LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER NOTE: RENDERING ABOVE REPRESENTS MODULAR AND SITE BUILT COMPONENTS. SITE BUILT COMPONENTS ARE NOT PART OF THIS CONTRACT AND ARE SHOWN FOR REFERENCE ONLY TO GIVE BIDDING PARTIES AN IMAGE OF HOW THEIR CONSTRUCTION WILL BE INTEGRATED INTO THE OVERALL CONSTRUCTION. 2700 E LELAND ROAD, PITTSBURG, CA 94565 01.22.2016 MODULAR BID PACKAGE 2484 Natomas Park Drive Suite 100 Sacramento CA 95833 916 443 0335 lpasdesign.com Architecture + Design Project # 985-0007 10 9 8 ABBREVIATIONS C D E F 1/25/2016 11:35:51 AM CATCH BASIN CALIFORNIA BUILDING CODE CORNER GUARD CAST IRON CAST IN PLACE CONTROL JOINT CENTERLINE CASED OPENING CURTAIN WALL CABINET CEMENT CERAMIC CEILING CAULKING CLOSET CLEAR COUNTER COLUMN COMPOSITE CONCRETE CONNECTION CONSTRUCTION CONTINUOUS CORRIDOR CENTER COUNTERSUNK D.F. D.G. D.O. D.S. D.S.P. DBL. DEMO. DEPT. DET. DIA. DIM. DISP. DN. DR. DTL. DWG. DWR. DRINKING FOUNTAIN DECOMPOSED GRANITE DOOR OPENING DOWNSPOUT DRY STANDPIPE DOUBLE DEMOLISH DEPARTMENT DETAIL DIAMETER DIMENSION DISPENSER DOWN DOOR DETAIL DRAWING DRAWER E. E.J. E.O.S. E.P. E.W.C. EA. EL. ELEC. ELEV. EMER. ENCL. EQ. EQPT. EXP. EXPO. EXST. EXT. EAST EXPANSION JOINT EDGE OF SLAB ELEC. PANEL ELEC. WATER COOLER EACH ELEVATION ELECTRICAL ELEVATOR EMERGENCY ENCLOSURE EQUAL EQUIPMENT EXPANSION EXPOSED EXISTING EXTERIOR F.A. F.B. F.D. F.E. F.E.C. F.F. F.H.C. F.O.C. F.O.F. F.O.M. F.O.S. F.S. FDN. FIN. FL. FLASH. FLUOR. FPRF. FRMG. FT. FTG. FURR. FUT. FIRE ALARM FLAT BAR FLOOR DRAIN FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FINISH FLOOR FIRE HOSE CABINET FACE OF CONCRETE FACE OF FINISH FACE OF MASONRY FACE OF STUD FIRE SPRINKLER FOUNDATION FINISH FLOOR FLASHING FLUORESCENT FIREPROOF FRAMING FOOT or FEET FOOTING FURRING FUTURE G.B. G.S.M. GA. GALV. GL. GND. GR. GYP. GRAB BAR GALVANIZED SHEET METAL GAUGE GALVANIZED GLASS GROUND GRADE GYPSUM H.B. H.C. H.M. HDWD. HDWR. HORIZ. HR. HT. HOSE BIB HOLLOW CORE HOLLOW METAL HARDWOOD HARDWARE HORIZONTAL HOUR HEIGHT I.D. I.S.A. INSUL. INT. INSIDE DIAMETER INTERNATIONAL SYMBOL OF ACCESSIBILITY INSULATION INTERIOR JAN. JT. JANITOR JOINT K.D. KNOCK DOWN L.F. LAM. LAV. LKR. LT. LINEAL FOOT LAMINATE LAVATORY LOCKER LIGHT M.H. M.O. MANHOLE MASONRY OPENING 12 O.A. O.C. O.D. O.F.C.I. O.F.D. O.F.O.I. O.H. O.S.B. O/ OBS. OCC. OFC. OPNG. OPP. NEW CONTOUR POROUS FILL EXISTING CONTOUR PROPERTY LINE CAST STONE PROJECTED LINE CONCRETE BLOCK HIDDEN LINE BREAK LINE BRICK MATCH LINE METAL CONTRACT LIMIT LINE CONTINUOUS WOOD ELEVATION MARK OR DATUM POINT 12 SHIM OR NON-CONT. WOOD BLKING WALL TYPE FINISH WOOD REVISION MARK PLYWOOD P.T.D.F. PL. PLAS. PLYWD. PNTD. PR. PRCST. PROPERTY LINE PLASTIC LAMINATE PAPER TOWEL DISPENSER PAPER TOWEL DISPENSER/RECEPTACLE PRESSURE TREATED DOUGLAS FIR PLATE PLASTER PLYWOOD PAINTED PAIR PRECAST R.C. R.D. R.O. R.R. R.W.L. RAD. REC. RECL. REF. REFR. REINF. REQ. RESIL. RGTR. RISER RM. RWD. RESILIENT CHANNEL ROOF DRAIN ROUGH OPENING RESTROOM RAIN WATER LEADER RADIUS RECESSED RECYCLING REFERENCE REFRIGERATOR REINFORCED REQUIRED RESILIENT REGISTER RISER ROOM REDWOOD S. S.A.F. S.C. S.C.D. S.D. S.F. S.M.S. S.N.D. S.N.R. S.O.G. S.S. S.SK. SCHED. SECT. SEP. SHT. SHTG. SHWR. SIM. SPEC. SQ. ST. STD. STL. STOR. STRL. SUSP. SYM. GYPSUM WALLBOARD 12 D STONE GRID LINES RIGID INSULATION BATT INSULATION NORTH ARROW ACOUSTIC TILE OFFICE PLASTER ON METAL LATH ROOM NAME AND NUMBER 155 PAVING IS1 00 1 WALL TAG TILE 201 DOOR NUMBER GLASS T WINDOW TYPE EXPANSION MATERIAL 1 KEYNOTE A ATTN: JAMES MCCURDY ARCHITECTURAL A1.00M OVERALL SITE PLAN (FOR REFERENCE ONLY) A1.01M ENLARGED SITE PLAN - MODULAR A2.01M FLOOR PLAN - MODULAR A2.14M ROOF PLAN - MODULAR A2.31M FINISH PLAN - MODULAR A2.81M DOOR & WINDOW SCHEDULE / DETAILS A3.11M EXTERIOR ELEVATIONS - MODULAR A3.21M BUILDING SECTIONS - MODULAR A5.01M INTERIOR ELEVATIONS A6.01M REFLECTED CEILING PLAN - MODULAR A8.31M EXTERIOR WINDOW / DOOR DETAILS A9.00M EXTERIOR & INTERIOR WALL ASSEMBLIES A9.10M INTERIOR / EXTERIOR DETAILS A9.60M TYPICAL CEILING DETAILS ATTN: BEN AZARNOUSH CONSTRUCTION MANAGER CRITICAL SOLUTIONS, INC. 1801 OAKLAND BOULEVARD, SUITE 300 WALNUT CREEK, CA 94596 PHONE (925) 944-5060 MECHANICAL / ELECTRICAL / PLUMBING/ LOW VOLTAGE / FIRE ALARM CANYON CONSULTING ENGINEERS 3150 HILLTOP MALL ROAD, SUITE 18 RICHMOND, CA 94806 PHONE (510) 243-5987 ATTN: KELLY JOHNSON ATTN: GEORGE ARELLANO B ARCHITECTURE LPAS 2484 NATOMAS PARK DRIVE, SUITE 100 SACRAMENTO, CA 95833 PHONE (916) 443-0335 K1 SECTION IDENTIFICATION A3.3 MECHANICAL M0.01 LEGEND, SYMBOLS, AND GENERAL NOTES M2.01 MECHANICAL FLOOR PLAN M2.02 MECHANICAL REFRIGERANT PIPING PLAN M4.01 MECHANICAL DETAILS M4.02 MECHANICAL DETAILS L-4001 CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 STRUCTURAL MERIDIAN STRUCTURAL ENGINEERS, INC. 850 IRON POINT ROAD, SUITE 110 FOLSOM, CA 95630 PHONE (916) 365-4740 PLUMBING P0.01 PLUMBING LEGEND, SYMBOLS, GENERAL NOTES, AND SCHEDULES P2.01 PLUMBING FLOOR PLAN P2.02 PLUMBING ROOF PLAN LOS MEDANOS COLLEGE C ATTN: MICHAEL BAKER NO. ELECTRICAL E0.01 GENERAL INFORMATION ELECTRICAL E2.01 FLOOR PLAN - LIGHTING E3.01 FLOOR PLAN - POWER & SIGNAL E5.01 DETAILS E6.01 SCHEDULES ISSUE DATE D SEALANT W/ BACK-UP MATERIAL SECTION SHEET WHERE SECTION IS DRAWN FIRE ALARM F0.01 GENERAL INFORMATION FIRE ALARM F2.01 FLOOR PLAN - FIRE ALARM CARPET DETAIL F1 DETAIL IDENTIFICATION A3.4 SHEET WHERE DETAIL IS DRAWN K10 INTERIOR ELEVATION ELEVATION IDENTIFICATION K1 SOUTH SELF-ADHERED FLASHING SOLID CORE SEAT COVER DISPENSER SOAP DISPENSER SQUARE FOOT SHEET METAL SCREW SANITARY NAPKIN DISPENSER SANITARY NAPKIN RECEPTACLE SLAB ON GRADE STAINLESS STEEL SERVICE SINK SCHEDULE SECTION SEPARATE or SEPARATION SHEET SHEATHING SHOWER SIMILAR SPECIFICATION SQUARE STATION STANDARD STEEL STORAGE STRUCTURAL SUSPENDED SYMMETRICAL TONGUE AND GROOVE TEMPERED GLASS TOWEL BAR TOP OF CONCRETE TOP OF PARAPET TOP OF STEEL TOP OF WALL TOP OF PAVEMENT TOILET PAPER DISPENSER TELEPHONE TERRAZZO THICK TRANSITION TREAD TYPICAL U.O.N. UNF. UR. UTIL. UNLESS OTHERWISE NOTED UNFINISHED URINAL UTILITY V.I.F. VER. VERT. VEST. VERIFY IN FIELD VERIFY VERTICAL VESTIBULE W. W.C. W.O. W.P. W.V. W/ W/O WD. WSCT. WT. WEST WATER CLOSET WHERE OCCURS WATERPROOF WOOD VENEER WITH WITHOUT WOOD WAINSCOT WEIGHT A5.01 K7 SHEET WHERE ELEVATION IS DRAWN E K4 ALIGN FINISH SURFACES GENERAL NOTES 1. 2. 3. 4. T&G T. T.B. T.O.C. T.O.P. T.O.STL. T.O.W. T.P. T.P.D. TEL. TER. THK. TRANS. TRD. TYP. CIVIL BkF ENGINEERS 980 9TH STREET, SUITE 1770 SACRAMENTO, CA 95814 (916) 556-5800 ATTN: TROY PENNINGTON N P.L. P.LAM. P.T.D. P.T.D./R. OWNER CONTRA COSTA COMMUNITY COLLEGE DISTRICT 500 COURT STREET MARTINEZ, CA 94553 PHONE (925) 229-1000 CONCRETE CENTERLINE OVERALL ON CENTER OUTSIDE DIAMETER OWNER FURNISHED CONTRACTOR INSTALLED OVERFLOW DRAIN OWNER FURNISHED OWNER INSTALLED OPPOSITE HAND ORIENTED STRAND BOARD OVER OBSCURE OCCUPANTS OR OCCUPANCY OFFICE OPENING OPPOSITE PROJECT TEAM GENERAL A0.00 COVER SHEET A0.10M GENERAL INFORMATION A0.40M ACCESSIBILITY COMPLIANCE EARTH 1 FOR THE PURPOSES OF THIS PACKAGE, UNLESS OTHERWISE IDENTIFIED AS "SITE BUILT CONTRACTOR" OR SIMILAR IDENTIFICATION, THE WORD CONTRACTORS SHALL BE CONSIDERED TO REFER TO MODULAR BUILDING MANUFACTURER. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS ON SITE PRIOR TO STARTING CONSTRUCTION. SHOULD A DISCREPANCY APPEAR IN THE SPECIFICATIONS OR DRAWINGS, OR IN THE WORK DONE BY OTHERS FROM THE CONTRACT DOCUMENTS THAT AFFECT ANY WORK, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED. IF THE CONTRACTOR PROCEEDS WITH THE WORK AFFECTED WITHOUT INSTRUCTIONS FROM THE ARCHITECT, THE CONTRACTOR SHALL MAKE GOOD ANY RESULTING DAMAGE OR DEFECT TO THE SATISFACTION OF THE ARCHITECT. SHOULD A CONFLICT OCCUR IN OR BETWEEN DRAWINGS AND SPECIFICATIONS, OR WHERE DETAIL REFERENCES ON CONTRACT DRAWINGS HAVE BEEN OMITTED, THE CONTRACTOR IS DEEMED TO HAVE ESTIMATED THE MOST EXPENSIVE MATERIALS AND CONSTRUCTION METHOD INVOLVED, UNLESS A WRITTEN DECISION FROM THE ARCHITECT HAS BEEN OBTAINED WHICH DESCRIBES AN ALTERNATE METHOD AND/OR MATERIALS. F THE CONTRACTOR SHALL CONFINE HIS OPERATIONS ON THE SITE TO AREAS PERMITTED BY THE OWNER. THE WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE LAWS, LOCAL ORDINANCES, PERMITS AND THE CONTRACT DOCUMENTS. THE JOB SITE SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF DEBRIS AND LITTER, AND SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR EQUIPMENT. EACH SUB-CONTRACTOR IMMEDIATELY UPON COMPLETION OF EACH PHASE OF HIS/HER WORK SHALL REMOVE ALL TRASH AND DEBRIS AS A RESULT OF HIS OPERATION. FILE NO.7-C1 THE INTENT OF THE DESIGN IS THAT THE MODULAR BUILDINGS AND THE SITE BUILT COMPONENTS OF THE BUILDING ARE STRUCTURALLY INDEPENDANT. HOWEVER, SOME COORDINATION WILL BE REQUIRED FOR STRUCTURAL ELEMENTS THAT WILL PASS THROUGH MODULAR ELEMENTS, AS WELL AS WITH THE FOOTING AND FOUNDATION SYSTEM. THE MODULAR MANUFACTURER IS RESPONSIBLE TO COORDINATE WITH DESIGN TEAM'S STRUCTURAL ENGINEER TO ENSURE\ A FULLY COORDINATED STRUCTURAL SYSTEM. CONTRACTOR SHALL NOTIFY THE ARCHITECT WHERE A CONFLICT OCCURS ON ANY OF THE CONTRACT DOCUMENTS OR DRAWINGS. CONTRACTOR IS NOT TO ORDER MATERIAL OR CONSTRUCT ANY PORTION OF THE BUILDING THAT IS IN CONFLICT UNTIL CONFLICT IS RESOLVED WITH THE AFFECTED PARTIES. 6. ALL LEGAL EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT. EXIT SIGNS SHALL BE PROVIDED AT ALL EXITS AS REQUIRED BY CODE. ALL DOOR SWINGS SERVING AN OCCUPANT LOAD OF 50 OR GREATER SHALL SWING IN THE DIRECTION OF EXIT. 7. PROVIDE ILLUMINATED EXIT SIGNS PER THE REQUIREMENTS OF 2013 C.B.C., SECTION 1011. 8. PROVIDE FIRE EXTINGUISHERS PER THE REQUIREMENTS OF THE STATE FIRE MARSHAL. 9. CONSTRUCTION SHALL COMPLY WITH THE AIR LEAKAGE REQUIREMENTS OF THE CALIFORNIA ADMINISTRATIVE CODE, TITLE 24, PART 2 CHAPTER 2-53 FOR WINDOWS, DOORS, CAULKING AND SEALING, ELEVATOR SHAFT VENTS AND ALL OTHER APPLICABLE REQUIREMENTS. 10. DIMENSIONSING RULES: A. NOTED DIMENSIONS SHALL AT ALL TIMES TAKE PRECEDENCE OVER SCALED DIMENSIONS. B. ALL DIMENSIONS OF NEW WORK ARE TO THE FACE OF STUD U.O.N. C. ALL DIMENSIONS OF EXISTING WORK ARE TO FACE OF FINISH U.O.N. D. CEILING HEIGHT DIMENSIONS ARE FROM TOP OF FLOOR SLAB TO FINISH FACE OF CEILING. E. DIMENSIONS NOTED "CLEAR" OR "CLR" MUST BE PRECISELY MAINTAINED. F. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT APPROVAL OF THE ARCHITECT. G. +/- VERTICAL DIMENSION ARE FROM THE TOP OF THE FLOOR SLAB DATUM LINE, ESTABLISHED BY THE CONTRACTOR SUBJECT TO THE APPROVAL OF THE OWNER OR ARCHITECT, UNLESS OTHERWISE NOTED. H. DIMENSIONS MARKED "A.F.F." ARE ABOVE FINISHED FLOOR MATERIALS. IN CARPETED AREAS, THE TOP OF SLAB IS CONSIDERED TO BE THE FINISH FLOOR. I. DIMENSIONS MARKED "V.I.F." SHALL BE "VERIFIED" IN THE FIELD BY THE CONTRACTOR. J. ALL DIMENSIONS ARE TO STRUCTURAL COMPONENTS UNLESS OTHERWISE NOTED. K. DIMENSION LOCATING DOORS ARE TO THE INSIDE EDGE OF JAMB, U.O.N. A R CH IT C-31285 XX-XXXXXX 5-31-17 G E RENEWAL DATE O F C A LI F O R APPLICABLE CODES 2013 2013 2013 2013 2013 2013 2013 2013 2013 1. COORDINATION OF MODULAR BUILDING CONSTRUCTION DOCUMENTS WITH SITE-BUILT CONSTRUCTION. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR COORDINATION WITH ARCHITECT AND ARCHITECT'S CONSULTANTS FOR INTERFACE OF ALL BUILDING SYSTEMS, INCLUDING BUT NOT LIMITED TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, FIRE ALARM, WEATHERPROOFING, ETC. ALL UTILITY CONNECTIONS, UNLESS OTHERWISE NOTED ARE TO BE STUBBED 5' OUTSIDE THE BUILDING LINE BY MODULAR MANUFACTURER, INCLUDING BUT NOT LIMITED TO DOMESTIC WATER, ELECTRICAL, STORM SEWER, SANITARY SEWER. PROVIDE CONCRETE CHRISTY BOX. 2. MODULAR BUILDING AS DESIGNED CONTAINS COMPONENTS THAT ARE NOT STANDARD MODULAR BUILDING COMPONENTS, INCLUDING BUT NOT LIMITED TO VRF (VARIABLE REFRIGERANT FLOW) MECHANICAL SYSTEM, WINDOW SIZES, STUCCO TRIMS, ETC. THESE ITEMS MAY NOT BE ALTERED WITHOUT THE EXPRESS WRITTEN CONSENT OF THE ARCHITECT. PARTIAL LIST OF APPLICABLE STANDARDS NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE (CALIFORNIA AMENDED) NFPA 253 - CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS 3. CONSTRUCTION DOCUMENTS FOR MODULAR BUILDINGS, APPROVAL THROUGH DIVISION OF STATE ARCHITECT. 4. DESIGN AND CONSTRUCTION OF FOOTING AND FOUNDATION SYSTEM FOR MODULAR BUILDING SYSTEM, INCLUDING BUT NOT LIMITED TO EXCAVATION FOR AND INSTALLATION OF CONCRETE FOOTINGS AND FOUNDATION SYSTEMS FOR MODULAR BUILDING, DRAINAGE, INSTALLATION OF RAT SLAB AND CRAWL SPACE DRAINAGE. FOOTING AND FOUNDATION SYSTEM DESIGN SHALL INCLUDE COORDINATION WITH FOOTINGS, FOUNDATIONS, SLABS REQUIRED FOR SITE BUILT CONSTRUCTION. 5. CONSTRUCTION, DELIVERY AND INSTALLATION OF MODULAR BUILDING SYSTEM. 6. COORDINATION OF INSTALLATION AND BUILDING SYSTEM INTERFACES WITH SITE BUILT CONSTRUCTION TEAM. CONSULTANT J GENERAL INFORMATION PROJECT NO: 985-0007 BID ALTERNATES DATE: 01.22.2016 1. OPTIONAL BID ALTERNATE: SLAB-ON-GRADE CONSTRUCTION IN LIEU OF PIT-SET (IF OFFERED BY MANUFACTURER). 2. SINGLE SLOPE ROOF IN LIEU OF GABLE. 3. BULLET RESISTANT WALL LINING. SHEET NO: A0.10M 8 7 6 5 4 3 2 APPROVAL H K 9 SS THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. CALIFORNIA BUILDING CODE (CBC) CALIFORNIA ELECTRICAL CODE (CEC) CALIFORNIA MECHANICAL CODE (CMC) CALIFORNIA PLUMBING CODE (CPC) CALIFORNIA ENERGY CODE CALIFORNIA FIRE CODE (CFC) CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN) NONE. FLS THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. SCOPE OF WORK DEFERRED APPROVALS 10 AC DATE ARCHITECT'S STAMP PROJECT LOCATION 11 IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON 5. VICINITY MAP E ED NS T K C.B. C.B.C. C.G. C.I. C.I.P. C.J. C.L. C.O. C.W. CAB. CEM. CER. CLG. CLKG. CLO. CLR. CNTR. COL. COMP. CONC. CONN. CONSTR. CONT. CORR. CTR. CTSK. NORTH NOT IN CONTRACT NON RATED NOT TO SCALE NUMBER NOMINAL SHEET INDEX 2 EC J BOARD BITUMINOUS BUILDING BLOCK BLOCKING BEAM BOTTOM N. N.I.C. N.R. N.T.S. NO. NOM. FLOW LINE 3 AT H BD. BITUM. BLDG. BLK. BLKG. BM. BOTT. MAXIMUM MECHANICAL MEDIUM MEMBRANE MANUFACTURER MINIMUM MIRROR MISCELLANEOUS MOUNTED METAL MULLION 4 ST G ASPHALT CONCRETE ALUMINUM COMPOSITE PANEL AREA DRAIN ABOVE FINISH FLOOR ASSISTED LISTENING SYSTEM ACOUSTICAL ADJUSTABLE or ADJACENT AGGREGATE ALUMINUM APPROXIMATELY ARCHITECTURAL ASBESTOS ASPHALT MAX. MECH. MED. MEMB. MFR. MIN. MIR. MISC. MTD. MTL. MUL. SYMBOLS 5 A B A.C. A.C.P. A.D. A.F.F. A.L.S. ACOUS. ADJ. AGGR. ALUM. APPROX. ARCH. ASB. ASPH. POUND OR NUMBER AND EXISTING NEW AT ANGLE DIAMETER or ROUND 6 NI A # & (E) (N) @ L Ø 7 C 11 LI 12 1 MODULAR BID PACKAGE 10 9 8 7 6 5 4 3 1 SIGNS AND SYMBOLS DOORS SANITARY FACILITIES A. ALL SIGNAGE SHALL COMPLY WITH CBC SECTION 11B-703. A. LATCHES AND LOCKSETS: PROVIDE LEVER TYPE, PUSH- PULL OR PANIC TYPE HARDWARE 30 INCHES TO 44 INCHES ABOVE FLOOR. OPERATING DEVICE SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST TO OPERATE. A. REFER TO SHEET K7/A0.40M FOR ROOM ID SIGNAGE AND RESTROOM IDENTIFICATION SYMBOL: B. OPENING FORCE: MAXIMUM FORCE TO OPERATE DOORS SHALL BE 5 LBS. PRESSURE. FIRE DOORS SHALL BE MAX. 15 LBS. A C. THRESHOLDS: THE FLOOR OR LANDING SHALL NOT BE MORE THAN 1/2 INCH LOWER THAN THE THRESHOLD OF THE DOOR WAY. CHANGE IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. (SEE "DOOR THRESHOLD" BELOW). CHARACTERS ON SIGNS SHALL BE RAISED 32 " (0.794mm) MIN. AND SHALL BE SANS SERIF UPPERCASE CHARACTERS ACCOMPANIED BY CONTRACTED GRADE 2 BRAILLE. (SEE SECTION BELOW) b. CHARACTER SIZE: RAISED CHARACTERS SHALL BE A MIN. OF 5/8" (15.9mm) AND A MAX. OF 2" (51mm) HIGH. c. PICTORIAL SYMBOL SIGNS (PICTOGRAMS): PICTORIAL SYMBOL SIGNS (PICTOGRAMS) SHALL BE ACCOMPANIED BY THE VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE PICTOGRAM. THE OUTSIDE DIMENSION OF THE PICTOGRAM FIELD SHALL BE A MIN. OF 6" (152mm) IN HEIGHT. d. E. MANEUVERING CLEARANCES: MINIMUM MANEUVERING CLEARANCES AT DOORS SHALL BE AS SHOWN IN DOOR PLAN FIGURES BELOW. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE LEVEL AND CLEAR. F. PASSAGE DOOR SIZE: MINIMUM NOMINAL DOOR DIMENSIONS ARE 3 FEET WIDE (4 FEET WIDE MAX) AND 6 FEET 8 INCHES HIGH. CLEAR WIDTH REQUIRED IS 32 INCHES MINIMUM WITH DOOR OPEN 90 DEGREES, MEASURED FROM THE FACE OF THE DOOR TO THE OPPOSITE STOP. G. SMOOTH SURFACE: THE BOTTOM 10 INCHES OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. CHARACTER PLACEMENT: CHARACTERS AND BRAILLE SHALL BE IN HORIZONTAL FORMAT. BRAILLE SHALL BE PLACED A MIN. OF 3/8 " & A MAX. OF 1/2 " DIRECTLY BELOW THE TACTILE CHARACTERS; FLUSH LEFT OR CENTERED. WHEN TACTILE TEXT IS MULTI-LINED, ALL BRAILLE SHALL BE PLACED TOGETHER BELOW ALL LINES OF TACTILE TEXT. B MOUNTING LOCATION & HEIGHT: WHERE PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL, PREFERABLY ON THE RIGHT. MOUNTING HEIGHT SHALL BE 60" (1524mm) ABOVE THE FINISH FLOOR TO THE CENTERLINE OF THE SIGN. MOUNTING LOCATION SHALL BE DETERMINED SO THAT A PERSON MAY APPROACH WITHIN 3" (76mm) OF SIGNAGE WITHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHIN THE SWING OF A DOOR. 2 1 TACTILE & BRAILLE SIGN REQUIREMENTS F. ACCESSORIES: WHERE TOWEL DISPENSERS, SANITARY NAPKIN DISPENSERS, WASTE RECEPTACLES, SEAT COVER DISPENSERS OR OTHER EQUIPMENT AND CONTROLS ARE PROVIDED, AT LEAST ONE OF EACH TYPE SHALL BE LOCATED ON AN ACCESSIBLE ROUTE. FLUSH ACTIVATOR ON WIDE SIDE DOOR THRESHOLD BRAILLE: CONTRACTED GRADE 2 BRAILLE SHALL BE USED WHEREVER BRAILLE IS REQUIRED IN OTHER PORTIONS OF THESE STANDARDS. DOTS SHALL BE 1/10" ON CENTERS IN EACH CELL WITH 2/10" SPACE BETWEEN CELLS, MEASURED FROM THE SECOND COLUMN OF DOTS IN THE FIRST CELL TO THE FIRST COLUMN OF DOTS IN THE SECOND CELL. DOTS SHALL BE RAISED A MIN. OF 1/40" ABOVE THE BACKGROUND. BRAILLE DOTS SHALL BE DOMED OR ROUNDED. PULL SIDE A. RESTROOM IDENTIFICATION SYMBOL: 1. DOORWAYS LEADING TO MEN'S SANITARY FACILITIES SHALL BE IDENTIFIED BY AN EQUILATERAL TRIANGLE, 1/4 INCH THICK WITH EDGES 12 INCHES LONG AND THE VERTEX POINTING UPWARD. 