Mechanical/Plumbing MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement

advertisement
MECKLENBURG COUNTY
Land Use and Environmental Services Agency
Code Enforcement
CODE
INTERPRETATION
Mechanical/Plumbing
Code Volume Reference: NC Mechanical Code (2006)
Code Chapter Reference: Chapter 506.3.6 & 105.2
Subject:
Grease Duct Clearance
Effective Date:
December 1995
Prepared/Revision Date:
December 2, 2008
CODE:
506.3.6 Grease duct clearances. Grease duct systems and exhaust equipment serving a Type I hood shall have a
clearance to combustible construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construction and gypsum wallboard attached to noncombustible structures of not less than 3 inches (76
mm).
Exception: Listed and labeled factory-built commercial kitchen grease ducts and exhaust equip ment
installed in accordance with Section 304.1.
105.2 Alternative materials, methods, equipment and appliances. The provisions of this code are not intended
to prevent the installation of any material or to prohibit any method of construction not specifically prescribed by
this code, provided that any such alternative has been approved. An alternative material or method of construction
shall be approved where the code official finds that the proposed design is satisfactory and complies with the intent
of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least
the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and
safety.
INTERPRETATION:
The use of Pyroscat, Firemaster or equal is approved as an alternative method per 105.2 provided that it is installed
per the manufacturer’s installation instructions and it is used to wrap the entire grease exhaust system from the
hood to the termination.
Approved by:
Philip B. Edwards, M/P Code Administrator