A. Provide labor, materials, tools, machinery

advertisement
04/30/10
DESIGN NO. 012090
SECTION 16010
GENERAL PROVISIONS FOR ELECTRICAL WORK
PART 1 - GENERAL
1.01 SCOPE OF WORK
A.
Provide labor, materials, tools, machinery, equipment,
and services necessary to complete the Electrical Work
under this Contract.
All systems and equipment shall
be complete in every aspect and all items of material,
equipment and labor shall be provided for a fully
operational system and ready for use.
Coordinate the
work with the work of the other trades in order to
resolve
all
conflicts
without
impeding
the
job
progress.
B.
When an item of equipment is indicated on a floor plan
and not shown on associated riser diagram or viceversa, the Contractor shall provide said item and all
required conduit and wiring connections for a complete
system as part of the Contract.
1.02 EXAMINATION OF SITE
A.
The Contractor shall be held to have examined the site
and
to have compared it with
the Drawings and
Specifications, and deemed to have been satisfied as to
the conditions existing at the site, as relating to the
actual conditions of the site at the time estimating
the Work, the storage and handling of materials, and
all other matters as may be incidental to the Work
under the Contract, before bidding, and no allowance
will subsequently be made to the Contractor by reason
of any error due to the Contractor's neglect to comply
with the requirements of this clause.
1.03 RELATED DOCUMENTS
A.
Drawings and General Provisions of the Contract.
B.
Division 1
-
General and Supplementary Requirements.
1.04 ELECTRICAL EQUIPMENT
A.
All electrical equipment shall be the latest of the
current year in design, material and workmanship, and
shall be the type or model called for in these
Specifications.
B.
If the type or model specified has been superseded by a
later type or model, the latest shall be submitted for
approval and shall be provided as part of the Contract.
NYCSCA
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 1
04/30/10
DESIGN NO. 012090
1.05 SUBMITTALS
Provide as outlined in each individual section
Specifications, including but not limited to:
of
these
A.
Product Data:
Submit manufacturer's product data for
equipment including capacity, performance charts, test
data, materials, dimensions, weights, and installation
instructions.
B.
Shop Drawings:
Submit manufacture's shop drawings
indicating
dimensions,
weight
loading,
required
clearances,
location,
and method of
assembly of
components.
Submittals are mandatory as noted in the respective
specifications. Schedules, installation instructions,
startup manuals, operation and maintenance manuals, and
shop drawings are always required to be submitted.
C.
Samples
D.
Special Warranty
E.
Quality Assurance submittals
F.
Operation and Maintenance Manuals
G.
Test results and certificates
H.
Manuals and video tape of the personnel training.
1.06 COORDINATION DRAWINGS
A.
Coordination Drawings; The Electrical contractor shall
cooperate with the HVAC, P&D, and Fire Protection
Systems
contractors
in
the
development
of
the
coordination
drawings.
The
drawings,
indicating
ductwork, steam, hydronic & fuel piping, etc. shall be
generated by the HVAC contractor, who in turn is to
provide them to the hiecurical contractor for the
inclusion of electrical work in this coordination set.
This is after the P&D and Fire Protection Systems
contractors have entered their information in the set.
The specified order in which the trade contractors
impose their work on the coordination drawings is not
intended to grant priority to any one trade contractor
in the allocation of space. At the completion of this
phase, hold a coordination meeting to eliminate any
interference
among the
trades
that
the
drawings
indicate and to avoid any conflicts in installing the
Work.
NYCSCA
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 2
04/30/10
DESIGN NO. 012090
1.07 BUREAU OF ELECTRICAL CONTROL
A.
B.
C.
Drawings and Specifications:
1.
The Contract Drawings and Specifications shall be
submitted by the Contractor to the Bureau of
Electrical Control to facilitate any inspections
that may be made by that agency.
2.
It is the intent of these Specifications that all
electric work shall be done in strict accordance
with the rules of the Bureau of Electrical
Control, and with the NYC Amendments to the 2005
National Electrical Code together with NEPA's 2005
National Electrical Code.
Where the requirement
of the Drawings or Specifications exceeds the
requirements
of
the
Electrical
Code,
the
requirements of the Drawings and Specifications
shall be binding upon the Contractor.
3.
Should the Bureau of Electrical Control inspect
the work and issue a violation, the Contractor
shall correct the Work and eliminate the violation
as part of the Contract.
Interpretation
1.
The electric work detailed in these Specifications
and
shown
on
Drawings
shall
be
under
the
jurisdiction of the Authority, subject to the
approval of the Bureau of Electric Control.
2.
The Authority shall be the sole source
for
interpretation of the Contract Documents.
Any
discrepancies or conflicts shall be brought to the
attention of the Authority for clarification.
Materials and Appliance:
All materials and appliance
shall be approved by the Authority's Representative and
installed in accordance with the rules and regulations
of the Building Department, Bureau of Electrical
Control;
certificates
of
approval
the
temporary light and power wiring, shall including
be obtained by
the Contractor
and delivered
to
the Authority's
Representative before the Work is finally accepted.
1.08 WORK IN EXISTING BUILDINGS
A.
NYCSCA
The Contractor is referred to Section 01900 on General
Requirements of Work in Existing Structures which shall
apply to the Work of this Contract.
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 3
04/30/10
DESIGN NO. 012090
B.
Refer to Section S01900 on the "Ownership of Removed
Materials."
Generally that article shall apply except
for those items which are listed here in for delivery
to the Bureau of Shops at 44-36 Vernon Boulevard, Long
Island City, New York 11101.
All other existing
material, fixtures, and equipment which have been
removed shall not be used again unless specifically
required by the Drawings or Specifications.
C.
Removals, Replacements, Adjustments
D.
1.
The Contractor shall remove, relocate, replace,
adjust or adapt, all existing conduit, wiring and
other
electric
equipment
or
apparatus,
as
required, to provide a complete installation.
2.
The Work shall include, providing all materials,
all necessary extensions, connections, cuttings,
repairing, adapting and other Work incidental
thereto, together with such temporary connections
as may be required to maintain service pending the
completion of the permanent Work. All Work shall
be left in good working order and in a condition
equal to the adjacent new or existing Work.
Care in Removing Existing Conductors
1.
E.
The Contractor shall use due care and diligence in
removing
existing
conductors
from
existing
conduits in order to prevent conductors from
breaking and becoming an irretrievable obstruction
within the conduits.
Cutting and Repairing
1.
Whenever the cutting, or drilling, or removal of
any part of the structure
(ceilings, walls,
floors, shelving, bookcases, partitions, etc.), is
required in order to remove, relocate, alter or
install
any
article
of
electrical
equipment
(including conduits, boxes, fittings, etc.), the
Contractor shall perform all cutting, drilling,
etc.,
and
remove
the
section
of
structure
required.
After removal and installation of the
electric equipment, the Contractor shall repair
the section of structure
as directed by the
Authority's Representative, with new materials,
equal to that of adjacent structure of the same
type.
Note that in general, all holes through existing
structures for conduit installation shall be core
drilled, unless prior written approval is provided
by the Authority.
NYCSCA
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 4
04/30/10
DESIGN NO. 012090
Contractor
shall
drilling
to
infrastructure.
use
avoid
extreme
damaging
care
the
when
core
existing
2.
Whenever holes are cut in fire-rated walls or
floor slabs in order to permit the installation of
conduit or electrical equipment, these holes shall
be repaired with material that will restore the
fire rating of the wall or floor slab to its
original condition.
3.
The Contractor shall paint all repaired areas of
the building. The paint shall match the paint of
adjacent surface areas, or extend to the nearest
architectural break-line, as directed.
4.
Wherever any part of the structure is marred or
damaged, the Contractor shall repair the damaged
or marred areas of the structure.
5.
Where a piece of electrical equipment is removed,
the Contractor shall finish that part of the
surface to match surroundings.
F.
Damaged Apparatus:
Should any damage, due to the
execution of this Contract, occur to the furniture,
fixtures, or any equipment or apparatus, such damage
shall be properly repaired and/or replaced by the
Contractor without charge.
G.
Non-Interruption of Services
1.
It is
imperative that all existing services
(electric,
light,
power,
fire
alarm,
telecommunications, etc.) be kept in operation at
all
times, unless prior written approval
is
received from the Authority.
2.
Provide fire watch services, as necessary, during
disruption of fire alarm system.
1.09 TESTS
A.
NYCSCA
The Contractor shall
demonstrate to
the Authority
operation of all equipment and systems.
All tests
shall
be
completed
to
the
satisfaction
of
the
Authority.
Each test shall be performed as indicated
in the individual specification section.
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 5
04/30/10
DESIGN NO. 012090
1.10 GUARANTEES, WARRANTIES, BONDS, AND MAINTENANCE CONTROL
A-
Refer to Section G01740 for procedures and submittal
requirements for warranties.
Refer to individual
equipment specifications for warranty requirements.
1.
Compile and assemble the warranties specified for
Electrical work into a separated set of documents,
tabulated and indexed for easy reference.
2.
Provide complete warranty information for each
item to include product or equipment including
duration
of
warranty
or
bond;
and
names,
addresses, and telephone numbers and procedures
for
filing
a claim
and
obtaining
warranty
services.
3.
Warranties for the equipment, workmanship and
materials should be provided for the period of one
year with the exception of the warranty on the
refrigeration
compressors.
Five(5) years
warranty shall be provided for the refrigeration
compressors.
4.
Manufacturers',
in
addition
to
Contractors'
warranties, shall be provided for all Electrical
equipment and accessories.
5.
All warranties are to
Substantial Completion.
start
from
the
date
of
1.11 OPERATIONS, TRAINING, AND MAINTENANCE MANUALS
A.
General
1.
Refer
to
Section
S01730:
SYSTEMS
OPERATION
AND
MAINTENANCE MANUAL for procedures and requirements
for preparation and submittal of operation and
maintenance manuals for each equipment.
Refer to
individual
equipment
specifications
for
mainteniance manual additional requirements.
In
addition, include the following information:
NYCSCA
2.
Description
of
function,
normal
operating
characteristics
and
limitations,
performance
curves, engineering data and tests, and complete
nomenclature
and
commercial
numbers
of
all
replaceable parts.
3.
Manufacturer's printed operating procedures to
include start-up, break-in, routine and normal
operating
instructions;
regulation,
control,
stopping, shut-down, and emergency instructions;
and summer and winter operating instructions
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 6
04/30/10
DESIGN NO. 012090
4.
Maintenance procedures for routine preventative
maintenance
and
troubleshooting;
disassembly,
repair, and reassemble; aligning and adjusting
instructions.
5.
Servicing instructions and lubrication charts and
schedules.
B.
Bind all the other Sections maintenance manuals in a
single final Operating and Maintenance Manual with the
requirements of Section S01730: SYSTEMS OPERATION AND
MAINTENANCE MANUAL.
C.
Refer
to
Section
S01650:
FACILITY
START-UP,
DEMONSTRATION
AND
TRAINING
for
procedures
and
requirements for training on each equipment.
Refer to
individual equipment specifications for the additional
training requirements.
D.
Contractor shall videotape all the training sessions
for various equipment and systems as specified in
individual sections of these Specifications.
If a
manufacturer's particular equipment item is furnished
with a training video, the manufacturer's video shall
be provided in addition to the requirements of this
Section, not in lieu thereof and at no additional cost
to the Authority. Contractor shall be responsible for
providing
informative videotapes covering all
the
materials and content outlined in each individual
section of these Specifications.
1.12 CLEANING AND REPAIR
A.
On completion of installation, inspect interior and
exterior of installed equipment. Remove paint splatters
and other spots.
Vacuum dirt and debris; do not use
compressed air to assist in cleaning.
Repair exposed
surfaces to match original finish.
B.
Contractor shall not leave sharp exposed metal edges
(bottom of
threaded
rods,
electrical
equipment
supports, etc.) that could otherwise present safety
hazards to the building's occupants/work staff.
1.13 SEISMIC RESTRAINT - NOT USED
1.14 EMS/DDC COORDINATION - NOT USED
1.15 SPECIAL INSPECTIONS
A.
NYCSCA
Refer to Section S01400 for requirements.
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010
-
7
04/30/10
B.
DESIGN NO. 012090
The following Special Inspection is required by the NYC
Building Code for the Electrical Trade:
Item
Code Section
Fire Alarm Test
BC 907 BC
1704.13
END OF SECTION
NYCSCA
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010 - 8
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED DATE APPROVED
Product Data
Shop Drawings
Samples
Special Warranty
Quality Assurance submittals
Operation and Maintenance
Manuals
Test results and certificates
Manuals and video tape of the
personnel training.
NYCSCA
GENERAL PROVISIONS FOR ELECTRICAL WORK 16010
-
9
-
THIS PAGE INTENTIONALLY
LEFT BLANK
-
04/30/10
DESIGN NO. 012090
SECTION 16120
WIRING SYSTEMS
PART 1 - GENERAL
1.01 DESCRIPTION OF WORK
Install all conductors as required for the proper operation
of the various systems specified. All connections shall be
made complete, and all systems shall be energized and
tested for proper operation.
1.02 QUALITY ASSURANCE
A.
Wire manufactured over one year prior to
the site will not be accepted.
B.
Tapes for splices or termination shall be dated by the
tape manufacturer to indicate that they have been
manufactured no longer than six months prior to use in
the Work of this Section.
delivery to
1.03 DELIVERY, STORAGE, AND HANDLING
A.
Conductors shall be delivered at the building in
original packages or on reels, and shall have the tag
of
the
manufacturer attached
thereto
indicating;
Contractor's name, Project title and number, Date of
manufacturing.
B.
Store material in a clean, dry space and protect from
weather.
1.04 SUPPLEMENTAL SUBMITTALS
A.
Submit
a
Product
Schedule
indicating
the
item
description and manufacturer name. The Schedule will
be accepted by the Authority for record purposes only,
provided that the items are in full compliance with
the Specifications.
B.
Certificates
Provide affidavit stating that all
listed and meet the specifications.
NYCSCA
items used are
UL
WIRING SYSTEMS 16120 - 1
04/30/10
C.
PART 2
DESIGN NO. 012090
Submit
field
test
results
for
wires and cables,
including "Megger" readings with the method used.
-
PRODUCTS
2.01 WIRES AND CABLES
A.
General
I.
Conductors
I.P.C.E.A.
labeled.
2-
Conductors shall have 600 volts insulation
shall be of soft-annealed-uncoated copper of
conductivity. Copper
clad
conductors
are
acceptable.
3-
All conductors shall have identifiable lettering
on the insulator jacket as to voltage rating,
wire
type,
A.W.G.
size,
insulation,
and
shall
conform
standards,
and
to
be
A.S.T.M.
UL
listed
and
and
and
98%
not
manufacturer I.D_
B.
NYCSCA
Wire Description
1.
