801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 • www.sdcsecurity.com • E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS - MODEL UR-1 UNIVERSAL RELAY MODULE UR-1 UNIVERSAL RELAY MODULE UR-1 UR-1 1 2 3 4 1 2 3 4 w A w B D D - + PWR J1 A w D C NO C NO - NO C NC TRIG A TRIG B RELAY A - NO C NC RELAY B w B D - + PWR J1 C NO C NO - NO C NC - NO C NC TRIG A TRIG B RELAY A RELAY B Fits all SDC Power Supplies. Requires 1 Module space. Supplied with mounting screws and standoffs for J-box mounting. FEATURES AND BENEFITS Microprocessor based relay controller that provides multiple, field selectable operational modes for up to two door stations. Each output relay is field selectable as a dry contact or voltage output. Centralized wiring for all locks, access controls, monitoring contacts and peripheral equipment. 1 or 2 controllers may be installed in SDC 600 series power supplies Field selectable relay modes include: - Conventional Relay (CR) - Dual Conventional Relay (2X CR) - Time Delay Relay (TD) – 1 to 60 Seconds - Dual Time Delay Relay (2X TD) - Latching Relay (LR) – Separate Latch and Release Inputs - Dual Latching Relay – (2X LR) Pulse On, Pulse Off Inputs - Time Delay/Latching Relay - Interlock A (airlock) - Interlock B (2 modules required) UR-1 TECHNICAL SPECIFICATIONS INPUT VOLTAGE 12 or 24VDC +/- 10% INPUT CONTROLLER CURRENT INPUTS 2 ea Dry Signal Inputs 2 ea 10 amp @ 30VDC (resistive) SPDT Lock Outputs (Configurable Wet or Dry). Wet output voltage is the same as the module power IN voltage. OUTPUTS 3.20"W x 2.00" L x 1.0" H [81.28mm W x 50.8mm L x 25.4mm H] DIMENSIONS P:\INSTALLATION INST\POWER SUPPLY\INST-UR-1.vsd 120/175mA Rev H 04-14 Page 1 Any suggestions or comments to this instruction or product are welcome. Please contact us through our website or email engineer@sdcsecurity.com To AC Mains UR-1 1 2 3 4 Program Dip Switches Time Adj A w D Relay Output Jumpers W = Wet (voltage) D = Dry w B D RELAY A - Power In 12/24 vdc C NO C NO - NO C NC - NO C NC TRIG A TRIG B + - + PWR J1 Power Supply RELAY B 12/24 vdc Output Relays Inputs WARNING!: The UR board Output Relays must be protected against inductive kickback generated when power is removed from an inductive load (e.g., electric strikes). Refer to the lock manufacturer's installation manual or contact the manufacturer for kickback protection recommendations. CR Mode Dual CR Mode Switch No: SW1 SW2 SW3 SW4 off ON off off Switch No: SW1 SW2 SW3 SW4 off off off off Position A w B D Position w D A - + w w B D D C NO C NO - NO C NC - NO C NC C NO C NO - NO C NC - NO C NC TRIG A TRIG B TRIG A TRIG B RELAY A RELAY B Access Control NC A or B NO + A or B - RELAY A RELAY B Access Control DRY CONTACTS COM Access Control - + PWR PWR A + Access Control Fail Safe Lock - B Fail Safe Lock + - Door A Push and hold to Unlock + - Push and hold to Unlock Fail Secure Lock TD Mode Time Adj 1 – 60 Sec Time Adj 1 – 60 Sec (Both A & B same time setting) Switch No: SW1 SW2 SW3 SW4 off off ON off Position A w B D +Fail - - Secure Lock A - + w w B D D C NO C NO - NO C NC - NO C NC C NO C NO - NO C NC - NO C NC TRIG A TRIG B RELAY B NC Access Control + Reset - RELAY A RELAY B Access Control DRY CONTACTS COM NO - + PWR TRIG A TRIG B RELAY A A Fail Safe Lock Access Control + B - Fail Safe Lock + - Door A Push & Release to Reset + - Push to Activate each Timer