2. DOORWAYS LEADING TO WOMEN'S SANITARY FACILITIES SHALL BE IDENTIFIED BY A CIRCLE 1/4 INCH THICK AND 12 INCHES IN DIAMETER. 3. UNISEX SANITARY FACILITIES SHALL BE IDENTIFIED BY A CIRCLE 1/4 INCH THICK AND 12 INCHES IN DIAMETER WITH A 1/4" THICK TRIANGLE SUPERIMPOSED ON THE CIRCLE AND WITHIN THE 12 INCH DIAMETER. THE TRIANGLE SYMBOL SHALL CONTRAST WITH THE CIRCLE BACKGROUND AND THE CIRCLE SHALL CONTRAST WITH THE DOOR. 36" MIN. PUSH SIDE B. GEOMETRIC (CIRCLE AND TRIANGLE) SYMBOLS ON SANITARY FACILITY DOORS SHALL BE CENTERED ON THE DOOR AT A HEIGHT OF 60" AND THEIR COLOR AND CONTRAST SHALL BE DISTINCTLY DIFFERENT FROM THE COLOR AND CONTRAST OF THE DOOR. NO TEXT OR I.S.A. IS REQUIRED. LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER 18" MIN. 2700 E LELAND ROAD, PITTSBURG, CA 94565 30" X 48" CLEAR FLOOR SPACE FOR LAVATORY (DOOR SWING MAY NOT OVERLAP) C 60" MIN. DIA. CLR. DOOR MAY SWING OVER HATCHED PORTION OF MANEUVERING SPACE 54" MIN. 48" MIN. * 24" MIN. 17" MIN. TO 18" MAX. 60" X 56" CLEAR FLOOR SPACE FOR TOILET (DOOR SWING MAY NOT OVERLAP) PULL SIDE 60" MIN. SANITARY FACILITIES B 60" MIN. CLR. 48" MIN. * 1. E. GRAB BARS: THE DIAMETER OR WIDTH OF GRIPPING SURFACES OF A GRAB BAR SHALL BE 1 1/4" TO 1 1/2" OR THE SHAPE SHALL PROVIDE AN EQUIVALENT GRIPPING SURFACE. IF GRAB BARS ARE MOUNTED ADJACENT TO A WALL, THE CLEARANCE BETWEEN THE GRAB BAR AND WALL SHALL BE 1 1/2". MINIMUM STRUCTURAL STRENGTH OF GRAB BARS WILL SUPPORT A 250 LB POINT LOAD. GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS. 1/4" MAX. VERTICAL 4. D. LAVATORY CONTROLS: FAUCET CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE CONTROLS TO BE NO MORE THAN 5 LBF. NO. 12" OV MAX. ERL AP ISSUE DATE CLR. a. D. FLOOR LEVEL: THERE SHALL BE A LEVEL AND CLEAR AREA ON EACH SIDE OF AN EXIT DOOR. THE LEVEL AREA SHALL BE AS SHOWN IN DOOR PLAN FIGURES BELOW. 17" MIN. RAISED CHARACTERS & PICTORIAL SYMBOL SIGNS: WHEN RAISED CHARACTERS ARE REQUIRED OR WHEN PICTORIAL SYMBOLS ARE USED ON SIGNS, THEY SHALL CONFORM TO THE FOLLOWING a. THRU d. A C. WATER CLOSET & URINAL CONTROLS: FLUSH CONTROLS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. FLUSH CONTROLS TO BE MOUNTED NO MORE THAN 44 INCHES ABOVE THE FLOOR. WATER CLOSET CONTROLS TO BE MOUNTED ON THE WIDE SIDE OF TOILET COMPARTMENT. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO MORE THAN 5 LBF. 60" MIN. 3. PROPORTIONS: CHARACTERS ON SIGNS SHALL HAVE A WIDTH-TO-HEIGHT RATIO OF BETWEEN 3:5 & 1:1 AND A STROKE WIDTH TO HEIGHT RATIO OF BETWEEN 1:5 & 1:10. 1/2" MAX. AT 1:2 SLOPE 2. B. ACCESSIBLE WATER CLOSET COMPARTMENT DOORS SHALL BE EQUIPPED WITH AN AUTOMATIC-CLOSING DEVICE. THE INSIDE AND OUTSIDE OF THE COMPARTMENT DOOR SHALL BE EQUIPPED WITH A LOOP OR U-SHAPED HANDLE IMMEDIATELY BELOW THE LATCH. THE LATCH SHALL BE FLIP-OVER STYLE, SLIDING, OR OTHER HARDWARE NOT REQUIRING THE USER TO GRASP OR TWIST, AND THE MAXIMUM PRESSURE TO OPERATE THE DOOR SHALL NOT EXCEED 5 LBF. 32" MIN. FINISH & CONTRAST: CHARACTERS, SYMBOLS & THEIR BACKGROUND SHALL HAVE A NON-GLARE FINISH. CHARACTERS & SYMBOLS SHALL CONTRAST A MIN. OF 70% WITH THEIR BACKGROUND, EITHER LIGHT ON DARK BACKGROUND OR DARK ON LIGHT BACKGROUND. 56" MIN. 1. C 2 MIN. 11 48" 12 SINGLE-ACCOMMODATION TOILET FACILITY PUSH SIDE * THIS DIMENSION MAY BE REDUCED TO 44" IF DOOR DOES NOT HAVE A CLOSER * THIS DIMENSION MAY BE REDUCED TO 44" IF DOOR DOES NOT HAVE BOTH A LATCH AND A CLOSER D D LATCH APPROACH HINGE APPROACH SEAT COVER DISPENSER 54" MIN. PULL SIDE 24" MIN. 12" MIN. 24" MIN. 48" MIN. 12" * MIN. E * THIS CLEARANCE IS NOT REQUIRED IF DOOR DOES NOT HAVE BOTH A LATCH AND A CLOSER 33" 36" MIN. GRAB BAR (42" PREFERRED) 16" TO 18" FLUSH ACTIVATOR ON WIDE SIDE PUSH SIDE 7" TO 9" C.L. 33" * C.L. 12" MAX. T.O.S. 24" MIN. CLR. AT EXTERIOR DOORS 18" MIN. CLR. AT INTERIOR DOORS 17" - 19" 60" MIN. C.L. 42" MIN. GRAB BAR (48" PREFERRED) E TOILET PAPER DISPENSER * REAR GRAB BAR ALLOWED AT 36" A.F.F. AT TANK-TYPE TOILET FRONT APPROACH TOILET REAR WALL ELEVATION FEMININE NAPKIN DISPENSER SOAP DISPENSER 29" MIN. BOTH DOORS OPEN OUT F MIN. DOORS IN A SERIES 40" MAX. TO HIGHEST OPERABLE PART MIN. TRASH RECEPTACLE BOTTOM OF REFLECTIVE SURFACE 34" MAX. 18" MIN. 12" * HAND DRYER MIRROR 9" F MIN. PAPER TOWEL DISPENSER 27" MIN. MIN. 12" * * THIS CLEARANCE IS NOT REQUIRED IF DOOR DOES NOT HAVE BOTH A LATCH AND A CLOSER 48" MIN. 48" MIN. 12" * * THIS CLEARANCE IS NOT REQUIRED IF DOOR DOES NOT HAVE BOTH A LATCH AND A CLOSER TOILET SIDE WALL ELEVATION INSULATE EXPOSED HOT WATER LINE AND DRAIN PIPES PER ASTM E-84 FILE NO.7-C1 IT T LI E A R CH EC C LAVATORY AND TOILET ROOM ACCESSORIES ED NS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 PROTRUDING OBJECTS TACTILE & BRAILLE ROOM ID SIGNAGE B. HEAD ROOM: 80 INCHES MINIMUM. IF VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE ROUTE IS REDUCED TO LESS THAN 80", A BARRIER TO WARN BLIND OR VISUALLY IMPAIRED PERSONS SHALL BE PROVIDED. TO BASELINE OF HIGHEST LINE OF TEXT ANY AMOUNT 4" MAX. K 10 9 80" MIN. A NI SS APPROVAL THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 10" 10" MAX. MAX. 24" MAX. 20" MAX. >20" TO 25" MAX. OBSTRUCTED SIDE REACH 2. EDGES OF SYMBOL SHALL BE ROUNDED, CHAMFERED, OR EASED. CORNERS SHALL HAVE A MINIMUM RADIUS OF 1/8". 3. SIGNAGE TO BE 1/4" THICK ACRYLIC (OR APPROVED MATERIAL.) 4. SYMBOLS SHALL HAVE A NONGLARE FINISH. 5. LETTERING, I.S.A., AND GENDER SYMBOLS ARE NOT REQUIRED ON THE GEOMETRIC SYMBOL, BUT WHEN PROVIDED THEY SHALL CONTRAST WITH THEIR BACKGROUND; EITHER LIGHT ON A DARK BACKGROUND OR DARK ON A LIGHT BACKGROUND. D. FIRE ALARM INITIATING DEVICES SHALL BE A MINIMUM OF 42 INCHES AND A MAXIMUM OF 48 INCHES ABOVE THE FLOOR OR SIDEWALK TO THE HIGHEST POINT OF THE ACTIVATING HANDLE OR LEVER OF THE BOX. CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL NOT EXCEED 5 POUNDS OF FORCE. 15" C. ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPERES OR LESS AND COMMUNICATION SYSTEM RECEPTACLES SHALL BE LOCATED NOT LESS THAN 15 INCHES ABOVE THE FINISH FLOOR (MEASURED TO THE BOTTOM OF THE OUTLET BOX OR HOUSING) AND NOT MORE THAN 48 INCHES ABOVE THE FINISH FLOOR (MEASURED TO THE TOP OF THE OUTLET BOX OR HOUSING.) MIN. 48" MAX. B. SWITCHES AND CONTROLS INTENDED TO BE USED BY THE OCCUPANT OF THE ROOM OR AREA TO CONTROL LIGHTING AND RECEPTACLE OUTLETS, APPLIANCES OR COOLING, HEATING AND VENTILATING EQUIPMENT, SHALL BE LOCATED NOT LESS THAN 15 INCHES ABOVE THE FINISH FLOOR (MEASURED TO THE BOTTOM OF THE OUTLET BOX) AND NOT MORE THAN 48 INCHES ABOVE THE FINISH FLOOR (MEASURED TO THE TOP OF THE OUTLET BOX.) UNOBSTRUCTED FORWARD REACH 48" MAX. >10" TO 48" MAX. A. A CLEAR FLOOR SPACE THAT ALLOWS A FORWARD OR PARALLEL APPROACH BY A PERSON USING A WHEELCHAIR SHALL BE PROVIDED AT CONTROLS, RECEPTACLES, AND OTHER OPERABLE EQUIPMENT. DOORWAYS LEADING TO SANITARY FACILITIES SHALL BE IDENTIFIED BY A GEOMETRIC SYMBOL IN A COLOR THAT CONTRASTS TO THE DOOR ON WHICH IT IS HUNG, EITHER A LIGHT COLOR ON A DARK DOOR OR A DARK COLOR ON A LIGHT DOOR. THE GEOMETRIC SYMBOL SHALL BE CENTERED HORIZONTALLY ON THE DOOR AT A HEIGHT OF 60" ABOVE THE FINISH FLOOR MEASURED TO THE CENTER OF THE SYMBOL. 34" MAX. 48" MAX. 34" MAX. 48" MAX. WALKING PERPENDICULAR TO A WALL ELECTRICAL SWITCHES AND OUTLETS UNISEX 8 FLS THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. 27" MAX. WALKING PARALLEL TO A WALL 15" 60" A.F.F. J 7 ACCESSIBILITY COMPLIANCE PROJECT NO: 985-0007 OBSTRUCTED FORWARD REACH DATE: 01.22.2016 K 1" = 1'-0" 11 H7 UNOBSTRUCTED SIDE REACH RESTROOM DOOR SYMBOL 12 AC DATE 44" MAX. WHERE OCCURS 6" MIN. 12" 1/25/2016 11:35:53 AM 1. WOMEN R CONSULTANT 12" 12" MEN A. OBJECTS PROJECTING FROM WALLS WITH LEADING EDGE BETWEEN 27 INCHES AND 80 INCHES ABOVE THE FINISHED FLOOR MAY PROJECT 4 INCHES MAXIMUM. LEADING EDGE AT OR BELOW 27 INCHES MAY PROJECT ANY AMOUNT. MIN. 1/4" = 1'-0" 12" O F C A LI F O H WHEN 27" OR BELOW ROOM ID SIGNAGE LOCATION J RENEWAL DATE B. HEAD ROOM: 80 INCHES MINIMUM. IF VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE ROUTE IS REDUCED TO LESS THAN 80", A BARRIER TO WARN BLIND OR VISUALLY IMPAIRED PERSONS SHALL BE PROVIDED. H 12" E ARCHITECT'S STAMP REACH RANGE FREE STANDING OBJECTS MOUNTED ON POSTS OR PYLONS WITH LEADING EDGE BETWEEN 27 INCHES & 80 INCHES ABOVE FLOOR MAY PROJECT 12 INCHES MAX. WIDTH OF AN PROJECTIONS MAY NOT REDUCE MANEUVERING SPACE, OR CLEAR WIDTH OF AN ACCESSIBLE ROUTE. LOBBY WHEN HIGHER THAN 27" 60" A.F.F. TO BASELINE OF LOWEST BRAILLE 48" MIN 9" PERMANENT ROOM ID FREE STANDING OBJECTS MOUNTED ON POSTS OR PYLONS WITH LEADING EDGE BETWEEN 27 INCHES & 80 INCHES ABOVE FLOOR MAY PROJECT 12 INCHES MAX. WIDTH OF AN PROJECTIONS MAY NOT REDUCE MANEUVERING SPACE, OR CLEAR WIDTH OF AN ACCESSIBLE ROUTE. G AT G XX-XXXXXX 5-31-17 A. OBJECTS PROJECTING FROM WALLS WITH LEADING EDGE BETWEEN 27 INCHES AND 80 INCHES ABOVE THE FINISHED FLOOR MAY PROJECT 4 INCHES MAXIMUM. LEADING EDGE AT OR BELOW 27 INCHES MAY PROJECT ANY AMOUNT. ST DOOR SIDELITE WHERE OCCURS SHEET NO: A0.40M K7 6 5 4 3 2 1 MODULAR BID PACKAGE 11 10 9 8 7 6 5 4 3 2 1 E 61 6940 0 12 E 61 6960 0 E 61 6950 0 BIKE LANE N 21 9200 0 A A E 61 6980 0 E 61 6970 0 N 21 9190 0 BIKE LANE E 61 BIKE 7000 0 LANE E 61 6990 0 N 21 9180 0 LE LA ND R D. Rip rap EA ST E 61 3001 64.0 8 2 7020 0 E 61 7010 0 N 21 9170 0 1-2 Pile Pile 7030 0 YIELD Pile N 21 9160 0 BIKE E 61 Pile B LANE BIKE LANE B STOP E 61 7040 0 SLOW 3001 66.2 5 1 E 61 7050 0 PED (E) PROP LINE XING LANE BIKE Rip rap E 61 7060 0 BIKE EAST LELAN D ROA D STOP LANE N 21 9150 0 LOS MEDANOS COLLEGE STOP 2700 E LELAND ROAD, PITTSBURG, CA 94565 (E) PARKING LOT A PED Rip rap C RD . BIKE LANE BIKE EA ST LE LE AN D LANE E 61 7070 0 L-4001 CAMPUS SAFETY CENTER (E) PARKING LOT 1A C XING ONLY BUS LANE DRI VE (A.C . PA VIN G) LA KE STOP TEL (E) D ROP OFF PROJECT SITE (E) D ROP OFF STOP AHEAD AHEAD GV SIGNAL SIGNAL (E) TENNIS COURTS (E) STAFF LOT D M IW OK W AY Rip-ra p LANE SC STOP BIKE p ra Rip s Stair L CS Ro cks STOP CSC PIV PS DATE 1-3 G Stair s D ISSUE (E) PARKING LOT 2A STOP GA Elec 2-1 NO. (E) FIRE LANE (A.C. PAVING) ME DA NO S STOP LO S STOP STOP (E) LMC LAKE KEEP EA ST LE LA ND KEEP RD . G CLEAR (E) BASEBALL DIAMOND Stairs GYM Stairs 4" CC Po ol 3" 4" 3" MU E Stairs AD Concrete Conduit for Elevator Utilities AD AD AD 4" 3" 4" 4" 4" 2-2 DR . ED AN OS 3002 75.7 0 0 M AD AD STOP LO S PIV ST OP STOP Rip rap FDC (E) FIRE LANE (A.C. PAVING) LR STOP y 3001 74.7 4 9 CLEAR Pipe wa E 1-4 LR STOP G GV (Abandoned) SDCO Elec Ped. (E) PRACTICE FIELD RWL MA SDCO? EL DR IVE (E) PARKING LOT C y (E) SOFTBALL DIAMOND F PG&E 21kV 5kV 5kV (E) STAFF LOT PG&E 21kV SL Bo F LO SM ED AN OS Pipe wa PE x (E) PROP LINE AY EW EG LL CO N 21 9180 0 FILE NO.7-C1 85 85 9170 0 IT 2-3 T LI E A R CH EC C 86 N 21 ED NS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 86 XX-XXXXXX 87 E RENEWAL DATE NI 9160 0 AT G N 21 86 ST (E) PARKING LOT B G A 5-31-17 O F C A LI F O R AC DATE FLS SS 87 87 (E) FOOTBALL STADIUM / TRACK TC FL 88.3 87 .9 88 ARCHITECT'S STAMP 88 N 21 APPROVAL 9150 0 DR . .8 87 TC 87.3 FL LO SM ED AN OS THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. 89 88 .9 88 TC 88 .5 FL 89 LO SM ED AN OS N 21 DR . 9140 0 THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 90 89 90 90 COLL EGE WAY 89 89 89 6"∅Subdrain 6"∅Subdrain 6"∅Subdrain 89 89 89 90 N 21 9130 0 H E 61 6840 0 H 90 y 91 Pipe wa 91 91 CONSULTANT 91 92 E 61 6850 0 STOP 91 E 61 6860 0 91 N 21 9120 0 92 92 93 3001 90.8 7 7 E 61 6870 0 92 91 91 92 93 (E) PARKING LOT B 93 E 61 6880 0 93 N 21 93 .8 TC 9110 0 E 61 6890 0 94 94 94 95 .2 95 T C E 61 6900 0 95 96 95 S DANO LOS ME 97 96 95.5 TC 95 94.8 TC IVE S DR O N A MED LOS 94 .7 TC 94 DR . N 21 9100 0 95.9 TC J E 61 6910 0 J 96.4 TC 96.7 TC E 61 6920 0 96.8 TC 9090 0 E 61 6940 0 E 61 6930 0 N 21 OVERALL SITE PLAN (FOR REFERENCE ONLY) PROJECT NO: 985-0007 9080 0 E 61 6950 0 N 21 DATE: 01.22.2016 ol Pile Pile s s E 61 6960 0 Po Pile s 3000 113. 5 89 1/25/2016 11:35:58 AM E 61 6970 0 N 21 Po 9070 0 ol Pile Pile K s s 0 50 100 N 150 FT SCALE: 1" = 100'-0" OVERALL SITE PLAN 1" = 100'-0" 12 11 10 9 8 7 6 5 4 3 2 1 K1 K SHEET NO: A1.00M MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 GENERAL NOTES 1. SEE SHEET A0.10M FOR CODE COMPLIANCE INFORMATION. 2. SEE SHEET A0.40M FOR ACCESS COMPLIANCE INFORMATION. 3. SOME SITE ELEMENTS ARE SHOWN FOR REFERENCE PURPOSES ONLY. UNLESS OTHERWISE NOTED, SITEWORK IS OUTSIDE THE SCOPE OF THIS DOCUMENT. A STOP (E) LANDSCAPE AREA (E) CROSSWALK B I (E) I A.C . DR IVE 4. SEE CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON PAVING. 5. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR SITE EXCAVATION REQUIRED TO SET MODULAR BUILDING COMPONENTS. COORDINATE REQUIREMENTS WITH SITE BUILT CONSTRUCTION REQUIREMENTS. COORDINATE FINISH FLOOR ELEVATION AND CRAWL SPACE DEPTH WITH DESIGN TEAM. 6. MODULAR BUILDING MANUFACTURER SHALL PROVIDE PERIMETER FOUNDATION VENTS, AS REQUIRED. PROVIDE NON-REMOVABLE STEEL GRATE COVERS. MODULAR BUILDING MANUFACTURER SHALL PROVIDE CRAWL SPACE ACCESS AND WELL. PROVIDE LOCKABLE COVER. COORDINATE LOCATION WITH SITE BUILT CONSTRUCTION. 7. FENCES, GATES, ETC. ARE OUTSIDE THE SCOPE OF THE MODULAR BUILDING CONTRACT AND ARE SHOWN FOR REFERENCE PURPOSES ONLY. 8. STUB ALL UTILITIES, INCLUDING BUT NOT LIMITED TO DOMESTIC WATER, SANITARY SEWER, STORMWATER, ELECTRICAL, ETC. 5'-0" MINIMUM FROM BUILDING FACE. COORDINATE POINTS OF CONNECTION WITH SITE BUILT CONTRACTOR. PROVIDE POINTS OF CONNECTION IN CONCRETE CHRISTY BOX OF ADEQUATE SIZE TO ACCOMODATE CONNECTIONS, SHUTOFFS, ETC. SEE MECHANICAL, ELECTRICAL, PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. A B LOS MEDANOS COLLEGE (E) CONC WALK (E) LANDSCAPE AREA (E) BOLLARD, TYP OF (3) IV I (E) C ONC WA I LEGEND: L-4001 CAMPUS SAFETY CENTER MODULAR BUILDING UNDER THIS SCOPE IV 2700 E LELAND ROAD, PITTSBURG, CA 94565 (E) CURB CUT BUILDING NOT IN MODULAR SCOPE LK ROCK LINED SWALE - NOT IN MODULAR SCOPE C C I CONCRETE PAVING IN SCOPE SLOPE DN 1" / 12" MAX CONC SEAT WALL - NIC ROCK LINED SWALE - NIC PEDESTRIAN ENTRY FOR REFERENCE ONLY NO. ISSUE DATE SPLIT SYSTEM OUTDOOR UNIT - SEE MECHANICAL VRF SYSTEM OUTDOOR UNIT - SEE MECHANICAL CONC WALK NIC D D 12" W. (MIN) CONC MOW STRIP BY MODULAR MANUFACTURER IV I I (E) FIRE LANE (CONC PAVING) IV E I E CAMPUS SAFETY CENTER IV (E) CONC SWALE (E) FIRE HYDRANT F F (E) RETAINING WALL SECURED PARKING AREA (A.C. PAVING) - NIC PIV MECHANICAL EQUIPMENT AND CONCRETE EQUIPMENT PAD - IN MODULAR CONTRACT COORDINATE WITH FENCE NOT IN CONTRACT IT T LI E A R CH EC C FILE NO.7-C1 ED NS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 XX-XXXXXX CONCRETE WALK NOT IN MODULAR CONTRACT NI RENEWAL DATE O F C A LI F O R ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. I IV(2) (E) BLDG SC E AT GOLF CART PARKING / CHARGING AREA - NIC ST G SS Vault G A 5-31-17 I THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. SWING GATE - NIC (E) CONC SWALE H H CONSULTANT (E) TENNIS COURTS J J ENLARGED SITE PLAN MODULAR PROJECT NO: 985-0007 DATE: 01.22.2016 I 1/25/2016 11:36:01 AM IV K K N PARTIAL SITE PLAN 1" = 10'-0" 12 11 10 9 8 7 6 5 4 3 SHEET NO: A1.01M K3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 A 7 6 A 6' - 1 1/2" 5 K3 B C A3.21M 4 C.1 D D.9 3 2 GENERAL NOTES E 1. CONSTRUCTION CONSISTS OF TWO COMPONENTS: A. MODULAR BUILDINGS B. SITE BUILT CONSTRUCTION 2. SCOPE OF WORK IN THIS SET OF DOCUMENTS IS FOR MODULAR BUILDING COMPONENTS ONLY. 3. AN APPROXIMATE AREA HAS BEEN IDENTIFIED ON THE DRAWINGS FOR MODULAR BUILDING COORDINATION REQUIRED WITH SITE BUILT COMPONENTS. COORDINATION MAY NOT BE LIMITED TO THIS AREA. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR COORDINATION WITH ARCHITECT AND ARCHITECT'S CONSULTANTS FOR INTERFACE OF ALL BUILDING SYSTEMS, INCLUDING BUT NOT LIMITED TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, FIRE ALARM, WEATHERPROOFING, ETC. 4. SITE BUILT COMPONENT WILL REQUIRE PENETRATION THROUGH MODULAR BUILDING ROOF AND FLOOR SYSTEM. MODULAR BUILDING MANUFACTURER SHALL ACCOUNT FOR COORDINATION REQUIRED. 5. REQUIRED INTERIOR SIGNAGE IS SHOWN, BUT IS NOT PART OF THE MODULAR CONTRACT. 6. PROVIDE (2) 4"Ø SLEEVE AND (1) 2"Ø SLEEVE FROM CRAWL SPACE TO ELECTRICAL ROOM FOR FUTURE LINE VOLTAGE, FIRE ALARM, ETC. PROVIDED UNDER SITE-BUILT CONSTRUCTION CONTRACT. 7. ALL DIMENSIONS ARE TO CENTERLINE OF OPENING, CENTERLINE OF GRID OR FACE OF STUD, UNLESS OTHERWISE NOTED. 8. UNLESS OTHERWISE NOTED, LOCATE DOORS 6" FROM NEAREST WALL INTERSECTION. 5' - 0" 1' - 6" 08 A A 02 04 1 1 1.1 1.1 06 RAMP, STAIRS, FLATWORK AND ASSOCIATED RAILINGS, ETC. BY SITE CONTRACTOR 4' - 6" 30" x 48" CLEAR SPACE B 1 ø 5' 0" EOC 01 102 K7 A3.11M 07 5' - 0" B LOS MEDANOS COLLEGE RESTROOM 117 2 L-4001 CAMPUS SAFETY CENTER 2 LEGEND: LOBBY 2700 E LELAND ROAD, PITTSBURG, CA 94565 SITE BUILT CONSTRUCTION - NIC 101 F3 A9.10M NOT IN SCOPE 40' - 0" C C 17' - 0" 9' - 0" MODULE 3 IS0 50 1 10' - 4" 5.6 12' - 0" F 60' - 0" C3 A3.11M 3' - 0" 5.8 HALL 118 107 PARKING OFFICER A 5' - 0" 118 IS0 00 2 3 1/8" 11' - 0 1/2" 9" 5' - 5 1/4" 12' - 0" 113A IS0 50 7 115 PREBOOKING / BOOKING 115 B11 3' - 0" 8' - 0" 116A 114A 5' MIN E RENEWAL DATE O F C A LI F O R AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. 