Type THHN/THWN:
750 C, THHN:
90 0 C shall have a
thermo-plastic polyvinyl chloride insulation with
nylon jacket for 600 volts, and shall comply with
ASTM, IPCEA S-61-402
(latest edition) and NEMA
WC5 (latest edition).
2.
Metal Clad Cable (Type MC) shall be a factory
assembly
of
conductors,
each
insulated
and
enclosed
in
a metallic
flexible
interlocking
metal tape armor of galvanized steel or aluminum.
A barc
inLernal grounding conductor shall be
included and
insulated
from
the outer
metal
armor.
All
conductors,
including
grounding
conductor, shall be a minimum of #12 AWG.
The
assembly shall be UL listed and rated 600 volts,
900 C.
3.
RHH/RHW-2
cable
is made
of
electrical
grade
ceramified silicon rubber insulating material to
protect the cable from fire and water. RHW power
cable shall be rated for 60OV, TUL listed and
shall maintain two hours fire rating.
WIRING SYSTEMS 16120 - 2
04/30/10
DESIGN NO. 012090
2.02 SPLICES AND TERMINATIONS
A.
PART 3
-
General
1.
All materials for making splices and terminations
shall be specifically designed for use with the
type
of
wire,
the
cable
insulation,
the
installation and the operating conditions of the
specific application and be UL listed.
2.
Grounding conductors and bonding jumpers shall be
connected by exothermic welding, listed pressure
connectors, listed clamps, or other listed means.
EXECUTION
3.01 PREPARATION
A.
Prior to pulling wires and cable, clean raceway
systems
of
all
foreign
matter
and
perform
all
operations necessary so as not to cause damage to
wires and cables while pulling.
3.02 INSTALLATION
A.
B.
General
1.
At least 6 inches of free conductor, measured
from the point in the box where it emerges from
its raceway or cable sheath, shall be left at
each outlet,
junction and
switch
point
for
splices
or
the
connection
of
luminaries
or
devices. Where the opening of an outlet, junction
or switch point is less than 8 inches in any
dimension, each conductor shall be long enough to
extend at least 3 inches outside the opening.
2.
Use approved lubrication when installing cables
in conduits and raceways. Any pulling compounds
shall be compatible with the finish of the wires
and cables furnished.
Type TNHN/THWN wire
1.
NYCSCA
Feeder and Branch Circuits
WIRING SYSTEMS 16120 - 3
04/30/10
DESIGN NO. 012090
2-
C.
Remote-Control
Signaling
Circuits:
Circuit Classes
otherwise indicated.
and
1, 2
Power-Limited
or 3, unless
Type MC Cable - Use in concealed installation of
ceiling and gypsum board for:
1.
2.
hung
Lighting Branch circuit.
Power branch circuit.
D.
Type RHW-2 Cable - Use where required by code. Install
as per manufacturer instruction.
E.
Lighting Fixture Wires
1.
F.
Identifications of Wires and Cables
1.
G.
For wiring within lighting fixtures only, where
sizes #14 AWG or smaller is required, use Type
TFFN.
Each wire and cable shall be identified by its
circuit
in
all
cabinets,
boxes,
manholes,
handholes,
wireways and
other
enclosures
and
access locations, and at all terminal points.
Terminations
1.
For Conductor Sizes Larger Than Terminal Capacity
On Equipment: Reduce the larger conductor to the
maximum
conductor
size
that
terminal
can
accommodate
(reduce section no longer than 1
ft.). Cutting of cable strands to fit terminal is
not acceptable.
3.03 FIELD TESTS
A.
NYCSCA
Test all feeder cables installed under this Contract
with a 1000-volt Megohmmeter.
Furnish the Authority's
Representative with
a copy of
the
"Megger" test
report, together with an outline of the method used.
Any
cable
not
attaining
the
minimum
reading
established in the code shall be replaced.
WIRING SYSTEMS 16120 - 4
04/30/10
DESIGN NO. 012090
3.04 COMMON NEUTRAL CONDUCTOR
A.
A common neutral may be used for 2 or 3 branch
circuits where the circuits are indicated on the
Drawings to be enclosed within the same raceway,
provided each branch circuit is connected to different
phase busses in the panelboard.
B.
Exceptions - The
separate neutral:
1.
following
Circuits
containing
interrupter devices.
circuits
ground
shall
fault
have
a
circuit
a.
Circuits containing solid state dimmers.
b.
Circuits
for
computers,
related equipment.
c.
Circuits
recommended
by
equipment
manufacturers to have separate neutrals.
peripherals
and
3.05 EQUIPMENT GROUNDING CONDUCTOR
Note that equipment-grounding conductors are not shown on
the Contract Drawings but it shall be provided when and as
required by code.
3.06 ELEVATOR WIRING - NOT USED
END OF SECTION
NYCSCA
WIRING SYSTEMS 16120 - 5
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Schedule
Certificates
Field test report
NYCSCA
WIRING SYSTEMS 16120 - 6
04/30/10
DESIGN NO. 012090
SECTION 16130
RACEWAYS, FITTINGS, SUPPORTING DEVICES, BOXES AND ACCESSORIES
PART 1
-
GENERAL
1.01 DESCRIPTION OF WORK
A.
Provide raceways, fittings, supporting devices, boxes
and accessories required for a complete system and its
proper operation.
B.
Coordinate layout and installation of raceways, boxes,
enclosures, cabinets, and suspension system with other
construction that penetrates ceilings or is supported
by them, including light fixtures, HVAC equipment,
fire-suppression system, and partition assemblies.
C.
Raceways, fittings, etc for the Fire Alarm System are
not part of this Section. Refer to Section 16720, Fire
Alarm
System,
for
tire
alarm
system
raceway
requirements.
1.02 RELATED SECTIONS
A.
Firestopping ............................
Section 07270
B.
Painting ................................
Section 09900
1.03 SUPPLEMENTAL SUBMITTALS
A.
Submit
a
Product
Schedule
indicating
the
item
description and manufacturer name. The Schedule will be
accepted by the Authority for record purposes only,
provided that the items are in full compliance with the
Specifications.
B.
Certificates
Provide affidavit stating that all
listed and meet the specifications.
items used are
UL
PART 2 - PRODUCTS
2.01 RACEWAYS
A.
Rigid Galvanized Conduit
(RGC)
Steel conduit, Schedule 40, hot dipped galvanized, with
Underwriters Laboratories label stamped on each length.
NYCSCA
RACEWAYS,
FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 1
04/30/10
B.
DESIGN NO. 012090
Electric Metallic Tubing
(EMT)
Industry
standard
conduit
with
Underwriters
Laboratories label stamped on each length.
C.
Flexible Metal Conduit (FMC)
Galvanized
listed.
D.
steel
conduit,
Underwriter
Laboratories
Liquid-tight Flexible Metal Conduit (LTFMC)
Industry
standard
conduit,
Underwriter
Laboratories
listed.
E.
Surface Metal Raceway
1.
Metal raceway shall be of a two-piece design with
a base and snap-on cover.
2.
Raceway and all components
Underwriters Laboratories
3.
Manufacturers
shall
be
listed
by
Wire Mold Co
or
a.
Mono-Systems,
Panduit.
b.
Single Channel:
Wire Mold V700, Hubbell Inc.
750 Series, Mono-Systems SMS700, or Panduit
PMR5/PMR7.
c.
Dual Channel: Wiremold V4000, Wiremold DS4000
Series, Hubbell Inc. 4000 Series or MonoSystems SMS4200 or Panduit PMR4O.
d.
Surface mounted Raceway V2000BC.
Hubbell
Inc.,
2.02 SUPPORTING DEVICES
A.
B.
NYCSCA
Hangers
1.
Separate hangers shall be installed for supporting
conduits.
Wherever possible, hangers shall be
supported from concrete slab by inserts.
2.
Hangers and piping installed by other trades shall
not be used for supporting electric conduits.
Individual and multiple pipe hangers and riser clamps
including all parts and hardware shall be hot-dipped
galvanized
throughout.
All
U-bolts,
clamps,
attachments
and hardware
for
hanger
assembly and
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 2
04/30/10
DESIGN NO. 012090
conduits shall be provided. Each multiple hanger shall
be designed to support a load equal to or greater than
the sum of the weights of the conduits, wires and
hanger itself, plus 200 pounds.
C.
Use pipe straps and specified method of attachment
where conduit is installed proximate to surface of
steel stud or masonry construction.
1.
Use hangers secured
method of attachment
from the surfaces.
to surface with
where conduit is
specified
suspended
D.
Use "C" beam clamps and hangers
supported from steel beams.
E.
Use deck clamps and hangers to support conduits from
steel decking having hanger tabs.
One conduit per tab
where
conduit
is
is permitted.
1.
Where conduit is supported from steel decking
which does not have hanger tabs, use clamps and
hangers secured to decking, utilizing specified
method of attachment.
F.
Use channel support system supported from structural
steel for multiple parallel conduit runs.
G.
Where conduits are installed above ceiling, do not rest
conduit directly on runners bars, T-Bars, etc.
H.
1.
Conduit Sizes 2-1/2' and Smaller: Support conduit
form ceiling supports or from construction above
ceiling.
2.
Conduit Sizes Over 2-1/2": Support conduit
beams, joist, or trusses above ceiling.
from
Conduits shall be supported within three (3) feet of
any kind of fitting and at every outlet or junction
box, panel, etc.
This shall apply to both horizontal
and vertical runs.
2.03 BOXES AND ENCLOSURES
A.
NYCSCA
The
Contractor
shall
provide
outlet
boxes
and
enclosures appropriate for the purpose at all locations
where
the
Drawings
require
the
installation of
electrical devices or electrical equipment. For exposed
conduit systems, the contractor shall use cast outlet
boxes in all locations below 8'-0" with number of
threaded hubs equal to the number of conduits, except
when installing surface metal raceway contractor shall
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 3
04/30/10
DESIGN NO. 012090
provide boxes from the same manufacturer of the surface
metal raceway.
B.
Where the Contractor selects and installs an item of
equipment that requires additional boxes, fittings,
etc., or a modification of the conduit system indicated
on the Drawings, such additional boxes, fittings, etc.
shall be furnished and installed and such modifications
shall be performed by the Contractor as part of this
Contract,
without
extra
compensation
from
the
Authority.
2.04 FITTINGS AND ACCESSORIES
A.
All fittings and accessories must be UL listed and
compatible with selected raceways and suitable for use
location. Compression fittings shall be provided with
the installation of EMT.
2.05 CONDUIT SIZES
A.
Where conduit is required to be installed, its nominal
diameter shall be not less than 3/4 inch.
B.
For conduit
size is 1".
C.
For conduit placed in formed slabs, the maximum size is
3/4" for 4" slabs and 1" for slabs greater than 4".
placed
in
metal
deck
slabs,
the
maximum
2.06 SLEEVES FOR CONDUIT
A.
Provide sleeves, Schedule 40, galvanized steel, for all
electrical
conduits
and
wiring
passing
through
foundation walls.
B.
Provide sleeves, Schedule 10, galvanized steel, for all
electrical
conduits
and
wirina
passing
through
partitions and slabs.
Proprietary sleeves that are
part of an NYC approved fire stopping assembly are also
acceptable.
PART 3 - EXECUTION
3.01 RACEWAY SCHEDULE
A.
Rigid Galvanized Steel Conduit
(RGC)
Provide RGC as follows:
1.
NYCSCA
All conduits buried in concrete slabs or in the
ground.
Where conduit is in contact with gravel
or earth, conduit shall have a bitumastic coating.
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 4
04/30/10
B.
DESIGN NO. 012090
2.
Elbows and stub ups
underground raceways.
3.
All outdoor raceway.
4.
Fire Rescue area intercom system.
through
floor
slabs
from
Electrical Metallic Tubing (EMT)
Provide EMT for feeders and branch circuits for power,
lighting and low voltage systems.
C_
Metal Clad Cable (MC)
Provide MC for branch circuit in concealed installation
of hung ceiling and gypsum board partitions.
D.
Flexible Metal Conduit
(FMC)
1.
Concealed
systems
2.
Provide FMC for final conduit connection to:
3.
4.
above
hung
ceiling
for
low
voltage
a.
Recessed
ceilings.
b.
Emergency lighting battery units.
c.
Motors
d.
Equipment
locations).
e.
Equipment requiring flexible connections for
adjustment or alignment (dry locations).
lighting
subject
fixtures
to
in
suspended
vibration
(dry
In
all
cases,
install
equipment-grounding
conductor in the flexible raceway and bond at each
box or equipment to which flex is connected.
Grounding
conductors
are
not
shown
on
the
Drawings.
E.
Liquid-tight Flexible Metal Conduit (LFMC)
Provide LFMC for final conduit connection to:
NYCSCA
1.
Motors and Equipment subject to vibration in damp
and wet locations and for Kitchen appliances.
2.
Equipment
requiring
flexible
connection
for
adjustment or alignment in damp and wet locations.
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 5
04/30/10
F.
DESIGN NO. 012090
Surface Metal Raceway
Provide surface metal raceway in finished spaces.
1.
Secure raceway of
one-piece
type
every 36"
alternately with one-hole straps, and support
clips (strap, support clip, strap, etc.) . Secure
raceway of two-piece type every 36" alternately
with straps and fasteners through back of raceway
(strap, fastener through back, strap, etc.).
2.
Install separate grounding conductor. Grounding
conductors for surface metal raceways are not
shown on the Drawings.
3.02 RACEWAY INSTALLATION
A.
General
1.
Keep raceways at least 6 inches away from parallel
runs of flues and steam or hot-water pipes.
Install horizontal raceway runs above water and
steam piping-
NYCSCA
2.
All conduit systems shall
electrically continuous.
3.
The ends of all conduit shall be square, carefully
reamed out to tull
size, shouldered in the
fittings, and bushed or capped wherever stubbed
clear of the building.
4.
Not more than four (4) 90 degree ells or bends or
the equivalent shall be used in any single run of
conduit.
Conduits for telephone, television,
video surveillance or data cable shall not have
more than three
(3) 90 degree bends or the
equivalent.
Where more bends are necessary,
provide suitable code size pull boxes or fittings.
All conduits for telephone, television, video
sur-eillance or daLa systems cable shall have
large radius bends. Pull boxes shall be installed
in accessible locations.
5.
Conduit installed on equipment shall not obstruct
any removable panel, access door, or control.
Control apparatus, outlet, junction, and pull
boxes shall be installed so as not to interfere
with any piping, fixtures, or equipment.
6.
Complete raceway installation
conductor installation.
be
mechanically
before
and
starting
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 6
04/30/10
DESIGN NO. 012090
7.
Conceal conduit and EMT within new finished walls,
ceilings, and floors, unless otherwise indicated.
Use of exposed raceways attached to new finished
walls, ceilings, or slabs is not permitted.
a.
