MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI- 621213. QUESTION BANK SEMESTER – III DEPARTMENT: ECE SUBJECT CODE: EC2201 SUBJECT NAME: Electrical Engineering UNIT 2 TRANSFORMERS PART – A 1. What is meant by transformation ration? [NOV/DEC 2009] Turns ratio= N2 N1 Transformation ratio= E2 E1 I1 I2 K 2. What is the purpose of conducting open circuit and short circuit tests in transformers? [NOV/DEC 2009] The open circuit test useful to find i) No – load loss (or) core loss ii) No – load current iii) Ro and Xo The short circuit test useful to find i) Full load copper loss. ii) Equivalent resistance and reactance referred to any side. By using above two tests, we can predetermine the i) Efficiency of the transformer ii) Regulation of the transformer 3. Why is the core of transformer is laminated? [NOV/DEC 20010] The core of the transformer is laminated in order to minimize eddy current loss. 4. Define voltage regulation of a transformer. [NOV/DEC 2009], [NOV/DEC 2010], [NOV/DEC 2011] Regulation of a transformer is defined as reduction in magnitude of the terminal voltage due to the load, with respect to the no-load terminal voltage. R.Thiyagarajan AP/EEE Page 1 % regulation= V2 onno load V2 whenloaded V2 onno load 100 5. Write down the emf equation of single phase transformer. [NOV/DEC 2009] Emf induced in primary coil E1= 4.44fФmN1 volt emf induced in secondary Coil E2 =4.44 fФmN2. f--freq of AC input, Ф--maximum value of flux in the core N1, N2--Number of primary & secondary turns. 6. State condition for maximum efficiency of a transformer. [NOV/DEC 2010] Efficiency of the transformer will be maximum when copper losses are equal to iron losses. Iron loss = Copper loss (or) Constant loss = Variable loss The load current corresponding to maximum efficiency is given by I2 Pi R02 7. Classify the type of transformer based on core construction. [NOV/DEC 2011] 1) Core type transformer 2) Shell type transformer 3) Berry type transformer 8. Draw the equivalent circuit of transformer. [APRIL/MAY 2010] 9. What is step-up transformer? [NOV/DEC 2011] R.Thiyagarajan AP/EEE Page 2 In a transformer, if the number of turns in the secondary winding is higher than the primary winding is called step up transformer. 10. Mention the function of breather in transformer. [NOV/DEC 2011] The function of breather is to prevent the entry of moisture to inside of the transformer tank. The breather filled with some drying agent, such as calcium chloride or silica gel. Silica gel or calcium chloride absorbs the moisture and allows dry air to enter in to the transformer tank 11. What is the function of the Bucholz relay in a transformer? [NOV/DEC 2008] It is a gas operated relay which mounted in between the conservator and transformer tank. The Bucholz relay give an alarm in case minor fault and disconnect the transformer from the main supply in case of severe fault. 12. Draw the no – load phasor diagram of a transformer. [NOV/DEC 2008] 13. Define all – day efficiency. [NOV/DEC 2007] The ratio of output in kwh to input in kwh of a transformer over a 24 hour period is known a s all – day efficiency. all day kwh output in 24 hrs kwh input in 24 hrs 14. Mention two different components of core loss in a transformer. [NOV/DEC 2007] 1. Hysteresis loss 2. Eddy current loss R.Thiyagarajan AP/EEE Page 3 15. What are the different losses occurring in a transformer? [APRIL/MAY 2008] 1. Copper loss 2. Iron loss 16. Define transformer. The transformer works on the principle of electromagnetic induction. A transformer is an electrical device, having no moving parts, which by mutual induction transfers electrical energy from one circuit another at the same frequency, with changed values of voltage and current 17. Draw the phasor diagram for a transformer with inductive load. 18. What is staggering in the construction of transformers? In transformer, the joints in alternate layers are staggered in order to avoid the presence of narrow gaps right through the cross – section of the core. 19. Why transformer rating is expressed in terms of KVA? Copper loss depends on current and iron loss depends upon voltage. Hence the total loss in a transformer depends upon volt – ampere only not on the phase angle between voltage and current i.e. it is independent of load power factor. That is why the rating of a transformer is given in kVA and not kW. 20. Name the factors on which hysteresis loss depends. R.Thiyagarajan AP/EEE Page 4 1. Frequency 2. Volume of the core 3. Maximum flux density 21. What are the different properties of ideal transformer? 