7 THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 12' - 0" LOCKER ROOM XX-XXXXXX ARCHITECT'S STAMP MIN 5' - 6" LOCKER ROOM IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES ES0 00 1 IS0 00 2 5' - 0" CLR 6' - 0" A3.21M MODULE 1 C3 12' - 0" H G AA A5.01M IS0 50 12 114 IS0 45 1 IT 5-31-17 3' - 0" MEN IS0 00 2 A R CH TROY PENNINGTON 113 114 E ED NS C-31285 IS0 50 7 5' - 6" 12' - 0" AA RESTROOM WOMEN AA FILE NO.7-C1 E IS0 00 1 116 5.8 6 IS0 50 7 Sim IS0 50 7 116 7' - 0 3/4" 10' - 11 1/2" IS0 50 7 117 6' - 0" 3' - 0" A B4 F 5.6 T 8' - 0" 111 C10 A2.01M 7 105 AT 9' - 0" IS0 00 2 ELEC B6 A5.01M B2 9 3/4" RESTROOM 117 IS0 00 14 PATROL / REPORT C11 A9.10M 06 IS0 00 1 IS0 00 13 112 IS0 00 4 C10 A2.01M 5 ST MODULE 2 IS0 45 1 F3 A3.11M EC AA POLICE AIDE EQUIP E 108 IS0 00 13 IS0 00 4 3' - 0" IS0 50 7 12' - 0" IS0 00 13 112 108 H5 A9.10M IS0 00 13 IS0 50 1 6 G 109 EVIDENCE STORAGE C IS0 45 1 IS0 00 13 4 LI COMBI TOILET / SINK, MFR: ACORN, MODEL #1449 119 RECORDS 3.8 60' - 0" 5 BREAK ROOM 9' - 0" GLASS MIRROR, MFR: BOBRICK, MODEL # B-165 2460 A 7' - 7 7/8" WALL TYPE - SEE SHEET A9.00M 9' - 0" 48" GRAB BAR, MFR: BOBRICK, MODEL # B-6806 SERIES 110 7' - 8" IS1 00 1 3' - 0" IS0 50 1 DOOR TYPE - SEE SHEET A2.81M 3' - 0" 09 LOST & FOUND 201 6' - 0" 36" GRAB BAR, MFR: BOBRICK, MODEL # B-6806 SERIES 3' - 0" 08 109 120 WASTE RECEPTACLE, O.F.O.I. IS0 00 13 110 119 07 IS0 00 13 120 ES0 00 1 IS0 45 1 IS0 45 1 DATE 2' - 7" 9' - 8" 9' - 0" 3' - 0" A 106 9' - 10 1/4" 06 IT C ISSUE WINDOW TYPE - SEE SHEET A2.81M D 13' - 0 3/4" E CORPORAL K7 A9.10M IS0 00 14 122 IS0 50 1 PAPER TOWEL DISPENSER, SURFACE MOUNTED, O.F.C.I. 106 122 4 TOILET PARTITION, MFR: BRADLEY, MODEL STAINLESS STEEL SERIES 700 FLOOR-TO-CEILING IS0 50 1 B B 3.4 5' - 0" CLR 9" 05 IS0 50 1 6' - 0" 04 121 121 MODULE 4 03 104 104B G8 DISPATCH/ RECEPTION COMBINATION SEMI-RECESSED TOILET TISSUE DISPENSER, SEAT COVER, AND SANITARY NAPKIN DISPOSAL, MFR: BOBRICK, MODEL # B-3574 SOAP DISPENSER, SURFACE-MOUNTED, O.F.C.I. K5 A9.10M G11 A5.01M G6 LIEUTENANT 3.8 12' - 0" 02 INTERVIEW IS0 50 0 IS0 50 1 9' - 0" RESTROOM ACCESSORIES 01 MODULE 5 12' - 0" 3.4 IS0 50 1 101B G4 A 3 103 22' - 0" A3.21M IS0 00 8 D F11 A9.10M G3 NOTE: ACCESSORIES TO BE STAINLESS STEEL, SEE SHEET A0.40 FOR MOUNTING HEIGHTS OF ACCESSORIES, ALL O.F.C.I. ACCESSORIES TO BE APPROVED BY ARCHITECT AND DSA BEFORE INSTALLATION. NO. STORAGE AREA REQUIRING COORDINATION C10 MODULAR CONSTRUCTION H7 A9.10M 7' - 1 5/8" 3 5'-0" MIN CLR 1/2" = 1'-0" 5' - 4 7/8" ES0 00 1 A AREA REQUIRING COORDINATION WITH SITE BUILT ENLARGED RESTROOM PLAN (RESTROOM 115 SIM O.H.) 10' - 7 1/4" 10' - 5 1/2" 3' - 0" A D 7' - 10 1/4" A 15' - 6 1/2" NI 6' - 0" H CONSULTANT 5' MIN A5.01M B8 IS0 45 1 AA 03 107 8 5 113B 8 ES0 00 1 (7) SINGLE TIER LOCKERS (1) ACCESSIBLE REQ'D. 09 4 (7) SINGLE TIER LOCKERS (1) ACCESSIBLE REQ'D. 3 J J CANOPY ABOVE, TYP 2 K1 A3.11M 11' - 1 1/2" 6' - 6" 10' - 11" 13' - 4" FLOOR PLAN MODULAR 1 11' - 5 1/2" 17' - 6" PROJECT NO: 985-0007 9' - 2" DATE: 01.22.2016 17' - 6" 22' - 6" 40' - 0" 1/25/2016 11:36:05 AM # = MODULE NUMBER N K A B D D.9 E FLOOR PLAN - MODULAR 1/4" = 1'-0" 12 11 10 9 8 7 6 5 4 N 3 KEY PLAN K3 1/16" = 1'-0" 2 1 K SHEET NO: A2.01M MODULAR BID PACKAGE 12 11 10 9 8 7 6 A 5 B C 4 C.1 D D.9 3 2 1 GENERAL NOTES E 1. CONSTRUCTION CONSISTS OF TWO COMPONENTS: A. MODULAR BUILDINGS B. SITE BUILT CONSTRUCTION 2. SCOPE OF WORK IN THIS SET OF DOCUMENTS IS FOR MODULAR BUILDING COMPONENTS ONLY. 3. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR COORDINATION WITH ARCHITECT AND ARCHITECT'S CONSULTANTS FOR INTERFACE OF ALL BUILDING SYSTEMS, INCLUDING BUT NOT LIMITED TO STRUCTURAL, MECHANICAL, WEATHERPROOFING, ETC. 4. SITE BUILT COMPONENT WILL REQUIRE PENETRATION THROUGH MODULAR BUILDING COMPONENT ROOF AND FLOOR SYSTEM. MODULAR BUILDING MANUFACTURER SHALL ACCOUNT FOR COORDINATION REQUIRED. 5. SITE BUILT ROOF HIDDEN IN THIS VIEW FOR CLARITY. 6. ROOF STRUCTURE INDICATED IS FLAT WITH TAPERED INSULATION CREATING THE SLOPE. MODULAR MANUFACTURER MAY SUGGEST ALTERNATE FOR SLOPED STRUCTURE. ALTERNATE MUST BE CLEARLY IDENTIFIED IN BID PROPOSAL. A A 1 1 1.1 1.1 B B ROOFING KEYNOTE LEGEND 2 2 C 3' - 1 1/2" 1 PARAPET CAP 2 MANUFACTURER'S STANDARD DOOR CANOPY 3 SINGLE PLY MEMBRANE ROOFING SYSTEM O/ TAPERED RIGID INSULATION (4" MIN THICKNESS) 4 ALUMINUM SUNSHADE 5 ROOF DRAIN AND OVER FLOW 6 NOT USED 7 ROOFING CRICKET 8 AREA UNDER SITE-BUILT ROOF - EXPOSED METAL DECK LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C 1 NO. 3 ISSUE DATE 3 RD OD 15' - 6 3/8" 3.4 14' - 2" 3.4 OPEN TO BELOW D 1/4" MIN. SLOPE AREA REQUIRING COORDINATION WITH SITE BUILT 3.8 4 RIDGE K9 E 1/4" MIN. SLOPE A9.10M 5 5.6 F TYP. 3.8 4 E 8 5 60' - 0" 5 D 5.6 RD F OD 5.8 5.8 RIDGE 5 RD OD 6 6 FILE NO.7-C1 SLOPE DN 1/4" / 12" MIN IT LI C A R CH T IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON TYP. RIDGE 1 7 E A RENEWAL DATE NI G AT 3 XX-XXXXXX 5-31-17 ST G C-31285 1/4" MIN. SLOPE 4 E ED NS EC 1/4" MIN. SLOPE SLOPE DN 1/4" / 12" MIN O F C A LI F O R AC DATE FLS SS TYP. ARCHITECT'S STAMP RIDGE APPROVAL 1/4" MIN. SLOPE TYP. 7 1/4" MIN. SLOPE 7 THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. H THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H SLOPE DN 1/4" / 12" SLOPE DN 1/4" / 12" CONSULTANT OD RD 5 RIDGE RD OD 4' - 0" 8 4' - 0" 8 2 J 2 6' - 10" J 5' - 0" ROOF PLAN - MODULAR PROJECT NO: 985-0007 1/25/2016 11:36:06 AM DATE: 01.22.2016 N K A B D D.9 E ROOF PLAN - MODULAR 1/4" = 1'-0" 12 11 10 9 8 7 6 5 4 K 3 SHEET NO: A2.14M K3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 A 5 B C 4 C.1 D D.9 3 2 1 GENERAL NOTES E 1. CONSTRUCTION CONSISTS OF TWO COMPONENTS: A. MODULAR BUILDINGS B. SITE BUILT CONSTRUCTION 2. SCOPE OF WORK IN THIS SET OF DOCUMENTS IS FOR MODULAR BUILDING COMPONENTS ONLY. 3. AN APPROXIMATE AREA HAS BEEN IDENTIFIED ON THE DRAWINGS FOR MODULAR BUILDING COORDINATION REQUIRED WITH SITE BUILT COMPONENTS. COORDINATION MAY NOT BE LIMITED TO THIS AREA. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR COORDINATION WITH ARCHITECT AND ARCHITECT'S CONSULTANTS FOR INTERFACE OF ALL BUILDING SYSTEMS, INCLUDING BUT NOT LIMITED TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, FIRE ALARM, WEATHERPROOFING, ETC. 4. SITE BUILT COMPONENT WILL REQUIRE PENETRATION THROUGH MODULAR BUILDING ROOF AND FLOOR SYSTEM. MODULAR BUILDING MANUFACTURER SHALL ACCOUNT FOR COORDINATION REQUIRED. 5. REQUIRED INTERIOR SIGNAGE IS SHOWN, BUT IS NOT PART OF THE MODULAR CONTRACT. 6. PROVIDE (2) 4"Ø SLEEVE AND (1) 2"Ø SLEEVE FROM CRAWL SPACE TO ELECTRICAL ROOM FOR FUTURE LINE VOLTAGE, FIRE ALARM, ETC. PROVIDED UNDER SITE-BUILT CONSTRUCTION CONTRACT. 7. ALL DIMENSIONS ARE TO CENTERLINE OF OPENING, CENTERLINE OF GRID OR FACE OF STUD, UNLESS OTHERWISE NOTED. 8. UNLESS OTHERWISE NOTED, LOCATE DOORS 6" FROM NEAREST WALL INTERSECTION. A A 1 1 1.1 1.1 EOC B 102 B LEGEND: 2 2 LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER SITE BUILT CONSTRUCTION - NIC 2700 E LELAND ROAD, PITTSBURG, CA 94565 NOT IN SCOPE LOBBY MODULAR CONSTRUCTION 101 C C WINDOW TYPE - SEE SHEET A2.81M B 3 3.4 STORAGE 104 103 DOOR TYPE - SEE SHEET A2.81M IS1 00 1 WALL TYPE - SEE SHEET A9.00M NO. ISSUE DATE 3 C DISPATCH/ RECEPTION 122 RF1 B1 P4 LIEUTENANT 121 C1 B1 P1 INTERVIEW 201 FINISH SYMBOL LEGEND 3.4 FINISH SCHEDULE BOX: IT 106 RF1 B1 P1 D 3.8 FLOORING FINISH WALL FINISH 3.8 CT1 RB1 P1* WP1 * SEE FINISH PLAN KEYNOTES 4 4 CORPORAL 120 C1 B1 P1 EVIDENCE STORAGE 108 SC1 B1 P1 1, 2, 3 BASE FINISH WAINSCOT FINISH FINISH PLAN KEYNOTES P6 EXTENT OF ACCENT FINISH 8 SEE FINISH PLAN KEYNOTE EVIDENCE STORAGE D CORNER GUARD CG1 108 BREAK ROOM 119 RF1 B1 P1,4 5 E RECORDS 109 RF1 B1 P1 INTERIOR MATERIALS LEGEND C1 5 POLICE AIDE EQUIP 112 RF1 B1 P1 RESILIENT LINOLEUM SHEET FLOORING MANUFACTURER: FORBO PRODUCT: MARMOLEUM TEXTURE: STRIATO COLOR: FRESH WALNUT 5229 T1 CERAMIC FLOOR TILE MANUFACTURER: DAL-TILE PRODUCT: KEYSTONES COLOR: TO BE SELECTED BY ARCHITECT F 5.6 T2 CERAMIC WALL TILE MANUFACTURER: DAL-TILE PRODUCT: MODERN DIMENSIONS COLOR: TO BE SELECTED BY ARCHITECT PARKING OFFICER 118 RF1 B1 P1 5.8 WP1 FRP WALL PANELS MANUFACTURER: MARLITE PRODUCT: INDURO COLOR: TITANIUM B1 RUBBER BASE MANUFACTURER: PRODUCT: COLOR: ELEC 105 PATROL / REPORT 111 RF1 B1 P1 5.6 5.8 6 F JOHNSONITE TRADITIONAL 4" TO BE SELECTED BY ARCHITECT FILE NO.7-C1 MEN 114 RF1 B1 P1 WOMEN 116 RF1 B1 P1 7 PREBOOKING / BOOKING 113 RF1 RF1 WP1 1 7 INTERIOR PAINT ACCENT COLOR MANUFACTURER: TBD PRODUCT: COLOR: "GRAY" (TO MATCH EP2) P3 INTERIOR PAINT ACCENT COLOR MANUFACTURER: PRODUCT: COLOR: "RED" (TO MATCH EP3) P4 SC1 LI IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 XX-XXXXXX 5-31-17 G P2 IT TROY PENNINGTON E AT RESTROOM 117 T1 T2 T4 INTERIOR PAINT MANUFACTURER: TBD PRODUCT: COLOR: "WHITE" (TO MATCH EP1) ST G RESTROOM 115 T1 T2 T4 A R CH T P1 E ED NS EC C 6 PATCRAFT RF1 REF. HALL 107 RF1 B1 P1 CARPET TILE MANUFACTURER: PRODUCT: TEXTURE: COLOR: RENEWAL DATE A LOST & FOUND 110 RF1 B1 P1 NI E O F C A LI F O R ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. INTERIOR PAINT ACCENT COLOR MANUFACTURER: PRODUCT: COLOR: ACCENT COLOR TBD THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. SEALED CONCRETE H H CONSULTANT 8 8 J J FINISH PLAN MODULAR PROJECT NO: 985-0007 1/25/2016 11:36:10 AM DATE: 01.22.2016 N K A B D D.9 E FINISH PLAN 1/4" = 1'-0" 12 11 10 9 8 7 6 5 4 K 3 SHEET NO: A2.31M K3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 ILLUMINATED EXIT SIGN NOTES 1. EXIT DOORS SHALL BE MARKED WITH AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION OF EGRESS TRAVEL. 2. 3. A EXIT ACCESS DOORS SHALL BE MARKED WITH AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION OF EGRESS TRAVEL. EXIT SIGNS ARE NOT REQUIRED IN ROOMS OR AREAS THAT REQUIRE ONLY ONE EXIT OR EXIT ACCESS. # 101B 104B 106 107 108 109 110 112 113A 113B 114 115 116 117 118 119 120 121 122 ILLUMINATED EXIT SIGNS ARE SHOWN ON THE ARCHITECTURAL CEILING PLAN FOR REFERENCE ONLY. REFER TO ELECTRICAL PLANS FOR SIGNS. 2. "LABEL" SHALL MEAN "FIRE ASSEMBLY" AS DEFINED IN 2013 CBC SECTION 716.5. 3. FIRE DOORS AND FIRE WINDOWS SHALL HAVE AN APPROVED LABEL OR LISTING MARK INDICATING THE FIRE PROTECTION RATING, WHICH IS PERMANENTLY AFFIXED AT THE FACTORY WHERE FABRICATION AND ASSEMBLY ARE DONE. (2013 CBC SECTIONS 716.5.7.1 AND 716.5.8.3) 4. ALL 60-MINUTE RATED ASSEMBLIES SHALL BE PROVIDED WITH APPROVED GASKETING MATERIAL SO INSTALLED TO PROVIDE A SEAL WHERE THE DOOR MEETS THE STOP ON BOTH SIDES AND ACROSS THE TOP. THE DOOR AND FRAME SHALL BEAR AN APPROVED LABEL OR OTHER IDENTIFICATION SHOWING THE RATING THEREOF, FOLLOWED BY THE LETTER "S". (2013 CBC SECTION 716.5.7.3) 5. FIRE RATED DOOR FRAMES SHALL BE INSTALLED STRICTLY PER MANUFACTURER'S PRINTED INSTRUCTIONS. (NFPA 80.) 6. ROOMS NOTED AS INCIDENTAL USE AREAS SHALL HAVE DOORS THAT ARE SELF-CLOSING OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH NFPA 80, TABLE 1-11.4. 7. ALL HAND-ACTIVATED DOOR OPENING HARDWARE, HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO OPERATE. HARDWARE SHALL BE CENTERED BETWEEN 34" AND 44" ABOVE THE FLOOR. LATCHING AND LOCKING DOORS THAT ARE HAND-ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER-TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE. LOCKED EXIT DOORS SHALL OPERATE AS ABOVE IN EGRESS DIRECTION. (2013 CBC 11B-309) 8. 2 1 DOOR SCHEDULE MODULAR DOOR NOTES: 1. ALL RATED DOORS ARE TO BE POSITIVE LATCHING AND SELF-CLOSING. B 3 DOOR AND WINDOW SIZES MAY NOT BE ALTERED WITHOUT THE EXPRESS WRITTEN CONSENT OF THE ARCHITECT. W 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" H 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" DOOR THICK TYPE 1 3/4" NV 1 3/4" F 1 3/4" F 1 3/4" NV 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" SV 1 3/4" NV 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" F 1 3/4" FV MATL HM WD WD HM WD WD WD WD HM HM WD WD WD WD WD WD WD WD WD FINISH TYPE P S ST S ST S P S ST S ST S ST S ST S P S P S ST S ST S ST S ST S ST S ST S ST S ST S ST SF MATL HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM AL FRAME HEAD K7/A2.81M K7/A2.81M K7/A2.81M H1/A8.31M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M H1/A8.31M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M K7/A2.81M H1/A8.31M FINISH P P P P P P P P P P P P P P P P P P FF JAMB K5/A2.81M K5/A2.81M K5/A2.81M K1/A8.31M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K1/A8.31M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K5/A2.81M K1/A8.31M RATING FIRE STC 45 45 45 45 45 45 45 45 45 45 45 THRESH H1/A2.81M H1/A2.81M - HDW GROUP REMARKS 02 DELETE SEALS, THRESHOLD 06 05 02 05 05 05 05 06 07 04 03 04 03 01 01 01 01 01 A B LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER Hardware Group 01 3 1 1 1 1 EA EA EA SET EA HINGES OFFICE STD IC CORE SEALS WALL STOP 5BB1HW 4.5x4.5 NRP CL3151 8000-6 5050CL WS407CCV C 652 626 626 CLR 626 IVES CORBIN-RUSSWIN CORBIN-RUSSWIN NGP IVES 3 1 1 1 1 EA EA EA SET EA HINGES PRIVACY SURFACE CLOSER SEALS WALL STOP 5BB1HW 4.5x4.5 NRP CL3120 4111 AVB EDA 5050CL WS407CCV Hardware Group 02 1 1 1 1 1 1 1 1 1 1 1 1 1 EA EA EA EA EA EA EA EA EA SET EA EA EA CONT HINGES ELEC PANIC POWER TRANSFER MORTISE CYLINDER STD IC CORE PULL SURFACE CLOSER DOOR SWEEP KICKPLATE SEALS THRESHOLD POWER SUPPLY CARD READER Hardware Group 06 Hardware Group 03 652 626 689 CLR 626 IVES CORBIN-RUSSWIN LCN NGP IVES 3 1 1 1 EA EA EA EA HINGES COMMUNICATING STD IC CORE WALL STOP 5BB1HW 4.5x4.5 NRP CL3162 8000-6 WS407CCV 652 626 626 626 IVES CORBIN-RUSSWIN CORBIN-RUSSWIN IVES 2700 E LELAND ROAD, PITTSBURG, CA 94565 LEGEND F FLUSH FV FULL VISION HV HALF VISION HL HALF LOUVER NV NARROW VISION SV SECURITY VISION (LOUVER WHERE OCCURS) Hardware Group 04 24HD EPT RX-3547A-L-17 EPT10 1080-CT6 x CYLINDER COLLAR 8000-6 VR900-NL 4111 AVB EDA 200NA 8400 10" x 34" B4E 628 626 689 626 626 626 689 CL 630 PER DETAIL AL PS914 900-2RS LGR BY ACCESS CONTROL SUPPLIER Hardware Group 07 IVES VON DUPRIN VON DUPRIN CORBIN-RUSSWIN CORBIN-RUSSWIN IVES LCN NGP IVES 3 1 1 1 1 2 EA EA EA SET EA EA HINGES PUSH/PULL SURFACE CLOSER SEALS WALL STOP KICKPLATE 5BB1HW 4.5x4.5 NRP 8200 / 8103EZ 4111 AVB EDA 5050CL WS407CCV 8400 10" x 34" B4E 652 626 689 CLR 626 630 IVES IVES LCN NGP IVES IVES 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Hardware Group 05 NGP VON DUPRIN 3 1 1 1 EA EA EA EA HINGES STOREROOM STD IC CORE WALL STOP 5BB1HW 4.5x4.5 NRP CL3157 8000-6 WS407CCV 652 626 626 626 IVES CORBIN-RUSSWIN CORBIN-RUSSWIN IVES EA EA EA EA EA EA EA EA EA SET EA EA EA EA CONT HINGES POWER TRANSFER MORTISE CYLINDER STD IC CORE PULL SURFACE CLOSER ELECTRIC STRIKE DOOR SWEEP KICKPLATE SEALS THRESHOLD POWER SUPPLY CARD READER LATCH GUARD 24HD EPT EPT10 1080-CT6 x CYLINDER COLLAR 8000-6 VR900-NL 4111 AVB EDA 7110 200NA 8400 10" x 34" B4E 628 689 626 626 626 689 626 CL 630 IVES VON DUPRIN CORBIN-RUSSWIN CORBIN-RUSSWIN IVES LCN ADAMS RITE NGP IVES F PER DETAIL AL PS914 900-2RS LGR BY ACCESS CONTROL SUPPLIER FV HV HL NV C NO. ISSUE DATE SV NGP VON DUPRIN D D DOOR LEGEND 1/4" = 1'-0" 3 K7 B1 LEVEL 3 BULLET RESISTANCE GLAZING 6' - 6" 4' - 8" K5 K5 A2.81M A2.81M SIM 7' - 2" A2.81M SIM 1' - 0" 5' - 0" 7' - 6" 6" A8.31M E 6' - 0" K5 8' - 9" 4' - 2" 3 A2.81M SIM 1' - 10" A2.81M SIM A2.81M SIM 4 A2.81M SIM K7 K7 K7 1' - 10" 6" 4' - 0" E GENERAL NOTES: 1. CONTRACTOR IS SOLELY RESPOBISBLE FOR MEANS AND METHODS.SEQUENCE IS SHOWN FOR CLARITY TO OVERLAPPNG MATERIAL ONLY. 2. CHECK ALL CONDITIONS TO ENSURE COVERAGE AND OVERLAP OF MULTIPLE PIECES. PATCH AS NECESSARY. 3. SELF-ADHERING WATERPROOF MEMBRANE SHALL NOT BE STAPLED AT EDGES AND JOINTS (EXCEPTION TO ALLOW AT OUTER EDGES TO SECURE DURING WEATHER (WINDY)CONDITIONS. 4. PRIMER TO BE USED IN APPLYING S.A.F. TO SHEATHING AND FRAME OPENING. 5. TOP OF J-MOLD AT JAMBS TO BE TUCKED UNDER OUTER EDGES OF HEAD FLASHING. SAME SELF-ADHERING WATERPROOFING MEMBRANE PRODUCT SHALL BE USED IN WINDOW INSTALL AND LATH PROCEDURES. 6. ALL SEALANTS USED AT WINDOWS SHALL BE COMPATIBLE WITH S.A.F. K5 A2.81M SIM F1 A8.31M SIM SIM A2.81M 3' - 0" A2.81M 6" DIA LEVEL 3 BULLET RESISTANCE SPEAKTHROUGH (SST) K7 2' - 6" FINISH FLOOR TWO-WAY TRANSPARENT MIRROR GLAZING (HEAT STRENGTHENED) K7 2 2' - 10" 9" 5 2' - 10" 11 D1 A8.31M SIM 10 12 B E 12" MIN. F 1 B D B C B B A NOTES: 1. F B AA SAME AS 'A' WITH OBSCURE GLAZING PROVIDE TEMPERED GLAZING WHERE REQUIRED BY CODE. 13 WINDOW LEGEND 1/4" = 1'-0" (3) MIN. JAMB ANCHORS PER SIDE, SHOP WELDED TO FRAME. LOCATE ABV. HINGE REINFORCEMENTS ON HINGE SIDE AND DIRECTLY OPPOSITE ON STRIKE SIDE. H INSTALL BUILDING PAPER UNDER 9" SILL MEMBRANE FLAP THEN ADHERE MEMBRANE TO PAPER 10 INSTALL BUILDING PAPER UP TO EDGE OF FRAME JAMBS AND THEN UP 9" ABOVE EDGE OF HEAD. (ONLY ONE JAMB SHOWN FOR CLARITY) 2 APPLY PREFABRICATED CORNER REINFORCING AT ALL SILL CORNERS 3 APPLY PRIMER PRIOR TO HEAD AND JAMB MEMBRANE INSTALLATION 4 INSTALL 9" MEMBRANE FLASHING 3" INTO OPENING PER DETAIL TO BOTH JAMBS (ONLY ONE SIDE SHOWN FOR CLARITY) 12 INSTALL GSM HEAD FLASHING (APPLY SEALANT BEAD BETWEEN WINDOW & FLASHING) INSTALL 9" MEMBRANE FLASHING AT HEAD 13 INSTALL 9" MEMBRANE FLASHING AT HEAD, REFER TO DRAWING ABOVE FOR OVERLAP. 5 STEEL STUD JAMB FRMG. BEYOND. 2 1 BOXED STEEL STUD JAMB FRAMING. NOTE: 1. FOR OPENINGS UP TO AND INCLUDING 3'-5". REFER TO DETAIL K3/FOR LARGER OPENINGS 2. FOR USE IN INTERIOR NON-LOAD BEARING WALLS ONLY. 3. DETAIL PROVIDED AS A MINIMUM STANDARD. MODULAR BUILDING MANUFACTURER'S DETAIL MAY VARY, BUT SHALL MEET OR EXCEED STANDARD. 16 GA. (MIN) FLOOR CLIPS SECURED TO FLOOR ASSEMBLY w/ (2) ANCHORS (MIN), TYP. EA. SIDE 11 INSTALL 6" MEMBRANE FLASHING OVER PLASTER J-TRIM AND BUILDING PAPER AND THEN UP 6" ABOVE EDGE OF HEAD, BOTH JAMBS (ONLY ONE SIDE SHOWN FOR CLARITY) NOTE: SEE JAMB DETAILS FOR ADDITIONAL INFO. 3" 9 14" MAX. APPLY PRIMER TO SILL, THEN INSTALL 12" SILL MEMBRANE FLASHING INTO OPENING 3" (IT SHOULD BE EQUAL TO WIDTH OF WINDOW PLUS WIDTH OF EACH JAMB FLASHING) LEAVE 9" BOTTOM EDGE FREE FOR FUTURE INSTALLATION OF BUILDING PAPER. FLOOR FINISH SEE PLAN C CONT. SHT. MTL. FLASHING FORMED AS SHOWN AND WITH HEMMED EDGE UNDER THRESHOLD, EXTEND FROM UNDER THRESHOLD AND INTO EXPANSION MATERIAL E RENEWAL DATE A G O F C A LI F O R ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. 