8.
9.
10.
NYCSCA
Install concealed raceways with a minimum of
bends in the shortest practical distance,
considering type of building construction and
obstructions, unless otherwise indicated.
Conduits
installed across
seismic
separations
(expansion joints) shall include, but not limited
to, the following:
a.
The conduit (rigid steel or EMT) shall be
securely anchored on each side of the seismic
separation with a pipe hanger per SMACNA
details.
b.
The spacing between conduit ends shall be 36"
minimum.
C.
A liquid-tight flexible metal conduit of the
same size shall be installed between the
conduit ends spanning the seismic separation.
d.
The liquid-tight flexible metal conduit shall
be of sufficient length to provide for a
longitudinal and axial deflection of
(2)
inches minimum in all directions.
Terminations:
a.
Where raceways are terminated with locknuts
and
bushings,
align
raceways
to
enter
squarely and install locknuts with dished
part against box.
Use two locknuts, one
inside and one outside box.
b.
Where raceways are terminated with threaded
hubs, screw raceways or fittings tightly into
hub so end bears against wire protection
shoulder.
Where chase nipples are used,
align raceways so coupling is square to box
tighten chase nipple so no threads are
exposed.
Install pull wires in empty raceways.
Use
polypropylene or monofilament plastic line with
not less than 200-1b (90-kg) tensile strength.
Leave at least 12 inches (300 mm) of slack at each
end of pull wire.
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130
-
7
04/30/10
DESIGN NO. 012090
11.
B.
Rooftop conduits (rigid steel) shall be neatly
grouped and installed parallel to the building
lines.
Support conduits on minimum 4 inches x 6
inches on pressure treated lumber sleepers at
minimum 5 feet spacing.
Exposed Conduits
Exposed
conduits
shall
be
rigidly
fastened
to
structure,
or
to
rigid
hangers
or angle
irons
connected to structure at intervals not exceeding
eight feet. Where the conduits or surface metal
raceways are installed exposed, they shall follow the
architectural lines of the enclosure and shall
be run
as to be as inconspicuous as possible.
Conduits or
surface
metal
raceways
shall
not
be
installed
diagonally on ceilings, walls or columns.
C.
Conduit Installed Concealed in Existing Building
Where new partition walls and new hung or furred
ceilings are being erected or where existing walls are
to have a new tile finish, the conduits and related
equipment shall be installed concealed in walls
and in
hung or furred ceilings.
D.
Conduit Installed in Concrete Floor Slabs
1.
General
a.
Where conduits cross expansion
floor
slabs,
special
conduit
fittings shall be installed.
b.
Conduits shall clear
door closers by 3".
c.
Conduits installed in the fill (or slab if no
fill is being used) of an auditorium floor
shall be run in the aisle spaces only.
all
joints in
expansion
concealed-in-floor
d.
E.
NYCSCA
The Contractor shall not cut any hole larger
than six (6) inches except where otherwise
directed in the Contract. Where the opening
(single or combined) is larger than six
inches, the Contractor shall request and
obtain approval before execution of work.
Low voltage systems (except for the fire alarm, refer
to specification section 16720) shall be installed
as
follows:
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 8
04/30/10
DESIGN NO. 012090
Existing Buildings:
1.
Vertical (Riser) Raceways:
EMT
2.
Horizontal Raceways:
EMT or surface metal raceway up to the outlet.
Concealed flexible metal conduit may be used for
low voltage systems above suspended ceiling.
F.
Raceways passing through fire-rated walls, floors,
roofs, ceilings, and other areas where indicated: the
space between sleeve and pipe/conduit shall be fire
stopped in accordance with Section 07270 to comply with
fire-rating of assembly through which it passes.
G.
Raceways passing through foundation walls shall be of
watertight utilizing "Link-Seal" type gasketing.
3.03 CONDUIT TO MOTORS, TABLES, ETC. IN SHOPS AND OTHER ROOMS
-
3.04
NOT USED
MOUNTING DEVICES
A.
Height of Wall Outlets
Unless otherwise indicated, locate outlet boxes with
their center lines at the following elevations above
finished floor:
Alarm Indicating
Devices
8'-0"
to
center
where
ceiling
height allows a minimum of 2"
clearance between ceiling and top
otherwise mount so that its top is
2" below finished ceiling.
Clock
2" below finished ceiling to a
maximum elevation of i0'-0".
8'-0" where ceiling height allows a
minimum of 6" clearance between
ceilings and top light, otherwise
mount exit light so that its top is
6" below finished ceiling.
Adjust
height and clearances as required
to suit installation over doors.
8'-0"1 AFF.
8'-0"
A.F.F.
or
6" below the
ceiling whichever is lower
Exit Lights
Indicators
Fire Alarm
Strobe Lights
NYCSCA
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 9
04/30/10
DESIGN NO. 012090
Manual Fire Alarm
4'-OT
Boxes
Single & Duplex
Receptacles
1-6"
Special Purpose
Receptacles
As indicated on the Drawings.
Switches
4
Telephone
1'-6"
Telephone Marked
"W"
Install outlet so that the highest
operable part of the telephone will
not be more than 4'-0" AFF.
Television outlet
li'6"
3.05 PAINTING
A.
All exposed raceways and boxes in finished parts
of
building shall be painted. Painting shall consist the
of a
prime coat and a finished coat, color as selected
by
project architect. Factory painting w .Il he accepted
as
a prime coat.
END OF SECTION
NYCSCA
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 10
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Schedule
Certificates
Coordination/Routing Drawings
NYCSCA
RACEWAYS, FITTINGS, SUPPORTING DEVICES,
BOXES AND ACCESSORIES 16130 - 11
THIS PAGE INTENTIONALLY LEFT BLANK
-
04/30/10
DESIGN NO. 012090
SECTION 16140
WIRING DEVICES
PART 1 - GENERAL
1.01 DESCRIPTION OF WORK
Provide receptacles and switches.
1.02 SUPPLEMENTAL SUBMITTALS
Field test report.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A.
Hubbell Incorporated
B.
Leviton Mfg. Company Inc.
C.
Bryant Electric, Inc. (a Hubbell Inc. subsidiary)
D.
Pass & Seymour/Legrand
2.02 AC SWITCH
Commercial specification grade, UL listed; compliance with UL
20 and NEMA standard WD-I, "General Purpose Wiring Devices".
A.
Toggle Single Pole:
1.
2.
B.
Three-way Toggle:
1.
2.
C.
15A, 120/277 VAC;
CS315 from Hubbell Inc.; CS315-2 from Leviton Mfg.;
20A, 120/277 VAC;
CS320 from Hubbell Inc.; CS320-2 from Leviton Mfg.;
Locking type (Key-operated) Single-pole
Industrial specification grade for this device.
1.
NYCSCA
15A, 120/277V AC;
CS115 from Hubbell Inc.; CS15-2 from Leviton Mfg.;
20A, 120/277 VAC;
CS120 from Hubbell Inc.; CS120-2 from Leviton Mfg.;
15A, 120/277V AC;
HBL 1201-L from Hubbell Inc.; l101-2L from Leviton
Mfg.;
WIRING DEVICES 16140 - 1
04/30/10
DESIGN NO. 012090
2.
20A, 120/277 VAC;
HEL 1221-L
from
Leviton Mfg.;
Hubbell
Inc.;
CS1T21-2L
from
2.03 RECEPTACLES
A.
NYCSCA
Straight-blade-type;
Commercial
Specification
Grade
minimum; compliance with NEMA WD 1; DSCC WC 596, AND UL
498 and UL 943 2006 Codes.
1.
Single receptacle, NEMA 5-20R (20A, 125V, 2P, 3W);
Leviton 5891 or Pass & Seymour/Legrand PS5351
2.
Duplex receptacle, NEMA 5-20R (20A, 125V, 2P, 3W);
Hubbell
Inc.
HBL5352,
Leviton
BR20,
Pass
&
Seymour/Legrand PS5362
3.
Ground-Fault Circuit Interrupter GFCI; duplex (20A,
125V, 2P, 3W)
Hubbell
Inc
GF5352SL,
Leviton
6899,
Pass
&
Seymour/Legrand PS2095
4.
Transient Voltage Surge Suppression Receptacle
TVSS; duplex (20A, 125V, 2P, 3W);
Hubbell
Inc
HBL5360SA, Leviton
5380,
Pass
&
Seymour/Legrand PS5362- ISP
5.
Tamper-Resistant
Commercial/Hospital
Grade
receptacle - Safety duplex receptacle for use in
Pre-Kindergarten and Kindergarten rooms - NEMA 520R (20A, 125V, 2P, 3W): Hubbell Inc. HBL 8300 SG
0OSGA, Leviton TBR 20, Pass & Seymour/Legrand
TR 63H (Hospital Grade)
6.
TVisted Lock receptacles Commercial Grade For use in
the Telecommunication Rooms
a.
Single receptacle (30A, 125V, 2P 3W) (NEMA
L530R):
Leviton part# 2660 or Hubbell Part # HBLL530R
b.
Single receptacle (20A, 220V, 2P 3W) (NEMA
L620R)Leviton Part# 2320 or Hubbell Part # HBLL53OR
C.
For the Mobile Hot Food Server:
Hubbell
Receptacle
Part
i
HBL9430A
3 Pole, 4 Wire Grounding
30A,
WIRING DEVICES 16140 - 2
04/30/10
DESIGN NO. 012090
2.04 WEATHERPROOF RECEPTACLE ENCLOSURE
For use in
WTUC10-G.
wet
location equal
to
Pass
& Seymour/Legrand
2.05 WALL PLATE
A.
PART 3
-
Provide wall plate for wiring devices. Material shall be
0.035-inch thick, satin-finished stainless steel. Metal
screw heads to match plate finish.
EXECUTION
3.01 INSTALLATION
A.
Install wiring devices in outlet boxes.
B.
Install devices and assemblies level, plumb and square.
C.
Where more than one switch occurs at the same location,
arrange switches
faceplate.
D.
in
gangs
and
cover
with
a
single
Install switches so that handle is up when switch is in
the "On" position.
NYCSCA
E.
Install receptacles with ground pole in up position.
F.
Install wall plates on all wiring devices.
G.
Install blank wall plates on outlet boxes which are for
future equipment except telephone outlets.
H.
Remove wall plates
during painting.
I.
Install weatherproof covers on wiring devices in damp and
wet locations.
J.
Where flush plates are required over outlet boxes that
cannot be set deep enough for the plates to fit closely
over the finished wall surfaces, provide extension collar
to fill the space between the finished wall surface and
the plate.
protecting devices
and
assemblies
WIRING DEVICES 16140 - 3
04/30/10
DESIGN NO. 012090
3.02 FIELD TESTS
A.
Ensure that proper polarity of connections is maintained.
Subsequent to energization, test wiring devices to
demonstrate
compliance
with
requirements
of
these
Specifications,
END OF SECTION
NYCSCA
WIRING DEVICES 16140 - 4
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Data
Field test report
NYCSCA
WIRING DEVICES 16140 - 5
-
THIS PAGE INTENTIONALLY LEFT BLANK -
04/30/10
DESIGN NO. 012090
SECTION 16450
GROUNDING AND BONDING
PART 1 - GENERAL
1.01 DESCRIPTION OF WORK
A.
The Contractor shall provide a complete
electrical systems and equipment.
grounding
of
1.02 SUPPLEMENTAL SUBMITTALS - NOT USED
PART 2 - PRODUCT
2.01 GROUNDING BUS BAR - NOT USED
2.02 GROUNDING ELECTRODES - NOT USED
2.03 GROUNDING CONDUCTORS
A.
Copper conductors, bare or insulated with THWN or THHN
insulation.
B.
Equipment Grounding Conductors:
colored insulation.
C.
Isolated Ground Conductors:
Insulated with green-colored
simulation with yellow stripe. On feeders with isolated
ground, use colored tape, alternating bands of green and
yellow tape to provide a minimum of three bands of green
and two bands of yellow.
D.
Grounding Electrode Conductors:
E.
Underground Conductors:
otherwise indicated.
Bare, tinned, stranded, unless
F.
Bare Copper Conductors:
Comply with the following:
G.
Stranded cable.
1.
Solid Conductors:
2.
Assembly of Stranded Conductors:
3.
Tinned Conductors:
ASTM B 3.
ASTM 2 8.
ASTM B 33.
Copper Bonding Conductors:
1.
NYCSCA
Insulated with green-
As follows:
Bonding Cable:
28 kcmil, 14 strands of No. 17 AWG
copper conductor, 1/4 inch (6.4 mm) in diameter.
GROUNDING AND BONDING 16450 - 1
04/30/10
DESIGN NO. 012090
2.
Bonding Conductor:
copper conductor.
3.
Bonding Jumper:
Bare copper tape, braided bare
copper conductors, terminated with copper ferrules;
1-5/8 inches (42 mm) wide and 1/16 inch (1.5 mm)
thick.
4.
Tinned Bonding Jumper;
Tinned-copper tape, braided
copper Jonductors, terminated with copper ferrules;
1-5/8 inches (42 mm) wide and 1/16 inch (1.5 mm)
thick.
No. 4 or No. 6 AWG, stranded
2.04 CONNECTOR PRODUCTS
A.
Comply with IEEE 837 and UL 467.
Listed for use for
specific types, sizes, and combinations of conductors and
connected items.
B.
Bolted Connectors:
compression type.
C.
Welded Connectors:
Exothermic-welded type, in kit form,
and selected per manufacturer's written instructions.
D.
All terminal lugs and bolts shall be 98%
copper.
Bolted-pressure-type connectors, or
silicon bronze
PART 3 - EXECUTION
3.01 APPLICATION
A.
In
raceways,
conductors.
use
insulated
equipment
grounding
Equipment Grounding Conductor Terminations:
pressure clamps.
Use bolted
3.02 INSTALLATION
A.
Nonmetallic Raceways:
Install an equipment grounding
conductor in non metallic raceways unless they are
designated for telephone or data cables.
P.
Water Heater, Heat-Tracing, and Antifrost Heating Cables:
Install a separate equipment grounding conductor to each
NYCSCA
GROUNDING AND BONDING 16450 - 2
04/30/10
DESIGN NO. 012090
electric water heater, heat-tracing, and antifrost
heating cable. Bond conductor to heater units, piping,
connected equipment, and components.
C.
Signal and Communication Systems: For telephone, alarm,
voice and data, and other communication systems, provide
insulated grounding conductor as described in individual
sections in raceway from main building grounding bus bar
to telecommunication room grounding bus bar and each
service location, terminal cabinet, wiring closet, and
central equipment location.
D.
Common Ground Bonding with Lightning Protection System:
Bond electrical power system ground directly to lightning
protection system grounding conductor at closest point to
electrical service grounding electrode.
Use bonding
conductor sized same as system grounding electrode
conductor, and install in conduit.
