FIREX ® Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE OVER 180 YEARS OF EXPERIENCE 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 FIREX®-II: CSA Type TECK90 Cables Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 600 V Multiconductor Cables 14 AWG and 12 AWG Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 10 AWG and Composite Cables. . . . . . . . . . . . . . . . . . . . . . . . . . 6 1 kV Cables 1 and 2 Conductor Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3 and 4 Conductor Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 5 kV Cables 3 Conductor Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 FIREX®-MC: UL Type MC Cables FIREX MC – 600 V Cables Applications and Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 14 AWG to 10 AWG Multiconductor Cables. . . . . . . . . . . . . . . . . 11 3 Conductor Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 FIREX MV – 5 kV Cables Applications and Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 5 kV Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Color Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 1-866-663-9267 1 Introduction Nexans is one of the largest wire and cable manufacturers in the world, and in North America. In North America we manufacture in locations across the United States and Canada. We design and produce a wide range of cables used in power, industrial, construction and communication applications. With more than nine decades of experience as a leader in the industrial and power cable markets, Nexans is contracted by heavy industry and utilities worldwide to provide turnkey solutions for the bulk transmission of power - from generating station through the transmission and distribution systems to commercial, residential and industrial areas. This catalog has been prepared for the convenience of those using electrical conductors in industrial, commercial and residential applications. The information included in the many tabulations will be of particular value to the architect, engineer, electrician, and layperson alike. Although we have listed the types of wires and cables suitable for most conditions, we are equipped to manufacture other types to suit special needs. We would be pleased to recommend the most suitable construction for any special condition that you may encounter. The determination of the correct cable size and type, and the selection of methods of installation suitable for the type and location of particular circuits, should be made in accordance with local regulations. Any questions in this respect should be directed primarily to the local Electrical Inspection Authority. We are pleased to note that all the cables in this catalog are LEAD FREE. This indicates that the Nexans cable components have less than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of hazardous substances) regulations and below the level requiring labeling by California proposition #65. 1-866-663-9267 2 TECK90 Applications FIREX®-II TECK Cables, originally developed for use in Canadian mines, are flexible, resistant to mechanical abuse, corrosion resistant, compact and reliable. They are suitable for a wide range of applications, including hazardous locations. Industries such as pulp and paper, chemical, petroleum and other primary and secondary manufacturing industries have used FIREX®-II TECK Cables, particularly in areas where cables are subject to the risk of mechanical damage and chemical attack. Commercial applications for FIREX®-II TECK Cables include apartment buildings and commercial complexes. FIREX®-II TECK Cables can be relocated easily because they are rugged and flexible. They can be used in both dry and wet locations in open wiring, in ventilated, non-ventilated and ladder-type cable troughs, in ventilated flexible cableways, and for direct burial. TECK Cables are also suitable for service entrance installations – above and below ground. Highlights Nexans FIREX®-II TECK Cables are • • • • • • • • • Available from stock Versatile Flexible Resistant to Mechanical Abuse and Corrosion Compact and Reliable “HL” and “FT4” Rated per CSA 90°C to -40°C Low Acid Gas (AG14) Lead Free 1-866-663-9267 3 TECK90 Aluminum Interlock Armored Power and Control Cable –40°C / +90°C rated - Lead Free Multiple conductors, with ground wire, inner PVC jacket, aluminum interlocked armor, outer PVC jacket Construction Conductor: bare, annealed copper Class B stranded in accordance with ASTM B8. In sizes 8 AWG to 1000 kcmil, the conductors are compact stranded to reduce cable diameter and weight. Conductor Shield: extruded semiconducting cross-linked polyethylene is applied for cables rated over 1000 volts. Insulation: cross linked polyethylene. Meets CSA C22.2 No. 38 type RW90 for unshielded cables rated 