Medium voltage switchgear Withdrawable circuit breaker 1 to 24 kV Catalogue 2005 Web enabled Power and control MCset MCset range 1 to 24 kV 0 Contents Presentation Schneider Electric 2 MCset range Presentation Technical characteristics Operating conditions Protection of people Specific applications Choice of functional units 8 8 10 11 12 13 14 Cubicle description AD type cubicles incomer and feeder CL - GL type cubicles line-up bussectioning TT type cubicles metering and busbar earthing DI type cubicles switch-fuse feeder 16 16 18 20 21 Protection, monitoring and control Thermal diagnosis Protection system - Sepam range Sepam 2000 - Sepam 100 Sepam series 20, series 40, series 80 Instrument transformers 22 22 23 24 26 28 Switchgear Withdrawable parts 32 32 LF circuit breaker SF circuit breaker Rollarc contactor 34 38 42 DI switch cubicle Withdrawable part extraction 46 49 Installation Implementation examples Connections 50 50 52 Appendices Cubicle equipment Current transformers (Selection guide) 54 54 56 A few references 57 Personal notes 58 1 Presentation 0 Field of application 63280 MCset adapts to all electrical power distribution requirements from 1 to 24 kV MCset is an indoor, metal switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations. b MCset offers you: v pre-engineered and adaptable solutions tailored to your specific requirements, v significantly reduced maintenance, v local support centres throughout the world. MT20051 b MCset gives you the advantages of: v continuity of service for your networks, v enhanced safety for your staff and operations, v optimized investment throughout the life of your installation, v the possibility of integrating your medium voltage switchboard in a monitoring and control system. MT20052 87158 Applications Power plants b Auxiliary substations Industry b b b b b b b Oil & gas, Chemical industry, Metallurgy, Car industry, Mining, Cement plants, … Infrastructure b b b b b Airports, Ports, Hospitals, Water treatment, … PE55540 Marine b b b b b 2 Cruisers, Container ships, Tankers, Offshore platforms, … Schneider Electric Presentation Continuity of service and complete safety MCset is solidly based on extensive experience acquired throughout the world and provides your networks with a high level of dependability and safety. MCset integrates a host of innovative solutions designed around proven techniques: high performance switchgear, digital protection, monitoring and control systems, enclosures capable of withstanding internal arcing. From its very conception, MCset has taken account of three key user requirements: MT20058EN Reliability b type testing was carried out for each performance level in the MCset range. b the design, manufacturing and testing of MCset was carried out according to ISO 9001: 2000 quality standard. b three-dimensional computer modeling techniques were used to study the electrical fields. MT20059 Simplicity b a user interface which is easily understood by everybody. b interlocks and padlocks preventing operator errors. b Sepam-type protection units enabling on-site information retrieval without any additional devices. b maintenance limited to simple, routine operating checks and cleaning and greasing every 5 to 10 years. b easy installation due to identical civil engineering dimensions for all cubicles and installation being possible against a wall. Safety b operations are all performed from the front, including access to connections and busbars. b racking in and out is only possible with the door closed. b the power-on indicator is situated on the front of the functional unit. b the earthing switch has making capacity. b one single ‘‘anti-reflex” handle is used for all MCset operations. b internal arc withstand developed for all functional units. Schneider Electric 3 Presentation MCset, a comprehensive solution PE55170 MCset provides the most efficient means to control and protect a wide range of applications. Due to the devices it comprises, MCset can be easily integrated into a monitoring and control system. Sepam protection and control units Sepam series 20, series 40 and series 80 digital protection relays take full advantage of Merlin Gerin experience in electrical network protection. Sepam series 20, series 40 and series 80 provides all the necessary functions: b effective protection of people and property, b accurate measurements and detailed diagnosis, b integral equipment control, b local or remote indication and operation. Easy evolution Addition of communication, digital I/O’s, analog output, or temperature acquisition are possible due to its modular design. PowerMeter and Circuit Monitor metering units PE55134 The PowerLogic PowerMeter replaces a full complement of basic analog meters. This cost effective, high performance meter provides a full complement of accurate true-rms metering values. The PowerLogic series 3000/4000 Circuit Monitor is designed for critical power users and large energy consumers, to provide the information needed to confidently enter the evolving world of deregulation. It can be adapted to meter almost any time-of-use or real-time rate. Monitoring and control MT20062 MCset can be easily: b integrated into an existing monitoring and control system: communication of Sepam digital relay or PowerMeter/Circuit Monitor metering device through a standard protocol (Modbus). b integrated into a SMS PowerLogic electrical installation monitoring system. Thermal diagnosis system PE55136 Specially designed for Schneider Electric MV equipment, this system continuously monitors the temperature rise, using optical fibres and sensors installed at the heart of the sensitive areas. Thermal diagnosis system reduces the probability of failure and reduces maintenance time. 4 Schneider Electric MCset, a comprehensive solution Presentation (cont.) DE55465EN PE55137 MCset Transparent Ready™ option MCset switchboards integrate Web technologies so that you can find out information about your electrical installation as easy as opening a Web page. All you need is a standard Web browser and a PC connected to your local area network. TCP/IP over Ethernet Hub Front socket EGX400 Sepam Sepam Simple choice A simple choice between TRe-1 and TRe-2 service levels allows you to easily order your Transparent Ready™ MCset switchboard. A customized level is also available. Your Transparent Ready™ MCset switchboard comes equipped with a Web server including Web pages dedicated to power equipment data. Easy commissioning Transparent Ready™ equipment is delivered ready to connect and commission. A Quick Start guide, packaged with your switchboard, provides three easy-to-follow steps. CM/PM MCset switchboard PE55138 Functionalities PE55140 PE55139 Instantaneous readings Displays automatically updated meter values Schneider Electric TRe-1 TRe-2 b b Circuit summary Displays the RMS current 3-phase average (A), the real power (kW), the power factor, the circuit breaker status (if applicable), etc. b b Load current summary Displays the current RMS value for each phase (A), for all circuits b b Demand current summary Displays the average demand current value for each phase (A), for all circuits b b Power summary Displays the present demand (kW), the peak demand (kW), and the times and dates of the records b b Energy summary Displays the energy (kWh) the reactive energy (kvarh), and the times and dates of the records b b Instantaneous readings, all devices Displays automatically updated meter values for all the communicating devices in the equipment b Basic historical data logging, energy and trending Displays automatically updated meter values for all the communicating devices in the equipment b Log displays Displays data as time curves, or tables b Export of data tables Allows data tables to be exported in a standard Windows format b 5 MCset, a comprehensive solution Presentation (cont.) MT20064 Schneider Electric Services, by your side throughout the life of your installation Modernizing Specifying Specifying We help you to define your solutions: selection guide, technical assistance, advice… Implementing We oversee the completion and commissioning of your installation: design, cost optimization, guaranteed performances and dependability, commissioning tests, etc. Operating Operating Implementing We help run your daily operations in real time: maintenance contract, technical assistance, supply of replacement parts, corrective and preventive maintenance, operation and maintenance training, etc. Modernizing We can bring the performance of your installation up to date: installation audit, switchgear diagnosis, adaptation and modification, end of life recycling, etc. Examples of services provided MT20065EN Warranty extension A warranty extension is proposed if your installation is checked by ourselves before being commissioned. Circuit breaker-contactor diagnosis Throughout the life of the equipment, it is possible to carry out routine measurement of its characteristics in order to optimize maintenance. This service may be part of a global installation maintenance contract. End-of-life recycling Schneider Electric Services has an operational subsidiary allowing you to recycle your medium voltage switchgear. 