International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 A Novel Controlled Technique for a Dual Unified Power Quality Conditioner 1 2 P. Lavanya Rekha , K.V.Sai Kumar PG Student, Department of EEE, KIET, Kakinada, India.1 Asst. Professor, Department of EEE, KIET, Kakinada, India.2 Abstract: This paper proposes a novel controlled technique for Dual three phase topology of unified power quality conditioner (dUPQC) adopted to compensate current and voltage quality problems of Non-linear loads. This project tends look at the solving the problems by using custom power devices by Dual Unified Power Quality Conditioner (dUPQC) using Fuzzy Logic Controller. A Fuzzy Logic controller is based on fuzzy sets and fuzzy rules with their membership functions of inputs and outputs. A Control technique of two active filters is to control the sinusoidal references. In dUPQC, series Active Filter (SAF) works as a current source and Parallel Active Filter(PAF) works as a voltage source different from a conventional UPQC and due to these there is a high and low impedances occurs which is indirectly compensates the harmonics and disturbance of the grid voltage and load current and also impedance path is low harmonic at load current. To deal with sinusoidal reference for wellknown frequency spectrum, a technique of pulse width modulation (PWM) is used. The proposed system can be able to compensate the non linear load condition and also ensure the sinusoidal voltage for the load in all the three phases. This results in the better power quality. It is important to note that the existing UPQC topology does not have this capability. A simulation design control, power flow analysis is proposed in Dual unified power quality conditioner and to eliminate harmonics using Fuzzy Logic controller (FLC). The simulation is verified using MATLAB/SIMULINK. Keywords : UPQC, Active Filters : SAF and PAF, Fuzzy Logic controller, Power Line conditioner, PWM. I.INTRODUCTION Presently, power quality problems in grid-integrated applications take great interest because of the growing applications in power electronics. Due to increasing complexity in the power system, power quality problems are most significant problems. If the power quality problem surpasses, leads to major problems, which ultimately leads to wastage of resources as well as financial losses. Non linear loads always reduces the power quality at electrical grid and contain a high harmonic content which effect the critical loads. To overcome such problems we are using a Unified power quality conditioners. The usage of power quality conditioners in the distribution system network has increased during the past years due to the steady increase of nonlinear loads connected to the electrical grid. The current exhausted by nonlinear loads has a high harmonic content, distorting the voltage at the utility grid and consequently affecting the operation of critical loads. By using a unified power quality conditioner (UPQC), it is possible to ensure a regulated voltage for the loads, balanced and with low harmonic distortion and at the same time exhausting undistorted currents from the utility grid, even if the grid voltage and the load current have harmonic contents. In UPQC they are two types of filters SAF and PAF, PAF is a current source and SAF is a voltage source both of them are a non-sinusoidal reference and also compensate the harmonic in grid voltage and load current. It is a complex method to solve such problems we are using active filters to control the harmonics and to eliminate harmonics using fuzzy controller. Its conditioner consists of two single-phase current source inverters where the SAF is controlled by a current loop and the PAF is controlled by a voltage loop both of them are interconnected to fuzzy controller and grid current and load voltage are sinusoidal, and therefore, their references are also sinusoidal. This concept is called “dual topology of unified power quality conditioner” (iUPQC), and the control schemes use the p−q theory, for a real time of positive sequence . The aim of this paper is to propose a novel controlled technique for Dual unified Power Quality Conditioner for power quality improvement to eliminate the harmonics from source to load . In ABC reference frame, the proposed control scheme is developed for the classical control theory is without the need for coordinate transformers and digital control implementation. The references to both SAF and PAF with fuzzy logic controller is a pure sinusoidal, dispensing the harmonic extraction from the grid current and load voltage. II. DUAL UNIFIED POWER QUALITY CONDITIONER (dUPQC) Dual Unified power quality conditioner (dUPQC) its structure is shown in Fig.1. Different from a conventional UPQC, in dUPQC, the SAF works as a current source and PAF works as a voltage source both of them are synchronized with the grid voltage uses sinusoidal 4170 