D1.0 DEMOLITION PLAN A1.0 FLOOR AND CLG. PLAN & NOTES A1.1 FINISH SCHEDULE AND DETAILS A2.0 EQUIPMENT PLAN & SCHEDULE A3.0 STOREFRONT ELEVATIONS A3.1 KITCHEN ELEVATIONS A4.0 DETAILS AS1.0 ARCHITECTURAL SPECIFICATIONS E1.0 ELECTRICAL POWER AND LIGHTING PLANS E2.0 DETAILS, PANEL SCHEDULES AND RISER DIAG. E3.0 ELECTRICAL SPECIFICATIONS PHILADELPHIA MILLS H1.0 HOOD DRAWING H2.0 HOOD DRAWING SPACE 852A ~ 818 SQ. FT. H3.0 HOOD DRAWING 1455 FRANKLIN MILLS CIR, PHILADELPHIA, PA, 19154 M1.0 MECHANICAL PLAN, DETAILS, & NOTES P1.0 PLUMBING WATER & WASTE PLANS P2.0 GAS PLANS, WATER AND WASTE ISOMETRICS GENERAL REQUIREMENTS 1. PERMITS AND FEES 2. TEMPORARY UTILITIES 4. TEMPORARY ENCLOSURE SPACE WORK 1. 2. DEMOLITION SAW CUT SLAB/CORE DRILL AS REQUIRED TO INSTALL UTILITIES, CORE DRILL ONLY CONCRETE SLAB CORE DRILLING 1. 2. 3. 4. 5. SAND PAD VAPOR BARRIER REINFORCING FABRIC CONCRETE SLAB POURED CONCRETE AS REQUIRED TO INSTALL UTILITIES CARPENTRY 1. 2. METAL STUDS A. DEMISING WALLS B. INTERIOR PARTITIONS C. FURRING D. SALES COUNTER E. SALES LOW WALL ROOF FRAMING FOR MECH. UNITS SEE PLANS KEY PLAN DOORS 1. 2. 3. SEE SCHEDULE SEE SCHEDULE SALES/KITCHEN DOOR(S) & FRAME SERVICE DOOR TOILET ROOM DOOR SYMBOLS LEGEND: FINISHES 1. 2. 3. 4. 5. 6. WALLS A. 5/8" TYPE "X" GYP. BD. B. 5/8" MOISTURE RESISTANT GYP. BD. C. FINISHES D. COUNTER TOP MATERIAL SEE PLAN AND STANDARD MATERIAL SCHEDULE G.C. TO SUPPLY SAMPLES TO OWNER FOR APPROVAL TAPING AND SPACKLING FLOORS A. WATER PROOF MEMBRANE B. QUARRY TILE C. DINING FLOORING FINISHES A. PAINT FOR ALL WET AREAS OF SLAB + FLOOD TEST TO BE WITNESSED BY LL. T.C. PLAN DETAIL INDICATION ELEVATION INDICATION DOOR IDENTIFICATION B. TILE C. TRIM BASE A. COVED QUARRY TILE B. COVED VINYL CEILING A. GYP. BD. B. 2'X4' LAY-IN TILE SEE REFLECTED CEILING SEE REFLECTED CEILING MALL PROVIDED PUBLIC RESTROOMS WITH-IN 300' FROM TENANT SPACE PLUMBING 1. 2. 3. 4. 5. 6. SECTION CUT INDICATION CHARLEY'S PHILLY STEAKS SPC# 852A 818 SQ. FT. WATER PIPING UNDERSLAB ROUGH-IN FOR WASTE FINAL CONNECTIONS & VENTS GAS PIPING AND ACCESSORIES FINAL GAS CONNECTIONS TO EQUIP. TOILET RM. FIXTURES/ACCESSORIES SEE SEE SEE SEE SEE PLUMBING PLUMBING PLUMBING PLUMBING PLUMBING DWG. DWG. DWG. DWG. DWG. 1. 2. 3. 4. 5. KITCHEN/SALES STOREFRONT SIGNS FIRE EXTINGUISHER INTERCOM SYSTEM SEATING SEE EQUIPMENT SCHEDULE FOR MORE INFO. COORD. PERMITS & INSTALLATION W/ SIGN VENDOR LOCATE PER FIRE MARSHALL 6. 7. MENU BOARD SALES AREA S/S COUNTERS COORDINATE WITH VENDOR (VERIFY W/ TENANT) COORDINATE WITH TENANT. SEE ELECTRICAL DRAWINGS SEE ELECTRICAL DRAWINGS SEE ELECTRICAL DRAWINGS SEE ELECTRICAL DRAWINGS HVAC SYSTEM A. HVAC UNIT B. DUCTWORK 2. 3. 4. 5. 6. 7. 8. 9. C. DIFFUSERS ROOF PENETRATIONS SPRINKLER SYSTEM EXHAUST HOODS & FANS EXHAUST HOOD DUCT WORK EXHAUST HOOD ANSUL SYSTEM ROOF PROTECTION ACCESSORIES EXH. HOOD MUA SUPPLY SYSTEM FIRE ALARM AND SMOKE CONTROL SYS. INSTALL/ MODIFY EXISTING SYSTEM PER L.L. REQUIREMENTS SEE HOOD DWG. COORD. W/ LL'S ROOFER FOR ROOFING WORK @ TEN.'S EXPENSE. SEE HOOD DWG. INSTALL SPEAKER/STROBE SYSTEM PER L.L. REQUIREMENTS PROJECT INFORMATION: LANDLORD: SIMON PROPERTY GROUP, INC. 225 WEST WASHINGTON STREET INDIANAPOLIS, IN 46204 TEL. 317-636-1600 PROJECT COORDINATOR MOSAD ELEWA 3386 CLARINE WAY WEST DUNEDIN, FL 34698 TEL: 813-245-6554 FAX: 801-218-6554 ARCHITECT DAVID HIATT, ARCHITECT 4410 W MELROSE AVE. TAMPA, FL 33629 TEL: (813) 333-2717 FAX: (813) 289-3332 OWNER / TENANT BUILDING DEPT. HEALTH DEPT. CPS OF PHILLY, LLC 10305 NW 41ST ST SUITE 201 DORAL, FL 33178 CITY OF PHILADELPHIA DEPARTMENT OF LICENSES & INSPECTIONS 1401 JOHN F. KENNEDY BLVD PUBLIC SERVICES CONCOURSE PHILADELPHIA, PA 19102-1687 TEL.: (215) 686-1776 PHILADELPHIA DEPARTMENT OF PUBLIC HEALTH OFFICE OF FOOD PROTECTION 321 UNIVERSITY AVE., 2ND FLOOR PHILADELPHIA, PA 19104 TEL.: (215) 685-7495 TEL: (305) 406-1583 ABOVE FINISH FLOOR ACT. ADJ. A.C. ACOUSTICAL ADJUSTABLE AIR CONDITION/CONDITIONED/ ALT. ALUM. A.B. & APPROX. @ AWN. MECHANICAL 1. A.F.F. B.C. B.P. BM. BLK. B.S. B.W. BTM. BRK. BLDG. CAB. CPT. C.I. C.B. CLG. CEM. CTR. C.T. CHBD. C.O. CLO. COL. COM. CONC. CONST. C.M.U. CONT. CONTR. C.J. C.TOP DEMO. DEPART. DTL. DIA. DIM. DR. DN. DWG. EA. E. ELEC. E.C. E.W.C. ELEV. ENCL. EQ. EQUIP. EXIST. E.J. EXP. EXT. CONDITIONER/CONDITIONING ALTERNATE ALUMINUM ANCHOR BOLT AND APPROXIMATELY AT AWNING BASE CABINET BASE PLATE BEAM BLOCK BOTH SIDES BOTH WAYS BOTTOM BRICK BUILDING CABINET CARPET CAST IRON CATCH BASIN CEILING CEMENT CENTER CERAMIC TILE CHALKBOARD CLEAN OUT CLOSET COLUMN COMBINATION CONCRETE CONSTRUCTION CONCRETE MASONRY UNIT CONTINUOUS CONTRACTOR CONTROL JOINT COUNTER TOP DEMOLITION DEPARTMENT DETAIL DIAMETER DIMENSION DOOR DOWN DRAWING EACH EAST ELECTRICAL ELECTRICAL CONTRACTOR ELECTRIC WATER COOLER ELEVATION ENCLOSURE EQUAL EQUIPMENT EXISTING EXPANSION JOINT EXPOSED EXTERIOR F.O.S. FT. F.N.D. F.N.V. FIN. FIN. OPNG. F.E. F.E.C.R. F.H. F.R.P. F.R.T. FL. F.D. F.P. FTG. F.M. GALV. GA. G.C. GL. G.B. G.W.B. GYP. HC. HDW. HT. H. H.C. H.M. HORIZ. IN. INCL. I.D. INSUL. JT. JST. LAM. L.L. LAV. L. MGR. M.H. MFR. MAS. M.O. MAT'L. MAX. MECH. MT. M.F. M.S. MIN. M. MISC. M.R. M.B.H. 1 CONSTRUCTION NOTES 1. TOILET ACCESSORIES A GENERAL NOTES 3). PLATE MTD. N. N.I.C. N.T.S. NO. NOTES WHICH APPLY TO SPECIFIC ITEMS ON DRAWINGS WHERE INDICATED. NOTES WHICH APPLY TO ALL DRAWINGS. 00'-0" ABOVE FIN. FLR. C C LEASE LINE ELEVATION SURFACE DESCRIPTION CENTERLINE DIAMETER CODE INDEX FACE OF STUD O.C. OPNG. FEET O.D. FEMININE NAPKIN DISPOSAL PR. FEMININE NAPKIN VENDOR P.T.D. FINISH FINISH OPENING P.T.H. FIRE EXTINGUISHER P.COL. FIRE EXTINGUISHER CABINET PLAS. RECESSED P.LAM. FIRE HYDRANT PLUMB. FIRE RETARDANT PANEL P.C. FIRE RETARDANT TREATED PLYWD. FLOOR P.T. FLOOR DRAIN Q.T. FLUSH PANEL R. FOOTING RECT. FRAMED MIRROR REINF. GALVANIZED REQ'D. GAUGE REV. GENERAL CONTRACTOR R.D. GLASS RM. GRAB BAR R.O. GYPSUM WALLBOARD S.C.O.F. GYPSUM SCH. HANDICAPPED SNT. HARDWARE SECT. HEIGHT SHT. HIGH SIM. HOLLOW CORE S.D. HOLLOW METAL S.H. HORIZONTAL S.C. INCH S. INCLUDE SPECS. INSIDE DIAMETER SQ. INSULATION JOINT SQ.FT. JOIST S.S. STD. LAMINATED STL. LANDLORD STR. LAVATORY S.M.S. LONG MANAGER SUSP. MANHOLE SYS. MANUFACTURER TKBD. MASONRY T.C. MASONRY OPENING T.P.H. MATERIAL T.& G. MAXIMUM T.B. MECHANICAL TYP. METAL METAL FRAME U.N.O. METAL STUD V.T.R. MINIMUM VERT. MIRROR V.T. MISCELLANEOUS MOISTURE RESISTANT MOP AND BROOM HOLDER MOUNTED NORTH NOT IN CONTRACT NOT TO SCALE NUMBER SHEET NUMBER A L.L. 1. CONDUIT INTO SPACE 2. METER 3. PANELS 4. TRANSFORMER AND GEAR 5. LIGHT FIXTURES AND LAMPS 6. TELEPHONE WIRING ELEVATION NUMBER MILWORK MOULDINGS PHILADELPHIA MILLS ABBREVIATIONS: DETAIL AREA DETAIL NUMBER SHEET NUMBER 0 A-0 P ELECTRICAL SHEET NUMBER 0 A-0 ELEVATION TARGET EQUIPMENT SECTION NUMBER 0 A-0 PHILADELPHIA, PA 19154 COVER SHEET 1455 FRANKLIN MILLS CIR, C1.0 SPACE 852A ~ 818 SQ. FT. REMARKS PHILADELPHIA MILLS DRAWING INDEX N/A TENANTS CONT TENANT LANDLORD TENANTS CONT INSTALLED TENANT ITEM: FURNISHED LANDLORD EXISTING RESPONSIBILITY SCHEDULE W.R. W.C. W.H. W.P. W. W/. W/O. WD. ON CENTER OPENING OUTSIDE DIAMETER PAIR PAPER TOWEL DISPENSER PAPER TOWEL HOLDER PIPE COLUMN PLASTER PLASTIC LAMINATE PLUMBING PLUMBING CONTRACTOR PLYWOOD PRESSURE TREATED QUARRY TILE RADIUS RECTANGULAR REINFORCEMENT REQUIRED REVISION ROOF DRAIN ROOM ROUGH OPENING SLIP COEFFICIENT SCHEDULE SEALANT SECTION SHEET SIMILAR SOAP DISPENSER SOAP HOLDER SOLID CORE SOUTH SPECIFICATIONS SQUARE SQUARE FEET STAINLESS STEEL STANDARD STEEL STRUCTURAL STRUCTURAL METAL STUD SUSPEND SYSTEM TACKBOARD TENANT CO-ORDINATOR TOILET PAPER HOLDER TONGUE AND GROOVE TOWEL BAR TYPICAL, UNLESS OTHERWISE NOTED UNLESS NOTED OTHERWISE VENT THROUGH ROOF VERTICAL VINYL TILE WASTE RECEPTACLE WATER CLOSET WATER HEATER WATER PROOF WEST / WIDE WITH WITHOUT WOOD BUILDING CODES: PHILADELPHIA CODE · THE PHILADELPHIA ADMINISTRATIVE CODE · PHILADELPHIA BUILDING CODE · PHILADELPHIA MECHANICAL CODE 2009 · PHILADELPHIA EXISTING BUILDING CODE · PHILADELPHIA ELECTRICAL CODE · PHILADELPHIA PERFORMANCE CODE · PHILADELPHIA ENERGY CONSERVATION CODE · PHILADELPHIA FIRE CODE · PHILADELPHIA FUEL GAS CODE · PHILADELPHIA ZONING CODE · PHILADELPHIA PLUMBING CODE INTERNATIONAL CODE COUNCIL · 2009 INTERNATIONAL BUILDING CODE · 2012 INTERNATIONAL BUILDING CODE (CHAPTER 11) · 2012 INTERNATIONAL BUILDING CODE (APPENDIX E) · 2009 ICC A117.1 · 2009 INTERNATIONAL MECHANICAL CODE · 2009 INTERNATIONAL EXISTING BUILDING CODE · 2009 INTERNATIONAL ENERGY CONSERVATION CODE · 2009 INTERNATIONAL FUEL GAS CODE · 2009 ICC PERFORMANCE CODE GENERAL NOTES TYPE OF CONSTRUCTION OCCUPANCY CLASS: TOTAL LEASED AREA: MAXIMUM ALLOWABLE AREA: OCCUPANT LOAD: IIB, FULLY SPRINKLED GROUP ' B ' 818 S.F. 818 S.F. 4 WORKERS AT ALL TIME REQUIRED EXIT WIDTH: PROVIDED EXIT WIDTH: 36" INCHES 36" INCHES U 465 UL DESIGN NUMBER FOR TENANT SEPARATION. LANDLORD NOTES 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 1. THESE DOCUMENTS REPRESENT THE SCOPE OF WORK TO BE TO PERFORMED BY THE GENERAL CONTRACTOR (U.N.O.) 2. CHECK DIMENSIONS AND CONDITIONS IN THE FIELD ALL DIMENSIONS AND CONDITIONS OF THIS JOB SHALL BE FIELD CHECKED BY GENERAL CONTRACTOR WHO WILL BE RESPONSIBLE FOR SAME. ANY DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO THE START OF CONSTRUCTION. COSTS DUE TO A FAILURE OF REPORTING THESE DISCREPANCIES WILL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. 3. ERRORS AND OMISSIONS ANY DISCREPANCIES OR OMISSIONS ON THESE DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE COMMENCEMENT OF CONSTRUCTION AND BID TO OWNER. FAILURE BY THE CONTRACTOR TO IDENTIFY DISCREPANCIES OR OMISSIONS WILL THEN BECOME THE RESPONSIBILITY OF THE CONTRACTOR. 4. COMPLY WITH DESIGN CRITERIA GENERAL CONTRACTOR TO FOLLOW AND COMPLY WITH LANDLORD'S TENANT DESIGN CRITERIA AND REQUIREMENTS FOR ALL EXHIBITS. ( IF APPLICABLE. ) 5. NOTES ALL NOTES ON ANY PORTION OF THESE DOCUMENTS APPLY TO ENTIRE DOCUMENT WHETHER OR NOT THEY ARE REPEATED IN OTHER AREAS. 6. WORK, MATERIALS AND CONSTRUCTION METHODS ALL WORK, MATERIALS AND CONSTRUCTION METHODS SHALL CONFORM WITH ALL GOVERNING AUTHORITIES HAVING JURISDICTION. 7. APPROVAL BY GOVERNING AUTHORITIES APPROVAL OF THESE DRAWINGS BY GOVERNING AUTHORITIES DOES NOT RELEASE THE CONTRACTOR FROM COMPLYING WITH ALL APPLICABLE CODES AND STANDARDS. 8. INSTALLATION BY GENERAL CONTRACTOR ALL MATERIALS AND EQUIPMENT ITEMS SUPPLIED BY THE OWNER/TENANT ARE TO BE INSTALLED BY GENERAL CONTRACTOR UNLESS INDICATED OTHERWISE. SPECIAL NOTES: 9. MATERIALS ALL MATERIALS SHALL BE NEW AND FIRST CLASS. ALL WORK AND EQUIPMENT ITEMS SHALL BE WARRANTIED BY THE CONTRACTOR FOR A MINIMUM OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE. EXCEPT FOR MANUFACTURE'S WARRANTY WHICH MAY BE LONGER. 10. COMBUSTIBLE MATERIALS NO COMBUSTIBLE MATERIALS ARE PERMITTED ABOVE CEILING. COVER SHEET 11. FIRE EXTINGUISHERS CAPACITY AND RATING AS REQUIRED BY N.F.P.A. PAMPHLET #10 AND LOCAL AUTHORITIES. LOCATE PER LOCAL AUTHORITIES AND N.F.P.A. 10. VERIFY LOCATION WITH FIRE DEPARTMENT 12. MISC. PRIOR TO INSTALLING SHELVING IN REFRIGERATOR, T.G.C. TO WASH DOWN (SPONGE) INTERIOR THREE (3) TIMES WITH A SOLUTION OF 50% VINEGAR AND 50%WATER. SET REFRIGERATOR TO OPERATE AT 34 - 38 F RANGE. 13. PERFORMANCE BOND AND PAYMENT BONDS ARE REQUIRED FOR THIS PROJECT. REFER TO SHEET AS-1. 14. SOME SPECIFIED ITEMS (SUCH AS FLUORESCENT FIXTURES IN SALES COUNTER, WALL STANDARDS, SHELVING BRACKETS, CERAMIC TILE, ETC.) MAY REQUIRE LONG DELIVERY 15. CONTRACTOR AND ALL SUB-CONTRACTORS SHALL VISIT JOB SITE PRIOR TO THE BID. TO REVIEW ACTUAL FIELD CONDITIONS THAT MAY AFFECT THE BID. CONTACT ARCHITECT WITH ANY FIELD CONDITION AFFECTING DRAWINGS BEFORE BID TO OWNER. IF NOT COMMUNICATED WITH THE ARCHITECT, THEN CONTRACTOR & SUB-CONTRACTOR WILL BECOME RESPONSIBLE FOR ALL COSTS INVOLVED. 16. COMPLY WITH ALL LANDLORD'S TENANT WORK RULES & INSURANCE REQUIREMENTS. C1.0 DEMOLITION NOTES 3 GENERAL CONTRACTOR SHALL COORDINATE WITH LANDLORD REP. AND REMOVE EXISTING DEMISING WALL AND INSTALL NEW DEMISING WALLS PER PLANS 4 GENERAL CONTRACTOR SHALL COORDINATE WITH LANDLORD REP. AND REMOVE EXISTING STOREFRONT SYSTEMS. TO NEW LEASE LINES 5 GENERAL CONTRACTOR SHALL REMOVE EXISTING CEILING THROUGH OUT THE LEASED AREA. 6 GENERAL CONTRACTOR SHALL REMOVE EXISTING HVAC UNITS AND DUCTWORK. INSTALL NEW PER MECHANICAL DRAWING. 7 GENERAL CONTRACTOR SHALL REMOVE EXISTING LIGHT THROUGH OUT LEASE AREA, INSTALL NEW FIXTURES PER REFLECTED CEILING PLAN. 8 EXISTING LANDLORD NEUTRAL PIERS TO REMAIN. PATCH AND REPAIR TO A "LIKE NEW" APPRARANCE 9 GENERAL CONTRACTOR SHALL REMOVE EXISTING FLOORING AND BASE & PREPARE FLOOR SLAB TO RECEIVE NEW FLOOR FINISH. SEE ROOM FINISH SCHEDULE ON SHEET A-1. 10 REMOVE PORTION O EXISTING STOREFRONT BULKHEAD 11 GENERAL CONTRACTOR SHALL COORDINATE WITH LANDLORD REPRESENTATIVE FOR THE LEASE LINE TO DETERMINE THE LIMITATION OF DEMOLITION 12 EXISTING STEEL STRUCTURE COLUMN TO REMAIN. 13 EXISTING LANDLORD PLUMBING CLEAN OUT TO REMAIN 2 2 11 GENERAL DEMOLITION NOTES A FIELD VERIFY ALL EXISTING CONDITIONS AND NOTIFY ARCHITECT OF ANY DISCREPANCIES IN WRITING PRIOR TO ONSET OF DEMOLITION. B DEMOLITION WORK SHALL BE EXECUTED IN CONFORMANCE WITH THE LOCAL BUILDING CODE AND LANDLORD'S STANDARD PROCEDURES. C EXERCISE EXTREME CAUTION IN DEMOLITION, COST OF REPAIR TO ANY ADJACENT CONDITIONS DAMAGED AS A RESULT OF THIS DEMOLITION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. D ALL MATERIAL TO BE DISPOSED OF IS TO BE DONE BY THE CONTRACTOR OFF THE PROJECT SITE IN ACCORDANCE WITH L.L. REQUIREMENTS & LOCAL RESTRICTIONS UNLESS OTHERWISE NOTED HEREIN. E ALL AREAS SHALL BE KEPT IN A BROOM CLEAN CONDITION AT ALL TIMES. F IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN HEREIN OR NOT, AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL THE EXPENSES OF REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGE BY OPERATIONS IN CONNECTION WITH EXECUTION OF THE WORK . INACTIVE OR ABANDONED UTILITIES SHALL BE CAPPED IN ACCORDANCE WITH LOCAL RESTRICTIONS, REMOVE INACTIVE SERVICES (PLUMBING, ELECTRICAL, MECHANICAL, ETC.) AS REQUIRED TO MAINTAIN OPERATION. 7 6 5 9 11 G MAINTAIN COMPLETE SECURITY OF THE JOB SITE WHILE JOB IS IN PROGRESS AND UNTIL JOB IS COMPLETE. H PROTECT ALL STRUCTURAL MEMBERS FROM DAMAGE, AND BRACE ALL EXISTING STRUCTURES AS NEEDED DURING THE DEMOLITION. 4 PHILADELPHIA, PA 19154 GENERAL CONTRACTOR SHALL REMOVE EXISTING WALL FINISHES AS SHOWN EXCEPT L.L. NEUTRAL PIER TILE. EXERCISE GREAT CARE IN NOT DAMAGING THE FIRE RATED DRYWALL AT THE DEMISING WALLS. IF DAMAGED, G.C. SHALL REPAIR AS NECESSARY AND PREPARE THE SPACE TO RECEIVE NEW FINISHES PER FINISH SCHEDULE. 1455 FRANKLIN MILLS CIR, 2 SPACE 852A ~ 818 SQ. FT. GENERAL CONTRACTOR SHALL REMOVE EXISTING NONBEARING PARTITION WALLS AS INDICATED. DISCONNECT AND REMOVE ALL EXISTING ELECTRIC, CAP OFF PLUMBING (IF ANY) WITHIN REMAINING WALLS OR ABOVE CEILING, AS REQUIRED. PATCH AND REPAIR REMAINING WALL, CEILING, AND FLOOR SURFACES TO ACCEPT FINISHES AS INDICATED. PHILADELPHIA MILLS 1 3 2 4 I DO NOT CUT ON EXISTING STRUCTURAL WORK IN A MANNER RESULTING IN A REDUCTION OF LOAD CARRYING CAPACITY OR LOAD/DEFLECTION RATIO. NOTIFY LANDLORD REP. OF ALL STRUCTURAL PROPOSED CUTS PRIOR TO EXECUTION TO OBTAIN APPROVAL. J IN ALL AREAS WHERE DEMOLITION CAUSES UNEVENNESS IN THE FLOOR SLAB, PERFORM THE NECESSARY WORK REQUIRED TO PROVIDE A SMOOTH SLAB PREPARED TO RECEIVE NEW FINISHES. 10 K ANY EXISTING TO REMAIN FIRE ASSEMBLIES DAMAGED DURING DEMOLITION SHALL BE REPAIRED TO MEET ORIGINAL FIRE PROTECTION REQUIREMENT. L IT WILL BE THE GENERAL CONTRACTORS RESPONSIBILITY TO COORDINATE WITH LANDLORD ON-SITE OPERATIONS DIRECTOR AND TENANT BELOW, BEFORE BELOW SLAB WORK IS TO BE DONE. 13 12 1 4 1 8 10 DEMOLITION PLAN SCALE: 1/4" = 1'-0" PROVIDE TEMPORARY CONSTRUCTION BARRICADE PRIOR TO COMMENCEMENT OF CONSTRUCTION, DO NOT FASTEN TO MALL FINISH MATERIAL. DO NOT ABANDON ANY UTILITIES OR MATERIALS WITHIN LEASE SPACE. REMOVE ALL UTILITY LINES, ETC. BACK TO THE SOURCE AND CAP AS REQUIRED TENANT'S CONTRACTOR WILL REPAINT AND/OR REPAIR LANDLORD PROPERTY (NEUTRAL PIERS, BULKHEAD, REAR CORRIDOR, ETC.) DAMAGED DURING CONSTRUCTION. 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 DEMOLITION PLAN & NOTES D1.0 OF.1 LEASE DIMENSION BALLAST/ TOTAL FIXT. WATT 3 14 * EXIT LIGHT * EMERGENCY LIGHT 1 1 JUNO ATLITE SURELITE IC1 LEDG4-3K- 1 14W-WH PNLRU CC-2 10%-100% DIMMING 1 1 10.8 14 WATT LED 3'-0" NOTE: 14 FURNISHED W/UNIT UNIVERSAL FURNISHED W/UNIT UNIVERSAL 120 120 90 MINUTE BATT. BACKUP POWER N/A 90 MINUTE BATT. BACKUP POWER N/A N/A N/A N/A N/A RECESSED FLUOR. LIGHT FIXT. SEE ELEC. DWGS. ALL LIGHT FIXTURES ABOVE THE SERVICE, PREPARATION, UTENSIL WASHING AND FOOD STORAGE AREAS (INCLUDING THOSE LIGHTS WITHIN STEAM TABLES, REFRIGERATION UNITS, HOODS, AND COOKING EQUIPMENT) SHALL BE SHIELDED OR EQUIPPED WITH SHATTER-PROOF BULBS. 5 5 A A ELECTRICAL CONTRACTOR TO INQUIRE ABOUT LOCAL REBATES ON LIGHT FIXTURES. 3 ALL LAMPS IN FLUORESCENT LIGHT FIXTURES TO BE SYLVANIA UNLESS NOTED OTHERWISE. 2 INSTALLATION OF LIGHT FIXTURES SHALL BE ACCORDING TO MANUFACTURER'S RECOMMENDATIONS AND ACCORDING TO CODE REQUIREMENTS. 4 PROVIDE LIGHT TUBE COVERS, LENSES, ETC., AS REQUIRED TO PROTECT FOOD SERVICE AREA. 1 A1.1 109 EM LIGHT FIXTURES AT WALK-IN BELOW 1/ 2" E RECESSED FLUOR. LIGHT FIXTURE. SEE ELEC. DRAWINGS. G G 3'10 " 1/ 2 " 10 3'1'-6" E G G G G G 2'-6 1/2" G G TYP. 1'-10" RECESSED FLUOR. LIGHT FIXTURE. SEE ELEC. DWGS. MALL COMMON AREA 107 101 105 106 105 2 A3.0 15'-0" 1 A3.1 111 100A 110 LINE OF EXH. HOODS ABOVE 107 112 1 A3.0 1'-5" SIGN 116 103 SALES 11" 7 LEASE LINE 4 A3.0 1 A3.0 TYP. 1'-3 1/2" REFLECTED CLG. PLAN FLOOR PLAN SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" 16'-9 1/2" 10 1/2" 104 A4.0 MALL COMMON AREA 117A 17'-11 1/2" LEASE DIMENSION ROOM FINISH SCHEDULE MARK DESCRIPTION COUNTER GATE N/A 1 EXISTING METAL WALL PANELS PAINT GYP. BD. CLG ACOUSTICAL CLG N/A CEILING EXISTING WALL COVERING METAL WALL PANELS FRP CERAMIC TILE N/A WALLS EXISTING CERAMIC TILE QUARRY TILE EXISTING BASE N/A FLOOR CERAMIC TILE AREA DOOR SCHEDULE SEE FINISH SCHEDULE, SHEET A-1.1 FOR FINISH SPECIFICATIONS SALES AREA TYPE FINISH JAMB - - - JAMB FINISH - JAMB DETAIL 2 A1.0 WALL LEGEND 1 WALK-IN COOLER EXTEND BEYOND MIN. OF 6" 5/8" WATER RESISTANCE GYP. BD. F.R.P. SECTION FIXTURE OR EQUIPMENT. LANDLORD NOTES: EXISTING. DEMISING WALL STUDS. AREA OF BLOCK'G. SHOWN HATCHED. F.F. TYP. BLOCKING DETAIL OPERABLE PART OF SOAP DISPENSER AND PAPER TOWEL DISPENSER SHALL NOT BE LOCATED MORE THAN 40”A.F.F. PER CBC 11B-603.5. SINK DEPTH SHALL NOT EXCEED 6.5” 5/8" TYP. "X" GYP. BD. AT DEMISING WALLS (EXIST.) F.R.P. SINK WITH LEVER HANDLE FAUCET F.R.T. PLYWOOD (SHEET BLOCKING) SECURED TO WALL STUDS. 