D-16110-001-A Bill Hussey 7/16/2015 Town of Greenwood Water Treatment Plant Electrical 16110 Raceways Submittals By Feazel Electrical Contracting - Electrical Contractor For Max Foote Construction - General Contractor BALAR Associates, Inc-Consulting Engineers PLASTI-BOND REDH2OT COATED GALVANIZED RIGID CONDUIT AND NIPPLES COATED CONDUIT Return To Index Print This Page COMPLIANCES FEATURES APPLICATION PVC Coated Galvanized Rigid Conduit Specifications PVC coated galvanized rigid conduit with red urethane interior coating protects conductors from mechanical damage and corrosive attack. Electrical continuity is maintained across assembled joints. Plasti-Bond REDH2OT... The Extra Distance in Protection from Corrosion • 40 mil gray PVC exterior coating • 2 mil red urethane interior coating • PROTECH threads – A clear urethane coating over hot galvanized threads • 12 trade sizes from 1/2" through 6" • Shipped in 10' lengths • Plastic thread protector caps are color coded for quick identification of conduit size. Thread Protection As a closed system, a coated conduit installation is only as good as its threaded joints. Plasti-Bond offers you ProTech™ a unique technology of hot galvanizing our conduit threads. This new system provides two important benefits to the user. First, the zinc coating coverage is consistently uniform. Second, the threads are hot galvanized after the conduit is PVC coated. This means that nothing in the PVC coating process can damage the zinc coating on the threads, delivering a “virgin thread” to the user. These features offer much improved corrosion protection for the new threads. After hot galvanizing, we apply a clear urethane topcoat to ensure the threads remain corrosion free before and after installation. Thread Protector Cap Colors: Black- for 1/2" sizes, 1/2", 1-1/2", 2-1/2", 3-1/2" Red- for 1/4" sizes, 3/4", 1-1/4" Blue- for even sizes, 1", 2", 3", 4", 5", 6" Steel and Aluminum • UL 6 (E2314); UL 6A (E98405) • CSA C22.2 No. 45 • PVC as the primary corrosion protection for steel conduit. The underlying zinc coating is a supplemental corrosion protection coating. Restricted for use with threaded fittings only. ETL VERIFIED PVC-001: The PVC coating adhesion performance of this product has been ETL verified to the Interek ETL SEMKO High Temperature H2O PVC Coating Adhesion Test Procedure for 200 hours. 1100 US Highway 271 South • Gilmer, TX 75644 APPROVAL STAMP 1 Phone: 903/843-5591 • www.plastibond.com Return To Index Print This Page PLASTI-BOND REDH2OT COATED CONDUIT AND NIPPLES Coated Conduit Technical Data COATED CONDUIT Metric Size Designators 16 21 27 35 41 53 63 78 91 103 129 155 Pipe Size Inches Catalog Number 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6" PRHCONDUIT-1/2 PRHCONDUIT-3/4 PRHCONDUIT-1 PRHCONDUIT-1-1/4 PRHCONDUIT-1-1/2 PRHCONDUIT-2 PRHCONDUIT-2-1/2 PRHCONDUIT-3 PRHCONDUIT-3-1/2 PRHCONDUIT-4 PRHCONDUIT-5 PRHCONDUIT-6 Outside Wall Thickness Inches Diameter With Coating Inches Internal Inside Diameter Inches Traverse Area Sq. Inches .104" .107" .126" .133" .138" .146" .193" .205" .215" .225" .245" .266" .920" 1.130" 1.395" 1.740" 1.980" 2.455" 2.955" 3.580" 4.080" 4.580" 5.643" 6.705" 0.632" 0.836" 1.063" 1.394" 1.624" 2.083" 2.489" 3.090" 3.570" 4.050" 5.073" 6.093" 0.314" 0.549" 0.887" 1.526" 2.071" 3.408" 4.866" 7.499" 10.010" 12.882" 20.212" 29.158" Nominal Weight 85 112 164 217 268 358 546 708 851 1009 1337 1993 Aluminum Catalog # PRCONDUIT-AL-1/2 PRCONDUIT-AL-3/4 PRCONDUIT-AL-1 PRCONDUIT-AL-1-1/4 PRCONDUIT-AL-1-1/2 PRCONDUIT-AL-2 PRCONDUIT-AL-2-1/2 PRCONDUIT-AL-3 PRCONDUIT-AL-3-1/2 PRCONDUIT-AL-4 PRCONDUIT-AL-5 PRCONDUIT-AL-6 COMPLIANCES FEATURES APPLICATION PLASTI-BOND REDH2 OT COATED NIPPLES PLASTI-BOND REDH2OT factory threaded nipples save you time and money in the field. Electrical continuity is maintained across assembled joints. *The exteriors of certain short nipples are coated with urethane in lieu of PVC. This is dictated by the manufacturing process as well as assembly considerations. • 40 mil gray PVC exterior coating • 2 mil red urethane interior and thread coating • 12 trade sizes from 1/2" through 6" • 11 standard lengths in available: Close, 2" to 12" • Made to order lengths available – Call for quote • Plastic thread protector caps are color coded for quick identification of conduit size. Thread Protector Cap Colors: Black- for 1/2" sizes, 1/2", 1-1/2", 2-1/2", 3-1/2" Red- for 1/4" sizes, 3/4", 1-1/4" Blue- for even sizes, 1", 2", 3", 4", 5", 6" Simple Steps To Ordering To order PLASTI-BOND coated nipples follow these simple steps to create a catalog number: 1. Determine Proper Prefix. • For steel conduit nipples use the prefix: PRHNIP• For aluminum conduit nipples use the prefix: PRNIP-AL- 2. Add the conduit trade size needed to your catalog prefix. Example - 1/2" coated steel nipple: PRHNIP-1/2 3 . Enter an “X” to represent “by” as in “2X4”. Example - PRHNIP-1/2X 4 . Enter the desired nipple length. Example - 10" PRHNIP-1/2X10 The catalog number for a Plasti-Bond coated steel, 1/2" nipple with a length of 10": PRHNIP-1/2X10 This number can then be looked up in the listing of pricing to determine price and availability. Call 903-843-5591 for custom orders, customer service and more information on Plasti-Bond REDH2OT. Steel and Aluminum • UL 6 (E2314); UL 6A (E98405) • CSA C22.2 No. 45 • PVC as the primary corrosion protection for steel conduit. The underlying zinc coating is a supplemental corrosion protection coating. Restricted for use with threaded fittings only. APPROVAL STAMP ETL VERIFIED: Plasti-Bond Nipples are manufactured from ETL-verified conduit. 1100 US Highway 271 South • Gilmer, TX 75644 (See online product submittal guide at www.plastibond.com) 2 Phone: 903/843-5591 • www.plastibond.com PLASTI-BOND REDH2OT COATED ELBOWS STANDARD RADIUS COATED ELBOWS Return To Index Print This Page COMPLIANCES FEATURES APPLICATION Coated Elbow Specifications Simple Steps To Ordering To order the PLASTI-BOND coated elbows follow these simple steps to creating a catalog number: PLASTI-BOND REDH2OT factory bent standard radius elbows are available and ready to ship. Factory bent elbows are more accurate, quicker to install and more economical, because they save field bending time and do not waste materials. Electrical continuity is maintained across assembled joints. 1. Determine Proper Prefix. • For steel conduit elbow use the prefix: PRHELB• For aluminum conduit elbow use the prefix: PRELB-AL- 2. Add the conduit trade size needed to your catalog prefix. Example - 1/2" steel conduit elbow: PRHELB-1/2 3 . Enter an “X” to represent “by” as in “2X4”. • 40 mil Gray PVC exterior coating • 2 mil Red urethane interior and thread coating • 12 trade sizes from 1/2" through 6" • Available in 90˚, 60˚, 45˚, and 30˚ bends • Plastic thread protector caps are color coded for quick identification of conduit size. Example - PRHELB-1/2X 4 . Enter the desired elbow degree of bend. Example - 45˚: PRHELB-1/2X45 For a coated steel, 1/2" elbow with a 45˚ bend, the catalog number would be: PRHELB 1/2X45 Thread Protector Cap Colors: Black- for 1/2" sizes, 1/2", 1-1/2", 2-1/2", 3-1/2" Red- for 1/4" sizes, 3/4", 1-1/4" Blue- for even sizes, 1", 2", 3", 4", 5", 6" STEP 5 AND 6 FOR CONFIGURING CATALOG NUMBERS FOR LARGE RADIUS ELBOWS 5 . Enter an “X” to represent “by” as in “2X4”. Example - PRHELB-1/2X45X 6 . Enter the desired elbow radius. Steel and Aluminum • UL 6 (E2314); UL 6A (E98405) • CSA C22.2 No. 45 • PVC as the primary corrosion protection for steel conduit. The underlying zinc coating is a supplemental corrosion protection coating. Restricted for use with threaded fittings only. Example - 30: PRHELB-1/2X45X30 For a coated steel, 1/2" elbow with a 45˚ bend, and a special radius of 30" the catalog number would be: PRHELB-1/2X45X30 This number can then be looked up in the listing of pricing to determine price and availability. Call 903-843-5591 for custom orders, customer service and more information on Plasti-Bond REDH2OT. ETL VERIFIED: Plasti-Bond Elbows are manufactured from ETL-verified conduit. APPROVAL STAMP (See online product submittal guide at www.plastibond.com) 1100 US Highway 271 South • Gilmer, TX 75644 3 Phone: 903/843-5591 • www.plastibond.com Return To Index Print This Page STANDARD RADIUS COATED ELBOWS Dimensions Diagram Legend A = Radius at inside of bend. TANGENT A B = Radius at center line of bend. B C C = Radius at outside of bend. D = Offset at inside of bend. E = Offset at center of bend. D E F = Offset at outside of bend. F STANDARD RADIUS ELBOWS DIAMETERS RADII OFFSET Metric Size Designators Nominal Size Inches External Inches Internal Inches Nipple Lengths Inches A Inches (standard) B Inches C Inches D Inches E Inches F Inches Tangent Inches 16 21 27 35 41 53 63 78 91 103 129 155 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6" 0.920" 1.130" 1.395" 1.740" 1.980" 2.455" 2.955" 3.580" 4.080" 4.580" 5.643" 6.705" 0.632" 0.836" 1.063" 1.394" 1.624" 2.083" 2.489" 3.080" 3.570" 4.050" 5.073" 6.093" 11-1/4" 12-1/2" 14-3/4" 17-3/4" 19-3/4" 22-1/2" 28" 32" 39-1/2" 39-1/2" 59-1/2" 76" 3.79" 3.94" 5.05" 6.38" 7.26" 8.27" 9.02" 11.21" 12.96" 13.71" 21.18" 26.65" 4.25" 4.50" 5.75" 7.25" 8.25" 9.50" 10.50" 13.00" 15.00" 16.00" 24.00" 30.00" 4.71" 5.07" 6.45" 8.12" 9.24" 10.73" 11.98" 14.79" 17.04" 18.29" 26.82" 33.35" 6.040" 6.685" 7.928" 9.567" 10.635" 12.086" 14.776" 17.000" 20.920" 20.890" 32.079" 41.088" 6.500" 7.250" 8.625" 10.437" 11.625" 13.313" 16.253" 18.790" 22.960" 23.180" 34.900" 44.440" 6.960" 7.815" 9.323" 11.307" 12.615" 14.541" 17.731" 20.580" 25.000" 25.470" 37.722" 47.793" 2.250" 2.750" 2.875" 3.187" 3.375" 3.813" 5.753" 5.790" 7.960" 7.180" 10.900" 14.440" PLASTI-BOND REDH2OT factory bent elbows are also available in larger than standard radii to accommodate your special needs. Simply follow the four steps for standard radius elbows on the previous page, then continue with Steps 5 and 6 for large radius elbows. Refer to the table below to determine which radius is available for the size of conduit you need. To use the Large Radius Elbow table, find the elbow radius required in the first row. Then look down the column to determine which conduit sizes are available in that radius. Use this information in Steps 5 and 6 on the previous page to build a catalog number. LARGE RADIUS ELBOWS Radius B in Inches E Offset Nipple Length Tangent Available Pipe Sizes 12" 15" 18" 1'5-1/2" 1'9-1/4" 2'1/4" 18" 2'3" 24" 2'8" 24" 2'10" 30" 3'4" 30" 3'5" 36" 3'11" 36" 36" 42" 3'11-1/4" 4'3-1/4" 4'5" 42" 4'6" 42" 4'9-1/2" 48" 5'1/4" 48" 48" 5'1-1/4" 5'3-1/4" 2'6" 5-1/2" 1" & 2" 3'10" 9" 1-1/2" to 3" 4'6" 8" 3/4" to 2" 4'9" 10" 2-1/2" to 5" 5'6" 10" 2" to 3" 5'9" 11" 4" to 6" 6'7" 11" 3/4" to 4" 6'7" 11-1/4" 7'3" 15-1/4" 7'4" 11" 7'6" 12" 8'1" 15-1/2" 8'6" 13-1/4" 8'10" 15-1/4" 5" only 6" only 4" 5" only n/a 8'4" 12-1/4" 1-1/2" to 4" 5" only 6" only 3'0" 6-1/4" 3'5" 6-1/4" 2" 1" 1100 US Highway 271 South • Gilmer, TX 75644 4 Phone: 903/843-5591 • www.plastibond.com PLASTI-BOND REDH2OT CONDUIT THREAD AND COUPLING COATED COUPLINGS Print This Page Return To Index APPLICATION PVC Coating on Conduit PVC Sleeve L2 E0 • 40 mil gray PVC exterior coating • 2 mil red urethane interior coating over galvanized threads • 12 trade sizes from 1/2” through 6” • Sealing sleeves on both ends • Molded external ribs on 1/2 ” – 4” to prevent tool damage during assembly • Couplings are straight tapped COMPLIANCES PVC Coating on Coupling PVC coated rigid metal conduit couplings with red urethane interior coating connects coated conduit sections. Electrical continuity is maintained across assembled joints. PVC sleeves on couplings seal off on conduit PVC coating