ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® Appendix D. H 03-155-1 List of regulators Each of the 19 exciters is documented separately in this appendix. Table of Contents 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) ESAC1A…………………………………3 ESAC2A…………………………………7 ESAC3A…………………………………11 ESAC4A…………………………………15 ESAC5A…………………………………19 ESAC6A…………………………………23 ESAC8A…………………………………27 ESDC1A…………………………………31 ESDC2A…………………………………35 ESST1A………………………………….39 ESST2A………………………………….43 ESST3A………………………………….47 ESST4B………………………………….51 EXBAS…………………………………..57 IEEET4…………………………………..61 IEEEX4………………………………….65 IEET1A………………………………….69 IEET1B………………………………….73 URST5T……………………………….…77 -1- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 -2- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 1 ESAC1A IEEE Type AC1A Excitation System VAMAX VS VU VRMAX VC 1 1+ sTR V1 - + VREF V2 ∑ KA V4 1+sTA 1+ sTC V3 1+ sTB HV GATE VF W FC VAMIN + LV GATE V5 ∑ VR VE UF Π sTE FEX - VRMIN 1 0 VX + VX=VE *SE(VE) V6 ∑ + FEX=f(IN) IN KE KC ⋅ IF + sKF 1+ sTF ∑ VE + V7 KD VFE Figure D.1 Block diagram of ESAC1A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signal VE is limited between 0 and infinity, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E IF IFD UF EFD VU VUEL VS VOTHSG WFC VOEL VC EC The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else KC ⋅ IF IN = VE We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) ⇒ FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current -3- IF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESAC1A/ SWOF n Identification number of the associated over excitation limiter which gives the value of WFC. (The parameter SWOF is often used when associating a field current limiter but not for this exciter.) Default = 0 NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of associated under excitation limiter. Controlling high voltage gate. If SWU is not equal to zero the output signal is equal to the largest input signal of VU and the internal exciter signal. Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.1 Recommended interval is 0 ≤ TR< 0.5 TB n Voltage regulator time constant in seconds. Default = 14 Recommended interval is 0 ≤ TB < 20 TC n Time constant in seconds. Default = 14.1 Recommended interval is 0 ≤ TC < 20 KA n Voltage regulator gain in p.u. Default = 800 Recommended interval is 0 < KA <1000 TA n Voltage regulator amplifier time constant in seconds. Default = 0.1 Recommended interval is 0 ≤ TA < 10 VAMAX n Maximum value of limitation of the signal VA in p.u Default = 15 Recommended interval is 0 < VAMAX ≤ 15 VAMIN n Minimum value of limitation of the signal VA in p.u. Default = −15 Recommended interval is −15 ≤ VAMIN < 0 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 14 Recommended interval is 0 < VRMAX < 15 VRMIN n Minimum value of limitation of the signal VR in p.u Default = − 14 Recommended interval is –15 < VRMIN < 0 KE n Exciter constant related to self-excited field. Default = 0.1 Recommended interval is 0 < KE ≤ 1 TE n Exciter time constant in seconds. Default = 1.8 Recommended interval is 0 < TE < 2 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default = 0.6 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) -4- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KF n Regulator stabilizing circuit gain p.u. Default = 0.15 Recommended interval is 0 ≤ KF < 0.3 TF n Regulator stabilizing circuit time constant in seconds. Default = 1.4 Recommended interval is 0 < TF < 1.5 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.2 Recommended interval is 0 ≤ KC ≤ 1 KD n Demagnetizing factor, a function of exciter alternator reactances. Default = 0.1 Recommended interval is 0 ≤ KD ≤ 1 EXAMPLE: REGULATORS 4 TYPE=DSLS/ESAC1A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 VRMIN = −14 VRMAX = 14 TE = 1.8 TA = 0.1 VAMIN = −15 TR = 0.1 KC = 0.2 KD = 0.1 KE = 0.1 TF = 1.4 TB = 14 KF = 0.15 VAMAX = 15 KA = 800 TC = 14.1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) -5- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESAC1A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 150 1.05 100 5 2 O 10 X 8 1.1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.6 1.05 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * * 1 50 6 1 1.2 + + + + O 0 0.95 0.4 2 0.9 -50 0 0 0.85 -100 4 0.8 0.9 0.85 * + + O O O O + 5 0 * + O O X * + O O * + 0.95 * * * 5 X 8 5 5 X X 16 24 X * 32 5 5 5 X 40 48 5 X 56 5 X 64 X 72 80 88 TIME SECONDS ID VREG JOB vreg DATE 2 JUN 2003 TIME 11:23:21 DIAGRAM SIM 1 Compare with standard type WC (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 5 1.1 150 4 1.05 100 3 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * * * O O * * O * * * * O O O O O O + 0 0.95 2 1.2 0.95 + 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 5 5 + + 5 8 X X 16 24 X 32 X * 40 5 5 5 X 48 X 56 64 X X 72 80 88 TIME SECONDS DATE 2 JUN 2003 TIME 11:36:57 RUN INSTRUCTION (for the two figures above). AT 1 increase VREF by 5%. AT 16 INST CONNECT LINE GENBUS MIDBUS AT 40 INST CONNECT FAULT F1 AT 40.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + + + + 5 5 + + -6- DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 2 ESAC2A IEEE type AC2A excitation system VFEMAX − KDIF VS VRMAX VC 1 1+sTR V1 - + VREF V4 V2 1+ sTC V3 KA VA + ∑ 1+sTB 1+sTA VH ∑ VF KE + SE(VE) VU VAMAX KB HV GATE LV GATE V5 VR+ ∑ - VAMIN Π UF FEX 0. VRMIN WFC VE 1 sTE V6 VX=VE*SE(VE) VX + ∑ + V7 IN KE + VFE FEX=f(IN) KC∗ IF VE ∑ KH + V8 sKF 1+ sTF KD IF Figure D.2 Block diagram of ESAC2A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E IF IFD UF EFD VU VUEL WFC VOEL VS VOTHSG VC EC The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else ⇒ KC ⋅ IF IN = VE We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current -7- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESAC2A/ SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 SWOF n Identification number of the associated over excitation limiter which gives the value of WFC. (The parameter SWOF is often used when associating a field current limiter but not for this exciter.) Default = 0 NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 TR n Voltage transducer filter time constant in seconds. Default = 0.01 Recommended interval is 0 ≤ TR < 0.5 TB n Voltage regulator time constant in seconds. Default = 1 Recommended interval is 0 ≤ TB < 20 TC n Voltage regulator time constant in seconds. Default = 1.1 Recommended interval is 0 ≤ TC < 20 KA n Voltage regulator gain in p.u Default = 300 Recommended interval is 0 < KA < 1000 TA n Voltage regulator time constant in second. Default = 0.1 Recommended interval is 0 ≤ TA < 10 VAMIN n Minimum value of limitation of the signal VA in p.u. Default = − 4 Recommended interval is −10 ≤ VAMIN < 0 VAMAX n Maximum value of limitation of the signal VR in p.u. Default = 10 Recommended interval is 0 < VAMAX ≤ 10 KB n Second stage regulator gain. Default = 400 Recommended interval is 0 < KB < 500 VRMAX n Maximum value of limitation of the signal VR in p.u. Default = 140 Recommended interval is 0 < VRMAX ≤ 500 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = − 40 Recommended interval is −500 ≤ VRMIN < 0 VFEMAX n A parameter for calculating the maximum value of the limiter for the output signal VE in p.u. Default = 14 Recommended interval is −5 < VFEMAX ≤ 20 TE n Exciter time constant in seconds. May be zero if KE is not equal to zero. Default = 0.001 Recommended interval is 0 < TE < 2 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) -8- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KE n Exciter constant related to self-excited field and it is a parameter for calculating the maximum value of the limiter for the output signal VE, see figure. Default = 0.1 Recommended interval is 0 < KE ≤ 1 KD n Demagnetizing factor, a function of exciter alternator reactance and it is a parameter for calculating the maximum value of the limiter for the output signal VE, see figure. Default = 0.1 Recommended interval is 0 ≤ KD ≤ 1 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.1 Recommended interval is 0 ≤ KC ≤ 1 TF n Excitation control system stabilizer time constant. Default = 1 Recommended interval is 0 < TF < 1.5 KF n Excitation control system stabilizer gains. Default = 0.1 Recommended interval is 0 ≤ KF < 0.3 KH n Exciter field current feedback gain. Default = 0.0000000001 Recommended interval is 0 ≤ KH ≤ 1.1 E1 Set point for saturation p.u Default = 1.0 E2 Set point for saturation p.u Default = 1.2 SE1 Saturation Se at E1. Default = 0.2 SE2 Saturation Se at E2. Default = 0.6 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESAC2A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 VFEMAX = 14 KB = 400 KH = 0.0000000001 VRMIN = − 40 VRMAX = 140 TE = 0.001 TA = 0.1 VAMIN = − 4 TR = 0.01 KC = 0.1 KD = 0.1 KE = 0.1 TF = 1 TB = 1 KF = 0.1 VAMAX = 10 KA = 200 TC = 1.1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) -9- ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESAC2A (figure below) VREG DYNAMIC DATA U POS. UF VOLTAGE I POS. SPEED TETA PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 O * 100 1.05 4 2.4 1.05 X 5 + 3 1.1 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN 1.1 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC * * * * * * * 50 1 3 1 1.8 * O O * O O O O O O O O + 0 0.95 2 1.2 0.95 + 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 0 + 5 5 5 5 5 + 5 5 + + 5 + + X + 5 + 8 X X X X 4 12 16 X 20 24 X 28 X X 32 36 X 40 44 TIME SECONDS ID VREG JOB vreg DATE 4 AUG 2003 TIME 11:26:17 DIAGRAM TM SIMPOW 1 Compare with standard type WFA (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN U POS. UF VOLTAGE I POS. SPEED TETA * X 5 1.1 3 5 1.1 150 1.05 2.4 4 1.05 100 1 3 1 50 2 * * * O O * * 0 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 O * O + 5 5 + 4 * * * O + 5 + O + O O + + + 5 5 5 5 O + 5 5 5 + X X X 8 12 16 X 20 X 24 X 28 32 X 36 X 40 X 44 TIME SECONDS DATE 4 AUG 2003 TIME 11:57:29 RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) * O 0.95 0.95 1.8 O 1.2 + PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN - 10 - DIAGRAM 1 SIMPOW TM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 3 ESAC3A IEEE Type AC3A Excitation System KR VS VC 1 1 + sTR V1 - V2 ∑ + 1 + STC 1 + sTB V3 VFEMAX − KD * IF KE + SE (VE ) VAMAX VU HV GATE + V4 V5 ∑ VA KA 1 + sTA VR + Π 1 sTE V6 ∑ - VF UF Π FEX V EMIN VFE VREF VE VAMIN VX VX=VE*SE(VE) + + ∑ V7 FEX=f(IN) IN KE KC * IF VE + + ∑ V8 KD IF VN KN S 1 + sTF VN KF EFDN UF Figure D.3 Block diagram of ESAC3A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E IF IFD UF EFD VU VUEL VS VOTHSG + VOEL VC EC The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else ⇒ KC ⋅ IF IN = VE We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current - 11 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESAC3A/ SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 TR n Voltage transducer filter time constant in seconds. Default = 0.001 Recommended interval is 0 ≤ TR < 0.5 TB n Voltage regulator time constant in seconds. Default = 1.1 Recommended interval is 0 ≤ TB < 20 TC n Voltage regulator time constant in seconds. Default = 1 Recommended interval is 0 ≤ TC < 20 KA n Voltage regulator gain in p.u Default = 80 Recommended interval is 0 < KA < 1000 TA n Voltage regulator time constant in second. Default = 0.1 Recommended interval is 0 ≤ TA < 10 VAMIN n Minimum value of limitation of the signal VA in p.u. Default = −1 Recommended interval is −10 ≤ VAMIN < 0 VAMAX n Maximum value of limitation of the signal VR in p.u. Default = 8 Recommended interval is 0 < VAMAX ≤ 10 TE n Exciter time constant in seconds. Default = 0.01 Recommended interval is 0 < TE < 4 KE n Exciter constant related to self-excited field. Default = 0.1 Recommended interval is 0 < KE ≤ 1 KD n Demagnetizing factor, a function of exciter alternator reactance. Default = 0.1 Recommended interval is 0 ≤ KD ≤ 1 VFEMAX n A parameter for calculating the maximum value of the limiter for the output signal VE in p.u. Default = 10 Recommended interval is −5 < VFEMAX ≤ 20 VEMIN n Minimum value of limitation of the signal VE in p.u. Default = 0.1 Recommended interval is 0 ≤ VEMIN ≤ 1.1 KR n Constant associated with regulator and alternator field power supply. Default = 2 Recommended interval is 0 ≤ KR < 75 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.2 Recommended interval is 0 ≤ KC ≤ 1 TF n Excitation control system stabilizer time constant. Default = 1 Recommended interval is 0 < TF < 1.5 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 12 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KF n Excitation feedback gain, see figure. Default = 0.2 Recommended interval is 0 ≤ KF < 0.3 KN n Exciter feedback gain, see figure. Default = 0.1 Recommended interval is 0 < KN < 0.3 EFDN n A parameter defining for which value of UF the feedback gain shall change from KF to KN, see figure. Default = 1 Recommended interval is 0 < EFDN ≤ 10 E1 n Set point for saturation p.u Default = 1.0 E2 n Set point for saturation p.u Default = 1.2 SE1 n Saturation Se at E1. Default = 0.2 SE2 n Saturation Se at E2. Default = 0.6 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESAC3A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 KF = 0.2 KN = 0.1 EFDN = 1 KR = 2 TA = 0.1 VAMIN = −1 VAMAX = 8 KA = 80 VFEMAX = 10 TE = 0.01 TR = 0.001 KC = 0.2 KD = 0.1 KE = 0.1 VEMIN = 0.1 TF = 1 TB = 1.1 TC = 1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 13 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESAC3A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 5 1.1 150 4 1.05 100 3 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * * * * * * * O O * O O O O O O O + 0 0.95 2 1.2 0.95 + 5 5 + 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + 0 X 2 X 4 + 5 + 5 5 5 + X X + 5 5 + + 6 X 8 X X 10 12 14 16 X 18 20 22 TIME SECONDS ID VREG JOB vreg DATE 30 SEP 2003 TIME 10:03:11 DIAGRAM SIM 1 Compare with standard type WHA (figure below) VREG DYNAMIC DATA U POS. UF VOLTAGE I POS. SPEED TETA O PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 X 5 + 3 1.1 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN 1.1 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 100 1.05 4 2.4 1.05 X * * * * * * 1 50 3 1 1.8 O * O O O * * * O O O O O 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + ID VREG JOB vreg X 0 2 5 X 4 + 5 + + 5 5 5 5 5 + + 6 X X X 8 10 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 4 AUG 2003 TIME 14:30:41 RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + + 0 0.95 2 1.2 0.95 + - 14 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 4 ESAC4A IEEE Type AC4A Excitation System The excitation system with alternator supplied controlled rectifier exciter. VS V R M A X - K C * IF V IM A X VU + V1 1 VC - 1 + sT R ∑ VI V2 1 + sTC 1 + sT B V3 KA HV G ATE UF 1 + sT A V IM IN VREF V R M IN Figure D.4 Block diagram of ESAC4A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E IF IFD UF EFD VU VUEL VS VOTHSG + VOEL VC EC Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESAC4A/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 15 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 TR n Voltage transducer filter time constant in seconds. Default = 0.05 Recommended interval is 0 ≤ TR < 0.1 VIMAX n Maximum value of limitation of the integrator signal VI in p.u. Default = 0.1 Recommended interval is 0 < VIMAX ≤ 0.2 VIMIN n Minimum value of limitation of the signal VI in p.u. Default = – 0.19 Recommended interval is – 0.2 < VIMIN ≤ 0 TB n Voltage regulator time constant in seconds. Default = 10 Recommended interval is 0 < TB < 20 TC n Voltage regulator time constant in seconds. Default = 0.3 Recommended interval is 0 ≤ TC < 10 KA n Voltage regulator gain in p.u Default = 500 Recommended interval is 50 < KA ≤ 1000 5 ≤ KA × TC ≤ 15 TB TA n Voltage regulator time constant in second. Default = 0.1 Recommended interval is 0 ≤ TA < 0.5 KC n A parameter for calculating the maximum value of the limiter for the output signal UF in p.u. Default = 0.2 Recommended interval is 0 ≤ KC < 0.3 VRMAX n A parameter for calculating the maximum value of the limiter for the output signal UF in p.u. Default = 3 Recommended interval is 3 ≤ VRMAX ≤ 8 VRMIN n Minimum value of limitation of the signal UF in p.u. Default = −3 Recommended interval is −8 ≤ VRMIN ≤ −3 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESAC4A/ VRMAX = 3 KC = 0.2 TA = 0.1 VRMIN = –3 KA = 500 VIMIN = – 0.19 VIMAX = 0.1 TB = 8 TC = 0.5 TR = 0.05 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 16 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESAC4A (figure below) VREG DYNAMIC DATA X 3 U POS. UF VOLTAGE I POS. SPEED TETA O 1.1 + 10 1.1 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 100 1.05 8 2.4 1.05 * * * * * * * * 1 50 * O O O O O 0 5 5 5 0.9 0.6 2 0.9 -50 0.85 0 0 0.85 -100 + X 0 X O 6 O + + + X + 5 5 5 5 5 5 + X X 4 O + + 2 O + + 0.95 6 4 1 1.8 0.95 1.2 * X 8 X X X 10 12 14 16 18 20 22 TIME SECONDS ID VREG JOB vreg DATE 13 AUG 2003 TIME 13:38:29 DIAGRAM SIM 1 Compare with standard type WG (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 10 1.1 150 8 1.05 100 6 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * * * * * O O O O * * * * O O O O O 0 0.95 4 1.2 0.95 + + 5 5 0.9 0.6 2 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 2 5 + + + X 4 X 6 5 + +X + 5 5 5 + X 8 X 10 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 28 MAY 2003 TIME 11:10:52 RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + 5 5 * - 17 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 - 18 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 5 ESAC5A IEEE Type AC5A Excitation System VS VC 1 1 + sT R V1 - VRM AX V2 ∑ + VREF VR KA 1+ sT A + - - V5 VF V R M IN ∑ 1 sT E V3 ∑ UF 0. + V4 + KE VX V X = U F *S E (U F ) sK F ( 1 + sT F 3 ) (1 + sT F 1 )( 1 + sT F 2 ) Figure D.5 Block diagram of ESAC5A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signal UF is limited between 0 and infinity, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E VC EC VS VOTHSG + VUEL + VOEL UF EFD Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESAC5A/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 19 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.001 Recommended interval is 0 ≤ TR < 0.5 KA n Regulator gain in p.u. Default = 450 Recommended interval is 10 < KA < 500 TA n Regulator amplifier time constant in seconds. May be zero. Default = 0.01 Recommended interval is 0 ≤ TA < 1 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 9 Recommended interval is 0.5 < VRMAX < 10 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = −8 Recommended interval is –10 < VRMIN < 0 KF n Regulator stabilizing circuit gain p.u. Can not be zero. Default = 0.1 Recommended interval is 0 < KF < 0.3 TF1 n Regulator stabilizing circuit time constant in seconds. Default = 1 Recommended interval is 0 < TF1 < 1.5 5≤ TF1 ≤ 15 KF TF2 n Regulator stabilizing circuit time constant in seconds. Default = 0.1 Recommended interval is 0 ≤ TF2 TF3 n Regulator stabilizing circuit time constant in seconds. Default = 0.002 Recommended interval is 0 ≤ TF3 KE n Exciter constant related to self-excited field. Default = 0.1 Recommended interval is –1 ≤ KE ≤ 1 TE n Exciter time constant in seconds. Default = 0.01 Recommended interval is 0 < TE < 1 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default = 0.6 1) If VRMAX is zero, the model will compute a new value of it. a) If KE is zero or negative, VRMAX will just allow the exciter to reach an output voltage of E2 i.e.: VRMAX = SE(E2 ) × E2 b) If KE is positive, VRMAX will just allow the exciter to reach an output voltage of E2 with the specified value of KE, i.e.: VRMAX = (SE (E2 ) + KE ) × E2 In either case above, VRMIN is then set to –VRMAX. 2) If KE is zero, the model will set a new value of KE. KE is set to the value that will require a voltage regulator output of (VRMAX /10) to maintain the present value of excitation voltage, UF, i.e.: KE = We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) VRMAX – SE (UF) 10 ⋅ UF - 20 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESAC5A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 TR = 0.001 KE = 0.1 TE = 0.01 TF2 = 0.1 TF1 = 1 KF = 0.1 TF3 = 0.002 TA = 0.01 VRMAX = 9 KA = 450 VRMIN = − 8 END Test of exciter ESAC5A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 150 100 50 3 5 3 2.4 1.1 1.1 1.05 1 PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 1.05 O 1 X U POS. UF VOLTAGE I POS. SPEED TETA 4 + 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * * * O * O O * O O O O O O 0 0.95 2 1.2 0.95 + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg 0 2 X 4 5 X 6 5 5 5 5 10 12 X X X X X 8 14 16 18 20 22 TIME SECONDS DATE 11 AUG 2003 TIME 10:05:16 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + + + + 5 + + + + X 5 * * * - 21 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 - 22 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 6 ESAC6A IEEE Type AC6A Excitation System VS VAMAX VU UT * VRMAX VC 1 1 + sTR V1 - + ∑ + V2 KA(1+ STK) 1+ sTA V3 1+ STC 1+ sTB VA VR V4 ∑ + 1 sTE V5 ∑ - - FEX V10 VAMIN VX VX=VE*SE(VE) + ∑ + V6 V9 KH VH V8 ∑ KC ∗ IF VE + + VFE ∑ FEX= f (IN) IN KE VHMAX 1+STC 1+sTB UF Π 0. UT * VRMIN VREF VE + V7 KD 0 VFELIM Figure D.6 Block diagram of ESAC6A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signal VE is limited between 0 and infinity, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) Simpow PSS/E VC EC VS VOTHSG +VOEL VU VUEL UT VT IF IFD UF EFD - 23 - IF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ ⇒ Else IN = KC ⋅ IF VE FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESAC6A/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.0001 Recommended interval is 0 ≤ TR < 0.5 KA n Voltage regulator gain in p.u. Default = 840 Recommended interval is 0 < KA < 1000 TA n Regulator amplifier time constant in seconds. May be zero. Default = 0.01 Recommended interval is 0 ≤ TA < 10 TK n Regulator lead time constant. Default = 0.01 Recommended interval is 0 < TK < 10 TB n Voltage regulator time constant in seconds. Default = 1 Recommended interval is 0 ≤ TB < 20 TC n Voltage regulator time constant in seconds. Default = 1.1 Recommended interval is 0 ≤ TC < 20 VAMAX n Maximum value of limitation of the signal VA in p.u Default = 10 Recommended interval is 0 < VAMAX ≤ 10 VAMIN n Minimum value of limitation of the signal VA in p.u. Default = −1 Recommended interval is −10 ≤ VAMIN < 0 VRMAX n Maximum value of limitation of the internal signal VR in p.u. Default = 80 Recommended interval is 0 < VRMAX ≤ 500 VRMIN n Minimum value of limitation of the internal signal VR in p.u. Default = −10 Recommended interval is −500 ≤ VRMIN < 0 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 24 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KE n Exciter constant related to self-excited field. Not used if VR is given. Default = 0.1 Recommended interval is 0 < KE ≤ 2 TE n Exciter time constant in seconds.May be zero if KE isn’t set to zero. Default = 0.01 Recommended interval 0 < TE < 2 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.1 Recommended interval is 0 ≤ KC ≤ 1 KD n Demagnetizing factor, a function of exciter alternator reactances. Default = 0.1 Recommended interval is 0 < KD ≤ 2 VFELIM n Exciter field current limit reference. Default = 1 Recommended interval is 0 < VFELIM ≤ 20 KH n Exciter field current limiter gain. Default = 0.0001 Recommended interval is 0 ≤ KH ≤ 1.1 VHMAX n Maximum value of limitation of the internal signal VH in p.u Default = 100 Recommended interval is 0 < VHMAX ≤ 100 TJ n Exciter time constant in seconds. Default = 1 Recommended interval is 0 ≤ TJ ≤ 1 TH n Exciter time constant in seconds. Default = 0.0005 Recommended interval is 0 ≤ TH ≤ 1 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default=0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default=0.6 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESAC6A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 KH = 0.0001 VFELIM=1 VHMAX = 100 TH = 0.0005 TJ=1 VRMIN = −10 VRMAX = 80 KA = 840 TE = 0.01 TB = 1 VAMIN = −1 TR = 0.0001 KC = 0.1 KD = 0.1 KE = 0.1 TA = 0.01 VAMAX = 10 TC = 1.1 TK=0.01 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 25 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESAC6A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 5 1.1 150 4 1.05 100 3 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * O * O * * O * O O O O O O 0 0.95 2 1.2 0.95 + + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + ID VREG JOB vreg X 0 5 X 4 X 6 8 X 10 + 5 5 5 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 11 AUG 2003 TIME 09:41:58 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + 5 5 5 + + + X 2 + * * * - 26 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 7 ESAC8B Basler DECS VRMAX VREF KP + VC 1 1 + sTR V1 - Σ + V2 KI s + - Σ + V3 KA 1 + sTA VR + V4 Σ - 1 sTE V6 0 sKD 1 + sTD VS VRMIN Σ + V5 KE + VX VX=UF*SE (UF) Figure D.7 Block diagram of ESAC8B as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signal UF is limited between 0 and infinity, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E VC EC VS VOTHSG + VOEL UF EFD Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/ESAC8B/ NSWS n Number of associated system stabilizers. Default =1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default=0 Voltage transducer filter time constant. Shall be given in seconds. Default = 0.1 Recommended interval is 0 ≤ TR < 0.5 TR n We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 27 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KP n Gain. Default = 400 Recommended interval is 10 < KP < 500 KI n Gain. Default = 200 Recommended interval is 10 < KI < 500 KD n Gain. Default = 490 Recommended interval is 10 < KD < 500 TD n Time constant in second Default = 0.4 Recommended interval is 0 ≤ TD < 0.5 KA n Voltage regulator gain in p.u Default = 0.1 Recommended interval is 0 < KA ≤ 1 TA n Voltage regulator time constant in second. Default = 1 Recommended interval is 0 ≤ TA ≤ 1 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 8 Recommended interval is 0 < VRMAX ≤ 10 VRMIN n Minimum value of limitation of the signal VR in p.u Default = 1 Recommended interval is –1 < VRMIN < 1.5 KE n Exciter constant related to self-excited field Default = 1 Recommended interval is –1.0 ≤ KE ≤ 1.0 TE n Exciter time constant in seconds. Default = 0.01 Recommended interval is 0 < TE E1 n Set point for saturation p.u Default =1.0 E2 n Set point for saturation p.u Default = 1.2 SE1 n Saturation Se at E1. Default = 0.2 SE2 n Saturation Se at E2. Default = 0.6 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESAC8B/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 TA = 1 VRMIN = 1 TD = 0.4 KD = 490 TE = 0.01 KE = 1 VRMAX = 8 KA = 0.1 KP = 400 KI = 200 TR = 0.1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 28 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESAC8B (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 100 5 1.1 O 1.05 3 X U POS. UF VOLTAGE I POS. SPEED TETA 4 1.1 2.4 + 1.05 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * * * * * * * * 50 1 3 1 1.8 * O * O O O O O O + O O + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + ID VREG JOB vreg X 0 2.667 5 5 5 + 5 5 5 5 + X 5.333 X 8 13.333 X X X X 10.667 16 18.667 21.333 TIME SECONDS DATE 11 AUG 2003 TIME 11:07:05 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + + + 0 0.95 2 1.2 0.95 + - 29 - DIAGRAM 1 X 24 X 26.667 29.333 ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 - 30 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 8 ESDC1A IEEE Type DC1A Excitation System VS VRMAX VU VC 1 1 + sTR V1 - V2 ∑ + 1 + sTC 1 + sTB V3 HV GATE KA 1 + sTA - VR + V4 ∑ 1 sTE - VFE 0 VREF VRMIN + ∑ VF VX V5 KE + VX = UF * SE sKF 1 + sTF Figure D.8 Block diagram of ESDC1A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signal UF is limited between 0 and infinity, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E VU VUEL VS VOTHSG + VOEL UF EFD VC EC Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/ESDC1A/ NSWS n Number of associated system stabilizers. Default =1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 31 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 TR n Voltage transducer filter time constant. Default = 0.1 Recommended interval is 0 ≤ TR < 0.5 TB n Voltage regulator time constant in seconds. Default = 1 Recommended value is 0 ≤ TB TC n Voltage regulator time constant in seconds. Default = 1.1 Recommended value is 0 ≤ TC and if TB = 0 then TC ≠ 0 KA n Voltage regulator gain in p.u. Default = 499 Recommended interval is 10 < KA < 500 TA n Voltage regulator amplifier time constant in seconds. Default = 0.4 Recommended interval is 0 ≤ TA < 1 VRMIN n Minimum value of limitation of the signal VR in p.u Default = − 4 Recommended interval is –10 < VRMIN < 0 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 3 Recommended interval is 0.5 < VRMAX < 10 KE n Exciter constant related to self-excited field. Default = 0.8 Recommended interval is –1 ≤ KE ≤ 1 TE n Exciter time constant in seconds. Default = 0.4 Recommended interval is 0 < TE < 1 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default = 0.6 KF n Regulator stabilizing circuit gain p.u. Default = 0.1 Recommended interval is 0 < KF < 0.3 5≤ TF n TF ≤ 15 KF Regulator stabilizing circuit time constant in seconds. Default = 1.2 Recommended interval is 0 < TF 1) If VRMAX is zero, the model will compute a new value of it. a) If KE is zero or negative, VRMAX will just allow the exciter to reach an output voltage of E2 i.e.: VRMAX = SE(E2 ) × E2 b) If KE is positive, VRMAX will just allow the exciter to reach an output voltage of E2 with the specified value of KE, i.e.: VRMAX = (SE (E2 ) + KE ) × E2 In either case above, VRMIN is then set to –VRMAX. 2) If KE is zero, the model will set a new value of KE. KE is set to the value that will require a voltage regulator output of (VRMAX /10) to maintain the present value of excitation voltage, UF, i.e.: KE = We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) VRMAX – SE (UF) 10 ⋅ UF - 32 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESDC1A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 KE = 0.8 TF = 1.2 KF =0.1 TE = 0.4 VRMAX = 3 TA = 0.4 VRMIN = −4 KA = 499 TB = 1 TC = 1.1 TR = 0.1 END Test of exciter ESDC1A (figure below) VREG DYNAMIC DATA U POS. UF VOLTAGE I POS. SPEED TETA O PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 X 10 1.1 + 1.5 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN 1.1 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC + + + 100 50 8 6 1.05 1.3 1 1.05 1 1.1 + * * + * * * * + * * * O * O O O O O + + + O O O 0 -50 -100 4 0.95 2 0.9 ID VREG JOB vreg 5 5 0 0.7 0.5 X 0.85 0.9 0.9 0.85 0.95 + X 0 2 X 4 5 X 6 X X 8 10 X X X 12 5 5 14 16 18 20 22 TIME SECONDS DATE 11 AUG 2003 TIME 11:36:01 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) 5 5 5 5 - 33 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 - 34 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 9 ESDC2A IEEE Type DC2A Excitation System VS UT*VRMAX VU VC 1 1+ sTR V1 - V2 ∑ + 1+ sTC V3 1+ sTB HV GATE KA VR+ 1+sTA ∑ V4 - - 1 sTE VFE VF VREF UT*VRMIN ∑ + V5 KE + VX VX=UF*SE (UF) sKF 1+sTF Figure D.9 Block diagram of ESDC2A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E VC EC VS VOTHSG + VOEL VU VUEL UT VT UF EFD Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/ESDC2A/ SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 NSWS n Number of associated system stabilizers. Default = 1 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 35 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.001 Recommended interval is 0 ≤ TR < 0.5 TB n Voltage regulator time constant in seconds. Default = 1 Recommended interval is 0 ≤ TB TC n Voltage regulator time constant in seconds. Default = 1.1 NOTE THAT TB = 0 and TC ≠ 0 Recommended interval is 0 ≤ TC KA n Voltage regulator gain in p.u. Default = 400 Recommended interval is 10 < KA < 500 TA n Voltage regulator amplifier time constant in seconds. May be zero. Default = 0.4 Recommended interval is 0 ≤ TA < 1 VRMAX n Maximum value of limitation of the signal VR in p.u. Default = 8 Recommended interval is 0.5 < VRMAX < 10 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = −1 Recommended interval is –10 < VRMIN < 0 KE n Exciter constantrelated to self-excited field. Not used if VR is given. Default = 0.1 Recommended interval is –1 ≤ KE ≤ 1 TE n Exciter time constant in seconds. Default = 1 Recommended interval is 0 < TE < 2 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default = 0.6 KF n Regulator stabilizing circuit gain p.u. Can not be zero. Default = 0.1 Recommended interval is 0 < KF < 0.3 TF n Regulator stabilizing circuit time constant in seconds. Default = 1.2 Recommended interval is 0 < TF < 1.5 5≤ We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) TF ≤ 15 KF - 36 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 1) If VRMAX is zero, the model will compute a new value of it. a) If KE is zero or negative, VRMAX will just allow the exciter to reach an output voltage of E2 i.e.: VRMAX = SE(E2 ) × E2 b) If KE is positive, VRMAX will just allow the exciter to reach an output voltage of E2 with the specified value of KE, i.e.: VRMAX = (SE (E2 ) + KE ) × E2 In either case above, VRMIN is then set to –VRMAX. 2) If KE is zero, the model will set a new value of KE. KE is set to the value that will require a voltage regulator output of (VRMAX /10) to maintain the present value of excitation voltage, UF, i.e.: KE = VRMAX – SE (UF) 10 ⋅ UF EXAMPLE: REGULATORS 4 TYPE = DSLS/ESDC2A/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 VRMIN = –1 VRMAX = 8 KE = 0.1 TF = 1.2 KF = 0.1 TE = 1 TA = 0.4 KA = 200 TB = 1 TC = 1.1 TR = 0.001 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 37 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESDC2A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 150 100 50 3 5 3 2.4 1.1 1.1 1.05 1 PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 1.05 O 1 X U POS. UF VOLTAGE I POS. SPEED TETA 4 + 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * * O O * O O * * * O * * O O O O + 0 0.95 2 1.2 0.95 + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + X 0 5 X 2 + + 5 + + 5 5 5 5 5 + + X X X 4 6 8 10 X X 12 14 16 X 18 20 22 TIME SECONDS ID VREG JOB vreg DATE 1 SEP 2003 TIME 13:23:17 DIAGRAM SIM 1 Compare with standard type 1 (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 150 1.05 100 50 5 1 O 5 3 2.4 X U POS. UF VOLTAGE I POS. SPEED TETA 4 1.1 1.05 1 + 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN 3 X * * * * O O O O * * * * O O * O O O + 0 0.95 2 1.2 0.95 + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + ID VREG JOB vreg X 0 2 5 + X 4 + + 5 + 5 5 5 + X 6 X X 8 10 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 5 AUG 2003 TIME 12:11:54 RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + 5 5 * - 38 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 10 ESST1A IEEE Type ST1A Excitation System VU VU U E L= 1 UEL = 3 A ltern ate U E L In pu ts VS VS UEL = 2 A ltern ate S ta bilizer In puts VOS = 1 VOS = 2 VU VAMAX V IM A X VC 1 1 + sTR V1 - - Σ + + V2 - VI HV GATE 1 + sTC 1 + sT C1 1 + sT B 1 + sTB1 V3 KA 1 + sT A U T *V R M A X - K C *IF VA + V IM IN HV GATE LV GATE UF V5 U T *V R M IN V7 V A M IN VREF Σ V4 W FC VF sK F 1 + sTF V6 K LR Σ + - 0 IL R Figure D.10 Block diagram of ESST1A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signal V7 is limited between 0 and infinity, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) Simpow PSS/E VC EC VS VOTHSG VU VUEL WFC VOEL UT VT IF IFD UF EFD - 39 - IF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/ESST1A/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 VOS n A switch that controls where the input signal VS is subtracted to the exciter. The parameter SWS sets which system stabilizer that calculates the value of VS. n=1 The input signal VS is subtracted to the sum with the output signal V2. n=2 The input signal VS is subtracted to the sum with the output signal V4. If no system stabilizer is associated, i.e., SWS = 0, the parameter VOS is ignored. Default = 1 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 UEL n A switch that controls where the input signal VU is injected to the exciter. The parameter SWU sets which under excitation limiter that calculates the value of VU. n=1 The input signal VU is added to the sum with the output signal V2. n=2 The input signal VU is one of the input signals to the left HV-gate. n=3 The input signal VU is one of the input signals to the right HV-gate. If no under excitation limiter is associated, i.e., SWU = 0, the parameter UEL is ignored. Default = 1 SWOF n Identification number of the associated over excitation limiter which gives the value of WFC. (The parameter SWOF is often used when associating a field current limiter but not for this exciter.) Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.09 Recommended interval is 0 ≤ TR < 0.1 VIMAX n Maximum value of limitation of the internal integrator signal VI in p.u. Default = 0.2 Recommended interval is 0 < VIMAX ≤ 0.2 VIMIN n Minimum value of limitation of the internal integrator signal VI in p.u. Default = 0 Recommended interval is – 0.3 ≤ VIMIN ≤ 0 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 40 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 TB n Voltage regulator time constant in seconds. Default = 15 Recommended interval is 0 < TB < 20 TC n Voltage regulator time constant in seconds. Default = 3 Recommended interval is 0 ≤ TC < 10 TC1 n Voltage regulator time constant in seconds. Default = 1.1 Recommended interval is 0 ≤ TC1 < 10 TB1 n Voltage regulator time constant in seconds. Default = 1 Recommended interval is 0 < TB1 < 20 KA n Voltage regulator gain in p.u. Default = 55 Recommended interval is 50 < KA ≤ 1000 5 ≤ KA TC ≤ 15 TB TA n Voltage regulator amplifier time constant in seconds. Default = 0.01 Recommended interval is 0 ≤ TA < 0.5 VAMAX n Maximum value of limitation of the signal VA in p.u. Default = 8 Recommended interval is 3 ≤ VAMAX ≤ 8 VAMIN n Minimum value of limitation of the signal VA in p.u. Default = − 4 Recommended interval is – 8 < VAMIN ≤ – 3 KLR n Exciter output current limiter gain. Default = 0.0004 Recommended interval is 0 < KLR ≤ 5 ILR n Exciter output current limit reference. Default = 0.01 Recommended interval is 0 < ILR ≤ 5 KF n Regulator stabilizing circuit gain p.u. Default = 0.01 Recommended interval is 0 < KF ≤ 0.3 TF n Regulator stabilizing circuit time constant in seconds. Default = 1 Recommended interval is 0.3 < TF ≤ 1.5 VRMAX n A parameter for calculating the maximum value of the limiter for the output signal UF in p.u. Default = 8 Recommended interval is 3 ≤ VRMAX ≤ 8 VRMIN n A parameter for calculating the minimum value of the limiter for the output signal UF in p.u. Default = −8 Recommended interval is −8 ≤ VRMIN ≤ −3 KC n A parameter for calculating the maximum of the limiter for the output signal UF in p.u. Default = 0.1 Recommended interval is 0 ≤ KC < 0.3 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESST1A/ ILR = 0.01 KLR = 0.0004 TR = 0.09 TF = 1 KF = 0.01 TA = 0.01 VAMIN = −4 VAMAX = 8 KA = 55 TC1 = 1.1 TB1 = 1 TC = 3 TB = 15 VIMIN = 0 VIMAX = 0.2 VRMIN = −8 KC = 0.1 VRMAX = 8 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 41 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESST1A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 150 1.05 100 5 3 O 5 X 4 1.1 + U POS. UF VOLTAGE I POS. SPEED TETA 2.4 1.05 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * 1 50 3 1 1.8 * O O * O * * O O O O O O + 0 0.95 2 1.2 0.95 + 5 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + X 0 5 X 2 + + + 5 5 5 5 5 + X X X 4 + 5 + + * * * 6 8 X X 10 12 14 16 X 18 20 22 TIME SECONDS ID VREG JOB vreg DATE 5 AUG 2003 TIME 12:42:35 DIAGRAM 1 Compared with standard type WK (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 5 1.1 150 4 1.05 100 3 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * * * * * O O O O * * O O O * O O + 0 0.95 2 1.2 0.95 + 5 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 5 + + + 2 X 4 6 X 5 + X 8 X 10 X X 12 14 16 TIME SECONDS DATE 5 AUG 2003 TIME 12:58:35 - 42 - + 5 5 5 + RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + 5 5 + DIAGRAM 1 18 X 20 22 ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 11 ESST2A Modified IEEE Type ST2A Excitation System VS VRMAX VU UFMAX VC 1 1 + sTR V1 + VREF V2 Σ KA 1 + sTA HV GATE VR V3 + Π VB VF 1 STE V4 Σ - 0. V5 VRMIN KE sKF 1 + sTF UD+jUQ VE VE=|KP(UD+jUQ) +jKI(ID+jIQ)| ID+jIQ Π FEX IF IN = KC IF VE IN FEX=f(IN) Figure D.11 Block diagram of ESST2A as modelled in Simpow The bus voltage’s d- and q-components, UD and UQ, and the stator current’s dand q-components of the machine, ID and IQ, are inputs to the exciter. The signal UF is limited between 0 and UFMAX, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) Simpow PSS/E VC EC VS VOTHSG + VOEL VU VUEL UD + jUQ VT ID + jIQ IT IF IFD UFMAX EFDMAX UF EFD - 43 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else IN = KC ⋅ IF VE FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/ESST2A/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.001 Recommended interval is 0 ≤ TR < 0.5 KA n Voltage regulator gain in p.u Default = 800 Recommended interval is 10 < KA < 1000 TA n Voltage regulator amplifier time constant in seconds. Default = 0.01 Recommended interval is 0 ≤ TA < 1 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 1 Recommended interval is 0.5 < VRMAX < 1.5 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = −1 Recommended interval is −1.5 < VRMIN < 0.5 KE n Exciter constant related to self-excited field. Not used if VR is given. Default = 0.1 Recommended interval is 0 < KE ≤ 1 TE n Exciter time constant in seconds. Default = 0.0001 Recommended interval is 0 < TE < 2 KF n Regulator stabilizing circuit gain p.u. Default = 0.1 Recommended interval is 0 < KF < 0.3 TF n Regulator stabilizing circuit time constant in seconds. TF > 0. Default = 1 Recommended interval is 0 < TF < 1.5 UFMAX n Maximum value of limitation of the signal UF in p.u Default = 8 Recommended interval is 1 < UFMAX < 10 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 44 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.2 Recommended interval is 0 < KC < 2 KP n Potential circuit gain coefficient. KP = 1.19 KI n Potential circuit gain coefficient. Default = 1 Recommended interval is 0 ≤ KI ≤ 8 EXAMPLE: REGULATORS 4 TYPE= DSLS/ESST2A/ UFMAX = 8 KP = 1.19 KI = 1 KE = 0.1 TF = 1 KF = 0.1 KC = 0.2 TA = 0.01 VRMIN = −1 VRMAX = 1 KA = 800 TE = 0.0001 TR = 0.001 END Test of exciter ESST2A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 1.1 100 150 1.05 1 50 3 5 4 3 1.1 PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * O * * O * * O O * * * O O O * O O + 0 0.95 2 1.2 0.95 + 5 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 2 5 X 4 5 5 5 6 X X X 8 10 + 5 5 5 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 5 AUG 2003 TIME 14:25:46 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + + + + + + + - 45 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 - 46 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 12 ESST3A IEEE Type ST3A Excitation System V G M AX V4 KG VS VM M AX V R M AX VIM AX VG VU VC 1 1 + sTR V1 - - V2 Σ + VI HV G AT E 1 + sTC 1 + sTB VA KA 1 + sTA VR + KM 1+sTM V3 Σ VIM IN VM VB VM M IN VR M IN V R EF V BM A X ID + j IQ UD + j UQ VE = KP ( Cos θ + jSin θ ) ⋅ (U D + jUQ ) + j ( KI + ( KP ⋅ ( Cosθ + jSin θ )) ⋅ XL )( ID + jIQ ) VE Π V5 F EX IF IN = KC VE IF IN FE X =f(IN ) Figure D.12 Block diagram of ESST3A as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The signals VB and VG is limited between (− infinity) and VBMAX respective VGMAX. See block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) Simpow PSS/E IF IFD UF EFD VU VUEL VS VOTHSG + VOEL VC EC KP ⋅ (cosθ + jsinθ) KP∠THETAP ID + jIQ UD + jUQ IT - 47 - VT UF Π ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else IN = KC ⋅ IF VE FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/ESST3A/ SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 TR n Voltage transducer filter time constant in seconds. Default = 0.0001 Recommended interval is 0 ≤ TR < 0.5 VIMAX n Maximum value of limitation of the signal VI in p.u. Default = 0.8 Recommended interval is 0 < VIMAX < 1 VIMIN n Minimum value of limitation of the signal VI in p.u. Default = −0.1 Recommended interval is −1 < VIMIN < 0 TB n Voltage regulator time constant in seconds. Default = 15 Recommended interval is 0 < TB < 20 TC n Voltage regulator time constant in seconds. Default = 3 Recommended interval is 0 < TC < 20 KA n Voltage regulator gain in p.u. Default = 50.1 Recommended interval is 0 < KA ≤ 200 TA n Voltage regulator time constant in second. Default = 0.1 Recommended interval is 0 ≤ TA < 1 VRMAX n Maximum value of limitation of the signal VR in p.u. Default = 8 Recommended interval is 0.5 < VRMAX ≤ 10 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = 0 Recommended interval is −10 ≤ VRMIN < 0.5 KM n Forward gain constant of the inner loop field regulator. Default = 800 Recommended interval is 0 < KM < 1000 TM n Forward time constant of the inner loop field regulator. Default = 0.1 Recommended interval is 0 ≤ TM < 1 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 48 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VMMAX n Maximum value of limitation of the signal VM in p.u. Default = 1 Recommended interval is 0.5 < VMMAX ≤ 1.5 VMMIN n Minimum value of limitation of the signal VM in p.u. Default = 0.1 Recommended interval is −1.5 < VMMIN < 0.5 KG n Feedback gain constant of the inner loop field regulator. Default = 1 Recommended interval is 0 ≤ KG < 1.1 VGMAX n Maximum value of limitation of the signal VG in p.u. Default = 4 Recommended interval is 0 < VGMAX < 20 VBMAX n Maximum value of limitation of the signal VB in p.u. Default = 18 Recommended interval is 0 < VBMAX < 20 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.1 Recommended interval is 0 ≤ KC < 1 KP n Potential circuit gain coefficient. Default = 4 Recommended interval is 1 < KP < 10 KI n Potential circuit gain coefficient. Default = 0.1 Recommended interval is 0 ≤ KI ≤ 1.1 XL n Reactance associated with potential source. Default = 0.01 Recommended interval is 0 < XL < 0.5 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESST3A/ VGMAX = 4 TB = 15 TC = 3 VMMIN = 0.1 KM = 800 TM = 0.1 VMMAX = 1 TA = 0.1 KA = 50.1 VRMIN = 0 VRMAX = 8 VIMIN = −0.1 VIMAX = 0.8 KI = 0.1 XL = 0.01 KP = 4 TR = 0.0001 KC = 0.1 VBMAX = 18 KG = 1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 49 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESST3A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 150 100 50 3 5 3 2.4 1.1 1.1 1.05 1 PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 1.05 O 1 X U POS. UF VOLTAGE I POS. SPEED TETA 4 + 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * * * O O O O * * * O O * O * O O + + 0 0.95 2 1.2 0.95 + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + X 0 X 2 5 + + 4 X 6 + X 5 X 8 10 5 5 5 X X 12 + + 5 5 14 16 X 18 20 22 TIME SECONDS ID VREG JOB vreg DATE 1 SEP 2003 TIME 13:38:13 DIAGRAM SIM 1 Compare of standard type ST3A (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 5 1.1 150 4 1.05 100 3 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * O O * O O * * * * O O * O * O O 0 0.95 2 1.2 0.95 + + 5 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 5 X 2 X 4 6 X 8 + 5 + 5 5 5 X 10 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 6 AUG 2003 TIME 14:23:50 RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + 5 5 + + + + + - 50 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 13 ESST4B IEEE Type ST4B Potential or Compounded Source-Controlled Rectifier Exciter KG VS + VC 1 1 + sTR VMMAX VRMAX VU V1 - - Σ WFC V6 KIR KPR + S V2 + VR - 1 1 + sTA V3 + Σ V4 KPM + KIM S V18 V5 LV GATE Π VB VMMIN VRMIN VREF ID + j IQ UD + j UQ VE = K P (Cos θ + jSinθ ) (UD + jUQ ) + j ( K I + K P (Cos θ + jSin θ ) X L )( ID + jIQ ) VE Π VBMAX V7 FEX IF IN = KC IF VE IN FEX=f(IN) Figure D.13.1 Block diagram of ESST4B as modelled in Simpow The signals VB is limited between − infinity and VBMAX, see block diagram. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) SIMPOW PSS/E IF IFD UF EFD VU VUEL VS VOTHSG VC EC KP ⋅ (cosθ + jsinθ) KP∠THETAP ID + jIQ IT UD + jUQ VT WFC VOEL - 51 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else IN = KC ⋅ IF VE FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/ESST4B/ SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 SWOF n Identification number of the associated over excitation limiter which gives the value of WFC. (The parameter SWOF is often used when associating a field current limiter but not for this exciter.) Default = 0 NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 KPM n Regulator gain. Default = 0.0001 Recommended interval is 0 ≤ KPM ≤ 1.2 KPR n Regulator gain. Default = 40 Recommended interval is 0 ≤ KPR ≤ 75 KIR n Regulator gain. Default = 0.8 Recommended interval is 0 ≤ KIR ≤ 75 KIM n Regulator gain. Default = 5 Recommended interval is 0 ≤ KIM ≤ 18 KI n Potential circuit gain coefficient. Default = 1 Recommended interval is 0 ≤ KI ≤ 1.1 XL n Reactance associated with potential source. Default = 0.1 Recommended interval is 0 ≤ XL < 0.5 KP n Potential circuit gain coefficient. Default = 8 Recommended interval is 1 ≤ KP < 10 TR n Voltage transducer filter time constant in seconds. Default = 0.01 Recommended interval is 0 ≤ TR < 0.5 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.1 Recommended interval is 0 ≤ KC < 1 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 52 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VBMAX n Maximum value of limitation of the signal VB in p.u. Default = 18 Recommended interval is 1 < VBMAX < 20 KG n Feedback gain constant of the inner loop field regulator. Default = 0.4 Recommended interval is 0 ≤ KG < 1.1 VMMIN n Minimum value of limitation of the signal V18 in p.u. Default = −100 Recommended interval is −118.8 ≤ VMMIN ≤ 0 VMMAX n Maximum value of limitation of the signal V18 in p.u. Default = 118 Recommended interval is 0.8 ≤ VMMAX ≤ 118 TA n Voltage regulator time constant in second. Default = 0.01 Recommended interval is 0 ≤ TA < 1 VRMAX n Maximum value of limitation of the signal VR in p.u. Default = 4 Recommended interval is 0.8 ≤ VRMAX ≤ 10 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = −1 Recommended interval is −6 ≤ VRMIN ≤ 0 EXAMPLE: REGULATORS 4 TYPE = DSLS/ESST4B/ KIM = 5 KPR = 40 KI = 1 TA = 0.01 XL = 0.1 KP = 8 TR = 0.01 KIR = 0.8 KC = 0.1 VBMAX = 18 KG = 0.4 KPM = 0.0001 VMMIN = −100 VMMAX = 118 VRMAX = 4 VRMIN= −1 END The initiation of the exciter ESST4B The initiation of the exciter is done as described below. The LV-gate should not function as usual. Instead, the value of V5 is forced to be equal to V18. However, if it would happen that WFC should be less than V18, the simulation will automatically stop during the start-up. There are two PI-blocks in ESST4B. The abbreviation PI stands for Proportional Integration block. We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 53 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 The PI-block (the most right PI-block in the figure above) is modelled as described in the figure below, figure D.13.2. VMMAX Parameter KIM Parameter V4 K 1 S V14 V15 + Σ V17 V18 + KPM Parameter VMMIN K Parameter V16 Figure D.13.2 The most-right PI-block in the exciter The initiation of the block diagrams in figure D.13.2 is done so that the input signal V14 to the integrator is initially equal to zero, i.e., V14 = 0. At the same time should the output signal of the integrator V15, match the initial state of the exciter which is given from a corresponding power-flow solution. To do so V18 should be adjusted so that UF, see figure D.13.1, is equal to the initial value UF0 calculated from the corresponding power-flow solution. V18 is therefore set to: V 18 = UF 0 VB (13.1) Where VB is the initial VB calculated according to ID, IQ, UD, UQ, and IF. Since the LV-gate initially is set to V 5 = V 18 (13.2) then UF is equal to: UF = V 5 ⋅ VB = {Equation (11.25)} = V 18 ⋅ VB = = {Equation (11.24)} = UF 0 ⋅ VB = UF 0 VB (13.3) Since the most right limiter in figure D.13.2 is in unlimited mode during start-up, V 17 = V 18 (13.4) and since the input signal to the integrator V14 is equal to zero, also the signal V16 will be equal to zero. This means that the initial value of V15 is equal to V17 and from equations (13.1) – (13.4) we can derive that V15 is set to: V 15 = We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) UF 0 VB (13.5) - 54 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 To enable V4 equal to zero the exciter has to be further initiated to the left of the signal V4 in figure D.13.1, so that V3 is equal to V6 and is set to: V 3 = KG ⋅ UF 0 (13.6) The most-left PI-block is modelled as described in the figure below, figure D.13.3. VREF V1 - Parameter VS + Σ VRMAX Parameter - V8 + Σ V2 KIR V10 K + VU Parameter 1 S V11 + Σ V9 VR + KPR VRMIN K Parameter V12 Figure D.13.3 The most-left PI-block in the exciter (The marked area) Under initiation VR is equal to V3, see figure D.13.1, VR = V 3 = KG ⋅ UF 0 (13.7) Since the most right limiter in figure D.13.3 is in unlimited mode during start-up, V 9 = VR (13.8) and since the input signal to the integrator V10 is equal to zero, also the signal V12 will be equal to zero. This means that the initial value of V11 is equal to V9 and from equations (13.6) – (13.8) we can derive that V11 is set to: V 11 = V 9 = KG ⋅ UF 0 (13.9) To enable V2 equal to zero the exciter has to be further initiated to the left of the signal V2 in figure D.13.3, so the value of VREF is set as: VREF = VS + V 1 − VU (13.10) The value of VREF in equation (13.10) is kept through all the simulation which is the normal routine for exciters as well as many other regulators. The initiation of the exciter is done exactly as the exciter ESST4B is initialized in the power system simulation software PSS/E. We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 55 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter ESST4B (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 10 5 1.1 150 1.05 7.6 4 1.04 100 3 0.98 50 2 0.92 0 5 1 O 5.2 X 2.8 + U POS. UF VOLTAGE I POS. SPEED TETA 0.95 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * O O O O O 5 5 0.9 0.4 1 0.86 -50 -2 0 0.8 -100 + X 0 5 * * * O O + + + + X 2 X 4 X 6 8 5 5 5 + X 10 O O + + + X X 12 5 5 5 14 16 18 + X 20 22 TIME SECONDS DATE 12 AUG 2003 TIME 12:51:38 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) * * * * 0.85 ID VREG JOB vreg * - 56 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 14 EXBAS Basler Static Voltage Regulator Feeding dc or ac Rotating Exciter VS VREF VC 1 V1 1+sTR + ∑ + VU V0 ∑ VRMAX V2 KP+ + KI S V3 1+ sTC V4 1+ sTB KA 1+ sTA VR + 1 V5 ∑ VE Π UF sTE FEX V8 VF WFC VRMIN FEX=f(IN) IN V6 KE+SE + sKF 1+ sTF V9 1+ sTF1 ∑ 1+ sTF2 + V7 KD Figure D.14 Block diagram of EXBAS as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E VC EC VS VOTHSG + VOEL + VUEL VU VUEL WFC VOEL IF IFD UF EFD The Rectifier Regulation Characteristic: If IN ≤ 0 Else if IN ≤ 0.433 ⇒ ⇒ Else if 0 .433 < IN < 0.75 ⇒ ⇒ Else if 1 ≥ IN ≥ 0.75 ⇒ Else IN = KC ⋅ IF VE We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) FEX = 1 FEX = 1 − 0.577 ⋅ IN FEX = 0.75 − IN 2 FEX = 1.732 ⋅ (1 − IN) FEX = 0 where IF = field current - 57 - KC * IF VE IF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/EXBAS/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 SWOF n Identification number of the associated over excitation limiter which gives the value of WFC. (The parameter SWOF is often used when associating a field current limiter but not for this exciter.) Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.1 Recommended interval is 0 ≤ TR < 0.5 KP n Potential circuit gain coefficient. Default = 1 Recommended interval is 0 < KP < 5 KI n Potential circuit gain coefficient. Default = 0.1 Recommended interval is 0 ≤ KI < 1.1 TB n Voltage regulator time constant in seconds. Default = 1 Recommended interval is 0 ≤ TB < 20 TC n Voltage regulator time constant in seconds. Default = 1.1 Recommended interval is 0 ≤ TC < 20 KA n Voltage regulator gain in p.u. Default = 4000 Recommended interval is 10 < KA ≤ 4000 TA n Voltage regulator amplifier time constant in seconds. Default = 0.01 Recommended interval is 0 ≤ TA ≤ 10 VRMAX n Maximum value of limitation of the signal VR in p.u. Default = 18 Recommended interval is 0.5 < VRMAX < 20 VRMIN n Minimum value of limitation of the signal VR in p.u. Default = −14 Recommended interval is –20 < VRMIN < 0 KE n Exciter constant related to self-excited field. Default = 1 Recommended interval is –1 ≤ KE ≤ 1 TE n Exciter time constant in seconds. Default = 0.01 Recommended interval is 0 < TE < 10 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default = 0.6 KF n Regulator stabilizing circuit gain p.u. Default = 0.1 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 58 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® TF n H 03-155-1 Regulator stabilizing circuit time constant in seconds. Default = 1.4 Recommended interval is 0 < TF < 1.5 5≤ TF ≤ 15 KF TF1 n Regulator stabilizing circuit time constant in seconds. Default = 0.2 Recommended interval is 0 ≤ TF1 TF2 n Regulator stabilizing circuit time constant in seconds. Default = 0.3 Recommended interval is 0 ≤ TF2 KC n Rectifier loading factor proportional to commutating reactance. Default = 0.1 Recommended interval is KC ≤ 1 KD n Demagnetizing factor, a function of exciter alternator reactances. Default = 0.1 Recommended interval is KD ≤ 2 EXAMPLE: REGULATORS 4 TYPE = DSLS/EXBAS/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 VRMIN = −14 TB = 1 TC = 1.1 TE = 0.01 KP = 1 KI = 0.1 KC = 0.1 KD = 0.1 KE = 1 TR = 0.1 TF2 = 0.3 TF = 1.4 KF = 0.1 TF1 = 0.2 TA = 0.01 VRMAX = 18 KA = 4000 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 59 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Test of exciter EXBAS (figure below) VREG DYNAMIC DATA PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 150 5 * 100 5 U POS. UF VOLTAGE I POS. SPEED TETA O 1.1 X 4 3 + 2.4 1.05 1.1 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN 1.05 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC * * * * * * 50 1 3 1 1.8 * O * O O * O O O 5 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg 0 + 5 5 O + + + 5 5 5 5 5 3.333 X 6.667 X X X 10 13.333 16.667 X 20 23.333 X 26.667 X 30 X 33.333 36.667 TIME SECONDS DATE 11 AUG 2003 TIME 14:19:55 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) O + + + X O + + 0 0.95 2 1.2 0.95 + - 60 - DIAGRAM 1 SIMPO ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 15 IEEET4 IEEE Type 4 Excitation System V4=UF*SE(UF) VREF V4 VRMAX + VC - Σ 1 ∆V - 1 sTRH V1 -KR KR -1 ∆V < KV VRMIN VR + Σ V3 1 KE+ sTE ∆ V > KV VRMAX V2 -KV KV VRMIN Figure D.15 Block diagram of IEEET4 as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The input signal VC is the same as the signal mentioned as EC in PSS/E and the output signal UF is the same as the signal mentioned as EFD in PSS/E. The signal V1 is calculated according to the value of ∆V, see figure D.15, as follows: If -KR < ∆V < KR then V1 = 0 (15.1) If ∆V ≤ -KR then V1 = -1 (15.2) If ∆V ≥ KR then V1 = 1 (15.3) The signal V2 is calculated according to the value of ∆V, see figure D15.1, as follows: If -KV < ∆V < KV then V2 = 0 (15.4) If ∆V ≤ -KV then V2 = VRMIN (15.5) If ∆V ≥ KV then V2 = VRMAX (15.6) Parameter settings: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 61 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/IEEET4/ TRH n Rheostat time constant in seconds. Default = 40 Recommended interval is 12 < TRH < 100 VRMAX n Maximum value of limitation of the signal VRH in p.u Default = 9.9 Recommended interval is 2 < VRMAX <10 VRMIN n Minimum value of limitation of the internal signal VRH in p.u Default = 0 Recommended interval is 0 ≤ VRMIN < 2 KV n Specifies a deadband which is used in one of the block diagrams, see figure above. Default = 0.099 Recommended interval is 0.02 < KV < 0.1 KR n Specifies a deadband which is used in one of the block diagrams, see figure above. Default = 0.002 Recommended interval is 0.01 < KR < 0.05 KE n Exciter constant. Default = 0.099 Recommended interval is –1 < KE < 0.1 TE n Exciter time constant in seconds. Default = 0.099 Recommended interval is 0< TE < 1 E1 Set point for saturation p.u Default = 1.0 E2 Set point for saturation p.u Default = 1.2 SE1 Saturation Se at E1. Default = 0.2 SE2 Saturation Se at E2. Default = 0.6 1) If VRMAX is zero, the model will compute a new value of it. a) If KE is zero or negative, VRMAX will just allow the exciter to reach an output voltage of E2 i.e.: VRMAX = SE(E2 ) × E2 b) If KE is positive, VRMAX will just allow the exciter to reach an output voltage of E2 with the specified value of KE, i.e.: VRMAX = (SE (E2 ) + KE ) × E2 In either case above, VRMIN is then set to –VRMAX. 2) If KE is zero, the model will set a new value of KE. KE is set to the value that will require a voltage regulator output of (VRMAX /10) to maintain the present value of excitation voltage, UF, i.e.: KE = VRMAX – SE (UF) 10 ⋅ UF EXAMPLE: We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 62 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 REGULATORS 4 TYPE = DSLS/IEEET4/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 TE = 0.099 KE = 0.099 VRMIN = 0 TRH = 40 VRMAX = 9.9 KV = 0.099 KR = 0.002 END Test of exciter IEEET4 (figure below) VREG DYNAMIC DATA U POS. UF VOLTAGE I POS. SPEED TETA PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 5 1.1 O 1.05 3 X 4 + 2.4 1.05 1.1 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * 100 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC * * * * * * 50 1 3 0 0.95 1 O O O 5 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 8 5 + + + X 16 5 5 + + X 24 32 X O 5 + 48 5 X 56 O 64 + + + + X X 40 5 * 5 X X 72 80 88 TIME SECONDS DATE 11 AUG 2003 TIME 13:50:54 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 40 INST CONNECT LINE GENBUS MIDBUS AT 70 INST CONNECT FAULT F1 AT 70.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) O O 2 1.2 0.95 1.8 * O * O - 63 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 16 IEEEX4 IEEE Type 4 Excitation System We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 64 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Excitation system with DC generator commutator exciter and non-continuously acting regulators. VREF VRM AX KV VC 1 1 + sTR V1 - + ∑ VER R V2 V RMAX − V RM IN sK V T RH VRH - KV VR MIN If VERR ≥ KV, VR =VRM AX If |VER R| < KV, VR=VRH If VER R ≤ -KV, VR =VRM IN + 1 sTE V3 ∑ VR UF V4 KE+SE Figure D.16 Block diagram of IEEEX4 as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The input signal VC is the same as the signal mentioned as EC in PSS/E and the output signal UF is the same as the signal mentioned as EFD in PSS/E. Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/IEEEX4/ TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.1 Recommended interval is 0 < TR < 0.5 KV n Minimum / maximum value of the limiter for the output signal V2 in p.u. and it is a constant i block diagram, see figure. The signal V2 is between plus-minus KV. Default = 0.09 Recommended interval is 0.02 < KV < 0.1 VRMAX n Maximum value of limitation of the signal VR in p.u. Default = 9 Recommended interval is 2 < VRMAX < 10 VRMIN n Minimum value of limitation of the signal VR in p.u Default = 0 Recommended interval is 0 ≤ VRMIN < 2 TRH n Rheostat time constant in seconds. Default = 80 Recommended interval is 12 < TRH < 100 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 65 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 KE n Exciter constant. Default = 0.09 Recommended interval is –1 < KE < 0.1 TE n Exciter time constant in seconds. May be zero if KE is not equal to zero. Default = 0.9 Recommended interval is 0 < TE <1 E1 n Set point for saturation p.u Default = 1.0 E2 n Set point for saturation p.u Default = 1.2 SE1 n Saturation Se at E1. Default = 0.2 SE2 n Saturation Se at E2. Default = 0.6 1) If VRMAX is zero, the model will compute a new value of it. a) If KE is zero or negative, VRMAX will just allow the exciter to reach an output voltage of E2 i.e.: VRMAX = SE(E2 ) × E2 b) If KE is positive, VRMAX will just allow the exciter to reach an output voltage of E2 with the specified value of KE, i.e.: VRMAX = (SE (E2 ) + KE ) × E2 In either case above, VRMIN is then set to –VRMAX. 2) If KE is zero, the model will set a new value of KE. KE is set to the value that will require a voltage regulator output of (VRMAX /10) to maintain the present value of excitation voltage, UF, i.e.: KE = VRMAX – SE (UF) 10 ⋅ UF EXAMPLE: REGULATORS 4 TYPE = DSLS/IEEEX4/ E1 = 1.0 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 KE = 0.09 KV = 0.09 TE = 0.9 VRMAX = 9 TRH = 80 VRMIN = 0 TR = 0.1 END Test of exciter IEEEX4 (figure below) We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 66 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VREG DYNAMIC DATA 10 1.1 X U POS. UF VOLTAGE I POS. SPEED TETA O PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 + 1.6 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN 1.1 *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 100 1.05 * * * * 50 * 1 8 6 1 1.344 1.05 1.472 * O * * O O O O * O O O + O 0.95 1.216 4 0.95 0 0.9 2 0.9 -50 5 5 5 5 5 5 5 + 5 + + + + -100 + 0.85 0 5 + + 0.96 0.85 1.088 + X 0 X 8 X 16 24 32 X X 40 X 48 X X 56 64 X * 72 80 88 TIME SECONDS ID VREG JOB vreg DATE 1 SEP 2003 TIME 13:51:08 DIAGRAM SIM 1 Compared to standard type 4 (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 10 1.1 150 8 1.05 100 5 1.1 O 1.6 X 1.05 + U POS. UF VOLTAGE I POS. SPEED TETA 1.472 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * * * * * 0 -50 * 50 0.95 0.9 1 6 4 2 1 1.344 0.95 1.216 0.9 1.088 * O O * 5 5 5 O 5 5 * O 5 O 5 O 5 5 + + + + + + + X 0 8 X 16 X 24 32 X 40 X 48 X X X 56 64 72 * 80 X 88 TIME SECONDS DATE 27 MAY 2003 TIME 15:51:53 RUN INSTRUCTION (for the two figures above) AT 1 increase VREF by 5%. AT 60 INST CONNECT LINE GENBUS MIDBUS AT 80 INST CONNECT FAULT F1 AT 80.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) O + -100 0.85 0 0.96 0.85 O + + ID VREG JOB vreg O - 67 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 17 IEET1A Modified IEEE Type1 Excitation System We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 68 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VRMAX VREF FDMA + VC - ∑ V1 VS + ∑ KA 1 + sTA V2 VF VR + ∑ V3 1 sTE V5 FDMI VRMIN sKF 1 + sTF UF V4 KE+SE Figure D.17 Block diagram of IEET1A as modelled in Simpow The parameters E1, SE1, EFDM and SEMAX describes a quadratic saturation function with respect to SE(UF). The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E UF EFD FDMA EFDMAX FDMI EFDMIN VS VOTHSG +VUEL + VOEL VC EC Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n =DSLS/IEET1A/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 KA n Regulator gain in p.u. Default = 499 Recommended interval is 10 < KA < 500 TA n Regulator amplifier time constant in seconds. May be zero. Default = 0 Recommended interval is 0 ≤ TA < 1 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 8 Recommended interval is 0.5 < VRMAX < 10 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 69 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VRMIN n Minimum value of limitation of the signal VR in p.u Default = −4 Recommended interval is −10 < VRMIN < 0 KE n Exciter constant. Not used if VR is given. Default = 1 Recommended interval is −1 ≤ KE ≤ 1 TE n Exciter time constant in seconds. May be zero if KE isn’t set to zero. Default = 0.3 Recommended interval is 0 < TE < 1 TF n Regulator stabilizing circuit time constant in seconds. TF > 0 Default = 1.3 5 ≤ TF/KF ≤ 15 KF n Regulator stabilizing circuit gain p.u. Can not be zero. Default = 0.1 Recommended interval is 0 < KF < 0.3 FDMI n Minimum value of limitation of the signal UF in p.u Default = −5 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 FDMA n Set point for saturation.p.u. Default = 2 SEMAX n Saturation Se at E2. Default = 0.6 EXAMPLE: REGULATORS 4 TYPE = DSLS/IEET1A/ E1 = 1.0 SE1 = 0.2 FDMA = 2 SEMAX = 0.6 FDMI = −5 TA = 0 TF = 1.3 KF = 0.1 VRMIN = −4 VRMAX = 8 KA = 499 KE = 1 TE = 0.3 END Test of exciter IEET1A (figure below) We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 70 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 1.1 3 5 1.1 150 4 1.05 100 3 1 50 5 2.4 O 1.05 X 1 + U POS. UF VOLTAGE I POS. SPEED TETA 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN * O * * O O O 5 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 X 0 2 5 X 4 * O O O + + + + 5 5 5 O + 5 5 5 + + + * * O X 6 X X 8 10 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 1 SEP 2003 TIME 14:02:52 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) * * + 5 + ID VREG JOB vreg * 0 0.95 2 1.2 0.95 X * - 71 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 18 IEET1B We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 72 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Modified Type 1 Excitation System sKF 1 1 + sTF 1 V9 SWITCH=1 SWITCH=0 V7=UF*SE(UF) QEG VC ÷ VR/KA XE VREF + + VSMAX Σ V1 1 1 + sTR VT - Σ V3 + V2 - VRMAX V10 + + Σ V4 + - Σ V5 KA 1 + sTA1 V7 VR VREG 1 1 + sTA 2 + Σ - V6 1 sTE + V8 VSMIN VS VRMIN - KE Figure D.18 Block diagram of IEET1B as modelled in Simpow The parameters E1, SE1, E2 and SE2 describes a quadratic saturation function with respect to SE(UF). The value of the signal (VR/KA) is calculated during the initiating and is constant thereafter. The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E UF EFD VR/KA BIAS QEG/VC IMAG VS VOTHSG +VUEL + VOEL VC EC Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/IEET1B/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 TR n Voltage transducer filter time constant. Default = 0.001 VSMAX n Maximum value of limitation of the signal V3in p.u We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 73 - UF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 Default = 8 VSMIN n Minimum value of limitation of the signal V3 in p.u Default = −2 KA n Regulator gain in p.u. Default = 800 TA1 n Regulator amplifier time constant in seconds. Default = 0.0001 VRMAX n Maximum value of limitation of the signal VR in p.u Default = 8 VRMIN n Minimum value of limitation of the signal VR in p.u Default = −4 TA2 n Regulator amplifier time constant in seconds. Default = 0.001 KE n Exciter constant. Not used if VR is given. Default = 0.1 TE n Exciter time constant in seconds. Default = 0.008 TF1 n Regulator stabilizing circuit time constant in seconds. Default = 1 KF1 n Regulator stabilizing circuit gain p.u. Default = 0.1 E1 n Set point for saturation.p.u. Default = 1.0 SE1 n Saturation Se at E1. Default = 0.2 E2 n Set point for saturation.p.u. Default = 1.2 SE2 n Saturation Se at E2. Default = 0.6 1) If VRMAX is zero, the model will compute a new value of it. a) If KE is zero or negative, VRMAX will just allow the exciter to reach an output voltage of E2 i.e.: VRMAX = SE(E2 ) × E2 b) If KE is positive, VRMAX will just allow the exciter to reach an output voltage of E2 with the specified value of KE, i.e.: VRMAX = (SE (E2 ) + KE ) × E2 In either case above, VRMIN is then set to –VRMAX. 2) If KE is zero, the model will set a new value of KE. KE is set to the value that will require a voltage regulator output of (VRMAX /10) to maintain the present value of excitation voltage, UF, i.e.: KE = VRMAX – SE (UF) 10 ⋅ UF EXAMPLE: REGULATORS 4 TYPE = DSLS/IEET1B/ E1 = 1 SE1 = 0.2 E2 = 1.2 SE2 = 0.6 TF1 = 1 KF1 = 0.1 XE = 0.0989 KE = 0.1 TE = 0.008 TA2 = 0.001 VRMAX = 8 VRMIN = −4 KA = 800 TA1 = 0.0001 VSMIN = −2 VSMAX = 8 TR = 0.001 END Test of exciter IEET1B (figure below) We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 74 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 150 100 5 1.1 O 1.05 3 X U POS. UF VOLTAGE I POS. SPEED TETA 4 1.1 2.4 + 1.05 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * 50 1 3 1 1.8 O * O O * O O O O O O 0 0.95 2 1.2 0.95 + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 ID VREG JOB vreg X 0 2 5 X 4 + 5 X 6 + 5 + 5 + 5 5 10 X X X X 8 12 14 16 18 X 20 22 TIME SECONDS DATE 28 AUG 2003 TIME 10:34:58 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) 5 + + + + * * * * * - 75 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 19 URST5T We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 76 - ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 IEEE Proposed Type ST5B Excitation System VU VC 1 1 + sTR V1 - Σ V2 VRMAX / KR WFC HV GATE LV GATE V3 + Σ V4 1 + sTC1 1 + sTB1 V5 VRMAX VRMAX / KR 1 + sTC 2 1 + sTB 2 V6 KR V7 VRMAX * UT 1 1 + sT 1 V8 + Σ + + VREF VS UF - V9 VRMIN / KR VRMIN VRMIN / KR VRMIN * UT KC Figure D.19 Block diagram of URST5T as modelled in Simpow The following input/output signals in the block diagram are defined in Simpow and PSS/E respectively as: Simpow PSS/E VC EC VS VOTHSG VU VUEL WFC VOEL UT VT IF IFD UF EFD Parameter settings: n Unique number of the regulator. This number must be the first data, beginning in column 1-4. TYPE n = DSLS/URST5T/ NSWS n Number of associated system stabilizers. Default = 1 SWS n Identification number of the associated system stabilizers. NSWS stabilizers must be given. Default = 0 SWU n Identification number of the associated under excitation limiter which gives the value of VU. See “Under Excitation Limiter”. Default = 0 SWOF n Identification number of the associated over excitation limiter which gives the value of WFC. (The parameter SWOF is often used when associating a field current limiter but not for this exciter.) Default = 0 TR n Voltage transducer filter time constant. Shall be given in seconds. Default = 0.001 TB1 n Voltage regulator time constant in seconds. Default = 1 TC1 n Voltage regulator time constant in seconds. Default = 1.1 We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) - 77 - IF ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® H 03-155-1 TC2 n Voltage regulator time constant in seconds. Default = 1 TB2 n Voltage regulator time constant in seconds. Default = 1.2 VRMAX n A parameter for calculating the maximum value of the output signal for the filters in p.u. see figure. Default = 10 VRMIN n A parameter for calculating the minimum value of the output signal for the filters in p.u. see figure. Default = −1 KR n Voltage regulator gain in p.u. and it is also a parameter for calculating the maximum and minimum values of the filters output signal, see figure. Default = 80 T1 n Voltage regulator amplifier time constant in seconds. Default = 0.0001 KC n Gain in p.u. Default = 0.01 EXAMPLE: REGULATORS 4 TYPE = DSLS/URST5T/ TR = 0.001 TC2 = 1 TC1 = 1.1 T1 = 0.0001 TB2 = 1.2 TB1 = 1 VRMIN = −1 KC = 0.01 KR = 80 VRMAX = 10 END Test of exciter URST5T (figure below) VREG DYNAMIC DATA *=SYNC +=SYNC X=SYNC O=SYNC 5=SYNC 150 100 50 3 5 3 2.4 1.1 1.1 1.05 1 PU 10.00/SQRT[3] KV PU PU 0.58 KA PU DEGREES RELATIVE TO GRIDGEN 5 1.05 O 1 X U POS. UF VOLTAGE I POS. SPEED TETA 4 + 1.8 * TESTGEN TESTGEN TESTGEN TESTGEN TESTGEN X * * * O * O O * * * O O O O O O + 0 0.95 2 1.2 0.95 + 5 5 + 0.9 0.6 1 0.9 -50 0.85 0 0 0.85 -100 + ID VREG JOB vreg X 0 5 X 4 6 X 8 X 10 + 5 + 5 5 5 X X 12 14 16 18 X 20 22 TIME SECONDS DATE 11 AUG 2003 TIME 14:08:25 RUN INSTRUCTION AT 1 increase VREF by 5%. AT 8 INST CONNECT LINE GENBUS MIDBUS AT 16 INST CONNECT FAULT F1 AT 16.1 INST DISCONNECT FAULT F1 END We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) + + + X 2 + 5 5 * * * - 78 - DIAGRAM 1 SIM ABB Power Technologies Technical Report Implementation of PSS/E-regulators in SIMPOW® We reserve all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Power Technologies (SE) H 03-155-1 - 79 -