2.1 QTB-1 SEE EQUIPMENT PLAN FOR PLUMBING ACCESS. SCHEDULE BLOCK'G. PER DETAIL THIS SHEET. SECTION DEMISING AND EXISTING INTERIOR WALLS TYP. ELEV .AT HAND SINK SCALE: AS NOTED NO SCALE SSM-1 WHITE PLASTIC LAMINATE 3/4" PLYWOOD SS-1 NEW DEMISING WALL, 6" METAL STUDS @ 16" O.C. = WITH 5/8" TYPE 'X' GYP. BD. ON TENANT SIDE. 6B A-3.1 1 A1.1 SS-1 DOUBLE ACTING GATE DETAIL 2A SCALE: 3" = 1' A1.0 3 = 4" WALK-IN COOLER/FREEZER INSULATED WALLS 2 2B GATE ELEVATION A1.0 NOT TO SCALE GATE DETAILS AS SHOWN A1.0 CEILING. PER REFLECTED CEILING PLAN. PROVIDE SECOND TIER OF SHELVING WHERE CLG. SPACE ALLOWS. HORIZONTAL BLOCKING SUPPORT; 2 1/2" 16 GA METAL STUDS BETWEEN WALL STUDS. EXIST. DEMISING WALL 2'-6" 4 A-1 BLOCK'G. PER DETAIL THIS SHEET. 5 A-1 (5) 3 5/8" DPx2"-5/8" X 16 GA. METAL JOISTS EQUALLY SPACED WITH 3/4" PLYWD. SHEATHING. EXTERIOR GRADE SCALE: AS NOTED BLOCKING DETAILS 3 5/8" MTL. JOISTS FRP 6'-0" 3 5/8"DPx1-5/8"x16 GA. MTL.JOISTS QTB-1 2'-0" ALL NEW WALL BOARD TO BE WATER AND MOLD RESISTANT 3-5/8"X18 GA. MTL. STUD WALL BELOW COND. AT WALL SHOWN DOTTED 5/8" WATER RESISTANT GYP. BD. PAINT SEMI GLOSS (WHITE) FRP (WALLS) TYPICAL SHELVING ELEVATION 5/8" WATER RESISTANT GYP. BD. PAINT SEMI GLOSS (WHITE) FRP 103 SCALE: 1/4" = 1'-0" 1 A1.0 FLOOR PLAN, CEILING PLAN & NOTES END JOISTS 3 5/8"DPx2"x16 GA. NOTE: SECTION: NON DEMISING WALL EXTERIOR GRADE F.R.T. 3/4" PLYWD. SHEATHING s/s CORNER GUARD F.R.P. 3 5/8" M.S. JOIST TO WALL AT EACH STUD IN WALL 3/4" PLYWOOD ADHERED TO TO GYP. BD. "NO AIRSPACE" METAL SHELVING PER EQUIPMENT PLAN. 3/4" FIRE RATED PLY-WOOD BLOCKING FLUSH TO BACK SIDE OF GYP.BD. 3" =1'-0" G.C. TO PROVIDE PIANO HINGES TO LIFT UP PORTION OF COUNTER TO ACCESS GATE. S/S TRIM WRAP AROUND SCALE: AS NOTED 5/8" WATER RESISTANCE GYP. BD. INSTALL FINISH PER ELEVATIONS AND NOTES. A1.1 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 EXIST SALES AREA WALL FLIP-UP COUNTER TOP ABOVE. 2 EXISTING DEMISING WALL, 6" METAL STUDS @ 16" = O.C. WITH 5/8" TYPE 'X' GYP. BD. ON TENANT SIDE. SOAP DISP. SEE DETAIL 2/A1.0 DOUBLE ACTING SURFACE MOUNTING SPRING PIVOT HINGE. BOMMER BOM-7112-633 3-5/8" METAL STUDS @ 16" = O.C. (12" O.C. AT LOW WALLS) SEE DETAIL 2/A1.1 2 TOWEL DISP. HARDWARE 2X (F.R.T.) WOOD BLOCKING AS REQ'D. WITHIN NEUTRAL PIER KITCHEN 2'-0" MECHANICAL DIFFUSERS SEE M-1 FOR EXTENT OF MECHANICAL WORK D 1 2.1 D D LINE OF EXH. HOODS ABOVE 1'-4" 3 A3.0 MENU BOARDS 116 G G D GENERAL CONTRACTOR SHALL COORDINATE WITH LANDLORD, PROVIDE AND INSTALL NEW NEUTRAL PIER TO MATCH EXISTING. GENERAL CONTRACTOR WILL CONTACT THE LANDLORD'S SPRINKLER AND/OR FIRE ALARM CONTRACTOR FOR ALL ADDITIONS AND REVISIONS TO THE EXISTING SYSTEM AT THE CONTRACTORS EXPENSE. SPRINKLER CONTRACTOR TO PROVIDE NECESSARY DOCUMENTS FOR CONSTRUCTION AND PERMITTING UNDER SEPARATE COVER TO THE ARCHITECT, LANDLORD, AND GOVERNING AUTHORITIES FOR APPROVAL PRIOR TO MAKING ANY MODIFICATIONS TO THE EXISTING SPRINKLER SYSTEM. COORDINATE MODIFICATION SCHEDULE W/LANDLORD FIELD REP. SYSTEM IS TO BE FULLY CHARGED AND OPERATIONAL WHEN G.C. IS OFF SITE. FINAL SPRINKLER LAYOUT TO BE DETERMINED BY SUBCONTRACTORS SHOP DRAWINGS. G 2'-4" D E QUARRY TILE GENERAL CONTRACTOR SHALL REFURBISH ANY LANDLORD AREAS DAMAGED AT THE STOREFRONT TO A LIKE NEW CONDITION (NEUTRAL PIERS, NEUTRAL BANDS, ETC.).INSTALL METAL CAP AT WALL END IN VISUAL ALIGNMENT TO NEUTRAL PIER AS REQUIRED BY DESIGN CRITERIA. ADD NOTE: "GC TO COORDINATE FIELD APPROVAL FROM LANDLORD PRIOR TO FINAL INSTALLATION" - TYP ℄ 114 2 A1.1 1 A3.1 E G NEW EXH. HOOD 100A 106 2" G 2.1 1/ 117 8 A4.0 1'-1" 6'-10 1/2" 10 119 E 111 115 104 48'' G11 A1.1 105 8'- E P-2 TYP 103 2" COORDINATE WITH OWNER AND SIGN VENDOR FOR NEW STOREFRONT SIGN INSTALL, ALL SIGNAGE TO BE APPROVED UNDER SEPARATE SUBMISSION BY SIGN MANUFACTURER. TYP. 4 108 7'-11" 2 A1.1 1/ 116 110 110 11 GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL NEW CASEWORK AND COORDINATE WITH EQUIP. SUPPLIER, SEE SECTIONS ON SHEET #A4.0 INSTALL ALL FINISHES AS SPECIFIED. ALL JOINTS IN AND AROUND CABINETS, SINKS, VENTILATOR, ICE BIN, ETC., TO BE SEALED WITH CLEAR SILICONE SEALANT. PROVIDE BLACK PLASTIC WIRE WAY GROMMETS AT ALL DRILLED OPENINGS. 2'-2" 1 " N '-9 " IO 16 -0 NS ' 18 IME D E 115 D AS GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL 5/8" TYP. "X" GYP. BD. CEILING/SOFFITS AND PAINT PER REFLECTED CLG. PLAN, SECTIONS, AND ELEVATIONS. 118 LE 114 KITCHEN 108 2" 1/ U EN GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL 2'x4' LAY-IN CEILING SYSTEM AS INDICATED ON REFLECTED CEILING PLAN. THE ENTIRE PERIMETER MUST BE SILICONE CAULKED WHERE GRID MEETS WALL. 106 106 2 A3.0 1'-8" '' M 113 119 96 EXISTING LANDLORD STRUCTURE COLUMN NOT TO BE CHANGED OR MOVED. WALK-IN COOLER 105 1'-5" CUT OUT FOR EQUIPMENT, VERIFY SIZE PRIOR TO CUTTING COUNTER TOP. SEE EQUIPMENT PLAN AND SCHEDULE ON SHEET A2.1 FOR MORE INFORMATION. 112 118 P. QUARRY TILE FLOOR FINISH QT-1 TO BE SUPPLIED AND INSTALLED BY THE GENERAL CONTRACTOR PER THE LATEST ADDITION OF THE TILE COUNCIL OF AMERICA, INC. "HANDBOOK FOR CERAMIC TILE INSTALLATION" #F113-94 FOR INTERIOR FLOORS. PROVIDE SANDED GROUT WITH ACRYLIC ADDITIVE; INSTALL PER MANUFACTURER'S SPECIFICATIONS OVER WATERPROOF MEMBRANE, TY 110 118 NEW EXH. HOOD E E 9'-0" A.F.F. NEW L.L. BULKHEAD HT. GENERAL CONTRACTOR SHALL INSTALL 1-1/2" X 1-1/2" 16ga.S/S CORNER GUARDS OR END CAPS FROM FLOOR TO CEILING AT ALL OUTSIDE CORNERS WITHIN THE PREP. ROOM. SCREW FASTEN AND SEAL WITH CLEAR SILICONE, TYP., AT ALL OUTSIDE CORNERS. SEE DETAIL 6/A1.1 CONTRACTOR TO INSTALL REMOVEABLE CEILING TILE AND AIR GRILL TO CLOSE OFF AREA ABOVE WALK-IN COOLER 117A 114 D E E E 11'-0" A.F.F. GYP. BD CEILING GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL STAINLESS STEEL PANELS OVER GYPSUM WALL BOARD FROM TOP OF QUARRY TILE BASE TO BOTTOM OF HOOD, ALONG THE LENGTH OF THE HOOD AT BACK AND SIDES, AND OVER THE BACK SIDE OF THE FRONT COUNTER LOW WALL BEHIND THE COOKING EQUIPMENT. 109 111 116 0" 108 E SIGN GENERAL CONTRACTOR SHALL PROVIDE & INSTALL F.R.P. ACCORDING TO THE MANUFACTURERS INSTRUCTIONS FOR APPLICATION OVER GYPSUM DRYWALL. 117 SCP-1 3'- 107 E 113 D E " 106 110 10'-0" A.F.F. SUSPEND CLG E 1 '' G WALL TILE, SOFFIT TILE AND BASES IN ROOMS WITH GYPSUM WALLBOARD WALLS SHALL BE THIN SET WITH ADHESIVE IN ACCORDANCE WITH THE TILE COUNCIL OF AMERICA, INC. ANSI A1.008.5. NOTE: ALL WALL AND SOFFIT TILE SUPPLIED AND INSTALLED BY GENERAL CONTRACTOR. 106 110 5 A3.1 3 6'- E E 30 105 1 2" A WALK-IN FREEZER 4 A3.1 1/ A 2 GENERAL CONTRACTOR TO CONTINUE MALL FINISHES ON FLOOR FROM LEASE LINE TO FACE OF TOE KICK. 105 EX D 11 104 0" 1 3'- '' G D TE 101 5 E E 8'-0" 3'3 D A 48 LEASE LINE 3'8 EN C JA 2" 2'- P. TY MENU BOARDS 116 GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL AT 16" O.C. & 3-5/8" METAL STUD PART. WITH 5/8" WATER RESISTANT WALLBOARD ON BOTH SIDES OF WALL BETWEEN SALES/KITCHEN; TAPE AND SPACKLE; REMAINING INTERIOR WALLS TO HAVE 5/8" WATER RESISTANT GYP. BD. BOTH SIDES, TAPE & SPACKLE. T 1 P-2 4 A1.1 103 " 2'- 1'- 1'10 " " '-8 E 105 8'- GENERAL CONTRACTOR SHALL PROVIDE F.R.T. BLOCKING AS INDICATED ON THE EQUIPMENT SCHEDULE OR AS NORMALLY REQUIRED. ALL BLOCKING TO BE 3/4" F.R.T. PLYWOOD (MARINE GRADE IN WET AREAS). SCREW FASTEN BETWEEN METAL STUDS AT NEW PARTITIONS AND FURRED WALLS. AT DEMISING WALLS, APPLY F.R.T. BLOCKING OVER 5/8" TYPE 'X' GYPSUM BD. COVER W/ 5/8" GYP BD. AND FINISH WITH F.R.P. TILE. SECURE TO DEMISING WALL METAL STUDS. SEE BLOCKING DETAILS THIS SHEET. N D 2.1 3 3 A3.1 100 105 4'5 2 6" 114 1'- N A 2" 1/ 1 7'-0" A.F.F. GYP BD SOFFIT T 8" 6" 103 P-2 1'- 101 118 114 WALK-IN COOLER/ FREEZER BELOW A 4 5'- 2 100A 8'-6" A.F.F. GYP. BD CEILING LEASE LINE I 0" '-1 ENS 4 2 IM D SE A LE 119 GENERAL CONTRACTOR SHALL VERIFY 1-LAYER OF 5/8" TYPE 'X' GYPSUM WALLBOARD AT ALL EXISTING DEMISING WALLS. ALL DEMISING PARTITIONS ARE TO HAVE 5/8" TYPE 'X' GYPSUM WALLBOARD FROM FINISH FLOOR TO UNDERSIDE OF DECK, CONTINUOUS. PER #U425. GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL AT 16" O.C. & 6" METAL STUD PART. WITH 5/8" TYPE 'X' WALLBOARD ON TENANT SIDE FROM FINISH FLOOR TO UNDERSIDE OF DECK, CONTINUOUS. PER #U425. OTHER SIDE OF STUD TO INSTALLED BY ADJACENT TENANT'S CONTRACTOR. 2 A3.1 TYP ON CONSTRUCTION NOTES 108 108 A 100 106 TYP NOTE: NO FRP PERMITTED IN FRONT-OF-HOUSE (SALES) AREA WHERE EXPOSED TO DIRECT CUSTOMER SIGHTLINES - TYP 1 A1.1 105 110 NOTES: 1 1 PHILADELPHIA, PA 19154 RECESSED DOWN LIGHT 120 106 103 1455 FRANKLIN MILLS CIR, * RECESSED 10.8 SPACE 852A ~ 818 SQ. FT. 10.8 WATT LED (620 LUMENS) 1 PHILADELPHIA MILLS 6G1MW LED 1 LEASE DIMENSION LITHONIA 10%-100% DIMMING LINE VOLTAGE DIMMING 39'-9 1/2" 20 120 105 TYP ADJACENT TENANT * RECESSED DOWN LIGHT RECESSED 2'-6" ℄ 10.8 WATT LED (620 LUMENS) 100A 9'-4" 6G1MW LED 2 108 1'-9 1/2" LITHONIA 15 9'-6" 12 N/A LEASE DIMENSION RECESSED CAN LIGHT WALL WASH N/A ℄ * 120 COLOR ‘DAYLIGHT’ PROVIDE ALL REQ'D. HARDWARE " F15T8/D UNDER COUNTER 39 " EM PHILLIPS 18 INCH T8 DAYLIGHT WHITE FLUORESCENT BULB LEASE LINE 1/ 2 EX 20 2GTL4 347 LP835 1 1/ 2 G LITHONIA ELECTRONIC ℄ E * UNDER COUNTER FLUORESCENT LIGHT 6 1 11 '-4 D 2x4 RECESS TROFFER 120 5'-6" ℄ C * RECESSED 1/ 2" A LED (39W) 4000 LUMEN 4'-6 1/2" 2'-6" A1.0 PROVIDE ALL REQ'D. HARDWARE 0-10V DIMMING 10%-100% DIMMING 6'-6" BALLASTS 3'-5" LAMPS/ FIXT. 11'-7" REMARKS 3'-3" VOLT 3'-5 1/2" MTG. 7'-5" LAMP CATALOG 3'-10" MANUFAC. 5'-9 1/2" QTY. 13'-1 1/2" 4 5'-9 1/2" DESCRIPTION 3 1'-6" SYMBOL 2 4'-2" TYPE NEW 1 3'-0 1/2" LIGHTING FIXTURE SCHEDULE FRAMING PLAN 1/2" =1'-0" 3 A1.0 DETAIL 1-1/2" =1'-0" 4 A1.0 DETAIL 1-1/2" =1'-0" 5 A1.0 A1.0 3-5/8" GA DEFLECTION TRACK W/2-#10 SCREWS TO EA. LOW FLUTE (12" O.C. MAX) 100 GYPSUM 1B PROVIDE DOUBLE 3-5/8"X20 GA. DIAGONAL BRACING @ 48" O.C. W/ 3-#10 SCREWS EA. END. 2 1/2" DIA. ALL-THREAD HANGER ROD FOR CONNECTION BELOW S.A.T. CLG. @ SEE R.C.P. UNISTRUT P2867A BEAM CLAMP EA. END SALES KITCHEN AREA 5/8" F.C. TYPE GYP. BD. TO MIN. 6" ABOVE FIN CLG. ON SALES/KITCHEN SIDE 2 A MENU BOARDS / EXHAUST HOODS 3 5/8" X 20 GA. RUNNER TRACK (362T125-33) RAMSET AT 24" O.C. "HILTI" BRAND MODEL X-DNI 32 P8 ICC-ES REPORT #1663 INTERIOR PARTITION AND BRACING DETAIL SCALE: NONE 2 A1.1 U.L. DESIGN NO. U425 NONBEARING WALL RATING - 1 HR. WATER RESISTANCE GYP. BD. KITCHEN 1 A1.1 CONT. 12" HIGH CEMENT BD. SAME THICKNESS AS GYP. BD. F.R.P. TO TOP OF BASE QTB-1 BASE NOTE: TRIM AND SEAL COOLER TO WALL BOTH VERTICALLY AND HORIZONTALLY. ADJACENT WALL CONSTRUCTION FINISH SCHEDULE: MANUFACTURER TYPICAL 5 A1.1 FLOOR/WALL WATER PROOFING DETAIL THRU-OUT SPACE. SCALE: N.T.S. 4 A1.1 ALL COVE BASES IN KITCHEN, WALK-IN COOLER/FREEZER, AND * JANITOR'S AREAS SHALL HAVE A MINIMUM OF 3/8" RADIUS COVE. MARK MATERIAL SCP-1 CEILING TILE USG INTERIORS 1.800.950.3839 USG CLEAN ROOM CLIMAPLUS, VINYL CLAD GYPSUM ROCK GRID 24"x48" CHICAGO METALLIC SERIES 830 ALUMINUM WITH #41 WHITE FINISH. (CLASS A, FLAME SPREAD=<20, SMOKE DEVELOPED=5) GYPSUM BOARD USG INTERIORS 1.800.950.3839 5/8" TYPE 'X', SMOOTH FINISH, PAINTED PER REFLECTED CEILING PLAN SALES AREA CEILINGS GB-1 DAL-TILE LYNDA GUNDLING lynda.gundling@dal-tile.com 740-815-3693 SERIES: IDENTITY MATT WALL TILE COLOR: MY 67 PARAMOUNT WHITE SIZE: 8"X20"X3/8" GROUT: #333 ALABASTER, 1/8" JOINT MIN. (CLASS A, FLAME SPREAD=0, SMOKE DEVELOPED=0) SALES AREA / COOKING AREA ALFALUX HAMILTON PARKER GABRIEL CANTRELL GCANTRELL@HAMILTONPARKER.COM 614-358-7814/C:614-206-1443 STYLE: ALFALUX, TIMERSTONE-LOVE WOOD COLOR: WENGE, NATURAL RETTIGFICATO SIZE: 6"X24" GROUT: TAUPE #185 CUSTOM BUILDING PRODUCT (CLASS A, FLAME SPREAD=0, SMOKE DEVELOPED=0) DAL-TILE LYNDA GUNDLING lynda.gundling@dal-tile.com 740-815-3693 STYLE: QUARRY TEXTURES COLOR: ADOBE FLASH SIZE: 6"X6" BASE" 6" H. GROUT: MAPAE TERRA COTTA #37 (CLASS A, FLAME SPREAD=0, SMOKE DEVELOPED=0) FLOOR TILE ALL AREAS CORIAN PRODUCT: TERRA COLLECTION COLOR: DESIGNER WHITE (P/N 030784) FINISH: SATIN (CLASS A, FLAME SPREAD=<25, SMOKE DEVELOPED=<25) COUNTERTOPS COLOR:DESIGNER WHITE D354 FINISH: MATTE (CLASS A, FLAME SPREAD=30, SMOKE DEVELOPED=15) COLOR:MONTANA WALNUT 7110K-78 FINISH: FINE GRAIN (CLASS A, FLAME SPREAD=30, SMOKE DEVELOPED=15) T-1 T-2 PORCELAIN TILE PORCELAIN TILE QT-1 QUARRY FLOOR TILE QTB-1 * S-1 SOLID SURFACE MATERIAL PL-1 PLASTIC LAMINATE WILSONART 1.800.433.3222 PL-2 PLASTIC LAMINATE WILSONART 1.800.433.3222 MT-1 STAINLESS STEEL LOCAL SUPPLIER MT-2 STAINLESS STEEL LOCAL SUPPLIER DESCRIPTION GRAPHIC SCHEDULE KITCHEN CEILING FRONT COUNTER FACE INSIDE FACE OF CABINETS OUTSIDE FACE OF CABINETS/OFFICE DESK SMOOTH 18-20 GAUGE, INSTALL PER SMACNA STANDARDS. ALL EDGES TO BE HEMMED, ALL SEAMS TO BE WELDED AND GROUND SMOOTH. (CLASS A, FLAME SPREAD=0, SMOKE DEVELOPED=0) BEHIND GRILL AND FRYER BRUSHED, 18-20 GAUGE, INSTALL PER SMACNA STANDARDS. ALL EDGES TO BE HEMMED, ALL SEAMS TO BE WELDED AND GROUND SMOOTH. (CLASS A, FLAME SPREAD=0, SMOKE DEVELOPED=0) FRONT COUNTER BASE WALL COVERING TO BE PURCHASED AND INSTALLED BY G.C. CONTACT ONMOVA SOLUTIONS. CUSTOM WALL COVERING ONMOVA SOLUTION CUSTOM WALL VINYL WALL COVERING (CLASS C, FLAME SPREAD=<200, SMOKE DEVELOPED=450) P-1 PAINT SHERWIN WILLIAMS EXTRA WHITE - SW7006 HIGH GLOSS LATEX ENAMEL SOFFITS, CEILING GRID, DOOR FRAME, DOORS P-2 PAINT SHERWIN WILLIAMS PAINT TO MATCH EXISTING LANDLORD PAINT COLOR LANDLORD BULKHEAD FRP FIBERGLASS REINFORCED POLYESTER PANELS MARLITE 1.216.343.6621 P-100 WHITE. INSTALL PER MANUFACTURER'S INSTRUCTIONS. PROVIDE TOP AND VERTICAL MOLDING AS REQUIRED, CAULK ALL EDGES FOR WATER TIGHT SEAL. (CLASS C, FLAME SPREAD=<200, SMOKE DEVELOPED=450) KITCHEN WALLS WC-1 SUPPLY INSTALL LOCATION/REMARKS NOTE: 5. ALL MATERIALS USED FOR INTERIOR FINISHES AND TRIM SHALL BE CLASSIFIED IN ACCORDANCE WITH ASTM E84. 1. IT IS THE CONTRACTORS RESPONSIBILITY TO FURNISH AND INSTALL ALL FINISHES. I. CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450 2. ALL ITEMS SHOWN AS EXISTING ARE TO BE VERIFIED, PATCHED, AND REPAIRED BY CONTRACTOR. 3. SEE CONSTRUCTION NOTES AND SPECIFICATIONS FOR GROUT INSTALLATION PROCEDURES. II. CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450 4. ALL FINISHES TO BE MIN. CLASS "C". III.CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450 QTY MARK DESCRIPTION G.C. SCALE: 1 1/2" = 1'-0" BASE AS APPLICABLE FRANCHISEE COOLER TRIM DETAIL A1.1 SALES ELECTRIC SIGNS STAINLESS STL. CLOSURE, 2" X 2". SET INTO SEALANT AND FASTEN @ 12" O.C. INSTALL FROM TOP OF BASE TO TOP OF WALK-IN. 6 SCALE: 1 1/2" = 1'-0" VINYL INTERIOR MENU SIGNS BOARDS WALL OF WALK-IN COOLER/FREEZER 6" BASE & W.P MEMBRANE FACE OF WALL SEE FLOOR PLAN WATER PROOF MEMBRANE SHALL BE LATICRETE 9325 OR EPOXY OR NEOGUARD MEMBRANE OR MER-KRETE HYDRO-GUARD 2000 S.S. DETAILS SEE SALES AREA FINISHES 12" 1" PLAN VIEW 16 GA.S/S END WALL CAP GUARD, SET IN PLACE W/ STR'L ADHESIVE & SILICONE ALL EDGES G.C. SCALE: 3/4" = 1'-0" 2" 16 GA S/S ANGLE CORNER GUARD, SET IN PLACE W/ STR'L ADHESIVE & SILICONE ALL EDGES FRANCHISEE TYP. WALL SECTION AT EXIST. DEMISING WALL 3 A1.1 FIN. FLOOR (SEE A-1 FOR TYPE) 2" QTB-1 BASE SALES AND KITCHEN AREA, SCALE: 1 1/2" = 1'-0" 1. Wall Assembly — The fire rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3-5/8 in. wide and spaced max 24 in. OC. B. Gypsum Board* — Nom 5/8 in. thick gypsum wallboard, as specified in the individual Wall and Partition Design. Diam of opening is 1-1/2 in. larger than the outside diam of pipe. 2. Through-Penetrant — One metallic pipe, conduit or tubing to be centered within the firestop system. An annular space of 3/4 in. is required within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe — Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Conduit — Nom 6 in. diam (or smaller) electrical metallic tubing or steel conduit. C. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. thickness of fill material applied within annulus, flush with both surfaces of wall assembly. 3M COMPANY — FB-2000+ 2" EXISTING SLAB SECTION A-1 HOOD HANGING DETAIL 6" EXISTING STEEL STUDS: 3 5/8" IN. WIDE (MIN.) 1-1/4 IN. LEGS, 3/8 IN. RETURN, FORMED OF 25 MSG (MIN.) GALV STEEL MAX STUD SPACING 24 IN. O.C. SPACE 852A ~ 818 SQ. FT. 3 5/8" x 20 GA. MTL. STUDS (362S162-33) @ 16" O.C. TO STRUCTURE ABOVE, (1CC ER-4943P) OR EQUAL. EXIST.FLOOR & CEILING RUNNER: 20 MSG (MIN.) GALV. STEEL 1 IN. HIGH, RETURN LEGS 3-5/8 IN. WIDE (MIN.) ATTACHED TO FLOOR AND CEILING WITH FASTENERS 24 IN. O.C. 1A PHILADELPHIA MILLS 100 A 5/8" F.C. TYPE "X" GYP. BD. 6" ABV. SALES AREA FINISH CEILING WALLBOARD: 5/8 IN. THICK, TYPE X, 4 FT. WIDE, ATTACHED TO STEEL STUDS AND FLOOR AND CEILING TRACK WITH 1 IN. LONG, TYPE S SELFTAPPING STEEL SCREWS SPACED 8 IN. O.C. ALONG EDGES OF BOARD AND 12 IN. O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY. U.S. GYPSUM CO.