when assembled to prevent corrosive liquids and vapors from attacking threaded joints. FEATURES Thread and Coupling Specifications See “Thread and Coupling Technical Data” for reference. L4 All female pipe openings are provided with a PVC sleeve sized to fit tightly over the PVC coated conduit when assembled. This prevents corrosives from contacting threaded joints. Steel and Aluminum • UL 6 (E2314); UL 6A (E98405) • CSA C22.2 No. 45 Thread and Coupling Technical Data COUPLING THREADS Metric Size Designators Pipe Size Inches Steel Catalog # 16 21 27 35 41 53 63 78 91 103 129 155 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6" PRCPLG-1/2 PRCPLG-3/4 PRCPLG-1 PRCPLG-1-1/4 PRCPLG-1-1/2 PRCPLG-2 PRCPLG-2-1/2 PRCPLG-3 PRCPLG-3-1/2 PRCPLG-4 PRCPLG-5 PRCPLG-6 Nominal Weight Per 100 (Pounds) Outside Diameter With Ribs Inches Threads Per Inch 19 32 40 50 69 93 123 217 422 391 550 884 1.344" 1.531" 1.781" 2.156" 2.469" 2.969" 3.594" 4.250" 4.875" 5.250" 6.080" 7.280" 14 14 11-1/2 11-1/2 11-1/2 11-1/2 8 8 8 8 8 8 Pitch At End of Thread 3/4 in. Taper E0 .5337" .5457" .6828" .7068" .7235" .7565" 1.1375" 1.2000" 1.2500" 1.3000" 1.4063" 1.5125" .7815" .7935" .9845" 1.0085" 1.0252" 1.0582" 1.5712" 1.6337" 1.6837" 1.7337" 1.8400" 1.9462" .7584" .9677" 1.2136" 1.5571" 1.7961" 2.2690" 2.7195" 3.3406" 3.8375" 4.3344" 5.3907" 6.4461" Aluminum Catalog # PRCPLG-AL-1/2 PRCPLG-AL-3/4 PRCPLG-AL-1 PRCPLG-AL-1-1/4 PRCPLG-AL-1-1/2 PRCPLG-AL-2 PRCPLG-AL-2-1/2 PRCPLG-AL-3 PRCPLG-AL-3-1/2 PRCPLG-AL-4 PRCPLG-AL-5 PRCPLG-AL-6 APPROVAL STAMP Couplings are straight tapped. Tolerance, thread length =± 1 thread. Plus or minus 1 turn is the maximum variation permitted from the gauging face of the working thread gauges. This is equivalent to plus or minus 1 and 1-1/2 turns from the basic dimensions, since the variation of plus or minus 1/2 turn from basic dimension is permitted in working gauges. 1100 US Highway 271 South • Gilmer, TX 75644 Effective Length L2 Total Length of Threads to Vanish Point L4 (See online product submittal guide at www.plastibond.com) 6 Phone: 903/843-5591 • www.plastibond.com 52 /53 Series Liquidtight Fittings and Flexible Metallic Conduits Liquidtight Flexible Metal Conduit Fittings ® ® Body, Gland, Locknut & Ground Cones: Steel ( ⁄4"–1 ⁄4") or malleable iron (11⁄2"–6") •To positively bond conduit to box or enclosure Sealing Ring and Insulator: All thermoplastic Standard Material 5331-5361-5271 Series 1 1 Sealing Gasket: Stainless Steel and Santoprene® Features •Ability to install quickly with low torque effort 5331SST-5331SSTHT Series •Ground cone design offers the following advantages: Sealing Ring and Insulator: All thermoplastic (1)Compresses metallic convolutions; provides highquality ground contact with low impedance and high raceway holding power (A) 5231 AL Series (2)Single helical thread on ground cone is easy to install without cross thread; accepts variations in raceway diameters and convolution pitch (B) Standard Finish (3) Rolled-over edge protects conductors (C) Electro Zinc Plated with Chromate Coating Sealing Ring Design Features 5331ST-5331STH Series (1)Grips and seals at leading and trailing edge — will not abrade raceway jacket (D) Electro Zinc Plated with Chromate Coating (2)Provided with grooves on inside diameter for anti-sleeving (E) Copper-free Aluminum (3) Shoulders on both ends for extra sealing (F) Range (4) Symmetrical shape assures foolproof assembly 5331 Series................... 3⁄8" through 6"* conduit •Can be disconnected and reused 5341 Series..................... 3⁄8" through 4" conduit •Watertight/oil-tight installation at box or enclosure termination is ensured by: 304 Stainless Steel insulated 5361 Series Sealing Gasket: Stainless Steel and Santoprene ® All Copper-free Aluminum (non-insulated) 5331-5361-5271 Series 5231 AL Series 5271 Series.................. 3⁄8" through 11⁄4" conduit (2) Captivated sealing O-Ring on 5361 series (H) 5331SSTHT Series........... 3⁄8" through 2" conduit (3) Taper tapped hole on 5271 series 5231 AL Series................ 3⁄8" through 4" conduit • Suitable for use in Class I Division 2, Class II Division 1 and 2 and Class III Division 1 and 2 Hazardous Locations per NEC® Section 500 *All hubs provided with taper pipe threads (NPT) • Conforms with JIC requirements •Available with imperial, ISO and PG threaded hub * 5341 Series… same as 5331, except 45° Connectors 5351 Series… same as 5331, except 90° Connectors 5361 Series..................... 3⁄8" through 4" conduit 5331SST Series............... 3⁄8" through 2" conduit •1⁄2" & 11⁄4" sizes laboratory tested to carry ground fault current of up to 1,000 amps RMS with duration of fault current three cycles 5271 Series 5351 Series..................... 3⁄8" through 4" conduit (1)External taper thread hub on 5331 series and use of sealing gasket 5262 series (G) • Suitable as a grounding means per NEC Section 351-9 (up to 11⁄4" trade size on) 5331 Series* 5231 AL Series Conduit & Fittings — T&B® Liquidtight Fittings Application • Used where flexible metal raceway is installed in outdoor or indoor locations where exposed to continuous or intermittent moisture Predetermined Compression Listings/Compliances UL UL File No. E-23018 (H) CSA LR-2884, LR-4484, LR-9555 UL 514B CSA C22.2 No. 18 NEMA FB-1 NFPA 70-1999 (ANSI) 5361 Series CHASE ® Style JIC EGP1 JIC EMP1 Federal Specification A-A-50552 Federal Standard H-28 (Threads) NEC and National Electrical Code are registered trademarks of the National Fire Protection Association, Inc. Santoprene is a registered trademark of Advanced Elastomer Systems. www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 E-5 Titan® - Type UL Corrected per engineers notes (Liquidtight Flexible Metal Conduit) Liquidtight Flexible Metal Conduit. UL Listed. CSA Listed. Oil-Resistant. Sunlight-Resistant. Temperature Rated -30°C to 80°C. APPLICATIONS Titan® Type UL Liquidtight Flexible Metal Conduit is suitable of the following installations: • • • • • • • • • For the installation and protection of electrical conductors in circuits of 600 Volts nominal, or less Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment Where the conditions of installation, operation, or maintenance require flexibility or protection from liquids, vapors, solids, or weather Applications requiring movement, crossover connections, or tight bends Exposed or concealed locations For use as a grounding conductor per NEC® 250.118(7) For flexible connections to swimming pool, spa, and hot tub motors per 2011 NEC® 680.21(A)(3) & 680.42(A)(1) Electric signs and outline lighting supply and secondary-circuit per 2011 NEC® 600.31 (1000 Volts or less) & NEC® 600.32 (over 1000 Volts) For use in Hazardous locations - see Additional Applications Section on following page for more details STANDARDS & REFERENCES • • • • NEC® Type designation - Type LFMC (Liquidtight Flexible Metal Conduit) ANSI / NFPA-70, NEC Article 350 UL Listed to Underwriters Laboratories Standard ANSI / UL-360 for Liquidtight Flexible Steel Conduit CSA Listed to CSA 22.2 No.56 for use per the Canadian Electrical Code C22.1 Section 12-1300 CONSTRUCTION Titan® Type UL is manufactured with a spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steel. For 3/8" through 1-1/4" trade sizes, the core is constructed with a square locked steel strip with an integral copper-bonding strip enclosed within the steel convolutions. For 1-1/2" through 4" trade sizes, the core is constructed with a fully interlocked steel strip. A rugged, flame retardant, flexible PVC jacket is extruded over the steel core. The grey jacket resists oils, mild acids and exposure to sunlight. Also available in other colors subject to minimum runs. Tue Jan 24 10:38:59 EST 2012 Page 1 of 4 Titan - Type UL Trade Size (Inches) Approximate Weight (lbs/100 ft) Inner Diameter Min./Max. (inches) Outer Diameter Min./Max. (inches) Approx. Bend Radius* (Inches) Standard Coil Length (feet) Standard ReelLength (feet) 3/8 27 0.484 / 0.504 0.690 / 0.710 4 100 600 1/2 31 0.622 / 0.642 0.820 / 0.840 4 100 500/1000 3/4 40 0.820 / 0.840 1.030 / 1.050 5 100 500/1000 1 76 1.041 / 1.066 1.290 / 1.315 6 100 400 1-1/4 102 1.380 / 1.410 1.630 / 1.660 8 50 250 1-1/2 103 1.575 / 1.600 1.865 / 1.900 10 50 150 2 145 2.020 / 2.045 2.340 / 2.375 12 50 100 2-1/2 197 2.480 / 2.505 2.840 / 2.875 15 25 100 3 265 3.070 / 3.100 3.460 / 3.500 18 25 - 3-1/2 300 3.500 / 3.540 3.960 / 4.000 21 25 - 4 333 4.000 / 4.040 4.460 / 4.500 24 25 - * Minimum bend radius based on NEC Chapter 9, Table 2 (other bends) per Article 350. FEATURES • • • • • • A protective thermoplastic outer jacket which seals out water, liquids, abrasives, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, nonconcentrated fixed alkalines, petroleum oils, salt air and spray, and weather Smooth metal interior for easy wiring pulling UV sunlight resistant jacket Rated for temperature range of -30°C to 80°C, 60°C Oil (-22°F to +176°F, 140°F Oil) Accepts standard metallic liquidtight fittings Rated for direct burial applications including concrete encasement ADDITIONAL APPLICATIONS • • • • • In Hazardous Locations - where necessary for flexible connections within hazardous locations in accordance with the following: - Class I, Div. 2 - NEC® 501.10(B)(2) & 501.30(B) - Class II, Div. 1 - NEC® 502.10(A)(2) & 502.30(B) - Class II, Div. 2 - NEC® 502.10(B)(2) - Class III, Div. 1 - NEC® 503.10(A)(2) & 503.30(B) - Class III, Div. 2 - NEC® 503.10(A)(2) Permitted for equipment grounding in sizes 3/8" through 1-1/4" in lengths not exceeding 6 feet per NEC® 250.118(6) Floating building feeders and services per NEC® 553.7(B) Boatyards & Marinas in accordance with NEC® 555.13 Cranes & Hoists in accordance with NEC® 610.11(C) Tue Jan 24 10:38:59 EST 2012 Page 3 of 4 Titan - Type UL • • • For Elevator, Dumbwaiters, Escalators, Moving Walks, Wheel Chair Lifts & Stairway Chair Lifts in accordance with NEC® 620.21 (where expressly permitted) Under raised floors in data processing areas per NEC® 645.5(D) & 645.5(D)(2) Service entrance in lengths up to six feet per NEC® 230.43(15) ONLINE CERTIFICATIONS AND TOOLS • • • • UL Online Certifications Directory ( www.ul.com ) CSA Online Certifications Directory ( www.csa.ca ) UL Guide Information - Flexible Metal Conduit, Liquidtight (DXHR) CSA Product Information - Conduit-Flexible Metal, Liquidtight Conduit (1812-03) Tue Jan 24 10:38:59 EST 2012 Page 4 of 4 52 /53 Series Liquidtight Fittings and Flexible Metallic Conduits Conduit & Fittings — T&B® Liquidtight Fittings ® ® High-quality, corrosion-resistant, liquidtight termination for LTA flexible aluminum conduit. 