Introduction Nexans is one of the largest wire and cable manufacturers in the world, and in North America. In North America we manufacture in locations across the United States and Canada. We design and produce a wide range of cables used in power, industrial, construction and communication applications. With more than a century of experience as a leader in the industrial and power cable markets, Nexans is contracted by heavy industry and utilities worldwide to provide turnkey solutions for the bulk transmission of power - from generating station through the transmission and distribution systems to commercial, residential and industrial areas. This catalog has been prepared for the convenience of those using electrical conductors in industrial, commercial and residential applications. The information included in the many tabulations will be of particular value to the architect, engineer, electrician, and layperson alike. For your convenience, we have referenced applicable Articles and Tables from both the 2008 NEC and the 2011 NEC. Although we have listed the types of wires and cables suitable for most conditions, we are equipped to manufacture other types to suit special needs. We would be pleased to recommend the most suitable construction for any special condition that you may encounter. The determination of the correct cable size and type, and the selection of methods of installation suitable for the type and location of particular circuits, should be made in accordance with local regulations. Any questions in this respect should be directed primarily to the local Electrical Inspection Authority. We are pleased to note that all the cables in this catalog are LEAD FREE. This indicates that the component has less than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of hazardous substances) regulations and below the level requiring labeling by California Proposition #65. Nexans wire and cable Contact us for all your wire and cable needs Nexans Energy USA inc. 25 Oakland Avenue Chester, NY 10918 Tel: 1-866-663-9267 www.nexans.us A t t h e c o r e o f p e r f o r m a n c e 1 ENERGEX® Building Wire INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 ENERGEX® BARE COPPER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3 ENERGEX® TFN/TFFN Copper . . . . . . . . . . . . . . . . . . . . . . Pages 4 & 5 ENERGEX® THHN/THWN-2/MTW Copper . . . . . . . . . . . . . Pages 6 & 7 ENERGEX® NM-B Copper . . . . . . . . . . . . . . . . . . . . . . . . . Pages 8 & 9 ENERGEX® UF-B Copper . . . . . . . . . . . . . . . . . . . . . . . . Pages 10 & 11 ENERGEX® XHHW-2 Copper . . . . . . . . . . . . . . . . . . . . . Pages 12 & 13 ENERGEX® 8000 XHHW-2 Aluminum . . . . . . . . . . . . . . . Pages 14 & 15 ENERGEX® RHH/RHW-2/USE-2 Copper . . . . . . . . . . . . . Pages 16 & 17 ENERGEX® 8000 RHH/RHW-2/USE-2 Aluminum . . . . . . . Pages 18 & 19 ENERGEX® 8000 Mobile Home Feeder Aluminum . . . . . . Pages 20 & 21 ENERGEX® PV 600 Volt Copper . . . . . . . . . . . . . . . . . . . Pages 22 & 23 ENERGEX® 8000 PV 600 Volt Aluminum . . . . . . . . . . . . . Pages 24 & 25 ENERGEX® PV 2 kV Copper . . . . . . . . . . . . . . . . . . . . . . Pages 26 & 27 ENERGEX® 8000 PV 2 kV Aluminum . . . . . . . . . . . . . . . . Pages 28 & 29 ENERGEX® MC 120 Volt Copper . . . . . . . . . . . . . . . . . . Pages 30 & 31 ENERGEX® MC 277 Volt Copper . . . . . . . . . . . . . . . . . . Pages 32 & 33 ENERGEX® 8000 SER Aluminum . . . . . . . . . . . . . . . . . . . Pages 34 & 35 ENERGEX® 8000 SEU Aluminum . . . . . . . . . . . . . . . . . . Pages 36 & 37 ENERGEX® URD Aluminum . . . . . . . . . . . . . . . . . . . . . . . Pages 38 & 39 WARRANTY & NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 40 1-866-663-9267 2 Soft Drawn Bare Copper Description Application Solid or stranded 100% conductivity copper conductors. ASTM B3 Soft or Annealed Copper Wire* ASTM B8 Concentric - Lay - Stranded Copper Conductors Used for bonding and grounding electrical circuits and systems. Conductor Size Number of Strands AWG/kcmil 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 750 1000 1 1 1 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 Nominal Diameter Approximate Net Cable Weight inches mm lbs/kftkg/km UL Solid - ASTM B3 Stranded - ASTM B8 Average D.C. Resistance at 25° C Ω/kft Ω/km 0.0641 1.63 12.68 18.87 2.58 8.46 0.0808 2.05 20.16 30.00 1.63 5.53 0.1012.5932.0647.72 1.02 3.35 0.1423.6150.9775.86 0.640 2.10 0.1784.5281.05120.6 0.403 1.32 0.2255.72128.9191.8 0.253 1.05 0.2837.19204.9304.9 0.159 0.659 0.3228.18258.4384.6 0.127 0.522 0.3629.19325.8484.9 0.100 0.328 0.40510.29410.9 611.5 0.0795 0.261 0.45611.58518.1 771.1 0.0630 0.207 0.51213.00653.1 972.0 0.0500 0.164 0.55814.17771.9 1149 0.0423 0.139 0.61115.52926.3 1379 0.0353 0.116 0.661 16.79 1081 1609 0.0302 0.0991 0.706 17.93 1235 1838 0.0264 0.0866 0.789 20.04 1544 2298 0.0212 0.0695 0.866 22.00 1883 2758 0.0177 0.0581 0.968 24.59 2316 3447 0.0141 0.0462 1.117 28.37 3088 4596 0.0106 0.0348 Notes: •W here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. *ASTM B3 Specification details the requirements for solid wires and the individual wires in stranded conductors. 1-866-663-9267 3 ENERGEX® TFN/TFFN PVC Insulated Cable 600 Volts, 90°C - Lead Free Copper Conductors Applications Construction Specifications Nexans ENERGEX® TFN (solid) /TFFN (flexible stranded) copper conductors may be used as fixture wire, machine tool wire (MTW) or for appliance wiring material (AWM), as outlined in the NEC 2008 and NEC 2011. These conductors are heat, moisture, and gasoline and oil resistant II. Conductor: TFN - solid annealed soft bare copper per ASTM B3. TFFN/MTW/AWM - flexible stranded annealed soft bare copper per ASTM B174 • Nexans ENERGEX® TFN/TFFN meets or exceeds UL 66 (Fixture Wires) and the requirements of the National Electrical Code - Fixture wire. • TFFN meets or exceeds UL 1063 (Machine-Tool Wires and Cables) for Machine Tool Wire and UL 758 (Appliance Wiring Materials) for AWM Style 1316. • The insulation is heat, moisture, gasoline and oil resistant II. • TFN/TFFN shall be lead free and RoHS compliant. • Voltage rating - 600 Volts. TFN and TFFN are used for internal wiring of lighting fixtures and similar equipment, and for connection to branch circuit wiring inside lighting fixtures and similar equipment. TFN/TFFN is rated at a conductor temperature of 90°C in dry locations. MTW is used for internal wiring of machines tools, rated 90°C in dry locations and 60°C when exposed to oils or coolants. AWM is used as factory installed internal wiring of appliances, rated 105°C in dry locations. Nexans TFN/TFFN conductors are Lead Free and RoHS compliant. Insulation: Color coded, heat, moisture and flame resistant polyvinyl chloride (PVC). Covering: Strong, slick polyamide (Nylon) outer covering, Colors: Standard TFN and TFFN colors available in black, white, red, blue, green, yellow, pink, purple, orange, brown and gray. Additional colors are made per request subject to factory minimum order quantities. Surface Print Legend: NEXANS-F 16 AWG (1.31 mm2) (UL) TFFN or MTW or AWM 600V VW-1 GASOLINE AND OIL RESISTANT II LEAD FREE MADE IN CANADA (MFG. DATE) 1-866-663-9267 4 Product Features • Heat and moisture resistant • Gasoline and oil resistant II • Rated for use as appliance wiring • Available from inventory in 11 colors • Lead Free and RoHS compliant ENERGEX® TFN/TFFN UL 66 UL 1063 UL 758, Style 1316 PVC Insulated Cable 600 Volts, 90°C - Lead Free Copper Conductors Conductor Size PVC Insulation Nylon Nominal ThicknessThickness Diameter Approximate Net Cable Weight Ampacity (Amps) AWG mils mm mils mm inches mm lbs/kft kg/km TFN/TFFN MTW1 @ 90°C TFN 18 (1) 15 0.38 4 0.10 0.081 2.05 7.1 10.6 6 16 (1) 15 0.38 4 0.10 0.094 2.39 10.6 15.8 8 TFFN / MTW 18 (16) 15 0.38 4 0.10 0.087 2.21 7.4 11.0 6 7 16 (26) 15 0.38 4 0.10 0.100 2.54 11.0 16.4 8 10 Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Article 336.80, and Table 402.5 “Allowable Ampacity for Fixture Wires” at an ambient temperature of 30°C (with no load diversity). • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • Refer to NEC 2008 and NEC 2011 Article 240.4(D) for overcurrent protection requirements. Allowable ampacities for MTW are as shown in NFPA 79. 1 1-866-663-9267 5 ENERGEX® THHN/ THWN-2/MTW PVC/Nylon Cable 600 Volts, 90°C - Lead Free Copper Conductors Applications Nexans ENERGEX® THHN/THWN-2/ MTW* is a general purpose wiring product for use in power, lighting and control circuits. It can be used in conduit, ducts and trays for service feeders and branch circuits in industrial and commercial installations. When used in accordance with the 2008 or 2011 NEC, THHN/THWN-2 is suitable for use in wet and dry locations, at conductor temperatures not exceeding 90°C or for use in oil or coolants at conductor temperatures not exceeding 75°C. THHN/THWN-2 is gasoline and oil resistant II. When used as Machine Tool Wire (MTW) it is rated at 90°C in dry locations and 60°C in wet locations or when exposed to oil or coolants. Nexans THHN/THWN-2/MTW wire is Lead Free and RoHS compliant. * Only stranded cables are MTW listed per UL 1063. Construction Conductor: Solid bare, annealed copper per ASTM B3. Stranded bare annealed copper per ASTM B3 and ASTM B787 for sizes 14, 12, 10 and 8 AWG and ASTM B8 for sizes 6 AWG and larger. Covering: A tough abrasion resistant polyamide (Nylon) covering Surface Print Legend: NEXANSC 500 kcmil (253mm2) TYPE MTW OR THHN OR THWN-2 GRII SR FOR CT USE VW-1 600V (UL) LEAD FREE (MFG. DATE) Specifications • Nexans ENERGEX® THHN/THWN2 or MTW meets or exceeds all applicable ASTM specifications • UL 83: Thermoplastic Insulated Wires and Cables • UL 1063: Machine-Tool Wires and Cables (stranded cables only) • Nema WC70 / ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy • Federal Specification A-A-59544 and requirements of the NEC • CSA C22.2 No. 75: Thermoplastic Insulated Wires and Cables •14 AWG through 750 kcmil are rated VW-1 • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • Black sizes 1/0 AWG and larger are sunlight resistant • Voltage rating - 600 volts. Insulation: Color coded polyvinyl chloride (PVC), heat, moisture and flame retardant compound per UL 83 and UL 1063 1-866-663-9267 6 Product Features • Sizes 8 AWG to 600 kcmil available in various colors from stock • Cables are UL listed as Type THHN/ THWN-2/MTW* • Meets UL VW-1 flame test requirements • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • Black 1/0 AWG and larger is sunlight resistant • High heat and moisture resistant • THWN-2 90°C rated for dry and wet locations • Gasoline and Oil Resistant II • Small diameter for improved conduit fill • Lead Free and RoHS compliant Packaging •14 & 12 AWG: 4 x 500’ spools (2000’ per carton) or 2500’ reel •10 AWG: 2 x 500’ spools (1000’ per carton) or 2500’ reel •8 AWG - 4/0 kcmil: 500’, 1000’, 2500’ or 5000’ reel •250 kcmil - 600 kcmil: 500’, 1000’, or 2500’ reel • 750 kcmil: 1000’ reel ENERGEX® THHN/ THWN-2/MTW UL 83 / CSA C22.2 No. 75 UL 1063 ICEA S-95-658 PVC/Nylon Cable 600 Volts, 90°C - Lead Free Copper Conductors ConductorPVC Insulation Nylon Nominal Diameter Approximate NetAmpacity* Size Thickness Thickness AWG/kcmil 14 (1) 12 (1) 10 (1) 14 (19) 12 (19) 10 (19) 8 (19) 6 (19) 4 (19) 3 (19) 2 (19) 1 (19) 1/0 (19) 2/0 (19) 3/0 (19) 4/0 (19) 250 (37) 300 (37) 350 (37) 400 (37) 500 (37) 600 (61) 750 (61) mils 15 15 20 15 15 20 30 30 40 40 40 50 50 50 50 50 60 60 60 60 60 70 70 mm mils 0.38 4 0.38 4 0.51 4 0.38 4 0.38 4 0.51 4 0.76 5 0.76 5 1.01 6 1.01 6 1.01 6 1.27 7 1.27 7 1.27 7 1.27 7 1.27 7 1.52 8 1.52 8 1.52 8 1.52 8 1.52 8 1.78 9 1.78 9 mm 0.10 0.10 0.10 0.10 0.10 0.10 0.13 0.13 0.15 0.15 0.15 0.18 0.18 0.18 0.18 0.18 0.20 0.20 0.20 0.20 0.20 0.23 0.23 inches mm 0.11 2.8 0.12 3.1 0.15 3.8 0.11 2.8 0.13 3.8 0.17 4.3 0.22 5.6 0.26 6.6 0.33 8.4 0.36 9.1 0.39 9.9 0.43 10.9 0.47 12.0 0.52 13.2 0.57 14.5 0.64 16.0 0.69 17.4 0.76 19.3 0.79 20.1 0.85 21.6 0.94 23.9 1.10 27.9 1.16 29.5 Cable Weight (Amps) lbs/kftkg/km 60°C 75°C 90°C 15 22.3 15 15 15 23 34.2 20 20 20 37 53.6 30 30 30 16 23.8 15 15 15 24 35.7 20 20 20 39 58.0 30 30 30 63 93.7 40 50 55 98 145 55 65 75 157 234 70 85 95 193 287 85 100 110 240 357 95 115 130 300 446 110 130 150 376 560 125 150 170 467 695 145 175 195 581 864 165 200 225 724 1077 195 230 260 855 1272 215 255 290 1022 1521 240 285 320 1191 1772 260 310 350 1345 2001 280 335 380 1668 2482 320 380 430 1994 2967 355 420 475 2465 3668 400 475 535 *60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. For MTW in wet locations or when exposed to oil or coolant. 75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG. THWN-2 when exposed to oil or coolant. 90°C - THHN dry locations. THWN-2 wet or dry locations. For ampacity derating purposes. Available colors: Black, White, Red, Blue, Green, Yellow, Brown, Orange, Purple, Gray, Pink. Notes: •W here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. •A mpacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. • F or correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16). •N EC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1-866-663-9267 7 ENERGEX® NM-B PVC/Nylon Insulated Cable 600 Volts, 90°C Dry - Lead Free Copper Conductors Applications Construction Specifications Nexans ENERGEX® non-metallic sheathed cable NM-B is used in normally dry installations in residential wiring, as branch circuits for outlets, lighting and other residential loads. Its applications are outlined in NEC 2008 and NEC 2011 Article 334. NM-B is rated at 600 volts and although it is rated at a conductor temperature of 90°C dry, its ampacity is limited to 60°C according to the NEC 2008 and NEC 2011. It may be fished through masonry or tile walls, where not exposed or subject to excessive moisture or dampness. Conductor: Solid 14 to 10 AWG annealed soft bare copper per ASTM B3. Stranded 8 AWG and larger annealed soft bare copper per ASTM B3 and B8. • Nexans ENERGEX® NM-B meets or exceeds all applicable ASTM specifications. • UL 83: Thermoplastic Insulated Wires and Cables • UL 719: Non-Metallic Cables • Federal Specification A-A-59544 and requirements of the NEC. • Voltage rating - 600 volts. Nexans NM-B cables are Lead Free and RoHS compliant. Sheath: 30 mil color coded PVC sheath rated 90°C is applied over the completed assembly: • White 14 AWG • Yellow 12 AWG • Orange 10 AWG • Black 8 to 2 AWG Insulation: Color coded polyvinyl chloride (PVC) compound with a nylon covering meeting the required thickness of Type THHN. Conductor insulation is rated 90°C. Ground: Soft, bare copper solid per ASTM B3 and stranded per ASTM B3 and B8 Surface Print Legend: NEXANS-C ENERGEX 2C-14 AWG TYPE NM-B 600V W/GRD (UL) LEAD FREE MM/ DD/YY MADE IN U.S.A. 1-866-663-9267 8 Product Features • Slick proprietary sheathing material designed for ease of installation • Color coded sheaths designed for quick cable identification • Lead free and RoHS compliant • 14 AWG 2C and 12 AWG 2C available with two neutral conductors Packaging •14, 12 & 10 AWG; 2, 3 and 4 conductor - 250 ft coil and 1000 ft reel •8 AWG and larger 2 and 3 conductor - 125 ft coil, 500 and 1000 ft reel ENERGEX® NM-B UL 83 UL 719 PVC/Nylon Insulated Cable 600 Volts, 90°C Dry - Lead Free Copper Conductors Conductor # of Size Conductors AWG Two Conductor 14 (1) 2 12 (1) 2 10 (1) 2 8 (7) 2 6 (7) 2 Three Conductor 14 (1) 3 12 (1) 3 10 (1) 3 8 (7) 3 6 (7) 3 4 (7) 3 2 (7) 3 Four Conductor 14 (1) 2/21 14 (1) 42 12 (1) 2/21 12 (1) 42 PVC Insulation Ground Nylon Thickness Wire Size Thickness mils mm AWG mils mm Nominal Cable Dimensions inches mm 15 15 20 30 30 0.38 0.38 0.51 0.76 0.76 14 12 10 10 10 (1) (1) (1) (1) (1) 4 4 4 5 5 0.10 0.10 0.10 0.13 0.13 15 15 20 30 30 40 40 0.38 0.38 0.51 0.76 0.76 1.02 1.02 14 (1) 12 (1) 10 (1) 10 (1) 10 (1) 8 (7) 6 (7) 4 4 4 5 5 6 6 0.10 0.10 0.10 0.13 0.13 0.15 0.15 0.31 0.34 0.43 0.56 0.63 0.85 0.98 15 15 15 15 0.38 0.38 0.38 0.38 14 14 12 12 4 4 4 4 0.10 0.10 0.10 0.10 0.35 0.35 0.38 0.38 (1) (1) (1) (1) 0.16 0.17 0.21 0.27 0.32 x x x x x 0.36 4.0 x 9.1 0.40 4.3 x 10.2 0.49 5.3 x 12.4 0.59 6.9 x 15.0 0.68 8.1 x 17.3 Approximate Net Ampacity Cable Weight (Amps) lbs/kftkg/km 57 82 124 186 255 85 122 185 277 379 15 20 30 40 55 7.9 8.6 10.9 14.2 16.0 21.6 24.9 74 107 163 254 357 593 856 110 159 243 378 531 882 1274 15 20 30 40 55 70 95 8.9 8.9 9.7 9.7 91 91 132 132 135 135 196 196 15 15 20 20 Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature and 60°C rated conductors. • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4 (E) through (G) 1 Insulation color code for 2 / 2 conductor cable is Black, White, Red, and White with Red stripe. Cable ampacity is based on the White and White with Red stripe conductors being connected as the neutrals for the system. 2 Insulation color code for 4 conductor cable is Black, White, Red and Blue. Cable ampacity is based on the 4th conductor being connected as the neutral conductor of a balanced 3 phase system. 1-866-663-9267 9 ENERGEX® UF-B PVC/Nylon Insulated Cable 600 Volts, 90°C Dry - Lead Free Copper Conductors Applications Construction Product Features Nexans ENERGEX® UF-B is an underground feeder and branch circuit wiring cable. Its applications are outlined in Article 340 NEC 2008 and NEC 2011. UF-B is rated at 600 volts. Although it is rated at a conductor temperature of 90° C dry / wet its ampacity is limited to 60°C according to the NEC 2008 and NEC 2011. UF-B may be directly buried or installed where exposed to sunlight. When used as an NM cable it must comply with the requirements in NEC 2008 or NEC 2011 Article 334. It can be used as an underground feeder from an existing building to outdoor lighting fixtures, pumps, outbuildings and other equipment. Conductor: Solid annealed soft bare copper per ASTM B3. Stranded annealed soft bare copper per ASTM B3 and ASTM B8. • Slick proprietary jacketing compound designed for quick and easy installation • Gray jacket designed for quick cable identification • Lead free and RoHS compliant • Meets or exceeds all applicable industry standards Nexans UF-B cables are Lead Free and RoHS compliant. Insulation: Polyvinyl chloride (PVC) with a nylon covering. Color coded phase identification. Ground: Soft bare copper, solid per ASTM B3 and stranded per ASTM B3 and ASTM B8. Jacket: Sunlight, moisture and fungus resistant gray PVC. Surface Print Legend: NEXANS-C ENERGEX 2C-14 AWG W/GRND TYPE UF-B SUN RES 600V (UL) LEAD FREE MM/DD/YY MADE IN U.S.A. Specifications • Nexans ENERGEX® UF-B meets or exceeds all applicable ASTM specifications. • UL 83: Thermoplastic Insulated Wires and Cables • UL 493: Thermoplastic-Insulated Underground Feeder and Branch Circuit Cables • Federal Specification A-A-59544 and requirements of the NEC. • Voltage rating - 600 volts. 1-866-663-9267 10 Packaging •14, 12 & 10 AWG; 2, 3 and 4 conductor: 250 ft coil and 1000 ft reel •8 & 6 AWG; 2 and 3 conductor: 125 ft coil and 500 ft reel •Bar coded reels and coils for ease of material handling ENERGEX® UF-B UL 83 UL 493 PVC/Nylon Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Copper Conductors Conductor PVC Insulation Nylon PVC Jacket Ground Size Thickness Thickness Thickness Wire Size AWG mils mm mils mm mils mm AWG Two Conductor With Ground 14 (1) 15 0.38 4 0.10 30 0.76 14 (1) 12 (1) 15 0.38 4 0.10 30 0.76 12 (1) 10 (1) 20 0.51 4 0.10 30 0.76 10 (1) 8 (7) 30 0.76 5 0.13 45 1.14 10 (1) 6 (7) 30 0.76 5 0.13 45 1.14 10 (1) Three Conductor With Ground 14 (1) 15 0.38 4 0.10 30 0.76 14 (1) 12 (1) 15 0.38 4 0.10 30 0.76 12 (1) 10 (1) 20 0.51 4 0.10 30 0.76 10 (1) 8 (7) 30 0.76 5 0.13 45 1.14 10 (1) 6 (7) 30 0.76 5 0.13 45 1.14 10 (1) Nominal Cable Dimensions inches mm Approximate Net Ampacity Cable Weight (Amps) lbs/kft kg/km 0.18 0.19 0.22 0.31 0.34 x x x x x 0.36 0.39 0.45 0.68 0.78 4.6 x 9.2 4.8 x 9.9 5.6 x 11.4 7.9 x 17.3 8.6 x 19.8 55 75 140 213 305 82 112 208 317 454 15 20 30 40 55 0.18 0.19 0.22 0.32 0.38 x x x x x 0.58 0.62 0.67 0.99 1.20 4.6 4.8 5.6 8.1 9.7 93 134 194 330 449 138 200 289 491 668 15 20 30 40 55 x x x x x 14.7 15.7 17.0 25.1 30.5 Notes: •W here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. •A mpacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature and 60°C rated conductors. • F or correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16). •N EC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1-866-663-9267 11 ENERGEX® XHHW-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Copper Conductors Applications Specifications Product Features Nexans ENERGEX® XHHW-2 is a copper conductor, with crosslinked polyethylene insulation. The cable is rated at 600 volts and 90°C for use in wet and dry locations. XHHW-2 can be used in conduit and other raceways for services, feeders and other applications recognized by the NEC 2008 and NEC 2011. • Nexans ENERGEX® Type XHHW2 meets or exceeds all applicable ASTM specifications. • UL 44: Thermoset-Insulated Wires and Cables • Federal Specification A-A-59544 and the requirements of the NEC. • NEMA WC70 / ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use. • Sunlight resistant in black 8 AWG and larger. • 14 to 10 AWG are available in 10 distinct colors for identification purposes. • Sizes 14 to 4/0 AWG rated SIS. • Nexans XHHW-2 is lead free. • Voltage rating - 600 Volts. • Sizes 14, 12 and 10 AWG are available in 10 colors: Black, White, Red, Blue, Green, Yellow, Brown, Orange, Gray, Purple. • Size 8 AWG and larger in black only. • Meets IEEE 1202 • Conforms to ICEA S-95-658 • Sunlight Resistant 8 AWG and larger in black • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • Sizes 14 to 4/0 AWG rated SIS • Meets or exceeds all applicable industry standards • Lead Free Sizes 14 to 4/0 AWG are approved as Type SIS. Sizes 1/0 AWG and larger (4 AWG and larger in green) in all colors are cable tray (CT) rated. Nexans XHHW-2 conductors are Lead Free. Construction Conductor: Annealed soft bare copper per ASTM B3, B787 and B8 Insulation: Cross-linked polyethylene (XLPE) insulation per UL 44 Surface Print Legend: NEXANS EXELENE 500 kcmil (253 mm2) XHHW2 (UL) E64801 F 600V FOR CT USE SR - MADE IN CANADA LEAD FREE (MFG. DATE) 1-866-663-9267 12 Packaging •14 to 10 AWG 2 x 500’ spools (1000 feet) per carton; 2500’ reel • 8 AWG - 600 kcmil long length • 750 kcmil 500’ reel or long length ENERGEX® XHHW-2 UL 44 ICEA S-95-658 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Copper Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 14 (7) 30 0.76 0.13 3.4 12 (7) 30 0.76 0.15 3.8 10 (7) 30 0.76 0.17 4.5 8 (7) 45 1.14 0.24 6.0 6 (7) 45 1.14 0.27 6.9 4 (7) 45 1.14 0.32 8.2 2 (7) 45 1.14 0.38 9.6 1 (19) 55 1.40 0.43 10.9 1/0 (19) 55 1.40 0.48 12.1 2/0 (19) 55 1.40 0.52 13.2 3/0 (19) 55 1.40 0.56 14.2 4/0 (19) 55 1.40 0.61 15.6 250 (37) 65 1.65 0.68 17.1 300 (37) 65 1.65 0.75 18.9 350 (37) 65 1.65 0.80 20.2 400 (37) 65 1.65 0.84 21.4 500 (37) 65 1.65 0.93 23.5 600 (61) 80 2.03 1.04 26.3 700 (61) 80 2.03 1.10 27.9 750 (61) 80 2.03 1.14 28.8 1000 (61) 80 2.03 1.29 32.7 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 90°C 18 27 15 15 15 26 39 20 20 20 40 60 30 30 30 64 95 40 50 55 97 144 55 65 75 149 222 70 85 95 230 342 95 115 130 288 429 110 130 150 360 536 125 150 170 456 679 145 175 195 563 838 165 200 225 703 1046 195 230 260 837 1245 215 255 290 995 1481 240 285 320 1155 1719 260 310 350 1324 1970 280 335 380 1643 2445 320 380 430 1986 2955 355 420 475 2283 3397 385 460 520 2467 3671 400 475 535 3230 4806 455 545 615 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1-866-663-9267 13 ENERGEX® 8000 Type XHHW-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free ACM Aluminum Conductors Applications Specifications Product features Nexans ENERGEX® 8000 XHHW-2 is an AA-8000 series aluminum (ACM) conductor with cross-linked polyethylene insulation. The cable is rated at 600 volts and 90°C for use in wet and dry locations. XHHW-2 can be used in conduit and other raceways for services, feeders and other applications recognized by the NEC 2008 and NEC 2011. • Nexans ENERGEX® 8000 XHHW-2 meets or exceeds all applicable ASTM specifications. • UL 44: Thermoset-Insulated Wires and Cables • NEC 2008 Article 310.13 or NEC 2011 Article 310.104 • Federal Specification A-A-59544 and the requirements of the NEC. • NEMA WC7O / ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • Sunlight Resistant 8 AWG and larger in black • Sizes 12 to 4/0 AWG rated SIS • Voltage rating - 600 Volts. • Meets IEEE 1202 • Cables are UL listed as Type XHHW-2 • Temperature rating of 90°C dry and wet • Sunlight Resistant, black 8 AWG and larger • Lead Free • Bare conductors are heat treated after stranding for maximum flexibility • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • Sizes 12 to 4/0 AWG rated SIS Sizes 12 to 4/0 AWG are approved as SIS. Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use. Nexans XHHW-2 is lead free. Construction Conductor: compact stranded AA-8000 series aluminum alloy per ASTM B800 and B801 Insulation: black sunlight resistant, cross-linked polyethylene (XLPE) meeting the requirements for XHHW-2 per UL 44. Surface Print Legend: NEXANS-C 1/0 AWG COMPACT AA8000-AL XHHW-2 600V FOR CT USE SR LEAD FREE (UL) (MFG. DATE) 1-866-663-9267 14 ENERGEX® 8000 Type XHHW-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free ACM Aluminum Conductors Conductor Size Insulation Thickness Nominal Diameter Approximate Net Cable Weight UL 44 ICEA S-95-658 Ampacity* (Amps) AWG/kcmil mils mm inches mm lb/kft kg/km 60°C 75°C 90°C 6 (7)451.14 0.26 6.64059 4050 55 4 (7)451.14 0.31 7.95785 5565 75 2 (7)451.14 0.36 9.1841257590100 1 (18) 55 1.40 0.42 10.7 108 161 85 100 115 1/0 (18) 55 1.40 0.45 11.4 131 196 100 120 135 2/0 (18) 55 1.40 0.49 12.4 161 239 115 135 150 3/0 (18) 55 1.40 0.54 13.7 198 294 130 155 175 4/0 (18) 55 1.40 0.59 15.0 243 361 150 180 205 250 (35) 65 1.65 0.66 16.8 292 434 170 205 230 300 (35) 65 1.65 0.71 18.0 352 524 195 230 260 350 (35) 65 1.65 0.75 19.1 394 586 210 250 280 400 (35) 65 1.65 0.80 20.3 446 663 225 270 305 500 (35) 65 1.65 0.87 22.1 548 815 260 310 350 600 (58) 80 2.03 0.98 24.9 670 997 285 340 385 700 (58) 80 2.03 1.04 26.4 787 1171 315 375 425 750 (58) 80 2.03 1.08 27.4 822 1224 320 385 435 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 12 through 1 AWG. 75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for aluminum conductors in a raceway or direct buried at 30°C ambient temperature. • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1-866-663-9267 15 ENERGEX® RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Copper Conductors Applications Construction Specifications Nexans ENERGEX® RHH/RHW-2/ USE-2 conductors may be installed in raceways and conduits or directly buried. They are 90°C, 600 volts per NEC 2008 and NEC 2011 Articles 310 and 338. Conductor: Stranded annealed soft bare copper conductors per ASTM B8 and B787 • Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables • Meets UL 854: (USE-2) Service Entrance Cables • Federal Specification A-A-59544 • ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy • National Electrical Code - NFPA 70 • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use Type USE-2 conductors are suitable as service entrance conductors which can be installed directly buried in accordance with the NEC. When used as type RHH, the cables are suitable for installation in dry locations. Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation per UL 854 and UL 44. Black only. Surface Print Legend: NEXANS 1/0 AWG (53.5 mm2) (UL) E64801 F RHW-2 OR USE-2 600V FOR CT USE SR MADE IN CANADA LEAD FREE (MFG DATE). As type RHW-2 and USE-2, they are suitable for installation in both wet and dry locations. Product Features • Cables are UL listed as Type USE-2 • Temperature rating of 90°C dry and wet • Suitable for direct burial • Sunlight resistant • Lead Free Nexans RHH/RHW-2/USE-2 conductors are Lead Free. 1-866-663-9267 16 ENERGEX® RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Copper Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 14 (1) 45 1.14 0.16 4.0 12 (1) 45 1.14 0.17 4.4 10 (1) 45 1.14 0.19 4.9 14 (7) 45 1.14 0.16 4.1 12 (7) 45 1.14 0.18 4.7 10 (7) 45 1.14 0.21 5.2 8 (7) 60 1.52 0.27 6.8 6 (7) 60 1.52 0.31 7.8 4 (7) 60 1.52 0.35 8.9 2 (7) 60 1.52 0.41 10.4 1 (19) 80 2.03 0.49 12.4 1/0 (19) 80 2.03 0.53 13.4 2/0 (19) 80 2.03 0.57 14.5 3/0 (19) 80 2.03 0.61 15.4 4/0 (19) 80 2.03 0.68 17.2 250 (37) 95 2.41 0.74 18.7 300 (37) 95 2.41 0.81 20.5 350 (37) 95 2.41 0.86 21.8 400 (37) 95 2.41 0.90 22.9 500 (37) 95 2.41 0.99 25.1 600 (61) 110 2.79 1.09 26.4 700 (61) 110 2.79 1.16 29.5 750 (61) 110 2.79 1.20 30.4 1000 (61) 110 2.79 1.35 34.2 UL 44 UL 854 ICEA S-95-658 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 21 31 15 15 30 44 20 20 44 65 30 30 21 31 15 15 30 44 20 20 44 65 30 30 70 105 40 50 104 156 55 65 157 234 70 85 240 357 95 115 309 460 110 130 379 564 125 150 474 706 145 175 583 869 165 200 755 1124 195 230 867 1291 215 255 1029 1531 240 285 1192 1773 260 310 1352 2012 280 335 1686 2509 320 380 2012 2995 355 420 2332 3470 385 460 2492 3710 400 475 3288 4895 455 545 90°C 15 20 30 15 20 30 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 615 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - RHH dry locations. RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1-866-663-9267 17 ENERGEX® 8000 RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free ACM Aluminum Conductors Applications Construction Specifications Nexans ENERGEX® RHH/RHW-2/ USE-2 conductors may be installed in raceways and conduits or directly buried. They are 90°C, 600 volts per NEC 2008 and NEC 2011 Articles 310 and 338. Conductor: compact stranded AA-8000 series aluminum alloy per ASTM B800 and B801 • Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables • Meets UL 854: (USE-2) Service Entrance Cables • Federal Specification A-A-59544 • ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy • National Electrical Code - NFPA 70 • Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use Type USE-2 conductors are suitable as service entrance conductors which can be installed directly buried in accordance with the NEC. When used as type RHH, the cables are suitable for installation in dry locations. Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation per UL 854 and UL 44. Black only. Surface Print Legend: NEXANS-C 1/0 AWG COMPACT AA-8000-AL USE-2 OR RHH OR RHW-2 600V FOR CT USE SUN RES (UL) LEAD FREE (MFG. DATE) As type RHW-2 and USE-2, they are suitable for installation in both wet and dry locations. Product Features • Cables are UL listed as Type USE-2 • Temperature rating of 90°C dry and wet • Suitable for direct burial • Sunlight resistant • Lead Free • Bare conductors are heat treated after stranding for maximum flexibility Nexans RHH/RHW-2/USE-2 conductors are Lead Free. 1-866-663-9267 18 ENERGEX® 8000 RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free ACM Aluminum Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 6 (7) 60 1.52 0.29 7.4 4 (7) 60 1.52 0.33 8.4 2 (7) 60 1.52 0.39 9.9 1 (18) 80 2.03 0.46 11.7 1/0 (18) 80 2.03 0.50 12.7 2/0 (18) 80 2.03 0.54 13.7 3/0 (18) 80 2.03 0.59 15.0 4/0 (18) 80 2.03 0.64 16.3 250 (35) 95 2.41 0.71 18.0 300 (35) 95 2.41 0.76 19.3 350 (35) 95 2.41 0.81 20.6 400 (35) 95 2.41 0.85 21.6 500 (35) 95 2.41 0.93 23.6 600 (58) 110 2.79 1.07 27.2 700 (58) 110 2.79 1.11 28.2 750 (58) 110 2.79 1.13 28.7 1000(58) 110 2.79 1.28 32.5 UL 44 UL 854 ICEA S-95-658 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 47 70 40 50 66 98 55 65 96 143 75 90 127 189 85 100 152 226 100 120 182 271 115 135 222 330 130 155 271 403 150 180 328 488 170 205 385 573 195 230 435 647 210 250 494 735 225 270 600 893 260 310 721 1073 285 340 828 1232 315 375 899 1338 320 385 1141 1698 375 445 90°C 55 75 100 115 135 150 175 205 230 260 280 305 350 385 425 435 500 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 12 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - RHH dry locations. RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1-866-663-9267 19 ENERGEX® 8000 Mobile Home Feeder XLPE Insulated Cable 600 Volts, 90°C Dry and Wet - Lead Free ACM Aluminum Conductors Applications Construction Specifications Nexans ENERGEX® Mobile Home Feeder is a twisted assembly of RHH / RHW-2 / USE-2 insulated aluminum conductor material (ACM), AA-8000 series alloy conductors. The cable is used as a service cable to feed mobile homes in parks and permanent locations. ENERGEX® 8000 Mobile Home Feeders are designed to be directly buried. The cable is rated at 600 volts and 90°C for use in wet and dry locations in accordance with NEC 2008 and NEC 2011 Article 550.33. Conductor: compact stranded AA-8000 series aluminum alloy per ASTM B800 and B801 • Meets UL 854: Service Entrance Cables • Meets UL 44: Thermoset-Insulated Wires and Cables Nexans Mobile Home Feeder cables are Lead Free. Insulation: solid color-coded sunlight resistant cross-linked polyethylene (XLPE) Assembly: black and red conductors are cabled with the white neutral conductor and green equipment grounding conductor. Surface Print Legend: NEXANS-C 4/0 AWG COMPACT AA8000-AL USE-2 OR RHH OR RHW-2 600V SUN RES LEAD FREE (UL) (MFG. DATE) 1-866-663-9267 20 Product features • Cables are UL listed as Service Entrance Cable • Solid color insulation • Temperature rating of 90°C dry and wet • Sunlight Resistant • Lead Free • Bare conductors are heat treated after stranding for maximum flexibility ENERGEX® 8000 Mobile Home Feeder UL 854 UL 44 XLPE Insulated Cable 600 Volts, 90°C Dry and Wet - Lead Free ACM Aluminum Conductors Cable Construction Insulation Thickness Phase Conductors Insulation Thickness Neutral Conductor Insulation Thickness Cable Grounding Conductor Diameter Approximate Net Cable Weight Ampacity* (Ph 1 + Ph 2 + N + G) mils 2 + 2 + 4 + 6 4/0 + 4/0 + 2/0 + 4 60 1.52 60 1.52 60 1.52 0.94 301 448 100 80 2.03 80 2.03 60 1.521.53 794 1182200 mm mils mm mils mm inches lb/mft kg/km Amps Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. *A mpacities are in accordance with NEC 2008 Table 310.15(B)(6) or NEC 2011 Table 310.15(B)(7) and are based on 90°C conductor temperatures, 20°C ambient earth temperature, earth thermal resistivity Rho=90, cables buried 36” deep, only the phase conductors carrying current and 100% load factor. 1-866-663-9267 21 ENERGEX® PV/RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry and Wet - Lead Free Copper Conductors Applications Construction Product features Nexans ENERGEX® PV solar cables offer exceptional performance, easy installation and long-term reliability for DC connections. They link photovoltaic panels on rooftops or solar farms, and also connect them to the array box (if one exists), and to the inverter which transforms DC solar energy into usable AC electricity. These cables have a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, and are certified as UL type PV. Conductor: Stranded annealed soft bare copper conductors per ASTM B8 and B787 • Cables are UL listed as Type PV • Cables are UL listed as Type USE-2 • Temperature rating of 90°C dry and wet • Suitable for direct burial • Sunlight resistant in black and colors • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • LEAD FREE Nexans ENERGEX® PV/RHH/RHW-2/ USE-2 cables may be installed indoors or outdoors, in raceways and conduits, or directly buried. They are 90°C, 600 V per NEC Articles 310 and 338, and suitable for use in a photovoltaic system per NEC Article 690. Type PV cables are for use on the DC side of a photovoltaic system, suitable for installation in both wet and dry locations, and may be exposed to sunlight. Type USE-2 cables are suitable as service entrance cables, which can be installed directly buried in accordance with the NEC. When used as type RHH, the cables are suitable for installation in dry locations. Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation in black or colors per UL 854 and UL 44 Surface Print Legend: (mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) (UL) RHW-2 OR USE-2 OR PV WIRE 600V 90C WET OR DRY SR DIR BUR LEAD FREE Specifications • Meets UL Subject 4703 (PV) Photovoltaic Wire • Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables • Meets UL 854 (USE-2) Service Entrance Cables • Federal Specification A-A-59544 • National Electrical Code - NFPA 70 • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2) As type RHW-2 and USE-2, they are suitable for installation in both wet and dry locations. Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE. 1-866-663-9267 22 Options • Class C stranding available ENERGEX® PV/RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Copper Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 8 (7) 75 1.91 0.29 7.5 6 (7) 75 1.91 0.33 8.4 4 (7) 75 1.91 0.38 9.6 2 (7) 75 1.91 0.44 11.0 1 (19) 95 2.41 0.51 12.9 1/0 (19) 95 2.41 0.55 13.9 2/0 (19) 95 2.41 0.59 15.0 3/0 (19) 95 2.41 0.64 16.2 4/0 (19) 95 2.41 0.69 17.6 250 (37) 110 2.79 0.77 19.5 300 (37) 110 2.79 0.82 20.8 350 (37) 110 2.79 0.87 22.0 400 (37) 110 2.79 0.91 23.1 500 (37) 110 2.79 0.99 25.1 600 (61) 125 3.18 1.10 27.8 700 (61) 125 3.18 1.19 30.2 750 (61) 125 3.18 1.22 31.0 1000 (61) 125 3.18 1.37 34.8 UL 44 UL 854 UL 854 subject 4703 ICEA S-95-658 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 76 113 40 50 110 164 55 65 164 244 70 85 248 369 95 115 316 470 110 130 390 580 125 150 481 716 145 175 596 887 165 200 740 1101 195 230 884 1316 215 255 1048 1560 240 285 1207 1796 260 310 1375 2046 280 335 1700 2530 320 380 2048 3048 355 420 2378 3539 385 460 2542 3783 400 475 3347 4981 455 545 90°C 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 615 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes. Allowable ampacities shown are for general use as specified by the NEC, Section 310.15. For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC. Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. 1-866-663-9267 23 ENERGEX® 8000 PV/RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry and Wet - Lead Free Aluminum Conductors Applications Construction Product features Nexans ENERGEX® PV solar cables offer exceptional performance, easy installation and long-term reliability for DC connections. They link photovoltaic panels on rooftops or solar farms, and also connect them to the array box (if one exists), and to the inverter which transforms DC solar energy into usable AC electricity. These cables have a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, and are certified as UL type PV. Conductor: Compact stranded AA8000 series aluminum alloy (ACM) per ASTM B801 or B836 • Cables are UL listed as Type PV • Cables are UL listed as Type USE-2 • Temperature rating of 90°C dry and wet • Suitable for direct burial • Sunlight resistant in black and colors • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • LEAD FREE Nexans ENERGEX® PV/RHH/RHW-2/ USE-2 cables may be installed indoors or outdoors, in raceways and conduits, or directly buried. They are 90ºC, 600 V per NEC Articles 310 and 338, and suitable for use in a photovoltaic system per NEC Article 690. Type PV cables are for use on the DC side of a photovoltaic system, suitable for installation in both wet and dry locations, and may be exposed to sunlight. Type USE-2 cables are suitable as service entrance cables, which can be installed directly buried in accordance with the NEC. When used as type RHH, the cables are suitable for installation in dry locations. Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation in black or colors per UL 854 and UL 44 Surface Print Legend: (mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) CPT ACM ALUM (UL) RHW-2 OR USE-2 OR PV WIRE 600V 90C WET OR DRY SR DIR BUR LEAD FREE Specifications • Meets UL Subject 4703 (PV) Photovoltaic Wire • Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables • Meets UL 854 (USE-2) Service Entrance Cables • Federal Specification A-A-59544 • National Electrical Code - NFPA 70 • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2) As type RHW-2 and USE-2, they are suitable for installation in both wet and dry locations. Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE. 1-866-663-9267 24 Options • Class C stranding available ENERGEX® 8000 PV/RHH/RHW-2/USE-2 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Aluminum Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 6 (7) 75 1.91 0.32 8.2 4 (7) 75 1.91 0.37 9.3 2 (6) 75 1.91 0.42 10.7 1 (8) 95 2.41 0.49 12.5 1/0 (10) 95 2.41 0.53 13.4 2/0 (12) 95 2.41 0.57 14.5 3/0 (16) 95 2.41 0.62 15.6 4/0 (18) 95 2.41 0.67 17.0 250 (35) 110 2.79 0.74 18.9 300 (35) 110 2.79 0.79 20.2 350 (35) 110 2.79 0.84 21.3 400 (35) 110 2.79 0.88 22.4 500 (35) 110 2.79 0.96 24.4 600 (58) 125 3.18 1.07 27.1 750 (58) 125 3.18 1.16 29.5 1000 (58) 125 3.18 1.31 33.4 UL 44 UL 854 UL 854 subject 4703 ICEA S-59-658 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 52 77 40 50 72 107 55 65 102 151 75 90 135 201 85 100 161 240 100 120 193 288 115 135 231 344 130 155 282 420 150 180 344 512 170 205 401 596 190 230 456 679 210 250 512 762 225 270 621 925 260 310 755 1124 285 340 918 1367 320 385 1195 1778 375 445 90°C 60 75 100 115 135 150 175 205 230 255 280 305 350 385 435 500 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes. Allowable ampacities shown are for general use as specified by the NEC, Section 310.15. For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC. Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. 1-866-663-9267 25 ENERGEX® PV/RHH/RHW-2/USE-2 XLPE Insulated Cable 2 kV, 90°C Dry and Wet - Lead Free Copper Conductors Applications Construction Product features Nexans ENERGEX® PV solar cables offer exceptional performance, easy installation and long-term reliability for DC connections. They link photovoltaic panels on rooftops or solar farms, and also connect them to the array box (if one exists), and to the inverter which transforms DC solar energy into usable AC electricity. These cables have a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, and are certified as UL type PV. Conductor: Stranded annealed soft bare copper conductors per ASTM B8 and B787 • Cables are UL listed as Type PV • Cables are UL listed as Type USE-2 • Temperature rating of 90°C dry and wet • Suitable for direct burial • Sunlight resistant in black and colors • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • LEAD FREE Nexans ENERGEX® PV/RHH/RHW-2/ USE-2 cables may be installed indoors or outdoors, in raceways and conduits, or directly buried. They are 90ºC, 2 kV per NEC Articles 310 and 338, and suitable for use in a photovoltaic system per NEC Article 690. Type PV cables are for use on the DC side of a photovoltaic system, suitable for installation in both wet and dry locations, and may be exposed to sunlight. Type USE-2 cables are suitable as service entrance cables, which can be installed directly buried in accordance with the NEC. When used as type RHH, the cables are suitable for installation in dry locations. Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation in black or colors per UL 854 and UL 44 Surface Print Legend: (mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) (UL) USE-2 600V OR RHW-2 OR PV WIRE 2000V 90C WET OR DRY SR DIR BUR LEAD FREE Specifications • Meets UL Subject 4703 (PV) Photovoltaic Wire • Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables • Meets UL 854 (USE-2) Service Entrance Cables • Federal Specification A-A-59544 • National Electrical Code - NFPA 70 • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2) As type RHW-2 and USE-2, they are suitable for installation in both wet and dry locations. Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE. 1-866-663-9267 26 Options • Class C stranding available ENERGEX® PV/RHH/RHW-2/USE-2 UL 44 UL 854 UL 854 subject 4703 ICEA S-95-658 XLPE Insulated Cable 2 kV, 90°C Dry or Wet - Lead Free Copper Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 8 (7) 85 2.16 0.31 7.9 6 (7) 85 2.16 0.35 8.8 4 (7) 85 2.16 0.40 10.0 2 (7) 85 2.16 0.46 11.5 1 (19) 105 2.67 0.53 13.3 1/0 (19) 105 2.67 0.57 14.3 2/0 (19) 105 2.67 0.61 15.4 3/0 (19) 105 2.67 0.66 16.6 4/0 (19) 105 2.67 0.71 18.0 250 (37) 120 3.05 0.79 19.9 300 (37) 120 3.05 0.84 21.6 350 (37) 120 3.05 0.89 22.4 400 (37) 120 3.05 0.93 23.5 500 (37) 120 3.05 1.10 25.6 600 (61) 135 3.43 1.12 28.2 700 (61) 135 3.43 1.21 29.9 750 (61) 135 3.43 1.24 30.7 1000 (61) 135 3.43 1.39 35.2 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 80 119 40 50 115 171 55 65 169 251 70 85 253 377 95 115 323 481 110 130 398 592 125 150 489 728 145 175 605 900 165 200 750 1116 195 230 896 1333 215 255 1059 1576 240 285 1220 1816 260 310 1388 2066 280 335 1714 2551 320 380 2064 3072 355 420 2395 3564 385 460 2560 3810 400 475 3367 5011 455 545 90°C 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 615 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through 1 AWG. 75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes. Allowable ampacities shown are for general use as specified by the NEC, Section 310.15. For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC. Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. 1-866-663-9267 27 ENERGEX® 8000 PV/RHH/RHW-2/USE-2 XLPE Insulated Cable 2 kV, 90°C Dry and Wet - Lead Free Aluminum Conductors Applications Construction Product features Nexans ENERGEX® PV solar cables offer exceptional performance, easy installation and long-term reliability for DC connections. They link photovoltaic panels on rooftops or solar farms, and also connect them to the array box (if one exists), and to the inverter which transforms DC solar energy into usable AC electricity. These cables have a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, and are certified as UL type PV. Conductor: Compact stranded AA8000 series aluminum alloy (ACM) per ASTM B801 or B836 • Cables are UL listed as Type PV • Cables are UL listed as Type USE-2 • Temperature rating of 90°C dry and wet • Suitable for direct burial • Sunlight resistant in black and colors • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • LEAD FREE Nexans ENERGEX® PV/RHH/RHW-2/ USE-2 cables may be installed indoors or outdoors, in raceways and conduits, or directly buried. They are 90ºC, 2 kV per NEC Articles 310 and 338, and suitable for use in a photovoltaic system per NEC Article 690. Type PV cables are for use on the DC side of a photovoltaic system, suitable for installation in both wet and dry locations, and may be exposed to sunlight. Type USE-2 cables are suitable as service entrance cables, which can be installed directly buried in accordance with the NEC. When used as type RHH, the cables are suitable for installation in dry locations. Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation in black or colors per UL 854 and UL 44. Surface Print Legend: (mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) CPT ACM ALUM (UL) USE-2 600V OR RHW-2 OR PV WIRE 2000V 90C WET OR DRY SR DIR BUR LEAD FREE Specifications • Meets UL Subject 4703 (PV) Photovoltaic Wire • Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables • Meets UL 854 (USE-2) Service Entrance Cables • Federal Specification A-A-59544 • National Electrical Code - NFPA 70 • Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated for CT use • UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2) As type RHW-2 and USE-2, they are suitable for installation in both wet and dry locations. Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE. 1-866-663-9267 28 Options • Class C stranding available ENERGEX® 8000 PV/RHH/RHW-2/USE-2 UL 44 UL 854 UL 854 subject 4703 ICEA S-95-658 XLPE Insulated Cable 2 kV, 90°C Dry or Wet - Lead Free Aluminum Conductors Conductor Insulation Thickness Nominal Diameter Size AWG/kcmilmils mm inches mm 6 (7) 85 2.16 0.34 8.6 4 (7) 85 2.16 0.39 9.9 2 (6) 85 2.16 0.44 11.2 1 (8) 105 2.67 0.51 13.0 1/0 (10) 105 2.67 0.55 14.0 2/0 (12) 105 2.67 0.59 15.0 3/0 (16) 105 2.67 0.64 16.3 4/0 (18) 105 2.67 0.69 17.5 250 (35) 120 3.05 0.76 19.3 300 (35) 120 3.05 0.81 20.6 350 (35) 120 3.05 0.86 21.8 400 (35) 120 3.05 0.90 22.9 500 (35) 120 3.05 0.98 24.9 600 (58) 135 3.43 1.09 27.7 750 (58) 135 3.43 1.18 30.0 1000 (58) 135 3.43 1.33 33.8 Approximate Net Ampacity* Cable Weight (Amps) lb/kft kg/km 60°C 75°C 57 84 40 50 77 115 55 65 108 160 75 90 142 212 85 100 169 251 100 120 202 300 115 135 240 357 130 155 292 434 150 180 354 528 170 205 412 613 190 230 468 697 210 250 525 781 225 270 607 904 260 310 771 1147 285 340 935 1391 320 385 1214 1806 375 445 90°C 60 75 100 115 135 150 175 205 230 255 280 305 350 385 435 500 *60°C - W hen terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 8 through 1 AWG. 75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - RHH dry locations. PV, RHW-2 and USE-2 wet or dry locations. For ampacity derating purposes. Allowable ampacities shown are for general use as specified by the NEC, Section 310.15. For conductors installed in conduit on a rooftop, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC. Note: Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. 1-866-663-9267 29 ENERGEX® MC 120 Aluminum Armored MC Cable UL Type MC, 600 Volts, 90°C dry - Lead Free Copper Conductors Applications ENERGEX® MC 120 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC 2008 and NEC 2011 Article 330. They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645. These cables may be installed in approved raceways and as open runs of cable on a messenger. They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300.22(C) ONLY. Nexans MC 120 cable is Lead Free and RoHS compliant. Construction Conductor: Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copper per ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger. Insulation: Colored PVC/Nylon type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test for sizes 14 to 1 AWG. Colored crosslinked polyethylene type XHHW-2 per UL 44 for sizes 1/0 AWG and larger. Ground Wire: bare copper, sized in accordance with NEC 2008 and NEC 2011 and UL, with green THHN insulation (XHHW-2 for 1/0 and larger). Assembly: conductors are cabled with grounding wires. A marker tape/core protection tape combination assembles the core in an essentially round configuration. Armor: interlocking aluminum tape armor applied directly over the core. Marker Tape Print: Nexans Type MC 600 Volt For CT Use (size) THHN (UL) E-47409 LEAD FREE (MFG DATE). Specifications • Meets UL 44: Thermoset Insulated Wires and Cables (1/0 AWG and larger) • Meets UL 83: Thermoplastic Insulated Wires and Cables (14 to 1 AWG) • Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG) • Meets UL 1569: Metal Clad Cables • Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords • Designated Type MC per NEC 2008 and NEC 2011 Article 330 1-866-663-9267 30 Product features • Cables are UL listed as Type MC, 600V •UL listed insulated conductors • Fire Wall Penetration rated depending on type of installation and fire-stop system used • UL listed for use in cable trays per NEC 2008 and NEC 2011 Article 330.10(A)(6) • UL listed for use in Class I, Div. 2 per NEC 2008 and NEC 2011 Article 501.10(B)(1)(6), Class II, Div.2 per NEC 2008 and NEC 2011 Article 502.10(B)(1)(6) and Class III, Div. 1 & 2 per NEC 2008 and NEC 2011 Articles 503.10(A) and (B) with approved termination fittings. • Temperature rating of 90°C dry • Excellent mechanical & physical properties • Lightweight aluminum armor • Conductor sizes larger than 1/0 AWG • Lead Free and RoHS compliant. Options The following constructions can be provided on special orders: • Special conductor counts • XHHW-2 insulation on sizes 14 to 1 AWG • Conductor sizes larger than 1/0 AWG ENERGEX® MC 120 UL 44 UL 83 UL 1569 Aluminum Armored MC Cable UL Type MC, 600 Volts, 90°C Dry - Lead Free Copper Conductors Number of Conductor Ground Circuit Conductor Nominal Diameter Conductors Size Size Color Code over Armor AWG AWG inches mm 2 14 (1) 14 (1) white/black 0.45 11.3 3 14 (1) 14 (1) white/black/red 0.47 12.0 4 14 (1) 14 (1) white/black/red/blue 0.51 12.8 2 12 (1) 12 (1) white/black 0.48 12.3 3 12 (1) 12 (1) white/black/red 0.51 13.1 4 12 (1) 12 (1) white/black/red/blue 0.55 14.0 2 10 (1) 10 (1) white/black 0.55 14.0 3 10 (1) 10 (1) white/black/red 0.59 14.9 4 10 (1) 10 (1) white/black/red/blue 0.64 16.3 2 12 (19) 12 (19) white/black 0.48 12.3 3 12 (19) 12 (19) white/black/red 0.51 13.1 4 12 (19) 12 (19) white/black/red/blue 0.55 14.0 2 10 (19) 10 (19) white/black 0.55 14.0 3 10 (19) 10 (19) white/black/red 0.58 14.9 4 10 (19) 10 (19) white/black/red/blue 0.64 16.3 2 8 (19) 10 (19) white/black 0.66 16.7 3 8 (19) 10 (19) white/black/red 0.71 18.1 4 8 (19) 10 (19) white/black/red/blue 0.78 19.7 2 6 (19) 8 (19) white/black 0.74 18.9 3 6 (19) 8 (19) white/black/red 0.81 20.6 4 6 (19) 8 (19) white/black/red/blue 0.89 22.5 3 4 (19) 8 (19) white/black/red 0.94 23.9 4 4 (19) 8 (19) white/black/red/blue 1.06 26.8 3 3 (19) 6 (19) white/black/red 1.02 25.8 4 3 (19) 6 (19) white/black/red/blue 1.13 28.7 3 2 (19) 6 (19) white/black/red 1.09 27.7 4 2 (19) 6 (19) white/black/red/blue 1.20 30.5 3 1 (19) 6 (19) white/black/red 1.20 30.6 3 1/0 (19) 6 (19) white/black/red 1.27 32.3 Approximate Net Cable Weight lb/kft kg/km 87 129 106 158 123 183 118 176 145 216 173 257 164 244 207 308 244 363 118 176 145 216 173 257 164 244 207 308 244 363 229 341 300 446 371 552 330 491 435 647 541 805 624 929 855 1272 795 1183 1049 1561 966 1438 1245 1853 1427 2124 1585 2359 Ampacity* (Amps) 60°C 75°C 90°C 15 15 15 15 15 15 151151 151 20 20 20 20 20 20 201201 201 30 30 30 30 30 30 301 301 301 20 20 20 20 20 20 201 201201 30 30 30 30 30 30 301 301301 40 50 55 40 50 55 401 501 551 55 65 75 55 65 75 651 751 551 70 85 95 851 951 701 85 100 110 1001 1101 851 95 115 130 1151 1301 951 110 130 150 125 150 170 Bend Radius: 7 × overall diameter *60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. Ampacities for cables having more than three conductors have been derated per NEC 2008 Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3)(a). • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G). 1 Where the 4th conductor is the neutral of a balanced 3 phase system. 1-866-663-9267 31 ENERGEX® MC 277 Aluminum Armored MC Cable 277 Volts and Special Color Codes UL Type MC, 600 Volts, 90°C Dry - Lead Free Copper Conductors Applications ENERGEX® MC 277 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC 2008 and NEC 2011 Article 330. They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645. These cables may be installed in approved raceways and as open runs of cable on a messenger. They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300.22(C) ONLY. Nexans MC 277 cable is Lead Free and RoHS compliant. Construction Conductor: Solid soft bare, annealed copper per ASTM B3. Stranded soft bare annealed copper per ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger. Ground Wire: bare copper, sized in accordance with NEC 2008 and NEC 2011 and UL, with green THHN insulation. Assembly: conductors are cabled with grounding wires. A marker tape/core protection tape combination assembles the core in an essentially round configuration. Armor: interlocking aluminum tape armor applied directly over the core. Marker Tape Print: Nexans Type MC 600 Volt For CT Use (size) THHN (UL) E-47409 LEAD FREE (MFG DATE). Specifications • Meets UL 83: Thermoplastic Insulated Wires and Cables • Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG) • Meets UL 1569: Metal Clad Cables • Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords • Designated Type MC per NEC 2008 and NEC 2011 Article 330 Insulation: Colored PVC/Nylon type THHN per UL 83, flame retardant, meeting UL VW-1 flame test. 1-866-663-9267 32 Product Features • Cables are UL listed as Type MC, 600V • UL listed insulated conductors • Fire Wall Penetration rated depending on type of installation and fire-stop system used • UL listed for use in cable trays per NEC 2008 and NEC 2011 Article 330.10(A)(6) • For use in Class I, Div. 2 per NEC 2008 and NEC 2011 Article 501.10(B)(1)(6), Class II, Div. 2 per NEC 2008 and NEC 2011 Article 502.10(B)(1)(6) and Class III, Div. 1 & 2 per NEC 2008 and NEC 2011 Articles 503.10(A) and (B) with approved termination fittings. • Temperature rating of 90°C dry • Excellent mechanical & physical properties • Lightweight aluminum armor • Lead Free and RoHS compliant. Options The following constructions can be provided on special orders: • Special conductor counts • XHHW-2 insulation ENERGEX® MC 277 UL 83 UL 1569 Aluminum Armored MC Cable 277 Volts and Special Color Codes UL Type MC, 600 Volts, 90°C Dry - Lead Free Copper Conductors Number of Conductor Ground Circuit Conductor Nominal DiameterApproximate Net Ampacity* Conductors Size Size Color Code over Armor Cable Weight (Amps) AWG AWG inches mm lb/kft kg/km60°C 75°C 90°C 2 12 (1) 12 (1) brown/gray 0.48 12.3 118 176 20 20 20 2 12 (1) 12 (1) orange/gray 0.48 12.3 118 176 20 20 20 2 12 (1) 12 (1) yellow/gray 0.48 12.3 118 176 20 20 20 2 12 (1) 12 (1) purple/gray 0.48 12.3 118 176 20 20 20 2 12 (1) 12 (1) brown/yellow 0.48 12.3 118 176 20 20 20 2 12 (1) 12 (1) red/white 0.48 12.3 118 176 20 20 20 2 12 (1) 12 (1) blue/white 0.48 12.3 118 176 20 20 20 3 12 (1) 12 (1) brown/orange/gray 0.51 13.1 145 216 20 20 20 3 12 (1) 12 (1) brown/purple/gray 0.51 13.1 145 216 20 20 20 3 12 (1) 12 (1) purple/yellow/gray 0.51 13.1 145 216 20 20 20 3 12 (1) 12 (1) brown/yellow/gray 0.51 13.1 145 216 20 20 20 3 12 (1) 12 (1) red/blue/white 0.51 13.1 145 216 20 20 20 3 12 (1) 12 (1) black/blue/white 0.51 13.1 145 216 20 20 20 201 201 4 12 (1) 12 (1) brown/orange/yellow/gray 0.55 14.0 173 257 201 4 12 (1) 12 (1) brown/purple/yellow/gray 0.55 14.0 173 257 201 201 201 2 10 (1) 10 (1) brown/gray 0.55 14.0 164 244 30 30 30 3 10 (1) 10 (1) brown/orange/gray 0.59 14.9 207 308 30 30 30 301 301 4 10 (1) 10 (1) brown/orange/yellow/gray 0.64 16.3 244 363 301 2 12 (19) 12 (19) brown/gray 0.48 12.3 118 176 20 20 20 3 12 (19) 12 (19) brown/orange/gray 0.51 13.1 145 216 20 20 20 201 201 4 12 (19) 12 (19) brown/orange/yellow/gray 0.55 14.0 173 257 201 2 10 (19) 10 (19) brown/gray 0.55 14.0 164 244 30 30 30 3 10 (19) 10 (19) brown/orange/gray 0.59 14.9 207 308 30 30 30 301 301 4 10 (19) 10 (19) brown/orange/yellow/gray 0.64 16.3 244 363 301 3 8 (19) 10 (19) brown/orange/gray 0.71 18.1 300 446 40 50 55 3 6 (19) 8 (19) brown/orange/gray 0.81 20.6 435 647 55 65 75 Bend Radius: 7 × overall diameter *60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities are in accordance with NEC 2008 and NEC 2011 Articles 310.15 and 334.80, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature. Ampacities for cables having more than three conductors have been derated per NEC 2008 Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3) (a). • For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B) (16). • NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction 1 Where the 4th conductor is the neutral of a balanced 3 phase system. 1-866-663-9267 33 ENERGEX® 8000 SER Service Entrance Type SE, Style R XLPE Insulated Cable - Lead Free 600 Volts, 90°C Dry or Wet ACM Aluminum Conductors Applications Nexans ENERGEX® SER is type SE, Style R cable, used as an above ground service entrance cable, a panel feeder and in branch circuits. The cable is rated at 600 volts and 90°C for use in wet and dry locations in accordance with NEC 2008 and NEC 2011 Article 338. Nexans SER cables are lead free and RoHS compliant. Construction Conductor: Compact stranded AA8000 series aluminum alloy per ASTM B800 and B801 (8 AWG is solid). Assembly: Insulated conductors are cabled with the bare ground wire. A flame retardant fiberglass reinforced binder tape assembles the core in a circular configuration. Jacket: Sunlight resistant, lead free, flame retardant, gray polyvinyl chloride (PVC) material. Conductor Identification: Color coded: Black, White and Red Surface Print Legend: NEXANS-C ENERGEX 8000 TYPE SE - STYLE: R 600V XHHW AA-8000AL 3/C 4/0 AWG + 1/C 2/0 AWG (UL) E-49786 SUN RES LEAD FREE (MFG. DATE) Insulation: color coded cross-linked polyethylene (XLPE). 1-866-663-9267 34 Specifications • Meets UL 854: Service Entrance Cables Product features • Cables are UL listed as Type SE, Style R • Temperature rating of 90°C dry and wet • Sunlight Resistant • Moisture Resistant • Lead Free and RoHS compliant • Bare conductors are heat treated after stranding for maximum flexibility ENERGEX® 8000 SER UL 854 Service Entrance Type SE, Style R XLPE Insulated Cable - Lead Free 600 Volts, 90°C Dry or Wet ACM Aluminum Conductors 3 Insulated Conductors with Bare Ground Insulated Insulation Thickness Bare Jacket Thickness Nominal Diameter Approximate Net Ampacity* Conductor Neutral over Jacket Cable Weight (Amps) Size Size AWGmils mmAWGmils mm inchesmm lb/kft kg/km Dwelling 60°C 75°C 90°C 8 (1) 6 (7) 4 (7) 2 (7) 1 (18) 1/0 (18) 2/0 (18) 3/0 (18) 4/0 (18) 45 45 45 45 55 55 55 55 55 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 8 (1) 6 (7) 6 (7) 4 (7) 2 (7) 2 (7) 1 (18) 1/0 (18) 2/0 (18) 30 30 30 30 30 30 30 30 30 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.56 0.67 0.74 0.88 0.97 1.05 1.14 1.22 1.32 14.2 17.0 18.8 22.4 24.6 26.7 29.0 31.0 33.5 130 193 185 275 243 362 350 521 451 671 553 823 696 1036 780 1161 956 1423 – – – 100 110 125 150 175 200 30 40 55 75 85 100 115 130 150 40 50 65 90 100 120 135 155 180 45 55 75 100 115 135 150 175 205 *60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. • Ampacities for 8, 6 and 4 AWG are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for aluminum conductors in a raceway or direct buried at 30°C ambient temperature, and a conductor temperature of 90°C. • Ampacities for 2 AWG and larger are in accordance with NEC 2008 Table 310.15(B)(6) or NEC 2011 Table 310.15(B)(7) for aluminum conductors. 1-866-663-9267 35 ENERGEX® 8000 SEU Service Entrance Type SE, Style U XLPE Insulated Cable - Lead Free 600 Volts, 90°C Dry or Wet ACM Aluminum Conductors Applications Nexans ENERGEX® SEU is type SE, Style U, cable used as an above ground service entrance cable, a panel feeder and in branch circuits. The cable is rated at 600 volts and 90°C for use in wet and dry locations in accordance with NEC 2008 and NEC 2011 Article 338. Nexans SEU cables are Lead Free and RoHS compliant. Construction Conductor: Compact stranded AA8000 series aluminum alloy per ASTM B800 and B801 (8 AWG is solid). Insulation: color coded cross-linked polyethylene (XLPE). Insulated Assembly: Insulated conductors are laid in a parallel configuration. Solid bare wires are applied concentrically over the conductors forming the neutral conductor. A flame retardant fiberglass reinforced binder tape assembles the core in a tight configuration. Jacket: Sunlight resistant, lead free, flame retardant, gray, polyvinyl chloride (PVC) material. Conductor Identification: Color coded: Black and Red Surface Print Legend: NEXANS-C ENERGEX 8000 TYPE SE STYLE: U 600V AA-8000-AL 2/C 4/0 AWG + 1/C 2/0 AWG (UL) E-49786 SUN RES LEAD FREE (MFG. DATE) 1-866-663-9267 36 Specifications • Meets UL 854: Service Entrance Cables Product features • Cables are UL listed as Type SE, Style U • Temperature rating of 90°C dry and wet • Sunlight Resistant • Moisture Resistant • Lead Free and RoHS compliant • Bare conductors are heat treated after stranding for maximum flexibility ENERGEX® 8000 SEU UL 854 Service Entrance Type SE, Style U XLPE Insulated Cable - Lead Free 600 Volts, 90°C Dry or Wet ACM Aluminum Conductors 2 Insulated Conductors with Bare Concentric Neutral Insulated Insulation Bare Jacket Thickness Nominal Dimension Approximate Net Ampacity* Conductor Thickness Neutral over Jacket Cable Weight (Amps) SizeSize AWG mils mm AWG mils mm inches mm lb/kft kg/km Dwelling60°C 75°C 90°C 8 (1) 6 (7) 4 (7) 2 (7) 2 (7) 1 (18) 1/0 (18) 2/0 (18) 2/0 (18) 3/0 (18) 4/0 (18) 4/0 (18) 45 45 45 45 45 55 55 55 55 55 55 55 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 8 6 6 4 2 1 1/0 1 2/0 3/0 2/0 4/0 30 30 30 30 30 30 30 30 30 30 30 30 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.40 x 0.26 0.46 x 0.73 0.51 x 0.82 0.56 x 0.93 0.56 x 0.93 0.64 x 1.05 0.67 x 1.12 0.73 x 1.22 0.77 x 1.26 0.80 x 1.35 0.86 x 1.45 0.90 x 1.49 10.2 x 6.6 11.7 x 18.5 13.0 x 20.8 14.2 x 23.6 14.2 x 23.6 16.3 x 26.7 17.0 x 28.5 18.5 x 31.0 19.6 x 32.0 20.3 x 34.3 21.8 x 36.8 22.9 x 37.9 105 156 147 216 188 200 265 394 286 426 350 521 425 632 487 725 527 784 620 923 697 1037 784 1167 – – – 100 100 110 125 150 150 175 200 200 30 40 55 75 75 85 100 115 115 130 150 150 40 50 65 90 90 100 120 135 135 155 180 180 45 55 75 100 100 115 135 150 150 175 205 205 *60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. Notes: •W here stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. •D welling ampacities are far 120/240-Volt, 3-Wire, single-phase dwelling services and feeders in accordance with NEC 2008 Table 310.15(8)(6) or NEC 2011 Table 310.15(B)(7) for aluminum conductors. •6 0°C, 75°C and 90°C ampacities are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for aluminum conductors in a raceway or direct buried at 30°C ambient temperature, and a conductor temperature of 90°C. 1-866-663-9267 37 Underground Secondary Distribution Cables XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Aluminum Conductors Applications Underground Secondary Distribution Cables are twisted assemblies of alloy 1350 aluminum conductors insulated with cross-linked polyethylene. They are used in various underground applications in secondary distribution circuits. Nexans Underground Secondary Distribution Cables are Lead Free and RoHS compliant. Construction Conductor: Compressed Class B stranded, 1350 series aluminum alloy. Insulation: black cross-linked polyethylene (XLPE). Conductor Identification: Phase conductors: Black Neutral: Black with three extruded yellow stripes. Surface Print Legend: NEXANS-WE 4/0 AWG ALUM 600V XLPE (PHASE IDENTIFICATION FOR QUADRUPLEX CONSTRUCTIONS) SUN RES LEAD FREE (MFG DATE) Specifications • Meets UL 854: Service Entrance Cables • Meets ICEA S-105-692 Standard for 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables Assembly: Phase conductors and neutral conductor are cabled together to form a twisted assembly. 1-866-663-9267 38 Product features • Available as single conductors, or as a cabled assembly: Duplex, Triplex or Quadruplex • Temperature rating of 90°C dry and wet, 130°C for emergency overloads and 250°C under short circuit conditions • Suitable for direct burial or installation in duct (such as a pole riser) • Sunlight Resistant • Lead Free and RoHS compliant • UL listing and marking for Type USE-2 Underground Secondary Distribution Cables UL 854 ICEA S-105-692 XLPE Insulated Cable 600 Volts, 90°C Dry or Wet - Lead Free Aluminum Conductors Duplex 1 Insulated Conductor with Insulated Neutral Phase Conductor Neutral Conductor Cable Code word Size InsulationInsulation Nominal Approximate (Black Neutral)1 AWG/kcmil Thickness Size Thickness Diameter Net Weight Ampacity* (ICEA) (# of mils mm (# of mils mm inches mm lb / kg / Direct Pole Riser wires)wires) 1000 ft km Buried2Conduit3 CLAFLIN/XLP 6 (7) 60 1.52 6 (7) 60 1.52 0.60 15.24 91 135 97 47 Triplex 2 Insulated Conductors with Insulated Neutral Code word (Black Neutral)1 ERSKINE/XLP VASSAR/XLP STEPHENS/XLP RAMAPO/XLP BRENAU/XLP CONVERSE/XLP SWEETBRIAR/XLP MONMOUTH/XLP PRATT/XLP WESLEYAN/XLP Phase Conductor Neutral Conductor Cable Size Insulation Size Insulation Nominal Approximate AWG/kcmil Thickness (# of Thickness Diameter Net Weight Ampacity* (ICEA) (# of mils mm wires) mils mm inches mm lb / kg / Direct Pole Riser wires) 1000 ft km Buried2 Conduit3 6 (7) 4 (7) 2 (7) 2 (7) 1/0 (19) 2/0 (19) 4/0 (19) 4/0 (19) 250 (37) 350 (37) 60 60 60 60 80 80 80 80 95 95 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.41 2.41 6 (7) 4 (7) 4 (7) 2 (7) 2 (7) 1 (19) 2/0 (19) 4/0 (19) 3/0 (19) 4/0 (19) 60 60 60 60 60 80 80 80 80 80 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 0.65 0.75 0.83 0.88 1.05 1.17 1.38 1.46 1.53 1.72 16.5 143 19.1 202 21.1 262 22.4 292 26.7 407 29.7 504 35.1 741 37.1 831 38.9 890 43.7 1160 213 301 390 435 606 750 1103 1237 1324 1726 97 123 160 160 205 233 301 301 329 395 47 60 82 82 112 132 185 185 199 248 Quadruplex 3 Insulated Conductors with Insulated Neutral Code word (Black Neutral)1 DYKE/XLP WAKE FOREST/XLP SLIPPERY ROCK/XLP Phase Conductor Neutral Conductor Cable Size Insulation Size Insulation Nominal Approximate AWG/kcmil Thickness (# of Thickness Diameter Net Weight Ampacity* (ICEA) (# of mils mm wires) mils mm inches mm lb / kg / Direct Pole Riser wires) 1000 ft km Buried2 Conduit3 2 (7) 60 4/0 (19) 80 350 (37) 95 1.52 2.03 2.41 4 (7) 2/0 (19) 4/0 (19) 60 80 80 1.52 0.94 23.9 332 494 2.03 1.57 39.9 959 1427 2.03 1.95 49.5 1529 2275 160 301 395 82 185 248 *60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. 75°C - W hen terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - Wet or dry locations. For ampacity derating purposes. These ampacity values are not to be used for NEC. Notes: • Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances. 1 For yellow stripes on neutral, add “EYS” to black neutral code word (eg. “Erskine/xLP/EYS”). 2 Non-NEC applications are based on the following installation parameters: 90°C conductor temperature, 20°C earth ambient temperature, earth thermal resistivity (RHO) of 90°C cm / W, 36 inch depth of burial and 100% load factor 3 Non-NEC applications for pole riser conduit ampacities are based on the following installation parameters: 90°C conductor temperature, 40°C ambient air temperature, no sun (shaded), no wind, non-metallic duct and 100% load factor 1-866-663-9267 39 END-USER WARRANTY WARRANTY LIMITATIONS Nexans warrants to the end-user that its cable will meet Nexans’ published specifications for the cable and be otherwise free from defects in material and workmanship for a period of one (1) year after the in-service date, or one (1) year and six (6) months from the original date of shipment from the manufacturer, whichever occurs first (the “Warranty Period”). If during the Warranty Period, end-user believes that there is a breach of warranty, end-user must provide Nexans within ten (10) days with written notification setting forth the nature of the claimed breach. Nexans shall promptly investigate such claimed breach and shall, after its investigation, either (i) provide information to end-user confirming that no breach of warranty has in fact occurred; or (ii) advise end-user of Nexans’ planned corrective action. If a breach of warranty has in fact occurred, Nexans shall, at its election, promptly repair or replace the defective cable at no cost to end-user. All costs incidental to such corrective action including, but not limited to removal, disassembly, reinstallation and reconstruction shall be borne by the enduser and in no event shall Nexans be liable for such costs. Furthermore, Nexans will not be responsible for any damage or repairs to, or replacement of, adjacent or connected equipment to which the cable may supply electrical power, or from which it may take electrical power, or with which it may, in any manner, be connected. All warranty repairs or replacements made during the Warranty Period shall be warranted for the balance of the Warranty Period. This warranty does not cover the repair or replacement of any cable which fails as a result of damage in transit, misuse, neglect, accident, Acts of God, abuse, improper handling, improper storage, excessive stress, faulty or improper or unauthorized installation or repair, negligent maintenance or failure to comply with the written instructions for installation, use or maintenance provided by Nexans. SOLE AND EXCLUSIVE Remedy THIS document sets forth Nexans’ sole and exclusive warranty obligation to EndUSER AND END-USER’s sole and exclusive remedy in the event of Defective cable. EXCLUSION OF OTHER WARRANTIES THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, AND ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. LIMITATION OF LIABILITY AND LIMITATION OF ACTIONS IN NO EVENT SHALL NEXANS BE LIABLE FOR ANY INDIRECT, INCIDENTAL, SPECIAL, PUNITIVE OR CONSEQUENTIAL LOSS, DAMAGE OR EXPENSE (WHICH SHALL BE DEEMED TO INCLUDE WITHOUT LIMITATION, ANY LOSS OF PROFIT OR REVENUE, ANY LOSS OF GOODWILL, LOSS CLAIMED BY END-USER’S CUSTOMERS, OR ANY LOSS OF BUSINESS OPPORTUNITY), OF ANY NATURE OR KIND, HOWEVER ARISING, WHETHER IN CONTRACT, IN TORT OR OTHERWISE, EVEN IF NEXANS IS DEEMED TO BE AWARE OF THE POSSIBILITY OF SUCH DAMAGES. NEXANS’ MAXIMUM LIABILITY FOR ANY CLAIM, LOSS OR DAMAGE SHALL UNDER NO CIRCUMSTANCES EXCEED THE PURCHASE PRICE FOR THE CABLE SUBJECT TO A CLAIM, EVEN IF END-USER HAS CLAIMS OR IS SUBJECT TO CLAIMS IN EXCESS OF THIS LIMITATION. ANY LEGAL PROCEEDING RELATING TO THIS WARRANTY MUST BE BROUGHT WITHIN (1) YEAR AFTER THE CAUSE OF ACTION ARISES. NOTICE WARNING Nexans has endeavored to ensure the accuracy of the data in this publication, however we cannot be liable for the consequences of errors or omissions. All data is subject to change without notice. The installer and / or user assumes all liability for the consequences of the installation and / or use of any of our products in contravention of any applicable law, regulation or code. FLAMMABLE Non-metallic covering of electrical cables will burn and under certain conditions may transmit fire when ignited 1-866-663-9267 40 TOXIC Burning non-metallic coverings may emit acid gases, which are highly toxic and may generate dense smoke. CORROSIVE Emission of acid gases may corrode metal in the vicinity, such as sensitive instruments and reinforcing rod in concrete.