-TYPE 'C' JOINT TAPE & COMPOUND VINYL, DRY OR PREMIXED JOINT COMPOUND, APPLIED IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE, 2 IN. WIDE, EMBEDDED IN FIRST LAYER OF COMPOUND OVER ALL JOINTS. AS AN ALTERNATE, NOMINAL 3/32 IN. THICK GYPSUM VENEER PLASTER MAY BE APPLIED TO THE ENTIRE SURFACE OF CLASSIFIED VENEER BASEBOARD, JOINTS REINFORCED. UNI-STRUT P1001 EXISTING METAL FRAMING DECK PHILADELPHIA, PA 19154 EXISTING FLOOR & CEILING RUNNER: 20 MSG (MIN.) GALV. STEEL 1 IN. HIGH, RETURN LEGS 3-5/8 IN. WIDE (MIN.) ATTACHED TO FLOOR AND CEILING WITH FASTENERS 24 IN. O.C. EXISTING SEAL TO DECK July 29, 1995 F Rating — 1 Hr T Rating — 0 Hr P106 PLATE STEAL BEAM / TRUSSES 6" EXISTING DECK System No. W-L-1084 1455 FRANKLIN MILLS CIR, EXISTING FILL VOIDS WITH U.L. #HW-S-0009 (1-HR) L2X2X20 GAX1'-0" W/ 3-#10 SCREWS TO UNDERSIDE OF EXISTING MTL. DECK. 1 G1 STOREFRONT SIGN REFERENCE CHARLEY'S STANDARD SIGNAGE REQUIREMENTS AND MALL CRITERIA X 1 G1 INTERNALLY ILLUMINATED LIGHT BOX (30"Wx39"H) "CHICKEN PHILLY & FRIES" X X 1 G2 INTERNALLY ILLUMINATED LIGHT BOX (48"Wx39"H) "GOURMET FRIES" X X 0 G4 INTERNALLY ILLUMINATED LIGHT BOX (21"Wx39"H) "BREAKFAST" X X 0 G6 X X 1 G11 INTERNALLY ILLUMINATED LIGHT BOX (30"Wx39"H) "PHILLY STEAKS" X X 0 G12 INTERNALLY ILLUMINATED LIGHT BOX (30"Wx39"H) "#1 CHEESETEAKS IN THE WORLD" X X 1 MG1 INTERNALLY ILLUMINATED MENU BOARDS (96"Wx39"H) X X 0 SG1 BACK DOOR SIGNAGE (VERIFY WITH LANDLORD) X X 2 SG5 "EMPLOYEES MUST WASH HANDS BEFORE RETURNING TO WORK" X X 1 VG1 "COOLER KEEP DOOR CLOSED" X X 1 VG2 "FREEZER KEEP DOOR CLOSED" X X INTERNALLY ILLUMINATED LIGHT BOX (30"Wx39"H) "CHICKEN TERIYAKI & CHICKEN BUFFALO" X 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 FINISH SCHEDULE AND DETAILS A1.1 120 - 0.36 - C/P - - - - - 0.10 - - - - - - REMARKS B.T.U.H. OWNER G.C. OWNER G.C. E1 2 X BY OWNER BY OWNER E2 2 X - - E3 2 X BY OWNER BY OWNER CASH REGISTER 120 - - 0.10 - - - - - - X X E4 2 X BY OWNER BY OWNER REGISTER PRINTER 120 - - 0.36 - - - - - - X X E5 2 X - - PASEO 20WATT AMPLIFIER 120 - - 0.10 - - - - - - X X E6 1 X - - CEILING MOUNT SPEAKER 120 - - 0.10 - - - - - - X X E7 2 X BY OWNER BY OWNER LCD ORDER MONITOR 120 - - 0.36 - - - - - - X E8 2 X BY OWNER BY OWNER LCD ORDER MONITOR BRACKET - - - - - - - - - - X E10 1 X BY OWNER BY OWNER PHONE 120 - - - - - - - - - X X PHONE AND FAX MACHINE MAY BE COMBINATION UNIT. E11 1 X BY OWNER BY OWNER FAX 120 - - - - - - - - - X X PHONE AND FAX MACHINE MAY BE COMBINATION UNIT. E12 1 X BY OWNER BY OWNER TV/DVD COMBINATION UNIT 120 - - - - - - - - - X X INCLUDED IN NEW STORE OFFICE SUPPLY LIST. E13 1 X BY OWNER BY OWNER COMPUTER (CPU) KEYBOARD, AND MOUSE 120 - - - - - - - - - X X INCLUDED IN NEW STORE OFFICE SUPPLY LIST. E14 1 X BY OWNER BY OWNER COMPUTER MONITOR 120 - - - - - - - - - X X INCLUDED IN NEW STORE OFFICE SUPPLY LIST. E15 1 X BY OWNER BY OWNER COMPUTER PRINTER & PRINTER CABLE 120 - - - - - - - - - X X H1 2 X CAPTIVE AIR CUSTOM TYPE 1 EXHAUST HOOD W/ SELF-CONTAINED M/U AIR, ROOF CURB, AND ROOFTOP EXHAUST FAN. 120 - 0.1 - - - - - - - X H2 1 X ANSUL R-102 HOOD FIRE SUPPRESSION SYSTEM 120 - 0.1 - - - - - - - X H3-1 1 X STANDARD 4A: 60B: C FIRE EXTINGUISHER PER LOCAL CODE - - - - - - - - - - H3-2 1 X K-CLASS 60B: C FIRE EXTINGUISHER PER LOCAL CODE K1-1 1 X MIGIKITCH'N MKG72 GAS GRILL, 180,000 BTU, LOW PROFILE, 72" GRIDDLE PLATE W/ CORD & PLUG FOR CONTROLS K 1-2 1 X DORMONT 1675 KI T 2S- 48 GAS CONNECTION HOSE, QUICK DISCONNECT - - 120 1 - - 1.32 - X X G.C. TO FURNISH AND INSTALL CAT 5 AND VGA CABLES X X PROVIDE (2) TILLS M11 P11-1 P11-2 X X X X - - - - - - - - - - - - - 180,000 BTU X X - - - - - - - X X X X S3 T18 P6-2 P6-1 SAFETY RESTRAINT - - - - - - - - - - X X K 1-4 1 X BY G.C. BY G.C. GRILL STOP. 2" GALV. PIPE W/ FLANGE - - - - - - - - - - X X K2-1 1 X PITCO SG-14 GAS FRYER W/ FILTER 120 1 - - - C/P - - - 110,000 BTU K 2-2 1 X BY G.C. BY G.C. SAFETY RESTRAINT - - - - - - - - - - K 2-3 1 X DORMONT 16500 KI T 2S- 48 GAS CONNECTOR KIT - - - - - - - - - - X X K3 1 X PITCO SEBNB14 DUMP STATION 120 1 6.9 0.83 - - - - - - X X K4 1 X HATCO K3 MOUNTED HEAT LAMP 120 1 6.9 0.83 - - - - - - X X X LINCOLN 208 1 27.0 6.0 - - - - - X X X SEE MECHANICAL DWGS. 3'-0 1/2" S15 M4 K8 INPINGER 1301 CONVEYOR TOASTER NEMA 6-50P COORDINATE W/ LOCAL FIRE MARSHALL FOR LOCATION S6 P7-1 81290 HOT TOPPING S8 T15 soffit above 3'- F2 3 2" 1/ S12 P9-2 P10 E15 E11 P3 existing landlord cleanouts C/P - - - - X X - - - - - - - - - - X X - - - - - - - - - - X X 115 1 4.9 - - C/P - - - - X X M5 M4 NORLAKE KOLD LOCKER K9 2 X TRUE T SSU- 27- 12M - C WALK-IN FREEZER W/FLOOR AND SELF CONTAINED CONDENSER REFRIGERATED SANDWICH TABLE W/ CASTERS (27 IN) K10 1 X TRUE T SSU- 48- 18M REFRIGERATED SANDWICH TABLE W/ CASTERS (48 IN) 115 1 8.6 - 1/3 C/P - - - - X X K11 1 X CRATHCO D-25 2 - 5 GALLON BOWL LEMONADE DISPENSER 120 1 5.5 0.64 - C/P - - - - X X K12-2 LIPTON X ICED TEA URN X BY OWNER BY OWNER 18"(D)x30"(W)x24"(H) S.S. FLOOR SHELVING (2 TIER) K14 1 X ROBOT COUPE R2N ULTRA FOOD PROCESSOR K15 1 X EASY LETTUCEKUTTER LETTUCE CUTTER P 1-1 1 X ICD 2300 POST MIX DISPENSER, ICE BIN W STAND (CB2323) 1 1 X X NEMCO LANCER COKE COKE COKE CARBONATOR & WATER FILTER PACKAGE COKE BAG IN BOX W/ SHELVES & LINES 120 1 15 1.8 - C/P - 1/4" - - - X K12-2 96 '' P5 M EN K9 U E7 X T17 E8 - - - - - - - - - - - - - - X X 120 1 7.0 - - C/P - - - - X X - - - - - X X C/P - - 1" I.D. - X - - - - - - - - - 120 1 3.5 - - 120 120 1 1 7.0 6.2 - - - C/P - - 1/2" 1/2" - - - - - - X X - - - - - - - X 7-PS-60 WALL MOUNTED HAND SINK - - - - - - 1/2" 1/2" 2" - X X ADVANCE DI-1-5 DROP-IN HAND SINK - - - - - - 1/2" 1/2" 2" - X X X ADVANCE 9-61-18-24L (1) COMPARTMENT PREP SINK - - - - - - 1/2" 1/2" - X X 1 X T&S BRASS B-0231 FAUCET - - - - - - - - - - X X P 7-1 1 X ADVANCE 9-3-54-18RL (3) COMPARTMENT SINK W/ DRAINBOARDS - - - - - - 1/2" 1/2" 2" - X X P 7-2 1 X T&S BRASS B-0133-01 PRE-RINSE ASSEMBLY - - - - - - - - - - X X P 7-3 1 X T&S BRASS B-0156 ADD-ON FAUCET - - - - - - - - - - X X P8 1 X MANITOWOC I-450 ICE MAKER 115 1 13.2 - - C/P 1/2" - - - X X P 9-1 1 X MANITOWOC B-570 ICE BIN - - - - - - - - 3/4" I.D. - X X - TOP KIT - - - - - - - - - - X X WATER FILTER - - - - - - - - - - X X EVERPURE COLDRINK 2 7CLM EV9327-12 WATER FILTER - - - - - - - - - - X X P4 1 X ADVANCE P5 1 X P 6-1 1 P 6-2 - 1-1/2" I.D. 1 X MANITOWOC P 10 1 X ARCTIC PURE P 10-1 1 X P 11-1 1 X ADVANCE 9-OP-20 MOP SINK - - - - - - 1/2" 1/2" 3" - X X P 11- 2 1 X ADVANCE K-240 SERVICE SINK FAUCET - - - - - - - - - - X X P 14 1 X A.O. SMITH DEL-50 WATER HEATER 480 3 - 12 - - 1" I.D. - X X NEW EXIST. MF G MODEL OWNER G.C. INSTALL OWNER G.C. I T EM REMARKS XPRESSNAP INTROFOLD NAPKIN X X RECESSED IN COUNTER CONDIMENTS HOLDER X X RECESSED IN COUNTER CUP DISPENSER X X RECESSED IN COUNTER SOAP DISPENSER X X INCLUDED IN SMALLWARES PACKAGE PAPER TOWEL DISPENSER X X INCLUDED IN SMALLWARES PACKAGE MB2720IC SAFE X X SEE DET 8/A-4.0 FOR SAFE ANCHORING Weight: 186 lbs EXC-700 COAT RACK X X M1 2 X M2 3 X TORK VOLLRATH M3 6 X DISPENSE-RITE ADJ-2 M4 2 X M5 2 X M6 1 X WILSON M7 1 X EXCELL BOBRICK DESCRI P T I ON SUPPLY N4 SYSTEM 78710 B-4112 AW MENDENHALL GPT74C M8 1 X BY OWNER BY OWNER 24" x 36" BULLETIN BOARD M9 1 X BY OWNER BY OWNER M10 1 X MAGNAGRIP M11 1 X RUBBERMAID M12 0 SERTEK S1 0 BY OWNER 12 X 24 S3 4 X NEXEL 18 X 36 S5 1 X NEXEL 18 X 42 S6 2 X NEXEL 18 X 48 MARK QT Y . WORK TABLES MARK QT Y SP ECI F I CAT I ON 3/4" IN 3/4" OUT INCLUDED W/ NEW STORE OFFICE SUPPLY LIST NEW EXIST. E7 E2 E5 1/2" FW 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 MODEL DESCRI P T I ON SUPPLY OWNER G.C. OWNER X 6" CASTERS W/ RESTRAINTS. SEE CASTER RESTRAINT DETAIL, SHEET P-2. KMS-2436 WORK TABLE W/ 5" BACKSPLASH, CASTERS, & 2 SHELVES 24"X36" X X STANDARD HEIGHT ADVANCE KMS-2442 WORK TABLE W/ 5" BACKSPLASH, CASTERS, & 2 SHELVES 24"X42" X X STANDARD HEIGHT X ADVANCE KMS-2448 WORK TABLE W/ 5" BACKSPLASH, CASTERS, & 2 SHELVES 24"X48" X X STANDARD HEIGHT 1 X ADVANCE KMS-2472 WORK TABLE W/ 5" BACKSPLASH, CASTERS, & 2 SHELVES 24"X72" X X STANDARD HEIGHT T 22 1 X ADVANCE KMS-3048 WORK TABLE W/ 5" BACKSPLASH, CASTERS, & 2 SHELVES 30"X48" X X TOASTER TABLE F1 1 X BY G.C. BY G.C. COUNTER BASE W/ ADJUSTABLE SHELVES W/OUT DOORS X X SEE MILLWORK DWGS SHEET A4.0 X X INSTALL CABINET DOORS AT BACK COUNTERS X X 48" WIDE MAX. X ADVANCE - T 15 1 X ADVANCE T 16 1 X T 17 1 T 18 018 INCLUDED IN SMALLWARES PACKAGE 1992 GREY MOP HOLDER X X INCLUDED IN SMALLWARES PACKAGE CUSTOM TOASTER OVEN CART X X SINGLE WALL MOUNTED SOLID STAINLESS STEEL SHELF WALL MOUNTED (REGULAR ERECTA SHELF ) W/ 2 SHELVES EACH X X EQUIPMENT NOTES: X X 1. ALL EQUIPMENT SHALL BE PURCHASED BY THE OWNER AND INSTALLED BY THE GENERAL CONTRACTOR. SIGNAGE TO BE INSTALLED BY SIGN VENDOR. WALL MOUNTED (REGULAR ERECTA SHELF ) W/ 2 SHELVES EACH X X WALL MOUNTED (REGULAR ERECTA SHELF ) W/ 2 SHELVES EACH X X 18 X 30 5-TIER FLOOR SHELVING (WITH 7' POLES) X X S9 1 X NEXEL 18 X 36 5-TIER FLOOR SHELVING (WITH 7' POLES) X X S11 2 X NEXEL 18 X 48 5-TIER FLOOR SHELVING (WITH 7' POLES) X X S12 4 X NEXEL 18 X 60 5-TIER FLOOR SHELVING (WITH 7' POLES) X X S13 1 X KEL MAX DR36188 DUNNAGE RACK (18 x 36) X X S1 5 1 X KEL MAX DR48188 DUNNAGE RACK (18 x 48) X X S16 1 X KEL MAX DR60188 DUNNAGE RACK (18 x 60) X X REMARKS X 1 MAGNETIC KNIFE HOLDER NEXEL G.C. GRILL TABLE (30"x48") T1 X X FIRE EXTINGUISHER NOTES INSTALL X 2 F1 SCALE: 1/4" = 1'-0" WALL MOUNTED FIRST AID KIT S8 E4 E3 X X INCLUDED W/ NEW STORE OFFICE SUPPLY LIST E8 E1 EQUIPMENT PLAN SP ECI F I CAT I ON MF G. H3-2 K11 X X MILL WORK I T EM AR-10000 K10 6'-0" P1-2 PROVIDED BY COCA COLA K1-4 48'' G11 K1-1 P1-1 PROVIDED BY COCA COLA - NUC02 K1-3 M2 X T22 E6 T1 K4 K5 S H1 K1-2 K2-3 M1 PROVIDED BY COCA COLA X - X E3 K3 K2-2 PROVIDED BY COCA COLA X X K2-1 E4 E5 - 2 E1 E2 X - S3 K6 INCLUDED IN EQUIPMENT PACKAGE X 90LB C02 TANK P3 P 9-2 MISCELLANEOUS L T B103 AUTOMATIC ICED TEA BREWER 0 P2 SHELVING L T B103 K13 P 1-2 P LUMBING E QUIPMENT 1 LIPTON X S3 2 M3 1 F3 E12 1 X K14 M6 M8 E10 M9 '' G 1 E13 30 K8 K15 P2 - KOLD LOCKER T16 M7 E14 H2 P10-1 H3-1 60" P9-1 1 1 NORLAKE S12 3'0" 8.3 X 36" K7 3 1 S13 30" 6" PIPE LENGTH, PAINT-ALUMINUM 120 K7 60" S8 P7-2 S6 X WALK-IN COOLER W/FLOOR AND SELF CONTAINED CONDENSER K12-1 S12 P7-3 2 SERVER S16 M5 P8 - 48" P4 COORDINATE W/ LOCAL FIRE MARSHALL FOR LOCATION '' G X K12-1 S9 X X S11 " BY G.C. 1 S11 S5 3'-3 BY G.C. 60" P14 WALL MOUNT SEE MECHANICAL DWGS. X K6 S12 36" X 1 1 MATCH COLOR OF CEILING X K 1-3 K5 GOOSENECK MICROPHONE (13" FLEX) F2 1 X BY G.C. BY G.C. WALL BASE CABINETRY, W/ LAMINATE DOORS & CORIAN TOP F3 1 X BY G.C. BY G.C. MANAGERS WORKTOP 1 CLASS ABC FIRE EXTINGUISHER: EXTINGUISHERS SHALL BE CONSPICUOUSLY LOCATED AND READILY ACCESSIBLE. THE TOP OF THE EXTINGUISHER SHALL NOT BE MORE THAN 5 FT. ABOVE THE FLOOR AND THE BOTTOM OF THE EXTINGUISHER SHALL NOT BE LESS THAN 4 INCHES ABOVE THE FLOOR. EXTINGUISHERS SHALL BE INSTALLED IN ACCORDANCE WITH CLASSIFICATION, RATING, AND DISTRIBUTION REQUIREMENTS OF NFPA 10. [NFPA 1: 13.6.1.2] 2 CLASS K FIRE EXTINGUISHER: CLASS K FIRE EXTINGUISHERS SHALL BE PROVIDED FOR HAZARDS WHERE THERE IS A POTENTIAL FOR FIRES INVOLVING COMBUSTIBLE COOKING MEDIA. [NFPA 10:4.3.2] LANDLORD NOTES: 2. FOOD SERVICE AND BEVERAGE DISPENSING EQUIPMENT SHALL COMPLY W/ NSF REQUIREMENTS AND REQUIREMENTS OF LOCAL HEALTH OFFICIALS HAVING JURISDICTION. 3. INSTALLATION AND CONNECTION OF ALL FOOD SERVICE EQUIPMENT IS TO BE PERFORMED BY THE GENERAL CONTRACTOR UNLESS OTHERWISE INDICATED. 4. SHELVING UNITS SHALL BE ASSEMBLED AND SET IN PLACE BY THE GENERAL CONTRACTOR. PROVIDE "GREEN WALK-INS PROVIDE "GREEN WALK-INS PROVIDE "GREEN WALK-INS PROVIDE "GREEN WALK-INS KOTE" SHELVING IN 5. FOOD SERVICE EQUIPMENT REQUIRING AN ELECTRICAL CONNECTION IS TO BE FURNISHED W/ CORD AND PLUG UNLESS OTHERWISE INDICATED. KOTE" SHELVING IN 6. VERIFY THE ELECTRICAL AND MECHANICAL REQUIREMENTS OF FOOD SERVICE EQUIPMENT PRIOR TO INSTALLATION. KOTE" SHELVING IN KOTE" SHELVING IN PHILADELPHIA, PA 19154 GOOSENECK MICROPHONE (13" FLEX) WASTE 1455 FRANKLIN MILLS CIR, 20 C.W. H.W. SPACE 852A ~ 818 SQ. FT. 1 CONN. PHILADELPHIA MILLS 120 H.P. ELECTRICAL PANELS CASH REGISTER WITH EXTRA TILL AMP. KW. 60" / 0 DESCRI P T I ON SUPPLY INSTALL 48'' MECH VOLTS MODEL PLUMBING 48 KI TCHEN EQUI PME NT MF G. ELECTRICAL 48'' EL E CT RONIC COMPONE NT E QUIPMENT MARK QT Y . NEW EXIST. SP ECI F I CAT I ON 60" I T EM 30" XX 7. SINKS SHALL BE PROVIDED W/ DRAIN TAILPIECES AND FITTINGS. THE GENERAL CONTRACTOR SHALL PROVIDE SHUT-OFF VALVES, SUPPLIES AND TRAPS NECESSARY TO CONNECT SUCH SINKS. 8. PROVIDE A SHUT-OFF VALVE AT HOT AND/OR COLD WATER SERVICE TO EACH PIECE OF EQUIPMENT REQUIRING WATER CONNECTION(S). 9. PROVIDE A BACKFLOW PREVENTER AT EACH PIECE OF EQUIPMENT REQUIRING WATER CONNECTIONS. ( NOT INCLUDING SINKS ) 10. APPLIANCES WITH CASTERS: MOVEMENT OF APPLIANCES SHALL BE LIMITED BY A RESTRAINING DEVICE INSTALLED IN ACCORDANCE WITH THE CONNECTOR AND APPLIANCE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER CMC SECTION 303.5. A2.0 REMOVE ARCH CONSTRUCTION INSTALL NEW CROWN MOLDING IN HATCHED AREA, PAINT TO MATCH EXISTING "CHARLEY'S PHILLY STEAKS" LOGO. G.C. SHALL SUBMIT G1 SHOP DRAWINGS TO L.L. FOR APPROVAL. 3 A3.0 "CHARLEY'S PHILLY STEAKS" SIGN. G.C. SHALL SUBMIT SHOP DRAWINGS G1 TO L.L. FOR APPROVAL. 3'-6" P-3 6 A3.1 11'-0' A.F.F. GYP. BD. CLG. PAINT P-1 FACE AND SIDE T-2 9'-0" A.F.F. BOT. OF LL. BULKHEAD 6" 6" MENU BEYOND T-2 FACE AND SIDE 8" 1 A4.0 2 A4.0 7'-0" A.F.F. BOT. OF EXH. HOOD MT-1 SNEEZE GUARD 1 A4.0 5 A4.0 4 A4.0 3 A4.0 98 1 e sinc 3'-10" A.F.F. TOP OF TILE S-1 S-1 6" T-2 7'-0" A.F.F. BOT. OF GYP. BD. CURTAIN WALL 4'-10" A.F.F. TOP OF SNEEZE GUARD 4'-4" A.F.F. TOP OF SNEEZE GUARD 2'-10" A.F.F. TOP OF COUNTER MT-2 SEE GATE DETAILS, 2/A1.0 S-1 T-2 1'-0" 6 T-1 8 A4.0 QTB-1 LEASE LINE 1'-0" 1 A3.0 SCALE: 1/2" = 1'-0" RECESSED MENU BOARDS. G.C. TO SUBMIT SHOP DWGS. TO L.L. FOR APPROVAL PRIOR TO FABRIC. 11'-0' A.F.F. GYP. BD. CLG. PAINT LEASE LINE T-2 NEW 3-5/8" MTL. STUD WALL W/5/8" GYP. BD. EA. SIDE. FINISH PER ELEVATIONS. T-1 SECTION STOREFRONT ELEVATION 6 A3.1 MT-2 1'-0" WC-1 1 A-4 EXISTING L.L. NEUTRAL PIER WITH FINISHES TO REMAIN. 1'-0" P-1 2'-10" A.F.F. TOP OF COUNTER P-3 LEASE LINE 8'-6' A.F.F. GYP. BD. CLG. PAINT Y L L I PH EAKS ST WC-1 S-1 3 A4.0 H S E R F MADE MENU BEYOND EXH. HOOD 11" PAINT STEEL COL. P-1 9'-0" A.F.F. BOT. OF LL. BULKHEAD 3 A3.0 SCALE: 1/2" = 1'-0" 6 A3.1 T-2 "CHARLEY'S PHILLY STEAKS" LOGO. G.C. SHALL SUBMIT SHOP DRAWINGS TO L.L. FOR APPROVAL. RECESSED MENU BOARDS. G.C. TO SUBMIT SHOP DWGS. TO L.L. FOR APPROVAL PRIOR TO FABRIC. T-2 P-1 11'-0' A.F.F. GYP. BD. CLG. PAINT T-2 48'' 30'' 8'-6' A.F.F. GYP. BD. CLG. PAINT 96'' P-1 48'' 9'-0" A.F.F. BOT. OF LL. BULKHEAD P-1 MG1 G11 EXH. HOOD EXH. HOOD 7'-0" A.F.F. BOT. OF GYP. BD. CURTAIN WALL P-1 IED TIF CER WC-1 3'-10" A.F.F. TOP OF TILE 7'-0" A.F.F. BOT. OF GYP. BD. CURTAIN WALL/ EXH. HOOD % 100 MT-1 DA US ICE O CHSTEAK WC-1 8'-6' A.F.F. GYP. BD. CLG. PAINT 8" P-1 P-1 NEW 3-5/8" MTL. STUD WALL W/5/8" GYP. BD. EA. SIDE. FINISH PER ELEVATIONS. # RECESSED LIGHT FIXTURE CHEESE IN THE WORLD STOREFRONT ELEVATION SCALE: 1/2" = 1'-0" T-1 8 A4.0 QTB-1 4'-10" A.F.F. TOP OF SNEEZE GUARD 5 A-4 STOREFRONT ELEVATIONS LCD ORDER MONITOR QTB-1 2 A3.0 7'-0" A.F.F. BOT. OF EXH. HOOD 2'-10" A.F.F. TOP OF COUNTER T-1 QTB-1 1'-0" T-1 T-1 T-1 MT-1 WC-1 3'-10" A.F.F. TOP OF TILE 2'-10" A.F.F. TOP OF COUNTER 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 3-5/8" MTL. STUDS CURTAIN WALL, (3) SIDES OF HOOD. STEAK N. AMERICA . S. AMERICA . ASIA . AFRICA . EUROPE WC-1 T-1 G1 6" G1 8" G2 1455 FRANKLIN MILLS CIR, 16'-0" PHILADELPHIA, PA 19154 P-3 T-2 SPACE 852A ~ 818 SQ. FT. P-3 4 A4.0 PHILADELPHIA MILLS "CHARLEY'S PHILLY STEAKS" SIGN. G.C. SHALL SUBMIT G1 SHOP DRAWINGS TO L.L. FOR APPROVAL. SECTION SCALE: 1/2" = 1'-0" LEASE LINE 4 A3.0 A3.0 8'-6' A.F.F. GYP. BD. CLG. PAINT 7'-0" A.F.F. BOT. OF GYP. BD. CURTAIN WALL/ EXH. HOOD P-1 MALL COMMON AREA MALL COMMON AREA SNEEZE GUARD SNEEZE GUARD 2'-10" A.F.F. TOP OF COUNTER QTB-1 FRP MT-1 STOREFRONT ELEVATION SCALE: 1/2" = 1'-0" QTB-1 FRP FRP 1 A3.1 REMOVABLE 2'x2' METAL AIR GRILL, PAINT P-1. 2-1/2" GA. STRAP. FRP WATER HEATER SPACE 852A ~ 818 SQ. FT. LCD ORDER MONITOR PHILADELPHIA MILLS 4'-10" A.F.F. TOP OF SNEEZE GUARD 4'-4" A.F.F. TOP OF SNEEZE GUARD PHILADELPHIA, PA 19154 P-1 EXH. HOOD 1455 FRANKLIN MILLS CIR, P-1 P-1 REMOVABLE CEILING PANELS FRP SHELVING SHELVING SHELVING SHELVING FRP 1-COMP SINK VG1 VG1 WALK-IN FREEZER WALK-IN COOLER 10'-0" 10'-0" FRP SHELVING ELECTRICAL PANELS QTB-1 QTB-1 STOREFRONT ELEVATION STOREFRONT ELEVATION 2 A3.1 SCALE: 1/2" = 1'-0" QTB-1 SCALE: 1/2" = 1'-0" SEE SHEET A-1 FOR BLOCKING DETAILS 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 3 A3.1 2-1/2" GA. STRAP. SEE SHEET A-1 FOR BLOCKING DETAILS FRP 5/8" GYP BD. OVER 6", 22 GA. MTL STUDS AT 24" O.C. FRP SHELVING SHELVING SHELVING SHELVING FRP SHELVING SHELVING WATER HEATER 3/4" MTL TRIM ANGLE. TRIM COLOR TO MATCH MENU BD. COLOR AND FINISH 1 COMP. SINK ICE MACHINE QTB-1 STOREFRONT ELEVATION HAND SINK QTB-1 4 A3.1 2'-10" 3 COMP. SINK SAFE 3'-0" 4'-0" 3 COMP. SINK WORK TABLE SCALE: 1/2" = 1'-0" 10'-0" 10'-0" SG2 CO2 5/8" GYP BD. OVER 2-1/2, 22 GA. MTL STUDS AT 24" O.C.. LAP TO 6" STUDS ABOVE. FRP SHELVING MANAGER'S DESK LAP STUDS 36" MIN. T-2 SEE SHEET A-1 FOR BLOCKING DETAILS MOP SINK RECESSED MENU BOARD. VERIFY RECESS DEPTH WITH MANUFACTURER SHIM AS NEC. TO ACHIEVE FLUSH CONDITION AT FACE OF MENU BD. AND SOFFIT STAINLESS STEEL TRIM CAP AT BOTTOM OF SOFFIT/MENU BD. CONTINUOUS 18 GA. MTL CLIP ANGLE 4" QTB-1 STOREFRONT ELEVATION SCALE: 1/2" = 1'-0" KITCHEN ELEVATIONS 2" QTB-1 5 A3.1 MENU SECTION SCALE: 1-1/2" = 1'-0" 6 A3.1 A3.1 3'-10" 1'-2 1/2" 3'-10" 1'-2 1/2" S-1 S-1 BULLNOSE EDGE, TYP. 9 1/2" 8" SODA DISPENSER SEE EQUIPMENT PLAN S-1 3'-10" LEASE LINE 2" 1'-2 1/2" 8" BULLNOSE EDGE, TYP. BULLNOSE EDGE, TYP. 1" 2" 2" 1" S-1 6" S-1 S-1 ADJUSTABLE S/S LEGS ADJUSTABLE S/S LEGS A4.0 MT-2 3 5/8" X 20 GA. RUNNER TRACK RAMSET AT 24" O.C. "HILTI" BRAND MODEL X-DNI ICC-ES REPORT #1663 Scale: 1-1/2" = 1'-0" QTB-1 QTB-1 PATCH MALL TILE AS REQ'D PATCH MALL TILE AS REQUIRED 2 COUNTER SECTION A4.0 3 3 3 5/8" X 20 GA. RUNNER TRACK RAMSET AT 24" O.C. "HILTI" BRAND MODEL X-DNI ICC-ES REPORT #1663 Scale: 1-1/2" = 1'-0" 3 4 COUNTER SECTION A4.0 Scale: 1-1/2" = 1'-0" SNEEZE GUARD. SEE SNEEZE GUARD DETAIL 7/A4.0 2 1 SEE SNEEZE GUARD DETAIL 7/A4.0 R IE LP 11" 75° 11" 6" 2" 1/ " 10 3'- M-100A CENTER M-112A CENTER 4 M-100A LEFT AND RIGHT CLEAR SILICONE SEALANT '-1 1" MT-2 1/ 2" 4 11 1/ S 2'- NOTE: PVC SLEEVES AT EACH SIDE FOR INTER-CABINET CHASE, LOCATE CHASE TOWARDS THE TOP OF THE CABINET, TYP. 8 3'- 1/ 2" ℄ MT-2 4 COUNTER SECTION A4.0 1/ 5 COUNTER SECTION A4.0 Scale: 1-1/2" = 1'-0" 4'-10" 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 PATCH MALL TILE AS REQUIRED Scale: 1-1/2" = 1'-0" 3 5/8" X 20 GA. RUNNER TRACK RAMSET AT 24" O.C. "HILTI" BRAND MODEL X-DNI ICC-ES REPORT #1663 2'-0" S-1 2" 2'- 10 1/2" 12'-7 1/2" 2'-7" 2" 7 1/ 2" 8" QTB-1 POWER SET FASTENERS, TYP. 8" " 9 1/2" ALUMINUM CHANNEL '-8 10 ADJUSTABLE SHELF PL-1 A4.0 Scale: 3/4" = 1'-0" 2'-10" 2'-7 1/2" 3'-10" 2'-4" 2" PL-2 ON DOORS 1'-2 1/2" 1'-6" 11" 11 1/2" PL-1 STUDS COUNTER SECTIONS AND DETAILS 13'-5" ADJUSTABLE S/S LEGS 1'-0" 15'-8" 6" FRONT COUNTER PLAN PL-1 1/ ℄ 0" 1'- 7 SEE SNEEZE GUARD DETAIL 6/A4.0 2'-2" GRILL STOP. SEE EQUIPMENT PLAN & SCHEDULE. 