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 references to the classical topology for both active filters. The high impedance occurs at SAF to indirectly compensate the harmonics, unbalances, and disturbances of the grid voltage. The connection transformer voltages are equal to the difference between the grid voltage and the load voltage. In the same way, the PAF indirectly compensates the unbalances, displacement, and harmonics of the grid current, providing a low-impedance path for the harmonic load current. Table 1.FuzzyRules In this system the input scaling factor is between -1 and +1 has design. The triangular shape of the membership function of this arrangement presumes that for any particular input there is only one dominant fuzzy subset . The input error E(k) and change in error C(k) for the FLC is given as ሻ = ሻ − ( − 1) Fig. 1. Dual UPQC (dUPQC) III. FUZZY LOGIC CONTROL Fig.3 Input1 Membership function FLC determined by the set of linguistic rules. The mathematical modeling is not required in fuzzy controller due to the conversion of numerical variable into linguistic variables. FLC consists of three part: a. Fuzzification, b. Interference engine, c. Defuzzification. The fuzzy controller is characterized as; For each input and output there are seven fuzzy sets. For simplicity a membership functions is Triangular. Fuzzification is using continuous universe of discourse. Implication is using Mamdani's "min" operator. Defuzzification is using the "height" method. FLC block diagram as shown in figure 2. Fig.4 Input2 Membership function b. Inference Method Several composition methods such as Max-Min and MaxDot have been proposed and Min method is used. Minimum operator and Maximum operator of output membership function is of each rule and it is shown in Table 1. c. Defuzzification Fig. 2. Fuzzy Logic Controller a. Fuzzification Membership function values are assigned to the linguistic variables, using seven fuzzy subsets: NB(Negative Big), NM(Negative Medium), NS (Negative Small), ZE (Zero), PS (Positive Small),PM(Positive Medium) and PB (Positive Big). The partition of fuzzy subsets and the shape of membership function adapt the shape up to appropriate system. Input error E(k) and change in error CE(k) of values which is normalized by an input scaling factor as shown in table 1. As a plant usually requires a non-fuzzy value of control, a defuzzification stage is needed. To compute the output of the FLC, "height" method is used and the FLC output modifies the control output.Further, the output of FLC controls the switch in the inverter. In order to control these parameters, they are sensed and compared with the reference values. To achieve this, the membership functions of Fuzzy controller are: error, change in error and output as shown in Figs.(3), (4). In the present work, for fuzzification, nonuniform fuzzifier has been used. If the exact values of error and change in error are small or large, they are divided conversely. = −[ + 1 − ሻ ∗ ] (3) The α is self-adjustable factor and to regulate operation. E 4171 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 is the error of the system, C is the change in error and u is the control variable. If the system is not in balanced it indicates an error 'E' if the value is large. While the error 'E' value is small it indicates that the system is near to balanced state. If system is unbalanced, the control variables should be enlarge to balance the system as early as possible. For system stability overshoot plays an important role. For restraining oscillations and system stability it requires less overshoot. 'C' plays an important role, while the role of 'E' is diminished. The optimization is done by α. The set of Fuzzy controller rules is given in Table 1. V. OUTPUT PASSIVE FILTER DESIGN Single-phase wiring diagram ofdUPQC, is shown in Fig. 6. The grid impedance is Zs = jωLs + Rs, and leakage impedance of coupling transformer is Zlg = jωLlg + Rlg, in series and shunt filters, the voltage sources is vsc and vpc and the harmonic which are generated from the switches are composed by the components. The high frequency of iUPQC is filtered by the output passive filters for sinusoidal grid current and load voltage as shown in Fig.6. IV. POWER CIRCUIT The power circuit of the proposed scheme of dUPQC is made up of two four-wire three-phase converters connected back to back and their respective output filters, as shown in Fig.5. Three single-phase transformers are used to connect the SAF to the utility grid, and PAF is connected to the load. The design specifications of the dUPQC as shown in Table 3. The passive components are shown in Table 2. Fig.6 Single-phase wiring diagram of the dual UPQC SAF and PAF output impedances is as shown in Fig.7 and Fig.8. The current source is in series and connected to voltage source vsc and inductance Lsf, in PAF. The transfer function of PAF in high-frequency filter is