STAMPED REVISION 1 ELECTRICAL 2015-04

advertisement
ENGINEER STAMP:
SYMBOL LEGEND
SYMBOL
DESCRIPTION
SYMBOL LEGEND
SYMBOL
REFERENCE AND LINE SYMBOLS
XX
X-XXX
?
X
XX-XX
WP
DETAIL INDICATOR: XX INDICATES DETAIL NUMBER, X-XXX
INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.
DESCRIPTION
SYMBOL LEGEND
SYMBOL
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER, WEATHERPROOF: NEMA 5-20R.
SYMBOL
DESCRIPTION
STRUCTURED CABLING
XX
C/B
DIGITAL MULTIMETER (ONE-LINE DIAGRAM).
SERVICE ENTRANCE SURGE PROTECTION (ONE-LINE
DIAGRAM).
RECEPTACLE, QUADRAPLEX: NEMA 5-20R.
KEYNOTE INDICATOR.
REVISION INDICATOR.
RECEPTACLE, SPECIAL PURPOSE. PROVIDE RECEPTACLE TO
MATCH EQUIPMENT PLUG.
EQUIPMENT INDICATOR.
SWITCH, SINGLE POLE ("x" INDICATES FIXTURES
CONTROLLED).
BREAK, ROUND.
2
SWITCH, DOUBLE POLE ("x" INDICATES FIXTURES
CONTROLLED).
3
SWITCH, THREE-WAY ("x" INDICATES FIXTURES
CONTROLLED).
SOLID STATE REDUCED VOLTAGE MOTOR STARTER.
GENERATOR, POWER (ONE-LINE DIAGRAM).
X
METER.
XX
VARIABLE FREQUENCY DRIVE (ONE-LINE DIAGRAM).
DISCONNECT SWITCH, FUSED.
STARTER (ONE-LINE DIAGRAM).
W
TELEPHONE, WALL MOUNTED: WALL PHONE.
X
OUTLET, DATA COMMUNICATION ("X" INDICATES QUANTITY
OF CABLES).
X
OUTLET, BUILDING STANDARD COMBINATION TELEPHONE/
DATA COMMUNICATION.
SYMBOL
C/B
WI-FI.
CIRCUIT BREAKER, MOLDED CASE (ONE-LINE DIAGRAM).
PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.
C/B
ELECTRICAL POWER AND DISTRIBUTION
CIRCUIT BREAKER, MOLDED CASE WITH SHUNT TRIP
CONT? (ONE-LINE DIAGRAM).
FUSE WITH RATING (ONE-LINE DIAGRAM).
J
JUNCTION BOX.
X
PULL BOX.
FUSE
EARTH GROUND (ONE-LINE DIAGRAM).
DISC
DISC
DESCRIPTION
PANELBOARD CABINET, FLUSH MOUNTED.
SWITCH, ESD (EMERGENCY STOP DEVICE).
CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR.
REFER TO ONE-LINE DIAGRAM.
MISCELLANEOUS
SYMBOL LEGEND
DISCONNECT SWITCH, NONFUSED.
CONT?
WIRING METHODS
X
OVERLOAD RELAY (ONE-LINE DIAGRAM).
SWITCH, KEY OPERATED.
K
LIGHTING (REFER TO FIXTURE SCHEDULE FOR SYMBOLS)
(W-3)
FIXTURE IDENTIFICATION: (W-3) INDICATES FIXTURE TYPE AS
SCHEDULED.
C/B
CIRCUIT BREAKER, MOTOR CIRCUIT PROTECTION (ONE-LINE
CONT? DIAGRAM).
DISCONNECT, FUSED (ONE-LINE DIAGRAM).
(W-3)
C/B
DISCONNECT, NONFUSED (ONE-LINE DIAGRAM).
CONT?
CIRCUIT BREAKER, SOLID STATE (ONE-LINE DIAGRAM).
FIXTURE IDENTIFICATION, EMERGENCY WITH BATTERY PACK,
CONNECTED TO GENERATOR AS INDICATED: (W-3) INDICATES
FIXTURE TYPE AS SCHEDULED.
GROUND CONNECTION.
CONDUIT SEAL OFF (ONE LINE DIAGRAM).
C/B
C/B
WIRING DEVICES
CIRCUIT BREAKER, SOLID STATE WITH GROUND FAULT
CONT? PROTECTION (ONE-LINE DIAGRAM).
GFP
CONT?
RECEPTACLE, SINGLE: NEMA 5-20R.
MOTOR.
X
RECEPTACLE, SINGLE: NEMA 10-30R.
G
GREEN LIGHT.
R
RED STROBE.
LIGHTING CONTROL
P
MOTOR CIRCUIT PROTECTOR (MCP) COMBINATION MOTOR
STARTER.
RECEPTACLE, DUPLEX: NEMA 5-20R.
X
DESCRIPTION
SYMBOL LEGEND
CONT?
RECEPTACLE, QUADRAPLEX, CONNECTED TO UPS: NEMA
5-20R.
CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.
SYMBOL
RECEPTACLE, DUPLEX, CONNECTED TO UPS: NEMA 5-20R.
BREAK, STRAIGHT: TO BREAK PARTS OF DRAWING.
X-X
DESCRIPTION
SYMBOL LEGEND
EXHAUST FAN OUTLET.
HEATER, ELECTRIC RESISTANCE.
PHOTOCELL SENSOR, DIRECTIONAL.
WALL MOUNTED LED LIGHT FIXTURE
CLASS I DIV 2,CLASS I ZONE 2, CLASS II DIV 1
CLASS II DIV 2, CLASS III.
SURFACE MOUNTED LED LIGHT FIXTURE
CLASS I DIV 2,CLASS I ZONE 2, CLASS II DIV 1
CLASS II DIV 2, CLASS III.
TRANSFORMER (ONE-LINE DIAGRAM).
A
AMBER STROBE.
Y
YELLOW BEACON.
M
SIERRA MONITOR METHANE SENSOR.
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
SPECIALITY EQUIPMENT
TRANSFORMER, CURRENT (ONE-LINE DIAGRAM).
DELTA CONNECTION (ONE-LINE DIAGRAM).
PURGE BLOWER.
WYE CONNECTION (ONE-LINE DIAGRAM).
CCT CAMERA.
XXX
A/3
PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE AND
PHASE AS SHOWN (ONE-LINE DIAGRAM).
CONNECTION TO THE GROUND CIRCUIT CONDUCTOR
(NEUTRAL).
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
SYMBOLS
AND LEGENDS
SHEET:
E-0
ENGINEER STAMP:
SITE COORDINATION
THE LOCATION, CAPACITY, AND VOLTAGE OF THE LINES ARE ALL IN ACCORDANCE
WITH DATA GIVEN THIS OFFICE BY THE UTILITY COMPANY. ACCORDANCE WITH DATA
GIVEN THIS OFFICE BY THE UTILITY COMPANY. ACCORDANCE WITH DATA GIVEN THIS
OFFICE BY THE UTILITY COMPANY. COORDINATE WITH THE LOCAL UTILITY COMPANY
THE INSTALLATION OF THE ELECTRICAL SERVICE. COMPLY WITH UTILITY
REGULATIONS. REPORT DISCREPANCIES TO THE ENGINEER.
ELECTRIC UTILITY
-
PERSON CONTACTED: DATE: PHONE NUMBER: -
CODES
1. NATIONAL ELECTRICAL CODE
2. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA).
A. NFPA 52, 2010 EDITION : COMPRESSED NATURAL GAS (CNG) VEHICULAR
FUEL SYSTEMS CODE.
B. NFPA 70, 2011 EDITION: NATIONAL ELECTRIC CODE AMENDMENTS, AS
APPLICABLE.
C. NFPA 30A, 2012 EDITION: CODE FOR MOTOR FUEL DISPENSING FACILITIES
AND REPAIR GARAGES.
D. NFPA 496: STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR
ELECTRICAL EQUIPMENT.
3. INTERNATIONAL BUILDING CODE W/ LOCAL AMENDMENTS.
4. INTERNATIONAL FIRE CODE, WITH LOCAL AMENDMENTS.
A. IFC 2208.7
5. OCCUPATIONAL SAFETY AND HEALTH ACT (WORK AREA SOUND-LEVEL LIMITS).
6. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM).
7. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) NEMA 250
ENCLOSURES FOR ELECTRICAL EQUIPMENT (1000 VOLTS MAXIMUM).
DEFINITIONS
NOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS, NOTES,
OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR SCHEDULES IN THE
SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE CONTRACT DOCUMENTS. WHERE
TERMS SUCH AS "SHOWN", "NOTED", "SCHEDULED", AND "SPECIFIED" ARE USED, IT IS
TO HELP THE READER LOCATE THE REFERENCE, NO LIMITATION ON LOCATION IS
INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED", "SELECTED",
"APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY THE ENGINEER",
"REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE
ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND
REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS STATED IN
GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO THE
PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND
SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT SITE
INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING,
ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING,
CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE AND
READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY THE
CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-SUBCONTRACTOR,
FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION ACTIVITY, INCLUDING
INSTALLATION, ERECTION, APPLICATION, AND SIMILAR OPERATIONS. INSTALLERS ARE
REQUIRED TO BE EXPERIENCED IN THE OPERATIONS THEY ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO DESCRIBE
ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS "SPECIAL SYSTEMS". THESE
SYSTEMS INCLUDE BUT ARE NOT NECESSARILY LIMITED TO ALL SYSTEMS WHICH UTILIZE
VOLTAGES OF LESS THAN 71 VOLTS SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV
SYSTEMS, SECURITY SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...
ABBREVIATIONS
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
1P
1PH
1WAY
2/C
2WAY
3/C
3PH
3WAY
4OUT
SINGLE POLE
SINGLE-PHASE
ONE-WAY
TWO-CONDUCTOR
TWO-WAY
THREE-CONDUCTOR
THREE-PHASE
THREE-WAY
QUADRUPLE RECEPTACLE
OUTLET
4PDT
FOUR-POLE DOUBLE THROW
4PST
FOUR-POLE SINGLE THROW
4W
FOUR-WIRE
4WAY
FOUR-WAY
A
ABOVE COUNTER
AC
ARMORED CABLE
ADA
AMERICANS WITH DISABILITIES ACT
ADJ
ADJACENT
AFF
ABOVE FINISHED FLOOR
AFG
ABOVE FINISHED GRADE
AIC
AMPERE INTERRUPTING CAPACITY
ALUM
ALUMINUM
AMP
AMPERE
ANN
ANNUNCIATOR
AP
ACCESS POINT (WIRELESS DATA)
AR
AS REQUIRED
ASC
AMPS SHORT CIRCUIT
ATS
AUTOMATIC TRANSFER SWITCH
AV
AUDIO VISUAL
AWG
AMERICAN WIRE GAGE
BB XFMR BUCK-BOOST TRANSFORMER
C
CEILING MOUNTED
CATV
COMMUNITY ANTENNA TELEVISION
CB
CIRCUIT BREAKER
CCBA
CUSTOM COLOR AS SELECTED BY
ARCHITECT
CCTV
CLOSED CIRCUIT TELEVISION
CFBA
CUSTOM FINISH AS SELECTED BY
ARCHITECT
CF/CI
CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI
CONTRACTOR FURNISHED/
OWNER INSTALLED
CKT
CIRCUIT
CM
CONSTRUCTION MANAGER
CND
CONDUIT
CO
CONVENIENCE OUTLET
COR
CONTRACTING OFFICER'S
REPRESENTATIVE
CP
CONTROL PANEL
CT
CURRENT TRANSFORMER
CTV
CABLE TELEVISION
CU
COPPER
dBA
UNIT OF SOUND LEVEL
DPDT
DOUBLE POLE DOUBLE THROW
DS
DISCONNECT SWITCH
EA
EACH
EM
EMERGENCY
EMT
ELECTRICAL METALLIC TUBING
ENT
ELECTRICAL NONMETALLIC TUBING
EPO
EMERGENCY POWER OFF
EQUIP
EQUIPMENT
EXIST
EXISTING
F
FURNITURE MOUNTED
FA
FIRE ALARM
FCP
FIRE ALARM CONTROL PANEL
FLA
FULL LOAD AMPS
FMC
FLEXIBLE METAL CONDUIT
FOB
FREIGHT ON BOARD
FVNR
FULL VOLTAGE NON-REVERSING
FVR
FULL VOLTAGE REVERSING
G
GROUND
GEN
GENERATOR
GFCI
GROUND FAULT CIRCUIT
INTERRUPTER
GFP
GROUND FAULT PROTECTION
HD
HEAVY DUTY
HID
HIGH INTENSITY DISCHARGE
HOA
HAND-OFF-AUTOMATIC
HP
HORSE POWER
HPF
HIGH POWER FACTOR
HPS
HIGH PRESSURE SODIUM
HV
HIGH VOLTAGE
HZ
HERTZ
IG
ISOLATED GROUND
IMC
INTERMEDIATE METAL CONDUIT
IN/IS
INSULATED/ISOLATED
I/O
INPUT/OUTPUT
IR
INFRARED
J-BOX
JUNCTION BOX
KV
KILOVOLT
KVA
kVAR
kW
kWh
LED
LFMC
LFNC
LPS
LRA
LTG
LV
MATV
MAX
MC
MCA
MCB
MCC
MCP
MDP
MG
MH
MIN
MLO
MOCP
NA
NC
NEC
NEMA
NFC
NFPA
NIC
NL
NO
NTS
OC
OCP
OF/CI
OF/OI
OFP
OH DR
OL
PB
PF
PH
PNL
PT
PTZ
QTY
R
RCP
RMC
RNC
RPM
RR
RVNR
SCA
SCBA
SF
SFBA
SPDT
SPEC
SPST
S/S
ST
SWBD
SWGR
TL
TP
TP
TTB
TV
TVSS
TYP
UF
UGND
UPS
V
VA
VFC
W/
W/O
WP
XFMR
KILOVOLT AMPERE
KILOVOLT AMPERE REACTIVE
KILOWATT
KILOWATT HOUR
LIGHT EMITTING DIODE
LIQUID TIGHT FLEXIBLE METAL
CONDUIT CONDUIT
LIQUID TIGHT FLEXIBLE
NONMETALLIC CONDUIT
LOW PRESSURE SODIUM
LOCKED ROTOR AMPS
LIGHTING
LOW VOLTAGE
MASTER ANTENNA TELEVISION
SYSTEM
MAXIMUM
METAL CLAD
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTION
MAIN DISTRIBUTION PANEL
MOTOR GENERATOR
MANHOLE
MINIMUM
MAIN LUGS ONLY
MAXIMUM OVERCURRENT
PROTECTION
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NATIONAL FIRE CODE
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OVER CURRENT PROTECTION
OWNER FURNISHED/
CONTRACTOR INSTALLED
OWNER FURNISHED/ OWNER
INSTALLED
OBTAIN FROM PLANS
OVERHEAD (COILING) DOOR
OVERLOAD
PUSHBUTTON
POWER FACTOR
PHASE
PANEL
POTENTIAL TRANSFORMER
PAN/TILT/ZOOM
QUANTITY
REMOVE
REFLECTED CEILING PLAN
RIGID METAL CONDUIT
RIGID NONMETALLIC CONDUIT
REVOLUTIONS PER MINUTE
REMOVE AND RELOCATE
REDUCED VOLTAGE NON REVERSING
SHORT CIRCUIT AMPS
STANDARD COLOR AS SELECTED
BY ARCHITECT
SQUARE FOOT (FEET) SFBA
STANDARD FINISH AS SELECTED
BY ARCHITECT
SINGLE POLE, DOUBLE THROW
SPECIFICATION
SINGLE POLE, SINGLE THROW
START/STOP
SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TWIST LOCK
TELEPHONE POLE
TWISTED PAIR
TELEPHONE TERMINAL BOARD
TELEVISION
TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYPICAL
UNDER FLOOR
UNDERGROUND
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLT AMPERE
VARIABLE FREQUENCY CONTROLLER
WITH
WITHOUT
WEATHERPROOF
TRANSFORMER
GENERAL ELECTRICAL NOTES
1.
CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL
FAMILIARIZE THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY
QUESTIONS, MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED
PRODUCTS, CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN
THE EQUIPMENT SUPPLIED AND THE INTENT OR FUNCTION OF THE
EQUIPMENT, ETC., SHALL BE SUBMITTED TO THE ENGINEER IN WRITING FOR
CLARIFICATION PRIOR TO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING
OF THE PROJECT. WHERE DISCREPANCIES OR MULTIPLE INTERPRETATIONS
OCCUR, THE MOST STRINGENT THAT MEETS THE INTENT OF THE THAT
MEETS THE INTENT OF THE DOCUMENTS SHALL BE ENFORCED.
2.
OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND
EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE
INCORPORATED INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE
INSTALLER AND COSTS FOR RECEIVING, HANDLING, STORAGE (IF REQUIRED)
AND INSTALLATION ARE INCLUDED IN THE CONTRACT SUM.
A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE
INSTALLER FURNISHED THE MATERIALS OR EQUIPMENT.
B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER
FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER
WILL INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS
ARE DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS
WITH THE TRANSPORT COMPANY AND THE OWNER WILL ARRANGE
FOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR
MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF
MANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.
C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE
DELIVERY DATES OF OWNER FURNISHED ITEMS AND FOR RECEIVING,
UNLOADING AND HANDLING OWNER FURNISHED ITEMS AT THE SITE.
THE INSTALLER IS RESPONSIBLE FOR PROTECTING OWNER FURNISHED
ITEMS FROM DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE
ELEMENTS, AND TO REPAIR OR REPLACE ITEMS DAMAGED AS A
RESULT OF HIS OPERATIONS.
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
3.
EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL,
AND COMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK AND
STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.
ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL
CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT
COMPLY WITH THESE REQUIREMENTS TO THE ENGINEER.
4.
SUBMITTALS: PROVIDE SUBMITTALS IN THREE RING BINDERS WITH
JOB NAME, SUBCONTRACTOR, AND VOLUME ON THE BINDING. PREPARE
TABS FOR EACH SPECIFICATION SECTION REQUIRING SUBMITTALS.
PREPARE INDEX OF EQUIPMENT SUBMITTED IN EACH TAB.
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
SYMBOLS
AND LEGENDS
SHEET:
E-1
ENGINEER STAMP:
GENERAL NOTES
1. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SIZES AND LOCATION OF
EQUIPMENT AND WIRING ARE SHOWN TO SCALE WHERE POSSIBLE, BUT MAY BE
DISTORTED FOR CLARITY ON THE DRAWINGS. FINAL LOCATION OF OUTLETS
AND EQUIPMENT SHALL BE AS APPROVED BY THE ENGINEER OR HIS
REPRESENTATIVE. IT IS NOT WITHIN THE SCOPE OF DRAWINGS TO SHOW ALL
NECESSARY BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS. IT SHALL BE
THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO CONFORM
TO THE STRUCTURE, PRESERVE HEADROOM AND KEEP OPENINGS AND
PASSAGEWAYS CLEAN.
2. BIDDERS, BEFORE SUBMITTING A PROPOSAL, SHALL VISIT AND CAREFULLY
EXAMINE THE AREAS AFFECTED BY THIS WORK TO BECOME FAMILIAR WITH
EXISTING CONDITIONS AND WITH THE DIFFICULTIES THAT WILL ATTEND THE
EXECUTION OF THIS WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED
AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS
WILL NOT BE RECOGNIZED FOR EXTRA LABOR, EQUIPMENT OR MATERIALS
REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN
FORESEEN HAD SUCH EXAMINATION BEEN MADE.
