2354235 11/2008
Altivar 312
Variable speed drives
for asynchronous motors
Programming manual
BBV46385 05/2009
05/2009
www.schneider-electric.com
Contents
Important information __________________________________________________________________________________________ 4
Before you begin______________________________________________________________________________________________ 5
Documentation structure________________________________________________________________________________________ 7
Steps for setting up the drive ____________________________________________________________________________________ 8
Setup - Preliminary Recommendations ____________________________________________________________________________ 9
Factory configuration _________________________________________________________________________________________ 10
Basic functions ______________________________________________________________________________________________ 11
Remote display terminal option, ATV31 ___________________________________________________________________________ 13
Remote graphic display terminal option, ATV61/ATV71_______________________________________________________________ 14
Remote display terminal option, ATV12 ___________________________________________________________________________ 18
Structure of the parameter tables ________________________________________________________________________________ 19
Compatibility of functions ______________________________________________________________________________________ 20
List of functions that can be assigned to inputs/outputs _______________________________________________________________ 22
List of functions that can be assigned to the Network and Modbus control word bits ________________________________________ 24
Checklist ___________________________________________________________________________________________________ 25
Programming _______________________________________________________________________________________________ 26
[SPEED REFERENCE] (rEF-) menu _____________________________________________________________________________ 30
[SETTINGS] (SEt-) menu ______________________________________________________________________________________ 31
[MOTOR CONTROL] (drC-) menu _______________________________________________________________________________ 39
[INPUTS / OUTPUTS CFG] (I-O-) menu __________________________________________________________________________ 45
[COMMAND] (CtL-) menu______________________________________________________________________________________ 48
[COMMAND] (CtL-) menu______________________________________________________________________________________ 59
[APPLICATION FUNCT.] menu (FUn-) ___________________________________________________________________________ 60
[FAULT MANAGEMENT] (FLt-) menu ____________________________________________________________________________ 86
[COMMUNICATION] (COM-) menu ______________________________________________________________________________ 92
[MONITORING] (SUP-) menu __________________________________________________________________________________ 94
Migration ATV31 - ATV312_____________________________________________________________________________________ 99
Diagnostics and troubleshooting________________________________________________________________________________ 100
Index of functions ___________________________________________________________________________________________ 105
Index of parameter codes and customer settings___________________________________________________________________ 106
1
Important information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain
it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or
equipment damage.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death, serious injury or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in injury or equipment damage.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can
result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the "controller portion" of the adjustable speed drive as defined by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this documentation.
© 2009 Schneider Electric. All rights reserved.
4
BBV46385 05/2009
Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altivar 312 drive. Installation, adjustment, repair, and
maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of
all equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically
insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/– or across the DC bus capacitors.
• Before repairing the variable speed drive:
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/– terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair
or operate the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the Altivar 312 drive.
• Any changes made to the parameter settings must be performed by qualified personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not install or operate any drive that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
BBV46385 05/2009
5
Before you begin
WARNING
LOSS OF CONTROL
• The designer of any wiring diagram must take account of potential control channel failure modes and, for certain critical control
functions, incorporate a way of achieving a safe state during and after a channel failure. Examples of critical control functions are
emergency stop and overtravel stop.
• Separate or redundant control channels must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission
delays or failures of the link. a
Failure to follow these instructions can result in death, serious injury, or equipment damage.
a) For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and Maintenance of
Solid State Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and
Operation of Adjustable-Speed Drive Systems".
6
BBV46385 05/2009
Documentation structure
The following Altivar 312 technical documents are available on the Schneider Electric website (www.schneider-electric.com) as well as on
the DVD-ROM (reference VW3A8200).
Installation Manual
This manual describes how to install and connect the drive.
Programming manual
This manual describes the functions and parameters of the drive's terminals and how to use them.
Simplified manual
This manual is a simplified version of the installation and programming manuals. It is supplied with the drive.
Quick Start
This document describes how to connect and configure the drive so that the motor can be started both quickly and easily for basic
applications. This document is supplied with the drive.
Manuals for Modbus, CANopen, etc.
These manuals describe the installation process, the bus or network connections, signaling, diagnostics and the configuration of parameters
specific to communication.
They also describe the communication services of the protocols.
BBV46385 05/2009
7
Steps for setting up the drive
INSTALLATION
1. Please refer to the Installation Manual.
PROGRAMMING
2. Apply input power to the drive, but do not
give a run command.
3. Configure:
v The
Tips:
• Before beginning programming, complete the customer
setting tables, page 106.
• Use the [Restore config.] (FCS) parameter, page 44,
to return to the factory settings at any time.
• To locate the description of a function quickly, use the index
of functions on page 105.
• Before configuring a function, read carefully the "Function
compatibility" section on pages 20 and 21.
• Note:
The following operations must be performed for optimum
drive performance in terms of accuracy and response time:
- Enter the values indicated on the (motor) rating plate in
the [MOTOR CONTROL] (drC-) menu, page 39.
- Perform auto-tuning with the motor cold and connected
using the [Auto-tuning] (tun) parameter, page 41.
- Adjust the [FreqLoopGain] (FLG) parameter, page 32
and the [Fr.Loop.Stab] (StA) parameter, page 33.
nominal frequency of the motor
[Standard mot. freq] (bFr) page 39 if this is
not 50 Hz,
v The motor parameters in the [MOTOR
CONTROL] (drC-) menu, page 39, only if
the factory configuration of the drive is
not suitable,
v The application functions in the
[INPUTS / OUTPUTS CFG] (I-O-) menu,
page 45, the [COMMAND] (CtL-) menu,
page 48, and the [APPLICATION
FUNCT.] (FUn-) menu, page 60, only if
the factory configuration of the drive
is not suitable.
4. In the [SETTINGS] (SEt-) menu,
adjust the following
parameters:
v [Acceleration] (ACC), page 31 and
[Deceleration], (dEC) page 31,
v [Low speed] (LSP), page 32 and [High
speed] (HSP), page 32,
v [Mot. therm. current] (ItH), page 32.
5. Start the drive.
8
BBV46385 05/2009
Setup - Preliminary Recommendations
Before powering up the drive
DANGER
UNINTENDED EQUIPMENT OPERATION
Make sure that all logic inputs are inactive to avoid any unintended operation.
Failure to follow these instructions will result in death or serious injury.
Before configuring the drive
DANGER
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the ATV312 drive.
• Any changes made to the parameter settings must be performed by qualified personnel.
• Make sure that all logic inputs are inactive to avoid any unintended operation when parameters are being changed.
Failure to follow these instructions will result in death or serious injury.
Start-up
Note: When factory settings apply and during power-up/manual reset or after a stop command, the motor can only be powered once the
"forward", "reverse" and "DC injection stop" commands have been reset. If they have not been reset, the drive will display [Freewheel stop]
(nSt) but will not start. If the automatic restart function has been configured ([Automatic restart] (Atr) parameter in the [FAULT
MANAGEMENT] (FLt-) menu, page 86), these commands are taken into account without a reset (to zero) being necessary.
Line contactor
CAUTION
RISK OF DAMAGE TO DRIVE
• Frequent use of the contactor will cause premature ageing of the filter capacitors.
• Do not have cycle times less than 60 seconds.
Failure to follow these instructions can result in equipment damage.
Using a motor with a lower rating or dispensing with a motor altogether
• With the factory settings, motor output phase loss detection is active ([Output Phase Loss] (OPL) = [YES] (YES), page 89). To avoid
having to use a motor with the same rating as the drive when testing the drive or during a maintenance phase, deactivate motor output
phase loss detection ([Output Phase Loss] (OPL) = [No] (nO)). This can prove particularly useful if very powerful drives are being
used.
• Set the [U/F mot 1 selected] (UFt) parameter, page 42, on [Cst. torque] (L) in the [MOTOR CONTROL] (drC-) menu.
CAUTION
RISK OF DAMAGE TO MOTOR
Motor thermal protection will not be provided by the drive if the motor 's nominal current is 20% lower than that of the drive. Find an
alternative source of thermal protection.
Failure to follow these instructions can result in equipment damage.
BBV46385 05/2009
9
Factory configuration
Factory settings
The Altivar 312 is factory-set for the most common operating conditions:
• Display: drive ready [Ready] (rdY) with motor stopped, and motor frequency with motor running.
• The LI5 and LI6 and logic inputs, AI3 analog input, AOC analog output, and R2 relay are unaffected.
• Stop mode when fault detected: freewheel
Code
Description
Value
Page
bFr
[Standard mot. freq]
[50Hz IEC]
39
tCC
[2/3 wire control]
[2 wire] (2C): 2-wire control
29
UFt
[U/F mot 1 selected]
[SVC] (n): Sensorless flux vector control for constant torque applications
42
ACC
DEC
[Acceleration]
[Deceleration]
3.00 seconds
61
LSP
[Low speed]
0 Hz
32
HSP
[High speed]
50 Hz
32
ItH
[Mot. therm. current]
Nominal motor current (value depending on drive rating)
32
SdC1
[Auto DC inj. level 1]
0.7 x nominal drive current, for 0.5 seconds
33
SFr
[Switching freq.]
4 kHz
38
rrS
[Reverse assign.]
[LI2] (LI2): Logic input LI2
46
PS2
[2 preset speeds]
[LI3] (LI3): Logic input LI3
69
PS4
[4 preset speeds]
[LI4] (LI4): Logic input LI4
69
Fr1
[Ref.1 channel]
[AI1] (AI1) - Analog input AI1
28
SA2
[Summing ref. 2]
[AI2] (AI2) - Analog input AI2
67
r1
[R1 Assignment]
[No drive flt] (FLt): The contact opens when a fault is detected or when the drive has
been switched off
47
brA
[Dec ramp adapt.]
[Yes] (YES): Function active (automatic adaptation of deceleration ramp)
62
Atr
[Automatic restart]
[No] (nO): Function inactive
86
Stt
[Type of stop]
[Ramp stop] (rMP): On ramp
63
CFG
[Macro configuration]
[Factory set.] (Std) (1)
43
Check whether the values above are compatible with the application. If necessary, the drive can be used without changing the settings.
(1) If you want to keep the drive's presettings to a minimum, select the macro configuration [Macro configuration] (CFG) = [Start/stop] (StS)
followed by [Restore config.] (FCS) = [Config. CFG] (InI) (page 44).
The [Start/stop] (StS) macro configuration is the same as the factory configuration, apart from the I/O assignment:
• Logic inputs:
- LI1, LI2 (reversing): 2-wire transition detection control, LI1 = run forward, LI2 = run reverse.
- LI3 to LI6: Inactive (not assigned).
• Analog inputs:
- AI1: Speed reference 0-10 V.
- AI2, AI3: Inactive (not assigned).
• Relay R1: The contact opens in the event of a detected fault (or drive off).
• Relay R2: Inactive (not assigned).
• Analog output AOC: 0-20 mA, inactive (not assigned).
10
BBV46385 05/2009
Basic functions
Drive thermal protection
Functions:
Thermal protection by PTC probe fitted on the heatsink or integrated in the power module.
Indirect protection of the drive against overloads by tripping in the event of an overcurrent. Typical tripping values:
- Motor current = 185% of nominal drive current: 2 seconds
- Motor current = 150% of nominal drive current: 60 seconds
Time
(seconds)
Motor current/In drive
Drive ventilation
The fan starts up when the drive is powered up then shuts down after 10 seconds if a run command has not been received.
The fan is powered automatically when the drive is unlocked (direction of operation + reference). It is powered down a few seconds after
the drive is locked (motor speed < 0.2 Hz and injection braking completed).
BBV46385 05/2009
11
Basic functions
Motor thermal protection
Function:
Thermal protection by calculating the I2t.
The protection takes account of self-cooled motors.
Tripping time t
in seconds
Motor current/
[Mot. therm. current] (ItH)
CAUTION
RISK OF DAMAGE TO MOTOR
External protection against overloads is required under the following circumstances:
• When the product is being switched on again, as there is no memory to record the motor thermal state
• When supplying more than one motor
• When supplying motors with ratings less than 0.2 times the nominal drive current
• When using motor switching
Failure to follow these instructions can result in equipment damage.
12
BBV46385 05/2009
Remote display terminal option, ATV31
This terminal is a local control unit which can be mounted on the door of the wall-mounted or floor-standing enclosure. It has a cable with
connectors, which is connected to the drive serial link (see the manual supplied with the terminal). Its display capabilities are practically
identical to those of the Altivar 312. With this terminal, however, up and down arrows are used for navigation rather than a jog dial. There
is also an access locking switch for the menus. There are three buttons for controlling the drive (1):
• FWD/REV: Reversal of the direction of rotation
• RUN: Motor run command
• STOP/RESET: Motor stop command or reset
Pressing the button a first time stops the motor, and if DC injection standstill braking is configured, pressing it a second time stops this
braking.
View of the front panel::
View of the rear panel :
4-character
display
Connector
Access locking switch:
• Position:
• Position:
• Position:
[MONITORING] (SUP-) and [SPEED
REFERENCE] (rEF-) menus can be
accessed.
[SETTINGS] (SEt-), [MONITORING]
(SUP-) and [SPEED REFERENCE]
(rEF-) can be accessed.
All menus can be accessed
Note: Protection via customer confidential code has priority over the switch.
Note:
• The remote terminal access locking switch also locks access by the drive keys.
• When the remote display terminal is disconnected, any locking remains active for the drive keys.
• The remote display terminal will only be active if the [Modbus baud rate] (tbr) parameter in the [COMMUNICATION] (COM-) menu,
page 92, still has its factory setting: [19.2 Kbps] (19.2).
(1) To activate the buttons on the remote display terminal, you first have to configure [HMI command] (LCC) = [Yes] (YES), page 58.
Saving and loading configurations
Up to four complete configurations for ATV312 drives without an option card can be stored on the remote display terminal. These
configurations can be saved, transported and transferred from one drive to another of the same rating. 4 different operations for the same
device can also be stored on the terminal.
See the [Saving config.] (SCS) and [Restore config.] (FCS) parameters in the [MOTOR CONTROL] (drC-) menu, pages 43 and 44, the
[INPUTS / OUTPUTS CFG] (I-O-) menu, pages 47 and 47, the [COMMAND] (CtL-) menu, pages 59 and 59, and the [APPLICATION
FUNCT.] (FUn-) menu, pages 85 and 85.
To transfer a configuration between an ATV31 and an ATV32, follow the procedure on page 85.
BBV46385 05/2009
13
Remote graphic display terminal option, ATV61/ATV71
Description of the terminal
Thanks to the screen size of this graphic display terminal, which works with FLASH V1.1IE19 or higher and is part of the ATV71, it is possible
to display more detailed information than can be shown on an on-board display. It is connected in the same way as the ATV31 remote
display terminal.
1 Graphic display
2 Function keys:
F1: CODE
F2, F3: not used
F4: MODE
3 Button to stop/reset
7 ESC button:cancels a value, a
parameter or a menu to return
to the previous selection
4 Run button
6 Button for reversing the direction
of rotation of the motor
5 Navigation button:
• Press (ENT):
- To save the current value
- To enter the selected menu or parameter
• Turn CW/CCW:
- To increase or decrease a value
- To go to the next or previous line
- To increase or decrease the reference if control via
the display terminal is activated
Note: Keys 3, 4, 5 and 6 can be used to control the drive directly, if control via the terminal is activated.
To activate the buttons on the remote display terminal, you first have to configure [HMI command] (LCC) = [Yes] (YES), page 58.
14
BBV46385 05/2009
Remote graphic display terminal option, ATV61/ATV71 (continued)
Powering up the graphic display terminal for the first time
When powering up the graphic display terminal for the first time, the user has to select the required language.
LANGUAGE
English
Français
Deutsch
Espanol
Italiano
Display after the graphic display terminal has been
powered up for the first time.
Select the language and press ENT.
Chinese
Russian
Turkish
The drive's rating details will now appear.
ATV312HU15M2
1.5kW/2HP 200/240V
MAIN MENU
DRIVE MENU
LANGUAGE
The [MAIN MENU]
follows automatically.
3 seconds
or ENT
DRIVE MENU
SPEED REFERENCE
SETTINGS
MOTOR CONTROL
INPUTS / OUTPUTS CFG
COMMAND
Code
APPLICATION FUNCT.
FAULT MANAGEMENT
COMMUNICATION
BBV46385 05/2009
Automatically switches to the [DRIVE MENU]
menu after 3 seconds.
Select the menu and press ENT.
Mode
15
Remote graphic display terminal option, ATV61/ATV71 (continued)
Powering up the drive for the first time
When powering up the drive for the first time, the user immediately accesses the 3 parameters below: [Standard mot. freq] (bFr), [Ref.1
channel] (Fr1), and [2/3 wire control] (tCC), page 29. .
Display after the drive has been powered up for the
first time.
ATV312HU15M2
1.5kW/2HP 200/240V
MAIN MENU
DRIVE MENU
LANGUAGE
The [MAIN MENU]
follows automatically.
3 seconds
Automatically switches to the [DRIVE MENU]
menu after 3 seconds.
Select the menu and press ENT.
DRIVE MENU
Standard mot. freq
2/3 wire control
Ref.1 channel
SPEED REFERENCE
SETTINGS
MOTOR CONTROL
INPUTS / OUTPUTS CFG
COMMAND
APPLICATION FUNCT.
FAULT MANAGEMENT
COMMUNICATION
ESC
The word "Ready" appears on the graphic display
terminal if you press the ESC key when in the
[DRIVE MENU].
DRIVE MENU
Ready
Code
16
Mode
BBV46385 05/2009
Remote graphic display terminal option, ATV61/ATV71 (continued)
Subsequent power-ups
Display after powering up.
ATV312HU15M2
1.5kW/2HP 200/240V
MAIN MENU
DRIVE MENU
LANGUAGE
The [MAIN MENU]
follows automatically.
3 seconds
DRIVE MENU
SPEED REFERENCE
SETTINGS
MOTOR CONTROL
INPUTS / OUTPUTS CFG
COMMAND
Code
APPLICATION FUNCT.
FAULT MANAGEMENT
COMMUNICATION
Automatically switches to the [DRIVE MENU]
menu after 3 seconds.
Select the menu and press ENT.
Mode
ESC
The word "Ready" appears on the graphic display
terminal if you press the ESC key when in the
[DRIVE MENU].
DRIVE MENU
Ready
Code
BBV46385 05/2009
Mode
17
Remote display terminal option, ATV12
Description of the terminal
This terminal is a local control unit which can be mounted on the door of the wall-mounted or floor-standing enclosure. It has a cable with
connectors, which is connected to the drive serial link (see the manual supplied with the terminal). Its display capabilities are practically
identical to those of the Altivar 312. With this terminal, up and down arrows are used for navigation rather than a jog dial.
1 Graphic display
2 MODE button (1): If [SPEED
REFERENCE] (rEF-) is displayed,
this will take you to the
[SETTINGS] (SEt-) menu. If not, it
will take you to the [SPEED
REFERENCE] (rEF-) menu.
3 ESC button
Used to quit a menu/parameter or
remove the currently displayed
value in order to revert
to the previous value
retained in the memory
4 RUN button
Executes the function
assuming it has been
configured
5 Navigation keys
6 ENT button
Used to save the current value or
access the selected menu/parameter
7 STOP button
Used to stop the motor and
perform a reset
8 Button for reversing the direction
of rotation of the motor
(1) If the drive is locked by a code ([PIN code 1] (COd), page 97), pressing the Mode key enables you to switch from the [MONITORING]
(SUP-) menu to the [SPEED REFERENCE] (rEF-) menu and vice versa.
To activate the buttons on the remote display terminal, you first have to configure [HMI command] (LCC) = [Yes] (YES), page 58.
18
BBV46385 05/2009
Structure of the parameter tables
The parameter tables contained in the descriptions of the various menus are organized as follows.
Example :
5
APPLICATION FUNCT.] menu (Fun-)
1
Code
2
PI-
6
Name/Description
b
Adjustment
range
Factory
setting
[PI regulator]
Note: The "PI regulator" function is incompatible with several functions (see page 20). It can only
be configured if these functions are unassigned, in particular the summing inputs (set [Summing
ref. 2] (SA2) to [No] (nO), page 67) and the preset speeds (set [2 preset speeds] (PS2) and
[4 preset speeds] (PS4) to [No] (nO), page 69) which will have been assigned as part of the
factory settings.
3
PIF
4
no
AI1
A12
A13
M [PID feedback ass.]
v [Non] (nO): not assigned
v [AI1] (AI1): analog input AI1
v [AI2] (AI2): analog input AI2
v [AI3] (AI3): analog input AI3
7
[Non] (nO)
8
1. Name of menu on 4-digit 7-segment display
5. Name of menu on ATV61/ATV71 graphic display terminal
2. Submenu code on 4-digit 7-segment display
6. Name of submenu on ATV61/ATV71 graphic display terminal
3. Parameter code on 4-digit 7-segment display
7. Name of parameter on ATV61/ATV71 graphic display terminal
4. Parameter value on 4-digit 7-segment display
8. Value of parameter on ATV61/ATV71 graphic display terminal
BBV46385 05/2009
19
Compatibility of functions
Incompatible functions
The following functions will be inaccessible or deactivated in the cases described below:
Automatic restart
This is only possible for the 2-wire level control type ([2/3 wire control] (tCC) = [2 wire] (2C) and [2 wire type] (tCt) = [Level] (LEL) or
[Fwd priority] (PFO)).
Catch on the fly
This is only possible for the 2-wire level control type ([2/3 wire control] (tCC) = [2 wire] (2C) and [2 wire type] (tCt) = [Level] (LEL) or
[Fwd priority] (PFO)).
This function is locked if automatic standstill injection has been configured as DC ([Auto DC injection] (AdC) = [Continuous] (Ct)).
Function compatibility table
The choice of application functions may be limited by the number of I/O and by the fact that some functions are incompatible with one
another. Functions which are not listed in this table are compatible.
If there is an incompatibility between functions, the first function configured will prevent the others being configured.
p
p
p
Management of limit switches
Freewheel stop
A
Fast stop
p
DC injection stop
A
Brake control
Jog operation
Management of limit switches
p
PI regulator
+/- speed (1)
p
Preset speeds (factory setting)
Summing inputs (factory setting)
+/- speed (1)
Summing inputs (factory setting)
To configure a function, first check that functions which are incompatible with it are unassigned, especially those which are
assigned in the factory settings.
p
Preset speeds (factory setting)
X
p
PI regulator
p
p
Jog operation
X
p
p
p
Brake control
p
X
A
p
p
p
p
p
p
DC injection stop
p
p
A
Fast stop
A
Freewheel stop
X
X
(1) Excluding special application with reference channel [Ref.2 channel] (Fr2) (see diagrams 51 and 53)
p
Incompatible functions
Compatible functions
Not applicable
Priority functions (functions which cannot be active at the same time):
The function marked with the arrow takes priority over the other.
X
A
Stop functions take priority over run commands.
Speed references via logic command take priority over analog references.
20
BBV46385 05/2009
Compatibility of functions
Logic and analog input application functions
Each of the functions on the following pages can be assigned to one of the inputs.
A single input can activate several functions at the same time (reverse and 2nd ramp for example). The user must therefore ensure that
these functions can be used at the same time.
The [MONITORING] (SUP-) menu ([[LOGIC INPUT CONF.]] (LIA-) parameter, page 98, and [[ANALOG INPUTS IMAGE]] (AIA-) parameter,
page 98) can be used to display the functions assigned to each input in order to check their compatibility.
Before assigning a reference, command or function to a logic or analog input, the user must check that this input has not already been
assigned in the factory settings and that no other input has been assigned to an incompatible or unwanted function.
• Example of incompatible function to be unassigned:
In order to use the "+speed/-speed" function, the preset speeds and summing input 2 must first be unassigned.
The table below lists the factory-set input assignments and the procedure for unassigning them.
Assigned input
Function
Code
To unassign, set to:
LI2
Run reverse
rrS
nO
46
LI3
2 preset speeds
PS2
nO
69
LI4
4 preset speeds
PS4
nO
69
AI1
Reference 1
Fr1
Anything but AI1
56
LI1
Run forward
tCC
2C or 3C
45
AI2
Summing input 2
SA2
nO
67
BBV46385 05/2009
Page
21
List of functions that can be assigned to inputs/outputs
Logic inputs
Page
Code
Not assigned
-
-
LI5 - LI6
Run forward
-
-
LI1
2 preset speeds
69
PS2
LI3
4 preset speeds
69
PS4
LI4
8 preset speeds
69
PS8
16 preset speeds
70
PS16
2 preset PI references
77
Pr2
4 preset PI references
78
Pr4
+ speed
74
USP
- speed
74
dSP
Jog operation
72
JOG
Ramp switching
62
rPS
2nd current limit switching
81
LC2
Fast stop via logic input
63
FSt
DC injection via logic input
63
dCI
Freewheel stop via logic input
64
nSt
Run reverse
46
rrS
External fault
88
EtF
RESET
87
rSF
Forced local mode
93
FLO
Reference switching
57
rFC
Control channel switching
58
CCS
Motor switching
82
CHP
Forward limit switch
84
LAF
Reverse limit switch
84
LAr
Fault inhibition
91
InH
Analog inputs
Page
Code
Not assigned
-
-
AI3
Reference 1
56
Fr1
AI1
Reference 2
56
Fr2
Summing input 2
67
SA2
Summing input 3
67
SA3
PI regulator feedback
77
PIF
22
Factory setting
LI2
Factory setting
AI2
BBV46385 05/2009
List of functions that can be assigned to inputs/outputs
Analog/logic output
Page
Code
Not assigned
-
-
Motor current
46
OCr
Motor frequency
46
OFr
Motor torque
46
Otr
Power supplied by the drive
46
OPr
Drive detected fault (logic data)
46
FLt
Drive running (logic data)
46
rUn
Frequency threshold reached (logic data)
46
FtA
High speed (HSP) reached (logic data)
46
FLA
Current threshold reached (logic data)
46
CtA
Frequency reference reached (logic data)
46
SrA
Motor thermal threshold reached (logic data)
46
tSA
Brake sequence (logic data)
46
bLC
Page
Code
Relay
Factory setting
AOC/AOV
Factory setting
Not assigned
-
-
R2
Detected fault
47
FLt
R1
Drive running
47
rUn
Frequency threshold reached
47
FtA
High speed (HSP) reached
47
FLA
Current threshold reached
47
CtA
Frequency reference reached
47
SrA
Motor thermal threshold reached
47
tSA
Brake sequence
47
bLC
Copy of the logic input
47
LI1 to LI6
BBV46385 05/2009
23
List of functions that can be assigned to the Network and
Modbus control word bits
Bits 11 to 15 of the control word
Page
Code
2 preset speeds
69
PS2
4 preset speeds
69
PS4
8 preset speeds
69
PS8
16 preset speeds
70
PS16
2 preset PI references
77
Pr2
4 preset PI references
78
Pr4
Ramp switching
62
rPS
2nd current limit switching
81
LC2
Fast stop via logic input
63
FSt
DC injection
63
dCI
External fault
88
EtF
Reference switching
57
rFC
Control channel switching
58
CCS
Motor switching
82
CHP
24
BBV46385 05/2009
Checklist
Carefully read the information contained in the programming, installation and simplified manuals, as well as the information in the catalog.