6 Schneider Electric Presentation Quality assurance - environment MT20066 Certified quality: ISO 9001 A major asset In each of its units, Schneider Electric integrates a functional organization whose main role is to check quality and monitor compliance with standards. This procedure is: b uniform throughout all departments; b recognized by many customers and approved organizations. But above all, it is its strict application that has allowed us to obtain the recognition of an independent organization: The French Quality Assurance Association (AFAQ). The quality system for the design and manufacture of MCset is certified to be in conformity with the requirements of ISO 9001: 2000 quality assurance standard. Strict and systematic checks MT20067 During its manufacture, each MCset is subject to systematic routine testing, intended to check both quality and conformity: b sealing test; b filling pressure test; b measuring of opening and closing speeds; b measuring of operating torque; b dielectric test; b testing of safety systems and interlocks; b testing of low voltage components; b conformity with drawings and diagrams. The results obtained are given by the quality control department on each device’s test certificate. Protected environment MT20069EN As part of the group’s environmental policy, Schneider Electric Services provides you with an operational subsidiary to recover medium voltage switchgear and thus eliminate any discharge to atmosphere. In order to help you protect the environment and to relieve you of any concerns in terms of stock or dismantling, Schneider Electric Services offers to take back your equipment at the end of its life. MCset has been designed with environmental protection in mind: b the materials used, insulators and conductors are identified, easily separable and recyclable; b the SF6 can be recovered at the end of the equipment’s life and reused after treatment; b production sites are certified to ISO 14000. Schneider Electric 7 Presentation PE55045 MCset range Busbars LV control cabinet Sepam Circuit breaker Current transformers Cables connection Voltage transformers compartment 8 Schneider Electric MCset range Presentation (cont.) Make up of an MCset switchboard MCset switchboards are made up of several interconnected functional units. Power connections are made between functional units within a switchboard via a single busbar. The electrical continuity of all metal frames is provided by the connection of each functional unit’s earthing busbar to the switchboard’s main earthing circuit. Low voltage wiring trays are provided in the switchboard above the LV control cabinets. LV cables can enter the switchboard through the top or bottom of each functional unit. Description of a functional unit A functional unit comprises all equipment in the main and auxiliary circuits which together provide a protection function. Each functional unit combines all the components which are required to fulfil this function: b the cubicle; b the protection, monitoring and control system; b the withdrawable part. The cubicle The cubicle is of LSC2B (Loss of Service Continuity Category) type as defined by IEC standard 62271-200, in other words the medium voltage parts are compartmented using metal partitions (PM class) which are connected to earth and which separate: b the busbars; b the withdrawable part (circuit breaker, fuse-contactor, disconnector truck or earthing truck); b MV connections, earthing switch, current sensors and voltage transformers as required. MCset guarantees a high level of protection of people; when a compartment containing a main circuit is open, the other compartments and/or functional units may remain energised. The low voltage auxiliaries and monitoring unit are in a control cabinet separated from the medium voltage section. Four basic cubicle layouts are offered: b incomer or feeder AD b line up bussection CL - GL b busbar metering and earthing TT b switch-fuse feeder DI AD and CL cubicles have withdrawable switchgear. The protection, monitoring and control system This includes: b Sepam, protection, monitoring and control unit; b current sensors, which may be of 3 types: v conventional current transformers, v low voltage toroid type current transformers, v CSP type broad-range current transformers. b voltage transformers; b zero sequence core balance current transformers (CSH type). The withdrawable part This includes: b the circuit breaker, contactor or the earthing truck with its closing and opening mechanism, or the disconnector truck; b the lever-type propulsion mechanism for racking in-out; b interlocks to fix the withdrawable part on the fixed part either in service position or disconnected. Schneider Electric 9 MCset range Technical characteristics MT20071 The values below are given for normal operating conditions. Rated voltage (kV) 7.2 12 17.5 24 20 28 38 50 60 75 95 125 Rated insulation level power frequency withstand voltage 50 Hz - 1 min (rms kV) lightning impulse withstand voltage 1.2/50 µs (kV peak) Nominal current and maximum short time withstand current (1) Functional unit with circuit breaker short time withstand Ith max. (kA/3 s) current rated current rated current (kA/1 s) In max. busbar (A) In CB (A) Functional unit with fuse-contactor (3) short time withstand Ith max. (kA) current rated current In max. (A) Functional unit with switch-fuse (DI cubicle) short time withstand Ith max. (kA) current rated current In max. y (A) 31.5 40 50 4000 630 1250 2500 4000 (2) 31.5 40 50 4000 630 1250 2500 4000 (2) 31.5 40 40 4000 630 1250 2500 4000 (2) 16 25 31.5 2500 630 1250 2000 2500 50 (4) 50 (4) 250 200 50 (4) 50 (4) 31.5 (4) 31.5 (4) 200 200 200 200 40 50 40 40 25 31.5 Internal arc withstand (maximum value) (kA/1 s) 40 (kA/0.15 s) 50 (1) For functional units equipped with circuit breakers or fuse-contactors, the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (2) With fan. For greater values, please consult us. (3) Lightning impulse dielectric impulse withstand voltage = 60 kV peak. (4) Limited by fuses. 10 Schneider Electric MCset range Operating conditions Operating conditions MT20072 Normal operating conditions, according to IEC 60694 for indoor switchgear b ambient air temperature: v less than or equal to 40°C, v less than or equal to 35°C on average over 24 hours, v greater than or equal to –5°C. b altitude: v less than or equal to 1000 m, v above 1000 m, a derating coefficient is applied (please consult us). b atmosphere: v no dust, smoke or corrosive or inflammable gas and vapor, or salt (clean industrial air). b humidity: v average relative humidity over a 24 hour period y 95%, v average relative humidity over a 1 month period y 90%, v average vapor pressure over a 24 hour period y 2.2 kPa, v average vapor pressure over a 1 month period y 1.8 kPa. Specific operating conditions (please consult us) MCset has been developed to meet the following specific conditions: b temperature (possible derating); b corrosive atmospheres, (possible adaptation). Storage conditions In order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between –25°C and +55°C. Standards The MCset range meets the following international standards: IEC 60694: clauses common to high voltage switchgear IEC 62271-200 (60298): metal-enclosed switchgear for alternating current at rated voltages of between 1 and 52 kV IEC 62271-100 (60056): high voltage alternating current circuit breakers IEC 60470: high voltage alternating current contactors IEC 60265-1: high voltage alternating current switches IEC 60282-2: high voltage fuses IEC 62271-102 (60129): alternating current disconnectors and earthing switches IEC 60255: measurement relay and protection unit (Sepam) IEC 60044-1: current transformers IEC 60044-2: voltage transformers. Schneider Electric 11 MCset range Protection of people MT20076 Internal arc withstand MCset switchboard with tunnel Internal arc version: MCset is designed to withstand and protect operators in the case of failure due to an internal arc. MCset has been successfully tested using type tests. MCset proposes several options to install an internal arc switchboard. b 3-sided internal arc protection For an MCset switchboard fitted against a wall, access to the rear of the cubicle is impossible. Internal arc protection on 3 sides is sufficient. b 4-sided internal arc protection In the case of an MCset switchboard installed in the middle of a room, internal arc protection on 4 sides is necessary in order to protect an operator who goes behind the cubicle. b installation in a room with limited ceiling height v ceiling height over 2.8 meters, it is possible to install a tunnel in order to avoid hot gas to be reflected by the ceiling. b internal arcing detector MCset has a system enabling the detection of internal arcing and disconnecting of power supply in order to limit the duration of the fault to less than 140 ms. This system incorporates an electro-mechanical fail-safe trip system, located on the cubicle flaps. This unit transmits information to Sepam to give the circuit breaker upstream of the fault the opening order. MCset Basic version (gas exhaust): MCset is designed to eliminate the effects of internal arcing in total safety, due to: b metal flaps positioned above the enclosure, which in the case of internal fault, limit overpressure in the compartments. b nonflammable materials used for the cubicle. Dependable mechanical control devices MT20077 All operations are carried out from the front face, including access to connections and busbars. The user is guided through icon-diagrams on each front panel making it easy to understand the operating sequence and device status. Interlocks and padlocks prevent operator errors. Several additional levels of security also protect operators: b racking in and out is only possible with the door closed. b the very extensive set of mechanical and electrical interlocks do not allow operator error. These can be added to by key locks or padlocks according to specific operating procedures. Each selector can be fitted with one to three padlocks. b all operations are carried out from the front face, including access to connections and busbars. b the voltage present indicator is located on the front face of the functional unit, in the immediate vicinity of the earthing switch control. Options b disarming of circuit breaker when racking out. This function enables the circuit breaker control springs to be disarmed during the extraction operation. b disabling of racking in. This function disables the possibility of racking the withdrawable part in if the front panel (cable compartment) is not installed. 12 Schneider Electric MCset range Specific applications 0 Marine application PE55541 Derived from standard MCset, a Marine version has been developed to meet specific conditions when used on ships, offshore platforms,…: b vibrations/shocks, b steepness, b etc. E74225 MCset is particularly adapted and its characteristics meet Marine requirements: b compartmented cubicle (LSC2B type), b front access, b withdrawable circuit breaker, b Sepam protection and control chain, b internal arc withstand, b thermal diagnosis. MT20073 Certifications MCset Marine is approved by: b Lloyds Register (LR), b Registro Italiano Navale (RINA), b Det Norske Veritas (DNV), b Bureau Veritas (BV), b Germanischer Lloyd (GL). Seismic areas MCset meets international seismic specifications. Test procedures follow IEC 60068-3-3 standard. MCset is qualified following the standards: b UBC 97, b IBC 2000, b MSK 64, b ENDESA. MCset switchboards are certified by Shell n compliance with DEP 33.67.51.31 Gen (July 1998) for MV equipments (amendment to IEC 62271-200). Schneider Electric 13 Choice of functional units MCset range The MCset range comprises 13 functional applications. The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit. Selection guide: You want to supply power to a transformer. The chosen solution is a transformer feeder/breaker. The corresponding functional unit will therefore be a TF-B, comprising a AD cubicle equipped with a withdrawable circuit breaker, and a transformer application Sepam. Function Incomer (1) Feeder line transformer generator line transformer transformer Functional unit LI-B TI-B GI-B LF-B TF-B TF-S cubicle AD (1 to 4) AD (1 to 4) AD (1 to 4) AD (1 to 4) AD (1 to 4) DI 2 - DI 4 device Sepam protection relay circuit breaker substation application circuit breaker transformer application circuit breaker generator application circuit breaker substation application circuit breaker transformer application fuse-switch MT20082 Sepam MT20081 MT20080 Single line diagrams (1) The direct incomer (functional unit without a circuit breaker, equipped with a fixed busbar bridge) is produced using cubicles AD1-2-3 for U ð to 17.5 kV. For the 24 kV version, the direct incomer is produced using a specific cubicle: RD4. 