52 Series Liquidtight Aluminum Connectors — Straight and 90° ® B A C Liquidtight Aluminum Fitting — 90° Angle B Liquidtight Aluminum Fitting — A Straight C .................................... Specifications.................................... Standard Material • Body, Gland, Locknut...................................................................6061 Aluminum • Sealing Ring...................................................................................Thermoplastic • Ground Cone................................................................................................Steel Standard Finish • Body, Gland, Locknut..................Zinc Plating with Clear Chromate Ground Cones • Ground Cone......................................................................... Electro-Zinc Plating Designed to resist corrosion. LTA Flexible Aluminum Conduit Use T&B® LTA Flexible Aluminum Conduit with T&B Aluminum Liquidtight Fittings in corrosive environments or where weight is a major consideration — such as oil platforms, saltwater applications, pulp and paper, refineries, wastewater and food processing. .................................... Specifications.................................... Cat. No. Straight 5231AL 5232AL 5233AL 5234AL 5235AL 5236AL 5237AL 5238AL 5239AL 5240AL 90° Angle 5251AL 5252AL 5253AL 5254AL 5255AL 5256AL 5257AL E-8 Dimensions (in.) Conduit Size (in.) A B C ⁄8 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 15⁄32 13⁄8 121⁄32 17⁄8 29⁄32 222⁄32 31⁄4 33⁄4 41⁄2 51⁄2 11⁄2 19⁄16 15⁄8 21⁄16 21⁄2 211⁄16 31⁄16 41⁄8 41⁄4 41⁄2 ⁄16 ⁄16 9 ⁄16 3 ⁄4 13 ⁄16 13 ⁄16 7 ⁄8 1 1 11⁄8 3 1 ⁄8 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 3 1 15⁄32 13⁄8 121⁄32 17⁄8 29⁄32 223⁄32 31⁄4 13⁄8 19⁄16 13⁄4 23⁄16 23⁄4 215⁄16 37⁄16 United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 9 9 ⁄16 ⁄16 9 ⁄16 3 ⁄4 13 ⁄16 13 ⁄16 7 ⁄8 9 9 • Construction: Utilizes the flexibility of a lightweight aluminum core, coupled with the advantage of a PVC jacket that is virtually unaffected by sunlight, acid and oil. WEEE and RoHS compliant • Application: Used in situations where concerns of excessive weight and corrosion exist • Standard Color: Machine tool gray • Working Temperature­: -20° C to +80° C • Standard Materials/Finish: Conduit Core — Aluminum; Outer Jacket — PVC • UL Listed Cat. NO. LTA50-100 LTA75-100 LTA100-100 LTA125-50 LTA150-50 LTA200-50 LTA250-25 LTA300-25 LTA400-25 Technical Services Tel: 888.862.3289 Conduit Size (in.) Length (ft.) ⁄2 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 100 100 100 50 50 50 25 25 25 1 3 Inside Bend Wt. (lbs.)/ Radius (in.) 100 ft. 2.5 3.0 4.0 4.5 5.5 7.0 9.5 11.5 14 www.tnb.com 15 20 29 — — — 188 244 332 Wt. (lbs.)/ 50 ft. — — — 20 28 36.5 — — — Tab 3 Rigid Aluminum Conduit !"#$%%&'#()*+,-'./(''001021%3''&405'67''689:'0 Recommended Installation Practices Why Rigid Aluminum Conduit? Costs Less Than Steel Cutting – A hacksaw is recommended for trade sizes 1 1/4 and smaller. Power cut-off equipment is recommended for larger trade sizes. • Cost Per Foot Savings of 10-20% Versus Rigid Steel Bending – Standard EMT benders, one size larger than the size of the conduit, should be used on conduit trade sizes 1 and smaller. Conventional equipment is recommended for larger trade sizes. Lower Installation Cost Threading – Sharp dies and conventional cutting oil should be used. • • • • Fishing and Wire Pulling Fittings – Aluminum fittings are recommended, but cadmium-plated or galvanized fittings are satisfactory for most installations. Labor Savings of 35-75% Versus Rigid Steel 1/3 the Weight of Rigid Steel Conduit Less Chance of a Workers Compensation Injury Easy Field Fabrication Small Conduit – In trade sizes 11/2 and smaller and on shorter runs (up to 100 feet), polyethylene fish tapes and round, flexible, speedometer-type steel cables are recommended. Use of flat steel tapes should be avoided. Large Conduit – For larger conduit or longer runs, polypropylene rope is recommended. Explosion Proof • Replaces Rigid Steel in Virtually All Locations • Non-Sparking • Aluminum Conduit Meets All National Electrical Codes – Article 500 Hazardous Area Requirements • No Toxic Fumes Soil or Concrete Installation – Underwriters’ Laboratories Electrical Construction Equipment Directory (UL Green Book) states that aluminum conduit used in concrete or in contact with soil requires supplemental corrosion protection. Examples are paints and tape wraps approved for the purpose, or PVC coated conduit. Nationwide Distribution Network Superior Attractive Appearance • Corrosion Resistant Oxide Film • No Rust or Unsightly Discoloration or Streaking WA ME MT Non-Magnetic ND MN VT OR • Protection for Sensitive Environments • Power Savings Over the Life of the Installation Why Buy From Sapa? OH IN IL UT CO KS WV TN OK AZ AR NM Quality – QC Systems that Surpass Industry Standards TX Cost – We Extrude and Thread In-House Experience – Over 35 Years Manufacturing Nationwide Distribution – 33 Representative AK SC MS AL GA LA FL HI Organizations, 20 with Stocking Warehouses VA NC Sapa Extrusions Rigid Aluminum Conduit 1512 Industry Drive Burlington, NC 27215 Phone: 800-334-6825 or 336-227-8826 Fax: 336-229-5968 www.sapagroup.com RI CT NJ MD KY MO NH MA PA IA NE NV Supported by Sapa’s North American Technical Center NY MI WY CA Support – Training Programs and Personnel Service – Dedicated Customer Service Department Technology – Design and Product Solutions WI SD ID DE !"#$%%&'#()*+,-'./(''001021%3''&405'67''689:'; Tolerances and Specifications 3+8" :5,+%'6)!+.")3+8" @;A;)J) <'66 @1&-+0" A+',"&"# 7+%; 7'K; Composition of Aluminum Alloy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igid Aluminum Conduit Weight Chart Decision-makers — use the obvious choice for a code approved, UL listed, lightweight, lower cost rigid metal conduit, ALUMINUM! !"#$"%&'(")*+,+&-)."# /%01-&#2)3&'%0'#0- S61,+%1,)$5%01+&T P2.+$'6)!"#$"%&'("- !"#$"%&'(")*+,+&-)."# /%01-&#2)3&'%0'#0- FEET S61,+%1,)$5%01+&T P2.+$'6)!"#$"%&'("- A B C L B Rigid Aluminum Couplings 3&'%0'#0 !'$9'(+%( :5,;)<&=>?? !$-; @;A;)+% /%$B"- *"%(&B)+% /%$B"- 3+8" >=CD H77 K H(N(EOK8 H(N(DOHK E=FD E7 D H(N(CHOK8 HN(EOL 3&'%0'#0 !'$9'(+%( :5,;)<&=>?? !$-; S /%$B"- M /%$B"- 4 /%$B"- >=CD E7 CK 8(N K(N(HOC E=FD E7 ML 8(N(HOC 3/4" 37 1" 55 72 89 2" 119 2-1/2" 188 3" 246 3-1/2" 296 4" 350 5" 479 6" 630 200 56 75 109 143 177 237 375 493 591 700 958 1261 1891 300 84 112 164 215 266 356 563 739 887 1051 1437 747C 4B#5,+1, 74H7(&#$4 747H 400 112 150 218 286 355 474 750 985 1182 1401 1916 2522 3+6+$5% 74C7(*2(74K 7487 P+&'%+1, 74H7(&#$4 747H 500 141 187 273 358 444 593 938 1232 1478 1751 2395 3152 /#5% 74ME(&#$4 74C7 R+%$ 74H7(&#$4 747C 600 169 224 327 430 532 711 1125 1478 1774 2101 2873 3782 7'(%"-+1, 748E(*2(74D 74P7 @&B"#- 74HE(&#$ W:#3, 700 197 262 382 501 621 830 1313 1724 2069 2451 3352 4413 7'%('%"-" 47H7(&#$4 747H S61,+%1, V,&#%1<,: V,&#%1<,: 800 225 299 436 573 710 948 1500 1970 2365 2802 3831 5043 900 253 337 491 644 798 1067 1688 2217 2660 3152 4310 5674 1000 281 374 545 716 887 1185 1875 2463 2956 3502 4789 6304 1100 309 411 600 788 976 1304 2063 2709 3252 3852 5268 6934 1200 337 449 654 859 1064 1422 2250 2956 3547 4202 5747 7565 1300 365 486 709 931 1153 1541 2438 3202 3843 4553 6226 8195 1400 393 524 763 1002 1242 1659 2625 3448 4138 4903 6705 8826 1500 422 561 818 1074 1331 1778 2813 3695 4434 5253 7184 9456 1600 450 598 872 1146 1419 1896 3000 3941 4730 5603 7662 10086 1700 478 636 927 1217 1508 2015 3188 4187 5025 5953 8141 10717 1800 506 673 981 1289 1596 2133 3375 4433 5321 6304 8620 11347 1900 534 711 1036 1360 1685 2252 3563 4680 5616 6654 9099 11978 2000 562 748 1090 1432 1774 2370 3750 4926 5912 7004 9578 12608 2500 703 935 1363 1790 2218 2963 4688 6158 7390 8755 11973 15760 3000 843 1122 1635 2148 2661 3555 5625 7389 8868 10506 14367 18912 3500 984 1309 1908 2506 3105 4148 6563 8620 10346 12257 16762 22064 4000 1124 1496 2180 2864 3548 4740 7500 9852 11824 14008 19156 25216 4500 1265 1683 2453 3222 3992 5333 8438 11084 13302 15759 21551 28368 5000 1405 1870 2725 3580 4435 5925 9375 12315 14780 17510 23945 31520 6000 1686 2244 3270 4296 5322 7110 11250 14778 17736 21012 28734 37824 7000 1967 2618 3815 5012 6209 8295 13125 17241 20692 24514 33523 44128 8000 2248 2992 4360 5728 7096 9480 15000 19704 23648 28016 38312 50432 56736 ! "#$%&'&()%&%*(+,*(-.(*/,(0)'&%1'&(0++23%#*%214(0))2.+(5%*/('6(*2(74879(3266,:(#:,(#33,6*#-),(*2(;1<,:5:%*,:+(=#-2:#*2:%,+>(?134(@2:('+,(%1(:%A%<( #)'&%1'&(321<'%*B(*.6%3#)(321<'%*('+,+(21).(747C>(2:(DE9(),++4(F#6#(321<'%*(%+(#:2'1<(747789>(5/%3/(%+(G'+*(#(*:#3,(#1<(321+%<,:,<(*2(-,(3266,:(@:,,4 Rigid Aluminum Elbows (standard radius only) 3+8" 1-1/2" 28 74H7(&#$(! S6652U K7KM(0)'&%1'&(0))2.>(WNH(*,&6,:4(TY2:&,:(<,+%A1#*%21(WN8CU 3."$+L+$'&+5%)45,.6+'%$"U Y,<,:#)(F6,3%@%3#*%21(ZZN[NE8734 ;1<,:5:%*,:+R =#-2:#*2:%,+(;=NK0>()#*,+*(:,\%+%21 0&,:%3#1(]#*%21#)(F*#1<#:<+(?1+*%*'*,(T0]F?U([L74E [#1#<%#1(F*#1<#:<(0++23%#*%21([F0 [(CC4C(]24(8E PB#"'0)!#5&"$&5#-U V%A%<(0)'&%1'&([21<'%*(%+(+/%66,<(5%*/(32)2:(32<,<( */:,#<(6:2*,3*2:+>(5/%3/(+/%,)<(*/:,#<+>(#1<(+%&6)%@.(+%^,(+,),3*%214 C 1/2" 45.."# F6,3%@%3#*%21(X#*# O.D. 1-1/4" 100 Manufacturer’s ID/Part# Part # Coupling Size Part # 90º Elbow Size Part # 45º Elbow Size Part # C(N(HOC Conduit Size P(N(HO8 C(N(MO8 1/2" !"#!$"!#"## 1/2" $"#!$ 1/2" %"#!$ 1/2" %"#!$"&' >D E7 HC HN(DOHK C(N >D CE K8 E(N(MO8 L(N(MOL( C(N(POL 3/4" !"#%&"!#"## 3/4" $"#%& 3/4" %"#%& 3/4" %"#%&"&' 9000 2529 3366 4905 6444 7983 10665 16875 22167 26604 31518 43101 >G>=FD E7 HL HN((KHOK8 C(N(HOHK >G>=FD C7 H77 P(N(HO8 H7(N(HO8 M((N 1" !"!##"!#"## 1" $"!## 1" %"!## 1" %"!##"&' 10000 2810 3740 5450 7160 8870 11850 18750 24630 29560 35020 47890 63040 >G>=CD E7 CM C(N(POMC C(N(HOHK >G>=CD H7 H87 L(N(HO8 HH(N(POL M(N(EOL 1-1/4" !"!!&"!#"## 1-1/4" $"!!& 1-1/4" %"!!& 1-1/4" %"!!&"&' 15000 4215 5610 8175 10740 13305 17775 28125 36945 44340 52530 71835 94560 CD E7 MM C(N(MO8 C(N(HOL CD H7 CMK D(N(HOC H8((N 8(N(HOC 1-1/2" !"!!$"!#"## 1-1/2" $"!!$ 1-1/2" %"!!$ 1-1/2" %"!!$"&' 20000 5620 7480 10900 14320 17740 23700 37500 49260 59120 70040 95780 126080 CG>=CD CE KD M(N(DOMC M(N(HOL CG>=CD H7 877 H7(N(HOC HE(N(MO8( E(N(HO8 2" !"$##"!#"## 2" $"$## 2" %"$## 2" %"$##"&' 25000 7025 9350 13625 17900 22175 29625 46875 61575 73900 87550 119725 157600 ED CE DC M(N(HEOHK M(N(HO8 ED H7 K88 HM((N HL(N(MO8 E(N(MO8 2-1/2" !"$!$"!#"## 2-1/2" $"$!$ 2-1/2" %"$!$ 2-1/2" %"$!$"&' 30000 8430 11220 16350 21480 26610 35550 56250 73890 88680 105060 143670 189120 EG>=CD H7 H7E 8(N(POHK M(N(MOL EG>=CD E L88 HE((N CH(N(MO8 K(N(MO8 3" !"%##"!#"## 3" $"%## 3" %"%## 3" %"%##"&' 35000 9835 13090 19075 25060 31045 41475 65625 86205 103460 122570 167615 220640 FD H7 H8C E((N M(N(HOC FD E H7EE HK((N CM((N P((N 3-1/2" !"%!$"!#"## 3-1/2" $"%!$ 3-1/2" %"%!$ 3-1/2" %"%!$"&' 40000 11240 14960 21800 28640 35480 47400 75000 98520 118240 140080 191560 252160 HD E CM8 K(N(HDOK8 M(N(MO8 HD I;=J CME7 C8((N MK((N HH((N 4" !"&##"!#"## 4" $"&## 4" %"&## 4" %"&##"&' ID I;=J MHL PN((CEOK8 8((N ID I;=J MP77 M7((N 8C(N(HOC HC(N(HOC 5" !"'##"!#"## 5" $"'## 5" %"'## 5" %"'##"&' 6" !"(##"!#"## 6" $"(## 6" %"(## 6" %"(##"&' !"#$%%&'#()*+,-'./(''001021%3''&405'67''689:'; Tolerances and Specifications 3+8" :5,+%'6)!+.")3+8" @;A;)J) <'66 @1&-+0" A+',"&"# 7+%; 7'K; Composition of Aluminum Alloy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igid Aluminum Conduit Weight Chart Decision-makers — use the obvious choice for a code approved, UL listed, lightweight, lower cost rigid metal conduit, ALUMINUM! !"#$"%&'(")*+,+&-)."# /%01-&#2)3&'%0'#0- S61,+%1,)$5%01+&T P2.+$'6)!"#$"%&'("- !"#$"%&'(")*+,+&-)."# /%01-&#2)3&'%0'#0- FEET S61,+%1,)$5%01+&T P2.+$'6)!"#$"%&'("- A B C L B Rigid Aluminum Couplings 3&'%0'#0 !'$9'(+%( :5,;)<&=>?? !$-; @;A;)+% /%$B"- *"%(&B)+% /%$B"- 3+8" >=CD H77 K H(N(EOK8 H(N(DOHK E=FD E7 D H(N(CHOK8 HN(EOL 3&'%0'#0 !'$9'(+%( :5,;)<&=>?? !