Before starting to use the drive, please check the following points relating to mechanical and electrical installations.
For the full range of documentation, please visit www.schneider-electric.com.
1. Mechanical installation (see the simplified and installation manuals)
• For details of the different installation types and recommendations concerning ambient temperature, please refer to the installation
instructions in the simplified or installation manuals.
• Install the drive vertically in accordance with the specifications. Please refer to the installation instructions in the simplified or
installation manuals.
• When using the drive, both the environmental conditions defined under standard 60721-3-3 and the levels defined in the catalog must
be respected.
• Install the required options for your application. Refer to the catalog for details.
2. Electrical installation (see the simplified and installation manuals)
• Ground the drive. See the sections on how to ground equipment in the simplified and installation manuals.
• Make sure the input supply voltage matches the nominal drive voltage and connect the line supply in accordance with the simplified
and installation manuals.
• Make sure you use appropriate input line fuses and circuit breakers. See the simplified and installation manuals.
• Arrange the cables for the control terminals as required (see the simplified and installation manuals). Separate the supply and control
cables in accordance with EMC compatibility rules.
• The ATV312ppppM2 and ATV312ppppN4 ranges include an EMC filter Using an IT jumper helps reduce leakage current. This is
explained in the paragraph about the internal EMC filter on the ATV312ppppM2 and the ATV312ppppN4 in the installation manual.
• Make sure the motor connections are right for the voltage (star, delta).
3. Using and starting up the drive
• Start the drive. [Standard mot. freq] (bFr), page 28, is displayed the first time the drive is powered up. Make sure the frequency defined
by frequency bFr (the factory setting is 50 Hz) matches the motor's frequency.
• When the drive is powered up for the first time, the [Ref.1 channel] (Fr1) parameter, page 28, and the [2/3 wire control] (tCC)
parameter, page 29, are displayed after [Standard mot. freq] (bFr). These parameters will need to be adjusted if you wish to control
the drive locally.
• When the drive is powered up subsequently, [Ready] (rdY) is displayed on the HMI.
• The [Restore config.] (FCS) function, page 44, is used to reinitialize the drive with the factory settings.
BBV46385 05/2009
25
Programming
Description of the HMI
Functions of the display and the keys
• 4 x 7 segment display
• REF LED, illuminated if
[SPEED REFERENCE]
(rEF-) menu is active
• Load LED
• MON LED, illuminated if
[MONITORING] (SUP-)
menu is active
• 2 CANopen status LEDs
• Used to quit a menu or parameter
or to clear the value displayed in
order to revert to the value in the
memory
• CONF LED, illuminated if the
[SETTINGS] (SEt-),
[MOTOR CONTROL]
(drC-),[INPUTS / OUTPUTS
CFG] (I-O-), [COMMAND]
(CtL-), [APPLICATION
FUNCT] (FUn-), [FAULT
MANAGEMENT] (FLt-)
or [COMMUNICATION]
(COM-) menus are active
• MODE button (1): If
[SPEED REFERENCE]
(rEF-) is displayed, this will
take you to the
[SETTINGS] (SEt-) menu.
If not, it will take you to the
[SPEED REFERENCE]
(rEF-) menu.
• Jog dial - can be used for
navigation by turning it clockwise
or counter-clockwise - pressing
the jog dial enables the user to
make a selection or confirm
information.
Functions as a potentiometer if [Ref.1
channel] (Fr1-) in the [COMMAND]
(CtL-) menu is set to [Image input
AIV1] (AIV1)
• RUN button: Controls powering up
of the motor for forward running if
the [2/3 wire control] (tCC)
parameter in the [INPUTS /
OUTPUTS CFG] (I-O-) menu is set
to [Local] (LOC), page 45
STOP/RESET button
• Enables detected fault to be reset
• Can be used to control motor stopping
- If [2/3 wire control] (tCC) is not set to
[Local] (LOC), freewheel stop
- If [2/3 wire control] (tCC) is set to [Local]
(LOC), stop on ramp or freewheel stop
during DC injection braking
Normal display, with no fault code displayed and no startup:
-
-
: Displays the parameter selected in the [MONITORING] (SUP-) menu (default: motor frequency).
If the current is limited, the display flashes. In such cases, CLI will appear at the top left if an ATV61/ATV71 graphic display
terminal is connected to the drive.
InIt: Initialization sequence
rdY: Drive ready
dCb: DC injection braking in progress
nSt: Freewheel stop
FSt: Fast stop
tUn : Auto-tuning in progress
In the event of a detected fault, the display will flash to notify the user accordingly. If an ATV61/ATV71 graphic display terminal is
connected, the name of the detected fault will be displayed.
(1) If the drive is locked by a code ([PIN code 1] (COd), page 97), pressing the Mode key enables you to switch from the [MONITORING]
(SUP-) menu to the [SPEED REFERENCE] (rEF-) menu and vice versa.
26
BBV46385 05/2009
Programming
Structure of the menus
Powering up
Parameter selection
These three parameters are
only visible when the drive is
powered up for the first time.
The settings can be amended
subsequently in the menus:
[MOTOR CONTROL] (drC-)
for [Standard mot. freq] (bFr),
[COMMAND] (CtL-) for [Ref.1
channel] (Fr1)
[INPUTS / OUTPUTS CFG]
(I-O-) for [2/3 wire control]
(tCC)
[SPEED REFERENCE] (rEF-)
[SETTINGS] (SEt-)
[MOTOR CONTROL] (drC-)
[INPUTS / OUTPUTS CFG]
(I-O-)
[COMMAND] (CtL-)
[APPLICATION FUNCT.] (FUn-)
[FAULT MANAGEMENT] (FLt)
[COMMUNICATION] (COM-)
[MONITORING] (SUP-)
On the 7-segment display, a dash after menu and submenu codes is used to differentiate them from parameter codes.
Examples: [APPLICATION FUNCT.] (FUn-) menu, [Acceleration] (ACC) parameter
BBV46385 05/2009
27
Programming
Configuring the [Standard mot. freq] (bFr), [2/3 wire control] (tCC), and
[Ref.1 channel] (Fr1) parameters
These parameters can only be modified when the drive is stopped and no run command is present.
Code
Description
M [Standard mot. freq]
bFr
Fr1
AI1
AI2
AI3
AIU1
Factory
setting
[50Hz IEC] (50)
This parameter is only visible the first time the drive is powered up.
It can be modified at any time in the [MOTOR CONTROL] (drC-) menu.
[50Hz IEC] (50): 50 Hz
[60Hz NEMA] (60): 60 Hz
This parameter modifies the presets of the following parameters: [High speed] (HSP), page 32, [Freq.
threshold] (Ftd), page 37, [Rated motor freq.] (FrS), page 39, and [Max frequency] (tFr), page 42
50
60
28
Adjustment
range
M [Ref.1 channel]
v [AI1] (AI1) - Analog input AI1
v [AI2] (AI2) - Analog input AI2
v [AI3] (AI3) - Analog input AI3
v [Network AI] (AIV1) - In terminal control mode, the jog dial functions as a potentiometer.
UPdt
UPdH
v
v
LCC
v
Mdb
nEt
v
v
[AI1] (AI1)
If [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), the following additional assignments are possible:
[+/- SPEED] (UPdt): +/- speed reference via LI. See configuration page 74.
[+/-spd HMI] (UPdH): +/- speed reference by turning the jog dial on the ATV312 keypad.
To use, display the frequency [Output frequency] (rFr), page 95. The +/- speed function via the keypad or the
terminal is controlled from the [MONITORING] (SUP-) menu by selecting the [Output frequency] (rFr)
parameter.
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following additional assignments are possible:
[HMI] (LCC) reference via the remote display terminal, [HMI Frequency ref.] (LFr) parameter in the
[SETTINGS] (SEt-) menu, page 31
[Modbus] (Mdb): Reference via Modbus
[Network] (nEt): Reference via network communication protocol
BBV46385 05/2009
Programming
Code
tCC
Description
Adjustment
range
Factory
setting
[2 wire] (2C)
M [2/3 wire control]
DANGER
UNINTENDED EQUIPMENT OPERATION
When the [2/3 wire control] (tCC) parameter is changed, the [Reverse assign.] (rrS) parameter, page 46, and the
[2 wire type] (tCt) parameter, page 45, and all the assignments involving the logic inputs will revert to their default
values.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
2C
3C
LOC
v
v
v
Control configuration:
[2 wire] (2C): 2-wire control
[3 wire] (3C): 3-wire control
[Local] (LOC): Local control (RUN/STOP/RESET drive) (invisible if [ACCESS LEVEL] (LAC) = [Level 3] (L3),
page 56)
2-wire control: The open or closed state of the input controls running or stopping.
Wiring example:
LI1: Forward
LIx: Reverse
2s
3-wire control (pulse control): A "forward" or "reverse" pulse is sufficient to control startup, a "stop" pulse is
sufficient to control stopping.
Wiring example:
LI1: Stop
LI2: Forward
LIx: Reverse
2s
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
29
[SPEED REFERENCE] (rEF-) menu
rEFSEt-
The [SPEED REFERENCE] (rEF-) menu displays [HMI Frequency ref.] (LFr), [Image input AIV1] (AIV1) or [Frequency ref.] (FrH) depending
on which control channel is active.
drCI-0-
During local control, the HMI's jog dial functions as a potentiometer, making it possible to increase or reduce the reference value within
limits defined by the [Low speed] (LSP) and [High speed] (HSP) parameters.
CtLFUn-
When local control is deactivated, by the [Ref.1 channel] (Fr1) parameter, only the reference values are displayed. The value will be readonly and can only be changed via the jog dial (the speed reference is supplied by an AI or another source).
FLtCOM-
The reference displayed will depend on how the drive has been configured.
Code
SUP-
LFr
Description
Factory setting
M [HMI Frequency ref.]
0 to 500 Hz
This parameter only appears if the function has been enabled.
It is used to change the speed reference from the remote control.
ENT does not have to be pressed to enable a change of reference.
AIU1
M [Image input AIV1]
0 to 100%
Used to amend the speed reference via the jog dial
FrH
M [Frequency ref.]
LSP to HSP Hz
This parameter is read-only. It enables you to display the speed reference applied to the motor, regardless of
which reference channel has been selected.
30
BBV46385 05/2009
[SETTINGS] (SEt-) menu
rEFSEtdrCI-0-
Speed reference via the display terminal
CtLFUnFLtCOMSUP-
Scaling factor for the [Cust. output value] (SPd1) parameter
The adjustment parameters can be modified with the drive running or stopped.
Note: Changes should preferably be made with the drive stopped.
Code
Description
M [HMI Frequency ref.]
LFr
Adjustment range
Factory setting
0 to HSP
-
This parameter is displayed if [HMI command] (LCC) = [Yes] (YES), page 58 or if [Ref.1 channel] (Fr1)/[Ref.2
channel] (Fr2) = [HMI] (LCC) page 56, and if a remote display terminal is connected. In such cases, [HMI
Frequency ref.] (LFr) can also be accessed via the drive's keypad.
[HMI Frequency ref.] (LFr) is reinitialized to 0 when power is switched off.
g
M [Internal PID ref.]
rPI
g
0.0 to 100%
0%
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
M [Acceleration]
ACC
In accordance with
Inr, page 61
3s
Defined to accelerate from 0 to the nominal frequency [Rated motor freq.] (FrS) in the [MOTOR CONTROL]
(drC-) menu.
M [Acceleration 2]
AC2
In accordance with
Inr, page 61
5s
Parameter can be accessed if [Ramp 2 threshold] (Frt) > 0, page 62, or if [Ramp switch ass.] (rPS) is assigned,
page 62.
g
M [Deceleration 2]
dE2
In accordance with
Inr, page 61
5s
Parameter can be accessed if [Ramp 2 threshold] (Frt) > 0, page 62, or if [Ramp switch ass.] (rPS) is assigned,
page 62.
g
M [Deceleration]
dEC
In accordance with
Inr, page 61
3s
Defined to decelerate from the nominal frequency [Rated motor freq.] (FrS) (parameter in the [MOTOR CONTROL]
(drC-)) menu to 0.
Check that the value for [Deceleration] (dEC) is not too low in relation to the load to be stopped.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
31
[SETTINGS] (SEt-) menu
rEFSEt-
Code
Description
drCI-0-
tA1
CtL-
g
FUnFLt-
tA2
COM-
g
SUP-
tA3
g
tA4
g
LSP
M [Begin Acc round]
Adjustment
range
Factory
setting
0 to 100
10
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [End Acc round]
0 to (100-tA1)
10
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [Begin Dec round]
0 to 100
10
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [End Dec round]
0 to (100-tA3)
10
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [Low speed]
0 to HSP
0
LSP to tFr
bFr
Motor frequency at min. reference
HSP
M [High speed]
Motor frequency at max. reference: Ensure that this setting is appropriate for the motor and the application.
ItH
M [Mot. therm. current]
0.2 to 1.5 In (1)
In accordance
with the drive
rating
Set [Mot. therm. current] (ItH) to the nominal current indicated on the motor's rating plate.
If you wish to suppress thermal protection, see [Overload fault mgt] (OLL), page 89.
UFr
M [IR compensation]
0 to 100%
20%
- For [U/F mot 1 selected] (UFt) = [SVC] (n) or [Energy sav.] (nLd), page 42: IR compensation
- For [U/F mot 1 selected] (UFt) = [Cst. torque] (L) or [Var. torque] (P), page 42: Voltage boost
Used to optimize the torque at very low speed (increase [IR compensation] (UFr) if the torque is insufficient).
Check that the value for [IR compensation] (UFr) is not too high when the motor is in a hot state otherwise some
instabilities can occur.
Note: Changing [U/F mot 1 selected] (UFt), page 42, will cause [IR compensation] (UFr) to return to its factory
setting (20%).
FLG
g
M [FreqLoopGain]
1 to 100%
20%
Parameter can only be accessed if [U/F mot 1 selected] (UFt) = [SVC] (n) or [Energy sav.] (nLd), page 42.
The FLG parameter adjusts the drive's ability to follow the speed ramp on the basis of the inertia of the machine
being driven.
Too high a gain may result in operating instability.
FLG low
FLG correct
In this case,
increase FLG.
FLG high
In this case,
reduce FLG.
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
32
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[SETTINGS] (SEt-) menu
rEF-
Code
Adjustment range Factory setting SEt-
Description
M [Fr.Loop.Stab]
StA
1 to 100%
drC-
20%
I-0-
Parameter can only be accessed if [U/F mot 1 selected] (UFt) = [SVC] (n) or [Energy sav.] (nLd), page 42.
Used to adapt the return to steady state after a speed transient (acceleration or deceleration), according to the
dynamics of the machine.
Gradually increase the stability to avoid any overspeed.
StA low
g
CtLFUnFLt-
StA high
StA correct
COM-
In this case,
increase StA.
In this case,
reduce StA.
M [Slip compensation]
SLP
0 to 150%
SUP-
100%
Parameter can only be accessed if [U/F mot 1 selected] (UFt) = [SVC] (n) or [Energy sav.] (nLd), page 42.
Adjusts the slip compensation around the value set by the nominal motor speed.
The speeds given on motor rating plates are not necessarily exact.
• If slip setting < actual slip: the motor is not rotating at the correct speed in steady state.
• If slip setting > actual slip: the motor is overcompensated and the speed is unstable.
g
M [DC inject. level 1]
IdC
(2)
0 to In (1)
0.7 In (1)
Parameter can be accessed if [Type of stop] (Stt) = [DC injection] (dCI), page 63, or if [DC injection assign.] (dCI)
is not set to [No] (nO), page 63.
After 5 seconds, the injection current is limited to 0.5 [Mot. therm. current] (ItH) if set to a higher value.
g
M [DC injection time 2]
tdC
g
(2)
0.1 to 30 s
0.5 s
Parameter can be accessed if [Type of stop] (Stt) = [DC injection] (dCI) , page 63.
M [Auto DC inj. time 1]
tdC1
g
0.1 to 30 s
0.5 s
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
M [Auto DC inj. level 1]
SdC1
0 to 1.2 In (1)
0.7 In (1)
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
Note: Check that the motor will withstand this current without overheating.
g
M [Auto DC inj. time 2]
tdC2
g
0 to 30 s
0s
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
M [Auto DC inj. level 2]
SdC2
0 to 1.2 In (1)
0.5 In (1)
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
Note: Check that the motor will withstand this current without overheating.
g
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
(2) Note: These settings are not related to the "automatic standstill DC injection" function.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
33
[SETTINGS] (SEt-) menu
rEFSEt-
Code
drC-
JPF
Description
Adjustment range Factory setting
M [Skip Frequency]
I-0-
0 to 500 Hz
0 Hz
Helps to prevent prolonged operation at a frequency range of ± 1 Hz around [Skip Frequency] (JPF). This function
helps to prevent a critical speed which leads to resonance. Setting the function to 0 renders it inactive.
CtLFUn-
JF2
M [Skip Frequency 2]
FLt-
1 to 500 Hz
0 Hz
Helps to prevent prolonged operation at a frequency range of ± 1 Hz around [Skip Frequency 2] (JF2). This
function helps to prevent a critical speed which leads to resonance. Setting the function to 0 renders it inactive.
COM-
JGF
SUP-
M [Jog frequency]
g
rPG
M [PID prop. gain]
M [PID integral gain]
nO
YES
g
rP2
g
rP3
g
rP4
g
M [PID fbk scale factor]
34
0.01 to 100/s
1
0.1 to 100
1
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
For adapting the process.
M [PID correct. reverse]
v
v
[No] (nO)
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
[No] (nO): Normal
[Yes] (YES): Reverse
M [Preset ref. PID 2]
0 to 100%
30%
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77, and if [2 preset PID ref.]
(Pr2), page 77, has been enabled by the input selection.
M [Preset ref. PID 3]
0 to 100%
60%
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77, and if [4 preset PID ref.]
(Pr4), page 78, has been enabled by the input selection.
M [Preset ref. PID 4]
0 to 100%
90%
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77, and if [4 preset PID ref.]
(Pr4), page 78, has been enabled by the input selection.
SP2
M [Preset speed 2]
g
See page 70.
g
1
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
It provides static precision when PI feedback is changing slowly.
g
PIC
0.01 to 100
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
It provides dynamic performance when PI feedback is changing quickly.
g
FbS
10 Hz
Parameter can be accessed if [JOG] (JOG) is not set to [No] (nO), page 72.
g
rIG
0 to 10 Hz
0 to 500 Hz
10 Hz
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[SETTINGS] (SEt-) menu
rEF-
Code
Description
SP3
M [Preset speed 3]
g
See page 70.
SP4
M [Preset speed 4]
g
See page 70.
SP5
M [Preset speed 5]
g
See page 70.
SP6
M [Preset speed 6]
g
See page 70.
SP7
M [Preset speed 7]
g
See page 70.
SP8
M [Preset speed 8]
g
See page 70.
SP9
M [Preset speed 9]
g
See page 70.
SP10
M [Preset speed 10]
g
See page 70.
SP11
M [Preset speed 11]
g
See page 71.
SP12
M [Preset speed 12]
g
See page 71.
SP13
M [Preset speed 13]
g
See page 71.
SP14
M [Preset speed 14]
g
See page 71.
SP15
M [Preset speed 15]
g
See page 71.
SP16
M [Preset speed 16]
g
See page 71.
g
Adjustment
range
Factory setting
0 to 500 Hz
15 Hz
drCI-0CtL-
0 to 500 Hz
FUn-
20 Hz
FLtCOM-
0 to 500 Hz
25 Hz
0 to 500 Hz
30 Hz
0 to 500 Hz
35 Hz
0 to 500 Hz
40 Hz
0 to 500 Hz
45 Hz
0 to 500 Hz
50 Hz
0 to 500 Hz
55 Hz
0 to 500 Hz
60 Hz
0 to 500 Hz
70 Hz
0 to 500 Hz
80 Hz
0 to 500 Hz
90 Hz
0 to 500 Hz
100 Hz
SUP-
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
SEt-
35
[SETTINGS] (SEt-) menu
rEF-
Code
SEt-
Description
drC-
CLI
I-0-
M [Current Limitation]
Adjustment
range
Factory setting
0.25 to 1.5 In (1)
1.5 In (1)
0.25 to 1.5 In (1)
1.5 In (1)
Used to limit the torque and the temperature rise of the motor.
CtLFUn-
CL2
FLt-
g
COM-
tLS
SUP-
M [I Limit. 2 value]
Parameter is only visible if [Current limit 2] (LC2) is not set to [No] (nO), page 81.
M [Low speed time out]
0 to 999.9 s
0 (no time limit)
After operating at [Low speed] (LSP) for a given time, the motor is stopped automatically. The motor restarts if
the frequency reference is greater than the [Low speed] (LSP) and if a run command is still present.
Note: Value 0 corresponds to an unlimited period.
rSL
g
UFr2
g
M [PID wake up thresh.]
0 to 100%
0%
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
If the "PI" and "Low speed operating time" [Low speed time out] (tLS) functions, page 36, are configured at the
same time, the PI regulator may attempt to set a speed lower than [Low speed] (LSP).
This results in unsatisfactory operation, which consists of starting, operating at [Low speed] (LSP), then
stopping, and so on.
The [PID wake up thresh.] (rSL) parameter (restart error threshold) is used to set a minimum PID error threshold
for restarting after a stop at prolonged [Low speed] (LSP).
The function is inactive if [Low speed time out] (tLS) = 0.
M [IR compensation 2]
0 to 100%
20%
For [U/F mot.2 selected] (UFt2) = [SVC] (n) or [Energy sav.] (nLd): IR compensation.
For [U/F mot.2 selected] (UFt2) = [Cst. torque] (L) or [Var. torque] (P): voltage boost.
Used to optimize the torque at very low speed (increase [IR compensation 2] (UFr2) if the torque is insufficient).
Check that the value for [IR compensation 2] (UFr2) is not too high when the motor is in a hot state otherwise
some instabilities can occur. Changing [U/F mot.2 selected] (UFt2) will cause [IR compensation 2] (UFr2) to
return to its factory setting (20%).
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
36
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[SETTINGS] (SEt-) menu
rEF-
Code
Description
M [FreqLoopGain 2]
FLG2
Adjustment
range
Factory setting
0 to 100%
20%
SEtdrCI-0-
Parameter can only be accessed if [U/F mot.2 selected] (UFT2) = [SVC] (n) or [Energy sav.] (nLd), page 83.
The [FreqLoopGain 2] (FLG2) parameter adjusts the drive's ability to follow the speed ramp on the basis of the
inertia of the machine being driven.
Too high a gain may result in operating instability.
FLG2 low
g
CtLFUnFLt-
FLG2 high
FLG2 correct
COMSUP-
In this case,
increase FLG2.
In this case,
reduce FLG2.
M [Freq. loop stability 2]
StA2
0 to 100%
20%
Parameter can only be accessed if [U/F mot.2 selected] (UFT2) = [SVC] (n) or [Energy sav.] (nLd) , page 83.
Used to adapt the return to steady state after a speed transient (acceleration or deceleration), according to the dynamics
of the machine.
Gradually increase the stability to avoid any overspeed.
StA2 low
StA2 correct
StA2 high
g
In this case,
increase StA2
M [Slip compensation 2]
SLP2
In this case,
reduce StA2
0 to 150%
100%
Parameter can only be accessed if [U/F mot.2 selected] (UFT2) = [SVC] (n) or [Energy sav.] (nLd), page 83.
Adjusts the slip compensation around the value set by the nominal motor speed.
The speeds given on motor rating plates are not necessarily exact.
• If slip setting < actual slip: The motor is not rotating at the correct speed in steady state.
• If slip setting > actual slip: The motor is overcompensated and the speed is unstable.
g
M [Freq. threshold]
Ftd
0 to 500 Hz
bFr
Threshold beyond which the contact on the relay ([R1 Assignment] (r1) or [R2 Assignment] (r2) = [Freq.Th.att.]
(FtA)) closes or output AOV = 10 V ([Analog./logic output] (dO) = [Freq. limit] (FtA)).
M [Motor therm. level]
ttd
1 to 118%
100%
Threshold beyond which the contact on the relay ([R1 Assignment] (r1) or [R2 Assignment] (r2) = [Th.mot. att.]
(tSA)) closes or output AOV = 10 V ([Analog./logic output] (dO) = [Drv thermal] (tSA)).
M [Current threshold]
Ctd
0 to 1.5 In (1)
In (1)
Threshold beyond which the contact on the relay ([R1 Assignment] (r1) or [R2 Assignment] (r2) = [I attained] (CtA))
closes or output AOV = 10 V ([Analog./logic output] (dO) = [Current limit] (CtA)).
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
37
[SETTINGS] (SEt-) menu
rEFSEt-
Code
Description
drC-
SdS
I-0CtL-
M [Scale factor display]
Adjustment
range
Factory setting
0.1 to 200
30
Used to display a value in proportion to the output frequency [Output frequency] (rFr): the machine speed, the motor
speed, etc.
• If [Scale factor display] (SdS) y 1, [Cust. output value] (SPd1) is displayed (possible definition = 0.01)
• If 1 < [Scale factor display] (SdS) y 10, [Cust. output value] (SPd2) is displayed (possible definition = 0.1)
• If [Scale factor display] (SdS) > 10, [Cust. output value] (SPd3) is displayed (possible definition = 1)
• If [Scale factor display] (SdS) > 10 and [Scale factor display] (SdS) x [Output frequency] (rFr) > 9,999:
FUnFLtCOMSUP-
the display will show
[Cust. output value] (SPd3) =
[Scale factor display] (SdS) x [Output frequency] (rFr)
1000
to 2 decimal places
example: for 24,223, display will show 24.22
- If [Scale factor display] (SdS) > 10 and [Scale factor display] (SdS) x [Output frequency] (rFr) > 65,535, display
locked at 65.54
Example: Display motor speed for
4-pole motor, 1,500 rpm at 50 Hz (synchronous speed):
[Scale factor display] (SdS) = 30
[Cust. output value] (SPd3) = 1,500 at [Output frequency] (rFr) = 50 Hz
SFr
M [Switching freq.]
(1)
2.0 to 16 kHz
4 kHz
Parameter can also be accessed in the [MOTOR CONTROL] (drC-) menu. The frequency can be adjusted to
reduce the noise generated by the motor.
If the frequency has been set to a value higher than 4 kHz, in the event of excessive temperature rise, the drive
will automatically reduce the switching frequency and increase it again once the temperature has returned to
normal.
(1) Parameter can also be accessed in the [MOTOR CONTROL] (drC-) menu.
38
BBV46385 05/2009
[MOTOR CONTROL] (drC-) menu
rEFSEtdrCI-0-
Standard motor frequency
CtLFUnFLtCOMSUP-
Return to factory settings/Restore configuration
With the exception of [Auto tuning] (tUn), which can power up the motor, parameters can only be changed in stop mode, with no run
command present.
On the optional ATV31 remote display terminal, this menu can be accessed with the switch in the
position.
Drive performance can be optimized by:
- Entering the values given on the motor rating plate in the Drive menu
- Performing an auto-tune operation (on a standard asynchronous motor)
Code
bFr
50
60
UnS
Description
Adjustment
range
M [Standard mot. freq]
Factory
setting
[50Hz IEC] (50)
[50Hz IEC] (50): 50 Hz: IEC
[60Hz NEMA] (60): 60 Hz: NEMA
This parameter modifies the presets of the following parameters: [High speed] (HSP), page 32, [Freq.
threshold] (Ftd), page 37, [Rated motor freq.] (FrS), page 39, and [Max frequency] (tFr), page 42.
M [Rated motor volt.]
In accordance
with the drive
rating
In accordance
with the drive
rating
Nominal motor voltage given on the rating plate. When the line voltage is lower than the nominal motor voltage,
set [Rated motor volt.] (UnS) to the same value as the line voltage for the drive terminals.
ATV312pppM2: 100 to 240 V
ATV312pppM3: 100 to 240 V
ATV312pppN4: 100 to 500 V
ATV312pppS6: 100 to 600 V
FrS
M [Rated motor volt.]
10 to 500 Hz
50 Hz
Nominal motor frequency marked on the rating plate. The factory setting is 50 Hz, or 60 Hz if [Standard mot.
freq] (bFr) is set to 60 Hz.
Note: The ratio
[Rated motor volt.] (UnS) (in volts)
[Rated motor freq.] (FrS) (in Hz)
must not exceed the following values:
ATV312pppM2: 7 max.
ATV312pppM3: 7 max.
ATV312pppN4: 14 max.
ATV312pppS6: 17 max.
The factory setting is 50 Hz, or preset to 60 Hz if [Standard mot. freq] (bFr) is set to 60 Hz.
nCr
M [Rated mot. current]
0.25 to 1.5 In (1)
In accordance
with the drive
rating
Nominal motor current given on the rating plate.
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
BBV46385 05/2009
39
[MOTOR CONTROL] (drC-) menu
rEFSEt-
Code
drC-
nSP
Description
Adjustment range Factory setting
M [Rated motor speed]
0 to 32,760 rpm
I-0CtL-
In accordance
with the drive
rating
0 to 9,999 rpm then 10.00 to 32.76 krpm
If, rather than the nominal speed, the nameplate indicates the synchronous speed and the slip in Hz or as a
%, calculate the nominal speed as follows:
FUnFLt-
• Nominal speed = synchronous speed x
or
• Nominal speed = synchronous speed x
or
• Nominal speed = synchronous speed x
COMSUP-
COS
100 - slip as a %
100
50 - slip in Hz
50
60 - slip in Hz
60
M [Motor 1 Cosinus Phi]
(50 Hz motors)
(60 Hz motors)
0.5 to 1
In accordance
with the drive
rating
Motor Cos Phi given on the motor rating plate
rSC
nO
InIt
8888
[No] (nO)
M [Cold stator resist.]
v [No] (nO): function inactive. For applications which do not require high performance or do not tolerate
v
v
automatic auto-tuning (passing a current through the motor) each time the drive is powered up.
[Init] (InIt): activates the function. To improve low-speed performance whatever the thermal state of the motor.
Value of cold state stator resistance used, in mΩ.
Note:
• It is strongly recommended that this function is activated for mechanical handling applications.
• The function should only be activated [Init] (InIt) when the motor is cold.
• When [Cold stator resist.] (rSC) = [Init] (InIt), the [Auto-tuning] (tUn) parameter is forced to [Power on] (POn).
At the next run command the stator resistance is measured with an auto-tune. The [Cold stator resist.] (rSC)
then changes to a value of (8888) and maintains it, [Auto-tuning] (tUn) is still forced to [Power on] (POn).
The [Cold stator resist.] (rSC) parameter remains at [Init] (InIt) as long as the measurement has not been
performed.
• Value 8888 can be forced or changed using the jog dial (1).
(1) Procedure:
- Check that the motor is cold.
- Disconnect the cables from the motor terminals.
- Measure the resistance between 2 of the motor terminals (U. V. W.) without modifying its connection.
- Use the jog dial to enter half the measured value.
- Increase the factory setting of [IR compensation] (UFr), page 32, to 100% rather than 20%.
Note: Do not use [Cold stator resist.] (rSC) if it is not set to [No] (nO) or = [Power on] (POn) with catch on the fly ([CATCH ON THE FLY]
(FLr-), page 88).
40
BBV46385 05/2009
[MOTOR CONTROL] (drC-) menu
rEF-
Code
tUn
Description
Adjustment
range
M [Auto tuning]
SEt-
Factory setting
drC-
[No] (nO)
I-0CtL-
DANGER
FUn-
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
FLt-
• During auto-tuning the motor operates at nominal current.
• Do not work on the motor during auto-tuning.
COMSUP-
Failure to follow these instructions will result in death or serious injury.
DANGER
UNINTENDED EQUIPMENT OPERATION
• It is essential that the [Rated motor volt.] (UnS), [Rated motor freq.] (FrS), [Rated motor freq.] (nCr), [Rated motor
speed] (nSP) , and [Rated motor power] (nPr) or [Motor 1 Cosinus Phi.] (COS) parameters are configured
correctly before starting auto-tuning.
• When one or more parameters have been changed after auto-tuning has been performed, [Auto-tuning] (tUn)
will return [No] (nO) and the procedure will have to be repeated.
Failure to follow these instructions will result in death or serious injury.
nO
YES
dOnE
rUn
POn
LI1
to
LI6
v
v
v
v
v
v
[No] (nO): Auto-tuning not performed
[Yes] (YES): Auto-tuning is performed as soon as possible, then the parameter automatically changes to
[Done] (dOnE) or [No] (nO) in the event that Auto-tuning is not successful [AUTO TUNING FAULT] (tnF)
is displayed if [Autotune fault mgt] (tnL) = [Yes] (YES), page 90).
[Done] (dOnE): Use of the values given the last time auto-tuning was performed
[Drv running] (rUn): Auto-tuning is performed every time a run command is sent.
[Power on] (POn): Auto-tuning is performed on every power-up.
[LI1] to [LI16] (LI1) to (LI6): Auto-tuning is performed on the transition from 0 V 1 of a logic input assigned
to this function.
Note:
[Auto-tuning] (tUn) is forced to [Power on] (POn) if [Cold stator resist.] (rSC) = [Init] (InIt).
Auto-tuning is only performed if no command has been activated. If a "freewheel stop" or "fast stop"
function is assigned to a logic input, this input must be set to 1 (active at 0).
Auto-tuning may take 1 to 2 seconds. Do not interrupt the process. Wait for the display to change to [Done]
(dOnE) or [No] (nO).
tUS
tAb
PEnd
PrOG
FAIL
dOnE
Strd
BBV46385 05/2009
M [Auto tuning state]
v
v
v
v
v
v
[Not done] (tAb)
(For information only, cannot be modified)
[Not done] (tAb): The default stator resistance value is used to control the motor.
[Pending] (PEnd): Auto-tuning has been requested but not yet performed.
[In Progress] (PrOG): Auto-tuning in progress.
[Failed] (FAIL): Auto-tuning was unsuccessful.
[Done] (dOnE): The stator resistance measured by the auto-tuning function is used to control the motor.
[Entered R1] (Strd): The cold state stator resistance ([Cold stator resist.] (rSC) which is not set to [No]
(nO)) is used to control the motor.
41
[MOTOR CONTROL] (drC-) menu
rEF-
Code
SEt-
Description
Adjustment
range
drC-
UFt
I-0-
L
P
n
nLd
CtLFUnFLt-
Factory setting
[SVC] (n)
M [U/F mot 1 selected]
v [Cst. torque] (L): Constant torque for motors connected in parallel or special motors.
v [Var. torque] (P): Variable torque for pump and fan applications.
v [SVC] (n): Sensorless flux vector control for constant torque applications.
v [Energy sav.] (nLd): Energy saving, for variable torque applications not requiring high dynamics (behaves
in a similar way to the [Var. torque] (P) ratio with no load and the [SVC] (n) ratio on load).
COM-
Voltage
SUP-
Frequency
nrd
YES
nO
M [Noise reduction]
v [Yes] (YES): Frequency with random modulation.
v [No] (nO): Fixed frequency.
[Yes] (YES)
Random frequency modulation helps to prevent any resonance which may occur at a fixed frequency.
SFr
M [Switching freq.]
(1)
2.0 to 16 kHz
4 kHz
The frequency can be adjusted to reduce the noise generated by the motor.
If the frequency has been set to a value higher than 4 kHz, in the event of excessive temperature rise, the
drive will automatically reduce the switching frequency and increase it again once the temperature has
returned to normal.
tFr
M [Max frequency]
10 to 500 Hz
60 Hz
The factory setting is 60 Hz, or preset to 72 Hz if [Standard mot. freq] (bFr) is set to 60 Hz.
SrF
nO
YES
[No] (nO):
M [Speed loop filter]
v [No] (nO): The speed loop filter is active (helps to prevent the reference being exceeded).
v [Yes] (YES): The speed loop filter is suppressed (in position control applications, this reduces the response
time and the reference may be exceeded).
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
42
BBV46385 05/2009
[MOTOR CONTROL] (drC-) menu
rEF-
Code
Description
SCS
nO
StrI
SEt-
(1)
[No] (nO)
M [Saving config.]
v [No] (nO): Function inactive
v [Config 1] (Str1): Saves the current configuration (but not the result of auto-tuning) to EEPROM. [Saving
drCI-0CtL-
config.] (SCS) automatically switches to [No] (nO) as soon as the save has been performed. This function
is used to keep another configuration in reserve, in addition to the current configuration.
When drives leave the factory the current configuration and the backup configuration are both initialized
with the factory configuration.
• If the ATV31 remote display terminal option is connected to the drive, the following additional selection
options will appear: [File 1] (FIL1), [File 2] (FIL2), [File 3] (FIL3), [File 4] (FIL4) (files available in the
remote display terminal's EEPROM memory for saving the current configuration). They can be used to
store between 1 and 4 different configurations which can also be stored on or even transferred to other
drives of the same rating.
[Saving config.] (SCS) automatically switches to [No] (nO) as soon as the save has been performed.
2s
CFG
Adjustment range Factory setting
M [Macro configuration]
(1)
FUnFLtCOMSUP-
[Factory set.] (Std)
DANGER
2s
UNINTENDED EQUIPMENT OPERATION
Check that the selected macro configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
StS
v
Std
v
Choice of source configuration.
[Start/Stop] (StS): Start/stop configuration
Identical to the factory configuration apart from the I/O assignments:
• Logic inputs:
- LI1, LI2 (reversing): 2-wire transition detection control, LI1 = run forward, LI2 = run reverse
- LI3 to LI6: Inactive (not assigned)
• Analog inputs:
- AI1: Speed reference 0-10 V
- AI2, AI3: Inactive (not assigned)
• Relay R1: The contact opens in the event of a detected fault (or drive off).
• Relay R2: Inactive (not assigned)
• Analog output AOC: 0-20 mA, inactive (not assigned)
[Factory set.] (Std): Factory configuration (see page 10).
Note: The assignment of [Macro configuration] (CFG) results directly in a return to the selected
configuration.
(1) [Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed from several configuration menus,
but they apply to all menus and parameters.
(2) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
2s
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
43
[MOTOR CONTROL] (drC-) menu
rEFSEt-
Code
drC-
Description
FCS
Adjustment range Factory setting
M [Restore config.]
(1)
[No] (nO)
I-0-
DANGER
CtLFUn-
2s
FLtCOM-
UNINTENDED EQUIPMENT OPERATION
Check that the changes made to the current configuration are compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
SUP-
nO
rECI
v
v
InI
v
[No] (nO): Function inactive.
[Internal] (rEC1): The current configuration becomes identical to the backup configuration previously
saved by [Saving config.] (SCS) = [Config 1] (Str1).
[Internal] (rEC1) is only visible if the backup has been carried out. [Restore config.] (FCS) automatically
switches to [No] (nO) as soon as this action has been performed.
[Config. CFG] (InI): The current configuration is replaced by the configuration selected by the [Macro
configuration] (CFG) parameter (2). [Restore config.] (FCS) automatically switches to [No] (nO) as soon
as this action has been performed.
If the ATV31 remote display terminal option is connected to the drive (3), the following additional selection
options appear, as long as the corresponding files in the remote display terminal's EEPROM memory
have been loaded (0 to 4 files): [File 1] (FIL1), [File 2] (FIL2), [File 3] (FIL3), [File 4] (FIL4). They enable
the current configuration to be replaced with one of the 4 configurations that may be loaded on the remote
display terminal.
[Restore config.] (FCS) automatically switches to [No] (nO) as soon as this action has been performed.
Note: If nAd appears on the display briefly before the parameter switches to [No] (nO), this means that
the configuration transfer is not possible and has not been performed (different drive ratings, for
example). If ntr appears on the display briefly before the parameter switches to [No] (nO), this means
that an invalid configuration transfer has occurred and that the factory settings will need to be restored
using [Config. CFG] (InI).
In both cases, check the configuration to be transferred before trying again.
(1) [Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed from several configuration menus,
but they apply to all menus and parameters.
(2) The following parameters are not modified by this function; they retain their configuration:
- [Standard mot. freq] (bFr), page 39
- [HMI command] (LCC), page 58
- [PIN code 1] (COd), (terminal access code), page 97
- The parameters in the [COMMUNICATION] (COM-) menu
- The parameters in the [MONITORING] (SUP-) menu
(3) Options [File 1] (FIL1) to [File 4] (FIL4) continue to be displayed on the drive, even after the ATV31 remote terminal has been
disconnected.
2s
44
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
[INPUTS / OUTPUTS CFG] (I-O-) menu
rEFSEtdrCI-0-
2-wire/3-wire control
CtLFUnFLtCOMSUP-
Return to factory settings/Restore configuration
The parameters can only be modified when the drive is stopped and no run command is present.
On the optional ATV31 remote display terminal, this menu can be accessed with the switch in the
Code
Description
position.
Adjustment range
M [2/3 wire control]
tCC
Factory setting
[2 wire] (2C)
See page 29.
2s
M [2 wire type]
tCt
[Transition] (trn)
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the changes made to 2-wire control are compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
LEL
trn
v
v
PFO
v
2s
Parameter can be accessed if [2/3 wire control] (tCC) = [2 wire] (2C), page 45.
[Level] (LEL): State 0 or 1 is taken into account for run or stop.
[Transition] (trn): A change of state (transition or edge) is necessary to initiate operation, in order to help
prevent accidental restarts after a break in the power supply.
[Fwd priority] (PFO): State 0 or 1 is taken into account for run or stop, but the "forward" input takes priority
over the "reverse" input.
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
45
[INPUTS / OUTPUTS CFG] (I-O-) menu
rEF-
Code
Description
Adjustment
range
SEtdrC-
rrS
M [Reverse assign.]
I-0-
nO
LI1
LI2
LI3
LI4
LI5
LI6
CtLFUnFLtCOMSUP-
v
v
v
v
v
v
v
Factory setting
[LI2] (LI2)
If [Reverse assign.] (rrS) = [No] (nO), run reverse remains active by means of negative voltage on AI2, for
example.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2 can be accessed if [2/3 wire control] (tCC) = [2 wire] (2C), page 45.
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
CrL3
M [AI3 min. value]
0 to 20 mA
4 mA
CrH3
M [AI3 max. value]
4 to 20 mA
20 mA
These two parameters are used to configure the input for 0-20 mA, 4-20 mA, 20-4 mA, etc.
Frequency
Frequency
Example:
20 - 4 mA
AO1t
M [AO1 Type]
[Current](0A)
This parameter is not visible when a communication card is connected to the product.
0A
4A
10U
dO
v
v
v
[Current] (0A): 0 - 20 mA configuration (use terminal AOC)
[Cur. 4-20] (4A): 4 - 20 mA configuration (use terminal AOC)
[Voltage] (10U): 0 - 10 V configuration (use terminal AOV)
M [Analog./logic output]
[No] (nO)
This parameter is not visible when a communication card is connected to the product.
nO
OCr
OFr
v
v
v
Otr
OPr
v
v
FLt
rUn
FtA
v
v
v
FLA
CtA
v
v
SrA
tSA
v
v
bLC
v
APL
v
[No] (nO): Not assigned
[I motor] (OCr): Motor current. 20 mA or 10 V corresponds to twice the nominal drive current.
[Motor freq.] (OFr): Motor frequency. 20 mA or 10 V corresponds to the maximum frequency [Max
frequency] (tFr), page 42.
[Motor torq.] (Otr): Motor torque. 20 mA or 10 V corresponds to twice the nominal motor torque.
[P. supplied] (OPr): Power supplied by the drive. 20 mA or 10 V corresponds to twice the nominal drive
power.
Making the following assignments (1) will transform the analog output to a logic output (see diagram in the
Installation Manual):
[Drive fault] (FLt): Fault detected
[Drv running] (rUn): Drive running
[Freq. limit] (FtA): Frequency threshold reached ([Freq. threshold] (Ftd) parameter in the [SETTINGS] (SEt-)
menu, page 37)
[HSP limit] (FLA): [High speed] (HSP) reached
[I attained] (CtA): Current threshold reached ([Current threshold] (Ctd) parameter in the
[SETTINGS] (SEt-) menu, page 37)
[Freq. ref.] (SrA): Frequency reference reached
[Drv thermal] (tSA): Motor thermal threshold reached ([Motor therm. level] (ttd) parameter in the
[SETTINGS] (SEt-) menu, page 37)
[Brake seq] (bLC): Brake sequence (for information, as this assignment can only be activated or deactivated
from the [APPLICATION FUNCT.] (FUn-) menu, page 80)
[No 4-20mA] (APL): Loss of 4-20 mA signal, even if [4-20mA loss] (LFL) = [No] (nO), page 90
The logic output is in state 1 (24 V) when the selected assignment is active, with the exception of [Drive
fault] (FLt) (state 1 if the drive operation is normal).
Note: (1) With these assignments, configure [AO1 Type] (AO1t) = [Current] (OA).
46
BBV46385 05/2009
[INPUTS / OUTPUTS CFG] (I-O-) menu
rEF-
Code
Description
Adjustment range
M [R1 Assignment]
r1
nO
FLt
rUn
FtA
v
v
v
v
FLA
CtA
v
v
SrA
tSA
v
v
APL
LI1
to
LI6
r2
nO
FLt
rUn
FtA
v
v
SrA
tSA
v
v
bLC
v
2s
CFG
2s
FCS
2s
[No drive flt]
(FLt)
drCI-0-
This parameter is not visible when a communication card is connected to the product.
CtL-
[No] (nO): Not assigned
[No drive flt] (FLt): No drive detected fault
[Drv running] (rUn): Drive running
[Freq.Th.att.] (FtA): Frequency threshold reached ([Freq. threshold] (Ftd) parameter in the [SETTINGS]
(SEt-) menu, page 37)
[HSP attain.] (FLA): [High speed] (HSP) reached
[I attained] (CtA): Current threshold reached ([Current threshold] (Ctd) parameter in the
[SETTINGS] (SEt-) menu, page 37)
[Freq.ref.att] (SrA): Frequency reference reached
[Th.mot. att.] (tSA): Motor thermal threshold reached ([Motor therm. level] (ttd) parameter in the
[SETTINGS] (SEt-) menu, page 37)
[4-20mA] (APL): Loss of 4-20 mA signal, even if [4-20mA loss] (LFL) = [No] (nO), page 90
[LI1] to [LI6] (LI1) to (LI6): Returns the value of the selected logic input
FUnFLtCOMSUP-
[No] (nO)
M [R2 Assignment]
v [No] (nO): Not assigned
v [No drive flt] (FLt): No drive detected fault
v [Drv running] (rUn): Drive running
v [Freq.Th.att.] (FtA): Frequency threshold reached ([Freq. threshold] (Ftd) parameter in the [SETTINGS]
v
v
SCS
SEt-
The relay is energized when the selected assignment is active, with the exception of [No drive flt] (FLt)
(energized if the drive has not detected a fault).
FLA
CtA
APL
LI1
to
LI6
Factory setting
v
v
(SEt-) menu, page 37)
[HSP attain.] (FLA): [High speed] (HSP) reached
[I attained] (CtA): Current threshold reached ([Current threshold] (Ctd) parameter in the
[SETTINGS] (SEt-) menu, page 37)
[Freq.ref.att] (SrA): Frequency reference reached
[Th.mot. att.] (tSA): Motor thermal threshold reached ([Motor therm. level] (ttd) parameter in the
[SETTINGS] (SEt-) menu, page 37)
[Brk control] (bLC): Brake sequence (for information, as this assignment can only be activated or
deactivated from the [APPLICATION FUNCT.] (FUn-)- menu, page 80)
[4-20mA] (APL): Loss of 4-20 mA signal, even if [4-20mA loss] (LFL) = [No] (nO), page 90
[LI1] to [LI6] (LI1)to (LI6): Returns the value of the selected logic input
The relay is energized when the selected assignment is active, with the exception of [No drive flt] (FLt)
(energized if the drive has not detected a fault).
M [Saving config.] (1)
nO
See page 43.
M [Macro configuration] (1)
Std
See page 43.
M [Restore config.] (1)
nO
See page 44.
(1) [Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed from several configuration menus,
but they apply to all menus and parameters.
2s
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
47
[COMMAND] (CtL-) menu
rEFSEtdrCI-0-
Function access level
CtLFUnFLtCOM-
Return to factory settings/Restore configuration
SUP-
The parameters can only be modified when the drive is stopped and no run command is present.
On the optional remote display terminal, this menu can be accessed with the switch in the
position.
Control and reference channels
Run commands (forward, reverse, etc.) and references can be sent using the following channels:
Command CMD
tEr: Terminals (LI.)
LCC: Remote display terminal (RJ45 socket)
LOC: Control via the keypad
Mdb: Modbus (RJ45 socket)
nEt: Network
Reference rFr
AIx: Terminals
LCC: ATV312 keypad or remote display terminal
AIV1: Jog dial
Mdb: Modbus (RJ45 socket)
nEt: Network
WARNING
LOSS OF CONTROL
The stop buttons on the ATV312 (integrated into the drive and on the remote terminals) can be programmed as non-priority buttons. A
stop button can only have priority if the [Stop Key priority] (PSt) parameter in the [COMMAND] (CtL-) menu, page 59, is set to [Yes] (YES).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The [ACCESS LEVEL] (LAC) parameter in the [COMMAND] (CtL-) menu, page 56, can be used to select priority modes for the control and
reference channels. It has 3 function levels:
• [ACCESS LEVEL] (LAC) = Basic functions. The channels are managed in order of priority.
[Level 1] (L1):
• [ACCESS LEVEL] (LAC) = Provides the option of additional functions compared with [Level 1] (L1):
[Level 2] (L2):
- +/- speed (motorized jog dial)
- Brake control
- 2nd current limit switching
- Motor switching
- Management of limit switches
• [ACCESS LEVEL] (LAC) = Same functions as with [Level 2] (L2). Management of the control and reference channels is
[Level 3] (L3):
configurable.
48
BBV46385 05/2009
[COMMAND] (CtL-) menu
rEF-
These channels can be combined in order of priority if [ACCESS LEVEL] (LAC) = [Level 1] (L1) or
[Level 2] (L2).
SEt-
Highest priority to lowest priority: Forced local mode, Network, Modbus, Remote display terminal, Terminals/Keypad (from right to left in the drCdiagram below)
I-0CtLFUn-
Terminals/Keypad
FLtCOM-
Remote display terminal
Network
SUP-
Forced local mode
See the detailed block diagrams on pages 51 and 52.
• On ATV312 drives, in factory settings mode, control and reference are managed by the terminals.
• With a remote terminal display, if [HMI command] (LCC) = [Yes] (YES) ([COMMAND] (CtL-) menu), control and reference are managed
by the remote terminal display (reference via [HMI Frequency ref.] (LFr) in the [SETTINGS] (SEt-) menu).
The channels can be combined by configuration if [ACCESS LEVEL] (LAC) = [Level 3] (L3).
Combined control and reference ([Profile] (CHCF) parameter = [Not separ.] (SIM)):
Selection of reference channel:
[Ref.1 channel] (Fr1) parameter
The control channel is
connected to the same
source.
Control and reference
Selection of reference
channel:
[Ref.2 channel] (Fr2)
parameter
The control channel is
connected to the same source.
The [Ref. 2 switching] (rFC) parameter can be used to select the [Ref.1 channel] (Fr1) or [Ref.2 channel] (Fr2) channel, or to configure a
logic input or a control word bit for remote switching of either one.
See the detailed block diagrams on pages 53 and 55.
BBV46385 05/2009
49
[COMMAND] (CtL-) menu
rEF-
Separate control and reference ([Profile] (CHCF) parameter = [Separate] (SEP)):
SEt-
Reference
drC-
Selection of reference
channel:
[Ref.1 channel] (Fr1)
parameter
I-0CtL-
Reference
FUnFLt-
Selection of reference
channel:
[Ref.2 channel] (Fr2)
parameter
COMSUP-
The [Ref. 2 switching] (rFC) parameter can be used to select the [Ref.1 channel] (Fr1) or [Ref.2 channel] (Fr2) channel, or to configure a
logic input or a control word bit for remote switching of either one.
Control
Selection of control
channel: [Cmd channel 1]
(Cd1) parameter
Control
Selection of control
channel:
[Cmd channel 2] (Cd2)
parameter
The [Cmd switching] (CCS) parameter, page 58, can be used to select the [Cmd channel 1] (Cd1) or [Cmd channel 2] (Cd2) channel, or
to configure a logic input or a control bit for remote switching of either one.
See the detailed block diagrams on pages 53 and 54.
50
BBV46385 05/2009
[COMMAND] (CtL-) menu
Reference channel for [ACCESS LEVEL] (LAC) = [Level 1] (L1) or [Level 2] (L2)
rEFSEtdrCI-0-
Note: In order to configure the +/- speed command ([Ref.1 channel]
(Fr1) = [+/- SPEED] (UPdt) or [+/-spd HMI] (UPdH)), the SA2/SA3
summing inputs and the preset speeds must be deconfigured
beforehand.
+
speed
speed
CtLFUnFLtCOMSUP-
Remote display
terminal
Preset speeds
Jog
operation
PI not assigned
PI function
see page 75
+
speed
speed
Reference B
Ramps
Channel 2
Reference A
Channel 1
PI assigned
Network
Forced local mode
"Modbus" or "Network" is selected online by
writing the appropriate control word (see the
specific bus documentation).
Key:
Parameter:
The black square represents the
factory setting assignment.
Function can be accessed for
[ACCESS LEVEL] (LAC) = [Level 2] (L2)
BBV46385 05/2009
51
[COMMAND] (CtL-) menu
rEF-
Control channel for [ACCESS LEVEL] (LAC) = [Level 1] (L1) or [Level 2] (L2)
SEtdrC-
The [Forced local assign.] (FLO) parameter, page 93, the [HMI command] (LCC) parameter, page 58, and the selection of the Modbus bus
I-0- or network are common to the reference and control channels.
Example: If [HMI command] (LCC) = [Yes] (YES), the command and reference are given by the remote display terminal.
CtLFUnFLtCOMSUP-
Forward
Reverse
STOP
Network
Keypad
Remote display
terminal
Keypad
Remote display terminal
(Stop Key
priority)
Key:
Parameter:
The black square represents
the factory setting assignment
52
BBV46385 05/2009
[COMMAND] (CtL-) menu
rEF-
Reference channel for [ACCESS LEVEL] (LAC) = [Level 3] (L3)
+
speed
Note: In order to configure the +/- speed command ([Ref.1 channel] (Fr1) = [+/- SPEED]
(UPdt) or [+/-spd HMI] (UPdH)), the SA2/SA3 summing inputs and the preset speeds must
be deconfigured beforehand.
SEtdrCI-0CtL-
speed
FUnFLtCOM-
Preset speeds
SUP-
Remote
display
terminal
Jog
operation
PI not assigned
Note:
Jog operation is only
active when the
reference and control
are managed by the
terminals (ALp and LIp).
PI assigned
Channel 1
Ramps
Channel 2
Remote
display
terminal
Forced local mode
Reference A
PI function
see page 75
Remote
display
terminal
+
speed
Reference B
speed
Key:
Parameter:
The black square represents the
factory setting assignment.
Remote
display
terminal
BBV46385 05/2009
53
[COMMAND] (CtL-) menu
rEFSEtdrC-
Control channel for [ACCESS LEVEL] (LAC) = [Level 3] (L3)
Combined reference and control
The [Ref.1 channel] (Fr1) parameter, page 56, the [Ref.2 channel] (Fr2) parameter, page 56, the [Ref. 2 switching] (rFC) parameter, page
57, the [Forced local assign.] (FLO) parameter, page 93, and the [Forced local Ref.] (FLOC) parameter, page 93, are common to reference
and
control. The control channel is therefore determined by the reference channel.
CtLExample: If the [Ref.1 channel] (Fr1) reference = [AI1] (AI1) (analog input at the terminals), control is via LI (logic input at the terminals).
I-0-
FUnFLtCOMSUP-
Keypad
Remote display terminal
Forced local mode
Keypad
Forward
Reverse
STOP
(Stop Key priority)
Remote display terminal
Keypad
Remote display
terminal
54
Key:
Parameter:
The black square represents
the factory setting assignment.
BBV46385 05/2009
[COMMAND] (CtL-) menu
rEF-
Control channel for [ACCESS LEVEL] (LAC) = [Level 3] (L3)
SEt-
Mixed mode (separate reference and control)
drC-
The [Forced local assign.] (FLO) parameter, page 93, and the [Forced local Ref.] (FLOC) parameter, page 93, are common to reference
I-0and control.
Example: If the reference is in forced local mode via [AI1] (AI1) (analog input at the terminals), control in forced local mode is via LI (logic CtLinput at the terminals).
FUnFLtCOMSUP-
Keypad
Remote display terminal
Forced local
mode
Keypad
Forward
Reverse
STOP
(Stop Key
priority)
Remote display terminal
Keypad
Remote display terminal
Key:
Parameter:
The black square represents
the factory setting assignment.
BBV46385 05/2009
55
[COMMAND] (CtL-) menu
rEF-
Note: There may be an incompatibility between functions (see the incompatibility table, page 20). In this case, the first function configured
SEt- will prevent the remainder being configured.
drC-
Code
Description
Adjustment
range
I-0CtL-
M [ACCESS LEVEL]
LAC
Factory setting
[Level 1] (L1)
FUn-
DANGER
FLt-
UNINTENDED EQUIPMENT OPERATION
COM-
• Assigning [ACCESS LEVEL] (LAC) to [Level 3] (L3) will restore the factory settings of the [Ref.1 channel] (Fr1)
parameter, page 56, the [Cmd channel 1] (Cd1) parameter, page 57, the [Profile] (CHCF) parameter, page 57, and
the [2/3 wire control] (tCC) parameter, page 45.
• [Level 3] (L3) can only be restored to [Level 2] (L2) or [Level 1] (L1), and [Level 2] (L2) can only be restored to [Level
1] (L1) by means of a "factory setting" via [Restore config.] (FCS), page 44.
• Check that this change is compatible with the wiring diagram used.
2s
SUP-
Failure to follow these instructions will result in death or serious injury.
L1
L2
v
v
L3
v
[Level 1] (L1): Access to standard functions and channel management in order of priority.
[Level 2] (L2):Access to advanced functions in the [APPLICATION FUNCT.] (FUn-) menu:
- - +/- speed (motorized jog dial)
- Brake control
- 2nd current limit switching
- Motor switching
- Management of limit switches
[Level 3] (L3): Access to advanced functions and management of mixed control modes
M [Ref.1 channel]
Fr1
[AI1] (AI1)
See page 28.
Fr2
nO
AI1
AI2
AI3
AIU1
M [Ref.2 channel]
v [No] (nO): Not assigned
v [AI1] (AI1): Analog input AI1
v [AI2] (AI2): Analog input AI2
v [AI3] (AI3): Analog input AI3
v [Network AI] (AIV1): Jog dial
UPdt
UpdH
v
v
LCC
v
Ndb
nEt
v
v
[No] (nO)
If [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), the following additional assignments are
possible:
[+/-Speed] (UPdt): (1) +/- speed reference via LI. See configuration page 74.
[+/-spd HMI] (UPdH): (1) +/- speed reference via the jog dial on the ATV312 keypad.
To use, display the frequency [Output frequency] (rFr), page 95. The +/- speed function via the keypad or
the terminal is controlled from the [MONITORING] (SUP-) menu by selecting the [Output frequency] (rFr)
parameter.
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following additional assignments are possible:
[HMI] (LCC): Reference via the remote display terminal, [HMI Frequency ref.] (LFr) parameter in the
[SETTINGS] (SEt-) menu, page 31.
[Modbus] (Mdb): Reference via Modbus
[Network] (nEt): Reference via network
(1) NOTE:
• It is not possible to simultaneously assign [+/- SPEED] (UPdt) to [Ref.1 channel] (Fr1) or [Ref.2 channel] (Fr2), and [+/-spd HMI]
(UPdH) to [Ref.1 channel] (Fr1) or [Ref.2 channel] (Fr2). Only one of the [+/- SPEED] (UPdt)/[+/-spd HMI] (UPdH) assignments is
permitted on each reference channel.
• The +/- speed function in [Ref.1 channel] (Fr1) is incompatible with several functions (see page 20). It can only be configured if these
functions are unassigned, in particular the summing inputs (set [Summing ref. 2] (SA2) to [No] (nO), page 67) and the preset speeds
(set [2 preset speeds] (PS2) and [4 preset speeds] (PS4) to [No] (nO), page 69) which will have been assigned as part of the factory
settings.
• In [Ref.2 channel] (Fr2), the +/- speed function is compatible with the preset speeds, summing inputs, and the PI regulator.
2s
56
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
[COMMAND] (CtL-) menu
rEF-
Code
Description
Adjustment
range
M [Ref. 2 switching]
rFC
SEt-
Factory setting
drC-
[ch1 active] (Fr1)
Fr1
Fr2
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
v
The [Ref. 2 switching] (rFC) parameter can be used to select the [Ref.1 channel] (Fr1) or [Ref.2 channel] (Fr2)
channel, or to configure a logic input or a control word bit for remote switching of [Ref.1 channel] (Fr1) or [Ref.2
channel] (Fr2).
[ch1 active] (Fr1): Reference = reference 1
[ch1 active] (Fr2): Reference = reference 2
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
C111
C112
C113
C114
C115
C211
C212
C213
C214
C215
v
v
v
v
v
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following additional assignments are possible:
[C111] (C111): Bit 11 of Modbus control word
[C112] (C112): Bit 12 of Modbus control word
[C113] (C113): Bit 13 of Modbus control word
[C114] (C114): Bit 14 of Modbus control word
[C115] (C115): Bit 15 of Modbus control word
[C211] (C211): Bit 11 of network control word
[C212] (C212): Bit 12 of network control word
[C213] (C213): Bit 13 of network control word
[C214] (C214): Bit 14 of network control word
[C215] (C215): Bit 15 of network control word
I-0CtLFUnFLtCOMSUP-
The reference can be switched with the drive running.
[Ref.1 channel] (Fr1) is active when the logic input or control word bit is at state 0.
[Ref.2 channel] (Fr2) is active when the logic input or control word bit is at state 1.
M [Profile]
CHCF
[Not separ.] (SIM)
(control channels separated from reference channels)
v
v
SIN
SEP
M [Cmd channel 1]
Cd1
g
v
v
v
v
v
tEr
LOC
LCC
Ndb
nEt
g
v
v
v
v
v
tEr
LOC
LCC
Ndb
nEt
[Terminal] (tEr)
Parameter can be accessed if [Profile] (CHCF) = [Separate] (SEP), page 57, and [ACCESS LEVEL] (LAC) =
[Level 3] (L3), page 56.
[Terminal] (tEr): Control via terminals
[Local] (LOC): Control via keypad
[Remot. HMI] (LCC): Control via remote display terminal
[Modbus] (Mdb): Control via Modbus
[Network] (nEt): Control via the network
M [Cmd channel 2]
Cd2
g
Parameter can be accessed if [ACCESS LEVEL] (LAC) = [Level 3] (L3), page 56.
[Not separ.] (SIM): Combined
[Separate] (SEP): Separate
[Modbus] (Mdb)
Parameter can be accessed if [Profile] (CHCF) = [Separate] (SEP), page 57, and [ACCESS LEVEL] (LAC) =
[Level 3] (L3), page 56.
[Terminal] (tEr): Control via terminals
[Local] (LOC): Control via keypad
[Remot. HMI] (LCC): Control via remote display terminal
[Modbus] (Mdb): Control via Modbus
[Network] (nEt): Control via the network
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
57
[COMMAND] (CtL-) menu
rEF-
Code
SEt-
Description
M [Cmd switching]
CCS
drCI-0-
g
CtLFUn-
Cd1
Cd2
LI1
LI2
LI3
LI4
LI5
LI6
C111
C112
C113
C114
C115
C211
C212
C213
C214
C215
FLtCOMSUP-
Adjustment range
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
Factory setting
[ch1 active]
(Cd1)
Parameter can be accessed if [Profile] (CHCF) = [Separate] (SEP), page 57, and [ACCESS LEVEL] (LAC)
= [Level 3] (L3), page 56.
The [Cmd switching] (CCS) parameter can be used to select the [Cmd channel 1] (Cd1) or [Cmd channel
2] (Cd2) channel, or to configure a logic input or a control word bit for remote switching of [Cmd channel 1]
(Cd1) or [Cmd channel 2] (Cd2).
[ch1 active] (Cd1): Control channel = channel 1
[ch2 active] (Cd2): Control channel = channel 2
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
[C111] (C111): Bit 11 of Modbus control word
[C112] (C112): Bit 12 of Modbus control word
[C113] (C113): Bit 13 of Modbus control word
[C114] (C114): Bit 14 of Modbus control word
[C115] (C115): Bit 15 of Modbus control word
[C211] (C211): Bit 11 of network control word
[C212] (C212): Bit 12 of network control word
[C213] (C213): Bit 13 of network control word
[C214] (C214): Bit 14 of network control word
[C215] (C215): Bit 15 of network control word
Channel 1 is active when the input or control word bit is at state 0,
Channel 2 is active when the input or control word bit is at state 1.
M [Copy channel 1<>2]
COp
[No] (nO)
(copy only in this direction)
nO
SP
Cd
ALL
v
v
v
v
Parameter can be accessed if [ACCESS LEVEL] (LAC) = [Level 3] (L3), page 56.
[No] (nO): No copy
[Reference] (SP): Copy reference
[Command] (Cd): Copy control
[Cmd + ref.] (ALL): Copy control and reference
• If channel 2 is controlled via the terminals, channel 1 control is not copied.
• If the channel 2 reference is set via AI1, AI2, AI3 or AIU1, the channel 1 reference is not copied.
• The reference copied is [Frequency ref.] (FrH) (before ramp), unless the channel 2 reference is set
via +/- speed.
In this case, the reference copied is [Output frequency] (rFr) (after ramp).
Note: Copying the control and/or reference can change the direction of rotation.
M [HMI command]
LCC
nO
YES
g
58
v
v
[No] (nO)
Parameter can only be accessed using a remote display terminal, and for [ACCESS LEVEL] (LAC) = [Level
1] (L1) or [Level 2] (L2), page 56.
[No] (nO): Function inactive
[Yes] (YES): Enables control of the drive using the STOP/RESET, RUN and FWD/REV buttons on the
display terminal. Here, the speed reference is given by the [HMI Frequency ref.] (LFr) parameter in the
[SETTINGS] (SEt-) menu. Only the freewheel stop, fast stop and DC injection stop commands remain active
on the terminals. If the drive/terminal connection is cut or if the terminal has not been connected, the drive
detects a fault and locks in [MODBUS FAULT] (SLF).
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[COMMAND] (CtL-) menu
rEF-
Code
Description
Adjustment
range
M [Stop Key priority]
PSt
Factory setting
SEtdrC-
[Yes] (YES)
I-0-
This parameter can be used to activate or deactivate the stop button on the drive and the remote terminals. The
stop button will be deactivated if the active control channel is different from that on the integrated display terminal or
remote terminals.
CtLFUnFLt-
WARNING
2s
COM-
LOSS OF CONTROL
SUP-
Only set [Stop Key priority] (PSt) to [No] (nO) if there is an external method of stop control.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
nO
YES
v
v
[No] (nO): Function inactive
[Yes] (YES): STOP key priority
M [Rotating direction]
rOt
[Forward] (dFr)
This parameter is only visible if [Ref.1 channel] (Fr1), page 28, or [Ref.2 channel] (Fr2), page 56, are
assigned to LCC or AI1.
dFr
drS
bOt
M [Saving config.]
SCS
2s
2s
2s
nO
(1)
Std
(1)
nO
See page 43.
M [Restore config.]
FCS
(1)
See page 43.
M [Macro configuration]
CFG
2s
v
v
v
Direction of operation authorized for the RUN key on the keypad or the RUN key on the remote display
terminal.
[Forward] (dFr): Forward
[Reverse] (drS): Reverse
[Both] (bOt): Both directions are authorized.
See page 44.
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
(1) [Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed from several configuration menus,
but they apply to all menus and parameters.
BBV46385 05/2009
59
[APPLICATION FUNCT.] (FUn-) menu
rEFSEtdrCI-0CtL-
Submenu
FUnFLtCOM-
Submenu
SUP-
The parameters can only be modified when the drive is stopped and no run command is present.
On the optional remote display terminal, this menu can be accessed with the switch in the
position.
Some functions have numerous parameters. In order to clarify programming and avoid having to scroll through endless parameters, these
functions have been grouped in submenus.
PSSLike menus, submenus are identified by a dash after their code:
for example.
Note: There may be an incompatibility between functions (see the incompatibility table, page 20). In this case, the first function configured
will prevent the remainder being configured.
Code
Name/Description
b
rPCrPt
LIn
S
U
CUS
Adjustment range
Factory setting
[RAMPS]
M [Ramp type]
v
v
v
v
[Linear] (LIn)
Defines the shape of the acceleration and deceleration ramps
[Linear] (LIn): Linear
[S ramp] (S): S ramp
[U ramp] (U): U ramp
[Customized] (CUS): Customized
S ramps
f (Hz)
f (Hz)
GV
The rounding coefficient is fixed,
where t2 = 0.6 x t1
and t1 = set ramp time.
GV
0
t
t2
0
t
t2
t1
t1
U ramps
f (Hz)
f (Hz)
GV
GV
0
t2
t
The rounding coefficient is fixed,
where t2 = 0.5 x t1
and t1 = set ramp time.
0
t2
t1
t
t1
Customized ramps
f (Hz)
f (Hz)
GV
0
tA1
GV
tA2
ACC ou AC2
60
t
0
tA3
tA4
t
tA1: Adjustable from 0 to 100% (of ACC or AC2)
tA2: Adjustable from 0 to (100% - tA1) (of ACC or AC2)
tA3: Adjustable from 0 to 100% (of dEC or dE2)
tA4: Adjustable from 0 to (100% - tA3) (of dEC or dE2)
dEC ou dE2
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
rPC-
Adjustment range
g
drC-
[RAMPS] (continued)
I-0-
M [Begin Acc round]
tA1
SEt-
Factory
setting
0 to 100
CtL-
10
FUn-
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [End Acc round]
tA2
g
0 to (100-tA1)
FLt-
10
COM-
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [Begin Dec round]
tA3
g
0 to 100
SUP-
10
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
M [End Dec round]
tA4
g
0 to (100-tA3)
10
Parameter can be accessed if the [Ramp type] (rPt) = [Customized] (CUS), page 60.
Inr
0.01
0.1
1
M [Ramp increment]
v [0.01] (0.01): Ramp can be set between 0.05 s and 327.6 s.
v [0.1] (0.1): Ramp can be set between 0.1 s and 3,276 s.
v [1] (1): Ramp can be set between 1 s and 32,760 s (1).
0.01 - 0.1 - 1
0.1
This parameter applies to the [Acceleration] (ACC), [Deceleration] (dEC), [Acceleration 2] (AC2), and
[Deceleration 2] (dE2) parameters.
Note: Changing the [Ramp increment] (Inr) parameter causes the settings for the [Acceleration] (ACC),
[Deceleration] (dEC), [Acceleration 2] (AC2), and [Deceleration 2] (dE2) parameters to be modified as well.
M [Acceleration]
M [Deceleration]
ACC
dEC
(2)
In accordance with
Inr, page 61
3s
3s
Defined to accelerate/decelerate between 0 and the nominal frequency [Rated motor freq.] (FrS)
(parameter in the [MOTOR CONTROL] (drC-) menu).
Check that the value for [Deceleration] (dEC) is not too low in relation to the load to be stopped.
(1) When values higher than 9,999 are displayed on the drive or on the remote display terminal, a point is inserted after the thousands digit.
Note:
This type of display can lead to confusion between values which have two digits after a decimal point and values higher than 9,999. Check
the value of the [Ramp increment] (Inr) parameter.
Example:
- If [Ramp increment] (Inr) = 0.01, the value 15.65 corresponds to a setting of 15.65 s.
- If [Ramp increment] (Inr) = 1, the value 15.65 corresponds to a setting of 15,650 s.
(2) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
61
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
Adjustment range
drCI-0-
b
rPC-
CtL-
[RAMPS] (continued)
M [Ramp switch ass.]
rPS
FUn-
[No] (nO)
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
This function remains active regardless of the control channel.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
FLtCOMSUP-
Factory
setting
[Acceleration] (ACC) and [Deceleration] (dEC) are enabled when the logic input or control word bit is at state 0.
[Acceleration 2] (AC2) and [Deceleration 2] (dE2) are enabled when the logic input or control word bit is at
state 1.
M [Ramp 2 threshold]
Frt
0 to 500 Hz
0 Hz
The 2nd ramp is switched if [Ramp 2 threshold]] (Frt) is not 0 (the value 0 corresponds to the inactive
function) and the output frequency is higher than [Ramp 2 threshold]] (Frt).
Threshold ramp switching can be combined with switching via LI or bit as follows:
LI or bit
Frequency
Ramp
0
0
1
1
<Frt
>Frt
<Frt
>Frt
ACC, dEC
AC2, dE2
AC2, dE2
AC2, dE2
M [Acceleration 2]
AC2
(1)
In accordance with
Inr, page 61
5
Parameter can be accessed if [Ramp 2 threshold] (Frt) > 0, page 62, or if [Ramp switch ass.] (rPS) is
assigned, page 62.
g
M [Deceleration 2]
dE2
(1)
In accordance with
Inr, page 61
5
Parameter can be accessed if [Ramp 2 threshold] (Frt) > 0, page 62, or if [Ramp switch ass.] (rPS) is
assigned, page 62.
g
M [Dec ramp adapt.]
brA
nO
YES
v
v
[Yes] (YES)
Activating this function automatically adapts the deceleration ramp, if this has been set at too low a value
for the inertia of the load.
[No] (nO): Function inactive
[Yes] (YES): Function active. The function is incompatible with applications requiring:
• Positioning on a ramp
• The use of a braking resistor (the resistor would not operate correctly)
[Dec ramp adapt.] (brA) is forced to [No] (nO) if brake control [Brake assignment] (bLC) is assigned, page 80.
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
g
62
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
StC-
Adjustment
range
rMP
FSt
nSt
dCI
FSt
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
drC-
[STOP MODES]
I-0-
M [Type of stop]
Stt
SEt-
Factory
setting
v
v
v
v
FUnFLt-
Stop mode on disappearance of the run command or appearance of a stop command.
[Ramp stop] (rMP): On ramp
[Fast stop] (FSt): Fast stop
[Freewheel] (nST): Freewheel stop
[DC injection] (dCI): DC injection stop
M [Fast stop]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
v
v
v
v
v
CtL-
[Ramp stop]
(rMP)
COMSUP-
[No] (nO)
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
The stop is activated when the logic state of the input changes to 0 and the control word bit changes to 1.
The fast stop is a stop on a reduced ramp via the [Ramp divider] (dCF) parameter. If the input falls back
to state 1 and the run command is still active, the motor will only restart if 2-wire level control has been
configured [2/3 wire control] (tCC) = [2 wire] (2C), and [2 wire type] (tCt) = [Level] (LEL) or [Fwd priority]
(PFO), page 45). In other cases, a new run command must be sent.
M [Ramp divider]
dCF
0 to 10
4
Parameter can be accessed where [Type of stop] (Stt) = [Fast stop] (FSt), page 63, and where [Fast stop]
(FSt) is not [No] (nO), page 63.
Ensure that the reduced ramp is not too low in relation to the load to be stopped.
The value 0 corresponds to the minimum ramp.
g
M [DC injection assign.]
dCI
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Note: This function is incompatible with the "Brake control" function (see page 20).
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
[No] (nO)
Braking is activated when the logic state of the input or control word bit is at 1.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
63
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
drCI-0-
b
StC-
CtL-
COM-
(1)(3)
M [DC injection time 2]
tdC
SUP-
(1)(3)
0 to In (2)
0.7 In (2)
Parameter can be accessed if [Type of stop] (Stt) = [DC injection] (dCI), page 63, or if [DC injection assign.]
(dCI) is not set to [No] (nO), page 63.
After 5 seconds, the injection current is limited to 0.5 [Mot. therm. current] (ItH) if set to a higher value.
g
FLt-
Factory
setting
[STOP MODES] (continued)
M [DC inject. level 1]
IdC
FUn-
Adjustment
range
g
0.1 to 30 s
0.5 s
Parameter can be accessed if [Type of stop] (Stt) = [DC injection] (dCI) , page 63.
nSt
nO
LI1
LI2
LI3
LI4
LI5
LI6
M [Freewheel stop ass.]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
[No] (nO)
The stop is activated when the logic state of the input is at 0. If the input falls back to state 1 and the run
command is still active, the motor will only restart if 2-wire level control has been configured. In other cases,
a new run command must be sent.
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
(3) Note: These settings are not related to the "automatic standstill DC injection" function.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
WARNING
NO HOLDING TORQUE
• DC injection braking does not provide any holding torque at zero speed.
• DC injection braking does not work when there is a loss of power or when the drive detects a fault.
• Where necessary, use a separate brake to maintain torque levels.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
CAUTION
RISK OF DAMAGE TO MOTOR
• Long periods of DC injection braking can cause overheating and damage the motor.
• Protect the motor by avoiding long periods of DC injection braking.
Failure to follow these instructions can result in equipment damage.
64
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
AdC-
Adjustment
range
drC-
[AUTO DC INJECTION]
I-0-
M [Auto DC injection]
AdC
SEt-
Factory
setting
CtL-
[Yes] (YES)
FUn-
If set to [Continuous] (Ct), this parameter causes injection current to be generated, even when there is no run
command. This parameter can be changed at any time.
FLt-
DANGER
COM-
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
SUP-
Do not work on the motor during DC injection.
Failure to follow these instructions will result in death or serious injury.
nO
YES
Ct
tdC1
g
v
v
v
[No] (nO): No injection
[Yes] (YES): Standstill injection for adjustable period
[Continuous] (Ct): Continuous standstill injection
M [Auto DC inj. time 1]
(1)
0.1 to 30 s
0.5 s
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
SdC1
M [Auto DC inj. level 1]
(1)
0 to 1.2 In (2)
0.7 In (2)
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
Note: Check that the motor will withstand this current without overheating.
g
tdC2
g
M [Auto DC inj. time 2]
(1)
0 to 30 s
0s
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
65
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
drCI-0-
b
AdC-
CtL-
SdC2
FUn-
g
FLt-
Adjustment
range
Factory
setting
0 to 1.2 In (2)
0.5 In (2)
[AUTO DC INJECTION] (continued)
M [Auto DC inj. level 2]
(1)
Parameter can be accessed if [Auto DC injection] (AdC) is not set to [No] (nO), page 65.
Note: Check that the motor will withstand this current without overheating.
COMSUP-
AdC
SdC2
YES
x
Ct
≠0
Ct
=0
Operation
Run command
Speed
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
66
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
SAI-
Adjustment
range
SEt-
Factory
setting
drC-
[SUMMING INPUTS]
I-0-
Can be used to sum one or two inputs to the [Ref.1 channel] (Fr1) reference only.
Note: The "Summing inputs" function may be incompatible with other functions (see page 20).
SA2
nO
AI1
AI2
AI3
AIU1
M [Summing ref. 2]
v [No] (nO): Not assigned
v [AI1] (AI1): Analog input AI1
v [AI2] (AI2): Analog input AI2
v [AI3] (AI3): Analog input AI3
v [Network AI] (AIV1): Jog dial
LCC
v
Ndb
nEt
v
v
SA3
nO
AI1
AI2
AI3
AIU1
v
Ndb
nEt
v
v
FUn-
[AI2] (AI2)
FLtCOMSUP-
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[HMI] (LCC): Reference via the remote display terminal, [HMI Frequency ref.] (LFr) parameter in the
[SETTINGS] (SEt-) menu, page 31.
[Modbus] (Mdb): Reference via Modbus
[Network] (nEt): Reference via network
M [Summing ref. 3]
v [No] (nO): Not assigned
v [AI1] (AI1): Analog input AI1
v [AI2] (AI2): Analog input AI2
v [AI3] (AI3): Analog input AI3
v [Network AI] (AIV1): Jog dial
LCC
CtL-
[No] (nO)
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[HMI] (LCC): Reference via the remote display terminal, [HMI Frequency ref.] (LFr) parameter in the
[SETTINGS] (SEt-) menu, page 31.
[Modbus] (Mdb): Reference via Modbus
[Network] (nEt): Reference via network
Summing inputs
Note:
AI2 is a ± 10 V input which can be used for subtraction by summing
a negative signal.
See the complete block diagrams on pages 51 and 53.
BBV46385 05/2009
67
[APPLICATION FUNCT.] (FUn-) menu
rEFSEtdrCI-0-
Preset speeds
2, 4, 8 or 16 speeds can be preset, requiring 1, 2, 3 or 4 logic inputs respectively.
The following assignment order must be observed: [2 preset speeds] (PS2), then [4 preset speeds] (PS4), then [8 preset speeds] (PS8),
then [16 preset speeds] (PS16).
FUnCtL-
FLt-
Combination table for preset speed inputs
COMSUP-
16 speeds
LI (PS16)
8 speeds
LI (PS8)
4 speeds
LI (PS4)
2 speeds
LI (PS2)
Speed reference
0
0
0
0
Reference (1)
0
0
0
1
SP2
0
0
1
0
SP3
0
0
1
1
SP4
0
1
0
0
SP5
0
1
0
1
SP6
0
1
1
0
SP7
0
1
1
1
SP8
1
0
0
0
SP9
1
0
0
1
SP10
1
0
1
0
SP11
1
0
1
1
SP12
1
1
0
0
SP13
1
1
0
1
SP14
1
1
1
0
SP15
1
1
1
1
SP16
(1) See the block diagrams on page 51 and page 53: Reference 1 = (SP1).
68
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
PSS-
Name/Description
b
Adjustment
range
SEt-
Factory setting
drC-
[PRESET SPEEDS]
I-0CtL-
Note: The "Preset speeds" function may be incompatible with other functions (see page 20).
PS2
M [2 preset speeds]
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Selecting the assigned logic input activates the function.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
PS4
M [4 preset speeds]
FLtCOMSUP-
[LI4] (LI4)
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Selecting the assigned logic input activates the function.
Ensure that [2 preset speeds] (PS2) has been assigned before assigning [4 preset speeds] (PS4).
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
PS8
M [8 preset speeds]
[No] (nO)
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Selecting the assigned logic input activates the function.
Ensure that [4 preset speeds] (PS4) has been assigned before assigning [8 preset speeds] (PS8).
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
BBV46385 05/2009
FUn-
[LI3] (LI3)
69
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
Adjustment
range
drCI-0-
b
PSS-
CtL-
PS16
FUn-
Factory
setting
[PRESET SPEEDS] (continued)
M [16 preset speeds]
[No] (nO)
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Selecting the assigned logic input activates the function.
Ensure that [8 preset speeds] (PS8) has been assigned before assigning [16 preset speeds] (PS16).
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
FLtCOMSUP-
SP2
M [Preset speed 2]
(1)
0.0 to 500.0 Hz (2) 10 Hz
SP3
M [Preset speed 3]
(1)
0.0 to 500.0 Hz (2) 15 Hz
SP4
M [Preset speed 4]
(1)
0.0 to 500.0 Hz (2) 20 Hz
SP5
M [Preset speed 5]
(1)
0.0 to 500.0 Hz (2) 25 Hz
SP6
M [Preset speed 6]
(1)
0.0 to 500.0 Hz (2) 30 Hz
SP7
M [Preset speed 7]
(1)
0.0 to 500.0 Hz (2) 35 Hz
SP8
M [Preset speed 8]
(1)
0.0 to 500.0 Hz (2) 40 Hz
SP9
M [Preset speed 9]
(1)
0.0 to 500.0 Hz (2) 45 Hz
M [Preset speed 10]
(1)
0.0 to 500.0 Hz (2) 50 Hz
g
g
g
g
g
g
g
g
SP10
g
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu. This parameter will depend on how many speeds have been
configured.
(2) Reminder: The speed remains limited by the [High speed] (HSP) parameter, page 32.
g
70
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
PSS-
Adjustment
range
drC-
[PRESET SPEEDS] (continued)
I-0-
SP11
M [Preset speed 11]
(1)
SP12
M [Preset speed 12]
(1)
0.0 to 500.0 Hz (2) 60 Hz
SP13
M [Preset speed 13]
(1)
0.0 to 500.0 Hz (2) 70 Hz
SP14
M [Preset speed 14]
(1)
0.0 to 500.0 Hz (2) 80 Hz
SP15
M [Preset speed 15]
(1)
0.0 to 500.0 Hz (2) 90 Hz
SP16
M [Preset speed 16]
(1)
0.0 to 500.0 Hz (2) 100 Hz
g
SEt-
Factory
setting
CtL-
0.0 to 500.0 Hz (2) 55 Hz
FUnFLt-
g
COMSUP-
g
g
g
g
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu. This parameter will depend on how many speeds have been
configured.
(2) Reminder: The speed remains limited by the [High speed] (HSP) parameter, page 32.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
71
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
Adjustment
range
drCI-0-
b
JOG-
Factory setting
[JOG]
Note: The "Jog operation" function may be incompatible with other functions (see page 20).
CtLFUn-
M [JOG]
JOG
FLt-
nO
LI1
LI2
LI3
LI4
LI5
LI6
COMSUP-
v
v
v
v
v
v
v
[No] (nO)
Selecting the assigned logic input activates the function.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Example: 2-wire control operation ([2/3 wire control] (tCC) = [2 wire] (2C))
Motor
frequency
Ramp dEC/dE2 Ramp forced to 0.1 s
Reference
JGF reference
JGF reference
LI (JOG)
u 0.5 s
Forward
Reverse
JGF
g
M [Jog frequency] (1)
0 to 10 Hz
10 Hz
Parameter can be accessed if [JOG] (JOG) is not set to [No] (nO), page 72.
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
g
72
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
+/- speed
drC-
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), page 56.
Two types of operation are available.
I-0CtL-
1. Use of single action buttons: Two logic inputs are required in addition to the direction(s) of operation.
The input assigned to the "+ speed" command increases the speed, the input assigned to the "- speed" command decreases
the speed.
Note:
If the "+ speed" and "- speed" commands are activated at the same time, "- speed" will be given priority.
FUnFLtCOM-
2. Use of double action buttons: Only one logic input assigned to "+ speed" is required.
SUP-
+/- speed with double action buttons:
Description: 1 button pressed twice for each direction of rotation. Each action closes a contact.
Released
(- speed)
1st press
(speed maintained)
2nd press
(+ speed)
Forward button
–
a
a and b
Reverse button
–
c
c and d
Wiring example:
LI1: Forward
LIx: Reverse
LIy: + speed
ATV312
control terminals
Motor frequency
LSP
0
LSP
Forward
2nd press
1st press
0
Reverse
2nd press
1st press
0
This type of +/- speed is incompatible with 3-wire control.
Whichever type of operation is selected, the max. speed is set by the [High speed] (HSP) parameter, page 32.
Note:
If the reference is switched via [Ref. 2 switching] (rFC), page 57, from one reference channel to any other reference channel with "+/- speed",
the value of the [Output frequency] (rFr) reference (after ramp) is copied at the same time. This prevents the speed being incorrectly reset
to zero when switching takes place.
BBV46385 05/2009
73
[APPLICATION FUNCT.] (FUn-) menu
rEFSEtdrC-
Code
Name/Description
I-0CtL-
b
UPd-
FUn-
Adjustment
range
Factory
setting
[+/- SPEED]
(motorized jog dial)
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), and [+/-spd HMI]
(UPdH) or [+/- SPEED] (UPdt) selected, page 56.
Note: The "+/- speed" function is incompatible with several functions (see page 20). It can only be configured
if these functions are unassigned, in particular the summing inputs (set [Summing ref. 2] (SA2) to [No] (nO),
page 67) and the preset speeds (set [2 preset speeds] (PS2) and [4 preset speeds] (PS4) to [No] (nO),
page 69) which will have been assigned as part of the factory settings.
FLtCOMSUP-
M [+ speed assignment]
USP
g
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
g
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
g
nO
rAN
EEP
74
v
v
v
[No] (nO)
Parameter accessible for [+/- SPEED] (UPdt) only. Selecting the assigned logic input activates the
function.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
M [Reference saved]
Str
g
Parameter accessible for [+/- SPEED] (UPdt) only. Selecting the assigned logic input activates the
function.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
M [-Speed assignment]
dSP
[No] (nO)
[No] (nO)
Associated with the "+/- speed" function, this parameter can be used to save the reference:
• When the run commands disappear (saved to RAM)
• When the line supply or the run commands disappear (saved to EEPROM)
Therefore, the next time the drive starts up, the speed reference is the last reference saved.
[No] (nO): No saving
[RAM] (rAM): Saving in RAM
[EEprom] (EEP): Saving in EEPROM
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
PI regulator
SEt-
Block diagram
drC-
The function is activated by assigning an analog input to the PI feedback (measurement).
I-0CtL-
Error
inversion
Internal
reference
Restart error
threshold
(wake-up)
FUnFLt-
Ramps
COMSUP-
Reference A
Pages 51 and
53
Gains
Preset PI
references
Key:
Parameter:
The black rectangle
represents the factory
setting assignment.
PI
feedback
Reference B
Pages 51 and 53
PI feedback:
PI feedback must be assigned to one of these analog inputs, AI1, AI2, or AI3.
PI reference:
The PI reference can be assigned to the following parameters in order of priority:
- Preset references via logic inputs, [Preset ref. PID 2] (rP2), [Preset ref. PID 3] (rP3), and [Preset ref. PID 4] (rP4), page 78
- Internal reference [Internal PID ref.] (rPI), page 78
- Reference [Ref.1 channel] (Fr1), page 56
Combination table for preset PI references
LI (Pr4)
LI (Pr2)
0
0
1
1
0
1
0
1
Pr2 = nO
Reference
rPI or Fr1
rPI or Fr1
rP2
rP3
rP4
Parameters can also be accessed in the [SETTINGS] (SEt-) menu:
• [Internal PID ref.] (rPI), page 31
• [Preset ref. PID 2] (rP2), [Preset ref. PID 3] (rP3), and [Preset ref. PID 4] (rP4), page 34
• [PID prop. gain] (rPG), page 34
• [PID integral gain] (rIG), page 34
• [PID fbk scale factor] (FbS), page 34:
The [PID fbk scale factor] (FbS) parameter can be used to scale the reference according to the variation range for PI feedback (sensor
rating).
Example: Regulating pressure
PI reference (process) 0-5 bar (0-100%)
Rating of pressure sensor 0-10 bar
[PID fbk scale factor] (FbS) = max. sensor scaling/max. process
[PID fbk scale factor] (FbS) = 10/5= 2
• [PID wake up thresh.] (rSL), page 36:
Can be used to set the PI error threshold above which the PI regulator will be reactivated (wake-up) after a stop due to the max. time
threshold being exceeded at low speed [Low speed time out] (tLS)
• [PID correct. reverse] (PIC), page 34: If [PID correct. reverse] (PIC) = [No] (nO), the speed of the motor will increase when the error
is positive (example: pressure control with a compressor). If [PID correct. reverse] (PIC) = [Yes] (YES), the speed of the motor will
decrease when the error is positive (example: temperature control using a cooling fan).
BBV46385 05/2009
75
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
"Manual - Automatic" operation with PI
drC-
This function combines the PI regulator and [Ref. 2 switching] (rFC) reference switching, page 57. The speed reference is given by
[Ref.2 channel] (Fr2) or by the PI function, depending on the state of the logic input.
I-0CtL-
Setting up the PI regulator
1. Configuration in PI mode
See the block diagram on page 75.
FLt2. Perform a test in factory settings mode (in most cases, this will be sufficient).
COMTo optimize the drive, adjust [PID prop. gain.] (rPG) or [PID integral gain] (rIG) gradually and independently, and observe the effect on
the PI feedback in relation to the reference.
SUP- 3. If the factory settings are unstable or the reference is incorrect:
Perform a test with a speed reference in manual mode (without PI regulator) and with the drive on load for the speed range of the system:
- In steady state, the speed must be stable and comply with the reference, and the PI feedback signal must be stable.
- In transient state, the speed must follow the ramp and stabilize quickly, and the PI feedback must follow the speed.
If this is not the case, see the settings for the drive and/or sensor signal and cabling.
FUn-
Switch to PI mode.
Set [Dec ramp adapt.] (brA) to no (no auto-adaptation of the ramp).
Set the [Acceleration] (ACC) and [Deceleration] (dEC) speed ramps to the minimum level permitted by the mechanics without triggering an
[OVERBRAKING] (ObF) fault.
Set the integral gain [PID integral gain] (rIG) to the minimum level.
Observe the PI feedback and the reference.
Switch the drive ON/OFF repeatedly or quickly vary the load or reference a number of times.
Set the proportional gain [PID prop. gain] (rPG) in order to ascertain a good compromise between response time and stability in transient
phases (slight overshoot and 1 to 2 oscillations before stabilizing).
If the reference varies from the preset value in steady state, gradually increase the integral gain [PID integral gain] (rIG), reduce the
proportional gain [PID prop. gain] (rPG) in the event of instability (pump applications), and find a compromise between response time and
static precision (see diagram).
Perform in-production tests over the whole reference range.
Stabilization time
Regulated
value
rPG high
Reference
Overshoot
Static error
Proportional
gain
rPG low
Rise time
Time
rIG high
Reference
Integral
gain
rIG low
Reference
Time
rPG and rIG correct
Time
The oscillation frequency depends on the system dynamics.
Parameter
Rise time
Overshoot
Stabilization
time
Static error
[PID prop. gain] (rPG)
=
[PID integral gain] (rIG)
76
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
PI-
Adjustment
range
SEt-
Factory
setting
drC-
[PI REGULATOR]
I-0CtL-
Note: The "PI regulator" function is incompatible with several functions (see page 20).
It can only be configured if these functions are unassigned, in particular the summing inputs (set [Summing
ref. 2] (SA2) to [No] (nO), page 67) and the preset speeds (set [2 preset speeds] (PS2) and [4 preset speeds]
(PS4) to [No] (nO), page 69) which will have been assigned as part of the factory settings.
PIF
nO
AI1
AI2
AI3
M [PID feedback ass.]
v [No] (nO): Not assigned
v [AI1] (AI1): Analog input AI1
v [AI2] (AI2): Analog input AI2
v [AI3] (AI3): Analog input AI3
M [PID prop. gain]
rPG
FUnFLt-
[No] (nO)
COMSUP-
(1)
0.01 to 100
1
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
It provides dynamic performance when PI feedback is changing quickly.
g
M [PID integral gain]
rIG
(1)
0.01 to 100
1
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
It provides static precision when PI feedback is changing slowly.
g
M [PID fbk scale factor]
FbS
(1)
0.1 to 100
1
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
For adapting the process.
g
M [PID correct. reverse]
PIC
g
[No] (nO)
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
nO
YES
v
v
[No] (nO): Normal
[Yes] (YES): Reverse
M [2 preset PID ref.]
Pr2
g
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
Selecting the assigned logic input activates the function.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
[No] (nO)
(1) Parameter(s) can also be accessed in the [SETTINGS] (SEt-) menu.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
77
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
Adjustment
range
drCI-0-
b
PI-
CtL-
[PI REGULATOR] (continued)
M [4 preset PID ref.]
Pr4
FUn-
g
FLtCOM-
nO
LI1
LI2
LI3
LI4
LI5
LI6
SUP-
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
v
v
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
M [Preset ref. PID 2]
g
See page 34.
rP3
M [Preset ref. PID 3]
g
See page 34.
rP4
M [Preset ref. PID 4]
g
See page 34.
M [PID wake up thresh.]
(1)
0 to 100%
30%
(1)
0 to 100%
60%
(1)
0 to 100%
90%
(1)
0 to 100%
0%
If the "PI" and "Low speed operating time" [Low speed time out] (tLS) (page 36) are configured at the same
time, the PI regulator may attempt to set a speed lower than[Low speed] (LSP).
This results in unsatisfactory operation, which consists of starting, operating at [Low speed] (LSP), then
stopping, and so on.
The rSL (restart error threshold) parameter can be used to set a minimum PI error threshold
for restarting after a stop at prolonged [Low speed] (LSP).
The function is inactive if [Low speed time out] (tLS) = 0.
g
M [Act. internal PID ref.]
PII
g
nO
YES
rPI
g
[No] (nO)
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
Selecting the assigned logic input activates the function.
Make sure that [2 preset PID ref.] (Pr2), page 77, has been assigned before assigning [4 preset PID ref.]
(Pr4).
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
rP2
rSL
Factory
setting
v
v
[No] (nO)
[No] (nO): The reference for the PI regulator is [Ref.1 channel] (Fr1), except for [+/-spd HMI] (UPdH) and
[+/- SPEED] (UPdt) (+/- speed cannot be used as a reference for the PI regulator).
[Yes] (YES): The reference for the PI regulator is provided internally via the [Internal PID ref.] (rPI)
parameter.
M [Internal PID ref.]
(1)
0 to 100%
0%
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
(1) Parameter(s) can also be accessed in the [SETTINGS] (SEt-) menu.
g
78
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Brake control
drC-
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3) (page 51).
This function, which can be assigned to relay R2 or logic output AOC, enables the drive to manage an electromagnetic brake.
I-0CtL-
Principle
Synchronize brake release with the build-up of torque during startup and brake engage at zero speed on stopping, to help prevent jolting.
FUnFLt-
Brake sequence
COM-
Motor speed
SUP-
Speed reference
Relay R2 or logic output AOC
Settings which can be accessed in the
application functions [APPLICATION
FUNCT.] (FUn-) menu:
• Brake release frequency [Brake
release freq] (brL)
• Brake release current
[Brake release I FW] (Ibr)
• Brake release time delay [Brake
Release time] (brt)
• Brake engage frequency [Brake
engage freq] (bEn)
• Brake engage time delay [Brake
engage time] (bEt)
• Brake release pulse [Brake
impulse] (bIP)
Motor current
Motor frequency
Speed
reference
LI forward or reverse
State of brake
Engaged
Released
Engaged
Recommended brake control settings:
1. [Brake release freq] (brL), page 80:
- Horizontal movement: Set to 0.
- Vertical movement: Set to a frequency equal to the nominal motor slip in Hz.
2. [Brake release I FW] (Ibr), page 80:
- Horizontal movement: Set to 0.
- Vertical movement: Preset the nominal current of the motor then adjust it in order to help prevent jolting on start-up, making sure
that the maximum load is held when the brake is released.
3. [Brake Release time] (brt), page 80:
Adjust according to the type of brake. It is the time required for the mechanical brake to release.
4. [Brake engage freq] (bEn), page 80:
- Horizontal movement: Set to 0.
- Vertical movement: Set to a frequency equal to the nominal motor slip in Hz. Note: Max. [Brake engage freq] (bEn) = [Low speed]
(LSP); this means an appropriate value must be set in advance for [Low speed] (LSP).
5. [Brake engage time] (bEt), page 80:
Adjust according to the type of brake. It is the time required for the mechanical brake to engage.
6. [Brake impulse] (bIP), page 80:
- Horizontal movement: Set to [No] (nO).
- Vertical movement: Set to [Yes] (YES) and check that the motor torque direction for "run forward" control corresponds to the
upward direction of the load. If necessary, reverse two motor phases. This parameter generates motor torque in an upward
direction regardless of the direction of operation commanded in order to maintain the load whilst the brake is releasing.
BBV46385 05/2009
79
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
drCI-0-
b
bLC-
Adjustment
range
Factory
setting
[BRAKE LOGIC CONTROL]
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), page 56.
Note: This function may be incompatible with other functions (see page 20).
CtLFUn-
bLC
FLt-
nO
r2
dO
COMSUP-
M [Brake assignment]
v [No] (nO): Not assigned
v [R2] (r2): Relay R2
v [DO] (dO): Logic output AOC
[No] (nO)
If [Brake assignment] (bLC) is assigned, the [Catch on the fly] (FLr) parameter, page 88, and the [Dec ramp
adapt.] (brA) parameter, page 62, are forced to [No] (nO), and the [Output Phase Loss] (OPL) parameter,
page 89, is forced to [Yes] (YES).
[Brake assignment] (bLC) is forced to [No] (nO) if [Output Phase Loss] (OPL) = [Output cut] (OAC), page 89.
M [Brake release freq]
brL
g
0.0 to 10.0 Hz
In accordance
with the drive
rating
0 to 1.36 In (1)
In accordance
with the drive
rating
0 to 5 s
0.5 s
0 to HSP
(page 32)
0 LSP
Brake release frequency.
M [Brake release I FW]
Ibr
g
Brake release current threshold for ascending or forward movement.
M [Brake Release time]
brt
g
Brake release time delay.
M [Low speed]
LSP
Motor frequency at min. reference.
This parameter can also be changed in the [SETTINGS] (SEt-) menu, page 32.
g
M [Brake engage freq]
bEn
nO - 0 to LSP
nO
g
nO
0
to
LSP
v
v
M [Brake engage time]
bEt
g
0 to 5 s
0.5 s
Brake engage time (brake response time).
bIP
nO
YES
g
Not set
Adjustment range in Hz
If [Brake assignment] (bLC) is assigned and [Brake engage freq] (bEn) remains set to [No] (nO), the drive
will lock in [BRAKE CONTROL FAULT] (bLF) mode on the first run command.
[No] (nO)
M [Brake impulse]
v [No] (nO): Whilst the brake is releasing, the motor torque direction corresponds to the direction of rotation
v
commanded.
[Yes] (YES): Whilst the brake is releasing, the motor torque direction is forward, regardless of the direction
of operation commanded.
Note: Check that the motor torque direction for "run forward" control corresponds to the upward direction of
the load. If necessary, reverse two motor phases.
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
80
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
LC2-
Adjustment
range
SEt-
Factory
setting
drC-
[CURRENT LIMITATION 2]
I-0CtL-
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), page 56.
M [Current limit 2]
LC2
FUn-
[No] (nO)
FLt-
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
Selecting the assigned logic input activates the function.
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
Cd11
Cd12
Cd13
Cd14
Cd15
v
v
v
v
v
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
COMSUP-
[Current Limitation] (CLI) is enabled when the logic input or control word bit is at state 0 ([SETTINGS]
(SEt-) menu, page 36).
[I Limit. 2 value] (CL2) is enabled when the logic input or control word bit is at state 1.
M [I Limit. 2 value]
CL2
g
(1)
0.25 to 1.5 In (2)
1.5 In (2)
See page 36.
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
81
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Code
Name/Description
Adjustment
range
drCI-0-
b
CHP-
Factory setting
[SWITCHING MOTOR]
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), page 56.
CtLFUn-
CHP
FLt-
nO
LI1
LI2
LI3
LI4
LI5
LI6
COMSUP-
Cd11
Cd12
Cd13
Cd14
Cd15
M [Motor switching]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
v
v
v
v
v
[No] (nO)
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
LI or bit = 0: Motor 1
LI or bit = 1: Motor 2
Note:
• If this function is used, the auto-tuning function, page 41, is not active on motor 2.
• Changes to parameters are only taken into account when the drive is locked.
CAUTION
RISK OF DAMAGE TO MOTOR
The motor switching function disables motor thermal protection.
The use of external overload protection is required when using motor switching.
Failure to follow these instructions can result in equipment damage.
UnS2
M [Nom. mot. 2 volt.]
In accordance
with the drive
rating
In accordance
with the drive
rating
10 to 500 Hz
50 Hz
ATV312pppM2: 100 to 240 V
ATV312pppM3: 100 to 240 V
ATV312pppN4: 100 to 500 V
ATV312pppS6: 100 to 600 V
g
FrS2
M [Nom. motor 2 freq.]
Note:
The ratio
g
g
82
[Rated motor volt.] (UnS) (in volts)
[Rated motor freq.] (FrS) (in Hz)
must not exceed the following values:
ATV312pppM2: 7 max.
ATV312pppM3: 7 max.
ATV312pppN4: 14 max.
ATV312pppS6: 17 max.
The factory setting is 50 Hz, or preset to 60 Hz if [Standard mot. freq] (bFr) is set to 60 Hz.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FUn-) menu
rEF-
Code
Name/Description
b
CHP-
Adjustment
range
g
drC-
[SWITCHING MOTOR] (continued)
I-0-
M [Nom. mot. 2 current]
nCr2
SEt-
Factory setting
0.25 to 1.5 In
(2)
CtL-
In accordance
with the drive
rating
FUnFLt-
Nominal motor 2 current given on the rating plate.
COM-
M [Nom. mot. 2 speed]
nSP2
0 to 32,760 rpm In accordance
with the drive
rating
SUP-
0 to 9,999 rpm then 10.00 to 32.76 krpm
If, rather than the nominal speed, the nameplate indicates the synchronous speed and the slip in Hz or as
a %, calculate the nominal speed as follows:
100 - slip as a %
• Nominal speed = synchronous speed x
100
or
50 - slip in Hz
• Nominal speed = synchronous speed x
(50 Hz motors)
50
or
60 - slip in Hz
• Nominal speed = synchronous speed x
(60 Hz motors)
60
g
M [Motor 2 Cosinus Phi]
COS2
g
0.5 to 1
In accordance
with the drive
rating
Cos Phi given on the rating plate of motor 2.
UFt2
L
P
n
nLd
[SVC] (n)
M [U/F mot.2 selected]
v [Cst. torque] (L): Constant torque for motors connected in parallel or special motors
v [Var. torque] (P): Variable torque for pump and fan applications
v [SVC] (n): Sensorless flux vector control for constant torque applications
v [Energy sav.] (nLd): Energy saving, for variable torque applications not requiring high dynamics (behaves
in a similar way to the P ratio at no load and the n ratio on load)
g
Voltage
UnS
L
n
P
FrS
M [IR compensation 2]
UFr2
g
See page 36.
FLG2
M [FreqLoopGain 2]
g
See page 37.
M [Freq. loop stability 2]
StA2
g
Frequency
(1)
0 to 100%
20%
(1)
1 to 100%
20%
(1)
1 to 100%
20%
(1)
0 to 150%
100%
See page 37.
M [Slip compensation 2]
SLP2
g
See page 37.
(1) Parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive nameplate.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
83
[APPLICATION FUNCT.] (FUn-) menu
rEFSEt-
Management of limit switches
drC-
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), page 56.
This function can be used to manage the operation of one or two series limit switches (non-reversing or reversing).
- Assignment of one or two logic inputs (forward limit switch, reverse limit switch)
CtL- Selection of the stop type (on ramp, fast or freewheel)
FUnFollowing a stop, the motor is permitted to restart in the opposite direction only.
The stop is performed when the input is in state 0. The direction of operation is authorized in state 1.
FLtI-0-
COMSUP-
Restarting after stop caused by a limit switch
• Send a run command in the other direction (when control is via the terminals, if [2/3 wire control] (tCC) = [2 wire] (2C) and [2 wire
type] (tCt) = [Transition] (trn), first remove all the run commands).
or
• Invert the reference sign, remove all the run commands then send a run command in the same direction as before the stop caused
by a limit switch.
Code
Name/Description
b
LSt-
Adjustment
range
Factory
setting
[LIMIT SWITCHES]
Function can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3), page 56.
Note: This function is incompatible with the "PI regulator" function (see page 20).
LAF
nO
LI1
LI2
LI3
LI4
LI5
LI6
LAr
M [Stop FW limit sw.]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
[No] (nO)
M [Stop RV limit sw.]
[No] (nO)
g
nO
LI1
LI2
LI3
LI4
LI5
LI6
v
v
v
v
v
v
v
M [Stop type]
LAS
g
84
[Freewheel]
(nSt)
Parameter can be accessed if [Stop FW limit sw.] (LAF), page 84, or [Stop RV limit sw.] (LAr), page 84, is
assigned.
rMP
FSt
nSt
g
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
v
v
v
[Ramp stop] (rMP): On ramp
[Fast stop] (FSt): Fast stop
[Freewheel] (nSt): Freewheel stop
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
[APPLICATION FUNCT.] (FLt-) menu
rEFrEFSEtSEt-
Code
ArE
Name/Description
Adjustment
range
M [Select ATV31 conf.]
nO
31E
v
v
31A
v
drCdrC-
Factory setting
I-0I-0-
[No] (nO)
CtLCtL-
This parameter is invisible if a communication option is present. It is only used to transfer a configuration
via a loader tool or an ATV31 remote terminal.
[Select ATV31 conf.] (ArE) can be used during a transfer between an ATV31 and ATV312 to specify the
type of ATV31 (ATV31 or ATV31ppppppA).
FUnFUn-
[No] (nO): Transfer between two ATV312
[ATV31 std] (31E): Transfer from an ATV31 to an ATV312. Set ARE = 31E to download a configuration
from a European ATV31.
[ATV31...A] (31A): Transfer from an ATV31ppppppA to an ATV312. Set ARE = 31A to download a
configuration from an Asian ATV31.
SUPSUP-
FLtFLtCOMCOM-
Procedure for transferring a configuration:
• Set [Select ATV31 conf.] (ArE) to the required value.
• Perform the configuration transfer.
• Once the transfer is complete, turn the drive off.
• Power the drive up again to initialize the configuration.
• The parameter is restored to its factory setting.
SCS
2s
CFG
2s
FCS
2s
M [Saving config.]
(1)
[No] (nO)
(1)
[Factory set.] (Std)
(1)
[No] (nO)
See page 43.
M [Macro configuration]
See page 43.
M [Restore config.]
See page 44.
(1) [Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed from several configuration menus,
but they apply to all menus and parameters.
2s
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
85
[FAULT MANAGEMENT] (FLt-) menu
rEFSEtdrC-
Automatic restart
I-0CtLFUnFLtCOM-
Operating time reset to zero
SUP-
The parameters can only be modified when the drive is stopped and no run command is present.
On the optional remote display terminal, this menu can be accessed with the switch in the
position.
Code
Atr
Description
Adjustment
range
M [Automatic restart]
Factory
setting
[No] (nO)
DANGER
UNINTENDED EQUIPMENT OPERATION
• The automatic restart can only be used on machines or installations which do not pose any danger to either
personnel or equipment.
• If the automatic restart is activated, R1 will only indicate a fault has been detected once the time-out period for the
restart sequence has expired.
• The equipment must be used in compliance with national and regional safety regulations.
Failure to follow these instructions will result in death or serious injury.
nO
YES
v
v
The motor's automatic restart function will only be active in 2-wire level control ([2/3 wire control] (tCC) =
[2 wire] (2C), and [2 wire type] (tCt) = [Level] (LEL) or [Fwd priority] (PFO)).
[No] (nO): Function inactive
[Yes] (YES): Automatic restart if the fault has been cleared and the other operating conditions permit the
restart. The restart is performed by a series of automatic attempts separated by increasingly longer waiting
periods: 1 s, 5 s, 10 s, then 1 min for subsequent ones.
If the restart has not taken place once the [Max. restart time] (tAr) configurable time has elapsed, the
procedure is aborted and the drive remains locked until it is turned off and then on again.
This function is possible with the following conditions:
[NETWORK FAULT] (CnF): Communication detected fault on the communication card
[CANopen com.] (COF): CANopen communication detected fault
[External] (EPF): External fault
[4-20mA] (LFF): 4-20 mA loss
[Overbraking] (ObF): DC bus overvoltage
[Drive overheat] (OHF): Drive overheating
[Motor overload] (OLF): Motor overload
[Mot. phase] (OPF): Motor phase loss
[Mains overvoltage] (OSF): Line supply overvoltage
[Mains phase loss] (PHF): Line phase loss
[MODBUS FAULT] (SLF): Modbus communication
Relay R1 remains activated if this function is active. The speed reference and the operating direction must
be maintained.
86
BBV46385 05/2009
[FAULT MANAGEMENT] (FLt-) menu
rEF-
Code
Description
M [Max. restart time]
tAr
g
5
10
30
1h
2h
3h
Ct
rSF
nO
LI1
LI2
LI3
LI4
LI5
LI6
g
Adjustment
range
v
v
v
v
v
v
v
Factory
setting
SEtdrC-
[5 min] (5)
I-0-
Parameter is only visible if [Automatic restart] (Atr) = [Yes] (YES).
It can be used to limit the number of consecutive restarts in the event of a recurrent detected fault.
[5 min] (5): 5 minutes
[10 min] (10): 10 minutes
[30 min] (30): 30 minutes
[1 hour] (1h): 1 hour
[2 hours] (2h): 2 hours
[3 hours] (3h): 3 hours
[Unlimited] (Ct): Unlimited (except for [MOTOR PHASE LOSS] (OPF) and [INPUT PHASE LOSS] (PHF);
the max. duration of the restart process is limited to 3 hours)
M [Fault reset]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
CtLFUnFLtCOMSUP-
[No] (nO)
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
87
[FAULT MANAGEMENT] (FLt-) menu
rEFSEt-
Code
Description
Adjustment
range
drC-
FLr
I-0-
M [Catch on the fly]
CtLFUnFLtCOMSUP-
nO
YES
EtF
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
LEt
v
v
v
v
v
HIG
v
nO
YES
rNP
FSt
[Active high]
(HIG)
[Active low] (LO): The external fault is detected when the logic input assigned to [External fault ass.] (EtF)
changes to state 0.
Note: In this case, [External fault ass.] (EtF) cannot be assigned to a control word bit from a communication
network.
[Active high] (HIG): The external fault is detected when the logic input or the bit assigned to [External fault
ass.] (EtF) changes to state 1.
Note: Where [External fault config] (LEt) = [Active high] (HIG), [External fault ass.] (EtF) is assigned to a
control word bit from a communication network, and where there is no [External fault ass.] (EtF) fault
detection, switching to [External fault config] (LEt) = [Active low] (LO) triggers [External fault ass.] (EtF) fault
detection. In this case, it is necessary to turn the drive off and then back on again.
M [External fault mgt]
v
v
v
v
[No] (nO)
If [ACCESS LEVEL] (LAC) = [Level 3] (L3), the following assignments are possible:
[CD11] (CD11): Bit 11 of the control word from a communication network
[CD12] (CD12): Bit 12 of the control word from a communication network
[CD13] (CD13): Bit 13 of the control word from a communication network
[CD14] (CD14): Bit 14 of the control word from a communication network
[CD15] (CD15): Bit 15 of the control word from a communication network
M [External fault config]
v
[No] (nO)
Used to enable a smooth restart if the run command is maintained after the following events:
- Loss of line supply or simple power off
- Reset of current drive or automatic restart
- Freewheel stop
The speed given by the drive resumes from the estimated speed of the motor at the time of the restart, then
follows the ramp to the reference speed.
This function requires 2-wire control ( [2/3 wire control] (tCC) = [2 wire] (2C)) with [2 wire type] (tCt) = [Level]
(LEL) or [Fwd priority] (PFO).
[No] (nO): Function inactive
[Yes] (YES): Function active
When the function is operational, it activates at each run command, resulting in a slight delay
(1 second max.).
[Catch on the fly] (FLr) is forced to [No] (nO) if brake control [Brake assignment] (bLC) is assigned, page 80.
M [External fault ass.]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
LO
EPL
88
v
v
Factory
setting
[Freewheel]
(YES)
[Ignore] (nO): Ignore
[Freewheel] (YES): Detected fault management with freewheel stop
[Ramp stop] (rMP): Detected fault management with stop on ramp
[Fast stop] (FSt): Detected fault management with fast stop
BBV46385 05/2009
[FAULT MANAGEMENT] (FLt-) menu
rEF-
Code
OPL
nO
YES
OAC
Description
Adjustment
range
SEt-
Factory setting
drC-
[Yes] (YES)
M [Output Phase Loss]
v [No] (nO): Function inactive
v [Yes] (YES): Tripping on the [MOTOR PHASE LOSS] (OPF)
v [Output cut] (OAC): No tripping on a [MOTOR PHASE LOSS] (OPF), but management of the output voltage
in order to avoid an overcurrent when the link with the motor is re-established and catch on the fly performed
even if [Catch on the fly] (FLr) = [No] (nO). To be used with output contactor.
[Output Phase Loss] (OPL) is forced to [Yes] (YES) if [Brake assignment] (bLC) is not set to [No] (nO),
page 80.
IPL
nO
YES
OHL
nO
YES
rNP
FSt
OLL
nO
YES
rNP
FSt
SLL
M [Input phase loss]
v
v
[Yes] (YES)
This parameter is only accessible on 3-phase drives.
[No] (nO): Ignore
[Yes] (YES): Detected fault management with fast stop
M [Overtemp fault mgt]
v
v
v
v
[Freewheel]
(YES)
[Ignore] (nO): Ignore
[Freewheel] (YES): Detected fault management with freewheel stop
[Ramp stop] (rMP): Detected fault management with stop on ramp
[Fast stop] (FSt): Detected fault management with fast stop
M [Overload fault mgt]
v
v
v
v
[Freewheel]
(YES)
[Ignore] (nO): Ignore
[Freewheel] (YES): Detected fault management with freewheel stop
[Ramp stop] (rMP): Detected fault management with stop on ramp
[Fast stop] (FSt): Detected fault management with fast stop
M [Modbus fault mgt]
[Fast stop]
(FSt)
WARNING
LOSS OF CONTROL
If [Modbus fault mgt] (SLL) = [Ignore] (n0), communication control will be inhibited. For safety reasons, inhibiting
the communication fault detection should be restricted to the debug phase or to special applications.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
nO
YES
rNP
FSt
BBV46385 05/2009
v
v
v
v
[Ignore] (nO): Ignore
[Freewheel] (YES): Detected fault management with freewheel stop
[Ramp stop] (rMP): Detected fault management with stop on ramp
[Fast stop] (FSt): Detected fault management with fast stop
This parameter does not apply to PowerSuite and SoMove software.
89
I-0CtLFUnFLtCOMSUP-
[FAULT MANAGEMENT] (FLt-) menu
rEFSEt-
Code
Description
Adjustment
range
drC-
COL
I-0-
M [CANopen fault mgt]
Factory setting
[Fast stop] (FSt)
CtLFUn-
WARNING
FLt-
LOSS OF CONTROL
COM-
If [CANopen fault mgt] (COL) or [Network fault mgt] (CLL) = [Ignore] (n0), communication control will be inhibited.
For safety reasons, inhibiting the communication fault detection should be restricted to the debug phase or to
special applications.
SUP-
Failure to follow these instructions can result in death, serious injury, or equipment damage.
nO
YES
rNP
FSt
tnL
nO
YES
LFL
v
v
v
v
M [Autotune fault mgt]
v
v
[Yes] (YES)
This parameter can be used to manage drive behavior in the event that auto-tuning is unsuccessful [AUTO
TUNING FAULT] (tnF)
[No] (nO): Ignored (the drive reverts to the factory settings)
[Yes] (YES): Detected fault management with drive locked
If [Cold stator resist.] (rSC), page 40, is not set to [No] (nO), [Autotune fault mgt] (tnL) is forced to [Yes]
(YES).
M [4-20mA loss]
nO
YES
LFF
rLS
v
v
v
v
rNP
FSt
v
v
LFF
[Ignore] (nO): Ignore
[Freewheel] (YES): Detected fault management with freewheel stop
[Ramp stop] (rMP): Detected fault management with stop on ramp
[Fast stop] (FSt): Detected fault management with fast stop
[Freewheel]
(YES)
[Ignore] (nO): Ignored (only possible value if [AI3 min. value] (CrL3) y 3 mA, page 46)
[Freewheel] (YES): Detected fault management with freewheel stop
[fallback spd] (LFF): The drive switches to the fallback speed ([fallback spd] (LFF) parameter).
[Spd maint.] (rLS): The drive maintains the speed at which it was operating when the loss was detected.
This speed is saved and stored as a reference until the fault has disappeared.
[Ramp stop] (rMP): Detected fault management with stop on ramp
[Fast stop] (FSt): Detected fault management with fast stop
Note: Before setting [4-20mA loss] (LFL) to [fallback spd] (LFF) check the connection of input AI3.
If [4-20mA loss] (LFL) = [fallback spd] (LFF) or [Spd maint.] (rLS), no code is displayed.
M [Fallback speed]
0 to 500 Hz
10 Hz
Fallback speed setting in the event of a [4-20mA loss] (LFL).
90
BBV46385 05/2009
[FAULT MANAGEMENT] (FLt-) menu
rEF-
Code
Description
Adjustment
range
M [Derated operation]
drn
2s
nO
YES
v
v
Factory
setting
SEt-
[No] (nO)
I-0-
drC-
Lowers the tripping threshold of [Undervoltage] (USF): in order to operate on line supplies with 50%
voltage drops.
CtL-
[No] (nO): Function inactive
[Yes] (YES): Function active
In this case, drive performance is derated.
FLt-
FUn-
COMSUP-
CAUTION
RISK OF DAMAGE TO DRIVE
When [Derated operation] (drn) = [Yes] (YES), use a line choke (see catalog).
Failure to follow these instructions can result in equipment damage.
M [UnderV. prevention]
StP
nO
NNS
v
v
rMP
FSt
v
v
[No] (nO)
This function can be used to control the type of stop where there is a loss of line supply.
[No] (nO): Locking of the drive and freewheel stopping of the motor
[DC Maintain] (MMS): This stop mode uses the inertia to maintain the drive power supply as long as
possible.
[Ramp stop] (rMP): Stop according to the valid ramp ([Deceleration] (dEC) or [Deceleration 2] (dE2))
[Fast stop] (FSt): Fast stop, the stopping time depends on the inertia and the braking ability of the drive.
M [Fault inhibit assign.]
InH
[No] (nO)
DANGER
LOSS OF PERSONNEL AND EQUIPMENT PROTECTION
2s
• Enabling the fault inhibition parameter (inH) will disable the drive controller protection features.
• InH should not be enabled for typical applications of this equipment.
• InH should be enabled only in extraordinary situations where a thorough risk analysis demonstrates that the
presence of adjustable speed drive protection poses a greater risk than personnel injury or equipment damage.
Failure to follow these instructions will result in death or serious injury.
nO
LI1
LI2
LI3
LI4
LI5
LI6
rPr
nO
rtH
v
v
v
v
v
v
v
This function disables drive protection for the following detected faults:
CFF, CFI, SLF, CnF, EPF, OCF, CrF, LFF, OHF, OBF, OLF, OSF, OPF, PHF, USF, SOF, tnF, IF1, IF2,
IF3, IF4, EEF, COF, bLF
[No] (nO): Not assigned
[LI1] (LI1): Logic input LI1
[LI2] (LI2): Logic input LI2
[LI3] (LI3): Logic input LI3
[LI4] (LI4): Logic input LI4
[LI5] (LI5): Logic input LI5
[LI6] (LI6): Logic input LI6
The logic inputs are active in the high state.
M [Operating t. reset]
v [No] (nO): No
v [rst. runtime] (rtH): Operating time reset to zero
[No] (nO)
The [Operating t. reset] (rPr) parameter automatically returns to [No] (nO) after resetting to 0.
rp
nO
YES
2s
M [Product reset]
v [No] (nO): No
v [Yes] (YES): Yes
[No] (nO)
The jog dial (ENT) needs to be pressed and held down (for 2 s) to change the assignment for this parameter.
BBV46385 05/2009
91
[COMMUNICATION] (COM-) menu
rEFSEtdrCI-0CtLFUnFLtCOMSUP-
The parameters can only be modified when the drive is stopped and no run command is present. Modifications to the [Modbus Address]
(Add), [Modbus baud rate] (tbr), [Modbus format] (tFO), [CANopen address] (AdCO), and [CANopen bit rate] (bdCO) parameters are not
taken into account until the drive has been switched off and back on again.
On the optional ATV31 remote display terminal, this menu can be accessed with the switch in the
position.
Code
Description
M [Modbus Address]
Add
Adjustment
range
Factory
setting
1 to 247
1
Modbus address for the drive.
M [Modbus baud rate]
tbr
4.8
9.6
19.2
tFO
8O1
8E1
8n1
8n2
ttO
AdCO
v
v
v
19,200 bps
Modbus transmission speed
[4.8 Kbps] (4.8): 4,800 bits/second
[9.6 Kbps] (9.6): 9,600 bits/second
[19.2 Kbps] (19.2): 19,200 bits/second (Note: This is the only value which supports the use of the remote
display terminal.)
[8-E-1] (8E1)
M [Modbus format]
v [8-O-1] (8O1): 8 data bits, odd parity, 1 stop bit
v [8-E-1] (8E1): 8 data bits, even parity, 1 stop bit (Note: This is the only value which supports the use of the
v
v
remote display terminal.)
[8-N-1] (8n2): 8 data bits, no parity, 1 stop bit
[8-N-2] (8n2): 8 data bits, no parity, 2 stop bits
M [Modbus time out]
0.1 to 10 s
10 s
M [CANopen address]
0 to 127
0
CANopen address for the drive.
M [CANopen bit rate]
bdCO
10.0
20.0
50.0
125.0
250.0
500.0
1000
ErCO
0
1
2
3
4
92
v
v
v
v
v
v
v
125 bps
Modbus transmission speed
[10 kbps] (10.0): 10 kbps
[20 kbps] (20.0): 20 kbps
[50 kbps] (50.0): 50 kbps
[125 kbps] (125.0): 125 kbps
[250 kbps] (250.0): 250 kbps
[500 kbps] (500.0): 500 kbps
[1 Mbps] (1000): 1000 kbps
M [Error code]
v No error
v Bus off
v Life time
v CAN overrun
v Heartbeat
-
BBV46385 05/2009
[COMMUNICATION] (COM-) menu
rEF-
Code
Description
FLO
nO
LI1
LI2
LI3
LI4
LI5
LI6
Adjustment
range
M [Forced local assign.]
v [No] (nO): Not assigned
v [LI1] (LI1): Logic input LI1
v [LI2] (LI2): Logic input LI2
v [LI3] (LI3): Logic input LI3
v [LI4] (LI4): Logic input LI4
v [LI5] (LI5): Logic input LI5
v [LI6] (LI6): Logic input LI6
Factory
setting
SEt-
[No] (nO)
I-0-
drC-
CtLFUnFLtCOMSUP-
In forced local mode, the terminals and the display terminal regain control of the drive.
M [Forced local Ref.]
FLOC
g
AI1
AI2
AI3
AIU1
LCC
g
v
v
v
v
v
[AI1] (AI1)
Parameter can only be accessed if [ACCESS LEVEL] (LAC) = [Level 3] (L3), page 56.
In forced local mode, only the speed reference is taken into account. PI functions, summing inputs, etc. are
not active.
See the diagrams on pages 53 to 55.
[AI1] (AI1): Analog input AI1, logic inputs LI
[AI2] (AI2): Analog input AI2, logic inputs LI
[AI3] (AI3): Analog input AI3, logic inputs LI
[Network AI] (AIV1): Jog dial, RUN/STOP buttons
[HMI] (HMI): Remote display terminal: [HMI Frequency ref.] (LFr) reference, page 31, RUN/STOP/FWD/
REV buttons
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
93
[MONITORING] (SUP-) menu
rEFSEtdrCI-0CtLFUnFLtCOM-
Submenu
SUP-
The parameters can be accessed with the drive running or stopped.
On the optional remote display terminal, this menu can be accessed with the switch in any position.
Some functions have numerous parameters. In order to clarify programming and avoid having to scroll through endless parameters, these
functions have been grouped in submenus.
Like menus, submenus are identified by a dash after their code: LIA- for example.
When the drive is running, the value displayed is that of one of the monitoring parameters. By default, the value displayed is the output
frequency applied to the motor ([Output frequency] (rFr) parameter).
While the value of the new monitoring parameter required is being displayed, press and hold down the jog dial (ENT) again (for 2 seconds)
to confirm the change of monitoring parameter and store it. From then on, it is the value of this parameter that will be displayed during
operation (even after powering down).
"Unless the new choice is confirmed by pressing and holding down ENT again, the display will revert to the previous parameter after
powering down.
Note: After the drive has been turned off or following a loss of line supply, the parameter displayed is the drive status ([Ready] (rdY), for
example).
The selected parameter is displayed following a run command.
94
BBV46385 05/2009
[MONITORING] (SUP-) menu
rEF-
Code
Description
M [HMI Frequency ref.]
LFr
g
Variation range
SEt-
0 to 500 Hz
drCI-0-
Frequency reference for control via built-in display terminal or remote display terminal.
CtL-
M [Internal PID ref.]
rPI
0 to 100%
FUnFLt-
Internal PID reference
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 77.
g
M [Frequency ref.]
FrH
COM-
0 to 500 Hz
SUP-
Frequency reference before ramp (absolute value).
M [Output frequency]
rFr
- 500 Hz to + 500 Hz
This parameter is also used for the +/- speed function using the jog dial on the keypad or display terminal.
It displays and validates operation (see page 56). In the event of a loss of line supply, [Output frequency]
(rFr) is not stored and the +/- speed function must be re-enabled in [MONITORING] (SUP-) and [Output
frequency] (rFr).
SPd1
or
SPd2
or
SPd3
M [Cust. output value]
[Cust. output value] (SPd1), [Cust. output value] (SPd2) or [Cust. output value] (SPd3) depending on the
[Scale factor display] (SdS) parameter, page 38 ([Cust. output value] (SPd3) in the factory setting)
M [Motor current]
LCr
Estimation of current in the motor
M [Motor power]
Opr
100% = nominal motor power, calculated using the parameters entered in the [MOTOR CONTROL]
(drC-) menu
M [Mains voltage]
ULn
This parameter gives the line voltage via the DC bus, both in motor mode or when the motor is stopped.
M [Motor thermal state]
tHr
100% = nominal thermal state
118% = "OLF" threshold (drive overload)
M [Drv. Therm att.]
tHd
100% = nominal thermal state
118% = "OHF" threshold (drive overheating)
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.
BBV46385 05/2009
95
[MONITORING] (SUP-) menu
rEFSEt-
Code
drC-
LFt
I-0-
bLF
CFF
CFI
CnF
COF
CrF
EEF
EPF
IF1
IF2
IF3
IF4
LFF
nOF
ObF
OCF
OHF
OLF
OPF
OSF
PHF
SCF
SLF
SOF
tnF
USF
CtLFUnFLtCOMSUP-
Otr
Description
Variation range
M [Last fault occurred]
v [Brake control] (bLF): Brake control detected fault
v [Incorrect config.] (CFF): Incorrect configuration (parameters)
v [Invalid config.] (CFI): Invalid configuration (parameters)
v [NETWORK FAULT] (CnF): Communication detected fault on the communication card
v [CANopen com.] (COF): Communication detected fault line 2 (CANopen)
v [Capa.charg] (CrF): Capacitor precharge detected fault
v [EEPROM] (EEF): EEPROM memory detected fault
v [External] (EPF): External fault
v [INTERNAL FAULT] (IF1): Unknown rating
v [INTERNAL FAULT] (IF2): HMI card not recognized or incompatible/display absent
v [INTERNAL FAULT] (IF3): EEPROM detected fault
v [INTERNAL FAULT] (IF4): Industrial EEPROM detected fault
v [4-20mA] (LFF): 4-20 mA loss
v [No fault] (nOF): No fault code saved
v [Overbraking] (ObF): DC bus overvoltage
v [Overcurrent] (OCF): Overcurrent
v [Drive overheat] (OHF): Drive overheating
v [Motor overload] (OLF): Motor overload
v [Mot. phase] (OPF): Motor phase loss
v [Mains overvoltage] (OSF): Line supply overvoltage
v [Mains phase loss] (PHF): Line phase loss
v [Mot. short circuit] (SCF): Motor short-circuit (phase, ground)
v [Modbus] (SLF): Modbus communication detected fault
v [Overspeed] (SOF): Motor overspeed
v [Auto-tuning] (tnF): Auto-tuning detected fault
v [Undervoltage] (USF): Line supply undervoltage
M [Motor torque]
100% = nominal motor torque, calculated using the parameters entered in the [MOTOR CONTROL]
(drC-) menu.
rtH
M [Run time]
0 to 65,530 hours
Total time the motor has been powered up: 0 to 9,999 (hours), then 10.00 to 65.53 (kilo-hours).
Can be reset to zero by the [Operating t. reset] (rPr) parameter in the [FAULT MANAGEMENT] (FLt-)
menu, page 91.
96
BBV46385 05/2009
[MONITORING] (SUP-) menu
rEF-
Code
Description
SEt-
Variation range
drC-
M [PIN code 1]
COd
I-0-
Enables the drive configuration to be protected using an access code.
When access is locked by means of a code, only the parameters in the [MONITORING]
(SUP-) and [SPEED REFERENCE] (rEF-) menus can be accessed. The MODE button can be used to
switch between menus.
CtLFUnFLt-
0FF
v
On
v
8888
v
tUS
tAb
PEnd
PrOG
FAIL
dOnE
Strd
Note: Before entering a code, do not forget to make a careful note of it.
[OFF] (OFF): No access locking codes
• To lock access, enter a code (2 to 9,999). The display can be incremented using the jog dial. Then
press ENT. [ON] (On) appears on the screen to indicate that access has been locked.
[ON] (On): A code is locking access (2 to 9,999).
• To unlock access, enter the code (incrementing the display using the jog dial) and press ENT. The
code remains on the display and access is unlocked until the next time the drive is turned off. Access
will be locked again the next time the drive is turned on.
• If an incorrect code is entered, the display changes to [ON] (On), and access remains locked.
Access is unlocked (the code remains on the screen).
• To reactivate locking with the same code when access has been unlocked, return to [ON] (On)
using the jog dial and then press ENT. [ON] (On) remains on the screen to indicate that access has
been locked.
• To lock access with a new code when access has been unlocked, enter the new code (increment
the display using the jog dial) and then press ENT. On appears on the screen to indicate that access
has been locked.
• To clear locking when access has been unlocked, return to [OFF] (OFF) using the jog dial and then
press ENT. [OFF] (OFF) remains on the display. Access is unlocked and will remain so until the next
restart.
COMSUP-
M [Auto tuning state]
v [Not done] (tAb): The default stator resistance value is used to control the motor.
v [Pending] (PEnd): Auto-tuning has been requested but not yet performed.
v [In Progress] (PrOG): Auto-tuning in progress.
v [Failed] (FAIL): Auto-tuning was unsuccessful.
v [Done] (dOnE): The stator resistance measured by the auto-tuning function is used to control the motor.
v [Entered R1] (Strd): The cold state stator resistance ([Cold stator resist.] (rSC) which is not set to [No]
(nO)) is used to control the motor.
M [Drv.Soft.Ver]
UdP
This parameter gives the software version for the drive.
Example: 1102 = V1.1 IE02
O1Ct
M [OPT1 card type]
This parameter is only visible if an option card is present.
nO
dnt
PbS
CnF
It is used to visualize the name of the option currently present.
No card, CANopen card or DaisyChain card (these cards are unable to send their names to the
ATV312)
DeviceNet card
Profibus card
M [Network fault]
Option card fault code
This parameter is read-only and is only visible if an option card is present.
The fault code remains saved in the parameter, even if the cause disappears. The parameter is reset
after the drive is disconnected and then reconnected. The values of this parameter depend on the
network card. Consult the manual for the corresponding card.
BBV46385 05/2009
97
[MONITORING] (SUP-) menu
rEF-
Code
SEtdrCI-0-
LIA-
CtL-
Name/Description
b
FLtCOMSUP-
Factory
setting
[LOGIC INPUT CONF.]
Can be used to display the functions assigned to each input. If no functions have been assigned, [No] (nO)
is displayed. The jog dial can be used to scroll through all the functions. If a number of functions have been
assigned to the same input, check that they are compatible.
LI1A
LI2A
LI3A
LI4A
LI5A
LI6A
FUn-
Adjustment
range
Can be used to display the state of logic inputs (display segment assignment: high = 1, low = 0)
LIS
State 1
State 0
LI1
LI2 LI3
LI4 LI5
LI6
Example above: LI1 and LI6 are at 1; LI2 to LI5 are at 0.
AIAAI1A
AI2A
AI3A
98
b
[ANALOG INPUTS IMAGE]
Can be used to display the functions assigned to each input. If no functions have been assigned, [No] (nO)
is displayed. The jog dial can be used to scroll through all the functions. If a number of functions have been
assigned to the same input, check that they are compatible.
BBV46385 05/2009
Migration ATV31 - ATV312
The ATV312 is compatible with the ATV31.
To retrieve the configuration of the ATV31, simply transfer the configuration from the ATV31 to the ATV312.
Dimensions
For all sizes, the ATV312 is 6 mm less deep than the ATV31ppppppA.
Replacing an ATV31ppppppA with an ATV312
Note: Position of the logic input switch
On the ATV31ppppppA, the logic input switch was set to "Sink" in the factory setting.
On the ATV312, it is set to "Source" in the factory setting.
Set the switch to match the setting on the product being replaced. For more information, see the "Control terminals" chapter in the
Installation Manual.
Note: Position of the IT jumper
There was no integrated EMC filter on the ATV31ppppppA. For details on how to deactivate the integrated EMC filter on the ATV312, see
the "Operation with IT connection" chapter in the Installation Manual.
When the drive is powered up for the first time, the two parameters shown below appear after [Standard mot. freq] (bFr). They need to be
set as follows:
[Ref.1 channel] (Fr1), page 28, to [Network AI] (AIV1)
[2/3 wire control] (tCC), page 29, to [Local] (LOC)
The following parameters can be used subsequently to return to the other HMI version:
[Ref.1 channel] (Fr1) in the [COMMAND] (CtL-) menu
[2/3 wire control] (tCC) in the [INPUTS / OUTPUTS CFG] (I-O-) menu
Factory settings
As well as the differences in terms of control by potentiometer, the following differences apply between the factory settings for the
ATV31ppppppA and those of the ATV312:
Parameter
ATV31ppppppA
ATV312
[2/3 wire control] (tCC)
Local control LOC
[2 wire] (2C)
[Ref.1 channel] (Fr1)
Analog input AIP
AI1
[Cmd channel 1] (Cd1)
Local control LOC
tEr
[Reverse assign.] (rrS)
[No] (nO) (if [2/3 wire control] (tCC) = [Local] (LOC))
LI2
[Forced local Ref.] (FLOC)
AIP jog dial
AIU1
[Select ATV31 conf.] (ArE)
Parameter does not exist on the ATV31
[No] (nO)
Configuration transfer between an ATV31 and an ATV312 (using the ATV31 remote
terminal or a loader tool)
A new [Select ATV31 conf.] (ArE) parameter has been added to the [APPLICATION FUNCT.] (FUn-) menu.
It can be used to specify the ATV31 type (ATV31 or ATV31ppppppA) during transfers between an ATV31 and ATV312.
Values of the [Select ATV31 conf.] (ArE) parameter:
• [No] (nO), factory setting, transfer between two ATV312
• [ATV31...A] (31A), transfer from ATV31ppppppA to ATV312
• [ATV31 std] (31E), transfer from ATV31 to ATV312
To perform a configuration transfer, see the procedure on page 85.
BBV46385 05/2009
99
Diagnostics and troubleshooting
Drive does not start, no code displayed
• If the display does not light up, check the power supply to the drive and check the wiring of inputs AI1 and AI2 and the connection to
the RJ45 connector.
• The assignment of the "Fast stop" or "Freewheel stop" functions will prevent the drive from starting if the corresponding logic inputs
are not powered up. The ATV312 then displays [Freewheel stop] (nSt) or [Fast stop] (FSt). This is normal since these functions are
active at zero so that the drive will be stopped if there is a wire break.
• Check that the run command input(s) have been actuated in accordance with the chosen control mode (the [2/3 wire control] (tCC)
parameter in the [INPUTS / OUTPUTS CFG] (I-O-) menu, page 45).
• If an input is assigned to the limit switch function and this input is at zero, the drive can only be started up by sending a command for
the opposite direction (see page 84).
• If the reference channel (page 51) or the control channel (page 52) is assigned to a communication network, when the power supply
is connected, the drive will display [Freewheel stop] (nSt) and remain in stop mode until the communication bus sends a command.
• If the LED on the DC bus is lit and nothing appears on the display, check that there is no short-circuit on the 10 V power supply.
• If the drive displays [Ready] (rdy) and refuses to start, check that there is no short-circuit on the 10 V power supply and check the
wiring of inputs AI1 and AI2 and the connection to the RJ45 connector.
• In the factory setting, the "RUN" button is inactive. Set the [Ref.1 channel] (Fr1) parameter, page 28 , and the [Cmd channel 1] (Cd1)
parameter, page 57, to control the drive locally.
Fault detection codes which require a power reset after the fault is cleared
The cause of the fault must be removed before resetting by cycling power to the drive.
[PRECHARGE FAULT] (CrF), [OVERSPEED] (SOF), [AUTO-TUNING FAULT] (tnF), and [BRAKE CONTROL FAULT] (bLF) can also be
reset remotely using a logic input (the [Fault reset] (rSF) parameter in the [FAULT MANAGEMENT] (FLt-) menu, page 87).
Code
Name
bLF
[BRAKE CONTROL
FAULT]
• Brake release current not reached
• Brake engage frequency threshold
[Brake engage freq] (bEn) = [No]
(nO) (not set) whereas the brake
control [Brake assignment] (bLC) is
assigned
• Check the drive/motor connection.
• Check the motor windings.
• Check the [Brake release I FW] (Ibr) setting in the
[APPLICATION FUNCT.] (FUn-) menu, page 80.
• Apply the recommended settings for [Brake engage
freq] (bEn), pages 79 and 80.
CrF
[PRECHARGE
FAULT]
• Precharge relay control or damaged
precharge resistor
• Replace the drive.
EEF
[EEPROM FAULT]
• Internal memory
• Check the environment (electromagnetic
compatibility)
• Replace the drive.
IF1
[INTERNAL
FAULT]
• Unknown rating
IF2
[INTERNAL
FAULT]
• HMI card not recognized
• HMI card incompatible
• No display present
• Replace the drive.
• Restart the drive.
• Contact a Schneider Electric representative.
IF3
[INTERNAL
FAULT]
• EEPROM
IF4
[INTERNAL
FAULT]
• Industrial EEPROM
100
Probable cause
Remedy
BBV46385 05/2009
Diagnostics and troubleshooting (continued)
Fault detection codes which require a power reset after the fault is cleared
(continued)
Code
Name
Probable cause
Remedy
OCF
[OVERCURRENT]
• Parameters in the [SETTINGS]
(SEt-) and [MOTOR CONTROL]
(drC-) menus are incorrect.
• Inertia or load too high
• Mechanical locking
• Check the parameters in [SETTINGS] (SEt-) , page
31, and [MOTOR CONTROL] (drC-) page 39.
• Check the size of the motor/drive/load.
• Check the state of the mechanism.
SCF
[MOTOR SHORT
CIRCUIT]
• Short-circuit or grounding at the
drive output
• Significant ground leakage current at
the drive output if several motors are
connected in parallel
• Check the cables connecting the drive to the motor,
and the motor insulation.
• Reduce the switching frequency
• Connect chokes in series with the motor
SOF
[OVERSPEED]
• Instability or
• Driving load too high
• Check the motor, gain and stability parameters
• Add a braking resistor
• Check the size of the motor/drive/load.
tnF
[AUTO TUNING
FAULT]
• Special motor or motor whose power
is not suitable for the drive
• Motor not connected to the drive
• Use the L ratio or the [Var. torque] (P) ratio (see [U/F
mot 1 selected] (UFt), page 42).
• Check that the motor is present during auto-tuning.
• If an output contactor is being used, close it during
auto-tuning.
Fault detection codes that can be reset with the automatic restart function after the
cause has disappeared
See the [Automatic restart] (Atr) function, page 86.
These detected faults can also be reset by turning the drive off then on again or by means of a logic input (the [Fault reset] (rSF) parameter,
page 87, in the [FAULT MANAGEMENT] (FLt-) menu, page 86).
Code
Name
Probable cause
Remedy
CnF
[NETWORK FAULT]
• Communication detected fault on the
communication card
• Check the environment (electromagnetic
compatibility)
• Check the wiring.
• Check the time out.
• Replace the option card.
COF
[CANopen FAULT]
• Interruption in communication on the
CANopen bus
• Check the communication bus
• Refer to the relevant product documentation.
EPF
[EXTERNAL FAULT]
• Depending on user
• Depending on user
LFF
[4-20mA LOSS]
• Loss of the 4-20 mA reference on
input AI3
• Check the connection on input AI3.
ObF
[OVERBRAKING]
• Braking too sudden
or driving load
• Increase the deceleration time
• Install a braking resistor if necessary.
• Activate the [Dec ramp adapt.] (bra) function,
page 62, if it is compatible with the application.
OHF
[DRIVE OVERHEAT]
• Drive temperature too high
• Check the motor load, the drive ventilation and the
environment. Wait for the drive to cool before
restarting.
BBV46385 05/2009
101
Diagnostics and troubleshooting (continued)
Fault detection codes that can be reset with the automatic restart function after the
cause has disappeared (continued)
Code
OLF
Name
[MOTOR OVERLOAD]
Probable cause
• Triggered by excessive motor
current
• [Cold stator resist.] (rSC) parameter
value incorrect
Remedy
• Check the [Mot. therm. current] (ItH) setting, page
32, of the motor thermal protection, check the
motor load. Wait for the drive to cool before
restarting.
• Remeasure [Cold stator resist.] (rSC), page 40.
OPF
[MOTOR PHASE
LOSS]
• Loss of one phase at drive output
• Output contactor open
• Motor not connected or motor power
too low
• Instantaneous instability in the motor
current
• Check the connections from the drive to the motor.
• If an output contactor is being used, set [Output
Phase Loss] (OPL) to [Output cut] (OAC) ([FAULT
MANAGEMENT] (FLt-) menu, page 89).
• Test on a low-power motor or without a motor: In
factory settings mode, motor output phase loss
detection is active ([Output Phase Loss] (OPL) =
[Yes] (YES)). To check the drive in a test or
maintenance environment without having to
switch to a motor with the same rating as the drive
(particularly useful in the case of high-power
drives), deactivate motor phase loss detection
([Output Phase Loss] (OPL) = [No] (nO)).
• Check and optimize the [IR compensation] (UFr),
[Rated motor volt.] (UnS), and [Rated mot. current]
(nCr) parameters, and perform an [Auto tuning]
(tUn) operation, page 41.
OSF
[MAINS
OVERVOLTAGE]
• Line voltage is too high.
• Disturbed line supply
• Check the line voltage.
PHF
[INPUT PHASE LOSS]
SLF
[MODBUS FAULT]
102
• Drive incorrectly supplied or a fuse
blown
• Failure of one phase
• Three-phase ATV312 used on a
single-phase line supply
• Unbalanced load
This protection only operates with the drive
on load
• Interruption in communication on the
Modbus bus
• Remote display terminal enabled
([HMI command] (LCC) = [Yes]
(YES), page 58) and terminal
disconnected.
•
•
•
•
Check the power connection and the fuses.
Reset
Use a three-phase line supply.
Disable the detection by setting [Input phase loss]
(IPL) = [No] (nO) ([FAULT MANAGEMENT] (FLt-)
menu, page 89).
• Check the communication bus
• Refer to the relevant product documentation.
• Check the link with the remote display terminal.
BBV46385 05/2009
Diagnostics and troubleshooting (continued)
Fault detection codes that are reset as soon as their cause disappears
Code
Name
Probable cause
Remedy
CFF
[INCORRECT
CONFIG.]
• The current configuration is
inconsistent.
• Addition or removal of an option
• Return to factory settings or retrieve the backup
configuration, if it is valid. See the [Restore config.]
(FCS) parameter, page 44.
CFI
[INVALID CONFIG]
• Invalid configuration
The configuration loaded in the
drive via the serial link is
inconsistent
• Check the configuration loaded previously.
• Load a consistent configuration.
USF
[UNDERVOLTAGE]
• Insufficient line supply
• Transient voltage dip
• Check the voltage and the voltage parameter.
Tripping threshold in [UNDERVOLTAGE] (USF)
ATV312ppppM2: 160 V
ATV312ppppM3: 160 V
ATV312ppppN4: 300 V
ATV312ppppS6: 430 V
• Replace the drive.
• Damaged precharge resistor
BBV46385 05/2009
103
Diagnostics and troubleshooting (continued)
Fault detection codes displayed on the ATV12 remote display terminal
Code
Name
Description
Initialization in
progress
• The microcontroller is initializing.
• Search underway for communication configuration
Communication error
• Time out detected fault (50 ms)
• This message is displayed after 20 attempts at communication.
Alarm button
• A button has been held down for more than 10 seconds.
• The keypad is disconnected.
• The "keypad" wakes up when a button is pressed.
Confirmation of
detected fault reset
• This is displayed when the STOP button is pressed once during a remote terminal detected
fault.
dEU.E
(1)
Drive disparity
• The drive brand does not match that of the remote terminal.
rOM.E
(1)
ROM anomaly
• The remote terminal detects a ROM anomaly on the basis of checksum calculation.
rAM.E
(1)
RAM anomaly
• The remote terminal detects a RAM anomaly.
CPU.E
(1)
Other detected faults
• Other detected faults
InIt:
COM.E
(1)
A-17
(1)
cLr
(1)
(1) Flashing
104
BBV46385 05/2009
Index of functions
[+/- SPEED]
73
[2/3 wire control]
45
[ACCESS LEVEL]
56
[Analog./logic output]
46
[Auto DC injection]
65
[Automatic restart]
86
[Auto tuning]
41
Brake control
79
[CANopen address]
92
[Catch on the fly]
88
[Cmd switching]
58
Control and reference channels
48
[Current limit 2]
81
[Current Limitation]
36
[DC injection assign.]
63
[Dec ramp adapt.]
62
Drive thermal protection
11
Drive ventilation
11
[Fast stop]
63
[Fault reset]
87
[Forced local assign.]
93
[Freewheel stop ass.]
64
[JOG]
72
Management of limit switches
84
[Modbus Address]
92
[Mot. therm. current]
32
Motor thermal protection
12
PI regulator
75
Preset speeds
68
[R1 Assignment]
47
[R2 Assignment]
47
[RAMPS]
60
[Ramp switch ass.]
62
[Ref. 2 switching]
57
Return to factory settings/Restore configuration
44
Saving the configuration
43
[Skip Frequency]
34
[STOP MODES]
63
[SUMMING INPUTS]
67
[Switching freq.]
38
[SWITCHING MOTOR]
82
[U/F mot 1 selected]
42
BBV46385 05/2009
105
Index of parameter codes and customer settings
Page
AC2
31
62
[Acceleration 2]
s
In accordance
with Inr
-
5
ACC
31
61
[Acceleration]
s
In accordance
with Inr
-
3
AdC
65
[Auto DC injection]
-
nO
YES
Ct
[No]: No injection
[Yes]: Standstill injection for adjustable period
[Continuous]: Continuous standstill injection
AdCO
92
[CANopen address]
-
0 to 127
-
0
Add
92
[Modbus Address]
-
1 to 247
-
1
AI1A
98
[AI1 assignment]
-
-
-
-
AI2A
98
[AI2 assignment]
-
-
-
-
AI3A
98
[AI3 assignment]
-
-
-
-
AIU1
30
[Image input AIV1]
%
0 to 100
-
-
AO1t
46
[AO1 Type]
-
0A
4A
10U
[Current]: Configuration 0 - 20 mA
[Cur. 4-20]: Configuration 4 - 20 mA
[Voltage]: Configuration 0 - 10 V
0
ArE
85
[Select ATV31 conf.]
nO
31A
nO
31E
[No]: Transfer between two ATV312
[ATV31...A]: Transfer from an ATV31ppppppA to an
ATV312
[ATV31 std] : Transfer from an ATV31 to an ATV312
nO
YES
[No]: Function inactive
[Yes]: Automatic restart
nO
10.0
20.0
50.0
125.0
250.0
500.0
1000
[10 kbps]: 10 kbps
[20 kbps]: 20 kbps
[50 kbps]: 50 kbps
[125 kbps]: 125 kbps
[250 kbps]: 250 kbps
[500 kbps]: 500 kbps
[1 Mbps]: 1000 kbps
Atr
86
Name
[Automatic restart]
Unit
-
kbps
Value/Possible function
Factory
setting
Code
Customer
setting
YES
bdCO
92
[CANopen bit rate]
bEn
80
[Brake engage freq]
-
nO
0 to LSP
Not set
Adjustment range in Hz
bEt
80
[Brake engage time]
s
0 to 5
-
bFr
28
39
[Standard mot. freq]
Hz
50
60
[50Hz IEC]
[60Hz NEMA]
50
nO
[No]: Motor torque during brake release in the direction
of rotation requested
[Yes]: Motor torque during brake release in forward
rotation
nO
125.0
nO
0.5
bIP
80
[Brake impulse]
-
bLC
80
[Brake assignment]
-
nO
r2
dO
[No]: Not assigned
[R2]: Relay R2
[DO]: Logic output AOC
nO
brA
62
[Dec ramp adapt.]
-
nO
YES
[No]: Function inactive
[Yes]: Function active
YES
brL
80
[Brake release freq]
Hz
0.0 to 10.0
-
In accordance
with the drive
rating
brt
80
[Brake Release time]
s
0 to 5
-
0.5
106
YES
BBV46385 05/2009
Index of parameter codes and customer settings
Code
CCS
Cd1
Page
58
57
Name
[Cmd switching]
[Cmd channel 1]
Factory
setting
-
Cd1
Cd2
LI1
LI2
LI3
LI4
LI5
LI6
C111
C112
C113
C114
C115
C211
C212
C213
C214
C215
[ch1 active] : Control channel = channel 1
[ch2 active] : Control channel = channel 2
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[C111]: Bit 11 of Modbus control word
[C112]: Bit 12 of Modbus control word
[C113]: Bit 13 of Modbus control word
[C114]: Bit 14 of Modbus control word
[C115]: Bit 15 of Modbus control word
[C211]: Bit 11 of network control word
[C212]: Bit 12 of network control word
[C213]: Bit 13 of network control word
[C214]: Bit 14 of network control word
[C215]: Bit 15 of network control word
Cd1
-
tEr
LOC
LCC
Ndb
nEt
[Terminal]: Control via terminals
[Local]: Control via keypad
[Remot. HMI]: Control via remote display terminal
[Modbus]: Control via Modbus
[Network]: Control via the network
tEr
-
tEr
LOC
LCC
Ndb
nEt
[Terminal]: Control via terminals
[Local]: Control via keypad
[Remot. HMI]: Control via remote display terminal
[Modbus]: Control via Modbus
[Network]: Control via the network
Mdb
StS
Std
[Start/Stop]: Start/stop configuration
[Factory set.]: Factory configuration
SIN
SEP
[Not separ.]: Combined
[Separate]: Separate
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication
network
[CD12]: Bit 12 of the control word from a communication
network
[CD13]: Bit 13 of the control word from a communication
network
[CD14]: Bit 14 of the control word from a communication
network
[CD15]: Bit 15 of the control word from a communication
network
Cd2
57
CFG
43
47
59
85
[Macro configuration]
-
CHCF
57
[Profile]
-
CHP
82
[Cmd channel 2]
Value/Possible function
Unit
[Motor switching]
Cd12
Cd13
Cd14
Cd15
Std
SIM
nO
CLI
36
[Current Limitation]
In
0.25 to 1.5
-
1.5
CL2
36
81
[I Limit. 2 value]
In
0.25 to 1.5
-
1.5
CnF
97
[Network fault]
-
-
-
-
COd
97
[PIN code 1]
-
0FF
On
8888
[OFF]: No code is locking access
[ON]:
A code is locking access.
Access is unlocked.
-
BBV46385 05/2009
Customer
setting
107
Index of parameter codes and customer settings
Code
Page
Name
Unit
Value/Possible function
nO
YES
COL
90
[CANopen fault mgt]
-
rNP
FSt
[Ignore]: Ignore
[Freewheel]: Detected fault management with
freewheel stop
[Ramp stop]: Detected fault management with stop
on ramp
[Fast stop]: Detected fault management with fast
stop
[No]: No copy
[Reference]: Copy reference
[Command]: Copy command
[Cmd + ref.] : Copy command and reference
Factory
setting
Customer
setting
YES
COp
58
[Copy channel 1<>2]
-
nO
SP
Cd
ALL
COS
40
[Motor 1 Cosinus Phi]
-
0.5 to 1
-
In accordance
with the drive
rating
COS2
83
[Motor 2 Cosinus Phi]
-
0.5 to 1
-
In accordance
with the drive
rating
CrH3
46
[AI3 max. value]
mA
4 to 20
-
20
CrL3
46
[AI3 min. value]
mA
0 to 20
-
4
Ctd
37
[Current threshold]
In
0 to 1.5
-
1
dCF
63
[Differential current fault]
-
0 to 10
-
4
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a
communication network
[CD12]: Bit 12 of the control word from a
communication network
[CD13]: Bit 13 of the control word from a
communication network
[CD14]: Bit 14 of the control word from a
communication network
[CD15]: Bit 15 of the control word from a
communication network
dCI
63
[DC injection assign.]
Cd12
Cd13
Cd14
Cd15
nO
nO
dE2
31
62
[Deceleration 2]
s
In
accordance
with Inr
-
5
dEC
31
61
[[Deceleration]
s
In
accordance
with Inr
-
3
[No]: Not assigned
[I motor]: Motor current
[Motor freq.]: Motor frequency
[Motor torq.]: Motor torque
[P. supplied]: Power supplied by the drive
[Drive fault]: Detected fault.
[Drv running]: Drive running
[Freq. limit]: Frequency threshold reached
[HSP limit]: High speed reached
[Brake seq.]: Current threshold reached
[Freq. ref.]: Frequency reference reached
[Drv thermal]: Motor thermal threshold reached
[Brake seq.]: Brake sequence
[No 4-20mA]: Loss of 4-20 mA signal
nO
[No]: Function inactive
[Yes]: Function active
nO
dO
46
[Analog./logic output]
-
nO
OCr
OFr
Otr
OPr
FLt
rUn
FtA
FLA
CtA
SrA
tSA
bLC
APL
drn
91
[Derated operation]
-
nO
YES
108
BBV46385 05/2009
Index of parameter codes and customer settings
Code
dSP
EPL
ErCO
EtF
Page
74
88
92
88
Name
[-Speed assignment]
[External fault mgt]
[Error code]
[External fault ass.]
Unit
-
-
-
Value/Possible function
nO
LI1
LI2
LI3
LI4
LI5
LI6
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nO
YES
FSt
[Ignore]: Ignore
[Freewheel]: Detected fault management with
freewheel stop
[Ramp stop]]: Detected fault management with stop on
ramp
[Fast stop]: Detected fault management with fast stop
0
1
2
3
4
No error
Bus off
Life time
CAN overrun
Heartbeat
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a
communication network
[CD12]: Bit 12 of the control word from a
communication network
[CD13]: Bit 13 of the control word from a
communication network
[CD14]: Bit 14 of the control word from a
communication network
[CD15]: Bit 15 of the control word from a
communication network
rNP
Cd12
Cd13
Cd14
Cd15
FbS
34
77
FCS
44
47
59
85
[Restore config.]
FLG
32
[FreqLoopGain]
%
FLG2
37
83
[FreqLoopGain 2]
FLO
93
[PID fbk scale factor]
-
YES
-
nO
1
nO
1 to 100
-
20
%
1 to 100
-
20
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nO
AI1
AI2
AI3
AIUI
LCC
[AI1]: Analog input AI1, logic inputs LI
[AI2]: Analog input AI2, logic inputs LI
[AI3]: Analog input AI3, logic inputs LI
[Network AI]: Jog dial, RUN/STOP buttons
[HMI]: Remote display terminal, RUN/STOP/FWD/
REV buttons
nO
YES
[No]: Function inactive
[Yes]: Function active
InI
[Forced local assign.]
-
93
[Forced local Ref.]
-
FLr
88
[Catch on the fly]
-
Customer
setting
nO
[NO]: Function inactive
[Internal]: The current configuration becomes identical
to the backup configuration previously saved by SCS
= StrI.
[Config. CFG]: Current configuration replaced by the
configuration selected by the CFG parameter.
nO
rECI
FLOC
BBV46385 05/2009
0.1 to
100
Factory
setting
AI1
nO
109
Index of parameter codes and customer settings
Code
Fr1
Page
28
56
Name
[Ref.1 channel]
Unit
-
Value/Possible function
[AI1]: Analog input AI1
[AI2]: Analog input AI2
[AI3]: Analog input AI3
[Network AI]: Jog dial
[+/-Speed]: +/- speed reference via LI
[+/-spd HMI]: +/- speed reference using the jog dial on
the ATV312 keypad
[HMI]: Reference via the remote display terminal
[Modbus]: Reference via Modbus
[Network]: Reference via network
AI1
nO
LCC
Ndb
nEt
[No]: Not assigned
[AI1]: Analog input AI1
[AI2]: Analog input AI2
[AI3]: Analog input AI3
[Network AI]: Jog dial
[+/-Speed]: +/- speed reference via LI
[+/-spd HMI]: +/- speed reference using the jog dial on
the ATV312 keypad
[HMI]: Reference via the remote display terminal
[Modbus]: Reference via Modbus
[Network]: Reference via network
AI1
AI2
AI3
AIU1
UPdt
UpdH
LCC
Ndb
nEt
Fr2
56
[Ref.2 channel]
-
Factory
setting
nO
AI1
AI2
AI3
AIU1
UPdt
UpdH
FrH
95
[Frequency ref.]
Hz
0 to 500
-
-
FrS
39
[Rated motor volt.]
Hz
10 to 500
-
50
FrS2
82
[Nom. motor 2 freq.]
Hz
10 to 500
-
50
Frt
62
[Ramp 2 threshold]
Hz
0 to 500
-
0
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication
network
[CD12]: Bit 12 of the control word from a communication
network
[CD13]: Bit 13 of the control word from a communication
network
[CD14]: Bit 14 of the control word from a communication
network
[CD15]: Bit 15 of the control word from a communication
network
FSt
63
[Fast stop]
Cd12
Cd13
Cd14
Cd15
Customer
setting
nO
Ftd
37
[Freq. threshold]
Hz
0 to 500
-
bFr
HSP
32
[High speed]
Hz
LSP to tFr
-
bFr
Ibr
80
[Brake release I FW]
In
0 to 1.36
-
In accordance
with the drive
rating
IdC
33
64
[DC inject. level 1]
In
0 to In
-
0.7
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
InH
110
91
[Fault inhibit assign.]
nO
BBV46385 05/2009
Index of parameter codes and customer settings
Name
Page
Inr
61
[Ramp increment]
-
0.01
0.1
1
[0.01]: Ramp can be set between 0.05 s and 327.6 s.
[0.1]: Ramp can be set between 0.1 s and 3,276 s.
[1]: Ramp can be set between 1 s and 32,760 s.
0.1
IPL
89
[Input phase loss]
-
nO
YES
[No]: Ignore
[Yes]: Detected fault management with fast stop
YES
ItH
32
[Mot. therm. current]
In
0.2 to 1.5
-
In accordance
with the
drive rating
JF2
34
[Skip Frequency 2]
Hz
1 to 500
-
0
JGF
34
72
[Jog frequency]
Hz
0 to 10
-
10
nO
LI1
LI2
LI3
LI4
LI5
LI6
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nO
0 to 500
-
L1
L2
[Level 1]: Access to standard functions
[Level 2]: Access to advanced functions in the FUnmenu
[Level 3]: Access to advanced functions and management of
mixed control modes
L1
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nO
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nO
JOG
72
[JOG]
JPF
34
[Skip Frequency]
LAC
56
[ACCESS LEVEL]
Unit
-
Hz
Value/Possible function
Factory
setting
Code
L3
LAF
84
[Stop FW limit sw.]
0
LAr
84
[Stop RV limit sw.]
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
LAS
84
[Stop type]
-
rMP
FSt
nSt
[Ramp stop]: On ramp
[Fast stop]: Fast stop
[Freewheel]: Freewheel stop
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication
network
[CD12]: Bit 12 of the control word from a communication
network
[CD13]: Bit 13 of the control word from a communication
network
[CD14]: Bit 14 of the control word from a communication
network
[CD15]: Bit 15 of the control word from a communication
network
nO
nO
LC2
81
[Current limit 2]
Cd12
Cd13
Cd14
Cd15
LCC
58
[HMI command]
-
nO
YES
[No]: Function inactive
[Yes]: Enables control of the drive using the STOP/RESET,
RUN and FWD/REV buttons on the display terminal
LCr
95
[Motor current]
A
-
-
BBV46385 05/2009
Customer
setting
nSt
-
111
Index of parameter codes and customer settings
Code
Page
Name
LEt
88
[External fault config]
LFF
90
[Fallback speed]
Unit
Value/Possible function
LO
LFL
90
[4-20mA loss]
-
Hz
HIG
31
95
[HMI Frequency ref.]
Customer
setting
HIG
0 to 500
-
nO
YES
FSt
[Ignore]: Ignore
[Freewheel]: Detected fault management with
freewheel stop
[fallback spd]: The drive switches to the fallback speed.
[Spd maint.]: The drive maintains the speed at which it
was operating when the fault occurred.
[Ramp stop]: Detected fault management with stop on
ramp
[Fast stop] : Detected fault management with fast stop
-
0 to HSP
-
[Brake control]: Brake control detected fault
[Incorrect config.]: Incorrect configuration
[Invalid config.]: Invalid configuration
[NETWORK FAULT]: Communication detected fault on the communication card
[CANopen com.]: Communication detected fault line 2 (CANopen)
[Capa.charg]: Capacitor precharge detected fault
[EEPROM]: EEPROM memory detected fault
[External]: External fault
[INTERNAL FAULT]: Unknown rating
[INTERNAL FAULT]: HMI card not recognized or incompatible/display absent
[INTERNAL FAULT]: EEPROM detected fault
[INTERNAL FAULT]: Industrial EEPROM detected fault
[4-20mA]: 4-20 mA loss
[No fault]: No fault code saved
[Overbraking]: DC bus overvoltage
[Overcurrent]: Overcurrent
[Drive overheat]: Drive overheating
[Motor overload]: Motor overload
[Mot. phase]: Motor phase loss
[Mains overvoltage]: Line supply overvoltage
[Mains phase loss]: Line phase loss
[Mot. short circuit]: Motor short-circuit (phase, ground)
[Modbus]: Modbus communication detected fault
[Overspeed]: Motor overspeed
[Auto-tuning]: Auto-tuning detected fault
[Undervoltage]: Line supply undervoltage
-
LFF
rLS
rNP
LFr
[Active low]: The external fault is detected when the
logic input assigned to EtF changes to state 0.
[Active high]: The external fault is detected when the
logic input or bit assigned to EtF changes to state 1.
Factory
setting
10
YES
-
LFt
96
[Last fault occurred]
-
bLF
CFF
CFI
CnF
COF
CrF
EEF
EPF
IF1
IF2
IF3
IF4
LFF
nOF
ObF
OCF
OHF
OLF
OPF
OSF
PHF
SCF
SLF
SOF
tnF
USF
LI1A
98
[Config.LI1]
-
-
LI2A
98
[Config.LI2]
-
-
LI3A
98
[Config.LI3]
-
-
LI4A
98
[Config.LI4]
-
-
LI5A
98
[Config.LI5]
-
-
LI6A
98
[Config.LI6]
-
-
LSP
32
80
[Low speed]
Hz
0 to HSP
-
0
nCr
39
[Rated mot. current]
In
0.25 to 1.5
-
In accordance
with the
drive rating
nCr2
83
[Nom. mot. 2 current]
In
0.25 to 1.5
-
In accordance
with the
drive rating
nrd
42
[Noise reduction]
-
YES
nO
[Yes]: Frequency with random modulation
[No]: Fixed frequency
112
YES
BBV46385 05/2009
Index of parameter codes and customer settings
Code
Page
nSP
nSP2
Unit
40
[Rated motor speed]
rpm
0 to 32,760
-
In accordance
with the
drive rating
83
[Nom. mot. 2 speed]
rpm
0 to 32,760
-
In accordance
with the
drive rating
nO
LI1
LI2
LI3
LI4
LI5
LI6
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nSt
64
[Freewheel stop ass.]
-
O1Ct
97
[OPT1 card type]
-
Value/Possible function
89
[Overtemp fault mgt]
-
YES
[Ignore]: Ignore
[Freewheel]: Detected fault management with freewheel
stop
[Ramp stop]: Detected fault management with stop on
ramp
[Fast stop]: Detected fault management with fast stop
YES
nO
YES
OAC
[No]: Function inactive
[Yes]: Tripping on OPF
[Output cut]: No tripping on [MOTOR PHASE LOSS]
(OPF), but output voltage is managed
YES
rNP
nO
YES
89
[Overload fault mgt]
-
nO
[Ignore]: Ignore
[Freewheel]: Detected fault management with freewheel
stop
[Ramp stop]: Detected fault management with stop on
ramp
[Fast stop]: Detected fault management with fast stop
FSt
OLL
rNP
FSt
OPL
89
[Output Phase Loss]
-
Opr
95
[Motor power]
%
-
-
-
Otr
96
[Motor torque]
%
-
-
-
PIC
34
77
[PID correct. reverse]
-
nO
YES
[No]: Normal
[Yes]: Reverse
nO
-
nO
AI1
AI2
AI3
[No]: Not assigned
[AI1]: Analog input AI1
[AI2]: Analog input AI2
[AI3]: Analog input AI3
nO
nO
[No]: The reference for the PI regulator is Fr1, except
for UPdH and UPdt.
[Yes]: The reference for the PI regulator is provided
internally via the rPI parameter.
nO
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication
network
[CD12]: Bit 12 of the control word from a communication
network
[CD13]: Bit 13 of the control word from a communication
network
[CD14]: Bit 14 of the control word from a communication
network
[CD15]: Bit 15 of the control word from a communication
network
nO
PIF
PII
77
78
[PID feedback ass.]
[Act. internal PID ref.]
-
YES
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Pr2
77
[2 preset PID ref.]
Cd12
Cd13
Cd14
Cd15
BBV46385 05/2009
Customer
setting
YES
nO
YES
OHL
Factory
setting
Name
113
Index of parameter codes and customer settings
Code
Pr4
PS16
PS2
PS4
Page
78
70
69
69
Name
[4 preset PID ref.]
[16 preset speeds]
[2 preset speeds]
[4 preset speeds]
Unit
Value/Possible function
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication network
[CD12]: Bit 12 of the control word from a communication network
[CD13]: Bit 13 of the control word from a communication network
[CD14]: Bit 14 of the control word from a communication network
[CD15]: Bit 15 of the control word from a communication network
nO
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication network
[CD12]: Bit 12 of the control word from a communication network
[CD13]: Bit 13 of the control word from a communication network
[CD14]: Bit 14 of the control word from a communication network
[CD15]: Bit 15 of the control word from a communication network
nO
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication network
[CD12]: Bit 12 of the control word from a communication network
[CD13]: Bit 13 of the control word from a communication network
[CD14]: Bit 14 of the control word from a communication network
[CD15]: Bit 15 of the control word from a communication network
LI3
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication network
[CD12]: Bit 12 of the control word from a communication network
[CD13]: Bit 13 of the control word from a communication network
[CD14]: Bit 14 of the control word from a communication network
[CD15]: Bit 15 of the control word from a communication network
LI4
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication network
[CD12]: Bit 12 of the control word from a communication network
[CD13]: Bit 13 of the control word from a communication network
[CD14]: Bit 14 of the control word from a communication network
[CD15]: Bit 15 of the control word from a communication network
nO
[No]: Function inactive
[Yes]: STOP key priority
PS8
69
[8 preset speeds]
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
PSt
59
[[Stop Key priority]]
-
nO
YES
114
Factory
setting
Customer
setting
YES
BBV46385 05/2009
Index of parameter codes and customer settings
Code
r1
r2
Page
47
47
Name
Unit
Value/Possible function
Factory
setting
nO
FLt
rUn
FtA
FLA
CtA
SrA
tSA
APL
LI1 to LI6
[No]: Not assigned
[No drive flt]: No drive detected fault
[Drv running] : Drive running
[Freq.Th.att.]: Frequency threshold reached
[HSP attain.] : High speed reached
[I attained] : Current threshold reached
[Freq.ref.att]: Frequency reference reached
[Th.mot. att.]: Motor thermal threshold reached
[4-20mA]: Loss of 4-20 mA signal
[LI1] to [LI6]: Returns the value of the selected logic input
FLt
[R2 Assignment]
nO
FLt
rUn
FtA
FLA
CtA
SrA
tSA
bLC
APL
LI1 to LI6
[No]: Not assigned
[No drive flt]: No drive detected fault
[Drv running] : Drive running
[Freq.Th.att.]: Frequency threshold reached
[HSP attain.] : High speed reached
[I attained] : Current threshold reached
[Freq.ref.att]: Frequency reference reached
[Th.mot. att.]: Motor thermal threshold reached
[Brk control]: Brake sequence
[4-20mA]: Loss of 4-20 mA signal
[LI1] to [LI6]: Returns the value of the selected logic input
nO
Fr1
Fr2
LI1
LI2
LI3
LI4
LI5
LI6
C111
C112
C113
C114
C115
C211
C212
C213
C214
C215
[ch1 active] : Reference 1
[ch2 active] : Reference 2
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[C111]: Bit 11 of Modbus control word
[C112]: Bit 12 of Modbus control word
[C113]: Bit 13 of Modbus control word
[C114]: Bit 14 of Modbus control word
[C115]: Bit 15 of Modbus control word
[C211]: Bit 11 of network control word
[C212]: Bit 12 of network control word
[C213]: Bit 13 of network control word
[C214]: Bit 14 of network control word
[C215]: Bit 15 of network control word
[R1 Assignment]
-
rFC
57
[Ref. 2 switching]
rFr
95
[Output frequency]
Hz
-500 to +500
-
-
rIG
34
77
[PID integral gain]
-
0.01 to 100
-
1
rOt
59
[Rotating direction]
-
dFr
drS
bOt
[Forward]: Forward
[Reverse]: Reverse
[Both]: Both directions are authorized.
rp
91
[Product reset]
-
nO
YES
[No]: No
[Yes]: Yes
nO
rP2
34
78
[Preset ref. PID 2]
%
0 to 100
-
30
rp3
34
78
[Preset ref. PID 3]
%
0 to 100
-
60
rp4
34
78
[Preset ref. PID 4]
%
0 to 100
-
90
rPG
34
77
[PID prop. gain]
-
0.01 to 100
-
1
rPI
31
78
95
[Internal PID ref.]
%
0 to 100
-
0
rPr
91
[Operating t. reset]
-
nO
rtH
[No]: No
[rst. runtime]: Operating time reset to zero
BBV46385 05/2009
-
Customer
setting
Fr1
dFr
nO
115
Index of parameter codes and customer settings
Code
Page
Name
Unit
Value/Possible function
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
[CD11]: Bit 11 of the control word from a communication network
[CD12]: Bit 12 of the control word from a communication network
[CD13]: Bit 13 of the control word from a communication network
[CD14]: Bit 14 of the control word from a communication network
[CD15]: Bit 15 of the control word from a communication network
Factory
setting
rPS
62
[Ramp switch ass.]
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
Cd11
Cd12
Cd13
Cd14
Cd15
rPt
60
[Ramp type]
-
LIn
S
U
CUS
[Linear]: Linear
[S ramp]: S ramp
[U ramp]: U ramp
[Customized]: Customized
LIn
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2 can be accessed if tCC = 2C.
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
LI2
nO
rrS
46
[Reverse assign.]
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
rSC
40
[Cold stator resist.]
-
nO
InIt
8888
[NO]: Function inactive
[Init]: Activates the function
Value of cold state stator resistance used
nO
[No]: Not assigned
[LI1]: Logic input LI1
[LI2]: Logic input LI2
[LI3]: Logic input LI3
[LI4]: Logic input LI4
[LI5]: Logic input LI5
[LI6]: Logic input LI6
nO
rSF
87
[Fault reset]
-
nO
LI1
LI2
LI3
LI4
LI5
LI6
rSL
36
78
[PID wake up thresh.]
%
0
to 100
-
0
rtH
96
[Run time]
-
-
-
nO
AI1
AI2
AI3
AIU1
LCC
Ndb
nEt
[No]: Not assigned
[AI1]: Analog input AI1
[AI2]: Analog input AI2
[AI3]: Analog input AI3
[Network AI]: Jog dial
[HMI]: Reference via the remote display terminal
[Modbus]: Reference via Modbus
[Network]: Reference via network
nO
AI1
AI2
AI3
AIU1
LCC
Ndb
nEt
[No]: Not assigned
[AI1]: Analog input AI1
[AI2]: Analog input AI2
[AI3]: Analog input AI3
[Network AI]: Jog dial
[HMI]: Reference via the remote display terminal
[Modbus]: Reference via Modbus
[Network]: Reference via network
nO
StrI
[No]: Function inactive
[Config 1] : Saves the current configuration to EEPROM
SA2
67
[Summing ref. 2]
-
-
AI2
SA3
67
SCS
43
47
59
85
[Saving config.]
-
SdC1
33
65
[Auto DC inj. level 1]
In
0
to 1.2
-
0.7
SdC2
33
66
[Auto DC inj. level 2]
In
0
to 1.2
-
0.5
SdS
38
[Scale factor display]
-
0.1
to 200
-
30
116
[Summing ref. 3]
Time
Customer
setting
nO
nO
BBV46385 05/2009
Index of parameter codes and customer settings
Code
Page
SFr
38
42
Name
Unit
[Switching freq.]
kHz
Value/Possible function
Factory
setting
2.0 to 16
[Ignore]: Ignore
[Freewheel]: Detected fault management with freewheel stop.
[Ramp stop]: Detected fault management with stop on ramp
[Fast stop]: Detected fault management with fast stop
YES
4
SLL
89
[Modbus fault mgt]
-
nO
YES
rNP
FSt
SLP
33
[Slip compensation]
%
0 to 150
-
100
SLP2
37
83
[Slip compensation 2]
%
0 to 150
-
100
SP10
35
70
[Preset speed 10]
Hz
0 to 500
-
50
SP11
35
71
[Preset speed 11]
Hz
0 to 500
-
55
SP12
35
71
[Preset speed 12]
Hz
0 to 500
-
60
SP13
35
71
[Preset speed 13]
Hz
0 to 500
-
70
SP14
35
71
[Preset speed 14]
Hz
0 to 500
-
80
SP15
35
71
[Preset speed 15]
Hz
0 to 500
-
90
SP16
35
71
[Preset speed 16]
Hz
0 to 500
-
100
SP2
34
70
[Preset speed 2]
Hz
0 to 500
-
10
SP3
35
70
[Preset speed 3]
Hz
0 to 500
-
15
SP4
35
70
[Preset speed 4]
Hz
0 to 500
-
20
SP5
35
70
[Preset speed 5]
Hz
0 to 500
-
25
SP6
35
70
[Preset speed 6]
Hz
0 to 500
-
30
SP7
35
70
[Preset speed 7]
Hz
0 to 500
-
35
SP8
35
70
[Preset speed 8]
Hz
0 to 500
-
40
SP9
35
70
[Preset speed 9]
Hz
0 to 500
-
45
SPd1
95
[Cust. output value]
-
-
-
-
SPd2
95
[Cust. output value]
-
-
-
-
SPd3
95
[Cust. output value]
-
-
-
-
SrF
42
[Speed loop filter]
-
nO
YES
[No]: Filter remains active
[Yes]: Filter suppressed
nO
StA
33
[Fr.Loop.Stab]
%
1 to 100
-
20
StA2
37
83
[Freq. loop stability 2]
%
0 to 100
-
20
BBV46385 05/2009
Customer
setting
117
Index of parameter codes and customer settings
Code
Page
Name
Unit
Value/Possible function
nO
rMP
FSt
[No]: Locking of the drive and freewheel stopping of the motor
[DC Maintain]: Stop mode using inertia to maintain the drive
power supply as long as possible
[Ramp stop]: Stop according to the valid ramp
[Fast stop]: Fast stop
nO
nO
NNS
StP
91
[UnderV. prevention]
Factory
setting
-
Str
74
[Reference saved]
-
nO
rAN
EEP
[No]: No saving
[RAM]: Saving in RAM
[EEprom]: Saving in EEPROM
Stt
63
[Type of stop]
-
rMP
FSt
nSt
dCI
[Ramp stop]: On ramp
[Fast stop]: Fast stop
[Freewheel]: Freewheel stop
[DC injection]: DC injection stop
tA1
32
61
[Begin Acc round]
%
0 to 100
-
10
tA2
32
61
[End Acc round]
%
0 to
(100-tA1)
-
10
tA3
32
61
[Begin Dec round]
%
0 to 100
-
10
tA4
32
61
[End Dec round]
%
0 to
(100-tA3)
-
10
-
5
10
30
1h
2h
3h
Ct
[5 minutes]: 5 minutes
[10 minutes]: 10 minutes
[30 minutes]: 30 minutes
[1 hour]: 1 hour
[2 hours]: 2 hours
[3 hours]: 3 hours
[Unlimited]: Unlimited
4.8
9.6
19.2
[4.8 Kbps]: 4,800 bits/second
[9.6 Kbps]: 9600 bits/second
[19.2 Kbps]: 19,200 bits/second
2C
3C
LOC
[2 wire]: 2-wire control
[3 wire]: 3-wire control
[Local]: Local control (drive RUN/STOP/RESET)
LEL
trn
PFO
[Level]: State 0 or 1
[Transition]: Change of state (transition or edge)
[Fwd priority]: State 0 or 1, "forward" input takes priority over
the "reverse" input
trn
tAr
87
[Max. restart time]
tbr
92
[Modbus baud rate]
tCC
29
45
[2/3 wire control]
bps
-
rMP
5
19.2
2C
tCt
45
[2 wire type]
-
tdC
33
64
[DC injection time 2]
s
0.1 to 30
-
0.5
tdC1
33
65
[Auto DC inj. time 1]
s
0.1 to 30
-
0.5
tdC2
33
65
[Auto DC inj. time 2]
s
0 to 30
-
0
8O1
8E1
8n1
8n2
[8-O-1]: 8 data bits, odd parity, 1 stop bit
[8-E-1]: 8 data bits, even parity, 1 stop bit
[8-N-1]: 8 data bits, no parity, 1 stop bit
[8-N-2]: 8 data bits, no parity, 2 stop bits
10 to 500
-
60
tFO
92
[Modbus format]
-
tFr
42
[Max frequency]
Hz
tHd
95
[Drv. Therm att.]
-
-
-
-
tHr
95
[Motor thermal state]
-
-
-
-
tLS
36
[Low speed time out]
s
0 to 999.9
-
0
118
Customer
setting
8E1
BBV46385 05/2009
Index of parameter codes and customer settings
Page
tnL
90
[Autotune fault mgt]
-
nO
YES
[No]: Ignore
[Yes]: Detected fault management with drive locked
YES
ttd
37
[Motor therm. level]
%
1 to 118
-
100
ttO
92
[Modbus time out]
s
0.1 to 10
-
10
nO
YES
dOnE
[No]: Auto-tuning not performed
[Yes]: Auto-tuning performed as soon as possible
[Done]: Use of the values given the last time auto-tuning
was performed
[Drv running]: Auto-tuning performed every time a run
command is sent
[Power on]: Auto-tuning performed on every power-up
[LI1] to [LI6]: Auto-tuning performed on the transition from
0 V 1 of a logic input assigned to this function
nO
[Not done]: Default stator resistance value used to control
the motor
[Pending]: Auto-tuning requested but not yet performed
[In progress]: Auto-tuning in progress
[Failed]: Auto-tuning failed
[Done]: Stator resistance measured by the auto-tuning
function used to control the motor
[Entered R1]: Cold state stator resistance used to control
the motor
tAb
tUn
41
Name
[Auto tuning]
Unit
-
Value/Possible function
Factory
setting
Code
rUn
POn
LI1 to LI6
tAb
tUS
41
97
[Auto tuning state]
-
PEnd
PrOG
FAIL
dOnE
Strd
UdP
97
[Drv.Soft.Ver]
-
-
-
-
UFr
32
[IR compensation]
%
0 to 100
-
20
UFr2
36
83
[IR compensation
2]
%
0 to 100
-
20
UFt
42
[U/F mot 1
selected]
-
L
P
n
nLd
[Cst. torque]: Constant torque
[Var. torque] : Variable torque
[SVC]: Flux vector control
[Energy sav.]: Energy saving
n
UFt2
83
[U/F mot.2
selected]
-
L
P
n
nLd
[Cst. torque]: Constant torque
[Var. torque] : Variable torque
[SVC]: Flux vector control
[Energy sav.]: Energy saving
n
ULn
95
[Mains voltage]
V
-
-
-
UnS
39
[Rated motor volt.]
V
-
-
In accordance
with the
drive rating
UnS2
82
[Nom. mot. 2 volt.]
V
-
-
In accordance
with the
drive rating
BBV46385 05/2009
Customer
setting
119
BBV46385
ATV312_programming_manual_EN_V1
05/2009