1/2" MAX 1/2" MAX. 8" MAX. RUNNER TRACK TO MATCH SIZE AND GA. OF STUDS. CUT FLANGES, BEND WEB UP AND FASTEN TO STUD w/ (2) #10 S.M.S. ADA COMPLIANT ALUM. THRESHOLD SET IN FULL BED OF MASTIC XX-XXXXXX 5-31-17 AT DOOR FRAME BEYOND C-31285 ST G IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON NI STEEL STUD CRIPPLE FRMG. TO MATCH WALL STUD SIZE. IT LI A2.81M A2.81M STEEL STUD CRIPPLE FRAMING TO MATCH WALL STUD SIZE. 9 ATTACH THRESHOLD w/ #10 FH CONC. SCREWS @ 12" O.C. MAX. - 2" MAX. FROM EA. END - SET SCREWS IN SEALANT E A R CH T 8 K3 ED NS EC STEEL STUD BOX HEADER FRMG., SEE 1/4" MAX H3 1 1 FILE NO.7-C1 DOOR AS SCHEDULED 9" THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. CONC. WALK H SEALANT CONSULTANT COMPRESSIBLE FILLER 14 PROVIDE CONSISTENT JOINT BETWEEN J-TRIM AND WINDOW FRAME. HEAD FLASHING SHALL LAP OVER JAMB J METAL (NOT SHOWN) 1/2" TYP. 1/25/2016 11:36:14 AM K JAMB MEMBRANE FLASHING INTO OPENING SILL MEMBRANE FLASHING MEMBRANE FLASHING AT JAMB / SILL 1 1/2" = 1'-0" 12 11 STEEL STUD CRIPPLE FRMG - MATCH WALL STUD GA. & SIZE RUNNER STEEL TRACK TO MATCH WALL STUD GA. & SIZE 5/8" TYPE 'X' GYP. BD. CONT. SEALANT BEAD, TYP. BOTH SIDES METAL FLASHING AP RL G E N OV HI N. LAS I M F 2" MB JA NOTE: WINDOW NOT SHOWN FOR CLARITY DBL. STUD JAMB FRMG., TYP. GYP BD, TYP. HEAD MEMBRANE FLASHING INTO OPENING HEAD MEMBRANE FLASHING OVER HEAD DRIP FLASHING SILL MEMBRANE FLASHING (NOT HATCHED FOR CLARITY) OBSTRUCTION, TYP. BOTH SIDES NOTE: WINDOW NOT SHOWN FOR CLARITY JAMB MEMBRANE FLASHING (OVER JTRIM) MEMBRANE FLASHING AT HEAD K11 1 1/2" = 1'-0" 10 9 H.M. DOOR FRAME DOOR, PER SCHED. FRAME DEPTH TO BE DETERMINED 6" = 1'-0" 7 INTERIOR H.M. DOOR JAMB K7 6" = 1'-0" 6 5 J DOOR FRAME CARPET RESILIENT FLOORING DOOR & WINDOW SCHEDULE / DETAILS 18 GA. (MIN) STEEL RUNNER TRACK - SIZE TO MATCH WALL STUDS. 1/16" 1. 3. DOOR OPENING SEE DOOR SCHED. H1 DOOR 1/16" 1-16 NOTE: DOOR PER SCHED. 3" = 1'-0" STEEL STUD BOX HEADER. (2) 6", 18 GA. STUDS. 2. JAMB ANCHOR PER DOOR MFR. INTERIOR H.M. DOOR HEAD 8 CONT. SEALANT BEAD, TYP. BOTH SIDES H.M. DOOR FRAME BY OVERALL WALL THICKNESS +1" K9 5/8" TYPE 'X' GYP. BD. ALUM THRESHOLD AT EXTERIOR DOOR H3 ALTERNATE OPTION AS AN ALTERNATE (FOR INTERIOR CONDITION ONLY), IN LIEU OF WELDING, CUT FLANGES AND EXTEND WEB 3" BEYOND EA. SIDE AND ATTACH FLANGES TO JAMB STUDS w/ (4) #10 S.M.S. PER FLANGE. NOTE: PROVIDE LABELED DOOR AND FRAME AT RATED CONDITION. FRAME DEPTH TO BE DETERMINES JAMB MEMBRANE FLASHING INTO OPENING 3" = 1'-0" 4" MIN. TO WALL OR BOX HEADER WHERE OCCURS, SEE K3/- FOR ADDITIONAL INFO. DOOR OPENING SEE DOOR SCHED. PRE-FAB CORNERS UNDER SILL MEMBRANE FLASHING STEEL STUD FRAMING, TYP. 6" J NOTE: PROVIDE LABELED DOOR AND FRAME AT RATED CONDITION. 2" MIN. OVERLAP JAMB FLASHING JAMB MEMBRANE FLASHING OVER PLASTER J-TRIM 3" = 1'-0" STEEL STUD INTERIOR DOOR HEADER H5 3/8" U.O.N. 1/2" = 1'-0" DOOR ANCHORS AT STUD WALL H9 BY OVERALL WALL THICKNESS +1" WINDOW FLASHING AT WINDOWS ALTERNATE OPTIONAS AN ALTERNATE (FOR INTERIOR CONDITION ONLY), IN LIEU OF WELDING, BEND WEB & FASTEN w/ (2) #10 S.M.S. AND ATTACH FLANGES TO JAMB STUDS w/ (2) #10 S.M.S. PER FLANGE. STEEL STUD JAMB FRMG. BEYOND. FOR INTERIOR OPENINGS GREATER THAN 8'-0" AND UP TO 14'-0" OR EXTERIOR OPENINGS GREATER THAN 3'-5" AND UP TO 8'-0". AT EXTERIOR WALL CONDITION, HEADER STUDS AND RUNNING TRACKS SHALL MATCH WALL STUD GA. DETAIL PROVIDED AS A MINIMUM STANDARD. MODULAR BUILDING MANUFACTURER'S DETAIL MAY VARY, BUT SHALL MEET OR EXCEED STANDARD. STEEL STUD DOOR HEADER K5 3" = 1'-0" 4 3 K3 PROJECT NO: 985-0007 CONC. SLAB DATE: 01.22.2016 VINYL THRESHOLD/ FLOORING TRANSITION K NOTE: SHEET NO: VINYL THRESHOLD/FLOORING TRANSITION SHALL BE CENTERED BELOW DOOR THRESHOLD CARPET TO RESILIENT FLOORING 3" = 1'-0" 2 1 K1 A2.81M MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 GENERAL NOTES: 1 A 1.1 2 D1 D8 A3.21 A3.21 3 3.4 3.8 4 5 5.6 5.8 6 7 8 1. CONSTRUCTION CONSISTS OF TWO COMPONENTS: A. MODULAR BUILDINGS B. SITE BUILT CONSTRUCTION 2. SCOPE OF WORK IN THIS SET OF DOCUMENTS IS FOR MODULAR BUILDING COMPONENTS ONLY. 3. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR COORDINATION WITH ARCHITECT AND ARCHITECT'S CONSULTANTS FOR INTERFACE OF ALL BUILDING SYSTEMS, INCLUDING BUT NOT LIMITED TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, FIRE ALARM, WEATHERPROOFING, ETC. 4. SITE BUILT COMPONENT WILL REQUIRE PENETRATION THROUGH MODULAR BUILDING ROOF AND FLOOR SYSTEM. MODULAR BUILDING MANUFACTURER SHALL ACCOUNT FOR COORDINATION REQUIRED. 5. INSTALL CEMENT PLASTER IN CONFORMANCE WITH CBC SECTION 2512. 6. COORDINATE CONNECTION OF SITE-BUILT EXTERIOR BUILDING FINISHES TO MODULAR BUILDING EXTERIOR FINISHES. SEE FLOOR PLAN AND SECTIONS FOR POINTS OF CONNECTION. A SITE-BUILT COMPONENTS SHOWN FOR REFERENCE ONLY T.O. ROOF 18' - 10 1/2" 7 5 2 7 1 6 T.O. MODULAR PARAPET FRAMING 12' - 6" 2' - 6" MP2 B PAINTED STL CANOPY BY MODULAR MANUF (EP1) 2' - 6" B 2' - 6" ROOF DRAIN OVERFLOW, TYP OF (3) THIS ELEVATION L-4001 CAMPUS SAFETY CENTER FINISH FLOOR 0" 2' - 6" A A CP1 F9 A A AA 4 TYP. 3 TYP. AA 2700 E LELAND ROAD, PITTSBURG, CA 94565 AA EXTERIOR ELEVATION KEYNOTE LEGEND A9.10M C LOS MEDANOS COLLEGE C 1 CEMENT PLASTER FINISH 2 MODULAR MANUFACTURER'S STANDARD TRIM AT MOD LINE 3 ALUMINUM STOREFRONT WINDOW SYSTEM 4 ALUMINUM CEMENT PLASTER REVEAL 5 ALUMINUM SUNSHADE 6 PRE-FINISHED ALUMINUM CAP FLASHING 7 EXTERIOR LIGHT FIXTURE - SEE ELECTRICAL M WINDOW TYPE - SEE SHEET A2.81M NO. WEST ELEVATION 1/4" = 1'-0" 8 7 6 5.8 5.6 5 4 3.8 3.4 3 2 1.1 C3 1 D ISSUE DATE D T.O. ROOF 18' - 10 1/2" SITE BUILT COMPONENT HIDDEN FOR CLARITY EXTERIOR FINISH MATERIALS CP1 CEMENT PLASTER MANUFACTURER: PRODUCT: TEXTURE: COLOR: CP2 CEMENT PLASTER MANUFACTURER: PRODUCT: TEXTURE: COLOR: MP1 CORRUGATED METAL PANEL MANUFACTURER: PRODUCT: COLOR: MP2 METAL CAP FLASHING MANUFACTURER: PRODUCT: COLOR: MP3 METAL FASCIA PANELS MANUFACTURER: PRODUCT: COLOR: EP1 EXTERIOR PAINT MANUFACTURER: PRODUCT: COLOR: EP2 EXTERIOR PAINT MANUFACTURER: PRODUCT: COLOR: 6 T.O. MODULAR PARAPET FRAMING 12' - 6" 7 2' - 6" 2' - 6" E 2' - 6" 2' - 6" OPEN TO BEYOND FINISH FLOOR 0" 3 AA CP1 TYP. AA A PLY1 PLY1 F 4 TYP. 1 TYP. P4 BUILDING TIE-IN ROOF DRAIN OVERFLOW TYP OF (2) THIS ELEVATION EAST ELEVATION 1/4" = 1'-0" E F F3 IT T LI E A R CH EC C FILE NO.7-C1 ED NS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 XX-XXXXXX E D.9 D C.1 C B A A K3 B A3.21M C C.1 D D.9 RENEWAL DATE NI E AT G ST G A 5-31-17 O F C A LI F O R ARCHITECT'S STAMP E AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. T.O. ROOF 18' - 10 1/2" H T.O. ROOF 18' - 10 1/2" H 5 6 5 1 6 TYP. 2' - 6" 4 7 2' - 6" TYP. 2' - 6" 2' - 6" 8" H. x 3" D. INTERNALLY ILLUMINATED CHANNEL LETTERS - ARIAL TYPE FACE 3 7 T.O. MODULAR PARAPET FRAMING 12' - 6" 2' - 6" P1 2' - 6" P4 CONSULTANT T.O. MODULAR PARAPET FRAMING 12' - 6" J 2' - 6" OPEN TO BEYOND BUILDING TIE-IN B1 D 2' - 6" 2' - 6" 2' - 6" J FINISH FLOOR 0" A BUILDING TIE-IN FINISH FLOOR 0" F9 F9 A9.10M A9.10M 1/25/2016 11:36:19 AM PROJECT NO: 985-0007 1 4 DATE: 01.22.2016 TYP. K K NORTH ELEVATION 1/4" = 1'-0" 12 11 10 9 8 7 SOUTH ELEVATION K7 1/4" = 1'-0" 6 5 EXTERIOR ELEVATIONS - MODULAR 4 3 2 1 K1 SHEET NO: A3.11M MODULAR BID PACKAGE 12 11 10 9 8 7 6 A 5 B 4 C C.1 K3 3 D 2 1 GENERAL NOTES D.9 A3.21M 1. CONSTRUCTION CONSISTS OF TWO COMPONENTS: A. MODULAR BUILDINGS B. SITE BUILT CONSTRUCTION 2. SCOPE OF WORK IN THIS SET OF DOCUMENTS IS FOR MODULAR BUILDING COMPONENTS ONLY. 3. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR COORDINATION WITH ARCHITECT AND ARCHITECT'S CONSULTANTS FOR INTERFACE OF ALL BUILDING SYSTEMS, INCLUDING BUT NOT LIMITED TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, FIRE ALARM, WEATHERPROOFING, ETC. 4. SITE BUILT COMPONENTS WILL REQUIRE PENETRATION THROUGH MODULAR BUILDING ROOF AND FLOOR SYSTEM. MODULAR BUILDING MANUFACTURER SHALL ACCOUNT FOR COORDINATION REQUIRED. 5. BASIS OF DESIGN SHOWN IN BUILDING SECTIONS IS CONCRETE FILLED METAL PAN DECK FLOOR FRAMING SYSTEM OVER CRAWL SPACE. SLAB-ON-GRADE CONSTRUCTION IS ALSO ACCEPTABLE. MANUFACTURER SHALL SUBMIT PROPOSED FLOOR SYSTEM TO ARCHITECT AND DISTRICT FOR APPROVAL PRIOR TO SUBMITTING BID. PROVIDE RAT SLAB AT CRAWL SPACE WITH AREA DRAINS STUBBED TO 5' FROM BUILDING FOR SITE CONTRACTOR'S CONNECTION TO STORM DRAINAGE SYSTEM. 6. MODULAR BUILDING MANUFACTURER IS RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF CONCRETE FOOTING AND FOUNDATION SYSTEM SUPPORTING MODULAR BUILDING COMPONENTS. MODULAR BUILDING MANUFACTURER SHALL COORDINATE THE INSTALLATION AND DESIGN OF THESE ELEMENTS WITH DESIGN AND INSTALLATION OF FOOTING AND FOUNDATION SYSTEMS FOR SITE BUILT ELEMENTS. A A T.O. ROOF 18' - 10 1/2" SINGLE-PLY MEMBRANE ROOFING O/ TAPERED RIGID INSULATION O/ METAL DECK T.O. MODULAR PARAPET FRAMING 12' - 6" ALUM SUNSHADE B 7. PREBOOKING / BOOKING HALL 107 113 CONC FILLED MTL DECK CONC FOUNDATION SYSTEM 8. FINISH FLOOR 0" B SITE BUILT COMPONENT IS DESIGNED TO BE STRUCTURALLY INDEPENDANT OF THE MODULAR STRUCTURE. MOVEMENT JOINTS BETWEEN THE TWO STRUCTURES ARE NOT PART OF THE MODULAR CONTRACT. WHILE MODULAR MANUFACTURER IS NOT RESPONSIBLE FOR INSTALLATION OF MOVEMENT JOINTS, COORDINATION OF INTERSECTION OF MODULAR COMPONENTS WITH DESIGN TEAM TO DEVELOP INTERSECTION DETAILS WITH SITE BUILT COMPONENTS IS PART OF THE SCOPE. L-4001 CAMPUS SAFETY CENTER PROJECT WILL ULTIMATELY GO THROUGH DIVISION OF THE STATE ARCHITECT (DSA) FOR REVIEW. WHILE NOT REQUIRED, PC DRAWINGS FOR MODULAR BUILDING COMPONENETS ARE PREFERRED TO FACILITATE REVIEW. C LOS MEDANOS COLLEGE 2700 E LELAND ROAD, PITTSBURG, CA 94565 C NO. BUILDING SECTION 1/4" = 1'-0" ISSUE DATE LEGEND: C3 SITE BUILT CONSTRUCTION - NIC NOT IN SCOPE D D A B C K3 C.1 D D.9 MODULAR CONSTRUCTION E A3.21M MODULAR MANUFACTURER COORDINATION WITH DESIGN TEAM REQUIRED T.O. ROOF 18' - 10 1/2" 12" 1 1/2" SINGLE-PLY MEMBRANE ROOFING O/ TAPERED RIGID INSULATION O/ METAL DECK E E T.O. MODULAR PARAPET FRAMING 12' - 6" ALUM SUNSHADE DISPATCH/ RECEPTION LIEUTENANT CONC FILLED MTL DECK F 122 121 CONC MOW STRIP HALL INTERVIEW 107 104 STORAGE F 103 CONC FOUNDATION SYSTEM FINISH FLOOR 0" IT T LI E A R CH EC C FILE NO.7-C1 ED NS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 XX-XXXXXX 1/4" = 1'-0" G3 RENEWAL DATE NI E AT BUILDING SECTION G ST G A 5-31-17 O F C A LI F O R ARCHITECT'S STAMP 1 1.1 2 3 3.4 3.8 4 5 5.6 5.8 6 7 8 G3 C3 A3.21M A3.21M AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. T.O. ROOF 18' - 10 1/2" H H CONSULTANT SINGLE-PLY MEMBRANE ROOFING O/ TAPERED RIGID INSULATION O/ METAL DECK T.O. MODULAR PARAPET FRAMING 12' - 6" COORDINATE INTERFACE J J LOBBY HALL 101 107 RECORDS PATROL / REPORT 109 111 PREBOOKING / BOOKING BUILDING SECTIONS MODULAR CONC FILLED MTL DECK 113 CONC FOUNDATION SYSTEM FINISH FLOOR 0" PROJECT NO: 985-0007 1/25/2016 11:36:23 AM DATE: 01.22.2016 K K BUILDING SECTION 1/4" = 1'-0" 12 11 10 9 8 7 6 5 4 3 SHEET NO: A3.21M K3 2 1 MODULAR BID PACKAGE 12 11 10 9 WP1 A 8 7 6 5 4 WP1 3 P4 2 1 A P4 03 P4 OPEN TO BEYOND 06 07 09 PL1 PL1 09 CT2 B B1 B1 113 BOOKING B11 1/4" = 1'-0" 1/4" = 1'-0" 111 PATROL/REPORT B8 1/4" = 1'-0" 111 PATROL/REPORT B6 B A9.10M A9.10M 113 BOOKING B1 B1 B1 111 PATROL/REPORT B4 1/4" = 1'-0" 1/4" = 1'-0" B2 LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER RESTROOM ACCESSORIES 2700 E LELAND ROAD, PITTSBURG, CA 94565 NOTE: ACCESSORIES TO BE STAINLESS STEEL, SEE SHEET A0.40 FOR MOUNTING HEIGHTS OF ACCESSORIES, ALL O.F.C.I. ACCESSORIES TO BE APPROVED BY ARCHITECT AND DSA BEFORE INSTALLATION. P1 C P1 P1 P1 01 COMBINATION SEMI-RECESSED TOILET TISSUE DISPENSER, SEAT COVER, AND SANITARY NAPKIN DISPOSAL, MFR: BOBRICK, MODEL # B-3574 02 SOAP DISPENSER, SURFACE-MOUNTED, O.F.C.I. 03 TOILET PARTITION, MFR: BRADLEY, MODEL STAINLESS STEEL SERIES 700 FLOOR-TO-CEILING 04 PAPER TOWEL DISPENSER, SURFACE MOUNTED, O.F.C.I. 05 WASTE RECEPTACLE, O.F.O.I. 06 36" GRAB BAR, MFR: BOBRICK, MODEL # B-6806 SERIES 07 48" GRAB BAR, MFR: BOBRICK, MODEL # B-6806 SERIES 08 GLASS MIRROR, MFR: BOBRICK, MODEL # B-165 2460 09 COMBI TOILET / SINK, MFR: ACORN, MODEL #1449 04 08 06 C NO. ISSUE DATE 02 07 T2 T2 T2 01 T2 D 117 RESTROOM (115 SIM OPP HAND) 117 RESTROOM (115 SIM OPP HAND) D11 1/4" = 1'-0" 1/4" = 1'-0" D8 117 RESTROOM (115 SIM OPP HAND) 1/4" = 1'-0" D6 117 RESTROOM (115 SIM OPP HAND) D D4 1/4" = 1'-0" E E DIAGONALLY HATCHED AREA NOT IN MODULAR SCOPE, TYP TOP OF WALL IN MODULAR SCOPE P1 P1 F F STL COLUMN UNDER SITEBUILT CONTRACT COORDINATE W/ ARCHITECT STL COLUMN UNDER SITEBUILT CONTRACT COORDINATE W/ ARCHITECT P1 P1 PL1 PL1 FILE NO.7-C1 P1 A R CH IT T LI E ED NS EC C PL1 IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON B1 B1 B1 C-31285 E AT RENEWAL DATE A G ST G XX-XXXXXX 5-31-17 A9.10M NI B1 B1 O F C A LI F O R ARCHITECT'S STAMP 122 DISPATCH 1/4" = 1'-0" 122 DISPATCH G11 1/4" = 1'-0" 122 DISPATCH G8 1/4" = 1'-0" 122 DISPATCH G6 G4 1/4" = 1'-0" INTERIOR MATERIALS LEGEND C1 302 2' - 7 1/4" W 326 4' - 3" W 15" D 15" D D5 B5 A9.10M A9.10M 2' - 0" H 1' - 11" MICRO. 3' - 3" RF1 MICRO. P4 2' - 10" 154 3' - 0" W 24" D B7 B1 RESILIENT LINOLEUM SHEET FLOORING MANUFACTURER: FORBO PRODUCT: MARMOLEUM TEXTURE: STRIATO COLOR: FRESH WALNUT 5229 1/25/2016 11:36:27 AM 1/4" = 1'-0" K3 T2 CERAMIC WALL TILE MANUFACTURER: DAL-TILE PRODUCT: MODERN DIMENSIONS COLOR: TO BE SELECTED BY ARCHITECT WP1 FRP WALL PANELS MANUFACTURER: MARLITE PRODUCT: INDURO COLOR: TITANIUM B1 RUBBER BASE MANUFACTURER: PRODUCT: COLOR: CONSULTANT JOHNSONITE TRADITIONAL 4" TO BE SELECTED BY ARCHITECT P1 INTERIOR PAINT MANUFACTURER: TBD PRODUCT: COLOR: "WHITE" (TO MATCH EP1) P2 INTERIOR PAINT ACCENT COLOR MANUFACTURER: TBD PRODUCT: COLOR: "GRAY" (TO MATCH EP2) P3 INTERIOR PAINT ACCENT COLOR MANUFACTURER: PRODUCT: COLOR: "RED" (TO MATCH EP3) P4 INTERIOR PAINT ACCENT COLOR MANUFACTURER: PRODUCT: COLOR: ACCENT COLOR TBD K SC1 J INTERIOR ELEVATIONS PROJECT NO: 985-0007 DATE: 01.22.2016 K SHEET NO: SEALED CONCRETE A5.01M 12 11 10 9 8 7 6 5 4 3 APPROVAL H A9.10M A9.10M 119 BREAKROOM SS THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. CERAMIC FLOOR TILE MANUFACTURER: DAL-TILE PRODUCT: KEYSTONES COLOR: TO BE SELECTED BY ARCHITECT H1 FLS THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. PATCRAFT T1 J 254 1' - 3" W 24" D CARPET TILE MANUFACTURER: PRODUCT: TEXTURE: COLOR: AC DATE 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 A 5 3 2 1 REFLECTED CEILING PLAN GENERAL NOTES K3 B 4 C A3.21M C.1 D D.9 E 1. SEE SHEET A2.31M FOR MATERIALS LEGEND. 2. ELEVATIONS SHOWN ARE RELATIVE TO FINISH FLOOR. 3. ALL GYP. BOARD CEILINGS AND UNDERSIDE OF SOFFITS TO BE PAINTED P1 U.O.N. 4. SEE SHEET A9.60M FOR TYPICAL CEILING DETAILS. 5. UNLESS OTHERWISE NOTED, CENTER ACOUSTICAL CEILING GRID IN ROOM IN BOTH DIRECTIONS. 6. SEE ELECTRICAL DRAWINGS FOR LUMINAIRE SCHEDULE. A A 1 1 1.1 1.1 B B REFLECTED CEILING PLAN LEGEND LOS MEDANOS COLLEGE AC1, UNLESS OTHERWISE NOTED ON CEILING PLAN 2 L-4001 CAMPUS SAFETY CENTER 2 GYPSUM BOARD CEILING O/ MTL STUD FRAMING 2700 E LELAND ROAD, PITTSBURG, CA 94565 CEILING HEIGHT ABOVE FINISH FLOOR 11'-0" C SUSPENDED LIGHT FIXTURE -SEE ELECTRICAL C RECESSED DOWNLIGHT FIXTURE - SEE ELECTRICAL NO. 3 G3 SURFACE MOUNTED LIGHT FIXTURE - SEE ELECTRICAL INTERVIEW 122 A3.21M 2x4 LIGHT FIXTURE - SEE ELECTRICAL 104 LIEUTENANT 3.4 3.4 OPEN TO ABOVE 121 DATE PENDANT LIGHT FIXTURE - SEE ELECTRICAL 3 DISPATCH/ RECEPTION ISSUE OPEN TO ABOVE 9' - 0" EXTERIOR LIGHT FIXTURE - SEE ELECTRICAL IT D EMERGENCY EXIT SIGN - SEE ELECTRICAL D 106 RECESSED LINEAR FIXTURE - SEE ELECTRICAL 3.8 3.8 MOD-LINE BEAMS 9' - 0" AREA REQUIRING COORDINATION WITH SITE BUILT 4 CORPORAL 120 9' - 0" E BREAK ROOM 119 5 9' - 0" PARKING OFFICER 5.6 F 118 4 EVIDENCE STORAGE 108 LOST & FOUND RECORDS 110 109 E 9' - 0" 9' - 0" 5 POLICE AIDE EQUIP EQ 112 EQ 5.6 F 9' - 0" PATROL / REPORT 5.8 5.8 EQ 111 9' - 0" 9' - 0" 6 EQ 6 FILE NO.7-C1 A R CH IT 117 115 TROY PENNINGTON C-31285 ST E AT G RENEWAL DATE O F C A LI F O R AC DATE FLS SS 9' - 0" HALL ARCHITECT'S STAMP EQ 6' - 0" EQ 7 7 MEN 116 114 113 6' - 0" WOMEN PREBOOKING / BOOKING APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. 107 H XX-XXXXXX 5-31-17 G 9' - 0" IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES A RESTROOM NI RESTROOM T LI E ED NS EC C 9' - 0" THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 9' - 0" H C3 A3.21M 9' - 0" LOCKER ROOM LOCKER ROOM 116A 114A EQ CONSULTANT 9' - 0" 8 8 J J STL CANOPY - PAINT EP1 REFLECTED CEILING PLAN - MODULAR PROJECT NO: 985-0007 1/25/2016 11:36:28 AM DATE: 01.22.2016 K K N A B D D.9 E REFLECTED CEILING PLAN - MODULAR 1/4" = 1'-0" 12 11 10 9 8 7 6 5 4 3 SHEET NO: A6.01M K3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 2 LAYERS BUILDING PAPER HEADER - SEE STRL FOR SIZES 9" S.A.F. A A 3 COAT CEMENT PLASTER SYSTEM O/ SELF-FURRING LATH 6" S.A.M. 8" S.A.M. RIGID INSULATION O/ MAT FACED GYP SHEATHING J BEAD W/ WEEP METAL FLASHING SLOPED TO DRAIN ALUM WINDOW 5/8" GYP BD L TRIM & SEALANT B B WINDOW HEAD AT CEMENT PLASTER 3" = 1'-0" B1 LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER SHIM AS REQUIRED ALUM WINDOW 2700 E LELAND ROAD, PITTSBURG, CA 94565 3/4" MDF WINDOW SILL WITH SEALANT SEALANT C 4" S.A.M. C NO. ISSUE DATE 1' - 0" S.A.M. J-BEAD (NO WEEP) o/ WINDOW FIN RIGID INSULATION O/ MAT FACED GYP SHEATHING D D BUILDING PAPER WINDOW SILL AT CEMENT PLASTER 3" = 1'-0" D1 2 LAYERS BUILDING PAPER RIGID INSULATION O/ MAT FACED GYP SHEATHING J MOLD BACKER ROD & SEALANT (1/4" MIN.