3. BIDS SHALL INCLUDE ALL POWER, GROUNDING, AND EMPTY CONDUIT
REQUIREMENTS NECESSARY FOR THE COMPLETE ELECTRICAL INSTALLATION.
4. FURNISH AND INSTALL WIRING FOR EQUIPMENT FURNISHED BY OTHERS, AS
SHOWN ON MECHANICAL, HVAC, PLUMBING AND/OR ELECTRICAL DRAWINGS.
COORDINATE WITH OTHER TRADES FOR DETAILS OF INSTALLATION AND WIRING
REQUIREMENTS. THE TERM "WIRING" AS USED HEREIN SHALL INCLUDE
FURNISHING AND INSTALLING CONDUIT, WIRES, JUNCTION/OUTLET BOXES,
DISCONNECTS, OVER CURRENT PROTECTION AND FINAL CONNECTIONS.
COORDINATE FINAL CONDUCTOR SIZES, QUANTITIES, VOLTAGE REQUIREMENTS,
AND OVER CURRENT DEVICE AND OUTLET RATINGS WITH ACTUAL EQUIPMENT
TO BE FURNISHED TO THE SITE PRIOR TO FINALIZING WIRING INSTALLATION.
MINOR ADJUSTMENTS TO WIRING REQUIREMENTS NECESSARY TO
ACCOMMODATE ACTUAL FURNISHED EQUIPMENT SHALL BE PROVIDED AT NO
ADDITIONAL COST TO OWNER.
5. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH THE FOLLOWING
CODES AND STANDARDS:
A.
B.
C.
D.
E.
F.
G.
H.
I.
UNDERWRITERS LABORATORIES, INC. (UL).
NATIONAL ELECTRICAL CODE (NEC) NFPA 70.
INTERNATIONAL BUILDING CODE WITH LOCAL AMENDMENTS.
INTERNATIONAL FIRE CODE WITH LOCAL AMENDMENTS.
OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA).
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
AMERICAN DISABILITIES ACT (ADA).
BUILDING RULES AND REGULATIONS
ALL LOCAL JURISDICTION DIRECTIVES AND REQUIREMENTS.
6. THIS CONTRACTOR SHALL DO ALL CUTTING AND PATCHING OF THE
EXISTING CONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER
INSTALLATION OF THE ELECTRICAL WORK. ALL PATCHING SHALL BE OF THE
SAME MATERIALS, WORKMANSHIP AND FINISH AS, AND SHALL ACCURATELY
MATCH, ALL SURROUNDING CONSTRUCTION.
7. VERIFY LOCATIONS OF ALL ELECTRICAL EQUIPMENT. IN CENTERING
OUTLETS AND LOCATING BOXES OR OUTLETS, ALLOW FOR OVERHEAD PIPES,
DUCTS, MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND
PLASTERING, WINDOW AND DOOR TRIM, PANELING, HUNG CEILING, ETC., AND
CORRECT ANY INACCURACY
RESULTING FROM FAILURE TO DO SO WITHOUT EXPENSE TO TRILLIUM.
8. LOCATE JUNCTION AND PULL BOXES TO BE CONCEALED IN FINISH SPACES.
WHERE NECESSARY, REROUTE RACEWAYS OR MAKE OTHER ARRANGEMENTS
FOR CONCEALMENT. PROVIDE PULL BOXES WHERE NECESSARY
FOR WIRE PULLING. COORDINATE ALL BOX LOCATIONS WITH OTHER TRADES.
COVERS OF JUNCTION AND PULL
BOXES SHALL BE ACCESSIBLE.
9. SECURE ALL SUPPORTS TO BUILDING STRUCTURE AS REQUIRED. SUPPORT
HORIZONTAL CONDUIT RUNS AT NO MORE THAN 10' INTERVALS.
10. UPON COMPLETION OF ALL ELECTRICAL WORK, ELECTRICAL CONTRACTOR
SHALL ADJUST AND TEST ALL CIRCUITS, OUTLETS, SWITCHES, LIGHTS, MOTORS
AND ANY OTHER ELECTRICAL ITEMS INSTALLED. ANY DEFECTIVE ITEMS SHALL
BE IMMEDIATELY REPAIRED OR REPLACED WITH NEW EQUIPMENT OR MATERIALS
AND THAT PORTION OF THE SYSTEM SHALL BE RETESTED. ALL SUCH REMEDIAL
WORK SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE TRILLIUM.
TESTING SHALL BE DONE IN ACCORDANCE WITH THE "ACCEPTANCE TESTING
SPECIFICATIONS FOR ELECTRICAL POWER DISTRIBUTION EQUIPMENT AND
SYSTEMS" OF THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA).
17. ALL PENETRATIONS THROUGH FIRE RATED WALLS OR FLOORS SHALL BE
SEALED TO PREVENT THE SPREAD OF SMOKE AND FIRE. THE FIRE RATING OF
THE PENETRATION SEALING METHOD SHALL MATCH THE RATING OF THE WALL
OR FLOOR. USE A UL MEA/BSA APPROVED SEALING METHOD WHICH IS
ACCEPTABLE TO BUILDING MANAGEMENT.
18. ALL HARD WIRING OF FIRE ALARM SYSTEM SHALL BE DONE BY THIS
CONTRACTOR AND SHALL MEET BUILDING AND FIRE DEPARTMENT STANDARDS.
19. UPON COMPLETION OF JOB, CONTRACTOR MUST OBTAIN A LETTER OF
ACCEPTANCE OF SYSTEM FROM FIRE
DEPARTMENT AND SUBMIT TO TRILLIUM'S REPRESENTATIVE.
20. CONTRACTOR SHALL FURNISH ALL NEW CONDUIT, WIRE, BOXES, ETC., AS
REQUIRED AND SHALL RECONNECT ALL EXISTING OUTLETS TO REMAIN. ALL
DISTURBED ELECTRICAL WORK TO REMAIN, AFTER REMOVAL OF PARTITIONS,
CEILINGS, ETC., SHALL BE REROUTED AND RECONNECTED WITH ALL NEW
CONDUITS WIRE, BOXES, OUTLETS, ETC., AS REQUIRED. ALL EXISTING WORK
TO REMAIN SHALL BE LEFT IN COMPLETE, OPERATING CONDITION.
21. ABANDONED OUTLETS SHALL BE REMOVED COMPLETE WITH ALL WIRING
AND CONDUITS. SAME SHALL BE DISCONNECTED, CUT, AND DEAD-ENDED IN
AN APPROVED MANNER.
22. PROVIDE GFI TYPE PROTECTION FOR ANY RECEPTACLES WITHIN 5' OF
WATER OR LIQUIDS.
23. ALL WORK ON BRANCH CIRCUITRY, FEEDERS, RISERS, AND EQUIPMENT
SHALL BE COMPLETED WITH EQUIPMENT OR CIRCUITS DE-ENERGIZED (SHUT
DOWN).
24. FURNISH AND INSTALL INCLUDING LABOR, SUPERVISION, MATERIAL, TOOLS,
SERVICES, TRANSPORTATION, OVERHEAD COSTS, FEES, PLAN CHECK FEES,
INSPECTION CHARGES, ROYALTIES, PROFIT, ETC., A COMPLETE ELECTRICAL
INSTALLATION AS SPECIFIED HEREIN AND INDICATED ON THE ELECTRICAL
DRAWINGS IN AN APPROVED, NEAT, FIRST-CLASS, FINISHED, SAFE,
WORKMANSHIP LIKE MANNER THAT COMPLIES WITH ALL APPLICABLE LOCAL,
STATE, FEDERAL, ETC., CODES, ORDINANCES, RULES, REGULATIONS,
STANDARDS, ETC. THE ENTIRE ELECTRICAL INSTALLATION SHALL COMPLY WITH
OR SURPASS THE MOST RECENT EDITION OF THE NATIONAL ELECTRICAL CODE
AND OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA) STANDARDS.
25. ALL MATERIALS AND EQUIPMENT FURNISHED BY THE ELECTRICAL
CONTRACTOR SHALL BE NEW OF FIRST CLASS QUALITY, UNLESS NOTED
OTHERWISE, FREE FROM DEFECTS, AND CONFORM WITH UNDERWRITERS
LABORATORIES, INC. STANDARDS AND BE SO LABELED. MATERIALS,
EQUIPMENT, ETC., NOT INDICATED ON DRAWING OR SPECIFIED HEREIN, BUT
REQUIRED FOR A SUCCESSFUL AND EFFICIENT COMPLETION OF THE
ELECTRICAL INSTALLATION SHALL BE HELD TO BE IMPLIED AND SHALL BE
FURNISHED AND INSTALLED FOR NO ADDITIONAL COST. ENCLOSURES FOR ALL
EQUIPMENT SHALL BE SUITABLE FOR USE INTENDED, E.G., WEATHERPROOF FOR
EXTERIOR AND WET LOCATIONS. ALL EQUIPMENT SHALL BE RATED FOR USE
INTENDED, E.G., VOLTAGE, HORSEPOWER, RATING OF DISCONNECT SWITCHES,
ETC.
26. MATERIALS, EQUIPMENT, ETC., INCLUDING THOSE FURNISHED BY OTHERS,
THAT ARE TO BE INSTALLED BY THE ELECTRICAL CONTRACTOR SHALL BE
RECEIVED AND PROPERLY PROTECTED BY THIS CONTRACTOR UNTIL ENTIRE
INSTALLATION IS COMPLETE.
27. MAKE NO INSTALLATION OF WORK WHICH WOULD LEAVE INADEQUATE
OPERATION OR SERVICING SPACE FOR ANY ITEM FOR THE ENTIRE PROJECT.
DRAWINGS ARE NOT INTENDED TO SHOW IN DETAIL ALL FEATURES OF WORK,
CHECK LOCATION AT ELECTRICAL WORK TO DETERMINE IN ADVANCE THAT IT
CLEARS ALL OPENINGS, STRUCTURAL MEMBERS, ETC. WHERE CONTRACT
DOCUMENTS, E.G., DRAWINGS AND SPECIFICATIONS DO NOT MEET WITH
MINIMUM CODES, ETC., THIS CONTRACTOR SHALL INSTALL ALL THE MINIMUM
REQUIRED MATERIALS AND EQUIPMENT FOR NO ADDITIONAL COST.
28. ALL WIRING SHALL BE INSTALLED IN APPROVED RACEWAYS PER CODE.
RACEWAYS SHALL BE APPROVED FOR USE INTENDED. ALL EMT CONDUIT SHALL
HAVE COMPRESSION TYPE FITTINGS. PVC CONDUIT AND FITTINGS FOR ALL
UNDERGROUND CONDUITS. ALL ELECTRICAL CONDUCTORS SHOWN ARE
COPPER, MINIMUM SIZE IS NO. 12 AWG. INSULATION TO BE THHN/THWN FOR
WIRE SIZES #6 AND SMALLER THHN/THWN/XHHW FOR WIRE SIZES #4 AND
LARGER. THE USE OF "MC" CABLE IS NOT APPROVED.
12. AFTER COMPLETION OF WORK, CLEAN UP ALL RESULTANT DEBRIS AND
REMOVE FROM THE SITE. DISPOSE OF PROPERLY.
13. ALL ABOVE GROUND CONDUIT SHALL BE THREADED RIGID STEEL (RGS),
MINIMUM 3/4", UNLESS OTHERWISE NOTED. FLEXIBLE METAL CONDUIT
("GREENFIELD") MAY BE USED ONLY FOR FINAL CONNECTIONS TO LIGHTING
FIXTURES OR VIBRATING EQUIPMENT UNLESS OTHERWISE INDICATED ON
DRAWINGS.
31. PROVIDE NECESSARY LABOR, TOOLS, EQUIPMENT, E.G., VOLTMETER,
AMMETER, MEGGER, ETC., AND CHECK ELECTRICAL SYSTEM IN THE PRESENCE
OF THE TRILLIUM'S REPRESENTATIVE. ALL TESTING SHALL BE IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATION OF EQUIPMENT, MATERIAL, ETC.,
BEING TESTED.
14. CONDUCTORS #10 AWG AND SMALLER SHALL BE COPPER, STRANDED,
TYPE THHN/THWN; #8 AWG AND LARGER SHALL BE COPPER, STRANDED, TYPE
THHN/THWN. ALL WIRING FOR LIGHTING AND POWER SHALL BE #12 AWG
MINIMUM.
32. THE ELECTRICAL CONTRACTOR SHALL FULLY GUARANTEE THE ENTIRE
ELECTRICAL INSTALLATION AND ALL WORK UNDER THIS SECTION FOR A PERIOD
OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER AGAINST
ALL EVIDENCE OF IMPERFECT WORKMANSHIP OF FAILURE OR MALFUNCTION OF
MATERIALS AND EQUIPMENT. WORK FOUND TO BE DEFECTIVE WITHIN THIS
PERIOD SHALL BE REPLACED PROMPTLY AT NO EXPENSE TO THE OWNER.
15. BRANCH CIRCUIT HOME RUN CONDUCTORS SHALL BE INCREASED ONE SIZE
(MINIMUM) TO COMPENSATE FOR VOLTAGE DROP FOR 120 VOLT CIRCUITS
EXCEEDING 100' FEET AND FOR 277 VOLT CIRCUITS EXCEEDING 150' FEET.
16. ALL CHOPPING FOR ELECTRICAL INSTALLATION SHALL BE COORDINATED
WITH CONSTRUCTION MANAGER AND OTHER TRADES.
37. ALL WIRING AND CONDUIT FITTINGS AT DISPENSER, DISPENSER PIT,
COMPRESSOR, STORAGE VESSELS AND METER SET ASSEMBLY SHALL BE IN
COMPLIANCE WITH HAZARDOUS LOCATION AS DEFINED IN NFPA 70 (NEC)
ARTICLE 501 AND NFPA 52 (CNG FUEL SYSTEMS).
38. ALL CONDUIT FITTINGS AND BOXES SHALL BE LISTED AND/OR LABELED BY
UNDERWRITERS LABORATORIES OR FACTORY MUTUAL TESTING LABORATORIES.
THIS INCLUDES DEVICES, MOTORS AND RELATED ELECTRICAL EQUIPMENT.
39. UNDERGROUND ELECTRICAL CONDUITS SHALL BE PVC CONDUIT AND
INSTALLED A MINIMUM OF 8" FROM GAS LINES. ALL BENDS SHALL BE LARGE
RADIUS, CONDUIT RUNS OVER 200' WILL HAVE RIGID GALVANIZED STEEL
SWEEPS, THAT HAVE BEEN WRAPPED WITH TAPE TO PREVENT CORROSION.
40. CONTRACTOR SHALL VERIFY CONDUIT STUB-UP LOCATION(S) ON PAD PRIOR
TO INSTALLATION AND SUBMIT DRAWINGS FOR APPROVAL. ALL CONDUIT
STUB-UPS SHALL BE PVC COATED RIDGID STEEL CONDUIT, OR WRAPPED
RIDGED STEEL CONDUIT AS APPROVED BY TRILLIUM & OWNER. IF APPROVED,
STEEL CONDUIT WILL BE WRAPPED WITH TWO (2) WRAPS OF 20 MIL CONDUIT
WRAP.
41. CONTRACTOR MUST VERIFY ALL MEASUREMENTS AFFECTING HIS WORK AND
ASSUME THE RESPONSIBILITY FOR THEIR CORRECTNESS.
50. GROUND RODS SHALL BE TESTED FOR RESISTANCE TO GROUND. WHERE
RESISTANCE OF ANY SINGLE GROUND ROD EXCEEDS 25 OHMS, ADDITIONAL
GROUND ROD(S) SHALL BE DRIVEN. UNTIL GROUND RESISTANCE OF LESS THAN
25 OHMS IS OBTAINED.
51. ALL GROUNDING STUB-UPS IN CONCRETE FOR EQUIPMENT GROUND SHALL
BE PROTECTED BY 1" PVC CONDUIT.
52. ALL EQUIPMENT USED IN HAZARDOUS AREAS SHALL BE LISTED AND/OR
LABELED FOR USE IN CLASS 1, GROUP D, AND DIVISION 1 OR 2 AS REQUIRED.
CONTRACTOR SHALL PATCH, PAINT, REPAIR, AND CLEAN AS REQUIRED TO
MATCH SURROUNDING OF ANY SURFACE DISTURBED OR DAMAGED DURING
THE DURATION OF THE PROJECT.
53. CONTRACTOR IS RESPONSIBLE FOR TERMINATION OF ALL CONDUCTORS.
54. UNLESS OTHERWISE NOTED, ALL ELECTRICAL COMPONENTS SHALL BE
SUPPLIED BY CONTRACTOR.
REVISIONS:
REV
NO.
DESCRIPTION
33. ALL CONDUITS ABOVE GROUND SHALL BE RIGID GALVANIZED STEEL UNLESS
NOTED OTHERWISE.
34. ALL ELECTRICAL WORK SHALL BE IN COMPLIANCE WITH ALL LOCAL CITY &
COUNTY CODES, NFPA 52 (CNG FUEL SYSTEMS), & NFPA 70 (NEC).
35. ALL WORK SHOWN IS NEW UNLESS OTHERWISE INDICATED.
REV
DATE
55. ALL CONDUCTORS SHALL BE RATED FOR WET LOCATIONS FOR
UNDERGROUND INSTALLATIONS & A MIN. OF THHN FOR ABOVE GROUND
INSTALLATION.
56. IN CASE OF A CONFLICT BETWEEN SPECIFICATIONS, NOTES AND GENERAL
REQUIREMENTS, OR CODES AND STANDARDS FOR THE INSTALLATION - MOST
STRINGENT REQUIREMENTS SHALL GOVERN. OBTAIN CLARIFICATION FROM
ENGINEER WHERE CONFLICT IS ENCOUNTERED.
57. SEISMIC REQUIREMENTS: ALL EQUIPMENT PROVIDED SHALL WITHSTAND
SEISMIC FORCES DEFINED IN IBC 2012 FOR SEISMIC RISK CATEGORY II AND
SEISMIC DESIGN CATEGORY FOR SITE LOCATION . THE TERM "WITHSTAND"
MEANS THE UNIT WILL REMAIN IN PLACE WITHOUT SEPARATION OF ANY PARTS
FROM THE DEVICE WHEN SUBJECTED TO THE SEISMIC FORCES SPECIFIED AND
THE UNIT WILL BE FULLY OPERATIONAL AFTER THE SEISMIC EVENT.
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
29. THIS CONTRACT IS TO INCLUDE ALL CONTINGENCIES WHICH MAY ARISE
AND WHICH MAY BE REQUIRED TO MAKE A COMPLETE ELECTRICAL SYSTEM.
30. THE ELECTRICAL CONTRACTOR SHALL VISIT SITE AND DETERMINE EXTENT
OF THE WORK. AT COMPLETION OF ELECTRICAL INSTALLATION PROVIDE
TRILLIUM WITH ACCURATE AS-BUILT DRAWINGS INDICATING ALL VARIATIONS
FROM CONTRACT DRAWINGS, AND A LETTER TO THE OWNER'S REPRESENTATIVE
STATING PROJECT FULLY COMPLIES WITH ALL CONTRACT DOCUMENTS AND IF
NOT, HOW INSTALLATION WAS ACCOMPLISHED. ALL CHANGES SHALL BE
SUBJECT TO TRILLIUM'S REPRESENTATIVE'S APPROVAL.
11. UPON COMPLETION OF ALL ELECTRICAL WORK, ELECTRICAL CONTRACTOR
SHALL BALANCE ALL PANEL BOARDS AFFECTED TO WITHIN 10% DEVIATION
BETWEEN PHASES.
