IMPORTANT SAFETY INSTRUCTIONS
•
•
•
•
•
•
•
•
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels. Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions. Installation and service of luminaires should be performed by a qualified licensed electrician. Maintenance of the luminaires should be performed by person(s) familiar with the luminaires’ construction and operation and any hazards involved. Regular fixture maintenance programs are recommended. It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on ambient dirt level and minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm water and any mild, nonā€abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on the inside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary. DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced. If the lamp is marked (Hg) it contains Mercury. Follow all disposal laws. See www.lamprecycle.org. These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity Brands Lighting, Inc. WARNING RISK OF ELECTRIC SHOCK
9
9
9
9
WARNING RISK OF BURN
9
Disconnect or turn off power before installation or servicing. Verify that supply voltage is correct by comparing it with the luminaire label information. Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements. All wiring connections should be capped with UL approved recognized wire connectors. 9
9
9
Allow lamp/fixture to cool before handling. Do not touch hot lens, lamp, guard, or enclosure. Do not exceed maximum wattage marked on luminaire label. Follow all lamp manufacturer’s warnings, recommendations and restrictions on lamp operation including but not limited to: ballast type, burning position, replacement, and recycling. Use only lamps that comply with ANSI standards. 9
9
CAUTION RISK OF INJURY Wear gloves and safety glasses at all times when removing luminaire from carton, installing, servicing or performing maintenance. Avoid direct eye exposure to the light source while it is on. CAUTION RISK OF FIRE
9
9
Keep combustible and other materials that can burn away from lamp/lens. Do not operate in close proximity to persons, combustible materials or substances affected by heat or drying. Failure to follow any of these instructions could void product warranties. For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com. Our Brands Indoor/Outdoor Lithonia Lighting Carandini Holophane RELOC Indoor Lighting Gotham Mark Architectural Lighting Peerless Renaissance Lighting Winona Lighting Outdoor Lighting American Electric Lighting Antique Street Lamps Hydrel Tersen Controls DARK TO LIGHT Lighting Control & Design ROAM Sensor Switch Synergy Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products. © 2010 Acuity Brands Lighting, Inc. All rights reserved. 12/01/10 ABL General Warnings, Form No. 503.204
IM-306
HOLOPHANE®
7300 Industrial Fluorescent
Two & Four Foot Luminaires
Installation and
Maintenance
Manual
AFTER INSTALLATION DELIVER THIS
MANUAL TO OWNER
IMPORTANT SAFETY INSTRUCTIONS
WARNING – READ THESE INSTRUCTIONS
CAREFULLY BEFORE ATTEMPTING TO INSTALL OR
MAINTAIN THIS FIXTURE. WORK MUST BE DONE BY
QUALIFIED PERSONNEL.
WARNING – BE CERTAIN THAT ALL ELECTRICAL
POWER IS DISCONNECTED FROM THE FIXTURE
BEFORE INSTALLING OR MAINTAINING THE FIXTURE.
WARNING – FOLLOW LAMP MANUFACTURER’S
OPERATING AND MAINTENANCE INSTRUCTIONS.
FAILURE TO FOLLOW THESE WARNINGS MAY RESULT
IN DEATH, INJURY OR SIGNIFICANT PROPERTY
DAMAGE.
1 INTRODUCTION
1.1 Product Description.
The 7300 Industrial Fluorescent
has been designed and tested in accordance with CSA standards and
are suitable for use in wet locations and with ambient temperatures up
to 25 degrees C.
• 7300 Industrial Fluorescent is available in 2 and 4 foot lengths with
either surface or stem mounting.
• Major components of the fluorescent are identified in Figure 1.
• 7300 Fluorescent has been designed for easy maintenance and
repair of components.
• The lamps can be accessed by pressing the latch buttons on one
side of lens. Rotate lens open to replace lamps.
Electrical components are mounted on the reflector. Access to the
ballast assembly is made by unlatching and swinging open the
reflector.
GR1943, GR1944
Figure 1
1.2 Alternate Information Sources.
Holophane
Field Service Department
P.O. Box 3004
Newark, OH 43058-3004
(740) 345-9631
GR1945
2 INSTALLATION
2.1 Tools and Materials Required.
TABLE 1. Installation Tools and Materials
DESCRIPTION
USE
1/4" Nut Driver or Medium Slotted
Continuous Row Kit
Screwdriver
1/4" Fasteners and
Appropriate Tool(s)
Mounting Surface
Luminaires.
2.2 General Installation of Two and Four Foot
Luminaires.
2.2.1 Two and Four foot luminaires are contained in one box.
Open
and examine.
2.2.2 Rest luminaire on flat surface. Lens side up.
2.2.3 Open luminaire by pressing both latch buttons on one side of
lens. Rotate lens open.
2.2.4 Rotate (2) reflector thumb latches 90 degrees away from
housing. Reflector should freely hinge open allowing access to
ballast. Proceed to 2.3 for surface mounting or 2.4 for stem mounting.