-3/8" MAX) E E 6" S.A.M. 8" S.A.M. ALUM WINDOW L TRIM & SEALANT 5/8" GYP BD F F WALL - TYPE PER PLAN MTL CORNER BEAD WINDOW JAMB AT CEMENT PLASTER 3" = 1'-0" F1 FILE NO.7-C1 C A R CH IT T LI E ED NS EC NOTE: PROVIDE LABELED DOOR AND FRAME AT RATED CONDITION. IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 A RENEWAL DATE NI E AT G ST G XX-XXXXXX 5-31-17 12" S.A.F. TO WRAP INTO DOOR OPENING O F C A LI F O R 8" S.A.F. OVER G.S.M. DRIP 6" S.A.F. OVER J-MOLD CONT. SEALANT BEAD ARCHITECT'S STAMP J-MOLD PLASTER STOP, PAINT TO MATCH PLASTER FINISH SS APPROVAL THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. A8.31M SEALANT FLS THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. METAL DRIP FLASHING "I", PAINT TO MATCH DOOR FRAME, SEE K3 ANCHOR PER AC DATE HM FRAME PER SCHEDULE DOOR PER SCHEDULE FRAME WIDTH TO BE DETERMINED H H BY OVERALL WALL WIDTH + 1 1/4" CONSULTANT H.M. DOOR HEAD AT PLASTER FINISH 3" = 1'-0" VARIES 3/8" 3/8" J NOTE: PROVIDE LABELED DOOR AND FRAME AT RATED CONDITION. SHT. MTL. DIVERTER FLASHING w/ 1/2" LEG SLOPE H1 J-BEAD PLASTER STOP WITH BACKER ROD & SEALANT JAMB ANCHOR PER DOOR MFR. S.A.F., WRAP INTO DOOR OPENING DOOR PER SCHED. H.M. DOOR FRAME J 4" EXTERIOR WINDOW / DOOR DETAILS 4" THRESHOLD FLASHING "G" 8" SLOPE TO DRAIN VARIES PROJECT NO: 985-0007 MIN. MIN. TO WALL OR OBSTRUCTION, DOOR OPENING TYP. BOTH SIDES SEE DOOR SCHED. K VARIES HEAD FLASHING "I" 3" = 1'-0" 11 10 9 8 7 6 5 4 K TRESHOLD FLASHING "H" DOOR FLASHING PROFILES 12 4" 4" 1/25/2016 11:36:30 AM 2" 1/ DBL. STUD JAMB FRMG., TYP. CONT. SEALANT BEAD 3/8" 3" DATE: 01.22.2016 3 K3 H.M. DOOR JAMB AT PLASTER FINISH 3" = 1'-0" 2 1 K1 SHEET NO: A8.31M MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 NOTE: ELECTRICAL BOXES ON OPPOSITE SIDES OF WALL SHOULD BE OFFSET FROM EACH OTHER A MINIMUM OF 24" 3/8" BULLET RESISTANT FIBERGLASS PANEL PROTECTION LEVEL 2 A 6" X 20GA METAL STUDS @ 16" O.C. (2) LAYERS 5/8" GYPSUM BOARD NOTE: WHERE FACE LAYER OF GYPSUM BOARD OF THIS WALL DOES NOT ALIGN WITH THE GYPSUM BOARD FINISH OF AN ADJACENT WALL TYPE, ADDITIONAL LAYER(S) OF GYPSUM BOARD SHALL BE ADDED ALONG THE ADJACENT WALL TO ALIGN THE FINISHES. THE ADDITIONAL LAYER(S) SHALL CONTINUE UNTIL THE SURFACE IS INTERRUPTED BY AN INTERSECTING WALL, COLUMN, OR OTHER NATURAL TRANSITION POINT. 5/8" DENSSHIELD TILE BACKER BOARD A 1/2" MAT FACED GYP BOARD 5/8" GYPSUM BOARD 3 5/8" x 20GA MTL STUDS @ 16"O.C. (MAX) 6" x 20 GA METAL STUDS @ 16" O.C. VENEER ONE SIDE ACOUSTIC BATT INSULATION 5/8" GYP 5/8" GYP (1 SIDE) FIRE RATING: NA. GA FILE NO.: NA ACOUSTICAL RATING: NA B FIRE RATING: NA. GA FILE NO.: NA ACOUSTICAL RATING: NA2 FIRE RATING: NA GA FILE NO.: NA ACOUSTICAL RATING: 50 PENETRATIONS: ACOUST. SEAL ALTERNATE 6" MTL GYP-BULLET/GYP 3" = 1'-0" 3" = 1'-0" 3 5/8" MTL GYP / VENEER IS0-50-00 3" = 1'-0" NOTE: WHERE FACE LAYER OF GYPSUM BOARD OF THIS WALL DOES NOT ALIGN WITH THE GYPSUM BOARD FINISH OF AN ADJACENT WALL TYPE, ADDITIONAL LAYER(S) OF GYPSUM BOARD SHALL BE ADDED ALONG THE ADJACENT WALL TO ALIGN THE FINISHES. THE ADDITIONAL LAYER(S) SHALL CONTINUE UNTIL THE SURFACE IS INTERRUPTED BY AN INTERSECTING WALL, COLUMN, OR OTHER NATURAL TRANSITION POINT. 5/8" HIGH IMPACT GYP BD C 6" MTL 2GYP/1GYP IS0-00-11 B IS0-50-07 LOS MEDANOS COLLEGE L-4001 CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 6" x 20GA MTL STUD @ 16" O.C. (MAX) C 5/8" GYP (1 LAYER EA. SIDE) (2) LAYERS 5/8" GYP. BOARD NO. 3 5/8" X 20 GA METAL STUDS @ 16" O.C. ISSUE DATE 3 5/8" x 20 GA METAL STUDS @ 16" O.C., TYPICAL 5/8" GYP. BOARD 5/8" GYP (1 SIDE) BATT INSULATION FRP ONE SIDE FIRE RATING: NA. GA FILE NO.: NA ACOUSTICAL RATING: NA D FIRE RATING: 0 HOUR GA FILE NO.: NA ACOUSTICAL RATING: 50-54 PENETRATIONS: ACOUST. SEAL 3 5/8" MTL IMPACT GYP-FRP / GYP 3" = 1'-0" FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: N/A 3-5/8" MTL 2GYP/1GYP IS0-00-12 3" = 1'-0" D 6" MTL / GYP EA SIDE IS0-50-01 3" = 1'-0" IS0-00-08 3 5/8" x 20 GA METAL STUDS @ 16" O.C. (MAX) E E 5/8" TYPE "X" EA. SIDE 5/8" GYPSUM BOARD 5/8" GYPSUM BOARD 3 5/8" x 20GA METAL STUDS @ 16" O.C. (MAX) 3 5/8" X 20GA METAL STUDS @ 16" O.C., TYPICAL 3/4" PLYWOOD BATT INSULATION BATT INSULATION FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: N/A F FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: 45 FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: N/A 3 5/8" MTL PLY/GYP 3" = 1'-0" 3 5/8" MTL FURRING IS0-00-13 3" = 1'-0" F 3-5/8" MTL GYP / GYP IS0-00-04 3" = 1'-0" IS0-45-01 IT T LI E A R CH EC C FILE NO.7-C1 ED NS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON C-31285 6" X 20GA METAL STUDS @ 16" O.C. 5/8" GYPSUM BOARD 5/8" DENSSHIELD 3" = 1'-0" A R AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: N/A 6" MTL PLY / GYP O F C A LI F O THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: N/A H RENEWAL DATE ARCHITECT'S STAMP TILE/ VENEER 3/4" PLYWOOD E NI G AT 3 5/8" x 20GA METAL STUDS @ 16" O.C. (MAX) ST G XX-XXXXXX 5-31-17 H CONSULTANT 3-5/8" MTL / VEN. 1 SIDE IS0-00-14 3" = 1'-0" NOTE: WHERE GYP. SHTG. IS INSTALLED OVER STRUCTURAL SHTG., THE LENGTH OF FASTENERS SHALL BE INCREASED BY AN AMOUNT EQUAL TO THE THICKNESS OF THE STRUCTURAL SHTG. IS0-00-01 5/8" TYPE 'X' GYP. BOARD (1 LAYER ) (2 LAYERS) GRADE "D" BLDG. PAPER J J 6" X 20GA METAL STUDS @ 16" O.C., TYPICAL EXTERIOR & INTERIOR WALL ASSEMBLIES 1" RIGID INSULATION 3 COAT CEMENT PLASTER SYSTEM SELF-FURRING METAL LATH PROJECT NO: 985-0007 BATT INSULATION DATE: 01.22.2016 1/25/2016 11:36:32 AM 5/8" MAT FACED GYP FIRE RATING: N/A GA FILE NO.: N/A ACOUSTICAL RATING: N/A K K 6" MTL W/ PLASTER W/1"RIGID 3" = 1'-0" 12 11 10 9 8 7 6 5 4 3 2 ES0-00-01 1 SHEET NO: A9.00M MODULAR BID PACKAGE 10 9 8 7 6 5 4 3 2 X 6 FLAT BLOCKING P-LAM. COUNTERTOP, UNO - SEE FINISH SCHEDULE FOR MORE INFORMATION 2 6 X 16 GA. CONTINUOUS SHEET METAL STUD COUNTERTOP WITH INTEGRAL BACK SPLASH, SIDE SPLASH (WHERE OCCURS), AND FACE PIECE OVER 3/4" PLYWD. AS REQUIRED FOR COUNTER AND LAVATORY SUPPORT 1'-0" U.O.N. WIRE PULLS, TYP MAX BACK PANEL SHALL BE MELAMINE OVER 1/2" MDF BOARD 3' - 3" STEEL MACHINE SCREW. BACK PANEL SHALL BE MELAMINE OVER 1/2" MDF BOARD #14 X 3" MODIFIED TRUSS HEAD SCREW @ 16" O.C. MIN. 2 PER CABINET 1' - 3" 2' - 4 1/2" 2' - 10" MAX SITE BUILT WALL (4) EQ SPACES MOVEMENT JOINT BY SITE BUILT CONTRACTOR 2' - 0" DRAWER UNIT W/ MTL. GLIDE HARDWARE WALL TYPE PER PLAN TYP. TBD TYPICAL BLOCKING AT WOOD STUDS TBD NOTE: CABINET INTERIORS SHALL BE MELAMINE, COLOR TO BE SELECTED BY ARCHITECT RESILIENT BASE TO MATCH ROOM BASE CABINET WITH DRAWERS 1" = 1'-0" MOVEMENT JOINT BY SITE BUILT CONTRACTOR 1" = 1'-0" B5 BLOCKING FOR WOOD OR METAL STUDS 3" = 1'-0" B COUNTERTOP B3 1" = 1'-0" B1 L-4001 CAMPUS SAFETY CENTER A9.10M LINE OF WALL W.O. SHEET METAL SCREW (#14 @ 12" O.C. MIN 3 PER SIDE) INTO MTL STUD BACKING D FLOORING TO CONTINUE UNDER COUNTER TO BACK WALL MOVEMENT JOINT BY SITE BUILT CONTRACTOR SINK CABINET W/INTEGRAL TOE SPACE 1" = 1'-0" J TRIM NOTE: CABINET INTERIORS SHALL BE MELAMINE, COLOR TO BE SELECTED BY ARCHITECT NOTE: ENTIRE FABRICATION TO BE PAINTED BLACK U.O.N. WALL CABINET W/DOORS H1 MITER & WELD CORNER 1" = 1'-0" 1/2" = 1'-0" DATE 2'0" 8" 8" 3" (2) STEEL STUD FRAMING. 16 GA. MIN. BRACE @ 36" O.C. MAX D 2" x 2" x 1/4" HSS W/ 1/8" PL CAP ON EXPOSED END - GRIND SMOOTH & PAINT CONCEALED BRACE SUPPORT-STEEL D3 ISSUE ISOMETRIC VIEW 5" PLAN VIEW COUNTER SUPPORT PLAN VEIW D5 C NO. 7" INTERIOR OF CASEWORK TO BE HPDL TO MATCH EXTERIOR, TYP ALUM CURTAINWALL SYSTEM 27" MIN. A.F.F. KNEE CLEARANCE 1/2" DIA. BOLT THRU STUDS AT BRACE (MIN 3 PER BRACE) WELD CONNECTION & GRIND SMOOTH, TYP. U-SHAPED WIRE PULL, TYP. WRAP SINK PIPES, DRAIN PIPES AND TRAPS PER TITLE 24 REQUIREMENTS WOOD SCREWS #12 X 3/4" (3) PER BRACE - DRILL THROUGH FACE OF HSS COUNTERTOP ATTACHED TO SUPPORT FRAME WITH WOOD SCREWS AT 8" O.C.. PLASTIC LAMINATE DOORS, U.O.N. 2700 E LELAND ROAD, PITTSBURG, CA 94565 34" MAX. A.F.F. 7" RESILIENT BASE TO MATCH ROOM 1'-0" U.O.N. BACK PANEL SHALL BE MELAMINE OVER 1/2" MDF BOARD SINK - SEE PLUMBING FIXTURE SCHEDULE CLR 2' - 3" MIN 2' - 10" MAX C11 T.O. RIM 5" FIXED PANEL C D1 LOS MEDANOS COLLEGE SECTION STEEL ANGLE (2" X 3" X 1/4"), TYP. CLIP VERT LEG AT CONCEALED BRACE SUPPORT 3" P-LAM. COUNTERTOP - SEE FINISH PLANS 2' - 0" U.O.N. WALL TYPE PER PLAN ADJUSTABLE SHELVES, TYP. SHELVES SHALL BE MELAMINE OVER 3/4" MDF BOARD. 5MM DIA. HOLES AT 32MM CENTERS FOR SHELVES 3" 1 1/2" 2'-0" U.O.N. CONCEALED BRACE WHERE OCCURS 4" HIGH BACK SPLASH AND SIDE SPLASH (WHERE OCCURS) 1'-8" 3 COAT CEMENT PLASTER SYSTEM 3" = 1'-0" D1 A9.10M EQ.EQ. J TRIM INSIDE CORNER AT MODULAR INTERSECTION WALL CABINET W/OPEN SHELVING B7 TYPICAL BLOCKING AT METAL STUDS NOTE: EACH CABINET OR UNDIVIDED SPAN SHALL HAVE A MINIMUM OF 4 ANCHORAGE FASTENERS; 2 AT TOP AND 2 AT BOTTOM. MAXIMUM HORIZONTAL SPACING TO BE 16" O.C. OR 12" O.C. IF CABINET OVER 48"H. ANCHORAGE FASTENERS TO BE LOCATED WITHIN 2" OF THE OUTSIDE TOP OR BOTTOM AND WITHIN 2" OF THE OUTSIDE END 4" B A 2'-10" MAX. T.O. A B3 A9.10M ADJUSTABLE SHELVES, TYP. SHELVES SHALL BE MELAMINE OVER 3/4" MDF BOARD. 5MM DIA. HOLES AT 32MM CENTERS FOR SHELVES B3 TYP. A9.10M 4" U.O.N. 1 1/2" 2' - 0" 1 27" MIN. KNEE CLEARANCE 11 FINISH FLOOR 12 1" = 1'-0" D1 TBD 3 COAT CEMENT PLASTER SYSTEM DOOR AS SCHEDULED 3 COAT CEMENT PLASTER SYSTEM TBD SELF-FURRING LATH DOOR FRAME BEYOND, SEE DOOR SCHEDULE LAP MOISTURE BARRIER OVER SELF-ADHERED FLASHING SELF-ADHERED FLASHING E 4' - 0" E MAT FACED GYP SHEATHING TAPERED RIGID INSULATION @ ROOF DRAINS FINISH PER FINISH PLAN / SCHEDULE 1/4" MAX TILE WALL TYPE PER PLAN H3 3' - 0" 1/2" ALUM. TRANSITION STRIP W/ 2:1 SLOPE MAX. A9.10M ALUM REVEAL - WEEP CHANGE FLOORING UNDER CENTERLINE OF DOOR INSIDE CORNER AT MODULAR INTERSECTION 3" = 1'-0" ALUMINUM REVEAL - HORIZONTAL F11 6" = 1'-0" TILE TO RESILIENT TRANSITION F9 6" = 1'-0" SHEET METAL CLOSURE BY SITE BUILT CONTRACTOR F ROOF DRAIN PLAN F3 3/4" = 1'-0" ROOF DRAIN F1 FILE NO.7-C1 OVERFLOW DRAIN INTERIOR WALL BY SITE BUILT CONTRACTOR C LI SLOPE G T.O. SUNSHADE 13'-9" 2" INTERIOR WALL BY SITE BUILT CONTRACTOR RENEWAL DATE O F C A LI F O R K1 A9.10M SHEET METAL CLOSURE BY SITE BUILT CONTRACTOR MODULAR STRUCTURE WALL TYPE PER PLAN WALL TYPE PER PLAN STEEL ANGLE GSM - PAINT TO MATCH DECK DECK CLAMP NOTES: AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. METAL DECK COMPRESSIBLE INSULATION 1' - 3" E ARCHITECT'S STAMP MOVEMENT JOINT BY SITE BUILT CONTRACTOR H XX-XXXXXX 5-31-17 TBD EQ C-31285 AT EQ TBD IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES TROY PENNINGTON ST 1" X 3" ALUMINUM FRAME G SINGLE PLY MEMBRANE ROOFING O/ COVER BOARD & RIGID INSULATION CLAMP RING IT T EXTRUDED ALUM. BARS @ 2 1/2" OC E A R CH EC 2' - 0" ED NS A F NI MOISURE BARRIER - EXTEND UP BEHIND REVEAL THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 4" RIGID INSULATION 3/4" FIRE TREATED PLYWD 1. MODULAR STRUCTURE 4" X 7" X 1/4" ALUMINUM PLATE WELDED TO VERT. POST 2" X 2" 1/8" ALUM. ANGLE EACH SIDE OF 1"x3" FRAME MOD LINE 2. MODULAR STRUCTURE 3. 4. METAL BRACKET PER SUNSHADE MANUF. WELDED TO VERT. POST WALL JOINT AT INTERVIEW 3" = 1'-0" OUTSIDE CORNER AT EVIDENCE STORAGE H7 3" = 1'-0" ALL DRAIN BOLTS OR CLAMPS MUST BE IN PLACE TO PROVIDE COMPRESSION ON WATER-BLOCK MASTIC. CUT MEMBRANE SO IT EXTENDS MIN. OF 1/2" FROM ATTACHMENT JOINTS OF THE CLAMP RING. APPROX. 1/8" DIAMETER BEAD OF CUT-EDGE SEALANT IS REQUIRED ON ALL CUT EDGES OF MEMBRANE. FILL PENETRATION VOID WITH BATT INSULATION. INSTALL RIGID INSULATION UNDER DRAIN AS SHOWN. H CONSULTANT ROOF DRAIN SECTION H5 1" = 1'-0" H3 T.O.P. 12'-6" PRE-FINISHED ALUM CAP FLASHING 6" WALL TYPE PER PLAN 1' - 0" TBD 4" X 4" X 1/4" VERTICAL METAL POST J INTERIOR WALL BY SITE BUILT CONTRACTOR INTERIOR WALL BY SITE BUILT CONTRACTOR SEAL AT PENETRATION ROOF DRAIN ASSEMBLY W/ DOMED STRAINER WATER BLOCK MASTIC ALL AROUND OVERFLOW DAM 2" ABOVE ROOF DRAIN FLOW LINE AT OVERFLOW DRAIN SINGLE PLY MEMBRANE ROOFING J COVER BOARD TAPERED RIGID INSULATION (1:12 MAX. SLOPE) 4" X 6" X 1/4" METAL BRACKET INTERIOR / EXTERIOR DETAILS PROJECT NO: 985-0007 DATE: 01.22.2016 1/25/2016 11:36:34 AM SINGLE PLY ROOFING MEMBRANE WRAP OVER TOP OF PARAPET RAINWATER LEADER 4" X 4" X 1/4" METAL BRACKET K MOVEMENT JOINT BY SITE BUILT CONTRACTOR MOVEMENT JOINT BY SITE BUILT CONTRACTOR METAL DECK PROFILE MAY VARY WALL TYPE PER PLAN WALL TYPE PER PLAN K HEAT WELD SECTION AT SUNSHADE 3" = 1'-0" 12 11 10 9 WALL JOINT AT INTERVIEW K9 3" = 1'-0" 8 7 WALL JOINT AT INTERVIEW K7 3" = 1'-0" 6 5 ROOF DRAIN ASSEMBLY K5 1 1/2" = 1'-0" 4 3 2 1 K1 SHEET NO: A9.10M MODULAR BID PACKAGE 10 9 8 7 6 5 4 3 2 METAL STRUT SLOTTED AT MAIN RUNNER AND CROSS RUNNER, TYP. F5 4' - 0" NOTES 1. LIGHT FIXTURES AND MECHANICAL GRILLES WEIGHING LESS THAN 54 POUNDS: INSTALL MIN. TWO 12 GA. SLACK WIRES AT DIAGONAL CORNERS. SURFACE OR CEILING GRID MOUNTED LIGHT FIXTURES AND MECHANICAL GRILLES WEIGHING MORE THAN 54 POUNDS: SUPPORT INDEPENDENTLY WITH TAUT WIRES CAPABLE OF SUPPORTING 4 TIMES THE WEIGHT OF THE ITEM. CEILING SYSTEM TO BE HEAVY DUTY. ATTACH ALL FIXTURES TO GRID RUNNERS TO RESIST HORIZONTAL FORCE EQUAL TO WEIGHT OF FIXTURE/GRILLE. 8" MAX. TYP. OR 1/4 THE LEGNTH OF END T (WHICHEVER IS LESS) A9.60M MAX. F3 F5 A9.60M A9.60M SUSPENDED CEILING SYSTEM CROSS RUNNER 8" MAX. TYP. SUSPENDED CEILING SUPPORT WIRE AT 4'-0" O.C. EA. WAY HEAVY DUTY MAIN RUNNER F3 A9.60M A9.60M A9.60M B 4-SPLAY BRACE WIRES AT 90 DEGREES, @ 12'-0" O.C. (NO SPLICING ALLOWED) EACH WAY ACOUSTICAL CEILING SPLAY LAYOUT 1/8" = 1'-0" 12GA. SPLAY BRACE WIRE (NO SPLICING ALLOWED) W/4 TIGHT TURNS IN 2" TYP. C GENERAL NOTES: COMPRESSION STRUT, SEE E F7 . YP "T -0 4' 45 SEE RCP H7 A9.60M A9.60M 45 S 6" MIN. 45 SEE RCP 12GA. HANGER WIRE AT 4'-0" O.C. W/ NO SPLICES BULKHEAD @ CEILING TRANSITION 1 1/2" = 1'-0" 12 GA. HANGER WIRE TYP. 4'-0" O.C. (3 TIGHT WRAPS) D 6. ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. ALL LIGHT FIXTURES SHALL BE ATTACHED SECURELY TO THE GRID WITH 4 SCREWS, ONE AT EACH CORNER OF THE FIXTURE. MAIN RUNNER, TYP. ACOUSTICAL CEILING SPLAY D7 7. WHEN DRILLED-IN CONCRETE ANCHORS ARE USED IN REINFORCED CONCRETE FOR HANGER WIRES, 1 OUT OF 10 MUST BE FIELD TESTED FOR 200 POUNDS OF TENSION. WHEN DRILLED-IN CONCRETE ANCHORS ARE USED FOR BRACING WIRES, 1 OUT OF 2 MUST BE FIELD TESTED FOR 440 POUNDS OF TENSION. SHOT IN ANCHORS IN CONCRETE ARE NOT PERMITTED FOR BRACING WIRE. IF ANY SHOT-IN OR DRILLED-IN ANCHOR FAILS, ALL ADJACENT ANCHORS MUST BE TESTED. NOTES: DRILLED-IN OR SHOT-IN ANCHORS REQUIRE SPECIAL INSPECTION WHEN USED IN PRESTRESSED CONCRETE. D5 1/8" = 1'-0" VERTICAL POST #6 S.M.S. @ 32" O.C. MAIN BEAM @ 4'-0" O.C. E 8. FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINALS OR SERVICES WEIGHING LESS THAN 56 POUNDS MAY BE SUPPORTED DIRECTLY ON THE RUNNERS OF A HEAVY DUTY GRID SYSTEM BUT, IN ADDITION, THEY MUST HAVE A MINIMUM OF TWO 12 GA. SLACK SAFETY WIRES ATTACHED TO THE FIXTURES AT DIAGONAL CORNERS AND ANCHORED TO THE STRUCTURE ABOVE. ALL 4 FT. X 4 FT. LIGHT FIXTURES MUST HAVE SLACK SAFETY WIRES AT EACH CORNER. #6 S.M.S. @ 32" O.C. 8" MAX. HANGER WIRE (12 GA.) CROSS TEES @ 2'-0" O.C. TIGHT SCREW 3 TIGHT TURNS WITHIN 1 1/2" MAIN RUNNER OR CROSS RUNNER 3/4" 10. SUPPORT SURFACE MOUNTED LIGHT FIXTURES BY AT LEAST TWO POSITIVE DEVICES WHICH SURROUND THE CEILING RUNNER AND WHICH ARE EACH SUPPORTED FROM THE STRUCTURE ABOVE BY A 12 GA. WIRE. SPRING CLIPS OR CLAMPS THAT CONNECT ONLY TO THE RUNNER ARE NOT ACCEPTABLE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT FIXTURES ARE 8 FT. OR LONGER. MAIN RUNNER OR CROSS RUNNER 7/8" 7/8" BRACING NOTES: 11. SUPPORT PENDANT MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE ABOVE WITH HANGER WIRES OR CABLES PASSING THROUGH EACH PENDANT HANGER AND CAPABLE OF SUPPORTING 4 TIMES THE WEIGHT OF THE FIXTURE. ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. SPECIAL DETAILS ARE NECESSARY FOR THIS CONDITION AT THE CEILING GRID. 1. VERTICAL POSTS MAY NOT BE REQUIRED IN SOME CITIES AND NOT ENFORCED IN ALL SEISMIC ZONES. SEISMIC CLIP PER MANUFACTURER 2. BRACING WIRES TO BE ATTACHED MAXIMUM OF 45 DEGREES TO THE PLANE OF THE CEILING AND PARALLEL TO THE COMPONENTS AT THE BRACING POINT. BRACE WIRES TO BE TAUT AND TIED AT BOTH ENDS WITH THREE TIGHT WRAPS COMPRESSION POST 1 1/2" = 1'-0" ATTACH TO STRUCTURE ABOVE OPEN END OF ACOUSTICAL CEILING 1/8" = 1'-0" COMPRESSION STRUCT (SEE TABLE BELOW) 45 MAX. T YP. MAX. LENGTH H 3 5/8" X 1 3/8" X 20 GA. (SCREWED TOGETHER @ 16" O.C.) SEE 24'-0" T-BAR CEILING GRID SYSTEM (MAIN OR CROSS RUNNER) SLOTTED ANGLE SPACER W/ HORIZ. STEEL PIN, BOTH TO RUN CONT. AT ALL FREE END T-BAR RUNNERS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 XX-XXXXXX 5-31-17 E RENEWAL DATE O F C A LI F O R AC DATE FLS SS 1/2" MIN. CLR. ARCHITECT'S STAMP APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2015. ACOUSTICAL CEILING TILE PER ASTM C635 AND ASTM C636 F3 A9.60M T-BAR CROSS RUNNER THRU CONNECTION W/ #6 S.M.S. TO CROSS RUNNERS ACOUSTICAL TILE CEILING SUSPENDED ACOUSTICAL CEILING SYSTEM EDGE TRIM ANGLE. ATTACH TO WALL STRUCTURE (NOT FINISH) W/ #10 S.M.S. AT EA. WALL STUD. 1" MIN. EMBED IN STUD 12'-0" EA. WAY B1 F1 A9.60M A9.60M FOR ADDITIONAL INFORMATION T-BAR MAIN RUNNER ACOUSTICAL TILE CEILING THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. SUSPENDED ACOUSTICAL CEILING SYSTEM EDGE TRIM ANGLE. ATTACH TO WALL STRUCTURE (NOT FINISH) W/ #10 S.M.S. AT EA. WALL STUD. 1" MIN. EMBED IN STUD SEISMIC CLIP - SEE F5 A9.60M H 5/8" TYPE 'X' GYPSUM BOARD CONSULTANT SUSPENDED ACOUSTICAL LAY-IN CEILING SYSTEM ATTACHMENTS 5/8" TYPE 'X' GYPSUM BOARD 1 1/2" = 1'-0" IT 1" MIN. SEISMIC CLIP - SEE COMPRESSION STRUT (STUD) E TROY PENNINGTON G ATTACH TO RUNNER W/ 2 # 8 SMS SCREW 12'-0" EA. WAY 12'-0" EA. WAY 12'-0" EA. WAY 12'-0" EA. WAY 12'-0" EA. WAY SPACING T-BAR CEILING GRID SYSTEM (MAIN OR CROSS RUNNER) A R CH T DOUBLE STUD SIZE A9.60M FILE NO.7-C1 ED NS EC 7'-0" 6'-9" 10'-1" 10'-1" 9'-11" 12 GA. HANGER OR SPLAY BRACE WIRES DRILL 5/32" HOLE & INSTALL 1/8" BOLT & LOCKNUT CROSS RUNNER SPACING F1 AT 2 1/2" X 25 GA. 3 5/8" X 25 GA. 1 5/8" X 20 GA. 2 1/2" X 20 GA. 3 5/8" X 20 GA. 1/2" = 1'-0" 12 GA. HANGER OR SPLAY BRACE WIRES 45 YP. T X. MA MAX. LENGTH SUSPENDED CEILING GENERAL NOTES 8" MAX. COMPRESSION STRUT SEE H7 MAIN RUNNER MAX. T YP. F3 8" MAX. 1/2" MIN. CLR. SINGLE STUD SIZE 1/8" = 1'-0" 12 GA. HANGER WIRE W/ (3) TIGHT TURNS WITHIN 1 1/2" 45 P. TY . X MA FIXED END OF ACOUSTICAL CEILING F5 F ST 12 GA. WIRE IN PLANE OF EACH RUNNER AT 45 DEGREES, SECURE 2" FROM INTERSECTION 45 G F7 SEISMIC CLIP PER MANUFACTURER 1 1/2" F E 9. ALL FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINALS OR SERVICES WEIGHING 56 POUNDS OR MORE MUST BE INDEPENDENTLY SUPPORTED BY NOT LESS THAN 4 TAUT 12 GA. WIRES, EACH ATTACHED TO THE FIXTURE AND TO THE STRUCTURE ABOVE REGARDLESS OF THE TYPE OF CEILING GRID SYSTEM USED. THE 4 TAUT 12 GA. WIRES INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE MUST BE CAPABLE OF SUPPORTING 4 TIMES THE WEIGHT OF THE UNIT. HANGER WIRE (12 GA.) 8" MAX. 3 TIGHT TURNS WITHIN 1 1/2" 12 GA. BRACE WIRES NOTE #2 DATE 5. SEPARATE ALL CEILING HANGING AND BRACING WIRES AT LEAST 6 INCHES FORM ALL UNBRACED DUCTS, PIPES, CONDUITS, ETC. 2" M AX 2" M AX METAL CORNER BEAD, PAINT TO MATCH ADJ. SURFACES, TYP. ACOUSTICAL CEILING SYSTEM ISSUE 4. FASTEN HANGER WIRES WITH NOT LESS THAN 3 TIGHT TURNS. FASTEN BRACING WIRES WITH 4 TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 11/2". HANGER OR BRACING WIRE ANCHORS TO THE STRUCTURE SHALL BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF THE WIRE ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE FORCES ON THAT WIRE. CONT. 20 GAUGE RUNNER D NO. 3. PROVIDE TRAPEZE OR OTHER SUPPLEMENTAL SUPPORT MEMBERS AT OBSTRUCTIONS TO MAIN HANGER SPACING. PROVIDE ADDITIONAL HANGERS, STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS OR DISCONTINUOUS AREAS. HANGER WIRES THAT ARE MORE THAN 1 IN 6 OUT OF PLUMB SHALL HAVE COUNTER-SLOPING WIRES. 