14 Schneider Electric Choice of functional units MCset range (cont.) motor motor capacitor capacitor switchboard substation MF-B MF-C CB-B CB-C BS-B SS-B BB-V AD (1 to 4) AD1 AD (1 to 4) AD1 AD (1 to 4) TT (1-2-4) circuit breaker motor application fuse-contactor motor application circuit breaker capacitor application fuse-contactor capacitor application CL (1 to 4) and GL (1 to 4) circuit breaker busbar application MT20081 MT20083 MT20084 DE55076 Metering and busbar earthing MT20083 Bussectioning MT20081 Feeder Schneider Electric MT20078 circuit breaker substation application 15 AD type cubicles incomer and feeder Cubicle description 1 DE55501 DE55082 DE55081 AD1, AD2, AD3 7 2 H H 5 4 6 3 W D W AD2 DE55083 AD1 H MV compartments 1 busbars for cubicle interconnection 2 withdrawable part (circuit breaker LF1-2-3, contactor R400-R400D equipped with fuse disconnector truck or earthing truck) 3 MV connections by cables accessible from the front face 4 earthing switch 5 current sensors 6 voltage transformers (optionally equipped with withdrawable fuses). LV control cabinet 7 low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separated from the medium voltage part. W AD3 Characteristics Rated voltage Rated insulation level Rated current kV kV, rms 50 Hz - 1 min kV, impulse 1.2/50 µs A Breaking capacity kA Short time withstand current (kA rms 1 s) Short time withstand current (kA rms 3 s) Dimensions and weight 200 250 630 1250 2000 2500 3150 4000 (3) H (mm) W (mm) D (mm) (2) Approximative weight (kg) (4) (1) Limited by fuses. (2) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, or 2 sets of CT’s. (3) With fan. For greater values, please consult us. (4) Fully equipped cubicle. 16 Schneider Electric AD type cubicles incomer and feeder Cubicle description (cont.) 1 7 DE55502 DE55085 AD4 2 H 4 5 6 3 D W AD4 MV compartments 1 busbars for cubicle interconnection 2 withdrawable part (SF1-2 circuit breaker, disconnector truck or earthing truck) 3 MV connections by cables accessible from the front face 4 earthing switch 5 current sensors 6 voltage transformers (optionally equipped with withdrawable fuses). LV control cabinet 7 low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separated from the medium voltage part. AD1 7.2 20 60 12 28 75 b b b b 31.5 31.5 31.5 2300 570 1550 850 31.5 31.5 31.5 Schneider Electric AD1 contactor AD2 7.2 20 60 b b 7.2 20 60 12 28 75 17.5 38 95 b b b b b b 50 (1) 50 (1) 50 (1) 2300 570 1550 850 12 28 60 b 50 (1) 50 (1) 50 (1) 50 50 40 2300 700 1550 1000 AD3 40 40 40 31.5 31.5 31.5 7.2 20 60 AD4 12 28 75 17.5 38 95 b b b b b 50 50 40 2300 900 1550 1300 b b b 50 50 40 24 50 125 b b b b b 31.5 31.5 31.5 b b b 40 40 40 b b b b 31.5 31.5 16 or 25 2325 900 1750 1100 17 CL - GL type cubicles line-up bussectioning Cubicle description GL1, GL2, GL3 1 5 1 6 DE55504 CL1, CL2, CL3 DE55503 DE55087 The bussectioning functional unit comprises 2 cubicles mounted side by side (one cubicle equipped with a circuit breaker, the other with a busbar return). 2 3 H 4 W D W D CL1-2-3 or GL1-2-3 MV compartments 1 busbars to connect the bussectioning functional unit with other switchboard functional units 2 withdrawable part (circuit breaker LF1-2-3, disconnector truck or earthing truck) 3 current sensors 4 voltage transformers (optionally equipped with withdrawable fuses). LV control cabinet 5 low voltage auxiliaries and protection, monitoring and control unit are in one control cabinet, separated from the medium voltage part. Characteristics Rated voltage Rated insulation level Rated current kV kV, rms 50 Hz - 1 min kV, impulse 1.2/50 µs A Breaking capacity kA Short time withstand current (kA rms 1 s) Short time withstand current (kA rms 3 s) Dimensions and weight 630 1250 2000 2500 3150 4000 (3) H (mm) W (mm) D (mm) (1) Approximative weight (kg) (2) (1) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, or 2 sets of CT’s. (2) Fully equipped cubicle. (3) With fan. For greater values, please consult us. 18 Schneider Electric CL - GL type cubicles line-up bussectioning Cubicle description (cont.) V/H W/ W clear tri alar 1 5 1 6 DE55506 O I GL4 DE55505 DE55090 CL4 rese 2 H L L 3 L M 4 W W D D CL4 or GL4 MV compartments 1 busbars to connect the bussectioning functional unit with other switchboard cubicles 2 withdrawable part (circuit breaker SF1-2, disconnector truck or earthing truck) 3 current sensors 4 voltage transformers (optionally equipped with withdrawable fuses) LV control cabinet 5 low voltage auxiliaries and protection, monitoring and control unit are in one control cabinet, separated from the medium voltage part. CL1 / GL1 7.2 20 60 b b CL2 / GL2 12 28 75 b b 31.5 31.5 31.5 31.5 31.5 31.5 2300 570 (x 2) 1550 1300 (CL1 + GL1) Schneider Electric 7.2 20 60 b b CL3 / GL3 12 28 75 b b 50 40 50 40 40 40 2300 700 (x 2) 1550 1500 (CL2 + GL2) 17.5 38 95 b b 31.5 31.5 31.5 7.2 20 60 CL4 / GL4 12 28 75 b b 17.5 38 95 b b b b b b 50 50 50 50 40 40 2300 900 (x 2) 1550 1700 (CL3 + GL3) b b b 31.5 31.5 31.5 b b b b b 40 40 40 24 50 125 b b b b 31.5 31.5 2325 900 (x 2) 1750 1600 (CL4 + GL4) 19 TT type cubicles metering and busbar earthing Cubicle description TT4 1 4 DE55508 1 4 DE55507 DE55094 DE55093 TT1, TT2 H H 2 2 3 W W TT1 3 D D TT2 DE55095 MV compartments 1 busbars to connect the TT functional unit with other switchboard cubicles 2 earthing switch 3 voltage transformers H LV control cabinet 4 low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separate from the medium voltage part. W TT4 Characteristics TT1 TT2 TT4 Rated voltage kV Rated insulation level kV, rms 50 Hz - 1 min kV, impulse 1.2/50 µs Rated current A 630 (busbar intensity) 1250 2000 2500 3150 Short time withstand current (kA rms 1 s) Short time withstand current (kA rms 3 s) 7.2 20 60 b b 12 28 75 b b 7.2 20 60 b b 12 28 75 b b 17.5 38 95 b b b b b b 31.5 31.5 b b 31.5 31.5 b b 50 40 b b 50 40 b b 31.5 31.5 b b 40 40 Dimensions and weight 2300 570 1550 500 H (mm) W (mm) D (mm) (1) Weight (kg) 2300 700 1550 550 24 50 125 b b b b 31.5 16 or 25 2325 900 1750 560 (1) Overall + 175 mm for 4-sided internal arcing protected switchboards. 20 Schneider Electric DI type cubicles switch-fuse feeder Cubicle description DI4 4 1 DE55510 4 1 DE55509 DE55099 DE55098 DI2 2 H 2 H 3 3 W DI2 W D D DI4 MV compartments 1 busbars to connect the DI functional unit with other switchboard cubicles 2 switch - earthing switch 3 MV fuses LV control cabinet 4 Low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separate from the medium voltage part. Characteristics DI2 Rated voltage kV Rated insulation level kV, rms 50 Hz - 1 min kV, impulse 1.2/50 µs Rated current A 200 Breaking capacity kA (2) Short time withstand current (kA rms) (2) Dimensions and weight H (mm) W (mm) D (mm) (1) Weight (kg) 7.2 20 60 b 50 50 2300 700 1550 500 DI4 12 28 75 b 50 50 17.5 38 95 b 31.5 31.5 24 50 125 b 31.5 31.5 2325 900 1750 640 (1) Overall + 175 mm for switchboard internal arcing 4 sides. (2) Limited by fuses. DI cubicles including a fuse switch are used to supply power and protect low power transformers. E.g.: auxiliary service transformers in primary substations. All operations are carried out from the front face, including access to connections and busbars. All functional interlocks meet recommendations in IEC 62271-200: b the switch is only possible to close if the earthing switch is open and the connection access panel is in place; b closing of the earthing switch is only possible if the switch is open; b opening of the access panel to medium voltage connections and fuses is only possible of the earthing switches upstream and downstream of the fuses are closed; b the switch is locked in the open position when the access panel is taken off. The voltage presence indicator is situated on the front face of the functional unit, integrated in the switch’s control panel. Schneider Electric 21 Protection, monitoring and control Thermal diagnosis DE55109 Continuity of service is of prime importance for electrical power supplies, particularly. for heavy industries. By using the new thermal diagnosis system developed for MCset, we offer you the possibility of monitoring on an on-going basis, thus reducing the probability of failure and reducing maintenance time. 0 Thermal diagnosis: Schneider Electric’s medium voltage know-how PE55160 This innovative system has been specifically designed for the MCset range. It incorporates fibre optic temperature measurement systems within an environment subject to high dielectric stresses. Schneider Electric’s expertise provides you with the assurance of perfect electromagnetic compatibility between the various cubicle components. The advantages of thermal diagnosis b permanent monitoring of temperature rise in power circuits (busbars, cable connectors, switchgear); b indication of the fault zone; b 2 trip thresholds are available, using a dry contact. Components The thermal diagnosis system comprises the following components: b 1 or 2 modules mounted in the LV control cabinet; b 3 -point temperature probes (spread over the 3 phases) can be installed in various monitored zones: v 3 sensors in the busbar compartment, v 3 sensors in the cable connector compartment, v 3 sensors in the switchgear compartment. b fibre optic links to transmit the signal. 