3.03 CONNECTIONS
A.
B.
NYCSCA
General:
Make connections so galvanic action or
electrolysis
possibility
is
minimized.
Select
connectors,
connection
hardware,
conductors,
and
connection methods so metals in direct contact will be
galvanically compatible.
1.
Use electroplated or hot-tin-coated materials to
ensure high conductivity and to make contact points
closer to order of galvanic series.
2.
Make connections with clean, bare metal at points
of contact.
3.
Make aluminum-to-steel connections with stainlesssteel separators and mechanical clamps.
4.
Make aluminum-to-galvanized steel connections with
tin-plated copper jumpers and mechanical clamps.
5.
Coat and seal connections having dissimilar metals
with inert material to prevent future penetration
of moisture to contact surfaces.
Exothermic-Welded Connections: Comply with manufacturer's
written instructions. Welds that are puffed up or that
show convex surfaces indicating improper cleaning are not
acceptable.
GROUNDING AND BONDING 16450 - 3
04/30/10
DESIGN NO. 012D90
C.
Equipment
Grounding
Conductor
Terminations:
For
No. 8 AWG and larger, use pressure-type grounding lugs.
No. 10 AWG and smaller grounding conductors may be
terminated with winged pressure-type connectors.
D.
Noncontact Metal Raceway Terminations:
It metallic
raceways terminate at metal housings without mechanical
and electrical connection to housing, terminate each
conduit with a grounding bushing.
Connect grounding
bushings with a bare grounding conductor to grounding bus
or terminal in housing. Bond electrically noncontinuous
conduits at entrances and exits with grounding bushings
and
bare
grounding
conductors,
unless
otherwise
indicated.
E.
Tighten screws and bolts for grounding and bonding
connectors and terminals according to manufacturer's
published torque-tightening values.
If manufacturer's
torque values are not indicated, use those specified in
UL 486A [and UL 486] .
F.
Compression-Type Connections: Use hydraulic compression
tools to provide correct circumferential pressure for
compression connectors. Use tools and dies recommended
by connector manufacturer. Provide embossing die code or
other standard method to make a visible indication that a
connector has been adequately compressed on grounding
conductor.
3.04 UNDERGROUND DISTRIBUTION SYSTEM GROUNDING - NOT USED
3.05 TESTING - NOT USED
END OF SECTION
NYCSCA
GROUNDING AND BONDING 16450
-
4
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product data
Details of grounding bus bar
installation
Field Test Reports
NYCSCA
GROUNDING AND BONDING 16450
-
5
-
THIS PAGE INTENTIONALLY
LEFT BLANK
-
DESIGN NO. 012090
04/30/10
SECTION 16475
OVERCURRENT PROTECTIVE DEVICES
AND CIRCUIT BREAKERS
PART
I - GENERAL
1.01 DESCRIPTION OF WORK
A.
use in panelboards.
Provide circuit breakers for
- NOT USED
1.02 SUPPLEMENTAL SUBMITTALS
1.03 SPARES - NOT USED
1.04 ELECTRICAL SYSTEM COORDINATION
A.
overcurrent
or
fuses,
of
Rating and arrangement
which have a rating above
devices on service switches,
601 amperes, shall be coordinated.
PART 2 - PRODUCTS
2.01 CIRCUIT BREAKERS
A.
General
thermal-magnetic
be
shall
breakers
Circuit
Specifications:
conforming to the following
1.
be by "bolt-on".
Connection to bus shall
not acceptable.
type circuit breakers are
2.
Multi-pole
poles
3.
4.
NYCSCA
breakers
shall
have
barriers
type,
Plug-in
between
have separate tripping
Multi-pole breakers shall
Each tripping element
element for each pole.
Multi-pole breakers shall
shall open all poles.
all poles.
have one handle controlling
rating or less shall
Breakers of 225-ampere trip
trip
set
permanently
non-tamperable,
have
molded
in
sealed
and
enclosed
elements
composition housing.
OVERCURRENT PROTECTIVE DEVICES
BREAKERS 16475 - 1
AND CIRCUIT
DESIGN NO. 012090
04/30/10
5.
6.
7.
not less
Single pole breakers shall be rated for
shall
than 120 volts, A.C., multi-pole breakers
be rated for not less than 250 volts A.C.
Where spaces for future breakers are required,
future
of
mounting
for
connections
copper
breakets shall be provided.
standard
Circuit breakers shall be mounted in
Frame
panel boards as indicated on the drawings.
to
conform
shall
and sizes of circuit breakers
the following:
a.
b.
C.
d.
Use standard molded-case type.
the
at
controlled
circuits
lighting
For
panel, provide circuit breakers rated for
switching duty.
For circuit breaker serving heat tracing,
devices
heating
similar
or
melting
snow
milliamp
(30
feature
GFI
provide
on the drawings.
shown
as
sensitivity)
convenience
serving
breakers
circuit
For
receptacles in bathrooms, kitchens and other
GFI
such code mandated locations provide
shown
as
feature (5 milliamps sensitivity)
on the drawings.
Size, Trip Rating, Short
Table with Frame
Circuit Interrupting Capacity and recommended
Manufacturers:8.
Trip
Ratings-
No
of
Size
PolesFrame
100 AMP - Frame
15-30
15-20
Square D, Type QOB-VH (22,000
120/240V:
I.C.)
Square D, Type QOB-VH (65,000
120/240V:
I.C.)
Cutler-Hammer, Type GHBS (65,000
120-240V:
I.C.)* 480/277V: 2EB (14,000 I.C )
125 AMP - Frame
15-125
1120V:
NYCSCA
SIEMENS, Type ED4
(65,000 1.C.)
OVERCURRENT PROTECTIVE DEVICES
AND CIRCUIT BREAKERS 16475 - 2
DESIGN NO. 012090
04/30/10
100 AMP - Frame
120/240V:
2&3
15-100
Square D, Type QOB-VH
(22,000
Square D, Type QOB-VH
(65,000
I .C.)
15-30
2&3
120/240V:
I.C.)
15-30
2&3
240V:
Cutler-Hammer, Type GB
(65,000
I.C.) *
___
125 AMP - Frame
15-125
240V:
20
SIEMENS, Type ED4
(65,000 I.C)
225 AMP - Frame
101-225
2&3
240V:
Square D, Type KA (42,000 I.C.)
125-225
2&3
240V:
Cutler-Hammer, Type HCA
125-225
2&3
240V:
SIEMENS, Type QJ2-H (42,000 I.C.)
l.C.)*
(42,000
400 AMP - Frame
240V: Square D, type LA (42,000 I.C.)
226-400
_480V:
Type LA (30,000 I.C.)
2.02 FUSES - NOT USED
2.03 SPARE FUSE CABINET - NOT USED
PART 3 - EXECUTION
3.01 INSTALLATION - NOT USED
END OF SECTION
NYCSCA
OVERCURRENT PROTECTIVE DEVICES
AND CIRCUIT BREAKERS 16475 - 3
DESIGN NO. 012090
04/30/10
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APROVED
Product Data
Shop Drawings
Specifications, Installation
Instructions
NYCSCA
OVERCURRENT PROTECTIVE DEVICES
AND CIRCUIT BREAKERS 16475 - 4
DESIGN NO. 012090
04/30/10
SECTION 16500
INTERIOR BUILDING LIGHTING
PART 1 - GENERAL
1.01 DESCRIPTION OF WORK
A.
Provide
lighting
fixtures,
supports
and
accessories
including plaster frames, trim rings and backboxes for
plaster, drywall, or concrete ceilings as necessary.
B.
The
types
of
lighting
fixtures
to
be
installed
are
indicated and detailed on fixture schedule on the
Drawings, which also provides details on manufacturers,
catalog numbers, lamping, etc.
C.
Coordinate with other trades to avoid conflicts between
the
of
fixtures
and
supports
with
installation
installation of mechanical equipment, ceiling structures,
etc.
D.
All lighting fixtures shall operate on nominal 120 volts,
60 Hz single phase service as indicated on the Drawings
and in the Specifications.
1.02 SUPPLEMENTAL SUBMITTALS
A.
Product Data
1.
B.
Provide
standard
print
catalog
sheets,
Specifications,
installation
instructions,
and
photometric data from a recognized independent
Submittals
laboratory for each type of fixture.
that do not include distribution curves and
photometric data will be rejected. All options and
specified requirements shall be identified on
submittal.
Mounting Details
Submit mounting details for each type of fixture
including attachments to structure, anchors, rods,
hickeys, etc.
C.
NYCSCA
Samples
1.
Submit fixture samples as requested by the Authority.
2.
Submit mounting
Authority.
hardware
as
requested
by
INTERIOR BUILDING LIGHTING 16500
the
-
1
04/30/10
D.
E.
DESIGN NO. 012090
Submission of Substitute Fixtures (fixtures other than
specified herein or on the Fixture Schedule).
1.
Submittals for substitute fixtures shall be the
standard
print
catalog
sheets
from
the
manufacturers (CADD drawings and computer printouts
are not acceptable).
2.
Substitute fixture shall meet or exceed photometric
quality of fixture designated on the schedule.
Photometric data of substitute fixture shall be
substantiated by an independent testing lab, such
as I.T.L. Photometric data by Lumen Micro or
similar software programs are not acceptable.
3.
Substitute fixture shall meet or exceed the quality
of the fixture designated on fixture schedule in
construction,
finishing,
materials,
reflector,
louver, diffuser etc.
4_
Substitute
fixture
shall
closely
match
the
appearance, dimensions and features of the fixture
designated.
5.
Submit one sample of each type of substitute
fixture as requested, with one set of mounting
hardware for approval.
6.
Tn order to ensure that the work is performed in an
orderly and expeditious manner, the Contractor
shall
be permitted
no more
than three
(3)
submittals for substitution of
each specific
fixture type.
Should the third submittal be
rejected, then the Contractor shall be required to
provide the fixture specified on the fixture
schedule.
Spare Parts.
1.03 FIXTURE PROTECTION
A.
The Contractor is required to protect fixtures from
damage during installation and up to time of acceptance
by the Authority. Broken fixtures, glassware, plastics,
lamps, etc. shall be replaced by the Contractor with new
parts, without any additional expense to the Authority
until final acceptance-
NYCSCA
INTERIOR BUILDING LIGHTING 16500 - 2
04/30/10
DESIGN NO. 012090
1.04 SPARE PARTS
A.
Diffusers
Provide a spare diffuser for every twenty (20 of each
type and size installed, but not less than one (1) of
each.
B.
Screwdrivers
Provide one (1) screwdriver suitable for each type of
vandal resistant screw installed on fixtures.
C.
Delivery
1.
Spares shall be provided and delivered to the
Authority's Representative with an itemized list
and a receipt taken, certifying that these spare
parts have been delivered securely packed and
received in acceptable condition.
PART 2 - PRODUCTS
2.01 GENERAL
A.
Provide lighting fixtures as designated on the fixture
schedule. Lighting fixtures of the fixture schedule are
designated by types, manufacturers and catalog numbers.
Substitute fixtures by approved manufacturers listed in
these specifications will be approved, provided that all
requirements are satisfied.
B.
The
requirements
specified
herein
are
minimum
requirements and shall be supplemented by any other
requirements indicated on the fixture schedule. All
fixtures, including those designated on the fixture
schedule on the drawings by Catalog Numbers, or Catalog
Numbers
mentioned
in
the
Specifications,
shall
nevertheless
be
specially modified
to
meet
the
requirements of these specifications.
C.
All fixtures and components shall be UL listed and meet
NYC Electrical Code.
2.02 FIXTURE COMPONENTS
A.
Equip fixtures with:
1.
NYCSCA
Ballasts (electronic) suitable for operation on 60
Hz circuit, voltage rating to suit branch circuit
voltage.
INTERIOR BUILDING LIGHTING 16500 - 3
DESIGN NO. 012090
04/30/10
2.
3.
4.
Diffusers
a.
Unless otherwise noted, parabolic diffusers
semi-specular
fabricated
from
shall
be
iridescence free aluminum with precisely
blades.
assembled
and
rigidly
formed
Reflectors shall be die formed of 20-ga. cold
rolled steel.
b.
Lens type diffusers shall be 100% clear virgin
The over-all plastic thickness of
acrylic.
the diffuser or lens shall be a minimum of
0.130" and shall be a "male' type pyramidal in
shape"; "female" types are not acceptable.
c.
Diffusers
shall
be
as
manufactured
Diversified, KSH, or Holophane.
d.
Diffusers shall be fastened in a regressed
extruded aluminum envelope door frame of code
gauge metal with positive latching and shall
be secured to the fixture housing by two (2)
safety chains with spring clips or approved
equivalent means.
Holders and Spun Work
a.
All shells, canopies or other spun parts shall
be not less than No. 20 gauge unless otherwise
specified with a reasonable tolerance allowed
for finishing.
b.
All
screw type globe
holders
shall
be
reinforced so that screws shall have a hearing
of at least four full threads. Screws holding
glassware and/or plastics shall have check
nuts or equivalent.
c.
Globe holders shall be not less than 6" in
diameter
unless
otherwise
specified.
are
Screwless safety type globe holders
acceptable.
Wire guards
a.
NYCSCA
by
Wire guards shall be provided where indicated
on the Drawings, typically with a "C" next to
the fixture.
However, all Gymnasium and
INTERIOR BUILDING LIGHTING 16500 - 4
04/30/10
DESIGN NO. 012090
playroom fixtures shall be equipped with wire
guards unless otherwise noted.
B.
C.
NYCSCA
b.
Guards shall be made of #9 gauge minimum steel
wire, fully welded at all points.
Finish
shall be bright zinc plate. Additional wire
guard information may be shown on Drawing
Details and Notes.
c.
Guards for surface mounted fixtures shall be
secured to ceiling/wall with hinge access.
5.
Finishing collar and/or
collar/outlet box.
6.
Provide
end
caps
positively
attached
for
individually mounted fluorescent fixtures and ends
of continuous rows.
7.
Lamps for all fixtures shall be as
Drawing or in these Specifications.
combination
finishing
indicated on
Stems and Hickeys
1.
Stems for pendant fixtures shall be standard pipes
not less than 3/8" diameter. Stems shall be no less
than 6" long with a cut thread.
Pipe stems at
fixture end shall have a length of threads of
approximately l-l/2' for fixture alignment.
2.
Each stem shall be provided with a brass/steel
swivel or other self-aligning device of type
approved by the Authority, a hickey, a malleable
iron
bushing,
a
canopy,
minimum
of
three
locknuts/washers (one locknut/washer above and two
below for locking purpose) and other accessories
for the safe support of pendant fixtures.
Fixture Finishes
1.
The finish of all lighting fixtures not described
on fixture schedule or in the Specifications shall
be as selected by the Authority's Representative.