derived in equation (1) and circuit is shown in Fig.8. Fig.5 Power circuit of the dUPQC. TABLE 1 Leakage inductance of SAF coupling Transformer Transformer ratio of the SAF coupling Transformer SAF connection inductance PAF connection inductance DC Link Capacitance Llg=2.33mH Fig.7 Equivalent circuit as viewed by SAF. n=1 Lsf=650µH Lpf=650µH Cb =3mF Fig.8 Equivalent circuit as viewed by PAF TABLE2: COMPONENT SPECIFICATION OF POWER MODULES Input line to line RMS voltage The high frequency filter transfer function of the PAF is derived by analysing the circuit as shown in Fig.8. Vin=220V Output nominal power Po=2500VA DC link voltage Vb=400V Utility grid frequency fgrid=50Hz Switching frequency of SAFs and PAFs Transformer ratio fs=20KHz n=1 Power design of inductor Lpf and cut off frequency of filter capacitor Cpf which is of 2.9 kHz and 10μF. The transfer function of SAF in high-frequency filter is derived in equation (2) and circuit is shown in Fig.7. and also the α,β,γ equations (3),(4) and (5). 4172 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 Here cutoff frequency of filter capacitor Cpf which is of 45kHz and 1μF. The low cutoff frequency response is to reduce the filter bandwidth of the SAF, and grid voltage contents the harmonic. The leakage impedance of coupling transformers is of low-frequency attenuation is undesirable and intrinsic towards the characteristic. As per the previous articles, it deal with the same dUPQC control strategy, the output filter of inductor is impose of voltage and SAF current and through the filter its frequency is sinusoidal with current. It is a narrow band frequency control to distort the current drained from the utility grid. The usage of high-power coupling transformers, with low leakage inductance, and the design of higher voltage dc link, allowing the imposition of higher current rate of change on the filter output inductor, and solutions to change the characteristics of the filter in low frequencies. VI. PROPOSED CONTROL SCHEME The proposed iUPQC control structure is an ABC reference frame based on the compensation of harmonics, unbalances, disturbances, and displacement . To compensate we are using the SAF is a current loop and PAF is a voltage loop in order to ensure the sinusoidal grid current and load voltage with low harmonic distortion. The dc link voltage is a reference amplitude for the current loop, in the power factor converter control schemes of SAF. With the sinusoidal references for both SAF and PAF controllers are generated by a digital signal processor (DSP), and to ensure the grid voltage synchronism using a phase locked loop. A. SAF Control: The control block diagram for the SAF as shown in Fig.9. It consists of two voltage loops and three current loops.The current loops are responsible for tracking the reference to each grid input phases. The dc link voltage is regulated to one voltage loop and another voltage loop is avoiding the unbalance towards dc link capacitors and grid current is independently tracking to each grid input reference. For a low- frequency of total dc link voltage control loop and its response is determined the reference amplitude for the current loops. Due to these we can increase the load to overcoming input of grid current and to decrease the voltage of an dc link supplies of an resultant active power consumption. The grid current reference is increased by voltage controller to restore the dc link voltage. The neutral point of three phase four wire converter is represent by the circuit is shown in Fig.9 and current source is parallel with the dc link impendence and its source is average charge of current . The resistor Rb is infinite (Rb →∞); in a circuit to represent instantaneous active power consumption of the dc link is related to switching period is null for the utility grid voltage frequency. The average charge current of the dc link is given by Fig.9 :Control block diagram of the SAF controller The control block diagram for the SAF as shown in Fig.9. It consists of two voltage loops and three current loops.The current loops are responsible for tracking the reference to each grid input phases. The dc link voltage is regulated to one voltage loop and another voltage loop is avoiding the unbalance towards dc link capacitors and grid current is independently tracking to each grid input reference. For a lowfrequency of total dc link voltage control loop and its response is determined the reference amplitude for the current loops. Due to these we can increase the load to overcoming input of grid current and to decrease the voltage of an dc link supplies of an resultant active power consumption. The grid current reference is increased by voltage controller to restore the dc link voltage. The neutral point of three phase four wire converter is represent by the circuit is shown in Fig.9 and current source is parallel with the dc link impendence and its source is