5/8" GYPSUM BOARD OVER METAL STUDS 45 C 2. SPLICES WILL NOT BE PERMITTED IN ANY HANGER WIRES. CROSS RUNNER, TYP. W 2700 E LELAND ROAD, PITTSBURG, CA 94565 1. PROVIDE SETS OF FOUR 12 GA. SPLAYED BRACING WIRES ORIENTED 90 DEGREES FROM EACH OTHER AT THE FOLLOWING SPACING: A. PLACE SETS OF BRACING WIRES NOT MORE THAN 12 FT. X 12 FT. ON CENTER. B. PROVIDE BRACING WIRES AT LOCATIONS NOT MORE THAN 1/2 THE SPACING GIVEN IN 'A' ABOVE FROM EACH PERIMETER WALL AND AT THE EDGE OF VERTICAL CEILING OFFSETS. N A9.60M 4' -0 "T YP . PROVIDE DIAGONAL SUPPORT PER STRUCTURAL L-4001 CAMPUS SAFETY CENTER C B1 B1 LOS MEDANOS COLLEGE LI FOR ADDITIONAL INFO SEE A 2. TOTAL WEIGHT OF CEILING SYSTEM INCLUDING CEILING MOUNTED AIR TERMINALS, SERVICES, AND LIGHT FIXTURES DOES NOT EXCEED 4 PSF. CROSS RUNNER AT 2' X 4' CLG. TYP. COMPRESSION STRUCT AT 12'-0" O.C. EACH WAY, SEE H7 F7 B SUSPENDED CEILING SUPPORT WIRE AT PERIMETER MAX. 4' - 0" A 1 A 11 NI 12 H7 6" = 1'-0" H1 GYPSUM BOARD, W.O. GYPSUM BOARD STEEL STUD FRAMING J J TYPICAL CEILING DETAILS PROJECT NO: 985-0007 1/25/2016 11:36:36 AM WALL OR CEILING MOUNTED ACCESS DOOR, WITH PAINTED SURFACE, SEE FINISH PLAN (COLORS TO MATCH WALL/CEILING DATE: 01.22.2016 #10 S.M.S. @ 24" O.C. @ EA. SIDE K NON-RATED ACCESS PANEL 3" = 1'-0" 12 11 10 9 8 7 6 5 4 3 2 1 K K1 SHEET NO: A9.60M MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 A A B B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C C NO. D E E F F EN SE D ARCH DATE IT E C D ISSUE LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 A TE RENEWAL DATE OF CA NI ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J LEGEND, SYMBOLS, AND GENERAL NOTES PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K LEGEND, SYMBOLS, AND GENERAL NOTES NONE 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\M001.dwg, 1/25/2016 11:06:53 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: M0.01 DSA SUBMITTAL 12 11 10 9 8 7 A 6 B C 5 C.1 D D.9 4 3 2 1 E A A 1 1 1.1 1.1 EOC B B 102 LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2 2 2700 E LELAND ROAD, PITTSBURG, CA 94565 LOBBY 101 C C STORAGE NO. ISSUE DATE 103 3 3 INTERVIEW 104 3.4 3.4 LIEUTENANT DISPATCH/ RECEPTION 121 D IT D 106 122 3.8 3.8 4 4 CORPORAL 120 E LOST & FOUND BREAK ROOM RECORDS 108 109 110 119 5 F E EVIDENCE STORAGE 5 HALL POLICE AIDE EQUIP 107 112 ELEC PATROL / REPORT 105 111 5.6 F 5.6 PARKING OFFICER 5.8 5.8 118 6 EN SE D ARCH IT E C 6 LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 RESTROOM 117 115 PREBOOKING / BOOKING RENEWAL DATE OF CA NI TE A RESTROOM ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL 113 7 WOMEN MEN 116 114 THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND 7 THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT 8 8 J J MECHANICAL FLOOR PLAN PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K A B D D.9 E MECHANICAL FLOOR PLAN 1/4"=1'-0" 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\M201.dwg, 1/25/2016 11:09:21 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: M2.01 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A A B B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C C NO. D E E F F EN SE D ARCH DATE IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES IT E C D ISSUE LI CT C-31285 A TE RENEWAL DATE OF CA NI ST G A 5-31-2015 G R LI F O AC DATE ARCHITECT'S STAMP FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J MECHANICAL REFRIGERANT PIPING PLAN PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K MECHANICAL REFRIGERANT PIPING PLAN 1/4"=1'-0" 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\M201.dwg, 1/25/2016 11:09:00 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: M2.02 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A A B B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C C NO. D E E F F EN SE D ARCH DATE IT E C D ISSUE LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 A TE RENEWAL DATE OF CA NI ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J MECHANICAL DETAILS PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K MECHANICAL DETAILS NONE 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\M401.dwg, 1/25/2016 11:09:48 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: M4.01 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A A B B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C C NO. D E E F F EN SE D ARCH DATE IT E C D ISSUE LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 A TE RENEWAL DATE OF CA NI ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J MECHANICAL DETAILS PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K MECHANICAL DETAILS NONE 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\M401.dwg, 1/25/2016 11:10:14 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: M4.02 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A A B B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C C NO. D E E F F EN SE D ARCH DATE IT E C D ISSUE LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 A TE RENEWAL DATE OF CA NI ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J PLUMBING LEGEND, SYMBOLS, GENERAL NOTES, AND SCHEDULES PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K PLUMBING LEGEND, SYMBOLS, GENERAL NOTES, AND SCHEDULES NONE 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\P001.dwg, 1/25/2016 11:12:53 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: P0.01 DSA SUBMITTAL 12 11 10 9 8 7 A 6 B C 5 C.1 D D.9 4 3 2 1 E A A 1 1 1.1 1.1 EOC B B 102 LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2 2 2700 E LELAND ROAD, PITTSBURG, CA 94565 LOBBY 101 C C STORAGE NO. ISSUE DATE 103 3 3 INTERVIEW 104 3.4 3.4 LIEUTENANT DISPATCH/ RECEPTION 121 D IT D 106 122 3.8 3.8 4 4 CORPORAL 120 E LOST & FOUND BREAK ROOM RECORDS 108 109 110 119 5 F E EVIDENCE STORAGE 5 HALL POLICE AIDE EQUIP 107 112 ELEC PATROL / REPORT 105 111 5.6 F 5.6 PARKING OFFICER 5.8 5.8 118 6 EN SE D ARCH IT E C 6 LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 RESTROOM 117 115 PREBOOKING / BOOKING RENEWAL DATE OF CA NI TE A RESTROOM ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL 113 7 WOMEN MEN 116 114 THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND 7 THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT 8 8 J J PLUMBING FLOOR PLAN PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K A B D D.9 E PLUMBING FLOOR PLAN 1/4"=1'-0" 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\P201.dwg, 1/25/2016 11:13:31 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: P2.01 DSA SUBMITTAL 12 11 10 9 8 7 A 6 B C C.1 5 D D.9 4 3 2 1 E A A 1 1 1.1 1.1 B B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2 2 2700 E LELAND ROAD, PITTSBURG, CA 94565 C C NO. 3 ISSUE DATE 3 15' - 6 3/8" 3.4 14' - 2" 3.4 D D 3.8 3.8 4 4 E E F 5 5 5.6 5.6 5.8 5.8 6 6 F SLOPE DN 1/4" / 12" MIN EN SE D ARCH IT E C 1/4" / 12" MIN LI CT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 A TE RENEWAL DATE OF CA NI ST G A 5-31-2015 G R LI F O ARCHITECT'S STAMP 7 AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND 7 THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H 1/4" / 12" 1/4" / 12" CONSULTANT 4' - 0" 8 4' - 0" 8 J J 6' - 10" PLUMBING ROOF PLAN 5' - 0" PROJECT NO: 985-0007 8/18/2015 4:24:01 PM DATE: 08.24.2015 N K A B D D.9 E PLUMBING ROOF PLAN 1/4"=1'-0" 12 11 10 9 J:\2015 JOBS\15-06 LMC CCC Floor PLAN 3190\LMC\MECH\P202.dwg, 1/25/2016 11:13:51 AM, DWG To PDF.pc3 8 7 6 5 4 3 2 1 K1 K SHEET NO: P2.02 DSA SUBMITTAL 12 11 10 9 GENERAL SYMBOLS A 3 E2.1 3 6 SINGLE RECEPTACLE - INSTALL AT + 18" AFF UON. DESIGNATION AS NOTED. "E2.1" DENOTES SHEET NUMBER. BLANK DENOTES SAME SHEET. DUPLEX RECEPTACLE - INSTALL AT + 18" AFF UON. A AFF AIC C CATV CBC CEC CFC CKT CO (D) DWG (E) ELEC G, GND GFCI IDF IMC JB KAIC KV KVA KW LTG LV KCMIL MDF MPOE N/A NC NFPA NIC NO NTS PB REQD SHT SWBD TBD UON V W WP XFMR GFCI DUPLEX RECEPTACLE - INSTALL AT + 18" AFF UON. DOUBLE DUPLEX RECEPTACLE - INSTALL AT + 18" AFF UON. DUPLEX RECEPTACLE - INSTALL AT + 1" ABOVE COUNTER TOP BACK SPLASH TO BOTTOM OF RECEPTACLE FACEPLATE UON. LUMINAIRE - RECESSED. SEE SCHEDULE. LUMINAIRE - SURFACE MOUNT STRIP. SEE SCHEDULE. GFCI DUPLEX RECEPTACLE - INSTALL AT + 1" ABOVE COUNTER TOP BACK SPLASH TO BOTTOM OF RECEPTACLE FACEPLATE UON. LUMINAIRE - SURFACE MOUNT. SEE SCHEDULE. HALF SWITCHED RECEPTACLE - INSTALL RECEPTACLE AT + 18" AFF UON. INSTALL SWITCH AT 48" UON. LUMINAIRE - PENDANT MOUNT LINEAR FIXTURE. SEE SCHEDULE. LUMINAIRE - WALL MOUNT LINEAR FIXTURE. SEE SCHEDULE. FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE. B LUMINAIRE - RECESSED DOWNLIGHT. SEE SCHEDULE. CEILING BOX WITH DUPLEX RECEPTACLE. LUMINAIRE - PENDANT MOUNT ROUND FIXTURE. SEE SCHEDULE. TOUCHING FLOOR BOXES DENOTE A SINGLE BOX WITH MULTIPLE GANGS. IE. SHOWN IS A FLUSH FLOOR BOX WITH DIVIDED COMPARTMENTS HOUSING DUPLEX RECEPTACLE AND RJ45 DATA. LUMINAIRE - WALL MOUNT CAN. SEE SCHEDULE. EXIT LIGHT - WALL MOUNT SINGLE FACE. BUILDING STANDARD POWER DISTRIBUTION SYMBOLS (PLANS) EXIT LIGHT - CEILING MOUNT DOUBLE FACED. BUILDING STANDARD J JUNCTION BOX - CEILING OR WALL MOUNTED, SIZE TO CODE, TAPE AND TAG WIRES. PROVIDE FLEX AND/OR RECEPTACLE AS REQUIRED TO CONNECT EQUIPMENT. EXIT LIGHT - WALL MOUNT SINGLE FACE WITH ARROW. BUILDING STANDARD EXIT LIGHT - CEILING MOUNT DOUBLE FACED WITH DOUBLE ARROWS. BUILDING STANDARD PANELBOARD - FLUSH MOUNTED. OCCUPANCY SENSOR - CEILING MOUNT WITH BI-DIRECTIONAL VIEW. ARROWS INDICATE AIMING DIRECTION. PANELBOARD - SURFACE MOUNTED. DT = DUAL TECHNOLOGY PIR = PASSIVE INFARED U = ULTRASONIC MOTOR OCCUPANCY SENSOR - WALL MOUNT WITH DIRECTIONAL VIEW. ARROW INDICATES AIMING DIRECTION. UNFUSED DISCONNECT SWITCH DISTRIBUTION PANEL EQUIPMENT WITH MOTOR FUSED DISCONNECT SWITCH PHOTOSENSOR - CEILING MOUNT WITH DIRECTIONAL VIEW. ARROW INDICATES AIMING DIRECTION. COMBINATION MAGNETIC STARTER/FUSED DISCONNECT SWITCH 4 3 P A. AMPERE ABOVE FINISHED FLOOR AMPERE INTERRUPTING CAPACITY CONDUIT CABLE TELEVISION CALIFORNIA BUILDING CODE CALIFORNIA ELECTRICAL CODE CALIFORNIA FIRE CODE CIRCUIT CONDUIT ONLY DEMOLISH DRAWING EXISTING TO REMAIN ELECTRICAL GROUND GROUND FAULT CIRCUIT INTERRUPTER INTERMEDIATE DISTRIBUTION FRAME INTERMEDIATE METAL CONDUIT JUNCTION BOX KILOAMPERE INTERRUPTING CAPACITY KILOVOLT KILOVOLT AMPERE KILOWATT LIGHTING LOW VOLTAGE THOUSAND CIRCULAR MILS MAIN DISTRIBUTION FRAME MAIN POINT OF ENTRY NOT APPLICABLE NORMALLY CLOSED NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NORMALLY OPEN NOT TO SCALE PULL BOX REQUIRED SHEET SWITCHBOARD TO BE DETERMINED UNLESS OTHERWISE NOTED VOLT WATT, WIRE WEATHERPROOF TRANSFORMER D TS LCD SINGLE POLE SWITCH - WALL MOUNTED AT + 48" AFF UON. CH 2 EQUIPMENT TAG TIME SWITCH P/D POWER/DATA WALL OUTLET BOXES WITH FURNITURE WHIP P/D POWER/DATA POKE THRU FLOOR BOX WITH FURNITURE WHIP DAYLIGHT CONTROL PANEL DRC 2. DIGITAL ROOM CONTROLLER TYPICAL CONTROLLED RECEPTACLE NOMENCLATURE 3, r1-1 TYPICAL LUMINAIRE & SWITCH NOMENCLATURE "3" DENOTES CIRCUIT "r1" DENOTES RELAY PANEL NAME "1" DENOTES RELAY NUMBER UNSHADED SYMBOL DENOTES STANDARD LUMINAIRE. A SHADED SYMBOL DENOTES EMERGENCY LUMINAIRE. A "A" DENOTES LUMINAIRE TYPE "L1" DENOTES PANEL NAME "3" DENOTES CIRCUIT NUMBER "b" DENOTES SWITCH LEG L1-3b U A Xx LOWER CASE LETTER = SWITCH LEG D = DIMMER SWITCH. SEE SPECIFICATIONS K = KEY OPERATED SWITCH L = LOW VOLTAGE SWITCH M = MOMENTARY CONTACT SWITCH T = DIGITAL WALL TIMER S = OCCUPANCY SENSOR SWITCH 3 = 3 WAY SWITCH 4 = 4 WAY SWITCH C. BEFORE BEGINNING CONSTRUCTION, PROVIDE TO THE ARCHITECT A CONSTRUCTION SCHEDULE OF ELECTRICAL WORK. THE CONSTRUCTION SCHEDULE SHALL IDENTIFY ALL SIGNIFICANT MILESTONES WITH COMPLETION DATES. D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF PERSONS AND PROPERTY AD SHALL PROVIDE INSURANCE COVERAGE AS NECESSARY FOR LIABILITY, PERSONAL, AND PROPERTY DAMAGE, TO FULLY PROTECT THE OWNER, ARCHITECT AND ENGINEER FROM ANY AND ALL CLAIMS RESULTING FROM THIS WORK. E. MAINTAIN RECORD DRAWINGS AT THE PROJECT SITE INDICATING ALL MODIFICATIONS TO ELECTRICAL SYSTEMS. AT THE CONCLUSION OF THE PROJECT, PROVIDE ACCURATE "AS-BUILT" DRAWINGS IN CAD FORMAT ACCEPTABLE TO THE ARCHITECT. F. ALL MATERIALS PROVIDED FOR THE PROJECT SHALL BE NEW, UNLESS OTHERWISE NOTED. PROVIDE ALL INCIDENTAL MATERIALS REQUIRED FOR A COMPLETE INSTALLATION. G. PROVIDE ALL REQUIRED "CUTTING, PATCHING, BACK FILL AND REPAIRS" NECESSARY TO RESTORE DAMAGED SURFACES TO EQUAL OR BETTER THAN ORIGINAL CONDITIONS EXISTING AT START OF WORK. H. ALL ELECTRICAL EQUIPMENT INSTALLED OUTDOORS SHALL BE WEATHERPROOF. EXTERIOR CONDUIT RUNS INTO BUILDINGS SHALL BE INSTALLED WITH FLASHING, CAULKED AND SEALED. CONDUITS FOR EXTERIOR ELECTRICAL DEVICES SHALL BE RUN INSIDE BUILDING U.O.N. UNDERGROUND AND EXTERIOR CONDUIT SHALL HAVE WATERTIGHT FITTINGS. F PLUG LOAD CONTROLLED DUPLEX RECEPTACLE, REFER TO DETAILS J. THERE SHALL BE NO ROOF PENETRATIONS WITHIN 5'-0" OF FIRE RATED OR AREA SEPARATION WALLS. VERIFY EXACT LOCATIONS OF THESE WALLS WITH ARCHITECTURAL DRAWINGS. K. NOTE THAT BRANCH CIRCUIT WIRING IS NOT SHOWN. CIRCUIT NUMBERS ARE SHOWN ADJACENT TO ALL OUTLETS/FIXTURES/DEVICES. PROVIDE ALL BRANCH CIRCUIT WIRING BASED ON CIRCUIT NUMBERS SHOWN TO COMPLETE THE WIRING SYSTEM. L. THE CONTRACTOR SHALL, PRIOR TO BID, FIELD VERIFY ALL REQUIREMENTS FOR MODIFYING THE EXISTING, DATA, TELEPHONE, SYSTEMS TO ACCOMMODATE ADDITIONS NOTED. PROVIDE ALL MATERIALS NEEDED TO MAKE A FULLY OPERATIONAL SYSTEM AT THE CONCLUSION OF PROJECT WORK. N. VERIFY ALL VOLTAGES OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. 2013 CALIFORNIA ELECTRICAL CODE (PART 3, TITLE 24, CCR). O. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SITE LOCATING ALL EXISTING UNDERGROUND SYSTEMS IN THE AREA OF UNDERGROUND WORK. REPAIR ALL DAMAGED SYSTEMS TO OWNERS SATISFACTION. MAINTAIN EXTREME CARE DURING TRENCHING AS EXISTING SYSTEMS ARE KNOWN TO EXIST IN THE AREA. THE DRAWING AND SPECIFICATIONS ARE FOR THE ASSISTANCE AND GUIDANCE OF THE CONTRACTOR. EXACT LOCATIONS, DISTANCES AND ELEVATIONS WILL BE GOVERNED BY ACTUAL CONDITIONS. COORDINATE THE CONTRACT DOCUMENTS AND FIELD CONDITIONS TO DETERMINE EXACT ROUTING AND FINAL TERMINATIONS FOR ALL WORK. P. SEISMIC ANCHORAGE OF ALL ELECTRICAL EQUIPMENT SHALL BE PROVIDED IN ACCORDANCE WITH TITLE 24, CBC SECTION 1615A. 4. 2013 CALIFORNIA PLUMBING CODE (CPC) (PART 5, TITLE 24, CCR). 5. 2013 CALIFORNIA ENERGY CODE (PART 6,TITLE 24, CCR). 2013 CALIFORNIA FIRE CODE (CFC) (PART 9,TITLE 24, CCR). 7. 2013 CALIFORNIA GREEN CODE (PART 11, TITLE 24, CCR). 8. 2013 CALIFORNIA REFERENCED STANDARDS CODE (PART 12, TITLE 24, CCR). 9. 2013 NFPA 72 NATIONAL FIRE ALARM CODE. CONDUIT - EXPOSED. CONDUIT - STUB UP. 11. ADA STANDARDS FOR ACCESSIBLE DESIGN: ADA ACCESSIBILITY GUIDELINES (ADAAG) 28, PART 36 APPENDIX A. CONDUIT - STUB DOWN. E COMMUNICATIONS SYMBOLS CONDUIT - EMERGENCY POWER SYSTEM. LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER C NO. ISSUE DATE E Q. PLANS SHALL BE APPROVED BY THE AUTHORITY HAVING JURISDICTION PRIOR TO BEGINNING WORK. SUBMIT SHOP DRAWINGS TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING WORK. R. SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRIC EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT PER CEC ARTICLE 110-16. S. PROVIDE DEFERRED APPROVAL AND DESIGN BUILD FOR FIRE ALARM SYSTEM. SUBMIT COMPLETE DRAWINGS TO FIRE MARSHAL FOR APPROVAL AND ASSUME FULL RESPONSIBILITY FOR SYSTEM, DEVICE QUANTITY AND LOCATION, WIRING, PROGRAMMING, AND CONTROL PANELS. COORDINATE FINAL DESIGN LOCATIONS WITH ARCHITECT PRIOR TO ROUGH IN. T. PROVIDE COMPLETE DESIGN/BUILD FOR LOW VOLTAGE TELE/DATA SYSTEM. EXISTING CABLING AND INFRASTRUCTURE TO BE RE-USED TO THE EXTENT POSSIBLE. 10. 2013 NFPA 13 STANDARDS FOR FIRE SPRINKLER SYSTEMS. B D PROVIDE A PULL CORD IN EVERY EMPTY CONDUIT FOR USE IN FUTURE CONSTRUCTION. CONDUIT - CONCEALED IN WALLS OR CEILING. CONDUIT - DIRECT BURIAL. ALL CONDUITS SHALL BE A MINIMUM 3/4" , U.O.N. POWER AND LIGHTING BRANCH CIRCUITS SHALL HAVE A MINIMUM TWO (2) #12 AWG AND ONE (1) #12 AWG GROUND TYPE THWN/THHN. ALL POWER AND FIRE ALARM WIRING SHALL BE RUN IN CONDUIT. THE USE OF ROMEX (NMC) OR BX (AC) CABLE IS NOT PERMITTED. PROVIDE ALL WIRES AND WIRE SIZES REQUIRED BY LATEST CODES. M. 2013 CALIFORNIA MECHANICAL CODE (CMC) (PART 4, TITLE 24, CCR). A 2700 E LELAND ROAD, PITTSBURG, CA 94565 2013 CALIFORNIA BUILDING CODE (CBC), VOLUMES #1 AND #2 (PART 2,TITLE 24, CCR). 3. 6. DUPLEX RECEPTACLE WITH TWO USB PORTS WIRING & CONDUIT RUN SYMBOLS "X" DENOTES SENSOR TYPE. SEE SCHEDULE. IN LIEU OF SCHEDULE: DT = DUAL TECHNOLOGY P = PASSIVE INFRARED U = ULTRASONIC X PLUG LOAD CONTROLLED QUAD RECEPTACLE WITH SWITCHED DUPLEX RECEPTACLE, REFER TO DETAILS THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO BIDDING AND ALLOW FOR ALL FIELD CONDITIONS. OBTAIN CONTRACT DOCUMENTS FOR ALL OTHER TRADES AND BE RESPONSIBLE FOR ALL ELECTRICAL WORK NOTED AND CALLED OUT ON THE CONTRACT DOCUMENTS. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES ON PROJECT. COORDINATE ALL CONDUIT RUNS, ELECTRICAL EQUIPMENT AND PANEL LOCATIONS WITH ALL OTHER WORK TO AVOID CONFLICTS. COMPLY WITH ALL APPLICABLE CODES AND REGULATIONS. MATERIALS AND EQUIPMENTS SHALL BE U.L. LISTED AND LABELED FOR THE APPLICATION. CODES AND STANDARDS 1. 