MECKLENBURG COUNTY Land Use and Environmental Services Division Code Enforcement Memo Date: To: From: Re: April 21, 2009 All customers Jim Bartl, Director of Code Enforcement 2009 NC State Building Code effective dates I’m writing to remind customers that North Carolina is transitioning to the new 2009 NC Building Code family. In March, 2008, the NC Building Code Council (BCC) adopted the 2009 NC State Building Code family. In doing so, the BCC set various effective dates for the implementation of the new Code, as follows: NC Electrical Code effective date was June 1, 2008, except for 3/11/08 amendment items 3 (relates to wet location receptacles; see amended NEC 406.3) and 6 (relates toAFCI protection; see amended NEC 210.12), which had effective dates of January 1, 2009. NC Building, Fire Prevention, Residential, Mechanical, Plumbing, Fuel Gas and Energy Codes, with effective date of January 1, 2009, and a transition period of January 1, 2009 through June 30, 2009. This meant a project could use either the 2006 or 2009 Code in the period January 1, 2009 through June 30, 2009. However, on or after July 1, 2009, the new 2009 NC Building Code family must be used. Since the BCC prescribed transition period is quickly drawing to a close, customers should take care to assure they comply with the Department policy on code transitions, as follows. Department policy on the transition period Regarding the absolute cutoff date for use of the 2006 code, given the extremely long transition period provided by the BCC, we see no reason to extend this with a further grace period after June 30, 2009. Consequently, permits issued after June 30, 2009 must comply with the 2009 NC State Building Code. It is very important that professionals monitor their work closely to carefully determine when a project’s design basis must switch to the new NC Codes to comply with the above transition periods and the Department’s policy about them. While state law requires us to issue a permit on any project compliant with the effective code, the burden is on the owner’s team to estimate when your permit will be issued. Projects not permitted by June 30, 2009 must comply with the 2009 NCSBC, regardless of when they entered the system for permitting. Feel free to contact me or any of the trade or plan review chiefs, if you have questions on the effective dates of the NC State Building Code. PEOPLE PRIDE PROGRESS PARTNERSHIPS 700 North Tryon Street Charlotte, North Carolina (704) 336-2831 Fax (704) 336-3839 www..meckpermit.com MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Memo Date: April 21, 2009 TO: From: RE: all contractors Jim Bartl Code Compliance Report For over 11 years, the Department has collected data on inspection failures, based on a system of defect codes, which are recorded at the time of inspection. Those reports are summarized for presentation to the Building Development Commission on a quarterly basis. Attached is a copy of the most recent Code Compliance Report Data Summary for the period January 1, 2009 to March 31, 2009. This report highlights the most frequent code defects sighted in each of the trades. Since July 1, 2001, detailed contractor code defect data has been available on the Department web site (go to the contractors’ tool box at www.meckpermit.com). Questions on the data may be directed to the appropriate trade chief or Kathleen Rivers (704-336-3545). Prior to July 1,2002, we also held hard copies of individual contractor defect reports at the Building Development Center front desk for contractor pickup. Given the huge amount of paper involved, and the fact that the vast majority of these reports were not picked up, this service was discontinued. However, Hal Marshal Center Document Control staff will provide assistance to contractors on downloading their reports over the counter or by phone (704-336-3830). PEOPLE PRIDE PROGRESS PARTNERSHIPS 700 North Tryon Street Charlotte, North Carolina (704) 336-2831 Fax (704) 336-3839 www.meckpermit.com January 1, 2009 through March 31, 2009 Mecklenburg County Code Enforcement Department Code Compliance Report Data Summary 1. Building Inspections Top Fifteen Code Defects task item # item # defects % of total framing 111 fire stopping/draftstopping 237 4.38% final 105 call clerk 183 3.39% mono slab 108 need soil compaction test 171 3.16% framing 197 other defects listed on job 167 3.09% footing 108 need soil compaction test 158 2.92% frame 105 call clerk 156 2.88% final 197 other defects listed on job 140 2.59% final 118 handrail construction 127 2.35% final 104 not ready for inspection 110 2.03% framing 109 foundation anchors missing 95 1.76% frame 104 not ready for inspection 94 1.74% frame 195 previous list incomplete 73 1.35% final 123 exterior grading incorrect 67 1.24% final 121 insulation missing or exposed 60 1.11% final 114 flashing/caulking 59 1.09% TOTAL 1897/5404 35.10% Note 1: all 04 (incomplete not ready for inspection) total 350 or 6.47% of total bldg code defects noted Note 2: Rough O2's = 35.95% of total; Final 02's = 27.75% of total 2. Electrical Inspections Top Fifteen Code Defects task item # item # defects % of total final 30 improper wiring method 172 4.10% final 25 improper overcurrent protection 158 3.76% final 9 grounding 155 3.69% final W8 defects created by others 154 3.67% final 4 not ready for inspection 117 2.78% final 19 label panel 111 2.64% final 55 GFCI general 99 2.36% final 5 too many defects to list 78 1.86% final 10 bonding 78 1.86% final 6 defect not corrected 74 1.76% final 31 cables subject to damage 64 1.53% final 65 AFCI 58 1.38% final 11 incorrect size or wire type 52 1.24% final 41 improper joints or terminations 50 1.19% rough W8 defects created by others 48 1.15% TOTAL 2068/4871 34.98% Note 1: all 04 (incomplete not ready) total 231 or 5.5% of total electrical code defects noted Note 2: Rough O2's = 13.3% of total; Final 02's = 55.99% of total 1 3. Mechanical Inspections Top Fifteen Code Defects task item # item # defects final H01 damage caused by others 189 final Z99 other defect or no code 127 gas test G03 test not to code or bad gauge 108 final A04 not ready for inspection 100 final P1 primary/secondary drain missing 74 final Z98 ext'g cond'tn not code compliant 66 final F01 flue clearance 65 final E8 eqpt installation instructions 64 final A13 need ladder 62 final G03 gas test not to code 57 rough H01 damage caused by others 53 final F02 flue material installed incorrectly 52 final Z96 approval withheld for other trades 43 final F06 flue termination incorrect 38 final G09 gas line regulator missing 38 TOTAL 1136/2765 % of total 6.84% 4.59% 3.90% 3.60% 2.68% 2.39% 2.35% 2.32% 2.24% 2.06% 1.92% 1.88% 1.55% 1.37% 1.37% 41.09% Note 1: all 04 (not ready for inspection) total 145 or 5.24% of total mechanical code defects noted Note 2: Rough O2's = 17.5% of total; Final 02's = 66.55% of total 4. Plumbing Inspections Top Fifteen Code Defects task item # item rough B31 piping test missing/incorrect final E31 handicapped regulation missing final H01 damage by others final D31 T&P drain missing or incorrect final 41 not ready for inspection wtr distr B31 piping test missing/incorrect final C21 pipe insulation missing final E71 fixture installed incorrect final J41 existing condition not to code final B51 piping support missing/incorrect rough B51 piping support missing/incorrect final C71 equipment missing or incomplete final C91 cleanouts missing or incorrect final D21 water heater pan missing rough B81 vent piping or AAV size incorrect TOTAL # defects 74 60 56 55 49 40 34 33 33 27 26 23 20 20 20 570/1112 % of total 6.65% 5.39% 5.04% 4.95% 4.40% 3.60% 3.06% 2.96% 2.96% 2.43% 2.34% 2.07% 1.80% 1.80% 1.80% 51.26% Note 1: all 04 (not ready for inspection) total 77 or 6.92% of total plumbing code defects noted Note 2: Rough O2's = 18.17% of total; Final 02's = 57% of total 2 Building Consistency Meeting Residential Date: 1/7/09 Recorder and minutes prepared by: Danny Wooten/Jeff Griffin Staff present: Jeff Griffin, Tim Taylor, Danny Wooten, Ron Featherstone, Steve Kellen, Harold Sinclair, Walt Nash, Darrell McAllister, Rob Ellis, Jimmy Butler, Russ Fisher, David Williams, Mike Brown, Don Sprinkle, Mike Creech, Sam Caulder, Steve Pearson, Mark Wyte, Paul Cupp, TW Anthony, Eric Brown, Michael Johnson, Ron Dishman, Andrew DeMaury, Andy