04/30/10 DESIGN NO. 012090 SECTION 16010 GENERAL PROVISIONS FOR ELECTRICAL WORK PART 1 - GENERAL 1.01 SCOPE OF WORK A. Provide labor, materials, tools, machinery, equipment, and services necessary to complete the Electrical Work under this Contract. All systems and equipment shall be complete in every aspect and all items of material, equipment and labor shall be provided for a fully operational system and ready for use. Coordinate the work with the work of the other trades in order to resolve all conflicts without impeding the job progress. B. When an item of equipment is indicated on a floor plan and not shown on associated riser diagram or viceversa, the Contractor shall provide said item and all required conduit and wiring connections for a complete system as part of the Contract. 1.02 EXAMINATION OF SITE A. The Contractor shall be held to have examined the site and to have compared it with the Drawings and Specifications, and deemed to have been satisfied as to the conditions existing at the site, as relating to the actual conditions of the site at the time estimating the Work, the storage and handling of materials, and all other matters as may be incidental to the Work under the Contract, before bidding, and no allowance will subsequently be made to the Contractor by reason of any error due to the Contractor's neglect to comply with the requirements of this clause. 1.03 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract. B. Division 1 - General and Supplementary Requirements. 1.04 ELECTRICAL EQUIPMENT A. All electrical equipment shall be the latest of the current year in design, material and workmanship, and shall be the type or model called for in these Specifications. B. If the type or model specified has been superseded by a later type or model, the latest shall be submitted for approval and shall be provided as part of the Contract. NYCSCA GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 1 04/30/10 DESIGN NO. 012090 1.05 SUBMITTALS Provide as outlined in each individual section Specifications, including but not limited to: of these A. Product Data: Submit manufacturer's product data for equipment including capacity, performance charts, test data, materials, dimensions, weights, and installation instructions. B. Shop Drawings: Submit manufacture's shop drawings indicating dimensions, weight loading, required clearances, location, and method of assembly of components. Submittals are mandatory as noted in the respective specifications. Schedules, installation instructions, startup manuals, operation and maintenance manuals, and shop drawings are always required to be submitted. C. Samples D. Special Warranty E. Quality Assurance submittals F. Operation and Maintenance Manuals G. Test results and certificates H. Manuals and video tape of the personnel training. 1.06 COORDINATION DRAWINGS A. Coordination Drawings; The Electrical contractor shall cooperate with the HVAC, P&D, and Fire Protection Systems contractors in the development of the coordination drawings. The drawings, indicating ductwork, steam, hydronic & fuel piping, etc. shall be generated by the HVAC contractor, who in turn is to provide them to the hiecurical contractor for the inclusion of electrical work in this coordination set. This is after the P&D and Fire Protection Systems contractors have entered their information in the set. The specified order in which the trade contractors impose their work on the coordination drawings is not intended to grant priority to any one trade contractor in the allocation of space. At the completion of this phase, hold a coordination meeting to eliminate any interference among the trades that the drawings indicate and to avoid any conflicts in installing the Work. NYCSCA GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 2 04/30/10 DESIGN NO. 012090 1.07 BUREAU OF ELECTRICAL CONTROL A. B. C. Drawings and Specifications: 1. The Contract Drawings and Specifications shall be submitted by the Contractor to the Bureau of Electrical Control to facilitate any inspections that may be made by that agency. 2. It is the intent of these Specifications that all electric work shall be done in strict accordance with the rules of the Bureau of Electrical Control, and with the NYC Amendments to the 2005 National Electrical Code together with NEPA's 2005 National Electrical Code. Where the requirement of the Drawings or Specifications exceeds the requirements of the Electrical Code, the requirements of the Drawings and Specifications shall be binding upon the Contractor. 3. Should the Bureau of Electrical Control inspect the work and issue a violation, the Contractor shall correct the Work and eliminate the violation as part of the Contract. Interpretation 1. The electric work detailed in these Specifications and shown on Drawings shall be under the jurisdiction of the Authority, subject to the approval of the Bureau of Electric Control. 2. The Authority shall be the sole source for interpretation of the Contract Documents. Any discrepancies or conflicts shall be brought to the attention of the Authority for clarification. Materials and Appliance: All materials and appliance shall be approved by the Authority's Representative and installed in accordance with the rules and regulations of the Building Department, Bureau of Electrical Control; certificates of approval the temporary light and power wiring, shall including be obtained by the Contractor and delivered to the Authority's Representative before the Work is finally accepted. 1.08 WORK IN EXISTING BUILDINGS A. NYCSCA The Contractor is referred to Section 01900 on General Requirements of Work in Existing Structures which shall apply to the Work of this Contract. GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 3 04/30/10 DESIGN NO. 012090 B. Refer to Section S01900 on the "Ownership of Removed Materials." Generally that article shall apply except for those items which are listed here in for delivery to the Bureau of Shops at 44-36 Vernon Boulevard, Long Island City, New York 11101. All other existing material, fixtures, and equipment which have been removed shall not be used again unless specifically required by the Drawings or Specifications. C. Removals, Replacements, Adjustments D. 1. The Contractor shall remove, relocate, replace, adjust or adapt, all existing conduit, wiring and other electric equipment or apparatus, as required, to provide a complete installation. 2. The Work shall include, providing all materials, all necessary extensions, connections, cuttings, repairing, adapting and other Work incidental thereto, together with such temporary connections as may be required to maintain service pending the completion of the permanent Work. All Work shall be left in good working order and in a condition equal to the adjacent new or existing Work. Care in Removing Existing Conductors 1. E. The Contractor shall use due care and diligence in removing existing conductors from existing conduits in order to prevent conductors from breaking and becoming an irretrievable obstruction within the conduits. Cutting and Repairing 1. Whenever the cutting, or drilling, or removal of any part of the structure (ceilings, walls, floors, shelving, bookcases, partitions, etc.), is required in order to remove, relocate, alter or install any article of electrical equipment (including conduits, boxes, fittings, etc.), the Contractor shall perform all cutting, drilling, etc., and remove the section of structure required. After removal and installation of the electric equipment, the Contractor shall repair the section of structure as directed by the Authority's Representative, with new materials, equal to that of adjacent structure of the same type. Note that in general, all holes through existing structures for conduit installation shall be core drilled, unless prior written approval is provided by the Authority. NYCSCA GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 4 04/30/10 DESIGN NO. 012090 Contractor shall drilling to infrastructure. use avoid extreme damaging care the when core existing 2. Whenever holes are cut in fire-rated walls or floor slabs in order to permit the installation of conduit or electrical equipment, these holes shall be repaired with material that will restore the fire rating of the wall or floor slab to its original condition. 3. The Contractor shall paint all repaired areas of the building. The paint shall match the paint of adjacent surface areas, or extend to the nearest architectural break-line, as directed. 4. Wherever any part of the structure is marred or damaged, the Contractor shall repair the damaged or marred areas of the structure. 5. Where a piece of electrical equipment is removed, the Contractor shall finish that part of the surface to match surroundings. F. Damaged Apparatus: Should any damage, due to the execution of this Contract, occur to the furniture, fixtures, or any equipment or apparatus, such damage shall be properly repaired and/or replaced by the Contractor without charge. G. Non-Interruption of Services 1. It is imperative that all existing services (electric, light, power, fire alarm, telecommunications, etc.) be kept in operation at all times, unless prior written approval is received from the Authority. 2. Provide fire watch services, as necessary, during disruption of fire alarm system. 1.09 TESTS A. NYCSCA The Contractor shall demonstrate to the Authority operation of all equipment and systems. All tests shall be completed to the satisfaction of the Authority. Each test shall be performed as indicated in the individual specification section. GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 5 04/30/10 DESIGN NO. 012090 1.10 GUARANTEES, WARRANTIES, BONDS, AND MAINTENANCE CONTROL A- Refer to Section G01740 for procedures and submittal requirements for warranties. Refer to individual equipment specifications for warranty requirements. 1. Compile and assemble the warranties specified for Electrical work into a separated set of documents, tabulated and indexed for easy reference. 2. Provide complete warranty information for each item to include product or equipment including duration of warranty or bond; and names, addresses, and telephone numbers and procedures for filing a claim and obtaining warranty services. 3. Warranties for the equipment, workmanship and materials should be provided for the period of one year with the exception of the warranty on the refrigeration compressors. Five(5) years warranty shall be provided for the refrigeration compressors. 4. Manufacturers', in addition to Contractors' warranties, shall be provided for all Electrical equipment and accessories. 5. All warranties are to Substantial Completion. start from the date of 1.11 OPERATIONS, TRAINING, AND MAINTENANCE MANUALS A. General 1. Refer to Section S01730: SYSTEMS OPERATION AND MAINTENANCE MANUAL for procedures and requirements for preparation and submittal of operation and maintenance manuals for each equipment. Refer to individual equipment specifications for mainteniance manual additional requirements. In addition, include the following information: NYCSCA 2. Description of function, normal operating characteristics and limitations, performance curves, engineering data and tests, and complete nomenclature and commercial numbers of all replaceable parts. 3. Manufacturer's printed operating procedures to include start-up, break-in, routine and normal operating instructions; regulation, control, stopping, shut-down, and emergency instructions; and summer and winter operating instructions GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 6 04/30/10 DESIGN NO. 012090 4. Maintenance procedures for routine preventative maintenance and troubleshooting; disassembly, repair, and reassemble; aligning and adjusting instructions. 5. Servicing instructions and lubrication charts and schedules. B. Bind all the other Sections maintenance manuals in a single final Operating and Maintenance Manual with the requirements of Section S01730: SYSTEMS OPERATION AND MAINTENANCE MANUAL. C. Refer to Section S01650: FACILITY START-UP, DEMONSTRATION AND TRAINING for procedures and requirements for training on each equipment. Refer to individual equipment specifications for the additional training requirements. D. Contractor shall videotape all the training sessions for various equipment and systems as specified in individual sections of these Specifications. If a manufacturer's particular equipment item is furnished with a training video, the manufacturer's video shall be provided in addition to the requirements of this Section, not in lieu thereof and at no additional cost to the Authority. Contractor shall be responsible for providing informative videotapes covering all the materials and content outlined in each individual section of these Specifications. 1.12 CLEANING AND REPAIR A. On completion of installation, inspect interior and exterior of installed equipment. Remove paint splatters and other spots. Vacuum dirt and debris; do not use compressed air to assist in cleaning. Repair exposed surfaces to match original finish. B. Contractor shall not leave sharp exposed metal edges (bottom of threaded rods, electrical equipment supports, etc.) that could otherwise present safety hazards to the building's occupants/work staff. 1.13 SEISMIC RESTRAINT - NOT USED 1.14 EMS/DDC COORDINATION - NOT USED 1.15 SPECIAL INSPECTIONS A. NYCSCA Refer to Section S01400 for requirements. GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 7 04/30/10 B. DESIGN NO. 012090 The following Special Inspection is required by the NYC Building Code for the Electrical Trade: Item Code Section Fire Alarm Test BC 907 BC 1704.13 END OF SECTION NYCSCA GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 8 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data Shop Drawings Samples Special Warranty Quality Assurance submittals Operation and Maintenance Manuals Test results and certificates Manuals and video tape of the personnel training. NYCSCA GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 9 - THIS PAGE INTENTIONALLY LEFT BLANK - 04/30/10 DESIGN NO. 012090 SECTION 16120 WIRING SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION OF WORK Install all conductors as required for the proper operation of the various systems specified. All connections shall be made complete, and all systems shall be energized and tested for proper operation. 