average charge of current . The resistor Rb is infinite (Rb →∞); in a circuit to represent instantaneous active power consumption of the dc link is related to switching period is null for the utility grid voltage frequency. The average charge current of the dc link is given by 4173 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 Through equation (6), the voltage loop transfer fumction is obtained and is presented by equation (7) cycle. The single-phase four wire convertor is of two current sources on the inverter switches. The unbalanced voltage loop transfer function is obtained by mesh analysis and Laplace is given by Where: Vgdpk - Peak of grid voltage; The open-loop transfer function (OLT Fd) is given by eqn (10) Vb - dc link voltage; Rb - load equivalent resistance; Cb - Total dc link equivalent capacitance; n - Transformer ratio; The open loop transfer function (OLTFv) is given by equation (8): Where: Kmfs - Multiplier gain; Kvsf - Voltage sensor gain; Kisf - Current sensor gain; A proportional integral (PI) controller is designed to eliminate, and ensures a crossover frequency of 0.5Hz and a phase margin of 50◦ with frequency of differential voltage loop , and including the open-loop transfer function (OLTFd), controller transfer function (Hdsf ), compensated loop transfer function (OLTFd + Hdsf ). It consists of three identical current loops, except for the 120◦ phase displacements. To decoupling the voltage loop and its source on the coupling transformer and the current loop transfer function as shown in Fig.11.The dynamic model of an circuit has an average value related to the switching period and voltage vs(t) and vL(t) are constants. The current loop transfer function and small signal is analyzed by Laplace is given by and in Ls - series grid Fig.10 Equivalent circuit of the SAF voltage loop. Rs – series grid resistance Llg – Leakage inductance of the coupling transformer Rlg – Series resistance of the coupling transformer The open loop transfer function (OLTFi) is given by eqn (13) Fig.11 Single-phase equivalent circuit of SAF Where A proportional integral (PI) controller is designed to regulate, and ensures a crossover frequency of 4 Hz and a phase margin of 45◦ with total voltage loop frequency, and including the K pwmsf - Series filter PWM modulator gain; open-loop transfer function (OLTFv), controller transfer The K pwmsf gain equals the inverse peak value of the triangular carrier. A proportional integral (PI) controller is designed to tack the current reference, and ensures a crossover frequency of 5 kHz and a phase margin of 70◦ with frequency response of current loop, and including the open-loop transfer function (OLTFi), controller transfer function (Hisf ), compensated loop transfer function (OLTFi + Hisf ). function (Hvsf ), compensated loop transfer function (OLTFv+ Hvsf ). Under the unbalanced voltage loop condition the grid current reference is CL1 and CL2 is equilibrium the voltage loop in a dc link capacitor. To analysis of these function a current isc(t) is a neutral point, and d(t) is a duty 4174 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 B. PAF Control A control block diagram of shunt active filter is shown in Fig.12.The control scheme of three identical load voltage and towards feedback loops in 120◦ phase displacement. VII. SIMULATION OF dUPQC AND SIMULINK RESULTS Simulation was built in several steps from grid source to load, Dual UPQC operation at different loads is as shown in figure 14. Power Circuit of DUPQC is made up of two four wire three-phase converters connected back-back and their respective output filters as shown in figure 15. The Control structure is an ABC reference frame based where SAF and PAF are controlled in an independent way. SAF Control block is as shown in figure 16 and PAF control block is as shown in figure 17. Fig.12 Control block diagram of the PAF voltage loop The transfer function of voltage loop is analyzed by a single-phase equivalent circuit as shown in Fig.13.The voltage loop transfer function is using average values for switching period and small signal is analyzed by Laplace is given Fig. 14 Simulink design of Dual UPQC Fig.13 Single-phase equivalent circuit of PAF. Where Gvpf (s) = VL (s)/D(s). The open loop transfer function (OLT F vpf ) is given by equation(15): Where: K pwmpf - Shunt filter PWM modulator gain; An additional (PID) pole controller is designed to track the voltage reference, and ensures a crossover frequency in a proportional integral derivate of 4 kHz and a phase margin of 35◦ with frequency response of voltage loop, and including the open-loop transfer function (OLTFvpf ), controller transfer function (Hvpf ), compensated loop transfer function (OLTFvpf + Hvpf ). Fig. 16 SAF Control Block 4175 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 FIG.18.(b)Source Current (Iabc) ( 20A/div, 5ms/div) Fig. 15 Power Circuit of Dual UPQC Fig.18.