IM-306
HOLOPHANE®
7300 Industrial Fluorescent
Two & Four Foot Luminaires
Installation and
Maintenance
Manual
2.3 Surface Mounting for Two and Four Foot
Luminaires.
2.4.6 Install correct wattage and type lamp.
2.4.7 Swing the lens closed and push up on the lens supports until
2.3.1 See Figure 2 for mounting hole locations on 2 foot luminaires.
the latches engage with an audible click. Do not push on the plastic
lens. Make sure all latches are engaged.
See Figure 3 for mounting hole locations on 4 foot luminaires.
2.3.2 Mount the luminaire to a horizontal surface or structure with
Figure 4
1/4" fasteners. Use nylon washer provided between housing and
fastener head.
2.3.3 Wire way entry is achieved by removing the Ø.875 EKO on
either end of housing. Seal the joint appropriately using a sealing
type connector or other suitable means.
2.3.4 Wire per NEC (National Electrical Code) and appropriate
wiring diagram shown on the ballast.
2.3.5 Close reflector. Push thumb latches into housing slots.
2.3.6 Install correct wattage and type lamp.
2.3.7 Swing the lens closed and push up on the lens supports until
the latches engage with an audible click. Do not push on the plastic
lens. Make sure all latches are engaged.
GR1900
Figure 2
Figure 5
GR1901
GR1898
2.5 Installation of Continuous Row Kit. Continuous Row
Kit is available with surface mounting only.
Figure 3
2.5.1 During installation, remove EKO and drill two 3/16" holes in the
GR1899
2.4 Stem Mounting for Two and Four Foot
Luminaires.
2.4.1 Mount luminaire to 1/2" threaded conduit by using the conduit
entries on the top of the luminaire. See Figure 4 for dimensions on 2
foot luminaires. See Figure 5 for dimensions on 4 foot luminaires.
Two and Four foot luminaires have two entries.
2.4.2 Seal all conduit to entry connections with a silicone sealant.
2.4.3 Wire entry is achieved through the support stems or by
removing the Ø.875 EKO on either end of housing.
2.4.4 Wire per the NEC and appropriate wiring diagram shown on
the ballast.
2.4.5 Close reflector. Push thumb latches into housing slots.
end of housing. Dimples are provided for holes.
See Figure 6.
2.5.2 Join units with two #8 bolts and nuts (provided in kit). Locate
gasket (provided in kit) around conduit entry between luminaires. See
Figure 7.
2.5.3 Seal all knockout and drilled holes with a silicone sealant.
2.5.4 See Figure 3 for mounting hole locations.
2.5.5 Mount the luminaire to a surface or structure with 1/4"
fasteners. Use nylon washer provided between housing and fastener
head.
Figure 6
GR1902
IM-306
HOLOPHANE®
7300 Industrial Fluorescent
Two & Four Foot Luminaires
Figure 7
Installation and
Maintenance
Manual
3.2.8 Install new component using previously retained mounting
hardware.
3.2.9 Make electrical connections in accordance with tags and
approved wiring practices.
3.2.10 Complete connection of remaining tagged wires. Reconnect
common and electrical leads.
3.2.11 Close reflector. Push thumb latches into housing slots.
3.2.12 Install correct wattage and type lamp.
3.2.13 Swing the lens closed and push up on the lens supports until
the latches engage with an audible click. Do not push on the plastic
lens. Make sure all latches are engaged.
4 Limited Warranty and Limitation of Liability
GR1946
2.5.6 Wire way entry is achieved by removing the EKO from end of
housing at end of row.
2.5.7 Wire per NEC (National Electrical Code) and appropriate wiring
diagram shown on the ballast.
The Holophane limited warranty and limitation of liability is published
in the "Terms and Conditions" section of the current Holophane
buyer's guide, and is available from your local Holophane sales
representative.
3 MAINTENANCE
3.1 Relamping and Cleaning.
3.1.1 Disconnect all electrical power to the fluorescent luminaire.
3.1.2 Wipe off exterior dirt and debris.
3.1.3 Open fluorescent by pressing latch buttons on one side of lens.
Rotate open.
3.1.4 Remove lamp and discard properly.
3.1.5 Install correct wattage and type lamp.
3.1.6 Swing the lens closed and push up on the lens supports until
the latches engage with an audible click. Do not push on the plastic
lens. Make sure all latches are engaged.
3.2 Electrical Component Replacement.
3.2.1 Disconnect all electrical power to the fluorescent luminaire.
3.2.2 Wipe off exterior dirt and debris.
3.2.3 Open luminaire by pressing latch buttons on one side of lens.
Rotate lens open.
3.2.4 Rotate (2) reflector thumb latches 90 degrees away from
housing. Reflector should freely hinge open allowing access to
ballast.
3.2.5 Tag and disconnect common and electrical leads.
3.2.6 Remove and retain component mounting hardware.
3.2.7 Tag associated electrical leads, and remove involved
component.
®
Acuity Brands Lighting, Inc.
3825 Columbus Rd., Granville, OH 43023
IM-306 02/11 ©2011 Acuity Brands Lighting, Inc.
All Rights Reserved.
Visit our web site at www.holophane.com
IM-306