Herring. Public present: Daniel McBride (Cunnane Group); Greg Sloan/Hans Kasak (Ryland Homes); Kevin Ratliff (Griffin Masonry); Charles Sofinowski/Darren Price (M/I Homes); Lou Salvador/Jeff Dunn (DR Horton); Bob Mckee (Ryan Homes); Jason Whitener (Southern Tradition Homes); Matthew Klapheke (L&M Const); Darek Burns (Essex Homes); Dave Reynolds (Bldrs, 1st source); A. Wynn Yates (Yates/Starnes Eng); David R. .Schwieman (DR Schwieman, Inc); Bill Green/David Piddock (Barefoot & Co.); Joseph Murray (McCar Homes); Wayne Carter (J&B Development); Mary Nash/Jeff Neudecker (Centex Homes); Brad Crysler (John Wieland); Doug Tino (DE Tino, Inc); Beverly Newell (Sixteen Penny Const). Topics/Subject Decisions/Conclusions/Actions Old Business New 2009 Codes We received all the 2009 code books on January 21st and we are at this time taking any plans for review under the new codes. Books are available at: http://www.iccsafe.org/. New Business Buildings located close to transformers Garage definition Residential plan review thresholds changed Electrical Department has come out with an interpretation on transformer location related to building structures. This is more of an electrical issue but several builders have called about this new interpretation and a handout was passed out to the group including an invitation to a lunch discussion on the issue. This issue is still being discussed but may have some impact on wall ratings and openings on certain jobsites. The full Department policy can be found on www.meckpermit.com under electrical services listed on the left side of that main page. Question has been raised about situation with an attached or detached structure that may have access for vehicle parking. A new interpretation was handed out dealing with the issue of spaces that have roll up overhead doors more than 6’ wide that have the potential to be used as a garage area. These spaces will need to be constructed as garage per attached interpretation. Being April 1st 2009 the thresholds for residential projects will be expanded slightly to include detached accessory structures more than 400 square feet or more than 1 story in height. Also any residential structure that has an additional floor level added will require plan review (see attached customer notice). Building Consistency Meeting Residential Date: 2/11/09 Recorder and minutes prepared by: Danny Wooten/Jeff Griffin Staff present: Ron Featherstone, Jeff Griffin, Tim Taylor, Danny Wooten, Steve Kellen, Harold Sinclair, Walt Nash, Darrell McAllister, Rob Ellis, Russ Fisher, David Williams, Mike Brown, Don Sprinkle, Sam Caulder, Steve Pearson, Eric Brown, Ron Dishman, Andrew DeMaury, Andy Herring, Mort Robins, Darren Bishop, Randy Newman, Ralph Vernon, Mike Jackson, Steve Lineberger, Ken Turull, Steve Miller, Greg Walsh, Barry Human, Gene Morton, George Rogers, Tony Kiser, David Ries, Steve Honeycutt. Public present: Greg Sloan/Hans Kasak (Ryland Homes); Kevin Ratliff/Rob Merrell (Griffin Masonry); Charles Sofinowski (M/I Homes); Bob Mckee (Ryan Homes); Jason Whitener (Southern Tradition Homes); Darek Burns (Essex Homes); Dave Reynolds (Bldrs, 1st source); Wynn Yates (Yates/Starnes Eng); David R. .Schwieman (DR Schwieman, Inc); Chad Huges (Barefoot & Co.); Wayne Carter (J&B Development); Mary Nash (Centex Homes); Scott Dellinger (Drafting & Design) Beverly Newell (Sixteen Penny Const); Terry Cleary (Meeting Street Homes); Kevin Adkins (Regent Homes); Brad Crysler (John Weiland Homes); Dennis Adams (CPCC); David Little (Banister Homes); Joe Stewart (Stewart Builders). Topics/Subject Decisions/Conclusions/Actions Old Business None New Business Remodel vs. new construction Trade defect codes handout Townhouse dormer windows Issue has been discussed within the Department and with the Industry related to a residential remodeling job that ends up tearing down more of the original structure than what’s left. A threshold limit was established as to when we would permit as a new structure vs. a remodeling job, an interpretation was passed out and is attached to the minutes for review. Discussed issue of current code defects used by field inspectors to indicate failed items on the electronic record. This list is being updated, expanded and the Department is looking at providing more useful tools in working with this data. Input from the industry has been requested and a handout of the current codes and change recommendations of staff was distributed at the meeting. More information to include a final list to follow. Issue brought up about dormer windows installed on townhouses closer than 4’ from property line in the protected roof sheathing area (option for not building parapet wall between units). There is nothing in the Code that allows this application the language is very specific under section R317.2.2 item #2 exception where it states “a parapet is not required when the roof is covered with a minimum class C roof covering and the roof decking or sheathing is of a non-combustible material or approved fire-retardant-treated wood for a distance of 4 feet”. Adding a dormer window on top with or without a rated side wall can still add fire load with the burning of a vinyl siding or other covering material in this area. All dormer windows must be kept out of this 4’ roof protected area or a parapet wall between will be required. In addition there was a question about the overhang (eaves) on that dormer window into the 4’ protected area. This overhang is not the same as the section R302 requirement for 3’ fire separation distance and projection allowances. Due to the new requirement to protect townhouse soffits there are no additional requirements and nothing prohibiting a 12” eave overhang. Handrail height vs. guards 2006 Code 2009 Code Issue brought up in regards to the 2006 Code that was mandatory from July 1, 2008 to today and an item that was approved by mistake in the this 2006 Code. That item had to do the mounting height of the guard on an open side of a stair. This had created a problem when you use the guard as a handrail also, handrail could be as low as 30” but guards were raised to 34”(in previous codes even back under CABO NC has allowed guards to be 30” to match the start of the handrail mounting height). This has been corrected in the 2009 code and we are allowing currently the installation on open stairs sides to match the allowances under the 2009 residential code. ICC sprinkler appeal New Code classes at CPCC Electrical transformer policy 60” standing surface at tub to glazing Appeal to the IRC approval of sprinkler systems was made by the National Home Builders Association to the appeal board of ICC in their December meeting. The board heard the argument not on the basis of the technical requirement but on the procedural aspects of the approval, based upon that the appeal was denied. See attached information from ICC website. This will mean that the issue will go forward to the State of NC in their review of the 2012 Code. Classes on the changes to the 2009 code will be held at CPCC being 1 ever month for the next 4-5 months. This class is designed for 3 hours of classroom instruction and then a 3 hour field frame class. For code officials this will qualify for the 6 hours of continued education, see this link for information on the class from CPCC website (Crowder Construction Institute) http://www.cpcc.edu/codeinspector/courseschedule. Go to the bottom of the page and you will see the schedule for class COD 8000. Question was asked about the status of this interpretation from our electrical Department. This item was reviewed with them and is still being drafted any input or inquiries can be directed to Joe Weathers Chief Electrical inspector or Angela Miller or Gary Mullis Asst. Chief’s at 704/336-3523. Issue was brought up by the industry as a reminder of a Code change we have had since going to the International codes starting with the 2002 NC residential code with a January 1st, 2003 mandatory enforcement date. This change effected where you measure from and is no longer from the drain inlet (per previous CABO Code) but is anywhere from the standing or walking surface. See commentary picture below that illustrates this issue from section R3084 item #5. Remodel vs. new construction There has been a concern in the past about remodeling that ends up with a structure being torn down past a responsible point where it should be considered a new building structure. The topic was discussed with feedback requested to establish these thresholds. An interpretation on the issue is being drafted and should be available at the next consistency meeting. New FD tables The 2009 code has new foundation tables that start with plain masonry construction thru reinforced masonry to a single table for concrete (plain concrete and reinforced). These tables R404.1.1(1-5) were reviewed in the meeting to include a new limitation on crawl space wall unbalanced fill which is 48” and a new bolting requirement for basement walls as found under section R404.1. Foundation walls that meet all of the following shall be considered laterally supported: 1. Full basement floor shall be 3.5 inches (89 mm) thick concrete slab poured tight against the bottom of the foundation wall. 2. Deleted 3. Bolt spacing for the sill plate shall be no greater than 36 inches (914 mm). 