1 B. I. MOTOR RATED SWITCH PHOTOSENSOR - WALL MOUNT WITH DIRECTIONAL VIEW. ARROW INDICATES AIMING DIRECTION. 2 GENERAL NOTES MAGNETIC STARTER - NEMA SIZE INDICATED. P E 5 ABBREVIATIONS PLAN OR DETAIL DESIGNATION "3" DENOTES DETAIL OR PLAN NUMBER LUMINAIRE & SWITCH SYMBOLS P 7 RECEPTACLE SYMBOLS SHEET NOTE TAG - SEE ASSOCIATED NOTE ON SAME SHEET. C 8 F 12. ADA STANDARDS FOR ACCESSIBLE DESIGN CODE OF REGULATIONS (INCLUDING AMENDMENTS). CONDUIT - CAPPED. CONDUIT - CONTINUATION. COMBINATION RJ11/BLANK TELEPHONE OUTLET - INSTALL AT + 18" AFF UON. PROVIDE 1-1/4" CONDUIT TO TR ROOM. SURFACE MOUNTED WIRE RACEWAY - INSTALL AT + 36" AFF UON. COMBINATION RJ11/RJ45 TELEPHONE/DATA OUTLET - INSTALL AT + 18" AFF UON. PROVIDE 1-1/4" CONDUIT TO TR ROOM SURFACE MOUNTED WIRE RACEWAY UP/DOWN LI C WIRELESS ACCESS POINT E2.01 FLOOR PLAN - LIGHTING TGB TELECOM GROUND BUS E3.01 FLOOR PLAN - POWER & SIGNAL LADDER TRAY E5.01 DETAILS BASKET TRAY E6.01 SCHEDULES LIGHTING ACCEPTANCE CERTIFICATE BEFORE AN OCCUPANCY PERMIT IS GRANTED FOR A NEWLY CONSTRUCTED BUILDING OR AREA, OR A NEW LIGHTING SYSTEM SERVING A BUILDING, AREA, OR SITE IS OPERATED FOR NORMAL USE, ALL INDOOR AND OUTDOOR LIGHTING CONTROLS SERVING THE BUILDING, AREA, OR SITE, SHALL BE CERTIFIED AS MEETING THE ACCEPTANCE REQUIREMENTS FOR CODE COMPLIANCE IN ACCORDANCE WITH CEC SECTION 130.4. A CERTIFICATE OF ACCEPTANCE SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY UNDER CEC SECTION 10-103(a) OF PART 1. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TESTING AND COMPLETION OF REQUIRED ACCEPTANCE FORMS. IF GENERAL CONTRACTOR IS NOT LICENSED FOR THIS WORK, GENERAL CONTRACTOR SHALL HIRE LICENSED THIRD PARTY. E RENEWAL DATE OF CA A G AT WAP IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES 5-31-2015 GENERAL INFORMATION - ELECTRICAL NI E0.01 IT C-31285 ST G D ARCH CT DRAWING INDEX COMBINATION RJ45/BLANK DATA OUTLET - INSTALL AT +1" ABOVE COUNTER TOP BACK SPLACH TO BOTTOM OF FACEPLATE UON. SE E COMBINATION RJ45/BLANK DATA OUTLET - INSTALL AT + 18" AFF UON. PROVIDE 1-1/4" CONDUIT TO TR ROOM. EN R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J GENERAL INFORMATION ELECTRICAL PROJECT NO: 985-0007 DATE: 08.24.2015 K K SHEET NO: E0.01 12 11 10 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 GENERAL NOTES A. A A B B C C.1 D D.9 E 1 B. LIGHTING CONTROL BASIS OF DESIGN IS WATTSTOPPER DLM. PROVIDE MANUFACTURER SHOP DRAWINGS INDICATING ALL PARTS AND PIECES FOR A COMPLETE WORKING SYSTEM. C. LUMINAIRES INDICATED AS EMERGENCY SHALL BE CIRCUITED TO A CENTRAL LIGHTING INVERTER VIA UL924 EMERGENCY LIGHTING RELAY. REFER TO DETAILS FOR ADDITIONAL INFORMATION. D. EXIT SIGNS SHALL BE CIRCUITED TO THE CENTRAL LIGHTING INVERTER AND UNSWITCHED. E. CIRCUITS WITH PREFIX 'E' INDICATES CIRUIT TO CENTRAL LIGHTING INVERTER 1 1.1 COORDINATE EXACT LOCATION OF LUMINAIRES AND LIGHTING CONTROL DEVICES WITH ARCHITECT PRIOR TO COMMENCEMENT OF WORK. F. PROVIDE QUANTITY OF WATTSTOPPER DLM ROOM CONTROLLERS AS REQUIRED TO MEET LIGHTING CONTROL INTENT SHOWN. LOCATE ROOM CONTROLLERS ABOVE DROP CEILING. G. DAYLIGHT CONTROLS: PRIMARY AND SECONDARY DAYLIT LIGHTING ZONES SHALL AUTOMATICALLY DIM BASED ON AVAILABLE DAYLIGHT. SET POINT SHALL BE 30FC. PRIMARY AND SECONDARY ZONES SHALL BE AUTOMATICALLY CONTROLLED SEPARATELY. 1.1 H. BRANCH CIRCUITS OVER 75'-0", PROVIDE #10 AWG CONDUCTORS I. TITLE 24 BRANCH CIRCUIT VOLTAGE DROP: MAXIMUM 75'-0", AT MAX LOADING OF 12A, PROVIDE #12. C # A B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C SHEET NOTES NO. 2 2 1. ISSUE DATE NOT USED NOT IN SCOPE D D 3 DISPATCH/ RECEPTION A 3 L1 INTERVIEW A 122 104 LIEUTENANT 3.4 OPEN TO ABOVE DT 121 3.4 OPEN TO ABOVE 9' - 0" IT A 106 L1 3.8 3.8 S E E MOD-LINE BEAMS 9' - 0" 4 A CORPORAL DT DT A F BREAKDTROOM L1 119 5 A 9' - 0" PARKING OFFICER 118 A A 110 RECORDS A 109 DT F 9' - 0" 9' - 0" L1 5 POLICE AIDE EQUIP A A EQ 112 DT EQ A L1 5.6 A 9' - 0" PATROL / REPORT DT L1 DT EQ 6 6 X EQ 9' - 0" 9' - 0" A 117 C 9' - 0" OF CA R LI F O AC DATE FLS SS APPROVAL C 9' - 0" S H RENEWAL DATE THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 115 S EQ HALL A 107 L1 7 L1 CONSULTANT A 7 C DT PREBOOKING / BOOKING DT 113 DT 6'-0" DT A A H EQ 6'-0" C D E THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND RESTROOM A IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES IT ARCHITECT'S STAMP L1 RESTROOM AT 9' - 0" D ARCH 5-31-2015 G ST A SE C-31285 5.8 111 G EN T 5.8 LOST & FOUND 108 A EC 5.6 S A A S LI 9' - 0" AREA REQUIRING COORDINATION WITH SITE BUILT 120 D EVIDENCE STORAGE L1 NI 4 X A C A 9' - 0" A C WOMEN MEN 116 114 9' - 0" 8 X D J EQ J 9' - 0" L1 D X L1 FLOOR PLAN LIGHTING 8 D PROJECT NO: 985-0007 DATE: 08.24.2015 K K 1 FLOOR PLAN - LIGHTING E2.01 1/4" = 1'-0" 12 11 SHEET NO: 10 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 GENERAL NOTES A. A A B B C C.1 D D.9 E 1 1 1.1 1.1 COORDINATE EXACT LOCATIONS OF ALL ARCHITECTURAL, MECHANICAL AND PLUMBING EQUIPMENT WITH ARCHITECTURAL, MECHANICAL AND PLUMBING DRAWINGS. B. SIZE FUSES FOR ALL MECHANICAL AND PLUMBING EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS. C. IN FINISHED INTERIOR AREAS, RUN ALL CONDUITS CONCEALED, UNLESS OTHERWISE NOTED. PAINT ALL EXPOSED CONDUITS AND ELECTRICAL EQUIPMENT. REFER TO ARCHITECTS PAINTING SECTION FOR REQUIREMENTS. D. SEE EQUIPMENT SCHEDULE ELECTRICAL REQUIREMENTS FOR CIRCUITING OF EQUIPMENT AND REFER TO RISER DIAGRAMS AND DETAILS FOR ADDITIONAL INFORMATION ON WIRING, LAYOUT AND CONNECTIONS. SEE MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. E. A B PROVIDE POWER 120V/24V TRANSFORMER AS REQUIRED TO POWER VAV/BY-PASS DAMPERS, RESTROOM PLUMBING CONTROLS, DUCT SMOKE DETECTORS, MAGNETIC DOOR HOLDERS AND FIRE SMOKE DAMPERS FOR MECHANICAL EQUIPMENT. SEE DIAGRAMS ON MECHANICAL AND PLUMBING DRAWINGS FOR CONNECTION TO MECHANICAL AND PLUMBING EQUIPMENT. PROVIDE CIRCUIT FORM NEAREST AVALIABLE PANEL, UNLESS OTHERWISE NOTED. LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER EOC 2700 E LELAND ROAD, PITTSBURG, CA 94565 102 C C # SHEET NOTES NO. 2 2 1. PROVIDE GROUNDING BUSBAR EQUIVALENT TO CHATTSWORTH PRODUCTS 10622-010 FOR COMMUNICATIONS AND DATA EQUIPMENT. GROUND WITH ONE (1) #6 AWG CABLE. GROUND BUSBAR TO NEAREST ELECTRICAL PANELBOARD WITH ONE (1) #6 AWG CABLE. 2. PROVIDE ONE FLOOR TO CEILING, 3/4" THICK FIRE RATED PLYWOOD BACKBOARD FOR COMMUNICATIONS DEVICE MOUNTING. 3. ADD ALTERNATE: 6"W X 4"D BASKET TRAY FOR ROUTING OF HORIZONTAL LOW VOLTAGE CABLING IN LIEU OF CONDUIT HOME RUN TO TR ROOM. CABLING BY OTHERS. ROUTE ABOVE DROP CEILING THROUGH CORRIDOR SPACE PER DISTRICT TECHNOLOGY STANDARDS LOBBY 101 NOT IN SCOPE 7 STORAGE D WP 103 J 3 3 A A A INTERVIEW 104 2 A WAP A 5 3.4 3.4 A DISPATCH/ RECEPTION 121 A TGB A LIEUTENANT IT 3.8 4 E 12"W LADDER RACK 5. 2-4"C SLEEVES. 6. PROVIDE TWO L6-30R RECEPTACLES ABOVE EACH 4 POST RACK. 7. PROVIDE 120V CONNECTION FOR WALL MOUNTED SIGNAGE. 8. FOR EWH 9. MOUNT RECEPTACLE INSIDE EACH LOCKER SPACE 1 106 122 4. 3.8 6 ISSUE DATE D E A A 4 4 3 10. 1-1/4"C ROUTE UP WALL CAVITY TO CEILING SPACE. ROUTE CONDUIT ABOVE CEILING TO ELECTRICAL ROOM. 2 CORPORAL 120 A A LOST & FOUND BREAK ROOM 108 109 110 F 119 5 A 107 112 A ELEC A 105 111 5.6 D ARCH IT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 5-31-2015 118 A AT G ST 5.8 A E RENEWAL DATE OF CA A PARKING OFFICER 5.8 G SE CT 5.6 EN E HALL PATROL / REPORT C A POLICE AIDE EQUIP NI A 5 RECORDS LI F EVIDENCE STORAGE R LI F O AC DATE FLS SS WP A WAP 6 J 6 ARCHITECT'S STAMP THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND J A 8 THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 8 RESTROOM PREBOOKING / BOOKING RESTROOM 117 115 APPROVAL A H H 113 CONSULTANT 7 WOMEN MEN 116 114 7 A 10 J 9 J 9 8 FLOOR PLAN POWER & SIGNAL 8 WP PROJECT NO: 985-0007 DATE: 08.24.2015 K K 1 FLOOR PLAN - POWER & SIGNAL E3.01 1/4" = 1'-0" 12 11 10 SHEET NO: 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 WATTSTOPPER DLM NOTES B. LOCATE SENSOR MINIMUM 5 FEET FROM ANY AIR SUPPLY AND/OR RETURN REGISTERS. NORMAL SWITCHED SENSE (RED 18AWG) ELCU-200 NORMAL POWER SENSE (BLACK 18AWG) PUSH TO TEST NORMAL POWER NORMAL NEUTRAL (WHITE 18AWG) ESRU1C 120V OR ESRH1C 277V C. THE CONTRACTOR SHALL COMMISSION SENSITIVITY AND TIME DELAY SETTINGS AND PROVIDE TITLE 24 COMMISIONING DOCUMENTS. CUT JUMPER LOOP TO USE WITH NORMALLY CLOSED -TEST SWITCH -FIRE ALARM PANEL -SECURITY PANEL -OTHER EMERGENCY POWER A. ALL SENSOR LOCATIONS ARE APPROXIMATE AND SHOWN FOR DESIGN INTENT ONLY. LOCATE SENSORS PER MANUFACTURER GUIDELINES AND INSTALLATION MANUAL. PROVIDE QUANTITIES AND LOCATIONS AS REQUIRED FOR PROPER SENSING. FINAL DEVICE LAYOUT SHALL BE SUBMITTTED AS A SHOP DRAWING AS PART OF SUBMITTAL REVIEW. SHOP DRAWING APPROVAL IS REQUIRED PRIOR TO PROCUREMENT AND ROUGH-IN. RELAY STATUS LED 4 3 2 1 EMERG POWER OUT (RED 12AWG) EMERG LIGHTING LOAD 0-10VDC DIMMING DRIVER REQUIRED REMOTE ACTIVATION A 5 YEL LMRC-213 DIMMING ROOM CONTROLLER EMERG NEUTRAL (WHITE 18AWG) EMERG POWER IN (BLACK 12AWG) A LIGHTING LOAD (a) RED LIGHTING LOAD (b) PLUG LOAD CONTROLLER LMPL-201 NEUTRAL WHT HOT BLK 120/277V RED CONTROLLED NEUTRAL WHT HOT BLK 120 120/277 B B D. THE CONSTRACTOR SHALL PROVIDE ALL REQUIRED OCCUPANCY SENSOR POWER PACKS. PROVIDE J-BOXES WITH BLANK FACEPLATES AT CEILING. E. ROOM CONTROLLERS SHALL BE MOUNTED IN AN ACCESSIBLE LOCATION, INSIDE A MULTI-GANG J-BOX WITH BLANK FACEPLATE, CONCEALED IN CABINETRY, ABOVE DROP CEILING/CLOUD, OR AT A NEARBY REMOTE LOCATION. COORDINATE FINAL LOCATION OF DEVICES WITH ARCHITECT. F. ROOM CONTROLLER QUANTITIES SHOWN ON PLANS FOR DESIGN INTENT. PROVIDE QUANTITIES AS REQUIRED FOR A COMPLETE SYSTEM. ONE ROOM CONTROLLER IS REQUIRED FOR EACH LIGHTING CIRCUIT. PROVIDE ROOM CONTROLLER SERIES WITH THE FOLLOWING THREE SWITCHING ZONES (INCLUDING MULTIPLE DAYLIGHT SWITCHING ZONES) AND CONTINUOUS DIMMING CAPABILITIES. C WHT/YEL WHT/BLK 120/277VAC UNCONTROLLED LMRJ SERIES PRE-TERMINATED CABLES OR CAT5E (TYP). FREE TOPOLOGY & SPLITTER ACCEPTABLE "SWITCHING" LINE SENSING LINE UNSWITCHED 120/277 WHT NUT BLK HOT DLM OCCUPANCY SENSOR LIGHTING LOAD (a) RED 0-10VDC DIMMING DRIVER REQUIRED (COORDINATE FINAL SWITCH SELECTIONS WITH OWNER) * GRY LMRJ CABLES OR CAT5E. 2700 E LELAND ROAD, PITTSBURG, CA 94565 <RJ45 (TYP.) SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE. CLASS 2 0-10 VOLT CONTROL WIRING C TO DLM DEVICES H. COORDINATE WITH MANUFACTURER SO THAT DEVICES ALLOW FOR OPEN TOPOLOGY, AND DO NOT REQUIRE ADDITIONAL CLASS 2 0-10V CONTROL WIRING. DEVICES SHALL HAVE NETWORK CAPABILITY FOR FUTURE USE. I. COMPATIBILITY WITH THIRD PARTY EQUIPMENT REQUIRES SELECT DEVICES. THIRD PARTY PROJECTION SCREENS REQUIRE #LMDI-101 AND #LMSW-102 TO UTILIZE DLM CONTROL SWITCH. THIRD PARTY SHADES REQUIRE #LMDI-010 AND #LMSW-102 TO UTILIZE DLM CONTROL SWITCH. COORDINATE WITH ARCHITECT AND OWNER FOR SUCH REQUIREMENTS ON THE PROJECT. 3 LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER *BREAK-OFF REMOVAL ON HOT SIDE REQUIRED FOR SPLIT-CIRCUIT WIRING. VIO LMRC-211 DIMMING RM CONTROLLER G. LMRJ SERIES PRE-TERMINATED CABLES OR CAT5E IS ACCEPTABLE. MANUFACTURER RECOMMENDS PROVIDING LMRJ SERIES PRE-TERMINATED CABLES FOR EASE OF INSTALLATION. D ORG N.O. YEL COMM NO. DIGITAL LIGHTING CONTROL DIMMING WITH EMERGENCY WIRING DIAGRAM 1 NO SCALE ISSUE DATE PLUG LOAD CONTROL DIAGRAM NO SCALE D J. ALL PART NUMBERS SHOWN ARE BY WATTSTOPPER. SEE MANUFACTURER'S WEBSITE FOR SUPPORT DOCUMENTATION AND TECHNICAL SUPPORT. LIGHTING LOAD (a) K. SYSTEM SHALL HAVE NETWORK CAPABILITY FOR FUTURE CONNECTION TO BMS AND WATTSTOPPER SYSTEMS. LIGHTING LOAD (b) LMRC-213 DIMMING ROOM CONTROLLER LIGHTING LOAD (b) NEUTRAL WHT HOT BLK 120/277V CONTROLLED CONTROLLED E 0-10VDC DIMMING BALLAST REQUIRED. E LMRJ SERIES PRE-TERMINATED CABLES OR CAT5E. FREE TOPOLOGY & SPLITTER ACCEPTABLE WALL MOUNT BUTTON CONTROL AND DIMMER SWITCH CONTROLLED LMLS-500 DIMMING PHOTOSENSOR LMLS-500 DIMMING PHOTOSENSOR (AS NEEDED) DLM OCCUPANCY SENSOR WALL MOUNT BUTTON CONTROL AND DIMMER SWITCH (COORDINATE FINAL SWITCH SELECTIONS WITH OWNER) F DETAIL NOTES 1. CONTROLLED RECEPTACLES SHALL BE MARKED WITH PERMANENT IDENTIFICATION C SE D ARCH IT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 NO SCALE 5-31-2015 TE A G ST G RENEWAL DATE OF CA A NO SCALE EN CT 2 DIGITAL LIGHTING CONTROL DIMMING WIRING DIAGRAM E 4 IDENTIFICATION FOR PLUG LOAD CONTROL F NI PLUG LOAD CONTROLLED QUAD RECEPTACLE WITH SWITCHED DUPLEX RECEPTACLE LI PLUG LOAD CONTROLLED HALF SWITCHED RECEPTACLE <RJ45 (TYP.) R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J DETAILS PROJECT NO: 985-0007 DATE: 08.24.2015 K K SHEET NO: E5.01 12 11 10 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 2 1 A A LUMINAIRE SCHEDULE DESCRIPTION TYPE HOUSING LENS REFLECTOR 2X4 RECESSED LED DIE FORMED 20 GAUGE COLD ROLLED STEEL WITH INTEGRATED SEISMIC BRACKETS. UV STABALIZED IMPACT RESISTANT FROSTED VIRGIN ACRYLIC LINEAR PENDANT LED DIE FORMED STEEL WITH DIE FORMED JOINER SYSTEM. PLUG TOGEHTER WIRING STANDARD. RECESSED 1X4 LED MOUNTING FINISH LAMP(S) BALLAST MANUFACTURERS NOTES DIRECT/INDIRECT RECESSED STANDARD WHITE 0-10V STD DRIVER. 10%-100% DIM HIGH OUTPUT ENGINE 5585 LUMENS FINELISTE #HPR LED-A-2X4-DCO-HO-3500K-120V-SC-CX OR APPROVED EQUAL DIFUSE CENTER OPTIC, NA 73% TRANSMISSIVE, 99% DIFFUSION DIRECT/INDIRECT PENDANT STANDARD WHITE 0-10V STD DRIVER. 10%-100% DIM HIGH OUTPUT 2 ENGINE 3652 LUMEN PER 4 FOOT SECTION FINELITE # S16 LED-ID-DCO-X-3E-HO-HO-3500--SC-120-FA-F E-CX OR APPROVED EQUAL DIE FORMED 20 GAUGE COLD ROLLED STEEL WITH INTEGRATED SEISMIC BRACKETS. UV STABALIZED IMPACT RESISTANT FROSTED VIRGIN ACRYLIC DIRECT/INDIRECT RECESSED STANDARD WHITE 0-10V STD DRIVER. 10%-100% DIM STD OUTPUT 3152 LUMENS FINELISTE #HPR LED-A-1X4-DCO-SO-3500K-120V-SC-DW OR APPROVED EQUAL EXTERIOR WALL MOUNT LED TRAPZOIDAL WEDGE LED, DIE CAST ALUMINUM LENSED TYPE III DISTRIBUTION - DIRECT WALL NATURAL ALUMINUM 0-10V STD DRIVER. 10%-100% DIM 34 WATT, 3559 LUMEN GARDCO #101L-APD-3-NW-120-NP OR APPROVED EQUAL EXIT SIGN DIE CAST ALUMINUM WITH FIELD SELECTABLE CHEVRONS NA NA NA UNIVERSAL STANDARD ELECTRONIC LED LITHONIA #LRP-1-GMR-120 OR APPROVED EQUAL A B C B D. X HIGH REFLECTANCE MATTE WHITE DISTRIBUTION HIGH REFLECTANCE MATTE WHITE B CAMPUS SAFETY CENTER NOTES: A. THIS LUMINAIRE SCHEDULE IS NOT COMPLETE WITHOUT A COPY OF THE PROJECT MANUAL CONTAINING THE ELECTRICAL SPECIFICATIONS. B. PROVIDE +/- 12 INCH ADJUSTABILITY IN AIRCRAFT CABLE LENGTH WHERE USED. C. COORDINATE ALL CEILING TYPES WITH LUMINAIRE LOCATIONS PRIOR TO ORDERING LUMINAIRES. COORDINATE INSTALLATION WITH REFLECTED CEILING PLAN. D. SPECIFIED MANUFACTURERS ARE APPROVED TO SUBMIT BID. INCLUSION DOES NOT RELIEVE MANUFACTURER FROM SUPPLYING PRODUCT AS DESCRIBED. E. PROVIDE SUBMITTALS THAT INCLUDE THE LUMINAIRE, LAMP AND BALLAST INFORMATION OF EACH LUMINAIRE, WITH APPLICABLE OPTIONS CLEARLY CHECKED OR HIGHLIGHTED. SUBMITTALS NOT INCLUDING THIS INFORMATION WILL BE RETURNED AS REJECTED BY THE ENGINEER OF RECORD. F. PROVIDE COMMISSIONING OF THE LIGHTING AND LIGHTING CONTROLS IN ACCORDANCE WITH CALIFORNIA TITLE 24 LIGHTING COMMISSIONING REQUIREMENTS. 2700 E LELAND ROAD, PITTSBURG, CA 94565 C NO. SWITCHBOARD DSBA 208/120 V 3 PH 4W 400 A 400 A 35000 A SURFACE 1 2 D 3 PHASE A: 0 VA 0A PHASE B: 0 VA 0A PHASE C: 0 VA 0A CONNECTED: 0 VA 0A DEMAND: 0 VA 0A 4 5 VA LOAD DESCRIPTION NOTES A B C A B C A B LOAD DESCRIPTION 3. 10 BKR CKT CKT BKR VA LOAD DESCRIPTION NOTES NOTES LOAD DESCRIPTION VA BKR CKT CKT BKR VA LOAD DESCRIPTION A A 20/1 1 2 20/1 A B B 20/1 3 4 20/1 B B C 20/1 5 6 20/1 C C 20/1 5 6 20/1 C C A 20/1 7 8 20/1 A A 20/1 7 8 20/1 A A B 20/1 9 10 20/1 B B 20/1 9 10 20/1 B B C 20/1 11 12 20/1 C C 20/1 11 12 20/1 C A 20/1 13 14 20/1 A A 20/1 13 14 20/1 A B B B 20/1 15 16 20/1 B B 20/1 15 16 20/1 B C 20/1 17 18 20/1 C C 20/1 17 18 20/1 C A 20/1 19 20 20/1 A A 20/1 19 20 20/1 A B 20/1 21 22 20/1 B B 20/1 21 22 20/1 B C 20/1 23 24 20/1 C C 20/1 23 24 20/1 C A 20/1 25 26 20/1 A A 20/1 25 26 20/1 A B 20/1 27 28 20/1 B B 20/1 27 28 20/1 B C 20/1 29 30 20/1 C C 20/1 29 30 20/1 C A 20/1 31 32 20/1 A A 20/1 31 32 20/1 A B B 20/1 33 34 20/1 B B 20/1 33 34 20/1 B C C 20/1 35 36 20/1 C C 20/1 35 36 20/1 C A A 20/1 37 38 20/1 A A 20/1 37 38 20/1 A B B 20/1 39 40 20/1 B B 20/1 39 40 20/1 B C 20/1 41 42 20/1 C C 20/1 41 42 20/1 C B GENERAL NOTES SCHEDULE NOTES B a. C b. c. C A B C CONNECTED (kVA) SUBFED (kVA) TOTAL BY TYPE (kVA) DEMAND FACTOR (kVA) DEMAND BY TYPE (kVA) G GENERAL 0.00 0.00 0.00 100% 0.00 L LIGHTING 0.00 0.00 0.00 125% 0.00 R RECEPTACLES 0.00 0.00 0.00 100%/50% 0.00 K KITCHEN 0.00 0.00 0.00 100% 0.00 H HEATING 0.00 0.00 0.00 100% 0.00 M MOTORS 0.00 0.00 0.00 100% 0.00 LM LARGEST MOTOR 0.00 0.00 0.00 125% 0.00 WH WATER HEATER 0.00 0.00 0.00 125% 0.00 C CONTINUOUS 0.00 0.00 0.00 125% 0.00 a. 1. 2. b. 2. 3. c. 3. LOAD TYPE LOAD DESCRIPTION CONNECTED (kVA) SUBFED (kVA) TOTAL BY TYPE (kVA) DEMAND FACTOR (kVA) G L R K H M LM WH C GENERAL LIGHTING RECEPTACLES KITCHEN HEATING MOTORS LARGEST MOTOR WATER HEATER CONTINUOUS 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 100% 125% 100%/50% 100% 100% 100% 125% 125% 125% DEMAND BY TYPE (kVA) LOAD TYPE LOAD DESCRIPTION CONNECTED (kVA) SUBFED (kVA) TOTAL BY TYPE (kVA) DEMAND FACTOR (kVA) DEMAND BY TYPE (kVA) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 G L R K H M LM WH C GENERAL LIGHTING RECEPTACLES KITCHEN HEATING MOTORS LARGEST MOTOR WATER HEATER CONTINUOUS 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 100% 125% 100%/50% 100% 100% 100% 125% 125% 125% 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 F EN SE D ARCH IT CT LOAD DESCRIPTION 1. E LOAD TYPE SCHEDULE NOTES E C B GENERAL NOTES NOTES LI B A 14 VA 20/1 C F 0A 0A 20/1 A 13 0 VA 0 VA 4 A 12 CONNECTED: DEMAND: 2 C 11 0A 0A 0A 1 A 2. PANEL L1 0 VA 0 VA 0 VA 3 C 9 0A 0A PHASE A: PHASE B: PHASE C: 20/1 A 1. 