11 5-1/4" X 7" CUT OUT FOR NAPKIN HOLDER 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING 1 @ 16" O.C. MAX. A4.0 NEUTRAL PIER 1'- 2 1/ 2" 2" A4.0 1/ 5-1/4" X 7" CUT OUT FOR NAPKIN HOLDER (3) 4-1/4" Ø CUT OUT TO FIT VOLRATH MODEL #78710 2 5-1/4" Ø CUT OUT FOR CUP DISP. MODEL # ADJ-2 T-2 CLEAR SILICONE SEALANT QTB-1 2" UD ST 1 A4.0 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. 1/2" ALUMINUM CHANNEL 10 2'- ℄ UNDER COUNTER LIGHTING. TYP. T-2 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. 6" " 11 2 M-112A LEFT AND RIGHT 3 ACRYLIC LENS COVER. 2'-10" 5 2'- 0" 3'- 1 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. LED LIGHT FIXTURE 1'-8" 0" LEASE LINE 5-1/4" Ø CUT OUT FOR CUP DISP. MODEL # ADJ-2 SODA MACHINE 3/4 " PLYWOOD OVER 2X4 FIRE RETARDANT WOOD STUDS @ 16" O.C. BULLNOSE EDGE, TYP. 6" 2'- UNDER COUNTER FLUORESCENT T-8 LIGHTING COLOR ‘DAYLIGHT’ ACRYLIC LENS COVER. SNEEZE GUARD SUPPORT PART NUMBERS GRILL STOP. SEE EQUIPMENT PLAN & SCHEDULE. S-1 STUDS 2" 1/ 11 " 0 1'- CONTRACTOR SHALL SUPPLY AND INSTALL SNEEZE GUARD FRP TYPICAL MT-1 BEHIND GRILL & FRYER 4'-4" A4.0 Scale: 3/4" = 1'-0" S-1 2'-10" 6 BULLNOSE EDGE, TYP. FRP TYPICAL NOTE: 1. ALL FACE GLASS TO BE 1/4" TEMPERED 2. ALL SHELF GLASS TO BE 3/8" TEMPERED 3. NO FROSTED GLASS OR LOGOS 4. FINISH TO BE BRUSHED STAINLESS STEEL 5. LIGHT FIXTURE REQUIRED FOR 48" SHELF SECTION ONLY. 6. TO ORDER CONTACT: Andrew Nelson Senior Estimator English Mfg., Inc. 916-638-9902 ext. 108 ℄ 0" 3'- SNEEZE GUARD DETAIL S-1 6" BULLNOSE EDGE, TYP. STUDS 1'- 42" H. WALL 6" S-1 4'-2" 8" 3'-1" 1'-8" 3'-1" 2" 2" UT RA NE 2'-9 1/2" 13'-5" 3 A4.0 1'-2 1/2" ° 1/ 7 2'- " 2" GLASS 6" BULLNOSE EDGE, TYP. 2 1/ GLASS MATRIX SERIES FLUORESCENT LIGHT FIXTURE KIT SUPPLIED BY ENGLISH MANUFACTURING 0" 3'10 3'- 4'-0 1/2" 75 GLASS 2'-11 1/2" 12" O.A. GLASS 2" 2'-11 1/2" 1'-0" 1'-2 1/2" 2'-8" 3 5/8" X 20 GA. RUNNER TRACK RAMSET AT 24" O.C. "HILTI" BRAND MODEL X-DNI ICC-ES REPORT #1663 1'-6" COUNTER SECTION 1 6" PATCH MALL TILE AS REQUIRED PHILADELPHIA, PA 19154 1/2" ALUMINUM CHANNEL QTB-1 1455 FRANKLIN MILLS CIR, PL-1 SPACE 852A ~ 818 SQ. FT. 2'-10" ℄ 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. PHILADELPHIA MILLS 6" ADJUSTABLE S/S LEGS STUDS 2'-7" 2'-10" 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. T-2 MT-2 1'-8" ℄ ACRYLIC LENS COVER. 1/2" ALUMINUM CHANNEL PL-1 PL-1 UNDER COUNTER FLUORESCENT T-8 LIGHTING COLOR ‘DAYLIGHT’ STUDS 2'-10" 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. PL-1 S-1 ADJUSTABLE SHELF BULLNOSE EDGE, TYP. 2'-7" 2'-7" ACRYLIC LENS COVER. T-2 S-1 PL-1 1'-8" ℄ UNDER COUNTER FLUORESCENT T-8 LIGHTING COLOR ‘DAYLIGHT’ STUDS PL-1 1" BULLNOSE EDGE, TYP. PL-1 8" ADJUSTABLE SHELF 1'-0" QTB-1 3/4 " FRT. PLYWOOD OVER 3-5/8" 20 GA. STEEL FRAMING @ 16" O.C. MAX. 5 A4.0 UNDER COUNTER LIGHTING. TYP. 4 A4.0 3 A4.0 8 A4.0 A4.0 SECTION @ BACK COUNTER Scale: 1-1/2" = 1'-0" OF.4 SCOPE OF WORK BARRICADE: A. CONTRACTOR WILL SUPPLY, INSTALL AND REMOVE ALL BARRICADES AS REQUIRED. DEMOLITION: A. SUPPLY ALL LABOR, MATERIALS AND EQUIPMENT FOR DEMOLITION IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. B. REMOVE AND DISPOSE OF ALL DEBRIS AND GARBAGE AWAY FROM THE SITE. PLUMBING & GAS: A. SUPPLY AND INSTALL ALL PLUMBING AND GAS, INCLUDING METER PLACEMENT IF APPLICABLE, AS REQUIRED PER FINAL APPROVED DRAWINGS INCLUDING ALL MATERIALS AND EQUIPMENT. ELECTRICAL: A. SUPPLY AND INSTALL ALL ELECTRICAL, INCLUDING METER IF APPLICABLE, AS REQUIRED PER FINAL APPROVED DRAWINGS INCLUDING ALL MATERIALS AND EQUIPMENT. HVAC: A. SUPPLY AND INSTALL ALL HVAC AS REQUIRED PER FINAL APPROVED DRAWINGS INCLUDING ALL MATERIALS AND EQUIPMENT. HOOD, EXHAUST SYSTEMS, ANSUL FIRE SYSTEMS AND MAKE-UP AIR: A. SUPPLY AND INSTALL ALL DUCTWORK AND RELATED WORK (i.e. DUCT SHAFT, FIRE WRAP) TO INSTALL THE EXHAUST SYSTEMS AND MUA SYSTEMS AS PER CONTRACT DOCUMENTS AND LOCAL AUTHORITIES. B. INSTALL EXHAUST HOODS, FANS AND MAKE-UP AIR UNIT AS SUPPLIED BY THE OWNER. C. COORDINATE ANSUL SYSTEM INSTALLATION WITH THE OWNER'S APPOINTED CONTRACTOR. D. SCHEDULE AND ATTEND ALL HOOD AND ANSUL INSPECTIONS. E. CONTRACTOR SHALL ENAGE A QUALIFIED INDEPENDENT TESTING COMPANY TO PERFORM SMOKE TEST OF ALL DUCTWORK, AND TO PERFORM AIR TESTING AND BALANCING OF THE AIR SYSTEM, INCLUDING EXHAUST MAKE-UP AIR AND AIR CONDITIONING SYSTEMS. CONTRACTOR SHALL PROVIDE SEPARATELY A CERTIFIED REPORT OF THE SMOKE TEST, AND A CERTIFIED REPORT OF THE AIR TESTING AND BALANCING REPORT. THE REPORTS MUST BE CERTIFIED BY A QUALIFIED INDEPENDENT PROFESSIONAL. THE CONTRACTOR SHALL SUBMIT THE TESTING REPORTS TO THE OWNER WITHIN THREE DAYS AFTER THE TESTING. THE REPORT MUST BE RECEIVED BY THE OWNER PRIOR TO DISBURSEMENT OF ANY HOLDBACK AMOUNT. 1455 FRANKLIN MILLS CIR, PERMITS: A. CONTRACTOR WILL BE RESPONSIBLE FOR PICK-UP OF BUILDING PERMITS. B. CONTRACTOR WILL BE RESPONSIBLE FOR ELECTRICAL, PLUMBING, SPRINKLER AND ALL OTHER PERMITS REQUIRED BY ALL SUB TRADES. C. CONTRACTOR TO ATTEND AND SCHEDULE ALL INSPECTIONS AND TO ENSURE ALL WORK MEETS WITH ALL LOCAL AND ANY OTHER APPLICABLE CODES AND REGULATIONS. D. CONTRACTOR TO OBTAIN ALL FINAL INSPECTIONS APPROVALS AND OBTAIN THE CERTIFICATE OF OCCUPANCY. PHILADELPHIA, PA 19154 GENERAL: A. CONTRACTOR SHALL INCLUDE IN HIS COST ALL HIS EQUIPMENT AND MATERIALS INCLUDING HANDLING SHIPPING AND RECEIVING. CONTRACTOR WILL TAKE FULL RESPONSIBILITY FOR ALL ITEMS. B. CONTRACTOR SHALL INCLUDE IN HIS COST ALL HANDLING AND RECEIVING OF OWNER'S EQUIPMENT AND MATERIALS. C. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE SECURE STORAGE AS REQUIRED FOR OWNER'S EQUIPMENT AND INCLUDE COSTS IN HIS WORK. D. REMOVE ALL DEBRIS MATERIALS AND EQUIPMENT FOR FINAL CLEAN UP OF THE ENTIRE STORE. E. CONSTRUCT AS PER FINAL APPROVED STAMPED "CONSTRUCTION" DRAWINGS AND STAMPED "PERMIT" SET OF DRAWINGS. F. IT IS CONTRACTOR'S RESPONSIBILITY TO VERIFY THE CORRECTNESS OF THE DRAWING BEFORE STARTING CONSTRUCTION, AND TO NOTIFY THE OWNER IN WRITING IF THERE ARE ANY ISSUES OR ERRORS WITHIN 3 DAYS. SPACE 852A ~ 818 SQ. FT. ARCHITECTURAL SPECIFICATIONS PHILADELPHIA MILLS GENERAL NOTES SPRINKLERS: A. SUPPLY AND INSTALL SPRINKLERS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. B. WHERE APPLICABLE, EXISTING SPRINKLER PIPING SHALL BE ADJUSTED TO SUIT NEW HEAD LOCATIONS. ALL EXISTING PIPING THAT DOES NOT MEET CODE REQUIREMENTS SHALL BE REMOVED AND REPLACED, AS REQUIRED. C. THE SYSTEM INSTALLATION IS TO BE CARRIED OUT BY A QUALIFIED SPRINKLER COMPANY APPROVED BY LANDLORD. D. APPLY FOR, OBTAIN AND PAY FOR ALL PERMITS, LICENSES, WORKING DOCUMENTS REVIEWS, INSPECTIONS AND EXAMINATIONS. E. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH ALL TRADES AT SITE. F. THE CONTRACTOR SHALL COORDINATE WITH THE MALL ADMINISTRATION FOR DRAIN TIME AND REFILL OF SPRINKLER SYSTEM AND PAY FOR ANY FEES AS REQUIRED. FLOORING: A. TO SUPPLY AND INSTALL FLOORING SYSTEM AS PER FINAL APPROVED DRAWINGS INCLUDING ALL MATERIALS AND EQUIPMENT. B. TO SUPPLY AND INSTALL NEW FLOOR MEMBRANE AS PER FINAL APPROVED DRAWINGS. FINISHES: A. TO SUPPLY AND INSTALL ALL SURFACES FINISHES AS PER FINAL APPROVED DRAWINGS. B. TO SUPPLY AND INSTALL ALL DOORS AS PER FINAL APPROVED DRAWINGS. EQUIPMENT AND FIXTURES AND GRAPHICS: A. INSTALL AND CONNECT ALL EQUIPMENT, FIXTURES AND GRAPHICS SUPPLIED BY OWNER AS PER FINAL APPROVED DRAWING. SIGNS: A. CONTRACTOR TO COORDINATE SIGN INSTALLATION WITH OWNER APPROVED SIGN CONTRACTOR. B. CONTRACTOR WILL ENSURE ALL ELECTRICAL WORK TO BE AVAILABLE FOR THIS INSTALLATION. 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 ARCHITECTURE SPECIFICATIONS AS1.0 OF-1 Z 2'X4' FLUORESCENT NIGHT LT (N/L) 2. 3. P14 GFI TIME CLOCK T/C 9 Z A-20 Z CEILING MOUNTED LT FIXTURE. 4. K12-1 PANEL "A" GFI SF-1 ON ROOF HD TELEPHONE BOARD 8 Z Z Z Z Z MANUAL PULL STATION - 270-SPO 42" A.F.F. F HORN/STROBE-792-7A-006 80" A.F.F. R FAN SHUT DOWN RELAY W/ ENCLOSURE-MR-199X-13/C S DUCT SMOKE DETECTOR 6264B-001/ 6260A-100/6261-003-6251B-001A RT REMOTE INDICATOR/TEST STATION 6262A-001 Z TIE TO 15 A-11 VIA T/C Z 15 5 S Z G Z Z Z G Z G J Z G Z G SIGN 6 3 Z G G E D Z Z J D G G G TIE TO A-11 COORDINATE WITH THE TENANT AND PROVIDE NEW UNDER COUNTER COVE LIGHTS TYPE "C" AS REQUIRED. MAKE ALL CONNECTIONS AS REQUIRED. 7 PROVIDE A MINIMUM 1/2" CONDUIT W/WIRE FROM TELEPHONE OUTLET BACK TO TELEPHONE BOARD LOCATED IN WORK AREA. THIS IS TYPICAL FOR ALL TELEPHONE OUTLETS. 8. FURNISH A TYPE WRITTEN CIRCUIT DIRECTORY CARD FOR ALL PANELS, LISTING ALL USED AND SPARE CIRCUITS. 8 9. CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL REQUIREMENTS AND LOCATIONS OF ALL HVAC EQUIPMENT PRIOR TO INSTALLATION. CONTRACTOR SHALL COORDINATE WITH LANDLORD AND INSTALL NEW TELEPHONE BOARD AS REQUIRED. EXTEND EXISTING TELEPHONE CONDUIT AND CABLE TO TENANT'S TEL. BD "TTB". COORDINATE ALL TELEPHONE REQUIREMENTS WITH TENANT. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL CABLES AND DATA/TEL. OUTLETS. THE TELEPHONE SYSTEM SHALL BE COMPLETE AND FUNCTIONAL. 9 ALL OUTLETS WITHIN 6' OF ANY SINK SHALL BE GFI OUTLETS. ALL KITCHEN AREA OUTLETS SHALL BE WITH GFI TO COMPLY WITH N.E.C. STD. #210.8(B)(2). TO ECONOMIZE THE COST THE CONTRACTOR SHALL INSTALL FIRST OUTLET AT WHICH THE HOME RUN IS CONNECTED, WITH GFI AND ALL OTHER DOWN STREAM OUTLET NORMAL WITHOUT GFI. 10 THE CONTRACTOR SHALL COORDINATE WITH LANDLORD AND DETERMINE WHAT KIND OF LIFE SAFETY AND FIRE ALARM DEVICES ARE REQUIRED BEFORE BIDDING FOR THE PROJECT. USE EXISTING OR FURNISH AND INSTALL NEW FA DEVICES AS REQUIRED, IN COMPLIANCE WITH THE POWER PLAN AND ANSUL WIRING DIAGRAM, LANDLORD'S CRITERIA, NFPA AND LATEST APPLICABLE CODE REQUIREMENTS. TIE TENANT'S FA SYSTEM TO THE BASE BUILDING FA SYSTEM AS REQUIRED. SMOKE DETECTOR - 6250B/6251B-001A CONCEALED IN WALL, CEILING OR UNDER CONDUIT RUN CONSISTING OF: - SMALL LINES INDICATE POWER NON GROUNDED CONDUCTORS. G THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE AND INSTALL ALL CABLES AND CONNECTIONS, AS REQUIRED, OF ALL COMPONENTS THAT ARE PART OF THE WALK-IN COOLER AND WALK-IN FREEZER TO BE FULLY FUNCTIONAL. A-7 VIA T/C 15 PROVIDE SHUNT TRIP CIRCUIT BREAKER TO ALL EQUIPMENT UNDER THE HOOD. 19. ALL CABLES AND WIRES SIZES SHALL COMPLY WITH N.E.C. TABLE 310-16, 2008. MINIMUM SIZE OF CONDUCTOR SHALL BE #12 AWG CU. NO. 10 WIRES SHALL BE USED IN PLACE OF #12 FOR CIRCUITS LONGER THAN 100 FEET FROM PANEL TO LOAD. ALUMINUM CONDUCTOR SHALL NOT BE PERMITTED. WIRE INSULATION SHALL BE THHN OR THWN. 16 FURNISH AND INSTALL POWER CIRCUITS FOR TOASTER, INSTALL 30A, 208V, 1P, TWIST AND DETERMINE EXACT RATING OF ALL EQUIPMENT AND TYPE OF REQUIRED POWER LEAD CONNECTIONS AT EACH EQUIP. MUST ADJUST SIZE OF BREAKERS IF OR AS REQUIRED. THIS IS TYPICAL. 18 DETERMINE EXACT LOCATION OF HOOD AND ANSUL PANELS AT SITE WITH HOOD PACKAGE. CONTRACTOR SHALL ROUTE POWER CIRCUIT FOR EXHAUST AND SUPPLY FANS FROM POWER PANEL TO THE HOOD PANEL AND FROM HOOD PANEL TO THE EXHAUST AND SUPPLY FANS. COORDINATE WITH HOOD MFG. DRAWING FOR ADDITIONAL INFORMATION. THE CONTRACTOR SHALL FURNISH AND INSTALL 460V, 3 POLE, FUSED NEMA 3R, DISC. SWITCHS FOR EXHAUST AND SUPPLY FANS. INSTALL A WEATHER PROOF GFI OUTLET NEAR THE FANS ON THE ROOF. MAKE ALL CONNECTIONS AS REQUIRED. 20 27. CONDUCTORS SHALL BE COPPER PER LL CRITERIA. 28. ALL BREAKERS USED FOR LIGHTING CIRCUITS SHALL BE CONTINUOUS DUTY LIGHT SWITCHING RATING. S ORDER ANNOUNCEMENT AMPLIFIER, LOCATED UNDER SALES COUNTER AMP ON SHELF EQUIPMENT ITEM E5. REMOTE CEILING RECESSED ORDER ANNOUNCEMENT SPEAKER EQUIPMENT ITEM E6. M ORDER ANNOUNCEMENT GOOSENECK MICROPHONE (18" FLEX) SALES COUNTER TOP MOUNTED EQUIPMENT ITEM E2. SYMBOL LEGEND SALES COUNTER SHELF ORDER ANNOUNCEMENT MICROPHONE EQUIPMENT ITEM E2. M OFFICE FAX OFFICE TELEPHONE OFFICE COMPUTER INTRANET AMP S NOTES: 1. G.C. IS RESPONSIBLE TO PULL THE CORRECT WIRE TO BRING THE PHONE LINE FROM THE DENMARK. 2. INSTALL THE APPROPRIATE JACK TO SUPPORT THE PHONE AND DSL ROUTER. 17 CONTRACTOR SHALL COORDINATE WITH KITCHEN AND REFRIGERATION CONTRACTORS 24. ALL BREAKERS IN ALL PANELS SHALL BE BOLTED THERMAL MAGNETIC TYPE. TWO (2) AND THREE (3) POLE MOLDED CASE CIRCUIT BREAKERS SHALL BE WITH COMMON TRIP. 26. ROMAX, TYPE AC AND NM CABLES SHALL NOT BE PERMITTED. EXISTING TELEPHONE SERVICE CONDUIT TO SPACE BY TTB LANDLORD TELEPHONE EQUIP. BD. OFFICE LOCK OUTLET, DETERMINE EXACT LOCATION OF OUTLET AT SITE WITH TENANT. MAKE ALL CONNECTIONS AS REQUIRED. 19 COORDINATE POWER REQUIREMENTS TO VAV-1 WITH SUPPLIER. INSTALL A GFI SCALE: 1/4" = 1'-0" CONDUIT TO TTB FROM EACH TELEPHONE OUTLET INTERLOCK SHUNT TRIP W/ ANSUL SYSTEM. 23. THE GROUND ON THE SEPARATELY DERIVED SERVICE SHALL BE BONDED TO THE BUILDING STEEL AND TO THE INCOMING COLD WATER METAL PIPING WITH CAD WELD CONNECTION. REFER TO KEY NOTE #22. SCALE: 1/4" = 1'-0" 4" COOLER AND FREEZER ARE SEALED ON THE INSIDE IN COMPLIANCE WITH N.E.C. ART. 300-7 "REQUIREMENT TO PREVENT CONDENSATE BUILD UP WITHIN THE CONDUIT". 18. ALL CONDUIT RUNS ABOVE CEILING SHALL BE PARALLEL OR PERPENDICULAR TO THE COLUMN LINES. ELECTRICAL LIGHTING PLAN 3 PHONE LINES 1. VOICE/FAX (OFFICE) 2. CREDIT CARD (NEXT TO CASH REGISTER) 3. DATA LINE FOR COMPUTER (OFFICE) 14 CONTRACTOR SHALL MAKE SURE THAT CONDUIT PENETRATIONS OF THE WALK IN 22. MC CABLES SHALL NOT BE USED FOR HOME RUN CIRCUITS AND FOR THE WIRING WITHIN PARTITION OR DEMISING WALL CONSTRUCTION. ALL IN-WALL CONCEALED WIRING MUST BE RUN IN RIGID CONDUITS. - BIG LINE INDICATES NEUTRAL CONDUCTOR UNDER COUNTER LIGHT TYPE "C" (16'-10") 13 21. CONTRACTOR MAY USE FLEXIBLE CONDUIT FROM JUNCTION BOX TO THE LIGHTING FIXTURE, BETWEEN LIGHTING FIXTURES, AND TO OTHER DEVICES PROVIDED THE LENGTH OF THE FLEX. CONDUIT IS NOT MORE THAN 6 FEET. Z - GROUND CONDUCTOR E 16. CONTRACTOR, UPON COMPLETION OF HIS WORK , SHALL BE RESPONSIBLE TO PROVIDE ANY AND ALL CERTIFICATIONS. 20. ALL INTERIOR WIRING SHALL BE CONCEALED AND IN GAL. STEEL OR EMT COND. AND IN COMPLIANCE WITH THE N.E.C. AND LAND LORD'S DESIGN CRITERIA. REFER TO THE CODED NOTE NUMBER. Z THE CONTRACTOR SHALL COORDINATE WITH THE KITCHEN APPLIANCES CONTRACTOR AND PROVIDE ALL HARDWARE AND CONNECTIONS AS REQUIRED. THIS IS TYPICAL. ELECTRICAL POWER PLAN 3 FOR THE VAV UNIT. TIE RELAY INTO DUCT MT'D SMOKE DETECTOR WHICH WHEN ACTIVATED WILL FULLY OPEN VAV UNIT, SHUT DOWN HOOD SUPPLY FAN AND SIGNAL LANDLORD'S MASTER FIRE ALARM CONT. PANEL, IF REQ'D. PROVIDE CONDUIT, WIRES AND MAKE ALL CONNECTIONS AS REQUIRED. DETERMINE BEST LOCATION OF REMOTE INDICATOR AT SITE. 12 25. UNLESS NOTED OTHERWISE, WIRE AND CABLE SIZES SHALL BE IN COMPLIANCE WITH KEY NOTE # 22, RISER DIAGRAM AND THE N.E.C. TABLE 310-16. EXTEND THE CONDUIT TO TTB IN OFFICE BY TENANT'S CONTRACTOR. 11 FURNISH AND INSTALL NEW DUCT SMOKE DETECTOR, RELAY AND REMOTE INDICATOR 15. COORDINATE FINAL INSTALLATION REQUIREMENTS WITH PROPER AUTHORITIES. AND LANDLORD'S MANAGER. 17. CONTRACTOR SHALL COMPLY WITH THE LANDLORD'S DESIGN CRITERIA FOR ELECTRICAL AND FIRE ALARM SYSTEMS. MAKE NECESSARY CONNECTIONS BETWEEN TENANT'S FIRE DETECTING DEVICES AND THE LAND LORD'S FIRE ALARM STATION. HEAT DETECTOR -281B Z Z F TYP G Z Z D 4 D Z 15 G Z A-34 15 S J G Z 5 TIE TO 15 A-11 Z Z 15 A-12 TIE TO A-23 6 INTERIOR TELEPHONE WIRING SHALL INCLUDE FURNISHING AND INSTALLING ALL TELEPHONE JACKS, AND COVER PLATES AS REQUIRED. COORDINATE WITH THE TENANT. 14. CONTRACTOR TO SEAL ALL WALL PENETRATIONS IN AN APPROVED MANNER TO INSURE THE FIRE RATING INTEGRITY OF THE INVOLVED AREAS. SD G D UNDER COUNTER LIGHT TYPE "C" (16'-9") 6 INSTALL NEW SWITCH LEG AS SHOWN. EACH SWITCH DESIGNATION WHICH CONTROL THE SPECIFIC LIGHT IS MARKED ON THE PLAN. 13. CONTRACTOR SHALL BE RESPONSIBLE FOR COMMUNICATION WITH THE PROPERTY OWNER'S PERSONNEL TO REVIEW CONTRACT DOCUMENTS PRIOR TO INSTALLATION. WATER HEATER H S 5 Z Z Z Z A-30 E E E7 FOR HOOD LIGHT MENU BOARDS GFI GFI Z FOR SNEEZE GUARD LIGHT SIGN Z 9 9 9 Z A-31 GFI GFI GFI 9 S TIE TO A-7 VIA T/C D Z IG Z E E K10 K1-1 J Z K9 E D Z E6 E2 5 7 21 10 2 TYP TIE TO A-27 K4 E Z D Z FOR HOOD LIGHT 15 A-11 Z Z K5 Z 3 Z E E Z 20 H1 Z Z K3 A-16,18 Z E Z 9 E1 A-6 E5 E3 GFI GFI S HD 15 A-19 E Z GFI A-22 K9 15 K11 A-20 E7 E4 K6 5 PULL STRINGS SHALL BE PROVIDED IN ALL EMPTY CONDUIT. FOR TELEPHONE AND LOW VOLTAGE SYSTEM. TWO WAY SWITCH Z A-2 20 A-25 9 SJ Z D Z 9 IG Z P1-1 16 #10 5 Z A-29 9 P1-2 20 E Z 21 9 A-38 Z 9 GFI ROUTE ALL LIGHTING/SIGN CIRCUITS THROUGH A WATT STOPPER 8 RELAY PEANUT PANEL LP8S-8-G-115 AND PROVIDE AS-100-W SWITCHES FOR ALL LIGHTING SWITCHES. (FOR LOCAL CONTROL AND TIME OF DAY OVERRIDE ) 12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL CONNECTIONS UNLESS NOTED OTHERWISE. E E Z H2 GFI Z 9 GFI GFI GFI D E Z Z GFI Z 7 4 ELECTRICAL POWER PANEL A A Z GFI GFI GFI GFI J D Z Z E5 E2 7 Z Z E12 5 WH Z 18 GFI E13 Z Z E1 GFI Z E3 9 Z E4 E10 E Z 9 9 E E14 E15 S TYP EX E E11 K-14 1 Z Z 4 Z P2 9 D S Z GFI A-21 A-15 EF-2 ON ROOF 18 TIE TO A-8 (4) RECESSED OUTLETS FOR LCD MENU BOARDS E CONTRACTOR FURNISH AND INSTALL ALL NEW WIRING AS SHOWN ON THE ELEC. PLANS AND RISER DIAGRAM. ALL NEW WIRING SHALL BE IN COMPLIANCE WITH N.E.C. TABLE 310-16, AND PANEL SCHEDULES. CONTRACTOR SHALL PROVIDE A NEW TIME CLOCK TC AS SHOWN ON THE LIGHT CONTROL DIAGRAM ON SHEET E2. INSTALL JUNCTION BOXES AND SWITCHES FOR THE MENU BOARD AND STORE SIGN CIRCUITS AS REQUIRED. 