1. No winding resistance 2. No magnetic leakage flux 3. No copper loss 4. No core loss 22. What is eddy current loss? When a magnetic core carries a time varying flux, voltages are induced in all possible path enclosing flux. Resulting is the production of circulating flux in core. These circulating current do no useful work are known as eddy current and have power loss known as eddy current loss. 23. How hysteresis and eddy current losses are minimized? Hysteresis loss can be minimized by selecting materials for core such as silicon steel & steel alloys with low hysteresis co-efficient and electrical resistivity. Eddy current losses are minimized by laminating the core. 24. Why the open circuit test on a transformer is conducted at rated voltage? The open circuit on a transformer is conducted at a rated voltage because core loss depends upon the voltage. This open circuit test gives only core loss or iron loss of the transformer. 25. Mention the difference between core and shell type transformers? In core type, the windings surround the core considerably and in shell type the core surrounds the windings i.e. winding is placed inside the core. PART – B 1. With necessary vector diagrams, discuss about transformer on no – load and loaded conditions. [NOV/DEC 2012] R.Thiyagarajan AP/EEE Page 5 If the primary winding is connected to an alternating voltage and secondary winding left open, then the transformer is said to be on n – load. Let the supply voltage be ‘V1’ volts. This causes an alternating current flow through the primary. Since secondary is open, this current is called no load primary current (Io). This ‘Io’ establishes the flux ‘ ’ weber in the core. Thus Io is not at 90o behind V1, but lags it by an angle o > 90o. No load input power Po=V1Iocos o . ‘Io’ has two components i) Active or working or iron loss or wattful component (Iw), Which is in phase with ‘V1’ and supplies the iron loss and negligible amount of primary copper loss. Iw = Io cos Where, cos R.Thiyagarajan AP/EEE o ----- (1) o = No load power factor Page 6 ii) Reactive or magnetizing or wattles component ( I ) which is in quadrature with V1, and its function is to sustain the flux in the core. I = Io sin o ----- (2) From the above two equations we get Io= I w2 I2 2. (i) Draw the equivalent circuit of a transformer with all its notations [NOV/DEC 2012] Under no load condition, the primary of a transformer draws no load current Io. It is mainly used to supply the iron loss and to produce the flux in the core. The effect of iron loss is represented by a non – inductive resistance Ro and the magnetizing current is represented by Xo. Both of them are connected in parallel with primary winding. This circuit is known as exciting branch or no – load branch. (ii) Write a note on open circuit test on transformer. [NOV/DEC 2012] R.Thiyagarajan AP/EEE Page 7 Open-Circuit or No-Load Test: This test is conducted to determine the iron losses (or core losses) and parameters R0 and X0 of the transformer. In this test, the rated voltage is applied to the primary (usually low-voltage winding) while the secondary is left open circuited. The applied primary voltage V1 is measured by the voltmeter, the no-load current I0 by ammeter and no-load input power W0 by wattmeter as shown in Fig. (i). As the normal rated voltage is applied to the primary, therefore, normal iron losses will occur in the transformer core. Hence wattmeter will record the iron losses and small copper loss in the primary. Since no-load current I0 is very small (usually 2-10 % of rated current). Cu losses in the primary under no-load condition are negligible as compared with iron losses. Hence, wattmeter reading practically gives the iron losses in the transformer. It is reminded that iron losses are the same at all loads. Fig. (ii) Shows the equivalent circuit of transformer on noload. Iron losses, Pi = Wattmeter reading = W0 No load current = Ammeter reading = I0 Applied voltage = Voltmeter reading = V1 Input power, W0 = V1 I0 cos f0 R.Thiyagarajan AP/EEE Page 8 3. (a) Deduce the equivalent circuit of the transformer from the basic principle. [NOV/DEC 2011] R.Thiyagarajan AP/EEE Page 9 Under no load condition, the primary of a transformer draws no load current Io. It is mainly used to supply the iron loss and to produce the flux in the core. The effect of iron loss is represented by a non – inductive resistance Ro and the magnetizing current is represented by Xo. Both of them are connected in parallel with primary winding. This circuit is known as exciting branch or no – load branch. Equivalent circuit of a transformer referred to primary If all the parameters are referred to primary side, we get the equivalent circuit of transformer referred to primary. When secondary parameters are referred to primary resistance and reactance are divided by K2, voltage are divided by K and currents multiplied by K. This circuit also called as exact equivalent circuit of a transformer. R '2 R2 , X '2 2 K X2 ' , I2 K2 KI 2 , Z'L ZL , V2' 2 K V2 , Ro K V1 , Xo Iw V2 Iμ Approximate equivalent circuit R.Thiyagarajan AP/EEE Page 10 The no – load current Io is only 1 – 3% of rated primary current. So I '2 practically equal to I1. Due to this, equivalent circuit can be simplified by transferring the exciting branch (Ro and Xo) to the left position of the circuit. R01=R1+R’2 and X01=X1+X’1 Z 01 2 2 R01 X 01 The above figure shows all the parameters referred to primary. R.Thiyagarajan AP/EEE Page 11 2 R02 Z02 2 X 02 The above figure shows all the parameters referred to secondary (b) A 2200/200 V transformer draws a no load primary current of 0.6A and absorbs 400 Watts. Find the magnetizing and iron loss current. Draw also the no load phasor diagram. [NOV/DEC 2011] Given Data: V1=2200V, V2=200V, Io=0.6A, Po=400W To find? Iw, I Solution: Iron loss component Iw = Po V1 400 2200 Iw = 0.18 A Magnetizing component Iμ I o2 I 2w 0.62 0.182 Iμ = 0.57A No load phasor diagram R.Thiyagarajan AP/EEE Page 12 4 . Explain the method of conducting OC and SC test on a transformer with neat diagram. [NOV/DEC 2011] The circuit constants, efficiency and voltage regulation of a transformer can be determined by two simple tests (i) open-circuit test and (ii) short-circuit lest. These tests are very convenient as they provide the required information without actually loading the transformer. Further, the power required to carry out these tests is very small as compared with full-load output of the transformer. These tests consist of measuring the input voltage, current and power to the primary first with secondary open-circuited (open- circuit test) and then with the secondary short-circuited (short circuit test). Open-Circuit or No-Load Test: This test is conducted to determine the iron losses (or core losses) and parameters R0 and X0 of the transformer. In this test, the rated voltage is applied to the primary (usually low-voltage winding) while the secondary is left open circuited. The applied primary voltage V1 is measured by the voltmeter, the no-load current I0 by ammeter and noload input power W0 by wattmeter as shown in Fig. ((i)). As the normal rated voltage is applied to the primary, therefore, normal iron losses will occur in the transformer core. Hence wattmeter will record R.Thiyagarajan AP/EEE Page 13 the iron losses and small copper loss in the primary. Since no-load current I0 is very small (usually 2-10 % of rated current). Cu losses in the primary under no-load condition are negligible as compared with iron losses. Hence, wattmeter reading practically gives the iron losses in the transformer. It is reminded that iron losses are the same at all loads. Fig. (ii)) shows the equivalent circuit of transformer on noload. Iron losses, Pi = Wattmeter reading = W0 No load current = Ammeter reading = I0 Applied voltage = Voltmeter reading = V1 Input power, W0 = V1 I0 cos f0 Short-Circuit or Impedance Test: This test is conducted to determine R01 (or R02), X01 (or X02) and fullload copper losses of the transformer. In this test, the secondary R.Thiyagarajan AP/EEE Page 14 (usually low-voltage winding) is short-circuited by a thick conductor and variable low voltage is applied to the primary as shown in Fig. (i). The low input voltage is gradually raised till at voltage VSC, fullload current I1 flows in the primary. Then I2 in the secondary also has full-load value since I1/I2 = N2/N1. Under such conditions, the copper loss in the windings is the same as that on full load. There is no output from the transformer under short-circuit conditions. Therefore, input power is all loss and this loss is almost entirely copper loss. It is because iron loss in the core is negligibly small since the voltage V SC is very small. Hence, the wattmeter will practically register the fullload copper losses in the transformer windings. Fig. (ii) shows the equivalent circuit of a transformer on short circuit as referred to primary; the no-load current being neglected due to its smallness. Full load Cu loss, PC = Wattmeter reading = WS Applied voltage = Voltmeter reading = VSC F.L. primary current = Ammeter reading = I1 R.Thiyagarajan AP/EEE Page 15 Note: The short-circuit test will give full-load Cu loss only if the applied voltage VSC is such so as to circulate full-load currents in the windings. If in a short circuit test, current value is other than full-load value, the Cu loss will be corresponding to that current value. Advantages of Transformer Tests The above two simple transformer tests offer the following advantages: (i) The power required to carry out these tests is very small as compared to the full-load output of the transformer. In case of opencircuit lest, power required is equal to the iron loss whereas for a short-circuit test, power required is equal to full-load copper loss. (ii) These tests enable us to determine the efficiency of the transformer accurately at any load and p.f. without actually loading the transformer (iii) The short-circuit test enables us to determine R01 and X01 (or R02 and X02). We can thus find the total voltage drop in the transformer as R.Thiyagarajan AP/EEE Page 16 referred to primary or secondary. This permits us to calculate voltage regulation of the transformer. 5. (a) List the various parts of transformer. Also explain the constructional features of a transformer [MAY/JUNE 11] Various parts of transformer 1. Transformer tank 2. Transformer oil 3. Core 4. Winding 5. Conservator 6. Breather CONSTRUCTION OF A TRANSFORMER We usually design a power transformer so that it approaches the characteristics of an ideal transformer. To achieve this, following design features are incorporated: R.Thiyagarajan AP/EEE Page 17 (i) The core is made of silicon steel which has low hysteresis loss and high permeability. Further, core is laminated in order to reduce eddy current loss. These features considerably reduce the iron losses and the no-load current. (ii) Instead of placing primary on one limb and secondary on the other, it is a usual practice to wind one-half of each winding on one limb. This ensures tight coupling between the two windings. Consequently, leakage flux is considerably reduced. (iii) The winding resistances R1 and R2 are minimized to reduce I2R loss and resulting rise in temperature and to ensure high efficiency. TYPES OF TRANSFORMERS: Depending upon the manner in which the primary and secondary are wound on the core, transformers are of two types viz., (i) core-type transformer and (ii) shell-type transformer. (I) Core-type transformer. In a core-type transformer, half of the primary winding and half of the secondary winding are placed round each limb as shown in Fig. This reduces the leakage flux. It is a usual practice to place the low-voltage winding below the highvoltage winding for mechanical considerations. R.Thiyagarajan AP/EEE Page 18 (II) Shell-type transformer. This method of construction involves the use of a double magnetic circuit. Both the windings are placed round the central limb (See Fig, the other two limbs acting simply as a low-reluctance flux path. The choice of type (whether core or shell) will not greatly affect the efficiency of the transformer. The core type is generally more suitable for high voltage and small output while the shell-type is generally more suitable for low voltage and high output. R.Thiyagarajan AP/EEE Page 19 6. A 100 KVA transformer has iron loss of 720 Watts and full load copper loss of 2100 Watts. Determine its efficiency at full load at unity power factor and 0.8 power lagging. [MAY/JUNE 11] Given data: Transformer rating = 100 kVA, Iron loss Pi=720 W Full load copper loss Pcufl = 2100 W, Power factor cos =0.8 To find: Full load efficiency %η nkVA cosΦ 100 nkVA cosΦ Pi Pcufl Here n = 1 (for full load) % % 1 100 103 0.8 1 100 103 0.8 720 2100 100 96.59 7. (a) Draw the phasor diagram for an ideal transformer with resistive and inductive load. [MAY/JUNE 11] An ideal transformer is one that has (i) No winding resistance R.Thiyagarajan AP/EEE Page 20 (ii) No leakage flux i.e., the same flux links both the windings (iii) No iron losses (i.e., eddy current and hysteresis losses) in the core Although ideal transformer cannot be physically realized, yet its study provides a very powerful tool in the analysis of a practical transformer. In fact, practical transformers have properties that approach very close to an ideal transformer. Consider an ideal transformer on no load i.e., secondary is opencircuited. Under such conditions, the primary is simply a coil of pure inductance. When an alternating voltage V1 is applied to the primary, it draws a small magnetizing current Im which lags behind the applied voltage by 90°. This alternating current Im produces an alternating flux which is proportional to and in phase with it. The alternating flux links both the windings and induces e.m.f. E1 in the primary and e.m.f. E2 in the secondary. The primary e.m.f. E1 is, at every instant, equal to and in opposition to V1 (Lenz’s law). Both e.m.f.s E1 and E2 lag behind flux by 90°. However, their magnitudes depend upon the number of primary and secondary turns. Fig. (ii) shows the R.Thiyagarajan AP/EEE Page 21 phasor diagram of an ideal transformer on no load. Since flux is common to both the windings, it has been taken as the reference phasor. The primary e.m.f. E1 and secondary e.m.f. E2 lag behind the flux by 90 V1 and 180° out of phase with it. 7. The emf induced per turn of a single phase 11000 V/ 440 V, 50Hz single phase transformer approximately 11 volts. Calculate the number of turns in high voltage and low voltage windings and the net cross sectional area of the core for maximum flux density of 1.5 Tesla. [MAY/JUNE 11] Given data: Emf per turn = 11 V, Primary voltage = 11000 V, Secondary = 440 V, Frequency f = 50 Hz, Maximum flux density Bm = 1.5 T. R.Thiyagarajan AP/EEE Page 22 To find: Number turns in the HV and LV windings, Net cross sectional area Solution: E1 = N1 X emf induced/turn N1 = 11000/11 =1100 turn N2 = E2/Emf inducedper turn =440/11 N2 = 40 turns E1 = 4.44 f N1 Bm A A = E1/4.44 f N1 Bm = 4.44 11000 50 1100 1.5 A = 0.030 cm2 8. Derive the emf equation of a transformer. [NOV/DEC 2010] EMF Equation of Transformer: Since applied voltage is alternating in nature, the flux established is also an alternating one. It is clear that the flux is attaining its maximum value in one quarter of the cycle i.e., T/4 sec where ‘T’ is the time period in second. R.Thiyagarajan AP/EEE Page 23 We know that T= 1/f Φm Average rate of change of flux = 1 wb/seconds 4f Form factor = R.M .S value Average value 1.11 RMS value of induced emf/turn =(1.11) x (4f x m ) RMS value of induced emf in the entire primary winding E1= 4.44f m xN1 RMS value of induced emf in the entire primary winding E2= 4.44f m xN2 9. A single phase transformer is rated at 10 KVA, 50 Hz. The secondary rated voltage is 2400 V and the turn’s ratio is 10. The resistance and leakage reactance as referred to secondary are8.4 R.Thiyagarajan AP/EEE Page 24 and 13.7 respectively. Find voltage regulation at full – loaf and power factors of 0.8 lagging, 0.8 leading and unity. [NOV/DEC 2010] Given data: Transformer rating = 10 kVA Frequency = 50 Hz Turns ratio (K) = 10 Resistance referred to secondary R01 = 8.4 Ω Reactance referred to secondary X01 = 13.7 Ω To find: Full – load voltage regulation At 0.8 Lagging =? At 0.8 Leading =? At unity =? Solution: Secondary current (I2) = kVA 10000 = V2 2400 4.166 A Full – load voltage regulation at 0.8 lagging p.f cos R.Thiyagarajan AP/EEE = 0.8 Page 25 = cos-1 (0.8) = 36.86 Sin (36.86) = 0.6 % Voltage regulation = = I 2 (R 02 cos Φ X 02sin ) 100 V2 4.166 (8.4 0.8 13.7 0.6) 100 2400 = 2.59 % Full – load voltage regulation at 0.8 leading p.f % Voltage regulation = I 2 (R 02 cos Φ X 02sin ) 100 V2 4.166 (8.4 0.8 13.7 0.6) 100 = 2400 = - 0.260 % Full – load voltage regulation at unity p.f % Voltage regulation = = I 2 R02 cos V2 100 4.167 8.4 1 2400 = 1.45 % 10. A 30 KVA, 2000/200V single phase, 50Hz transformer has a primary resistance of 3.5 ohms and reactance of 4.5 ohms. The secondary resistance and reactance are 0.015 ohms and 0.02 ohms R.Thiyagarajan AP/EEE Page 26 respectively. Find the equivalent resistance, reactance and impedance (i) Referred to primary (ii) Referred to secondary side [APRIL/MAY 2010] Given data: Transformer rating = 30 kVA, Primary voltage V1 = 2000 V Secondary voltage V2 = 200 V, R1 = 3.5 Ω, X1 = 4.5 Ω, R2 = 0.015 Ω, X2 = 0.02 Ω To find: R01, X01, Z01, R02, X02, Z02 Transformation ratio K = V2/ V1=200/2000 =0.1 R01 = R1+ R!2 = R1+R2/K2 R01 = 3.5 + 0.015/0.12 R01 = 5 Ω X01 = X1 + X!2 = X1 + X2/K2 X01 = 4.5 + 0.02/0.12 X01 = 6.5 Ω Z01 = 2 R01 2 X 01 2 2 Z01 = 5 6.5 Z01 =8.2 Ω R.Thiyagarajan AP/EEE Page 27 R02 = R2+ R!1 = R2+R1 K2 R02 = 0.015 + 3.5 X 0.12 R02 = 0.05 Ω X02 = X2 + X!1 = X2 + X1 K2 X02 = 0.02 + 4.5 X 0.12 X02 = 0.065 Ω Z02 = 2 R02 2 X 02 Z01 = 0.052 0.0652 Z01 = 0.082 Ω R.Thiyagarajan AP/EEE Page 28