US Building Wire catalog PDF, Brochures

advertisement
Introduction
Nexans is one of the largest wire
and cable manufacturers in the
world, and in North America. In
North America we manufacture in
locations across the United States and
Canada. We design and produce
a wide range of cables used in
power, industrial, construction and
communication applications.
With more than a century of
experience as a leader in the
industrial and power cable markets,
Nexans is contracted by heavy
industry and utilities worldwide
to provide turnkey solutions for the
bulk transmission of power - from
generating station through the
transmission and distribution systems
to commercial, residential and
industrial areas.
This catalog has been prepared
for the convenience of those using
electrical conductors in industrial,
commercial and residential
applications. The information
included in the many tabulations will
be of particular value to the architect,
engineer, electrician, and layperson
alike. For your convenience, we have
referenced applicable Articles and
Tables from both the 2008 NEC and
the 2011 NEC.
Although we have listed the types
of wires and cables suitable for
most conditions, we are equipped
to manufacture other types to suit
special needs. We would be pleased
to recommend the most suitable
construction for any special condition
that you may encounter.
The determination of the correct
cable size and type, and the
selection of methods of installation
suitable for the type and location of
particular circuits, should be made
in accordance with local regulations.
Any questions in this respect should
be directed primarily to the local
Electrical Inspection Authority.
We are pleased to note that all the
cables in this catalog are LEAD FREE.
This indicates that the component
has less than 300 ppm of lead, which
is well below the 1000 ppm level
indicated in RoHS (restriction of
hazardous substances) regulations and
below the level requiring labeling by
California Proposition #65.
Nexans wire and cable
Contact
us for all
your wire
and cable
needs
Nexans Energy USA inc.
25 Oakland Avenue
Chester, NY 10918
Tel: 1-866-663-9267
www.nexans.us
A t
t h e
c o r e
o f
p e r f o r m a n c e
1
ENERGEX® Building Wire
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1
TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2
ENERGEX® BARE COPPER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
ENERGEX® TFN/TFFN Copper . . . . . . . . . . . . . . . . . . . . . . Pages 4 & 5
ENERGEX® THHN/THWN-2/MTW Copper . . . . . . . . . . . . . Pages 6 & 7
ENERGEX® NM-B Copper . . . . . . . . . . . . . . . . . . . . . . . . . Pages 8 & 9
ENERGEX® UF-B Copper . . . . . . . . . . . . . . . . . . . . . . . . Pages 10 & 11
ENERGEX® XHHW-2 Copper . . . . . . . . . . . . . . . . . . . . . Pages 12 & 13
ENERGEX® 8000 XHHW-2 Aluminum . . . . . . . . . . . . . . . Pages 14 & 15
ENERGEX® RHH/RHW-2/USE-2 Copper . . . . . . . . . . . . . Pages 16 & 17
ENERGEX® 8000 RHH/RHW-2/USE-2 Aluminum . . . . . . . Pages 18 & 19
ENERGEX® 8000 Mobile Home Feeder Aluminum . . . . . . Pages 20 & 21
ENERGEX® PV 600 Volt Copper . . . . . . . . . . . . . . . . . . . Pages 22 & 23
ENERGEX® 8000 PV 600 Volt Aluminum . . . . . . . . . . . . . Pages 24 & 25
ENERGEX® PV 2 kV Copper . . . . . . . . . . . . . . . . . . . . . . Pages 26 & 27
ENERGEX® 8000 PV 2 kV Aluminum . . . . . . . . . . . . . . . . Pages 28 & 29
ENERGEX® MC 120 Volt Copper . . . . . . . . . . . . . . . . . . Pages 30 & 31
ENERGEX® MC 277 Volt Copper . . . . . . . . . . . . . . . . . . Pages 32 & 33
ENERGEX® 8000 SER Aluminum . . . . . . . . . . . . . . . . . . . Pages 34 & 35
ENERGEX® 8000 SEU Aluminum . . . . . . . . . . . . . . . . . . Pages 36 & 37
ENERGEX® URD Aluminum . . . . . . . . . . . . . . . . . . . . . . . Pages 38 & 39
WARRANTY & NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 40
1-866-663-9267
2
Soft Drawn
Bare Copper
Description
Application
Solid or stranded 100% conductivity
copper conductors.
ASTM B3 Soft or Annealed Copper
Wire*
ASTM B8 Concentric - Lay - Stranded
Copper Conductors
Used for bonding and grounding
electrical circuits and systems.
Conductor
Size
Number of
Strands
AWG/kcmil
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000
1
1
1
7
7
7
7
19
19
19
19
19
37
37
37
37
37
61
61
61
Nominal
Diameter
Approximate Net
Cable Weight
inches mm lbs/kftkg/km
UL
Solid - ASTM B3
Stranded - ASTM B8
Average D.C.
Resistance at 25° C
Ω/kft
Ω/km
0.0641 1.63 12.68 18.87 2.58
8.46
0.0808 2.05 20.16 30.00 1.63
5.53
0.1012.5932.0647.72 1.02 3.35
0.1423.6150.9775.86 0.640 2.10
0.1784.5281.05120.6 0.403 1.32
0.2255.72128.9191.8 0.253 1.05
0.2837.19204.9304.9 0.159 0.659
0.3228.18258.4384.6 0.127 0.522
0.3629.19325.8484.9 0.100 0.328
0.40510.29410.9 611.5 0.0795 0.261
0.45611.58518.1 771.1 0.0630 0.207
0.51213.00653.1 972.0 0.0500 0.164
0.55814.17771.9 1149 0.0423 0.139
0.61115.52926.3 1379 0.0353 0.116
0.661 16.79 1081 1609 0.0302 0.0991
0.706 17.93 1235 1838 0.0264 0.0866
0.789 20.04 1544 2298 0.0212 0.0695
0.866 22.00 1883 2758 0.0177 0.0581
0.968 24.59 2316 3447 0.0141 0.0462
1.117 28.37 3088 4596
0.0106 0.0348
Notes:
•W
here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
*ASTM B3 Specification details the requirements for solid wires and the individual wires in stranded conductors.
1-866-663-9267
3
ENERGEX®
TFN/TFFN
PVC Insulated Cable
600 Volts, 90°C - Lead Free
Copper Conductors
Applications
Construction
Specifications
Nexans ENERGEX® TFN (solid) /TFFN
(flexible stranded) copper conductors
may be used as fixture wire, machine
tool wire (MTW) or for appliance
wiring material (AWM), as outlined in
the NEC 2008 and NEC 2011. These
conductors are heat, moisture, and
gasoline and oil resistant II.
Conductor: TFN - solid annealed soft
bare copper per ASTM B3.
TFFN/MTW/AWM - flexible stranded
annealed soft bare copper per ASTM
B174
• Nexans ENERGEX® TFN/TFFN meets
or exceeds UL 66 (Fixture Wires)
and the requirements of the National
Electrical Code - Fixture wire.
• TFFN meets or exceeds UL 1063
(Machine-Tool Wires and Cables)
for Machine Tool Wire and UL 758
(Appliance Wiring Materials) for
AWM Style 1316.
• The insulation is heat, moisture,
gasoline and oil resistant II.
• TFN/TFFN shall be lead free and
RoHS compliant.
• Voltage rating - 600 Volts.
TFN and TFFN are used for internal
wiring of lighting fixtures and similar
equipment, and for connection to
branch circuit wiring inside lighting
fixtures and similar equipment.
TFN/TFFN is rated at a conductor
temperature of 90°C in dry locations.
MTW is used for internal wiring of
machines tools, rated 90°C in dry
locations and 60°C when exposed
to oils or coolants. AWM is used
as factory installed internal wiring
of appliances, rated 105°C in dry
locations.
Nexans TFN/TFFN conductors are
Lead Free and RoHS compliant.
Insulation: Color coded, heat,
moisture and flame resistant polyvinyl
chloride (PVC).
Covering: Strong, slick polyamide
(Nylon) outer covering,
Colors: Standard TFN and TFFN colors
available in black, white, red, blue,
green, yellow, pink, purple, orange,
brown and gray. Additional colors are
made per request subject to factory
minimum order quantities.
Surface Print Legend: NEXANS-F
16 AWG (1.31 mm2) (UL) TFFN
or MTW or AWM 600V VW-1
GASOLINE AND OIL RESISTANT II
LEAD FREE MADE IN CANADA (MFG.
DATE)
1-866-663-9267
4
Product Features
• Heat and moisture resistant
• Gasoline and oil resistant II
• Rated for use as appliance wiring
• Available from inventory in 11 colors
• Lead Free and RoHS compliant
ENERGEX®
TFN/TFFN
UL 66
UL 1063
UL 758, Style 1316
PVC Insulated Cable
600 Volts, 90°C - Lead Free
Copper Conductors
Conductor
Size
PVC Insulation
Nylon
Nominal
ThicknessThickness Diameter
Approximate Net
Cable Weight
Ampacity
(Amps)
AWG
mils
mm
mils
mm
inches
mm
lbs/kft
kg/km TFN/TFFN MTW1
@ 90°C
TFN
18 (1)
15
0.38
4
0.10
0.081
2.05
7.1
10.6
6
16 (1)
15
0.38
4
0.10
0.094
2.39
10.6
15.8
8
TFFN / MTW
18 (16)
15
0.38
4
0.10
0.087
2.21
7.4
11.0
6
7
16 (26)
15
0.38
4
0.10
0.100
2.54
11.0
16.4
8
10
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 336.80, and Table 402.5 “Allowable Ampacity for
Fixture Wires” at an ambient temperature of 30°C (with no load diversity).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B) (16).
• Refer to NEC 2008 and NEC 2011 Article 240.4(D) for overcurrent protection requirements.
Allowable ampacities for MTW are as shown in NFPA 79.
1
1-866-663-9267
5
ENERGEX® THHN/
THWN-2/MTW
PVC/Nylon Cable
600 Volts, 90°C - Lead Free
Copper Conductors
Applications
Nexans ENERGEX® THHN/THWN-2/
MTW* is a general purpose wiring
product for use in power, lighting
and control circuits. It can be used
in conduit, ducts and trays for service
feeders and branch circuits in industrial
and commercial installations. When
used in accordance with the 2008 or
2011 NEC, THHN/THWN-2 is suitable
for use in wet and dry locations, at
conductor temperatures not exceeding
90°C or for use in oil or coolants at
conductor temperatures not exceeding
75°C. THHN/THWN-2 is gasoline
and oil resistant II. When used as
Machine Tool Wire (MTW) it is rated
at 90°C in dry locations and 60°C in
wet locations or when exposed to oil or
coolants.
Nexans THHN/THWN-2/MTW wire is
Lead Free and RoHS compliant.
* Only stranded cables are MTW listed per
UL 1063.
Construction
Conductor:  Solid bare, annealed
copper per ASTM B3. Stranded bare
annealed copper per ASTM B3 and
ASTM B787 for sizes 14, 12, 10 and
8 AWG and ASTM B8 for sizes 6
AWG and larger.
Covering: A tough abrasion resistant
polyamide (Nylon) covering
Surface Print Legend: NEXANSC 500 kcmil (253mm2) TYPE MTW
OR THHN OR THWN-2 GRII SR FOR
CT USE VW-1 600V (UL) LEAD FREE
(MFG. DATE)
Specifications
• Nexans ENERGEX® THHN/THWN2 or MTW meets or exceeds all
applicable ASTM specifications
• UL 83: Thermoplastic Insulated Wires
and Cables
• UL 1063: Machine-Tool Wires and
Cables (stranded cables only)
• Nema WC70 / ICEA S-95-658:
Power Cables Rated 2000 Volts or
Less for the Distribution of Electrical
Energy
• Federal Specification A-A-59544 and
requirements of the NEC
• CSA C22.2 No. 75: Thermoplastic
Insulated Wires and Cables
•14 AWG through 750 kcmil are
rated VW-1
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
• Black sizes 1/0 AWG and larger are
sunlight resistant
• Voltage rating - 600 volts.