11. ALL ELECTRICAL DEVICES AND EQUIPMENT SHALL BE EFFECTIVELY GROUNDED IN ACCORDANCE WITH N.E.C. REQUIREMENTS. ALL BRANCH CIRCUITS SHALL HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN EACH CONDUIT RUN. A Z F 21 A-28 10 F P8 HD DISCONNECT SWITCH SS A-26 Z H-14,16,18 THROUGH HOOD PANEL A-5 VIA T/C Z 110 CD 10 JUNCTION BOX 1 3 10. ALL OUTLET AND SWITCHES COVER PLATES SHALL BE STAINLESS STEEL. ALL OUTLET BOXES SHALL BE MOUNTED FLUSH IN WALLS AND SHALL BE MOUNTED AT HEIGHT AS INDICATED ON THE EQUIP. PLAN. COORDINATE ALL LOCATIONS WITH EQUIPMENT INSTALLATION AND ARCHITECTURAL DRAWINGS. TELEPHONE JACK Z 18 Z A-3 Z F H-8,10,12 TIE TO THROUGH A-8 HOOD PANEL J A-1 CONTRACTOR SHALL VERIFY AND USE EXISTING POWER SUPPLY AND EQUIPMENT. HOWEVER PROVIDE NEW POWER PANELS, XFRMR AND FEEDERS TO COMPLY WITH PANEL SCHEDULES. REFER TO KEY NOTE #22. CONTRACTOR MUST COORDINATE AND SUBMIT CUT SHEETS OF ALL LIGHT FIXTURE AND MUST GET APPROVAL FROM THE OWNER OF ALL LIGHT FIXTURE MODEL NUMBERS BEFORE PURCHASING ANY NEW LIGHT FIXTURES. Z Z A-35,37 K7 KITCHEN EQUIP. WITH AMPERE RATING AS SHOWN AT PANEL SCHEDULE AND AT DRAWING. S 14 13 Z Z S Z GFI Z K8 N/L EF-1 ON ROOF 9 A-9 2 LABEL ALL ELECT. EQUIPMENT WITH ENGRAVED BAKELITE NAMEPLATE OR EMBOSSED PLASTIC NAME STRIP. LABEL ALL PANELS AS SHOWN ON THE RISER DIAGRAM. SPECIAL "TWIST LOCK RECEPT" WTR PROOF, 208V, 3Ø, OR 208V, 1Ø, FOR 13 11 TIE TO A-8 Z A ALL INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF THE DESIGN DOCUMENTS, LANDLORD DESIGN CRITERIA AND N.E.C. REQUIREMENTS. PROVIDE LOCK TAB AT THESE CIRCUITS WHICH FEED POWER TO EXIT, NIGHT AND EMERG. LIGHTS IN "ON" POSITION. NIGHT LIGHTS SHALL BE CONTROLLED BY A KEYED SWITCH AND ALL EXIT AND EMERGENCY LIGHTS SHALL BE WIRED AHEAD OF ANY LOCAL SWITCHES. 7. HEIGHT 16" TO BOTTOM UNLESS NOTED OTHERWISE. (TYP.) 14 Z 6. DUPLEX RECEPTACLE WITH 120 V, 20 AMPERE RATING. 1 Z RT R EM Z 19 EM S Z Z 22 EMERGENCY LIGHT TYP A-40,42 VAV-1 ABOVE CEILING GFI A-33 PANEL "H" Z Z Z 2 1 H-7,9,11 THROUGH HOOD PANEL 110 CD H-1,3,5 5. 10 45 KVA XFRMR ABOVE CEILING WP GFI 10 EXIT LIGHT A 22 22 18 A Z A-23 3 1 PHILADELPHIA, PA 19154 CONTRACTOR SHALL REVIEW THE SPECIFICATIONS, GENERAL NOTES, KEY NOTES, ELECTRICAL PLANS AND THE LANDLORD DESIGN CRITERIA BEFORE BIDDING AND STARTING ANY CONSTRUCTION WORK. Z 1. 1455 FRANKLIN MILLS CIR, 2'X4' FLUORESCENT SPACE 852A ~ 818 SQ. FT. A-8 H-13,15,17 KEY NOTES: GENERAL NOTES: PHILADELPHIA MILLS SYMBOLS OUTLET NEAR THE VAV IN THE CEILING AS REQUIRED. MAKE ALL CONNECTIONS AS REQUIRED. ALL CONDUIT PENETRATIONS THROUGH CASEWORK SHALL BE CLEAN, TIGHT AND SEALED WITH WHITE SILICONE. THIS IS TYPICAL. 21 PROVIDE KEY-LOCK TABS AT THESE CIRCUITS. ROUTE CASH REGISTER CIRCUITS WITH AN ISOLATED GROUND CONDUCTOR. 22 INSTALL NEW POWER SUPPLY (100 AMP, 277/480V, 3 PHASE, 4W) IN COMPLIANCE WITH THE RISER DIAGRAM, THE PANEL SCHEDULES AND AS DESCRIBED BELOW:, COORDINATE WITH LANDLORD AND INSTALL NEW DISC. SWITCH AND METER AT LANDLORD`S METER CENTER. RUN NEW CONDUITS AND POWER FEEDERS FROM LANDLORD`S METER CENTER TO TENANT'S SPACE. FURNISH AND INSTALL NEW PANELS "H" & " A" IN COMPLIANCE WITH THE RISER DIAGRAM AND PANEL SCHEDULES. ALL BREAKERS IN ALL PANELS SHALL BE BOLTED TYPE. REFER TO FOOT NOTES AT PANEL SCHEDULES. FURNISH AND INSTALL 45 KVA, 480V- 120/ 208V, 3 PHASE 4 WIRE SECONDARY DRY TYPE TO REMAIN. VERIFY THE XFRMR IS WITH SIX STANDARD TAPS (2+2.% AND 4- -2.5%). . THE XFRMR NEUTRAL SHALL BE BONDED TO THE BUILDING STEEL AND COLD WATER PIPE IN COMPLIANCE WITH N.E.C. 250 REQUIREMENTS. THE GROUNDING SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH N.E.C. STD #250 REQUIREMENTS. ALL EQUIPMENT SHALL BE GROUNDED IN COMPLIANCE WITH N.E.C. STD. #250, 2008. AND UL REQUIREMENTS. UNLESS NOTED OTHERWISE THE CONTRACTOR SHALL USE FOLLOWING SIZE OF WIRES PER N.E.C. TABLE 310-16. (1) USE # 12 AWG, COPPER, THWN OR THHN, FOR 20A BREAKERS. (2) USE # 10 AWG, COPPER, THWN OR THHN, FOR 25A AND 30A BREAKERS. ORDER ANNOUNCEMENT AMPLIFIER EQUIPMENT ITEM E5. (3) USE # 10 AWG, COPPER, THWN OR THHN, FOR EXH. FANS AND RTU UNIT BREAKERS. (4) USE # 8 AWG, COPPER, THWN OR THHN, FOR 35A AND 50A BREAKERS. ORDER ANNOUNCEMENT CEILING RECESSED SPEAKER EQUIPMENT ITEM E6. (5) USE # 6 AWG, COPPER, THWN OR THHN, FOR 60A BREAKERS. 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 ORDER ANNOUNCEMENT DIAGRAM NO SCALE TELEPHONE DIAGRAM NO SCALE LIGHTING FIXTURE SCHEDULE TYPE SYMBOL DESCRIPTION 2x4 RECESS TROFFER A LED LIGHTING STRIP C D E G EX QTY. 6 34' MANUFAC. LITHONIA W.A.C. LIGHTING LAMP CATALOG 2GTL4 347 LP835 LED-T24-5-WT (TAPE) EN-24100-RB2-T & LEDT-CL LED (39W) 4000 LUMEN 12 LED / FT 3 WATTS / FT. RECESSED CAN LIGHT WALL WASH 12 LITHONIA 6G1MW LED 10.8 WATT LED (620 LUMENS) RECESSED DOWN LIGHT 20 LITHONIA 6G1MW LED 10.8 WATT LED (620 LUMENS) RECESSED DOWN LIGHT 14 JUNO EXIT LIGHT 1 ATLITE EMERGENCY LIGHT 1 SURELITE IC1 LEDG4-3K- 1 14W-WH PNLRU CC-2 EM MTG. VOLT RECESSED 120 UNDER COUNTER RECESSED RECESSED 120 120 120 1 2 REMARKS PROVIDE ALL REQ'D. HARDWARE 0-10V DIMMING 10%-100% DIMMING 3 4 LAMPS/ FIXT. BALLASTS ELECTRONIC 1 BALLAST/ FIXT. TOTAL WATT 1 39 FURNISHED W/UNIT UNIVERSAL 120 PROVIDE ALL REQ'D. HARDWARE N/A N/A 120 MR MR CAT5E 1 1 10.8 10%-100% DIMMING 1 1 10.8 90 MINUTE BATT. BACKUP POWER POS STATIONS (VERIFY NUMBER OF POS STATIONS W/ OWNER) 102 10%-100% DIMMING LINE VOLTAGE DIMMING 90 MINUTE BATT. BACKUP POWER VGA CAT5E 14 UNIVERSAL LEGEND VGA 14 WATT LED FURNISHED W/UNIT LCD MONITORS (VERIFY NUMBER OF MONITORS W/ OWNER) N/A N/A N/A N/A N/A 20 N/A 20 NOTES: 1 ELECTRICAL CONTRACTOR TO INQUIRE ABOUT LOCAL REBATES ON LIGHT FIXTURES. 3 ALL LAMPS IN FLUORESCENT LIGHT FIXTURES TO BE SYLVANIA UNLESS NOTED OTHERWISE. 2 INSTALLATION OF LIGHT FIXTURES SHALL BE ACCORDING TO MANUFACTURER'S RECOMMENDATIONS AND ACCORDING TO CODE REQUIREMENTS. 4 PROVIDE LIGHT TUBE COVERS, LENSES, ETC., AS REQUIRED TO PROTECT FOOD SERVICE AREA. POS USB CR USB KEYPAD "BUMP BAR" (VERIFY NUMBER OF BUMP BARS W/ OWNER) CAT5E CAT5E COMP "DENMARK" OFFICE CP CPU SERVER PR REG. PRINTER ON SALES COUNTER SHELF POS USB CR PR REG. PRINTER ON SALES COUNTER SHELF P.O.S. DIAGRAM NO SCALE CR REGISTER W/ CASH DRAWER EQUIPMENT ITEM E1 PR REGISTER PRINTER EQUIPMENT ITEM E4 MR REGISTER W/ VDU CONTROLLER EQUIPMENT ITEM E7 CP COMPUTER, CPU, KEYBD, & MOUSE EQUIPMENT ITEM E13 MR COMPUTER MONITOR EQUIPMENT ITEM E14 PR COMPUTER PRINTER EQUIPMENT ITEM E1 P.O.S. SYSTEM NOTES: (A) PROVIDE 1-1/2" CONDUIT FOR ALL CABLING. (B) G.C. TO PROVIDE AND INSTALL A SEPARATE IG OUTLET FOR EACH MONITOR. SEE PLAN FOR LOCATION. (C) G.C. TO PROVIDE AND INSTALL A SEPARATE IG OUTLET FOR EACH POS STATION. SEE PLAN FOR LOCATION. P.O.S. SPECIAL NOTES: ELECTRICAL CONTRACTOR TO FURNISH AND INSTALL ALL POS SYSTEM RACEWAYS AND OUTLET BOXES, WIRING AND TERMINATIONS FOR POS. EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY OWNER'S DESIGNATED SUPPLIER/CONTRACTOR. CONTACT VENDORS BELOW FOR COMPLETE INFORMATION ON WIRING REQUIREMENTS, POS DATA LINES SHALL BE INSTALLED IN CONDUIT SEPARATE FROM ALL POWER CONDUCTORS. AUPHAN DINING AND NEW CREDIT CARD PROCESSOR CONTACT: THINH PHAN (AUPHAN SOFTWARE) DIRECT: 604.836.2095 TOLL FREE: 888.618.6688 X8000 OFFICE: 604.639.7049, 888.618.6688 FAX: 866.607.9645 CREDIT CARD APPLICATION WITH MERCURY SYSTEM (THIS SYSTEM WILL COME WITH THE REGISTER) CONTACT: PETE ZIEROLF MERCURY PAYMENT SYSTEMS MERCHANT RELATIONS MANAGER 800.846.4472 x4825 DIRECT: 970.335.4825 FAX: 970.385.2730 ELECT. POWER & LIGHTING PLANS NOTES AND DETAILS E1.0 MTD: RECESSED DESCRIPTION OF LOAD BRKR KVA PHASE LOAD CIR PHASE CIR KVA PHASE LOAD BRKR DESCRIPTION OF LOAD AMP P ØA ØB ØC NO A B C NO ØA ØB ØC P AMP 20 3 3.00 1 2 14.57 3 70 45 KVA XFRMR - PANEL "A" 14.00 3 4 3.00 3.00 5 14.47 6 20 3 0.56 7 8 0.54 3 20 EF-1 0.56 9 10 0.54 0.54 0.56 11 12 13 14 0.24 30 3 4.00 3 20 EF-2 15 16 4.00 0.24 4.00 17 0.24 18 EQ. NO. H VAV-1 WITH ELEC HEATER M SF-1 P14 W WATER HEATER SPACE 19 21 23 TOTAL H M T 7.56 7.56 7.56 LEGEND AIR CONDITION MOTOR/FAN TRANSFORMER/PANEL W WATER HEATER T (1) ELECTRICALLY HELD CONTACTOR (TYP.) M M C SPACE 20 22 24 MANUAL OVERRIDE SWITCH "TR" 15.35 14.78 15.25 TOTAL A-1 ØA ØB ØC 22.91 22.34 22.81 TOTAL CONNECTED KVA TOTAL CONNECTED AMPS 81 83 83 A-3 A-5 T (1) REFER TO PANEL "A" SCHEDULE FOR THIS LOAD DETAILS. A-7 VOLTS / 0 H.P. CONN. CASH REGISTER WITH EXTRA TILL 120 1 20 0.36 - C/P GOOSENECK MICROPHONE (13" FLEX) 120 - - 0.10 - - MODEL DESCRI P T I ON AMP. KW. E1 2 X BY OWNER BY OWNER E2 2 X - - E3 2 X BY OWNER BY OWNER CASH REGISTER 120 - - 0.10 - - E4 2 X BY OWNER BY OWNER REGISTER PRINTER 120 - - 0.36 - - E5 2 X - - PASEO 20WATT AMPLIFIER 120 - - 0.10 - - E6 1 X - - CEILING MOUNT SPEAKER 120 - - 0.10 - - E7 2 X BY OWNER BY OWNER LCD ORDER MONITOR 120 - - 0.36 - - E10 1 X BY OWNER BY OWNER PHONE 120 - - - - - E11 1 X BY OWNER BY OWNER FAX 120 - - - - - E12 1 X BY OWNER BY OWNER TV/DVD COMBINATION UNIT 120 - - - - - E13 1 X BY OWNER BY OWNER COMPUTER (CPU) KEYBOARD, AND MOUSE 120 - - - - - E14 1 X BY OWNER BY OWNER COMPUTER MONITOR 120 - - - - - E15 1 X BY OWNER BY OWNER COMPUTER PRINTER & PRINTER CABLE 120 - - - - - CUSTOM TYPE 1 EXHAUST HOOD W/ SELF-CONTAINED M/U AIR, ROOF CURB, AND ROOFTOP EXHAUST FAN. 120 - 0.1 - - - H1 2 X CAPTIVE AIR H2 1 X ANSUL R-102 HOOD FIRE SUPPRESSION SYSTEM 120 - 0.1 - - - K1-1 1 X MIGIKITCH'N MKG72 GAS GRILL, 180,000 BTU, LOW PROFILE, 72" GRIDDLE PLATE W/ CORD & PLUG FOR CONTROLS 120 1 1.32 - - - K3 1 X PITCO SEBNB14 DUMP STATION 120 1 6.9 0.85 - - K4 1 X HATCO K3 MOUNTED HEAT LAMP 120 1 6.9 0.85 - - K5 1 X LINCOLN IMPINGER 1301 CONVEYOR TOASTER 208 1 27.0 6.00 - NEMA 6-50P K6 1 X SERVER 81290 HOT TOPPING TO LIGHTING A-11 SPARE PANEL "A" (2)(3) K K R K R (4)(1) M MTD: RECESSED INTERIOR LIGHTING CONTROLS BRKR KVA PHASE LOAD CIR PHASE CIR KVA PHASE LOAD DESCRIPTION OF LOAD EQ. NO. AMP P ØA ØB ØC NO A B C NO ØA ØB ØC 20 1 0.30 1 2 0.60 LIGHTS KITCHEN 0.40 SALES 3 4 1.00 5 MENU BOARDS 6 0.65 SIGN 1.00 7 8 1.50 0.50 0.40 WALK-IN CLR/FRZR K7,8 9 10 0.20 HOODS, U/C, S.G. 12 1.00 11 RESERVED FOR SHUNT TRIP 13 14 15 16 3.00 20 1 0.84 K14 FOOD PROCESSOR SPACE 17 18 3.00 K6 HOT TOPPING 19 20 1.80 20 1 1.00 0.80 21 22 1.70 BAG`N`BOX P2 1.00 23 ROOF OUTLET 24 SODA DISPENSER 1.85 25 26 1.50 P1-1,P1-2 0.36 SPEAKER, ORDER MONITORS E6, E7 27 28 1.00 0.60 1.02 29 30 CASH REG. / PRINT. / KV'S E1-1:E1-5 1.02 31 32 CASH REG. / PRINT. / KV'S E1-1:E1-5 1.00 VAV SERVICE OUTLET 1.00 33 34 K7 3.00 35 WALK-IN COOLER 30 2 36 37 38 1.00 3.00 SPACE 39 40 3.00 3.00 41 42 TOTAL L R LEGEND LIGHTING RECEPTACLE K I M KITCHEN EQUIPMENT MISCELLANEOUS MOTOR/FAN 8.17 3.80 7.02 BRKR DESCRIPTION OF LOAD P AMP EQ. NO. 1 20 K9 REFRIG. SANDWITCH PREP. K (2) RESERVED FOR SHUNT TRIP LEMONADE DISPENSER 1 20 K11 K CONVENIENCE OUTLETS R T.C. / TRIP REL I (1) K1-1 GAS GRILL/GRIDDLE K (2) RESERVED FOR SHUNT TRIP 2 50 1 20 1 1 1 2 20 20 20 30 K5 THE TIME CLOCK SHALL PROVIDE 365 DAYS, ADVANCE HOLIDAY, ASTRONOMICAL PROGRAMMABLE SHUT OFF SWITCH AND 0-2 HOURS MAXIMUM OVERRIDE SWITCH THE TIME CLOCK CAN BE INTERMATIC ET 7000 SERIES. THE TIME CLOCK SHALL HAVE BATTERY BACKUP 78 HOURS MIN. TIMER CONTROL FOR SIGNS AND LIGHTS K TOASTER K12-1 ICED TEA BREWER K3, K4 DUMP STATION / LAMP RESERVED FOR SHUNT TRIP P8 ICE MAKER H1,H2 HOOD AND ANSUL PANELS K9 REFRIG. SANDWITCH PREP. RESERVED FOR SHUNT TRIP K10 REFRIG. SANDWITCH PREP. SCALE: N.T.S. (2) NOTE K I (1) K (2) BEFORE BIDDING FOR THE PROJECT, THE TENANT'S FIRE PROTECTION CONTRACTOR SHALL VERIFY WITH THE LANDLORD'S ON-SITE REPRESENTATIVE THE TYPE OF FIRE LIFE SAFETY SYSTEM TO BE USED, FURNISHED AND INSTALLED. K (2) RESERVED FOR SHUNT TRIP R OFFICE OUTLETS WALK-IN FREEZER M K8 ØA ØB ØC 14.57 14.00 14.47 TOTAL CONNECTED KVA 117 122 121 TOTAL CONNECTED AMPS NORLAKE 8.3 1.00 - C/P KOLD LOCKER - - - - - - KOLD LOCKER WALK-IN FREEZER W/FLOOR AND SELF CONTAINED CONDENSER - - - - - - REFRIGERATED SANDWICH TABLE W/ CASTERS (27 IN) REFRIGERATED SANDWICH TABLE W/ CASTERS (48 IN) 115 1 4.9 0.60 - C/P 115 1 8.6 1/3 C/P D-25 2 - 5 GALLON BOWL LEMONADE DISPENSER 115 1 - C/P L T B103 AUTOMATIC ICED TEA BREWER 120 1 15 R2N ULTRA FOOD PROCESSOR 120 1 7.0 - K8 1 X NORLAKE K9 2 X TRUE T SSU- 27- 12 M K10 1 X TRUE T SSU- 48- 18M K11 1 X CRATHCO K12-1 1 X LIPTON K14 1 X ROBOT COUPE P 1-1 1 X CORNELIUS 2323 POST MIX DISPENSER, ICE BIN W STAND (CB2323) 120 1 3.5 1.00 - C/P P 1-2 1 X PEPSI PEPSI CARBONATOR & WATER FILTER PACKAGE 120 1 7.0 0.85 - C/P P2 1 X PEPSI PEPSI BAG IN BOX W/ SHELVES & LINES 120 1 6.2 0.80 - - P8 1 X MANITOWOC I-450 ICE MAKER 115 1 13.2 1.50 - C/P P 14 1 X A.O. SMITH DEL-50 WATER HEATER 480 3 - 12 0.65 5.5 1.8 - H CONTACT FROM FIRE DETECTION SYSTEM. SV N (2) PROVIDE THIS BREAKER WITH SHUNT TRIP DEVICE. (3) ROUTE THESE LIGHT CIRCUITS THROUGH TIME CLOCK. GAS SOLENOID VALVE CONNECTED (KVA) FACTOR LIGHTING 120 4.10 125% 5.13 CONV. OUTLETS 120 6.90 100% 6.90 MISC. 120 1.50 100% 1.50 18.54 65% 12.06 MOTORS 208 12.00 125% 15.00 MOTORS 480 4.02 125% 5.03 WATER HEATER 480 12.00 65% 7.80 AIR CONDITION 480 9.00 100% 9.00 45 KVA --- 100% 68.06 TOTAL 1.50% ANSUL SYSTEM CONTROL PANEL DEMAND (KVA) 120/208 480 --- SPEAKER/STROBE WITH UNIT VERIFY LOCATION. DUCT SMOKE DETECTOR VOLT 18 TO HOOD CONTROL PANEL FOR FAN SHUT DOWN TOTAL DEMAND LOADS DEMAND CURRENT/Ø DESIGNED PANEL "A" DESIGNED TRANSFORMER = = = = CONTACT LOCATED IN ANSUL SYSTEM CONTROL HEAD. c (1) TO A/C FAN CONTROL CIRCUIT (CONTRACTOR TO VERIFY) HEAT DET. VERIFY LOCATION. Z A-28 (2) TO LANDLORD'S JB FOR CENTRAL ALARM, 1 SPARE NOTES: 1 ALL WIRING SHALL BE #12 THWN IN 1/2" CONDUIT. ANSUL SYSTEM WIRING DIAGRAM (2) GAS SUPPLY SOLENOID VALVE SHUNT TRIP BREAKER USED FOR UNDER HOOD COOK DEVICES. AS REQUIRED NO SCALE 0.68 --- RELAY SQ.-"D" CLASS 8501 TYPE XM040-VO2 120 VAC COIL, NEMA 1 ENCLOSURE, CLASS - 9991-UE7. PULL STATION (1) SEQUENCE OF OPERATION: UPON ACTIVATION OF THE ANSUL SYSTEM, AND/OR FIRE DETECTION SYSTEM. ALL EQUIPMENT UNDER HOOD, AHU FAN AND GAS SUPPLY SOLENOID VALVE SHALL AUTOMATICALLY SHUT OFF. EXH FANS SHALL BE LOCKED IN "ON" POSITION. 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 (2) COORDINATE WITH THE LANDLORD AND TIE IT TO THE LANDLORD'S CENTRAL ALARM SYSTEM IF REQUIRED. COORDINATE WITH LANDLORD'S FIRE CONTRACTOR FINAL CONNECTION TO LANDLORD'S SYSTEM MUST BE BY LANDLORD'S CONTRACTOR AT TENANT'S EXPENSE. 63.10 120/208, 3Ø POWER SUPPLY CALCULATIONS: 1. 2. 3. 4. X 1 (1) PROVIDE LOCK TAB AT THESE BREAKERS IN "ON" POSITION. LOAD OTHERS 1 120 WALK-IN COOLER W/FLOOR AND SELF CONTAINED CONDENSER A-10 (2) LOAD ANALYSIS XFRMR LOSSES K7 - SPRINKLER SYSTEM MUST BE FACTORY MUTUAL COMPLIANT. J LANDLORD'S FA SYSTEM BOX 6.40 10.20 7.45 TOTAL (4) ROUTE THIS CIRCUIT WITH ISO. GROUND CONDUCTOR. KITCHEN EQUIP. KI TCHEN EQUI PME NT BLDG: CHARLEY`S PHILLY STEAKS KITCHEN PHASE: 3, S/N WIRE: 4 WITH ISO. & EQUIP. GROUND BUSSES MLO: N/A (1) (3) L SPARE P LUMBING EQUIP. A.I.C.: 22,000 AMPS VOLTS: 120/208 V MCB: 150 AMP PHILADELPHIA, PA 19154 WIRE: 4 MF G. ELECTRICAL 1455 FRANKLIN MILLS CIR, PHASE: 3, S/N WITH GROUND BUSS NE W EXIST. SP ECI F I CAT I ON SPACE 852A ~ 818 SQ. FT. BLDG: CHARLEY`S PHILLY STEAKS KITCHEN I T EM MARK QT Y . E L ECT RONIC COMPONE NT EQUIPMENT MLO: N/A PANEL A-10 MECH A.I.C.: 10,000 AMPS VOLTS: 277/480 V MCB: 100 AMP TIME CLOCK "TC" 365 DAYS ASTRONOMICAL PROGRAMMABLE PHILADELPHIA MILLS XX PANEL "H" TYPICAL SHUNT TRIP RELAY CONTROL 40.59 KVA 113 AMPS @ 120/208V,3Ø 150 AMP MCB, 120/208V, 3Ø, 4W. 45 KVA TENANT SPACE ELECTRICAL ROOM NO SCALE 45 KVA DRY TYPE XFRMR. 480 V. "DELTA" PRIMARY 120/ 208 V. "WYE" SECONDARY 277/480, 3Ø POWER SUPPLY CALCULATIONS: = T/C M 5 2 3 (4)-#3, CU, 1-#8, CU, GRND IN 1-1/4"C. 1 2 PANEL "H" 2 100 AMP MCB COLD WTR METAL PIPE PANEL "A" 1 # 6, CU, TO GRND, BLDG. STEEL AND COLD WTR METAL PIPE PER N.E.C. #250. 7 DAY, 24 HRS PROGRAMMABLE TIME CLOCK T/C 2 INSTALL GROUNDING SYSTEM TO COMPLY WITH RISER DIAGRAM AND WITH N.E.C. STD. #250, REQUIREMENTS. 3 FURNISH AND INSTALL NEW PANELS "H" AND "A" IN COMPLIANCE WITH THE RISER DIAGRAM AND PANEL SCHEDULES. ALL PANELS SHALL BE WITH BOLTED TYPE BREAKERS. EF-2 2 2 150 AMP MCB 4 INSTALL POWER FEEDERS FROM PANEL "H" TO THE XFRMR AND FROM XFRMR TO PANEL "A" AS SHOWN ON THE RISER DIAGRAM. 5 FURNISH AND INSTALL A 45KVA XFRMR AS SHOWN. THE XFRMR SHALL BE DRY TYPE WITH 6 STANDARD VOLTAGE REGULATION TAPS. THE NEUTRAL OF THE TRANSFORMER SHALL BE BONDED WITH THE BUILDING STEEL AND TO THE INCOMING COLD WATER METAL PIPE WITH EXOTHERMIC WELD CONNECTIONS AS SHOWN ON THE RISER DIAGRAM. SUPPORT THE XFRMR ABOVE THE PANELS AS RECOMMENDED BY THE MANUFACTURER. SF-1 HOOD CONTROL PANEL 2 RISER DIAG. NOTES: THE CONTRACTOR SHALL COORDINATE WITH THE LANDLORD AND SHALL FURNISH AND INSTALL DISC. SWITCH AND ELECTRIC METER AS SHOWN AND AS REQUIRED. FURNISH AND INSTALL NEW POWER SUPPLY FEEDERS AND CONDUIT TO COMPLY WITH THE RISER DIAGRAM AND N.E.C. CODE REQUIREMENTS. 2 3 ELECT POWER RISER DIAGRAM 1 EF-1 4 Z 1 2 45 KVA 3 #4, CU, 1#8, CU, GRND, IN 1" C. 100AF COORDINATE W/ LL AND PROVIDE 100A FUSED DISC. SWITCH AND METER AS REQUIRED FOR TENANT SPACE FOR 100A, 480V, 3Ø, SERVICE 2 Z A-28 (FOR HOOD CONT. AND LTS) 1 Z Z TO FAN CIRCUITS J. BOX ON HOOD #1 LTS. & FAN SWITCH. Z J Z J TO ANSUL PANEL NOTES: (#10) 4. DESIGNED POWER SUPPLY 4 4-#1/0, CU, 1- #6, CU, ISO. GRND, 1-#6, CU, GRND IN 2" C. (#10) = 5 EXIST LL'S WIREWAY Z 3. DESIGNED PANEL "H" 63.10 KVA 76 AMPS @ 277/480V,3Ø 100 AMP MCB, 277/480V, 3Ø, 4W. 100 AMPS, 277/480V, 3Ø, 4W. Z = = (#10) 1. TOTAL DEMAND LOADS 2. DEMAND CURRENT/Ø J. BOX ON HOOD #2 LTS. & FAN SWITCH. 1 CONTROL WIRING SHALL BE #12 THWN IN 1/2" CONDUIT UNLESS NOTED OTHERWISE. 