4. Deleted. 5. Where foundation walls support unbalanced load on opposite sides of the building, such as a daylight basement, the building aspect ratio, L/W, shall not exceed the value specified in Table R404.1(3). For such foundation walls, the rim board shall be attached to the sill with a 20 gage metal angle clip at 24 inches (610 mm) on center, with five 8d nails per leg, or an approved connector supplying 230 pounds per linear foot (3.36kN/m) capacity. Maximum vertical rise in stairways There is a new section of code that limits the vertical rise in a stairway this language is found in section R311.5.4. R311.5.4 Landings for stair ways. There shall be a floor or landing at the top and bottom of each stair way. Exception: A floor or landing is not required at the top of an interior flight of stairs, provided a door does not swing over the stairs. A flight of stairs shall not have a vertical rise greater than 12 feet (3658 mm) between floor levels or landings. The limitation covers all types of stairs and therefore will apply to specialty stairs was well such as circular or spiral stairs. Recent site issue found a spiral stairway that had been constructed with more than a 12’ vertical rise and there is no exception under the code for these specialty stairways, landings would be required. Building Consistency Meeting Residential Date: 3/4/09 Recorder and minutes prepared by: Danny Wooten/Jeff Griffin Staff present: Ron Featherstone, Jeff Griffin, Tim Taylor, Danny Wooten, Steve Kellen, Harold Sinclair, Walt Nash, Russ Fisher, David Williams, Mike Brown, Don Sprinkle, Sam Caulder, Steve Pearson, Eric Brown, Ron Dishman, Andrew DeMaury, Andy Herring, Randy Newman, Steve Lineberger, Steve Miller, George Rogers, David Ries, Michale Johnson, Patrick Biddy, Mark Wyte, Scott Linhardt. Public present: Hans Kasak (Ryland Homes); Charles Sofinowski (M/I Homes); Bob Mckee (Ryan Homes); Dave Reynolds (Bldrs, 1st source); Wynn Yates (Yates/Starnes Eng); David R. .Schwieman (DR Schwieman, Inc); Wayne Carter (J&B Development); Terry Cleary (Meeting Street Homes); Brad Crysler (John Weiland Homes); Dennis Adams (CPCC); Lou Salvador (DR Horton); Ben Brookhart (Timberline Homes); Daniel Mcbride (Cunnane Group); John Meeks (Apple Blossom Insulators); Brendan Shea (True Homes); Chad Ritter (Intelligent Design Engineering); Joe Stewart (Stewart Builders). Topics/Subject Decisions/Conclusions/Actions Old Business None New Business Sealed crawl space permits Move-on floor insulation Sheathing vs. framing inspection Question was asked about requirements for permits on existing structures when going to a closed crawl system. A Department formal interpretation requirement is attached to these minutes for review. Issue in the field came up in regards to moving an existing structure from one location to a new site and new foundation. Since the crawl space and all aspects of that new area are being looked at should the floor system be insulated to meet the code requirements at time of setup? Since the cavity is open and exposed sitting on a new foundation the floor system should be insulated as required by Chapter 11 of the NC residential code? No other area of the move on has to be insulated as long as cavities not opened up such as removing sheetrock from a wall or ceilings. Concern brought up specifically concerning an insulation inspection that when the history of a job was checked by an inspector, shows a previous open sheathing inspection (sheathing had failed). Contractor did not request another sheathing inspection to correct items that he was turned down for on the first inspection. Contractor is not required to call back in another sheathing inspection if the structure is ready and the next inspection is a frame check then all sheathing related items he was failed for should be addressed at that frame inspection. Any inspector that would go behind and finds that frame has passed in this case should conclude that the sheathing had passed. Inspectors should not try and enter a sheathing result since sheathing inspections are handled differently and result in a $50 charge each time a contractor request one. Handrails at winder treads Sales centers New code classes Fastening schedule Fireplace chase with shed roof There is a change in the codes (section R311.5.6) related to the location of a required handrail up a flight of stairs in the residential code. Under previous versions of the code on a winder flight of stairs the handrail had to be on the narrow side of the stairs. Under the NC2006 & NC2009 code the handrail can be on any side of a flight of stairs regardless of having a winder tread as long as continuous. Additional issue discussed with sales centers located in a home and what has to meet the NC Accessibility Code. Once a sales center is located inside a residence even for temporary usage that area has to be fully accessible to include an interior bathroom on that level. Only the areas that are being used by sales staff have to be modified for public access to include door sizes and hardware, kitchens and bedrooms are not required to be modified. Several classes are scheduled at CPCC dealing with the new residential codes. These classes will be held over the next couple of months (next class scheduled for March 12th. The classes are split with 3 hours of classroom instruction and 3 hours of a field frame class, this is open to all at a cost of $61.00 and enrollment information can be found by going to CPCC’s Crowder construction institute. Discussed the new fastening schedule that is in the 2009 code which will address gun nails but will prohibit the use of clipped head nails, see attached schedule for review. Question was asked about fireblocking inside a fireplace wood frame chase which is typical with a direct vent factory fireplace. Under previous codes fireblocking was required at 10’ vertical heights this would require some chases to have a break at each 10’ level, this has been removed in the ’06 and ’09 codes. The only concern with the exterior fireplace/shed roof type chase now is that if it passes a floor level there needs to be fireblocking to prevent entering into the floor assembly, this is an issue specific to open web floor trusses since conventional framing with have a band that will also act as a fireblock. As long as fire cannot enter into the floor assembly then the shingled roof line at the top of the chase is ok without any additional fireblocking. Consistency Meeting January 7th, 2009 INSPECTORS JOE WEATHERS 704-336-5379 ANGELA MILLER 704-432-1775 GARY MULLIS 704-336-3521 JOSEPH.WEATHERS@MECKLENBURGCOUNTYNC.GOV ANGELA.MILLER@MECKLENBURGCOUNTYNC.GOV GARY.MULLIS@MECKLENBURGCOUNTYNC.GOV SARRAH KELLY JIM ELLIS DAVID SELLERS 704-719-7114 704-336-3810 704-719-7048 CONTRACTORS DANNY SIMPSON 704-821-5200 JIM LONG 704-553-7552 ext.113 BRUCE SAIMES 704-596-2525 RONALD JUDSON 704-814-4733 RUSSELL SANTOS 704-821-5200 PATRICK KOSMELA 704-426-0047 DREW GOAN 704-821-5200 MIKE TISDELL 704-243-3639 TRINA BRASWELL 704-821-4485 MATT CURRAN CELL: 704-363-0234 CELL: 704-361-2226 CELL: 704-634-3020 CELL: 704-400-1048 CELL: 704-506-7319 CELL: 704-400-5067 CELL: 704-999-3771 CELL: 704-320-6820 CELL: 704-309-7442 csimp12@aol.com jim.long@fryeelectric.com bsaims@andersenservices.com rljudson@carylelectrical.com russellsantos@carolina.rr.com pat@obelectric.com