5 kV or less. Assembly: conductors are cabled in concentric layers with grounding wire, interstices are filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially round configuration, as required. Inner Jacket: black polyvinyl chloride jacket per CSA C22.2 No. 131-07, 90°C temperature rating, flameretardant, low-acid-gas-emitting. Armor: interlocking aluminum tape armor applied directly over the inner jacket. Outer Jacket: overall polyvinyl chloride jacket per CSA C22.2 No. 131-07; low acid gas emission; limited flame spread and excellent corrosion resistance. Jacket color is black for 600 V and 1 kV cables, orange for 5 kV cables. Conductor Identification 1 conductor: black 2 conductors: black, white 3 conductors: red, black, blue 4 conductors: red, black, blue, white 5 or more: number coding Composite: Power: color coded Control: number coded For color coding: 14 AWG to 2 AWG: colored insulation 1 AWG and larger: printed color stripe Bending Radius Fixed position: Unshielded Cables: 7 × cable overall diameter Shielded Cables: 12 × cable overall diameter During pulling: Twice the above values Specifications • Meets the requirements of CSA C22.2 No. 38 type RW90 for unshielded conductors • Meets CSA C22.2 No. 131-07 type TECK Cables up to 5 kV unshielded • Control cables meet CSA C22.2 No. 239-97(R2006). Product features •Cables are CSA listed as Type TECK (for cables up to 5 kV) •CSA listed insulated conductors •Cables are flame-retardant and pass CSA FT1 •Cables are fire-retardant and pass CSA FT4 •ICEA T-29-520 Fire Test at 210,000 BTU/hr, IEEE 1202, 383 and UL 1685 •Cables are low-acid-gas-emitting per CSA C22.2 No. 0.3-01 and marked AG14 • Cables exhibit a –40°C low temperature rating with suitable precautions •Temperature rating of 90°C dry and wet •130°C emergency rating and 250°C short circuit rating •Cables are rated for Hazardous Locations (HL) per CSA C22.2 No. 174-M1987(R2008)* •Excellent mechanical and physical properties •Sunlight and oil resistant jacket •Lead Free and RoHS compliant •Suitable for direct burial, use in cable tray and embedment in concrete Options The following constructions can be provided on special orders: • Aluminum conductors •Steel interlock armor • Extra ground wires • Special color or number coding • Specially colored jackets • Other constructions and combinations (some manufacturing restrictions apply) *Note: These cables cannot be used in Class I or II Division 1 locations in accordance with the N.E.C. 1-866-663-9267 4 TECK90 Aluminum Interlocked Armored Power and Control Cable –40°C / +90°C rated - Lead Free 600 V, Multiconductor, 14 AWG (7w) with 14 AWG (7w) bare ground Insulation Thickness: 30 mils / 0.76 mm *Ampacity at 30°C Ambient Temperature: 15 Amps Part # of Number Cond. 422204 422212 422220 422238 422246 422253 422261 444182 388207 ———— 422279 443184 670101 398883 398875 432989 ———— 444547 443796 369785 ———— ———— 2 3 4 5 6 7 8 9 10 11 12 15 19 20 25 30 35 40 50 60 80 90 Inner Jacket Thickness mils mm 45 45 45 45 45 45 60 60 60 60 60 60 60 60 80 80 80 80 80 80 80 80 Nominal Diameter over Inner Jacket inches mm 1.14.369 1.14.390 1.14.444 1.14.472 1.14.515 1.14.522 1.52.597 1.52.608 1.52.671 1.52.679 1.52.700 1.52.764 1.52.835 1.52.850 2.03.983 2.03 1.060 2.03 1.152 2.03 1.179 2.03 1.282 2.03 1.435 2.03 1.604 2.03 1.689 Nominal Diameter over Armor inches mm 9.37.600 9.91.621 11.27.676 11.99.703 13.08.743 13.26.755 15.16.825 15.45.836 17.04.898 17.25.906 17.78.927 19.41.990 21.21 1.073 21.59 1.105 24.99 1.239 26.92 1.311 29.26 1.372 29.95 1.431 32.56 1.535 36.45 1.710 40.74 1.954 42.90 2.039 Nominal Diameter over Outer Jacket inches mm 15.24.688 15.77.709 17.17.761 17.86.787 18.87.828 19.18.844 20.96.909 21.23.923 22.81.984 23.01.992 23.55 1.013 25.15 1.090 27.25 1.157 28.07 1.189 31.47 1.326 33.30 1.399 34.85 1.488 36.35 1.519 38.99 1.642 43.43 1.850 49.63 2.094 51.79 2.183 17.48 18.01 19.33 19.99 21.03 21.44 23.09 23.44 24.99 25.18 25.73 27.69 29.39 30.20 33.68 35.53 37.80 38.58 41.71 46.99 53.18 55.44 Approximate Net Cable Weight lb/kft kg/km 191 225 266 306 316 338 384 409 448 466 489 583 748 766 852 995 1066 1224 1468 1613 2132 2347 284 335 396 455 471 502 571 609 667 693 728 868 1113 1140 1268 1481 1587 1822 2184 2400 3173 3494 600 V, Multiconductor, 12 AWG (7w) with 14 AWG (7w) bare ground Insulation Thickness: 30 mils / 0.76 mm *Ampacity at 30°C Ambient Temperature: 20 Amps Part # of Number Cond. Inner Jacket Thickness mils mm 422287 422295 422303 383679 422311 422329 383695 ———— 422337 ———— 416388 444653 ———— 432732 291104 444638 ———— ———— ———— ———— ———— ———— 45 45 45 45 60 60 60 60 60 60 60 60 80 80 80 80 80 80 80 80 110 110 2 3 4 5 6 7 8 9 10 11 12 15 19 20 25 30 35 40 50 60 80 90 Nominal Diameter over Inner Jacket inches mm 1.14.405 1.14.429 1.14.502 1.14.522 1.52.599 1.52.614 1.52.656 1.52.700 1.52.744 1.52.760 1.52.776 1.52.842 2.03.905 2.03.974 2.03 1.093 2.03 1.167 2.03 1.308 2.03 1.367 2.03 1.483 2.03 1.615 2.79 1.865 2.79 1.962 Nominal Diameter over Armor inches mm 10.29.636 10.90.660 12.75.733 13.26.752 15.21.828 15.60.843 16.66.884 17.78.940 18.90.988 19.30 1.028 19.71 1.037 21.39 1.101 22.99 1.141 24.74 1.233 27.76 1.348 29.64 1.421 33.22 1.528 34.72 1.642 37.67 1.758 41.03 1.965 47.37 2.215 49.85 2.312 Nominal Diameter over Outer Jacket inches mm 16.15.724 16.76.745 18.62.817 19.10.839 21.03.912 21.41.927 22.45.971 23.87 1.014 25.10 1.077 26.11 1.096 26.34 1.125 27.97 1.189 29.46 1.233 31.32 1.321 34.24 1.436 36.09 1.509 38.81 1.668 41.71 1.737 44.65 1.853 49.91 2.015 56.26 2.269 58.72 2.366 18.39 18.92 20.75 21.31 23.16 23.55 24.66 25.76 27.35 27.84 28.58 30.20 31.32 33.55 36.47 38.32 42.36 44.12 47.06 51.18 57.63 60.09 Approximate Net Cable Weight lb/kft kg/km 238 280 298 347 402 438 476 496 531 622 651 755 937 973 1165 1302 1533 1593 1884 2311 3021 3318 *Ampacity in accordance with the Canadian Electrical Code, Part 1. Derating required for more than 3 conductors. 1-866-663-9267 5 354 417 443 516 598 652 708 738 790 925 969 1123 1394 1448 1733 1938 2281 2370 2804 3439 4495 4937 TECK90 Aluminum Interlocked Armored Power and Control Cable –40°C / +90°C rated - Lead Free 600 V, Multiconductor, 10 AWG (7w) with 12 AWG (7w) bare ground Insulation Thickness: 30 mils / 0.76 mm *Ampacity at 30°C Ambient Temperature: 30 Amps Part # of Number Cond. Inner Jacket Thickness mils mm 383588 422345 422352 ———— 069815 248153 318246 ———— 444562 ———— 105395 444612 ———— 444620 ———— 626804 ———— ———— ———— ———— ———— ———— 45 45 45 60 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 110 110 110 2 3 4 5 6 7 8 9 10 11 12 15 19 20 25 30 35 40 50 60 80 90 Nominal Diameter over Inner Jacket inches mm 1.14.452 1.14.481 1.14.560 1.52.604 1.52.671 1.52.699 1.52.726 1.52.766 1.52.840 1.52.879 2.03.917 2.03.987 2.03 1.066 2.03 1.098 2.03 1.229 2.03 1.317 2.03 1.494 2.03 1.567 2.03 1.701 2.79 1.910 2.79 2.133 2.79 2.246 Nominal Diameter over Armor inches mm 11.48.684 12.23.712 14.22.783 15.35.833 17.04.900 17.75.928 18.44.954 19.45 1.006 21.33 1.100 22.33 1.135 23.29 1.178 25.06 1.247 27.07 1.321 27.89 1.357 31.22 1.504 33.45 1.573 37.96 1.714 39.80 1.917 43.21 2.051 48.50 2.260 54.18 2.483 57.05 2.596 Nominal Diameter over Outer Jacket inches mm 17.37.769 18.08.798 19.89.867 21.16.918 22.86.985 23.57 1.018 24.23 1.047 24.55 1.094 27.94 1.188 28.83 1.222 29.92 1.266 31.67 1.335 33.55 1.414 34.47 1.445 38.20 1.596 39.95 1.680 43.54 1.854 48.69 1.967 52.10 2.105 57.40 2.314 63.07 2.570 65.94 2.683 19.53 20.27 22.02 23.32 25.01 25.85 26.59 27.79 30.18 31.03 32.16 33.91 35.92 36.70 40.54 42.67 47.10 49.96 53.47 58.78 65.28 68.15 Approximate Net Cable Weight lb/kft kg/km 272 339 383 421 517 539 617 633 776 795 885 1056 1209 1291 1528 1770 2097 2298 2743 3303 4225 4656 *Ampacity in accordance with the Canadian Electrical Code, Part 1, Derating required for more than 3 conductors. 405 504 570 627 770 802 918 942 1154 1183 1318 1571 1800 1921 2274 2634 3121 3421 4082 4916 6288 6928 600 V, Composite Power and Control Conductor Size Power Cond. Inner Jacket Nominal Diameter Nominal Diameter Nominal Diameter Approximate Net Ampacity** Part Insulation Thickness Thickness over Inner Jacket over Armor over Outer Jacket Cable Weight 30°C Number Power Control Ground Ambient AWG mils mm mils mm inches mm inches mm inches mm lb/kft kg/km amps 252197 252213 260877 252338 218544 252379 ——— 067330 ——— ——— ——— 459156 ——— 302976 ——— 306621 ——— 306639 ——— ——— ——— 306613 ——— 12 10 10 8 8 6 6 4 4 3 3 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 14 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 12 10 10 8 8 8 8 6 6 6 6 6 6 6 6 6 6 4 4 4 4 30 30 30 45 45 60 60 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 .76 .76 .76 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 .591 .596 .665 .715 .755 .900 .900 .904 .904 .964 .964 1.026 1.026 1.182 1.182 1.263 1.263 1.348 1.348 1.450 1.450 1.567 1.567 15.00 15.14 16.90 18.16 19.17 22.86 22.86 22.96 22.96 24.48 24.48 26.05 26.05 30.03 30.03 32.08 32.08 34.23 34.23 36.82 36.82 39.80 39.80 **Ampacity of power conductors per Canadian Electrical Code, Part 1. 1-866-663-9267 6 .831 .836 .905 .955 1.010 1.175 1.175 1.179 1.179 1.239 1.239 1.301 1.301 1.457 1.457 1.538 1.538 1.623 1.623 1.725 1.725 1.872 1.872 21.10 21.23 23.00 24.26 25.27 29.85 29.85 29.57 29.57 31.09 31.09 32.66 32.66 36.64 36.64 38.69 38.69 40.84 40.84 43.13 43.13 47.17 47.17 .929 .936 1.003 1.053 1.159 1.288 1.288 1.308 1.308 1.368 1.368 1.430 1.430 1.586 1.586 1.667 1.667 1.772 1.772 1.854 1.854 2.051 2.051 23.59 24.37 25.49 26.75 29.43 32.72 32.72 33.22 33.22 34.74 34.74 36.31 36.31 40.29 40.29 42.34 42.34 44.49 44.49 47.08 47.08 52.09 52.09 380 414 442 530 558 700 843 985 1001 1155 1172 1322 1339 1609 1626 1823 1885 2218 2235 2667 2683 3294 3312 566 616 658 789 830 1042 1254 1466 1490 1719 1744 1967 1992 2394 2420 2713 2805 3300 3326 3969 3993 4902 4929 20 30 30 45 45 65 65 85 85 105 105 120 120 140 140 155 155 185 185 210 210 235 235 TECK90 Aluminum Interlocked Armored Power Cable –40°C / +90°C rated - Lead Free 1 kV, 1 Conductor with Concentric Bare Ground Part Cond. Ground Insulation Thickness Inner Jacket Nominal Diameter Nominal Diameter Approximate Net Approximate Net Number Size Size Thickness over Inner Jacket over Armor over Outer Jacket Cable Weight AWG/ kcmil AWG mils mm mils mm inches mm inches mm inches mm lb/kft kg/km ——— ——— ——— 295170 ——— 550335 550343 550350 550368 550376 535443 550384 208702 550392 391847 526319 528000 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 750 1000 8 6 6 6 4 4 4 3 3 2 2 1 1 1/0 1/0 2/0 2/0 60 60 60 60 80 80 80 80 80 90 90 90 90 90 90 90 90 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 30 30 30 30 45 45 45 45 45 60 60 60 60 60 60 60 60 .76 .76 .76 .76 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 .453 .497 .525 .555 .658 .725 .750 .807 .859 .955 1.005 1.080 1.123 1.237 1.278 1.408 1.561 11.50 12.63 13.33 14.10 16.70 18.42 19.05 20.49 21.82 24.25 25.53 27.43 28.53 31.42 32.47 35.75 39.64 .693 .737 .765 .795 .898 .965 1.025 1.070 1.134 1.247 1.280 1.353 1.398 1.514 1.553 1.683 1.911 17.60 18.72 19.43 20.19 22.81 24.51 26.04 27.18 28.80 31.67 32.51 34.37 35.51 38.46 39.45 42.75 48.53 .791 .835 .863 .893 .996 1.069 1.135 1.180 1.244 1.355 1.409 1.465 1.527 1.625 1.682 1.812 2.045 20.09 21.21 21.92 22.68 25.30 27.15 28.83 29.97 31.60 34.42 35.79 37.21 38.79 41.28 42.72 46.02 51.94 331 428 473 528 696 781 944 1121 1272 1466 1715 1947 2164 2596 2960 3648 4674 493 637 704 786 1036 1162 1405 1668 1893 2181 2552 2897 3220 3863 4405 5429 6955 Ampacity* 30°C Ambient amps 100 135 155 180 210 245 285 330 385 425 480 530 575 660 740 845 1000 1 kV, 2 Conductors with Bare Ground Part Cond. Ground Insulation Thickness Inner Jacket Nominal Diameter Nominal Diameter Approximate Net Approximate Net Ampacity* Number Size Size Thickness over Inner Jacket over Armor over Outer Jacket Cable Weight 30°C Ambient AWG/ kcmil AWG mils mm mils mm inches mm inches mm inches mm lb/kft kg/km amps 184838 133280 138941 307884 422493 302968 ——— 260315 ——— 119917 527572 ——— 413187 318873 ——— ——— ——— 318865 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 14 14 12 10 8 8 6 6 6 6 6 4 4 4 4 3 3 3 45 45 45 45 60 60 60 60 80 80 80 80 80 90 90 90 90 90 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.29 2.29 2.29 2.29 2.29 45 45 45 60 60 60 80 80 80 80 80 80 80 80 80 110 110 110 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 .423 .464 .510 .590 .718 .812 .902 .963 1.110 1.185 1.263 1.358 1.463 1.598 1.699 1.852 1.938 2.097 10.74 11.78 12.95 14.98 18.25 20.61 22.91 24.45 28.20 30.09 32.09 34.50 37.16 40.59 43.15 47.03 49.23 53.27 .663 .696 .750 .819 .945 1.084 1.177 1.235 1.385 1.454 1.533 1.633 1.731 1.948 2.049 2.202 2.288 2.447 *Ampacity in accordance with the Canadian Electrical Code, Part 1. 1-866-663-9267 7 16.84 17.68 19.05 20.80 24.00 27.53 29.90 31.37 35.18 36.93 38.94 41.48 43.97 49.48 52.04 55.93 58.11 62.15 .761 .794 .848 .926 1.055 1.188 1.306 1.339 1.514 1.558 1.641 1.762 1.863 2.082 2.183 2.336 2.422 2.581 19.32 20.17 21.54 23.52 26.80 30.18 33.17 34.01 38.45 39.57 41.68 44.75 47.32 52.88 55.44 59.33 61.52 65.56 216 272 296 407 545 742 912 1029 1252 1451 1675 2031 2385 2870 3291 3837 4236 5082 321 405 440 606 811 1104 1357 1531 1863 2159 2493 3022 3549 4270 4882 5710 6303 7563 15 20 30 45 65 85 105 120 140 155 185 210 235 265 295 325 345 395 TECK90 Aluminum Interlocked Armored Power Cable –40°C / +90°C rated - Lead Free 1 kV, 3 Conductors with Bare Ground Part Cond. Ground Insulation Thickness Inner Jacket Nominal Diameter Nominal Diameter Approximate Net Approximate Net Ampacity* Number Size Size Thickness over Inner Jacket over Armor over Outer Jacket Cable Weight 30°C Ambient AWG/ kcmil AWG mils mm mils mm inches mm inches mm inches mm lb/kft kg/km amps 654228 307850 307843 422360 422378 422386 307876 422394 422402 422410 422428 438929 438937 438945 438952 438960 438978 438986 442632 560094 *Ampacity 14 14 12 14 10 12 8 10 6 8 4 8 3 6 2 6 1 6 1/0 6 2/0 6 3/0 4 4/0 4 250 4 300 4 350 3 400 3 500 3 600 2 750 2 in accordance 45 1.14 45 1.14 .448 11.38 45 1.14 45 1.14 .503 12.77 45 1.14 60 1.52 .576 14.63 45 1.14 60 1.52 .627 15.93 60 1.52 60 1.52 .766 19.44 60 1.52 80 2.03 .904 22.96 60 1.52 80 2.03 .964 24.48 60 1.52 80 2.03 1.026 26.05 80 2.03 80 2.03 1.182 30.03 80 2.03 80 2.03 1.263 32.08 80 2.03 80 2.03 1.348 34.23 80 2.03 80 2.03 1.450 36.82 80 2.03 80 2.03 1.567 39.80 90 2.29 110 2.79 1.768 44.91 90 2.29 110 2.79 1.877 47.67 90 2.29 110 2.79 1.976 50.20 90 2.29 110 2.79 2.074 52.68 90 2.29 110 2.79 2.241 56.92 90 2.29 110 2.79 2.408 61.17 90 2.29 110 2.79 2.614 66.40 with the Canadian Electrical Code, Part 1. .685 .735 .807 .855 1.035 1.176 1.236 1.300 1.457 1.537 1.621 1.725 1.815 2.120 2.235 2.330 2.422 2.595 2.758 2.959 17.40 18.67 20.50 21.72 26.29 29.87 31.39 33.02 37.01 39.04 41.14 43.82 46.10 53.85 56.77 59.18 61.52 65.91 70.05 75.16 .770 .821 .891 .942 1.125 1.265 1.326 1.388 1.547 1.630 1.729 1.835 1.925 2.250 2.367 2.462 2.554 2.757 2.935 3.121 19.56 20.85 22.63 23.93 28.58 32.13 33.68 35.26 39.29 41.40 43.92 46.61 48.90 57.15 60.12 61.52 64.87 70.03 74.55 79.27 247 297 381 491 644 924 1026 1274 1539 1796 2165 2571 3196 3830 4382 4990 5534 6674 7747 9596 367 441 567 730 959 1375 1526 1896 2291 2672 3222 3827 4756 5700 6520 7426 8235 9932 11528 14281 15 20 30 45 65 85 105 120 140 155 185 210 235 265 295 325 345 395 455 500 1 kV, 4 Conductors with Bare Ground Part Cond. Ground Insulation Thickness Inner Jacket Nominal Diameter Nominal Diameter Approximate Net Approximate Net Ampacity** Number Size Size Thickness over Inner Jacket over Armor over Outer Jacket Cable Weight 30°C Ambient AWG/ kcmil AWG mils mm mils mm inches mm inches mm inches mm lb/kft kg/km amps 133298 14 14 369322 12 14 649707 10 12 383612 8 10 383620 6 8 529271 4 8 199588 3 6 383646 2 6 105312 1 6 568261 1/0 6 443358 2/0 6 568279 3/0 4 568709 4/0 4 568337 250 4 167890 300 4 568295 350 3 227462 400 3 568345 500 3 **Ampacity assuming 4th Code, Part 1. 45 1.14 45 1.14 45 1.14 45 1.14 60 1.52 60 1.52 60 1.52 60 1.52 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03 90 2.29 90 2.29 90 2.29 90 2.29 90 2.29 conductor is a 45 60 60 60 80 80 80 80 80 80 80 80 110 110 110 110 110 110 neutral 1.14 .493 1.52 .569 1.52 .632 1.52 .694 2.03 .895 2.03 .995 2.03 1.085 2.03 1.145 2.03 1.303 2.03 1.394 2.03 1.488 2.03 1.607 2.79 1.793 2.79 1.952 2.79 2.077 2.79 2.189 2.79 2.294 2.79 2.481 of a 3 phase. 4 12.52 .733 14.46 .809 16.04 .878 17.62 .921 22.73 1.170 25.27 1.270 27.55 1.360 29.09 1.420 33.11 1.578 35.40 1.669 37.81 1.757 40.81 1.852 45.55 2.033 49.57 2.302 52.76 2.427 55.60 2.539 58.26 2.644 63.02 2.831 wire system in 1-866-663-9267 8 18.61 .827 20.33 .903 22.30 .965 23.39 1.028 29.71 1.280 32.26 1.351 34.54 1.441 36.07 1.501 39.50 1.663 42.39 1.774 44.63 1.865 47.04 1.960 51.64 2.141 58.52 2.417 61.65 2.542 64.49 2.654 67.16 2.833 71.91 3.020 accordance with 21.00 282 420 22.94 356 530 24.51 436 649 26.11 583 867 32.51 838 1247 34.31 1122 1669 36.60 1359 2022 38.13 1580 2351 42.24 1927 2868 45.06 2295 3415 47.37 2711 4034 49.78 3395 5053 54.38 4197 6239 61.39 4828 7230 65.57 5630 8378 67.41 6399 9522 71.96 7132 10613 76.71 8555 12732 the Canadian Electrical 15 20 30 45 65 85 105 120 140 155 185 210 235 265 295 325 345 395 TECK90 Aluminum Interlocked Armored Power Cable –40°C / +90°C rated - Lead Free 5 kV Unshielded, 3 Conductors with Bare Ground Part Cond. Ground Insulation Thickness Inner Jacket Nominal Diameter Nominal Diameter Nominal Diameter Approximate Net Ampacity* Number Size Size Thickness over Inner Jacket over Armor over Outer Jacket Cable Weight 30°C Ambient AWG/ kcmil AWG mils mm mils mm inches mm inches mm inches mm lb/kft kg/km amps ——— 645952 645960 ——— 226225 217760 200766 226233 ——— 226241 226274 ——— 226282 ——— 226290 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 10 8 8 6 6 6 6 6 4 4 4 4 3 3 3 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 60 80 80 80 80 80 80 80 80 80 110 110 110 110 110 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 .931 1.051 1.146 1.200 1.266 1.335 1.415 1.500 1.606 1.724 1.882 1.990 2.094 2.188 2.355 23.64 26.69 29.11 30.49 32.15 33.91 35.95 38.10 40.80 43.79 47.80 50.55 53.19 55.56 59.81 1.206 1.326 1.421 1.475 1.541 1.610 1.690 1.775 1.956 2.074 2.232 2.340 2.444 2.538 2.705 *Ampacity in accordance with the Canadian Electrical Code, Part 1. 1-866-663-9267 9 30.63 33.68 36.09 37.46 39.14 40.89 42.93 45.09 49.68 52.68 56.69 59.44 62.08 64.47 68.71 1.315 1.435 1.530 1.584 1.670 1.739 1.819 1.904 2.090 2.208 2.366 2.474 2.578 2.672 2.839 33.40 36.45 38.86 40.23 42.42 44.17 46.20 48.36 53.09 56.08 60.10 62.84 65.48 67.87 72.11 721 872 1155 1322 1503 1732 2013 2339 2929 3544 4032 4605 5242 5852 7053 1073 1297 1719 1968 2237 2577 2997 3481 4359 5274 6001 6853 7800 8709 10495 45 65 85 105 120 140 155 185 210 235 265 295 325 345 395 FIREX® MC Aluminum Interlock Armored Power and Control Cable UL Type MC, 600 V, 90°C rated - Lead Free Multiple conductors, with ground wire, aluminum interlocked armor, PVC jacket Applications Construction Specifications Firex MC is suitable and allowed by the NEC for use in the following applications: • for power, lighting and control circuits and as branch circuits and power feeders in industrial, commercial, institutional and residential installations up to 600 volts. • fished or embedded in plaster and concrete. • direct buried or used as an aerial cable when fixed to a messenger support cable. • used in concealed or exposed applications. • installed in cable trays and other raceways. • in Class I and II, Division 2 as well as Class III, Division 1 and 2 hazardous locations. • under raised floors of information technology rooms. • where exposed to harsh chemicals and vapors. Conductor: bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8. •Meets UL 44, XHHW-2 600V conductors •Meets UL 1569 requirements for Type MC, Metal Clad cables •Designated Type MC per NEC Article 330 Insulation: cross linked polyethylene type XHHW-2 per UL 44. Assembly: conductors are cabled in concentric layers with grounding wire, interstices are filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially round configuration. Armor: interlocking aluminum tape armor applied directly over the core. Jacket: overall polyvinyl chloride jacket per UL 1569, 90°C temperature rating; low acid gas emission; limited flame spread and excellent corrosion resistance. Conductor Identification Sizes #14 AWG to #10 AWG: Method #1-E2 per ICEA S-73-532 Sizes #8 AWG to 500 kcmil: Method #4 per ICEA S-73-532 See page 15. Bending Radius Fixed position: 7 x cable overall diameter During pulling: 12 x cable overall diameter 1-866-663-9267 10 Product features • Cables are UL listed as Type MC, 600 V • UL listed insulated conductors • Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEEE 1202 and CSA FT4 • Cables exhibit a –25°C cold bend rating with suitable precautions • Temperature rating of 90°C dry and wet • 130°C emergency rating and 250°C short circuit rating • Excellent mechanical and physical properties • Sunlight and oil resistant jacket •Lead Free •Suitable for direct burial, use in cable tray and embedment in concrete •Can be installed in hazardous locations designated Class I or II Division 2, NEC Articles 501.10(B) and 502.10(B) as well as Class III Division 1 and 2, NEC Article 503.10 A and B. Options The following constructions can be provided on special orders: • Aluminum conductors •Steel interlock armor • Extra ground wires • Special color or number coding • Specially colored jackets • Other constructions and combinations (some manufacturing restrictions apply) FIREX® MC Aluminum Interlocked Armored Power and Control Cable UL Type MC, 90°C rated - Lead Free 600 V, Multiconductor with Bare Ground Insulation Thickness: 30 mils / 0.76 mm Part Number # of Cond. Nominal Diameter Jacket Thickness over Armor Nominal Diameter over Jacket AWG inches mm inches mm lb/kft 640540 2 14 (7w) 14 (7w) 639930 3 14 (7w) 14 (7w) ——— 4 14 (7w) 14 (7w) ——— 5 14 (7w) 14 (7w) ——— 7 14 (7w) 14 (7w) ——— 9 14 (7w) 14 (7w) ——— 12 14 (7w) 14 (7w) ——— 15 14 (7w) 14 (7w) ——— 19 14 (7w) 14 (7w) ——— 25 14 (7w) 14 (7w) ——— 37 14 (7w) 14 (7w) 640524 2 12 (7w) 12 (7w) 639963 3 12 (7w) 12 (7w) 633511 4 12 (7w) 12 (7w) ——— 5 12 (7w) 12 (7w) ——— 7 12 (7w) 12 (7w) ——— 9 12 (7w) 12 (7w) ——— 12 12 (7w) 12 (7w) ——— 15 12 (7w) 12 (7w) ——— 19 12 (7w) 12 (7w) ——— 25 12 (7w) 12 (7w) ——— 37 12 (7w) 12 (7w) 670322 2 10 (7w) 10 (7w) 639971 3 10 (7w) 10 (7w) ——— 4 10 (7w) 10 (7w) ——— 5 10 (7w) 10 (7w) ——— 7 10 (7w) 10 (7w) ——— 9 10 (7w) 10 (7w) ——— 12 10 (7w) 10 (7w) ——— 37 10 (7w) 10 (7w) .480 .520 .560 .590 .645 .715 .790 .840 .900 1.045 1.175 .498 .508 .550 .606 .642 .785 .831 .950 .981 1.196 1.380 .556 .620 .626 .751 .782 .915 .971 1.570 12.19 50 1.27 13.54 50 1.27 14.22 50 1.27 14.99 50 1.27 16.38 50 1.27 18.16 50 1.27 20.07 50 1.27 21.34 50 1.27 22.86 50 1.27 26.54 50 1.27 29.85 50 1.27 12.65 50 1.27 12.90 50 1.27 13.97 50 1.27 15.39 50 1.27 16.31 50 1.27 19.94 50 1.27 21.11 50 1.27 24.13 50 1.27 24.92 50 1.27 30.38 50 1.27 35.05 50 1.27 14.12 50 1.27 15.75 50 1.27 15.90 50 1.27 19.08 50 1.27 19.86 50 1.27 23.24 50 1.27 24.66 50 1.27 39.88 50 1.27 .580 .625 .665 .695 .750 .820 .895 .950 1.010 1.155 1.300 .602 .612 .654 .706 .743 .890 .935 1.049 1.080 1.300 1.498 .658 .720 .730 .855 .882 1.020 1.077 1.715 14.73 15.88 16.89 17.65 19.05 20.83 22.73 24.13 25.65 29.34 33.02 15.29 15.54 16.61 17.93 18.87 22.61 23.75 26.64 27.43 33.02 38.05 16.71 18.29 18.54 21.72 22.40 25.91 27.36 43.56 160 180 210 230 275 330 400 465 550 730 980 196 226 246 302 362 458 545 664 779 1040 1430 240 312 343 423 509 630 758 2070 Cond. Size AWG Ground Wire Size mm mils Approximate Net Cable Weight Ampacity kg/km amps (1,3) 238 268 313 342 409 491 595 692 819 1086 1458 292 336 366 449 539 682 811 988 1159 1548 2128 357 464 510 630 757 938 1128 3081 25 25 20/25(2) 20 17.5 17.5 12.5 12.5 12.5 11.5 10 30 30 24/30(2) 24 21 21 15 15 15 13.5 12 40 40 32/40(2) 32 28 28 20 16 (1) Ampacities are in accordance with Table 310.16 of NEC for conductors in raceway or direct buried at 30°C ambient temperature and 90°C conductor temperature. The overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied (NEC Article 240.4(D)). For correction factors for different ambient temperatures and ampacities at different conductor temperatures see Table 310.16 of NEC. Ampacities for cables having more than three conductors have been derated per Article 310.15(B)(2)(a) of NEC. (2) Where the 4th conductor is the neutral of a balanced 3 phase system. (3) With load diversity of 50% (see Table B.310.11 of NEC). 1-866-663-9267 11 FIREX® MC Aluminum Armored Power and Control Cable UL Type MC, 90°C rated - Lead Free 600 V, 3 Conductors with Bare Ground Part Number Cond. Size Insulation Thickness Ground Wire Size Nominal Diameter Jacket Thickness over Armor Nominal Diameter over Jacket Approximate Net Cable Weight Ampacity AWG/kcmil mils mm AWG inches mm mils mm inches mm lb/kft kg/km amps(1) 634725 8 (7w) 634733 6 (7w) 634741 4 (7w) 634766 2 (7w) 660594 1 (19w) 634758 1/0 (19w) 634774 2/0 (19w) 645499 3/0 (19w) 634782 4/0 (19w) 634790 250 (37w) 634808 350 (37w) 634816 500 (37w) ——— 750 (61w) ——— 1000 (61w) 45 45 45 45 55 55 55 55 55 65 65 65 80 80 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 2.03 2.03 10 (7w) 8 (7w) 8 (7w) 6 (7w) 6 (7w) 6 (7w) 6 (7w) 4 (7w) 4 (7w) 4 (7w) 3 (7w) 2 (7w) 1 (19w) 1/0 (19w) 0.750 0.820 0.920 1.040 1.169 1.260 1.349 1.459 1.590 1.733 1.922 2.300 2.760 3.080 19.05 20.83 23.37 26.42 29.69 32.00 34.26 37.06 40.39 44.02 48.82 58.42 70.10 78.23 50 50 50 50 50 50 50 50 60 60 60 75 75 85 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.52 1.52 1.52 1.91 1.91 2.16 0.855 0.925 1.029 1.151 1.279 1.360 1.459 1.567 1.722 1.861 2.050 2.465 2.920 3.265 21.72 23.50 26.16 29.21 32.49 34.54 37.08 39.80 43.69 47.27 52.07 62.61 74.17 82.93 405 545 727 1038 1262 1501 1807 2244 2725 3173 4252 6205 8970 11685 603 811 1082 1545 1878 2234 2689 3339 4055 4722 6327 9234 13349 17389 55 75 95 130 150 170 195 225 260 290 350 430 535 615 (1) Ampacities are in accordance with Table 310.16 of NEC for conductors in raceway or direct buried at 30°C ambient temperature and 90°C conductor temperature. For correction factors for different ambient temperatures and ampacities at different conductor temperatures see Table 310.16 of NEC. 1-866-663-9267 12 FIREX® MV Aluminum Interlocked Armored Power Cable UL Type MV-90 2.4 kV* or 5 kV*, XLPE insulation, non-shielded, aluminum interlocked armor, PVC jacket Applications Construction Specifications Firex MV-90 is suitable and allowed by the NEC for use in the following applications: • for power feeders in industrial, commercial, and institutional installations up to 5000 volts. (2400 volts per NEC) • fished or embedded in plaster and concrete. • direct buried or used as an aerial cable when fixed to a messenger support cable. • used in concealed or exposed applications. • installed in cable trays and other raceways. • in Class I and II, Division 2 as well as Class III, Division 1 and 2 hazardous locations. • where exposed to harsh chemicals and vapors. Conductor: bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8. •Meets ICEA S-96-659 for nonshielded cables •Meets UL 1072 for Medium Voltage Cables, Type MV-90 •Designated Type MV as per NEC Article 328 Conductor shield: extruded thermosetting semi-conducting layer Insulation: XLPE as per UL 1072 ICEA S-96-659 Product features Unshielded cable: Number coded • Cables are UL listed as Type MV-90, 2.4 kV • UL listed insulated conductors • Cables are 5 kV rated per ICEA S-96-659 • Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEEE 1202 and CSA FT4 • Cables exhibit a –25°C cold bend rating with suitable precautions • Temperature rating of 90°C dry and wet • 130°C emergency rating and 250°C short circuit rating • Excellent mechanical and physical properties • Sunlight and oil resistant jacket •Suitable for direct burial, use in cable tray and embedment in concrete Bending Radius Options Fixed position: Unshielded: 7 x cable overall diameter The following constructions can be provided on special orders: • Aluminum conductors •Steel interlock armor • Extra ground wires • Special color or number coding • Specially colored jackets • Other constructions and combinations (some manufacturing restrictions apply) Assembly: insulated conductors are cabled with bare copper grounding conductor(s) and interstices are filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially round configuration. Armor: interlocking aluminum tape armor applied directly over the core. Jacket: overall polyvinyl chloride jacket, 90°C temperature rating; low acid gas emission; limited flame spread and excellent corrosion resistance. Conductor Identification During pulling: Unshielded: 12 x cable overall diameter *The NEC and UL 1072 limit unshielded cable to circuits operating at a maximum of 2400 volts phase to phase. ICEA S-96-659 rates unshielded cable with the same insulation thickness to a maximum operating voltage of 5000 volts phase to phase. 1-866-663-9267 13 FIREX® MV Aluminum Interlocked Armored Power Cable UL Type MV-90, 90°C rated 2.4 kV* or 5 kV* Unshielded, 3 Conductors with Bare Ground Insulation Thickness: 90 mils / 2.29 mm Part Number ——— ——— ——— ——— ——— ——— ——— ——— 650754 ——— 650747 650663 641464 ——— Cond. Size Ground Wire Size AWG/kcmil AWG 8 (7w) 8 (7w) 6 (7w) 6 (7w) 4 (7w) 6 (7w) 2 (7w) 6 (7w) 1 (19w) 6 (7w) 1/0 (19w) 4 (7w) 2/0 (19w) 4 (7w) 3/0 (19w) 4 (7w) 4/0 (19w) 3 (7w) 250 (37w) 3 (7w) 350 (37w) 2 (7w) 500 (37w) 1 (19w) 750 (61w) 1/0 (19w) 1000 (61w) 1/0 (19w) Nominal Diameter Jacket Thickness over Armor Nominal Diameter over Jacket Approximate Net Ampacity Cable Weight inches mm mils mm inches mm lb/kft 1.055 1.130 1.235 1.360 1.465 1.555 1.650 1.785 1.905 2.015 2.235 2.510 2.905 3.335 26.80 28.70 31.67 34.54 37.21 39.50 41.91 45.34 48.39 51.18 56.77 63.75 73.79 84.71 50 50 50 60 60 60 60 60 60 60 75 75 85 85 1.27 1.27 1.27 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.91 1.91 2.16 2.16 1.165 1.240 1.345 1.470 1.575 1.685 1.780 1.915 2.030 2.145 2.365 2.675 3.070 3.410 29.59 31.50 34.16 37.34 40.01 42.80 45.21 48.64 51.56 54.48 60.07 67.95 77.98 86.61 605 785 990 1295 1515 1855 2175 2700 3230 3655 4795 6535 9245 11850 kg/km 900 1168 1473 1927 2255 2761 3237 4018 4807 5439 7136 9725 13758 17635 amps(1,2) amps(3) 59 79 105 140 160 185 215 250 285 320 395 485 615 705 85 105 135 180 200 230 260 295 335 365 440 530 650 730 (1) Ampacity for cable in air in accordance with Table 310.71 of NEC, conductor temperature of 90°C and ambient temperature of 40°C. (2) Ampacity for cable in ventilated tray in accordance to Article 392.13(A)(2) and Table 310.71 of NEC. (3) Ampacity for cable direct buried in accordance with Table 310.83 with 90°C conductor temperature, R.H.O. 90, 100% load factor, 20°C earth temperature, one circuit. *The NEC and UL 1072 limit unshielded cable to circuits operating at a maximum of 2400 volts phase to phase. ICEA S-96-659 rates unshielded cable with the same insulation thickness to a maximum operating voltage of 5000 volts phase to phase. 1-866-663-9267 14 Conductor or Phase Identification Per ICEA S-73-532-E3.4 Method 4 Number Code Conductor Printing Details Conductor Printing Details 1st “1-ONE-1” 4th “4-FOUR-4” 2nd “2-TWO-2” 5th “5-FIVE-5” 3rd “3-THREE-3” 6th “6-SIX-6” Per ICEA S-73-532-E3.1 Method 1 and Table E2 (formerly K2) Colored Insulation with/without Colored Stripe Conductor Insulation Stripe Conductor Insulation Stripe 1st BLACK — 19th ORANGE Blue 2nd RED — 20th YELLOW Blue 3rd BLUE — 21st BROWN Blue 4th ORANGE — 22nd BLACK Orange 5th YELLOW — 23rd RED Orange 6th BROWN — 24th BLUE Orange 7th RED Black 25th YELLOW Orange 8th BLUE Black 26th BROWN Orange 9th ORANGE Black 27th BLACK Yellow 10th YELLOW Black 28th RED Yellow 11th BROWN Black 29th BLUE Yellow 12th BLACK Red 30th ORANGE Yellow 13th BLUE Red 31st BROWN Yellow 14th ORANGE Red 32nd BLACK Brown 15th YELLOW Red 33rd RED Brown 16th BROWN Red 34th BLUE Brown 17th BLACK Blue 35th ORANGE Brown 18th RED Blue 36th YELLOW Brown Note: The color code repeats at #1 “BLACK” as the 37th conductor (for cables with more than 36 conductors) for FIREX MC. 1-866-663-9267 15 WARNING NOTICE FLAMMABLE Non-metallic covering of electrical cables will burn and under certain conditions may transmit fire when ignited. Nexans has endeavoured to ensure the accuracy of the data in this publication, however we cannot be liable for the consequences of errors or omissions. All data is subject to change without notice. The installer and / or user assumes all liability for the consequences of the installation and / or use of any of our products in contravention of any applicable law, regulation or code. TOXIC Burning non-metallic coverings may emit acid gases, which are highly toxic, and may generate dense smoke. CORROSIVE Emission of acid gases may corrode metal in the vicinity, such as sensitive instruments and reinforcing rod in concrete. 1-866-663-9267 16 U.S. Sales Office: 25 Oakland Avenue, Chester, New York 10918 Tel:1-866-663-9267/ (845) 469-2141 Fax: (845) 469-9935 International Sales Office: 140 Allstate Parkway Markham, Ontario, Canada L3R 0Z7 Tel: (905) 944-4300 / Fax (905) 944-4330 Printed in Canada w w w. n e x a n s e n e r g y. c o m 09/2008 LEAD FREE