Insulation: Color coded polyvinyl
chloride (PVC), heat, moisture and
flame retardant compound per UL 83
and UL 1063
1-866-663-9267
6
Product Features
• Sizes 8 AWG to 600 kcmil available
in various colors from stock
• Cables are UL listed as Type THHN/
THWN-2/MTW*
• Meets UL VW-1 flame test
requirements
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
• Black 1/0 AWG and larger is
sunlight resistant
• High heat and moisture resistant
• THWN-2 90°C rated for dry and wet
locations
• Gasoline and Oil Resistant II
• Small diameter for improved conduit
fill
• Lead Free and RoHS compliant
Packaging
•14 & 12 AWG: 4 x 500’ spools
(2000’ per carton) or 2500’ reel
•10 AWG: 2 x 500’ spools
(1000’ per carton) or 2500’ reel
•8 AWG - 4/0 kcmil: 500’, 1000’,
2500’ or 5000’ reel
•250 kcmil - 600 kcmil: 500’,
1000’, or 2500’ reel
• 750 kcmil: 1000’ reel
ENERGEX® THHN/
THWN-2/MTW
UL 83 / CSA C22.2 No. 75
UL 1063
ICEA S-95-658
PVC/Nylon Cable
600 Volts, 90°C - Lead Free
Copper Conductors
ConductorPVC Insulation
Nylon Nominal Diameter Approximate NetAmpacity*
Size Thickness Thickness
AWG/kcmil
14 (1)
12 (1)
10 (1)
14 (19)
12 (19)
10 (19)
8 (19)
6 (19)
4 (19)
3 (19)
2 (19)
1 (19)
1/0 (19)
2/0 (19)
3/0 (19)
4/0 (19)
250 (37)
300 (37)
350 (37)
400 (37)
500 (37)
600 (61)
750 (61)
mils
15
15
20
15
15
20
30
30
40
40
40
50
50
50
50
50
60
60
60
60
60
70
70
mm mils
0.38
4
0.38
4
0.51
4
0.38
4
0.38
4
0.51
4
0.76
5
0.76
5
1.01
6
1.01
6
1.01
6
1.27
7
1.27
7
1.27
7
1.27
7
1.27
7
1.52
8
1.52
8
1.52
8
1.52
8
1.52
8
1.78
9
1.78
9
mm
0.10
0.10
0.10
0.10
0.10
0.10
0.13
0.13
0.15
0.15
0.15
0.18
0.18
0.18
0.18
0.18
0.20
0.20
0.20
0.20
0.20
0.23
0.23
inches mm
0.11
2.8
0.12
3.1
0.15
3.8
0.11
2.8
0.13
3.8
0.17
4.3
0.22
5.6
0.26
6.6
0.33
8.4
0.36
9.1
0.39
9.9
0.43 10.9
0.47
12.0
0.52 13.2
0.57
14.5
0.64 16.0
0.69
17.4
0.76 19.3
0.79
20.1
0.85 21.6
0.94
23.9
1.10
27.9
1.16
29.5
Cable Weight (Amps)
lbs/kftkg/km 60°C 75°C 90°C
15
22.3
15
15
15
23
34.2
20
20
20
37
53.6
30
30
30
16
23.8
15
15
15
24
35.7
20
20
20
39
58.0
30
30
30
63
93.7
40
50
55
98
145
55
65
75
157
234
70
85
95
193
287
85
100
110
240
357
95
115
130
300
446
110
130
150
376
560
125
150
170
467
695
145
175
195
581
864
165
200
225
724
1077
195
230
260
855
1272
215
255
290
1022
1521
240
285
320
1191
1772
260
310
350
1345
2001
280
335
380
1668
2482
320
380
430
1994
2967
355
420
475
2465
3668
400
475
535
*60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through
1 AWG. For MTW in wet locations or when exposed to oil or coolant.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size
1 AWG. THWN-2 when exposed to oil or coolant.
90°C - THHN dry locations. THWN-2 wet or dry locations. For ampacity derating purposes.
Available colors: Black, White, Red, Blue, Green, Yellow, Brown, Orange, Purple, Gray, Pink.
Notes:
•W
here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
•A
mpacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature.
• F or correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
•N
EC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG,
20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient
temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011
Article 240.4(E) through (G).
1-866-663-9267
7
ENERGEX® NM-B
PVC/Nylon Insulated Cable
600 Volts, 90°C Dry - Lead Free
Copper Conductors
Applications
Construction
Specifications
Nexans ENERGEX® non-metallic
sheathed cable NM-B is used in
normally dry installations in residential
wiring, as branch circuits for outlets,
lighting and other residential loads. Its
applications are outlined in NEC 2008
and NEC 2011 Article 334. NM-B
is rated at 600 volts and although it
is rated at a conductor temperature
of 90°C dry, its ampacity is limited
to 60°C according to the NEC 2008
and NEC 2011. It may be fished
through masonry or tile walls, where
not exposed or subject to excessive
moisture or dampness.
Conductor:  Solid 14 to 10 AWG
annealed soft bare copper per ASTM
B3. Stranded 8 AWG and larger
annealed soft bare copper per ASTM
B3 and B8.
• Nexans ENERGEX® NM-B meets
or exceeds all applicable ASTM
specifications.
• UL 83: Thermoplastic Insulated Wires
and Cables
• UL 719: Non-Metallic Cables
• Federal Specification A-A-59544 and
requirements of the NEC.
• Voltage rating - 600 volts.
Nexans NM-B cables are Lead Free
and RoHS compliant.
Sheath:
30 mil color coded PVC sheath rated
90°C is applied over the completed
assembly:
• White 14 AWG
• Yellow 12 AWG
• Orange 10 AWG
• Black 8 to 2 AWG
Insulation: Color coded polyvinyl
chloride (PVC) compound with a nylon
covering meeting the required thickness
of Type THHN. Conductor insulation is
rated 90°C.
Ground: Soft, bare copper solid per
ASTM B3 and stranded per ASTM B3
and B8
Surface Print Legend: NEXANS-C
ENERGEX 2C-14 AWG TYPE NM-B
600V W/GRD (UL) LEAD FREE MM/
DD/YY MADE IN U.S.A.
1-866-663-9267
8
Product Features
• Slick proprietary sheathing material
designed for ease of installation
• Color coded sheaths designed for
quick cable identification
• Lead free and RoHS compliant
• 14 AWG 2C and 12 AWG 2C
available with two neutral conductors
Packaging
•14, 12 & 10 AWG; 2, 3 and 4
conductor - 250 ft coil and 1000 ft reel
•8 AWG and larger 2 and 3
conductor - 125 ft coil, 500 and
1000 ft reel
ENERGEX® NM-B
UL 83
UL 719
PVC/Nylon Insulated Cable
600 Volts, 90°C Dry - Lead Free
Copper Conductors
Conductor
# of
Size
Conductors
AWG
Two Conductor
14 (1)
2
12 (1)
2
10 (1)
2
8 (7)
2
6 (7)
2
Three Conductor
14 (1)
3
12 (1)
3
10 (1)
3
8 (7)
3
6 (7)
3
4 (7)
3
2 (7)
3
Four Conductor
14 (1)
2/21
14 (1)
42
12 (1)
2/21
12 (1)
42
PVC Insulation Ground
Nylon
Thickness Wire Size Thickness
mils mm AWG mils mm
Nominal Cable Dimensions
inches
mm
15
15
20
30
30
0.38
0.38
0.51
0.76
0.76
14
12
10
10
10
(1)
(1)
(1)
(1)
(1)
4
4
4
5
5
0.10
0.10
0.10
0.13
0.13
15
15
20
30
30
40
40
0.38
0.38
0.51
0.76
0.76
1.02
1.02
14 (1)
12 (1)
10 (1)
10 (1)
10 (1)
8 (7)
6 (7)
4
4
4
5
5
6
6
0.10
0.10
0.10
0.13
0.13
0.15
0.15
0.31
0.34
0.43
0.56
0.63
0.85
0.98
15
15
15
15
0.38
0.38
0.38
0.38
14
14
12
12
4
4
4
4
0.10
0.10
0.10
0.10
0.35
0.35
0.38
0.38
(1)
(1)
(1)
(1)
0.16
0.17
0.21
0.27
0.32
x
x
x
x
x
0.36 4.0 x 9.1
0.40 4.3 x 10.2
0.49 5.3 x 12.4
0.59 6.9 x 15.0
0.68 8.1 x 17.3
Approximate Net Ampacity
Cable Weight
(Amps)
lbs/kftkg/km
57
82
124
186
255
85
122
185
277
379
15
20
30
40
55
7.9
8.6
10.9
14.2
16.0
21.6
24.9
74
107
163
254
357
593
856
110
159
243
378
531
882
1274
15
20
30
40
55
70
95
8.9
8.9
9.7
9.7
91
91
132
132
135
135
196
196
15
15
20
20
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient
temperature and 60°C rated conductors.
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20
amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature
and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article
240.4 (E) through (G)
1
Insulation color code for 2 / 2 conductor cable is Black, White, Red, and White with Red stripe. Cable ampacity is based on
the White and White with Red stripe conductors being connected as the neutrals for the system.
2
Insulation color code for 4 conductor cable is Black, White, Red and Blue. Cable ampacity is based on the 4th conductor
being connected as the neutral conductor of a balanced 3 phase system.
1-866-663-9267
9
ENERGEX® UF-B
PVC/Nylon Insulated Cable
600 Volts, 90°C Dry - Lead Free
Copper Conductors
Applications
Construction
Product Features
Nexans ENERGEX® UF-B is an
underground feeder and branch circuit
wiring cable. Its applications are
outlined in Article 340 NEC 2008 and
NEC 2011. UF-B is rated at 600 volts.
Although it is rated at a conductor
temperature of 90° C dry / wet its
ampacity is limited to 60°C according
to the NEC 2008 and NEC 2011.
UF-B may be directly buried or installed
where exposed to sunlight. When
used as an NM cable it must comply
with the requirements in NEC 2008
or NEC 2011 Article 334. It can be
used as an underground feeder from
an existing building to outdoor lighting
fixtures, pumps, outbuildings and other
equipment.
Conductor: Solid annealed soft bare
copper per ASTM B3.
Stranded annealed soft bare copper
per ASTM B3 and ASTM B8.
• Slick proprietary jacketing compound
designed for quick and easy
installation
• Gray jacket designed for quick cable
identification
• Lead free and RoHS compliant
• Meets or exceeds all applicable
industry standards
Nexans UF-B cables are Lead Free and
RoHS compliant.
Insulation: Polyvinyl chloride (PVC)
with a nylon covering. Color coded
phase identification.
Ground: Soft bare copper, solid per
ASTM B3 and stranded per ASTM B3
and ASTM B8.
Jacket: Sunlight, moisture and fungus
resistant gray PVC.
Surface Print Legend: NEXANS-C
ENERGEX 2C-14 AWG W/GRND
TYPE UF-B SUN RES 600V (UL) LEAD
FREE MM/DD/YY MADE IN U.S.A.
Specifications
• Nexans ENERGEX® UF-B meets
or exceeds all applicable ASTM
specifications.