agoan@carolina.rr.com Tisdell-electric@carolina.rr.com eandhelectrical@yahoo.com ATTENDANCE AT PREVIOUS MEETING Present: Joe Weathers, Angela Miller, Gary Mullis, Andy Scoggins, Jim Ellis, Sarah Kelly, David Sellers, Bruce Saimes, Ronald Judson, Patrick Kosmela, Mike Tisdell, Trina Braswell, Matt Curran, Buster Beaver, Danny Blackwelder, Scott Blackwelder, Chris Dellinger, Ryan Steed, Roger Ward CODE ISSUES FROM PREVIOUS MEETING Jan 1st begins enforcement of new AFCI and Weather Resistant Receptacle Requirements Lock outs – NEC 422.31 B – must stay in place without lock Need to be attached behind deadfront Existing NM cables that are sleeved on the exterior may remain in place, all new wiring must be rated for wet location Closet recessed incandescent luminaires must be enclosed type even if compact fluorescent bulbs are installed, make sure listing is followed for lamp type Comments were received about perceived retaliation by inspectors, we do not tolerate this behavior and encourage open communication between all our staff and customers Equal potential grounding is required on hot tub replacements Pool bonding points are to be evenly spaced Utility transformer clearances are still being worked on, Duke Energy has offered another standard, we will do a mailing when policy change is finaled AGENDA ITEMS Tamper proof receptacles are required for floor receptacles 210.52 G 1 & 2 and 406.11; Detached garages at dwellings are an accessory of the dwelling and will need tamper proof receptacles. Unfinished basements will require tamperproof receptacles CSSC, gas line appliance connector, does not need to be bonded. Tracpipe PS-11 is a pre-sleeved underground, rooftop, or exterior wall pipe system. It is black in color and needs to be bonded per the manufacturer’s instructions. AFCI 210.12 expansion applies in assisted living apartments and extended stay hotels, with cooking; they both meet the definition of dwelling unit. Appliance companies can not connect hardwired appliances, they may only attach the cord set to the appliances, all else is contractor’s work and is to be permitted Labeling & listing requirements are again being questioned; for approval be sure that all options are given and allowed – listed and labeled equipment/field evaluation by a test lab/design professionals evaluation/wired to meet methods of NEC Transformer policy sent out to contact base by email, brown bag lunch on the 12th, 11:30 – 1:00 AFCI to be installed basically in all heated areas of the residence except kitchens and baths Other Next Meeting: February 11th, 09 Consistency Meeting Feb 4th, 2009 CONTRACTORS/DESIGN PROFESSIONALS DANNY SIMPSON 704-821-5200 JIM LONG 704-553-7552 ext.113 BRUCE SAIMES 704-596-2525 RONALD JUDSON 704-814-4733 RUSSELL SANTOS 704-821-5200 PATRICK KOSMELA 704-426-0047 DREW GOAN 704-821-5200 MIKE TISDELL 704-243-3639 TRINA BRASWELL 704-821-4485 ED JACKSON 704-599-4377 CELL: 704-363-0234 CELL: 704-361-2226 CELL: 704-634-3020 CELL: 704-400-1048 CELL: 704-506-7319 CELL: 704-400-5067 CELL: 704-999-3771 CELL: 704-320-6820 CELL: 704-309-7442 INSPECTORS JOE WEATHERS 704-336-5379 ANGELA MILLER 704-432-1775 GARY MULLIS 704-336-3521 csimp12@aol.com jim.long@fryeelectric.com bsaims@andersenservices.com rljudson@carylelectrical.com russellsantos@carolina.rr.com pat@obelectric.com agoan@carolina.rr.com Tisdell-electric@carolina.rr.com eandhelectrical@yahoo.com ejackson@jordanskala.com JOSEPH.WEATHERS@MECKLENBURGCOUNTYNC.GOV ANGELA.MILLER@MECKLENBURGCOUNTYNC.GOV GARY.MULLIS@MECKLENBURGCOUNTYNC.GOV SARRAH KELLY JIM ELLIS DAVID SELLERS 704-719-7114 704-336-3810 704-719-7048 ATTENDANCE AT PREVIOUS MEETING Present: Angela Miller, Gary Mullis, David Sellers, Ronald Judson, Jim Long, Ed Jackson, Lou Villanella, Mike Kale, Mark Caldwell CODE ISSUES FROM PREVIOUS MEETING Tamper proof receptacles are required for floor receptacles 210.52 G 1 & 2 and 406.11; Detached garages at dwellings are an accessory of the dwelling and will need tamper proof receptacles. Unfinished basements will require tamperproof receptacles CSSC, gas line appliance connector whip, does not need to be bonded. Tracpipe PS-11 is a pre-sleeved underground, rooftop, or exterior wall pipe system. It is black in color and needs to be bonded per the manufacturer’s instructions. AFCI 210.12 expansion applies in assisted living apartments and extended stay hotels, with cooking; they both meet the definition of dwelling unit. Appliance companies can not connect hardwired appliances, they may only attach the cord set to the appliances, all else is contractor’s work and is to be permitted Please have contractors/customers inquiring as to why power as not been turned on or meter has not been set call document and inspections @ 704-336-3830 Loads on residential general lighting circuits; # of circuits (NOT LOAD ON CIRCUIT) are determined by 3va x SF/ circuit breaker amps; typical is 800 sf for 20 amp & 600 sf for 15 amp, loading must follow 210.21 & 23. We need to expand the participation in these meetings. We would like to have more commercial project representation as well. We hope these meetings will keep us all on the same page and enable us to prepare for equitable solutions to our industry challenges in a timely matter. Please pass this information to your peers. Code Defect list CAFCI info Bonding of building metal NEC 250.104 (C) Conductor I. D. NEC 310.12 GS rewrite to have no permit at $5k level Grouping of mains NEC 230.71 & .72 AGENDA ITEMS NEC 406.8 B 2 b; HVAC service receptacle? NEC 404.14 E and 406.3 F; dimmer on switched receptacle? 517.13; redundant grounding on patient care switches NEC 250.24 C 1; grounded conductor routed with phase conductor RIF Other Next Meeting: April 1st, 09 Consistency Meeting March 4th, 2009 CONTRACTORS/DESIGN PROFESSIONALS DANNY SIMPSON 704-821-5200 JIM LONG 704-553-7552 ext.113 BRUCE SAIMES 704-596-2525 RONALD JUDSON 704-535-3263 RUSSELL SANTOS 704-821-5200 PATRICK KOSMELA 704-426-0047 DREW GOAN 704-821-5200 MIKE TISDELL 704-243-3639 TRINA BRASWELL 704-821-4485 ED JACKSON 704-599-4377 BRIAN WINKLER 704-376-2999 RIED SAWYER 704-309-9541 SCOTT LOWERY 704- 357-9333 LEE TEETER 704-376-2999 CELL: 704-363-0234 CELL: 704-361-2226 CELL: 704-634-3020 CELL: 704-506-7319 CELL: 704-400-5067 CELL: 704-999-3771 CELL: 704-320-6820 CELL: 704-309-7442 CELL: 704-771-9435 csimp12@aol.com jim.long@fryeelectric.com bsaims@andersenservices.com rljudsonsr@gmail.com russellsantos@carolina.rr.com pat@obelectric.com agoan@carolina.rr.com Tisdell-electric@carolina.rr.com eandhelectrical@yahoo.com ejackson@jordanskala.com brianw@tegpa.com rsawyer@caryleelectrical.com leet@tegpa.com INSPECTORS JOE WEATHERS 704-336-5379 ANGELA MILLER 704-432-1775 GARY MULLIS 704-336-3521 JOSEPH.WEATHERS@MECKLENBURGCOUNTYNC.GOV ANGELA.MILLER@MECKLENBURGCOUNTYNC.GOV GARY.MULLIS@MECKLENBURGCOUNTYNC.GOV SARRAH KELLY JIM ELLIS DAVID SELLERS 704-719-7114 704-336-3810 704-719-7048 CODE ISSUES FROM PREVIOUS MEETING Number of Services and Mains on multi tenant properties; NEC 230.2 Listed fireplace inserts are on the market with unit modules being cord connected. Be sure electrical system connection is accessible, cord is covered under listing. No 60% policy/rule for remodel & repair. See interpretation policy online under heading, Fire/Remodel Jobs Transformer update; policy revisions, web expansion, future meetings Meg Test: Please research the job and make sure permits were in place at the time the work was covered up. Our policy is to allow meg test only if permit was issued before the work was covered up. Labeling & listing requirements are again being questioned; for approval be sure that all options are given and allowed – listed and labeled equipment/field evaluation by a test lab/design professionals evaluation/wired to meet methods of NEC Transformer policy sent out to contact base by email, brown bag lunch on the 12th, 11:30 – 1:00 AFCI to be installed basically in all heated areas of the residence except kitchens and baths AGENDA ITEMS Number of Services and Mains on multi tenant properties; NEC 230.2 Listed fireplace inserts are on the market with unit modules being cord connected. Be sure electrical system connection is accessible, cord is covered under listing. No 60% policy/rule for remodel & repair. See interpretation policy online under heading, Fire/Remodel Jobs (see attachment) Transformer update; policy revisions, web expansion, future meetings Meg Test: Please research the job and make sure permits were in place at the time the work was covered up. Our policy is to allow meg test only if permit was issued before the work was covered up. Please have contractors/customers inquiring as to why power as not been turned on or meter has not been set call document and inspections @ 704-336-3830 Loads on residential general lighting circuits; # of circuits (NOT LOAD ON CIRCUIT) are determined by 3va x SF/ circuit breaker amps; typical is 800 sf for 20 amp & 600 sf for 15 amp, loading must follow 210.21 & 23. We need to expand the participation in these meetings. We would like to have more commercial project representation as well. We hope these meetings will keep us all on the same page and enable us to prepare for equitable solutions to our industry challenges in a timely matter. Please pass this information to your peers. Code Defect list (see attachment) Other Next Meeting: March 4th, 09 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code & NC Administrative Code Code Chapter Reference: 607.6 & 206 Subject: Alternative Materials/Design Effective Date: December 1, 1995 Prepared/Revision Date: March 2009 CODE: [B] 607.6 Horizontal assemblies. Penetrations by air ducts of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 707 and Sections 716.6.1 through 716.6.3 the International Building Code or shall comply with Sections 607.6.1 through 607.6.3. [B] 607.6.1 Through penetrations. In occupancies other than Groups 1-2 and 1-3, a duct constructed of approved materials in accordance with Section 603 that penetrates a fire-resistance-rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection provided that a listed fire damper is installed at the floor line or the duct is protected in accordance with Section 712.4 of the International Building Code. For air transfer openings, see Exception 7 to Section 707.2 of the International Building Code. Exception: A duct is permitted to penetrate three floors or less without a fire damper at each floor provided it meets all of the following requirements. 1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel not less than 0.019 inch (0.48 mm) (26 gage) in thickness. 2. The duct shall open into only one dwelling unit or sleeping unit and the duct system shall be continuous from the unitto the exterior of the building. 3. The duct shall not exceed 4-inch (102 mm) nominal diameter and the total area of such ducts shall not exceed 100 square inches (0.065 m ) for any 100 square feet (9.3 m ) of the floor area. 4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature conditions under a minimum positive pressure differential of 0.0 I inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. 5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with a listed ceiling radiation damper installed in accordance with Section 607.6.2. 2 Continued: 2 [B] 607.6.2 Membrane penetrations. Ducts and air transfer openings constructed of approved materials, in accordance with Section 603, that penetrate the ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with one of the following: 1. A shaft enclosure in accordance with Sections 707 of the International Building Code . 2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fireresistance-rated floor/ceiling or roof/ceiling assembly. 3. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the cei1ing of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. [B] 607.6.2.1 Ceiling radiation dampers. Ceiling radiation dampers shall be tested in accordance with UL 555C and installed in accordance with the manufacturer's installation instructions and listing. Ceiling radiation dampers are not required where either of the following apply: 1. Tests in accordance with ASTM E 119 have shown that ceiling radiation dampers are not necessary in order to maintain the fire-resistance rating of the assembly. 2. Where exhaust duct penetrations are protected in accordance with Section 712.4.1.2 of the International Building Code and the exhaust ducts are located within the cavity of a wall, and do not pass through another dwelling unit or tenant space. [B] 607.6.3 Nonfire-resistance-rated floor assemblies. Duct systems constructed of approved materials in accordance with Section 603 that penetrate nonfire-resistance-rated floor assemblies shall be protected by any of the following methods: 1. A shaft enclosure in accordance with Section 707 of the International Building Code. 2. The duct connects not more than two stories, and the annular space around the penetrating duct is protected with an approved noncombustible material that resists the free passage of flame and the products of combustion. 3. The duct connects not more than three stories, and the annular space around the penetrating duct is protected with an approved noncombustible material that resists the free passage of flame and the products of combustion, and a listed fire damper is installed at each floor line. Exception: Fire dampers are not required in ducts within individual residential dwelling units. INTERPRETATION: Volume 1-A section 206 allows for the use of alternative materials, designs, and methods. The use of Firemaster, Pyroscat, or equal to wrap flues or duct in lieu of shaft requirements of the Building Code shall be determined by the “Building Code Official”. Wraps shall be installer per the manufacturer’s installation instructions and the product listing requirements. Consultants: North Carolina Department of Insurance Prepared by: Philip B. Edwards Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code (2006 & 2009) Code Chapter Reference: 506.3.10 Subject: Grease Duct Enclosure Exception Effective Date: 5/1/2009 Prepared/Revision Date: 3/9/2009 CODE: 506.3.10 Grease duct enclosure. A grease duct serving a Type I hood that penetrates a ceiling, wall or floor shall be enclosed from the point of penetration to the outlet terminal. A duct shall penetrate exterior walls only at locations where unprotected openings are permitted by the International Building Code. Ducts shall be enclosed in accordance with the International Building Code requirements for shaft construction. The duct enclosure shall be sealed around the duct at the point of penetration and vented to the outside of the building through the use of weather-protected openings. Clearance from the duct to the interior surface of enclosures of combustible construction shall be not less than 18 inches (457 mm). Clearance from the duct to the interior surface of enclosures of noncombustible construction or gypsum wall board attached to noncombustible structures shall be not less than 6 inches (152 mm). The duct enclosure shall serve a single grease exhaust duct system and shall not contain any other ducts, piping, wiring or systems. Exceptions: 1. 2. 3. 1. The shaft enclosure provisions of this section shall not be required where a duct penetration is protected with a throughpenetration fire stop system classified in accordance with ASTM E 814 and having an "F" and "T" rating equal to the fireresistance rating of the assembly being penetrated and where the surface of the duct is continuously covered on all sides from the point at which the duct penetrates a ceiling, wall or floor to the outlet terminal with a classified and labeled material, system, method of construction or product specifically evaluated for such purpose, in accordance with ASTM E 2336. Exposed duct wrap systems shall be protected where subject to physical damage. The shaft enclosure provisions of this section shall not be required where a duct penetration is protected with a throughpenetration fire stop system classified in accordance with ASTM E 814 and having an "F" and "T" rating equal to the fire resistance rating of the assembly being penetrated and where a prefabricated grease duct enclosure assembly is protected on all sides from the point at which the duct penetrates a ceiling, wall or floor to the outlet terminal with a classified and labeled prefabricated system specifically evaluated for such purposes in accordance with UL 222 I. A duct enclosure shall not be required for a grease duct that penetrates only a non fire-resistance-rated roof/ceiling assembly. INTERPRETATION: The new NC 2009 Mechanical Code now requires that duct wraps for grease field fabricated grease ducts shall meet ASTM E2336 standards (see exception 2) instead of the UL 1978 standards referenced in previous versions of the NC Mechanical Codes. In January 2009, Underwriters Laboratories (UL), Intertek Systems, and the International Code Council (ICC) Evaluation Services jointly are abandoning all listings or evaluations that are based on Southern Building Code Congress International Inc. (SBCCI) and Building Officials and Code Administrators (BOCA) acceptance criteria, both of which use the internal fire test portion of UL 1978, which addresses reduced clearances for field applied flexible wrap systems. Hence, the ONLY listing for flexible wraps applied to grease ducts will be ASTM E2336-04. Effective May 1, 2009, projects permitted after this date requesting to use the NC 2006 Mechanical Code will be required to meet the more stringent ASTM E2336-04 standards. The NC 2009 Mechanical Code already requires the use of ASTM E2336-04. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical 2009 Code Chapter Reference: Chapter 403, 404 Subject: Ventilation Power Source Effective Date: 1/1/2003 Prepared/Revision Date: 3/26/2009 CODE: See Chapter: 403, 404 INTERPRETATION: Parking garage ventilation systems shall be placed on standby power sources should permanent power be interrupted. It is the intent of the Code to supply constant ventilation to prevent the accumulation of carbon monoxide. The use of CO detectors to reduce the cfm’s as allowed by 404.1 is permitted provided the system is supplied with a reliable power source (i.e. primary + standby). Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: Mechanical Code 2009 Code Chapter Reference: 506.3.12.2 Subject: Grease Duct Termination Effective Date: 1/1/2003 Prepared/Revision Date: 3/26/2009 CODE: 506.3.12.2 Termination through an exterior wall. Exhaust outlets shall be permitted to terminate through exterior walls where the smoke, grease, gases, vapors, and odors in the discharge from such terminations do not create a public nuisance or a fire hazard. Such terminations shall not be located where protected openings are required by the International Building Code. Other exterior openings shall not be located within 3 feet (914 mm) of such terminations. INTERPRETATION: Horizontal termination of grease duct through an exterior wall shall extend 18” beyond finish surface and grade downward to grill termination. This will allow grease deposited on grill to drip to ground without fouling building finish (nuisance) and creating a fire hazard. Exception: Water wash hoods or listed and tested systems (not portable in nature) with greater filtration capabilities may terminate flush with exterior wall. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Fuel Gas 2009 Code Chapter Reference: Section 406 Subject: Testing systems with MP regulators Effective Date: 7/1/97 Prepared/Revision Date: 3/25/2009 CODE: 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, unless two valves are installed in series with a valved "telltale" located between these valves. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. INTERPRETATION: MP regulators in gas piping systems shall be removed and a “spool” piece shall be substituted during the pressure test to assure that all parts of the piping system receive a full test and to assure that the manufacturers specifications are not exceeded. The contractor is responsible for removing the “spool” piece and testing for leaks by bubble soaping the connections after the completion of the test. The regulator must be present at the appliance location to assure its applicability. See Attached Drawing Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Residential 2009 Code Chapter Reference: R606.10 Subject: Lintels on Package Equipment Effective Date: 2/1/2000 Prepared/Revision Date: 3/26/2009 CODE: 604.10 Lintels. Masonry over openings shall be supported by steel lintels, reinforced concrete or masonry lintels or masonry arches, designed to support load imposed. INTERPRETATION: Any outdoor HVAC equipment, whose duct system penetrates the outside masonry wall shall have the masonry above the penetration supported with a steel, concrete or masonry lintel as approved by the building section 604.10 of the 2009 NC Residential Building Code. Steel lintels must extend a minimum of three inches (3”) into undisturbed masonry on each side of the penetration. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator Mechanical Q&A 2009 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Quarter Land Use and Environmental Service Agency (Code Enforcement) February 2009 2) (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section 107.2 of the NC Administrative Code states that it is the duty of the permit holder “to provide access to and means for inspection of the work for any inspections that are required by this code.” (Q) An existing home with a package unit, installed prior to the requirement for lintels where the duct penetrates the foundation wall is being replaced with equipment and duct of the same size. Would a lintel have to be installed at this time? (A) No, provided there is no increase in size of the foundation opening. 1 1) st General: Mechanical Q&A 2009 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Land Use and Environmental Service Agency (Code Enforcement) February 2009 2) 3) 4) 5) (Q) May a contractor use the merchant coupling provided with each stick of gas pipe, to assemble the permitted gas piping system? (A) The NC Gas Code does not prohibit the use of all thread merchant couplings. (Q) How many gas tests are required for a single gas pipe installation? (A) The Code would require two tests. One before you cover the work and one on final inspection. We require an additional test if you would like “temporary heat” which would result in a total of three. (Q) Does gas piping have to be steel where the piping terminates at the meter? (A) The Code does not require a steel termination, but many gas utility providers (Piedmont Natural Gas) will refuse to connect to CSST or copper piping. (Q) May the valve for a free standing range be placed behind the range? (A) Yes. The valve is for servicing and does not have to be placed where it can be accessed without moving the appliance. (Q) Does the Code require a cut-off to be placed at the base of decorative gas yard lights? (A) Yes! The light is considered an appliance and would require a cut-off within 6 feet and accessible (box/vault). 1 1) st Gas Piping: Mechanical Q&A 2009 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Quarter Land Use and Environmental Service Agency (Code Enforcement) February 2009 (Q) What does the new 2009 Energy Code require for duct insulation? (A) Section 403. of the NC Energy Code states residential supplies and returns shall be R8 in unconditioned areas. Duct running through the web of floor truss systems may be R6 to limit duct compression. Duct installed between conditioned floors need not be insulated provided there is no condensation. Commercial supplies and returns shall be R5 in unconditioned areas. Commercial outside duct shall be R8. 1 1) st Duct: MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code 2009 Code Chapter Reference: 507.16, 507.16.1, 507.16.2 Subject: Performance Test Detail Effective Date: 1/1/2003 Prepared/Revision Date: 3/26/2009 CODE: 507.16 Performance test. A performance test shall be conducted upon completion and before final approval of the installation of a ventilation system serving commercial cooking appliances. The test shall verify the rate of exhaust airflow required by Section 507.13, makeup airflow required by Section 508, and proper operation as specified in this chapter. The permit holder shall furnish the necessary test equipment and devices required to perform the tests. 507.16.1 Capture and containment test. The permit holder shall verify capture and containment performance of the exhaust system. This field test shall be conducted with all appliances under the hood at operating temperatures, with all sources of outdoor air providing makeup air for the hood operating and with all sources of recirculated air providing conditioning for the space in which the hood is located operating. Capture and containment shall be verified visually by observing smoke or steam produced by actual or simulated cooking, such as with smoke candles, smoke puffers, etc. 507.16.2 Certification. These tests shall be witnessed by the code official. or at the code official's option, by a professional engineer who shall provide certification of performance to the code official. INTERPRETATION: The hood/s (Type I only) test shall verify the rate of airflow and proper operation with these additional requirements: 1. 