$-; S /%$B"- M /%$B"- 4 /%$B"- >=CD E7 CK 8(N K(N(HOC E=FD E7 ML 8(N(HOC 3/4" 37 1" 55 72 89 2" 119 2-1/2" 188 3" 246 3-1/2" 296 4" 350 5" 479 6" 630 200 56 75 109 143 177 237 375 493 591 700 958 1261 1891 300 84 112 164 215 266 356 563 739 887 1051 1437 747C 4B#5,+1, 74H7(&#$4 747H 400 112 150 218 286 355 474 750 985 1182 1401 1916 2522 3+6+$5% 74C7(*2(74K 7487 P+&'%+1, 74H7(&#$4 747H 500 141 187 273 358 444 593 938 1232 1478 1751 2395 3152 /#5% 74ME(&#$4 74C7 R+%$ 74H7(&#$4 747C 600 169 224 327 430 532 711 1125 1478 1774 2101 2873 3782 7'(%"-+1, 748E(*2(74D 74P7 @&B"#- 74HE(&#$ W:#3, 700 197 262 382 501 621 830 1313 1724 2069 2451 3352 4413 7'%('%"-" 47H7(&#$4 747H S61,+%1, V,&#%1<,: V,&#%1<,: 800 225 299 436 573 710 948 1500 1970 2365 2802 3831 5043 900 253 337 491 644 798 1067 1688 2217 2660 3152 4310 5674 1000 281 374 545 716 887 1185 1875 2463 2956 3502 4789 6304 1100 309 411 600 788 976 1304 2063 2709 3252 3852 5268 6934 1200 337 449 654 859 1064 1422 2250 2956 3547 4202 5747 7565 1300 365 486 709 931 1153 1541 2438 3202 3843 4553 6226 8195 1400 393 524 763 1002 1242 1659 2625 3448 4138 4903 6705 8826 1500 422 561 818 1074 1331 1778 2813 3695 4434 5253 7184 9456 1600 450 598 872 1146 1419 1896 3000 3941 4730 5603 7662 10086 1700 478 636 927 1217 1508 2015 3188 4187 5025 5953 8141 10717 1800 506 673 981 1289 1596 2133 3375 4433 5321 6304 8620 11347 1900 534 711 1036 1360 1685 2252 3563 4680 5616 6654 9099 11978 2000 562 748 1090 1432 1774 2370 3750 4926 5912 7004 9578 12608 2500 703 935 1363 1790 2218 2963 4688 6158 7390 8755 11973 15760 3000 843 1122 1635 2148 2661 3555 5625 7389 8868 10506 14367 18912 3500 984 1309 1908 2506 3105 4148 6563 8620 10346 12257 16762 22064 4000 1124 1496 2180 2864 3548 4740 7500 9852 11824 14008 19156 25216 4500 1265 1683 2453 3222 3992 5333 8438 11084 13302 15759 21551 28368 5000 1405 1870 2725 3580 4435 5925 9375 12315 14780 17510 23945 31520 6000 1686 2244 3270 4296 5322 7110 11250 14778 17736 21012 28734 37824 7000 1967 2618 3815 5012 6209 8295 13125 17241 20692 24514 33523 44128 8000 2248 2992 4360 5728 7096 9480 15000 19704 23648 28016 38312 50432 56736 ! "#$%&'&()%&%*(+,*(-.(*/,(0)'&%1'&(0++23%#*%214(0))2.+(5%*/('6(*2(74879(3266,:(#:,(#33,6*#-),(*2(;1<,:5:%*,:+(=#-2:#*2:%,+>(?134(@2:('+,(%1(:%A%<( #)'&%1'&(321<'%*B(*.6%3#)(321<'%*('+,+(21).(747C>(2:(DE9(),++4(F#6#(321<'%*(%+(#:2'1<(747789>(5/%3/(%+(G'+*(#(*:#3,(#1<(321+%<,:,<(*2(-,(3266,:(@:,,4 Rigid Aluminum Elbows (standard radius only) 3+8" 1-1/2" 28 74H7(&#$(! S6652U K7KM(0)'&%1'&(0))2.>(WNH(*,&6,:4(TY2:&,:(<,+%A1#*%21(WN8CU 3."$+L+$'&+5%)45,.6+'%$"U Y,<,:#)(F6,3%@%3#*%21(ZZN[NE8734 ;1<,:5:%*,:+R =#-2:#*2:%,+(;=NK0>()#*,+*(:,\%+%21 0&,:%3#1(]#*%21#)(F*#1<#:<+(?1+*%*'*,(T0]F?U([L74E [#1#<%#1(F*#1<#:<(0++23%#*%21([F0 [(CC4C(]24(8E PB#"'0)!#5&"$&5#-U V%A%<(0)'&%1'&([21<'%*(%+(+/%66,<(5%*/(32)2:(32<,<( */:,#<(6:2*,3*2:+>(5/%3/(+/%,)<(*/:,#<+>(#1<(+%&6)%@.(+%^,(+,),3*%214 C 1/2" 45.."# F6,3%@%3#*%21(X#*# O.D. 1-1/4" 100 Manufacturer’s ID/Part# Part # Coupling Size Part # 90º Elbow Size Part # 45º Elbow Size Part # C(N(HOC Conduit Size P(N(HO8 C(N(MO8 1/2" !"#!$"!#"## 1/2" $"#!$ 1/2" %"#!$ 1/2" %"#!$"&' >D E7 HC HN(DOHK C(N >D CE K8 E(N(MO8 L(N(MOL( C(N(POL 3/4" !"#%&"!#"## 3/4" $"#%& 3/4" %"#%& 3/4" %"#%&"&' 9000 2529 3366 4905 6444 7983 10665 16875 22167 26604 31518 43101 >G>=FD E7 HL HN((KHOK8 C(N(HOHK >G>=FD C7 H77 P(N(HO8 H7(N(HO8 M((N 1" !"!##"!#"## 1" $"!## 1" %"!## 1" %"!##"&' 10000 2810 3740 5450 7160 8870 11850 18750 24630 29560 35020 47890 63040 >G>=CD E7 CM C(N(POMC C(N(HOHK >G>=CD H7 H87 L(N(HO8 HH(N(POL M(N(EOL 1-1/4" !"!!&"!#"## 1-1/4" $"!!& 1-1/4" %"!!& 1-1/4" %"!!&"&' 15000 4215 5610 8175 10740 13305 17775 28125 36945 44340 52530 71835 94560 CD E7 MM C(N(MO8 C(N(HOL CD H7 CMK D(N(HOC H8((N 8(N(HOC 1-1/2" !"!!$"!#"## 1-1/2" $"!!$ 1-1/2" %"!!$ 1-1/2" %"!!$"&' 20000 5620 7480 10900 14320 17740 23700 37500 49260 59120 70040 95780 126080 CG>=CD CE KD M(N(DOMC M(N(HOL CG>=CD H7 877 H7(N(HOC HE(N(MO8( E(N(HO8 2" !"$##"!#"## 2" $"$## 2" %"$## 2" %"$##"&' 25000 7025 9350 13625 17900 22175 29625 46875 61575 73900 87550 119725 157600 ED CE DC M(N(HEOHK M(N(HO8 ED H7 K88 HM((N HL(N(MO8 E(N(MO8 2-1/2" !"$!$"!#"## 2-1/2" $"$!$ 2-1/2" %"$!$ 2-1/2" %"$!$"&' 30000 8430 11220 16350 21480 26610 35550 56250 73890 88680 105060 143670 189120 EG>=CD H7 H7E 8(N(POHK M(N(MOL EG>=CD E L88 HE((N CH(N(MO8 K(N(MO8 3" !"%##"!#"## 3" $"%## 3" %"%## 3" %"%##"&' 35000 9835 13090 19075 25060 31045 41475 65625 86205 103460 122570 167615 220640 FD H7 H8C E((N M(N(HOC FD E H7EE HK((N CM((N P((N 3-1/2" !"%!$"!#"## 3-1/2" $"%!$ 3-1/2" %"%!$ 3-1/2" %"%!$"&' 40000 11240 14960 21800 28640 35480 47400 75000 98520 118240 140080 191560 252160 HD E CM8 K(N(HDOK8 M(N(MO8 HD I;=J CME7 C8((N MK((N HH((N 4" !"&##"!#"## 4" $"&## 4" %"&## 4" %"&##"&' ID I;=J MHL PN((CEOK8 8((N ID I;=J MP77 M7((N 8C(N(HOC HC(N(HOC 5" !"'##"!#"## 5" $"'## 5" %"'## 5" %"'##"&' 6" !"(##"!#"## 6" $"(## 6" %"(## 6" %"(##"&' !"#$%%&'#()*+,-'./(''001021%3''&405'67''689:'; Tolerances and Specifications 3+8" :5,+%'6)!+.")3+8" @;A;)J) <'66 @1&-+0" A+',"&"# 7+%; 7'K; Composition of Aluminum Alloy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igid Aluminum Conduit Weight Chart Decision-makers — use the obvious choice for a code approved, UL listed, lightweight, lower cost rigid metal conduit, ALUMINUM! !"#$"%&'(")*+,+&-)."# /%01-&#2)3&'%0'#0- S61,+%1,)$5%01+&T P2.+$'6)!"#$"%&'("- !"#$"%&'(")*+,+&-)."# /%01-&#2)3&'%0'#0- FEET S61,+%1,)$5%01+&T P2.+$'6)!"#$"%&'("- A B C L B Rigid Aluminum Couplings 3&'%0'#0 !'$9'(+%( :5,;)<&=>?? !$-; @;A;)+% /%$B"- *"%(&B)+% /%$B"- 3+8" >=CD H77 K H(N(EOK8 H(N(DOHK E=FD E7 D H(N(CHOK8 HN(EOL 3&'%0'#0 !'$9'(+%( :5,;)<&=>?? !$-; S /%$B"- M /%$B"- 4 /%$B"- >=CD E7 CK 8(N K(N(HOC E=FD E7 ML 8(N(HOC 3/4" 37 1" 55 72 89 2" 119 2-1/2" 188 3" 246 3-1/2" 296 4" 350 5" 479 6" 630 200 56 75 109 143 177 237 375 493 591 700 958 1261 1891 300 84 112 164 215 266 356 563 739 887 1051 1437 747C 4B#5,+1, 74H7(&#$4 747H 400 112 150 218 286 355 474 750 985 1182 1401 1916 2522 3+6+$5% 74C7(*2(74K 7487 P+&'%+1, 74H7(&#$4 747H 500 141 187 273 358 444 593 938 1232 1478 1751 2395 3152 /#5% 74ME(&#$4 74C7 R+%$ 74H7(&#$4 747C 600 169 224 327 430 532 711 1125 1478 1774 2101 2873 3782 7'(%"-+1, 748E(*2(74D 74P7 @&B"#- 74HE(&#$ W:#3, 700 197 262 382 501 621 830 1313 1724 2069 2451 3352 4413 7'%('%"-" 47H7(&#$4 747H S61,+%1, V,&#%1<,: V,&#%1<,: 800 225 299 436 573 710 948 1500 1970 2365 2802 3831 5043 900 253 337 491 644 798 1067 1688 2217 2660 3152 4310 5674 1000 281 374 545 716 887 1185 1875 2463 2956 3502 4789 6304 1100 309 411 600 788 976 1304 2063 2709 3252 3852 5268 6934 1200 337 449 654 859 1064 1422 2250 2956 3547 4202 5747 7565 1300 365 486 709 931 1153 1541 2438 3202 3843 4553 6226 8195 1400 393 524 763 1002 1242 1659 2625 3448 4138 4903 6705 8826 1500 422 561 818 1074 1331 1778 2813 3695 4434 5253 7184 9456 1600 450 598 872 1146 1419 1896 3000 3941 4730 5603 7662 10086 1700 478 636 927 1217 1508 2015 3188 4187 5025 5953 8141 10717 1800 506 673 981 1289 1596 2133 3375 4433 5321 6304 8620 11347 1900 534 711 1036 1360 1685 2252 3563 4680 5616 6654 9099 11978 2000 562 748 1090 1432 1774 2370 3750 4926 5912 7004 9578 12608 2500 703 935 1363 1790 2218 2963 4688 6158 7390 8755 11973 15760 3000 843 1122 1635 2148 2661 3555 5625 7389 8868 10506 14367 18912 3500 984 1309 1908 2506 3105 4148 6563 8620 10346 12257 16762 22064 4000 1124 1496 2180 2864 3548 4740 7500 9852 11824 14008 19156 25216 4500 1265 1683 2453 3222 3992 5333 8438 11084 13302 15759 21551 28368 5000 1405 1870 2725 3580 4435 5925 9375 12315 14780 17510 23945 31520 6000 1686 2244 3270 4296 5322 7110 11250 14778 17736 21012 28734 37824 7000 1967 2618 3815 5012 6209 8295 13125 17241 20692 24514 33523 44128 8000 2248 2992 4360 5728 7096 9480 15000 19704 23648 28016 38312 50432 56736 ! "#$%&'&()%&%*(+,*(-.(*/,(0)'&%1'&(0++23%#*%214(0))2.+(5%*/('6(*2(74879(3266,:(#:,(#33,6*#-),(*2(;1<,:5:%*,:+(=#-2:#*2:%,+>(?134(@2:('+,(%1(:%A%<( #)'&%1'&(321<'%*B(*.6%3#)(321<'%*('+,+(21).(747C>(2:(DE9(),++4(F#6#(321<'%*(%+(#:2'1<(747789>(5/%3/(%+(G'+*(#(*:#3,(#1<(321+%<,:,<(*2(-,(3266,:(@:,,4 Rigid Aluminum Elbows (standard radius only) 3+8" 1-1/2" 28 74H7(&#$(! S6652U K7KM(0)'&%1'&(0))2.>(WNH(*,&6,:4(TY2:&,:(<,+%A1#*%21(WN8CU 3."$+L+$'&+5%)45,.6+'%$"U Y,<,:#)(F6,3%@%3#*%21(ZZN[NE8734 ;1<,:5:%*,:+R =#-2:#*2:%,+(;=NK0>()#*,+*(:,\%+%21 0&,:%3#1(]#*%21#)(F*#1<#:<+(?1+*%*'*,(T0]F?U([L74E [#1#<%#1(F*#1<#:<(0++23%#*%21([F0 [(CC4C(]24(8E PB#"'0)!#5&"$&5#-U V%A%<(0)'&%1'&([21<'%*(%+(+/%66,<(5%*/(32)2:(32<,<( */:,#<(6:2*,3*2:+>(5/%3/(+/%,)<(*/:,#<+>(#1<(+%&6)%@.(+%^,(+,),3*%214 C 1/2" 45.."# F6,3%@%3#*%21(X#*# O.D. 1-1/4" 100 Manufacturer’s ID/Part# Part # Coupling Size Part # 90º Elbow Size Part # 45º Elbow Size Part # C(N(HOC Conduit Size P(N(HO8 C(N(MO8 1/2" !"#!$"!#"## 1/2" $"#!$ 1/2" %"#!$ 1/2" %"#!$"&' >D E7 HC HN(DOHK C(N >D CE K8 E(N(MO8 L(N(MOL( C(N(POL 3/4" !"#%&"!#"## 3/4" $"#%& 3/4" %"#%& 3/4" %"#%&"&' 9000 2529 3366 4905 6444 7983 10665 16875 22167 26604 31518 43101 >G>=FD E7 HL HN((KHOK8 C(N(HOHK >G>=FD C7 H77 P(N(HO8 H7(N(HO8 M((N 1" !"!##"!#"## 1" $"!## 1" %"!## 1" %"!##"&' 10000 2810 3740 5450 7160 8870 11850 18750 24630 29560 35020 47890 63040 >G>=CD E7 CM C(N(POMC C(N(HOHK >G>=CD H7 H87 L(N(HO8 HH(N(POL M(N(EOL 1-1/4" !"!!&"!#"## 1-1/4" $"!!& 1-1/4" %"!!& 1-1/4" %"!!&"&' 15000 4215 5610 8175 10740 13305 17775 28125 36945 44340 52530 71835 94560 CD E7 MM C(N(MO8 C(N(HOL CD H7 CMK D(N(HOC H8((N 8(N(HOC 1-1/2" !"!!$"!#"## 1-1/2" $"!!$ 1-1/2" %"!!$ 1-1/2" %"!!$"&' 20000 5620 7480 10900 14320 17740 23700 37500 49260 59120 70040 95780 126080 CG>=CD CE KD M(N(DOMC M(N(HOL CG>=CD H7 877 H7(N(HOC HE(N(MO8( E(N(HO8 2" !"$##"!#"## 2" $"$## 2" %"$## 2" %"$##"&' 25000 7025 9350 13625 17900 22175 29625 46875 61575 73900 87550 119725 157600 ED CE DC M(N(HEOHK M(N(HO8 ED H7 K88 HM((N HL(N(MO8 E(N(MO8 2-1/2" !"$!$"!#"## 2-1/2" $"$!$ 2-1/2" %"$!$ 2-1/2" %"$!$"&' 30000 8430 11220 16350 21480 26610 35550 56250 73890 88680 105060 143670 189120 EG>=CD H7 H7E 8(N(POHK M(N(MOL EG>=CD E L88 HE((N CH(N(MO8 K(N(MO8 3" !"%##"!#"## 3" $"%## 3" %"%## 3" %"%##"&' 35000 9835 13090 19075 25060 31045 41475 65625 86205 103460 122570 167615 220640 FD H7 H8C E((N M(N(HOC FD E H7EE HK((N CM((N P((N 3-1/2" !"%!$"!#"## 3-1/2" $"%!$ 3-1/2" %"%!$ 3-1/2" %"%!$"&' 40000 11240 14960 21800 28640 35480 47400 75000 98520 118240 140080 191560 252160 HD E CM8 K(N(HDOK8 M(N(MO8 HD I;=J CME7 C8((N MK((N HH((N 4" !"&##"!#"## 4" $"&## 4" %"&## 4" %"&##"&' ID I;=J MHL PN((CEOK8 8((N ID I;=J MP77 M7((N 8C(N(HOC HC(N(HOC 5" !"'##"!#"## 5" $"'## 5" %"'## 5" %"'##"&' 6" !"(##"!#"## 6" $"(## 6" %"(## 6" %"(##"&' Rigid Non Metallic Schedule 40 Electrical Conduit April 18, 2012 Heritage Plastics created the long bell for ease and efficiency. In compliance with the industry standards, Heritage Plastics PVC Electrical Conduit is manufactured from virgin PVC compounds complying with the UL651 standards as described in the standards specifications for rigid PVC compounds ASTM D 1784-81. Our PVC Electrical Conduits are subject to in-process quality control to assure compliance with appropriate manufacturing and performance standards. · · · · · · · UL 651 RUS Listed NEMA TC-2 NEMA TC-3 (Accessories) UL Standard 514 B (Accessories) General Service Administration (GSA) WC 1094A National Electric Code - Article 352 Schedule 40 Electrical Conduit 10’ Part 20’ Part Nominal # # Size 510510 510520 ½” 510710 510720 ¾” 511010 511020 1” 511310 511320 1 ¼” 511510 511520 1 ½” 512010 512020 2” 512510 512520 2 ½” 513010 513020 3” 513510 513520 3 ½” 514010 514020 4” 515010 515020 5” 516010 516020 6” 861 N. Lisbon Street Carrollton, OH 44615 330.627.8002 Weight 100’ 16.4 21.8 32.1 43.4 51.8 69.5 109.6 143.5 169.1 204.3 277.6 360.0 Pack Qty 10’ 6,000’ 4,400’ 3,600’ 3,300’ 2,250’ 1,400’ 930’ 880’ 630’ 570’ 380’ 260’ 5128 West Hanna Ave. Tampa, FL 33634 330.627.8002 · · · · · Sunlight and Weather resistant Reduced emissions of smoke & HCL Listed for 90° C conductors or cable and direct sunlight Rigid nonmetallic raceway for wires and cables in accordance with the NEC Superior weathering characteristics O.D. I.D. Wall .840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625 .622 .824 1.049 1.380 1.610 2.067 2.469 3.068 3.548 4.026 5.047 6.065 .109 .113 .133 .140 .145 .154 .203 .216 .226 .237 .258 .280 1202 N. Bowie Drive Weatherford, TX 76086 817.594.8791 189 N. Heritage Park Dr. Milford, UT 84751 817.594.8791 Heritage Plastics Group COUPLINGS & ADAPTERS CLASS A FITTINGS COUPLINGS FEMALE ADAPTERS TERMINAL ADAPTERS Size Part # Package Qty Weight (lbs) UPC - A 694061 