1.02 QUALITY ASSURANCE A. Wire manufactured over one year prior to the site will not be accepted. B. Tapes for splices or termination shall be dated by the tape manufacturer to indicate that they have been manufactured no longer than six months prior to use in the Work of this Section. delivery to 1.03 DELIVERY, STORAGE, AND HANDLING A. Conductors shall be delivered at the building in original packages or on reels, and shall have the tag of the manufacturer attached thereto indicating; Contractor's name, Project title and number, Date of manufacturing. B. Store material in a clean, dry space and protect from weather. 1.04 SUPPLEMENTAL SUBMITTALS A. Submit a Product Schedule indicating the item description and manufacturer name. The Schedule will be accepted by the Authority for record purposes only, provided that the items are in full compliance with the Specifications. B. Certificates Provide affidavit stating that all listed and meet the specifications. NYCSCA items used are UL WIRING SYSTEMS 16120 - 1 04/30/10 C. PART 2 DESIGN NO. 012090 Submit field test results for wires and cables, including "Megger" readings with the method used. - PRODUCTS 2.01 WIRES AND CABLES A. General I. Conductors I.P.C.E.A. labeled. 2- Conductors shall have 600 volts insulation shall be of soft-annealed-uncoated copper of conductivity. Copper clad conductors are acceptable. 3- All conductors shall have identifiable lettering on the insulator jacket as to voltage rating, wire type, A.W.G. size, insulation, and shall conform standards, and to be A.S.T.M. UL listed and and and 98% not manufacturer I.D_ B. NYCSCA Wire Description 1. Type THHN/THWN: 750 C, THHN: 90 0 C shall have a thermo-plastic polyvinyl chloride insulation with nylon jacket for 600 volts, and shall comply with ASTM, IPCEA S-61-402 (latest edition) and NEMA WC5 (latest edition). 2. Metal Clad Cable (Type MC) shall be a factory assembly of conductors, each insulated and enclosed in a metallic flexible interlocking metal tape armor of galvanized steel or aluminum. A barc inLernal grounding conductor shall be included and insulated from the outer metal armor. All conductors, including grounding conductor, shall be a minimum of #12 AWG. The assembly shall be UL listed and rated 600 volts, 900 C. 3. RHH/RHW-2 cable is made of electrical grade ceramified silicon rubber insulating material to protect the cable from fire and water. RHW power cable shall be rated for 60OV, TUL listed and shall maintain two hours fire rating. WIRING SYSTEMS 16120 - 2 04/30/10 DESIGN NO. 012090 2.02 SPLICES AND TERMINATIONS A. PART 3 - General 1. All materials for making splices and terminations shall be specifically designed for use with the type of wire, the cable insulation, the installation and the operating conditions of the specific application and be UL listed. 2. Grounding conductors and bonding jumpers shall be connected by exothermic welding, listed pressure connectors, listed clamps, or other listed means. EXECUTION 3.01 PREPARATION A. Prior to pulling wires and cable, clean raceway systems of all foreign matter and perform all operations necessary so as not to cause damage to wires and cables while pulling. 3.02 INSTALLATION A. B. General 1. At least 6 inches of free conductor, measured from the point in the box where it emerges from its raceway or cable sheath, shall be left at each outlet, junction and switch point for splices or the connection of luminaries or devices. Where the opening of an outlet, junction or switch point is less than 8 inches in any dimension, each conductor shall be long enough to extend at least 3 inches outside the opening. 2. Use approved lubrication when installing cables in conduits and raceways. Any pulling compounds shall be compatible with the finish of the wires and cables furnished. Type TNHN/THWN wire 1. NYCSCA Feeder and Branch Circuits WIRING SYSTEMS 16120 - 3 04/30/10 DESIGN NO. 012090 2- C. Remote-Control Signaling Circuits: Circuit Classes otherwise indicated. and 1, 2 Power-Limited or 3, unless Type MC Cable - Use in concealed installation of ceiling and gypsum board for: 1. 2. hung Lighting Branch circuit. Power branch circuit. D. Type RHW-2 Cable - Use where required by code. Install as per manufacturer instruction. E. Lighting Fixture Wires 1. F. Identifications of Wires and Cables 1. G. For wiring within lighting fixtures only, where sizes #14 AWG or smaller is required, use Type TFFN. Each wire and cable shall be identified by its circuit in all cabinets, boxes, manholes, handholes, wireways and other enclosures and access locations, and at all terminal points. Terminations 1. For Conductor Sizes Larger Than Terminal Capacity On Equipment: Reduce the larger conductor to the maximum conductor size that terminal can accommodate (reduce section no longer than 1 ft.). Cutting of cable strands to fit terminal is not acceptable. 3.03 FIELD TESTS A. NYCSCA Test all feeder cables installed under this Contract with a 1000-volt Megohmmeter. Furnish the Authority's Representative with a copy of the "Megger" test report, together with an outline of the method used. Any cable not attaining the minimum reading established in the code shall be replaced. WIRING SYSTEMS 16120 - 4 04/30/10 DESIGN NO. 012090 3.04 COMMON NEUTRAL CONDUCTOR A. A common neutral may be used for 2 or 3 branch circuits where the circuits are indicated on the Drawings to be enclosed within the same raceway, provided each branch circuit is connected to different phase busses in the panelboard. B. Exceptions - The separate neutral: 1. following Circuits containing interrupter devices. circuits ground shall fault have a circuit a. Circuits containing solid state dimmers. b. Circuits for computers, related equipment. c. Circuits recommended by equipment manufacturers to have separate neutrals. peripherals and 3.05 EQUIPMENT GROUNDING CONDUCTOR Note that equipment-grounding conductors are not shown on the Contract Drawings but it shall be provided when and as required by code. 3.06 ELEVATOR WIRING - NOT USED END OF SECTION NYCSCA WIRING SYSTEMS 16120 - 5 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Schedule Certificates Field test report NYCSCA WIRING SYSTEMS 16120 - 6 04/30/10 DESIGN NO. 012090 SECTION 16130 RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. Provide raceways, fittings, supporting devices, boxes and accessories required for a complete system and its proper operation. B. Coordinate layout and installation of raceways, boxes, enclosures, cabinets, and suspension system with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, fire-suppression system, and partition assemblies. C. Raceways, fittings, etc for the Fire Alarm System are not part of this Section. Refer to Section 16720, Fire Alarm System, for tire alarm system raceway requirements. 1.02 RELATED SECTIONS A. Firestopping ............................ Section 07270 B. Painting ................................ Section 09900 1.03 SUPPLEMENTAL SUBMITTALS A. Submit a Product Schedule indicating the item description and manufacturer name. The Schedule will be accepted by the Authority for record purposes only, provided that the items are in full compliance with the Specifications. B. Certificates Provide affidavit stating that all listed and meet the specifications. items used are UL PART 2 - PRODUCTS 2.01 RACEWAYS A. Rigid Galvanized Conduit (RGC) Steel conduit, Schedule 40, hot dipped galvanized, with Underwriters Laboratories label stamped on each length. NYCSCA RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 1 04/30/10 B. DESIGN NO. 012090 Electric Metallic Tubing (EMT) Industry standard conduit with Underwriters Laboratories label stamped on each length. C. Flexible Metal Conduit (FMC) Galvanized listed. D. steel conduit, Underwriter Laboratories Liquid-tight Flexible Metal Conduit (LTFMC) Industry standard conduit, Underwriter Laboratories listed. E. Surface Metal Raceway 1. Metal raceway shall be of a two-piece design with a base and snap-on cover. 2. Raceway and all components Underwriters Laboratories 3. Manufacturers shall be listed by Wire Mold Co or a. Mono-Systems, Panduit. b. Single Channel: Wire Mold V700, Hubbell Inc. 750 Series, Mono-Systems SMS700, or Panduit PMR5/PMR7. c. Dual Channel: Wiremold V4000, Wiremold DS4000 Series, Hubbell Inc. 4000 Series or MonoSystems SMS4200 or Panduit PMR4O. d. Surface mounted Raceway V2000BC. Hubbell Inc., 2.02 SUPPORTING DEVICES A. B. NYCSCA Hangers 1. Separate hangers shall be installed for supporting conduits. Wherever possible, hangers shall be supported from concrete slab by inserts. 2. Hangers and piping installed by other trades shall not be used for supporting electric conduits. Individual and multiple pipe hangers and riser clamps including all parts and hardware shall be hot-dipped galvanized throughout. All U-bolts, clamps, attachments and hardware for hanger assembly and RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 2 04/30/10 DESIGN NO. 012090 conduits shall be provided. Each multiple hanger shall be designed to support a load equal to or greater than the sum of the weights of the conduits, wires and hanger itself, plus 200 pounds. C. Use pipe straps and specified method of attachment where conduit is installed proximate to surface of steel stud or masonry construction. 1. Use hangers secured method of attachment from the surfaces. to surface with where conduit is specified suspended D. Use "C" beam clamps and hangers supported from steel beams. E. Use deck clamps and hangers to support conduits from steel decking having hanger tabs. One conduit per tab where conduit is is permitted. 1. Where conduit is supported from steel decking which does not have hanger tabs, use clamps and hangers secured to decking, utilizing specified method of attachment. F. Use channel support system supported from structural steel for multiple parallel conduit runs. G. Where conduits are installed above ceiling, do not rest conduit directly on runners bars, T-Bars, etc. H. 1. Conduit Sizes 2-1/2' and Smaller: Support conduit form ceiling supports or from construction above ceiling. 2. Conduit Sizes Over 2-1/2": Support conduit beams, joist, or trusses above ceiling. from Conduits shall be supported within three (3) feet of any kind of fitting and at every outlet or junction box, panel, etc. This shall apply to both horizontal and vertical runs. 2.03 BOXES AND ENCLOSURES A. NYCSCA The Contractor shall provide outlet boxes and enclosures appropriate for the purpose at all locations where the Drawings require the installation of electrical devices or electrical equipment. For exposed conduit systems, the contractor shall use cast outlet boxes in all locations below 8'-0" with number of threaded hubs equal to the number of conduits, except when installing surface metal raceway contractor shall RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 3 04/30/10 DESIGN NO. 012090 provide boxes from the same manufacturer of the surface metal raceway. B. Where the Contractor selects and installs an item of equipment that requires additional boxes, fittings, etc., or a modification of the conduit system indicated on the Drawings, such additional boxes, fittings, etc. shall be furnished and installed and such modifications shall be performed by the Contractor as part of this Contract, without extra compensation from the Authority. 2.04 FITTINGS AND ACCESSORIES A. All fittings and accessories must be UL listed and compatible with selected raceways and suitable for use location. Compression fittings shall be provided with the installation of EMT. 2.05 CONDUIT SIZES A. Where conduit is required to be installed, its nominal diameter shall be not less than 3/4 inch. B. For conduit size is 1". C. For conduit placed in formed slabs, the maximum size is 3/4" for 4" slabs and 1" for slabs greater than 4". placed in metal deck slabs, the maximum 2.06 SLEEVES FOR CONDUIT A. Provide sleeves, Schedule 40, galvanized steel, for all electrical conduits and wiring passing through foundation walls. B. Provide sleeves, Schedule 10, galvanized steel, for all electrical conduits and wirina passing through partitions and slabs. Proprietary sleeves that are part of an NYC approved fire stopping assembly are also acceptable. PART 3 - EXECUTION 3.01 RACEWAY SCHEDULE A. Rigid Galvanized Steel Conduit (RGC) Provide RGC as follows: 1. NYCSCA All conduits buried in concrete slabs or in the ground. Where conduit is in contact with gravel or earth, conduit shall have a bitumastic coating. RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 4 04/30/10 B. DESIGN NO. 012090 2. Elbows and stub ups underground raceways. 3. All outdoor raceway. 4. Fire Rescue area intercom system. through floor slabs from Electrical Metallic Tubing (EMT) Provide EMT for feeders and branch circuits for power, lighting and low voltage systems. C_ Metal Clad Cable (MC) Provide MC for branch circuit in concealed installation of hung ceiling and gypsum board partitions. D. Flexible Metal Conduit (FMC) 1. Concealed systems 2. Provide FMC for final conduit connection to: 3. 4. above hung ceiling for low voltage a. Recessed ceilings. b. Emergency lighting battery units. c. Motors d. Equipment locations). e. Equipment requiring flexible connections for adjustment or alignment (dry locations). lighting subject fixtures to in suspended vibration (dry In all cases, install equipment-grounding conductor in the flexible raceway and bond at each box or equipment to which flex is connected. Grounding conductors are not shown on the Drawings. E. Liquid-tight Flexible Metal Conduit (LFMC) Provide LFMC for final conduit connection to: NYCSCA 1. Motors and Equipment subject to vibration in damp and wet locations and for Kitchen appliances. 