0 VA 0 VA 208/120 V 3 PH 4W MLO 100 A 22000 A SURFACE 20/1 C SCHEDULE NOTES CONNECTED: DEMAND: VOLTAGE: PHASE/WIRE: MAIN AMPS: BUS AMPS: AIC RATING MOUNTING: A A 8 0A 0A 0A B a. E 0 VA 0 VA 0 VA A C 7 PHASE A: PHASE B: PHASE C: C GENERAL NOTES c. 208/120 V 3 PH 4W 125 A 225 A 22000 A SURFACE D NOTES A b. VOLTAGE: PHASE/WIRE: MAIN AMPS: BUS AMPS: AIC RATING MOUNTING: PANEL R1 C 6 DATE IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 5-31-2015 TE A G ST G RENEWAL DATE OF CA A CKT VOLTAGE: PHASE/WIRE: MAIN AMPS: BUS AMPS: AIC RATING MOUNTING: ISSUE NI C LOS MEDANOS COLLEGE R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J SCHEDULES PROJECT NO: 985-0007 DATE: 08.24.2015 K K SHEET NO: E6.01 12 11 10 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE 10 GENERAL SYMBOLS PLAN OR DETAIL DESIGNATION "3" DENOTES DETAIL OR PLAN NUMBER 1. "E2.1" DENOTES SHEET NUMBER. BLANK DENOTES SAME SHEET. SECTION OR ELEVATION DESIGNATION "2" DENOTES SECTION OR ELEVATION NUMBER 2. "E1.0" DENOTES SHEET NUMBER. BLANK DENOTES SAME SHEET. 3. B 3 SHEET NOTE TAG - SEE ASSOCIATED NOTE ON SAME SHEET. 4. 11 FEEDER, CONDUIT OR RELAY SCHEDULE TAG FIRE ALARM SYMBOLS F C WP HORN/STROBE MODEL: COOPER WHEELOCK EXCEDER HS SERIES CSFM: 7125-0785:0168 F HORN - WEATHER PROOF, VANDAL RESISTANT MODEL: COOPER WHEELOCK AH-24WP CSFM: 7125-0785:0131 H C S (E) FACP D ACTIVATION OF A VALVE SUPERVISORY SWITCH OR SHOULD AN OPEN GROUND OR FAULT OCCUR IN THE WIRING, THE FACP(S) AND REMOTE ANNUNCIATOR(S) SHALL INITIATE A TROUBLE SIGNAL AND SHALL INDICATE THE SOURCE OF THE TROUBLE. ONCE THE SYSTEM IS BACK TO NORMAL, THE PANEL WILL RESOUND FOR PROPER RESETTING. WHERE REMOTE MONITORING IS NOT REQUIRED, THE FIRE ALARM PANEL SHALL BE BACKED UP BY STANDY BATTERIES FOR 24 HOURS AND 5 MINUTES OF ALARM. WHERE REMOTE MONITORING IS REQUIRED, THE FIRE ALARM PANEL SHALL BE BACKED UP BY STANDBY BATTERIES FOR 60 HOURS AND 5 MINUTES OF ALARM. ALARM SILENCE CAN ONLY BE PERFORMED AFTER 5 MIN. OF ALARM IN ANY CONDITION. STROBE MODEL: COOPER WHEELCOK EXCEDER ST SERIES CSFM: 7125-0785:0168 F HEAT DETECTOR - ABOVE CEILING MODEL: SYSTEM SENSOR 5251H (W/ BASE B210LP) CSFM: 7270-1653:0137 (7300-1653:0109) OCCUPANCY TYPE: B (EDUCATIONAL) 2. SYSTEM TYPE: CLASS B, ADDRESSABLE, AUTOMATIC 3. METHOD OF COMMUNICATION: TELEPHONE 4. SCOPE OF WORK: NEW AUTOMATIC EXTENSION OF AN EXISTING AUTOMATIC FIRE ALARM SYSTEM TO A NEW BUILDING AT AN EXISTING SCHOOL CAMPUS. SMOKE DETECTOR MODEL: SYSTEM SENSOR 2251B(W/ BASE B210LP) CSFM: 7272-1653:0123 (7300-1653:0109) (E) FIRE ALARM CONTROL PANEL MODEL: HARRINGTON HS-3400 CSFM: 7165-0476:114 EOL END OF LINE RESISTOR AM ADDRESSABLE MODULE MODEL: SYSTEM SENSOR M500M CSFM: 7300-1653:0103 RM PROJECT DESCRIPTION 1. 5 4 ABBREVIATIONS ACTIVATION OF ANY SYSTEM PULL STATION, SMOKE DETECTOR OR HEAT DETECTOR FLOW SWITCH OR ANSUL UNIT SHALL CAUSE ALL SIGNAL DEVICES ON THE CAMPUS TO ACTIVATE AND SOUND. FACP(S) AND REMOTE ANNUNCIATOR(S) SHALL INDICATE THE SOURCE OF THE ALARM AND ALARM LIGHT(S) ON THE FIRE ALARM PANEL WILL ILLUMINATE. ACTIVATION OF ALARM SHALL CAUSE THE DIGITAL ALARM COMMUNICATIONS TRANSMITTER TO TRANSMIT THE ALARM TO A U.L. LISTED CENTRAL STATION. 5. 6 A ABV AF AFF AIC ARCH AS AT ATS BKR BLDG C CATV CB CBC CD CEC CFC CKT CL CLG CO COMM CSFM CTR (D) DET DIM DIST DP DWG (E) ELEC EM EMT EOL EQP FA FACP (F) FIN FL G , GND HGT HP IC IDF AMPERE ABOVE AMPERE FRAME, AMPERE FUSE ABOVE FINISHED FLOOR AMPERE INTERRUPTING CAPACITY ARCHITECTURAL AMPERE SWITCH AMPERE TRIP AUTOMATIC TRANSFER SWITCH BREAKER BUILDING CONDUIT CABLE TELEVISION CIRCUIT BREAKER CALIFORNIA BUILDING CODE CANDELA CALIFORNIA ELECTRICAL CODE CALIFORNIA FIRE CODE CIRCUIT CENTER LINE CEILING CONDUIT ONLY COMMUNICATIONS CALIFORNIA STATE FIRE MARSHALL CENTER DEMOLISH DETAIL DIMENSION DISTRIBUTION DISTRIBUTION PANEL DRAWING EXISTING ELECTRICAL EMERGENCY ELECTRICAL METALLIC TUBING END OF LINE RESISTOR EQUIPMENT FIRE ALARM FIRE ALARM CONTROL PANEL FUTURE FINISH FLOOR GROUND HEIGHT HORSEPOWER INTERCOM INTERMEDIATE DISTRIBUTION FRAME 3 IMC JB KAIC KV KVA KW LTG LV MAX KCMIL MDF MECH MH MIN MTD MTG NC NFPA NIC NIEC NO NTS OC P PA PB PF PH PNL PVC (R) REQD REQT(S) RM RSC SHT STC SW SWBD TC TEL TYP UON V W WP XFMR INTERMEDIATE METAL CONDUIT JUNCTION BOX KILOAMPERE INTERRUPTING CAPACITY KILOVOLT KILOVOLT AMPERE KILOWATT LIGHTING LOW VOLTAGE MAXIMUM THOUSAND CIRCULAR MILS MAIN DISTRIBUTION FRAME MECHANICAL MANHOLE MINIMUM MOUNTED MOUNTING NORMALLY CLOSED NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NOT IN ELECTRICAL CONTRACT NUMBER, NORMALLY OPEN NOT TO SCALE ON CENTER POLE PUBLIC ADDRESS PULL BOX POWER FACTOR PHASE PANEL POLYVINYL CHLORIDE EXISTING TO BE RELOCATED REQUIRED REQUIREMENT(S) ROOM RIGID STEEL CONDUIT SHEET SIGNAL TERMINAL CABINET SWITCH SWITCHBOARD TERMINAL CABINET TELEPHONE TYPICAL UNLESS OTHERWISE NOTED VOLT WATT, WIRE WEATHERPROOF TRANSFORMER E 75 F H N2-4 D1-5 THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO BIDDING AND ALLOW FOR ALL FIELD CONDITIONS. OBTAIN CONTRACT DOCUMENTS FOR ALL OTHER TRADES AND BE RESPONSIBLE FOR ALL ELECTRICAL WORK NOTED AND CALLED OUT ON THE CONTRACT DOCUMENTS. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES ON PROJECT. COORDINATE ALL CONDUIT RUNS, ELECTRICAL EQUIPMENT AND PANEL LOCATIONS WITH ALL OTHER WORK TO AVOID CONFLICTS. B. COMPLY WITH ALL APPLICABLE CODES AND REGULATIONS. MATERIALS AND EQUIPMENT SHALL BE U.L. AND CALIFORNIA STATE FIRE MARSHAL (CSFM) LISTED AND LABELED FOR THE APPLICATION. C. BEFORE BEGINNING CONSTRUCTION, PROVIDE TO THE ARCHITECT A CONSTRUCTION SCHEDULE OF ELECTRICAL WORK. THE CONSTRUCTION SCHEDULE SHALL IDENTIFY ALL SIGNIFICANT MILESTONES WITH COMPLETION DATES. B THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF PERSONS AND PROPERTY AND SHALL PROVIDE INSURANCE COVERAGE AS NECESSARY FOR LIABILITY, PERSONAL, PROPERTY DAMAGE, TO FULLY PROTECT THE OWNER, ARCHITECT AND ENGINEER FROM ANY AND ALL CLAIMS RESULTING FROM THIS WORK. E. MAINTAIN RECORD DRAWINGS AT THE PROJECT SITE INDICATING ALL MODIFICATIONS TO ELECTRICAL SYSTEMS. AT THE CONCLUSION OF THE PROJECT, PROVIDE ACCURATE "AS-BUILT" DRAWINGS ACCEPTABLE TO THE ARCHITECT. CAMPUS SAFETY CENTER ALL MATERIALS PROVIDED FOR THE PROJECT SHALL BE NEW, UNLESS OTHERWISE NOTED. PROVIDE ALL INCIDENTAL MATERIALS REQUIRED FOR A COMPLETE INSTALLATION. 2700 E LELAND ROAD, PITTSBURG, CA 94565 F. G. ALL MATERIALS PROVIDED FOR THE PROJECT SHALL BE NEW, UNLESS OTHERWISE NOTED. PROVIDE ALL INCIDENTAL MATERIALS REQUIRED FOR A COMPLETE INSTALLATION. H. PROVIDE ALL REQUIRED "CUTTING, PATCHING, BACK FILL AND REPAIRS" NECESSARY TO RESTORE DAMAGED SURFACES TO EQUAL OR BETTER THAN ORIGINAL CONDITIONS EXISTING AT START OF WORK. I. THERE SHALL BE NO ROOF PENETRATIONS WITHIN 5'-0" OF FIRE RATED OR AREA SEPARATION WALLS. VERIFY EXACT LOCATIONS OF THESE WALLS WITH ARCHITECTURAL DRAWINGS. J. ALL ELECTRICAL EQUIPMENT INSTALLED OUTDOORS SHALL BE WEATHERPROOF. EXTERIOR CONDUIT RUNS INTO BUILDINGS SHALL BE INSTALLED WITH FLASHING, CAULKED AND SEALED. CONDUITS FOR EXTERIOR ELECTRICAL DEVICES SHALL BE RUN INSIDE BUILDING, UNLESS OTHERWISE NOTED. UNDERGROUND AND EXTERIOR CONDUIT SHALL HAVE WATERTIGHT FITTINGS. K. ALL CONDUITS SHALL BE A MINIMUM 3/4," UNLESS OTHERWISE NOTED. POWER BRANCH CIRCUITS SHALL HAVE A MINIMUM TWO (2) #12 AWG AND ONE (1) #12 AWG GROUND TYPE THWN/THHN. ALL POWER AND FIRE ALARM WIRING SHALL BE RUN IN CONDUIT. THE USE OF ROMEX (NMC) OR BX (AC) CABLE IS NOT PERMITTED. PROVIDE ALL WIRES AND WIRE SIZES REQUIRED BY LATEST CODES. C NO. CONDUITS SHALL NOT BE USED AS A GROUND PATH. ALL CONDUITS SHALL CONTAIN A GROUNDING CONDUCTOR, SIZED PER NEC/CEC REQUIREMENTS. M. PROVIDE A PULL CORD IN EVERY EMPTY CONDUIT FOR USE IN FUTURE CONSTRUCTION. N. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SITE LOCATING ALL EXISTING UNDERGROUND SYSTEMS IN THE AREA OF UNDER GROUND WORK. REPAIR ALL DAMAGED SYSTEMS TO OWNERS SATISFACTION. MAINTAIN EXTREME CARE DURING TRENCHING AS EXISTING SYSTEMS ARE KNOWN TO EXIST IN THE AREA. THE DRAWINGS AND SPECIFICATIONS ARE FOR THE ASSISTANCE AND GUIDANCE OF THE CONTRACTOR. EXACT LOCATIONS, DISTANCES AND ELEVATIONS WILL BE GOVERNED BY ACTUAL CONDITIONS. COORDINATE THE CONTRACT DOCUMENTS AND FIELD CONDITIONS TO DETERMINE EXACT ROUTING AND FINAL TERMINATIONS FOR ALL WORK. O. CONDUIT AND WIRING ARE SHOWN ON THESE PLANS DIAGRAMMATICALLY. EXACT LOCATIONS SHALL BE DETERMINED IN THE FIELD TO SUIT SITE CONDITIONS. P. SEISMIC ANCHORAGE OF ALL ELECTRICAL EQUIPMENT SHALL BE PROVIDED IN ACCORDANCE WITH TITLE 24, CBC SECTION 1632A. Q. PLANS SHALL BE APPROVED BY THE "DIVISION OF THE STATE ARCHITECT" (DSA) PRIOR TO BEGINNING WORK. SUBMIT SHOP DRAWINGS TO THE ENGINEER FOR REVIEW PRIOR TO PURCHASE. R. SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRIC EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT PER CEC ARTICLE 110-26. S. ALL FIRE ALARM DEVICES SHALL BE CALIFORNIA STATE FIRE MARSHAL (CSFM) LISTED. GENERAL NOTES CONT'D T. FIRE ALARM WIRING AND MATERIALS SHALL BE LISTED FOR USE AS REQUIRED BY TITLE 24/CEC, ARTICLE 760. MINIMUM WIRE SHALL BE TWO (2) #14 AWG FOR INITIATING CIRCUITS AND TWO (2) #14 AWG FOR INDICATING CIRCUITS. AE. AUDIBLE SIGNALS INTENDED FOR OPERATION IN THE PUBLIC MODE SHOULD HAVE A SOUND LEVEL OF NOT LESS THAN 75 dBA AT 10 FEET OR MORE THAN 110 dBA AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE APPLIANCE. (2010 NFPA 72 SECTION18.4) U. FIRE ALARM WIRE USED IN WET LOCATIONS SHALL BE OF AN APPROVED TYPE IN ACCORDANCE WITH 3-310-8, T24/CEC (i.e. THHW OR EQUAL). V. PER CEC STANDARDS ALL WIRING IS TO BE PULLED THROUGH EACH JUNCTION BOX AND CONNECTED DIRECTLY TO EACH FIRE DEVICE. DO NOT SPLICE WIRE. THERE MUST BE AT LEAST 6" OF LEAD WIRE FROM BOX TO THE DEVICE. ALL BOXES SIZED PER CEC. 2013 CALIFORNIA BUILDING CODE (CBC), VOLUMES #1 AND #2 (PART 2,TITLE 24, CCR). 2. 2013 CALIFORNIA ELECTRICAL CODE (PART 3, TITLE 24, CCR). 3. 2013 CALIFORNIA MECHANICAL CODE (CMC) (PART 4, TITLE 24, CCR). 4. 2013 CALIFORNIA PLUMBING CODE (CPC) (PART 5, TITLE 24, CCR). 5. 2013 CALIFORNIA ENERGY CODE (PART 6,TITLE 24, CCR). 6. 2013 CALIFORNIA FIRE CODE (CFC) (PART 9,TITLE 24, CCR). 7. 2013 CALIFORNIA GREEN CODE (PART 11, TITLE 24, CCR). 8. 2013 CALIFORNIA REFERENCED STANDARDS CODE (PART 12, TITLE 24, CCR). "75" DENOTES CANDELA RATING OF STROBE 9. 2013 NFPA 72 NATIONAL FIRE ALARM CODE. "D1" DENOTES DETECTION ZONE "5" DENOTES DEVICE NUMBER 10. 2013 NFPA 13 STANDARDS FOR FIRE SPRINKLER SYSTEMS. WIRING & CONDUIT RUN SYMBOLS CONDUIT - CONCEALED IN WALLS OR CEILING. CONDUIT - DIRECT BURIAL. CONDUIT - HOME RUN TO PANEL, TERMINAL CABINET, ETC. SIZE CONDUIT ACCORDING TO SPECIFICATIONS AND APPLICABLE CODES. ALL 20A, 1P BRANCH CIRCUITS SHALL BE #12 AWG WIRES WITH #12 AWG NEUTRALS AND GROUNDS. RUN A MAXIMUM OF 3 BRANCH CIRCUITS PER CONDUIT. AF. SMOKE DETECTORS SHALL NOT BE ANY CLOSER THAN 1' FROM FIRE SPRINKLERS OR 3' FROM ANY SUPPLY DIFFUSER. IN AREA OF CONSTRUCTION OR POSSIBLE DAMAGE/CONTAMINATION ON NEWLY INSTALLED FIRE ALARM DEVICES SHALL BE COVERED UNTIL THAT AREA IS READY TO BE TURNED OVER TO THE OWNER. CONDUIT - FLEX WITH CONNECTION. F W. PENETRATIONS OF FIRE RATED WALLS SHALL BE PROTECTED IN ACCORDANCE WITH CALIFORNIA BUILDING CODE, CHAPTER 7, TITLE 24. PROVIDE DETAILS OF FIRE- STOP SYSTEMS FOR ALL PIPE/CABLE/CONDUIT PASSING THROUGH FIRE RATED WALLS/FLOORS REQUIRING PROTECTED OPENINGS. EN SE D ARCH IT IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES C-31285 AH. DSA, ARCHITECT AND ENGINEER SHALL BE NOTIFIED A MINIMUM OF 48 HOURS PRIOR TO THE FINAL INSPECTION AND/OR TESTING. CONDUIT - EMERGENCY POWER SYSTEM. CONDUIT - CAPPED. AI. FINAL FIRE ALARM TEST SHALL BE MADE WITH THE DSA INSPECTOR OF RECORD (IOR). LOCAL FIRE AUTHORITY SHALL BE NOTIFIED OF DATE AND TIME OF FINAL FIRE ALARM TESTING AND SHALL ASSIST/WITNESS SUCH TESTING AT THEIR DISCRETION. CONDUIT - CONTINUATION. Y. AJ. SUPERVISORY MONITORING SHALL BE TESTED AND VERIFIED AS SENDING CORRECT SIGNALS IN CONJUNCTION WITH FINAL ACCEPTANCE TEST. NEW VS. EXISTING (N) CONDUIT - CONCEALED IN WALLS OR CEILING. AK. FIRE ALARM CONTRACTOR SHALL PROVIDE A "RECORD OF COMPLETION" TO THE OWNER, ARCHITECT AND INSPECTOR OF RECORD (IOR)/DSA AFTER COMPLETION OF OPERATIONAL ACCEPTANCE TESTS. (2013 NFPA 72 SECTION 10.18.2.1.2.4) (E) CONDUIT - CONCEALED IN WALLS OR CEILING. (E) CONDUIT - TO BE REMOVED. AL. OWNER SHALL BE RESPONSIBLE FOR ESTABLISHING A FIRE ALARM MONITORING CONTRACT OR PROVISIONS. THE SUPERVISORY STATION SHALL BE LISTED AS EITHER UUFX OR UUJS BY UNDERWRITERS LABORATORIES OR SHALL MEET THE REQUIREMENTS OF FACTORY MUTUAL RESEARCH APPROVAL STANDARD 3011. F (N) MANUAL PULL STATION F (E) MANUAL PULL STATION F (E) MANUAL PULL STATION - TO BE REMOVED. H GENERAL INFORMATION - FIRE ALARM F2.01 FLOOR PLAN - FIRE ALARM 5-31-2015 G ALL FIRE ALARM DEVICE CONNECTIONS TO THE LIGHT AND POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. (2010 NFPA 72 SECTION 10.5.5.1) E RENEWAL DATE OF CA R LI F O ARCHITECT'S STAMP AC DATE FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THE CONTRACTOR SHALL ADJUST ALL DEVICES TO MAXIMUM PERFORMANCE AND TO MINIMIZE FALSE ALARMS. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. AB. PROVIDE TEMPORAL-THREE DISTINCTIVE FIRE ALARM SOUND. (NFPA 72 SECTION 6.8.6.5.1) AC. AUDIBLE FIRE ALARM SOUND LEVEL SHALL BE AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL IN ALL OCCUPIABLE AREAS. (2010 NFPA 72 SECTION 18.4.3.1) (I.E. CLASSROOM AVERAGE AMBIENT ROOM NOISE IS 45 dBA PLUS 15 dBA EQUALS 60 dBA MINIMUM ALARM TONE REQUIRED). SOUND TO BE MAINTAINED FOR A MINIMUM DURATION OF 60 SECONDS. H CONSULTANT AD. STROBES SHALL FLASH AT A RATE OF NOT EXCEEDING TWO FLASHES PER SECOND NOR BE LESS THAN ONE FLASH EVERY SECOND. (2010 NFPA 72 SECTION 18.5.2.1) DRAWING INDEX F0.01 AA. VISUAL FIRE ALARM DEVICES SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN 15 CANDELAS. NO PLACE IN ANY ROOM SHALL BE MORE THAN 50 FEET FROM A DEVICE. DEVICES WITHIN 55' OF EACH OTHER SHALL BE SYNCHRONIZED. AT G X. ST E D T AG. THE INSTALLING CONTRACTOR SHALL PROVIDE SYSTEM PROGRAMMING FOR SUPERVISORY MONITORING PER CBC SECTION 901.6.2. CONDUIT - STUB DOWN. DATE EC CONDUIT - STUB UP. ISSUE E 12. ADA STANDARDS FOR ACCESSIBLE DESIGN - CODE OF REGULATIONS (INCLUDING AMENDMENTS). CONDUIT - EXPOSED. LOS MEDANOS COLLEGE D. L. 1. 11. ADA STANDARDS FOR ACCESSIBLE DESIGN: ADA ACCESSIBILITY GUIDELINES (ADAAG) 28, PART 36 APPENDIX A. F A A. TYPICAL ZONE NOMENCLATURE "N2" DENOTES NOTIFICATION CIRCUIT "4" DENOTES DEVICE NUMBER 1 GENERAL NOTES CALIFORNIA CODES AND STANDARDS RELAY MODULE MODEL: SYSTEM SENSOR M500R CSFM: 7300-1653:0103 2 A 2 E1.0 7 NI 3 E2.1 8 SEQUENCE OF OPERATION OF FIRE ALARM SYSTEM SYMBOL LIST A 9 C 11 LI 12 J J GENERAL INFORMATION FIRE ALARM PROJECT NO: 985-0007 DATE: 08.24.2015 K K SHEET NO: F0.01 12 11 10 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE 12 11 10 9 8 7 6 5 4 3 A. FIRE ALARM DEVICES ARE OUTSIDE THE SCOPE OF THE MODULAR MANUFACTURER. DEVICES SHOWN ARE FOR REFERENCE ONLY. MODULAR MANUFACTURER SHALL PROVIDE PATHWAYS AND BOXES FOR DEVICES TO BE PROVIDED BY OTHERS. A B B C C.1 1 GENERAL NOTES FIRE ALARM SCOPE A 2 D D.9 CONNECT REMOTE NOTIFICATION POWER SUPPLIES TO FIRE ALARM CONTROL PANEL WITH TWO (2) #14 AWG, UNLESS OTHERWISE NOTED. B. ALL DETECTION CIRCUITS SHALL USE TWO (2) #16AWG, UNLESS OTHERWISE NOTED. C. SEE VOLTAGE DROP CALCULATIONS FOR NOTIFICATION CIRCUIT CABLE QUANTITY AND SIZE. D. IN FINISHED INTERIOR AREAS, RUN ALL CONDUITS CONCEALED, UNLESS OTHERWISE NOTED. PAINT ALL EXPOSED CONDUITS AND ELECTRICAL EQUIPMENT. REFER TO ARCHITECTS PAINTING SECTION FOR REQUIREMENTS. E. ALL INTERIOR FIRE ALARM CONDUIT SHALL BE 3/4", UNLESS OTHERWISE NOTED. E 1 1 F. SEE DETAILS FOR MOUNTING REQUIREMENTS OF FIRE ALARM DEVICES. 1.1 1.1 G. THERE SHALL BE NO ROOF PENETRATIONS WITHIN 5'-0" OF FIRE RATED OR AREA SEPARATION WALLS. VERIFY EXACT LOCATIONS OF THESE WALLS WITH ARCHITECTURAL DRAWINGS. H. MAINTAIN ALL SPACING AND PENETRATION REQUIREMENTS THROUGH FIRE RATED OR AREA SEPARATION WALLS. VERIFY EXACT LOCATIONS OF THESE WALLS WITH ARCHITECTURAL DRAWINGS. I. CONNECT ALL DUCT SMOKE DETECTORS, MAGNETIC DOOR HOLDERS, ROLLING SMOKE DOORS AND FIRE SMOKE DAMPERS TO FACP. PROVIDE POWER SUPPLY AND 120V/24V TRANSFORMERS AS REQUIRED. SEE WIRING DIAGRAM. EOC 102 C J. 2 2 K. LOBBY A B LOS MEDANOS COLLEGE CAMPUS SAFETY CENTER 2700 E LELAND ROAD, PITTSBURG, CA 94565 C PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS TO ABOVE CEILING HEAT DETECTORS FOR MAINTENANCE. NO. ISSUE DATE HEAT DETECTORS MOUNTED BELOW CEILING SHALL BE UNLESS OTHERWISE NOTED. HEAT DETECTORS MOUNTED ABOVE CEILING SHALL BE HIGH FIXED TEMPURATURE, UNLESS OTHERWISE NOTED. 101 NOT IN SCOPE STORAGE D D 103 3 3 INTERVIEW 104 3.4 S H LIEUTENANT 3.4 S C DISPATCH/ RECEPTION 121 1. IT 106 122 3.8 # F S F H 3.8 C SHEET NOTES PROVIDE DUCT SMOKE DETECTOR IN SUPPLY SIDE DUCT OF MECHANICAL EQUIPMENT. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE ACCESS DOORS WHERE REQUIRED TO ALLOW ACCESS TO DUCT SMOKE DETECTOR FOR MAINTENANCE. SEE MECHANICAL DRAWINGS FOR CONNECTIONS TO MECHANICAL EQUIPMENT. E E F 4 S H 4 C F S H CORPORAL C 120 S 5 F C F HALL F 118 5 POLICE AIDE EQUIP S H ELEC PATROL / REPORT C 105 111 112 EN 5.6 SE D ARCH IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT OFFICE OF REGULATION SERVICES IT C-31285 5-31-2015 5.8 S H 6 C G 6 AT 5.8 G F ST PARKING S H OFFICER C 110 CT 5.6 108 E 107 C 109 E RENEWAL DATE OF CA A H EVIDENCE STORAGE NI S 119 RECORDS S H C C BREAK ROOM F S &H LOST C FOUND C H LI H AREA REQUIRING COORDINATION WITH SITE BUILT S R LI F O AC DATE ARCHITECT'S STAMP FLS SS APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. S S RESTROOM 117 H PREBOOKING / BOOKING RESTROOM 115 F H F 113 F 7 F CONSULTANT WOMEN MEN S 116 S H H F 114 C S C H C F J 7 S J F FLOOR PLAN FIRE ALARM F 8 8 PROJECT NO: 985-0007 DATE: 08.24.2015 CANOPY ABOVE, TYP K K 1 FLOOR PLAN - FIRE ALARM F2.01 1/4" = 1'-0" 12 11 SHEET NO: 10 9 8 7 6 5 4 3 2 1 MODULAR BID PACKAGE