(c) Load Voltage (Vabcl) (200V/div, 5ms/div) Fig. 17 PAF Control Block Fig.18.(d) Load Current (Iabcl)(20A/div, 5ms/div) The result is obtained through fuzzy based Dual Unified Power Quality Conditioner for power quality improvement. From grid source to load we are eliminating the harmonics using SAF and PAF filters and Fuzzy Logic Controller and injecting the dip voltage and compensating with DC link current load to discrete the RMS voltage. Hence the result output is without harmonics from grid source to load. Fig.18.(e) PAF Currents (IFabc) (10A/div, 5ms/div) FIG.18.(a) Source Voltages (Vabc )(200V/div, 5ms/div) Fig.18. (f) SAF Voltages (VFabc) (20V/div, 2.5ms/div) 4176 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 Fig 19(a) Waveform of three phase source voltages with voltage dip in phase A and load voltage with FLC. Fig 19(e) Waveform of DC Link Voltages (100V/div, 50ms/div) and Load currents (10A/div, 50ms/div) during a load step from 100% to 50% with FLC. VIII. CONCLUSION Fig 19(b) Waveform of three phase load voltage and source currents during a voltage dip in phase A with FLC Fig 19(c) Waveform of three phase Load Voltages (200V/div, 5ms/div) and Load Currents (10A/div, 5ms/div) during a load step from 50% to 100% with FLC . The results obtained with iUPQC using Fuzzy Logic Controller and design with Matlab Simulation Technique in ABC reference frame works very well and was able to compensate the harmonics from nonlinear load current. The proposed scheme of iUPQC using fuzzy controller in ABC reference frame of both the active filters and their control loops are generated by a digital control system blocks and to related to other proposed controls its utilization is better for a sinusoidal reference and to eliminate the harmonic from source to load. The main advantages of this proposed control in relation to other proposed schemes were the utilization of sinusoidal references for both series and shunt active filters controls without the need for complex calculations or coordinate transformations..Both the active filters from source to load are dip by the RMS voltage in phase ''A'' to eliminate the harmonics from grid source voltage to load current using fuzzy controller. The results validate the proposed dUPQC control scheme proving that the power quality can be meaningfully better with Fuzzy controller which uses only synchronized sinusoidal references. REFERENCES Fig 19 (d) Waveform of Load Voltages (200V/div, 5ms/div) and Load Currents (10A/div, 5ms/div)during a load step from 100% to 50% with FLC. [1] Raphael J. Millnitz dos Santos, Jean Carlo da Cunha, and Marcello Mezaroba, Member, IEEE “A Simplified Control Technique for a Dual Unified Power Quality Conditioner”, ieee transaction on industrial electronics,vol.61.no.11,Nov 2014. [2] M. Aredes, K. Heumann, and E. Watanabe, “An universal active power line conditioner,” IEEE Trans. on 4177 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR International Journal of Science, Engineering and Technology Research (IJSETR), Volume 4, Issue 12, December 2015 Power Deliv., vol. 13, no. 2, pp. 545– 551, Apr 1998. [3] H. Fujita and H. Akagi, “The unified power quality conditioner: the integration of series and shunt-active filters,” IEEE Trans. on Power Electron., vol. 13, no. 2, pp. 315–322, Mar 1998. [5] B. Han, B. Bae, S. Baek, and G. Jang, “New configuration of upqc for medium-voltage application,” IEEE Trans. on Power Deliv., vol. 21, no. 3, pp. 1438– 1444, July 2006. [6] S. Chakraborty, M. Weiss, and M. Simoes, “Distributed intelligent energy management system for a single-phase high-frequency ac mi- crogrid,” IEEE Trans. on Ind. Electron., vol. 54, no. 1, pp. 97–109, Feb 2007. [7] M. Forghani and S. Afsharnia, “Online wavelet transform-based control strategy for upqc control system,” IEEE Trans. on Power Deliv., vol. 22, no. 1, pp. 481–491, Jan 2007. [8] A. Jindal, A. Ghosh, and A. Joshi, “Interline unified power quality conditioner,” IEEE Trans. on Power Deliv., vol. 22, no. 1, pp. 364–372, Jan 2007. [9] Y. Kolhatkar and S. Das, “Experimental investigation of a single-phase upqc with minimum va loading,” IEEE Trans. on Power Deliv., vol. 22, no. 1, pp. 373–380, Jan 2007. [10] M. Basu, S. Das, and G. Dubey, “Investigation on the performance of upqc-q for voltage sag mitigation and power quality improvement at a critical load point,” IET Generation Transmission Distribution, vol. 2, no. 3, pp. 414–423, May 2008. [11] V. Khadkikar and A. Chandra, “A new control philosophy for a unified power quality conditioner (upqc) to coordinate load-reactive power demand between shunt and series inverters,” IEEE Trans. on Power Deliv., vol. 23, no. 4, pp. 2522–2534, Oct 2008. [12] M. Aredes and R. Fernandes, “A dual topology of unified power quality conditioner: The iupqc,” in 13th European Conf. on Power Electron. and Appl., Sept 2009, pp. 1–10. 4178 ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR