energized electrical conductors and circuit parts) V-Rated Tools 1 600V Class Motor Control Center (MCCs) - Note 3 Arc Flash Boundary = 165 in. (13' 9") Task (equipment is energized & work is done within the flash protection boundary) V-Rated Gloves Application of temporary safety grounds, after voltage test 2 Y Task (equipment is energized & work is done within the flash protection boundary) 0 1 Work on energized electrical conductors and circuit parts, including voltage testing Other 600V Class (277v thru 600v, nominal equipment) - Note 2 Arc Flash Boundary = 53 in. 4 Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >4 kA and <7 kA. - Potential arc flash boundary using above parameters at 7 kA: 48 in. Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >7 kA and <15 kA. - Potential arc flash boundary using above parameters at 15 kA: 72 in. V-Rated Gloves V-Rated Tools HRC Y Y 1 Y Y 2 Y Y 3 Storage Batteries, Direct-Currenty Switchboards and Other Direct-Curent Supply Sources >250 v < 600 V Maximum Arc Duration and Working Distance 2 sec @ 18 in. V-Rated Gloves V-Rated Tools HRC Note 2 Maximum of 65 kA short circuit current available, maximum of 0.03 second (2 cycle) fault clearing time. Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >1 kA and <1.5 kA. - Potential arc flash boundary using above parameters at 1.5 kA: 36 in. Y Y 1 Note 3 Maximum of 42 kA short circuit current available, maximum of 0.33 second (20 cycle) fault clearing time. Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >1.5 kA and <3 kA. - Potential arc flash boundary using above parameters at 3 kA: 48 in. Y Y 2 Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >3 kA and <7 kA. - Potential arc flash boundary using above parameters at 7 kA: 72 in. Y Y 3 Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is >7 kA and <10 kA. - Potential arc flash boundary using above parameters at 10 kA: 96 in. Y Y 4 Note 4 Maximum of 35 kA short circuit current available, maximum of 0.5 second (30 cycle) fault clearing time. Note 5 Maximum of 35 kA short circuit current available, maximum of 0.2 second (12 cycle) fault clearing time. *Working on circuits over 40 cal/cm2 should be avoided because of blast hazard. Task (equipment is energized & work is done within the flash protection boundary) Minimum HRC cal/cm Protective Clothing 2 0 Natural fiber long-sleeve shirt & pants Fabric wt 4.5 oz/yd² 4 1 FR long-sleeve shirt & pants or FR coveralls Arc rated face shield, Rubber insulating gloves (AN) FR long-sleeve shirt & pants or FR coveralls 8 2 Arc rated face shield with balaclava or Arc flash hood, Rubber insulating gloves (AN) N/A Definitions: Y = Yes (Required) Hard Hat, Safety Glasses or Goggles, Hearing Protection, Leather Work Shoes Apply to All &Leather Gloves(AN) V-Rated Gloves: Rubber Insulating Gloves rated and tested for the maximum line-to-line voltage upon which work will be done. Leather protectors must be worn externally if rubber insulating gloves could be damaged. Rubber insulating gloves (AN) 3 Arc rated flash suit 25 Arc rated switching hood, Rubber insulating gloves (AN) 4 Arc rated flash suit 40 Arc rated switching hood, Rubber insulating gloves (AN) V-Rated Tools: Insulated and Insulating Hand Tools rated and tested for the maximum lineto-line voltage upon which work will be done HRC: Hazard Risk Category FR: Flame Resistant AN: As Needed APPROACH BOUNDARIES – AC SYSTEMS Nominal System Voltage 2 Range, Phase to Phase Less than 50 50 to 300 301 to 750 751 to 15 kV 15.1 kV to 36 kV 1 2 3 Limited Approach Boundary Exposed Movable Exposed Fixed Circuit 3 Conductor Part Not specified Not specified 10 ft. 0 in. 3 ft. 6 in. 10 ft. 0 in. 3 ft. 6 in. 10 ft. 0 in. 10 ft. 0 in. 5 ft. 0 in. 6 ft. 0 in. Restricted Approach Boundary Includes Inadvertent Movement Adder Not specified Avoid contact 1 ft. 0 in. 2 2 ft. 2 in. 2 2 ft. 7 in. Arc Flash Protection Boundary Prohibited Approach Boundary Not specified Avoid contact 0 ft. 1 in. See Each Section 1 Of HRC Guide 0 ft. 7 in. 0 ft. 10 in. For panelboards only, rated up to 600 volts, set up arc flash boundary at 4 feet to keep unqualified people our of your work area. For all other situations, set up arc flash boundary at designated distance per HRC Guide. For single-phase systems, select the range that is equal to the system’s maximum phase-to-ground voltage multiplied by 1.732. A condition in which the distance between the conductor and a person is not under the control of the person. The term is normally applied to overhead line conductors supported by poles. a APPROACH BOUNDARIES – DC SYSTEMS Nominal Potential Difference < 100V 100 V – 300 V 301 V – 1 kV 1.1 kV – 5 kV a b Limited Approach Boundary Exposed Movable Exposed Fixed Circuit b Conductor Part Not specified Not specified 10 ft. 0 in. 3 ft. 6 in. 10 ft. 0 in. 3 ft. 6 in. 5 ft. 0 in. 10 ft. 0 in. Restricted Approach Boundary Includes Inadvertent Movement Adder Not specified Avoid contact 1 ft. 0 in. 1 ft. 5 in. Prohibited Approach Boundary Not specified Avoid contact 0 ft. 1 in. 0 ft. 4 in. All dimensions are distance from exposed energized electrical conductors or circuit parts to worker. This term describes a condition in which the distance between the conductor and a person is not under the control of the person. The term is normally applied to overhead line conductors supported by poles. APPOROACH BOUNDARIES ELECTRICAL SHOCK HAZARDS Limited Approach Boundary: An approach limit at a distance from an exposed energized conductor or circuit part within which a shock hazard exists. An electrical shock boundary whereby only qualified people can enter because they have the skills and knowledge to recognize and avoid electrical hazards. Unqualified people must stay outside the Limited Approach Boundary so they cannot contact energized parts. Restricted Approach Boundary: The distance from exposed energized parts where there is an increased risk of electrical shock due to electric arc over combined with inadvertent movement. A qualified person must wear PPE for protection (typically rubber insulating gloves and use insulated tools) from the electrical shock hazard when working within the Restricted Approach Boundary. Prohibited Approach Boundary: The distance from an exposed energized electrical conductor or circuit part within which work is considered the same as making contact with the electrical conductor or circuit part. A qualified person must avoid performing work with the Prohibited Approach Boundary. Arc Flash Protection Boundary: The distance from an arc source at which a person could receive a second-degree burn if an electrical arc flash would occur. All people must wear appropriate PPE while working/standing within this approach boundary. Unqualified People – Access to Working Space All unqualified people must stay outside the Limited Approach Boundary and the Arc Flash Protection Boundary, which ever distance is greater. They must remain outside these approach boundaries until the electrical hazard is eliminated / controlled. Develop a plan for keeping unqualified people and qualified people not wearing PPE, outside the approach boundary. For large electrical rooms, cordon off the work area with barricades and signs. Small electrical rooms can be controlled by keeping everyone outside the electrical room with a closed door and a spotter. When working in a panel in a hallway of an occupied building, set up a barricade system to keep unqualified people out. Justification for Work : Staff Electric’s company policy is – NO HOT WORK! Our policy is to de-energize by placing the energized electrical conductors and circuit parts into an electrically safe work condition to protect exposed employees working within the Limited Approach Boundary. Staff Electric follows the requirements of NFPA 70E and OSHA for justifying hot work. NFPA 70E 130.2 Energized electrical conductors and circuit parts to which an employee might be exposed shall be put into an electrically safe work condition before an employee performs work: 1. Within the limited approach boundary or 2. The employee interacts with equipment where conductors or circuit parts are not exposed, but an increased risk of injury from an exposure to an arc flash hazard exists. The only exceptions are: 1. Greater Hazard: The employee can demonstrate that de-energizing introduces hazards. 2. Infeasibility: The employee can demonstrate that the task to be performed is infeasible in a de-energized state due to the equipment design or operational limitations. 3. Less than 50 volts to ground. OSHA’s position regarding hot work is: OSHA 1910.333(a)(1) requires that live parts be de-energized before a potentially exposed employee works on or near them. Exception - if de-energizing introduces additional or increased hazards or if de-energizing is infeasible due to equipment design or operational limitations. Examples are: • • • • Interruption of life support equipment Deactivation of emergency alarm systems Shutdown of hazardous location ventilation equipment Removal of illumination from an area • Performing diagnostics and testing (e.g. start up and trouble shooting circuits that are part of a continuous process that would otherwise need to be completely shutdown in order to permit work on 1 circuit or piece of equipment.) 2012 Edition