2 PROVIDE NEMA 3R DISC SWITCHES FOR FANS AND ROUTE POWER CIRCUITS FROM HOOD PANEL TO ALL FANS. HOOD WIRING DIAGRAM NO SCALE PANEL SCHEDULES, RISER DIAGRAM AND DETAILS E2.0 BIDDERS QUALIFICATIONS AND INSTRUCTIONS: 1.1.1 QUALIFICATIONS: ALL INSULATED CONDUCTORS SHALL BE UNCOATED COPPER OF 98% CONDUCTIVITY, 600 VOLT AC, DUAL RATED, TYPE THHN/THWN AS NECESSARY TO MEET THE DESIGN REQUIREMENTS AND THE APPLICABLE CODES. THW (FOR # 4 AWG AND LARGER) AND THERMO PLASTIC WIRES RATED FOR 75 DEGREES CENTIGRADE OPERATIONS IN WET AND DRY LOCATIONS AND 90 DEGREES CENTIGRADE WITHIN ELECTRIC DISCHARGE LIGHTING EQUIPMENT MAY BE USED. CONDUCTORS NUMBER # 10 AWG AND LOWER SHALL BE SOLID COPPER AND #8 AWG AND ABOVE SHALL BE STRANDED COPPER. THE MINIMUM SIZE OF WIRE SHALL BE # 12 AWG FOR 20 AMP BREAKER, # 10 AWG FOR 30 AMP BREAKER, # 8 AWG FOR 40 AMP BREAKER. THE BIDDERS SHALL BE QUALIFIED, EXPERIENCED, AND LICENSED ELECTRICAL CONTRACTORS. THEY MUST BE FAMILIAR WITH ALL FEDERAL, STATE, AND LOCAL LAWS, ORDINANCES, RULES, AND REGULATIONS THAT MAY, IN ANY MANNER, AFFECT THE TASK. 1.1.2 BIDDING INSTRUCTIONS: BEFORE SUBMITTING THE BID, THE BIDDERS MUST REVIEW THE TENANT INFORMATION AND CRITERIA MANUAL, SPECIFICATIONS, PLANS, DRAWINGS, AND ALL OTHER CONDITIONS AND REQUIREMENTS THAT MAY, IN ANY MANNER AFFECT THE WORK UNDER CONTRACT. THEY MUST VISIT THE SITE OF THE PROPOSED PROJECT TO FAMILIARIZE THEMSELVES WITH THE LOCAL CONDITIONS, FIRE RATING REQUIREMENTS, AND THE NATURE OF THE PROJECT. THE PRICING SHALL BE BASED ON THESE SPECIFICATIONS AND THE MATERIALS SHOWN ON THE DRAWINGS. SUBMISSION OF THE BIDS SHALL BE CONSIDERED AS THE EVIDENCE THAT THE BIDDER IS FAMILIARIZED TO ALL THE FACETS OF THE SPECIFIED PROJECT. CONTRACTOR SHALL USE APPLICABLE SECTIONS OF THIS SPEC. 1.1.3 1.1.4 2.5 1.2 THE ELECTRICAL CONTRACTOR REQUIREMENTS AND INSTRUCTIONS: 1.2.1 THE CONTRACTOR SHALL USE EXPERIENCED AND SKILLED PERSONS TO PERFORM ALL THE ELECTRICAL INSTALLATION WORK UNDER THE CONSTANT SUPERVISION OF LICENSED ELECTRICIANS AND/OR LICENSED JOURNEYMAN ELECTRICIANS. 1.2.2 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED PERMITS, PAYING ALL FEES, AND PROVIDING ALL NECESSARY INSPECTIONS INCIDENTAL TO THE ELECTRICAL PORTION OF THE WORK. 1.2.3 THE CONTRACTOR SHALL BE RESPONSIBLE FOR CARRYING NECESSARY INSURANCE AS REQUIRED BY LAW TO PROTECT EMPLOYEES, OTHER PERSONS, EQUIPMENT, AND MATERIAL. 1.2.4 THE INSTALLATION WORK SHALL COMPLY WITH ALL APPLICABLE STATE, COUNTY, AND LOCAL BUILDING CODES. APPLICABLE CODES, AS A MINIMUM, WILL INCLUDE THE LATEST EDITION OF THE FOLLOWING. THESE WILL BE CONSIDERED PART OF THE SPECIFICATION OF THIS PROJECT. 2.7 IN CASE OF SUBSTITUTIONS THE CONTRACTOR SHALL PROVIDE A WRITTEN REQUEST TO THE ARCHITECT FOR HIS REVIEW . THE CONTRACTOR SHALL IDENTIFY CLEARLY THE DIFFERENCE BETWEEN THE SPECIFIED ITEMS AND THE SUBSTITUTE ITEMS, INCLUDING THE ECONOMIC IMPACT ON THE PROJECT. THE SUBSTITUTE ITEM SHALL NOT BE ORDERED OR USED UNLESS APPROVED BY THE ARCHITECT AND/OR BY THE OWNER IN WRITING. 2.8 C. D. LIGHTING FIXTURES, DIMMERS, LAMPS, AND SAFETY SWITCHES. TRANSFORMERS, SWITCH BOARDS, DISTRIBUTION PANELS , DISCONNECTS, AND WIREWAYS IF PURCHASED NEW. METER CENTERS, CIRCUIT BREAKERS, FUSES, MOTOR STARTERS IF PURCHASED FOR THIS PROJECT. TIME CLOCK AND OTHER DEVICES. E) SCHEMATIC DIAGRAMS FOR THE ABOVE ITEMS. THE CONTRACTOR SHALL PROVIDE FOLLOWING DOCUMENTS BEFORE THE CLOSING OF THE PROJECT AND PRIOR TO THE FINAL PAYMENT: A. B. C. D. 1.2.9 ALL SLAB OR ROOF PENETRATIONS SHALL BE MADE WITH APPROVED FIRE RATED SMOKE BARRIER FITTINGS. PROVIDE ACCESSORIES (PITCH POCKETS, SLEEVES, ETC.) AS REQUIRED. CONDUITS: 3.10 JUNCTION BOXES FOR NEON SIGN LIGHTS, SWITCHES, LIGHTING FIXTURES, RECEPTACLES AND FOR PULLING WIRES SHALL BE AS APPROXIMATE AS SHOWN ON THE PLANS BUT EXACT LOCATIONS SHALL BE GOVERNED BY THE ARCHITECTURAL PLANS. 3.11 ALL OUTLET BOXES SHALL HAVE SQUARE CUT CORNERS. AIR SPACE GREATER THAN 1/8" AROUND OUTLET BOXES, AND ADJACENT DRYWALL WILL NOT BE PERMITTED. THE CONTRACTOR SHALL COORDINATE WITH DRYWALL INSTALLER PRIOR TO INSTALLATION. CAULK AROUND BOXES TO ELIMINATE STEEL OUTLET. 2.9 OUTLET BOXES AND FITTINGS: 2.12 3.14 THE CONTRACTOR SHALL FURNISH AND INSTALL ALL LUMINARIES, DEVICES, AND EQUIPMENT AS SPECIFIED AND SHOWN ON THE PLAN DIAGRAMS. PROVIDE ALL CABLES, CONDUCTORS, CONDUITS, AND CONNECTIONS AS REQUIRED TO PROVIDE COMPLETE AND OPERATIONAL ELECTRICAL AND MECHANICAL SYSTEMS. ALL CONDUITS SHALL BE RUN CONCEALED IN FINISHED AREAS. 3.16 BRANCH CIRCUITS SHALL BE ARRANGED USING DOUBLE ROW CONSTRUCTION. ALL INTERIORS SHALL BE COMPLETELY FACTORY ASSEMBLED WITH SWITCHING AND PROTECTIVE DEVICES, WIRE CONNECTORS, ETC. ALL WIRE CONNECTORS, EXCEPT SCREW TERMINALS, SHALL BE OF THE ANTI-TURN SOLDERLESS TYPE AND ALL SHALL BE SUITABLE FOR COPPER WIRE OF THE SIZES INDICATED ON DRAWINGS OR IN THE PANEL SCHEDULES AND CONTINUOUSLY FUNCTIONING AT 75 DEGREE CENTIGRADE. INTERIORS SHALL BE SO DESIGNED THAT SWITCHING AND PROTECTIVE DEVICES CAN BE REPLACED WITHOUT DISTURBING ADJACENT UNITS AND WITHOUT REMOVING THE MAIN BUS CONNECTORS AND SHALL BE SO DESIGNED THAT CIRCUITS MAY BE CHANGED WITHOUT MACHINING, DRILLING, OR TAPPING. BUS BARS FOR THE MAINS SHALL BE OF COPPER AND SIZED IN ACCORDANCE WITH UNDERWRITERS' LABORATORIES STANDARDS. UNLESS NOTED OTHERWISE, FULL SIZE NEUTRAL BARS SHALL BE INCLUDED. BUS BAR TAPS FOR PANELS WITH SINGLE POLE BRANCHES SHALL BE ARRANGED FOR SEQUENCE PHASING OF THE BRANCH CIRCUIT DEVICES. THE SHORT CIRCUIT RATING OF THE ASSEMBLED PANEL BOARD SHALL BE IN ACCORDANCE WITH UL. INC. STANDARDS AND THEIR TEST VERIFICATION. PHASE BUSSING SHALL BE FULL HEIGHT WITHOUT REDUCTION. CROSS AND CENTER CONNECTORS SHALL BE COPPER. NEUTRAL AND GROUND BUSSING SHALL HAVE SUITABLE LUGS FOR OUTGOING FEEDERS REQUIRING A NEUTRAL AND GROUND CONNECTIONS. INDIVIDUAL BREAKERS WILL SUPPLY ELECTRICAL POWER TO INDIVIDUAL SIGN OR NEON LIGHT CIRCUITS. NEON TRANSFORMER EQUIPMENT IS TO BE CONCEALED ABOVE ADJACENT COLUMN ENCLOSURE OR TO BE INSTALLED AS SHOWN ON ARCHITECTURAL DRAWINGS. ALL JOINTS IN CONDUIT AND RACEWAY SHALL BE MADE TIGHT AND BENDS SHALL BE MADE OVER LONG RADIUS WHERE ENTERING A CABINET AND JUNCTION BOX. THE CONTRACTOR SHALL SUPPORT ALL CONDUIT AND RACEWAYS SECURELY FROM JOISTS AND/OR BEAMS (TIE WIRES ARE NOT ACCEPTABLE). THE CONTRACTOR SHALL VERIFY ALL RACEWAY SIZES IN ACCORDANCE WITH THE N.E.C. CODE. NO CONDUIT SHALL CARRY MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS. NOTE: ALL JOB CUT THREADS SHALL BE COATED WITH RUST RESISTANT ZINC CHROMATE FOR THIN WALL EMT. SPACES FOR FUTURE SWITCHING AND PROTECTIVE DEVICES ON LIGHTING AND APPLIANCE DISTRIBUTION PANELS SHALL BE BUSSED FOR THE MAXIMUM DEVICE THAT CAN BE FITTED INTO THEM. PROVIDE BLANK FILLER PLATES IN THE EMPTY SPACES. 4.2 TIME CLOCK SHALL BE ELECTRO-MECHANICAL 24 HOURS SEVEN DAYS TYPE WITH RESERVE POWER AND CONTACTS RATED 40 A. 4 PST AND N.E.M.A. TYPE 1 OR 3R ENCLOSURE. IT SHALL BE SELF POWERED BY A SELF STARTING SYNCHRONOUS MOTOR WITH MINIMUM 16 HR SPRING DRIVEN RESERVE POWER AND A DAY OMITTING DEVICE. TIME CLOCK SHALL BE PARAGON 7007-0, TORK "W" SERIES, OR APPROVED EQUAL. 3.17 LIGHTING CONDUITS SHALL BE SUPPORTED AT EVERY 8 FEET. 3.18 MOUNTING HEIGHT OF LIGHTING EQUIPMENT, UNLESS NOTED OTHERWISE ON ARCHITECTURAL PLANS SHALL BE APPROXIMATELY AS FOLLOWS: HANDLES INDICATING "ON" "OFF" AND "TRIPPED" CONDITION. 3.19 3.20 3.21 A. LIGHTING SWITCHES CENTERLINE B. CONVENIENCE OUTLETS CENTERLINE C. LIGHTING & POWER PANELS TOP D. EMERGENCY LIGHT FIXTURES EACH POLE SHALL PROVIDE INVERSE TIME DELAY AND INSTANTANEOUS CIRCUIT PROTECTION. THE BREAKER RATING AND CONFIGURATION SHALL BE AS INDICATED ON THE PANEL BOARD SCHEDULE. ALL MULTI POLE BREAKERS SHALL HAVE AN INTERNAL COMMON TRIP. 4 FEET ABOVE A.F.F ALL BREAKER LUGS SHALL BE SUITABLE TO WITHSTAND 75 DEGREE CENTIGRADE WITHOUT MALFUNCTIONING. 1 FEET, 6 INCHES A.F.F 6 FEET, 6 INCHES ABOVE A.F.F 4.3 9' ABOVE A.F.F TO BOTTOM OF THE UNIT. GUARANTEE: 3.22 ELECTRICAL RACEWAYS AND SHALL BE SIZED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (N.E.C.), ARTICLE 250. ALL BRANCH CIRCUITS SHALL HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN EACH CONDUIT RUN. ISOLATED GROUND CONDUCTORS SHALL BE ROUTED TO THOSE CIRCUITS WHICH NEED ISOLATED GROUND SPECIALLY FOR COMPUTERS AND CASH REGISTERS. 1. 2. THE CONTRACTOR SHALL PROVIDE LIGHTNING PROTECTION VOLTAGE SURGE PROTECTOR FOR ALL SERVICE PHASE CONDUCTORS TO GROUND (IF IT IS NOT ALREADY THERE IN CASE OF RENOVATIONS). DEVICE SHALL BE APT TE 400 OR APPROVED EQUIVALENT. INSTALLATION INSTRUCTIONS: 3.1 GENERAL: THE PLAN LOCATION OF LIGHTING FIXTURES, JUNCTION BOXES, CONVENIENCE OUTLETS, AND PANEL BOARDS ARE APPROXIMATE UNLESS DIMENSIONED AND ARE TO BE ADJUSTED BY THE CONTRACTOR AS REQUIRED IN THE AREAS WHERE CEILING GRID AND OTHER OBSTRUCTIONS DETERMINE FIXTURE LOCATIONS. THE CONTRACTOR SHALL COORDINATE WITH OTHER ARCHITECTURAL, MECHANICAL AND OTHER SYSTEMS TO AVOID INTERFERENCE. ALL CUTTING AND CONSEQUENT REPAIRS IN CONJUNCTION WITH THE WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. BEAMS OR OTHER STRUCTURAL COMPONENT SHALL NOT BE CUT WITHOUT THE KNOWLEDGE AND WRITTEN CONSENT OF THE ARCHITECT. 3.3 THE ELECTRICAL WORK SHALL BE EXECUTED IN ACCORDANCE WITH ALL APPLICABLE CODES AND SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING. WORKMANSHIP SHALL BE THE HIGHEST QUALITY AS ESTABLISHED BY TRADE STANDARD. 1.2.10 THE CONTRACTOR SHALL CONCEALED ALL THE CONDUIT IN THE FINISHED AREAS. 3.4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING NECESSARY PERMITS AND COMMUNICATIONS WITH THE LOCAL BUILDING DEPARTMENT AND INSPECTION PERSONNEL TO REVIEW CONTRACT DOCUMENTS PRIOR TO INSTALLATION. 3.5 OWNER WILL NOT BE HELD RESPONSIBLE FOR FIELD CHANGES THAT ARISE FROM CONTRACTOR'S ERROR OR OMISSION OF MATERIALS OR WORKMANSHIP IN WORK PERFORMANCE. DOORS SHALL NOT UNCOVER ANY LIVE PARTS WHILE MAKING SWITCHING DEVICE HANDLES ACCESSIBLE. DOORS SHALL HAVE FLUSH-TYPE CYLINDER LOCK AND CATCH, EXCEPT THAT DOORS OVER 48" IN HEIGHT SHALL HAVE AUXILIARY FASTENERS AT TOP AND BOTTOM OF DOOR IN ADDITION TO FLUSH -TYPE CYLINDER LOCK AND CATCH. DOOR HINGES SHALL BE CONCEALED. ALL LOCKS SHALL BE KEYED ALIKE. DIRECTORY FRAME AND CARD HAVING A TRANSPARENT COVER SHALL BE FURNISHED ON EACH DOOR. THE TRIMS SHALL BE FABRICATED FROM CODE GAUGE SHEET STEEL. ALL EXTERIOR AND INTERIOR STEEL SURFACES OF THE PANEL BOARDS SHALL BE PROPERLY CLEANED PRIMED AND PAINTED IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD SPECIFICATIONS AND COLOR. LUMINARIES SHALL BE AS SPECIFIED IN THE "LIGHTING FIXTURE SCHEDULE". ALL RECESSED AND LAY-IN FIXTURES SHALL BE SUPPORTED FROM THE FOUR CORNERS WITH SUPPORTS CAPABLE OF CARRYING TWICE THE WEIGHT OF THE FIXTURE. ALL SUPPORTS SHALL BE ATTACHED TO THE JOISTS AND/OR BEAMS. NO LIGHTING FIXTURE SHALL BE INSTALLED WITHIN 2 FEET OF ANY SPRINKLER HEAD. TRIMS FOR FLUSH MOUNT PANELS SHALL OVERLAP THE BOX BY AT LEAST 3/4" ALL AROUND. SURFACE MOUNT PANELS TRIMS SHALL HAVE THE SAME WIDTH AND HEIGHT AS OF THE BOX. TRIMS SHALL BE MOUNTABLE BY A SCREW DRIVER WITHOUT THE NEED FOR SPECIAL TOOLS. PANEL BOXES: THE CONTRACTOR SHALL INSTALL ALL TELEPHONE JACKS AND WIRING FROM THE MAIN TELEPHONE TERMINAL BOARD TO THE FINAL TELEPHONE OUTLETS. WIRING SHALL BE INSTALLED IN A MINIMUM 1/2 INCH CONDUIT. BOXES SHALL BE MADE FROM UNPAINTED GALVANIZED CODE GAUGE STEEL HAVING MULTIPLE KNOCKOUTS ON THE TOP AND THE BOTTOM EXCEPT WHERE NOTED OTHERWISE. BOXES SHALL BE OF SUFFICIENT SIZE TO PROVIDE A MINIMUM GUTTER SPACE OF 4" ON ALL SIDES. 3.23 THE CONTRACTOR SHALL COORDINATE WITH THE FIRE PROTECTION CONTRACTOR AND SHALL MAKE ALL NECESSARY CONNECTIONS BETWEEN DUCT SMOKE DETECTORS AND HVAC UNITS. WHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL ARE CARRIED THROUGH ITS BOX TO SUPPLY OTHER ELECTRICAL EQUIPMENT, THE BOX SHALL BE SO SIZED AS TO INCLUDE THIS WIRING SPACE. THIS WIRING SPACE SHALL BE IN ADDITION TO 3.24 ALL JUNCTION BOXES SHALL BE ACCESSIBLE FROM BELOW. OTHERWISE, CONTRACTOR SHALL PROVIDE ACCESS PANEL AT ALL JUNCTION BOX LOCATIONS AND SMOKE DETECTORS. 3.25 IF NOT ALREADY EXISTING, THE CONTRACTOR SHALL FURNISH ALL THE NECESSARY DISCONNECT SWITCHES, RELAY BOXES, AND CONTROL BOXES AS REQUIRED AND RECOMMENDED BY THE HVAC MANUFACTURER FOR THE HVAC UNIT AND WATER HEATER. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR AND MAKE ALL NECESSARY CONNECTIONS TO MAKE THE HVAC SYSTEM FUNCTIONAL. ALL ELECTRICAL EQUIPMENT, MATERIAL AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF ACCEPTANCE. 3.0 PANEL TRIM: HINGED DOORS IN PANEL TRIMS SHALL COVER ALL SWITCHING DEVICE HANDLES AND SHALL CONFORM TO THE FOLLOWING REQUIREMENTS: 4.4 2.13 CIRCUIT BREAKER: THE CIRCUIT BREAKERS ARE TO BE INDUSTRIAL MOLDED CASE BOLT ON TYPE, STANDARD THERMAL, MAGNETIC, WITH TRIP FREE MECHANISM, THREE POSITION TIME CLOCK OR TIME SWITCH: THE CONTRACTOR SHALL MAKE SURE ON A DAILY BASIS THAT ALL UNNECESSARY MATERIAL AND TRASH CONTRIBUTED BY HIS TRADE ARE REMOVED. THE ELECTRICAL CONTRACTOR SHALL PURCHASE AND USE ALL "NEW" MATERIAL AS SPECIFIED AND SHOWN ON THE ELECTRICAL PLAN OF THIS PROJECT. ALL THE MATERIAL SHALL BE FREE FROM DEFECTS AND SHALL CARRY A "UL" LABEL. THE MOUNTING ARRANGEMENT OF EACH FIXTURE WILL BE DETERMINED BY THE CONTRACTOR EXCEPT WHERE THE MANUFACTURER HAS GIVEN SPECIFIC MOUNTING INSTRUCTIONS. LIGHTING DEVICES: THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS, LABOR, TRANSPORTATION, RIGGING & HOISTING, TOOLS, AND STORAGE, ETC. FOR ALL WORK INDICATED AND REQUIRED FOR COMPLETE INSTALLATION. GENERAL: 3.13 LAMPS: 3.2 2.1 A NAMEPLATE LISTING PANEL NUMBER, TYPE, MANUFACTURER'S NAME, NUMBER OF PROTECTIVE AND SWITCHING DEVICES, VOLTAGE, CURRENT, PHASE AND AIC RATINGS SHALL BE PROVIDED. BALLASTS: THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE NECESSARY TEMPORARY ELECTRICAL POWER, AT HIS EXPENSE, AS REQUIRED BY HIS TRADE AND BY THE GENERAL CONTRACTOR. PRODUCTS: LIGHTING SWITCHES AND CONVENIENCE RECEPTACLES SHALL BE FLUSH MOUNTED IN SECTIONAL SWITCH BOXES WITH MATCHING COVER PLATES UNLESS NOTED OTHERWISE. DEVICE PLATES: ALL LIGHTING FIXTURES, EMERGENCY & EXIT LIGHTS SHALL BE AS LISTED ON THE LIGHT FIXTURE SCHEDULE; HOWEVER BEFORE PURCHASING ANY LIGHT FIXTURES, SUBMIT FIXTURE. CUT SHEETS FOR THE ARCHITECT AND THE OWNER'S APPROVAL. ONE YEAR WRITTEN WARRANTY FOR ANY DEFECT IN WORKMANSHIP, MATERIAL, AND EQUIPMENT. TWO SETS OF MANUFACTURER'S OPERATIONAL AND MAINTENANCE MANUALS IF APPLICABLE. MANUFACTURER'S WARRANTIES AND WARRANTY CERTIFICATES. TWO SETS OF REPRODUCIBLE OR RED MARKED UP PRINTS OF "AS-BUILT" DRAWINGS, ONE FOR THE ARCHITECT AND ONE FOR THE OWNER OF THE PROJECT. 2.0 3.12 RECEPTACLES: LAMPS SHALL BE MANUFACTURED BY SYLVANIA MODEL # SYL "FO28/841XP/SS/ECO OR EQUIVALENT. ALL LAMPS SHALL BE GUARANTEED FOR AT- LEAST 4 YEARS OF OPERATION AFTER THE ACCEPTANCE. PANEL BOARDS: PANEL BOARDS SHALL BE GENERAL PURPOSE N.E.M.A. TYPE 1 OR TYPE 3R ENCLOSURES SUITABLE FOR SPECIFIED INDOOR OR OUT DOOR LOCATIONS AND AND FLUSH OR SURFACE MOUNTING APPLICATIONS AS INDICATED ON THE PANEL SCHEDULE. PANEL BOARDS AND THE INTERNAL COMPONENTS SHALL BE RATED TO PERFORM THEIR FUNCTIONS CONTINUOUSLY AT 40°C AMBIENT AND 50% RELATIVE HUMIDITY. BUSSES, TERMINALS, AND LUGS SHALL BE RATED AND CAPABLE TO FUNCTION CONTINUOUSLY AT 75 DEGREES CENTIGRADE. PANEL BOARDS SHALL BE AS MANUFACTURED BY WESTINGHOUSE ELECTRIC CORP., GENERAL ELECTRIC, SQUARE 'D', CHALLENGER, OR APPROVED EQUAL. SWITCHES AND DIMMERS: BALLASTS FOR FLUORESCENT FIXTURES SHALL BE RAPID START, SYLVANIA ELECTRONIC ENERGY SAVING, HIGH POWER FACTOR AND SHALL BE CLASS "P," CBM, TITLE 24 CERTIFIED WITH INTERNAL THERMAL PROTECTOR WITH AUTOMATIC RESET AND CLASS "A" SOUND RATING NOISE LEVELS LESS THAN 30 dB MAXIMUM. BALLASTS SHALL BE MANUFACTURED BY SYLVANIA AS SHOWN ON THE LIGHTING SCHEDULE OR EQUAL EQUAL AND SHALL SHALL BE GUARANTEED AT LEAST FOR FIVE (5) YEARS OF OPERATION AFTER THE ACCEPTANCE. THE BALLAST MODEL NUMBER SHALL BE "2 OR 4 LAMP PSX-SYL Xtreme AS REQUIRED". 2.10 4.1 ALL BREAKERS, SIZED AS SHOWN ON PANEL SCHEDULE, SHALL BE BOLT-ON BREAKERS. PROVIDE DEVICE PLATE FOR EACH AND EVERY OUTLET BOX. FURNISH IN GANGS AS NECESSARY. PLATES AND SCREWS SHALL BE GRAY UNLESS THE OWNER PREFERS SOME OTHER COLOR, AND SHALL BE OF THE SAME MANUFACTURER AS OF THE DEVICES. THE CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP DRAWINGS FOR SPECIFIED PRODUCTS AT ONE TIME WITHIN THIRTY (30) DAYS FROM THE OFFICIAL NOTICE TO PROCEED. A. B. 1.2.8 3.9 RECEPTACLE SHALL BE COMMERCIAL GRADE, 125 VOLTS AC, AND 20 AMPERE RATING WITH GROUNDED POLE AND TWO CIRCUIT OPTION, AS MANUFACTURED BY LEVITON OR EQUIVALENT. PLATES SHALL MATCH THE RECEPTACLES. FURNISH IN GANGS AS NECESSARY. SHOP DRAWING SUBMITTAL SHALL BE MADE FOR THE FOLLOWING MATERIALS AND SYSTEMS: 1.2.7 SIGNAL CABLES, IF USED, SHALL BE COPPER AND SHALL MEET ALL UL AND N.E.C. CODE REQUIREMENTS. METAL CLAD (TYPE MC), ARMORED (TYPE AC) AND NON- METALLIC (NM) CABLES SHALL NOT BE USED. ALL CABLE ASSEMBLIES SHALL CONTAIN COPPER GROUND CONDUCTOR. 3.15 2.11 1.2.6 THE ELECTRICAL CONTRACTOR SHALL FOLLOW THE SAME COLOR CODE IDENTIFICATION FOR EACH PHASE THROUGHOUT THE SYSTEM FROM SERVICE SWITCH OR TRANSFORMER THROUGH ALL BRANCH CIRCUITS. SWITCHES AND DIMMERS SHALL BE TOTALLY ENCLOSED, RATED AT 120/277 VOLTS AC, 20 AMPS, 2000 WATTS WITH GRAY TOGGLE AND DEVICE PLATE. THESE SHALL BE QUIET OPERATION, COMMERCIAL GRADE AS MANUFACTURED BY LEVITON, LUTRON OR EQUIVALENT. PLATES SHALL MATCH THE SWITCHES. FURNISH IN GANGS AS NECESSARY. A) BUILDING CODE OF THE APPLICABLE CITY AND COUNTY. B) NATIONAL ELECTRIC CODE NFPA 70, 2008 C) LIFE SAFETY CODE NFPA 101, 2006 D) S.B.C.C.I. LATEST EDITION. 