22 Schneider Electric Protection system Sepam range Each MCset functional unit is equipped with a comprehensive protection, monitoring and control system comprising: b instrument transformers to measure the necessary electrical values (phase current, residual current, voltages, etc.) b protection relays, providing functions adapted to the part of the network to be protected b metering equipment, to inform operators b low voltage relaying, i.e. to provide control of the breaking device (contactor or circuit breaker) and of the withdrawable part b various auxiliaries: secondary circuit test units, etc. DE55111 Protection, monitoring and control protection relays metering equipment switchgear (circuit breaker or contactor) instrument transformers Sepam: protection, monitoring and control units PE55170 Sepam is a range of digital monitoring protection and control units. Sepam is at the centre of the protection, monitoring and control system for MCset functional units: all the necessary protection, metering, control, monitoring and signalling functions are carried out by Sepam. Like the MCset range, the Sepam range is a range of units defined to provide an optimal solution for each application, and includes: b Sepam S, substation incomer and feeder; b Sepam B, bussectioning; b Sepam T, transformer feeder; b Sepam M, motor feeder; b Sepam C, capacitor feeder; b Sepam G, generator feeder. The Sepam range hinges around 2 functional and hardware bases: b Sepam series 20, 40 and series 80, a range of modular reays to meet your exact needs, b Sepam 2000, focused on performance, covers all MCset functional applications. Sepam advantages Reliability b Over 20 years of experience in multi-function digital protection relays. b Over 150000 Sepam units in service in more than 90 countries. Quality b Quality design based on dependability studies and strict definition of environmental constraints: temperature, pollution, EMC, dielectric strength,… b Quality manufacturing based on procurement agreements with suppliers and inspection throuhghout all manufacturing phases. Simplicity of use b Ergonomic and intuitive use machine interface (UMI). b User friendly and powerful PC setting software. Schneider Electric 23 Protection, monitoring and control Sepam 2000 Sepam 100 Sepam 2000, for all applications MT20097 The Sepam 2000 range of digital protection, monitoring and control units provides a comprehensive solution for all applications: substation, busbar, transformer and motor, as well as generators and capacitors. Different types of Sepam 2000 are proposed for each type of equipment to be protected. For example, there are 30 different types of Sepam 2000 dedicated to protection, monitoring and control of transformers. Each Sepam 2000 is an optimized solution, designed to provide an exact response to the actual requirements of a functional application, including all the required functions, ready to use. Focused on performance, Sepam 2000 includes the following functions: b metering functions: measurement of current and voltage, measurement of power and active and reactive energy, etc. b protection functions: directional phase and earthing protection, differential transformer or machine protection, etc. b monitoring and control functions: in its function as a programmable logical controller, Sepam 2000 is pre-programmed to carry out standard monitoring and control functions, and can be reprogrammed to handle any specific automatic control function. E61780 Sepam 2000 PE60118 PE60117 PE60116 To choose the type of Sepam 2000 best suited to your application, the “Sepam range” catalogue includes selection charts for the whole Sepam 2000 range. (document AC0401). A “Sepam 2000 Selection Guide” software package is also available for computer-aided selection of Sepam 2000 for a given application. Sepam 100 units Sepam 100 units round off the Sepam range and can be installed either separately or combined with either Sepam series 20, 40 and series 80 or Sepam 2000. Sepam 100 has several variants: b Sepam 100 MI, local breaking device control and signalling modules (many different line diagram types are available); b Sepam 100 LD, high impedance differential protection; b Sepam 100 LA, self-powering protection (back-up protection without auxiliary power supply). Sepam 100MI 24 Sepam 100LD Sepam 100LA Schneider Electric Protection, monitoring and control Functions Measurements currents voltages and frequencies powers and energies temperatures Protection phase earth imbalance directional differential restricted earthing differential overload motor voltage frequency uncoupling (df/dt) specific Sepam offer panorama Sepam 2000 Applications Substation Busbar Transformer Motor Generator Capacitor I1/I2/I3/I0 IM1/IM2/IM3 Itrip 1/2/3/0 U21/U32/U13 V1,V2,V3 V0 Vd f P/Q, PM/QM, cos ϕ Ea/Er b b b b b b b b b b b b b b b b b b b b b b b b b b 67N 87M b b b b 87M b b 49 b 27/59 ANSI codes 50/51 50N/51N 46 67/67N 87T/87M/87B 64REF 49/49T/38 37/48/51LR/66 59/27 59N 81H/81L 81R Network diagnosis disturbance recording Switchgear diagnosis operation time trip currents, sum of breaking currents A2 trip circuit monitoring watchdog Communication protocol interface Monitoring and control inputs/outputs basic maximum breaking device control logical selectivity customizing 0 parameter setting programming b b b b b b 87T b b b b b b 32P 79 27R b b 25 27D b b b b b b 50N/51 (neutral point) 50/51 (tank earth) 27R 32P, 32Q/40 32P, 32Q/40 27D/47 25 50V/51V cap. bank imbalance b b b b b b b b b b b b b b b b b b 2 recordings of 86 periods b b b b b b 1 output/4 contacts: 2 x (1NC + 1NO) Modbus RS485 2 or 4 wire 10I/6O in/out 26I/14O in/out b b b b b b b b b b b b b available functions Schneider Electric 25 Sepam series 20, series 40, series 80 Protection, monitoring and control 0 Sepam protection relay A range of solutions adapted to your application b substation protection (incomers, feeders, busbars); b transformer protection; b motor and generator protection. A comprehensive solution, integrating all of the necessary functions for your application b effective protection of people and property; b accurate measurements and detailed diagnosis; b integral equipment control; b local or remote indication and operation. Flexibility and upgrading capability To adapt to as many situations as possible, and allow for future installation upgrading, optional modules may be added to Sepam at any time for new functions. PE40013 PE55170 The Sepam range of protection relays is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations at all levels of voltage. It includes 3 families: b Sepam series 20, for usual applications; b Sepam series 40, for demanding applications; b Sepam series 80, for custom applications. To cover all needs, from the simplest to the most complete. 1 4 3 5 Sepam series 20, series 40 and series 80 7 6 Sepam series 80 modular architecture 4- 2 independent Modbus 1- Base unit, with integrated communication ports. or remote advanced User Machine Interface. b direct connection to 2-wire RS 485, 4-wire RS 485 and 2- Parameter and protection fiber optic networks; settings saved on removable b connection to Ethernet TCP/IP memory cartridge. network via PowerLogic System 3- 42 logic inputs and webserver (Transparent Ready™). 23 outputs relays with 5- Processing of data from 3 optional modules providing 16 temperature sensors. 14 inputs and 6 outputs. 6- 1 low level analog output, 0-10 mA, 4-20 mA or 0-20 mA. 7- Software tools: b Sepam parameter and protection setting and control logic customization; b local or remote installation operation; b retrieval and display of disturbance recording data. Simplicity Easy installation b the same, easy-to-install remote modules for all Sepam units. Commissioning assistance b predefined functions implemented by simple parameter setting; b user-friendly, powerful PC setting software tool. Intuitive use b clear graphic LCD display of all data required for local operation and installation diagnosis; b working language may be customized to be understood by all users. 26 Schneider Electric Protection, monitoring and control Sepam series 20, series 40, series 80 Selection guide Sepam Protections 0 DE50116 Sepam series 80 b 42 logic inputs b 23 relay outputs b 16 temperature probe inputs b 2 Modbus communication ports b logic equations editor DE50115 Sepam series 40 b 10 logic inputs b 8 relay outputs b 16 temperature probe inputs b 1 Modbus communication port b logic equations editor DE50104 DE50114 Sepam series 20 b 10 logic inputs b 8 relay outputs b 8 temperature probe inputs b 1 Modbus communication port DE50113 Basic Specific Current protection Substation Transfo. Motor S20 T20 Generator Busbar M20 B21 Voltage and frequency protection Loss of mains (ROCOF) B22 S40 Current, voltage and frequency protection Directional earth fault S41 Directional earth fault and phase overcurrent S42 Current, voltage and frequency protection T40 G40 M41 T42 S80 Directional earth fault S81 T81 Directional earth fault and phase overcurrent Transformer or machinetransformer differential S82 T82 Machine differential Schneider Electric Applications T87 M81 G82 M88 G88 M87 G87 27 Protection, monitoring and control Instrument transformers Conventional current transformers Conventional current transformers are used to provide power to metering, measuring or control devices. They measure the value of primary current from 10 A to 3150 A. Schneider Electric has drawn up a list of current transformers which are appropriate for use with digital protection devices in order to make it easier to determine accuracy characteristics. This list is available in the selection guide on page 56. For contactor cubicle AD1 E28676 Transformer ARJP1/N2J b single primary current, double secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring* cl.0.5 protection* 5P20 ARJP1-2 or 3 10 20 1.2 2.4 1 1 15 VA 2.5 VA 30 3.6 1 50 6 1 75 10 1 100 10 1 150 10 1 200 10 1 250 10 1 For cubicles AD1-CL1-GL1-AD2-CL2-GL2-AD4-GL4 Transformer ARJP2/N2J b double primary current, double secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring* cl.0.5 protection* 5P20 50-100 40 1 75-150 40 1 100-200 31.5-40 1 5-10VA 2.5-5VA 2.5-5VA 2.5-5VA 150-300 40 1 10-20VA 2.5-5VA 200-400 40 1 7.5-15VA 5-10VA 250-500 40 1 10-20VA 5-10VA 600 50 1 20VA 7.5VA 750 50 1 20VA 7.5VA For cubicles AD1-CL1-GL1-AD2-CL2-GL2-AD4-GL4 Transformer ARJP3/N2J b single primary current, double secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring* cl.0.5 protection* 5P20 1000 50 1 30 VA 10 VA 1250 50 1 30 VA 10 VA For cubicles AD3-CL3-GL3-AD4-GL4 E74399 Transformer ARJA1/N2J b single primary current, double secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring cl.0.5 protection 5P20 1500 50 1 30 VA 15 VA 2000 50 1 30 VA 15 VA 2500 50 1 30 VA 15 VA ARJA1 For cubicles AD3-CL3-GL3 E74400 Transformer ARO1a/N3 b single primary current, triple secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring* cl.0.5 protection* 5P20 ARO1 28 3150 50 1 30 VA 7.5 VA * the secondary current for measuring and protection can be of 1 A or 5 A. Schneider Electric Protection, monitoring and control Instrument transformers (cont.) E72965 Low voltage toroid type current transformers For cubicles AD1-AD2-AD4 with one single-pole cable Transformer ARC2 b single primary current, single secondary current for protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) protection 5P20 75 50 1 2.5 VA 100 50 1 2.5 VA 150 50 1 5 VA 200 50 1 5 VA 250 50 1 5 VA 300 50 1 5 VA 400 50 1 5 VA 600 50 1 7.5 VA b single primary current, double secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring protection 5P20 200 50 1 5 VA cl.1 2.5 VA 250 50 300 50 400 50 600 50 10 VA cl.0.5 5 VA 10 VA cl.0.5 5 VA 15 VA cl.0.5 5 VA 15 VA cl.0.5 5 VA For cubicles AD1-AD2-AD4 with two single-pole cables Transformer ARC3 b single primary current, double secondary current for measurement or protection b frequency 50-60 Hz I1n (A) Ith (kA) t (s) measuring cl.0.5 protection 5P20 750 50 1 20 VA 7.5 VA 1000 50 1250 50 30 VA 10 VA 30 VA 10 VA CSP type broad-range current transformers E34400 CSP type current sensors, designed for the Sepam 2000, work on the Rogowski coil principle. CSP sensors use a winding around an insulating core with no magnetic circuit, which prevents saturated and residual flux. Therefore, they are completely linear, and deliver an accurate secondary signal, a perfect image of the primary current, without distortion for both steady and transient states in the primary circuits. These sensors have much wider primary current ranges than current transformers do. The combining of CSP sensors and Sepam 2000 gives a consistent protection and measurement system. This in turn makes current sensor specification simpler (choosing from 3 sensors for a rated insulation level of 24 kV). CSP sensor Sensors Rated current CSP 3110 CSP 3210 CSP 3310 CSP 3410 30 to 300 A 160 to 640 A 160 to 1600 A 500 to 2500 A For Sepam 2000, the primary current is chosen to be lower than the indicated range. Cubicle type AD1 - AD2 - AD4 AD1 - AD2 - AD4 CL1 - CL3 - CL4 AD3 - AD4 CL3 - CL4 I rated Isc (kA) 1 s Type 30 - 300 160 - 1250 40 50 500 - 2500 50 CSP 3110 CSP 3310 CSP 3210 CSP 3410 CSP cannot be used with differential protection devices. They should be preferred in all other cases in which measurement and protection uses Sepam. AD4 and CL4 limited to 31.5 kA. Schneider Electric 29 Protection, monitoring and control 0 Instrument transformers (cont.) Voltage transformers These supply power to: b measuring, metering and monitoring devices; b relays or protective devices; b auxiliary LV sources for various types of switchgear; all these devices are protected and insulated from the MV section. They are installed at the bottom of the functional unit. In the withdrawable fuse version, the voltage transformers are attached to a side wall. The energized part is entirely encapsulated in an epoxy resin, which provides both electrical insulation and excellent mechanical strength. They include the following models: b with one insulated MV terminal, for connection between neutral and phase conductors in three-phase systems with withdrawable MV fuses; b with two insulated MV terminals, for connection between phase conductors. For cubicles AD1-CL1-GL1-TT1-AD2-CL2-GL2-AD3-CL3-GL3 E28679 Transformer VRQ3n/S2 b phase-earth b frequency 50-60 Hz VRQ3 primary voltage (kV) 1st secondary voltage (V) 2nd secondary voltage (V) 1st secondary accuracy class (VA) 2nd secondary accuracy class (VA) 3/3 3.3/3 5.5/3 6/3 6.6/3 10/3 11/3 13.8/3 15/3 100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3 100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3 30-50 VA cl.0.5 50 VA cl.0.5 For cubicles AD4-CL4-TT4 E74401 Transformer VRQ1N/S2 b phase-earth b frequency 50-60 Hz VRQ1 primary voltage (kV) 1st second. voltage (V) 2nd second. voltage (V) 1st secondary accuracy class (VA) 2nd secondary accuracy class (VA) 20/3 100/3 100/3 50 VA cl.0.5 100 VA cl.1 50 VA cl.3P 22/3 110/3 110/3 For cubicles AD2-CL2-GL2-TT2-AD3-CL3-GL3 E28680 Transformer VRC1/S1F b phase-phase b frequency 50-60 Hz primary voltage (kV) secondary voltage (V) accuracy class (VA) 3.3 5.5 110 110 75 VA cl.0.5 6.6 110 11 110 13.8 110 15 100 VRC1/S1F 30 Schneider Electric Protection, monitoring and control 0 Instrument transformers (cont.) For cubicle AD1 contactor This transformer provides power to the coil in order to keep the magnetic circuit of the contactor closed. MT20104 Transformer VRCR/S1 b phase-phase b frequency 50-60 Hz primary voltage (kV) secondary voltage (V) accuracy class (VA) 3.3 110 50 VA cl.0.5 5.5 110 6.6 110 VRCR E28678 Zero sequence core balance current transformers (CSH type) CSH 120 and CSH 200 core balance CT’s, provide more sensitive protection by direct measurement of earth fault currents. Specifically designed for the Sepam range, they can be directly connected to the Sepam “residual current” input. They are only different in terms of their diameter: b CSH 120 - 120 mm internal diameter; b CSH 200 - 200 mm internal diameter. CSH toroid CT Schneider Electric 31 Switchgear Withdrawable parts PE55046 0 Withdrawable part Extraction table 32 Schneider Electric Switchgear 0 Withdrawable parts (cont.) These include: b the circuit breaker or contactor with their opening and closing mechanism, the disconnector truck or the earthing truck; b the lever-type propulsion mechanism for racking in-out; b interlocks to fix the withdrawable parts onto the fixed part; MCSet circuit breakers LF1-2-3, SF1-2, switches and R400-R400D contactors use sulphur hexafluoride (SF6) for insulation and breaking. The live parts are housed in an insulating enclosure in the sealed pressure system in compliance with IEC 62271-100. The devices used to equip the MCset range of functional units have outstanding features: b long service life; b maintenance-free live parts; b high electrical endurance; b very low overvoltages; b operating safety; b insensitivity to the environment; b breaking capacity and dielectric strength maintained at atmospheric pressure; b low filling pressure. Withdrawable parts Circuit breaker DE55112 A circuit breaker is a safety device enabling switching and protection of electrical distribution networks. Installed in the MCset cubicle, it protects all components situated downstream during a short-circuit. Earthing truck DE55113 The earthing truck is a safety feature which allows the cubicle busbar to be earthed. It is installed instead of the circuit breaker and has lots of interlock possibilities. Disconnector truck DE55114 The disconnector truck enables the upper and lower part of the cubicle to be shortcircuited. It is installed instead of the circuit breaker and has the same interlock possibilities. Schneider Electric 33 Withdrawable parts LF circuit breaker Switchgear Presentation PE55051 LF1-2-3 circuit breakers equip cubicles AD1-2-3 and CL1-2-3 for voltage values of between 7.2 and 17.5 kV. Breaking is based on the principle of self-expansion in SF6. The 3 main poles are contained in an insulating enclosure of the sealed system type, which requires no filling during the service life of the device (in conformity with standard IEC 62271-100). This gas-tight enclosure is filled with SF6 at a low relative pressure of 0.15 Mpa (1.5 bars). Low pressure filling ensures reliable gas tightness. LF circuit breakers are equipped with a pressure switch. LF1-2-3 circuit breakers are actuated by RI type stored energy release mechanisms. DE55117 Principle of the self-expansion breaking technique b a Fig. 1 Fig. 2 d c e Fig. 3 34 This technique is the result of a large amount of experience in SF6 technology and significant research effort. It combines the rotating arc technique with thermal expansion to create the conditions to cool and extinguish the arc. This enables the control mechanism energy to be reduced as well as arc contact erosion; mechanical and electrical endurance is therefore increased. The operating sequence in a self-expansion breaking chamber whose moving part is actuated by the mechanical control is as follows: b Fig. 1: the circuit breaker is closed; b Fig. 2: on opening of the main contacts (a), the current is transferred to the breaking circuit (b); b Fig. 3: on separation of the arcing contacts, an electrical arc appears in the expansion chamber (c); the arc rotates under the effect of the magnetic field created by the coil (d) which has the breaking current running through it; the overpressure produced by the increase in gas temperature in the gas expansion chamber (c) causes gas flow which blows the arc within the tubular arcing contact (e), thus causing it to extinguish when the current passes to zero; b Fig. 4: circuit breaker open. Fig. 4 Schneider Electric Withdrawable parts LF circuit breaker Switchgear (cont.) Characteristics of LF circuit breakers in MCset cubicles IEC 62271-100 Rated voltage Insulation level Rated nominal current (la) Breaking capacity Isc Making capacity Short time withstand current Capacitor breaking capacity (1) Rated operating sequence Approximate operating time for supply of releases at Un Mechanical endurance kV, 50/60 Hz kV, rms 50 Hz - 1 min kV, impulse 1.2/50 µs A 630 1250 2500 3150 kA, rms kA, peak kA, rms 3 s kA, rms 1 s A O-3 min-CO-3 min-CO O-0.3 s-CO-3 min-CO O-0.3 s-CO-15 s-CO ms opening breaking closing number of switching operations LF1/MCset 1 LF2/MCset 2 7.2 20 60 b b 7.2 20 60 b b 31.5 80 31.5 12 28 75 b b 31.5 80 31.5 440 50 125 40 50 440 b b b 48 65 65 10 000 b b b 48 65 65 10 000 12 28 75 b b 40 100 40 LF3/MCset 3 17.5 38 95 b b 31.5 80 31.5 7.2 20 60 12 28 75 17.5 38 95 b b 50 125 40 50 440 b b 50 125 40 50 b b 31.5 80 31.5 b b 40 100 40 b b b 48 65 65 10 000 (1) For other values, please consult us. Schneider Electric 35 Switchgear Withdrawable parts LF circuit breaker (cont.) RI operating mechanism 055120 LF range circuit breakers are actuated by an RI operating mechanism, that ensures a switching device closing and opening rate that is independent of the operator. This operating mechanism, which is always motorised, can perform remote control functions and enables fast reclosing cycles. The RI operating mechanism includes: b a spring system that stores the energy needed to close and open the breaker; b a manual spring charging system; b an electrical motor-operated spring charging device that automatically recharges the mechanism as soon as the contacts close (recharging time < 15 s); b two mechanical push buttons for opening and closing, accessible with the cubicle door open (circuit breaker in test position). For control with the door closed (circuit breaker racked in): v circuit breaker opening by controlling the propulsion device, v circuit breaker closing optional. b an electrical closing system comprising a closing release for remote control and an anti-pumping relay; b an electrical opening system comprising one or more opening releases of the following type: v single or double shunt, v undervoltage. b an operation counter; b an “operating mechanism charged” indication contact (M3); b an spring charging limit switch contact (M1-M2); b a black-white mechanical “open-closed” position indicator; b a multi-pin connector to isolate auxiliary circuits in the “racked out” position. Auxiliary contacts The RI operating mechanism is equipped with a block of 14 auxiliary contacts including: b 1 changeover contact for the electrical operating mechanism; b 1 changeover contact for indication; b 1 contact for the shunt release. The number of available contacts depends on the position of the available operating mechanism and the options chosen (see table opposite). Contact characteristics Rated current Breaking capacity 36 AC DC 10 A 10 A at 220 V (cos ϕ u 0.3) 1.5 A at 110 or 220 V (L/R y 0.01 s) Schneider Electric Withdrawable parts LF circuit breaker Switchgear (cont.) RI operating mechanism I Type of auxiliary Supply voltage Spring charging motor AC (V) 50 Hz 60 Hz DC (V) AC (VA) DC (W) possible combinations of auxiliaries and quantities or or or or Consumption Closing release Opening release Shunt single double 48 - 110 - 125 - 220 120 - 240 24 - 30 - 48 - 60 - 110 - 125 - 220 380 160 380 50 b b b b b b b b b b 160 50 b b Undervoltage 400/100 (1) 100/10( 1) b 320 100 b b consult us b Available contact NC NO Ch 5 5 5 5 5 4 4 3 3 5 1 1 1 1 1 (1) Pick-up/latched consumption. Auxiliaries diagram Circuit breaker Anti-pumping relay Spring charging motor End of charging contacts Operating mechanism charged indication Circuit breaker auxiliary circuits Latched tripping contact Closing push button (external) Opening push button for shunt trip release (external) Sm3 Opening push button for undervoltage release (external) Sn Closing disabling contact (external) SP Pressure switch contact SQ Device ready to operate contact YF Closing release Y01-Y02 Shunt opening release YM Undervoltage opening release RI circuit breaker operating mechanism DE55125 J KN M M1-M2 M3 QF SE Sm1 Sm2 Sm1 Sm2 Sm3 Sn M Q J M2 M1 S KN Y02 Y01 M3 YM SP SQ Y Schneider Electric 37 Withdrawable parts SF circuit breaker Switchgear Presentation PE55052 SF range circuit breakers equip cubicles AD4 and CL4 for rated voltage values of 24 kV. They work on the basis of the “puffer” type principle in SF6, which is used as a breaking and insulating medium. Each of the 3 poles have an independent insulating enclosure which forms a filled pressure system in compliance with IEC standard 62271-100. Each pole forms a gas-tight unit filled with low pressure SF6 at low relative pressure of 0.05 to 0.35 MPa (0.5 to 3.5 bars) according to the performance level required. No filling is required during the equipment’s life. According to the performance levels, it is possible to optionally equip SF6 circuit breakers with a pressure switch to act on an alarm in the case of a pressure drop. SF6 range circuit breakers are actuated by a GMH type spring mechanism. DE55118 Principle of the puffer breaking technique. The main contacts and arcing contacts are initially closed (Fig. 1). Pre-compression (Fig. 2) When the contacts begin to open, the piston slightly compresses the SF6 gas in the pressure chamber. Fig. 1 Fig. 2 Arcing period (Fig. 3) The arc appears between the arcing contacts. The piston continues its downward movement. A small quantity of gas, directed by the insulating nozzle is injected across the arc. For the breaking of low currents, the arc is cooled by forced convection. However, for high currents, thermal expansion causes the hot gases to move towards the cooler parts of the pole unit. The distance between the two arcing contacts becomes sufficient for the current to be broken when it reaches the zero point, due to the dielectric properties of the SF6. Sweeping overstroke (Fig. 4) The moving parts finish their movement and the injection of cold gas continues until the contacts are completely open. Fig. 3 38 Fig. 4 Schneider Electric Withdrawable parts SF circuit breaker Switchgear (cont.) Characteristics of SF circuit breakers in MCset cubicles Electrical characteristics Rated voltage Insulation level Rated nominal current (Ia) kV, 50/60 Hz kV, rms 50 Hz - 1 min kV, impulse 1.2/50 µs A Breaking capacity Isc Making capacity Short time withstand current kA, rms kA, peak kA, rms 3 s Capacitor breaking capacity A Rated operating sequence O-3 min-CO-3 min-CO O-0.3 s-CO-3 min-CO O-0.3 s-CO-15 s-CO ms Approximate operating time for supply of releases at Un Mechanical endurance Schneider Electric SF1/MCset 4 630 1250 2500 630 1250 2500 opening breaking closing number of switching operations SF2/MCset 4 24 50 125 b 24 50 125 b b 16 40 16 25 63 25 440 440 875 b b b 50 65 70 10 000 b b b 24 50 125 b 25 63 25 1750 b b b 50 65 70 10 000 24 50 125 b b b 31.5 80 31.5 440 875 1750 b b b 39 Switchgear Withdrawable parts SF circuit breaker (cont.) GMH operating mechanism 028368 SF range circuit breakers are actuated by a GMH operating mechanism that ensures a switching device closing and opening rate that is independent of the operator. This operating mechanism, always motorised, enables remote operation and fast reclosing cycles. The GMH operating mechanism includes: b a spring system that stores the energy needed to close and open the breaker; b a manual spring charging system; b an electrical motor spring charging device that automatically recharges the mechanism as soon as the contacts close (recharging time < 15 s); b two mechanical push buttons for opening and closing, accessible with the cubicle door open (circuit breaker in test position); b an electrical closing system comprising a closing release for remote control and an anti-pumping relay; b an electrical opening system comprising one or more opening releases of the following type: v shunt, v undervoltage. b an operation counter; b an optional “operating mechanism charged” indication contact; b an end of charging contact; b a black-white mechanical “open-closed” position indicator; b a multi-pin connector to isolate auxiliary circuits in the “racked out” position. Auxiliary contacts The GMH operating mechanism is equipped with a block of 14 auxiliary contacts including: b 1 changeover contact for the electrical operating mechanism; b 1 changeover contact for indication; b 1 contact for the shunt release. Contact characteristics Rated current Breaking capacity 40 AC DC 10 A 10 A at 220 V (cos ϕ u 0.3) 1.5 A at 110 or 220 V (L/R y 0.01 s) Schneider Electric Withdrawable parts SF circuit breaker Switchgear (cont.) GMH operating mechanism characteristics Type of auxiliaries Supply voltage Spring charging motor AC (V) 50 Hz 60 Hz DC (V) AC (VA) DC (W) Possible combinations of auxiliaries and quantities or or or or or Consumption Closing release Opening release Shunt single double 50 - 100 - 140 - 200 - 250 - 380 60 - 110 - 127 - 220 - 250 24 - 33 - 48 - 60 - 110 - 136 - 220 - 260 700 120 570 70 b b b b b b b b b b b b 120 70 b b b 240 140 b b Undervoltage 400/100 (1) 100/10 (1) b b b Available contact NC NO Ch 5 5 5 5 5 5 4 4 3 3 3 5 1 1 1 1 1 1 (1) Pick-up/latched consumption. Auxiliary diagram Sn Circuit breaker Spring charging motor Closing release End of charging contact Auxiliary circuit breaker contacts Anti-pumping relay Latched release contact Shunt opening releases Undervoltage opening release Operating mechanism charged contact Pressure switch contact Device ready to operate contact Closing push button (external) Opening push button for shunt releases (external) Opening push button for undervoltage releases (external) Closing disabling contact (external) GMH circuit breaker operating mechanism DE55126 J M YF M1-M2 QF KN SE Y01-Y02 YM M3 SP SQ Sm1 Sm2 Sm3 Sm1 Sm2 Sm3 Sn M Q M1 M2 SE S KN M3 SQ Y01 Y Y02 Y Schneider Electric 41 Withdrawable parts Rollarc contactor Switchgear Description PE55053 b three main poles located in the pressurised enclosure; b electromagnetic operating mechanism with: v magnetic latching for Rollarc 400, v mechanical latching for Rollarc 400D. b upstream and downstream terminals for power circuit connections; b pressure switch equipped with a NO contact for continuous monitoring of SF6; b mechanical interlocking of the contactor in the open position to prevent racking in or out with the contacts closed; b 3 HPC fuses with striker pin and auxiliary contact to trip the contactor. An optimum solution DE55119 The Rollarc contactor uses rotating arc breaking in SF6 gas. A magnetic field causes the arc to rotate between the arcing contacts, the field is created by the passage of the arc through a blow-out coil (Fig. 1). The rotation movement cools the arc by forced convention. The arc rotation rate depends on the current to be broken. The energy required to extinguish the arc is supplied by the electrical system. The operating mechanism is simple and economical. Modulation of the rotation rate ensures soft breaking without any dangerous overvoltage or current chopping. The Rollarc has a high breaking capacity and may be used without a time delay in combination with fuses. Fig. 1 DE55120 Contactor operation Fig. 2 Fig. 3 Fig. 4 Fig. 5 42 At the beginning of the opening operation, the main contacts and arcing contacts are closed (Fig. 2). The main circuit is interrupted by the separation of the main contacts (Fig. 3). The arcing contacts are still closed. The arcing contacts separate shortly after the main contacts. The arc that is created is subjected to the electromagnetic field produced by the coil, which is proportional to the current to be interrupted. The arc rotates rapidly, driven by the electromagnetic force and is cooled by forced convection (arcing period, Fig. 4). Due to the phase-shift between the current and the magnetic field, this force is still significant around the current zero point. At the zero point, the gap between the two arcing rings recovers its original dielectric strength due to the intrinsic properties of SF6 (contactor open, Fig. 5). Schneider Electric Withdrawable parts Rollarc contactor Switchgear (cont.) Electrical characteristics of the Rollarc R400/R400D (1) in MCset cubicles Rated voltage Dielectric strength (kV) 7.2 12 Fuse breaking Short time withstand capacity (2) current (3) 50 Hz 1 min (kV rms) Max. operating Rated current contactor current Impulse 1.2/50 µs (kV peak) (A) (A) (kA rms) (kA rms) (kA peak) 20 28 60 60 50 50 50 50 125 125 250 200 400 400 (1) Rollarc 400: without mechanical latching. Rollarc 400D: with mechanical latching. (2) For operating voltages of 3 to 12 kV. (3) Limited by fuses. E72898 Electrical endurance E13151-1 Maximum switchable power Calculation assumptions (motor) b ratio between starting current Id and maximum current In: Id/In = 5 ± 20%; b power factor x efficiency 0.88 x 0.9 = 0.792 for 300 y P < 600 kW 0.9 x 0.92 = 0.828 for 600 y P < 1100 kW 0.92 x 0.94 = 0.865 for 1100 y P < 5000 kW; b starting time < 10 s; b starts per hour y 3 according to IEC 60644. Operating voltage (kV) E13151-2 Fig. 1 3.3 4.16 5 5.5 6 6.6 10 (fus. 200 A) Direct starting motor (kW) with 315 A fuses Transformer (kVA) with 315 A fuses Capacitor (kvar) with 315 A fuses 1170 1480 1780 1960 2130 2350 2000 1430 1800 2160 2380 2600 2800 2250 1000 1260 1520 1670 1820 2000 2000 Operating schemes Temporary service or periodic service The two curve systems (Fig. 1 and 2) can be used to determine the maximum current surges accepted by the Rollarc 400 contactor, in temporary or periodic service. b temporary service: knowing the steady state current Ip, we determine the maximum duration Ts of a current surge Is from graph 1 (Fig. 2). b periodic service: knowing 3 of the following 4 parameters: v overcurrent Is, v overcurrent time Ts, v cooling current Ir, v cooling time Tr. We determine the 4th parameter using graph 2 (Fig. 1 and 2). Fig. 2 Schneider Electric Operating time b opening time 20 to 35 ms; b arcing time: < 20 ms; b closing time: 80 to 120 ms. 43 Switchgear Withdrawable parts Rollarc contactor (cont.) Fuses E32130 The fuses used are of the FUSARC CF or FERRAZ type (Standard IEC 60282.1 and DIN 43625) with high breaking capacity. Substantial fault current limitation reduces the electrodynamic stresses on the load-side components (contactor, cables, CT, etc). A “blown fuse” device is used to open the three poles of the contactor. Rated voltage (kV) Max. fuse rating (A) Breaking capacity (kA) * please consult us E32151 Fig. 1 7.2 315 50 12 250* 50 Trip curves The trip curves for FUSARC CF (Fig. 1) and FERRAZ (Fig. 2) fuses are shown opposite. These are the average curves with an rms current value tolerance ± 10%. Limitation curves FUSARC CF (Fig. 3) and FERRAZ (Fig. 4) fuses have current limiting capacity. These curves give the maximum value of the limited breaking current Ic (in kA peak), as a function of the value Ip (in kA rms) of the presumed current that would be created if there were no protection. For further details ask for the fuse catalogues. Operating mechanism Fig. 2 Supply voltage (1) DC: 48, 110, 127 and 220 V AC: 50, 100, 110, 127 and 220 V Acceptable variations: +10% –15% E32131 b Rollarc 400 contactor The contactor is closed by the pick-up coils. The latching coils are inserted in the circuit at the end of the stroke of the contactor. Consumption DC AC Pick-up 1050 W 900 VA Latched 30 W 30 VA b Rollarc 400D contactor The contacts are mechanically latched in the closed position. They are opened by a shunt trip release which releases the latching. Consumption DC AC Fig. 3 Pick-up coil (2) 1050 W 900 VA Shunt trip 80 W 100 VA (1) Optional supply possible by auxiliary transformer (see page 31). (2) Supply time < 0.12 s. E32152 Auxiliary contacts Auxiliary contacts are of the common point changeover type. The following are available: b 9 contacts for the Rollarc 400; b 8 contacts for the Rollarc 400D. Contact characteristics: Rated current: 10 A Breaking capacity: DC (L/R y 0.01 s): 2 A at 110 V AC (cos.ϕ u 0.3): 10 A at 220 V Fig. 4 44 Schneider Electric Withdrawable parts Rollarc contactor Switchgear (cont.) Auxiliaries diagram SQ1 X20 X51 X61 XAP XE XU YD YF YM S4 MV fuses LV fuse R400 AC MV contactor Operation counter Locking contact activated by the pretrip push button and during racking in/out operations Contactor limit switch LV connecter, 42 pins + earth Control plate Contactor terminal block Instantaneous auxiliary relay Instantaneous auxiliary control relay 0.6 s time delay auxiliary relay Shunt trip coil Closing coils Latching coil Trip button Operating mechanism for Rollarc 400 contactors E32149 FU1 FUBT K1 P61 S61 E32150 Operating mechanism for Rollarc 400D contactors Schneider Electric 45 DI switch cubicle Switchgear Switch 2 DE55121 E74222 The three rotating contacts are placed in an enclosure filled with gas to a relative pressure of 0.04 MPa (0.4 bars). The system offers maximum operating reliability: b gas tightness The SF6 filled enclosure is of the “sealed pressure system type”. Sealing tightness is always checked in the factory. b safety v the switch may be in one of three positions: “closed”, “open” or “earthed”, giving a natural interlocking system that prevents operator error. Moving contact rotation is driven by a fast acting mechanism that is independent of the operator. v the device combines the breaking and disconnecting functions. v the SF6-enclosed earthing switch has a short-circuit making capacity in compliance with standards. b breaking principle The outstanding qualities of SF6 gas are used to extinguish the electrical arc. To increase cooling of the arc, a relative movement is created between the arc and the gas. The arc strikes when the fixed and moving contacts separate. The combination of the current and a magnetic field created by a permanent magnet causes the arc to rotate around the fixed contact, extending and cooling it until it is extinguished at current zero point. The distance between the fixed and moving contacts is then sufficient to withstand the recovery voltage. This system is both simple and dependable, and it provides improved electrical endurance due to very low wear of contacts. 6 1 3 4 5 enclosure cover operating shaft fixed contact moving contact seal DE55122 1 2 3 4 5 6 Contacts closed 46 Contacts open Contacts earthed Schneider Electric Switchgear DI switch cubicle (cont.) 041497R Operating mechanism and auxiliaries 041496R CI2 double function operating mechanism b switch function: v independent closing in two steps: - operating mechanism recharged by a hand lever or motor, - stored energy released by a push button or trip unit, v independent opening by push button (O) or trip unit. b earthing switch function: v independent closing by a hand lever. Operating energy is provided by the compression of a spring which causes the contacts to close or open after the neutral point is passed. b auxiliary contacts: v switch (2 O + 2 C), v switch (2 O + 3 C) and earthing switch (1 O + 1 C), v switch (1 C) and earthing switch (1 O + 1 C) if motor option. b motor option b opening release: v shunt, v undervoltage (option). b closing release: shunt trip. b fuse blown release: any fuse blown trips the opening of the switch. Motor option and releases Un Supply Motor option AC (50 Hz) (1) DC (V) (W) (VA) (s) Opening releases Shunt (W) (VA) Undervoltage pick-up latched Closing releases Shunt (W) (VA) 24 48 110 125 220 120 230 200 200 <7 <7 200 (W) (VA) (W) (VA) 250 300 300 300 400 750 280 550 50 40 400 750 160 4 200 250 300 300 300 (1) Please consult us for other frequencies. Schneider Electric 47 DI switch cubicle Switchgear (cont.) Transformer protection By fuse-switches MT55097 The fuse rating to install in DI2 and DI4 protection cubicles depends amongst other things on the following information: b operating voltage b transformer power b fuse technology (manufacturer). Various types of fuses with medium energy strikers can be installed: b according to standard UTE NCF 64.210: Soléfuse type b according to IEC recommendation 60282.1 and dimensions DIN 43.625: Fusarc CF type. 35 Rated voltage ø 55 35 ø6 23 E.g.: General case for protection of a 400 kVA-10 kV transformer, we will choose Soléfuse fuses, rated at 43 A or Fusarc CF fuses rated at 50 A. ø 45 33 Fusarc CF L L (kV) (A) (mm) Soléfuse (UTE standards) 7.2 6.3 to 125 450 12 100 17.5 80 24 6.3 to 63 Fusarc CF (DIN standards) 7.2 125 292 12 6.3 to 20 292 25 to 40 292 50 to 100 292 24 6.3 to 20 442 25 to 40 442 50 to 63 442 80 442 Others (DIN standards) 7.2 160 292 200 292 12 125 292 160 292 200 292 17.5 125 442 24 100 442 125 442 Soléfuse 450 Rating Ø Ø Weight (mm) (kg) 55 2 86 50.5 57 78.5 50.5 57 78.5 86 3.3 1.2 1.5 2.8 1.6 2.2 4.1 5.3 85 85 67 85 85 85 85 85 3.8 3.8 2 3.8 3.8 5.4 5.4 5.4 33 ø6 23 Fuse selection table Rating in A - no overload at - 5°C < t < 40°C. Please consult us for overloads or for operation above 40°C. Operating voltage (kV) Transformer power (kVA) 25 50 100 125 160 Soléfuse (standards UTE NFC 13.100, 64.210) 5.5 6.3 16 31.5 31.5 63 6.3 6.3 16 16 31.5 10 6.3 6.3 16 16 16 15 20 6.3 6.3 6.3 6.3 16 Soléfuse (general case, standard UTE NFC 13.200) 3.3 16 16 31.5 31.5 31.5 5.5 6.3 16 16 31.5 31.5 6.6 6.3 16 16 16 31.5 6.3 6.3 16 16 16 10 13.8 6.3 6.3 6.3 16 16 6.3 6.3 16 16 16 15 20 6.3 6.3 6.3 6.3 16 22 6.3 6.3 6.3 6.3 16 Fusarc CF (DIN standard) 16 25 40 50 50 3.3 5.5 10 16 31.5 31.5 40 10 16 25 31.5 40 6.6 6.3 10 16 20 25 10 13.8 6.3 10 16 16 20 6.3 10 10 16 16 15 20 6.3 6.3 10 10 16 22 6.3 6.3 10 10 10 48 800 Rated 1000 1250 1600 2000 2500 voltage (kV) 200 250 315 400 500 630 63 31.5 16 16 63 31.5 16 16 63 63 43 16 63 63 43 43 63 43 43 63 43 43 43 43 63 63 31.5 31.5 16 16 16 16 63 63 43 31.5 16 16 16 16 100 63 43 31.5 31.5 31.5 16 16 100 80 63 43 31.5 31.5 31.5 16 80 80 43 31.5 31.5 31.5 31.5 100 100 63 43 43 31.5 31.5 125 125 80 63 43 43 31.5 125 80 63 63 43 43 100 80 80 63 63 80 50 50 31.5 25 20 16 16 80 50 50 40 31.5 25 25 20 100 63 63 50 31.5 31.5 25 25 125 80 80 50 40 40 31.5 25 125 100 80 63 50 50 40 31.5 160 125 100 80 50 50 40 40 200 125 125 80 63 63 50 40 160 125 100 80 80 50 50 160 160 100 80 80 63 50 7.2 63 43 63 24 7.2 12 17.5 24 63 7.2 125 100 100 80 80 200 125 125 100 80 12 17.5 125 125 100 24 Schneider Electric Switchgear Withdrawable part extraction Extraction table MT20112 Adaptable to 3 cubicle widths, this extraction table enables: b the withdrawable part to be removed from the cubicle; b the withdrawable part to be fitted into the cubicle. MT20113 Extraction and lowering tool - option Adaptable to 3 cubicle widths, this extraction tool enables: b the withdrawable part to be removed from the cubicle; b the withdrawable part to be introduced into the cubicle; b the withdrawable part to be lowered to the ground; b the withdrawable part to be lifted from the ground. MT20114 Racking handle This handle enables: b the withdrawable part to be racked in/out; b the earthing switch to be open/closed. Schneider Electric 49 Implementation examples MCset 1-2-3 layout Installation (7.2 to 17.5 kV) Line up switchboard DE55075 (2 supplies cubicles and 1 bussection at 12 kV - 31.5 kA) 500 570 570 2 feeders cubicle AD1 900 incomer cubicle AD3 900 900 bussection cubicles CL3/GL3 900 incomer cubicle AD3 570 570 3 feeders cubicle AD1 570 500 DE55074 Civil engineering with utility space (MCset 7.2 to 17.5 kV) Room entrance 1550 200 B 420 810 1520 (3) - 1720 2500 (1) (1)(5) 2800 (4) (1) A 1100 (2) (1) Minimum dimensions to be complied with when installing the MCset switchboard. (2) Minimum dimensions to be defined according to the cable bending radius. (3) Operating distance. (4) Distance needed to extract a functional unit from the switchboard without moving the other units. (5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres (see page 12). A anchor point B adjustment point Nota : for further information, refer to the civil engineering, user and instruction manual. 50 Schneider Electric Implementation examples MCset 4 layout Installation (24 kV) Line up switchboard DE55115 (2 supplies cubicles and 1 bussection at 24 kV) 500 900 900 3 feeders cubicle AD4 900 900 900 incomer cubicle AD4 900 900 900 900 incomer cubicle AD4 bussection cubicles CL4/GL4 900 900 500 4 feeders cubicle AD4 DE55116 Civil engineering with utility space (MCset 24 kV) room entrance (1) 2500 2800 150 (3) (1)(5) (4) 1700 - 2100 1750 A B 330 (1) 550 1100 (2) (1) Minimum dimensions to be complied with when installing the MCset switchboard. (2) Minimum dimensions to be defined according to the cable bending radius. (3) Operating distance. (4) Distance needed to extract a functional unit from the switchboard without moving the other units. (5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres (see page 12). A anchor point B adjustment point Nota : for further information, refer to the civil engineering, user and instruction manual. Schneider Electric 51 Installation Connections E72901R Switchgear resistance to ageing in a substation depends on 3 key factors b the need for correctly made connections New cold connecting technologies offer easy installation and favour durability in time. Their design means they can be used in polluted environments with harsh atmospheres. b the impact of relative humidity The installing of a heating element is essential in climates with high relative humidities and significant temperature differentials. b ventilation control The dimensions of air vents must be appropriate for the dissipated energy in the substation. They must only sweep across the transformer environment. Cold connected terminals Schneider Electric’s experience has led it to favour this technology wherever possible for optimum durability. The maximum acceptable cable cross-section for standard assemblies are: b 630 mm2 for incomer or feeder cubicles with single-pole cables; b 400 mm2 for incomer or feeder cubicles with three-pole cables; b 95 mm2 for transformer protection cubicles with fuses. Access to the compartment is only possible when the earthing switch is closed. Tightening torques for cables will be attained using a dynamo wrench set to 50 mN. Dry, single pole cable Short end piece, cold connectable Performance Cross section mm2 Supplier Number of cables Comments 3 to 24 kV - 400 A - 3150 A 50 to 630 mm2 all suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem... 1 to 8 per phase for greater cross section and number of cables, please consult us Dry, three-pole cable Short end piece, cold connectable Performance Cross section mm2 Supplier Number of cables Comments 3 to 24 kV - 400 A - 3150 A 50 to 400 mm2 all suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem... 1 to 4 per phase for greater cross-section, number of cables, please consult us Connection possibilities using dry cables Number of cables 1 single per phase 2 single per phase 3 single per phase 4 single per phase 6 single per phase 8 single per phase 1 three per cubicle 2 three per cubicle 3 three per cubicle 4 three per cubicle AD1 AD1 AD2 cont. b (1) b (1) b b b b b (1) b (1) b b b b AD3 AD3 AD4 RD4(2) DI2 DI4 b (1) b (1) b b b b b b b b b b b b b b b 2500 A 3150 A b (1) b (1) b b b b b b b b b b b b b b (1) Possibility of installing LV core balance type transformers. (2) Specific cubicle: direct incomer. 52 Schneider Electric Installation Connections (cont.) Bottom cable connection E72895 Cable connection height Type of cubicle Configuration AD1 - AD2 630 A 1250 A AD3 2500 A AD4 - RD4 3150 A 630 A 630 to 2500 A DI2 DI4 Fig.1 H (mm) LV core balance CT 1 set of 3 CT’s 2 sets of 3 CT’s LV core balance CT 1 set of 3 CT’s 2 sets of 3 CT’s 1 set of 3 CT’s 2 sets of 3 CT’s 1 set of 3 CT’s LV core balance CT 1 set of 3 CT’s 2 sets of 3 CT’s 650 (1) 500 465 650 (1) 480 465 435 435 410 530 420 410 450 650 (1) When installing with a LV core balance CT, use a LV core balance CT of type ARC3 when connecting with 2 cables (see page 29). E72896 b the cubicles and cables requiring the maximum depth should be taken into consideration when determining the depth P of a switchboard cable duct (Fig. 1). b when using cables of length greater than 460 mm for MCset 1-2-3 or 430 mm for MCset 4, install an additional compartment as marked (A) under the cubicle (Fig. 2). Top cable connection (optional) Two depths are available, function the number of cables and the internal arc withstand of the cubicle: 2000 and 2275 mm. Fig. 2 DE55511 Top busbar connection (optional, Fig. 3) The cubicle depth is equal to 2000 mm, it can be equipped with 1 or 2 CT’s. Fig. 3 Schneider Electric 53 Appendices 0 Cubicle equipment Equipment Switchgear circuit breaker (8) contactor pressure switch fuse switch disconnector truck earthing truck fixed busbars racking position indication contact for the withdrawable part 3 NO + 3 NC 6 NO + 6 NC padlocking of isolating shutters for withdrawable parts locking of withdrawable part/cable compartment disabling of circuit breaker operating mechanism voltage present indicator locking of mechanical racking of the withdrawable part locking of with keylock or electromagnetic the racking of the withdrawable part Earthing switch (SMALT) earthing switch earthing switch position indication contacts earthing switch position key locking (1) electromagnetic earthing switch position locking 3 NO + 3 NC Transformers voltage transformers (1 per phase) without fuse with plug-in fuses fuse melting indication contact current transformers single set double set LV core balance CT (4) phase-phase phase-earth phase-phase phase-earth 1 NO 3 TC 6 TC Connections connection with cable terminal height > 460 mm (MCset 1-2-3) or 430 mm (MCset 4) connection from top bar connection by cable from the bottom connection by cable from the top Cubicle protection index Key: b Basic equipment v Option (1) Basic equipment with earthing switch option. (2) According to the room in which the MCset switchboard is installed, you can choose option 3 or 4 sides, and possibly an exhaust tunnel for hot gases (see page 12). (3) Impossible for AD3 3150 A. (4) Connection 1 or 2 cables per phase. (5) Possibility of 1 phase-phase VT. (6) Only for 630 A cubicle. (7) 1 NO + 1 NC available. (8) Vacuum breaking circuit breakers: please consult us. (9) Compartment protection. 54 enclosure compartments (9) anti-arcing protection (2) IP3X IP4X IPX1 IP2XC 25 kA - 1 s 31.5 kA - 0.15 s 40 kA - 1 s lightning arrester Busbars 1250 A/2500 A/3150 A exposed insulated LV compartment key locking LV compartment lighting (220 V DC) anti-condensation heating element (220 V DC) Schneider Electric Type of cubicle AD1 AD1 cont. b AD2 AD3 AD4 RD4 CL1 CL2 CL3 CL4 b b b b b b b b b b b b v b b b v v v v v v v v v v v v v v v v v v v b v v v v b b v b b v v v v b b v b v v v v b b v b v v v v b v v v v b v v v v b v b v b v b v v v v v v b b v (1) (1) v v v v v (1) (1) v v v v (1) (1) v v v v (1) (1) v v v v v (1) (1) v v v v v v v v v v v v v v v v v v v v v v b b v v b b v v b b v v b b v v b b v v b b b b v b v b b v b v b b v b v b v v b v b v v b v v b v v b v v v v v v v v v v b v v v v b v v v v b v v v v b v v v v v b v v b v Schneider Electric v v v v v v v b v b v b b (3) v (5) v v v v v v v v (6) v v b GL2 b GL3 GL4 (1) (1) TT1 (5) v v v v (1) (1) v v v v v v v v v v (1) (1) v v v v v v v v v v TT4 DI2 DI4 b b (1) b b (1) b v (7) v b v (7) v v v b b b b b b v b v b v v b v v b v v v v v b v v b b v v b v v v v TT2 b (1) v v b v v b GL1 (1) b (1) b b v v v v (1) (1) v v v v v v v v v v v v v v v v v v v v (5) v v v v v (1) (1) v v v v v v v v v (1) (1) v v v v (1) v (5) v v v (6) b b v b v b v v v b b v b v b v v b v v v b v v v b v v v b v v b v v v b v v b b b v b v b b v b v b v v b v v v v v v b v v v v b v v v v b v v v v b v v b v v b b v b v b b v b v b v v b v v v v v v v v v b v v b b v v v v b v v v v v b v v b 55 Current transformers (Selection guide) Appendices Preferred current transformers: 7.2 to 24 kV secondary 1 A or 5 A Type of cubicle Accuracy class ratio Isc kA 1 s ratio number AD1 AD1 fuse contactor AD2 AD2 AD3 CL3 CL1 CL2 AD4 CL4 31.5 NA (1) 1 10/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 40 50 50 31.5 50 31.5 31.5 v v 40-80/1 or 5 2.5-5 VA - 5P20 v 50-100/1-5 2.5-5 VA - 5P20 v 20/1-1 2.5 VA - 5P20 15 VA - cl 0.5 v v v 75-150/1 or 5 2.5-5 VA - 5P20 v 30/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v accuracy class and 100-200/1-1 or 5-5 ratio 2.5-5 VA - 5P20 v 40/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v 150-300/1-1 or 5-5 2.5-5 VA - 5P20 10-20 VA - cl 0.5 v 50/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v 200-400/1-1 or 5-5 5-10 VA - 5P20 7.5-15 VA - cl 0.5 v 75/1-1 or 5/5 2.5 VA - 5P20 15 VA - cl 0.5 v v v 250-500/1-1 or 5-5 5-10 VA - 5P20 10-20 VA - cl 0.5 v 100/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v 600/1-1 or 5-5 7.5 VA - 5P20 20 VA - cl 0.5 v 150/1-1 or 5-5 7.5 VA - 5P10 15 VA - cl 0.5 v v v v v v 750/1-1 or 5-5 7.5 VA - 5P20 20 VA - cl 0.5 v 200/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v v v v 1000/1-1 or 5-5 10 VA - 5P20 30 VA - cl 0.5 v 250/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v v v v v 1250/1-1 or 5-5 10 VA - 5P20 30 VA - cl 0.5 v 300/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 v v v v v v v v v v 2000/1-1 or 5-5 15 VA - 5P20 30 VA - cl 0.5 v v v 2500/1-1 or 5-5 15 VA - 5P20 30 VA - cl 0.5 v v v 3150/1-1 or 5-5 15 VA - 5P20 30 VA - cl 0.5 v 1500/1-1 or 5-5 15 VA - 5P20 30 VA - cl 0.5 400/1-1 or 5-5 2.5 VA - 5P20 15 VA - cl 0.5 (1) Short-circuit current withstand is co-ordinated with the current limited through the fuses. Other characteristics are available, including the possibility of having 3 secondary windings. Please consult us detailing the type of protection or measuring required as well as the impedance of the outside loads and the cabling. 56 Schneider Electric MCset, a product for all your electrical distribution applications A few references Industry A53-MAPP b b b b b b b b oil, Girassol Mpg-Elf, Angola oil, Repsol, Santander, Spain oil, Sincor (Total), Venezuela pharmaceutical, Merck, Singapore automotive, Volvo, Belgium automotive, Ford, Germany cement production, Lafarge, France agri-food, Mastellone, Argentina Infrastructure b b b b port of KSA Jeddah, Saudi Arabia Santafe de Bogota airport, Colombia Slim River Hospital, Malaysia water treatment, Degremont, Argentina Energy b b b b b Sarlux power station, Italy EVN thermal power station, Vietnam Costa Nera SA power station, Argentina electrical distribution, DES (department of electrical services), Brunei renovation of the Chernobyl nuclear power station, Ukraine Marine E74225 E74226 PE55541 E74223 b Finaval/Marnavi-I chemical tankers, Italy b P&O North Sea Ferries, United Kingdom b Vietxopetro-VT offshore platform, Vietnam Schneider Electric 57 Personal notes 58 0 Schneider Electric Personal notes Schneider Electric 0 59 Personal notes 60 0 Schneider Electric RCS Nanterre B 954 503 439 ART.75202 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Industries SAS Production: Graphème Printing: Imprimerie du Pont de Claix 11-2004 AC0467EN © 2004 Schneider Electric - All rights reserved Schneider Electric Industries SAS 89 boulevard F. Roosevelt F-92500 Rueil Malmaison Tel.: +33 (0)1 41 29 85 00 Fax: +33 (0)1 41 29 89 01 http://www.schneiderelectric.com