36. PROVIDE CONDUIT SEALS AT EACH CONDUIT AS REQUIRED BY NFPA 70
(NEC) ARTICLE 501-15. SEALS ARE REQUIRED WITHIN 18" OF ALL GRADE
PENETRATIONS WITHIN HAZARDOUS AREAS. ALL CONDUITS SHALL HAVE
SEALOFFS WHERE ENTERINR OR LEAVING CLASSIFIED LOCATIONS PER NEC 501.
J BARBER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
ELECTRICAL
NOTES
SHEET:
E-2
ENGINEER STAMP:
ELECTRICAL SPECIFICATIONS
1. SCOPE OF WORK
A. THE WORK UNDER THIS DIVISION INCLUDES PROVIDING ALL MATERIAL
AND LABOR NECESSARY FOR A COMPLETE, FUNCTIONAL INSTALLATION OF
ELECTRICAL WORK AS SHOWN ON THE DRAWINGS AND AS HEREINAFTER
SPECIFIED, UNLESS SPECIFICALLY INDICATED TO THE CONTRARY. THIS
CONTRACTOR SHALL ALSO PROVIDE TEMPORARY LIGHT AND POWER FOR ALL
TRADES AS REQUIRED BY FIELD CONDITIONS. TEMPORARY POWER PROVISIONS
SHALL COMPLY WITH ALL OSHA REQUIREMENTS INCLUDING THOSE FOR GFCI
PROTECTION FOR RECEPTACLE CIRCUITS.
B. BIDDERS, BEFORE SUBMITTING PROPOSALS, SHALL VISIT THE SITE AND
CAREFULLY EXAMINE THE AREAS AFFECTED BY THE WORK IN THIS CONTRACT,
AND SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND ANY
DIFFICULTIES THAT WILL ATTEND THE EXECUTION OF THIS WORK.
2. CONNECTIONS TO EXISTING WORK SHALL BE PERFORMED AS FOLLOWS:
A. INSTALL NEW WORK AND CONNECT TO EXISTING WORK WITH MINIMUM
INTERFERENCE TO EXISTING FACILITIES.
B. TEMPORARY SHUTDOWNS OF EXISTING SERVICES:
1. AT NO ADDITIONAL CHARGES.
2. AT TIMES NOT TO INTERFERE WITH NORMAL OPERATION OF EXISTING
FACILITIES
3. ONLY WITH WRITTEN CONSENT OF BUILDING MANAGEMENT.
8. INSPECTION
A. ALL STAGES OF THE INSTALLATION WILL BE INSPECTED FOR
COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT DRAWINGS AND
SPECIFICATIONS. REPLACE ANY PORTION OF THE CONSTRUCTION THAT DOES
NOT MEET SUCH REQUIREMENTS TO THE SATISFACTION OF TRILLIUM.
B. PROVIDE PROPER FACILITIES AS THE ENGINEER AND INSPECTORS MAY
REQUIRE FOR ACCESS AND FOR INSPECTION AT THE CONSTRUCTION SITE.
C. CONTRACTOR SHALL PROVIDE ELECTRICIANS TO ASSIST ANY
INSPECTORS, MANUFACTURER'S REPRESENTATIVES, AND/OR TESTING
AGENCY'S THAT HAVE WORK ON SITE.
L. PULL AND SPLICE BOXES SHALL BE CODE GAUGE GALVANIZED STEEL
OF SIZE INDICATED OR REQUIRED TO MEET CALIFORNIA CODE SUFFICIENT TO
PULL, RACK AND SPLICE CABLES CONTAINED THEREIN. PROVIDE A GROUND LUG
WELDED TO BOXES CONTAINING FEEDER CONDUCTORS.
M. PROVIDE STEEL CORE NYLON ROPE DRAG LINE WITH TERMINAL BALL IN
ALL EMPTY CONDUITS OVER 10' LONG.
11. OUTLET BOXES
A. ALL DEVICE PLATES FOR WALL OUTLETS (LIGHTING CONTROL SWITCH,
POWER, DATA, TELEPHONE, TV, ETC.) SHALL BE LEVITON WITH SEPARATE
SUBPLATE. DEVICE PLATES FOR TELEPHONE, DATA AND TV OUTLETS SHALL
CONTAIN APPROPRIATE JACKS; COORDINATE WITH TRILLIUM.
9. CUTTING AND PATCHING
A. ALL CUTTING AND PATCHING REQUIRED FOR EQUIPMENT INCLUDED IN
THESE SPECIFICATIONS SHALL BE DONE BY THIS CONTRACTOR. IF CUTTING IS
DONE DUE TO FAILURE TO PERFORM PRELIMINARY ROUGHING WORK, THIS
CONTRACTOR WILL BE RESPONSIBLE FOR THE COST OF THE ADDITIONAL
PATCHING.
B. IN THOSE PARTITIONS OF THE BUILDING WHERE NEW FLOORS, WALLS
OR PARTITIONS ARE REQUIRED TO BE CONSTRUCTED, THE CONTRACTOR SHALL
FURNISH AND LOCATE ALL REQUIRED SLEEVES CONSTRUCTED. WHERE
SLEEVES AND INSERTS WERE NOT INSTALLED, OR WHERE SLEEVES AND INSERTS
WERE INCORRECTLY LOCATED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE COST OF ANY REQUIRED CUTTING AND PATCHING.
B. PROVIDE TELCOM DEVICE PLATE FOR EACH VOICE/DATA OUTLET. FINAL
CONFIGURATION OF TERMINATION DEVICES SHALL BE AS PER OWNER'S
REQUIREMENTS.
C. ALL CONVENIENCE TYPE RECEPTACLES SHALL BE OF THE GROUNDING
TYPE.
D. IN GENERAL, THE MOUNTING HEIGHTS OF THE VARIOUS OUTLETS SHALL
BE AS SHOWN ON DRAWINGS. IN CERTAIN LOCATIONS, THE REQUIRED HEIGHTS
WILL VARY TO ACCOMMODATE EQUIPMENT TO BE LOCATED PROPERLY IN THE
DRAWINGS, OR SHALL BE DETERMINED AT THE CONSTRUCTION SITE BY
TRILLIUM'S REPRESENTATIVE.
E. CEILING OUTLET BOXES MUST BE ACCESSIBLE FROM FIXTURE SERVED.
C. ALARM AND EMERGENCY SYSTEMS: NOT TO BE INTERRUPTED.
D. MAINTAIN CONTINUOUS OPERATION OF EXISTING FACILITIES AS
REQUIRED WITH NECESSARY TEMPORARY CONNECTIONS BETWEEN NEW AND
EXISTING WORK.
E. CONNECT NEW WORK TO EXISTING WORK IN NEAT AND ACCEPTABLE
MANNER. RESTORE EXISTING DISTURBED WORK TO ORIGINAL CONDITION
INCLUDING MAINTENANCE OF WIRING CONTINUITY AS REQUIRED.
3. REMOVAL AND RELOCATION OF EXISTING WORK:
A. DISCONNECT, REMOVE AND/OR RELOCATE EXISTING MATERIAL,
EQUIPMENT, AND OTHER WORK AS NOTED OR REQUIRED FOR PROPER
INSTALLATION OF NEW SYSTEM.
B. DISPOSE OF REMOVED ELECTRICAL EQUIPMENT AS DIRECTED IN
ACCORDANCE WITH LOCAL CODES AND STANDARDS.
4. CODES AND STANDARDS
A. THE ELECTRICAL INSTALLATION SHALL COMPLY WITH THE FOLLOWING
CODES AND STANDARDS:
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
UNDERWRITERS LABORATORIES, INC. (UL)
NATIONAL ELECTRICAL CODE OF THE NFPA (NEC)
ELECTRICAL CODE 2011 EDITION
INTERNATIONAL BUILDING CODE WITH LOCAL AMENDMENTS
INTERNATIONAL FIRE CODE WITH LOCAL AMENDMENTS
OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
AMERICAN DISABILITIES ACT (ADA)
BUILDING RULES AND REGULATIONS.
ALL LOCAL JURISDICTION DIRECTIVES AND REQUIREMENTS.
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION INC. ACCEPTANCE
TESTING SPECIFICATI0NS.
5. SHOP DRAWINGS AND CATALOG CUTS
A. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO TRILLIUM FOR
APPROVAL, DETAILED SHOP DRAWINGS, CATALOG CUTS AND WIRING DIAGRAMS
FOR THE FOLLOWING:
1.
2.
3.
4.
5.
6.
PANEL BOARDS
DISCONNECT SWITCHES
LIGHTING FIXTURES
WIRING DEVICES
TRANSFORMERS
CONDUIT FITTINGS, GROUNDING EQUIPMENT
6. SUBSTITUTIONS
A. ANY SUBSTITUTIONS FOR ELECTRICAL ITEMS DESCRIBED IN THIS
SPECIFICATION WILL ONLY BE PERMITTED UPON WRITTEN PRIOR APPROVAL BY
TRILLIUM. BASE BID SHALL BE FOR SPECIFIED EQUIPMENT.
B. REQUESTS FOR APPROVAL OF SUBSTITUTIONS FOR ITEMS OF LESSER
MATERIAL AND/OR LABOR COSTS THAN THOSE SPECIFIED MUST BE
ACCOMPANIED BY AN ITEMIZED COST SAVINGS BREAKDOWN TO BE
CONSIDERED.
7. QUALITY ASSURANCE
A. THE CONTRACTOR SHALL HAVE HAD EXPERIENCE ON AT LEAST FIVE
PROJECTS INVOLVING QUANTITIES AND COMPLEXITIES AT LEAST EQUAL TO
THOSE REQUIRED FOR UNDER THIS DIVISIONS OR THE APPLICABLE SECTION
THEREOF.
B. ALL WORKMEN PERFORMING UNDER THIS DIVISIONS SHALL BE SKILLED
WORKMEN OF THE TRADE INVOLVED.
C. THIS CONTRACTOR SHALL NOT DO ANY CUTTING THAT MAY IMPAIR THE
STRENGTH OF BUILDING CONSTRUCTION. NO HOLES ARE TO BE DRILLED INTO
THE TENSION SIDE OF STRUCTURAL MEMBERS. CLAMPS AND OTHER APPROVED
HOLDING DEVICES ARE TO BE USED. ALL WORK SHALL BE DONE IN A NEAT
MANNER BY MECHANICS SKILLED IN THEIR TRADES AND AS APPROVED.
10. RACEWAYS AND BOXES
A. WHERE SIZES OF RACEWAY OR BOXES ARE NOT INDICATED, THE
CONTRACTOR SHALL SIZE THESE ITEMS AS REQUIRED FOR THE INSTALLATION.
ALL ABOVE GROUND CONDUIT SHALL BE RIGID THREADED STEEL MINIMUM 3/4"
UNLESS OTHERWISE NOTED.
B. FITTINGS FOR RIGID CONDUIT SHALL BE OF THE THREADED TYPE.
FITTINGS FOR STEEL CONDUIT SHALL BE HOT DIPPED GALVANIZED MALLEABLE
IRON. FITTINGS FOR FLEXIBLE CONDUIT SHALL BE STEEL WITH NYLON
INSULATED THROATS.
C. FLEXIBLE METAL CONDUIT SHALL BE USED FOR FINAL CONNECTION OF
RECESSED LIGHTING FIXTURES AND OUTLET BOXES IN HUNG CEILINGS, AND
WIRING DEVICES INDICATED TO BE INSTALLED IN HUNG CEILINGS OR IN
REMOVABLE HOLLOW METAL STUD PARTITION CONSTRUCTION.
D. LIQUID TIGHT GALVANIZED FLEXIBLE STEEL CONDUIT, MINIMUM 18
INCHES LONG, MAXIMUM 36 INCHES LONG, SHALL BE PROVIDED AT ROTATING
EQUIPMENT AND TRANSFORMER CONNECTIONS.
E. ALL CONDUIT AND TUBING SHALL BE CUT SQUARE AND REAMED AT THE
ENDS.
F. PAINT MALE THREADS OF FIELD THREADED RACEWAYS WITH GRAPHITE
BASE PIPE COMPOUND. DRAW UP TIGHT WITH COUPLINGS WITH NO EXPOSED
THREADS.
G. CONDUIT AND TUBING RUNS SHALL BE MECHANICALLY AND
ELECTRICALLY CONTINUOUS FROM THE POINT OF SERVICE TO THE LAST
OUTLETS. CONDUIT SHALL ENTER AND BE SECURELY CONNECTED TO CABINET,
JUNCTION BOX, PULL BOX OR OUTLET BOX BY MEANS OF LOCK NUTS ON THE
OUTSIDE AND INSIDE AND PROVIDED WITH AN INSULATED BUSHING ON THE
INSIDE. IN TUBING OR FLEXIBLE METAL CONDUIT, THE ONE COMPRESSION
LOCK NUT SHALL BE MADE WRENCH-TIGHT. ALL LOCK NUTS SHALL BE OF THE
BONDING TYPE WITH SHARP EDGES AND DIGGING INTO THE METAL WALL OF AN
ENCLOSURE AND SHALL BE INSTALLED IN A MANNER THAT WILL ASSURE A
LOCKING AND ELECTRICALLY CONTINUOUS INSTALLATION. LOCK NUTS AND
BUSHINGS WILL NOT BE REQUIRED WHERE CONDUITS ARE SCREWED INTO
TAPPED CONNECTIONS.
H. ALL VERTICAL RUNS OF CONDUIT OR TUBING TERMINATING IN THE
BOTTOMS OF WALL BOXES OR CABINETS, OR SIMILAR LOCATIONS, SHALL BE
PROTECTED FROM THE ENTRANCE OF FOREIGN MATERIAL PRIOR TO THE
INSTALLATION OF CONDUCTORS.
I. UNLESS OTHERWISE SPECIFIED, ALL CONDUIT AND TUBING SHALL BE
INSTALLED CONCEALED. IN GENERAL, ALL CONDUIT AND TUBING SHALL BE RUN
IN HUNG CEILINGS AND FURRED SPACES, WHERE THEY EXIST. WHERE CONDUIT
IS RUN EXPOSED, IT SHALL BE SECURELY SUPPORTED WITH ZINC COATED
MALLEABLE IRON PIPE STRAPS OR OTHER APPROVED MEANS. CONDUITS SHALL
NOT BE RUN WITHIN ONE FOOT OF AND PARALLEL TO HOT WATER PIPES.
CONDUITS SHALL BE RUN PARALLEL OR PERPENDICULAR TO BUILDING
STRUCTURAL ELEMENTS.
15. WIRING
A. UNLESS OTHERWISE SPECIFIED OR SPECIFICALLY INDICATED ON THE
DRAWINGS, ALL CONDUCTORS FOR LIGHTING AND POWER SHALL BE TINNED
SINGLE CONDUCTOR ANNEALED COPPER BUILDING WIRES OF MINIMUM 98%
CONDUCTIVITY WITH DISTINCTIVE COLOR MARKING, 600 VOLT INSULATION,
COLOR CODED AS SPECIFIED HEREINAFTER. CONDUCTORS #10 AWG AND
SMALLER SHALL BE STRANDED, TYPE THHN/THWN; #8 AWG AND LARGER SHALL
BE STRANDED, TYPE THHN/THWN.
B. WIRING FOR LIGHTING AND POWER SHALL BE #12 AWG MINIMUM.
CONTROL WIRING SHALL BE #12 AWG MINIMUM, UNLESS OTHERWISE
INDICATED.
C. BRANCH CIRCUIT HOME RUN CONDUCTORS SHALL BE INCREASED ONE
SIZE (MINIMUM) TO COMPENSATE FOR VOLTAGE DROP FOR 120 VOLT CIRCUITS
EXCEEDING 100' AND 277 VOLT CIRCUITS EXCEEDING 140'.
D. ALL WIRES AND CABLES FOR BOTH LIGHTING AND POWER SHALL BE
PHASED OUT AND CONNECTED IN SUCH MANNER THAT CABLES HAVING
INSULATION OF THE SAME COLOR WILL BE CONNECTED TO THE SAME PHASE
THROUGHOUT. WIRE JOINTS THAT BECOME NECESSARY IN CIRCUIT WORK AT
THE OUTLETS SHALL BE MADE WITH APPROVED PRESSURE CONNECTORS AS
MANUFACTURED BY SCOTCH-LOCK, BUCHANAN, T&B OR APPROVED EQUAL.
ALL JOINTS SHALL BE COVERED WITH TAPE OF AN INSULATION EQUAL TO THAT
OF THE CONDUCTORS.
E. ALL WIRES 1/0 AND LARGER WILL BE MEGGERED TO ENSURE INSULATION
INTEGRITY BY CONTRACTOR. CONTRACTOR WILL SUBMIT A REPORT TO
TRILLIUM STATING COMPLIANCE AND RESULTS OF TEST.
12. WIRING DEVICES
16. COLOR CODING
A. WIRING DEVICES SHALL BE OF THE MOLDED COMPOSITION TYPE,
INDUSTRIAL SPECIFICATION GRADE, UNLESS OTHERWISE INDICATED. WIRING
DEVICES SHALL BE AS MANUFACTURED BY LEVITON, LUTRON, HUBBELL,
RUSSELL STOLL OR APPROVED EQUAL. ALL WIRING DEVICES SHALL BE WHITE IN
GENERAL UNLESS OTHERWISE SELECTED BY TRILLIUM OR OTHERWISE
INDICATED IN CONTRACT DOCUMENTS FOR SPECIFIC FUNCTIONS.
B. WALL SWITCHES SHALL BE INDUSTRIAL SPECIFICATION GRADE AND
SHALL HAVE ALTERNATING CURRENT RATINGS EQUAL TO FULL NOMINAL
CAPACITY WHEREVER HANDLING TUNGSTEN FILAMENT OR INDUCTIVE LOADS
AND THEN SHALL BE OF THE FLUSH QUIET TUMBLER TYPE. SWITCHES SHALL BE
WHITE IN COLOR (OR COLOR AS SELECTED BY TRILLIUM) OR OTHER COLOR TO
INDICATE SPECIAL FUNCTION.
1. 120/277 VOLT AC, 20 AMP, SINGLE POLE, ROCKER TYPE, SELF
GROUNDING LEVITON# 5621-2
2. 120/277 VOLT AC, 20 AMP, THREE WAY, ROCKER TYPE, SELF
GROUNDING LEVITON# 5623-2
3. 20 AMP, AC, PILOT TYPE, ROCKER TYPE, SELF GROUNDING, 120V
SINGLE POLE - LEVITON #5628-2, 120V THREE WAY - LEVITON #5638-2,
277V SINGLE POLE - LEVITON #5629-2, 277V THREE WAY - LEVITON
#5639-2,
C. RECEPTACLES SHALL BE INDUSTRIAL SPECIFICATION GRADE OF THE
NEMA STANDARD CONFIGURATION FOR EACH APPLICATION USING A
HORSESHOE SHAPED GROUNDING POLE, AS FOLLOWS:
1. 120 VOLT CONVENIENCE: DUPLEX RECEPTACLE, 15 AMPERE 125
VOLT RATED, PARALLEL BLADE AND U SHAPED GROUNDING CONTACT,
SIDE WIRED. LEVITON 16242.
2. 120 VOLT APPLIANCE: DUPLEX RECEPTACLE, 20 AMPERE 125 VOLT
RATED, PARALLEL BLADE AND U SHAPED GROUNDING CONTACT, SIDE
WIRED. LEVITON 16342
3. OTHER RECEPTACLE TYPES AS REQUIRED SHALL BE SPECIFIED ON
DRAWINGS OR SYMBOLS LIST.
D. ALL RECEPTACLES AND SWITCHES SHALL BE SIDE WIRED WITH
CONDUCTORS TERMINATED AT SCREW TERMINALS. PUSH IN WIRING WILL NOT
BE PERMITTED.
E. SWITCHES SHALL BE INSTALLED AT THE STRIKE SIDE DIRECTLY
ADJACENT TO THE ENTRANCE DOOR OF THE ROOM. CHECK THE DRAWINGS
FOR DOOR SWINGS SO THAT ALL SWITCHES SHALL BE LOCATED ON THE LOCK
SIDE OF THE OPENINGS.
F. ALL DEVICE PLATES FOR WALL OUTLETS (LIGHTING CONTROL SWITCH,
POWER, DATA, TELEPHONE, TV, ETC.) SHALL BE LEVITON. DEVICE PLATES FOR
TELEPHONE, DATA AND TV OUTLETS SHALL CONTAIN APPROPRIATE JACKS;
COORDINATE WITH ENGINEER AND OWNER.
13. GROUNDING
A. TRANSFORMERS, METAL RACEWAYS, METAL ENCLOSURES OF
ELECTRICAL DEVICES LIGHTING FIXTURES, ELECTRICAL EQUIPMENT AND OTHER
EQUIPMENT SHALL BE COMPLETELY GROUNDED IN AN APPROVED MANNER TO
NEAREST EFFECTIVELY GROUNDED BUILDING STEEL OR COLD WATER PIPE, IN
ACCORDANCE WITH THE REQUIREMENTS OF THE APPLICABLE CODES AND
AUTHORITIES. THIS IS IN ADDITION TO THOSE GROUNDING CONDUCTORS
REQUIRED BY THE DRAWINGS.
J. CONDUIT SYSTEMS SHALL BE INSTALLED COMPLETE BEFORE ANY
CONDUCTORS ARE DRAWN IN. WIRE PULLING LUBRICANTS, WHEN UTILIZED,
SHALL BE IN ACCORDANCE WITH UL REQUIREMENTS REGARDING THE SPECIFIC
CONDUCTOR OR CABLE INSULATION AND RACEWAY MATERIAL.
14. EQUIPMENT MOUNTING
K. SHERARDIZED OR HOT DIPPED GALVANIZED STAMPED STEEL OR
ELECTRO-GALVANIZED CAST IRON OR COPPER FREE CAST ALUMINUM ALLOY
OUTLET BOXES SHALL BE PROVIDED FOR EVERY OUTLET CALLED FOR ON
DRAWINGS, SUITABLE FOR THE NUMBER AND ARRANGEMENT OF CONDUITS,
CABLES, LOCATION, ETC. WHERE REQUIRED AND APPROVED BY ENGINEER,
EXTRA DEEP OR EXTRA SHALLOW OUTLET BOXES SHALL BE USED TO
FACILITATE THE INSTALLATION OF THE CONDUIT SYSTEM.
A. PROVIDE INSERTS, EXPANSION SHIELD LUGS, ANCHORS, BOLTS WITH
NUTS AND WASHER SHIM OR ANY OTHER TYPE OF FASTENING DEVICES
REQUIRED TO FASTEN PANELS OR OTHER EQUIPMENT, TO FOUNDATIONS,
FLOORS, WALLS OR CEILINGS. UNLESS OTHERWISE SPECIFIED HEREIN OR
SHOWN ON THE CONTRACT DRAWINGS, ALL FASTENERS SHALL BE HOT DIPPED
GALVANIZED AND OF SIZES AND TYPES RECOMMENDED BY THE EQUIPMENT
MANUFACTURER AND AS APPROVED BY TRILLIUM.
B. ALL PROPER HARDWARE REQUIRED FOR A COMPLETE GROUNDING
SYSTEM SHALL BE INSTALLED BY THE CONTRACTOR.
A. THE CONTRACTOR SHALL MATCH THE COLOR-CODING THAT IS BEING
USED IN THE BUILDING, IF APPLICABLE, OR AS FOLLOWS (DEVIATION DUE TO
LIMITED QUANTITIES OF CABLE MAY BE PERMITTED UPON WRITTEN APPROVAL
BY THE ENGINEER):
SYSTEM VOLTAGE
PHASE
A
B
C
NEUTRAL
GROUND
ISOLATED GROUND
277/480V
BROWN
ORANGE
YELLOW
GRAY
GREEN
-
120/208V
BLACK
RED
BLUE
WHITE
GREEN
GREEN/YELLOW STRIPE
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
17. IDENTIFICATION
EQUIPMENT AND CONDUCTORS SHALL BE IDENTIFIED AS FOLLOWS:
A. ALL MAJOR COMPONENTS OF THE DISTRIBUTION SYSTEM SUCH AS
STARTERS, DISCONNECT SWITCHES, PANEL BOARD, ETC, MUST HAVE
NAMEPLATES WITH EQUIPMENT IDENTIFICATION, VOLTAGE AND PHASE RATINGS
AND SOURCE OF FEED OR CIRCUIT UTILIZATION. PANEL BOARDS SHALL HAVE
TYPED DIRECTORIES.
B. ALL STARTERS, DISCONNECT SWITCHES AND CONTROLS SHALL HAVE
NAMEPLATES IDENTIFYING THE EQUIPMENT SERVED. NAMEPLATES SHALL BE
LAMINATED PHENOLIC, WITH WHITE LETTERS ON A BLACK FIELD SECURED WITH
FLUSHED FASTENINGS. LETTERS TO BE 1/4" HIGH, MINIMUM.
C. ALL WIRES SHALL BE IDENTIFIED BY CIRCUITS IN ALL CABINETS, BOXES,
WIRING TROUGH AND OTHER ENCLOSURES, AND AT ALL TERMINAL POINTS (I.E.,
RECEPTACLES, ETC.).
D. THE CIRCUIT DESIGNATIONS SHALL BE AS SHOWN ON THE CONTRACT
DRAWINGS OR AS DIRECTED BY THE ENGINEER. TAGS SHALL BE ATTACHED TO
WIRES SO THAT THEY WILL BE READILY VISIBLE.
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
E. BRADY-B500 VINYL CLOTH WIRE AND TERMINAL MARKERS SHALL BE
USED FOR ALL WIRE IDENTIFICATION OR APPROVED EQUAL.
F. ALL CONDUCTORS TO BE IDENTIFIED WITH NON-REPETITIVE NUMBERS,
ALL CONDUCTORS TO BE IDENTIFIED ON BOTH ENDS, AND WITHIN 18" OF
CONDUIT ENTRANCE OF ENCLOSURE.
18. SAFETY SWITCHES
A. SAFETY TYPE DISCONNECTING SWITCHES SHALL BE RATED AT 250 OR
600 VOLTS AS REQUIRED BY THE UTILIZATION VOLTAGE AND SHALL BE
QUICK-MAKE, QUICK-BREAK TYPE, HORSEPOWER RATED. SWITCHES SHALL BE
MANUFACTURED BY AMERICAN CIRCUIT BREAKER CORP., SIEMENS, SQUARE D,
OR APPROVED EQUAL. PROVIDE HEAVY DUTY SWITCHES
J BARBER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
B. ALL PARTS OF THE SWITCH SHALL BE MOUNTED ON INSULATED BASE
TO PERMIT REPLACEMENT OF ANY PARTS FROM THE FRONT OF THE SWITCH.
ALL CURRENT CARRYING PARTS SHALL BE OF HIGH CONDUCTIVITY COPPER,
DESIGNED TO CARRY RATED LOAD WITHOUT EXCESSIVE HEATING. SWITCH
CONTACTS SHALL BE SILVER TUNGSTEN TYPE OR PLATED TO PREVENT
CORROSION, PITTING AND OXIDATION AND TO ASSUME SUITABLE
CONDUCTIVITY. FUSE CLIPS, WHERE REQUIRED, SHALL BE OF THE POSITIVE
PRESSURE REJECTION TYPE. SWITCHES SHALL BE CAPABLE OF WITHSTANDING
THE AVAILABLE FAULT CURRENT OR LET-THROUGH CURRENT BEFORE THE
FUSE OPERATES WITHOUT DAMAGE OR CHANGE IN RATING. PROVIDE GROUND
LUGS IN ALL SWITCHES. PROVIDE INTERLOCKING COVER WHICH NORMALLY
CANNOT BE OPENED WHEN SWITCH IS IN "ON" POSITION AND WITH MEANS OF
BYPASSING THE MECHANICALLY INTERLOCK DOOR AND HANDLE.
ELECTRICAL
NOTES
SHEET:
E-3
C. LUGS SHALL BE RATED FOR THE USE OF CABLES WITH EITHER 75 DEG. C
OR 90 DEG. C INSULATION WITHOUT DERATING. MULTI-BARREL LUGS SHALL BE
PROVIDED TO ACCOMMODATE PARALLEL FEEDER CABLES AND/OR TAPS AS
REQUIRED. "DOUBLE LUGGING" WILL NOT BE PERMITTED.
D. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL DISCONNECT
SWITCHES, COPPER DETAIL, TROUGH, ETC., AS SHOWN IN ELECTRICAL DRAWINGS,
AND WIRING BETWEEN ALL DISCONNECT SWITCHES, STARTERS, LIGHTING AND
POWER PANELS AS WELL AS TO ALL MECHANICAL EQUIPMENT AS SHOWN IN
ELECTRICAL DRAWINGS.
19. FUSES
A. FUSES SHALL BE OF THE RATINGS SHOWN ON THE DRAWINGS AND THEY
SHALL BE UL LISTED. WHERE SIZES ARE NOT SHOWN, THEY SHALL BE OF
REQUIRED SIZE FOR PROPER OPERATION OF EQUIPMENT PROTECTED.
B. ALL FUSES SHALL HAVE AN INTERRUPTING CAPACITY AS REQUIRED TO
INTERRUPT THE AVAILABLE SHORT CIRCUIT CURRENT. CURRENT LIMITING FUSES
SHALL BE PROVIDED.
C. THE TIME CURRENT CHARACTERISTICS AND RATINGS OF FUSES SHALL BE
SUCH THAT POSITIVE SELECTIVE COORDINATION IS ASSURED.
2. RIGID CONDUIT WITH EXPLOSION PROOF JOINTS AND FITTINGS SHALL BE
EMPLOYED AS THE TYPE OF WIRING. WHERE IT IS NECESSARY TO EMPLOY
FLEXIBLE CONNECTIONS, AS AT MOTOR TERMINALS, A FLEXIBLE FITTING OF THE
EXPLOSION PROOF TYPE SHALL BE USED. AT POINTS WHERE CONDUIT
TERMINATES IN AN ENCLOSURE IN WHICH ARCING OR SPARKING IS LIKELY TO
OCCUR, SUCH AS AT MOTOR TERMINALS, SWITCH BOXES AND THE LIKE, AND
WHEREVER A CONDUIT LEADS FROM A HAZARDOUS TO A NONHAZARDOUS
LOCATION, THE CONDUIT SHALL BE SEALED OFF BY A SEALING COMPOUND
WHICH IS NOT AFFECTED BY THE SURROUNDING ATMOSPHERE OR LIQUIDS,
AND WHICH HAS A MELTING POINT OF NOT LESS THAN TWO HUNDRED DEGREES
FAHRENHEIT. THE SEALING COMPOUND SHALL HAVE A THICKNESS OF NOT
LESS THAN FIVE-EIGHTHS INCH. JOINTS IN RIGID CONDUIT MADE WITH
THREADED COUPLINGS HAVING FIVE FULL THREADS ENGAGED ARE
RECOGNIZED AS BEING EXPLOSION PROOF.
3. FUSES SHALL NOT BE INSTALLED UNLESS MOUNTED WITHIN
EXPLOSION PROOF ENCLOSURES. THE FUSE CUTOUT BASES AND THEIR
ENCLOSURES SHALL BE APPROVED AS UNIT DEVICES FOR USE IN CLASS 1, DIV 1
AREAS. CIRCUIT BREAKERS, IF USED, SHALL BE OF A TYPE APPROVED FOR USE
IN CLASS 1, DIV 1 AREAS.
C. ALL LUMINARIES AND LIGHTING EQUIPMENT SHALL BE DELIVERED TO
THE PREMISES COMPLETE, INCLUDING ALL MOUNTING ACCESSORIES AND
COMPONENTS NECESSARY FOR THE PROPER OPERATION OF THE EQUIPMENT
EXCLUSIVE OF LAMPS.
D. ALL FIXTURES AND COMPONENTS SHALL BE MADE IN ACCORDANCE
WITH THE NEC AND CALIFORNIA CODE AND SHALL CONFORM TO ALL
APPLICABLE UL REQUIREMENTS.
E. LAMPS SHALL BE MANUFACTURED BY GENERAL ELECTRIC,
WESTINGHOUSE, OSRAM/SYLVANIA OR PHILLIPS. ALL FLUORESCENT LAMPS
SHALL BE ENERGY SAVING TYPE. INCANDESCENT LAMPS (INCLUDING ANY
HALOGEN TYPE) SHALL BE 130 VOLT RATED, LONG LIFE TYPE. PROVIDE ALL
LAMPS REQUIRED. PROVIDE ONE SPARE LAMP OF EACH TYPE UTILIZED IN THE
PROJECT.
F. ALL LAMPS INCLUDING FLUORESCENT TUBES, INCANDESCENT BULBS,
ETC., ARE TO BE GUARANTEED FOR A MINIMUM 3 MONTH PERIOD. DURING THIS
THREE MONTH PERIOD THE CONTRACTOR IS TO REPLACE, AT NO COST TO THE
OWNER, ANY "BURNED-OUT" LAMPS. THE THREE MONTH PERIOD IS TO
COMMENCE AT THE COMPLETION OF THE PAINTING PHASE OF THE PROJECT.
4. MOTORS SHALL BE CLASS 1,DIV 1 RATED.
INSTALLATION AND LOCATING OF FIXTURES
20. PANEL BOARDS
A. PANEL BOARDS SHALL BE DESIGNED FOR THE SPECIFIED VOLTAGES AND
NUMBER OF CIRCUIT BREAKERS AS SHOWN IN THE SCHEDULES. PANEL BOARD
INTERIORS AND CIRCUIT BREAKERS SHALL BE MANUFACTURED BY GENERAL
ELECTRIC, EATION/CUTLER-HAMMER, AMERICAN CIRCUIT BREAKER CORP.,
SIEMENS, SQUARE D OR APPROVED EQUAL.
B. PANEL BOARD CABINETS SHALL BE OF THE GENERAL PURPOSE DEAD
FRONT TYPE FOR FLUSH OR SURFACE MOUNTING AS INDICATED ON THE DRAWINGS.
TRIM OF PANEL BOARD FRONT SHALL BE MADE OF COLD ROLLED SHEET STEEL OF
NOT LESS THAN 12 GAUGE PROVIDED WITH A COAT OF ZINC CHROMATE PRIMER
AND ONE FINISH COAT OF ANSI-61LIGHT GRAY ENAMEL. TRIMS SHALL HAVE FLUSH
CLOSING DOORS OF SHEET STEEL HAVING CONCEALED CONTINUOUS HINGES
COMPLETE WITH CHROME PLATED FLUSH TYPE COMBINATION LOCK AND CATCH.
ALL CNG PANELS SHALL BE KEYED ALIKE. GUTTER SPACE SHALL CONFORM TO
CALIFORNIA CODE REQUIREMENTS.
C. BUS BARS SHALL BE OF HARD DRAWN COPPER AND SHALL EXTEND FULL
HEIGHT OF PANEL. PROVIDE A SEPARATE AND ISOLATED GROUND BUS IN ADDITION
TO THE NEUTRAL BUS WHERE INDICATED IN THE SCHEDULES.
D. THE PHASE BUS TO WHICH EACH SINGLE POLE BRANCH IS CONNECTED
SHALL BE SO ARRANGED THAT THE SAME RELATIONSHIP OF PHASE SEQUENCE IS
MAINTAINED FOR EACH CONSECUTIVE POLE.
E. CIRCUIT BREAKERS SHALL BE BOLT-DOWN TYPE. MINIMUM AIC RATING
SHALL BE 10,000 A FOR 250 VOLT CLASS AND 14,000 A FOR 600 VOLT CLASS OR AS
INDICATED IN THE SCHEDULE. CIRCUIT BREAKERS SHALL BE IN ACCORDANCE WITH
AVAILABLE SHORT CIRCUIT CURRENT.
F. PROVIDE HACR TYPE CIRCUIT BREAKERS FOR HVAC EQUIPMENT CIRCUITS.
G. ALL PANEL BOARDS SHALL BE BALANCED TO WITHIN 10% DEVIATION
BETWEEN PHASES PRIOR TO FINAL PAYMENT, IN SO FAR AS IS POSSIBLE.
H. ALL LUGS, BUSSING, AND SECTIONS WILL BE TORQUED ACCORDING TO
PANEL BOARD MANUFACTURES RECOMMENDATIONS. CONTRACTOR TO SUBMIT A
REPORT TO TRILLIUM STATING COMPLIANCE AND TORQUE SETTINGS.
21. DRY TYPE TRANSFORMERS
A. TRANSFORMERS SHALL BE DRY TYPE, TWO WINDING, DESIGNED FOR 460V
DELTA PRIMARY, 208/120V WYE SECONDARY, 3 PHASE, 60 HZ SERVICE. OPEN
DELTA OR T-WOUND TRANSFORMERS WILL NOT BE ACCEPTABLE.
B. ALL INSULATED MATERIALS SHALL BE 200 DEGREES C CLASS.
C. TRANSFORMERS SHALL BE DESIGNED NOT TO EXCEED 115 DEGREES RISE
ABOVE 40 DEGREES C AMBIENT TEMPERATURE AT FULL LOAD.
D. TRANSFORMER SHALL HAVE A MINIMUM OF FOUR 2-1/2% FULL CAPACITY
TAPS, TWO ABOVE AND TWO BELOW NORMAL.
E. WINDINGS SHALL BE COPPER.
F. TRANSFORMERS SHALL BE AS MANUFACTURED BY GENERAL ELECTRIC,
EATON/CUTLER HAMMER, SORGEL, SQUARE D OR APPROVED EQUAL.
G. PROVIDE SYSTEM AND EQUIPMENT GROUNDING IN ACCORDANCE WITH NEC.
H. CONNECT ISOLATED GROUNDING CONDUCTORS TO TRANSFORMER
NEUTRAL GROUNDING POINT, AS REQUIRED.
22. ELECTRICAL CODE CLASS I DIVISION 1 LOCATION REQUIREMENTS
A. IN CLASS I LOCATIONS, THE FOLLOWING PROVISIONS SHALL BE OBSERVED:
1. NO SERVICE ENTRANCE EQUIPMENT, SWITCHBOARDS OR PANEL BOARDS
SHALL BE INSTALLED UNLESS OF A TYPE APPROVED FOR USE IN CLASS 1, DIV 1
AREAS.
5. MOTOR CONTROLLERS, THERMAL CUTOUTS, SWITCHES, RELAYS,
THE SWITCHES AND CONTACTORS OF AUTO TRANSFORMER STARTERS,
RESISTANCE OR IMPEDANCE DEVICES OR OTHER DEVICES OR APPARATUS
WHICH, IN THEIR NORMAL OPERATION, TEND TO CREATE ARCS, SPARKS, OR
HIGH TEMPERATURES, SHALL NOT BE INSTALLED UNLESS SUCH DEVICES OR
APPARATUS ARE OF A TYPE APPROVED FOR USE IN CLASS 1, DIV 1 AREAS.
MOTOR CONTROLLERS SHALL PREFERABLY BE OF THE REMOTE CONTROL TYPE
WITH THE MAIN CONTACTORS LOCATED AT A POINT WHERE THE HAZARDOUS
CONDITIONS OF THIS CLASS DO NOT PREVAIL. AUXILIARY CONTROL PUSH
BUTTON OR SWITCHES OF A TYPE APPROVED FOR USE IN CLASS 1, DIV 1 AREAS
MAY BE PLACED IN THE MOST CONVENIENT LOCATIONS.
6. ELECTRIC HEATING APPLIANCES SHALL NOT BE USED UNLESS OF A
TYPE APPROVED FOR THE PARTICULAR LOCATION OR TYPE OF MATERIAL IN OR
WITH WHICH THEY ARE USED.
7. SWITCHES CONTROLLING LIGHTING CIRCUITS SHALL NOT BE
INSTALLED UNLESS OF A TYPE APPROVED FOR USE IN CLASS 1, DIV 1 AREAS.
G. FIXTURE LOCATION AS INDICATED ON THE ELECTRICAL DRAWINGS IS
GENERALIZED AND APPROXIMATE. THE CONTRACTOR SHALL CAREFULLY
VERIFY FIXTURE LOCATION WITH TRILLIUM REPRESENTATIVE, REFLECTED
CEILING PLAN AND OTHER REFERENCE DATA PRIOR TO INSTALLATION.
H. CEILING JUNCTION BOXES MUST BE ACCESSIBLE FROM FIXTURE
SERVED.
9. SUFFICIENT GENERAL ILLUMINATION SHALL BE PROVIDED BY FIXED
LIGHTING UNITS TO ELIMINATE, SO FAR AS POSSIBLE, THE NEED FOR PORTABLE
LAMPS. WHEN PORTABLE LAMPS ARE NECESSARY, THEY SHALL BE ENCLOSED
IN A MANNER APPROVED FOR CLASS 1, DIV 1 AREAS AND SHALL BE PROPERLY
PROTECTED BY SUBSTANTIAL METAL OR OTHER TYPES OF GUARDS TO PREVENT
BREAKAGE. SOCKETS FOR PORTABLE LAMPS SHALL BE OF THE KEYLESS
MOLDED COMPOSITION TYPE WITH NO EXPOSED METAL PARTS.
10. WHEN NECESSARY TO USE PORTABLE LAMPS OR OTHER PORTABLE
CURRENT CONSUMING DEVICES, FLEXIBLE CORD APPROVED FOR HARD USAGE,
SUCH AS TYPE S OR TYPE PA, SHALL BE USED. SUCH A FLEXIBLE CORD SHALL
CONTAIN ONE EXTRA INSULATED CONDUCTOR WHICH SHALL BE PROPERLY
CONNECTED TO FORM A GROUNDING CONNECTION FOR METAL LAMP GUARDS,
MOTOR FRAMES AND ALL OTHER EXPOSED METAL PORTIONS OF SUCH
PORTABLE LAMPS AND DEVICES.
11. CONNECTIONS OF PORTABLE CORDS DIRECT TO SUPPLY
CONDUCTORS SHALL FIRST BE MADE MECHANICALLY SECURE AND SHALL THEN
BE SOLDERED AND HEAVILY TAPED. IN ADDITION, THE CORD SHALL BE
SECURELY SUPPORTED SO THAT THE PROBABILITY OF A BREAK IN THE
CONDUCTORS AT THIS POINT WILL BE MINIMIZED.
12. RECEPTACLES AND ATTACHMENT PLUGS, IF USED, SHALL BE SO
CONNECTED AS A PART OF A UNIT DEVICE WITH AN EXPLOSION PROOF
INTERLOCKING SWITCH THAT THE PLUG CANNOT BE REMOVED WHILE THE
SWITCH IS IN THE "ON" POSITION, OR APPROVED DEVICES WHICH SEAL THE
ARC, MADE WHEN CURRENT IS INTERRUPTED, BY MEANS OF AN EXPLOSION
PROOF ENCLOSURE, SHALL BE USED. SUCH RECEPTACLES AND PLUGS SHALL
BE OF THE POLARIZED TYPE PROVIDING A CONNECTION FOR THE GROUNDING
WIRE OF THE PORTABLE CORD.
I. SPLICES SHALL NOT BE PERMITTED IN ANY RUN OF FIXTURE HOOKUP
WIRE.
J. CONNECTIONS TO BRANCH CIRCUIT CONDUCTORS AND TO EXISTING
FIXTURE WIRING SHALL BE MADE BY INSULATED SPRING CONNECTORS OR
CRIMP TYPE CONNECTORS.
K. WIRING BETWEEN FLUORESCENT LAMPHOLDERS AND ASSOCIATED
OPERATING AND STARTING EQUIPMENT SHALL BE OF THE SAME OR HEAVIER
GAUGE THAN THE LEADS FURNISHED WITH THE APPROVED TYPES OF BALLASTS
AND SHALL HAVE EQUAL OR BETTER INSULATING AND HEAT-RESISTING
CHARACTERISTICS. ALL OTHER WIRING WITHIN FLUORESCENT LIGHTING
FIXTURES OR FROM A FIXTURE TO THE SPLICE WITH THE BUILDING WIRING
SHALL CONFORM TO THE APPLICABLE REQUIREMENTS AND SHALL HAVE A
MINIMUM OF 90 DEG. C RATED INSULATION.
L. UNLESS OTHERWISE SPECIFIED OR SHOWN ON DRAWINGS, ALL WIRING
IN CONJUNCTION WITH INCANDESCENT FIXTURES SHALL CONFORM TO THE
REQUIREMENTS OF THE LATEST ISSUE OF THE NATIONAL ELECTRICAL CODE
AND SHALL BE NOT LESS THAN #16 AWG. WIRING SHALL BE PROTECTED WITH
TAPE OR TUBING AT ALL POINTS WHERE ABRASION IS LIABLE TO OCCUR.
WIRING SHALL BE CONCEALED WITHIN FIXTURE CONSTRUCTION, EXCEPT
WHERE THE FIXTURE DESIGN OR MOUNTING DICTATES OTHERWISE.
M. CONNECTIONS OF WIRES TO TERMINALS OF LAMPHOLDERS AND OTHER
ACCESSORIES SHALL BE MADE IN A NEAT AND WORKMANLIKE MANNER AND
SHALL BE ELECTRICALLY AND MECHANICALLY SECURE WITH NO LOOSE
STRANDS PROTRUDING. THE NUMBER OF WIRES EXTENDING TO OR FROM THE
TERMINALS OF A LAMPHOLDER SHALL NOT EXCEED THAT WHICH THE
ACCESSORY IS DESIGNED TO ACCOMMODATE.
N. JOINTS IN WIRING WITHIN LIGHTING FIXTURES AND CONNECTIONS OF
THE FIXTURE WIRING TO THE WIRING OF THE BUILDING SHALL BE SO SPLICED
THAT THEY WILL BE MECHANICALLY AND ELECTRICALLY SECURE AND THEN
SOLDERED AND TAPED TO PROVIDE INSULATION EQUAL TO THAT OF THE
CONDUCTORS BEING JOINED. IN LIEU OF SOLDER AND TAPE, APPROVED TYPES
OF ADEQUATELY INSULATED SOLDERLESS PRESSURE CRIMPED TYPE
CONNECTORS MAY BE FURNISHED, PROVIDED SIZES USED, METHOD OF
APPLICATION AND TOOLS EMPLOYED ARE IN ACCORDANCE WITH THE
CONNECTOR MANUFACTURER'S RECOMMENDATIONS.
O. WIRING CHANNELS AND WIREWAYS SHALL BE FREE FROM PROJECTIONS
AND ROUGH OR SHARP EDGED THROUGHOUT, AND ALL POINTS OR EDGES
OVER WHICH CONDUCTORS MUST PASS AND MAY BE SUBJECT TO INJURY OR
WEAR SHALL BE ROUNDED OR BUSHED. INSULATED BUSHINGS SHALL BE
INSTALLED AT POINTS OF ENTRANCE AND EXIT OF FLEXIBLE WIRING.
FLUORESCENT FIXTURES
13. THE EXPOSED NONCURRENT CARRYING METAL PARTS OF
EQUIPMENT, SUCH AS THE FRAMES OR METAL EXTERIORS OF MOTORS, FIXED
OR PORTABLE APPLIANCES, FIXTURES, CABINETS, CASES AND CONDUIT SHALL
BE GROUNDED AS DESCRIBED ABOVE. THE LOCKNUT BUSHING AND THE
DOUBLE LOCKNUT TYPE OF CONTACT SHALL NOT BE DEPENDED UPON FOR
BONDING PURPOSES, BONDING JUMPERS WITH PROPER FITTINGS OR OTHER
APPROVED MEANS BEING REQUIRED TO ASSURE AN EFFECTIVE GROUNDING
CIRCUIT.
14. THERE SHALL BE NO EXPOSED LIVE PARTS.
23. LIGHTING FIXTURES
GENERAL
A. THIS CLAUSE OF THE SPECIFICATIONS COVERS THE FURNISHING OF
LABOR, MATERIALS, EQUIPMENT AND THE INSTALLATION OF ALL LIGHTING
FIXTURES, LIGHTING, EQUIPMENT AND LAMPS, INCLUDING THE CONNECTION OF
FIXTURES AND EQUIPMENT TO THE ELECTRICAL WIRING SYSTEM AS SHOWN ON
PLANS.
B. THE CONTRACTOR IS DIRECTED TO REVIEW THE APPLICABLE
ELECTRICAL DRAWINGS FOR DETAILS ON FIXTURE CONSTRUCTION AND
INSTALLATION MEDIA FOR FIXTURES TO BE PURCHASED BY ELECTRICAL
CONTRACTOR.
ENGINEER STAMP:
24. EMERGENCY LIGHTING
A. EXIT SIGNS PROVIDE EDGE LIT SELF-POWERED EXIT SIGNS WITH
SEALED NICKEL CADMIUM BATTERY, 8" LETTERS AND COMBINATION TEST
SWITCH/CHARGE MONITOR LED. UNIT SHALL BE APPROVED BY LOS ANGELES
FIRE DEPARTMENT, AND MANUFACTURED IN ACCORDANCE WITH UL 924
REQUIREMENTS, ATLITE EDGE LIT SERIES OR APPROVED EQUAL, WITH RED
LETTERS ON CLEAR FACE PANEL. ARROW DIRECTIONS, NUMBER OF FACES,
MOUNTING METHOD AND TRIM PLATE FINISH SHALL BE AS REQUIRED FOR EACH
LOCATION. EXIT SIGNS SHALL BE CONNECTED TO A SEPARATE, DEDICATED
BRANCH CIRCUIT.
B. BATTERY PACKS PROVIDE EMERGENCY FLUORESCENT POWER PACK
UNIT WITH SEALED NICKEL CADMIUM BATTERY AND EXTERNAL TEST SWITCH
AND PILOT LIGHT FOR NEW OR EXISTING FLUORESCENT FIXTURES INDICATED,
UNIT SHALL BE TRILLIUM AND OWNER APPROVED, WIRED TO TWO LAMPS, LIGHT
ALARMS SERIES AM10 OR APPROVED EQUAL. PROVIDE ADDITIONAL WIRING AS
REQUIRED TO ENERGIZE CHARGER FROM UNSWITCHED POWER SUPPLY,
PROVIDE LIGHT ALARMS SERIES AM11 OR APPROVED EQUAL EMERGENCY
POWER PACK FOR COMPACT FLUORESCENT LAMPS WHERE INDICATED.
LIGHTING FIXTURE HOOKUP WIRE
WIRING
8. LAMPS IN FIXED POSITIONS SHALL BE ENCLOSED IN A MANNER
APPROVED FOR CLASS 1, DIV 1 AREAS AND SHALL BE PROPERLY PROTECTED BY
SUBSTANTIAL METAL GUARDS OR OTHER APPROVED MEANS WHERE EXPOSED
TO BREAKAGE. LAMPS SHALL NOT BE OF THE PENDANT TYPE UNLESS
SUPPORTED BY AND SUPPLIED THROUGH HANGERS OF RIGID CONDUIT OR
FLEXIBLE CONNECTORS APPROVED FOR CLASS 1, DIV 1 AREAS. WHERE RUBBER
COVERED WIRE IS USED, IT SHALL HAVE INSULATION NOT LESS THAN THREE
SIXTY-FOURTHS OF AN INCH THICK.
S. FIXTURES SHALL BE ATTACHED TO STRUCTURAL CEILING MEMBERS,
AND SHALL NOT DEPEND UPON LATHING OR PLASTER FOR ALIGNMENT OR
SUPPORT. FIXTURES IN SUSPENDED CEILINGS SHALL BE SUPPORTED BY FOUR
WIRES, ONE FROM EACH CORNER TO STRUCTURE, AND SHALL BE SUPPORTED
BY SADDLE HANGERS OR TIE-BARS ATTACHED TO RUNNERS OR BETWEEN
CROSSBARS OF CEILING SYSTEMS. MOUNTING SPLINES OR OTHER POSITIVE
MEANS OF MAINTAINING ALIGNMENT AND RIGIDITY SHALL BE PROVIDED.
SUPPORTING MEMBERS SHALL BE SURFACE PASSIVATED, AND BE PRIMED OR
PAINT DIPPED TO RESIST CORROSION. FASTENING DEVICES SHALL BE OF A
POSITIVE LOCKING TYPE, AND SHALL NOT REQUIRE THE USE OF SPECIAL TOOLS
TO REMOVE. TIE WIRES SHALL NOT BE USED IN PLACE OF FASTENING DEVICES.
25. TELEPHONE AND COMMUNICATIONS SYSTEMS
A. CONTRACTOR SHALL INSTALL ALL EMPTY CONDUITS AS REQUIRED BY
THE TELEPHONE COMPANY AND COMMUNICATIONS SYSTEM AND AS SHOWN IN
ELECTRICAL DRAWINGS. PROVIDE A STEEL CORE NYLON ROPE DRAG LINE WITH
TERMINAL BALL IN ALL EMPTY CONDUITS OVER 10' LONG.
26. INTERLOCKS
A. ALL INTERLOCK WIRING SHALL BE PROVIDED UNDER THE MECHANICAL
CONTRACT, INCLUDING ALL POWER TO AUTOMATIC DAMPERS, VALVES, AND ANY
OTHER CONTROL EQUIPMENT SUPPORTING THE MECHANICAL SYSTEM.
27. FINAL CLEANUP AND FIELD TESTS
AFTER COMPLETION OF THE ENTIRE ELECTRICAL INSTALLATION:
DESCRIPTION
REV
DATE
A. THE CONTRACTOR, BEFORE FINAL ACCEPTANCE WILL BE GRANTED,
SHALL CLEAN ALL LIGHTING FIXTURES, DEVICE PLATES, SERVICE FITTINGS AND
OTHER ITEMS FURNISHED UNDER THIS CONTRACT AND SHALL ENSURE THAT
ALL DIRECTORIES ARE IN PLACE WITH COMPLETED OR REVISED SCHEDULES
AND ALL IDENTIFICATIONS AND MARKINGS OF EQUIPMENT, CABLES AND OTHER
ITEMS, ARE COMPLETED.
B. THE CONTRACTOR SHALL REPAIR OR REPLACE, AS DIRECTED BY THE
ENGINEER, AT NO ADDITIONAL COST TO THE OWNER, ANY ITEM DAMAGED DUE
TO INSTALLATION, RELOCATION OR REINSTALLATION.
C. IN ADDITION TO OTHER TESTS WHICH MAY BE REQUIRED IN THE
VARIOUS OTHER DISCIPLINES, PERFORM FIELD TESTS IN THE PRESENCE OF THE
ENGINEER TO DEMONSTRATE THE RELIABILITY OF THE ELECTRICAL
INSTALLATION. PROVIDE THE ENGINEER WITH 48 HOURS ADVANCE NOTICE OF
SUCH TESTS. AS A MINIMUM, THE FOLLOWING FIELD TESTS SHALL BE
PERFORMED BY THE CONTRACTOR:
1. OPERATE ALL ELECTRICAL EQUIPMENT FOR A PERIOD OF 24 HOURS,
UNLESS OTHERWISE DIRECTED BY THE ENGINEER.
2. TEST ALL WIRES AND CABLES INSTALLED UNDER THIS CONTRACT
WITH A 1,000 VOLT MEGOHMETER. FURNISH THE ENGINEER WITH A COPY OF
THE RESULTS TOGETHER WITH AN OUTLINE OF THE METHOD USES. IF IN THE
OPINION OF THE ENGINEER, ANY READINGS ARE LOWER THAN REQUIRED BY
GOOD PRACTICE OR APPLICABLE CODES, PROMPTLY REPLACE THE MATERIALS
OR EQUIPMENT INVOLVED.
3. COMPLETE SYSTEM TEST OF ALARM, SECURITY AND CONTROL
SYSTEMS IN THE PRESENCE OF ALL APPROPRIATE PARTIES. SHOULD THE
FOREGOING TESTS REVEAL ANY DEFECTS, PROMPTLY CORRECT SUCH DEFECTS
AND RE-RUN THE TESTS UNTIL THE ENTIRE INSTALLATION IS SATISFACTORY IN
ALL RESPECTS.
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
28. RECORD DRAWINGS
PROJECT NAME:
A. AS PART OF THESE REQUIREMENTS A COMPLETE SET OF "AS-BUILT" OR
RECORD DRAWINGS SHALL BE PRODUCED AND DELIVERED TO TRILLIUM.
P. BALLASTS SHALL PROVIDE AND ASSURE SAFE AND RELIABLE OPERATION
OF THE PARTICULAR FLUORESCENT LAMP OR LAMPS SPECIFIED FOR EACH
FIXTURE TYPE. BALLASTS SHALL BE ETL/CBM CERTIFIED, CLASS "P" THERMALLY
PROTECTED, SUPER LOW HEAT, ELECTRONIC TYPE, ENERGY SAVING, HIGH
POWER FACTOR TYPE, WITH "A" SOUND LEVEL RATING, FOR OPERATION OF
RAPID START LAMPS, SERIES-SEQUENCE FOR MULTI-LAMP APPLICATIONS.
B. THE DRAWINGS SHALL SHOW:
1. ALL ELECTRICAL WORK INSTALLED.
2. ALL MODIFICATIONS AND/OR ADDITIONS TO THE ORIGINAL DESIGN.
3. ALL DIMENSIONAL INFORMATION NECESSARY TO LOCATE BURIED OR
CONCEALED CONDUIT WORK WHICH CANNOT BE TRACED THROUGH REGULAR
MEANS OF ACCESS.
Q. THE BALLASTS SHALL BE PROTECTED BY A MINIMUM OF ONE YEAR
GUARANTEE STARTING FROM THE DATE OF ACCEPTANCE OF THE INSTALLED
FIXTURES, AGAINST DEFECTS IN WORKMANSHIP WHICH INCLUDES AN
IN-WARRANTY SERVICE PROGRAM PROVIDING FOR THE PAYMENT OF
AUTHORIZED LABOR CHARGES INCURRED IN THE REPLACEMENT OF
INOPERATIVE OR DEFECTIVE IN-WARRANTY BALLASTS. REPLACE BALLASTS
FOUND BY ARCHITECT OR ENGINEER TO BE TOO NOISY PRIOR TO FINAL
ACCEPTANCE OF JOB WITHOUT CHARGES
C. THE DRAWINGS SHALL BE OF REPRODUCIBLE TYPE AND IN ELECTRONIC
FORMAT, AUTOCAD 2010 OR EARLIER FORMAT.
R. RECESSED FIXTURES SHALL BE FURNISHED COMPLETE WITH MOUNTING
DEVICES AND ACCESSORIES. WHERE NECESSARY TO MEET CODE
REQUIREMENTS, ENCLOSURE HOUSING SHALL BE SUITABLE FOR A 1 HOUR FIRE
RATING. ATTACHMENT DEVICES INCLUDING BRACKETS, PLASTER RINGS,
SADDLE HANGERS, AND TIE-BARS SHALL BE MADE OF FORMED OR ROLLED
METAL SHAPES WITH THE REQUISITE RIGIDITY AND STRENGTH TO MAINTAIN
CONTINUOUS ALIGNMENT OF THE INSTALLED FIXTURES.
REVISIONS:
REV
NO.
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
ELECTRICAL
NOTES
29. GUARANTEE
A. THE CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A
PERIOD OF ONE YEAR FROM THE ACCEPTANCE OF THE PROJECT AGAINST
DEFECTIVE MATERIALS OR WORKMANSHIP.
SHEET:
E-4
ENGINEER STAMP:
ESD
#8
ESD
#9
C01
C02
C03
C07
MCC
MCP
MCP
MCP
A
E-6
C04
C05
C06
C08
MCC
MCP
MCP
MCP
ESD
#10
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
GENERAL SHEET NOTES
J BARBER
LEGEND
1.
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS PER NEC. 501
2.
ALL UNDERGROUND CONDUITS SHALL HAVE SEAL OFFS AS THE FIRST JOINT
ABOVE GROUND IN HAZARDOUS AREAS.
ESD BUTTON
3.
ALL CONDUITS ON EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL
HAVE SEAL OFFS ON THE FIRST CONDUIT INTO OR OUT OF THE FIXTURE OR
ENCLOSURE.
WALL LIGHT
4.
CONTRACTOR TO LABEL ALL PHASES AND TEST EACH PANEL TO ENSURE
CONSISTENT PHASING THROUGHOUT PROJECT.
CANOPY LIGHT
5.
CONDUIT LOCATIONS SHOWN ARE DIAGRAMMATIC. CONDUIT LOCATIONS TO
BE DETERMINED IN THE FIELD.
6.
TRILLIUM WILL PROVIDE MAIN ELECTRICAL GEAR. MAIN ELECTRICAL GEAR WILL
BE DELIVERED IN SECTION. SECTION WILL BE CONNECTED AND TORQUED PER
MANUFACTURERS SPECIFICATIONS AND INSTALLED BY CONTRACTOR.
7.
CONTRACTOR TO PROVIDE WIRE MARKERS ON EACH END OF EACH WIRE.
WIRE NUMBERS WILL BE MARKED ON AS-BUILT SET OF DRAWINGS BY
CONTRACTOR.
8.
FLEXIBLE METAL CONDUIT IS NOT PERMITTED IN CLASS 1 DIVISION 1 AREAS
(CLASS 1 DIV 1). THIS INCLUDES PIT CONDUITS FOR DISPENSER ELECTRICAL
RUNS.
#
ESD BUTTON #
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
ELECTRICAL
CONDUIT
LAYOUT
CEILING LIGHT
PHOTO CELL
CCTV CAMERA
SHEET:
E-5
ENGINEER STAMP:
MCP
C54
C46
MCC
BRKR
C19
C20
MCC
C22
C53
#20
3$
C23
MCC
PHONE COMPANY
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
C50
MCC
MCP
C59
MCC
MCC
C49
C52
MCC
C52
TRANSFORMER
C21
MCP
C47
MCC
MCC
C48
3$
#11
MCC
C50
MCC
C50
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
MCP
MCC
CHECKS:
GENERAL SHEET NOTES
C42
C43
1.
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS PER NEC. 501
2.
ALL UNDERGROUND CONDUITS SHALL HAVE SEAL OFFS AS THE FIRST JOINT
ABOVE GROUND IN HAZARDOUS AREAS.
3.
ALL CONDUITS ON EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL
HAVE SEAL OFFS ON THE FIRST CONDUIT INTO OR OUT OF THE FIXTURE OR
ENCLOSURE.
4.
CONTRACTOR TO LABEL ALL PHASES AND TEST EACH PANEL TO ENSURE
CONSISTENT PHASING THROUGHOUT PROJECT.
5.
CONDUIT LOCATIONS SHOWN ARE DIAGRAMMATIC. CONDUIT LOCATIONS TO
BE DETERMINED IN THE FIELD.
6.
TRILLIUM WILL PROVIDE MAIN ELECTRICAL GEAR. MAIN ELECTRICAL GEAR WILL
BE DELIVERED IN SECTION. SECTION WILL BE CONNECTED AND TORQUED PER
MANUFACTURERS SPECIFICATIONS AND INSTALLED BY CONTRACTOR.
7.
8.
0'
2'
4'
6'
8'
10'
CONTRACTOR TO PROVIDE WIRE MARKERS ON EACH END OF EACH WIRE.
WIRE NUMBERS WILL BE MARKED ON AS-BUILT SET OF DRAWINGS BY
CONTRACTOR.
FLEXIBLE METAL CONDUIT IS NOT PERMITTED IN CLASS 1 DIVISION 1 AREAS
(CLASS 1 DIV 1). THIS INCLUDES PIT CONDUITS FOR DISPENSER ELECTRICAL
RUNS.
C COGGINS
2015-01-21
J BARBER
LEGEND
#
ESD BUTTON #
ESD BUTTON
WALL LIGHT
CANOPY LIGHT
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
ELECTRICAL
CONDUIT
LAYOUT
CEILING LIGHT
PHOTO CELL
CCTV CAMERA
SHEET:
E-6
LEGEND
GENERAL SHEET NOTES
MCC - MOTOR CONTROL CENTER (POWER)
MCP - MASTER CONTROL PANEL (CONTROL)
TWSP - TWISTED SHIELDED PAIR
1.
COLORS OF WIRE ARE SHOWN IN ON E-3 ON NOTE 16A.
2.
FLEXIBLE METAL CONDUIT IS NOT PERMITTED IN CLASS 1 DIVISION 1 AREAS
(CLASS 1 DIV 1). THIS INCLUDES PIT CONDUITS FOR DISPENSER ELECTRICAL
RUNS.
ENGINEER STAMP:
EQUIPMENT NOTES
1.
ESD BUTTONS: SHALL BE EATON 10250T7007 W/ 10250TA56 SHROUD
2.
PURGE BLOWER: FANTECH FKD-BXL W/ WC15 CONTROLLER
3.
ELECTRICAL ROOM CEILING LIGHTS: LITHONIA STL4 48L D50 LP835 NX
4.
EQUIPMENT AREA LIGHTS: DIALIGHT SAFESITE WPC2C3LNLGC LED CLASS 1 DIV
2-RATED 120V/34W WALLPACKS W/ APPROPRIATE MOUNTING FIXTURES
CONDUIT INSTALLED BY OTHERS.
WIRES TO BE PULLED BY CONTRACTOR
CA MARINA MRWMD - ELECTRICAL CONDUIT SCHEDULE
MARK
SIZE
QTY
C01
1"
1
DISPENSER 1 POWER
(4) #12 AWG THWN
C02
1"
1
DISPENSER 1 CONTROL
C03
1"
1
C04
1"
C05
DESCRIPTION
WIRE
COLOR
SEE GENERAL SHEET NOTE 1
FROM
TO
NOTES
MCC
DISPENSER 1
(4) #18 TWSP
MCP
DISPENSER 1
DISPENSER 1 SPARE
PULL ROPE
MCP
DISPENSER 1
1
DISPENSER 2 POWER
(4) #12 AWG THWN
MCC
DISPENSER 2
1"
1
DISPENSER 2 CONTROL
(4) #18 TWSP
MCP
DISPENSER 2
C06
1"
1
DISPENSER 2 SPARE
PULL ROPE
MCP
DISPENSER 2
C07
3/4"
1
DISPENSER 1 ESD #1
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
DISPENSER 1 ESD #1
SEE EQUIPMENT NOTE 1
C08
3/4"
1
DISPENSER 2 ESD #2
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
DISPENSER 2 ESD #2
SEE EQUIPMENT NOTE 1
C09
3/4"
1
DE-FUEL PANEL POWER
(12) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
DE-FUEL PANEL
C10
3/4"
1
DE-FUEL PANEL CONTROL
(2) CAT 5e
MCP
DE-FUEL PANEL
TWSP TO BE OMNI CABLE DS 11802
C11
3/4"
1
ZONE 1: ESD #3
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ZONE 1 ESD BUTTON #3
SEE EQUIPMENT NOTE 1
C12
3/4"
1
ZONE 1: ESD #3 TO ESD #4
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
ESD BUTTON #3
ZONE 1 ESD BUTTON #4
SEE EQUIPMENT NOTE 1
C13
3/4"
1
ZONE 1: ESD #4 TO ESD #5
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
ESD BUTTON #4
ZONE 1 ESD BUTTON #5
SEE EQUIPMENT NOTE 1
C14
3/4"
1
ZONE1: ESD #5 TO ESD #6
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
ESD BUTTON #5
ZONE 1 ESD BUTTON #6
SEE EQUIPMENT NOTE 1
C15
3/4"
1
ZONE 1: ESD #6 TO ESD #7
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
ESD BUTTON #6
ZONE 1 ESD BUTTON #7
SEE EQUIPMENT NOTE 1
C16
3/4"
1
ZONE 2 : ESD #8
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ZONE 2 ESD BUTTON #8
SEE EQUIPMENT NOTE 1
C17
3/4"
1
ZONE 2: ESD #8 TO ESD #9
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
ESD BUTTON #8
ZONE 2 ESD BUTTON #9
SEE EQUIPMENT NOTE 1
C18
3/4"
1
ZONE 2: ESD #9 TO EDS #10
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
ESD BUTTON #9
ZONE 2 ESD BUTTON #10
SEE EQUIPMENT NOTE 1
C19
4"
4
POWER FROM TRANSFORMER
(3) 600 MCM THWN, (1) 600 MCM THWN GND
SEE GENERAL SHEET NOTE 1
TRANSFORMER
MAIN BREAKER
CONDUITS AND WIRE SUPPLIED BY OTHERS
C20
4"
4
MOTOR CONTROL CENTER - POWER
(3) 600 MCM THWN, (1) 600 MCM THWN GND
SEE GENERAL SHEET NOTE 1
MAIN BREAKER
MOTOR CONTROL CENTER (MCC)
C21
N/A
1
MASTER CONTROL PANEL - POWER
(6) #10 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
MASTER CONTROL PANEL (MCP)
WIRES TO BE PULLED THROUGH ELECTRICAL GUTTER
C22
N/A
1
MOTOR CONTROL PANEL - I/O CONTROLS
(2) #14 AWG THWN, (2) CAT 5e
SEE GENERAL SHEET NOTE 1
MCP
MCC
WIRES TO BE PULLED THROUGH ELECTRICAL GUTTER
C23
N/A
1
COMMUNICATIONS
(4) CAT 5e
MCP
PHONE COMPANY
TERMINATION POINT TBD
C24
1-1/2"
1
480 VAC TO 480-120/208 XFMR
(4) #1 AWG THWN, (1) #6 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
480-120/208 XFMR
C25
1-1/2"
1
120 VAC XFMR TO L1 & LS2 BREAKER
(3) #1 AWG THWN, (1) #2 AWG THWN GND
SEE GENERAL SHEET NOTE 1
480-120/208 XFMR
MCC
C26
3"
1
COMPRESSOR A POWER
(6) 3/0 MCM THWN, (1) #3 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
SKID A MOTOR
ANGI CONDUIT CONNECTION C4
C27
1"
1
COMPRESSOR A PRELUBE, COOLER & HEATER
(9) #10 AWG THWN, (3) #10 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
SKID A POWER BOX
ANGI CONDUIT CONNECTION C3
C28
1"
1
COMPRESSOR A 120V POWER
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
SKID A POWER BOX
ANGI CONDUIT CONNECTION C2
C29
1"
1
COMPRESSOR A CONTROL
(2) CAT 5e
MCP
SKID A POWER BOX
ANGI CONDUIT CONNECTION C1
C30
3"
1
COMPRESSOR B POWER
(6) 3/0 MCM THWN, (1) #3 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
SKID B MOTOR
ANGI CONDUIT CONNECTION C4
C31
1"
1
COMPRESSOR B PRELUBE, COOLER & HEATER
(9) #10 AWG THWN, (3) #10 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
SKID B POWER BOX
ANGI CONDUIT CONNECTION C3
C32
1"
1
COMPRESSOR B 120V POWER
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
SKID B POWER BOX
ANGI CONDUIT CONNECTION C2
C33
1"
1
COMPRESSOR B CONTROL
(2) CAT 5e
MCP
SKID B POWER BOX
ANGI CONDUIT CONNECTION C1
C34
3"
1
COMPRESSOR C POWER
(6) 3/0 MCM THWN, (1) #3 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
SKID C MOTOR
ANGI CONDUIT CONNECTION C4
C35
1"
1
COMPRESSOR C PRELUBE, COOLER & HEATER
(9) #10 AWG THWN, (3) #10 AWG THWN GND
SEE GENERAL SHEET NOTE 1
MCC
SKID C POWER BOX
ANGI CONDUIT CONNECTION C3
C36
1"
1
COMPRESSOR C 120V POWER
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
SKID C POWER BOX
ANGI CONDUIT CONNECTION C2
C37
1"
1
COMPRESSOR C CONTROL
(2) CAT 5e
MCP
SKID C POWER BOX
ANGI CONDUIT CONNECTION C1
C38
3"
1
FUTURE COMPRESSOR D POWER
PULL ROPE
SEE NOTE 16 ON PAGE E-3
MCC
SKID D MOTOR
ANGI CONDUIT CONNECTION C4
C39
1"
1
FUTURE COMPRESSOR D PRELUBE, COOLER & HEATER
PULL ROPE
SEE NOTE 16 ON PAGE E-3
MCC
SKID D POWER BOX
ANGI CONDUIT CONNECTION C3
C40
1"
1
FUTURE COMPRESSOR D 120V POWER
PULL ROPE
SEE NOTE 16 ON PAGE E-3
MCC
SKID D POWER BOX
ANGI CONDUIT CONNECTION C2
C41
1"
1
FUTURE COMPRESSOR D CONTROL
PULL ROPE
MCP
SKID D POWER BOX
ANGI CONDUIT CONNECTION C1
C42
2"
1
GAS DRYER POWER
(3) #6 AWG THWN, (1) #10 AWG THWN GND
MCC
GAS DRYER
C43
1"
1
GAS DRYER CONTROL
(2) CAT 5e
MCP
GAS DRYER
C44
3/4"
1
VALVE PANEL 120V CONTROL
(6) #18 TWSP, (12) #12 AWG THWN
MCP
VALVE PANEL
C45
3/4"
1
VALVE PANEL SPARE
PULL ROPE
MCP
VALVE PANEL
C46
3/4"
1
AIR COMPRESSOR POWER
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
AIR COMPRESSOR
C47
3/4"
1
AIR DRYER POWER
(3) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
AIR DRYER
C48
3/4"
1
PURGE BLOWER POWER
(3) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
PURGE BLOWER
SEE EQUIPMENT NOTE 2
C49
1"
1
ELECTRICAL ROOM CEILING LIGHTS
(3) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
ELECTRICAL ROOM LIGHTS
SEE EQUIPMENT NOTE 3
C50
1"
1
EQUIPMENT AREA C1D2 AREA LIGHTS
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
EQUIPMENT AREA LIGHTS
SEE EQUIPMENT NOTE 4
C51
1"
1
PHOTOCELL
(3) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
PHOTOCELL
C52
1"
1
CONTROL ROOM 120V OUTLETS
(3) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
120V OUTLETS
120V GFCI OUTLETS
C53
1"
1
208V OUTLET FOR HVAC
(3) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCC
208V OUTLET
208V 20A PLUG OUTLET FOR HVAC
C54
3/4"
1
EQUIPMENT AREA ESD BUTTON #11
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ESD BUTTON #11
SEE EQUIPMENT NOTE 1
C55
3/4"
1
EQUIPMENT AREA ESD BUTTON #12 & #13
(6) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ESD BUTTONS #12 & #13
SEE EQUIPMENT NOTE 1
C56
3/4"
1
EQUIPMENT AREA ESD BUTTON #14 & #15
(6) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ESD BUTTONS #14 & #15
SEE EQUIPMENT NOTE 1
C57
3/4"
1
EQUIPMENT AREA ESD BUTTON #16 & #17
(6) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ESD BUTTONS #16 & #17
SEE EQUIPMENT NOTE 1
C58
3/4"
1
EQUIPMENT AREA ESD BUTTON #18 & #19
(6) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ESD BUTTONS #18 & #19
SEE EQUIPMENT NOTE 1
C59
3/4"
1
EQUIPMENT AREA ESD BUTTON #20
(4) #12 AWG THWN
SEE GENERAL SHEET NOTE 1
MCP
ESD BUTTON #20
SEE EQUIPMENT NOTE 1
SEE GENERAL SHEET NOTE 1
SEE GENERAL SHEET NOTE 1
SEE GENERAL SHEET NOTE 1
TWSP TO BE OMNI CABLE DS 11802
TWSP TO BE OMNI CABLE DS 11802
TWSP TO BE OMNI CABLE DS 11802
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
CONDUIT
SCHEDULE
SHEET:
E-7
GENERAL SHEET NOTES
SHEET KEYNOTES
1.
120/208V 100A 24 CIRCUIT PANEL.
2.
CONTACTOR TO BE WIRED TO ESD CIRCUIT.
3.
1.
PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT LOCATED OUTDOORS. REFER
TO PLANS FOR EQUIPMENT LOCATIONS.
2.
REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
3.
ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO SPECIFICATIONS FOR
REQUIREMENTS.
TRANSFORMER TO BE PROVIDED BY OTHERS.
ENGINEER STAMP:
4. NEMA 3R SERVICE ENTRANCE RATED GEAR.
5.
NEMA 3R GEAR.
6.
CUTLER-HAMMER TYPE SERIES C, TYPE NW/HNW/NWC CIRCUIT BREAKER WITH
ELECTRONIC SHORT DELAY PICKUP AND TIME TRIP UNIT.
7.
CIRCUIT BREAKER TO PROVIDE GROUND FAULT PROTECTION.
8.
CIRCUIT BREAKER IS OPTIONAL IF SERVICE ENTRANCE BREAKER IS IN LINE OF
SITE OF MCC. REPLACE WITH A DISCONNECT.
4. CONTRACTOR TO LABEL ALL PHASES AND TEST EACH PANEL TO ENSURE
CONSISTENT PHASING THROUGHOUT PROJECT.
5.
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS AS PER NEC 501. ALL UNDER GROUND CONDUITS SHALL
HAVE A SEAL OFF AS THE FIRST JOINT ABOVE GROUND. ALL CONDUITS ON
EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL HAVE SEAL OFF ON FIRST
CONDUIT INTO OR OUT OF THE FIXTURE OF ENCLOSURE.
6.
SEE SHEET E-5, E-6, & E-7 FOR CONDUIT AND CONDUCTOR SCHEDULE.
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
ELECTRICAL
ONE LINE
DIAGRAM
SHEET:
E-8
5
GENERAL SHEET NOTES
5'-0"
VENT STACK DISCHARGE
2
1.
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS PER NEC. 501.
2.
ALL UNDERGROUND CONDUITS SHALL HAVE SEAL OFFS AS THE FIRST JOINT
ABOVE GROUND IN HAZARDOUS AREAS.
3.
ALL CONDUITS ON EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL
HAVE SEAL OFFS ON FIRST CONDUIT INTO OR OUT OF THE FIXTURE OF
ENCLOSURE.
4.
FORM 5 LB FITTINGS ALLOWED TO BE USED IN C1D2 AREAS WHERE IT IS USED
AS A PULL BOX FOR WIRE. SEAL OFFS ARE REQUIRED AT STUB UP AREAS AND
BEFORE ENTERING WIRE TERMINATION DEVICE.
5.
HAZARDOUS AREAS SHOWN PER NFPA 52-2013 TABLE 7.4.2.9 ELECTRICAL
INSTALLATIONS.
6.
INSIDE COMPRESSOR ENCLOSURES DEFINED AS CLASS 1 DIVISION 2 PER
NFPA 52-2013.
5'-0"
15'-0"
2
5'-0"
10'-0"
MIN.
5
5'-0"
COMPRESSED NATURAL GAS (CNG) DISPENSER
1
ENGINEER STAMP:
2
5'
-0
"
COMPRESSED NATURAL GAS (CNG) VENT STACK
HAZARDOUS LOCATION AROUND FUEL DISPENSERS (TYPICAL)
VENT STACK DISCHARGE
2
1
R5
'-0
"
R15'-0"
HAZARDOUS LOCATION AROUND VENT STACK (TYPICAL)
SHEET KEY NOTES
1
2
3
4
5
NEC CLASS 1 DIVISION 1 HAZARDOUS AREA
NEC CLASS 1 DIVISION 2 HAZARDOUS AREA
NFPA 52 - NEC CLASS 1 DIVISION 2 (LOCATED INSIDE COMPRESSORS)
VENTED ABOVE DISPENSER
NFPA 52 - NEC CLASS 1 DIVISION 1
(LOCATED INSIDE DISPENSER ENCLOSURE)
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
FUTURE TIME FILL ZONE 3
ADDRESS:
B
E-10
FUTURE TIME FILL ZONE 3
C DE-FUEL PANEL AREA
E-8
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
A
E-10
TIME FILL ZONE 2
C COGGINS
2015-01-21
TIME FILL ZONE 1
B
E-10
J BARBER
B
E-10
B
E-10
PROJECT NAME:
C
E-10
FUTURE TIME FILL ZONE 4
B
E-10
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
HAZARDOUS
AREA
SHEET:
E-9
5
5'-0"
VENT STACK DISCHARGE
2
1.
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS PER NEC. 501.
2.
ALL UNDERGROUND CONDUITS SHALL HAVE SEAL OFFS AS THE FIRST JOINT
ABOVE GROUND IN HAZARDOUS AREAS.
3.
ALL CONDUITS ON EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL
HAVE SEAL OFFS ON FIRST CONDUIT INTO OR OUT OF THE FIXTURE OF
ENCLOSURE.
4.
FORM 5 LB FITTINGS ALLOWED TO BE USED IN C1D2 AREAS WHERE IT IS USED
AS A PULL BOX FOR WIRE. SEAL OFFS ARE REQUIRED AT STUB UP AREAS AND
BEFORE ENTERING WIRE TERMINATION DEVICE.
5.
HAZARDOUS AREAS SHOWN PER NFPA 52-2013 TABLE 7.4.2.9 ELECTRICAL
INSTALLATIONS.
6.
INSIDE COMPRESSOR ENCLOSURES DEFINED AS CLASS 1 DIVISION 2 PER
NFPA 52-2013.
5'-0"
15'-0"
2
GENERAL SHEET NOTES
5'-0"
1
10'-0"
MIN.
5
5'-0"
COMPRESSED NATURAL GAS (CNG) DISPENSER
2
ENGINEER STAMP:
-0
5'
"
COMPRESSED NATURAL GAS (CNG) VENT STACK
HAZARDOUS LOCATION AROUND FUEL DISPENSERS (TYPICAL)
VENT STACK DISCHARGE
2
1
R5
R15'-0"
'-0
"
SHEET KEY NOTES
HAZARDOUS LOCATION AROUND VENT STACK (TYPICAL)
1
2
3
4
5
NEC CLASS 1 DIVISION 1 HAZARDOUS AREA
NEC CLASS 1 DIVISION 2 HAZARDOUS AREA
NFPA 52 - NEC CLASS 1 DIVISION 2 (LOCATED INSIDE COMPRESSORS)
VENTED ABOVE DISPENSER
NFPA 52 - NEC CLASS 1 DIVISION 1
(LOCATED INSIDE DISPENSER ENCLOSURE)
REVISIONS:
HAZARD ZONE DIRECTLY AROUND DISPENSER
REV
NO.
DESCRIPTION
REV
DATE
HAZARD ZONE AT DISPENSER VENT
5
2
ADDRESS:
2 4
14207 DEL MONTE BLVD
MONTEREY, CA 93933
2
CHECKS:
C COGGINS
2015-01-21
J BARBER
HAZARD ZONE DIRECTLY AROUND DISPENSER
1
4
PROJECT NAME:
HAZARD ZONE AT DISPENSER VENT
CA MARINA
MRWMD
CNG FUELING STATION
5
DRAWING NAME:
HAZARDOUS
AREA
2
2 4
SHEET:
B TIME FILL AREA
E-10
A FAST FILL AREA
E-10
C EQUIPMENT AREA
E-10
E-10
5
5'-0"
VENT STACK DISCHARGE
GENERAL SHEET NOTES
1.
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS PER NEC. 501.
2.
ALL UNDERGROUND CONDUITS SHALL HAVE SEAL OFFS AS THE FIRST JOINT
ABOVE GROUND IN HAZARDOUS AREAS.
3.
ALL CONDUITS ON EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL HAVE
SEAL OFFS ON FIRST CONDUIT INTO OR OUT OF THE FIXTURE OF ENCLOSURE.
4.
FORM 5 LB FITTINGS ALLOWED TO BE USED IN C1D2 AREAS WHERE IT IS USED
AS A PULL BOX FOR WIRE. SEAL OFFS ARE REQUIRED AT STUB UP AREAS AND
BEFORE ENTERING WIRE TERMINATION DEVICE.
5.
HAZARDOUS AREAS SHOWN PER NFPA 52-2013 TABLE 7.4.2.9 ELECTRICAL
INSTALLATIONS.
6.
INSIDE COMPRESSOR ENCLOSURES DEFINED AS CLASS 1 DIVISION 2 PER NFPA
52-2013.
5'-0"
15'-0"
2
2
5'-0"
ENGINEER STAMP:
1
10'-0"
MIN.
5
5'-0"
COMPRESSED NATURAL GAS (CNG) DISPENSER
2
5'
-0
"
COMPRESSED NATURAL GAS (CNG) VENT STACK
HAZARDOUS LOCATION AROUND FUEL DISPENSERS (TYPICAL)
VENT STACK DISCHARGE
2
R15'-0"
"
HAZARDOUS LOCATION AROUND VENT STACK (TYPICAL)
SHEET KEY NOTES
1
2
3
4
5
NEC CLASS 1 DIVISION 1 HAZARDOUS AREA
NEC CLASS 1 DIVISION 2 HAZARDOUS AREA
NFPA 52 - NEC CLASS 1 DIVISION 2 (LOCATED INSIDE COMPRESSORS)
VENTED ABOVE DISPENSER
NFPA 52 - NEC CLASS 1 DIVISION 1
(LOCATED INSIDE DISPENSER ENCLOSURE)
REVISIONS:
1
REV
NO.
DESCRIPTION
REV
DATE
1
2
2
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
1
1" SS TUBE VENT
MINIMUM 10' ABOVE GRADE
1
CHECKS:
VENT SUPPORT
C COGGINS
5'-3"
2015-01-21
J BARBER
2
2
8'-10"
R5
'-0
10'-0"
MIN.
1
5
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
HAZARDOUS
AREA
A SLOW FILL POST HAZARD ZONE
E-5
B DISPENSER HAZARD ZONE
E-11
SHEET:
E-11
ENGINEER STAMP:
EXISTING GROUNDING
STUBBED UP IN ELECTRICAL VAULT
FOR FUTURE TIME FILL BANK
NEW TIME FILL POST TO CONNECT
TO EXISTING GROUNDING TYP. FOR ALL POST
G
EXISTING
E-14
J
TYP. FOR ALL
E-14 TIME FILL POST
J TYP. FOR ALL
E-14 TIME FILL POST
G
EXISTING
E-14
J TYP. FOR ALL
E-14 TIME FILL POST
NEW FAST FILL DISPENSER TO CONNECT
TO EXISTING GROUNDING
G
EXISTING
E-14
N
E-14
NEW DE-FUEL PANEL TO CONNECT
TO EXISTING GROUNDING CABLE
EXISTING GROUNDING
EXISTING GROUNDING
J TYP. FOR ALL
E-14 TIME FILL POST
EXISTING GROUNDING
EXISTING GROUNDING
NEW TIME FILL POST TO CONNECT
TO EXISTING GROUNDING TYP. FOR ALL POST
EXISTING GROUNDING TO
CONNECT TO NEW GROUNDING
E
E-14
G
EXISTING
E-14
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
A
E-13 NEW GROUNDING AREA
E
E-14
GENERAL SHEET NOTES
1.
ALL COPPER BELOW GRADE 3/0 MINIMUM, CONTRACTOR MAY USE LARGER.
2.
ALL COPPER ABOVE GRADE 2/0.
3.
ALL INTERSECTIONS TO BE BONDED.
4.
ALL 2/0 COPPER COMING ABOVE GRADE MUST BE LONG ENOUGH TO TIE TO
EACH SPECIFIC PIECE OF EQUIPMENT.
5.
EACH STRUCTURE TO BE GROUNDED ON TWO SIDES USING COMPRESSION
TWO HOLE SPADE.
6.
ALL FUTURE COPPER MUST BE COILED AND PLACED ON PAD MAKING SURE
SUFFICIENT LENGTHS REMAIN, TO CONNECT TO EQUIPMENT.
NEW FAST FILL DISPENSER TO CONNECT
TO EXISTING GROUNDING
EXISTING GROUNDING
STUBBED UP IN ELECTRICAL VAULT
FOR FUTURE TIME FILL BANK
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
7.
REFER TO GROUNDING DETAIL DRAWING E-10 FOR ASSEMBLY DETAILS.
J BARBER
8.
SAWCUT, PATCH AND REPAIR PARKING LOT SURFACE AS NECESSARY.
9.
THE CONTRACTOR SHALL BE REQUIRED TO COMPACT THE TRENCHES USING
SPECIFIC EQUIPMENT THAT CAN COMPACT THE NARROW TRENCHES AND
ACHIEVE A MINIMUM OF 95 PERCENT RELATIVE COMPACTION PER ASTM
D-1557. JETTING IS NOT ALLOWED. THE TRENCH BACKFILL SHALL BE PLACED IN
THIN LIFTS NOT TO EXCEED 4 INCHES IN THICKNESS IN THE NARROW TRENCHES.
THE MOISTURE CONTENT SHALL RANGE FROM OPTIMUM TO 3 PERCENT ABOVE
OPTIMUM MOISTURE CONTENT AT TIME PLACEMENT. THE BACKFILL MATERIAL
SHALL CONFORM WITH THE ENGINEERED FILL REQUIREMENTS IN THE PROJECT
GEOTECHNICAL ENGINEERING REPORT, THE REQUIREMENTS OF THE PIPE
MANUFACTURER, AND THE PROJECT SPECIFICATIONS, WHICHEVER IS MORE
STRINGENT.
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
10. GROUND GRID CONDUCTORS SHALL BE BURIED A MINIMUM OF 1'-6" BELOW
FINAL EARTH GRADE.
GROUNDING
LAYOUT
11. GROUND RODS SHOULD BE INSTALLED WITH TOPS 1'-0" MINIMUM BELOW
GRADE AND BONDED TO THE GROUND GRID CONDUCTORS.
12. REFER TO SPECIFICATIONS FOR INSTALLATION AND MATERIAL REQUIREMENTS.
13. ALL BENDS SHOWN SHALL BE 4" MINIMUM RADIUS.
14. CONTRACTOR TO RECORD CONDUCTOR LAYOUT ON AS BUILT DRAWINGS.
15. GROUNDING IN FUEL DISPENSER AREA RUN OVERHEAD IN CONDUIT FROM FUEL
BUILDING PULL BOX TO FUEL DISPENSERS.
SHEET:
E-12
ZO
NE
S
ENGINEER STAMP:
M
E
FI
LL
STUB UP FOR EXISTING GROUNDING
UN
DI
N
G
TO
TI
R
E-14
O
E-14
O
E-14
EX
IS
T
IN
G
GR
O
P
E-14
H
E-14
A
E-14
C
E-14
I
E-14
EXISTING GROUNDING TO FAST FILL DISPENSERS
C
E-14
Q
E-14
L
E-14
B
E-14
G
E-14
B
E-14
F
E-14
C
E-14
A
E-14
G
E-14
H
E-14
P
E-14
REVISIONS:
F
E-14
O
E-14
H
E-14
GENERAL SHEET NOTES
1.
ALL COPPER BELOW GRADE 2/0 MINIMUM, CONTRACTOR MAY USE LARGER.
2.
ALL COPPER ABOVE GRADE 2/0.
3.
ALL INTERSECTIONS TO BE BONDED.
4.
ALL 2/0 COPPER COMING ABOVE GRADE MUST BE LONG ENOUGH TO TIE TO
EACH SPECIFIC PIECE OF EQUIPMENT.
5.
EACH STRUCTURE TO BE GROUNDED ON TWO SIDES USING COMPRESSION
TWO HOLE SPADE.
6.
REFER TO GROUNDING DETAIL DRAWING E-10 FOR ASSEMBLY DETAILS.
8.
SAWCUT, PATCH AND REPAIR PARKING LOT SURFACE AS NECESSARY.
9.
THE CONTRACTOR SHALL BE REQUIRED TO COMPACT THE TRENCHES USING
SPECIFIC EQUIPMENT THAT CAN COMPACT THE NARROW TRENCHES AND
ACHIEVE A MINIMUM OF 95 PERCENT RELATIVE COMPACTION PER ASTM
D-1557. JETTING IS NOT ALLOWED. THE TRENCH BACKFILL SHALL BE PLACED IN
THIN LIFTS NOT TO EXCEED 4 INCHES IN THICKNESS IN THE NARROW TRENCHES.
THE MOISTURE CONTENT SHALL RANGE FROM OPTIMUM TO 3 PERCENT ABOVE
OPTIMUM MOISTURE CONTENT AT TIME PLACEMENT. THE BACKFILL MATERIAL
SHALL CONFORM WITH THE ENGINEERED FILL REQUIREMENTS IN THE PROJECT
GEOTECHNICAL ENGINEERING REPORT, THE REQUIREMENTS OF THE PIPE
MANUFACTURER, AND THE PROJECT SPECIFICATIONS, WHICHEVER IS MORE
STRINGENT.
DESCRIPTION
REV
DATE
1
UPDATED CALLOUTS TO 'E-14'
04/15/15
F
E-14
A
E-14
F
E-14
ADDRESS:
F
E-14
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
A
E-14
ALL FUTURE COPPER MUST BE COILED AND PLACED ON PAD MAKING SURE
SUFFICIENT LENGTHS REMAIN, TO CONNECT TO EQUIPMENT.
7.
REV
NO.
C COGGINS
2015-01-21
J BARBER
H
E-14
F
E-14
PROJECT NAME:
G
E-14
CA MARINA
MRWMD
CNG FUELING STATION
F
E-14
F
E-14
DRAWING NAME:
10. GROUND GRID CONDUCTORS SHALL BE BURIED A MINIMUM OF 1'-6" BELOW
FINAL EARTH GRADE.
11. GROUND RODS SHOULD BE INSTALLED WITH TOPS 1'-0" MINIMUM BELOW
GRADE AND BONDED TO THE GROUND GRID CONDUCTORS.
12. REFER TO SPECIFICATIONS FOR INSTALLATION AND MATERIAL REQUIREMENTS.
GROUNDING
LAYOUT
F
E-14
O
E-14
SHEET:
13. ALL BENDS SHOWN SHALL BE 4" MINIMUM RADIUS.
14. CONTRACTOR TO RECORD CONDUCTOR LAYOUT ON AS BUILT DRAWINGS.
15. GROUNDING IN FUEL DISPENSER AREA RUN OVERHEAD IN CONDUIT FROM FUEL
BUILDING PULL BOX TO FUEL DISPENSERS.
0'
2'
4'
6'
8'
10'
E-13
ENGINEER STAMP:
STORAGE VESSELS
AIR
COMPRESSOR
TRAFFIC RATED HANDHOLD
MOUNTED FLUSH WITH GRADE
FELT PAD
EXISTING STUB UP
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
DE-FUEL PANEL
MCC CABINET
GROUND BUS INSIDE MCC
BACK PANEL
TRENCH
TO BE MOUNTED TO
BACK PANEL
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
VENT STACK
VALVE PANEL
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
GROUNDING
DETAILS
SHEET:
E-14
ENGINEER STAMP:
CA Marina MRWMD - MCC
VOLTS/PHASE/WIRE:
MAIN SIZE & TYPE:
LOCATION:
480 V, 3 PH 3 WIRE
1600 AMP GFI CB IN MCC
MCC
PANEL "HS1"
NOT AN ACTUAL PANEL. FOR LOAD TRACKING ONLY.
NOTES:
ACCESSORIES: IDENTIFICATION, GROUNDING BAR, INSULATED GROUND BAR
CKT
LOAD (kVA)
OCP
LTG
CO
PANEL / EQUIPMENT
PWR
LCL
AMP
POLE
1
400
3
66.5
-
-
-
66.5
66.5
-
-
-
66.5
66.5
3
400
3
66.5
-
-
-
66.5
66.5
-
-
-
66.5
66.5
5
400
3
66.5
-
-
-
66.5
-
-
-
66.5
400
3
66.5
-
-
-
66.5
-
-
-
66.5
PANEL SIZE & TYPE:
MAIN SIZE & TYPE:
LOCATION:
CABINET:
100 AMPERE BREAKER
100 AMPERE TERMINAL
MCC
NEMA 3R
SKID A COMPRESSOR
SKID B COMPRESSOR
SKID C COMPRESSOR
PHASE LOAD
kVA
A
66.5
75.1
66.5
66.5
B
74.2
72.3
77.6
78.2
78.2
77.6
77.6
66.5
(F) SKID D COMPRESSOR
66.5
kVA
77.6
66.5
66.5
PWR
AMP
POLE
NO
NO
AMP
POLE
LTG
CO
DESCRIPTION
LCL
PWR
7.8
0.5
1.0
7.2
50
3
2
1
20
3
3.9
SKID A COOLER
3.9
2.0
0.0
5.8
-
-
-
-
-
-
3.9
-
3.9
6.3
-
2.0
1.0
2.8
-
-
-
-
-
-
3.9
-
3.9
11.2
BREAKER HS1
0.0
0.0
11.2
100
3
4
3
15
3
0.3
SKID A PRELUBE
0.3
11.7
0.0
0.0
11.7
-
-
-
-
-
-
0.3
-
0.3
11.7
0.0
0.0
11.7
-
-
-
-
-
-
0.3
-
0.3
11.1
60
3
6
5
15
3
0.3
SKID A HEATER
0.3
11.1
-
-
-
-
-
-
0.3
-
0.3
11.1
-
-
11.1
SPACE
0.0
-
-
-
-
0.3
-
0.3
8
7
20
3
3.9
SKID B COOLER
3.9
-
-
-
-
3.9
-
3.9
-
-
-
3.9
-
3.9
CONNECTED kVA PER PHASE
297
296
295
CONNECTED TOTAL kVA
888
9
15
3
0.3
SKID B PRELUBE
0.3
CONNECTED AMPS PER PHASE
1072
1070
1063
CONNECTED AVERAGE AMPS PER PHASE
1069
-
-
-
0.3
-
0.3
TOTALS:
-
(F) = FUTURE
-
-
-
0.3
-
0.3
LIGHTING 4.5kVA @125% =
5.6 kVA
ALL OTHER LOADS @100% =
881.3 kVA
DIVERSIFIED TOTAL kVA =
939
11
15
3
0.3
SKID B HEATER
0.3
RECEPTACLES 2kVA @100% =
2.0 kVA
25% OF LARGEST MOTOR =
49.9 kVA
AVERAGE AMPS PER PHASE =
1129
-
-
-
0.3
-
0.3
REMAINDER 0kVA @ 50% =
0.0 kVA
-
-
-
0.3
-
0.3
13
15
3
2.1
AIR COMPRESSOR
2.1
-
-
-
2.1
-
2.1
-
-
-
2.1
-
2.1
NEC DIVERSIFIED LOAD CALCULATIONS
LOAD (kVA)
OCP
PANEL SIZE & TYPE:
MAIN SIZE & TYPE:
LOCATION:
CABINET:
100 AMP PANEL
50 AMP BREAKER
MCC
NEMA 3R
NO
AMP
POLE
1
20
1
LTG
CO
DESCRIPTION
LCL
PWR
1.2
PHASE LOAD
kVA
A
MCP SPARE
1.2
2.4
3
20
1
1.5
EQUIPMENT AREA LIGHTS
1.9
5
20
1
1.0
ELECTRICAL ROOM LIGHTS
1.3
7
20
1
0.5
SPARE
0.5
9
20
1
0.5
SPARE
0.5
11
20
1
0.5
SPARE
0.5
13
SPACE
0.0
15
SPACE
0.0
17
SPACE
0.0
19
SPACE
0.0
21
SPACE
0.0
23
SPACE
0.0
TOTALS:
B
NOTES:
2.0
1.8
1.8
1.0
0.0
0.0
0.0
0.0
0.0
0.0
0.6
0.7
1.2
1.2
7.8
7.8
7.8
0.6
0.6
0.6
0.7
0.7
0.7
2.1
2.1
2.1
CKT
AMP
POLE
NO
3.9
SKID C COOLER
3.9
20
3
2
3.9
-
3.9
-
-
-
3.9
-
3.9
-
-
-
0.3
SKID C PRELUBE
0.3
15
3
4
0.3
-
0.3
-
-
-
0.3
-
0.3
-
-
-
0.3
SKID C HEATER
0.3
15
3
6
0.9
-
0.9
-
-
-
0.9
-
0.9
-
-
-
3.9
(F) SKID D COOLER
3.9
20
-
8
3.9
-
3.9
-
-
-
3.9
-
3.9
-
-
-
0.3
(F) SKID D PRELUBE
0.3
15
-
10
0.3
-
0.3
-
-
-
0.3
-
0.3
-
-
-
0.3
(F) SKID D HEATER
0.3
15
-
12
0.3
-
0.3
-
-
-
0.3
-
0.3
-
-
0.0
SPACE
14
0.0
-
-
0.0
-
-
-
20.7
CONNECTED TOTAL kVA
61.7
CONNECTED AMPS PER PHASE
73.0
74.9
74.9
CONNECTED AVERAGE AMPS PER PHASE
74.3
0 kVA
ALL OTHER LOADS @100% =
61.7 kVA
DIVERSIFIED TOTAL kVA =
64.6
RECEPTACLES 0kVA @100% =
0 kVA
25% OF LARGEST MOTOR =
2.9 kVA
AVERAGE AMPS PER PHASE =
77.7
REMAINDER 0kVA @ 50% =
0 kVA
VOLTS/PHASE/WIRE:
LTG
CO
MASTER CONTROL (MCP)
OCP
CKT
CKT
LOAD (kVA)
OCP
AMP
POLE
NO
NO
AMP
POLE
1.2
20
1
2
1
15
1
PANEL SIZE & TYPE:
MAIN SIZE & TYPE:
LOCATION:
CABINET:
NOTES:
100 AMP DIST BLOCK
60 AMP BREAKER
MCC
NEMA 3R
ON SHUNT TRIP
1.8
20
1
4
3
15
1
20
1
6
5
15
1
20
2
8
7
15
1
-
10
9
15
1
12
11
15
1
LTG
CO
DESCRIPTION
LCL
PWR
A
1.6
1.2
MCC PLC
1.2
0.4
SKID A CONTROL
0.4
SKID A LIGHTING
0.6
0.4
SKID B CONTROL
0.4
SKID B LIGHTING
0.6
0.4
SKID C CONTROL
0.4
SKID C LIGHTING
0.6
0.4
FUTURE SKID D CONTROL
0.4
FUTURE SKID D LIGHTING
0.6
AIR DRYER
1.0
UTILITY ROOM OUTLETS
1.3
208V OULET FOR HVAC
1.3
1.3
-
1.3
-
0.5
SPARE
0.5
20
0.0
SPACE
14
13
15
1
0.0
SPACE
16
15
15
1
0.0
SPACE
18
17
15
1
0.0
SPACE
20
19
SPACE
0.0
0.0
SPACE
22
21
SPACE
0.0
0.0
SPACE
24
23
SPACE
0.0
CONNECTED kVA PER PHASE
4.2
5.1
3.0
CONNECTED TOTAL kVA
12
35.0
42.1
25.0
CONNECTED AVERAGE AMPS PER PHASE
34
0.5
0.5
0.5
0.5
TOTALS:
(S) = SHUNT TRIP WITH SWITCHED NEUTRAL
PHASE LOAD
kVA
1.8
1.0
REVISIONS:
REV
NO.
B
LCL
C
0.8
1.0
1.4
1.0
0.9
1.0
0.9
1.0
0.5
0.0
0.0
LOAD (kVA)
DESCRIPTION
kVA
LTG
CO
OCP
AMP
POLE
NO
2
0.4
VALVE PANEL PLC
0.4
15
1
0.5
DISPENSER 1 (S)
0.5
15
1
4
0.5
DISPENSER 2 (S)
0.5
15
1
6
1.0
QUAD OUTLETS
15
1
8
0.5
SPARE
0.5
15
1
10
0.5
SPARE
0.5
15
1
12
0.5
SPARE
0.5
14
0.5
SPARE
0.5
16
0.5
SPARE
0.5
18
0.5
SPARE
0.5
20
0.0
SPACE
22
0.0
SPACE
24
1.0
CONNECTED kVA PER PHASE
4.5
2.7
2.8
CONNECTED TOTAL kVA
10
CONNECTED AMPS PER PHASE
37.2
22.5
23.7
CONNECTED AVERAGE AMPS PER PHASE
28
ADDRESS:
(S) = SWITCHED NEUTRAL C/B
NEC DIVERSIFIED LOAD CALCULATIONS
LIGHTING 3kVA @125% =
3.1 kVA
ALL OTHER LOADS @100% =
8.8 kVA
DIVERSIFIED TOTAL kVA =
12.9
LIGHTING 2kVA @125% =
2.5 kVA
ALL OTHER LOADS @100% =
5.4 kVA
DIVERSIFIED TOTAL kVA =
8.9
1.0 kVA
25% OF LARGEST MOTOR =
0.0 kVA
AVERAGE AMPS PER PHASE =
35.7
RECEPTACLES 1kVA @100% =
1.0 kVA
25% OF LARGEST MOTOR =
0.0 kVA
AVERAGE AMPS PER PHASE =
24.7
REMAINDER 0kVA @ 50% =
0.0 kVA
REMAINDER 0kVA @ 50% =
0.0 kVA
DAT
FAULT CURRENT
MCC
65,000 SCA
L1
10,000 SCA
LS2
10,000 SCA
HS1
65,000 SCA
SKID MOUNTED MCC
65,000 SCA
L3
10,000 SCA
REV
DATE
CKT
PWR
RECEPTACLES 1kVA @100% =
FAULT CURRENT TABLE
DESCRIPTION
PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR, INSULATED GROUND BAR, SUBFEED LUGS
PWR
CONNECTED AMPS PER PHASE
NEC DIVERSIFIED LOAD CALCULATIONS
0.6
OCP
PWR
(F) = FUTURE
120/208 V, 3 PH, 4 WIRE
LOAD (kVA)
DESCRIPTION
kVA
1.2
3.3
0.6
CO
LIGHTING 0kVA @125% =
ACCESSORIES:
LCL
C
7.8
LTG
PANEL "LS2"
PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR, INSULATED GROUND BAR, SUBFEED LUGS
ACCESSORIES:
7.8
LOAD (kVA)
DESCRIPTION
kVA
20.7
PANEL "L1"
120/208 V, 3 PH, 4 WIRE
LCL
C
20.2
NEC DIVERSIFIED LOAD CALCULATIONS
VOLTS/PHASE/WIRE:
B
CONNECTED kVA PER PHASE
TOTALS:
CKT
A
-
GAS DRYER
PHASE LOAD
kVA
120/208 TRANSFORMER
0.0
66.5
OCP
8.3
0.0
66.5
CKT
CO
11.1
66.5
OCP
LOAD (kVA)
CKT
LTG
8.8
11.1
66.5
LOAD (kVA)
PANEL / EQUIPMENT
LCL
C
NOTES:
PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR, INSULATED GROUND BAR, SUBFEED LUGS
ACCESSORIES:
NO
7
VOLTS/PHASE/WIRE:
480 V, 3 PH, 3 WIRE
14207 DEL MONTE BLVD
MONTEREY, CA 93933
CHECKS:
C COGGINS
2015-01-21
J BARBER
PROJECT NAME:
PROVIDE FULLY RATED CIRCUIT BREAKERS IN PANELBOARDS FOR THE FAULT CURRENT
SHOWN. SERIES RATINGS WITH NEXT LEVEL UPSTREAM OVERCURRENT PROTECTIVE
DEVICES ARE PERMITTED SUBJECT TO FACTORY UL DOCUMENTATION OF SERIES RATING
SUBMITTED TO ENGINEER. IF DEVICE OR EQUIPMENT FAULT CURRENT RATING IS NOT
SHOWN, ASSUME 100,000 AIC. LS2 IS SERIES RATED WITH L1.
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
PANEL
SCHEDULE
SHEET:
E-15
ENGINEER STAMP:
(2'-0")
6"
6'-0"
5"
5"
2'-1 "
1
2
3'-0"
1
2
1
4
PROVIDED BY TRILLIUM
CONTRACTOR TO INSTALL
PROVIDED BY TRILLIUM
CONTRACTOR TO INSTALL
1'-0"
PROVIDED BY TRILLIUM
CONTRACTOR TO INSTALL
C20
PROVIDED BY TRILLIUM
CONTRACTOR TO INSTALL
MASTER
CONTROL
PANEL
(MCP)
C24
30 KVA
TRANSFORMER
MAIN
BREAKER
C25
MOTOR CONTROL
CENTER AND
DISTRIBUTION
(MCC)
3
4
4'-3 "
72" X 72" X 24"
REVISIONS:
REV
NO.
2
REV
DATE
2
7'-0" X 12" X 12" GUTTER
1'-0"
C21
C22
1'-0"
1
DESCRIPTION
ADDRESS:
C46
C39
C35
C31
C27
C42
C38
C34
C30
C26
C19
C19
C19
C19
14207 DEL MONTE BLVD
MONTEREY, CA 93933
SEAL OFF'S ON
ALL CONDUITS
BOTTOM VIEW
SEAL OFF'S ON
ALL CONDUITS
C COGGINS
C59
C57
C55
C45
C43
C37
C29
C11
C09
C07
C05
C02
C52
C51
C49
C47
C36
C28
C01
CHECKS:
2015-01-21
J BARBER
GENERAL SHEET NOTES
1.
TRILLIUM WILL SUPPLY THE FOLLOWING EQUIPMENT, CONTRACTOR TO INSTALL:
REMOTE MAIN BREAKER, MOTOR CONTROL CENTER, 30 kVA TRANSFORMER,
MASTER CONTROL PANEL, NETWORK COMMUNICATION BOX.
ALL UNDERGROUND CONDUITS SHALL HAVE SEAL OFFS AS THE FIRST JOINT
ABOVE GROUND IN HAZERDOUS AREAS.
ALL CONDUITS ON EXPLOSION PROOF FIXTURES AND ENCLOSURES SHALL
HAVE SEAL OFFS ON FIRST CONDUIT INTO OR OUT OF THE FIXTURE OF
ENCLOSURE.
1.
CONTRACTOR TO INSTALL GUTTER FOR MCP & MCC CONDUIT WIRE ROUTING.
SEE SHEET E-7 FOR CONDUIT AND CONDUCTOR SCHEDULE.
2.
CONTRACTOR TO INSTALL TWO (2) 2" CONDUITS BETWEEN ELECTRICAL GUTTER
AND MASTER CONTROL PANEL. INSTALL CONDUITS SUCH THAT KEYBOARD CAN
FULLY RETRACT.
ALL WIRE PULLED INTO MASTER PANEL PULL BOX WILL BE LABELED ON BOTH
ENDS WITH CLEAR TO READ NUMBERS. CONTRACTOR TO SUPPLY REVISED
CONDUIT SCHEDULE LISTING WIRE NUMBERS LOCATED IN WHICH CONDUITS.
7.
CONTRACTOR TO SUPPLY TEN FOOT MINIMUM EXTRA WIRE IN MASTER PANEL
PULL BOX TO ALLOW FOR WIRE TO BE PULLED INTO RESPECTIVE PANELS. WIRE
TO BE COILED NEATLY AND TIED PER CONDUIT.
8.
C58
C56
C54
C44
C41
CONTROL
CONTROL &
COMM
ELEVATION
6.
3.
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
ALL CONDUITS SHALL HAVE SEAL OFFS WHERE ENTERING OR LEAVING
CLASSIFIED LOCATIONS PER NEC. 501.
CONTRACTOR TO PROVIDE AND INSTALL GUTTER BOX (7'-0" X 1'-0" X 1'-0").
C33
C16
C10
C08
C06
C03
C53
C52
C50
C48
C40
120V POWER
5.
2.
4.
C32
C04
PROJECT NAME:
SHEET KEY-NOTES
SHEET:
E-16
ENGINEER STAMP:
CA Marina MCC - BILL OF MATERIALS
28
24
24
1
27
17
18
16
11
24V
24
#
QUANTITY
MANUFACTURER
1
3
ILSCO
1600A DISTRIBUTION BLOCK
2
4
EATON
400A MOTOR BREAKER
3
4
EATON
COMPRESSOR MOTOR SOFT START - 200 hp
4
1
EATON
60A DRYER CONTACTOR
5
1
EATON
60A "LS2" CONTACTOR
6
8
EATON
COMBINATION STARTERS 1 - 1.6 FLA W\ SIDE MOUNT TRIP INDICATOR
7
1
EATON
COMBINATION STARTERS 10 - 16 FLA W\ SIDE MOUNT TRIP INDICATOR
8
4
EATON
COMBINATION STARTERS 6.3 - 10 FLA W\ SIDE MOUNT TRIP INDICATOR
9
1
EATON
30 kVA XFMR
10
3
ILSCO
POWER DIST. BLOCK
11
1
EATON
24Vdc, 10A POWER SUPPLY
12
24
EATON
L1 120V 20A BREAKERS
13
24
EATON
LS2 120V 15A BREAKERS
14
1
EATON
100A "HS1" BREAKER
15
1
EATON
60A DRYER BREAKER
16
1
EATON
50A XFMR BREAKER
17
1
EATON
60A "LS2" MAIN BREAKER
18
1
EATON
50A "L1" MAIN BREAKER
DESCRIPTION
9
10A
10
Adjust
DC OK
L1
L2
L3
3 Phase 400-500V~ 0.8A 50-60Hz
1
21 22
24
4
19
5
20
25
1
23
MAIN
BREAKER
GROUND
24
12
2
2
2
13
2
24
15
23
NEUTRAL
26
23
GROUND
14
3
3
3
3
24
6
6
7
6
6
7
6
7
6
6
6
7
8
REVISIONS:
REV
NO.
19
3
DAYTON
RELAY BASE
20
3
DAYTON
RELAY
21
2
N/A
22
12
PHOENIX CONTACT
23
3
N/A
TERMINAL BAR
24
1
N/A
2.25" PANDUIT
25
30
C3 CONTROLS
26
1
EATON
20A LIGHTING CONTACTOR
27
1
EATON
1600A SERVICE ENTRANCE BREAKER W/ CABINET
28
1
HOFFMAN
DESCRIPTION
REV
DATE
DIN RAIL
DIN RAIL WIRE CLAMP
TERMINAL BLOCK
72" X 72" X 24" ENCLOSURE W/LEGS
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
HOLES FOR CONDUIT
SEE E-7 FOR SIZE OF
RIGID CONDUIT COMPRESSION
FITTING (TYP)
CAP ANY UNUSED HOLES
BOTTOM VIEW
CHECKS:
C COGGINS
2015-01-21
(6'-8 1/2")
J BARBER
3 1/2"
PROJECT NAME:
10"
3 1/2" TYP
(6'-6 3/4")
8"
8"
8"
8"
8"
4"
4"
4"
4"
4"
1'-0"
1'-0"
8"
4"
C46
C39
C35
C31
C27
C42
C38
C34
C30
C26
1'-2"
3 1/2" TYP
CA MARINA
MRWMD
CNG FUELING STATION
5 1/4"
DRAWING NAME:
7'-0"
MCC PANEL
HOLES FOR CONDUIT
SEE E-7 FOR SIZE
SHEET:
E-17
ENGINEER STAMP:
MAIN MOTOR
PRE-LUBE / HEATER
COOLER MOTOR
PANEL
COMMUNICATION
1'-4"
6'-10 1/2"
1'-10"
1'-11 3/4"
3"
PANEL POWER
PRE-LUBE / HEATER
COOLER MOTOR
PANEL COMMUNICATION
MAIN MOTOR
REVISIONS:
REV
NO.
B
E-18
1'-10"
1'-4"
3"
DESCRIPTION
REV
DATE
B GAS COMPRESSOR PIPE DETAIL
E-18
9"
1'-7"
6'-10 1/2"
1'-7"
PANEL POWER
PANEL
COMMUNICATION
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
PRE-LUBE / HEATER
COOLER MOTOR
MAIN MOTOR
(3) THREE CONDUITS ARE
INLINE. ONLY ONE SHOWN
CONTROL (C1)
POWER (C2)
PRELUB COOLER& HEATER (C7)
MAIN MOTOR (C9)
CHECKS:
C COGGINS
2015-01-21
1'-7"
A GAS COMPRESSOR PIPE DETAIL
E-18
C COMPRESSOR PIPE DETAIL
E-18
1'-7"
1'-11 3/4"
10 1/2"
10 1/2"
J BARBER
1'-11 3/4"
C
E-18
9"
10 1/2"
1'-7"
1'-7"
8"
PANEL POWER
PROJECT NAME:
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
COMPRESSOR
CONDUIT PLAN
AND ELEVATION
SHEET:
E-18
ENGINEER STAMP:
SEAL OFF
REVISIONS:
REV
NO.
DESCRIPTION
REV
DATE
ADDRESS:
14207 DEL MONTE BLVD
MONTEREY, CA 93933
6"
CHECKS:
SEAL OFF
C COGGINS
2'-5"
2'-5"
2015-01-21
2'-8"
J BARBER
2'-8"
PROJECT NAME:
DRYER POWER
SEAL OFF
DRYER POWER
DRYER COMMUNICATION
DRYER COMMUNICATION
A GAS DRYER CONDUIT DETAIL
E-19 PLAN VIEW
CA MARINA
MRWMD
CNG FUELING STATION
DRAWING NAME:
B GAS DRYER CONDUIT DETAIL
E-19 ELEVATION VIEW
DRYER CONDUIT
PLAN AND ELEVATION
SHEET:
E-19