• UL 83: Thermoplastic Insulated Wires
and Cables
• UL 493: Thermoplastic-Insulated
Underground Feeder and Branch
Circuit Cables
• Federal Specification A-A-59544 and
requirements of the NEC.
• Voltage rating - 600 volts.
1-866-663-9267
10
Packaging
•14, 12 & 10 AWG; 2, 3 and 4
conductor: 250 ft coil and 1000 ft
reel
•8 & 6 AWG; 2 and 3 conductor:
125 ft coil and 500 ft reel
•Bar coded reels and coils for ease of
material handling
ENERGEX® UF-B
UL 83
UL 493
PVC/Nylon Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Copper Conductors
Conductor PVC Insulation
Nylon PVC Jacket Ground Size
Thickness
Thickness
Thickness
Wire Size
AWG mils mm
mils
mm mils
mm
AWG
Two Conductor With Ground
14 (1)
15 0.38
4
0.10 30 0.76 14 (1)
12 (1)
15 0.38
4
0.10 30 0.76 12 (1)
10 (1)
20 0.51
4
0.10 30 0.76 10 (1)
8 (7)
30 0.76
5
0.13 45 1.14 10 (1)
6 (7)
30 0.76
5
0.13 45 1.14 10 (1)
Three Conductor With Ground
14 (1)
15 0.38
4
0.10 30 0.76 14 (1)
12 (1)
15 0.38
4
0.10 30 0.76 12 (1)
10 (1)
20 0.51
4
0.10 30 0.76 10 (1)
8 (7)
30 0.76
5
0.13 45 1.14 10 (1)
6 (7)
30 0.76
5
0.13 45 1.14 10 (1)
Nominal Cable Dimensions
inches
mm
Approximate Net Ampacity
Cable Weight
(Amps)
lbs/kft kg/km
0.18
0.19
0.22
0.31
0.34
x
x
x
x
x
0.36
0.39
0.45
0.68
0.78
4.6 x 9.2
4.8 x 9.9
5.6 x 11.4
7.9 x 17.3
8.6 x 19.8
55
75
140
213
305
82
112
208
317
454
15
20
30
40
55
0.18
0.19
0.22
0.32
0.38
x
x
x
x
x
0.58
0.62
0.67
0.99
1.20
4.6
4.8
5.6
8.1
9.7
93
134
194
330
449
138
200
289
491
668
15
20
30
40
55
x
x
x
x
x
14.7
15.7
17.0
25.1
30.5
Notes:
•W
here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
•A
mpacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient
temperature and 60°C rated conductors.
• F or correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
•N
EC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20
amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature
and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article
240.4(E) through (G).
1-866-663-9267
11
ENERGEX® XHHW-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Copper Conductors
Applications
Specifications
Product Features
Nexans ENERGEX® XHHW-2 is a
copper conductor, with crosslinked
polyethylene insulation. The cable is
rated at 600 volts and 90°C for use in
wet and dry locations. XHHW-2 can be
used in conduit and other raceways for
services, feeders and other applications
recognized by the NEC 2008 and
NEC 2011.
• Nexans ENERGEX® Type XHHW2 meets or exceeds all applicable
ASTM specifications.
• UL 44: Thermoset-Insulated Wires
and Cables
• Federal Specification A-A-59544 and
the requirements of the NEC.
• NEMA WC70 / ICEA S-95-658:
Power Cables Rated 2000 Volts or
Less for the Distribution of Electrical
Energy
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use.
• Sunlight resistant in black 8 AWG
and larger.
• 14 to 10 AWG are available in
10 distinct colors for identification
purposes.
• Sizes 14 to 4/0 AWG rated SIS.
• Nexans XHHW-2 is lead free.
• Voltage rating - 600 Volts.
• Sizes 14, 12 and 10 AWG are
available in 10 colors: Black, White,
Red, Blue, Green, Yellow, Brown,
Orange, Gray, Purple.
• Size 8 AWG and larger in black
only.
• Meets IEEE 1202
• Conforms to ICEA S-95-658
• Sunlight Resistant 8 AWG and larger
in black
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
• Sizes 14 to 4/0 AWG rated SIS
• Meets or exceeds all applicable
industry standards
• Lead Free
Sizes 14 to 4/0 AWG are approved
as Type SIS.
Sizes 1/0 AWG and larger (4 AWG
and larger in green) in all colors are
cable tray (CT) rated.
Nexans XHHW-2 conductors are
Lead Free.
Construction
Conductor: Annealed soft bare
copper per ASTM B3, B787 and B8
Insulation: Cross-linked polyethylene
(XLPE) insulation per UL 44
Surface Print Legend: NEXANS
EXELENE 500 kcmil (253 mm2) XHHW2 (UL) E64801 F 600V FOR CT USE
SR - MADE IN CANADA LEAD FREE
(MFG. DATE)
1-866-663-9267
12
Packaging
•14 to 10 AWG 2 x 500’ spools
(1000 feet) per carton; 2500’ reel
• 8 AWG - 600 kcmil long length
• 750 kcmil 500’ reel or long length
ENERGEX® XHHW-2
UL 44
ICEA S-95-658
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Copper Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
14 (7)
30
0.76
0.13
3.4
12 (7)
30
0.76
0.15
3.8
10 (7)
30
0.76
0.17
4.5
8 (7)
45
1.14
0.24
6.0
6 (7)
45
1.14
0.27
6.9
4 (7)
45
1.14
0.32
8.2
2 (7)
45
1.14
0.38
9.6
1 (19)
55
1.40
0.43
10.9
1/0 (19)
55
1.40
0.48
12.1
2/0 (19)
55
1.40
0.52
13.2
3/0 (19)
55
1.40
0.56
14.2
4/0 (19)
55
1.40
0.61
15.6
250 (37)
65
1.65
0.68
17.1
300 (37)
65
1.65
0.75
18.9
350 (37)
65
1.65
0.80
20.2
400 (37)
65
1.65
0.84
21.4
500 (37)
65
1.65
0.93
23.5
600 (61)
80
2.03
1.04
26.3
700 (61)
80
2.03
1.10
27.9
750 (61)
80
2.03
1.14
28.8
1000 (61)
80
2.03
1.29
32.7
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C 90°C
18
27
15
15
15
26
39
20
20
20
40
60
30
30
30
64
95
40
50
55
97
144
55
65
75
149
222
70
85
95
230
342
95
115
130
288
429
110
130
150
360
536
125
150
170
456
679
145
175
195
563
838
165
200
225
703
1046
195
230
260
837
1245
215
255
290
995
1481
240
285
320
1155
1719
260
310
350
1324
1970
280
335
380
1643
2445
320
380
430
1986
2955
355
420
475
2283
3397
385
460
520
2467
3671
400
475
535
3230
4806
455
545
615
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through
1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size
1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature.
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG,
20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient
temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011
Article 240.4(E) through (G).
1-866-663-9267
13
ENERGEX® 8000
Type XHHW-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
ACM Aluminum Conductors
Applications
Specifications
Product features
Nexans ENERGEX® 8000 XHHW-2 is
an AA-8000 series aluminum (ACM)
conductor with cross-linked polyethylene
insulation. The cable is rated at 600
volts and 90°C for use in wet and
dry locations. XHHW-2 can be used
in conduit and other raceways for
services, feeders and other applications
recognized by the NEC 2008 and NEC
2011.
• Nexans ENERGEX® 8000 XHHW-2
meets or exceeds all applicable
ASTM specifications.
• UL 44: Thermoset-Insulated Wires
and Cables
• NEC 2008 Article 310.13 or NEC
2011 Article 310.104
• Federal Specification A-A-59544 and
the requirements of the NEC.
• NEMA WC7O / ICEA S-95-658:
Power Cables Rated 2000 Volts or
Less for the Distribution of Electrical
Energy
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
• Sunlight Resistant 8 AWG and larger
in black
• Sizes 12 to 4/0 AWG rated SIS
• Voltage rating - 600 Volts.
• Meets IEEE 1202
• Cables are UL listed as Type
XHHW-2
• Temperature rating of 90°C dry
and wet
• Sunlight Resistant, black 8 AWG and
larger
• Lead Free
• Bare conductors are heat treated
after stranding for maximum flexibility
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
• Sizes 12 to 4/0 AWG rated SIS
Sizes 12 to 4/0 AWG are approved
as SIS.
Conductor sizes 1/0 AWG and larger
(4 AWG and larger in green) are rated
for CT use.
Nexans XHHW-2 is lead free.
Construction
Conductor: compact stranded
AA-8000 series aluminum alloy per
ASTM B800 and B801
Insulation: black sunlight resistant,
cross-linked polyethylene (XLPE) meeting
the requirements for XHHW-2 per UL 44.
Surface Print Legend:
NEXANS-C 1/0 AWG COMPACT AA8000-AL XHHW-2 600V FOR CT USE
SR LEAD FREE (UL) (MFG. DATE)
1-866-663-9267
14
ENERGEX® 8000
Type XHHW-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
ACM Aluminum Conductors
Conductor
Size
Insulation
Thickness
Nominal
Diameter
Approximate Net
Cable Weight
UL 44
ICEA S-95-658
Ampacity*
(Amps)
AWG/kcmil mils
mm
inches
mm
lb/kft
kg/km
60°C
75°C
90°C
6 (7)451.14
0.26 6.64059 4050 55
4 (7)451.14
0.31 7.95785 5565 75
2 (7)451.14
0.36 9.1841257590100
1 (18)
55
1.40
0.42
10.7
108
161
85
100
115
1/0 (18)
55
1.40
0.45
11.4
131
196
100
120
135
2/0 (18)
55
1.40
0.49
12.4
161
239
115
135
150
3/0 (18)
55
1.40
0.54
13.7
198
294
130
155
175
4/0 (18)
55
1.40
0.59
15.0
243
361
150
180
205
250 (35)
65
1.65
0.66
16.8
292
434
170
205
230
300 (35)
65
1.65
0.71
18.0
352
524
195
230
260
350 (35)
65
1.65
0.75
19.1
394
586
210
250
280
400 (35)
65
1.65
0.80
20.3
446
663
225
270
305
500 (35)
65
1.65
0.87
22.1
548
815
260
310
350
600 (58)
80
2.03
0.98
24.9
670
997
285
340
385
700 (58)
80
2.03
1.04
26.4
787
1171
315
375
425
750 (58)
80
2.03
1.08
27.4
822
1224
320
385
435
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 12 through
1 AWG.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for aluminum conductors in a raceway or direct buried at 30°C ambient
temperature.
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 12 AWG
and 25 amperes for 10 AWG aluminum conductors after any correction factors for ambient temperature and number of
conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E)
through (G).
1-866-663-9267
15
ENERGEX®
RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Copper Conductors
Applications
Construction
Specifications
Nexans ENERGEX® RHH/RHW-2/
USE-2 conductors may be installed
in raceways and conduits or directly
buried. They are 90°C, 600 volts per
NEC 2008 and NEC 2011 Articles
310 and 338.
Conductor: Stranded annealed soft
bare copper conductors per ASTM B8
and B787
• Meets UL 44: (RHH, RHW-2)
Thermoset Insulated Wires and
Cables
• Meets UL 854: (USE-2) Service
Entrance Cables
• Federal Specification A-A-59544
• ICEA S-95-658: Power Cables Rated
2000 Volts or Less for the Distribution
of Electrical Energy
• National Electrical Code - NFPA 70
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
Type USE-2 conductors are suitable
as service entrance conductors which
can be installed directly buried in
accordance with the NEC.
When used as type RHH, the cables
are suitable for installation in dry
locations.
Insulation: Heat, sunlight, moisture
and abrasion resistant cross-linked
polyethylene (XLPE) insulation per UL
854 and UL 44. Black only.
Surface Print Legend: NEXANS
1/0 AWG (53.5 mm2) (UL) E64801 F
RHW-2 OR USE-2 600V FOR CT USE
SR MADE IN CANADA LEAD FREE
(MFG DATE).
As type RHW-2 and USE-2, they are
suitable for installation in both wet and
dry locations.
Product Features
• Cables are UL listed as Type USE-2
• Temperature rating of 90°C dry
and wet
• Suitable for direct burial
• Sunlight resistant
• Lead Free
Nexans RHH/RHW-2/USE-2
conductors are Lead Free.
1-866-663-9267
16
ENERGEX®
RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Copper Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
14 (1)
45
1.14
0.16
4.0
12 (1)
45
1.14
0.17
4.4
10 (1)
45
1.14
0.19
4.9
14 (7)
45
1.14
0.16
4.1
12 (7)
45
1.14
0.18
4.7
10 (7)
45
1.14
0.21
5.2
8 (7)
60
1.52
0.27
6.8
6 (7)
60
1.52
0.31
7.8
4 (7)
60
1.52
0.35
8.9
2 (7)
60
1.52
0.41
10.4
1 (19)
80
2.03
0.49
12.4
1/0 (19)
80
2.03
0.53
13.4
2/0 (19)
80
2.03
0.57
14.5
3/0 (19)
80
2.03
0.61
15.4
4/0 (19)
80
2.03
0.68
17.2
250 (37)
95
2.41
0.74
18.7
300 (37)
95
2.41
0.81
20.5
350 (37)
95
2.41
0.86
21.8
400 (37)
95
2.41
0.90
22.9
500 (37)
95
2.41
0.99
25.1
600 (61)
110
2.79
1.09
26.4
700 (61)
110
2.79
1.16
29.5
750 (61)
110
2.79
1.20
30.4
1000 (61)
110
2.79
1.35
34.2
UL 44
UL 854
ICEA S-95-658
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C
21
31
15
15
30
44
20
20
44
65
30
30
21
31
15
15
30
44
20
20
44
65
30
30
70
105
40
50
104
156
55
65
157
234
70
85
240
357
95
115
309
460
110
130
379
564
125
150
474
706
145
175
583
869
165
200
755
1124
195
230
867
1291
215
255
1029
1531
240
285
1192
1773
260
310
1352
2012
280
335
1686
2509
320
380
2012
2995
355
420
2332
3470
385
460
2492
3710
400
475
3288
4895
455
545
90°C
15
20
30
15
20
30
55
75
95
130
150
170
195
225
260
290
320
350
380
430
475
520
535
615
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through
1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - RHH dry locations. RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature.
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG,
20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient
temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011
Article 240.4(E) through (G).
1-866-663-9267
17
ENERGEX® 8000
RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
ACM Aluminum Conductors
Applications
Construction
Specifications
Nexans ENERGEX® RHH/RHW-2/
USE-2 conductors may be installed
in raceways and conduits or directly
buried. They are 90°C, 600 volts per
NEC 2008 and NEC 2011 Articles
310 and 338.
Conductor: compact stranded
AA-8000 series aluminum alloy per
ASTM B800 and B801
• Meets UL 44: (RHH, RHW-2)
Thermoset Insulated Wires and
Cables
• Meets UL 854: (USE-2) Service
Entrance Cables
• Federal Specification A-A-59544
• ICEA S-95-658: Power Cables Rated
2000 Volts or Less for the Distribution
of Electrical Energy
• National Electrical Code - NFPA 70
• Conductor sizes 1/0 AWG and
larger (4 AWG and larger in green)
are rated for CT use
Type USE-2 conductors are suitable
as service entrance conductors which
can be installed directly buried in
accordance with the NEC.
When used as type RHH, the cables
are suitable for installation in dry
locations.
Insulation: Heat, sunlight, moisture
and abrasion resistant cross-linked
polyethylene (XLPE) insulation per UL
854 and UL 44. Black only.
Surface Print Legend: NEXANS-C
1/0 AWG COMPACT AA-8000-AL
USE-2 OR RHH OR RHW-2 600V
FOR CT USE SUN RES (UL) LEAD FREE
(MFG. DATE)
As type RHW-2 and USE-2, they are
suitable for installation in both wet and
dry locations.
Product Features
• Cables are UL listed as Type USE-2
• Temperature rating of 90°C dry
and wet
• Suitable for direct burial
• Sunlight resistant
• Lead Free
• Bare conductors are heat treated
after stranding for maximum flexibility
Nexans RHH/RHW-2/USE-2
conductors are Lead Free.
1-866-663-9267
18
ENERGEX® 8000
RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
ACM Aluminum Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
6 (7)
60
1.52
0.29
7.4
4 (7)
60
1.52
0.33
8.4
2 (7)
60
1.52
0.39
9.9
1 (18)
80
2.03
0.46
11.7
1/0 (18)
80
2.03
0.50
12.7
2/0 (18)
80
2.03
0.54
13.7
3/0 (18)
80
2.03
0.59
15.0
4/0 (18)
80
2.03
0.64
16.3
250 (35)
95
2.41
0.71
18.0
300 (35)
95
2.41
0.76
19.3
350 (35)
95
2.41
0.81
20.6
400 (35)
95
2.41
0.85
21.6
500 (35)
95
2.41
0.93
23.6
600 (58)
110
2.79
1.07
27.2
700 (58)
110
2.79
1.11
28.2
750 (58)
110
2.79
1.13
28.7
1000(58)
110
2.79
1.28
32.5
UL 44
UL 854
ICEA S-95-658
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C
47
70
40
50
66
98
55
65
96
143
75
90
127
189
85
100
152
226
100
120
182
271
115
135
222
330
130
155
271
403
150
180
328
488
170
205
385
573
195
230
435
647
210
250
494
735
225
270
600
893
260
310
721
1073
285
340
828
1232
315
375
899
1338
320
385
1141
1698
375
445
90°C
55
75
100
115
135
150
175
205
230
260
280
305
350
385
425
435
500
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 12 through
1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - RHH dry locations. RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature.
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 12 AWG
and 25 amperes for 10 AWG aluminum conductors after any correction factors for ambient temperature and number of
conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through
(G).
1-866-663-9267
19
ENERGEX® 8000
Mobile Home Feeder
XLPE Insulated Cable
600 Volts, 90°C Dry and Wet - Lead Free
ACM Aluminum Conductors
Applications
Construction
Specifications
Nexans ENERGEX® Mobile Home
Feeder is a twisted assembly of RHH
/ RHW-2 / USE-2 insulated aluminum
conductor material (ACM), AA-8000
series alloy conductors. The cable
is used as a service cable to feed
mobile homes in parks and permanent
locations. ENERGEX® 8000 Mobile
Home Feeders are designed to be
directly buried. The cable is rated at
600 volts and 90°C for use in wet and
dry locations in accordance with NEC
2008 and NEC 2011 Article 550.33.
Conductor: compact stranded
AA-8000 series aluminum alloy per
ASTM B800 and B801
• Meets UL 854: Service Entrance
Cables
• Meets UL 44: Thermoset-Insulated
Wires and Cables
Nexans Mobile Home Feeder cables
are Lead Free.
Insulation: solid color-coded sunlight
resistant cross-linked polyethylene
(XLPE)
Assembly: black and red conductors
are cabled with the white neutral
conductor and green equipment
grounding conductor.
Surface Print Legend:
NEXANS-C 4/0 AWG COMPACT AA8000-AL USE-2 OR RHH OR RHW-2
600V SUN RES LEAD FREE (UL) (MFG.
DATE)
1-866-663-9267
20
Product features
• Cables are UL listed as Service
Entrance Cable
• Solid color insulation
• Temperature rating of 90°C dry and
wet
• Sunlight Resistant
• Lead Free
• Bare conductors are heat treated
after stranding for maximum flexibility
ENERGEX® 8000
Mobile Home Feeder
UL 854
UL 44
XLPE Insulated Cable
600 Volts, 90°C Dry and Wet - Lead Free
ACM Aluminum Conductors
Cable Construction
Insulation Thickness
Phase Conductors
Insulation Thickness
Neutral Conductor
Insulation Thickness
Cable
Grounding Conductor Diameter
Approximate Net
Cable Weight
Ampacity*
(Ph 1 + Ph 2 + N + G)
mils
2 + 2 + 4 + 6
4/0 + 4/0 + 2/0 + 4
60
1.52
60
1.52
60
1.52
0.94
301 448
100
80 2.03 80 2.03 60 1.521.53 794 1182200
mm
mils
mm
mils
mm
inches
lb/mft
kg/km
Amps
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
*A
mpacities are in accordance with NEC 2008 Table 310.15(B)(6) or NEC 2011 Table 310.15(B)(7) and are based on
90°C conductor temperatures, 20°C ambient earth temperature, earth thermal resistivity Rho=90, cables buried 36” deep,
only the phase conductors carrying current and 100% load factor.
1-866-663-9267
21
ENERGEX®
PV/RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry and Wet - Lead Free
Copper Conductors
Applications
Construction
Product features
Nexans ENERGEX® PV solar cables
offer exceptional performance, easy
installation and long-term reliability for
DC connections. They link photovoltaic
panels on rooftops or solar farms, and
also connect them to the array box (if
one exists), and to the inverter which
transforms DC solar energy into usable
AC electricity. These cables have a wet
and dry temperature rating of 90°C,
are UV resistant, flame-retardant, and
are certified as UL type PV.
Conductor: Stranded annealed soft
bare copper conductors per ASTM B8
and B787
• Cables are UL listed as Type PV
• Cables are UL listed as Type USE-2
• Temperature rating of 90°C dry and
wet
• Suitable for direct burial
• Sunlight resistant in black and colors
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• LEAD FREE
Nexans ENERGEX® PV/RHH/RHW-2/
USE-2 cables may be installed indoors
or outdoors, in raceways and conduits,
or directly buried. They are 90°C,
600 V per NEC Articles 310 and 338,
and suitable for use in a photovoltaic
system per NEC Article 690.
Type PV cables are for use on the DC
side of a photovoltaic system, suitable
for installation in both wet and dry
locations, and may be exposed to
sunlight.
Type USE-2 cables are suitable as
service entrance cables, which can be
installed directly buried in accordance
with the NEC.
When used as type RHH, the cables
are suitable for installation in dry
locations.
Insulation: Heat, sunlight, moisture
and abrasion resistant cross-linked
polyethylene (XLPE) insulation in black
or colors per UL 854 and UL 44
Surface Print Legend:
(mon/year) NEXANS [plant] 350 kcmil
(177.3 mm2) (UL) RHW-2 OR USE-2
OR PV WIRE 600V 90C WET OR DRY
SR DIR BUR LEAD FREE
Specifications
• Meets UL Subject 4703 (PV)
Photovoltaic Wire
• Meets UL 44: (RHH, RHW-2)
Thermoset Insulated Wires and
Cables
• Meets UL 854 (USE-2) Service
Entrance Cables
• Federal Specification A-A-59544
• National Electrical Code - NFPA 70
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• UL File Numbers: E338981 (PV),
E49786 (USE-2), E64801 (RHH,
RHW-2)
As type RHW-2 and USE-2, they are
suitable for installation in both wet and
dry locations.
Nexans PV/RHH/RHW-2/USE-2 cables
are LEAD FREE.
1-866-663-9267
22
Options
• Class C stranding available
ENERGEX®
PV/RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Copper Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
8 (7)
75
1.91
0.29
7.5
6 (7)
75
1.91
0.33
8.4
4 (7)
75
1.91
0.38
9.6
2 (7)
75
1.91
0.44
11.0
1 (19)
95
2.41
0.51
12.9
1/0 (19)
95
2.41
0.55
13.9
2/0 (19)
95
2.41
0.59
15.0
3/0 (19)
95
2.41
0.64
16.2
4/0 (19)
95
2.41
0.69
17.6
250 (37)
110
2.79
0.77
19.5
300 (37)
110
2.79
0.82
20.8
350 (37)
110
2.79
0.87
22.0
400 (37)
110
2.79
0.91
23.1
500 (37)
110
2.79
0.99
25.1
600 (61)
125
3.18
1.10
27.8
700 (61)
125
3.18
1.19
30.2
750 (61)
125
3.18
1.22
31.0
1000 (61)
125
3.18
1.37
34.8
UL 44
UL 854
UL 854 subject 4703
ICEA S-95-658
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C
76
113
40
50
110
164
55
65
164
244
70
85
248
369
95
115
316
470
110
130
390
580
125
150
481
716
145
175
596
887
165
200
740
1101
195
230
884
1316
215
255
1048
1560
240
285
1207
1796
260
310
1375
2046
280
335
1700
2530
320
380
2048
3048
355
420
2378
3539
385
460
2542
3783
400
475
3347
4981
455
545
90°C
55
75
95
130
150
170
195
225
260
290
320
350
380
430
475
520
535
615
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through
1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes.
Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.
For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC.
Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to
standard manufacturing tolerances.
1-866-663-9267
23
ENERGEX® 8000
PV/RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry and Wet - Lead Free
Aluminum Conductors
Applications
Construction
Product features
Nexans ENERGEX® PV solar cables
offer exceptional performance, easy
installation and long-term reliability for
DC connections. They link photovoltaic
panels on rooftops or solar farms, and
also connect them to the array box (if
one exists), and to the inverter which
transforms DC solar energy into usable
AC electricity. These cables have a wet
and dry temperature rating of 90°C,
are UV resistant, flame-retardant, and
are certified as UL type PV.
Conductor: Compact stranded AA8000 series aluminum alloy (ACM) per
ASTM B801 or B836
• Cables are UL listed as Type PV
• Cables are UL listed as Type USE-2
• Temperature rating of 90°C dry and
wet
• Suitable for direct burial
• Sunlight resistant in black and colors
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• LEAD FREE
Nexans ENERGEX® PV/RHH/RHW-2/
USE-2 cables may be installed indoors
or outdoors, in raceways and conduits,
or directly buried. They are 90ºC,
600 V per NEC Articles 310 and 338,
and suitable for use in a photovoltaic
system per NEC Article 690.
Type PV cables are for use on the DC
side of a photovoltaic system, suitable
for installation in both wet and dry
locations, and may be exposed to
sunlight.
Type USE-2 cables are suitable as
service entrance cables, which can be
installed directly buried in accordance
with the NEC.
When used as type RHH, the cables
are suitable for installation in dry
locations.
Insulation: Heat, sunlight, moisture
and abrasion resistant cross-linked
polyethylene (XLPE) insulation in black
or colors per UL 854 and UL 44
Surface Print Legend:
(mon/year) NEXANS [plant] 350 kcmil
(177.3 mm2) CPT ACM ALUM (UL)
RHW-2 OR USE-2 OR PV WIRE 600V
90C WET OR DRY SR DIR BUR LEAD
FREE
Specifications
• Meets UL Subject 4703 (PV)
Photovoltaic Wire
• Meets UL 44: (RHH, RHW-2)
Thermoset Insulated Wires and
Cables
• Meets UL 854 (USE-2) Service
Entrance Cables
• Federal Specification A-A-59544
• National Electrical Code - NFPA 70
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• UL File Numbers: E338981 (PV),
E49786 (USE-2), E64801 (RHH,
RHW-2)
As type RHW-2 and USE-2, they are
suitable for installation in both wet and
dry locations.
Nexans PV/RHH/RHW-2/USE-2 cables
are LEAD FREE.
1-866-663-9267
24
Options
• Class C stranding available
ENERGEX® 8000
PV/RHH/RHW-2/USE-2
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Aluminum Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
6 (7)
75
1.91
0.32
8.2
4 (7)
75
1.91
0.37
9.3
2 (6)
75
1.91
0.42
10.7
1 (8)
95
2.41
0.49
12.5
1/0 (10)
95
2.41
0.53
13.4
2/0 (12)
95
2.41
0.57
14.5
3/0 (16)
95
2.41
0.62
15.6
4/0 (18)
95
2.41
0.67
17.0
250 (35)
110
2.79
0.74
18.9
300 (35)
110
2.79
0.79
20.2
350 (35)
110
2.79
0.84
21.3
400 (35)
110
2.79
0.88
22.4
500 (35)
110
2.79
0.96
24.4
600 (58)
125
3.18
1.07
27.1
750 (58)
125
3.18
1.16
29.5
1000 (58)
125
3.18
1.31
33.4
UL 44
UL 854
UL 854 subject 4703
ICEA S-59-658
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C
52
77
40
50
72
107
55
65
102
151
75
90
135
201
85
100
161
240
100
120
193
288
115
135
231
344
130
155
282
420
150
180
344
512
170
205
401
596
190
230
456
679
210
250
512
762
225
270
621
925
260
310
755
1124
285
340
918
1367
320
385
1195
1778
375
445
90°C
60
75
100
115
135
150
175
205
230
255
280
305
350
385
435
500
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through
1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes.
Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.
For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC.
Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to
standard manufacturing tolerances.
1-866-663-9267
25
ENERGEX®
PV/RHH/RHW-2/USE-2
XLPE Insulated Cable
2 kV, 90°C Dry and Wet - Lead Free
Copper Conductors
Applications
Construction
Product features
Nexans ENERGEX® PV solar cables
offer exceptional performance, easy
installation and long-term reliability for
DC connections. They link photovoltaic
panels on rooftops or solar farms, and
also connect them to the array box (if
one exists), and to the inverter which
transforms DC solar energy into usable
AC electricity. These cables have a wet
and dry temperature rating of 90°C,
are UV resistant, flame-retardant, and
are certified as UL type PV.
Conductor: Stranded annealed soft
bare copper conductors per ASTM B8
and B787
• Cables are UL listed as Type PV
• Cables are UL listed as Type USE-2
• Temperature rating of 90°C dry and
wet
• Suitable for direct burial
• Sunlight resistant in black and colors
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• LEAD FREE
Nexans ENERGEX® PV/RHH/RHW-2/
USE-2 cables may be installed indoors
or outdoors, in raceways and conduits,
or directly buried. They are 90ºC, 2 kV
per NEC Articles 310 and 338, and
suitable for use in a photovoltaic system
per NEC Article 690.
Type PV cables are for use on the DC
side of a photovoltaic system, suitable
for installation in both wet and dry
locations, and may be exposed to
sunlight.
Type USE-2 cables are suitable as
service entrance cables, which can be
installed directly buried in accordance
with the NEC.
When used as type RHH, the cables
are suitable for installation in dry
locations.
Insulation: Heat, sunlight, moisture
and abrasion resistant cross-linked
polyethylene (XLPE) insulation in black
or colors per UL 854 and UL 44
Surface Print Legend:
(mon/year) NEXANS [plant] 350 kcmil
(177.3 mm2) (UL) USE-2 600V OR
RHW-2 OR PV WIRE 2000V 90C WET
OR DRY SR DIR BUR LEAD FREE
Specifications
• Meets UL Subject 4703 (PV)
Photovoltaic Wire
• Meets UL 44: (RHH, RHW-2)
Thermoset Insulated Wires and
Cables
• Meets UL 854 (USE-2) Service
Entrance Cables
• Federal Specification A-A-59544
• National Electrical Code - NFPA 70
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• UL File Numbers: E338981 (PV),
E49786 (USE-2), E64801 (RHH,
RHW-2)
As type RHW-2 and USE-2, they are
suitable for installation in both wet and
dry locations.
Nexans PV/RHH/RHW-2/USE-2 cables
are LEAD FREE.
1-866-663-9267
26
Options
• Class C stranding available
ENERGEX®
PV/RHH/RHW-2/USE-2
UL 44
UL 854
UL 854 subject 4703
ICEA S-95-658
XLPE Insulated Cable
2 kV, 90°C Dry or Wet - Lead Free
Copper Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
8 (7)
85
2.16
0.31
7.9
6 (7)
85
2.16
0.35
8.8
4 (7)
85
2.16
0.40
10.0
2 (7)
85
2.16
0.46
11.5
1 (19)
105
2.67
0.53
13.3
1/0 (19)
105
2.67
0.57
14.3
2/0 (19)
105
2.67
0.61
15.4
3/0 (19)
105
2.67
0.66
16.6
4/0 (19)
105
2.67
0.71
18.0
250 (37)
120
3.05
0.79
19.9
300 (37)
120
3.05
0.84
21.6
350 (37)
120
3.05
0.89
22.4
400 (37)
120
3.05
0.93
23.5
500 (37)
120
3.05
1.10
25.6
600 (61)
135
3.43
1.12
28.2
700 (61)
135
3.43
1.21
29.9
750 (61)
135
3.43
1.24
30.7
1000 (61)
135
3.43
1.39
35.2
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C
80
119
40
50
115
171
55
65
169
251
70
85
253
377
95
115
323
481
110
130
398
592
125
150
489
728
145
175
605
900
165
200
750
1116
195
230
896
1333
215
255
1059
1576
240
285
1220
1816
260
310
1388
2066
280
335
1714
2551
320
380
2064
3072
355
420
2395
3564
385
460
2560
3810
400
475
3367
5011
455
545
90°C
55
75
95
130
150
170
195
225
260
290
320
350
380
430
475
520
535
615
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through
1 AWG.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes.
Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.
For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC.
Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to
standard manufacturing tolerances.
1-866-663-9267
27
ENERGEX® 8000
PV/RHH/RHW-2/USE-2
XLPE Insulated Cable
2 kV, 90°C Dry and Wet - Lead Free
Aluminum Conductors
Applications
Construction
Product features
Nexans ENERGEX® PV solar cables
offer exceptional performance, easy
installation and long-term reliability for
DC connections. They link photovoltaic
panels on rooftops or solar farms, and
also connect them to the array box (if
one exists), and to the inverter which
transforms DC solar energy into usable
AC electricity. These cables have a wet
and dry temperature rating of 90°C,
are UV resistant, flame-retardant, and
are certified as UL type PV.
Conductor: Compact stranded AA8000 series aluminum alloy (ACM) per
ASTM B801 or B836
• Cables are UL listed as Type PV
• Cables are UL listed as Type USE-2
• Temperature rating of 90°C dry and
wet
• Suitable for direct burial
• Sunlight resistant in black and colors
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• LEAD FREE
Nexans ENERGEX® PV/RHH/RHW-2/
USE-2 cables may be installed indoors
or outdoors, in raceways and conduits,
or directly buried. They are 90ºC, 2 kV
per NEC Articles 310 and 338, and
suitable for use in a photovoltaic system
per NEC Article 690.
Type PV cables are for use on the DC
side of a photovoltaic system, suitable
for installation in both wet and dry
locations, and may be exposed to
sunlight.
Type USE-2 cables are suitable as
service entrance cables, which can be
installed directly buried in accordance
with the NEC.
When used as type RHH, the cables
are suitable for installation in dry
locations.
Insulation: Heat, sunlight, moisture
and abrasion resistant cross-linked
polyethylene (XLPE) insulation in black
or colors per UL 854 and UL 44.
Surface Print Legend:
(mon/year) NEXANS [plant] 350 kcmil
(177.3 mm2) CPT ACM ALUM (UL)
USE-2 600V OR RHW-2 OR PV WIRE
2000V 90C WET OR DRY SR DIR BUR
LEAD FREE
Specifications
• Meets UL Subject 4703 (PV)
Photovoltaic Wire
• Meets UL 44: (RHH, RHW-2)
Thermoset Insulated Wires and
Cables
• Meets UL 854 (USE-2) Service
Entrance Cables
• Federal Specification A-A-59544
• National Electrical Code - NFPA 70
• Conductors 1/0 AWG and larger (4
AWG and larger in green) are rated
for CT use
• UL File Numbers: E338981 (PV),
E49786 (USE-2), E64801 (RHH,
RHW-2)
As type RHW-2 and USE-2, they are
suitable for installation in both wet and
dry locations.
Nexans PV/RHH/RHW-2/USE-2 cables
are LEAD FREE.
1-866-663-9267
28
Options
• Class C stranding available
ENERGEX® 8000
PV/RHH/RHW-2/USE-2
UL 44
UL 854
UL 854 subject 4703
ICEA S-95-658
XLPE Insulated Cable
2 kV, 90°C Dry or Wet - Lead Free
Aluminum Conductors
Conductor
Insulation Thickness
Nominal Diameter
Size
AWG/kcmilmils
mm inches mm
6 (7)
85
2.16
0.34
8.6
4 (7)
85
2.16
0.39
9.9
2 (6)
85
2.16
0.44
11.2
1 (8)
105
2.67
0.51
13.0
1/0 (10)
105
2.67
0.55
14.0
2/0 (12)
105
2.67
0.59
15.0
3/0 (16)
105
2.67
0.64
16.3
4/0 (18)
105
2.67
0.69
17.5
250 (35)
120
3.05
0.76
19.3
300 (35)
120
3.05
0.81
20.6
350 (35)
120
3.05
0.86
21.8
400 (35)
120
3.05
0.90
22.9
500 (35)
120
3.05
0.98
24.9
600 (58)
135
3.43
1.09
27.7
750 (58)
135
3.43
1.18
30.0
1000 (58)
135
3.43
1.33
33.8
Approximate Net
Ampacity*
Cable Weight
(Amps)
lb/kft kg/km 60°C 75°C
57
84
40
50
77
115
55
65
108
160
75
90
142
212
85
100
169
251
100
120
202
300
115
135
240
357
130
155
292
434
150
180
354
528
170
205
412
613
190
230
468
697
210
250
525
781
225
270
607
904
260
310
771
1147
285
340
935
1391
320
385
1214
1806
375
445
90°C
60
75
100
115
135
150
175
205
230
255
280
305
350
385
435
500
*60°C - W
hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through
1 AWG.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes.
Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.
For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC.
Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to
standard manufacturing tolerances.
1-866-663-9267
29
ENERGEX® MC 120
Aluminum Armored MC Cable
UL Type MC, 600 Volts, 90°C dry - Lead Free
Copper Conductors
Applications
ENERGEX® MC 120 cables may be
used for branch, feeder and service for
distribution in commercial, industrial,
and multi-residential construction in
accordance with NEC 2008 and NEC
2011 Article 330. They are suitable for
installation in motion picture studios,
theaters, and places of assembly
(100 people or more) per NEC 2008
and NEC 2011 Articles 230.43,
300.22(C), 330, 396, 518, 520, 530
and 645. These cables may be installed
in approved raceways and as open
runs of cable on a messenger. They
may be installed exposed, concealed
or in cable tray and may be run in
spaces used for environmental air in
accordance with NEC 2008 and NEC
2011 Article 300.22(C) ONLY.
 
Nexans MC 120 cable is Lead Free
and RoHS compliant.
Construction
Conductor: Solid soft bare annealed
copper per ASTM B3.
Stranded soft bare annealed copper
per ASTM B3 and ASTM B787 for
sizes 14 to 8 AWG and ASTM B8 for
sizes 6 AWG and larger.
Insulation: Colored PVC/Nylon type
THHN in accordance with UL 83, flame
retardant, meeting UL VW-1 flame test
for sizes 14 to 1 AWG. Colored crosslinked polyethylene type XHHW-2 per
UL 44 for sizes 1/0 AWG and larger.
Ground Wire: bare copper, sized
in accordance with NEC 2008 and
NEC 2011 and UL, with green THHN
insulation (XHHW-2 for 1/0 and
larger).
Assembly: conductors are cabled
with grounding wires. A marker
tape/core protection tape combination
assembles the core in an essentially
round configuration.
Armor: interlocking aluminum tape
armor applied directly over the core.
Marker Tape Print: Nexans Type
MC 600 Volt For CT Use (size)
THHN (UL) E-47409 LEAD FREE (MFG
DATE).
Specifications
• Meets UL 44: Thermoset Insulated
Wires and Cables (1/0 AWG and
larger)
• Meets UL 83: Thermoplastic Insulated
Wires and Cables (14 to 1 AWG)
• Tested to UL 1479: Fire Tests of
Through-Penetration Firestops for
one, two or three hour fire rated
assemblies (for cables up to 2 AWG)
• Meets UL 1569: Metal Clad Cables
• Meets UL 1581: Reference Standard
for Electrical Wire, Cable, and
Flexible Cords
• Designated Type MC per NEC 2008
and NEC 2011 Article 330
1-866-663-9267
30
Product features
• Cables are UL listed as Type MC,
600V
•UL listed insulated conductors
• Fire Wall Penetration rated
depending on type of installation and
fire-stop system used
• UL listed for use in cable trays per
NEC 2008 and NEC 2011 Article
330.10(A)(6)
• UL listed for use in Class I, Div. 2 per
NEC 2008 and NEC 2011 Article
501.10(B)(1)(6), Class II, Div.2 per
NEC 2008 and NEC 2011 Article
502.10(B)(1)(6) and Class III, Div. 1
& 2 per NEC 2008 and NEC 2011
Articles 503.10(A) and (B) with
approved termination fittings.
• Temperature rating of 90°C dry
• Excellent mechanical & physical
properties
• Lightweight aluminum armor
• Conductor sizes larger than 1/0
AWG
• Lead Free and RoHS compliant.
Options
The following constructions can be
provided on special orders:
• Special conductor counts
• XHHW-2 insulation on sizes 14 to 1
AWG
• Conductor sizes larger than 1/0
AWG
ENERGEX® MC 120
UL 44
UL 83
UL 1569
Aluminum Armored MC Cable
UL Type MC, 600 Volts, 90°C Dry - Lead Free
Copper Conductors
Number of Conductor Ground
Circuit Conductor
Nominal Diameter
Conductors
Size
Size
Color Code
over Armor
AWG
AWG
inches
mm
2
14 (1) 14 (1)
white/black
0.45
11.3
3
14 (1) 14 (1)
white/black/red
0.47
12.0
4
14 (1) 14 (1)
white/black/red/blue
0.51
12.8
2
12 (1) 12 (1)
white/black
0.48
12.3
3
12 (1) 12 (1)
white/black/red
0.51
13.1
4
12 (1) 12 (1)
white/black/red/blue
0.55
14.0
2
10 (1) 10 (1)
white/black
0.55
14.0
3
10 (1) 10 (1)
white/black/red
0.59
14.9
4
10 (1) 10 (1)
white/black/red/blue
0.64
16.3
2
12 (19) 12 (19)
white/black
0.48
12.3
3
12 (19) 12 (19)
white/black/red
0.51
13.1
4
12 (19) 12 (19) white/black/red/blue
0.55
14.0
2
10 (19) 10 (19)
white/black
0.55
14.0
3
10 (19) 10 (19)
white/black/red
0.58
14.9
4
10 (19) 10 (19) white/black/red/blue
0.64
16.3
2
8 (19) 10 (19)
white/black
0.66
16.7
3
8 (19) 10 (19)
white/black/red
0.71
18.1
4
8 (19) 10 (19) white/black/red/blue
0.78
19.7
2
6 (19) 8 (19)
white/black
0.74
18.9
3
6 (19) 8 (19)
white/black/red
0.81
20.6
4
6 (19) 8 (19)
white/black/red/blue
0.89
22.5
3
4 (19) 8 (19)
white/black/red
0.94
23.9
4
4 (19) 8 (19)
white/black/red/blue
1.06
26.8
3
3 (19) 6 (19)
white/black/red
1.02
25.8
4
3 (19) 6 (19)
white/black/red/blue
1.13
28.7
3
2 (19) 6 (19)
white/black/red
1.09
27.7
4
2 (19) 6 (19)
white/black/red/blue
1.20
30.5
3
1 (19) 6 (19)
white/black/red
1.20
30.6
3
1/0 (19) 6 (19)
white/black/red
1.27
32.3
Approximate Net
Cable Weight
lb/kft kg/km
87
129
106
158
123
183
118
176
145
216
173
257
164
244
207
308
244
363
118
176
145
216
173
257
164
244
207
308
244
363
229
341
300
446
371
552
330
491
435
647
541
805
624
929
855
1272
795
1183
1049 1561
966
1438
1245 1853
1427 2124
1585 2359
Ampacity*
(Amps)
60°C 75°C 90°C
15
15
15
15
15
15
151151
151
20
20
20
20
20
20
201201
201
30
30
30
30
30
30
301
301
301
20
20
20
20
20
20
201
201201
30
30
30
30
30
30
301
301301
40
50
55
40
50
55
401
501
551
55
65
75
55
65
75
651 751
551 70
85
95
851 951
701 85
100
110
1001 1101
851 95
115
130
1151 1301
951 110
130
150
125
150
170
Bend Radius: 7 × overall diameter
*60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. Ampacities
for cables having more than three conductors have been derated per NEC 2008 Table 310.15(B)(2)(a) or NEC 2011 Table
310.15(B)(3)(a).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008
Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes
for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of
conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G).
1
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
31
ENERGEX® MC 277
Aluminum Armored MC Cable
277 Volts and Special Color Codes
UL Type MC, 600 Volts, 90°C Dry - Lead Free
Copper Conductors
Applications
ENERGEX® MC 277 cables may be
used for branch, feeder and service for
distribution in commercial, industrial,
and multi-residential construction in
accordance with NEC 2008 and NEC
2011 Article 330. They are suitable
for installation in motion picture studios,
theaters, and places of assembly
(100 people or more) per NEC 2008
and NEC 2011 Articles 230.43,
300.22(C), 330, 396, 518, 520, 530
and 645. These cables may be installed
in approved raceways and as open
runs of cable on a messenger. They
may be installed exposed, concealed
or in cable tray and may be run in
spaces used for environmental air in
accordance with NEC 2008 and NEC
2011 Article 300.22(C) ONLY. 
Nexans MC 277 cable is Lead Free
and RoHS compliant.
Construction
Conductor: Solid soft bare, annealed
copper per ASTM B3. Stranded soft
bare annealed copper per ASTM B3
and ASTM B787 for sizes 14 to 8
AWG and ASTM B8 for sizes 6 AWG
and larger.
Ground Wire: bare copper, sized
in accordance with NEC 2008 and
NEC 2011 and UL, with green THHN
insulation.
Assembly: conductors are cabled
with grounding wires. A marker
tape/core protection tape combination
assembles the core in an essentially
round configuration.
Armor: interlocking aluminum tape
armor applied directly over the core.
Marker Tape Print: Nexans Type
MC 600 Volt For CT Use (size)
THHN (UL) E-47409 LEAD FREE (MFG
DATE).
Specifications
• Meets UL 83: Thermoplastic Insulated
Wires and Cables
• Tested to UL 1479: Fire Tests of
Through-Penetration Firestops for
one, two or three hour fire rated
assemblies (for cables up to 2 AWG)
• Meets UL 1569: Metal Clad Cables
• Meets UL 1581: Reference Standard
for Electrical Wire, Cable, and
Flexible Cords
• Designated Type MC per NEC 2008
and NEC 2011 Article 330
Insulation: Colored PVC/Nylon type
THHN per UL 83, flame retardant,
meeting UL VW-1 flame test.
1-866-663-9267
32
Product Features
• Cables are UL listed as Type MC,
600V
• UL listed insulated conductors
• Fire Wall Penetration rated
depending on type of installation and
fire-stop system used
• UL listed for use in cable trays per
NEC 2008 and NEC 2011 Article
330.10(A)(6)
• For use in Class I, Div. 2 per NEC
2008 and NEC 2011 Article
501.10(B)(1)(6), Class II, Div. 2 per
NEC 2008 and NEC 2011 Article
502.10(B)(1)(6) and Class III, Div. 1
& 2 per NEC 2008 and NEC 2011
Articles 503.10(A) and (B) with
approved termination fittings.
• Temperature rating of 90°C dry
• Excellent mechanical & physical
properties
• Lightweight aluminum armor
• Lead Free and RoHS compliant.
Options
The following constructions can be
provided on special orders:
• Special conductor counts
• XHHW-2 insulation
ENERGEX® MC 277
UL 83
UL 1569
Aluminum Armored MC Cable
277 Volts and Special Color Codes
UL Type MC, 600 Volts, 90°C Dry - Lead Free
Copper Conductors
Number of Conductor Ground
Circuit Conductor
Nominal DiameterApproximate Net
Ampacity*
Conductors
Size
Size
Color Code
over Armor
Cable Weight
(Amps)
AWG
AWG
inches mm lb/kft kg/km60°C 75°C 90°C
2
12 (1)
12 (1)
brown/gray
0.48
12.3
118
176
20
20
20
2
12 (1)
12 (1)
orange/gray
0.48
12.3
118
176
20
20
20
2
12 (1)
12 (1)
yellow/gray
0.48
12.3
118
176
20
20
20
2
12 (1)
12 (1)
purple/gray
0.48
12.3
118
176
20
20
20
2
12 (1)
12 (1)
brown/yellow
0.48
12.3
118
176
20
20
20
2
12 (1)
12 (1)
red/white
0.48
12.3
118
176
20
20
20
2
12 (1)
12 (1)
blue/white
0.48
12.3
118
176
20
20
20
3
12 (1)
12 (1)
brown/orange/gray
0.51
13.1
145
216
20
20
20
3
12 (1)
12 (1)
brown/purple/gray
0.51
13.1
145
216
20
20
20
3
12 (1)
12 (1)
purple/yellow/gray
0.51
13.1
145
216
20
20
20
3
12 (1)
12 (1)
brown/yellow/gray
0.51
13.1
145
216
20
20
20
3
12 (1)
12 (1)
red/blue/white
0.51
13.1
145
216
20
20
20
3
12 (1)
12 (1)
black/blue/white
0.51
13.1
145
216
20
20
20
201
201
4
12 (1)
12 (1) brown/orange/yellow/gray 0.55
14.0
173
257 201
4
12 (1)
12 (1) brown/purple/yellow/gray
0.55
14.0
173
257 201
201
201
2
10 (1)
10 (1)
brown/gray
0.55
14.0
164
244
30
30
30
3
10 (1)
10 (1)
brown/orange/gray
0.59
14.9
207
308
30
30
30
301
301
4
10 (1)
10 (1) brown/orange/yellow/gray 0.64
16.3
244
363 301
2
12 (19) 12 (19)
brown/gray
0.48
12.3
118
176
20
20
20
3
12 (19) 12 (19)
brown/orange/gray
0.51
13.1
145
216
20
20
20
201
201
4
12 (19) 12 (19) brown/orange/yellow/gray 0.55
14.0
173
257 201
2
10 (19) 10 (19)
brown/gray
0.55
14.0
164
244
30
30
30
3
10 (19) 10 (19)
brown/orange/gray
0.59
14.9
207
308
30
30
30
301
301
4
10 (19) 10 (19) brown/orange/yellow/gray 0.64
16.3
244
363 301
3
8 (19)
10 (19)
brown/orange/gray
0.71
18.1
300
446
40
50
55
3
6 (19)
8 (19)
brown/orange/gray
0.81
20.6
435
647
55
65
75
Bend Radius: 7 × overall diameter
*60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC 2008 Table
310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. Ampacities for
cables having more than three conductors have been derated per NEC 2008 Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3)
(a).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008
Table 310.16 or NEC 2011 Table 310.15(B) (16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for
12 AWG, and 30 amperes for 10 AWG copper conductors after any correction
1
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
33
ENERGEX® 8000 SER
Service Entrance Type SE, Style R
XLPE Insulated Cable - Lead Free
600 Volts, 90°C Dry or Wet
ACM Aluminum Conductors
Applications
Nexans ENERGEX® SER is type SE,
Style R cable, used as an above ground
service entrance cable, a panel feeder
and in branch circuits. The cable is
rated at 600 volts and 90°C for use in
wet and dry locations in accordance
with NEC 2008 and NEC 2011 Article
338.
Nexans SER cables are lead free and
RoHS compliant.
Construction
Conductor: Compact stranded AA8000 series aluminum alloy per ASTM
B800 and B801 (8 AWG is solid).
Assembly: Insulated conductors are
cabled with the bare ground wire. A
flame retardant fiberglass reinforced
binder tape assembles the core in a
circular configuration.
Jacket: Sunlight resistant, lead free,
flame retardant, gray polyvinyl chloride
(PVC) material.
Conductor Identification:
Color coded: Black, White and Red
Surface Print Legend:
NEXANS-C ENERGEX 8000 TYPE
SE - STYLE: R 600V XHHW AA-8000AL 3/C 4/0 AWG + 1/C 2/0 AWG
(UL) E-49786 SUN RES LEAD FREE
(MFG. DATE)
Insulation: color coded cross-linked
polyethylene (XLPE).
1-866-663-9267
34
Specifications
• Meets UL 854: Service Entrance
Cables
Product features
• Cables are UL listed as Type SE,
Style R
• Temperature rating of 90°C dry
and wet
• Sunlight Resistant
• Moisture Resistant
• Lead Free and RoHS compliant
• Bare conductors are heat treated
after stranding for maximum flexibility
ENERGEX® 8000 SER
UL 854
Service Entrance Type SE, Style R
XLPE Insulated Cable - Lead Free
600 Volts, 90°C Dry or Wet
ACM Aluminum Conductors
3 Insulated Conductors with Bare Ground
Insulated Insulation Thickness
Bare
Jacket Thickness
Nominal Diameter Approximate Net
Ampacity*
Conductor
Neutral
over Jacket
Cable Weight
(Amps)
Size
Size
AWGmils mmAWGmils mm
inchesmm lb/kft
kg/km
Dwelling
60°C
75°C
90°C
8 (1)
6 (7)
4 (7)
2 (7)
1 (18)
1/0 (18)
2/0 (18)
3/0 (18)
4/0 (18)
45
45
45
45
55
55
55
55
55
1.14
1.14
1.14
1.14
1.40
1.40
1.40
1.40
1.40
8 (1)
6 (7)
6 (7)
4 (7)
2 (7)
2 (7)
1 (18)
1/0 (18)
2/0 (18)
30
30
30
30
30
30
30
30
30
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.56
0.67
0.74
0.88
0.97
1.05
1.14
1.22
1.32
14.2
17.0
18.8
22.4
24.6
26.7
29.0
31.0
33.5
130
193
185
275
243
362
350
521
451
671
553
823
696 1036
780 1161
956 1423
–
–
–
100
110
125
150
175
200
30
40
55
75
85
100
115
130
150
40
50
65
90
100
120
135
155
180
45
55
75
100
115
135
150
175
205
*60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
• Ampacities for 8, 6 and 4 AWG are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for
aluminum conductors in a raceway or direct buried at 30°C ambient temperature, and a conductor temperature of 90°C.
• Ampacities for 2 AWG and larger are in accordance with NEC 2008 Table 310.15(B)(6) or NEC 2011 Table 310.15(B)(7)
for aluminum conductors.
1-866-663-9267
35
ENERGEX® 8000 SEU
Service Entrance Type SE, Style U
XLPE Insulated Cable - Lead Free
600 Volts, 90°C Dry or Wet
ACM Aluminum Conductors
Applications
Nexans ENERGEX® SEU is type SE,
Style U, cable used as an above
ground service entrance cable, a panel
feeder and in branch circuits. The cable
is rated at 600 volts and 90°C for use
in wet and dry locations in accordance
with NEC 2008 and NEC 2011 Article
338.
Nexans SEU cables are Lead Free and
RoHS compliant.
Construction
Conductor: Compact stranded AA8000 series aluminum alloy per ASTM
B800 and B801 (8 AWG is solid).
Insulation: color coded cross-linked
polyethylene (XLPE).
Insulated Assembly: Insulated
conductors are laid in a parallel
configuration. Solid bare wires
are applied concentrically over
the conductors forming the neutral
conductor. A flame retardant fiberglass
reinforced binder tape assembles the
core in a tight configuration.
Jacket: Sunlight resistant, lead
free, flame retardant, gray, polyvinyl
chloride (PVC) material.
Conductor Identification:
Color coded: Black and Red
Surface Print Legend:
NEXANS-C ENERGEX 8000 TYPE SE STYLE: U 600V AA-8000-AL 2/C 4/0
AWG + 1/C 2/0 AWG (UL) E-49786
SUN RES LEAD FREE (MFG. DATE)
1-866-663-9267
36
Specifications
• Meets UL 854: Service Entrance
Cables
Product features
• Cables are UL listed as Type SE,
Style U
• Temperature rating of 90°C dry
and wet
• Sunlight Resistant
• Moisture Resistant
• Lead Free and RoHS compliant
• Bare conductors are heat treated
after stranding for maximum flexibility
ENERGEX® 8000 SEU
UL 854
Service Entrance Type SE, Style U
XLPE Insulated Cable - Lead Free
600 Volts, 90°C Dry or Wet
ACM Aluminum Conductors
2 Insulated Conductors with Bare Concentric Neutral
Insulated
Insulation
Bare Jacket Thickness
Nominal Dimension
Approximate Net
Ampacity*
Conductor Thickness
Neutral
over Jacket
Cable Weight
(Amps)
SizeSize
AWG
mils
mm AWG mils
mm
inches
mm
lb/kft kg/km Dwelling60°C 75°C 90°C
8 (1)
6 (7)
4 (7)
2 (7)
2 (7)
1 (18)
1/0 (18)
2/0 (18)
2/0 (18)
3/0 (18)
4/0 (18)
4/0 (18)
45
45
45
45
45
55
55
55
55
55
55
55
1.14
1.14
1.14
1.14
1.14
1.40
1.40
1.40
1.40
1.40
1.40
1.40
8
6
6
4
2
1
1/0 1
2/0 3/0 2/0
4/0
30
30
30
30
30
30
30
30
30
30
30
30
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.76
0.40 x 0.26
0.46 x 0.73
0.51 x 0.82
0.56 x 0.93
0.56 x 0.93
0.64 x 1.05
0.67 x 1.12
0.73 x 1.22
0.77 x 1.26
0.80 x 1.35
0.86 x 1.45
0.90 x 1.49
10.2 x 6.6
11.7 x 18.5
13.0 x 20.8
14.2 x 23.6
14.2 x 23.6
16.3 x 26.7
17.0 x 28.5
18.5 x 31.0
19.6 x 32.0
20.3 x 34.3
21.8 x 36.8
22.9 x 37.9
105
156
147
216
188
200
265
394
286
426
350
521
425
632
487
725
527
784
620
923
697 1037
784 1167
–
–
–
100
100
110
125
150
150
175
200
200
30
40
55
75
75
85
100
115
115
130
150
150
40
50
65
90
90
100
120
135
135
155
180
180
45
55
75
100
100
115
135
150
150
175
205
205
*60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
Notes:
•W
here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
•D
welling ampacities are far 120/240-Volt, 3-Wire, single-phase dwelling services and feeders in accordance with NEC
2008 Table 310.15(8)(6) or NEC 2011 Table 310.15(B)(7) for aluminum conductors.
•6
0°C, 75°C and 90°C ampacities are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for
aluminum conductors in a raceway or direct buried at 30°C ambient temperature, and a conductor temperature of 90°C.
1-866-663-9267
37
Underground Secondary
Distribution Cables
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Aluminum Conductors
Applications
Underground Secondary Distribution
Cables are twisted assemblies of alloy
1350 aluminum conductors insulated
with cross-linked polyethylene. They
are used in various underground
applications in secondary distribution
circuits.
Nexans Underground Secondary
Distribution Cables are Lead Free and
RoHS compliant.
Construction
Conductor: Compressed Class B
stranded, 1350 series aluminum alloy.
Insulation: black cross-linked
polyethylene (XLPE).
Conductor Identification:
Phase conductors: Black
Neutral: Black with three extruded
yellow stripes.
Surface Print Legend:
NEXANS-WE 4/0 AWG ALUM 600V
XLPE (PHASE IDENTIFICATION FOR
QUADRUPLEX CONSTRUCTIONS)
SUN RES LEAD FREE (MFG DATE)
Specifications
• Meets UL 854: Service Entrance
Cables
• Meets ICEA S-105-692 Standard
for 600 Volt Single Layer Thermoset
Insulated Utility Underground
Distribution Cables
Assembly: Phase conductors and
neutral conductor are cabled together
to form a twisted assembly.
1-866-663-9267
38
Product features
• Available as single conductors, or as
a cabled assembly: Duplex, Triplex
or Quadruplex
• Temperature rating of 90°C dry and
wet, 130°C for emergency overloads
and 250°C under short circuit
conditions
• Suitable for direct burial or
installation in duct (such as a pole
riser)
• Sunlight Resistant
• Lead Free and RoHS compliant
• UL listing and marking for Type USE-2
Underground Secondary
Distribution Cables
UL 854
ICEA S-105-692
XLPE Insulated Cable
600 Volts, 90°C Dry or Wet - Lead Free
Aluminum Conductors
Duplex
1 Insulated Conductor with Insulated Neutral
Phase Conductor
Neutral Conductor
Cable
Code word Size
InsulationInsulation
Nominal
Approximate
(Black Neutral)1
AWG/kcmil
Thickness
Size
Thickness
Diameter
Net Weight
Ampacity* (ICEA)
(# of
mils
mm
(# of
mils mm inches mm
lb /
kg /
Direct Pole Riser
wires)wires)
1000 ft
km
Buried2Conduit3
CLAFLIN/XLP
6 (7)
60
1.52
6 (7)
60 1.52 0.60 15.24 91
135
97
47
Triplex
2 Insulated Conductors with Insulated Neutral
Code word
(Black Neutral)1
ERSKINE/XLP
VASSAR/XLP
STEPHENS/XLP
RAMAPO/XLP
BRENAU/XLP
CONVERSE/XLP
SWEETBRIAR/XLP
MONMOUTH/XLP
PRATT/XLP
WESLEYAN/XLP
Phase Conductor
Neutral Conductor
Cable
Size
Insulation
Size
Insulation
Nominal
Approximate
AWG/kcmil
Thickness
(# of
Thickness
Diameter
Net Weight
Ampacity* (ICEA)
(# of
mils
mm
wires)
mils
mm inches mm
lb /
kg /
Direct Pole Riser
wires) 1000 ft
km
Buried2 Conduit3
6 (7)
4 (7)
2 (7)
2 (7)
1/0 (19)
2/0 (19)
4/0 (19)
4/0 (19)
250 (37)
350 (37)
60
60
60
60
80
80
80
80
95
95
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.41
2.41
6 (7)
4 (7)
4 (7)
2 (7)
2 (7)
1 (19)
2/0 (19)
4/0 (19)
3/0 (19)
4/0 (19)
60
60
60
60
60
80
80
80
80
80
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
0.65
0.75
0.83
0.88
1.05
1.17
1.38
1.46
1.53
1.72
16.5 143
19.1 202
21.1 262
22.4 292
26.7 407
29.7 504
35.1 741
37.1 831
38.9 890
43.7 1160
213
301
390
435
606
750
1103
1237
1324
1726
97
123
160
160
205
233
301
301
329
395
47
60
82
82
112
132
185
185
199
248
Quadruplex
3 Insulated Conductors with Insulated Neutral
Code word
(Black Neutral)1
DYKE/XLP
WAKE FOREST/XLP
SLIPPERY ROCK/XLP
Phase Conductor
Neutral Conductor
Cable
Size
Insulation
Size
Insulation
Nominal
Approximate
AWG/kcmil Thickness
(# of
Thickness
Diameter
Net Weight
Ampacity* (ICEA)
(# of
mils
mm
wires)
mils mm inches mm
lb /
kg / Direct Pole Riser
wires)
1000 ft
km
Buried2 Conduit3
2 (7)
60
4/0 (19) 80
350 (37) 95
1.52
2.03
2.41
4 (7)
2/0 (19)
4/0 (19)
60
80
80
1.52 0.94 23.9 332 494
2.03 1.57 39.9 959 1427
2.03 1.95 49.5 1529 2275
160
301
395
82
185
248
*60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG.
75°C - W
hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90°C - Wet or dry locations. For ampacity derating purposes.
These ampacity values are not to be used for NEC.
Notes:
• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard
manufacturing tolerances.
1
For yellow stripes on neutral, add “EYS” to black neutral code word (eg. “Erskine/xLP/EYS”).
2
Non-NEC applications are based on the following installation parameters: 90°C conductor temperature, 20°C earth ambient temperature,
earth thermal resistivity (RHO) of 90°C cm / W, 36 inch depth of burial and 100% load factor
3
Non-NEC applications for pole riser conduit ampacities are based on the following installation parameters: 90°C conductor temperature,
40°C ambient air temperature, no sun (shaded), no wind, non-metallic duct and 100% load factor
1-866-663-9267
39
END-USER WARRANTY
WARRANTY LIMITATIONS
Nexans warrants to the end-user that
its cable will meet Nexans’ published
specifications for the cable and be
otherwise free from defects in material
and workmanship for a period of one
(1) year after the in-service date, or
one (1) year and six (6) months from
the original date of shipment from the
manufacturer, whichever occurs first
(the “Warranty Period”). If during the
Warranty Period, end-user believes that
there is a breach of warranty, end-user
must provide Nexans within ten (10)
days with written notification setting
forth the nature of the claimed breach.
Nexans shall promptly investigate
such claimed breach and shall, after
its investigation, either (i) provide
information to end-user confirming
that no breach of warranty has in fact
occurred; or (ii) advise end-user of
Nexans’ planned corrective action.
If a breach of warranty has in fact
occurred, Nexans shall, at its election,
promptly repair or replace the defective
cable at no cost to end-user. All costs
incidental to such corrective
action including, but not limited
to removal, disassembly,
reinstallation and reconstruction
shall be borne by the enduser and in no event shall
Nexans be liable for such costs.
Furthermore, Nexans will not
be responsible for any damage
or repairs to, or replacement
of, adjacent or connected
equipment to which the cable
may supply electrical power, or
from which it may take electrical
power, or with which it may,
in any manner, be connected.
All warranty repairs or replacements
made during the Warranty Period shall
be warranted for the balance of the
Warranty Period.
 
This warranty does not cover the repair
or replacement of any cable which fails
as a result of damage in transit, misuse,
neglect, accident, Acts of God, abuse,
improper handling, improper storage,
excessive stress, faulty or improper
or unauthorized installation or repair,
negligent maintenance or failure to
comply with the written instructions
for installation, use or maintenance
provided by Nexans.
SOLE AND EXCLUSIVE Remedy
THIS document sets forth
Nexans’ sole and exclusive
warranty obligation to EndUSER AND END-USER’s sole and
exclusive remedy in the event of
Defective cable.
EXCLUSION OF OTHER
WARRANTIES
THIS WARRANTY IS IN LIEU OF ALL
OTHER WARRANTIES, EXPRESS
OR IMPLIED, AND ALL OTHER
WARRANTIES, INCLUDING BUT NOT
LIMITED TO THE IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE, ARE
EXPRESSLY DISCLAIMED.
LIMITATION OF LIABILITY AND
LIMITATION OF ACTIONS
IN NO EVENT SHALL NEXANS
BE LIABLE FOR ANY INDIRECT,
INCIDENTAL, SPECIAL, PUNITIVE
OR CONSEQUENTIAL LOSS,
DAMAGE OR EXPENSE (WHICH
SHALL BE DEEMED TO INCLUDE
WITHOUT LIMITATION, ANY LOSS
OF PROFIT OR REVENUE, ANY LOSS
OF GOODWILL, LOSS CLAIMED
BY END-USER’S CUSTOMERS,
OR ANY LOSS OF BUSINESS
OPPORTUNITY), OF ANY NATURE
OR KIND, HOWEVER ARISING,
WHETHER IN CONTRACT, IN TORT
OR OTHERWISE, EVEN IF NEXANS
IS DEEMED TO BE AWARE OF THE
POSSIBILITY OF SUCH DAMAGES.
NEXANS’ MAXIMUM LIABILITY FOR
ANY CLAIM, LOSS OR DAMAGE
SHALL UNDER NO CIRCUMSTANCES
EXCEED THE PURCHASE PRICE FOR
THE CABLE SUBJECT TO A CLAIM,
EVEN IF END-USER HAS CLAIMS OR
IS SUBJECT TO CLAIMS IN EXCESS
OF THIS LIMITATION. ANY LEGAL
PROCEEDING RELATING TO THIS
WARRANTY MUST BE BROUGHT
WITHIN (1) YEAR AFTER THE CAUSE
OF ACTION ARISES.
NOTICE
WARNING
Nexans has endeavored to ensure
the accuracy of the data in this
publication, however we cannot be
liable for the consequences of errors
or omissions. All data is subject to
change without notice. The installer
and / or user assumes all liability for
the consequences of the installation
and / or use of any of our products in
contravention of any applicable law,
regulation or code.
FLAMMABLE
Non-metallic covering of electrical
cables will burn and under certain
conditions may transmit fire when
ignited
1-866-663-9267
40
TOXIC
Burning non-metallic coverings may
emit acid gases, which are highly
toxic and may generate dense smoke.
CORROSIVE
Emission of acid gases may corrode
metal in the vicinity, such as sensitive
instruments and reinforcing rod in
concrete.
Download