The Contractor shall submit a color chart to the
Authority's Representative for selection of finish.
2.
Exterior Fixtures shall have an anodized or baked
powder coat finish-
INTERIOR BUILDING LIGHTING 16500 - 5
04/30/10
DESIGN NO. 012090
2.03 FLUORESCENT FIXTURE
A.
Fluorescent fixture housing shall be constructed of sheet
metal not less than No. 20 gauge. Fixture housing shall
be electrically welded.
B.
Ballast covers may be 22 gauge.
C.
Diffusers shall be fastened in an extruded aluminum or 19
gauge flush steel door frame, and fasten to the fixture
body by means of approved hinges or hinging device. When
in closed position, hinged frame shall be held by captive
thumbscrews. Two (2) chain retainers shall be provided
attached to diffuser frame with spring clips.
D.
Self-threading or sheet metal screws and nuts will not be
accepted. Fixture and/or parts, such as finishing plates
and trims for recessed fixtures, shall not be installed
until all plastering and painting has been completed.
E.
Fluorescent fixture finish shall be white powder coat
post painted to provide a minimum of 90% reflectivitv
(including all internal and external components).
F.
Fluorescent fixtures shall be as indicated on fixture
schedule, or approved equal as manufactured by approved
manufacturers listed below in alphabetical order:
Cooper Lighting, Day Brite, General Electric, Guth,
Hasco, Holophane, ICON, Legion, Lightolier, Lightron,
Linear Lighting, Lumax, McGraw Edison, Lithonia, Mercury,
National, NeoRay, Paramount, SPI, Vantage and Hubbell
Lighting.
C.
Fixtures by these manufacturers must conform
applicable paragraphs in these specifications.
to
all
2.04 DIRECT/INDIRECT FLUORESCENT FIXTURE - NOT USED
2.05 HIGH INTENSITY DISCHARGE FIXTURE - NOT USED
2.06 DOWNLIGHTS - NOT USED
2.07 THEATRICAL LIGHTING FIXTURES - NOT USED
2.08 REMOTE CONTROL OF LIGHTING - NOT USED
NYCSCA
INTERIOR BUILDING LIGHTING 16500
-
6
04/30/10
DESIGN NO. 012090
2.09 ENERGY EFFICIENCY
A.
PART 3
Fluorescent lighting fixture, lamps and ballast shall
conform to energy efficiency requirements of all local
authorities having jurisdiction and qualify for any
available utility rebate to owner.
-
EXECUTION
3.01 FIXTURE INSTALLATION
A.
NYCSCA
General
1.
The Contractor shall be responsible for the proper
and safe mounting and support of all lighting
fixtures.
Installation
shall
meet
all
the
requirements of the National Electrical Code.
Provide all items of equipment (stems, hangers,
rods, inserts, boxes, brackets, yokes, channels,
frames, etc.) required to adequately and safely
support
each
lighting
fixture
in
a
manner
acceptable to the Authority.
2.
Provide a lighting fixture at each location shown
on Drawings of the type indicated by symbol or
other notation.
If the type is not specifically
noted on Drawings, the Contractor shall provide
without extra cost fixtures of the same type called
for under similar condition elsewhere on the
Drawings as determined by the Authority.
3.
The Contractor shall examine the drawings and
coordinate
closely
with
the
all
General
Construction trades on all work involved with each
type of fixtures to be installed. Contractor shall
verify all sizes, locations and conditions under
which lighting fixtures are to be installed.
Provide plaster frames and running bars (black
iron) etc. as required.
4.
The Contractor is required to protect fixtures from
damage
during
installation,
up
to
time
of
acceptance by the Authority. Any broken or marred
fixtures, glassware, plastics, lamps, etc. shall be
replaced by the Contractor at no additional cost to
the Authority.
5.
A suitable outlet box shall be provided by the
Contractor for each lighting fixture provided. The
box shall be cast into concrete or supported using
INTERIOR BUILDING LIGHTING 16500
-
7
04/30/10
DESIGN NO. 012090
two double split type anchors
concrete walls or ceiling.
installed
in
6.
Number of
supports for
fixtures shall be
as
specified in "Lighting Fixture Support Schedule" in
Article 3.07.
7.
A surface or pendant type fixture, regardless of its
weight,
shall
not be mounted directly on the
concealed
or
exposed
ceiling
spline
of
a
lightweight, mechanical acoustical ceiling system.
Such fixtures shall be supported from the running
channel (Black Iron) or the building structure.
3.02 LIGHTING
PENDANT)
A.
when
FIXTURES
Surface
Ceiling
and
ON SUSPENDED
Pendant
CEILING
Mounted
(RECESS,
Fixtures
SURFACE
on
OR
Suspended
1.
Surface mounted and pendant
fixtures shall be
supported above suspended ceiling by hanger rods,
3/16" in diameter minimum, or by 12 gauge hanger
wire, vertically attached to approved straps, bars,
channels secured to the black iron where available,
or to structural steel or concrete.
2.
Below suspended ceiling, support pendant
with 3/8" stems or stainless steel cable.
fixtures
3.03 PENDANT MOUNTED LIGHTING FIXTURES (NON-SUSPENDED CEILING)
- NOT USED
3.04 PENDANT LIGHT FIXTURES IN GYMNASIUM (FOR SUSPENDED AND NON
SUSPENDED CEILINGS) - NOT USED
3.05 LIGHTING FIXTURE WORK IN EXISTING CONSTRUCTION
A.
Canopies on Surface Mounted Outlet Boxes
Where lighting fixtures are mounted upon surface-mounted
outlet boxes with surface mounted conduit, the Contractor
shall provide a fixture canopy sufficiently deep to permit
exposed conduits to pass through.
Canopy shall have
proper openings cut by fixture manufacturer through which
conduits may pass. Submit sample of canopy for approval
before installation.
NYCSCA
INTERIOR BUILDING LIGHTING 16500 - 8
04/30/10
B.
DESIGN NO. 012090
Adapters
Where new lighting fixtures are mounted on existing outlet
boxes and mounting holes are not in proper position,
suitable adapter or extension collars shall be provided.
C.
Removed Fixture
1.
Where the Drawings or Specifications call for the
Contractor to remove an existing fixture, the
Contractor shall also install a suitable blank face
plate on the exposed outlet box.
2.
If the outlet box is to be used in the extension of
branch circuit wiring, this Contractor
shall
furnish and install a suitable extension collar
that may be required to receive surface raceway or
conduit.
3.06 MOUNTING HEIGHT OF FIXTURES
A.
Fixtures shall be hung in accordance with the mounting
heights indicated on Drawings and meeting the NYC
Electrical Code. Mounting heights A.F.F. (distance above
finished floor) are detailed on the Fixture Schedule, or
elsewhere on the drawings.
B.
The Contractor shall provide stems of sufficient length
to assure fixture mounting at the specified mounting
height.
3.07 LIGHTING FIXTURE SUPPORT SCHEDULE
A.
Unless otherwise indicated on drawings, provide
following number of supports for fixtures.
1.
B.
An adequately supported outlet box with fixture stud
may be utilized as one point of support for surface
or recess fixtures weighing less than 40 lbs. For
all pendant mounted fixtures, regardless of weight
and ceiling type, provide outlet boxes capable of
supporting up to 150 lbs., Westinghouse model
01050/01052 or equal.
Ceiling Mounted Fixtures (Surface Mounted, Pendant
Mounted or Recessed Mounted)
1.
Ceiling Mounted Fluorescent Fixtures:
a.
NYCSCA
the
Support individual fluorescent
than 2 feet wide at 2 points.
fixture
INTERIOR BUILDING LIGHTING 16500
less
-
9
04/30/10
DESIGN NO. 012090
b.
2.
3.
Support individual fluorescent fixtures 2 feet
or wider at 4 corners.
Ceiling Mounted H.I.D. Fixtures
a.
Commercial Style: Support fixture at 2 points.
b.
Industrial Style: Support fixture at one point
with safety chain.
Ceiling Mounted Incandescent Fixtures
Support fixture from adequately supported outlet box
to suit fixture design (fixture weight less than 50
lbs.).
C.
Wall Mounted Lighting Fixtures
1.
2.
Wall mounted Fluorescent Fixtures:
a.
Support individual fluorescent fixture 4 feet
long or less at 2 points.
b.
Support continuous row of fluorescent fixtures
at points equal to twice the number of fixtures
not to exceed 8 feet on center. Uniformly
distribute the points of support.
Wall Mounted H.I.D. Fixtures
Support H.I.D. fixture at 4 points.
3.
Wall Mounted Incandescent Fixtures
Support fixture from adequately supported outlet box
to suit fixture design (fixture weight less than 50
lbs.).
3.08 WIRING AND CONNECTIONS
A.
Each fixture shall be completely wired in approved
standard
trade
practices
in
accordance
with
the
requirements of the Electrical Code of the City of New
York.
B.
Wires within fluorescent fixtures, wiring between the
ceiling outlet box and the fixture, and all wiring
between fixtures in a continuous row shall be #14 AWG
minimum, insulated for 1,000 volts, and rated at 90C
NYCSCA
INTERIOR BUILDING LIGHTING 16500 - 10
04/30/10
DESIGN NO. 012090
minimum. Wiring shall be approved by the Advisory Board
for fluorescent
fixture wire and meet the above
requirements.
C.
Wiring to pendant fixtures shall be run through the stem
and iron bushing or straight cord and stainless steel
wire. Wiring to direct/indirect fixtures shall be by
means of power cord in SJT jacket.
3.09 AIMING
A-
All adjustments shall be made in the presence of and to
the satisfaction of the Authority, to provide the intent
of the Contract Documents.
3.10 CLEANING
A.
All lighting fixtures, both interior and exterior shall
be cleaned prior to final acceptance, for the removal of
all construction debris, dust, fingerprints, exposed
labels. Fixtures and or parts which have been damaged,
scratched, chipped or inadvertently painted during
construction shall be repaired and/or replaced at the
direction
and
discretion
of
the
Authority's
Representative.
END OF SECTION
NYCSCA
INTERIOR BUILDING LIGHTING 16500 - 11
04/30/10
DESIGN NO. 012090
LIST OP SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Data
Mounting Details
Samples
Submission of Substitute
Fixtures
Spare Parts
NYCSCA
INTERIOR BUILDING LIGHTING 16500 - 12
04/30/10
DESIGN NO. 012090
SECTION 16501
BALLASTS AND ACCESSORIES
LAMPS,
PART 1 - GENERAL
1.01 DESCRIPTION OF WORK
A.
Provide lamps, ballasts and accessories as specified
herein and as indicated on Drawings. All lamps and
ballasts and their installation shall comply with the NY
State Energy Conservation Construction Code
-
Effective
07/03/2002. All installations & equipment shall comply
with NYC Electrical Code.
B.
All fluorescent lamps shall be low mercury (green-endcap) type compliant with US EPA Toxicity Characteristic
Leaching Procedure (TCLP).
C.
Lamp type, wattage, CRI and color temperature shall be in
compliance with this specification and as indicated on
the drawings.
D.
Fixtures shall be high efficiency fluorescent or HID
type.
In general, fluorescent lamps shall be T-8 low
mercury triphosphor type with electronic ballasts suited
for the application.
1.02 LAMPS, GENERALLY
A.
Incandescent and fluorescent lamps for all fixtures shall
be provided by the Contractor. Quantity of lamps shall be
as indicated on Drawings, or as required by the fixture
installation.
B.
In general all interior lighting fixtures shall be
equipped with T8 lamps with tri-phosphor coating and low
mercury content-
C.
Lamps shall be the standard product of General Electric
Lamp Co., Osram/Sylvania Electric Co., and Philips Co.
D.
All fluorescent fixtures shall be furnished with solid
state energy saver type ballasts. Ballast for fluorescent
lamps shall be suitable for one, two, three and four lamp
configurations, as necessary, but shall not serve other
non-ballasted fixtures unless indicated on the Drawings.
E.
Linear T5 Fluorescent lamps may be used with written
permission from the Authority.
NYCSCA
LAMPS, BALLASTS AND ACCESSORIES 16501 - 1
04/30/10
DESIGN NO. 012090
1.03 SPARES
A.
In
addition to
those
installed
in
fixtures,
the
Contractor shall provide spare lamps in original cartons,
packaged and labeled and delivered to the Authority's
Representative as follows:
1.
Provide
___
spare lamps
1.04 SUPPLEMENTAL SUBMITTALS
A.
Submit samples as requested by the Authority.
D.
Spares.
PART 2 - PRODUCTS
2.01 INCANDESCENT LAMPS
A.
Lamps shall be inside frosted. Lamps of 200 watts or less
shall be of the medium base type- Fixtures equipped with
300 watts lamps may be of the medium or mogul based
uypes, unless otherwise noted. Lamp sizes of 500 watts or
larger
shall
be
equipped
with
mogul
bases.
All
incandescent lamps shall be Krypton filled energy
conservation savings lamps with approximately 10% energy
saving.
2.02 FLUORESCENT LAMPS
A.
Fluorescent lamps shall have a luminous efficacy of no
less than 90 lm/W, CRI (Color Rendering Index) of no less
than 80 and color temperature of 3500K.
B.
Linear fluorescent lamps shall be F32TS/835 and F25T8/835
medium bi-pin base with 20,000 hours lamp life.
C.
Linear T5 Fluorescent lamps may be
permission from the Authority.
used with
writtcn
2.03 METAL HALIDE - NOT USED
2.04 HIGH PRESSURE SODIUM - NOT USED
2.05 FLUORESCENT BALLASTS
A.
NYCSCA
Unless otherwise noted on the Drawings, fluorescent
ballasts shall be type "A" sound rated, high frequency
electronic type with .88 BF (Ballast Factor) normal light
LAMPS, BALLASTS AND ACCESSORIES 16501 - 2
04/30/10
B.
DESIGN NO. 012090
output, high power factor of .95 or greater and
less
than 10% total harmonic distortion.
Ballasts shall be installed by the fixture manufactures
in accordance with NEMA and NEC requirements. All
ballasts shall be UL listed.
C.
Electronic ballasts shall be by Advance,
Lighting Technologies, Osram/Sylvania and
warranted for five years including cost of
ballast replacement.
D.
Ballasts shall operate lamps on a parallel circuit and
allow remaining lamps to maintain full output if
companion lamp fails. Ballasts shall not be affected by
lamp failure and shall not affect normal lamp life.
E.
Instant start ballasts are allowed for circuits, which
are intended to be, switched no more than ones per day.
F.
Ballast
shall
meet
the
requirements
of
Federal
Communications Commission Part 18 for Electromagnetic
interference and RFI, Non Consumer Equipment.
G.
Ballasts
shall be
transients defined
location A2.
H.
Ballasts potting compound shall contain no PCB.
I.
T5 and Compact fluorescent ballasts shall incorporate
auto resetting end of life circuit interruption cut off.
