Interlock Armored Cables
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
FIREX®-II: CSA Type TECK90 Cables
Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
600 V Multiconductor Cables
14 AWG and 12 AWG Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
10 AWG and Composite Cables. . . . . . . . . . . . . . . . . . . . . . . . . . 6
1 kV Cables
1 and 2 Conductor Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 and 4 Conductor Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 kV Cables
3 Conductor Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
FIREX®-MC: UL Type MC Cables
FIREX MC – 600 V Cables
Applications and Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
14 AWG to 10 AWG Multiconductor Cables. . . . . . . . . . . . . . . . . 11
3 Conductor Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FIREX MV – 5 kV Cables
Applications and Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 kV Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Color Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1-866-663-9267
1
Introduction
Nexans is one of the largest wire
and cable manufacturers in the
world, and in North America. In
North America we manufacture
in locations across the United
States and Canada. We design
and produce a wide range of
cables used in power, industrial,
construction and communication
applications.
With more than nine decades
of experience as a leader in the
industrial and power cable markets,
Nexans is contracted by heavy
industry and utilities worldwide
to provide turnkey solutions for
the bulk transmission of power
- from generating station through
the transmission and distribution
systems to commercial, residential
and industrial areas.
This catalog has been prepared
for the convenience of those using
electrical conductors in industrial,
commercial and residential
applications. The information
included in the many tabulations
will be of particular value to the
architect, engineer, electrician, and
layperson alike.
Although we have listed the types
of wires and cables suitable for
most conditions, we are equipped
to manufacture other types to suit
special needs. We would be
pleased to recommend the most
suitable construction for any special
condition that you may encounter.
The determination of the correct
cable size and type, and the
selection of methods of installation
suitable for the type and location
of particular circuits, should be
made in accordance with local
regulations. Any questions in this
respect should be directed primarily
to the local Electrical Inspection
Authority.
We are pleased to note that all
the cables in this catalog are
LEAD FREE. This indicates that the
Nexans cable components have
less than 300 ppm of lead, which
is well below the 1000 ppm level
indicated in RoHS (restriction of
hazardous substances) regulations
and below the level requiring
labeling by California proposition
#65.
1-866-663-9267
2
TECK90
Applications
FIREX®-II TECK Cables, originally
developed for use in Canadian
mines, are flexible, resistant to
mechanical abuse, corrosion
resistant, compact and reliable.
They are suitable for a wide
range of applications, including
hazardous locations.
Industries such as pulp and
paper, chemical, petroleum and
other primary and secondary
manufacturing industries have used
FIREX®-II TECK Cables, particularly
in areas where cables are subject
to the risk of mechanical damage
and chemical attack.
Commercial applications for FIREX®-II
TECK Cables include apartment
buildings and commercial
complexes.
FIREX®-II TECK Cables can be
relocated easily because they are
rugged and flexible. They can be
used in both dry and wet locations
in open wiring, in ventilated,
non-ventilated and ladder-type
cable troughs, in ventilated flexible
cableways, and for direct burial.
TECK Cables are also suitable for
service entrance installations –
above and below ground.
Highlights
Nexans FIREX®-II TECK Cables
are
•
•
•
•
•
•
•
•
•
Available from stock
Versatile
Flexible
Resistant to Mechanical Abuse
and Corrosion
Compact and Reliable
“HL” and “FT4” Rated per CSA
90°C to -40°C
Low Acid Gas (AG14)
Lead Free
1-866-663-9267
3
TECK90
Aluminum Interlock Armored Power and Control Cable
–40°C / +90°C rated - Lead Free
Multiple conductors, with ground wire, inner PVC jacket,
aluminum interlocked armor, outer PVC jacket
Construction
Conductor: bare, annealed copper
Class B stranded in accordance with
ASTM B8. In sizes 8 AWG to 1000
kcmil, the conductors are compact
stranded to reduce cable diameter and
weight.
Conductor Shield: extruded semiconducting cross-linked polyethylene
is applied for cables rated over 1000
volts.
Insulation: cross linked polyethylene.
Meets CSA C22.2 No. 38 type RW90
for unshielded cables rated 5 kV or less.
Assembly: conductors are cabled
in concentric layers with grounding
wire, interstices are filled with suitable
non-hygroscopic fillers, as required.
A binder tape of synthetic material
assembles the core in an essentially
round configuration, as required.
Inner Jacket: black polyvinyl chloride
jacket per CSA C22.2 No. 131-07,
90°C temperature rating, flameretardant, low-acid-gas-emitting.
Armor: interlocking aluminum tape
armor applied directly over the inner
jacket.
Outer Jacket: overall polyvinyl
chloride jacket per CSA C22.2 No.
131-07; low acid gas emission; limited
flame spread and excellent corrosion
resistance. Jacket color is black for 600 V
and 1 kV cables, orange for
5 kV cables.
Conductor Identification
1 conductor: black
2 conductors: black, white
3 conductors: red, black, blue
4 conductors: red, black, blue, white
5 or more: number coding
Composite:
Power: color coded
Control: number coded
For color coding:
14 AWG to 2 AWG: colored insulation
1 AWG and larger: printed color stripe
Bending Radius
Fixed position:
Unshielded Cables: 7 × cable overall
diameter
Shielded Cables: 12 × cable overall
diameter
During pulling:
Twice the above values
Specifications
• Meets the requirements of CSA
C22.2 No. 38 type RW90 for
unshielded conductors
• Meets CSA C22.2 No. 131-07 type
TECK Cables up to 5 kV unshielded
• Control cables meet CSA C22.2
No. 239-97(R2006).
Product features
•Cables are CSA listed as Type TECK
(for cables up to 5 kV)
•CSA listed insulated conductors
•Cables are flame-retardant and pass
CSA FT1
•Cables are fire-retardant and pass
CSA FT4
•ICEA T-29-520 Fire Test at 210,000
BTU/hr, IEEE 1202, 383 and UL
1685
•Cables are low-acid-gas-emitting per
CSA C22.2 No. 0.3-01 and marked
AG14
• Cables exhibit a –40°C low
temperature rating with suitable
precautions
•Temperature rating of 90°C dry and
wet
•130°C emergency rating and 250°C
short circuit rating
•Cables are rated for Hazardous
Locations (HL) per CSA C22.2 No.
174-M1987(R2008)*
•Excellent mechanical and physical
properties
•Sunlight and oil resistant jacket
•Lead Free and RoHS compliant
•Suitable for direct burial, use in cable
tray and embedment in concrete
Options
The following constructions can be
provided on special orders:
• Aluminum conductors
•Steel interlock armor
• Extra ground wires
• Special color or number coding
• Specially colored jackets
• Other constructions and combinations
(some manufacturing restrictions
apply)
*Note: These cables cannot be used
in Class I or II Division 1 locations in
accordance with the N.E.C.
1-866-663-9267
4
TECK90
Aluminum Interlocked Armored Power and Control Cable
–40°C / +90°C rated - Lead Free
600 V, Multiconductor, 14 AWG (7w) with 14 AWG (7w) bare ground
Insulation Thickness: 30 mils / 0.76 mm
*Ampacity at 30°C Ambient Temperature: 15 Amps
Part
# of
Number
Cond.
422204
422212
422220
422238
422246
422253
422261
444182
388207
————
422279
443184
670101
398883
398875
432989
————
444547
443796
369785
————
————
2
3
4
5
6
7
8
9
10
11
12
15
19
20
25
30
35
40
50
60
80
90
Inner Jacket
Thickness
mils
mm
45
45
45
45
45
45
60
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
Nominal Diameter
over Inner Jacket
inches
mm
1.14.369
1.14.390
1.14.444
1.14.472
1.14.515
1.14.522
1.52.597
1.52.608
1.52.671
1.52.679
1.52.700
1.52.764
1.52.835
1.52.850
2.03.983
2.03
1.060
2.03
1.152
2.03
1.179
2.03
1.282
2.03
1.435
2.03
1.604
2.03
1.689
Nominal Diameter
over Armor
inches
mm
9.37.600
9.91.621
11.27.676
11.99.703
13.08.743
13.26.755
15.16.825
15.45.836
17.04.898
17.25.906
17.78.927
19.41.990
21.21
1.073
21.59
1.105
24.99
1.239
26.92
1.311
29.26
1.372
29.95
1.431
32.56
1.535
36.45
1.710
40.74
1.954
42.90
2.039
Nominal Diameter
over Outer Jacket
inches
mm
15.24.688
15.77.709
17.17.761
17.86.787
18.87.828
19.18.844
20.96.909
21.23.923
22.81.984
23.01.992
23.55
1.013
25.15
1.090
27.25
1.157
28.07
1.189
31.47
1.326
33.30
1.399
34.85
1.488
36.35
1.519
38.99
1.642
43.43
1.850
49.63
2.094
51.79
2.183
17.48
18.01
19.33
19.99
21.03
21.44
23.09
23.44
24.99
25.18
25.73
27.69
29.39
30.20
33.68
35.53
37.80
38.58
41.71
46.99
53.18
55.44
Approximate Net
Cable Weight
lb/kft
kg/km
191
225
266
306
316
338
384
409
448
466
489
583
748
766
852
995
1066
1224
1468
1613
2132
2347
284
335
396
455
471
502
571
609
667
693
728
868
1113
1140
1268
1481
1587
1822
2184
2400
3173
3494
600 V, Multiconductor, 12 AWG (7w) with 14 AWG (7w) bare ground
Insulation Thickness: 30 mils / 0.76 mm
*Ampacity at 30°C Ambient Temperature: 20 Amps
Part
# of
Number
Cond.
Inner Jacket
Thickness
mils
mm
422287
422295
422303
383679
422311
422329
383695
————
422337
————
416388
444653
————
432732
291104
444638
————
————
————
————
————
————
45
45
45
45
60
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
110
110
2
3
4
5
6
7
8
9
10
11
12
15
19
20
25
30
35
40
50
60
80
90
Nominal Diameter
over Inner Jacket
inches
mm
1.14.405
1.14.429
1.14.502
1.14.522
1.52.599
1.52.614
1.52.656
1.52.700
1.52.744
1.52.760
1.52.776
1.52.842
2.03.905
2.03.974
2.03
1.093
2.03
1.167
2.03
1.308
2.03
1.367
2.03
1.483
2.03
1.615
2.79
1.865
2.79
1.962
Nominal Diameter
over Armor
inches
mm
10.29.636
10.90.660
12.75.733
13.26.752
15.21.828
15.60.843
16.66.884
17.78.940
18.90.988
19.30
1.028
19.71
1.037
21.39
1.101
22.99
1.141
24.74
1.233
27.76
1.348
29.64
1.421
33.22
1.528
34.72
1.642
37.67
1.758
41.03
1.965
47.37
2.215
49.85
2.312
Nominal Diameter
over Outer Jacket
inches
mm
16.15.724
16.76.745
18.62.817
19.10.839
21.03.912
21.41.927
22.45.971
23.87
1.014
25.10
1.077
26.11
1.096
26.34
1.125
27.97
1.189
29.46
1.233
31.32
1.321
34.24
1.436
36.09
1.509
38.81
1.668
41.71
1.737
44.65
1.853
49.91
2.015
56.26
2.269
58.72
2.366
18.39
18.92
20.75
21.31
23.16
23.55
24.66
25.76
27.35
27.84
28.58
30.20
31.32
33.55
36.47
38.32
42.36
44.12
47.06
51.18
57.63
60.09
Approximate Net
Cable Weight
lb/kft
kg/km
238
280
298
347
402
438
476
496
531
622
651
755
937
973
1165
1302
1533
1593
1884
2311
3021
3318
*Ampacity in accordance with the Canadian Electrical Code, Part 1. Derating required for more than 3 conductors.
1-866-663-9267
5
354
417
443
516
598
652
708
738
790
925
969
1123
1394
1448
1733
1938
2281
2370
2804
3439
4495
4937
TECK90
Aluminum Interlocked Armored Power and Control Cable
–40°C / +90°C rated - Lead Free
600 V, Multiconductor, 10 AWG (7w) with 12 AWG (7w) bare ground
Insulation Thickness: 30 mils / 0.76 mm
*Ampacity at 30°C Ambient Temperature: 30 Amps
Part
# of
Number
Cond.
Inner Jacket
Thickness
mils
mm
383588
422345
422352
————
069815
248153
318246
————
444562
————
105395
444612
————
444620
————
626804
————
————
————
————
————
————
45
45
45
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
110
110
110
2
3
4
5
6
7
8
9
10
11
12
15
19
20
25
30
35
40
50
60
80
90
Nominal Diameter
over Inner Jacket
inches
mm
1.14.452
1.14.481
1.14.560
1.52.604
1.52.671
1.52.699
1.52.726
1.52.766
1.52.840
1.52.879
2.03.917
2.03.987
2.03
1.066
2.03
1.098
2.03
1.229
2.03
1.317
2.03
1.494
2.03
1.567
2.03
1.701
2.79
1.910
2.79
2.133
2.79
2.246
Nominal Diameter
over Armor
inches
mm
11.48.684
12.23.712
14.22.783
15.35.833
17.04.900
17.75.928
18.44.954
19.45
1.006
21.33
1.100
22.33
1.135
23.29
1.178
25.06
1.247
27.07
1.321
27.89
1.357
31.22
1.504
33.45
1.573
37.96
1.714
39.80
1.917
43.21
2.051
48.50
2.260
54.18
2.483
57.05
2.596
Nominal Diameter
over Outer Jacket
inches
mm
17.37.769
18.08.798
19.89.867
21.16.918
22.86.985
23.57
1.018
24.23
1.047
24.55
1.094
27.94
1.188
28.83
1.222
29.92
1.266
31.67
1.335
33.55
1.414
34.47
1.445
38.20
1.596
39.95
1.680
43.54
1.854
48.69
1.967
52.10
2.105
57.40
2.314
63.07
2.570
65.94
2.683
19.53
20.27
22.02
23.32
25.01
25.85
26.59
27.79
30.18
31.03
32.16
33.91
35.92
36.70
40.54
42.67
47.10
49.96
53.47
58.78
65.28
68.15
Approximate Net
Cable Weight
lb/kft
kg/km
272
339
383
421
517
539
617
633
776
795
885
1056
1209
1291
1528
1770
2097
2298
2743
3303
4225
4656
*Ampacity in accordance with the Canadian Electrical Code, Part 1, Derating required for more than 3 conductors.
405
504
570
627
770
802
918
942
1154
1183
1318
1571
1800
1921
2274
2634
3121
3421
4082
4916
6288
6928
600 V, Composite Power and Control
Conductor Size
Power Cond.
Inner Jacket
Nominal Diameter
Nominal Diameter
Nominal Diameter
Approximate Net
Ampacity**
Part
Insulation Thickness
Thickness
over Inner Jacket
over Armor
over Outer Jacket
Cable Weight
30°C
Number
Power Control Ground
Ambient
AWG
mils
mm
mils
mm
inches
mm
inches
mm
inches
mm
lb/kft
kg/km
amps
252197
252213
260877
252338
218544
252379
———
067330
———
———
———
459156
———
302976
———
306621
———
306639
———
———
———
306613
———
12
10
10
8
8
6
6
4
4
3
3
2
2
1
1
1/0
1/0
2/0
2/0
3/0
3/0
4/0
4/0
14
14
12
14
12
14
12
14
12
14
12
14
12
14
12
14
12
14
12
14
12
14
12
14
12
12
10
10
8
8
8
8
6
6
6
6
6
6
6
6
6
6
4
4
4
4
30
30
30
45
45
60
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
.76
.76
.76
1.14
1.14
1.52
1.52
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
.591
.596
.665
.715
.755
.900
.900
.904
.904
.964
.964
1.026
1.026
1.182
1.182
1.263
1.263
1.348
1.348
1.450
1.450
1.567
1.567
15.00
15.14
16.90
18.16
19.17
22.86
22.86
22.96
22.96
24.48
24.48
26.05
26.05
30.03
30.03
32.08
32.08
34.23
34.23
36.82
36.82
39.80
39.80
**Ampacity of power conductors per Canadian Electrical Code, Part 1.
1-866-663-9267
6
.831
.836
.905
.955
1.010
1.175
1.175
1.179
1.179
1.239
1.239
1.301
1.301
1.457
1.457
1.538
1.538
1.623
1.623
1.725
1.725
1.872
1.872
21.10
21.23
23.00
24.26
25.27
29.85
29.85
29.57
29.57
31.09
31.09
32.66
32.66
36.64
36.64
38.69
38.69
40.84
40.84
43.13
43.13
47.17
47.17
.929
.936
1.003
1.053
1.159
1.288
1.288
1.308
1.308
1.368
1.368
1.430
1.430
1.586
1.586
1.667
1.667
1.772
1.772
1.854
1.854
2.051
2.051
23.59
24.37
25.49
26.75
29.43
32.72
32.72
33.22
33.22
34.74
34.74
36.31
36.31
40.29
40.29
42.34
42.34
44.49
44.49
47.08
47.08
52.09
52.09
380
414
442
530
558
700
843
985
1001
1155
1172
1322
1339
1609
1626
1823
1885
2218
2235
2667
2683
3294
3312
566
616
658
789
830
1042
1254
1466
1490
1719
1744
1967
1992
2394
2420
2713
2805
3300
3326
3969
3993
4902
4929
20
30
30
45
45
65
65
85
85
105
105
120
120
140
140
155
155
185
185
210
210
235
235
TECK90
Aluminum Interlocked Armored Power Cable
–40°C / +90°C rated - Lead Free
1 kV, 1 Conductor with Concentric Bare Ground
Part
Cond. Ground Insulation Thickness
Inner Jacket
Nominal Diameter
Nominal Diameter Approximate Net
Approximate Net
Number
Size
Size
Thickness
over Inner Jacket
over Armor
over Outer Jacket
Cable Weight
AWG/
kcmil AWG
mils
mm
mils
mm
inches
mm
inches
mm
inches
mm lb/kft kg/km
———
———
———
295170
———
550335
550343
550350
550368
550376
535443
550384
208702
550392
391847
526319
528000
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000
8
6
6
6
4
4
4
3
3
2
2
1
1
1/0
1/0
2/0
2/0
60
60
60
60
80
80
80
80
80
90
90
90
90
90
90
90
90
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
30
30
30
30
45
45
45
45
45
60
60
60
60
60
60
60
60
.76
.76
.76
.76
1.14
1.14
1.14
1.14
1.14
1.52
1.52
1.52
1.52
1.52
1.52
1.52
1.52
.453
.497
.525
.555
.658
.725
.750
.807
.859
.955
1.005
1.080
1.123
1.237
1.278
1.408
1.561
11.50
12.63
13.33
14.10
16.70
18.42
19.05
20.49
21.82
24.25
25.53
27.43
28.53
31.42
32.47
35.75
39.64
.693
.737
.765
.795
.898
.965
1.025
1.070
1.134
1.247
1.280
1.353
1.398
1.514
1.553
1.683
1.911
17.60
18.72
19.43
20.19
22.81
24.51
26.04
27.18
28.80
31.67
32.51
34.37
35.51
38.46
39.45
42.75
48.53
.791
.835
.863
.893
.996
1.069
1.135
1.180
1.244
1.355
1.409
1.465
1.527
1.625
1.682
1.812
2.045
20.09
21.21
21.92
22.68
25.30
27.15
28.83
29.97
31.60
34.42
35.79
37.21
38.79
41.28
42.72
46.02
51.94
331
428
473
528
696
781
944
1121
1272
1466
1715
1947
2164
2596
2960
3648
4674
493
637
704
786
1036
1162
1405
1668
1893
2181
2552
2897
3220
3863
4405
5429
6955
Ampacity*
30°C
Ambient
amps
100
135
155
180
210
245
285
330
385
425
480
530
575
660
740
845
1000
1 kV, 2 Conductors with Bare Ground
Part
Cond. Ground Insulation Thickness
Inner Jacket
Nominal Diameter
Nominal Diameter Approximate Net
Approximate Net
Ampacity*
Number
Size
Size
Thickness
over Inner Jacket
over Armor
over Outer Jacket
Cable Weight
30°C
Ambient
AWG/
kcmil AWG
mils
mm
mils
mm
inches
mm
inches
mm
inches mm
lb/kft kg/km amps
184838
133280
138941
307884
422493
302968
———
260315
———
119917
527572
———
413187
318873
———
———
———
318865
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
14
14
12
10
8
8
6
6
6
6
6
4
4
4
4
3
3
3
45
45
45
45
60
60
60
60
80
80
80
80
80
90
90
90
90
90
1.14
1.14
1.14
1.14
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.29
2.29
2.29
2.29
2.29
45
45
45
60
60
60
80
80
80
80
80
80
80
80
80
110
110
110
1.14
1.14
1.14
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79
.423
.464
.510
.590
.718
.812
.902
.963
1.110
1.185
1.263
1.358
1.463
1.598
1.699
1.852
1.938
2.097
10.74
11.78
12.95
14.98
18.25
20.61
22.91
24.45
28.20
30.09
32.09
34.50
37.16
40.59
43.15
47.03
49.23
53.27
.663
.696
.750
.819
.945
1.084
1.177
1.235
1.385
1.454
1.533
1.633
1.731
1.948
2.049
2.202
2.288
2.447
*Ampacity in accordance with the Canadian Electrical Code, Part 1.
1-866-663-9267
7
16.84
17.68
19.05
20.80
24.00
27.53
29.90
31.37
35.18
36.93
38.94
41.48
43.97
49.48
52.04
55.93
58.11
62.15
.761
.794
.848
.926
1.055
1.188
1.306
1.339
1.514
1.558
1.641
1.762
1.863
2.082
2.183
2.336
2.422
2.581
19.32
20.17
21.54
23.52
26.80
30.18
33.17
34.01
38.45
39.57
41.68
44.75
47.32
52.88
55.44
59.33
61.52
65.56
216
272
296
407
545
742
912
1029
1252
1451
1675
2031
2385
2870
3291
3837
4236
5082
321
405
440
606
811
1104
1357
1531
1863
2159
2493
3022
3549
4270
4882
5710
6303
7563
15
20
30
45
65
85
105
120
140
155
185
210
235
265
295
325
345
395
TECK90
Aluminum Interlocked Armored Power Cable
–40°C / +90°C rated - Lead Free
1 kV, 3 Conductors with Bare Ground
Part
Cond. Ground Insulation Thickness
Inner Jacket
Nominal Diameter
Nominal Diameter Approximate Net
Approximate Net
Ampacity*
Number
Size
Size
Thickness
over Inner Jacket
over Armor
over Outer Jacket
Cable Weight
30°C
Ambient
AWG/
kcmil AWG
mils
mm
mils
mm
inches
mm
inches
mm
inches
mm lb/kft kg/km
amps
654228
307850
307843
422360
422378
422386
307876
422394
422402
422410
422428
438929
438937
438945
438952
438960
438978
438986
442632
560094
*Ampacity
14
14
12
14
10
12
8
10
6
8
4
8
3
6
2
6
1
6
1/0
6
2/0
6
3/0
4
4/0
4
250
4
300
4
350
3
400
3
500
3
600
2
750
2
in accordance
45
1.14
45
1.14
.448 11.38
45
1.14
45
1.14
.503 12.77
45
1.14
60
1.52
.576 14.63
45
1.14
60
1.52
.627 15.93
60
1.52
60
1.52
.766 19.44
60
1.52
80
2.03
.904 22.96
60
1.52
80
2.03
.964 24.48
60
1.52
80
2.03
1.026 26.05
80
2.03
80
2.03
1.182 30.03
80
2.03
80
2.03
1.263 32.08
80
2.03
80
2.03
1.348 34.23
80
2.03
80
2.03
1.450 36.82
80
2.03
80
2.03
1.567 39.80
90
2.29
110
2.79
1.768 44.91
90
2.29
110
2.79
1.877 47.67
90
2.29
110
2.79
1.976 50.20
90
2.29
110
2.79
2.074 52.68
90
2.29
110
2.79
2.241 56.92
90
2.29
110
2.79
2.408 61.17
90
2.29
110
2.79
2.614 66.40
with the Canadian Electrical Code, Part 1.
.685
.735
.807
.855
1.035
1.176
1.236
1.300
1.457
1.537
1.621
1.725
1.815
2.120
2.235
2.330
2.422
2.595
2.758
2.959
17.40
18.67
20.50
21.72
26.29
29.87
31.39
33.02
37.01
39.04
41.14
43.82
46.10
53.85
56.77
59.18
61.52
65.91
70.05
75.16
.770
.821
.891
.942
1.125
1.265
1.326
1.388
1.547
1.630
1.729
1.835
1.925
2.250
2.367
2.462
2.554
2.757
2.935
3.121
19.56
20.85
22.63
23.93
28.58
32.13
33.68
35.26
39.29
41.40
43.92
46.61
48.90
57.15
60.12
61.52
64.87
70.03
74.55
79.27
247
297
381
491
644
924
1026
1274
1539
1796
2165
2571
3196
3830
4382
4990
5534
6674
7747
9596
367
441
567
730
959
1375
1526
1896
2291
2672
3222
3827
4756
5700
6520
7426
8235
9932
11528
14281
15
20
30
45
65
85
105
120
140
155
185
210
235
265
295
325
345
395
455
500
1 kV, 4 Conductors with Bare Ground
Part
Cond. Ground Insulation Thickness
Inner Jacket
Nominal Diameter
Nominal Diameter Approximate Net
Approximate Net Ampacity**
Number
Size
Size
Thickness
over Inner Jacket
over Armor
over Outer Jacket
Cable Weight
30°C
Ambient
AWG/
kcmil AWG
mils
mm
mils
mm
inches
mm
inches
mm
inches
mm lb/kft kg/km
amps
133298
14
14
369322
12
14
649707
10
12
383612
8
10
383620
6
8
529271
4
8
199588
3
6
383646
2
6
105312
1
6
568261
1/0
6
443358
2/0
6
568279
3/0
4
568709
4/0
4
568337
250
4
167890
300
4
568295
350
3
227462
400
3
568345
500
3
**Ampacity assuming 4th
Code, Part 1.
45
1.14
45
1.14
45
1.14
45
1.14
60
1.52
60
1.52
60
1.52
60
1.52
80
2.03
80
2.03
80
2.03
80
2.03
80
2.03
90
2.29
90
2.29
90
2.29
90
2.29
90
2.29
conductor is a
45
60
60
60
80
80
80
80
80
80
80
80
110
110
110
110
110
110
neutral
1.14
.493
1.52
.569
1.52
.632
1.52
.694
2.03
.895
2.03
.995
2.03
1.085
2.03
1.145
2.03
1.303
2.03
1.394
2.03
1.488
2.03
1.607
2.79
1.793
2.79
1.952
2.79
2.077
2.79
2.189
2.79
2.294
2.79
2.481
of a 3 phase. 4
12.52
.733
14.46
.809
16.04
.878
17.62
.921
22.73 1.170
25.27 1.270
27.55 1.360
29.09 1.420
33.11 1.578
35.40 1.669
37.81 1.757
40.81 1.852
45.55 2.033
49.57 2.302
52.76 2.427
55.60 2.539
58.26 2.644
63.02 2.831
wire system in
1-866-663-9267
8
18.61
.827
20.33
.903
22.30
.965
23.39 1.028
29.71 1.280
32.26 1.351
34.54 1.441
36.07 1.501
39.50 1.663
42.39 1.774
44.63 1.865
47.04 1.960
51.64 2.141
58.52 2.417
61.65 2.542
64.49 2.654
67.16 2.833
71.91 3.020
accordance with
21.00
282
420
22.94
356
530
24.51
436
649
26.11
583
867
32.51
838 1247
34.31 1122 1669
36.60 1359 2022
38.13 1580 2351
42.24 1927 2868
45.06 2295 3415
47.37 2711 4034
49.78 3395 5053
54.38 4197 6239
61.39 4828 7230
65.57 5630 8378
67.41 6399 9522
71.96 7132 10613
76.71 8555 12732
the Canadian Electrical
15
20
30
45
65
85
105
120
140
155
185
210
235
265
295
325
345
395
TECK90
Aluminum Interlocked Armored Power Cable
–40°C / +90°C rated - Lead Free
5 kV Unshielded, 3 Conductors with Bare Ground
Part
Cond. Ground Insulation Thickness
Inner Jacket
Nominal Diameter
Nominal Diameter Nominal Diameter Approximate Net
Ampacity*
Number
Size
Size
Thickness
over Inner Jacket
over Armor
over Outer Jacket
Cable Weight
30°C
Ambient
AWG/
kcmil AWG
mils
mm
mils
mm
inches
mm
inches
mm
inches
mm lb/kft kg/km
amps
———
645952
645960
———
226225
217760
200766
226233
———
226241
226274
———
226282
———
226290
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
10
8
8
6
6
6
6
6
4
4
4
4
3
3
3
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
60
80
80
80
80
80
80
80
80
80
110
110
110
110
110
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79
2.79
2.79
.931
1.051
1.146
1.200
1.266
1.335
1.415
1.500
1.606
1.724
1.882
1.990
2.094
2.188
2.355
23.64
26.69
29.11
30.49
32.15
33.91
35.95
38.10
40.80
43.79
47.80
50.55
53.19
55.56
59.81
1.206
1.326
1.421
1.475
1.541
1.610
1.690
1.775
1.956
2.074
2.232
2.340
2.444
2.538
2.705
*Ampacity in accordance with the Canadian Electrical Code, Part 1.
1-866-663-9267
9
30.63
33.68
36.09
37.46
39.14
40.89
42.93
45.09
49.68
52.68
56.69
59.44
62.08
64.47
68.71
1.315
1.435
1.530
1.584
1.670
1.739
1.819
1.904
2.090
2.208
2.366
2.474
2.578
2.672
2.839
33.40
36.45
38.86
40.23
42.42
44.17
46.20
48.36
53.09
56.08
60.10
62.84
65.48
67.87
72.11
721
872
1155
1322
1503
1732
2013
2339
2929
3544
4032
4605
5242
5852
7053
1073
1297
1719
1968
2237
2577
2997
3481
4359
5274
6001
6853
7800
8709
10495
45
65
85
105
120
140
155
185
210
235
265
295
325
345
395
FIREX® MC
Aluminum Interlock Armored Power and Control Cable
UL Type MC, 600 V, 90°C rated - Lead Free
Multiple conductors, with ground wire, aluminum interlocked
armor, PVC jacket
Applications
Construction
Specifications
Firex MC is suitable and allowed
by the NEC for use in the following
applications:
• for power, lighting and control
circuits and as branch circuits
and power feeders in industrial,
commercial, institutional and
residential installations up to 600
volts.
• fished or embedded in plaster and
concrete.
• direct buried or used as an aerial
cable when fixed to a messenger
support cable.
• used in concealed or exposed
applications.
• installed in cable trays and other
raceways.
• in Class I and II, Division 2 as well as
Class III, Division 1 and 2 hazardous
locations.
• under raised floors of information
technology rooms.
• where exposed to harsh chemicals
and vapors.
Conductor: bare, annealed copper
conforming to ASTM B3 and Class B
stranded in accordance with ASTM B8.
•Meets UL 44, XHHW-2 600V
conductors
•Meets UL 1569 requirements for Type
MC, Metal Clad cables
•Designated Type MC per NEC Article
330
Insulation: cross linked polyethylene
type XHHW-2 per UL 44.
Assembly: conductors are cabled
in concentric layers with grounding
wire, interstices are filled with suitable
non-hygroscopic fillers, as required.
A binder tape of synthetic material
assembles the core in an essentially
round configuration.
Armor: interlocking aluminum tape
armor applied directly over the core.
Jacket: overall polyvinyl chloride
jacket per UL 1569, 90°C temperature
rating; low acid gas emission; limited
flame spread and excellent corrosion
resistance.
Conductor Identification
Sizes #14 AWG to #10 AWG:
Method #1-E2 per ICEA S-73-532
Sizes #8 AWG to 500 kcmil:
Method #4 per ICEA S-73-532
See page 15.
Bending Radius
Fixed position: 7 x cable overall
diameter
During pulling: 12 x cable overall
diameter
1-866-663-9267
10
Product features
• Cables are UL listed as Type MC,
600 V
• UL listed insulated conductors
• Cables pass UL 1685 and IEEE 383
vertical tray fire tests at 70,000
BTU/hr, ICEA T-29-520 fire test at
210,000 BTU/hr, IEEE 1202 and
CSA FT4
• Cables exhibit a –25°C cold bend
rating with suitable precautions
• Temperature rating of 90°C dry and
wet
• 130°C emergency rating and 250°C
short circuit rating
• Excellent mechanical and physical
properties
• Sunlight and oil resistant jacket
•Lead Free
•Suitable for direct burial, use in cable
tray and embedment in concrete
•Can be installed in hazardous
locations designated Class I or II
Division 2, NEC Articles 501.10(B)
and 502.10(B) as well as Class
III Division 1 and 2, NEC Article
503.10 A and B.
Options
The following constructions can be
provided on special orders:
• Aluminum conductors
•Steel interlock armor
• Extra ground wires
• Special color or number coding
• Specially colored jackets
• Other constructions and combinations
(some manufacturing restrictions
apply)
FIREX® MC
Aluminum Interlocked Armored Power and Control Cable
UL Type MC, 90°C rated - Lead Free
600 V, Multiconductor with Bare Ground
Insulation Thickness: 30 mils / 0.76 mm
Part
Number
# of
Cond.
Nominal Diameter
Jacket Thickness
over Armor
Nominal Diameter
over Jacket
AWG inches
mm
inches
mm
lb/kft
640540
2
14 (7w)
14 (7w)
639930
3
14 (7w)
14 (7w)
———
4
14 (7w)
14 (7w)
———
5
14 (7w)
14 (7w)
———
7
14 (7w)
14 (7w)
———
9
14 (7w)
14 (7w)
———
12
14 (7w)
14 (7w)
———
15
14 (7w)
14 (7w)
———
19
14 (7w)
14 (7w)
———
25
14 (7w)
14 (7w)
———
37
14 (7w)
14 (7w)
640524
2
12 (7w)
12 (7w)
639963
3
12 (7w)
12 (7w)
633511
4
12 (7w)
12 (7w)
———
5
12 (7w)
12 (7w)
———
7
12 (7w)
12 (7w)
———
9
12 (7w)
12 (7w)
———
12
12 (7w)
12 (7w)
———
15
12 (7w)
12 (7w)
———
19
12 (7w)
12 (7w)
———
25
12 (7w)
12 (7w)
———
37
12 (7w)
12 (7w)
670322
2
10 (7w)
10 (7w)
639971
3
10 (7w)
10 (7w)
———
4
10 (7w)
10 (7w)
———
5
10 (7w)
10 (7w)
———
7
10 (7w)
10 (7w)
———
9
10 (7w)
10 (7w)
———
12
10 (7w)
10 (7w)
———
37
10 (7w)
10 (7w)
.480
.520
.560
.590
.645
.715
.790
.840
.900
1.045
1.175
.498
.508
.550
.606
.642
.785
.831
.950
.981
1.196
1.380
.556
.620
.626
.751
.782
.915
.971
1.570
12.19
50
1.27
13.54
50
1.27
14.22
50
1.27
14.99
50
1.27
16.38
50
1.27
18.16
50
1.27
20.07
50
1.27
21.34
50
1.27
22.86
50
1.27
26.54
50
1.27
29.85
50
1.27
12.65
50
1.27
12.90
50
1.27
13.97
50
1.27
15.39
50
1.27
16.31
50
1.27
19.94
50
1.27
21.11
50
1.27
24.13
50
1.27
24.92
50
1.27
30.38
50
1.27
35.05
50
1.27
14.12
50
1.27
15.75
50
1.27
15.90
50
1.27
19.08
50
1.27
19.86
50
1.27
23.24
50
1.27
24.66
50
1.27
39.88
50
1.27
.580
.625
.665
.695
.750
.820
.895
.950
1.010
1.155
1.300
.602
.612
.654
.706
.743
.890
.935
1.049
1.080
1.300
1.498
.658
.720
.730
.855
.882
1.020
1.077
1.715
14.73
15.88
16.89
17.65
19.05
20.83
22.73
24.13
25.65
29.34
33.02
15.29
15.54
16.61
17.93
18.87
22.61
23.75
26.64
27.43
33.02
38.05
16.71
18.29
18.54
21.72
22.40
25.91
27.36
43.56
160
180
210
230
275
330
400
465
550
730
980
196
226
246
302
362
458
545
664
779
1040
1430
240
312
343
423
509
630
758
2070
Cond.
Size
AWG Ground
Wire Size
mm
mils
Approximate Net
Cable Weight
Ampacity
kg/km amps (1,3) 238
268
313
342
409
491
595
692
819
1086
1458
292
336
366
449
539
682
811
988
1159
1548
2128
357
464
510
630
757
938
1128
3081
25
25
20/25(2)
20
17.5
17.5
12.5
12.5
12.5
11.5
10
30
30
24/30(2)
24
21
21
15
15
15
13.5
12
40
40
32/40(2)
32
28
28
20
16
(1) Ampacities are in accordance with Table 310.16 of NEC for conductors in raceway or direct buried at 30°C ambient
temperature and 90°C conductor temperature.
The overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10AWG
copper conductors after any correction factors for ambient temperature and number of conductors have been applied (NEC
Article 240.4(D)).
For correction factors for different ambient temperatures and ampacities at different conductor temperatures see Table 310.16
of NEC.
Ampacities for cables having more than three conductors have been derated per Article 310.15(B)(2)(a) of NEC.
(2) Where the 4th conductor is the neutral of a balanced 3 phase system.
(3) With load diversity of 50% (see Table B.310.11 of NEC).
1-866-663-9267
11
FIREX® MC
Aluminum Armored Power and Control Cable
UL Type MC, 90°C rated - Lead Free
600 V, 3 Conductors with Bare Ground
Part
Number
Cond.
Size
Insulation
Thickness
Ground
Wire Size
Nominal Diameter
Jacket Thickness
over Armor
Nominal Diameter
over Jacket
Approximate Net
Cable Weight
Ampacity
AWG/kcmil
mils
mm
AWG
inches
mm
mils
mm
inches
mm
lb/kft
kg/km
amps(1)
634725
8 (7w)
634733
6 (7w)
634741
4 (7w)
634766
2 (7w)
660594
1 (19w)
634758 1/0 (19w)
634774 2/0 (19w)
645499 3/0 (19w)
634782 4/0 (19w)
634790 250 (37w)
634808 350 (37w)
634816 500 (37w)
———
750 (61w)
——— 1000 (61w)
45
45
45
45
55
55
55
55
55
65
65
65
80
80
1.14
1.14
1.14
1.14
1.40
1.40
1.40
1.40
1.40
1.65
1.65
1.65
2.03
2.03
10 (7w)
8 (7w)
8 (7w)
6 (7w)
6 (7w)
6 (7w)
6 (7w)
4 (7w)
4 (7w)
4 (7w)
3 (7w)
2 (7w)
1 (19w)
1/0 (19w)
0.750
0.820
0.920
1.040
1.169
1.260
1.349
1.459
1.590
1.733
1.922
2.300
2.760
3.080
19.05
20.83
23.37
26.42
29.69
32.00
34.26
37.06
40.39
44.02
48.82
58.42
70.10
78.23
50
50
50
50
50
50
50
50
60
60
60
75
75
85
1.27
1.27
1.27
1.27
1.27
1.27
1.27
1.27
1.52
1.52
1.52
1.91
1.91
2.16
0.855
0.925
1.029
1.151
1.279
1.360
1.459
1.567
1.722
1.861
2.050
2.465
2.920
3.265
21.72
23.50
26.16
29.21
32.49
34.54
37.08
39.80
43.69
47.27
52.07
62.61
74.17
82.93
405
545
727
1038
1262
1501
1807
2244
2725
3173
4252
6205
8970
11685
603
811
1082
1545
1878
2234
2689
3339
4055
4722
6327
9234
13349
17389
55
75
95
130
150
170
195
225
260
290
350
430
535
615
(1) Ampacities are in accordance with Table 310.16 of NEC for conductors in raceway or direct buried at 30°C ambient
temperature and 90°C conductor temperature.
For correction factors for different ambient temperatures and ampacities at different conductor temperatures see Table 310.16
of NEC.
1-866-663-9267
12
FIREX® MV
Aluminum Interlocked Armored Power Cable
UL Type MV-90
2.4 kV* or 5 kV*, XLPE insulation,
non-shielded, aluminum interlocked armor, PVC jacket
Applications
Construction
Specifications
Firex MV-90 is suitable and allowed
by the NEC for use in the following
applications:
• for power feeders in industrial,
commercial, and institutional
installations up to 5000 volts.
(2400 volts per NEC)
• fished or embedded in plaster and
concrete.
• direct buried or used as an aerial
cable when fixed to a messenger
support cable.
• used in concealed or exposed
applications.
• installed in cable trays and other
raceways.
• in Class I and II, Division 2 as well as
Class III, Division 1 and 2 hazardous
locations.
• where exposed to harsh chemicals
and vapors.
Conductor: bare, annealed copper
conforming to ASTM B3 and Class B
stranded in accordance with ASTM B8.
•Meets ICEA S-96-659 for nonshielded cables
•Meets UL 1072 for Medium Voltage
Cables, Type MV-90
•Designated Type MV as per NEC
Article 328
Conductor shield: extruded
thermosetting semi-conducting layer
Insulation: XLPE as per UL 1072
ICEA S-96-659
Product features
Unshielded cable:
Number coded
• Cables are UL listed as Type MV-90,
2.4 kV
• UL listed insulated conductors
• Cables are 5 kV rated per
ICEA S-96-659
• Cables pass UL 1685 and IEEE 383
vertical tray fire tests at 70,000
BTU/hr, ICEA T-29-520 fire test at
210,000 BTU/hr, IEEE 1202 and
CSA FT4
• Cables exhibit a –25°C cold bend
rating with suitable precautions
• Temperature rating of 90°C dry and
wet
• 130°C emergency rating and 250°C
short circuit rating
• Excellent mechanical and physical
properties
• Sunlight and oil resistant jacket
•Suitable for direct burial, use in cable
tray and embedment in concrete
Bending Radius
Options
Fixed position:
Unshielded: 7 x cable overall diameter
The following constructions can be
provided on special orders:
• Aluminum conductors
•Steel interlock armor
• Extra ground wires
• Special color or number coding
• Specially colored jackets
• Other constructions and combinations
(some manufacturing restrictions
apply)
Assembly: insulated conductors are
cabled with bare copper grounding
conductor(s) and interstices are filled
with suitable non-hygroscopic fillers,
as required. A binder tape of synthetic
material assembles the core in an
essentially round configuration.
Armor: interlocking aluminum tape
armor applied directly over the core.
Jacket: overall polyvinyl chloride
jacket, 90°C temperature rating; low
acid gas emission; limited flame spread
and excellent corrosion resistance.
Conductor Identification
During pulling:
Unshielded: 12 x cable overall
diameter
*The NEC and UL 1072 limit unshielded cable to circuits operating at a maximum of 2400 volts phase to phase.
ICEA S-96-659 rates unshielded cable with the same insulation thickness to a maximum operating voltage of 5000 volts phase
to phase.
1-866-663-9267
13
FIREX® MV
Aluminum Interlocked Armored Power Cable
UL Type MV-90, 90°C rated
2.4 kV* or 5 kV* Unshielded, 3 Conductors with Bare Ground
Insulation Thickness: 90 mils / 2.29 mm
Part
Number
———
———
———
———
———
———
———
———
650754
———
650747
650663
641464
———
Cond.
Size
Ground
Wire Size
AWG/kcmil
AWG
8 (7w)
8 (7w)
6 (7w)
6 (7w)
4 (7w)
6 (7w)
2 (7w)
6 (7w)
1 (19w)
6 (7w)
1/0 (19w)
4 (7w)
2/0 (19w)
4 (7w)
3/0 (19w)
4 (7w)
4/0 (19w)
3 (7w)
250 (37w)
3 (7w)
350 (37w)
2 (7w)
500 (37w)
1 (19w)
750 (61w) 1/0 (19w)
1000 (61w) 1/0 (19w)
Nominal Diameter
Jacket Thickness
over Armor
Nominal Diameter
over Jacket
Approximate Net
Ampacity
Cable Weight
inches
mm
mils
mm inches
mm
lb/kft
1.055
1.130
1.235
1.360
1.465
1.555
1.650
1.785
1.905
2.015
2.235
2.510
2.905
3.335
26.80
28.70
31.67
34.54
37.21
39.50
41.91
45.34
48.39
51.18
56.77
63.75
73.79
84.71
50
50
50
60
60
60
60
60
60
60
75
75
85
85
1.27
1.27
1.27
1.52
1.52
1.52
1.52
1.52
1.52
1.52
1.91
1.91
2.16
2.16
1.165
1.240
1.345
1.470
1.575
1.685
1.780
1.915
2.030
2.145
2.365
2.675
3.070
3.410
29.59
31.50
34.16
37.34
40.01
42.80
45.21
48.64
51.56
54.48
60.07
67.95
77.98
86.61
605
785
990
1295
1515
1855
2175
2700
3230
3655
4795
6535
9245
11850
kg/km
900
1168
1473
1927
2255
2761
3237
4018
4807
5439
7136
9725
13758
17635
amps(1,2)
amps(3)
59
79
105
140
160
185
215
250
285
320
395
485
615
705
85
105
135
180
200
230
260
295
335
365
440
530
650
730
(1) Ampacity for cable in air in accordance with Table 310.71 of NEC, conductor temperature of 90°C and ambient
temperature of 40°C.
(2) Ampacity for cable in ventilated tray in accordance to Article 392.13(A)(2) and Table 310.71 of NEC.
(3) Ampacity for cable direct buried in accordance with Table 310.83 with 90°C conductor temperature, R.H.O. 90, 100%
load factor, 20°C earth temperature, one circuit.
*The NEC and UL 1072 limit unshielded cable to circuits operating at a maximum of 2400 volts phase to phase.
ICEA S-96-659 rates unshielded cable with the same insulation thickness to a maximum operating voltage of 5000 volts phase
to phase.
1-866-663-9267
14
Conductor or Phase
Identification
Per ICEA S-73-532-E3.4 Method 4
Number Code
Conductor
Printing Details
Conductor
Printing Details
1st
“1-ONE-1”
4th
“4-FOUR-4”
2nd
“2-TWO-2”
5th
“5-FIVE-5”
3rd
“3-THREE-3”
6th
    
“6-SIX-6”
Per ICEA S-73-532-E3.1 Method 1 and Table E2 (formerly K2)
Colored Insulation with/without Colored Stripe
Conductor
Insulation
Stripe
Conductor
Insulation
Stripe
1st
BLACK
—
19th
ORANGE
Blue
2nd
RED
—
20th
YELLOW
Blue
3rd
BLUE
—
21st
BROWN
Blue
4th
ORANGE
—
22nd
BLACK
Orange
5th
YELLOW
—
23rd
RED
Orange
6th
BROWN
—
24th
BLUE
Orange
7th
RED
Black
25th
YELLOW
Orange
8th
BLUE
Black
26th
BROWN
Orange
9th
ORANGE
Black
27th
BLACK
Yellow
10th
YELLOW
Black
28th
RED
Yellow
11th
BROWN
Black
29th
BLUE
Yellow
12th
BLACK
Red
30th
ORANGE
Yellow
13th
BLUE
Red
31st
BROWN
Yellow
14th
ORANGE
Red
32nd
BLACK
Brown
15th
YELLOW
Red
33rd
RED
Brown
16th
BROWN
Red
34th
BLUE
Brown
17th
BLACK
Blue
35th
ORANGE
Brown
18th
RED
Blue
36th
YELLOW
Brown
Note: The color code repeats at #1 “BLACK” as the 37th conductor (for cables with more than 36 conductors) for FIREX MC.
1-866-663-9267
15
WARNING
NOTICE
FLAMMABLE
Non-metallic covering of electrical
cables will burn and under certain
conditions may transmit fire when
ignited.
Nexans has endeavoured to ensure
the accuracy of the data in this
publication, however we cannot be
liable for the consequences of errors
or omissions. All data is subject to
change without notice. The installer
and / or user assumes all liability for
the consequences of the installation
and / or use of any of our products in
contravention of any applicable law,
regulation or code.
TOXIC
Burning non-metallic coverings may
emit acid gases, which are highly toxic,
and may generate dense smoke.
CORROSIVE
Emission of acid gases may corrode
metal in the vicinity, such as sensitive
instruments and reinforcing rod in
concrete.
1-866-663-9267
16
U.S. Sales Office:
25 Oakland Avenue, Chester, New York 10918
Tel:1-866-663-9267/ (845) 469-2141
Fax: (845) 469-9935
International Sales Office:
140 Allstate Parkway
Markham, Ontario, Canada L3R 0Z7
Tel: (905) 944-4300 / Fax (905) 944-4330
Printed in Canada
w w w. n e x a n s e n e r g y. c o m
09/2008
LEAD FREE
Download