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 3 1/2” 4” 5” 6” 8" 59601 59602 59603 59604 59605 59606 59607 59608 59609 59610 59611 59612 59613 200 125 70 40 30 40 20 40 30 20 10 8 6 7 6 4 3 3 9 6 18 16 13 7 6 31 59601 5 59602 2 59603 9 59604 6 59605 3 59606 0 59607 7 59608 4 59609 1 59610 7 59611 4 59612 1 59613 8 UPC - A 694061 Size Part # Package Qty Weight (lbs) 1/2” 3/4” 1” 1 1/4” 1 1/2” 59630 59631 59632 59633 59634 200 125 70 40 30 7 6 4 3 4 59630 59631 59632 59633 59634 5 2 9 6 3 2” 2 1/2” 3” 3 1/2” 4” 5” 6” 8" 59635 59636 59637 59638 59639 59640 59641 59642 40 20 40 30 20 10 8 2 9 6 13 13 13 11 9 9 59635 59636 59637 59638 59639 59640 59641 59642 0 7 4 1 8 4 1 8 Size Part # Package Qty Weight (lbs) UPC - A 694061 1/2” 59615 200 5 59615 2 3/4” 59616 125 5 59616 9 1” 59617 70 3 59617 6 1 1/4” 59618 40 6 59618 3 1 1/2” 59619 30 5 59619 0 2” 59620 40 12 59620 6 2 1/2” 59621 20 11 59621 3 3” 59622 40 10 59622 0 3 1/2” 59623 30 21 59623 7 4” 59624 20 18 59624 4 5” 59625 10 16 59625 1 6” 59626 8 20 59626 8 8" 59627 2 9 59627 5 Page 4 Heritage Plastics Group Heritage Plastics Locations 861 N. Lisbon Street Carrollton, Ohio 5128 W. Hanna Avenue Tampa, Florida 1202 N. Bowie Drive Weatherford, Texas 189 N. Heritage Park Drive Milford, Utah Print version 2 11-01-09 COPYRIGHT© Heritage Plastics Inc. COOPER CROUSE-HINDS ® CONDUIT EXPANSION/ DEFLECTION COUPLINGS Installation Friendly Assembly FREE Internal Ground XJG XJG and XJG-EMT Conduit Expansion Joints Increase Productivity and Decrease Risk The assembly free XJG with internal ground eliminates the field assembly process. This advanced version of the XJG conduit expansion joint results in an increase in labor productivity and a decrease in installation complications. Internal Ground / Easy Installation / Weathertight These weathertight assembly free expansion joints employ our successful grounding system using metallic bushing with ground springs to create a high-integrity ground connection for telescoping conduit. 58127 SellSheet 1 6/28/06 1:22:08 PM CONDUIT EXPANSION/DEFLECTION COUPLINGS Applications Certifications and Compliances Assembly free XJG expansion/deflection couplings are used with rigid metal, IMC or EMT conduit to: • couple two sections of conduit subject to longitudinal movement with a pre-assembled XJG Fitting • maintain a ground connection without the need for an external bonding jumper and clamp • permit linear movement caused by thermal expansion and contraction in long conduit runs • facilitate expansion in both indoor and outdoor environments • prevent damage to conduit supports, such as in a building or on a bridge • UL Standard: 514 B • CSA Standard: C22.2 No. 18 • NEMA FB1 • Wet locations Bonding Jumper Optional bonding jumper provides redundant visible grounding Ordering Information Conduit Max. Conduit Cat. # Size Movement 1/2" Standard Materials • Body & washer—steel • Gland nut, reducer & bushing (1/2" - 1")—steel • Gland nut, reducer & bushing (1-1/4" - 4")— Feraloy® iron alloy • Packing—Teflon® • Gasket—vellum • Ground springs—phosphor bronze • Interlocking roll-pin—steel • Bonding jumper—tinned copper flexible braid • U-bolts—malleable iron 3/4" 1" 1-1/4" 1-1/2" Standard Finishes • Steel & phosphor bronze—electrogalvanized • Feraloy—electrogalvanized and aluminum acrylic paint • Copper-free aluminum, Teflon® & vellum—natural • Malleable iron—electrogalvanized 2" 2-1/2" Options Cutaway view showing our successful internal grounding mechanism and new interlocking roll pin feature that secures internal bushing during conduit installation, permitting factory complete XJG assembly. Standard product is for rigid and IMC conduit. For use with EMT conduit order catalog number with suffix—“EMT.” (See ordering infomation.) 3" 3-1/2" Available in copper-free aluminum (rigid and IMC versions only)—add suffix SA to Cat. # 4" Available with bonding jumper for redundant visible grounding—order separately 5" 6" Size Ranges • 1/2" - 6" conduit • 4" or 8" maximum conduit movement Teflon® is a registered trademark of EI DuPont Co. 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 4" 4" 8" 8" 8" XJG14 XJG14-EMT XJG18 XJG24 XJG24-EMT XJG28 XJG34 XJG34-EMT XJG38 XJG44 XJG44-EMT XJG48 XJG54 XJG54-EMT XJG58 XJG64 XJG64-EMT XJG68 XJG74 XJG74-EMT XJG78 XJG84 XJG84-EMT XJG88 XJG94 XJG94-EMT XJG98 XJG104 XJG104-EMT XJG108 XJ128 ‡ XJ148 ‡ Opt. Bonding Jumper Cat. # BJ14 BJ14 BJ18 BJ24 BJ24 BJ28 BJ34 BJ34 BJ38 BJ44 BJ44 BJ48 BJ54 BJ54 BJ58 BJ64 BJ64 BJ68 BJ74 BJ74 BJ78 BJ84 BJ84 BJ88 BJ94 BJ94 BJ98 BJ104 BJ104 BJ108 – – Dimensions Diameter Length 1-3/4" 1-3/4" 2-1/8" 2-1/8" 2-1/8" 2-1/4" 2-7/16" 2-7/16" 3-3/16" 3-3/16" 3-1/8" 3-11/16" 3-11/16" 3-5/8" 4-3/4" 4-3/4" 4-3/4" 4-7/8" 4-7/8" 4-7/8" 5-3/8" 5-3/8" 5-3/8" 6-5/8" 6-5/8" 6-5/8" 6-5/8" 6-5/8" 6-5/8" 6-5/8" 7.64" 9.56" 6-3/4" 10-3/4" 10-3/4" 6-3/4" 11" 10-3/4" 7-1/4" 11-1/2" 11-1/4" 7-9/16" 15-1/4" 11-9/16" 7-7/8" 15-1/4" 11-7/8" 8-1/4" 15-1/2" 12-1/4" 9-5/16" 18-3/4" 13-5/16" 10" 19-7/8" 14" 9-13/16" 20-5/8" 13-13/16" 9-13/16" 21-1/4" 13-13/16" 15.50" 16" ‡ XJ128 and XJ148 are not internally grounded. A pair of 36" bonding jumpers are provided with fitting. For more information: Contact an authorized Cooper Crouse-Hinds Distributor, Sales Office or Customer Service Department: Distributed by: In the U.S.: In Canada: Cooper Crouse-Hinds P.O. Box 4999 Syracuse, NY 13221 Toll Free: 866-764-5454 (315) 477-5531 FAX: (315) 477-5179 crouse.customerctr@crouse-hinds.com Cooper Crouse-Hinds Canada Toll Free: 800-265-0502 (905) 507-4187 FAX: (905) 568-7048 For office locations outside of North America or for additional product information, visit our website at: www.crouse-hinds.com Mexico • Latin America/Caribbean • Germany • Australia • Asia • Dubai • India Solutions.Worldwide.TM 4872-0606 58127 SellSheet 2 Crouse-Hinds is a registered trademark of Cooper Industries, Inc. © 2006 Cooper Industries, Inc. Printed in U.S.A 6/28/06 1:22:11 PM Tab 6 Rigid Aluminum Conduit Fittings 6-7.qxp 5/26/2011 11:07 PM 1F Page 6 Condulet® Conduit Bodies Cast Iron or Aluminum 1F Gasket and Covers see page 8 Applications: Certifications and Compliances: Conduit outlet bodies are installed in conduit systems to: Outlet Bodies – • UL Standard: 514B • Fed. Spec.: W-C-586D • CSA Standard 22.2 No. 18 • NEMA 3R Raintight (when installed with cover and gasket) • Act as pull outlets for conductors being installed • Provide openings for making splices and taps in conductors • Connect conduit sections • Provide taps for branch conduit runs • Make 90° bends in conduit runs Standard Materials: • Provide for access to conductors for maintenance and future system changes • • • • Features: Form 7, Form 8 outlet bodies – Feraloy iron alloy Mark 9 outlet bodies – copper-free aluminum Form 5 – malleable iron Series 5 – die cast aluminum Conduit Outlet Bodies • Form 7 Condulet outlet bodies approach conduit in size for neat, compact installations Standard Finishes: • Many shapes and sizes are available for rigid threaded conduit – for complete listings see pages 6–12 • Form 7, Form 8 outlet bodies – electrogalvanized with aluminum acrylic paint • Mark 9 outlet bodies – natural • Form 5 – electrogalvanized with aluminum acrylic paint • Series 5 – aluminum acrylic paint • Conduit hubs have tapered threads and feature integral bushings for protection of wire insulation Options: • Form 8 and Mark 9 bodies provide more room for heavier conductors • Form 7 has exclusive snaptight and wedgenut cover attachment to provide clear, unobstructed cover opening • Built-in rollers on all Form 5 11/4" to 4" C and LB bodies to facilitate wire pulling • Series 5 bodies available in optional configuration with set screws on hubs for EMT conduit (add suffix -MT to catalog number) Description Suffix Form 7 body and cover only: Copper-free aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SA Corro-free™ epoxy powder coat - external body only . . . . . . . . . S752 Corro-free™ epoxy powder coat - internal and external . . . . . . . S753 Series 5 in an EMT version with set screws on all hubs . . . . . . . MT Series 5 pre-packaged with neoprene gasket and cover . . . . . . CGN Gaskets Solid gaskets: • Are used with blank covers • For Mark 9 and Form 5, can be converted to open type gaskets by tearing out center section along scored lines – 1/2" to 2" sizes Form 7 • For Form 7 are used with all covers Open gaskets: • For Form 8 – 1/2" to 4" sizes • For Mark 9 – 21/2" to 4" sizes Blank Covers Mark 9 Stainless steel cover screws are standard on Form 7, Form 8, Mark 9, Series 5 and Form 5 covers. • Form 7 Wedge nut design facilitates installation and removal. Nuts are held captive in cover. Covers can be used with or without gaskets. SNAPTIGHT™ Form 7 Covers with integral sealing gaskets are installed without the use of screws, reducing installation time and costs. Covers are reusable. Form 8 • Form 8 Two cover screws provided on all sizes to provide tight cover and gasket assembly. Feraloy iron alloy covers have dome shapes for added strength and extra wiring room. • Mark 9 Mogul Self-retaining cover screws. 6 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 6-7.qxp 5/26/2011 11:07 PM Page 7 Condulet® Conduit Bodies Cast Iron or Aluminum 1F Dimensions Pgs. See pages 10–12 (Dimensions for Form 5 – see Section CP) Shape 1F Threaded Rigid Bodies Style C Form 7 Form 8 Mark 9 Form 5 Series 5 Hub Size 1 3 /2 /4 1 11/4 11/2 2 21/2 3 31/2 4 C17 C18 C19 C50M C15 C27 C28 C29 C75M C25 C37 C38 C39 C100M C35 C47 C448 C49 C125M* C45 C57 C58 C59 C150M* C55 C67 C68 C69 C200M* C65 C77 C78 C789 C250M* C75 C87 C88 C889 C300M* C85 C989 C350M* C95* C1089 C400M* C105* E Form 7 E17 E27 E37 L Form 7 L17 L27 L37 L47 L57 L67 Double faced – may be used as LL or LR – has 2 openings, one of which is furnished with a blank sheet steel cover LB Form 7 Form 8 Mark 9 Form 5 Series 5 LB17 LB18 LB19 LB50M LB15 LB27 LB28 LB29 LB75M LB25 LB37 LB38 LB39 LB100M LB35 LB47 LB448 LB49 LB125M* LB45 LB57 LB58 LB59 LB150M* LB55 LB67 LB68 LB69 LB200M* LB65 LB777 LB78 LB789 LB250M* LB75 LB87 LB888 LB889 LB300M* LB85 LB97 LB98 LB989 LB350M* LB95 LB107 LB108 LB1089 LB400M* LB105 LL Form 7 Form 8 Mark 9 Form 5 Series 5 LL17 LL18 LL19 LL50M LL15 LL27 LL28 LL29 LL75M LL25 LL37 LL38 LL39 LL100M LL35 LL47 LL448 LL49 LL125M LL45 LL57 LL58 LL59 LL150M LL55 LL67 LL68 LL69 LL200M LL65 LL777 LL78 LL789 LL250M LL75 LL87 LL888 LL889 LL300M LL85 LL97 LL107 LL989 LL350M LL95 LL1089 LL400M LL105 LR Form 7 Form 8 Mark 9 Form 5 Series 5 LR17 LR18 LR19 LR50M LR15 LR27 LR28 LR29 LR75M LR25 LR37 LR38 LR39 LR100M LR35 LR47 LR448 LR49 LR125M LR45 LR57 LR58 LR59 LR150M LR55 LR67 LR68 LR69 LR200M LR65 LR777 LR78 LR789 LR250M LR75 LR87 LR888 LR889 LR300M LR85 LR97 LR107 LR989 LR350M LR95 LR1089 LR400M LR105 T Form 7 Form 8 Mark 9 Form 5 Series 5 T17 T18 T19 T50M T15 T27 T28 T29 T75M T25 T37 T38 T39 T100M T35 T47 T448 T49 T125M T45 T57 T58 T59 T150M T55 T67 T68 T69 T200M T65 T77 T78 T789 T250M T75 T87 T88 T889 T300M T85 T97 T107 T989 T350M T95* T1089 T400M T105* TA Form 7 TA17 TA27 TA37 TA47 TA57 TA67 TB Form 7 Form 8 Mark 9 Series 5 Form 5 TB17 TB18 TB19 TB15 TB50M TB27 TB28 TB29 TB25 TB75M TB37 TB38 TB39 TB35 TB100M TB47 TB448 TB49 TB45 TB125M TB57 TB58 TB59 TB55 TB150M TB67 TB68 TB69 TB65 TB200M X Form 7 Form 8 Mark 9 Series 5 Form 5 X17 X18 X19 X15 X50M X27 X28 X29 X25 X75M X37 X38 X39 X35 X100M X47 X448 X57 X58 X67 X68 X45 X125M X55 X150M X65 X200M * 11/4" - 4" Form 5 LB and C bodies are supplied with built-in rollers to facilitate wire pulling. www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 7 1F Condulet® Conduit Bodies - Cast Iron or Aluminum 1F Covers and Gaskets Dimensions for Form 5 – see Section CP Blank Covers Sheet Steel Size