2. 3. 4. 5. 6. 7. All building exhausting equipment (i.e. misc. kitchen exhaust fans, bath fans, etc.) shall be energized and in operation during the performance test. The cooking equipment under the hood/s shall be in place, up to operational heat levels and sufficient smoke/ grease generating foods to simulate the desired cooking process. The hood shall capture all exhaust. T-T Puffers (or equal) shall be used during the test to check for spillage of exhaust to the kitchen area. The test shall also include the verifying of actual flow rates versus design flow rates. The Designer or installer shall provide documentation detailing and certification of all test results including the status of the structures systems during the tests (i.e. temperatures, food cooked, fans, etc.) Testing/verification shall be performed by a P.E or person/s certified through AABC, TABB, NEBB or NBC, who shall provide documentation of performance to the code official. The electrical interlocking of any system providing make up air to the hood. Technicians with one of these certifications is approved as an alternate to a Professional Engineer. AABC (Associated Air Balance Council) TABB (Testing & Balancing Bureau) NEBB (National Environmental Balancing Bureau) NBC (National Balancing Council) Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. February 2009 Quarter Quarter Plumbing Q & A 2009 General: st (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section 107.2 of the NC Administrative Code states that it is the duty of the permit holder “to provide access to and means for inspection of the work for any inspections that are required by this code.” 1 1) Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. February 2009 Quarter Plumbing Q & A 2009 2) 3) (Q) Does a ejector pump tank, installed for the future, require the contents (fluids) to be pumped prior to the final inspection? (A) The pumping of the tank would be advisable, but it would be the contractor’s discretion. However, the unused openings (vent, etc.) need to be capped until they are used. (Q) Does a residential fire sprinkler system require backflow devices? (A) If the fire sprinkler system is separate from the plumbing distribution system, then yes, a double check assembly would be required. (Q) What size/type water heater requires a safety pan? (A) Section 504.7 does not exempt any type or size water heater or tank from the requirement of safety pans. 1 1) st Equipment: Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. February 2009 Quarter Plumbing Q & A 2009 (Q) What are the stipulations, if any, on the replacement of drainage piping on fire damaged structures? (A) The damaged piping may be replaced with piping materials and methods used at the time the structure was built. The only difference would be penetrations through rated assemblies. These penetrations are considered “life safety” and would have to meet the Code. 1 1) st Drainage: MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: 2009 Residential Code Code Chapter Reference: R309.1.1 Subject: Garage Duct Penetration Effective Date: 1/1/2003 Prepared/Revision Date: 3/25/2009 CODE: R309.1.1 Duct penetration. Ducts in the garage and ducts penetrating the walls or ceilings separating the dwelling from the garage shall be constructed of a minimum No. 26 gage (0.48 mm) sheet steel or other approved material and shall have no openings into the garage. INTERPRETATION: The above excerpt from the 2002 Residential Code is applicable to all single family, duplex and town homes and will be enforced by the mechanical inspector. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code 2009 Code Chapter Reference: 504.6 Subject: Residential Dryer Exhaust Effective Date: August 30, 1996 Prepared/Revision Date: 3/25/2009 CODE: 504.6 Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall be constructed of metal and shall have a smooth interior finish. With the exception of the tion duct flexible ducts are prohibited The exhaust duct shall be a minimum nominal size of 4 inches (102 mm) in diameter. The entire exhaust system shall be supported and secured in place and terminate not less than 12 inches mm) above finished grade. The male end of the duct at overlapped duct joints shall extend in the direction of airflow. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet (2438 mm) and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction and must remain entirely within the room in which the appliance is installed. Exception: Where the duct termination is less than 12 inches (305 mm) above finished grade an areaway shall be provided with a cross-sectional area not Jess than 200 square feet (186m:?) The bottom of the duct termination shaJJ be no than 12 (305 mm) above the areaway bottom 504.6.1 Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed feet (13 716 from the dryer location to the outlet terminal. The maximum length of the duct shall be reduced 5 feet (1524 mm) for each 45 degree (0.79 rad) bend and IO feet (3048 mm) for each 90 degree (1.6 rad) bend. The maximum length of the exhaust duct does not include the transition duct. Table 603 4 for gage thickness. Exception: Where the make and model of the clothes dryer to be installed is known and the manufacturer's installation instructions for such dryer are provided to the code official, the maximum length of the exhaust duct, including any transition duct, shall be permitted to be in accordance with the dryer manufacturer's installation instructions. Where exhaust ducts are installed in concealed locations. the developed length of the exhaust duct system be indicated by permanent labels or tags installed in an observable location . 504.6.2 Rough-in required. Where a compartment or space for a domestic clothes dryer is provided, an exhaust duct system shall be installed in accordance with Sections 504.6 and 504.6.1. INTERPRETATION: To increase the dryer vent beyond the limitations set forth in the code would require the exhaust system to be installed per a particular dryer manufacturer’s installation requirements. These systems (Engineered) would be based on a specific brand and model dryer. The following must be submitted during the plan review stage: 1) 2) 3) 4) All documents submitted must reference a specific address or job. An engineer must provide necessary data to prove that the proposed design does not exceed the manufacturer’s specifications on this specific make and model of dryer. Documents must be signed and sealed by a N.C. Licensed Design Professional. All structures utilizing an a system engineered for a specific make and model of dryer shall have a permanent placard (framed or equal), permanently affixed to the wall (dryer location), stating the exhaust length, the number of bends and their respective radius of the duct installed so that a replacement dryer may be selected that is capable of exhausting properly. Notes: 1) Exhaust systems designed for a specific dryer are measured from the back of the dryer to the dryer exhaust termination. 2) The use of booster fans is prohibited! 3) The use of long radius ells is approved on a case by case basis. Consultants: N.C. Department of Insurance, ICC Prepared by: Philip B. Edwards Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code 2009 Code Chapter Reference: 306.5 Subject: Roof Access Effective Date: Jan. 1, 2003 Prepared/Revision Date: 3/25/2009 CODE: 306.5 Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances’ level service space. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center. 3. Ladders shall have a toe spacing not less than 6 inches (152 mm) deep. 4. There shall be a minimum of 18 inches ( 457 mm) between rails. 