Fail Secure Lock P:\INSTALLATION INST\POWER SUPPLY\INST-UR-1.vsd Rev H Secure Lock Switch No: SW1 SW2 SW3 SW4 off off off ON Position PWR Push to Activate Door B + Fail Dual TD Mode w D Fail Safe Lock 04-14 Page 2 Fail Safe Lock Door B + Fail +Fail - - Secure Lock Secure Lock WARNING!: The UR board Output Relays must be protected against inductive kickback generated when power is removed from an inductive load (e.g., electric strikes). Refer to the lock manufacturer's installation manual or contact the manufacturer for kickback protection recommendations. LR Mode Dual LR Mode (2 Independent Relays) Switch No: SW1 SW2 SW3 SW4 ON off off off Switch No: SW1 SW2 SW3 SW4 ON ON ON off Position Position A w w B D A D - + w w B D D PWR TRIG A TRIG B RELAY A - + PWR C NO C NO - NO C NC - NO C NC C NO C NO - NO C NC - NO C NC RELAY B TRIG A TRIG B RELAY A RELAY B NC Latch COM NO + Release - DRY CONTACTS Lock/Unlock A + Fail Safe Lock Lock/Unlock B - + Fail Safe Lock - Door A + Push Latch to Unlock Push Release to Relock - Fail Secure Lock Push to Unlock Push again to Relock Door B + Fail +Fail - - Secure Lock Sequencer Mode Sequencer Mode (2 Locking Devices) (ELR Device and Door Operator) Switch No: SW1 SW2 SW3 SW4 ON ON off off w w B D D AA - + ww BB DD ww DD PWR RELAY A TRIG A TRIG B After the delay time has expired, door B will unlock RELAY A RELAY B Access Control + - + Fail Safe Lock - Door A Push to activate the ELR device. Door B After the delay time has expired, The door operator will be signaled to activate. +Fail - - Secure Lock Rev H 04-14 Rex Fail Safe Lock + Fail P:\INSTALLATION INST\POWER SUPPLY\INST-UR-1.vsd DOOR OPERATOR POWER C NO C NO - NO C NC - NO C NC RELAY B Access Control Push to activate Door A will unlock. - + PWR C NO C NO - NO C NC - NO C NC TRIG A TRIG B Secure Lock Switch No: SW1 SW2 SW3 SW4 ON ON off off Position Position A Fail Safe Lock Secure Lock Page 3 + - Door Operator Electric Latch Retraction Device SDC LR100 SERIES WARNING!: The UR board Output Relays must be protected against inductive kickback generated when power is removed from an inductive load (e.g., electric strikes). Refer to the lock manufacturer's installation manual or contact the manufacturer for kickback protection recommendations. TD/LR Mode Interlock A Switch No: SW1 SW2 SW3 SW4 ON ON off ON Position w A w B D Switch No: SW1 SW2 SW3 SW4 ON off ON off Position A D - + w w B D D PWR C NO C NO - NO C NC - NO C NC C NO C NO - NO C NC - NO C NC TRIG A TRIG B TRIG A TRIG B RELAY A - + PWR RELAY B RELAY A RELAY B NC Timed DRY CONTACTS COM NO DPS Fail Safe Lock Latching Lock / Unlock * Fail Safe Lock + - Door A Fail Secure Lock *DPS switches should be in the Open state with the doors Closed DPS * Fail Safe Lock + - Door B Method of Operation: Both doors are normally closed and Unlocked. Opening either door will Lock the other door. Interlock B (2 Modules are Required) Switch No: SW1 SW2 SW3 SW4 Switch No: SW1 SW2 SW3 SW4 ON off off ON Position A w D Position w B ON A D - + off w D ON off B w D - + PWR PWR C NO C NO - NO C NC - NO C NC C NO C NO - NO C NC - NO C NC TRIG A TRIG B TRIG A TRIG B RELAY A RELAY B Access Control Access Control A B + Fail - Safe Lock DPS * RELAY A RELAY B + Fail - switches should * DPS be in the Open state Door A with the doors Closed Safe Lock DPS * Door B Method of Operation: Both