Form 7 Wedgenut Cat. # /2 /4 1 11/4 11/2 2 21/2 3 31/2 4 170 270 370 470 570 670 870 870 970 970 1 3 Form 7 Snaptight™ Covers‡ Cat. # Form 7 Wedgenut w/Integral Gasket Cat. # 170SG 270SG 370SG 470SG 570SG 670SG 870G 170G 270G 370G 470G 570G 670G Form 8§ Cat. # 180 280 380 480 580 680 880 880 980 980 970G Form 8 w/Integral Gasket Cat. # Form 5 w/Integral Gasket** Cat. # 180G 280G 380G 480G 580G 680G K50SG K75SG K100SG K125SG K125SG K200SG K250SG K250SG K350SG K350SG ‡Form 7 Snaptight covers with integral sealing gasket are installed without the use of screws. §Two cover screws on 1/2" to 2" Form 8 covers and four cover screws on 21/2" and larger Form 8 covers. **For cover without integral gasket, remove G from catalog number. Sheet Aluminum Mark 9 Size Cat. # /2 /4 1 11/4 11/2 2 21/2 3 31/2 4 1 3 190 290 390 490 590 690 889 889 989 989 Mark 9 w/Integral Gasket Cat. # 190G 290G 390G 490G 590G 690G Form 7 Cat. # 170 270 370 470 570 670 870 870 970 970 SA SA SA SA SA SA SA SA SA SA Feraloy® Iron Alloy Form 7 w/Integral Gasket Cat. # Series 5 w/Integral Form 7 Gasket** Wedgenut Cat. # Cat. # 170G 270G 370G 470G 570G 670G 150 250 350 450 450 650 850 850 950 950 SA SA SA SA SA SA G G G G G G G G G G 170F 270F 370F 470F 570F 670F 870F 870F 970F 970F Form 7 Wedgenut w/Integral Gasket Cat. # 170FG 270FG 370FG 470FG 570FG 670FG Cast Aluminum Form 8§ Cat. # Form 5‡ Cat. # Form 7 Wedgenut Cat. # 180F 280F 380F 480F 580F 680F 880F 880F 980F 980F K50CM K75CM K100CM K125CM K125CM K200CM K250CM K250CM K350CM K350CM 170F 270F 370F 470F 570F 670F 870F 870F 970F 970F SA SA SA SA SA SA SA SA SA SA ‡Malleable iron covers. §Two cover screws on 1/2" to 2" Form 8 covers and four cover screws on 21/2" and larger Form 8 covers. **For cover without integral gasket, remove G from catalog number. Solid Gaskets - Neoprene Size Form 7 Cat. # Form 8* Cat. # Mark 9† Cat. # Form 5 Cat. # Series 5 Cat. # /2 /4 1 11/4 11/2 2 21/2 3 31/2 4 GASK571 GASK572 GASK573 GASK574 GASK575 GASK576 GASK578 GASK578 GASK579 GASK579 GASK851N GASK852N GASK853N GASK854N GASK805N GASK806N GASK808N GASK808N GASK809N GASK809N GASK1941 GASK1942 GASK1943 GASK1944 GASK1945 GASK1946 GASK808N GASK808N GASK809N GASK809N GK50N GK75N GK100N GK125N GK125N GK200N GK250N GK250N GK350N GK350N GASK015N GASK025N GASK035N GASK045N GASK045N GASK065N GASK085N GASK085N GASK095N GASK095N 1 3 *1/2 – 11/4 are solid gaskets; 11/2 – 4 are open gaskets. †1/2 – 2 are solid gaskets; 21/2 – 4 are open gaskets. 8 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2012 Cooper Crouse-Hinds Rigid and Intermediate Metal Conduit Fittings Available in your choice of steel/malleable iron, aluminum or stainless steel. Ensures positive bonding of conduit to box and prevents loosening due to vibration! Locknuts Bonding Locknuts A (B) Thickness (B) Thickness • Steel from 1⁄4" to 2", malleable iron from 21⁄2" to 6" • Aluminum 624 or Type 304 stainless steel all sizes CAT. NO. STL./M.I. ALUM. ST. STL. SIZE (IN.) 139* 140* 141** 142** 143 144 145 146 147 148 149 150 151 152 153 — — 141AL 142AL 143AL 144AL 145AL 146AL 147AL 148AL 149AL 150AL 151AL 152AL 153AL — — 141-SST 142-SST 143-SST 144-SST 145-SST 146-SST — — — — — — — ⁄4 3 ⁄8 1 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 41⁄2 5 6 DIMENSIONS (IN.) A B ⁄4 15 ⁄16 17⁄64 13⁄8 111⁄16 25⁄32 21⁄2 3 39⁄16 43⁄16 413⁄16 55⁄16 515⁄16 61⁄2 73⁄4 ⁄64 9 ⁄64 5 ⁄32 3 ⁄16 13 ⁄64 13 ⁄64 13 ⁄64 7 ⁄32 13 ⁄32 13 ⁄32 15 ⁄32 15 ⁄32 17 ⁄32 17 ⁄32 19 ⁄32 3 1 • Steel or malleable iron (steel through 2") 9 *Hex shape **Case hardened locknuts Aluminum locknuts comply with federal standard of copper-free aluminum; less than .5% copper. Available with DURA-PLATE ® Finish. UL File E-23018 • Can be used anywhere an ordinary locknut is installed • Also can be used for Service Entrance applications in conformance with code • T&B rigid conduit and EMT (thinwall) fittings comply with Federal Specification A-A-50553 DIMENSIONS (IN.) CAT. NO. SIZE (IN.) A B ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 13⁄8 15⁄8 115⁄16 25⁄32 21⁄2 3 313⁄32 413⁄16 429⁄32 57⁄32 .125 .140 .170 .170 .170 .187 .375 .375 .438 .438 106† 107† 108 109 110 111 112† 113† 114† 115† 1 UL File No. E-3060 CSA File No. 638 † Not CSA certified. Available with DURA-PLATE ® Finish. CSA File No. 2884 Provides positive seal against water and oil. Sealing Locknuts A CAT. NO. B C Molded Santoprene Seal Color: Blue • For use with rigid and intermediate metal conduits or fittings • Provides watertight or raintight seal at all enclosures 141SL 142SL 143SL 144SL 145SL 146SL SIZE (IN.) A DIMENSIONS (IN.) B C ⁄2 ⁄4 1 11⁄4 11⁄2 2 1.140 1.420 1.770 2.281 2.598 3.175 ⁄8 ⁄32 11 ⁄64 11 ⁄64 11 ⁄64 3 ⁄16 ⁄4 ⁄32 9 ⁄32 5 ⁄16 9 ⁄32 7 ⁄64 1 3 1 5 1 9 UL File No. E-23018 CSA File No. 2884 United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 www.tnb.com A-5 Rigid and Intermediate Metal Conduit Fittings Perfect for grounding old work or new! Bonding & Grounding Wedges • Provides grounding without a jumper except in concentric knockouts • When jumper is required, it fits under set screw in grounding wedge • Update existing installations to meet code requirements for bonding (NEC Sect. 250-72e) without disconnecting wiring Series 3650 • For use on new wiring, just loosen bushing, position wedge and tighten bushing and bonding screw Application • To effectively bond terminating fitting or conduit to a box or enclosure Features • Sizes 3⁄4" thru 6" equipped with an additional bonding screw to install bonding jumper where required Series 3651 • Can be added to an existing installation without disconnecting conductors Grounding Wedges Standard Material/Finish Listings/Compliances CAT. NO. SIZE CAT. NO. SIZE ⁄2" size Steel/Electro Zinc Plated 3 ⁄4" thru 6" size Bronze/Tin Plated UL File #E3060 CSA File #638 UL 467 CSA C22.2 No. 41 NFPA-70 Federal Specification A-A-50552 3650 3651 3652 3653 3654 3655 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 3656 3657 3658 3659 3661 3662 21⁄2" 3" 31⁄2" 4" 5" 6" 1 Range ⁄2" thru 6" conduit 1 1 UL File No. E-3060 Sealing material resists oil, coolants and hydraulic fluids as well as water! Liquidtight Sealing Gasket The 5262 Series Sealing Gasket includes a stainless steel retaining ring to prevent elongation of the Santoprene® gasket, ensuring a superior seal. Stainless Steel Retainer Application • When used with an externally threaded connector, provides a tight seal against oil, fumes or moisture at the knockout opening Features 5262 Series Sealing Gasket • Design locks resilient sealing material in steel • Steel retainer protects seal from extruding out under torque and limits compression to an optimum predetermined value; provides high quality seal • Resilient material flows and seals rough surfaces • NEMA 3R, 4, 6 and 13 Standard Material A Retainer: 316 Stainless Steel Sealing Material: Santoprene® Thermoplastic Rubber Range ⁄4" thru 4" Hub Size 1 B Thickness A-6 www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Resilient Sealing Material Locked in Steel Retainer Resilient Seal CAT. NO. CONDUIT SIZE A B STD. PKG. QTY. 5262 5263 5264 5265 5266 5267 5268 5269 5270 ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 4" 1.16 1.49 1.75 2.15 2.42 2.92 3.44 4.08 5.29 .18 .19 .19 .22 .23 .23 .23 .23 .31 50 25 25 5 5 5 5 5 5 1 3 DIMENSIONS (IN.) UL File No. E 13938 CSA File No. 2884 Santoprene is a registered trademark of Advanced Elastomer Systems. Technical Services Tel: 888.862.3289 Rigid and Intermediate Metal Conduit Fittings Blackjack® — Grounding Bushing Innovative design makes installation quicker, easier. The Blackjack® Grounding Bushing never has to be threaded onto a conduit. It is simply placed in position on either a threaded or non-threaded rigid or IMC conduit, with the grounding lug in perfect position to accept the grounding wire — even in tight installations. It’s as simple as one, two, three! Compare the installation with conventional bushings that must be threaded onto the conduit. In tight areas, you may have to remove the grounding lug, keep up with the loose parts and then reattach the lug. Then you still have to twist and turn the bushing to get the lug Mounting screw in position to accept the grounding wire. with nylon locking patch has a cone The Blackjack bushing does away with these point to lock needless delays for good, making it the ideal bushing securely grounding bushing — and the only logical in place. choice for small spaces, corners and multiple conduit runs. And, because the grounding lug is an integral part of the bushing, it's designed not to fall off or get lost. Integral grounding lug enhances ground continuity. Added ground wire range taking reduces inventory. Accepts copper or aluminum ground wires. Insulating nylon surface is 150° C rated and covers top of bushing, including lug corners. Angle of lug screw improves accessibility when securing grounding wire. Innovative design improves performance. The Blackjack® bushing provides superior ground continuity. The design of the Blackjack bushing has an integral, cast-on grounding lug for better ground continuity. This means that the Blackjack bushing stands up to intense loads. Reduce inventory. Because the Blackjack Grounding Bushing is designed for threaded and non-threaded conduits, and the ground lugs are designed to handle an extended range, the number of parts in inventory is reduced by up to two-thirds without losing any application coverage. Secure grip forms lasting bond. The Blackjack bushing’s cone-point mounting screw bites securely into both threaded and non-threaded rigid conduits. And the Blackjack bushing’s nylon locking patch is designed to prevent the screw from loosening due to vibration. Insulator surface features a rounded design to reduce drag and prevent abrasion during wire pulling. Blackjack® — Conduit Grounding Bushing Lug Screw: Range 14-4: Slotted 14-2/0: Slotted Conduit: 1⁄2" thru 6" threaded or threadless rigid/IMC 6-4/0: Internal Hex Drive Wire Range: #14 AWG to 4/0 AWG CU/AL Standard Material/Finish Listings/Compliances Body: Malleable Iron or Aluminum UL File #E3060 Mounting Screw: (1⁄2"–2") Stainless Steel, (21⁄2"–6") Brass CSA File #LR2884 Lug Screw: Stainless Steel CSA C22.2 No. 18 & CSA C22.2 No. 41 UL 514B & U.L. 467 Finish: Zinc Plated A-8 www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 Cast “threads” opposite the mounting screw tighten the fit during installation. Rigid and Intermediate Metal Conduit Fittings Blackjack® — Grounding Bushing Mounting Screw Nylon Insulator (150º C) Lug Screw 14-4: Slotted 14-2/0: Slotted 6-4/0: Internal hex drive ØB Throat I.D. C E ØA D For Threaded and Threadless Rigid and IMC Conduit CAT. NO. ZINC PLATED MALLEABLE IRON ALUMINUM BG050-14-20 BG050-14-4 BG075-14-20 BG075-14-4 BG100-14-20 BG100-14-4 BG125-14-20 BG150-14-20 BG200-14-20 BG250-14-20 BG250-6-40 BG300-14-20 BG300-6-40 BG350-14-20 BG350-6-40 BG400-14-20 BG400-6-40 BG500-14-20 BG500-6-40 BG600-14-20 BG600-6-40 BGA050-14-20 BGA050-14-4 BGA075-14-20 BGA075-14-4 BGA100-14-20 BGA100-14-4 BGA125-14-20 BGA150-14-20 BGA200-14-20 BGA250-14-20 BGA250-6-40 BGA300-14-20 BGA300-6-40 BGA350-14-20 BGA350-6-40 BGA400-14-20 BGA400-6-40 BGA500-14-20 BGA500-6-40 BGA600-14-20 BGA600-6-40 CONDUIT SIZE ØA MAX. ØB MIN. THROAT I.D. C MAX. D MAX. E MAX. WIRE RANGE ⁄2" ⁄2" 3 ⁄4" 3 ⁄4" 1" 1" 11⁄4" 11⁄2" 2" 21⁄2" 21⁄2" 3" 3" 31⁄2" 31⁄2" 4" 4" 5" 5" 6" 6" 1.251 1.251 1.533 1.533 1.783 1.783 2.220 2.470 2.830 3.418 3.418 4.042 4.042 4.542 4.542 5.042 5.042 6.136 6.136 7.199 7.199 .569 .569 .772 .772 .993 .993 1.319 1.553 2.010 2.412 2.412 3.022 3.022 3.491 3.491 3.975 3.975 4.991 4.991 6.009 6.009 1.181 1.027 1.221 1.030 1.181 1.027 1.181 1.181 1.181 1.181 1.524 1.181 1.524 1.181 1.524 1.181 1.524 1.181 1.524 1.181 1.524 2.134 1.940 2.414 2.168 2.581 2.368 2.987 3.236 3.766 4.341 4.526 4.966 5.139 5.467 5.639 5.966 6.139 7.045 7.207 8.087 8.409 .696 .696 .696 .696 .696 .696 .759 .696 .696 .978 .978 .978 .978 .978 .978 .978 .978 .978 .978 .978 .978 14-2/0 14-4 14-2/0 14-4 14-2/0 14-4 14-2/0 14-2/0 14-2/0 14-2/0 6-4/0 14-2/0 6-4/0 14-2/0 6-4/0 14-2/0 6-4/0 14-2/0 6-4/0 14-2/0 6-4/0 1 1 Suggested Specifications: Insulated grounding and bonding bushing (Series BG050-BG600) Where code requires bonding and grounding of single or multiple metal conduits, or positive bonding and grounding of metal conduit to the box, enclosure or auxiliary gutter, the end of the conduit shall be equipped with an insulated metallic grounding and bonding bushing series BG050-14-20 as manufactured by Thomas & Betts. Grounding and bonding bushings used shall be approved for the purpose and (i) Shall be of malleable iron/steel/aluminum construction adequately protected against corrosion. (ii) Bushing insulator shall be listed or certified for 150° C/302° F application with a flammability rating of 94V-O. Insulator must be positively locked in place. United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 www.tnb.com A-9 Rigid and Intermediate Metal Conduit Fittings Meets and surpasses NEC® requirements! Insulated Throat Fittings Locknut-type base improves bonding and resists loosening under vibration. • Steel or malleable iron (steel through 11⁄2") Metallic Bushings • Exceeds NEC 373-6C requirements for protection of ungrounded connectors at entrance to raceways, pull boxes and junctions • Aluminum, steel or malleable iron (steel through 11⁄2") • Smoothly rounded shoulder covers end of conduit • Recognizable by distinctive trademarked blue insulating liner in throat • Broad flange covers knockout hole • Reduces wire pulling effort by as much as 50% • High ribs for easy tightening with fingers or with wrench • Temperature rating of 105° C Nylon insulated metallic bushings • Look for the unique T&B blue color, ensuring the highest quality fitting • 1⁄2" to 11⁄2" sizes, formed in steel, feature extra-smooth shoulders CAT. NO. CAT. NO. STL. OR M.I. ALUM. SIZE 1222 1223 1224 1225 1226 1227 1228 1229 1230 1231 1232† 586 587 1222AL 1223AL 1224AL 1225AL 1226AL 1227AL 1228AL 1229AL 1230AL 1231AL 1232AL† 586AL 587AL ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 41⁄2" 5" 6" 1 DIMENSIONS (IN.) A B 11⁄32 19⁄32 119⁄32 115⁄16 23⁄16 211⁄16 33⁄16 327⁄32 47⁄16 47⁄8 — 531⁄32 73⁄16 ⁄64 31 ⁄64 11 ⁄32 21 ⁄32 23 ⁄32 7 ⁄8 1 ⁄32 5 ⁄16 11⁄16 13⁄32 — 19⁄32 111⁄32 29 † Not CSA Certified Catalog series 1222 thru 1232, 586 and 587 are available in aluminum. Add suffix AL to Cat. No. The aluminum series fittings are not CSA certified. STL. OR M.I. ALUM. SIZE 122 123 124 125-TB 126 127 128 129 130-TB 131-TB 132-TB 133-TB 134-TB 122AL 123AL* 124AL** 125AL 126AL 127AL 128AL 129AL 130AL 131AL — 133AL 134AL ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 41⁄2" 5" 6" DIMENSIONS (IN.) A B 11⁄32 11⁄4 19⁄16 129⁄32 25⁄32 221⁄32 33⁄16 327⁄32 43⁄8 415⁄16 57⁄16 6 71⁄4 1 3 * Not UL Listed or CSA Certified UL File No. E-23018 ** Not CSA Certified CSA File No. 2884 ⁄32 ⁄16 1 ⁄2 9 ⁄16 19 ⁄32 5 ⁄8 3 ⁄4 13 ⁄16 15 ⁄16 1 15⁄64 13⁄16 11⁄4 13 7 Available with DURA-PLATE ® Finish. Perfect threads for easy thread-on! Plastic Insulating Bushings All Plastic Insulating Bushings • Impact-resistant plastic insulation • Ribbed for easy, secure gripping • UL Listed 105° C DIMENSIONS (IN.) CAT. NO. SIZE A 222-TB 223-TB 224 225-TB 226 227 228-TB 229-TB 230-TB 231 232 233 234 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 41⁄2" 5" 6" 11⁄16 19⁄32 19⁄16 129⁄32 27⁄32 225⁄32 33⁄8 41⁄16 45⁄8 51⁄8 511⁄16 65⁄16 77⁄16 1 UL Rated flame retardant 94V-1 A-10 www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 B ⁄8 ⁄32 9 ⁄16 9 ⁄16 9 ⁄16 5 ⁄8 3 ⁄4 3 ⁄4 7 ⁄8 7 ⁄8 1 1 1 3 13 Rigid and Intermediate Metal Conduit Fittings Bush holes in metal boxes or enclosures! CHASE® Nipples CAT. NO. STL. OR M.I. 841TB 842TB 843TB 844 845 846 847 848 849 850 851 853 854 • 3⁄8" and 1⁄2" sizes in steel • 3⁄4" to 6" sizes in malleable iron DIMENSIONS (IN.) B ALUM. SIZE A — 842ALTB† 843ALTB 844AL† 845AL† 846AL 847AL 848AL 849AL 850AL 851AL — — ⁄8" ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 5" 6" 15 ⁄16 19⁄16 13⁄8 111⁄16 21⁄32 23⁄8 215⁄16 39⁄16 43⁄8 51⁄8 51⁄8 61⁄2 75⁄8 3 1 ⁄16 ⁄64 19 ⁄32 3 ⁄64 25 ⁄32 13 ⁄16 31 ⁄32 11⁄16 11⁄4 15⁄16 15⁄16 15⁄16 13⁄8 7 43 † Not UL Listed • 1⁄2" to 4" sizes in copper-free aluminum Available with DURA-PLATE® Finish. UL File No. E-23018 CSA File No. 2884 Nylon insulator offers extra protection! CHASE® Nipples — Nylon-Insulated • 3⁄8" and 1⁄2" sizes in steel • 3⁄4" to 6" sizes in malleable iron • 1⁄2" to 6" sizes in copper-free aluminum • Look for the unique T&B blue color ensuring the highest quality fitting available A-14 www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 CAT. NO. SIZE A DIMENSIONS (IN.) B C 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1953 1954 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 5" 6" 19⁄64 13⁄8 111⁄16 21⁄32 23⁄8 215⁄16 39⁄16 43⁄8 51⁄8 51⁄8 63⁄8 75⁄8 ⁄16 17 ⁄32 21 ⁄32 25 ⁄32 13 ⁄16 31 ⁄32 11⁄16 1i 15⁄16 15⁄16 15⁄16 13⁄8 ⁄32 ⁄32 7 ⁄8 11⁄32 13⁄32 111⁄32 17⁄16 119⁄32 125⁄32 113⁄16 113⁄16 17⁄8 UL File No. E-23018 CSA File No. 2884 Technical Services Tel: 888.862.3289 1 7 19 23 Rigid and Intermediate Metal Conduit Fittings For Threaded Rigid Metal Conduit/IMC/PVC Coated Rigid Metal Conduit. Copper-Free Aluminum Threaded Hubs (Bullet® Hubs) Copper free aluminum castings for fittings have a maximum of 0.4% copper. The most detrimental effect of higher percentage of copper on aluminum base alloy is its decrease in corrosion resistance. (A) Predetermined Compression Standard Material (B) Body: 370-401 Series 370AL ⁄2" thru 1" Steel All Copper-Free Aluminum 1 11⁄4" thru 6" Malleable Iron (C) ⁄2" thru 2" Steel (hardened) Locknut: (E) 1 2 ⁄2" thru 6" Malleable Iron Aluminum 1 (D) 370 Series 370AL Series Application • To connect threaded metal conduit (ferrous rigid/non-ferrous rigid/ PVC coated/or intermediate metal) to a threadless opening in a box or enclosure in outdoors or indoor location exposed to continuous or intermittent moisture Screws: Steel (hardened) O-Ring: Buna N Insulator: Nylon Coating: PVC ⁄2" thru 2" Steel (hardened) 1 21⁄2" thru 4" Copper-Free Standard Finish • To positively bond conduit to box or enclosure Features • Rugged steel/malleable iron/copper-free aluminum construction • Tapered internal threads for water-tight/dust-tight union (A) • Threads relieved to prevent bottoming of conduit, ensuring sound assembly (B) Hub: 370-401 Series 370AL Electro Zinc Plated As Cast Chromate Coated Locknuts: All Ferrous Locknuts Electro Zinc Plated and Chromate Coated Screws: All Electro Zinc Plated and Chromate Coated • Recessed sealing ring at box end; sealing ring captivated (C) Range • Hardened steel/malleable iron/copper-free aluminum locknuts designed to provide high-quality ground continuity; extended reach of locknut permits clamping on thin boxes and enclosures (D) 370 Series: 1⁄2" thru 6" Conduit • Insulated throat, insulates conductors, prevents abrasion and thinning of conductor insulation, reduces wire pull effort (E) 370AL & 401 Series: 1 ⁄2" thru 4" Conduit All hub threads — straight pipe All female threads — taper pipe (NPT) • Suitable for hazardous location use per following: (i) Class I Division 2, Class II Division 1 & 2, Class III Division 1 & 2 per NEC 501-4 (b); 502-4 (a) and 503-3 (a) (ii) Class II Groups E, F, G, & Class III locations per CEC 18-202; 18-252; 18-302; 18-352 National Electrical Code states that, “Where practical, dissimilar metals in contact anywhere in the system shall be avoided to eliminate the possibility of galvanic action.” The only exceptions, aluminum fittings and enclosures, are permitted to be used with steel conduit. ® Joint Industrial Council (JIC) Electrical Standards also forbid dissimilar metals in contact for the same reason and require that the fittings for metal conduit be of malleable iron or ductile iron and have impact strength comparable to that of the conduit. Listing/Compliances UL (UL File No: E-23018) CSA (LR-637, LR-23086) UL 514B CSA C22.2 No. 18 NFPA 70 NEMA FB-1 JIC EGP1; JIC EMP 1 Federal Specification A-A-50553 Federal Standard H-28 (Threads) United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 www.tnb.com A-15 Rigid and Intermediate Metal Conduit Fittings T&B Hub A Never before has a single hub fit like this one. Designed for unequalled performance. The innovative engineering of the T&B® Hub will, quite simply, raise your performance expectations for threaded hubs. Look for the distinctive blue color to ensure the quality of a Thomas & Betts fitting. Sealing Ring and Groove with innovative profile outperforms standard O-ring design. Sealing ring is captivated in place before installation and resists buckling or slipping during installation. The seal groove is designed for optimum compression of the sealing ring. The sealing ring is designed to provide a complete 360° seal, even when the conduit is not perpendicular with the enclosure. (See Figure 1) 2 Locknut Design with peripheral slots and a hexagonal/ angled spline spaced every 30° enables easy application of torque with wrench or hammer and screwdriver. (See Figures 2 & 3) 3 Sharper and Deeper Teeth on locknut and body designed for a more penetrating bite for improved bonding to the enclosure. 4 Hexagonal/Splined Body Design for fast, easy installation with wrench or hammer and screwdriver. 5 Precision Machined Tapered Threads designed to create watertight union. 6 Insulated Throat molded from 105° C rated thermoplastic with a flammability rating of 94 V-O. C 19⁄16 119⁄32 113⁄16 17⁄8 17⁄8 115⁄16 29⁄16 27⁄16 223⁄32 223⁄32 31⁄32 35⁄32 ⁄8 ⁄32 11⁄16 11⁄16 11⁄16 15⁄32 19⁄16 119⁄32 15⁄8 15⁄8 115⁄16 2 D E MAX. PANEL THROAT THICKNESS DIA. CAT. NO. DIA. H050-TB H075-TB H100-TB H125-TB H150-TB H200-TB H250-TB H300-TB H350-TB H400-TB H500-TB H600-TB ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 5 6 17⁄16 17⁄16 2 23⁄8 23⁄4 31⁄4 33⁄4 43⁄8 5 51⁄2 67⁄8 711⁄16 Material – Hub and Locknut: zinc or copper-free aluminum Insulating Throat: thermoplastic temp. rating – 105° C 1 ⁄16 ⁄16 1 ⁄4 1 ⁄4 1 ⁄4 1 ⁄4 1 ⁄4 1 ⁄4 1 ⁄4 1 ⁄4 1 ⁄4 5 ⁄16 7 3 29 3 ⁄32 ⁄32 1 15⁄16 117⁄32 131⁄32 213⁄32 231⁄32 313⁄32 37⁄8 415⁄16 6 19 25 Flammability Rating – 94V-0 Sealing Ring: 1 B TRADE SIZE Nitrile (BUNA “N”) For Aluminum Hubs add suffix A (i.e., H050A). For Chrome-Plated Hubs add suffix CP (i.e., H050CP). For 316 Stainless Steel Hubs add suffix GRSST (i.e., H050GRSST). (1⁄2" through 2" only.) Meets NEMA sealing requirements for NEMA 3R, 4 & 13 enclosures. UL Listed and CSA Certified. CSA Certified for hazardous locations Class II Groups E, F, G, Class III (NEC 501.10B). UL File No. E-23018 CSA File No. 4484 Chrome-Plated Hubs (suffix-“CP”) are rated NEMA 4X. 4 5 1 3 2 6 Throat Dia. E B D Fig. 1 Fig. 2 C Fig. 3 A United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 www.tnb.com A-17 Rigid and Intermediate Metal Conduit Fittings Threaded Erickson® 3-Piece Coupling (For Threaded Rigid Metal Conduit and Intermediate Metal Conduit) 674 Series 675AL Series Standard Material 674 Series Bushing & Case . . . . . . . . . . . Malleable Iron With an ERICKSON® coupling, a conduit run may be completed when neither conduit can be turned. A conduit run may also be broken without taking down the whole run. Conduit joined with ERICKSON® Couplings is rigid and in line and vibration will not loosen the connections. Malleable iron. Ring . . . . . . . . . . . . . . Steel & Malleable Iron 675AL Series Application • To couple and effectively bond threaded ends of rigid metal conduit/intermediate metal conduit where neither length of conduit can be rotated Features • Malleable Iron/Steel/Copper-free Aluminum construction Bushing & Case . . . . . . . . . . . . . . Aluminum Ring . . . . . . . . . . . . . . . . . . . . . . . Aluminum Standard Finish 674 Series: Electro Zinc Plated & Chromate Coated CAT. NO. Range 674 675 676 677 678 679 680TB 681 682 683 684 685 686 687 ⁄8" thru 6" Conduit (malleable iron) 3 • Free fitting threads ensure easy assembly ⁄2" thru 6" Conduit (aluminum) 1 • Permits conduit coupling without rotating either conduit ALUM.* 675AL Series: Degreased All straight pipe threads (NPS) • Provides rigid in-line coupling with high- quality grounding; will not loosen under vibration Listings/Compliances • Suitable for concrete-tight application NEMA FB1 • Capable of carrying ground fault currents up to 10,000 amps RMS (1⁄2" through 11⁄2" size) and up to 20,000 amps RMS (2" and above) (duration of fault current 3 cycles) (674 series tested) NFPA 70-1999 (ANSI) UL 514B CSA C22.2 No. 18 Federal Specification A-A-50553 Federal Standard H-28 (Threads) CAT. NO. SIZE — 675AL 676AL 677AL 678AL 679AL 680AL 681AL 682AL 683AL 684AL 685AL 686AL 687AL ⁄8" ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 41⁄2" 5" 6" 3 1 DIMENSIONS (IN.) A B 11⁄8 115⁄32 19⁄16 129⁄32 23⁄8 25⁄8 37⁄32 331⁄32 47⁄16 5 51⁄2 61⁄4 625⁄32 8 11⁄8 11⁄4 113⁄32 15⁄8 113⁄16 131⁄32 27⁄32 211⁄16 229⁄32 3 33⁄16 315⁄32 33⁄4 41⁄32 *Copper-Free Aluminum UL Listed and CSA Certified concrete-tight. UL File No. E-23018 CSA File No. 2884 Raintight Split Couplings T&B’s Split Coupling is a simple method to join threaded conduits in retrofits or in snug areas. Available in 1 ⁄2" to 6". • Ideal for retrofit installations or in tight areas • Fast installation • Neoprene gasket provides a concrete-tight seal. • Joins threaded conduit even when the conduit can’t rotate. • Approved for direct burial . . . . . . . . . Specifications . . . . . . . . . • • • • Material: Malleable Iron Gasket: Neoprene Plating: Zinc Plated Standards: UL Standard 514B, NEMA FB-1 CAT. NO. TRADE SIZE DIMENSIONS (IN.) A B C WEIGHT PER 100 SPCP50 SPCP75 SPCP100 SPCP125 SPCP150 SPCP200 SPCP250 SPCP300 SPCP350 SPCP400 SPCP500 SPCP600 ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 5" 6" 2 11⁄4 11⁄4 25⁄16 11⁄4 11⁄2 25⁄8 15⁄8 113⁄16 31⁄16 15⁄8 23⁄16 35⁄16 115⁄16 27⁄16 313⁄16 2 27⁄8 5 1 4 ⁄8 3 ⁄16 39⁄16 55⁄16 31⁄8 41⁄8 61⁄16 31⁄4 413⁄16 69⁄16 37⁄16 53⁄8 81⁄16 37⁄8 69⁄16 91⁄4 43⁄16 75⁄8 34.4 39.4 60.0 75.0 112.5 112.5 275.0 300.0 425.0 500.0 900.0 1,300.0 ⁄2" and 3⁄4" furnished with one screw 1" and 6" furnished with two screws United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.3289 1 1 3 www.tnb.com A-29 Rigid and Intermediate Metal Conduit Fittings Stainless Steel Pipe Straps • Higher degree of corrosion resistance than traditional zinc-plated or hot-dipped galvanized straps • One and two-hole straps for EMT sizes 1⁄2" through 2" • One and two-hole straps for Rigid and IMC size 1⁄2" through 4" • 303 stainless steel TRADE WT. PER SIZE 100 HOLE DIA. STD. PKG. 1 TS101-SS ⁄2" 2.21 3 TS102-SS ⁄4" 2.49 TS103-SS 1" 3.31 TS104-SS 11⁄4" 3.64 TS105-SS 11⁄2" 3.87 TS106-SS 2" 4.03 One-Hole Rigid/IMC Straps ⁄4" 1 ⁄4" 1 ⁄4" 11 ⁄16" 11 ⁄16" 11 ⁄16" 25 25 25 10 5 5 HS100-SS HS101-SS HS102-SS HS103-SS HS104-SS HS105-SS HS106-SS HS107-SS HS108-SS HS110-SS ⁄32" ⁄32" 9 ⁄32" 9 ⁄32" 11 ⁄32" 13 ⁄32" 13 ⁄32" 15 ⁄32" 17 ⁄32" 17 ⁄32" 20 20 20 20 10 10 5 5 5 5 CAT. NO. One-Hole EMT Straps Thomas & Betts offers stainless steel pipe straps to support and securely fasten rigid, IMC and EMT conduit. One- and two-hole stainless steel straps are ideal for industrial applications such as petro-chemical plants, manufacturing plants, pulp and paper mills, food processing, power plants, refineries and mining operations. Stainless steel pipe straps are also useful in commercial applications in schools, hospitals, office buildings, airports, casinos and stadiums. ⁄8" ⁄2" 3 ⁄4" 1" 11⁄4" 1 1⁄2" 2" 21⁄2" 3" 4" 3 1 Reduces threaded opening in conduit bodies or any female threaded fitting! Threaded Reducers • Smooth, built-in bushing completely covers rough ends of conduit • Malleable iron or steel construction (steel through 606, also 614 and 615) HOLE DIA. STD. PKG. 1 TS901-SS ⁄2" 2.21 3 TS902-SS ⁄4" 3.31 TS903-SS 1" 3.87 TS904-SS 11⁄4" 7.54 TS905-SS 11⁄2" 12.21 TS906-SS 2" 18.23 Two-Hole Rigid/IMC Straps ⁄4" ⁄4" 1 ⁄4" 11 ⁄16" 11 ⁄16" 11 ⁄16" 25 25 25 10 5 5 HS901-SS HS902-SS HS903-SS HS904-SS HS905-SS HS906-SS HS907-SS HS908-SS HS909-SS HS910-SS ⁄32" ⁄32" 9 ⁄32" 11 ⁄32" 13 ⁄32" 13 ⁄32" 15 ⁄32" 17 ⁄32" 17 ⁄32" 17 ⁄32" 20 20 20 10 10 5 5 5 5 5 CAT. NO. Two-Hole EMT Straps 2.00 2.21 2.49 3.48 3.76 18.22 19.69 67.21 76.45 80.18 1 9 9 DIMENSION (IN.) A STL. ON MI ALUM. SIZE 600TB 601TB 602TB 603TB 604TB 605TB 606TB 607 608 609 610 611TB 612 613 614TB 615TB 600ALTB 601ALTB 602ALTB 603ALTB 604ALTB 605AL 606AL 607AL 608AL 609AL 610AL 611AL 612AL 613AL 614AL 615AL ⁄2" to 3⁄8" ⁄4" to 1⁄2" 1" to 1⁄2" 1" to 3⁄4" 11⁄4" to 1⁄2" 11⁄4" to 3⁄4" 11⁄4" to 1" 11⁄2" to 1⁄2" 11⁄2" to 3⁄4" 11⁄2" to 1" 11⁄2" to 11⁄4" 2" to 1⁄2" 2" to 3⁄4" 2" to 1" 2" to 11⁄4" 2" to 11⁄2" 1 3 ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 2.49 3.64 4.15 8.17 17.50 21.37 21.54 25.72 27.27 31.70 1 3 1 1 9 9 Reduce knockout hole in outlet box! Reducing Washers CAT. NO. TRADE WT. PER SIZE 100 ⁄16 ⁄16 5 ⁄8 5 ⁄8 13 ⁄16 5 ⁄8 15 ⁄16 13 ⁄16 13 ⁄16 15 ⁄16 3 ⁄4 15 ⁄16 15 ⁄16 15 ⁄16 15 ⁄16 7 ⁄8 9 9 • Used in pairs • Interlock to form a rib that centers washers and conduit in knockout • Galvanized steel construction CAT. NO. SIZE 3700 3701 3702 3703 3704 3705-TB 3706 3707 3708 3709 3710 3711 3712 3713 3714 3715-TB 3716 3717 3718 ⁄4" to 3⁄8" ⁄4" to 1⁄2" 1" to 3⁄8" 1" to 1⁄2" 1" to 3⁄4" 11⁄4" to 3⁄8" 11⁄4" to 1⁄2" 11⁄4" to 3⁄4" 11⁄4" to 1" 11⁄2" to 3⁄8" 11⁄2" to 1⁄2" 11⁄2" to 3⁄4" 11⁄2" to 1" 11⁄2" to 11⁄4" 2" to 1⁄2" 2" to 3⁄4" 2" to 1" 2" to 11⁄4" 2" to 11⁄2" 3 3 UL File No. E-23018 UL File No. E-13938 CSA File No. 2884 CSA File No. 2884 United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 DIMENSIONS (IN.) A B 13⁄8 13⁄8 15⁄8 15⁄8 15⁄8 2 2 2 2 21⁄4 21⁄4 21⁄4 21⁄4 21⁄4 23⁄4 23⁄4 23⁄4 23⁄4 23⁄4 ⁄64 ⁄8 45 ⁄64 7 ⁄8 13⁄32 45 ⁄64 7 ⁄8 13⁄32 123⁄64 45 ⁄64 7 ⁄8 13⁄32 123⁄64 123⁄32 7 ⁄8 13⁄32 123⁄64 123⁄32 131⁄32 45 7 Technical Services Tel: 888.862.3289 www.tnb.com A-31 14-15.qxp 5/26/2011 11:11 PM Page 15 Condulet® Conduit Bodies Cast Iron or Aluminum 1F LBD Mogul 1F Ordering Information Applications: LBD bodies are installed at 90° bends in rigid conduit to: • Act as pull outlets for conductors that are stiff due to large size or type of insulation • Make 90° bends in conduit system, allowing straight pull in either direction /2 – 1" 11/4 – 2", 5" – 6" 1 21/2 – 4" • Provide for conduit service entrance to buildings Size Cat. # Size Cat. # Size Cat. # • Provide for conductor entrance to motors /2 3 /4 1 LBD1100 LBD2200 LBD3300 11/4 11/2 2 21/2 3 LBD4400 LBD5500 LBD6600 LBD7700 LBD8800 31/2 4 5 6 LBD9900 LBD10900 LBD012 LBD014 1 • Provide access to wiring for maintenance and future expansion Replacement Gaskets for Above Sizes Features: Rubber LBD bodies have: Size Cat. # Size Cat. # Size Cat. # • Cover openings on an angle permitting conductors to be pulled straight through hubs from either direction /2 3 /4 1 GASK680R GASK681R GASK682R 11/4 11/2 2 21/2 3 GASK683R GASK684R GASK684R GASK990R GASK990R 31/2 4 5 6 GASK989R GASK989R GASK687R GASK688R 1 • Domed covers to permit easy conductor bends (relieves strain on insulation) • Cover and gasket furnished Replacement Cover Assembly with Hardware • Taper tapped hubs with integral bushings Size Cat. # Size Cat. # Size Cat. # /2 /4 1 LBD100 LBD200 LBD300 11/4 11/2 2 21/2 LBD400 LBD600 LBD600 LBD800 3 31/2 4 5 6 LBD800 LBD900 LBD900 LBD120 LBD140 1 3 Certifications and Compliances: • UL Standard: 514B Dimensions • Fed. Spec.: W-C-586d In Inches: • CSA 22.2 No. 18 Standard Materials: • Body and cover – Feraloy® iron alloy • Gasket – Neoprene Standard Finishes: • Feraloy iron alloy: 1 /2" to 4" sizes, electrogalvanized and aluminum acrylic paint; 5" and 6" sizes, zinc chromate primer and aluminum lacquer • Neoprene – natural Options: Description Material – All sizes, copper-free aluminum Suffix SA Cat. # Size a b c d e LBD1100 LBD2200 LBD3300 LBD4400 LBD5500 LBD6600 LBD7700 LBD8800 LBD9900 (iron) LBD10900 (iron) LBD9900 (-SA) LBD10900 (-SA) LBD012 LBD014 /2 3 /4 1 11/4 11/2 2 21/2 3 31/2 4 31/2 4 5 6 5 61/4 61/4 85/8 127/16 127/16 1911/16 1911/16 207/8 207/8 2713/16 2713/16 327/16 411/2 25/16 25/8 215/16 41/4 57/16 57/16 99/16 99/16 107/8 107/8 117/8 117/8 121/2 15 15/16 19/16 113/16 31/2 45/8 45/8 55/8 55/8 73/4 73/4 71/8 71/8 85/8 93/4 1 11/4 11/2 113/16 25/8 25/8 3 3 43/4 43/4 4 4 57/8 7 311/32 417/32 411/32 73/16 107/8 107/8 153/4 153/4 197/8 197/8 24 24 30 39 www.crouse-hinds.com 1 US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 15 Flexible Cord and Cable Fittings The Ranger® Series of Aluminum Liquidtight Cord Connectors Application • A liquidtight connector to connect flexible cord to an enclosure and provide adequate strain relief • Form a mechanical grip and water and liquidtight seal NEW! • Installer can simply use screwdriver to get into the hard-to-reach area and secure the gland nut • Marked with cable ranges and conduit hub sizes C Material • Form a non-slip connection • Body: Copper-free Aluminum or termination for flexible cord Gland Nut, Grip: Copper-free Aluminum — all series Cord & Cable Type Bushing: Thermoplastic Rubber • SJ, SJE, SJEW, SJEO, SJEOO, SJEOOW, Grip Ring: Nylon SJO, SJOW, SJOO, SJOOW, SJT, SJTW, Environment Classification SJTO, SJTOW, SJTOO, SJTOOW, SO, SOW, SOO, SOOW, SV, ST, STD, SVD • Ordinary locations Features • Available in straight or 90° designs • Designed to accept a wide range of cables, offering nine fittings that cover cord ranges from .125" through .950" • Slotted design gland nut to accommodate securing in tight spaces A B C D • Wet or dry locations • Temperature Range: -20º C to 105º C (-4º F to 221º F) A Range • Cord Range: .125" to .950 B • Hub Size Range: 1⁄2" to 1" Aluminum Liquidtight Strain-Relief Connectors CAT. NO. HUB SIZE CORD RANGE (IN.) A DIMENSIONS (IN.) B C ⁄ 2" ⁄ 2" 1 ⁄ 2" 3 ⁄ 4" 3 ⁄ 4" 3 ⁄ 4" 1" 1" 1" .125-.375 .310-.560 .500-.750 .125-.375 .310-.560 .500-.750 .310-.560 .500-.750 .700-.950 11⁄8 11⁄8 15⁄16 15⁄16 15⁄16 15⁄16 15⁄16 15⁄16 19⁄16 13⁄4 13⁄4 13⁄4 125⁄32 125⁄32 125⁄32 13⁄4 13⁄4 17⁄8 ⁄ 2" ⁄ 2" 3 ⁄4" 3 ⁄4" 3 ⁄4" 1" 1" 1" .125-.375 .360-.560 .125-.375 .310-.560 .500-.750 .310-.560 .500-.750 .700-.950 11⁄8 11⁄8 15 ⁄16 15 ⁄16 15 ⁄16 15 ⁄16 15 ⁄16 15 ⁄16 13⁄4 13⁄4 125⁄32 125⁄32 125⁄32 21⁄32 21⁄32 211⁄16 D STD. PKG. QTY. WT. PER 100 ⁄8 ⁄8 5 ⁄8 3 ⁄8 3 ⁄4 3 ⁄4 11⁄16 11⁄16 31⁄32 — — — — — — — — — 25 25 25 10 10 10 10 10 10 8.50 8.05 9.95 12.30 11.90 11.50 18.00 16.00 16.70 ⁄8 ⁄8 11 ⁄16 11 ⁄16 11 ⁄16 13 ⁄16 13 ⁄16 13 ⁄16 15⁄16 15⁄16 115⁄32 115⁄32 115⁄32 13⁄4 13⁄4 2 50 50 50 50 50 25 25 25 23.60 11.60 17.2 30.00 33.09 21.50 22.36 18.20 Straight 2920AL 2921AL 2922AL 2930AL 2931AL 2932AL 2940AL 2941AL 2942AL 1 1 5 5 90° Elbow 4960AL 4961AL 4970AL 4971AL 4972AL 4980AL 4981AL 4982AL 1 1 5 5 * It may be necessary to remove sufficient outer covering of cable to permit conductors to pass through connector body. All items shown on this page are suitable for use in hazardous locations where general purpose equipment is specifically permitted by the NEC. NEC 501-4(b). UL File No. E-13938 CSA File No. 52391 United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 For wire mesh grips refer to page A-147. Technical Services Tel: 888.862.3289 www.tnb.com A-141