2. Equipment requiring flexible connection for adjustment or alignment in damp and wet locations. RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 5 04/30/10 F. DESIGN NO. 012090 Surface Metal Raceway Provide surface metal raceway in finished spaces. 1. Secure raceway of one-piece type every 36" alternately with one-hole straps, and support clips (strap, support clip, strap, etc.) . Secure raceway of two-piece type every 36" alternately with straps and fasteners through back of raceway (strap, fastener through back, strap, etc.). 2. Install separate grounding conductor. Grounding conductors for surface metal raceways are not shown on the Drawings. 3.02 RACEWAY INSTALLATION A. General 1. Keep raceways at least 6 inches away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping- NYCSCA 2. All conduit systems shall electrically continuous. 3. The ends of all conduit shall be square, carefully reamed out to tull size, shouldered in the fittings, and bushed or capped wherever stubbed clear of the building. 4. Not more than four (4) 90 degree ells or bends or the equivalent shall be used in any single run of conduit. Conduits for telephone, television, video surveillance or data cable shall not have more than three (3) 90 degree bends or the equivalent. Where more bends are necessary, provide suitable code size pull boxes or fittings. All conduits for telephone, television, video sur-eillance or daLa systems cable shall have large radius bends. Pull boxes shall be installed in accessible locations. 5. Conduit installed on equipment shall not obstruct any removable panel, access door, or control. Control apparatus, outlet, junction, and pull boxes shall be installed so as not to interfere with any piping, fixtures, or equipment. 6. Complete raceway installation conductor installation. be mechanically before and starting RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 6 04/30/10 DESIGN NO. 012090 7. Conceal conduit and EMT within new finished walls, ceilings, and floors, unless otherwise indicated. Use of exposed raceways attached to new finished walls, ceilings, or slabs is not permitted. a. 8. 9. 10. NYCSCA Install concealed raceways with a minimum of bends in the shortest practical distance, considering type of building construction and obstructions, unless otherwise indicated. Conduits installed across seismic separations (expansion joints) shall include, but not limited to, the following: a. The conduit (rigid steel or EMT) shall be securely anchored on each side of the seismic separation with a pipe hanger per SMACNA details. b. The spacing between conduit ends shall be 36" minimum. C. A liquid-tight flexible metal conduit of the same size shall be installed between the conduit ends spanning the seismic separation. d. The liquid-tight flexible metal conduit shall be of sufficient length to provide for a longitudinal and axial deflection of (2) inches minimum in all directions. Terminations: a. Where raceways are terminated with locknuts and bushings, align raceways to enter squarely and install locknuts with dished part against box. Use two locknuts, one inside and one outside box. b. Where raceways are terminated with threaded hubs, screw raceways or fittings tightly into hub so end bears against wire protection shoulder. Where chase nipples are used, align raceways so coupling is square to box tighten chase nipple so no threads are exposed. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not less than 200-1b (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end of pull wire. RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 7 04/30/10 DESIGN NO. 012090 11. B. Rooftop conduits (rigid steel) shall be neatly grouped and installed parallel to the building lines. Support conduits on minimum 4 inches x 6 inches on pressure treated lumber sleepers at minimum 5 feet spacing. Exposed Conduits Exposed conduits shall be rigidly fastened to structure, or to rigid hangers or angle irons connected to structure at intervals not exceeding eight feet. Where the conduits or surface metal raceways are installed exposed, they shall follow the architectural lines of the enclosure and shall be run as to be as inconspicuous as possible. Conduits or surface metal raceways shall not be installed diagonally on ceilings, walls or columns. C. Conduit Installed Concealed in Existing Building Where new partition walls and new hung or furred ceilings are being erected or where existing walls are to have a new tile finish, the conduits and related equipment shall be installed concealed in walls and in hung or furred ceilings. D. Conduit Installed in Concrete Floor Slabs 1. General a. Where conduits cross expansion floor slabs, special conduit fittings shall be installed. b. Conduits shall clear door closers by 3". c. Conduits installed in the fill (or slab if no fill is being used) of an auditorium floor shall be run in the aisle spaces only. all joints in expansion concealed-in-floor d. E. NYCSCA The Contractor shall not cut any hole larger than six (6) inches except where otherwise directed in the Contract. Where the opening (single or combined) is larger than six inches, the Contractor shall request and obtain approval before execution of work. Low voltage systems (except for the fire alarm, refer to specification section 16720) shall be installed as follows: RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 8 04/30/10 DESIGN NO. 012090 Existing Buildings: 1. Vertical (Riser) Raceways: EMT 2. Horizontal Raceways: EMT or surface metal raceway up to the outlet. Concealed flexible metal conduit may be used for low voltage systems above suspended ceiling. F. Raceways passing through fire-rated walls, floors, roofs, ceilings, and other areas where indicated: the space between sleeve and pipe/conduit shall be fire stopped in accordance with Section 07270 to comply with fire-rating of assembly through which it passes. G. Raceways passing through foundation walls shall be of watertight utilizing "Link-Seal" type gasketing. 3.03 CONDUIT TO MOTORS, TABLES, ETC. IN SHOPS AND OTHER ROOMS - 3.04 NOT USED MOUNTING DEVICES A. Height of Wall Outlets Unless otherwise indicated, locate outlet boxes with their center lines at the following elevations above finished floor: Alarm Indicating Devices 8'-0" to center where ceiling height allows a minimum of 2" clearance between ceiling and top otherwise mount so that its top is 2" below finished ceiling. Clock 2" below finished ceiling to a maximum elevation of i0'-0". 8'-0" where ceiling height allows a minimum of 6" clearance between ceilings and top light, otherwise mount exit light so that its top is 6" below finished ceiling. Adjust height and clearances as required to suit installation over doors. 8'-0"1 AFF. 8'-0" A.F.F. or 6" below the ceiling whichever is lower Exit Lights Indicators Fire Alarm Strobe Lights NYCSCA RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 9 04/30/10 DESIGN NO. 012090 Manual Fire Alarm 4'-OT Boxes Single & Duplex Receptacles 1-6" Special Purpose Receptacles As indicated on the Drawings. Switches 4 Telephone 1'-6" Telephone Marked "W" Install outlet so that the highest operable part of the telephone will not be more than 4'-0" AFF. Television outlet li'6" 3.05 PAINTING A. All exposed raceways and boxes in finished parts of building shall be painted. Painting shall consist the of a prime coat and a finished coat, color as selected by project architect. Factory painting w .Il he accepted as a prime coat. END OF SECTION NYCSCA RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 10 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Schedule Certificates Coordination/Routing Drawings NYCSCA RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES 16130 - 11 THIS PAGE INTENTIONALLY LEFT BLANK - 04/30/10 DESIGN NO. 012090 SECTION 16140 WIRING DEVICES PART 1 - GENERAL 1.01 DESCRIPTION OF WORK Provide receptacles and switches. 1.02 SUPPLEMENTAL SUBMITTALS Field test report. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Hubbell Incorporated B. Leviton Mfg. Company Inc. C. Bryant Electric, Inc. (a Hubbell Inc. subsidiary) D. Pass & Seymour/Legrand 2.02 AC SWITCH Commercial specification grade, UL listed; compliance with UL 20 and NEMA standard WD-I, "General Purpose Wiring Devices". A. Toggle Single Pole: 1. 2. B. Three-way Toggle: 1. 2. C. 15A, 120/277 VAC; CS315 from Hubbell Inc.; CS315-2 from Leviton Mfg.; 20A, 120/277 VAC; CS320 from Hubbell Inc.; CS320-2 from Leviton Mfg.; Locking type (Key-operated) Single-pole Industrial specification grade for this device. 1. NYCSCA 15A, 120/277V AC; CS115 from Hubbell Inc.; CS15-2 from Leviton Mfg.; 20A, 120/277 VAC; CS120 from Hubbell Inc.; CS120-2 from Leviton Mfg.; 15A, 120/277V AC; HBL 1201-L from Hubbell Inc.; l101-2L from Leviton Mfg.; WIRING DEVICES 16140 - 1 04/30/10 DESIGN NO. 012090 2. 20A, 120/277 VAC; HEL 1221-L from Leviton Mfg.; Hubbell Inc.; CS1T21-2L from 2.03 RECEPTACLES A. NYCSCA Straight-blade-type; Commercial Specification Grade minimum; compliance with NEMA WD 1; DSCC WC 596, AND UL 498 and UL 943 2006 Codes. 1. Single receptacle, NEMA 5-20R (20A, 125V, 2P, 3W); Leviton 5891 or Pass & Seymour/Legrand PS5351 2. Duplex receptacle, NEMA 5-20R (20A, 125V, 2P, 3W); Hubbell Inc. HBL5352, Leviton BR20, Pass & Seymour/Legrand PS5362 3. Ground-Fault Circuit Interrupter GFCI; duplex (20A, 125V, 2P, 3W) Hubbell Inc GF5352SL, Leviton 6899, Pass & Seymour/Legrand PS2095 4. Transient Voltage Surge Suppression Receptacle TVSS; duplex (20A, 125V, 2P, 3W); Hubbell Inc HBL5360SA, Leviton 5380, Pass & Seymour/Legrand PS5362- ISP 5. Tamper-Resistant Commercial/Hospital Grade receptacle - Safety duplex receptacle for use in Pre-Kindergarten and Kindergarten rooms - NEMA 520R (20A, 125V, 2P, 3W): Hubbell Inc. HBL 8300 SG 0OSGA, Leviton TBR 20, Pass & Seymour/Legrand TR 63H (Hospital Grade) 6. TVisted Lock receptacles Commercial Grade For use in the Telecommunication Rooms a. Single receptacle (30A, 125V, 2P 3W) (NEMA L530R): Leviton part# 2660 or Hubbell Part # HBLL530R b. Single receptacle (20A, 220V, 2P 3W) (NEMA L620R)Leviton Part# 2320 or Hubbell Part # HBLL53OR C. For the Mobile Hot Food Server: Hubbell Receptacle Part i HBL9430A 3 Pole, 4 Wire Grounding 30A, WIRING DEVICES 16140 - 2 04/30/10 DESIGN NO. 012090 2.04 WEATHERPROOF RECEPTACLE ENCLOSURE For use in WTUC10-G. wet location equal to Pass & Seymour/Legrand 2.05 WALL PLATE A. PART 3 - Provide wall plate for wiring devices. Material shall be 0.035-inch thick, satin-finished stainless steel. Metal screw heads to match plate finish. EXECUTION 3.01 INSTALLATION A. Install wiring devices in outlet boxes. B. Install devices and assemblies level, plumb and square. C. Where more than one switch occurs at the same location, arrange switches faceplate. D. in gangs and cover with a single Install switches so that handle is up when switch is in the "On" position. NYCSCA E. Install receptacles with ground pole in up position. F. Install wall plates on all wiring devices. G. Install blank wall plates on outlet boxes which are for future equipment except telephone outlets. H. Remove wall plates during painting. I. Install weatherproof covers on wiring devices in damp and wet locations. J. Where flush plates are required over outlet boxes that cannot be set deep enough for the plates to fit closely over the finished wall surfaces, provide extension collar to fill the space between the finished wall surface and the plate. protecting devices and assemblies WIRING DEVICES 16140 - 3 04/30/10 DESIGN NO. 012090 3.02 FIELD TESTS A. Ensure that proper polarity of connections is maintained. Subsequent to energization, test wiring devices to demonstrate compliance with requirements of these Specifications, END OF SECTION NYCSCA WIRING DEVICES 16140 - 4 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data Field test report NYCSCA WIRING DEVICES 16140 - 5 - THIS PAGE INTENTIONALLY LEFT BLANK - 04/30/10 DESIGN NO. 012090 SECTION 16450 GROUNDING AND BONDING PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. The Contractor shall provide a complete electrical systems and equipment. grounding of 1.02 SUPPLEMENTAL SUBMITTALS - NOT USED PART 2 - PRODUCT 2.01 GROUNDING BUS BAR - NOT USED 2.02 GROUNDING ELECTRODES - NOT USED 2.03 GROUNDING CONDUCTORS A. Copper conductors, bare or insulated with THWN or THHN insulation. B. Equipment Grounding Conductors: colored insulation. C. Isolated Ground Conductors: Insulated with green-colored simulation with yellow stripe. On feeders with isolated ground, use colored tape, alternating bands of green and yellow tape to provide a minimum of three bands of green and two bands of yellow. D. Grounding Electrode Conductors: E. Underground Conductors: otherwise indicated. Bare, tinned, stranded, unless F. Bare Copper Conductors: Comply with the following: G. Stranded cable. 1. Solid Conductors: 2. Assembly of Stranded Conductors: 3. Tinned Conductors: ASTM B 3. ASTM 2 8. ASTM B 33. Copper Bonding Conductors: 1. NYCSCA Insulated with green- As follows: Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG copper conductor, 1/4 inch (6.4 mm) in diameter. GROUNDING AND BONDING 16450 - 1 04/30/10 DESIGN NO. 012090 2. Bonding Conductor: copper conductor. 3. Bonding Jumper: Bare copper tape, braided bare copper conductors, terminated with copper ferrules; 1-5/8 inches (42 mm) wide and 1/16 inch (1.5 mm) thick. 4. Tinned Bonding Jumper; Tinned-copper tape, braided copper Jonductors, terminated with copper ferrules; 1-5/8 inches (42 mm) wide and 1/16 inch (1.5 mm) thick. No. 4 or No. 6 AWG, stranded 2.04 CONNECTOR PRODUCTS A. Comply with IEEE 837 and UL 467. Listed for use for specific types, sizes, and combinations of conductors and connected items. B. Bolted Connectors: compression type. C. Welded Connectors: Exothermic-welded type, in kit form, and selected per manufacturer's written instructions. D. All terminal lugs and bolts shall be 98% copper. Bolted-pressure-type connectors, or silicon bronze PART 3 - EXECUTION 3.01 APPLICATION A. In raceways, conductors. use insulated equipment grounding Equipment Grounding Conductor Terminations: pressure clamps. Use bolted 3.02 INSTALLATION A. Nonmetallic Raceways: Install an equipment grounding conductor in non metallic raceways unless they are designated for telephone or data cables. P. Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate equipment grounding conductor to each NYCSCA GROUNDING AND BONDING 16450 - 2 04/30/10 DESIGN NO. 012090 electric water heater, heat-tracing, and antifrost heating cable. Bond conductor to heater units, piping, connected equipment, and components. C. Signal and Communication Systems: For telephone, alarm, voice and data, and other communication systems, provide insulated grounding conductor as described in individual sections in raceway from main building grounding bus bar to telecommunication room grounding bus bar and each service location, terminal cabinet, wiring closet, and central equipment location. D. Common Ground Bonding with Lightning Protection System: Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit. 3.03 CONNECTIONS A. B. NYCSCA General: Make connections so galvanic action or electrolysis possibility is minimized. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact will be galvanically compatible. 1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer to order of galvanic series. 2. Make connections with clean, bare metal at points of contact. 3. Make aluminum-to-steel connections with stainlesssteel separators and mechanical clamps. 4. Make aluminum-to-galvanized steel connections with tin-plated copper jumpers and mechanical clamps. 5. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces. Exothermic-Welded Connections: Comply with manufacturer's written instructions. Welds that are puffed up or that show convex surfaces indicating improper cleaning are not acceptable. GROUNDING AND BONDING 16450 - 3 04/30/10 DESIGN NO. 012D90 C. Equipment Grounding Conductor Terminations: For No. 8 AWG and larger, use pressure-type grounding lugs. No. 10 AWG and smaller grounding conductors may be terminated with winged pressure-type connectors. D. Noncontact Metal Raceway Terminations: It metallic raceways terminate at metal housings without mechanical and electrical connection to housing, terminate each conduit with a grounding bushing. Connect grounding bushings with a bare grounding conductor to grounding bus or terminal in housing. Bond electrically noncontinuous conduits at entrances and exits with grounding bushings and bare grounding conductors, unless otherwise indicated. E. Tighten screws and bolts for grounding and bonding connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A [and UL 486] . F. Compression-Type Connections: Use hydraulic compression tools to provide correct circumferential pressure for compression connectors. Use tools and dies recommended by connector manufacturer. Provide embossing die code or other standard method to make a visible indication that a connector has been adequately compressed on grounding conductor. 3.04 UNDERGROUND DISTRIBUTION SYSTEM GROUNDING - NOT USED 3.05 TESTING - NOT USED END OF SECTION NYCSCA GROUNDING AND BONDING 16450 - 4 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product data Details of grounding bus bar installation Field Test Reports NYCSCA GROUNDING AND BONDING 16450 - 5 - THIS PAGE INTENTIONALLY LEFT BLANK - DESIGN NO. 012090 04/30/10 SECTION 16475 OVERCURRENT PROTECTIVE DEVICES AND CIRCUIT BREAKERS PART I - GENERAL 1.01 DESCRIPTION OF WORK A. use in panelboards. Provide circuit breakers for - NOT USED 1.02 SUPPLEMENTAL SUBMITTALS 1.03 SPARES - NOT USED 1.04 ELECTRICAL SYSTEM COORDINATION A. overcurrent or fuses, of Rating and arrangement which have a rating above devices on service switches, 601 amperes, shall be coordinated. PART 2 - PRODUCTS 2.01 CIRCUIT BREAKERS A. General thermal-magnetic be shall breakers Circuit Specifications: conforming to the following 1. be by "bolt-on". Connection to bus shall not acceptable. type circuit breakers are 2. Multi-pole poles 3. 4. NYCSCA breakers shall have barriers type, Plug-in between have separate tripping Multi-pole breakers shall Each tripping element element for each pole. Multi-pole breakers shall shall open all poles. all poles. have one handle controlling rating or less shall Breakers of 225-ampere trip trip set permanently non-tamperable, have molded in sealed and enclosed elements composition housing. OVERCURRENT PROTECTIVE DEVICES BREAKERS 16475 - 1 AND CIRCUIT DESIGN NO. 012090 04/30/10 5. 6. 7. not less Single pole breakers shall be rated for shall than 120 volts, A.C., multi-pole breakers be rated for not less than 250 volts A.C. Where spaces for future breakers are required, future of mounting for connections copper breakets shall be provided. standard Circuit breakers shall be mounted in Frame panel boards as indicated on the drawings. to conform shall and sizes of circuit breakers the following: a. b. C. d. Use standard molded-case type. the at controlled circuits lighting For panel, provide circuit breakers rated for switching duty. For circuit breaker serving heat tracing, devices heating similar or melting snow milliamp (30 feature GFI provide on the drawings. shown as sensitivity) convenience serving breakers circuit For receptacles in bathrooms, kitchens and other GFI such code mandated locations provide shown as feature (5 milliamps sensitivity) on the drawings. Size, Trip Rating, Short Table with Frame Circuit Interrupting Capacity and recommended Manufacturers:8. Trip Ratings- No of Size PolesFrame 100 AMP - Frame 15-30 15-20 Square D, Type QOB-VH (22,000 120/240V: I.C.) Square D, Type QOB-VH (65,000 120/240V: I.C.) Cutler-Hammer, Type GHBS (65,000 120-240V: I.C.)* 480/277V: 2EB (14,000 I.C ) 125 AMP - Frame 15-125 1120V: NYCSCA SIEMENS, Type ED4 (65,000 1.C.) OVERCURRENT PROTECTIVE DEVICES AND CIRCUIT BREAKERS 16475 - 2 DESIGN NO. 012090 04/30/10 100 AMP - Frame 120/240V: 2&3 15-100 Square D, Type QOB-VH (22,000 Square D, Type QOB-VH (65,000 I .C.) 15-30 2&3 120/240V: I.C.) 15-30 2&3 240V: Cutler-Hammer, Type GB (65,000 I.C.) * ___ 125 AMP - Frame 15-125 240V: 20 SIEMENS, Type ED4 (65,000 I.C) 225 AMP - Frame 101-225 2&3 240V: Square D, Type KA (42,000 I.C.) 125-225 2&3 240V: Cutler-Hammer, Type HCA 125-225 2&3 240V: SIEMENS, Type QJ2-H (42,000 I.C.) l.C.)* (42,000 400 AMP - Frame 240V: Square D, type LA (42,000 I.C.) 226-400 _480V: Type LA (30,000 I.C.) 2.02 FUSES - NOT USED 2.03 SPARE FUSE CABINET - NOT USED PART 3 - EXECUTION 3.01 INSTALLATION - NOT USED END OF SECTION NYCSCA OVERCURRENT PROTECTIVE DEVICES AND CIRCUIT BREAKERS 16475 - 3 DESIGN NO. 012090 04/30/10 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APROVED Product Data Shop Drawings Specifications, Installation Instructions NYCSCA OVERCURRENT PROTECTIVE DEVICES AND CIRCUIT BREAKERS 16475 - 4 DESIGN NO. 012090 04/30/10 SECTION 16500 INTERIOR BUILDING LIGHTING PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. Provide lighting fixtures, supports and accessories including plaster frames, trim rings and backboxes for plaster, drywall, or concrete ceilings as necessary. B. The types of lighting fixtures to be installed are indicated and detailed on fixture schedule on the Drawings, which also provides details on manufacturers, catalog numbers, lamping, etc. C. Coordinate with other trades to avoid conflicts between the of fixtures and supports with installation installation of mechanical equipment, ceiling structures, etc. D. All lighting fixtures shall operate on nominal 120 volts, 60 Hz single phase service as indicated on the Drawings and in the Specifications. 1.02 SUPPLEMENTAL SUBMITTALS A. Product Data 1. B. Provide standard print catalog sheets, Specifications, installation instructions, and photometric data from a recognized independent Submittals laboratory for each type of fixture. that do not include distribution curves and photometric data will be rejected. All options and specified requirements shall be identified on submittal. Mounting Details Submit mounting details for each type of fixture including attachments to structure, anchors, rods, hickeys, etc. C. NYCSCA Samples 1. Submit fixture samples as requested by the Authority. 2. Submit mounting Authority. hardware as requested by INTERIOR BUILDING LIGHTING 16500 the - 1 04/30/10 D. E. DESIGN NO. 012090 Submission of Substitute Fixtures (fixtures other than specified herein or on the Fixture Schedule). 1. Submittals for substitute fixtures shall be the standard print catalog sheets from the manufacturers (CADD drawings and computer printouts are not acceptable). 2. Substitute fixture shall meet or exceed photometric quality of fixture designated on the schedule. Photometric data of substitute fixture shall be substantiated by an independent testing lab, such as I.T.L. Photometric data by Lumen Micro or similar software programs are not acceptable. 3. Substitute fixture shall meet or exceed the quality of the fixture designated on fixture schedule in construction, finishing, materials, reflector, louver, diffuser etc. 4_ Substitute fixture shall closely match the appearance, dimensions and features of the fixture designated. 5. Submit one sample of each type of substitute fixture as requested, with one set of mounting hardware for approval. 6. Tn order to ensure that the work is performed in an orderly and expeditious manner, the Contractor shall be permitted no more than three (3) submittals for substitution of each specific fixture type. Should the third submittal be rejected, then the Contractor shall be required to provide the fixture specified on the fixture schedule. Spare Parts. 1.03 FIXTURE PROTECTION A. The Contractor is required to protect fixtures from damage during installation and up to time of acceptance by the Authority. Broken fixtures, glassware, plastics, lamps, etc. shall be replaced by the Contractor with new parts, without any additional expense to the Authority until final acceptance- NYCSCA INTERIOR BUILDING LIGHTING 16500 - 2 04/30/10 DESIGN NO. 012090 1.04 SPARE PARTS A. Diffusers Provide a spare diffuser for every twenty (20 of each type and size installed, but not less than one (1) of each. B. Screwdrivers Provide one (1) screwdriver suitable for each type of vandal resistant screw installed on fixtures. C. Delivery 1. Spares shall be provided and delivered to the Authority's Representative with an itemized list and a receipt taken, certifying that these spare parts have been delivered securely packed and received in acceptable condition. PART 2 - PRODUCTS 2.01 GENERAL A. Provide lighting fixtures as designated on the fixture schedule. Lighting fixtures of the fixture schedule are designated by types, manufacturers and catalog numbers. Substitute fixtures by approved manufacturers listed in these specifications will be approved, provided that all requirements are satisfied. B. The requirements specified herein are minimum requirements and shall be supplemented by any other requirements indicated on the fixture schedule. All fixtures, including those designated on the fixture schedule on the drawings by Catalog Numbers, or Catalog Numbers mentioned in the Specifications, shall nevertheless be specially modified to meet the requirements of these specifications. C. All fixtures and components shall be UL listed and meet NYC Electrical Code. 2.02 FIXTURE COMPONENTS A. Equip fixtures with: 1. NYCSCA Ballasts (electronic) suitable for operation on 60 Hz circuit, voltage rating to suit branch circuit voltage. INTERIOR BUILDING LIGHTING 16500 - 3 DESIGN NO. 012090 04/30/10 2. 3. 4. Diffusers a. Unless otherwise noted, parabolic diffusers semi-specular fabricated from shall be iridescence free aluminum with precisely blades. assembled and rigidly formed Reflectors shall be die formed of 20-ga. cold rolled steel. b. Lens type diffusers shall be 100% clear virgin The over-all plastic thickness of acrylic. the diffuser or lens shall be a minimum of 0.130" and shall be a "male' type pyramidal in shape"; "female" types are not acceptable. c. Diffusers shall be as manufactured Diversified, KSH, or Holophane. d. Diffusers shall be fastened in a regressed extruded aluminum envelope door frame of code gauge metal with positive latching and shall be secured to the fixture housing by two (2) safety chains with spring clips or approved equivalent means. Holders and Spun Work a. All shells, canopies or other spun parts shall be not less than No. 20 gauge unless otherwise specified with a reasonable tolerance allowed for finishing. b. All screw type globe holders shall be reinforced so that screws shall have a hearing of at least four full threads. Screws holding glassware and/or plastics shall have check nuts or equivalent. c. Globe holders shall be not less than 6" in diameter unless otherwise specified. are Screwless safety type globe holders acceptable. Wire guards a. NYCSCA by Wire guards shall be provided where indicated on the Drawings, typically with a "C" next to the fixture. However, all Gymnasium and INTERIOR BUILDING LIGHTING 16500 - 4 04/30/10 DESIGN NO. 012090 playroom fixtures shall be equipped with wire guards unless otherwise noted. B. C. NYCSCA b. Guards shall be made of #9 gauge minimum steel wire, fully welded at all points. Finish shall be bright zinc plate. Additional wire guard information may be shown on Drawing Details and Notes. c. Guards for surface mounted fixtures shall be secured to ceiling/wall with hinge access. 5. Finishing collar and/or collar/outlet box. 6. Provide end caps positively attached for individually mounted fluorescent fixtures and ends of continuous rows. 7. Lamps for all fixtures shall be as Drawing or in these Specifications. combination finishing indicated on Stems and Hickeys 1. Stems for pendant fixtures shall be standard pipes not less than 3/8" diameter. Stems shall be no less than 6" long with a cut thread. Pipe stems at fixture end shall have a length of threads of approximately l-l/2' for fixture alignment. 2. Each stem shall be provided with a brass/steel swivel or other self-aligning device of type approved by the Authority, a hickey, a malleable iron bushing, a canopy, minimum of three locknuts/washers (one locknut/washer above and two below for locking purpose) and other accessories for the safe support of pendant fixtures. Fixture Finishes 1. The finish of all lighting fixtures not described on fixture schedule or in the Specifications shall be as selected by the Authority's Representative. The Contractor shall submit a color chart to the Authority's Representative for selection of finish. 2. Exterior Fixtures shall have an anodized or baked powder coat finish- INTERIOR BUILDING LIGHTING 16500 - 5 04/30/10 DESIGN NO. 012090 2.03 FLUORESCENT FIXTURE A. Fluorescent fixture housing shall be constructed of sheet metal not less than No. 20 gauge. Fixture housing shall be electrically welded. B. Ballast covers may be 22 gauge. C. Diffusers shall be fastened in an extruded aluminum or 19 gauge flush steel door frame, and fasten to the fixture body by means of approved hinges or hinging device. When in closed position, hinged frame shall be held by captive thumbscrews. Two (2) chain retainers shall be provided attached to diffuser frame with spring clips. D. Self-threading or sheet metal screws and nuts will not be accepted. Fixture and/or parts, such as finishing plates and trims for recessed fixtures, shall not be installed until all plastering and painting has been completed. E. Fluorescent fixture finish shall be white powder coat post painted to provide a minimum of 90% reflectivitv (including all internal and external components). F. Fluorescent fixtures shall be as indicated on fixture schedule, or approved equal as manufactured by approved manufacturers listed below in alphabetical order: Cooper Lighting, Day Brite, General Electric, Guth, Hasco, Holophane, ICON, Legion, Lightolier, Lightron, Linear Lighting, Lumax, McGraw Edison, Lithonia, Mercury, National, NeoRay, Paramount, SPI, Vantage and Hubbell Lighting. C. Fixtures by these manufacturers must conform applicable paragraphs in these specifications. to all 2.04 DIRECT/INDIRECT FLUORESCENT FIXTURE - NOT USED 2.05 HIGH INTENSITY DISCHARGE FIXTURE - NOT USED 2.06 DOWNLIGHTS - NOT USED 2.07 THEATRICAL LIGHTING FIXTURES - NOT USED 2.08 REMOTE CONTROL OF LIGHTING - NOT USED NYCSCA INTERIOR BUILDING LIGHTING 16500 - 6 04/30/10 DESIGN NO. 012090 2.09 ENERGY EFFICIENCY A. PART 3 Fluorescent lighting fixture, lamps and ballast shall conform to energy efficiency requirements of all local authorities having jurisdiction and qualify for any available utility rebate to owner. - EXECUTION 3.01 FIXTURE INSTALLATION A. NYCSCA General 1. The Contractor shall be responsible for the proper and safe mounting and support of all lighting fixtures. Installation shall meet all the requirements of the National Electrical Code. Provide all items of equipment (stems, hangers, rods, inserts, boxes, brackets, yokes, channels, frames, etc.) required to adequately and safely support each lighting fixture in a manner acceptable to the Authority. 2. Provide a lighting fixture at each location shown on Drawings of the type indicated by symbol or other notation. If the type is not specifically noted on Drawings, the Contractor shall provide without extra cost fixtures of the same type called for under similar condition elsewhere on the Drawings as determined by the Authority. 3. The Contractor shall examine the drawings and coordinate closely with the all General Construction trades on all work involved with each type of fixtures to be installed. Contractor shall verify all sizes, locations and conditions under which lighting fixtures are to be installed. Provide plaster frames and running bars (black iron) etc. as required. 4. The Contractor is required to protect fixtures from damage during installation, up to time of acceptance by the Authority. Any broken or marred fixtures, glassware, plastics, lamps, etc. shall be replaced by the Contractor at no additional cost to the Authority. 5. A suitable outlet box shall be provided by the Contractor for each lighting fixture provided. The box shall be cast into concrete or supported using INTERIOR BUILDING LIGHTING 16500 - 7 04/30/10 DESIGN NO. 012090 two double split type anchors concrete walls or ceiling. installed in 6. Number of supports for fixtures shall be as specified in "Lighting Fixture Support Schedule" in Article 3.07. 7. A surface or pendant type fixture, regardless of its weight, shall not be mounted directly on the concealed or exposed ceiling spline of a lightweight, mechanical acoustical ceiling system. Such fixtures shall be supported from the running channel (Black Iron) or the building structure. 3.02 LIGHTING PENDANT) A. when FIXTURES Surface Ceiling and ON SUSPENDED Pendant CEILING Mounted (RECESS, Fixtures SURFACE on OR Suspended 1. Surface mounted and pendant fixtures shall be supported above suspended ceiling by hanger rods, 3/16" in diameter minimum, or by 12 gauge hanger wire, vertically attached to approved straps, bars, channels secured to the black iron where available, or to structural steel or concrete. 2. Below suspended ceiling, support pendant with 3/8" stems or stainless steel cable. fixtures 3.03 PENDANT MOUNTED LIGHTING FIXTURES (NON-SUSPENDED CEILING) - NOT USED 3.04 PENDANT LIGHT FIXTURES IN GYMNASIUM (FOR SUSPENDED AND NON SUSPENDED CEILINGS) - NOT USED 3.05 LIGHTING FIXTURE WORK IN EXISTING CONSTRUCTION A. Canopies on Surface Mounted Outlet Boxes Where lighting fixtures are mounted upon surface-mounted outlet boxes with surface mounted conduit, the Contractor shall provide a fixture canopy sufficiently deep to permit exposed conduits to pass through. Canopy shall have proper openings cut by fixture manufacturer through which conduits may pass. Submit sample of canopy for approval before installation. NYCSCA INTERIOR BUILDING LIGHTING 16500 - 8 04/30/10 B. DESIGN NO. 012090 Adapters Where new lighting fixtures are mounted on existing outlet boxes and mounting holes are not in proper position, suitable adapter or extension collars shall be provided. C. Removed Fixture 1. Where the Drawings or Specifications call for the Contractor to remove an existing fixture, the Contractor shall also install a suitable blank face plate on the exposed outlet box. 2. If the outlet box is to be used in the extension of branch circuit wiring, this Contractor shall furnish and install a suitable extension collar that may be required to receive surface raceway or conduit. 3.06 MOUNTING HEIGHT OF FIXTURES A. Fixtures shall be hung in accordance with the mounting heights indicated on Drawings and meeting the NYC Electrical Code. Mounting heights A.F.F. (distance above finished floor) are detailed on the Fixture Schedule, or elsewhere on the drawings. B. The Contractor shall provide stems of sufficient length to assure fixture mounting at the specified mounting height. 3.07 LIGHTING FIXTURE SUPPORT SCHEDULE A. Unless otherwise indicated on drawings, provide following number of supports for fixtures. 1. B. An adequately supported outlet box with fixture stud may be utilized as one point of support for surface or recess fixtures weighing less than 40 lbs. For all pendant mounted fixtures, regardless of weight and ceiling type, provide outlet boxes capable of supporting up to 150 lbs., Westinghouse model 01050/01052 or equal. Ceiling Mounted Fixtures (Surface Mounted, Pendant Mounted or Recessed Mounted) 1. Ceiling Mounted Fluorescent Fixtures: a. NYCSCA the Support individual fluorescent than 2 feet wide at 2 points. fixture INTERIOR BUILDING LIGHTING 16500 less - 9 04/30/10 DESIGN NO. 012090 b. 2. 3. Support individual fluorescent fixtures 2 feet or wider at 4 corners. Ceiling Mounted H.I.D. Fixtures a. Commercial Style: Support fixture at 2 points. b. Industrial Style: Support fixture at one point with safety chain. Ceiling Mounted Incandescent Fixtures Support fixture from adequately supported outlet box to suit fixture design (fixture weight less than 50 lbs.). C. Wall Mounted Lighting Fixtures 1. 2. Wall mounted Fluorescent Fixtures: a. Support individual fluorescent fixture 4 feet long or less at 2 points. b. Support continuous row of fluorescent fixtures at points equal to twice the number of fixtures not to exceed 8 feet on center. Uniformly distribute the points of support. Wall Mounted H.I.D. Fixtures Support H.I.D. fixture at 4 points. 3. Wall Mounted Incandescent Fixtures Support fixture from adequately supported outlet box to suit fixture design (fixture weight less than 50 lbs.). 3.08 WIRING AND CONNECTIONS A. Each fixture shall be completely wired in approved standard trade practices in accordance with the requirements of the Electrical Code of the City of New York. B. Wires within fluorescent fixtures, wiring between the ceiling outlet box and the fixture, and all wiring between fixtures in a continuous row shall be #14 AWG minimum, insulated for 1,000 volts, and rated at 90C NYCSCA INTERIOR BUILDING LIGHTING 16500 - 10 04/30/10 DESIGN NO. 012090 minimum. Wiring shall be approved by the Advisory Board for fluorescent fixture wire and meet the above requirements. C. Wiring to pendant fixtures shall be run through the stem and iron bushing or straight cord and stainless steel wire. Wiring to direct/indirect fixtures shall be by means of power cord in SJT jacket. 3.09 AIMING A- All adjustments shall be made in the presence of and to the satisfaction of the Authority, to provide the intent of the Contract Documents. 3.10 CLEANING A. All lighting fixtures, both interior and exterior shall be cleaned prior to final acceptance, for the removal of all construction debris, dust, fingerprints, exposed labels. Fixtures and or parts which have been damaged, scratched, chipped or inadvertently painted during construction shall be repaired and/or replaced at the direction and discretion of the Authority's Representative. END OF SECTION NYCSCA INTERIOR BUILDING LIGHTING 16500 - 11 04/30/10 DESIGN NO. 012090 LIST OP SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data Mounting Details Samples Submission of Substitute Fixtures Spare Parts NYCSCA INTERIOR BUILDING LIGHTING 16500 - 12 04/30/10 DESIGN NO. 012090 SECTION 16501 BALLASTS AND ACCESSORIES LAMPS, PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. Provide lamps, ballasts and accessories as specified herein and as indicated on Drawings. All lamps and ballasts and their installation shall comply with the NY State Energy Conservation Construction Code - Effective 07/03/2002. All installations & equipment shall comply with NYC Electrical Code. B. All fluorescent lamps shall be low mercury (green-endcap) type compliant with US EPA Toxicity Characteristic Leaching Procedure (TCLP). C. Lamp type, wattage, CRI and color temperature shall be in compliance with this specification and as indicated on the drawings. D. Fixtures shall be high efficiency fluorescent or HID type. In general, fluorescent lamps shall be T-8 low mercury triphosphor type with electronic ballasts suited for the application. 1.02 LAMPS, GENERALLY A. Incandescent and fluorescent lamps for all fixtures shall be provided by the Contractor. Quantity of lamps shall be as indicated on Drawings, or as required by the fixture installation. B. In general all interior lighting fixtures shall be equipped with T8 lamps with tri-phosphor coating and low mercury content- C. Lamps shall be the standard product of General Electric Lamp Co., Osram/Sylvania Electric Co., and Philips Co. D. All fluorescent fixtures shall be furnished with solid state energy saver type ballasts. Ballast for fluorescent lamps shall be suitable for one, two, three and four lamp configurations, as necessary, but shall not serve other non-ballasted fixtures unless indicated on the Drawings. E. Linear T5 Fluorescent lamps may be used with written permission from the Authority. NYCSCA LAMPS, BALLASTS AND ACCESSORIES 16501 - 1 04/30/10 DESIGN NO. 012090 1.03 SPARES A. In addition to those installed in fixtures, the Contractor shall provide spare lamps in original cartons, packaged and labeled and delivered to the Authority's Representative as follows: 1. Provide ___ spare lamps 1.04 SUPPLEMENTAL SUBMITTALS A. Submit samples as requested by the Authority. D. Spares. PART 2 - PRODUCTS 2.01 INCANDESCENT LAMPS A. Lamps shall be inside frosted. Lamps of 200 watts or less shall be of the medium base type- Fixtures equipped with 300 watts lamps may be of the medium or mogul based uypes, unless otherwise noted. Lamp sizes of 500 watts or larger shall be equipped with mogul bases. All incandescent lamps shall be Krypton filled energy conservation savings lamps with approximately 10% energy saving. 2.02 FLUORESCENT LAMPS A. Fluorescent lamps shall have a luminous efficacy of no less than 90 lm/W, CRI (Color Rendering Index) of no less than 80 and color temperature of 3500K. B. Linear fluorescent lamps shall be F32TS/835 and F25T8/835 medium bi-pin base with 20,000 hours lamp life. C. Linear T5 Fluorescent lamps may be permission from the Authority. used with writtcn 2.03 METAL HALIDE - NOT USED 2.04 HIGH PRESSURE SODIUM - NOT USED 2.05 FLUORESCENT BALLASTS A. NYCSCA Unless otherwise noted on the Drawings, fluorescent ballasts shall be type "A" sound rated, high frequency electronic type with .88 BF (Ballast Factor) normal light LAMPS, BALLASTS AND ACCESSORIES 16501 - 2 04/30/10 B. DESIGN NO. 012090 output, high power factor of .95 or greater and less than 10% total harmonic distortion. Ballasts shall be installed by the fixture manufactures in accordance with NEMA and NEC requirements. All ballasts shall be UL listed. C. Electronic ballasts shall be by Advance, Lighting Technologies, Osram/Sylvania and warranted for five years including cost of ballast replacement. D. Ballasts shall operate lamps on a parallel circuit and allow remaining lamps to maintain full output if companion lamp fails. Ballasts shall not be affected by lamp failure and shall not affect normal lamp life. E. Instant start ballasts are allowed for circuits, which are intended to be, switched no more than ones per day. F. Ballast shall meet the requirements of Federal Communications Commission Part 18 for Electromagnetic interference and RFI, Non Consumer Equipment. G. Ballasts shall be transients defined location A2. H. Ballasts potting compound shall contain no PCB. I. T5 and Compact fluorescent ballasts shall incorporate auto resetting end of life circuit interruption cut off. J. Ballasts for control of lamps in one housing or fixture unit shall not control lamps of an adjoining unit, (except where specified or for continuous cove lighting and only if the unit with the ballast is properly identified. This requirement shall apply to all fluorescent fixtures unless otherwise indicated on the Drawings or in the Specifications for purposes of multiple switching and control). K. In three-lamp fixtures three-lamp ballast shall be provided. Where three lamp fixtures are split wired (wired to two switches), the center lamp (and its onelamp ballast) (of each fixture to a circuit) shall be wired to the same circuit, unless connected to the emergency circuit. internally in defined Universal shall be labor for protected from line in ANSI C62.41-1991 2.06 HIGH INTENSITY DISCHARGE BALLASTS - NOT USED NYCSCA LAMPS, BALLASTS AND ACCESSORIES 16501 - 3 04/30/10 DESIGN NO. 012090 2.07 EMERGENCY LIGHTING BALLAST A. Emergency ballast shall be New York City approved and comply with U.L.924 for installation on the top of the fixture (Internal Type) or remotely (External Type). n. Input power rating shall not exceed 8 watts at 120 volt. Inverter circuit shall be solid state design of the ferroresonant type. Charger shall be fully automatic by solid state constant potential type and shall be temperature compensated to assure optimum battery life. C. Upon failure of normal AC power, an automatic relay circuit shall instantly apply battery power to the inverter circuit to operate one or two lamps for 90 minutes. The unit shall be provided with solid state circuitry to allow for normal switching of fixture to OFF position. Normal OFF switching solid state circuitry shall permit the unit to differentiate between normal OFF switching and loss of normal AC power without activating the emergency battery. D. The unit shall consist of the following items: E. NYCSCA 1. Battery: type. 2. Charger: Fully automatic, solid state, constantcurrent type with sealed power transfer relay. 3. Test Push Button and Indicator Light: Visible and accessible without opening fixture or entering ceiling space. 4. Emergency Connection: Operate one fluorescent lamp continuously. Connect unswitched circuit to battery-inverter unit and switched circuit to fixture ballast. 5. Diagnostic LED panel shall include the following functions: battery charge/failure, lamp failure, and circuit transfer failure. 6. A double-pole momentary test switch. 7. Housing: Housing to be white powder coated. Heavy duty 18 gauge steel case. 24 volt, Field-replaceable Nickel-Cadmium Approved manufacturer: Bodine B30ST or approved equal. LAMPS, BALLASTS AND ACCESSORIES 16501 - 4 04/30/10 DESIGN NO. 012090 PART 3 - EXECUTION 3.01 INSTALLATION A. Provide the precise complement of lamps in every indoor and outdoor lighting fixture provided under the Contract. B. Install lamps instructions. C. Provide electronic ballasts of compatible design to lamps required. D. Ballast shall be screwed to fixture body and be provided with quick disconnects on wiring to allow for ease of replacement. in accordance with manufacturer's END OF SECTION NYCSCA LAMPS, BALLASTS AND ACCESSORIES 16501 - 5 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS STIBMITTAL DATE SUBMITTED DATE APPROVED Product data Samples Spares NYCSCA LAMPS, BALLASTS AND ACCESSORIES 16501 - 6 04/30/10 DESIGN NO. 012090 SECTION 16520 ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. 1.02 Provide battery-powered and/or line voltage Illuminated Exit Sign and Emergency Lighting Fixtures. SUPPLEMENTAL SUBMITTALS A. Submittal Package 2. Submit the Product Data items specified below at same time as a package. the Battery Emergency and Exit Lighting Fixtures warranty. C. Certificate of requirements. D. Operation and Maintenance Manuals: compliance with the Quality Assurance Deliver to the Authority's Representative. Include name, address and telephone number of the nearest fully equipped service organization. 1.03 QUALITY ASSURANCE A. Service Availability A fully equipped service organization available to service the completed Work. 1.04 2.01 - A minimum of three (3) year warranty shall cover the LED exit sign. An additional seven (7) year pro-rata warranty shall cover the sealed maintenance-free NiCad battery. PRODUCTS EXIT SIGN (SINGLE FACED/DOUBLE FACED) (LED) A. NYCSCA be WARRANTY A. PART 2 shall Housing shall consist of precision die cast from high strength aluminum. Unit shall have a stencil face with stenciled letters and field selectable chevron knockouts. Letters shall be red and 8" high. ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 1 04/30/10 DESIGN NO. 012090 Fixtures shall be provided with an ultra long life, high intensity LED light panel mounted totally within the exit housing. A color-enhanced diffuser shall be mounted in front of the light panel to provide even illumination. The unit shall also be provided with a maintenance-free sealed Nicad battery, which shall provide 90 minutes of illumination in the event of power failure. Provide a charger-monitor LED which when lit, will indicate current is supplied to the LED panel. Provide also momentary test switch to simulate power failure. Upon pressing of the test switch, the LED monitor should turn off, but the exit sign should stay lit, indicating that the battery is supplying power to the LED panel. Finish shall be aluminum face. matte black acrylic with brushed Provide suitable guard manufactured by Chase Security series CSGW, Atlite model AIGl6-12jw or approved equal, when indicated on the drawings. Fi:tures shall be McPhilben ER40Lll2R, Atlize #LN28DRl-TPS-SCAl25 for single face sign or McPhilben ER40L212R or Atlite #LN2-8DR2-TPS-SCA125 for double face sign, Guth, Lightalarms, Lightron, MagniFlood, Ruud Lighting, or Solux. 2.02 EMERGENCY LIGHTING REMOTE FIXTURES A. Double And Triple Lighting Heads: Head with fully adjustable swivel, all aluminum construction and satin aluminum finish. Unit shall be wall mounted directly to a 4" outlet box at 8'-0" above finished floor. Two-head unit shall be lightalarms #ELF622D or Atlite #RF402-MRS-12RS25 with two (2) 2S-watt double contact bayonet base lamps. Three-head unit shall be Lightalarms #ELF622T or Atlite #RF403-MRS-12RS25. B. Recessed Round Gimbal: Fixtures shall have welded steel housing and metal trim. Lamp shall have a horizontal rotation of 358 degrees and vertical angle adjustable to 42 degrees. Fixture shall be Lightalarms #ELF605M or approved equal of Atlite, with standard white finish, complete with one 25-watt double contact bayonet base lamp. NYCSCA ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 2 04/30/10 C. DESIGN NO. 012090 Surface Round Gimbal: Same as recessed unit detailed in "B" above, except suitable for surface mounting. Lightalarms #ELF606M, standard white finish or approved equal of Atlite, complete with one 25 watt lamp, 12 volts sealed beam incandescent. D. Emergency Battery Units 1. 2. 3. NYCSCA 12-volt maintenance free emergency battery unit with automatic solid state constant voltage charger and sealed lead calcium battery with mounting platform at locations shown on Drawings. Wattage of all battery units shall be 200 watt unless otherwise noted on the Drawings. Battery units shall power fixtures listed above. Battery units shall consist of the following items: a. Solid State Charger b. Full Wave Silicon Rectifier C. Instantaneous Transfer Relay d. Circuit shall be battery short circuit and reverse polarity protected. Output shall be electronically short circuit and overloaded protected. e. Automatic brown out requirement f. Diagnostic LED panel shall include minimum the following functions: battery charge/ failure, lamp failure, and circuit transfer failure. g. Momentary test switch and AC adapter h. Heavy duty 18 gauge steel case i. Finish: housing to be white powder amp heads to be brushed aluminum. j. Battery shall be 12 sealed lead calcium. volt, coated. maintenance tree Unit shall be Lightalarms Electronics Corp., Catalog #2P12Q1 (100 Watts) and #2P12Q2 (200 Watts) or Atlite Catalog #12ADSNY5-0 (100 Watts) or 12ADSNY7-0 (200 Watts). ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 3 DESIGN NO. 012090 04/30/10 E. 2.03 4. Mounting platform shall be Lightalarms Electronics Corp., Catalog #MP-PQ or approved equal of Atlite. 5. Wire guards for battery units shall be Lightalarms Electronics Corp., Catalog # WG3, Atlite Cat# AD, or Chase Security. 6. Lamps shall be 25-watt PAR 36 size, white flood high intensity, numbered as required on Drawings. Relay Remote Control 1. The Contractor shall provide and connect a remote emergency ceiling to control relay control lighting and battery operated emergency lighting as shown on Drawings. 2. Power for relay shall be obtained Lighting panel at each location. 3. Remote control relay shall be Square D #8903 with number of contacts required, suitable for 120-volt operation. from Local WIRE GUARDS A. PART 3 3.01 - Where fixtures are so designated, provide a guard suitable for that fixture, as provided by the fixture manufacturer. At a minimum, guards shall be provided on fixtures in gymnasiums and cafeterias. EXECUTION GENERAL A. The Contractor shall adjust the aim of the emergency lighting fixture heads to obtain maximum lighting level at areas so as to meet the footcandle levels required by the 2008 NYC Building Code. B. Install the emergency lighting system in a dedicated conduit system to comply with New York City Electrical Code 3.02 FIXTURE INSTALLATION A. NYCSCA The Contractor shall be responsible for the mounting and support of all exit signs, battery packs, and emergency lighting fixtures. Provide all items of equipment (stems, hangers, rods, inserts, boxes, brackets, yokes, channels, frames, etc.) required to adequately and safely support each exit sign and ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 4 04/30/10 DESIGN NO. 012090 emergency lighting fixture in a manner acceptable to the Authority B. The Contractor is required to protect fixtures from damage during installation, up to time of acceptance by the Authority. Any broken or marred fixtures shall be replaced by the Contractor at no additional cost to the Authority. C. Pendant Mounted Fixtures on Suspended Ceiling Pendant mounted exit sign shall be supported above suspended ceiling by hanger rods, 3/8" in diameter minimum, vertically attached to approve straps, bars, channels secured to the black iron where available, or to structural steel or concrete. ID. Surface mounted exit signs Surface mounted exit signs shall have their own back boxes, custom fitted to the signs. Ceiling and end wall-mounted exit signs shall be provided with a die cast canopy and a back box. All surface mounted exit signs and their back boxes shall be anchored to the wall at four (4) points. 3.03 AIMING A. 3.04 CLEANING A. 3.05 After the installation and prior to final acceptance, all Emergency Lighting shall be adjusted under the supervision of the Authority's Representative and the Engineer to provide code mandated lighting levels at means of egress. All fixtures shall be cleaned both inside and out prior to final acceptance to remove all construction debris, dust, fingerprints, exposed labels etc. Fixtures and or parts, which have been damaged, chipped, scratched or inadvertently painted during construction, shall be repaired or replaced at the direction and discretion of the Authority's Representative. FIELD QUALITY CONTROL A. Progress Inspections 1. NYCSCA The Authority will carry out all progress inspections in accordance with Section BC 109 and the applicable sections of the 2008 NYC Building Code. Inspections will include the following: ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 5 04/30/10 DESIGN NO. 012090 a. 2. Public assembly emergency §28-116.2.2 of Title 28. lighting per The Contractor must notify the Architect or Engineer for Progress Inspection at least 72 hours before the specific work commences. END OF SECTION NYCSCA ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 6 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data Warranty Certificate of compliance With the Quality Assurance Requirements Operation and Maintenance Manuals * NYCSCA ** ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES 16520 - 7 THIS PAGE INTENTIONALLY LEFT BLANK - 04/30/10 DESIGN NO. 012090 SECTION 16725 TELEPHONE CABLING SYSTEM PART I - GENERAL 1.01 DESCRIPTION OF WORK A. The intent is to provide new telephone device and telephone cabling system to replace the existing that are to be demolished. The specification includes horizontal and riser wiring for telephone system. The work shall include but not limited to all cables, conduits, outlets, etc. The Authority requires that all components including cable, connectors and outlets meet or exceed applicable performance standards for voice communications. 1.02 SUPPLEMENTAL SUBMITTALS A. Submittals Package Submit the Shop Drawings, Product Data submittals specified below at the same time as a single package. B. Shop Drawings 1. C. Composite wiring and/or schematic diagrams of the complete cabling system as proposed to be installed (standard diagrams will not be acceptable). Product Data 1. Catalog sheets, factory assembly drawings, specifications and installations for all products. Documents will not be accepted for review unless they are submitted as a package where they pertain to related items, and clearly identified or highlighted to indicate all items which are applicable. 2. Bill of materials. D. Sample of lock box & cable E. Cabling System acceptance test report. 1.03 CABLE DELIVERY A. NYCSCA No cable over one (1) year old when delivered to the site will be accepted. TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 1 04/30/10 DESIGN NO. 012090 1.04 CABLING SYSTEM ACCEPTANCE A. Inspection of the installed cable system shall be made by the Authority to verify that the installation conforms to all the requirements stated herein, and that the cabling system is 100% defects free. The acceptance criteria shall include, but not be limited to: Completed installation and wire, cable, and raceway. functional operation of PART 2 - PRODUCTS 2.01 LOCK BOX A. In new partitions, boxes shall be flush or semi-flush mounted type with finishing collars. Surface mounted boxes shall be utilized for existing partitions. All boxes shall utilize a piano hinge welded or bolted on the inside. Bolted assemblies shall utilize nylon locknuts. B. Lockbox shall be provided with means to connect a single line wall mounted Category C RJ-45 telephone jack plate. Telephone Lock Box Jack model number shall be MX-WP-K6-SS C. Surface Mounted Lockboxes: Four '" diameter holes shall be provided on the back of the enclosure for surface wall mounting. Surface mounted boxes shall not be provided with finishing collar. Two (2) knockout holes shall be provided (one on the top, one on the bottom) for surface metal raceway connections. D. Flush or Semi-flush Lockboxes: Flush or semi-flush mounted boxes shall utilize a 1-1/4" finishing collar. Two (2) 14" diameter holes shall be provided on each side of the box for flush or semi-flush mounting. Two (2) " diameter knockout holes shall be provided (one on the top, one on the bottom) for EMT conduit connectio-. E. Lockbox must be painted, beige textured, made of 16 gauge corrosion resistant steel, dimension 121H X 8"W X 61"D. F. The lockbox shall have a keyed latch installed. Provide two keys per lockbox. shall be keyed alike. G. Lockbox shall be mounted so that the center of phone, when installed, is 48" from the floor. NYCSCA door lock All boxes the TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 2 04/30/10 H. DESIGN NO. 012090 Recommended Lockbox: Anixter-Unity LBI, Hoffman, or Lee. 2.02 INTERMEDIATE DISTRIBUTION FRAME (MDF) - NOT USED FRAME (IDF) AND Lowell, Artel, MAIN DISTRIBUTION 2.03 WIRING A. Conductors All station wiring shall have legible color coding of conductors and be four (4) pair, Unshielded Twisted Pair (UTP), 24 gauge. Voice cable must adhere to all performance specifications indicated for TIA/EIA Category 6 UTP media as cited in TIA/EIA 568B.2 standard. Cable must be approved by the Underwriter Laboratories, Inc. and must bear exterior jacket markings of "Verified Level 6" or "Classified Level 6". 2.04 LABELING OF CABLES, JACKS AND CONNECTING BLOCKS: A. Cables are to be tagged at both station and closet ends with an alpha and four-digit number beginning with V001 and increasing in increment of 1. It shall be a sticky tag, wrapped and secured to the cable behind both the jack faceplate and connecting blocks. All cable and termination labels are unique identifiers, which shall be permanent and comply with TIA/EIA 606 labeling standards. At the closet end, the connecting block termination is labeled at the corresponding panel port with two points of information concerning the far end and each separated by a dash: (1) Room number at the other end of the cable (2) Cable number (four digits) At the station side, the jack faceplate is labeled with two points of information pertinent to the cable far end and each separated by a dash: (1) Room number from the IDF or MDF (2) Cable number on the jack faceplate (four digits) The cable numbers shall be in sequence for each closet. For example, if there are 50 voice cables originating from IDF-i, then the cable numbers shall be V001 thru V050. Each closet would start over from V001. B. Identification of all equipment frames, racks, and wall termination fields shall be by means of engraved lamacoid nameplates showing 1" high white lettering on a black background. C. Provide a riser diagram framed under glass mounted on wall near the MDF. NYCSCA TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 3 04/30/10 DESIGN NO. 012090 2.05 CABLE TIES A. All cable ties used to support telecommunications cabling shall be fire-resistant nylon type. The support rating of the cable ties used shall be a minimum of twice that of the weight per unit of the cables to be supported. Cable ties shall be deployed every four (4) feet minimum for voice cables in horizontal cable tray and two (2) feet minimum when fastening cables vertically on wall or rack. 2.06 TERMINATIONS A. Cable Runs Shall Terminate as Follows: 1. Standard desk phone station run in offices and in administrative areas shall be two (2) four pair Category 6 cables; one Category 6 designated for voice and the other Category 6 designated for data. This station shall be terminated on a duplex combination faceplate consisting of two RJ-45 type, eight conductor modular outlets configured as per TIA/FIA jack designation T568B. The voice and data modular RJ-45 inserts shall be color coded to differentiate the two. A blue insert for voice and orange for data is recommended. Connecting hardware shall be marked and comply with TIA/EIA performance levels 6 associated with the particular cable being terminated. 2. For wall mounted telephones in classrooms, four pairs of voice cable (Category 6e) shall terminate at a wall mounted assembly in a metal lockbox with eight conductors, modular RJ-45 outlet mounted at 41-0" A.F.F. At the station end, all four pairs must be terminated at the IDF/MDF. 3. At the IDF/MDF, all cable pairs shall be terminated in consecutive order starting in the upper left hand co.ner of the frame and proceeding from the top to bottom and left to right. PART 3 - EXECUTION 3.01 INSTALLATION - NOT USED 3.02 GROUNDING - NOT USED NYCSCA TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 4 04/30/10 DESIGN NO. 012090 3.03 TESTING A. Cabling System Acceptance Test: 1. B. Each station cable and wall phone assembly cable shall be tested end-to-end (from jack faceplate to associated IDF or MDF 110 block) for length, continuity(wiremap),Propagation delay, NEXT (near end crosstalk),PSENEXT, PSELFEXT impedance, resistance and attenuation. Testing shall be conducted with cable certification device capable of performing appropriate bandwidth /certification test; i.e. Category 6 cable for voice shall be tested at 100 MHz and Category 3 riser shall be tested for 16 MHz. Test result shall be printed for each test parameter and submitted to the Authority. Any cable run not meeting minimal requirements shall be repaired or re-run, and then re-tested for compliance. Category 6 cable testing shall be performed using PLUKE NETWORKS OMNISCANNER II. Refer to specification 16727, Local Area Network (LAN) Cabling System, for the testing of the cable. Category 3 riser cable testing shall be performed by INDEPENDENT TECHNOLOGIES TEST ALL 25 with 110 punch down adapter kit. C. All defects or deficiencies discovered in the cabling system work must be indicated on the test report and be corrected. Any connections determined to be not correctable shall be indicated at each end of termination as "bad" (in red). END OF SECTION NYCSCA TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 5 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Shop Drawings Product Data Sample of lock box & cable Cabling System acceptance test report. NYCSCA TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 6 04/30/10 DESIGN NO. 012090 SECTION 16727 DATA CABLING SYSTEM PART I - GENERAL 1.01 DESCRIPTION OF WORK The intent is to provide new data devices and cabling system to replace the existing that are to be demolished. 1.02 SUPPLEMENTAL SUBMITTALS A. Product Data: 1. Catalog sheets, factory assembly drawings, specifications and installations for all products. Documents will not be accepted for review unless they are submitted as a package where they pertain to related items, and clearly identified or highlighted to indicate all items that are applicable. D. Shop Drawings: 1. C. D. E. Composite wiring and/or schematic diagrams of the complete cabling system as proposed to be installed (standard diagrams will not be acceptable). Sample: Prior to assembling or installing the data communications works, the followings shall be submitted for review. 1. Category 6 Cable. 2. Cable connector 3. Wiring device plate complete with label 4. Identification label Certificate of compliance with the Quality Assurance and Maintenance requirements. Certified Test Report 1.03 CABLE DELIVERY A. No cable over one (1) year old when delivered to the site will be accepted. 1.04 QUALITY ASSURANCE A. Installer's Qualifications: The persons actually installing the work of this section shall have a minimum of two-(2) year's experience in Data Cabling System. Installer must be NYCSCA DATA CABLING SYSTEM 16727 - 1 04/30/10 DESIGN NO. 012090 certified by the certification must approval. PART 2 - cable manufacturer and proof of be submitted to the Authority for PRODUCT 2.01 MANUFACTURERS A. Acceptable manufacturers of Data cabling system are AMP/TYCO, Hubbell Premise Wiring, Ortronics, Krone, Panduit and Lucent. All equipment shall be the product of one manufacturer for compatibility and shall fully meet all the requirements of this specification. B. Acceptable cable manufacturers are AMP/TYCO,Belden, Mohawk, Berk-Tek, Hubbell Premise Wiring, Panduit and General Cable. 2.02 DATA NETWORK A. Data network cabling system described herein is based upon TIA/EIA 568A Commercial Building Wiring standard. The installation shall include but not be limited to the following. 1. Category 6 cable: Cable shall be four pairs of 23 AWG solid conductors, unshielded twisted pairs, UL/NEC CMR rated with PVC jacket, cable jacketing shall be lead-free, AMP/TYCO P/N 216560-1. The cable shall meet the following performance requirements in addition to other standard Cat 6 performance requirements. * Frequency 250 MHz " Max. Attenuation - 30.5 db/100 meter " NEXT (Near End Cross Talk) - 48 db minimum tolerance * ACR (Attenuation to Cross Talk Ratio) - 17.5 db at 90 meter Contractor shall provide UL-listed plenum rated cable (Type CMP) in environmental air spaces, including plenum ceiling. AMP/TYCO P/N 219567-1. The following color code shall be utilized: COLOR CODE PAIR NO. White/Blue and Blue/White White/Orange and Orange/White White/Green and Green/White white/Brown and Brown/white NYCSCA 1 2 3 4 DATA CABLING SYSTEM 16727 - 2 04/30/10 DESIGN NO. 012090 2- Faceplate: Provide faceplate with integrated connector and modular jacks to accept input cable and provide combination jacks as required. Faceplate shall be plastic in a color selected by the Architect, with color-matched screws. Unit shall be AMP/TYCO P/N 557505, Panduit P/N CFPL2EI Hubbell Premise Wiring IFP Series Faceplates, or approved equal suitable for mounting on a single device box. 3. Data Jack: Data jack shall be Category 6 modular eight-pin connector, EIA T568B wiring, UL listed. AMP P/N 1375055-1, Hubbell Premise Wiring P/N HXJ5EWH, Panduit P/N CJSE88TGWH or approved equal for single jack. 4. 5. NYCSCA Labels a. Provide laser Printable labels on all cables detailing cable run number. Identification shall be by means of wrap around Hubbell Premise Wiring P/N XPLCBLA2 adhesive cable labels produced via AMP/TYCOLabelingSoftware AMPNETCONNECT.COM/LA9EL, Hubbell Premise Wiring Labeling Software and a standard laser printer All station outlets, MDR and LDF must be labeled and all circuits clearly identified utilizing designation strips in compliance with TIA/EIA 606 standards. b. Labels for risers, cables, faceplates, cover plates etc. shall be provided with textual descriptions. c. Identification of all equipment frames, racks, and wall termination fields shall be by means of engraved lamacoid nameplates showing 1" high white lettering on a black background. Cable Ties: All cable Ties used to support telecommunications cabling shall be fire-resistant Velcro type. Cable Ties to be installed by Panduit GTS Cable Tie Tool. The support rating of the cable ties used shall be a minimum of twice that of the weight per unit of the cables to be supported. Cable ties shall be deployed every four (4) feet minimum data cables in horizontal cable tray and two (2) feet minimum when fastening cables vertically on wall or rack. DATA CABLING SYSTEM 16727 - 3 04/30/10 PART 3 - DESIGN NO. 012090 EXECUTION 3.01 INSTALLATION A. Workstation Cabling: 1. Workstation outlets may be described as one of the following: a. b. C. 2. 3. Voice and data outlet Data and data outlet Wireless Access Point data outlet A voice and data workstation outlet shall of the following cabling: consist a. One (1) Category Cat pair cable for voice AWG). b. One (1) Category 6 unshielded twisted pair cable for data (4 pair twisted, #23 AWG). A data and Data following cabling: outlet 6 unshielded twisted (4 pair twisted, #24 shall consist of the a. Iwo (2) Category 6 unshielded twisted pair cable for data (4 pair twisted, #23 AWG), 4. Workstation cabling may following locations: a. b. b. c. terminate in one of the Wall mounted box Floor flush or surface mounted poke-thru V4000 Wiremold Wireless Access Point 3.02 HORIZONTAL DISTRIBUTION CABLE INSTALLATION A. Maintain the twist of horizontal and backbone cables to within 0Y" at the fln of tcrmination. B. When running cable through dropped ceiling space, the Contractor shall assure proper cable strain relief at all times. C. Cable shall be installed so that there are no bends less than four times the cable's outside diameter (4X Cable O.D.) at any point in the run. D. Horizontal distribution cables shall not be bundled in groups of greater than 40 cables. Cable bundle quantities in excess of 40 may cause deformation of the bottom cables within the bundle. NYCSCA DATA CABLING SYSTEM 16727 - 4 04/30/10 E. DESIGN NO. 012090 Pulling tension on 4-pair UTP cables shall not exceed 25-pounds for a single cable. 3.03 LONWORKS LON DISTRIBUTION CABLE INSTALLATION - NOT USED 3.04 WIRELESS ACCESS POINT (AP) CABLE INSTALLATION A- The cable allocated for the wireless AP shall be home run from the floor's LDF or MDF to the room receiving the AP. The cable shall be terminated using a AMP/TYCO Premise Wiring Cat 6 yellow data jack P/N 1375055-8 or Hubbell Premise Wiring Cat 6 yellow data jack P/N HXJ5EY. Existing wireless access point shall be reinstalled. 3.05 GROUNDING - NOT USED 3.06 LABELING OF CABLES AND JACKS A. Cables are to be tagged at both station and closet ends with an alpha and four-digit number beginning with D001 and increasing in increment of I. It shall be a sticky tag, wrapped and secured to the cable behind both the jack faceplate and patch panel. All cable and termination labels are unique identifiers, which shall be permanent and comply with TIA/EIA 606 labeling standards. At the closet end, the patch panel termination is labeled at the corresponding panel port with two points of information concerning the far end and each separated by a dash: (1) Room number at the other end of the cable (2) Cable number (four digits) At the station side, the jack faceplate is labeled with two points of information pertinent to the cable far end and each separated by a dash: (1) Room number from the LDF or MDF (2) Cable number on the jack faceplate (four digits) The cable numbers shall be in sequence for each closet. For example, if there are 50 data cables originating from LDF-1, then the cable numbers shall be D001 thru D050. Each closet would start over from D001. 3.07 TESTING A. All tests are to be performed after installation of the complete system. E. The equipment indicated below represents test equipment utilized to develop this test specification. Substitute test equipment may be used only upon approval by the Authority's Engineer provided the same level and quality of testing is performed. NYCSCA DATA CABLING SYSTEM 16727 - 5 04/30/10 C. DESIGN NO. 012090 Test Equipment: FLUKE NETWORK OMNISCANNER II D. E. NYCSCA All tests are to be performed on the of data cabling system: following aspects 1. From Telecommunication room's main data rack (MDR) and LonWorks patch panels to corresponding telecommunication closets' patch panel and termination (backbone cable). For fiber optic backbone see section 16728. 2. From each telecommunication closet's to each and every workstation (workstation cable). patch panel termination Tests to be performed: 1. The test equipment shall be configured to test the maximum transmission performance for which the cable is rated (i.e. for category 6 cable is I to 250 Megahertz per second) 2. In accordance with TIA Standards for Category 6 (Full Duplex Parallel Transmission) cabling, the following minimum test information shall be provided for each permanent link: a. Wiremap: Verify Continuity on all 8 conductors and assure no opens, crosses, splits or shorts to another conductor or ground. When applicable, report continuity of shield on screen twisted pair. b. Length: Total length from LDF to workstation termination: The cable length shall conform to the maximum distance set forth in the TIA/EIA 568-A-5 standard (i.e. 90 M or 308 feet), C. Propagation Delay and Delay Skew: Will be measured and reported. Propagation Delay will not exceed 536 nanoseconds and Delay Skew will be within 45 nanoseconds between the fastest and slowest conductor pairs. d. Near End Cross Talk (NEXT) or Noise: Sweep and Measure (I MHz to 250 MHz) each pair combination. Limits will not be less than 48 db at 250 Mhz. on any combination. e. Attenuation: (db loss): Sweep and Measure each cable for proper attenuation according DATA CABLING SYSTEM 16727 - 6 04/30/10 DESIGN NO. 012090 to TIA specifications at 1 MHz to 250 Mhz. Limit will not be less then +17.5db at 250 MHz. f. Return Loss or Echo: Sweep and cable for minimum return loss TIA specifications from 1 MHz Limit will not be greater then 250 MHz. g. Equal Level Sweep and Far End Measure Cross each Measure each according to to 250 Mhz. -27.7 db at Talk cable for or ELFEXT: a minimum ELFEXT according to TIA specifications from 1 Mhz to 250 Mhz. Limit will not be greater than -29.9db at 250 MHz. F. h. PowerSum Near End Cross Talk or PSNEXT: Sweep and Measure each cable for a minimum PSNEXT according to TIA specifications from 1 MHz to 250 Mhz. Limit will not be greater than -49.2 db at 250 MHz. i. PowerSum Elfext or PSELFEXT: Sweep and measure each cable for a minimum PSELFEXT according to TIA specifications from 1 MHz to 250 Mhz. Limit will not be greater than -42.6 db at 250 MHz. All test formats: results shall be 1. Printed (3 bound copies) 2. CD ROM (Windows) provided in the following The test equipment specified has the ability to record test results to electronic memory for viewing and printing later utilizing free Microtest ScanLink software. Submitting electronic test results is preferred in lieu of handwritten forms. In no instance will test data be accepted in a spreadsheet or text based reporting software. This information shall be maintained as a permanent record for the purposes of maintenance and restorations. G. All tests shall be coordinated with and performed in the presence of the Authority's Representative. Any defects or deficiencies discovered in any of the cabling system work shall be indicated on the test report and be corrected. H. Upon completion of testing and problem resolution, all cables tested are to be 100% error free. NYCSCA DATA CABLING SYSTEM 16727 - 7 04/30/10 3.08 COORDINATION - NOT USED DESIGN NO. 012090 WITH SYSTEM INTEGRATOR FOR DATA LAN NETWORK END OF SECTION NYCSCA DATA CABLING SYSTEM 16727 - 8 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data Shop Drawings 1. Wiring Diagrams 2. Composite Rack panel Samples: 1. Cable 2. Cable Connector 3. Wiring Device 4. Identification label Certificate of Compliance with the Quality Assurance Requirements Certified Test Report NYCSCA DATA CABLING SYSTEM 16727 - 9 - THIS PAGE INTENTIONALLY LEFT BLANK - 04/30/10 DESIGN NO. 012090 SECTION 16728 FIBER OPTIC CABLING SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. 1.02 The intent of this specification is to provide new device and cabling system to replace the existing that are to be demolished. SUPPLEMENTAL SUBMITTALS A. Submit the shop drawings, product data, samples and quality control specified below at the same time as a single package. B. Product Data: C. 1. Catalog sheets, specifications instructions for all products. 2. Written statement from cable manufacturer indicating recommended pulling compounds. and installation Shop Drawings: 1. Complete manufacturers' construction details and specifications for the cables, including physical characteristics of optical fiber, strength members and jackets. 2. Overall dimension of cable. 3. Termination data, including the following: a. List of materials b. Method of terminating cables c. 4. Written statement from cable manufacturer that terminations submitted are acceptable, and suitable for the proposed application. Cable manufacturer's certified test data (attenuation, bandwidth). NYCSCA 5. Maximum pulling strain allowed for each type cable. 6. Composite wiring and/or schematic diagrams of the complete cabling system as proposed to be installed (standard diagrams will not be acceptable). FIBER OPTIC CABLING SYSTEM 16728 - 1 04/30/10 D. E. DESIGN NO. 012090 Samples: 1. Two(2) foot samples of each type cable. 2- Samples of termination materials if requested. Quality Control Submittals: 1. F. 1.03 Installers' Qualifications Data: Include following who will be performing the work: the a. Employers name, telephone number and b. Name and addresses of the required number of similar projects worked on which meet the experience criteria. business address Cabling system acceptance test report. QUALITY ASSURANCE A. Installers' Qualifications: The persons installing the work of this section shall be personally experienced in optical fiber cabling system and shall have been engaged in the installation of optical fiber cable for a minimum of two (2) years. 1.04 DELIVERY, STORAGE AND HANDLING A. B. Cable Delivery: 1. No cable over one (1) year old when delivered to the site will be accepted. 2. Keep ends of cables sealed at all times, except when making terminations. Use methods approved by cable manufacturer. Cable Storage: Store where cable will be at temperature recommended by cable manufacturer for optimum workability. PART 2 2.01 - PRODUCTS MANUFACTURER A. NYCSCA Acceptable Manufacturers are: Hubbell Premise Wiring, AMP Inc., Corning, ADC-Krone, Ortronics, Mohawk, Optical Cable Corporation, and Belden. FIBER OPTIC CABLING SYSTEM 16728 - 2 04/30/10 2.02 DESIGN NO. 012090 OPTICAL FIBER CABLE A. Six (6) strands (for horizontal run), single ripcords and core warp tape, full dielectric construction, UL listed OFNP for Plenum applications; continuous operating temperature -40"C to 700 C. Each fiber shall be 62.5/125 micron (core/clad)diameter, multimode graded index optical fiber waveguide operating at 850 and 1300 nanometer (nm), maximum attenuation 3.75 dB/km and 1.0 db/km respectively. Use UL-listed plenum cable in environmental air spaces, including plenum ceilings. 2.03 ENCLOSURE FOR OPTICAL FIBER TERMINATING BOX (OFTB) A. The unit is designed for termination of optical fiber cables. Individual strands shall be fanned out and terminated with SC connectors in an interconnect plate with twelve interconnect sleeves, following proper manufacturers' specifications for bend radius and strain relief1. Dimensions components. 2. Single lock. as gasketed required door for with installation continuous hinge of and a. Requires two box. b. c. Lock Kit: Hoffman's A-CLSN12 or approved equal of Lee Products Co. Lock shall be keyed the same as locks for fence accessory stations (FAS's). d. Provide two (2) coupler panels per 12 port (2) keys. 3. 14 gauge steel mounting plate within enclosure for mounting components and future components. 4. Louvers as required for ventilation and to prevent temperatures above equipment ratings. 5. Mounting accessories as required to mount in a standard 19" rack. 2.04 CONNECTORS A. NYCSCA Connector shall be a no-adhesive/no-epoxy/no-polish SC connector. The connector shall have a 62.5/125 micron fiber stub pre-epoxied and pre-polished in the ferrule tip. The fiber to be terminated shall be simply FIBER OPTIC CABLING SYSTEM 16728 - 3 04/30/10 DESIGN NO. 012090 prepped and cleaved before insertion into connector. The maximum optical attenuation per mated connector pair shall not exceed 0.5 dB. 2.05 INNERDUCT A. 2.06 Provide flame-retardant innerduct for protection, isolation and identification of fiber optic cable. Innerduct must meeL UL94 V-0 flame test for plenum. ACCESSORIES A. Pulling Compounds: manufacturer. H. Tags: Precision engrave letters and numbers with uniform margins, character size minimum 3/16" high. 1. C. PART 3 3.01 - As recommended by cable Phenolic: Two (2) color laminated engravers' stock, 1/16" minimum thickness, machine engraved to expose inner core color (white). Markers: Premarked self-adhesive; W.H. Brady Co.'s B940, Thomas and Petts Co.'s 7-Z Code WSL selflaminating, Ideal Industries' Mylar/Cloth wire markers, or Markwick Corp.'s permanent wire markers. EXECUTION PREPARATION A. 3.02 the each Before installing cable, test the cable on the reels to verify that the cables' parameters are in accordance with the manufacturers' certified test data. INSTALLATION A. Installing Cables: 1. No fiber optic cable shall be run unprotected. The cable shall bc protected as follows: NYCSCA Location Method of Protection Accessible ceiling Spaces Innerduct required Non-accessible ceiling Spaces Conduit Raised floor Wiremold Exposed Innerduct (plenum as FIBER OPTIC CABLING SYSTEM 16728 - 4 04/30/10 B. DESIGN NO. 012090 Location Method of Protection Within cabinets and Racks Innerduct or spiral wrapped buffer tubes 2. All raceways containing fiber optic cable shall be provided with a label "caution-Fiber Optic Cable" located on the raceway every 20 feet. 2. Keep ends of cables sealed watertight at all times, except when making splices or terminations. 3. No grease, oil, lubricant other than approved pulling compound may be used to facilitate the pulling-in of cables. 4. Use pulling attachment connected to the strength member for pulling in cables. pulling attachment watertight. Terminations: 1. All strands of fiber optic cable shall be terminated in SC type connectors at the outlets and fiber patch panels at the cabinet. 2. No splicing of allowed except: a. C. 2. fiber cables will be Connectorized splices will be allowed in the OFTB. Install tags on each cable indicating cable number, date installed (month, year), type of cable and manufacturer. Attach tags to cables with non-ferrous metal wire or brass chain. Use markers to identify each optical fiber in equipment to which they connect. FIELD QUALITY CONTROL A. Testing: 1. NYCSCA optical Identification of Optical Fiber Cables: Identify cables in MDR, LDFs and at all fiber outlet locations: 1. 3.03 cable Seal Perform test on optical fiber after cable has been installed complete with connectors. All strands shall be tested for end-to-end attenuation loss at 850 nm and 1300 nm. Procedure for the test shall comply with EIA/TIA 526-14-A, Method B: Optical FIBER OPTIC CABLING SYSTEM 16728 - 5 04/30/10 DESIGN NO. 012090 Power Loss Measurements Fiber Cable Plant. of Installed Multimode a. Demonstrate that the amount of power coupled into each optical fiber by its transmitter, the attenuation and connector losses, and the power received at the detector in the receiver is no greater than 75% of the parameters required by the transmitter/ receiver manufacturer. b. The total optical attenuation (dB loss) will not exceed .5 dB/per mated connector ports and 3.75 dB/km for the fiber. 2. Perform test in the presence of the Authority's Representative. Failed strands shall be corrected or replaced and re-tested for compliance. 3. Supply equipment Optical Time Domain Reflectometer (OTDR) necessary for performing test. 4. Submit printed results shall information : a. b. c. d. e. f. report of test results. Test contain the following minimum Cable origin Cable destination Cable ID Cable pair/strand Test date 2 point attenuation (d3) 3.04 EQUIPMENT INSTALLATION AND TESTING - NOT USED END OF SECTION NYCSCA FIBER OPTIC CABLING SYSTEM 16728 - 6 04/30/10 DESIGN NO. 012090 LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data: 1. Catalog Cuts 2. Written statement Shop Drawings: Samples: 1. Cables 2. Termination materials Quality Control Submittals 1. Installers Qualifications Test Report: NYCSCA FIBER OPTIC CABLING SYSTEM 16728 - 7