doors are normally closed and locked. Unlocking or opening the other door will make the other door incapable of being unlocked. P:\INSTALLATION INST\POWER SUPPLY\INST-UR-1.vsd Rev H 04-14 Page 4 Communicating Bath Using Fail Safe Electrified Locksets TO 115 VAC PRIMARY VOLTAGE 3 COND TO N/C FIRE ALARM INTERFACE 2 COND 10 COND Power Supply 10 COND Method of Operation 631RF 4 COND 4 COND x UR1 CB402B PUSH BUTTON 6 COND 6 COND DOOR 1 Both doors shall be normally unlocked. CB402B PUSH BUTTON System Activation: Both doors must be closed to lock. Pressing the CB402A Push Button will lock all the doors. DOOR 2 Egress: When the doors are locked, turning either door’s inside lever activates the lock’s REX switch and unlocks both doors. 4 COND Emergency Release: When the doors are locked, activating either CB402B Emergency Push Buttons will unlock both the doors. PTH-10 POWER TRANSFER HINGE ELECTRIFIED MORTISE LOCK x REX x DPS Set to ”LR Mode” PTH-10 POWER TRANSFER HINGE CB402A PUSH BUTTON (INSIDE) Switch No: SW1 SW2 SW3 SW4 ON off off off Position A w B D When used with an SDC 631RF power supply, Both doors will unlock automatically via signal from the fire panel. ELECTRIFIED MORTISE LOCK x REX x DPS To 12vdc or 24vdc Power Supply +- w D CB402B - + PWR 1 C NO C NO - NO C NC - NO C NC TRIG A TRIG B RELAY A RELAY B (Inside) PUSH TO UNLOCK DOOR Door 1 + CB402A - Fail Safe Electrified Lock DPS * REX EMERGENCY RELEASE ORG LAMP RED YEL BATHROOM LOCK RED WHT BOTH DOORS MUST BE CLOSED TO LOCK PUSH TO LOCK *DPS switches should LIGHT ON DOORLOCKED ORG LAMP CB402B be in the Open state with the doors Closed RED 2 YEL RED WHT PUSH TO UNLOCK DOOR Door 2 Push to lock Both Doors + - Fail Safe Electrified Lock DPS REX EMERGENCY RELEASE ORG LAMP RED YEL WHT P:\INSTALLATION INST\POWER SUPPLY\INST-UR-1.vsd Rev H 04-14 Page 5 RED Communicating Bath Using Magnetic Locks TO 115 VAC PRIMARY VOLTAGE 3 COND TO N/C FIRE ALARM INTERFACE 2 COND Power Supply CB401B PUSH BUTTON Method of Operation 631RF 4 COND x 4 COND CB401B PUSH BUTTON UR1 4 COND Both doors shall be normally unlocked. 4 COND System Activation: All doors must be closed to lock. Pressing the CB401A Push Button will lock all the doors. Egress: When the doors are locked, pressing the CB401A Push Button again unlocks all the doors. 4 COND Magnetic Lock x DPS Magnetic Lock x DPS Emergency Release: When the doors are locked, activating either of the CB401B Emergency Push Buttons will unlock both doors. Both doors will unlock automatically via signal from the fire panel. CB401A PUSH BUTTON (INSIDE) Set to “CR Mode” When used with an SDC 631RF power supply, Both doors will unlock automatically via signal from the fire panel. Switch No: SW1 SW2 SW3 SW4 off off off off Position A w D B To 12vdc or 24vdc Power Supply +- w D CB401B - + PWR 1 C NO C NO - NO C NC - NO C NC TRIG A TRIG B RELAY A RELAY B EMERGENCY RELEASE PUSH TO UNLOCK DOOR (Inside) CB401A + DPS MAGNETIC LOCK BATHROOM LOCK * ORG LAMP RED YEL RED WHT BOTH DOORS MUST BE CLOSED TO LOCK Door 1 PUSH TO LOCK OR UNLOCK * LIGHT ON DOOR LOCKED ORG LAMP CB401B DPS switches should be in the Closed state with the doors Closed RED YEL RED WHT 2 EMERGENCY RELEASE PUSH TO UNLOCK DOOR Push to Lock or Unlock Both Doors ORG + LAMP DPS RED MAGNETIC LOCK - YEL WHT Door 2 P:\INSTALLATION INST\POWER SUPPLY\INST-UR-1.vsd Rev H 04-14 Page 6 RED