J.
Ballasts for control of lamps in one housing or fixture
unit shall not control lamps of an adjoining unit,
(except where specified or for continuous cove lighting
and only if the unit with the ballast is properly
identified. This
requirement
shall
apply
to
all
fluorescent fixtures unless otherwise indicated on the
Drawings or in the Specifications for purposes of
multiple switching and control).
K.
In three-lamp fixtures three-lamp ballast shall be
provided.
Where three lamp fixtures are split wired
(wired to two switches), the center lamp (and its onelamp ballast) (of each fixture to a circuit) shall be
wired to the same circuit, unless connected to the
emergency circuit.
internally
in defined
Universal
shall be
labor for
protected from line
in ANSI C62.41-1991
2.06 HIGH INTENSITY DISCHARGE BALLASTS - NOT USED
NYCSCA
LAMPS, BALLASTS AND ACCESSORIES 16501 - 3
04/30/10
DESIGN NO. 012090
2.07 EMERGENCY LIGHTING BALLAST
A.
Emergency ballast shall be New York City approved and
comply with U.L.924 for installation on the top of the
fixture (Internal Type) or remotely (External Type).
n.
Input power rating shall not exceed 8 watts at 120 volt.
Inverter circuit shall be solid state design of the
ferroresonant type. Charger shall be fully automatic by
solid state constant potential
type
and shall be
temperature compensated to assure optimum battery life.
C.
Upon failure of normal AC power, an automatic relay
circuit shall instantly apply battery power to the
inverter circuit to operate one or two lamps for 90
minutes. The unit shall be provided with solid state
circuitry to allow for normal switching of fixture to OFF
position. Normal OFF switching solid state circuitry
shall permit the unit to differentiate between normal OFF
switching and loss of normal AC power without activating
the emergency battery.
D.
The unit shall consist of the following items:
E.
NYCSCA
1.
Battery:
type.
2.
Charger: Fully automatic, solid state, constantcurrent type with sealed power transfer relay.
3.
Test Push Button and Indicator Light: Visible and
accessible without opening fixture or entering
ceiling space.
4.
Emergency Connection: Operate one fluorescent lamp
continuously.
Connect
unswitched
circuit
to
battery-inverter unit and switched circuit to
fixture ballast.
5.
Diagnostic LED panel shall include the following
functions: battery charge/failure, lamp failure,
and circuit transfer failure.
6.
A double-pole momentary test switch.
7.
Housing: Housing to be white powder coated. Heavy
duty 18 gauge steel case.
24 volt, Field-replaceable Nickel-Cadmium
Approved manufacturer: Bodine B30ST or approved equal.
LAMPS, BALLASTS AND ACCESSORIES 16501 - 4
04/30/10
DESIGN NO. 012090
PART 3 - EXECUTION
3.01 INSTALLATION
A.
Provide the precise complement of lamps in every indoor
and outdoor lighting fixture provided under the Contract.
B.
Install
lamps
instructions.
C.
Provide electronic ballasts of compatible design to lamps
required.
D.
Ballast shall be screwed to fixture body and be provided
with quick disconnects on wiring to allow for ease of
replacement.
in
accordance
with
manufacturer's
END OF SECTION
NYCSCA
LAMPS, BALLASTS AND ACCESSORIES 16501
-
5
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
STIBMITTAL
DATE SUBMITTED
DATE APPROVED
Product data
Samples
Spares
NYCSCA
LAMPS, BALLASTS AND ACCESSORIES 16501 - 6
04/30/10
DESIGN NO. 012090
SECTION 16520
ILLUMINATED EXIT SIGN AND EMERGENCY LIGHTING FIXTURES
PART 1 - GENERAL
1.01
DESCRIPTION OF WORK
A.
1.02
Provide battery-powered and/or line voltage Illuminated
Exit Sign and Emergency Lighting Fixtures.
SUPPLEMENTAL SUBMITTALS
A.
Submittal Package
2.
Submit the Product Data items specified below at
same time as a package.
the
Battery Emergency and Exit Lighting Fixtures warranty.
C.
Certificate of
requirements.
D.
Operation and Maintenance Manuals:
compliance with the
Quality Assurance
Deliver to the Authority's Representative.
Include
name, address and telephone number of the nearest fully
equipped service organization.
1.03
QUALITY ASSURANCE
A.
Service Availability
A
fully
equipped
service
organization
available to service the completed Work.
1.04
2.01
-
A minimum of three (3) year warranty shall cover the
LED exit sign. An additional seven (7) year pro-rata
warranty shall cover the sealed maintenance-free NiCad
battery.
PRODUCTS
EXIT SIGN (SINGLE FACED/DOUBLE FACED) (LED)
A.
NYCSCA
be
WARRANTY
A.
PART 2
shall
Housing shall consist of precision die cast from high
strength aluminum. Unit shall have a stencil face with
stenciled
letters
and
field
selectable
chevron
knockouts. Letters shall be red and 8" high.
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520 - 1
04/30/10
DESIGN NO. 012090
Fixtures shall be provided with an ultra long life,
high intensity LED light panel mounted totally within
the exit housing.
A color-enhanced diffuser shall be
mounted in front of the light panel to provide even
illumination.
The unit shall also be provided with a
maintenance-free
sealed Nicad battery, which shall
provide 90 minutes of illumination in the event of
power failure.
Provide a charger-monitor LED which when lit, will
indicate current is supplied to the LED panel.
Provide
also momentary test switch to simulate power failure.
Upon pressing of the test switch, the LED monitor
should turn off, but the exit sign should stay lit,
indicating that the battery is supplying power to the
LED panel.
Finish shall be
aluminum face.
matte
black
acrylic
with
brushed
Provide suitable guard manufactured by Chase Security
series CSGW, Atlite model AIGl6-12jw or approved equal,
when indicated on the drawings.
Fi:tures shall be McPhilben ER40Lll2R, Atlize #LN28DRl-TPS-SCAl25
for
single face
sign or McPhilben
ER40L212R or Atlite #LN2-8DR2-TPS-SCA125 for double
face sign, Guth, Lightalarms, Lightron, MagniFlood,
Ruud Lighting, or Solux.
2.02
EMERGENCY LIGHTING REMOTE FIXTURES
A.
Double And Triple Lighting Heads:
Head
with
fully
adjustable
swivel,
all
aluminum
construction and satin aluminum finish.
Unit shall be
wall mounted directly to a 4" outlet box at 8'-0" above
finished floor.
Two-head unit shall be lightalarms #ELF622D or Atlite
#RF402-MRS-12RS25 with two (2) 2S-watt double contact
bayonet base lamps.
Three-head unit shall be Lightalarms #ELF622T or Atlite
#RF403-MRS-12RS25.
B.
Recessed Round Gimbal:
Fixtures shall have welded steel housing and metal
trim.
Lamp shall have a horizontal rotation of 358
degrees and vertical angle adjustable to 42 degrees.
Fixture shall be Lightalarms #ELF605M or approved equal
of Atlite, with standard white finish, complete with
one 25-watt double contact bayonet base lamp.
NYCSCA
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520 - 2
04/30/10
C.
DESIGN NO. 012090
Surface Round Gimbal:
Same as recessed unit detailed in "B" above, except
suitable for surface mounting.
Lightalarms #ELF606M,
standard white finish or approved equal of Atlite,
complete with one 25 watt lamp, 12 volts sealed beam
incandescent.
D.
Emergency Battery Units
1.
2.
3.
NYCSCA
12-volt maintenance free emergency battery unit
with automatic
solid
state
constant
voltage
charger and sealed lead calcium battery with
mounting platform at locations shown on Drawings.
Wattage of all battery units shall be 200 watt
unless otherwise noted on the Drawings.
Battery
units shall power fixtures listed above.
Battery units shall consist of the following
items:
a.
Solid State Charger
b.
Full Wave Silicon Rectifier
C.
Instantaneous Transfer Relay
d.
Circuit shall be battery short circuit and
reverse polarity protected. Output shall be
electronically short circuit and overloaded
protected.
e.
Automatic brown out requirement
f.
Diagnostic LED panel shall include minimum
the following
functions:
battery charge/
failure, lamp failure, and circuit transfer
failure.
g.
Momentary test switch and AC adapter
h.
Heavy duty 18 gauge steel case
i.
Finish: housing to be white powder
amp heads to be brushed aluminum.
j.
Battery shall be 12
sealed lead calcium.
volt,
coated.
maintenance
tree
Unit
shall be Lightalarms Electronics Corp.,
Catalog #2P12Q1
(100 Watts) and #2P12Q2
(200
Watts) or Atlite Catalog #12ADSNY5-0 (100 Watts)
or 12ADSNY7-0 (200 Watts).
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520 - 3
DESIGN NO. 012090
04/30/10
E.
2.03
4.
Mounting platform shall be Lightalarms Electronics
Corp., Catalog #MP-PQ or approved equal of Atlite.
5.
Wire guards for battery units shall be Lightalarms
Electronics Corp., Catalog # WG3, Atlite Cat# AD,
or Chase Security.
6.
Lamps shall be 25-watt PAR 36 size, white flood
high intensity, numbered as required on Drawings.
Relay Remote Control
1.
The Contractor shall provide and connect a remote
emergency
ceiling
to
control
relay
control
lighting and battery operated emergency lighting
as shown on Drawings.
2.
Power for relay shall be obtained
Lighting panel at each location.
3.
Remote control relay shall be Square D #8903 with
number of contacts required, suitable for 120-volt
operation.
from
Local
WIRE GUARDS
A.
PART 3
3.01
-
Where fixtures are so designated, provide a guard
suitable for that fixture, as provided by the
fixture manufacturer. At a minimum, guards shall
be
provided
on
fixtures
in
gymnasiums
and
cafeterias.
EXECUTION
GENERAL
A.
The Contractor shall adjust the aim of the emergency
lighting fixture heads to obtain maximum lighting level
at areas so as to meet the footcandle levels required
by the 2008 NYC Building Code.
B.
Install the emergency lighting system in a dedicated
conduit system to comply with New York City Electrical
Code
3.02 FIXTURE INSTALLATION
A.
NYCSCA
The Contractor shall be responsible for the mounting
and support of all exit signs, battery packs, and
emergency lighting fixtures.
Provide all items of
equipment
(stems,
hangers,
rods,
inserts,
boxes,
brackets, yokes, channels, frames, etc.) required to
adequately and safely support each exit sign and
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520 - 4
04/30/10
DESIGN NO. 012090
emergency lighting fixture in a manner acceptable to
the Authority
B.
The Contractor is required to protect fixtures from
damage during installation, up to time of acceptance by
the Authority. Any broken or marred fixtures shall be
replaced by the Contractor at no additional cost to the
Authority.
C.
Pendant Mounted Fixtures on Suspended Ceiling
Pendant mounted exit sign shall be supported above
suspended ceiling by hanger rods, 3/8" in diameter
minimum, vertically attached to approve straps, bars,
channels secured to the black iron where available, or
to structural steel or concrete.
ID.
Surface mounted exit signs
Surface mounted exit signs shall have their own back
boxes, custom fitted to the signs. Ceiling and end
wall-mounted exit signs shall be provided with a die
cast canopy and a back box. All surface mounted exit
signs and their back boxes shall be anchored to the
wall at four (4) points.
3.03
AIMING
A.
3.04
CLEANING
A.
3.05
After the installation and prior to final acceptance,
all Emergency Lighting shall be adjusted under the
supervision of the Authority's Representative and the
Engineer to provide code mandated lighting levels at
means of egress.
All fixtures shall be cleaned both inside and out prior
to final acceptance to remove all construction debris,
dust, fingerprints, exposed labels etc.
Fixtures and
or parts, which have been damaged, chipped, scratched
or inadvertently painted during construction, shall be
repaired or replaced at the direction and discretion
of the Authority's Representative.
FIELD QUALITY CONTROL
A.
Progress Inspections
1.
NYCSCA
The
Authority
will
carry
out
all
progress
inspections in accordance with Section BC 109 and
the applicable sections of the 2008 NYC Building
Code. Inspections will include the following:
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520
-
5
04/30/10
DESIGN NO. 012090
a.
2.
Public
assembly
emergency
§28-116.2.2 of Title 28.
lighting
per
The Contractor must
notify
the
Architect
or
Engineer for Progress Inspection at least 72 hours
before the specific work commences.
END OF SECTION
NYCSCA
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520 - 6
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Data
Warranty
Certificate of compliance
With the Quality Assurance
Requirements
Operation and Maintenance Manuals
*
NYCSCA
**
ILLUMINATED EXIT SIGN AND
EMERGENCY LIGHTING FIXTURES 16520 - 7
THIS PAGE INTENTIONALLY LEFT BLANK
-
04/30/10
DESIGN NO. 012090
SECTION 16725
TELEPHONE CABLING SYSTEM
PART I - GENERAL
1.01 DESCRIPTION OF WORK
A.
The intent is to provide new telephone device and
telephone cabling system to replace the existing that
are
to
be demolished. The
specification includes
horizontal and riser wiring for telephone system. The
work shall include but not limited to all cables,
conduits, outlets, etc. The Authority requires that all
components including cable, connectors and outlets meet
or exceed applicable performance standards for voice
communications.
1.02 SUPPLEMENTAL SUBMITTALS
A.
Submittals Package
Submit
the Shop Drawings, Product Data submittals
specified below at the same time as a single package.
B.
Shop Drawings
1.
C.
Composite wiring and/or schematic diagrams of the
complete
cabling
system
as
proposed
to
be
installed
(standard
diagrams
will
not
be
acceptable).
Product Data
1.
Catalog
sheets,
factory
assembly
drawings,
specifications and installations for all products.
Documents will not be accepted for review unless
they are submitted as a package where they pertain
to
related items,
and clearly identified
or
highlighted to indicate
all
items which are
applicable.
2.
Bill of materials.
D.
Sample of lock box & cable
E.
Cabling System acceptance test report.
1.03 CABLE DELIVERY
A.
NYCSCA
No cable over one (1) year old when delivered to the
site will be accepted.
TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 1
04/30/10
DESIGN NO. 012090
1.04 CABLING SYSTEM ACCEPTANCE
A.
Inspection of the installed cable system shall be
made
by the Authority
to verify that
the
installation
conforms to all the requirements stated herein,
and
that the cabling system is 100% defects free.
The
acceptance criteria shall include, but not be limited
to:
Completed
installation and
wire, cable, and raceway.
functional
operation
of
PART 2 - PRODUCTS
2.01 LOCK BOX
A.
In new partitions, boxes shall be flush or semi-flush
mounted type with finishing collars.
Surface mounted
boxes shall be utilized for existing partitions. All
boxes shall utilize a piano hinge welded or bolted on
the inside.
Bolted assemblies shall utilize nylon
locknuts.
B.
Lockbox shall be provided with means to connect a
single line wall mounted Category C RJ-45 telephone
jack plate. Telephone Lock Box Jack model number shall
be MX-WP-K6-SS
C.
Surface Mounted Lockboxes: Four '" diameter holes shall
be provided on the back of the enclosure for surface
wall mounting. Surface mounted boxes shall not be
provided with finishing collar. Two (2) knockout holes
shall be provided (one on the top, one on the bottom)
for surface metal raceway connections.
D.
Flush or Semi-flush Lockboxes: Flush or semi-flush
mounted boxes shall utilize a 1-1/4" finishing collar.
Two (2) 14" diameter holes shall be provided on each
side of the box for flush or semi-flush mounting. Two
(2) " diameter knockout holes shall be provided (one
on the top, one on the bottom) for EMT conduit
connectio-.
E.
Lockbox must be painted, beige textured, made of 16
gauge corrosion resistant steel, dimension 121H X 8"W X
61"D.
F.
The lockbox shall have a keyed latch
installed.
Provide two keys per lockbox.
shall be keyed alike.
G.
Lockbox shall be mounted so that the center of
phone, when installed, is 48" from the floor.
NYCSCA
door
lock
All boxes
the
TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 2
04/30/10
H.
DESIGN NO. 012090
Recommended Lockbox: Anixter-Unity LBI,
Hoffman, or Lee.
2.02 INTERMEDIATE DISTRIBUTION
FRAME (MDF) - NOT USED
FRAME
(IDF)
AND
Lowell, Artel,
MAIN DISTRIBUTION
2.03 WIRING
A.
Conductors
All station wiring shall have legible color coding of
conductors and be four (4) pair, Unshielded Twisted
Pair (UTP), 24 gauge. Voice cable must adhere to all
performance
specifications
indicated
for
TIA/EIA
Category 6 UTP media as cited in TIA/EIA 568B.2
standard. Cable must be approved by the Underwriter
Laboratories, Inc.
and must bear exterior jacket
markings of "Verified Level 6" or "Classified Level 6".
2.04 LABELING OF CABLES, JACKS AND CONNECTING BLOCKS:
A.
Cables are to be tagged at both station and closet ends
with an alpha and four-digit number beginning with V001
and increasing in increment of 1. It shall be a sticky
tag, wrapped and secured to the cable behind both the
jack faceplate and connecting blocks.
All
cable
and
termination
labels
are
unique
identifiers, which shall be permanent and comply with
TIA/EIA 606 labeling standards. At the closet end, the
connecting
block
termination
is
labeled
at
the
corresponding panel port with two points of information
concerning the far end and each separated by a dash:
(1) Room number at the other end of the cable
(2) Cable number (four digits)
At the station side, the jack faceplate is labeled with
two points of information pertinent to the cable far
end and each separated by a dash:
(1) Room number from the IDF or MDF
(2) Cable number on the jack faceplate (four digits)
The cable numbers shall be in sequence for each closet.
For example, if there are 50 voice cables originating
from IDF-i, then the cable numbers shall be V001 thru
V050. Each closet would start over from V001.
B.
Identification of all equipment frames, racks, and wall
termination fields shall be by means of
engraved
lamacoid nameplates showing 1" high white lettering on
a black background.
C.
Provide a riser diagram framed under glass mounted on
wall near the MDF.
NYCSCA
TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 3
04/30/10
DESIGN NO. 012090
2.05 CABLE TIES
A.
All
cable ties used to support telecommunications
cabling shall be fire-resistant nylon type. The support
rating of the cable ties used shall be a minimum of
twice that of the weight per unit of the cables to be
supported. Cable ties shall be deployed every four (4)
feet minimum for voice cables in horizontal cable tray
and
two
(2) feet
minimum when
fastening
cables
vertically on wall or rack.
2.06 TERMINATIONS
A.
Cable Runs Shall Terminate as Follows:
1.
Standard desk phone station run in offices and in
administrative areas shall be two (2) four pair
Category 6 cables; one Category 6 designated for
voice and the other Category 6 designated for
data. This station shall be terminated on a duplex
combination faceplate consisting of
two RJ-45
type, eight conductor modular outlets configured
as per TIA/FIA jack designation T568B. The voice
and data modular RJ-45 inserts shall be color
coded to differentiate the two. A blue insert for
voice
and
orange
for
data
is
recommended.
Connecting hardware shall be marked and comply
with TIA/EIA performance levels 6 associated with
the particular cable being terminated.
2.
For wall mounted telephones in classrooms, four
pairs of voice cable (Category 6e) shall terminate
at a wall mounted assembly in a metal lockbox with
eight conductors, modular RJ-45 outlet mounted at
41-0" A.F.F. At the station end, all four pairs
must be terminated at the IDF/MDF.
3.
At
the
IDF/MDF,
all
cable pairs
shall
be
terminated in consecutive order starting in the
upper left hand co.ner of the frame and proceeding
from the top to bottom and left to right.
PART 3
-
EXECUTION
3.01 INSTALLATION - NOT USED
3.02 GROUNDING - NOT USED
NYCSCA
TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 4
04/30/10
DESIGN NO. 012090
3.03 TESTING
A.
Cabling System Acceptance Test:
1.
B.
Each station cable and wall phone assembly cable
shall be tested end-to-end (from jack faceplate to
associated IDF or MDF 110 block) for length,
continuity(wiremap),Propagation delay, NEXT (near
end
crosstalk),PSENEXT,
PSELFEXT
impedance,
resistance
and attenuation.
Testing
shall
be
conducted with cable certification device capable
of performing appropriate bandwidth /certification
test; i.e. Category 6 cable for voice shall be
tested at 100 MHz and Category 3 riser shall be
tested for 16 MHz. Test result shall be printed
for each test parameter and submitted to the
Authority. Any cable run not meeting minimal
requirements shall be repaired or re-run, and then
re-tested for compliance.
Category 6 cable testing shall be performed using PLUKE
NETWORKS OMNISCANNER II. Refer to specification 16727,
Local Area Network
(LAN) Cabling System, for the
testing of the cable. Category 3 riser cable testing
shall be performed by INDEPENDENT TECHNOLOGIES TEST ALL
25 with 110 punch down adapter kit.
C.
All
defects
or
deficiencies
discovered
in
the
cabling
system work must be indicated on the test report and be
corrected. Any
connections
determined
to
be
not
correctable
shall
be
indicated
at
each
end
of
termination as "bad" (in red).
END OF SECTION
NYCSCA
TELEPHONE & INTERCOM CABLING SYSTEM 16725 - 5
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Shop Drawings
Product Data
Sample of lock box & cable
Cabling System acceptance
test report.
NYCSCA
TELEPHONE & INTERCOM CABLING SYSTEM 16725
-
6
04/30/10
DESIGN NO. 012090
SECTION 16727
DATA CABLING SYSTEM
PART I - GENERAL
1.01 DESCRIPTION OF WORK
The intent is to provide new data devices and cabling system
to replace the existing that are to be demolished.
1.02 SUPPLEMENTAL SUBMITTALS
A.
Product Data:
1.
Catalog
sheets,
factory
assembly
drawings,
specifications and installations for all products.
Documents will not be accepted for review unless
they are submitted as a package where they pertain
to
related items,
and
clearly
identified or
highlighted
to
indicate
all
items
that
are
applicable.
D.
Shop Drawings:
1.
C.
D.
E.
Composite wiring and/or schematic diagrams of the
complete
cabling
system
as
proposed
to
be
installed
(standard
diagrams
will
not
be
acceptable).
Sample: Prior to assembling or installing the data
communications works, the followings shall be submitted
for review.
1.
Category 6 Cable.
2.
Cable connector
3.
Wiring device plate complete with label
4.
Identification label
Certificate of compliance with the Quality Assurance
and Maintenance requirements.
Certified Test Report
1.03 CABLE DELIVERY
A.
No cable over one (1) year old when delivered to the
site will be accepted.
1.04 QUALITY ASSURANCE
A.
Installer's Qualifications:
The persons actually installing the work of this
section
shall
have
a minimum of
two-(2)
year's
experience in Data Cabling System.
Installer must be
NYCSCA
DATA CABLING SYSTEM 16727 - 1
04/30/10
DESIGN NO. 012090
certified by the
certification must
approval.
PART 2 -
cable manufacturer and proof of
be submitted to the Authority for
PRODUCT
2.01 MANUFACTURERS
A.
Acceptable manufacturers of Data cabling system are
AMP/TYCO, Hubbell
Premise Wiring, Ortronics, Krone,
Panduit and Lucent. All equipment shall be the product
of one manufacturer for compatibility and shall fully
meet all the requirements of this specification.
B.
Acceptable
cable
manufacturers
are AMP/TYCO,Belden,
Mohawk, Berk-Tek, Hubbell Premise Wiring,
Panduit and
General Cable.
2.02 DATA NETWORK
A.
Data network cabling system described herein is based
upon TIA/EIA 568A Commercial Building Wiring standard.
The installation shall include but not be limited to
the following.
1.
Category 6 cable:
Cable
shall
be
four
pairs
of
23
AWG solid
conductors, unshielded twisted pairs, UL/NEC CMR
rated with PVC jacket, cable jacketing shall be
lead-free, AMP/TYCO P/N 216560-1. The cable shall
meet
the following performance requirements in
addition to
other standard Cat
6 performance
requirements.
* Frequency
250 MHz
" Max. Attenuation - 30.5 db/100 meter
" NEXT (Near End Cross Talk) - 48 db minimum
tolerance
* ACR (Attenuation to Cross Talk Ratio) - 17.5 db
at 90 meter
Contractor shall provide UL-listed plenum rated
cable
(Type CMP) in environmental air spaces,
including plenum ceiling. AMP/TYCO P/N 219567-1.
The following color code shall be utilized:
COLOR CODE
PAIR NO.
White/Blue and Blue/White
White/Orange and Orange/White
White/Green and Green/White
white/Brown and Brown/white
NYCSCA
1
2
3
4
DATA CABLING SYSTEM 16727 - 2
04/30/10
DESIGN NO. 012090
2-
Faceplate:
Provide faceplate with integrated connector and
modular jacks to accept input cable and provide
combination jacks as required. Faceplate shall be
plastic in a color selected by the Architect, with
color-matched screws.
Unit shall be AMP/TYCO P/N
557505, Panduit P/N CFPL2EI Hubbell Premise Wiring
IFP Series Faceplates, or approved equal suitable
for mounting on a single device box.
3.
Data Jack:
Data jack shall be Category 6 modular eight-pin
connector, EIA T568B wiring, UL listed. AMP P/N
1375055-1, Hubbell Premise Wiring P/N HXJ5EWH,
Panduit P/N CJSE88TGWH or approved equal for
single jack.
4.
5.
NYCSCA
Labels
a.
Provide laser Printable labels on all cables
detailing cable run number. Identification
shall be by means of wrap around Hubbell
Premise Wiring P/N XPLCBLA2 adhesive cable
labels produced via AMP/TYCOLabelingSoftware
AMPNETCONNECT.COM/LA9EL,
Hubbell
Premise
Wiring Labeling Software and a standard laser
printer
All station outlets, MDR and LDF
must be labeled and all circuits clearly
identified utilizing designation strips in
compliance with TIA/EIA 606 standards.
b.
Labels for risers, cables, faceplates, cover
plates etc. shall be provided with textual
descriptions.
c.
Identification
of
all
equipment
frames,
racks, and wall termination fields shall be
by means of engraved lamacoid nameplates
showing 1" high white lettering on a black
background.
Cable Ties:
All cable Ties
used to
support
telecommunications cabling shall be fire-resistant
Velcro type. Cable Ties to be installed by Panduit
GTS Cable Tie Tool.
The support rating of the
cable ties used shall be a minimum of twice that
of the weight per unit of the cables to be
supported. Cable ties shall be deployed every four
(4) feet minimum data cables in horizontal cable
tray and two (2) feet minimum when fastening
cables vertically on wall or rack.
DATA CABLING SYSTEM 16727
-
3
04/30/10
PART 3
-
DESIGN NO. 012090
EXECUTION
3.01 INSTALLATION
A.
Workstation Cabling:
1.
Workstation outlets may be described as one of the
following:
a.
b.
C.
2.
3.
Voice and data outlet
Data and data outlet
Wireless Access Point data outlet
A voice and data workstation outlet shall
of the following cabling:
consist
a.
One
(1) Category Cat
pair cable for voice
AWG).
b.
One (1) Category 6 unshielded twisted pair
cable for data (4 pair twisted, #23 AWG).
A data and Data
following cabling:
outlet
6 unshielded twisted
(4 pair twisted, #24
shall
consist
of
the
a. Iwo (2) Category 6 unshielded twisted pair cable
for data (4 pair twisted, #23 AWG),
4.
Workstation cabling may
following locations:
a.
b.
b.
c.
terminate
in one
of
the
Wall mounted box
Floor flush or surface mounted poke-thru
V4000 Wiremold
Wireless Access Point
3.02 HORIZONTAL DISTRIBUTION CABLE INSTALLATION
A.
Maintain the twist of horizontal and backbone cables to
within 0Y" at the fln
of tcrmination.
B.
When running cable through dropped ceiling space, the
Contractor shall assure proper cable strain relief at
all times.
C.
Cable shall be installed so that there are no bends
less than four times the cable's outside diameter (4X
Cable O.D.) at any point in the run.
D.
Horizontal distribution cables shall not be bundled in
groups
of
greater
than
40
cables.
Cable
bundle
quantities in excess of 40 may cause deformation of the
bottom cables within the bundle.
NYCSCA
DATA CABLING SYSTEM 16727 - 4
04/30/10
E.
DESIGN NO. 012090
Pulling tension on 4-pair UTP cables shall not exceed
25-pounds for a single cable.
3.03 LONWORKS LON DISTRIBUTION CABLE INSTALLATION - NOT USED
3.04 WIRELESS ACCESS POINT (AP) CABLE INSTALLATION
A-
The cable allocated for the wireless AP shall be home
run from the floor's LDF or MDF to the room receiving
the AP. The cable shall be terminated using a AMP/TYCO
Premise Wiring Cat 6 yellow data jack P/N 1375055-8 or
Hubbell Premise Wiring Cat 6 yellow data jack P/N
HXJ5EY.
Existing
wireless
access
point
shall
be
reinstalled.
3.05 GROUNDING - NOT USED
3.06 LABELING OF CABLES AND JACKS
A.
Cables are to be tagged at both station and closet ends
with an alpha and four-digit number beginning with D001
and increasing in increment of I. It shall be a sticky
tag, wrapped and secured to the cable behind both the
jack faceplate and patch panel.
All
cable
and
termination
labels
are
unique
identifiers, which shall be permanent and comply with
TIA/EIA 606 labeling standards. At the closet end, the
patch panel termination is labeled at the corresponding
panel port with two points of information concerning
the far end and each separated by a dash:
(1) Room number at the other end of the cable
(2) Cable number (four digits)
At the station side, the jack faceplate is labeled with
two points of information pertinent to the cable far
end and each separated by a dash:
(1) Room number from the LDF or MDF
(2) Cable number on the jack faceplate (four digits)
The cable numbers shall be in sequence for each closet.
For example, if there are 50 data cables originating
from LDF-1, then the cable numbers shall be D001 thru
D050. Each closet would start over from D001.
3.07 TESTING
A.
All tests are to be performed after installation of the
complete system.
E.
The equipment indicated below represents test equipment
utilized
to
develop
this
test
specification.
Substitute test
equipment may be used only upon
approval by the Authority's Engineer provided the same
level and quality of testing is performed.
NYCSCA
DATA CABLING SYSTEM 16727
-
5
04/30/10
C.
DESIGN NO. 012090
Test Equipment:
FLUKE NETWORK OMNISCANNER II
D.
E.
NYCSCA
All tests are to be performed on the
of data cabling system:
following aspects
1.
From Telecommunication room's main data rack (MDR)
and
LonWorks
patch
panels
to
corresponding
telecommunication
closets'
patch
panel
and
termination
(backbone cable).
For fiber optic
backbone see section 16728.
2.
From each telecommunication closet's
to
each
and
every
workstation
(workstation cable).
patch panel
termination
Tests to be performed:
1.
The test equipment shall be configured to test the
maximum transmission performance for which the
cable is rated (i.e. for category 6 cable is I to
250 Megahertz per second)
2.
In accordance with TIA Standards for Category 6
(Full Duplex Parallel Transmission) cabling, the
following
minimum
test
information
shall
be
provided for each permanent link:
a.
Wiremap:
Verify
Continuity
on
all
8
conductors and assure
no
opens,
crosses,
splits or shorts to another conductor or
ground. When applicable, report continuity of
shield on screen twisted pair.
b.
Length: Total length from LDF to workstation
termination: The cable length shall conform
to the maximum distance set forth in the
TIA/EIA 568-A-5 standard (i.e. 90 M or 308
feet),
C.
Propagation Delay and Delay Skew: Will be
measured and reported. Propagation Delay will
not exceed 536 nanoseconds and Delay Skew
will be within 45 nanoseconds between the
fastest and slowest conductor pairs.
d.
Near End Cross Talk (NEXT) or Noise: Sweep
and Measure
(I MHz to 250 MHz) each pair
combination. Limits will not be less than 48
db at 250 Mhz. on any combination.
e.
Attenuation:
(db loss):
Sweep and Measure
each cable for proper attenuation according
DATA CABLING SYSTEM 16727 - 6
04/30/10
DESIGN NO. 012090
to TIA specifications at 1 MHz to 250 Mhz.
Limit will not be less then +17.5db at 250
MHz.
f.
Return Loss or Echo: Sweep and
cable for minimum return loss
TIA specifications from 1 MHz
Limit will not be greater then
250 MHz.
g.
Equal
Level
Sweep
and
Far
End
Measure
Cross
each
Measure each
according to
to 250 Mhz.
-27.7 db at
Talk
cable
for
or
ELFEXT:
a
minimum
ELFEXT according to TIA specifications from 1
Mhz to 250 Mhz. Limit will not be greater
than -29.9db at 250 MHz.
F.
h.
PowerSum Near End Cross Talk or PSNEXT: Sweep
and Measure each cable for a minimum PSNEXT
according to TIA specifications from 1 MHz to
250 Mhz. Limit will not be greater than -49.2
db at 250 MHz.
i.
PowerSum Elfext
or
PSELFEXT:
Sweep
and
measure each cable for a minimum PSELFEXT
according to TIA specifications from 1 MHz to
250 Mhz. Limit will not be greater than -42.6
db at 250 MHz.
All test
formats:
results
shall
be
1.
Printed (3 bound copies)
2.
CD ROM (Windows)
provided
in
the
following
The test equipment specified has the ability to
record test results to electronic memory for
viewing
and
printing
later
utilizing
free
Microtest ScanLink software. Submitting electronic
test results is preferred in lieu of handwritten
forms. In no instance will test data be accepted
in a spreadsheet or text based reporting software.
This
information
shall
be
maintained
as
a
permanent record for the purposes of maintenance
and restorations.
G.
All tests shall be coordinated with and performed in
the presence of the Authority's Representative. Any
defects or deficiencies discovered in any of the
cabling system work shall be indicated on the test
report and be corrected.
H.
Upon completion of testing and problem resolution, all
cables tested are to be 100% error free.
NYCSCA
DATA CABLING SYSTEM 16727 - 7
04/30/10
3.08 COORDINATION
- NOT USED
DESIGN NO. 012090
WITH
SYSTEM
INTEGRATOR
FOR
DATA
LAN
NETWORK
END OF SECTION
NYCSCA
DATA CABLING SYSTEM 16727 - 8
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Data
Shop Drawings
1.
Wiring Diagrams
2.
Composite Rack panel
Samples:
1.
Cable
2.
Cable Connector
3.
Wiring Device
4.
Identification label
Certificate of Compliance
with the Quality Assurance
Requirements
Certified Test Report
NYCSCA
DATA CABLING SYSTEM 16727
-
9
-
THIS PAGE INTENTIONALLY LEFT BLANK
-
04/30/10
DESIGN NO. 012090
SECTION 16728
FIBER OPTIC CABLING SYSTEM
PART 1 - GENERAL
1.01
DESCRIPTION OF WORK
A.
1.02
The intent of this specification is to provide new
device and cabling system to replace the existing that
are to be demolished.
SUPPLEMENTAL SUBMITTALS
A.
Submit the shop drawings, product data, samples and
quality control specified below at the same time as a
single package.
B.
Product Data:
C.
1.
Catalog sheets, specifications
instructions for all products.
2.
Written statement from cable manufacturer
indicating recommended pulling compounds.
and
installation
Shop Drawings:
1.
Complete manufacturers' construction details and
specifications for the cables, including physical
characteristics of optical fiber, strength members
and jackets.
2.
Overall dimension of cable.
3.
Termination data, including the following:
a.
List of materials
b.
Method of terminating cables
c.
4.
Written statement from cable manufacturer
that terminations submitted are acceptable,
and suitable for the proposed application.
Cable
manufacturer's
certified
test
data
(attenuation, bandwidth).
NYCSCA
5.
Maximum pulling strain allowed for each type cable.
6.
Composite wiring and/or schematic diagrams of the
complete cabling system as proposed to be installed
(standard diagrams will not be acceptable).
FIBER OPTIC CABLING SYSTEM 16728 - 1
04/30/10
D.
E.
DESIGN NO. 012090
Samples:
1.
Two(2) foot samples of each type cable.
2-
Samples of termination materials if requested.
Quality Control Submittals:
1.
F.
1.03
Installers'
Qualifications
Data:
Include
following who will be performing the work:
the
a.
Employers
name,
telephone number
and
b.
Name and addresses of the required number of
similar projects worked on which meet the
experience criteria.
business
address
Cabling system acceptance test report.
QUALITY ASSURANCE
A.
Installers' Qualifications:
The persons installing the work of this section shall
be personally experienced in optical fiber cabling
system and shall have been engaged in the installation
of optical fiber cable for a minimum of two (2) years.
1.04
DELIVERY, STORAGE AND HANDLING
A.
B.
Cable Delivery:
1.
No cable over one (1) year old when delivered to
the site will be accepted.
2.
Keep ends of cables sealed at all times, except
when making terminations. Use methods approved by
cable manufacturer.
Cable Storage:
Store where cable will be at temperature recommended by
cable manufacturer for optimum workability.
PART 2
2.01
- PRODUCTS
MANUFACTURER
A.
NYCSCA
Acceptable Manufacturers are: Hubbell Premise Wiring,
AMP
Inc.,
Corning,
ADC-Krone,
Ortronics,
Mohawk,
Optical Cable Corporation, and Belden.
FIBER OPTIC CABLING SYSTEM 16728 - 2
04/30/10
2.02
DESIGN NO. 012090
OPTICAL FIBER CABLE
A.
Six
(6) strands
(for horizontal run),
single ripcords
and core warp tape, full dielectric construction, UL
listed
OFNP
for
Plenum
applications;
continuous
operating temperature -40"C to 700 C. Each fiber shall
be
62.5/125
micron
(core/clad)diameter,
multimode
graded index optical fiber waveguide operating at 850
and
1300 nanometer
(nm),
maximum attenuation 3.75
dB/km and 1.0 db/km respectively. Use UL-listed plenum
cable in environmental air spaces, including plenum
ceilings.
2.03
ENCLOSURE FOR OPTICAL FIBER TERMINATING BOX (OFTB)
A.
The unit
is designed for termination of optical
fiber
cables.
Individual strands shall be fanned out and
terminated with SC connectors in an interconnect plate
with twelve interconnect sleeves, following proper
manufacturers'
specifications
for bend radius and
strain relief1.
Dimensions
components.
2.
Single
lock.
as
gasketed
required
door
for
with
installation
continuous
hinge
of
and
a.
Requires two
box.
b.
c.
Lock Kit: Hoffman's A-CLSN12 or approved
equal of Lee Products Co.
Lock shall be keyed the same as locks for
fence accessory stations (FAS's).
d.
Provide two
(2) coupler panels per 12 port
(2) keys.
3.
14 gauge steel mounting plate within enclosure for
mounting components and future components.
4.
Louvers as required for ventilation and to prevent
temperatures above equipment ratings.
5.
Mounting
accessories
as
required to
mount
in a
standard 19" rack.
2.04
CONNECTORS
A.
NYCSCA
Connector shall be a no-adhesive/no-epoxy/no-polish SC
connector.
The connector shall have a 62.5/125 micron
fiber stub pre-epoxied and pre-polished in the ferrule
tip. The fiber to be terminated shall be simply
FIBER OPTIC CABLING SYSTEM 16728 - 3
04/30/10
DESIGN NO. 012090
prepped
and
cleaved
before
insertion
into
connector. The maximum optical attenuation per
mated connector pair shall not exceed 0.5 dB.
2.05
INNERDUCT
A.
2.06
Provide
flame-retardant
innerduct
for
protection,
isolation and identification of fiber optic cable.
Innerduct must meeL UL94 V-0 flame test for plenum.
ACCESSORIES
A.
Pulling
Compounds:
manufacturer.
H.
Tags:
Precision
engrave
letters
and numbers
with
uniform margins, character size minimum 3/16" high.
1.
C.
PART 3
3.01
-
As
recommended
by
cable
Phenolic:
Two
(2) color
laminated engravers'
stock, 1/16" minimum thickness, machine engraved
to expose inner core color (white).
Markers:
Premarked self-adhesive;
W.H. Brady Co.'s
B940,
Thomas and Petts Co.'s 7-Z Code WSL selflaminating,
Ideal
Industries'
Mylar/Cloth
wire
markers, or Markwick Corp.'s permanent wire markers.
EXECUTION
PREPARATION
A.
3.02
the
each
Before installing cable, test the cable on the reels to
verify that the cables' parameters are in accordance
with the manufacturers' certified test data.
INSTALLATION
A.
Installing Cables:
1. No fiber optic cable shall be run unprotected. The
cable shall bc protected as follows:
NYCSCA
Location
Method of Protection
Accessible ceiling
Spaces
Innerduct
required
Non-accessible ceiling
Spaces
Conduit
Raised floor
Wiremold
Exposed
Innerduct
(plenum as
FIBER OPTIC CABLING SYSTEM 16728 - 4
04/30/10
B.
DESIGN NO. 012090
Location
Method of Protection
Within cabinets and
Racks
Innerduct or spiral
wrapped buffer tubes
2.
All raceways containing fiber optic cable shall be
provided with a label "caution-Fiber Optic Cable"
located on the raceway every 20 feet.
2.
Keep ends of cables sealed watertight at all
times, except when making splices or terminations.
3.
No grease, oil, lubricant other than approved
pulling compound may be used to facilitate the
pulling-in of cables.
4.
Use pulling attachment connected to the
strength member for pulling in cables.
pulling attachment watertight.
Terminations:
1.
All
strands
of
fiber optic cable
shall
be
terminated in SC type connectors at the outlets
and fiber patch panels at the cabinet.
2.
No splicing of
allowed except:
a.
C.
2.
fiber
cables
will
be
Connectorized splices will be allowed in the
OFTB.
Install tags on each cable
indicating cable
number, date installed (month, year), type of
cable and manufacturer.
Attach tags to cables
with non-ferrous metal wire or brass chain.
Use markers to identify each optical fiber in
equipment to which they connect.
FIELD QUALITY CONTROL
A.
Testing:
1.
NYCSCA
optical
Identification of Optical Fiber Cables: Identify cables
in MDR, LDFs and at all fiber outlet locations:
1.
3.03
cable
Seal
Perform test on optical fiber after cable has been
installed complete with connectors.
All strands
shall be tested for end-to-end attenuation loss at
850 nm and 1300 nm. Procedure for the test shall
comply with EIA/TIA 526-14-A, Method B: Optical
FIBER OPTIC CABLING SYSTEM 16728 - 5
04/30/10
DESIGN NO. 012090
Power Loss Measurements
Fiber Cable Plant.
of
Installed
Multimode
a.
Demonstrate that the amount of power coupled
into each optical fiber by its transmitter,
the attenuation and connector losses, and the
power
received
at
the
detector
in
the
receiver is no greater than 75%
of the
parameters
required
by
the
transmitter/
receiver manufacturer.
b.
The total optical attenuation (dB loss) will
not exceed .5 dB/per mated connector ports
and 3.75 dB/km for the fiber.
2.
Perform test in the presence of the Authority's
Representative. Failed strands shall be corrected
or replaced and re-tested for compliance.
3.
Supply equipment Optical Time Domain Reflectometer
(OTDR) necessary for performing test.
4.
Submit printed
results
shall
information :
a.
b.
c.
d.
e.
f.
report of test results.
Test
contain
the
following
minimum
Cable origin
Cable destination
Cable ID
Cable pair/strand
Test date
2 point attenuation
(d3)
3.04 EQUIPMENT INSTALLATION AND TESTING - NOT USED
END OF SECTION
NYCSCA
FIBER OPTIC CABLING SYSTEM 16728 - 6
04/30/10
DESIGN NO. 012090
LIST OF SUBMITTALS
SUBMITTAL
DATE SUBMITTED
DATE APPROVED
Product Data:
1.
Catalog Cuts
2.
Written statement
Shop Drawings:
Samples:
1.
Cables
2.
Termination materials
Quality Control Submittals
1.
Installers Qualifications
Test Report:
NYCSCA
FIBER OPTIC CABLING SYSTEM 16728 - 7
Download