1.2.5 3.8 CABLE: OUTLET BOXES, FITTING CLAMPS AND HANGERS ETC. SHALL BE GALVANIZED STEEL, RUST RESISTANT AND COMPATIBLE WITH THE RACEWAY. OUTLET BOXES FOR FIXTURES, SWITCHES, AND RECEPTACLES SHALL HAVE SMOOTH ROUND EDGES AND SHALL BE WITH COVER PLATES. BOXES SHALL BE "STEEL CITY" OR EQUIVALENT. FITTINGS FOR EMT CONDUITS SHALL BE COMPRESSION TYPE. NO SET SCREW WILL BE USED. UNUSED HOLES SHALL BE COVERED WITH APPROVED INSERT CAPS. 2.6 THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL UTILITIES PLACEMENT, AS IDENTIFIED ON THE RISER DIAGRAM, AND LOCATION OF THE ELECTRICAL SERVICE EQUIPMENT. THE CONTRACTOR SHALL PAY ALL NECESSARY CHARGES ASSOCIATED WITH INSTALLATION OF ALL UTILITIES TO THE POWER COMPANY PRIOR TO THE CONSTRUCTION. A LETTER SHALL BE PROVIDED FROM THE POWER COMPANY THAT ALL THE CHARGES HAVE BEEN PAID IN FULL. NECESSARY AND OBVIOUSLY REQUIRED, ELECTRICAL ITEMS THAT ARE NOT SHOWN ON THE DRAWINGS, SHALL NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES TO INSTALL A COMPLETE AND SAFE ELECTRICAL SYSTEM. THE CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND HOT DIPPED GALVANIZED STANDARD STEEL AS MANUFACTURED BY WHEATLAND TUBE COMPANY OR EQUIVALENT. SUCCESSFUL BIDDER: THE SUCCESSFUL BIDDER WILL BE REFERENCED AS THE CONTRACTOR FROM THIS POINT ONWARDS THROUGHOUT THE REST OF THE SPECIFICATION. 3.6 3.7 BID PRICE: THE BID PRICE SHALL INCLUDE LABOR AND MATERIAL COSTS, NECESSARY INSURANCE COSTS AND PERMITS FEES AS REQUIRED TO INSTALL THE COMPLETE ELECTRICAL SYSTEM IN COMPLIANCE WITH THE DESIGN REQUIREMENTS OF THIS PROJECT. 1.1.6 2.4 MATERIAL TAKE OFF: ALL MATERIAL TAKE OFFS, OTHER THAN THE EXISTING DEVICES, SHALL BE MADE USING THE LIGHT & POWER WIRING AND CONDUIT DRAWINGS AND THEIR ASSOCIATED REFERENCES INCLUDING THE SPECIFICATIONS OF THIS PROJECT ON THIS DRAWING. ALL LIGHTING MATERIALS INCLUDING TRANSFORMER, PANELS, FIXTURES, SWITCHES, RECEPTACLES, WIRES AND RACEWAYS, ETC. SHALL BE PURCHASED BY THE CONTRACTORS PER SECTION NO. 2, UNLESS NOTED OTHERWISE. 1.1.5 2.3 EXCEPTIONS: ANY EXCEPTIONS, OMISSIONS, DISCREPANCIES, AND DOUBTS REGARDING PLANS, DRAWINGS, AND SPECIFICATIONS, IF ANY, SHALL BE COMMUNICATED PROMPTLY IN WRITING TO THE ARCHITECT OR TO THE ENGINEER FOR THEIR REVIEW AND RESPONSE BACK BEFORE THE BID SUBMISSION DATE. NO ORAL COMMUNICATION REGARDING THE EXCEPTIONS OR CHANGES SHALL BE ACCEPTED. BIDDERS SHALL BE NOTIFIED OF ANY CHANGES, IF MADE, DUE TO THE ACCEPTANCE OF EXCEPTIONS BEFORE THE BID SUBMITTAL DATE. CONDUCTORS: 1455 FRANKLIN MILLS CIR, 1.1 2.2 SPACE 852A ~ 818 SQ. FT. GENERAL PHILADELPHIA MILLS 1.0 PHILADELPHIA, PA 19154 ELECTRICAL SPECIFICATIONS AND INSTRUCTIONS FOR INSTALLATION WORK 3.26 A PLASTIC COVERED TYPE WRITTEN IDENTIFICATION CARD FOR ALL MAIN AND BRANCH CIRCUITS INCLUDING SPARES SHALL BE POSTED AT THE INSIDE OF THE PANEL DOOR. 3.27 LOCK-ON DEVICES ON PANEL CIRCUIT BREAKERS FOR NIGHT, EXIT AND EMERGENCY LIGHTING CIRCUITS SHALL BE PROVIDED AND THE SHALL BE GIVEN TO THE OWNER. 3.28 LOW VOLTAGE WIRING LOCATED ABOVE THE CEILING SHALL BE PLENUM RATED OR INSTALLED IN METAL CONDUIT. 4.0 TRANSFORMER AND PANEL BOARD SPECIFICATIONS : 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 THE MINIMUM GUTTER SPACE SPECIFIED ABOVE AND THE LIMITING WIDTH MAY BE INCREASED ACCORDINGLY. AT LEAST FOUR (4) INTERIOR MOUNTING STUDS SHALL BE PROVIDED. ALL UNUSED HOLES IN THE BOXES SHALL BE PLUGGED WITH APPROVED INSERT CAPS. BOXES SHALL BE "STEEL CITY" OR EQUAL. 4.5 DISCONNECT SWITCHES: THE CONTRACTOR SHALL INSTALL N.E.M.A. TYPE 1 DISC. SWITCHES FOR INDOOR AND N.E.M.A. TYPE 3R DISC. SWITCHES FOR OUT DOOR APPLICATIONS. ALL DISCONNECT SWITCHES FOR SERVICE CONDUCTOR ENTRANCES SHALL BE RATED AT LEAST 100K AIC. DISCONNECT SWITCHES FOR MOTOR CIRCUIT AND FIXED LOAD (SUCH AS HVAC EQUIPMENT, AND WATER HEATER ETC.) CIRCUITS SHALL BE FUSIBLE OR NON FUSIBLE AS SHOWN ON THE DRAWINGS OR REQUIRED BY THE MANUFACTURER. 4.6 FUSE: THE CONTRACTOR SHALL USE DUAL ELEMENT, TIME DELAY CURRENT LIMITING, 100,000 AMP AIC RATED, CLASS RK-1 FUSES WHEN PROTECTING PANEL BOARDS AND TRANSFORMERS AND 100,000 AMP AIC RATED CLASS RK-5 FUSES WHEN PROTECTING MOTORS UNLESS NOTED OTHERWISE OR REQUIRED DIFFERENTLY BY THE MANUFACTURER. ALL FUSES IN ANY DISC.. SW SHALL BE OF THE SAME MANUFACTURER AND SHALL BE MANUFACTURED BY BUSSMANN, GOULD SHAWMUT OR EQUIVALENT. THIS SECTION SHALL APPLY TO THE NEW TRANSFORMER, PANEL BOARDS, CIRCUIT BREAKERS, PANEL BOXES & TRIMS, DISCONNECT SWITCHES, AND FUSES. ELECTRICAL SPECIFICATIONS E3.0 COOLING LOAD: ROOF 818 SF x 15 ° x 0.031 = 380.37 BTUH OUTSIDE AIR BY MALL UNITS = BTUH LIGHTING 1500 W X 3.413 = 5119.50 BTUH PEOPLE 5 = 1250.00 BTUH = 6749.87 BTUH x 250 SUB TOTAL............................. SYMBOL/NAME WALK-IN COOLER WALK-IN FREEZER 3 COOLERS ICE M/C TOASTER GRIDDLE (GAS) FRYER (GAS) WATER HEATER RADIATION BTU/H FACTOR 3000 W 1.0 0.50 3000 W 2200 W 1500 W 6000 W 150000 BTU 110000 BTU 12000 W 1.0 1.0 1.0 0.5 1.0 1.0 0.1 0.50 0.50 0.50 0.40 0.033 0.033 0.33 SUB TOTAL............................. = 5000.00 5000.00 3751.00 2557.50 4092.00 11850.00 3630.00 43980.73 REQ'D CFM = (75-55) 1.085 = 43980.73 300 CFM BTUH BTUH OUTSIDE AIR BY MALL UNITS = BTUH PEOPLE 5 = 10"Ø D BTUH 300 CFM = 54538.45 BTUH 8X12 8X14 584 CFM 584 CFM 584 CFM 24X12 24X12 24X12 400 CFM FAN DISCONNECT, FACTORY WIRED TO MOTOR. GREASE COLLECTOR 2152 CFM 16"Ø 40" MIN VENTILATED CURB HOOD#1 (5) #10 TEK SCREWS (4) SIDES 8" MIN 18" MIN LIQUID TIGHT FLEXIBLE CONDUIT BY EC. CURB CLEARANCE FROM THE DUCT TO THE INTERIOR SURFACE OF ANY ENCLOSURE OF COMBUSTIBLE MATERIAL SHALL BE NOT BE LESS THAN 18", AND CLEARANCE FROM THE DUCT TO THE INTERIOR OF ANY ENCLOSURE OF NON-COMBUSTIBLE MATERIAL SHALL NOT BE LESS THAN 6". INSTALL PER MANUFACTURES PRODUCT LITERATURE. "PRODUCT DATA" ROOF DECK EXHAUST SYSTEM PLAN OR TRANSVERSE JOINTS) SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" 2 LAYER = 2 HOUR ESR#1255 L 3"X3"X1/4" STEEL ANGLE CLEARANCE PER NFPA 96 TWO SIDES OF CURB NOTES: 1. PROVIDE CURB EXTENSION OF HEIGHT TO RAISE FAN DISCHARGE HEIGHT TO MIN. OF 2'-0" ABOVE ANY O/A INTAKE WITHIN 10'-0". CANTILEVER STRUT CHANNEL AS REQUIRED FOR REAR HOOD SUPPORT 2'-0" MAX 2 HOUR RATED ASSEMBLY. 16 GA. GREASE DUCT NOTE: PROVIDE SIMILAR CONSTRUCTION AROUND HOOD CONT. WELD 1 58"x1 58" 14 GA MIN. STRUT CHANNEL BETWEEN BAR JOIST AT SUPPORT LOCATIONS AT BOTTOM CHORD OF EXISTING BAR JOISTS NOTE: 2. A ROOF PROTECTION SYSTEM SHALL BE PROVIDED AND INSTALLED FOR ALL KITCHEN EXHAUST SYSTEMS BY MECHANICAL CONTRACTOR. 10. INSTALL METAL SHIELD (OR COLLAR) TO SEAL DUCT AT POINT OF PENETRATION OF CEILING. 11. DUCT SYSTEM SHOULD BE INSTALLED SO GREASE CANNOT BE POCKETED. THE SYSTEM SHALL SLOPE NOT LESS THAN 14" PER FOOT TOWARD THE HOOD OR TOWARD THE GREASE RESERVOIR. (WHERE HORIZONTAL DUCT EXCEED 75' IN LENGTH THE SLOPE SHALL BE MIN. 1" PER FOOT.) A/C PLAN 3M FIRE BARRIER DUCT WRAP 615+ BLANKET FOR GREASE DUCT ENCLOSURE ASSEMBLIES RATED FIRE DUCT WRAPPING SEE DETAIL THIS SHEET ANY OPENINGS IN AN ENCLOSURE WALL SHALL BE PROTECTED BY A SELF-CLOSING DOOR OF PROPER RATING ACCORDING TO NFPA 80. (TYP = LONGITUDINAL 3" MINIMUM OVERLAP EXISTING JOIST "GREASE GUARD" GREASE CAPTURE SYSTEM F NOTE: ALL DUCT WRAP SHALL BE SEALED WITH GLASS FLASHING BY GEN. CONTR., COUNTER FLASHING BY MECH. CONTR. CAULK WEATHER TIGHT. METAL DUCTS SHALL BE FABRICATED FROM A MINIMUM 16 GAUGE BLACK STEEL AND MUST BE ASSEMBLED WITH LIQUID-TIGHT WELDED JOINTS. REINFORCE ROOF OPENING WITH 3"X3"X1/4" STEEL ANGLE AS PER TPICAL STRUCTURE FRAMING PLAN OR AS DIRECTED BY LANDLORD. 16X12 12"Ø A RESIDUE TRAP SHALL BE PROVIDED AT THE BASE OF EACH VERTICAL RISER. OPENINGS LARGE ENOUGH TO PERMIT CLEANING SHALL BE PROVIDED AT EACH CHANGE OF DIRECTION OF THE DUCT. 9. 2152 CFM 16"Ø UP TO EF-1 ON ROOF D ALL DUCTS SHALL BE INSTALLED WITH OUT FORMING DIPS OR TRAPS WHICH MIGHT COLLECT RESIDUE. CONTRACTOR SHALL PROVIDE DUCTCLEAN OUT ACCESS DOORS AT NOT MORE THAN 12'-0" O.C. AND AT EVERY CHANGE IN DIRECTION AS PER NFPA-96. 400 CFM 8"Ø D 400 CFM 5 TON OVERHEAD CANOPY TYPE HOODS SHALL BE SIZED TO COMPLETELY COVER ALL GREASE EXHAUSTING EQUIPMENT PLUS AT LEAST 6" FROM COOKING SURFACES. DUCT SYSTEMS SHALL NOT BE INTERCONNECTED WITH ANY OTHER BUILDING VENTILATION OR EXHAUST SYSTEMS NOR SHALL THEY PASS THROUGH FIRE WALL UNLESS EXPRESSLY NOTED IN THESE PLANS OR AS DIRECTED BY BUILDING REPRESENTATIVE (LANDLORD). 8. HOOD#2 12"Ø FIELD APPLIED OR FACTORY BUILT GREASE DUCT ENCLOSURE SHALL BE INSTALLED PER THE LATEST MANUFACTURER'S INSTALLATION INSTRUCTIONS AND IN COMPLIANCE WITH TERMS OF ITS LISTING. 3. MINIMUM METAL GREASE CONTAINMENT BASIN SIZE SHALL BE CALCULATED BY MULTIPLYING THE SIZE OF THE ROOF CURB BY A FACTOR OF (TWO) 2 AND ROUNDING UP TO THE NEAREST ONE (1) FOOT INTERVAL. MINIMUM SIZE SHALL NOT BE LESS THAN 48"x48". ALL END CUTS OR CUTS IN THE FOIL JACKET OF FIELD APPLIED GREASE DUCT ENCLOSURE SHALL BE SEALED PER THE MANUFACTURER'S RECOMMENDATIONS. STRUT/BEAM "U" -BOLT/CLAMP TO SECURE STRUT TO BOTTOM CHORD OF BAR JOIST 3" MIN. ALL INSTALLATIONS SHALL BE COMPLETELY ACCESSIBLE FOR VISUAL INSPECTION. EXISTING STRUCTURE FIELD VERIFY SPACING AND LOCATION AT TIME OF INSPECTION, THE FIELD APPLIED OR FACTORY BUILT GREASE DUCT ENCLOSURE INSTALLATION INSTRUCTIONS SHALL BE MADE AVAILABLE AT THE JOB SITE. 4. THE EXHAUST FAN TO BE MOUNTED WITH A HINGE KIT AND FLEXIBLE POWER CONNECTION AND SERVICE SWITCH MOUNTED ON THE CURB 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 5. THE EXHAUST FAN SHALL HAVE FAN WHEEL ACCESS PORTS ITEM SUPPLY AIR VAV-1 2000 OUTSIDE AIR RETURN AIR 400 EXHAUST AIR RATED FIRE WRAP DETAIL ROOF PROTECTION & FAN TIE DOWN DETAIL & AIR BALANCE SCHEDULE STRUCTURAL SUPPORT SCALE: NONE PRESSURE 1600 FIELD DETERMINED SCALE: N.T.S. 400 10'-0" MIN. 2000.00 2152.00 1600.00 * 2552.00 -400.00 * TO BE DRAWN FROM MALL COMMON AREA TO CREAT NEGATIVE PRESSURE 0.25 D (4" MIN. PER SMACNA) MECHANICAL FIXTURE SCHEDULE MARK EQUIPMENT NOTE: ALL DUCT WRAP SHALL BE SEALED WITH GLASS FAB AND MASTIC. A SPIN-IN FITTING WITH VOLUME EXTRACTOR AND BALANCING DAMPER WRAPPED SHEETMETAL DUCT SEE NOTE #6 IN GENERAL HAVC. SPECS. VAV-1 B SMOKE DETECTOR C SUPPLY DIFFUSER HARD DUCT HORIZONTAL HARD ELBOWS WHERE BEND EXCEEDS 45° DUCT CLAMP DUCT CLAMP INSULATED FLEXIBLE DUCT SUPPLY D 1-1/2" INSULATION WITH VAPOR BARRIER COVERING TOP SIDE OF DIFFUSER FROM NECK TO CEILING AND SEALED TO DUCT INSULATION. (R=6.0) FLEX DUCT INSTL. DETAIL SCALE: NONE SLOT DIFFUSER E RETURN AIR GRILLE F COOKING EXHAUST SYSTEM DESCRIPTION/ MANUFACTURER/ ACCESSORIES MODEL FAN POWERED VARIABLE AIR VOLUME TERMINAL WITH 9KW ELEC. HEATER S/A & R/A MOUNTED & WIRED TO SHUT DOWN HVAC UNIT & HOOD SUPPLY AIR FAN CFM AS SHOWN ON PLAN W/ 8" ROUND COLLAR W/ OPPOSED BLADE DAMPER, & 4 WAYS DISTRIBUTION. CFM AS SHOWN ON PLAN 48"X8" 4 SLOT, WITH DAMPER WITH ROUND COLLAR NOTES RECTANGULAR DUCT ENVIRO-TEC CFR SERIES MODEL CFR EH 1421 SET FOR 2000 CFM CONTACT LOCAL REP. MUST HAVE DIGITAL CONTROL SEE PLAN FOR LOCATION SF-1 18" MIN. TOTAL 1752 SEE TIE-DOWN DETAIL AND FAN STRUCTURE SUPPORT THIS SHEET. ROOF note: THE EXHAUST OUTLET SHALL BE A MINIMUM OF TEN (10) FEET FROM ADJACENT BUILDINGS, PROPERTY LINES OR AIR INTAKES (THREE (3) FEET ABOVE ANY AIR INTAKE LOCATED WITHIN TEN (10) FEET IS ALLOWED) AND FORTY (40) INCHES AWAY FROM ANY WALL. 1 2" DIA. MIN. ALL THREADED RODS TOP OF KITCHEN HOOD WITH CLIP ANGLES @ SUPPORT LOCATIONS FRESH AIR INTAKE CONICAL FITTING WITH LOCKING TYPE VOLUME DAMPER. OR SIDE WALL TAKEOFF EQUAL TO FLEXMASTER STO. PYROTRONICS SERIES 3/3X MODEL DI-B3 OR EQUAL IONIZATION TYPE UNIT. VERIFY W/L.L. FIRE ALARM SYSTEM CONTRACTOR PRIOR TO BID AND/OR CONST. RATED FIRE DUCT WRAPPING SEE DETAIL THIS SHEET CLEAN OUT ACCESS SUSPENDED CEILING GRID SYSTEM STAINLESS STL CLOSURE FROM TOP OF HOOD TO UNDERSIDE OF CEILING- PROVIDED BY HOOD MANUFACTURE, INSTALLED BY G.C. VOLUME DAMPER SEAMLESS WELDED EXHAUST DUCT CONTRACTOR SHALL PROVIDE DUCTCLEAN OUT ACCESS DOORS AT NOT MORE THAN 12'-0" O.C. AND AT EVERY CHANGE IN DIRECTION AS PER NFPA-96. 1/4" PER FOOT SLOPE 6" 1752 D SF-1 MAX. 20° TRANSITION -400 MECHANICAL PLAN, NOTES & DETAILS TITUS TDC-AA FLEX DUCT OR ROUND SHEET METAL DUCT. FLEX DUCT MAX. 5'-0" LONG, USE CLAMP TO ATTACH FLEX DUCTS AND SEAL. SUPPORT DUCT EVERY FOUR FEET FROM STRUCTURE TITUS TBDI-30 1/2"X1/2"X1/2" CUBE CORE CONSTRUCTION (EGG CRATE) TITUS 355RL SEE 'CAPTIVE AIR' SHOP DRAWINGS (H-SHEETS) FOR SPECIFICATIONS ON HOOD & FAN EQUIP. 'CAPTIVE' AIR TECH EXHAUST SYSTEMS DUCTED RETURN BRANCH DUCT DETAILS SCALE: NONE CEILING 44" max. 400 CONTRACTOR MUST PROVIDE GREASE GUARD, GREASE CONTAINMENT SYSTEM FOR ALL FANS EXHAUSTING GREASE VAPORS AT EF-1 AND EF-2. 7'-0" A.F.F. EF-2 -2152 9'-6" 2152 10'-0" EF-1 1.25 D 7. F 16"Ø LATENT TOTAL........................ = 10557.72 BTUH F 16X16 = 9307.72 EF-1 8"Ø SENSIBLE LOAD x 0.25 HOOD DUCTWORK NOTES: 6. 300 CFM 12 6X EQUIPMENT 14. A/C UNIT INSTALLATION SHALL COMPLY WITH THE MFG. SPECIFICATIONS, LANDLORD CRITERIA, MECJANICAL CODES AND CLEARANCE REQUIREMENT FOR SERVICING. 15. REINFORCE ROOF OPENING WITH 3"X3"X1/4" STEEL ANGLE AS PER TPICAL STRUCTURE FRAMING PLAN OR AS DIRECTED BY LANDLORD. 5. F 400 CFM 8"Ø UP TO EF-2 ON ROOF C LATENT LOAD: GRAND TOTAL COOLING LOAD 1752 CFM 16X16 UP TO SF-1 ON ROOF F 21.7 1250.00 F EF-2 BTUH = 2026 CFM x 250 SF-1 F 10"Ø THE USE OF FLEXIBLE DUCTS AT DIFFUSERS IS REQUIRED. FLEXIBLE DUCTS SHALL NOT EXCEED 5' IN LENGTH & MAY BE USED AS THE FINAL CONNECTION ONLY. C BTUH 6749.87 SUB TOTAL FROM ABOVE .... TOTAL POTENTIAL SENSIBLE COOLING LOAD......................................= 43980.73 PROVIDE CERTIFIED TEST AND BALANCE OF HVAC SYSTEM (AND EXHAUST SYSTEM WHERE APPLICABLE) BY L.L. APPROVED CONTRACTOR, NO LATER THAN THIRTY (30) DAYS AFTER SYSTEM IS INSTALLED TO ARCHITECT FOR APPROVAL BY LANDLORD. F 1350.36 37230.86 13. ALL H.V.A.C EQUIPMENT & DUCTS SHALL BE PROVIDED WITH VIBRATION ISOLATORS, SOUND TRAPS, DUCT LINING, ACOUSTICAL HOUSINGS, ACOUSTICAL LOUVERS ETC. 4. 300 CFM . " MIN REGISTERS, DIFFUSERS AND GRILLES SHALL BE PROVIDED IN SIZES AND LOCATIONS AS SHOWN ON DRAWINGS. CEILING & WALL MOUNTED REGISTERS, DIFFUSERS AND GRILLES SHALL BE EQUIPPED WITH GASKETS BEHIND FACE FLANGES, WHICH SHALL MAKE AN AIRTIGHT SEAL BETWEEN OUTLET AND FACE OF WALL OR CEILING. OUTLETS SHALL BE INSTALLED PLUMB, LEVEL AND PARALLEL TO BUILDING, WALLS OR FLOORS. SUPPLY DIFFUSERS SHALL BE TITUS-PAS, OR OR APPROVED EQUAL, WITH PERFORATED PANEL SIZED AS SHOWN ON DRWG.'S AND WITH DEMOUNTABLE FACES WITH PATTERN CONTROLLERS OF STEEL CONST. WITH WHITE FINISH. RETURN AND EXHAUST REGISTERS SHALL BE TITUS 50-F5 OR APPROVED EQUAL, ALUMINUM CONSTRUCTION WITH 1/2 x 1/2 x 1/2 INCH GRID AND OPPOSED BLADE BALANCING DAMPER. FINISH TO BE WHITE. USAGE RATE INPUT 12. PRIOR TO OPENING THE PREMISES FOR BUSINESS, TENANT SHALL PROVIDE L.L. W/ WRITTEN VERIFICATION FROM AN AUTHORIZED REPRESENTATIVE OF TENANT'S H.V.A.C. EQUIP. THAT TENANT'S NEW H.V.A.C. EQUIPMENT IS INSTALLED AND OPERATING IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. 3. 18X18 R/A T C 18X18 KITCHEN EQUIPMENT 11. UNLESS SPECIFICALLY NOTED IN THE ARCHITECTURAL OR MECH. DRAWINGS, ALL DUCTWORK SHALL BE INSTALLED AS HIGH AS POSSIBLE WITHIN THE PREMISES. ALL DUCTWORK, EQUIPMENT AND OTHER ACCESSORIES IN PUBLIC OR SALES AREAS SHALL BE CONCEALED. 2. CONNECT TO LANDLORD R/A DUCT, COORDINATE LOCATION IN FIELD WITH LANDLORD REPRESENTATIVE B BTUH 1420.05 ~ PHILADELPHIA, PA 19154 TOTAL HEATING LOAD............= 10. MAXIMUM CONTROL SYSTEM WIRING VOLTAGE SHALL BE TWENTY FOUR (24) VOLTS AND ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES AND LANDLORD CRITERIA. 1. 1600 CFM R/A VAV-1 BTUH 1455 FRANKLIN MILLS CIR, BY MALL UNITS 1420.05 SPACE 852A ~ 818 SQ. FT. OUTSIDE AIR = PHILADELPHIA MILLS 818 10'-0 9. SF x 56 ° x 0.031 ROOF 10"Ø 8. E MI N. SHEET METAL DUCTS SHALL BE INSULATED WITH MINIMUM 1-1/2 INCH THICK FIBERGLASS FACED DUCT WRAP BY OWENS CORNING, OR APPROVED EQUAL, HAVING AN 'R' VALUE OF 6.0 AND FACTORY APPLIED FOIL FACING AND ONE 2 INCH FLANGE. INSULATION SHALL BE INSTALLED ACCORDING TO MFR'S. RECOMMENDATIONS. INSULATION AND VAPOR BARRIER SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS AND SMOKE DEVELOPMENT RATING OF 50. ~ 18X18 70° Fdb 10"Ø 6. 14° Fdb, A SPLITTER OR BALANCING DAMPERS WHERE SHOWN, SHALL BE OF SUFFICIENT GAUGE TO PREVENT BUCKLING OR VIBRATING, AND SHALL BE OPERATED BY A QUADRANT DAMPER ADJUSTER WITH LOCKING FEATURES WHICH WILL HOLD DAMPER SECURELY IN POSITION AT DESIRED SETTING. DUCT CONNECTIONS TO EQUIPMENT SHALL BE MADE THROUGH AIRTIGHT CANVAS OR OTHER APPROVED FLEXIBLE CONNECTIONS. 75° Fdb, 50% RH HEATING LOAD: DUCTWORK SHALL BE FURNISHED AND INSTALLED IN SIZES AND LAYOUT AS SHOWN. DUCT DIMENSIONS SHOWN ARE CLEAR INSIDE DIMENSIONS. DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEET STEEL OF GAUGES AND WITH CONNECTIONS AND BRACING IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE LATEST EDITION OF SMACNA. 5. 7. WINTER Fdb, 74° Fwb '-0 " MATERIALS, EQUIPMENT, WORKMANSHIP AND ARRANGEMENT OF WORK INSTALLED BY THE CONTRACTOR SHALL CONFORM TO GOVERNING CODES, ORDINANCES AND REGULATIONS OF CITY, COUNTY AND STATE, AND SHALL BE SUBJECT TO APPROVAL OF ARCHITECT AND OR ENGINEER. 90° AIRFLOW 4. SUMMER INSIDE 16X16 3. OUTSIDE 14X16 2. BASIS OF DESIGN: ALL FEES, LICENSES, PERMITS AND INSPECTIONS REQUIRED BY LOCAL AUTHORITY SHALL BE OBTAINED AND PAID FOR BY THE CONTRACTOR AS A PART OF THIS CONTRACT. CONNECT TO LANDLORD SUPPLY AIR DUCT, COORDINATE LOCATION IN FIELD WITH LANDLORD REPRESENTATIVE 12X14 1. HVAC LOAD CALCULATIONS 10 GENERAL HVAC SPECIFICATIONS: HOOD #1 18 GAUGE S.S. F EXH, HOOD, SEE HOOD DRAWINF SHEET H-1 FOR FRONT & EQUIP. UNDER HOOD. SEE ELEVATIONS FINISHED FLOOR SCHEMATIC EXHAUST SYSTEM DIAGRAM SCALE: NONE M1.0 HOOD HANGING DETAIL SCALE: N.T.S. FILTER COLLECTION EFFICIENCY 2" Captrate Grease-Stop Solo Filter 100 90 Ohio Selected Accounts RESISTANCE VS. AIRFLOW - 2" Captrate Grease-Stop Solo Filter 70 1.6 RESISTANCE (in. H20) FILTRATION EFFICIENCY (%) 80 60 50 40 30 20 1.4 1.2 1 0.8 0.6 0.4 0.2 10 0 0 0 0.1 1 PARTICLE DIAMETER (um) 200 400 600 800 1000 10 AIRFLOW (cfm) 100 E. Campus View Blvd., Suite 250, Westerville, OH, 43082 PHONE: (614) 679-7626 FAX: (919) 800-4534 EMAIL: tim.anderson@captiveaire.com www.captiveaire.com REVISIONS DATE: DWG.