5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1 kg) load. 6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds (488.2 kg/m2) per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for ser vice platforms. Exception: This section shall not apply to Group R-3 occupancies. continued INTERPRETATION: DOI and the ICC have determined, that tenant access to roof service ladders or roof stairs/stairwells for an individual tenants equipment service, shall be accessible to all of the building tenants all of the time (24hrs/day). This can only be accomplished by placing these access components in common areas of the building (i.e., outside, common equipment room, etc.) This Code interpretation is applicable to any structure constructed under the 2006 NC Mechanical Code. This will not apply to structures constructed under earlier versions of the NC Building Codes. (Existing Building designation) Provided that: • • • Any equipment changed has to be an exact equipment replacement . Note: The addition of any new equipment will be applicable to the 2006 NC Mechanical Code. (requires Full Plan Review) A “Change of Use” in occupancy type will be required to meet the 2006 NC Mechanical Code. (requires Full Plan Review) The addition of OR reduction in tenant space square footage will be required to meet the 2006 NC Mechanical Code. (requires Full Plan Review) Notes: • There will be NO Mechanical plan Review on “shell” buildings. Mechanical Plan Review will commence on upfit submission. Mechanical components depicted on “shell” drawings are the owner/designer’s risk. • In areas where “security” to the roof is an issue and the height of the roof exceeds 16’, modifications to the permanent ladder may be acceptable. (Requires approval) Examples: • • • Lockable caged ladder. Extendable ladder. Stop the permanent ladder short of the ground (10’ max.) and use portable ladder to access. (May require a platform) Approved by: Philip B. Edwards, M/P Code Administrator CODE INTERPRETATION CODE: SUBJECT: MECKLENBURG COUNTY Building Code Enforcement 2006 NC RESIDENTIAL CODE SEALED CRAWL SPACE PERMIT REVIEWED: RESIDENTIAL CONSISTENCY TEAM Question: Is a permit required for sealing a crawl space on an existing home? Code reference: Section 106.1 of the NC Administrative Code and Policies (“permit required for all work described in the technical codes unless specifically exempted by the North Carolina Statutes or the technical codes”) Answer: No building permit would be required unless the work exceeded $5,000 in cost. Mechanical and or electrical permits, regardless of cost, may be required based upon the design. The NC General statutes GS153A-357 and 160A417 states no permit (building) is required if the work is in a single family dwelling (commercial has no exceptions) and the cost of the work is $5,000 or less and is not structural in nature. No building permit would be required for installation within this scope; work over $5,000 would require a building permit and inspections. Work $5,000 or under would still need to be installed correctly and would fall back upon the owner of the property. A mechanical and or electrical permit is required for any modifications to existing mechanical or electrical systems that are made to meet one of the space moisture control methods found in section R409.5 such introduction of supply air with backflow dampers or introduction of continuous conditioned air. Any additional work such as installing an outlet for a dehumidifier or wiring in a mechanical fan would require an electrical permit. Modifications to these systems would require a licensed contractor in that field. Approved By ___Gene Morton_______ F:\CORE\CORESUP\KATHY\GENE\CDEINTRP\wythe.doc Date _______3/12/09_______________ MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code 2009 Code Chapter Reference: 507.1 Subject: TurboChef Exemption Effective Date: 2/1/2006 Prepared/Revision Date: March 2009 CODE: 507.1 General. Commercial kitchen exhaust hoods shall comply with the requirements ofthis section. Hoods shall be Type I or Type II and shall be designed to capture and confine vapors and residues. Commercial kitchen exhaust hood systems shall operate during the cooking operation. INTERPRETATION: Having reviewed documentation from UL, TurboChef, and North Carolina Department of Insurance, I have determined that TurboChef models HHB, C3 and NGC may be utilized in some restaurants. These will be approved on a case by case basis having met the following criteria: 1. The quantity of units total grease laden discharge shall exceed 5 mg/m3 when tested to EPA-202. All other equipment is subject to the requirements set forth in Section 507 of the NC Mechanical Code and shall be provided with a Type I or Type II hood as prescribed. 2. The oven shall not be used for the cooking of meats, poultry, fish, or other foods that may produce grease laden vapors. Foods that are pre-cooked and the fat rendered, shall be permitted. 3. The oven shall be installed and maintained per the manufacturer’s specifications. 4. This exemption does not supersede any other state or local agencies requirements. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical Code 2009 Code Chapter Reference: 507.2.1, 507.2.2 Subject: Type II Hood Clarification Effective Date: 12/21/2004 Prepared/Revision Date: 3/19/2009 CODE: 507.2.1 Type I hoods. Type I hoods shall be installed where appliances produce grease or smoke, such as occurs with griddles, fryers, broilers, ovens, ranges and wok ranges. 507.2.2 Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines. Exceptions: 1. 2. 3. 4. 5. Under-counter-type commercial dishwashing machines. A Type II hood is not required for dishwashers and potwashers that are provided with heat and water vapor exhaust systems that are supplied by the appliance manufacturer and are installed in accordance with the manufacturer's instructions. Light-duty electric convection, bread, retherm or microwave The additional heat and moisture loads generated by such appliances shall be accounted for in the design of the HVAC system. A Type II hood is not required for the following electrically heated appliances: toasters, steam tables, popcorn poppers, hot dog cookers, coffee makers, rice cookers, egg cookers, holding/warming ovens. The additional heat and moisture loads generated by such appliances shall be accounted for in the design of the HVAC system. Low-temperature [not greater than] 20°F (49°C)] commercial chemical-type dishwashers. 507.2.3 Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or Type II hoods as required for the type of appliances and processes in accordance with Sections 507.2, 507.2.] and 507.2.2. Exception: A maximum of two residential ranges (four burner) installed in dwelling units churches. schools, day care centers, break areas and similar installations INTERPRETATION: Definition: For purposes of clarification, the cooking equipment referenced in 507.2.1 would involve a “commercial cooking process” where by food is typically prepared and sold to customers. These processes would include culinary schools, public or private schools, hospitals, and large corporate kitchens and similar occupancies. The exception in 507.2.3 refers to cooking processes that are sporadic and not as intensive as those referred to in 507.2.1 and 507.2.2. These processes could utilize a type II hood due to the limited use and lesser grease accumulation. This would include apartment/condominium clubhouse, appliance sales center or similar. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement CODE INTERPRETATION Mechanical/Plumbing Code Volume Reference: NC Mechanical 2009 Code Chapter Reference: 602.2.1 Subject: Wood in a Plenum Effective Date: 1994 Prepared/Revision Date: March 2009 CODE: 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84. Exceptions: 1. Rigid and flexible ducts and connectors shall conform to Section 603. 2. Duct coverings, linings, tape and connectors shall conform to Sections 603 and 604. 3. This section shall not apply to materials exposed within plenums in dwellings. 4. This section shall not apply to smoke detectors. 5. Combustible materials enclosed in noncombustible raceways or enclosures, approved gypsum board assemblies or enclosed in materials listed and labeled for such application. INTERPRETATION: Wood products shall not be placed inside a plenum (treated or untreated). Only materials that are LISTED/ TESTED to meet the 25/50 flame/smoke rating will be allowed. Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator