Space Temperature Sensor Overview Installation Resistance Chart

Space Temperature Sensor
Product Information Sheet
809-6590
Overview
The 809-6590 is wall mounted space temperature
sensor. It is suited for a wide variety of applications.
The temperature sensor has a 10KΩ thermistor. The
sensor has been tested by CPC to maintain less than
0.72°F error between -40 and 248°F.
Installation
The sensor connections to the input point on the 16AI
board are not polarity sensitive. The sensor is
connected as shown below in the Sensor Wiring
Diagram. The sensor can be wired to any available
point on the 16AI board. Connect one lead to the 0V
input, and connect the other lead to the SIG input.
Temperature
( oF )
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
The dip switch for the 16AI input should be set to the
ON position.
Sensor Wiring Diagram
The sensor includes two mounting screws for
mounting the sensor to a standard single gang box.
Resistance Chart
The accuracy of the resistor can be verified using an
Ohm meter. The chart here shows the resistance for
various temperatures.
Temperature
(oC )
-40
-34
-29
-23
-18
-12
-7
-1
4
10
16
21
27
32
38
43
49
54
60
66
71
77
82
8
93
Resistance
(Ohms)
336,450
234,170
165,210
118,060
85,399
62,493
46,235
34,565
26,100
19,899
15,311
11,883
9,299
7,334
5,828
4,664
3,758
3,048
2,488
2,042
1,686
1,400
1,169
981
827
EmersonTM, Emerson. Consider It SolvedTM and Emerson Climate TechnologiesTM logos are trademarks and service marks of Emerson Electric Co.
Intelligent StoreTM is a trademark of Emerson Climate Technologies. All other trademarks are the property of their respective owners.
© 2011 Emerson Climate Technologies, Inc. All rights reserved.
12