#: DRAWN BY: SCALE: MASTER DRAWING * CAPTIVE-AIRE DUCT CONNECTION SIZES ARE CALCULATED USING AN EXHAUST VELOCITY OF 1500-1800 FPM AND A SUPPLY VELOCITY OF 300-400 FPM. CAPTIVE-AIRE HOODS ARE BUILT IN COMPLIANCE WITH: SHEET NO. Listed under ETL File number 3054804-001/002 SHEET NO. 100 E. Campus View Blvd., Suite 250, Westerville, OH, 43082 PHONE: (614) 679-7626 FAX: (919) 800-4534 EMAIL: tim.anderson@captiveaire.com Ohio Selected Accounts www.captiveaire.com REVISIONS DATE: DWG.#: DRAWN BY: SCALE: MASTER DRAWING 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 SHEET NO. 100 E. Campus View Blvd., Suite 250, Westerville, OH, 43082 PHONE: (614) 679-7626 FAX: (919) 800-4534 EMAIL: tim.anderson@captiveaire.com Ohio Selected Accounts 1 www.captiveaire.com REVISIONS DATE: DWG.#: DRAWN BY: SCALE: MASTER DRAWING NOTE: ~ 2"V C/O * THE DOMESTIC WATER PIPING SYSTEM SHALL BE FLUSHED WITH CLEAN POTABLE WATER UNTIL CONTAMINATED WATER DOES NOT APPEAR AT THE OUTLET AND SHALL BE FILLED WITH A SOLUTION CONTAINING 50 PPM OR CHLORINE AND ALLOWED TO STAND AS REQUIRED BY CODE BEFORE FLUSHING. THE SYSTEM SHALL BE FLUSHED COMPLETELY WITH CLEAR WATER UNTIL ALL RESIDUAL CHLORINE CONTENT IS REMOVED. CHLORINATION SHALL BE PERFORMED AFTER ALL PIPING AND FINAL CONNECTIONS AND PRESSURE TESTING HAVE BEEN COMPLETED. 2 P14 T P11-1 ~ 1 P1-1 P2 P6-1 P4 T 2"V C/O D P5 FOR WALL CONST. SEE ARCH. DWGS. C/O FLOW CONTROL THE WALK-IN COOLER / FREEZER IS SELF-CONTAINED AND DOES NOT REQUIRE A FLOOR SINK. CLEANOUT SHALL BE SAME DIA. AS MAIN (4" DIA. MAX.) P11-1 1/2" TRAP PRIMER C C1 1/8 BEND AT END OF LINE CLEANOUT 2"V C/O DRAIN BODY C1 WASTE LINE w/ LENGTH TO SUIT INSIDE CAULK P14 K12-1 DRAIN SUPPORT STRAP PIPE A T DEEP SEAL TRAP MAIN WASTE LINE FLOOR DRAIN DETAIL WALL CLEAN OUT DETAIL P8 SCALE: NONE 4 D C C SCALE: N.T.S. C/O C1 P2 T D T 2"V C/O T T 2"V C/O P5 2"V C/O PLUMBING EQUIPMENT NOTES: S 4 C1 C 1 TIE-IN PLUMBING DRAIN LINES TO EXISTING LANDLORD MAIN SANITARY WASTE LINE, CONTRACTOR TO VERIFY EXACT LOCATION IN FIELD. F 2 CONNECT NEW VENT LINES TO EXISTING LANDLORD MAIN VENT LINE, CONTRACTOR TO VERIFY EXACT LOCATION IN FIELD. G 3 CONNECT NEW WATER LINE TO EXISTING LANDLORD MAIN SUPPLY LINE. CONTRACTOR TO VERIFY EXACT LOCATION IN FIELD. FCO FLOOR CLEANOUT - ZURN NO. Z-1444, POLISHED BRONZE ACCESS COVER, DURA-COATED CAST IRON BODY. MATCH TO PIPE SIZE. 4 INSTALL 6" PVC PIPE CHASE UNDER SLAB FOR SODA LINES FROM BAG-IN BOX TO FRONT COUNTER, CONTRACTOR SHALL EXTEND PIPE UNDER THE COUNTER TO SODA MACHINE LOCATION. CO WALL CLEAN-OUT - ZURN, #Z-1441, SMOOTH STAINLESS STEEL ACCESS COVER, DURA-COATED CAST IRON D P1-1 E 5 PROVIDE BACK FLOW PREVENTER AS SHOWN OR WHEREVER BACK SIPHONAGE IS POSSIBLE. 6 FILTERED WATER TO BE SUPPLIED TO THE ICE MACHINE, SODA RACK AND ICE TEA BREWER LOCATIONS ONLY BODY. MATCH TO PIPE SIZE. GENERAL PLUMBING SPECIFICATIONS: WASTE PLAN SCALE: 1/4" = 1'-0" ISOMETRIC VIEW D FULL OPEN VALVE ON THE DISCHARGED SIDE OF METER F ~ E 3 WATER METER & SHUT OFF VALVE ABOVE CEILING. COORDINATE LOCATION IN FIELD P11-1 P14 5 HOT WATER TO FIXTURES AS SHOWN ON PLANS TYPICAL SHUT-OFF VALVE 5 P6-1 1. ALL WORK UNDER THIS HEADING SHALL BE PERFORMED AND ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH ALL RATINGS, CODES AND STANDARDS OR OTHER AUTHORITIES HAVING JURISDICTION. 2. ALL LICENSES, PERMITS, INSPECTIONS AND FEES REQUIRED FOR WORK UNDER THIS HEADING SHALL BE SECURED, PERFORMED AND PAID FOR BY THIS SUBCONTRACTOR AS A PART OF HIS CONTRACT. 3. ALL MATERIALS SHALL BE NEW, FREE FROM DEFECTS, AND FULLY EQUAL TO THE QUALITY SPECIFIED. WORK SHALL BE PERFORMED BY SKILLED MECHANICS AND WORKMANSHIP SHALL BE FIRST CLASS IN EVERY RESPECT. CONTRACTOR SHALL HAVE A COMPETENT SUPERINTENDENT (WHO IS EXPERIENCED IN THE WORK BEING INSTALLED UNDER THIS CONTRACT) IN CHARGE OF WORK AT ALL TIMES DURING CONSTRUCTION. 4. ALL PIPING SHALL HAVE THE MANUFACTURER'S NAME ROLLED INTO EACH LENGTH, OR SHALL OTHERWISE BE PROMINENTLY IDENTIFIED. AFTER CUTTING, ALL PIPE SHALL BE REAMED FULL BORE, AND ALL CUTTINGS, AND FOREIGN MATERIALS SHALL BE REMOVED BEFORE INSTALLATION. COLD WATER SUPPLY TO WATER HEATER CHECK VALVE VACUUM RELIEF VALVE, WATTS N36-M1 OR EQUAL THERMOMETER 6 K12-1 F TYPICAL PIPE UNION, DIELECTRIC IF REQUIRED FOR DISSIMILAR METALS COLD WATER PIPE TO EXPANSION TANK ELECTRIC WATER HEATER PER SPECIFICATIONS AND SCHEDULE INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE FURNISHED WITH WATER HEATER REPLACE HOSE BIBB WITH GATE OR BALL VALVE FOR DRAIN VALVE G SET WATER HEATER ON PLATFORM PROVIDED BY GENERAL CONTRACTOR ABOVE MOP SINK P4 SEAL FLOOR PENETRATION WITH FLEXIBLE WATER-PROOF MATERIAL TO COMPENSATE FOR PIPE EXPANSION FLOOR SLAB 5. ALL SANITARY WASTE AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON, WITH FITTINGS OF THE SAME WEIGHT AS THE PIPE. THE CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF SUCH UTILITIES DOES NOT INTERFERE WITH THE MALL STRUCTURE OR THE OPERATIONS OF TENANTS BELOW. UNDER GROUND PIPING TO HAVE 14" PER FOOT SLOPE. 6. FLOOR/CLG. ASSEMBLY ABOVE GRADE DOMESTIC WATER PIPE SHALL BE TYPE "L" SEAMLESS, HARD DRAWN COPPER TUBING AND TYPE "K" BELOW GRADE IN CONFORMANCE WITH ASTM B88-48. FITTINGS SHALL BE WROUGHT COPPER SUITABLE FOR 200 PSI. CONNECTIONS TO DISSIMILAR MATERIALS SHALL BE MADE WITH DIELECTRIC UNIONS. JOINTS SHALL BE 95-5 TIN ALTIMONY FOR 200 PSI. BELOW GROUND JOINTS SHALL BE BRAZED. 7. INSULATE ALL DOMESTIC WATER LINES WITH MINIMUM 1/2" FIBERGLASS INSULATION WITH AN ALL SERVICE VAPOR BARRIER JACKET WITH SEALED JOINTS. INSULATION AND JACKET SHALL HAVE A FLAME SPREAD RATING OF NOT OVER 25 W/O EVIDENCE OF CONTINUED PROGRESSIVE COMBUSTION AND A SMOKE DEVELOPED RATING OF NOT MORE THAN 50. ROUTE DRAIN PIPES TO DISCHARGE INTO MOP SINK WITH 6" AIR GAP REFER TO SPECIFICATIONS, SCHEDULES AND NOTES FOR MORE INFORMATION. PIPING ARRANGEMENT SHOWN IS SCHEMATIC; ADJUST AS REQUIRED TO SUIT ACTUAL CONDITIONS. VERIFY CONNECTION SIZES AND LOCATIONS WITH WATER HEATER FURNISHED. REFER TO FLOOR PLANS FOR PIPE SIXES. PROVIDE SEISMIC STRAP OR BRACING IF/AS REQUIRED BY LOCAL AUTHORITIES. PROVIDE HEAT TRAP AND AUTOMATIC VACUUM RELIEF VALVE WHEN REQUIRED BY LOCAL AUTHORITIES. P7-1 STUB ELBOWS ABOVE FLOOR AT LOCATIONS SHOWN ON PLAN, 2" ON CARBONATOR AND, 2" ON DISPENSER END: TRIM ELBOWS PROVIDE HARD COPPER RELIEF VALVE DISCHARGE PIPE FULL SIZE OF VALVE OUTLET PROVIDE DRAIN PAN WITH SEPARATE 3/4" DRAIN TO FLOOR SINK SEAL TO CABINET WITH SILCONE APPROX. 12" LENGTH AS REQUIRED SIX INCH PVC CONDUIT AND FITTINGS WITH WELDED JOINTS. USE MINIMUM QUANTITY OF FITTINGS. PROVIDE LONG SWEEP ELBOWS AT BOTH ENDS, WITH MINIMUM 24" RADIUS. AVOID ELBOWS IN HORIZONTAL RUN IF AT ALL POSSIBLE. CUT CONCRETE FLOOR SLAB & REPAIR WATERPROOFING, PATCH SLAB PER LANDLORD'S REQUIREMENTS. GENERAL CONTRACTOR SHALL SEAL ENDS OF CONDUIT WITH FOAM AFTER SYRUP LINE IS INSTALLED IN CONDUIT. SODA CONDUIT 4 SCALE: N.T.S. WATER HEATER INSTALATION DETAIL 8. ALL FIXTURES SHALL HAVE INDIVIDUAL FIXTURE CONTROL VALVES WHICH SHALL BE CRANE, WATTS, NIBCO OR APPROVED EQUAL. VALVES OF EACH TYPE, SUCH AS GATE OR GLOBE, SHALL BE THE PRODUCTS OF ONE MANUFACTURER. VALVES SHALL BEAR THE NAME OR TRADEMARK OF THE MANUFACTURER AND THE WORKING PRESSURE CAST OR STAMPED ON THE VALVE BODY. MIN. 125 PSI. ALL VALVES SHALL BE ACCESSIBLE FOR EASE OF OPERATION. 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 9. PROVIDE DIELECTRIC FITTINGS BETWEEN PIPING OF DISSIMILAR METALS AND AT WATER HEATER CONNECTIONS. 10. PROVIDE 1/2" THICK FLEXIBLE UNICELLULAR FIRE RETARDANT INSULATION ON EXPOSED LAVATORY TRAP AND EXPOSED HOT AND COLD WATER SUPPLY AND ANY MISCELLANEOUS PIPING SUCH AS CONDENSATE PIPING. ALL JOINTS SHALL BE INSULATED AND SEALED WITH VAPOR BARRIER CEMENT. 11. ALL PIPING, PIPE HANGERS, CLAMPS, SUPPORTS, ETC. SHALL BE FASTENED TO JOISTS OR BEAMS. WHERE PIPING IS SUSPENDED FROM STEEL JOISTS, THE CONNECTION SHALL BE MADE AT THE TOP CHORD OF JOIST. PIPE SUPPORTS SHALL BE SPACED MO MORE THAN 10 FEET APART. NOTHING SHALL BE ATTACHED DIRECTLY TO THE DECK, CEILING SYSTEM OR DUCT WORK ABOVE. SCALE: NONE 12. HANGERS SHALL NOT PIERCE PIPING INSULATION VAPOR BARRIER. 13. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO THE FIRE PROOFED STRUCTURAL STEEL SERVING THE FIRST FLOOR. 14. ALL HANGERS, RODS, BEAM CLAMPS ETC. EXPOSED TO PUBLIC VIEW SHALL BE PAINTED TO MATCH ADJACENT FINISHES AND BE MANUFACTURED BY F&M, GRINNEL, OR CENTRAL FOUNDRY. P8 6 G FLOW TO FIXTURE P2 F F SYMBOL CODE 5 6 P5 COLD WATER PIPING HOT WATER PIPING FILTERED WATER PIPING S AUTOMATIC TRAP PRIMER VALVE-MOUNT IN CW SUPPLY LINE OF FREQUENT USED FIXTURE NEAR FLOOR DRAIN(S) SUPPLIED 12" MINIMUM TO HORIZONTAL RUN IN PIPING 5 PHILADELPHIA, PA 19154 A P8 1455 FRANKLIN MILLS CIR, 2"V ADJUSTABLE DRAIN HEAD POLISHED S.S. ACCESS COVER FLUSH w/ WALL SPACE 852A ~ 818 SQ. FT. CLEANOUT TEE FLOW CONTROL VENT P7-1 COUNTERSUNK SCREW P4 2"V SLOPE FLOOR FINISH TO DRAIN - 1/4"/FT. MIN. PHILADELPHIA MILLS T 2"V C/O P6-1 STRAINER, FLUSH w/ FLOOR CLEANOUT PLUG MAY EXTEND AS WASTE OR VENT 1 2" COPPER TUBING - RUN UNDERFLOOR TO FLOOR DRAIN(S) 15. THE CONTRACTOR SHALL ENSURE THAT ALL SLAB PENETRATIONS WITHIN THE TENANT SPACE (AND THROUGH THE ROOF) ARE PROPERLY SEALED AND REMAIN WATERTIGHT TO PREVENT POSSIBLE WATER LEAKAGE AND/OR DAMAGE. ANY DAMAGE CAUSED FROM FAILURE TO DO SO SHALL BE A CONTRACTOR'S SOLE RISK AND EXPENSE. ALL ROOF AND SLAB PENETRATIONS MADE BY THE CONTRACTOR ARE SUBJECT TO L.L. APPROVAL AS TO LOCATION AND CONSTRUCTION DETAILS. ALL PENETRATIONS IN ROOF AND CEILING SHALL BE FIRE CAULKED. 16. PROVIDE CAST BRASS OR CHROME ESCUTCHEONS WITH SET SCREW DEEP TYPE, TO COVER SLEEVES OR OF A SIZE TO COVER FITTING PROJECTIONS, PROVIDE ESCUTCHEONS FOR ALL EXPOSED PIPING THROUGH WALLS, FLOORS, AND EXPOSED CEILINGS. 17. THE CONTRACTOR SHALL CORE DRILL EXISTING FLOOR SLAB AS REQUIRED FOR INSTALLATION OF UNDERSLAB UTILITIES. CONTRACTOR MUST COORDINATE ALL INSTALLATION OF BELOW-SLAB SERVICES WITH L.L. ALL MODIFICTIONS TO THE SLAB SHALL BE REPAIRED BY APPROVED L.L. METHODS THAT MEET OR EXCEED THE ORIGINAL SLAB DESIGN INCLUDING WATERPROOFING. THE CONTRACTOR SHALL PROPERLY SLEEVE AND SEAL ALL PENETRATIONS TO COMPLY WITH L.L AND CODE REQ.'S. FLOOR SLAB FLOOR DRAIN (SEE PLANS) 18. ALL UTILITIES NOT RE-USED SHALL BE CAPPED-OFF AND REMOVED. DISPOSAL SHALL BE PER L.L. APPROVED METHOD(S). NO UTILITES SHALL BE ABANDONED IN PLACE. INDIRECT WASTE PIPING PLUMBING WATER AND WASTE PLANS 19. CO ORDINATE ALL PENETRATIONS FLOOR, DRAINS/SINKS W/ WATERPROOFING OF SLAB SAN. WASTE PIPING EXIST. SAN. WASTE PIPING WASTE VENT PIPING UNION WATER PLAN CONNECT TO EXISTING ISOMETRIC VIEW TYPICAL FOR ALL FLOOR DRAINS & FLOOR SINKS UNLESS NOTED OTHERWISE ON DRAWINGS T & P RELIEF VALVE VALVED WATER TAP SCALE: 1/4" = 1'-0" P1.0 TRAP PRIMER CONNECTION IN FLOOR DRAIN SHUT OFF VALVE TRAP PRIMER CONNECTION DETAIL SCALE: N.T.S. C1 GAS EQUIPMENT SCHEDULE 180,000 110 3/4" 110,000 122 1 1" 122,000 2" 2" 2 ANSUL PULL TIED TO ANSUL SYSTEM P14 2" 2" 412,000 ~ 412.00 TOTAL TO MAKE-UP AIR UNIT ON ROOF VERIFY DISTANCE TO METER IN FIELD PRIOR TO SUBMITTING BID. COORDINATE THE EXACT ROUTING WITH THE LANDLORD'S FIELD REPRESENTATIVE. DEMAND PRESSURE = 10" W.C. DOWNSTREAM OF METER OR REGULATER 1" 2" 122 CFH 1 2" 2" 1-1/4" 1-1/2" 2" 1-1/2" 2" 1-1/2" 2" C/O 2" GAS SERVICE NOTE 2" P4 1-1/4" 2" THE CONTRACTOR SHALL VERIFY THE SIZE OF THE EXISTING SERVICE AND GAS METER. THE CONTRACTOR IS RESPONSIBLE FOR REPLACING EXISTING COMPONENTS IF THEY ARE INADEQUATE FOR THE NEW REQUIREMENTS OR INOPERABLE. COORDINATE REPLACEMENT COMPONENT SPECIFICATIONS WITH THE LANDLORD FIELD REP. AND LOCAL UTILITY. 2" C/O 3" 4" C/O 3" C C1 3" P5 P8 P1-1 K2-1 110 CFH 3/4" 4" TYPICAL 6" DIRT LEG C/O 1" 1-1/4" D 2" C/O C/O 2" K1-1 4" 3" 4" 1-1/4" P2 3" 180 CFH NOTE: P1-1 ALL GAS PIPING GOING TO MOVABLE EQUIPMENT SHALL HAVE A QUICK DISCONNECT AND SAFETY CHAIN (SHORTER THAN GAS LINE). 3" FLOW CONTROL 3/4" G WITH GAS SHUTOFF AND QUICK CONNECT FITTINGS TO FRYER CONFIRM CODE RESTRICTIONS FOR LOCATING GAS PIPING IN RETURN AIR PLENUM. ROOF- MOUNTED GAS PIPING SHALL BE INSTALLED ON FACTORY FABRICATED ROOF EQUIPMENT SUPPORTS EVERY 5' OR AT ELBOWS. ALL GAS PIPING SHALL BE FINISHED WITH TWO COATS OF A RUST INHIBITIVE PRIMER, ONE COAT OF FINAL PAINT (COLOR PER L.L.) AND IDENTIFICATION LABELS. A 1" 2" THE SYSTEM SHALL AUTOMATICALLY SHUT ALL THE SOURCES OF FUEL & HEAT TO ALL EQUIPMENT PROTECTED BY THE SYSTEM. SHUT-OFFS, VALVES, AND SWITCHES SHALL REQUIRE MANUAL RESET. ~ THE TENANT'S CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AVAILABLE CAPACITY, PRESSURE, SERVICE CONNECTION, UTILITY METER INSTALLATION, ETC., WITH THE LOCAL UTILITY AND THE LANDLORD. 1 4" 2" ALL FITTINGS USED IN CONNECTION WITH THE ABOVE PIPING SHALL BE OF MALLEABLE IRON, YELLOW BRASS (CONTAINING NOT MORE THAN SEVENTY- FIVE (75) PERCENT COPPER) 4" D C/O P7-1 1-1/4" ALL SUCH PIPE SHALL BE EITHER NEW OR SHALL PREVIOUSLY HAVE BEEN USED FOR NO OTHER PURPOSE THAN CONVEYING GAS. IT SHALL BE IN GOOD CONDITION AND FREE FROM INTERNAL OBSTRUCTIONS. BURRED ENDS SHALL BE REAMED TO THE FULL BORE OF THE PIPE. 4" 4" FLOW CONTROL VENT 2" ALL PIPING USED FOR THE INSTALLATION, EXTENSION, ALTERATION, OR REPAIR OF ANY GAS PIPING SHALL BE SCHEDULE 40 BLACK STEEL,ASTMA 120 w/150 LB. BANDED MALLEABLE IRON SCREWED FITTINGS. GAS CONSTRUCTION NOTES 4" 2" 2" AUTOMATIC GAS SOLENOID VALVE TIED TO ANSUL SYSTEM 3" C/O 1-1/4" MATERIAL FOR GAS PIPING P11-1 1-1/2" 2" 1-1/2" GAS SHUT OFF VALVE ALL VALVES AND APPURTENANCES USED IN CONNECTION WITH THE ABOVE PIPING SHALL BE OF A TYPE DESIGNED AND APPROVED FOR USE WITH FUEL GAS. P6-1 2" TENANTS REQUIRING GAS SERVICE SHALL CONTACT THE LOCAL GAS UTILITY TO MAKE ARRANGEMENTS FOR SERVICE. IF NOT EXISTING, METERS SHALL BE LOCATED AS DETERMINED BY THE LANDLORD. IF NOT EXISTING, PIPING FROM THE METER TO THE TENANT SPACE SHALL BE THE RESPONSIBILITY OF THE TENANTS CONTRACTOR AS SHALL BE THE COORDINATION OF SUCH INSTALLATION WITH THE LANDLORD. PIPING SHALL CONFORM TO ASTM-A-120 STANDARDS AND SHALL BE SCHD. 40 BLACK STEEL THROUGHOUT WITH ALL HIGH PRESSURE CONNECTIONS GREATER THAN 2.5" DIA. WELDED. NO VALVE SHALL BE PLACED IN THE RETURN AIR PLENUMS. DISCHARGE PRESSURE DOWNSTREAM OF THE PRESSURE REGULATOR SHALL BE 7" W.C. PHILADELPHIA, PA 19154 MAKE-UP AIR UNIT 3/4" 2" 1455 FRANKLIN MILLS CIR, 1 180 2" SPACE 852A ~ 818 SQ. FT. FRYER BTUH PHILADELPHIA MILLS 1 GRIDDLE K2-1 CONN. SIZE DISTANCE CFH TO METER REQUIRED ~ K1-1 EQUIPMENT 2" ~ MARK COORDINATE WITH LANDLORD AND LOCAL GAS COMPANY TO PROVIDE SERVICE TO THE SPACE. INSTALL 2" GAS LINE TO GAS METER AT ±250' DISTANCE FROM LAST PIECE OF GAS EQUIPMENT. VERIFY DISTANCE IN FIELD 3/4" G WITH GAS SHUTOFF AND QUICK CONNECT FITTINGS TO GRILL C/O 4 4 3" C1 C GAS PIPING ISOMETRIC WASTE ISOMETRIC SCALE: N.T.S. SCALE: N.T.S. ROOF G CEILING DO NOT INSTALL VALVES IN CEILING SPACE GAS COCK WITH LEVER HANDLE EXHAUST HOOD FULL OPEN VALVE ON DISCHARGED SIDE OF METER 3/4" COORDINATE WITH LANDLORD AND LOCAL GAS COMPANY TO PROVIDE SERVICE TO THE SPACE. INSTALL 2" GAS LINE TO GAS METER AT ±250' DISTANCE FROM LAST PIECE OF GAS EQUIPMENT. VERIFY DISTANCE IN FIELD 3/4" ~ 3/4" 1/2" PIPE DROP OF SIZE AND AT LOCATION SHOWN ON PLAN 3/4" ~ FLEXIBLE APPLIANCE CONNECTOR FURNISHED BY OTHERS AND INSTALLED BY PLUMBING CONTRACTOR WITH SWIVEL JOINTS IN BOTH ENDS. QUANTITY AND SIZE OF CONNECTIONS AS REQUIRED BY EQUIPMENT SERVED. PROVIDE GAS COCK LOCATED WHERE ACCESSIBLE BESIDE OR ABOVE EQUIPMENT. PLUMBING CONTRACTOR SHALL INSTALL AUTOMATIC GAS SHUT-OFF VALVE FURNISHED BY OTHERS 3/4" 3/4" E P14 GAS PIPE HEADER ALONG WALL BEHIND COOKING EQUIPMENT, APPROXIMATELY 12" ABOVE FLOOR, WITH SCREWED FITTINGS, SIZES AS SHOWN ON PLANS 3 1/2" WATER METER & SHUT OFF VALVE ABOVE CEILING. COORDINATE LOCATION IN FIELD G FLOOR TYPICAL 6" DIRT LEG TYPICAL PIPE SUPPORT ANCHORED TO WALL TYPICAL 6" DIRT LEG 3/4" 1/2" 1/2" 1/2" PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT ACTUAL CONDITIONS. ATTACH RISER AND HEADER TO WALL WITH 1" CLEARANCE BEHIND PIPE. MAKE FINAL CONNECTION TO EQUIPMENT AS RECOMMENDED BY MANUFACTURER. INSTALL ANY GAS PRESSURE REGULATORS FURNISHED BY FOOD SERVICE EQUIPMENT CONTRACTOR. 4410 W. MELROSE AVENUE TAMPA, FLORIDA 33629 TEL. 813.333.2717 FAX. 813.289.3332 3/4" 1/2" 1/2" COOKING APPLIANCE GAS PIPE F TO MAKE-UP AIR UNIT ON ROOF 3/4" ~ SCALE: N.T.S. 1/2" 5 P11-1 1/2" P6-1 3/4" 1/2" 1/2" GAS SHUT OFF VALVE AUTOMATIC GAS SOLENOID VALVE TIED TO ANSUL SYSTEM K12-1 F G 1/2" 6 5 P4 ANSUL PULL TIED TO ANSUL SYSTEM 3/4" 1/2" P7-1 SYMBOL CODE ONE BACKFLOW PREVENTER SHALL BE LOCATED BEFORE THE WATER FILTER AND ONE BEFORE THE ICE MACHINE TO PREVENT CONTAMINATION OF THE WATER SUPPLY WHEN THE FILTERS ARE BEING SERVICED. 1/2" COLD WATER PIPING HOT WATER PIPING FILTERED WATER PIPING 1/2" 3/4" G WITH GAS SHUTOFF AND QUICK S CONNECT FITTINGS TO FRYER K2-1 INDIRECT WASTE PIPING 3/4" SAN. WASTE PIPING 1/2" WASTE VENT PIPING G F SHUT OFF VALVE P8 P5 UNION 1/2" 5 CONNECT TO EXISTING 3/4" G WITH GAS SHUTOFF AND QUICK CONNECT FITTINGS TO GRILL GAS PLAN SCALE: 1/4" = 1'-0" F ISOMETRIC VIEW TIE-IN PLUMBING DRAIN LINES TO EXISTING LANDLORD MAIN SANITARY WASTE LINE, CONTRACTOR TO VERIFY EXACT LOCATION IN FIELD. 2 CONNECT NEW VENT LINES TO EXISTING LANDLORD MAIN VENT LINE, CONTRACTOR TO VERIFY EXACT LOCATION IN FIELD. 3 CONNECT NEW WATER LINE TO EXISTING LANDLORD MAIN SUPPLY LINE. CONTRACTOR TO VERIFY EXACT LOCATION IN FIELD. 4 INSTALL 6" PVC PIPE CHASE UNDER SLAB FOR SODA LINES FROM BAG-IN BOX TO FRONT COUNTER, CONTRACTOR SHALL EXTEND PIPE UNDER THE COUNTER TO SODA MACHINE LOCATION. WATER ISOMETRIC 5 PROVIDE BACK FLOW PREVENTER AS SHOWN OR WHEREVER BACK SIPHONAGE IS POSSIBLE. SCALE: N.T.S. 6 FILTERED WATER TO BE SUPPLIED TO THE ICE MACHINE, SODA RACK AND ICE TEA BREWER LOCATIONS ONLY 6 T & P RELIEF VALVE VALVED WATER TAP 1 ONE BACKFLOW PREVENTER SHALL BE LOCATED BEFORE THE WATER FILTER AND ONE BEFORE THE SODA SYRUP RACK TO PREVENT CONTAMINATION OF THE WATER SUPPLY WHEN THE FILTERS ARE BEING SERVICED. K1-1 EXIST. SAN. WASTE PIPING PLUMBING EQUIPMENT NOTES: 5 P2 6 PLUMBING WATER AND WASTE ISOMETRICS GAS PLAN AND ISOMETRIC P2.0