LATENT HEAT STORAGE WITH MELTING TEMPERATURE 29 °C SUPPORTING A SOLAR HEATING AND COOLING SYSTEM S. Hiebler, H. Mehling, M. Helm, C. Schweigler Bavarian Center for Applied Energy Research (ZAE Bayern e. V.) Walther-Meißner-Str. 6, 85748 Garching, Germany Tel: 49-89-329442-35 hiebler@muc.zae-bayern.de ABSTRACT Solar cooling systems with absorption chiller based on lithium bromide/water need a cooling tower to reject the waste heat to the ambient. Typically a wet cooling tower is used but water consumption, effort of conditioning water, fogging and risk of growth of legionella bacteria are hindering the market penetration of small solar cooling systems. To avoid a wet cooling tower and get on with a dry cooling tower, we support them with a low temperature latent heat storage. At high ambient temperatures the storage supports the dry cooling tower and stabilizes the temperature in the reject heat loop at moderate temperatures. This way, part of the heat rejection is shifted to lower temperatures during nighttime. During winter the storage is used as buffer storage for solar heating. The system concept and the development of the storage are presented, followed by a report on the operation of a first pilot installation. 1. INTRODUCTION In solar thermal installations, both solar cooling and solar heating can be provided synergistically, yielding a complete annual utilisation. During the cold season, solar heat serves for space heating. During the warm season, solar heat can be converted into useful cold by means of sorption cooling. A favourable situation is given when low temperature heating and cooling facilities, e.g. floor or wall heating systems or activated ceilings, are applied for heating and cooling. During heating operation, a low temperature latent heat storage can be used to balance the heat generation by the solar system and the supply to the heating system. Thus, a low operating temperature of the solar thermal system is accomplished yielding efficient operation with optimum solar gain. In the cooling mode, the same storage is used in combination with a dry cooling tower in order to replace a wet cooling tower. By that means heat rejection of the chiller is shifted partly to periods with lower ambient temperatures, i.e. night time, or to off-peak hours. 2. SYSTEM CONCEPT In conventional absorption cooling installations, wet cooling towers designed for a coolant supply/return temperature 27/35 °C are applied. To use a dry air-cooler, cooling water temperatures have to be increased to 40/45 °C. As a consequence of the increase of the cooling water temperature, the temperature level of the driving heat supplied to the regenerator of the absorption chiller has to be increased accordingly. This principal dependency of the required driving temperatures on the coolant temperatures of an absorption chiller can easily be estimated from the linear “characteristic-equation” model (Furukawa. 1983, Hellmann et al. 1998, Storkenmaier et al. 1999). The external heat carrier parameters for the discussed system configurations – governed by linear correlation according to the characteristic-equation model – are given in Figure 1. For chilled water 18/15 °C, starting from a chiller design with 80/75 °C, the required driving hot water temperature rises with increasing cooling water temperature to 90/85 °C when a dry air cooler together with a latent heat storage is used and further to 105/100 °C when solely a dry air cooler is applied. Similar, for chilled water temperature 12/6 °C the required driving hot water temperature increases from 90/85 °C to 100/95 °C for the system with dry air cooler assisted by a latent heat storage. For this chilled water layout, i.e. standard temperature 12/6 °C, complete dry aircooling is not feasible. driving heat temp. lled chi 105/100°C 100/95°C 90/85°C ll chi ed °C 2/6 r1 e t wa C 15° 18/ r te wa 80/75°C reject heat temp. 27/35°C wet cooling tower 32/40°C PCM + dry air-cooler 40/45°C dry air-cooler Figure 1: Influence of chilled water temperature and reject heat temperature on driving heat temperature. By integration of a heat storage into the heat rejection system of the absorption chiller, a part of the reject heat of the chiller can be buffered during the operation of the solar cooling system, allowing lower coolant temperatures during peak load operation of the chiller. Then the stored reject heat can be discharged during off-peak operation or at night time when more favourable ambient conditions, i.e. lower ambient temperatures, are available. As discussed above, as a consequence of the reduced coolant temperature arising from the integration of the latent heat storage, lower temperatures of the driving solar heat are feasible to operate the absorption chiller. Thus a higher solar gain is obtained for a given size of the solar collector system. A detailed analysis of the overall system design has been presented earlier (Schweigler et al. 2007). During heating operation, the latent heat storage balances the heat generation by the solar system and other heat sources and the heat supply to the heating system. Thus, a low operating temperature of the solar thermal system is accomplished yielding efficient operation with optimum solar gain. A simplified system structure for cooling (top) and heating operation (bottom) is given in Figure 2. COOLING MODE CHILLER Absorptionswä rmepumpe bzw. Kä ltemaschine 15°C V 18°C 40°C G A/C 90°C 85°C Wä rmeSpeicher AUX. Heizkessel BOILER 32°C Luftwä rme- 40°C tauscher 32° C DRY AIR COOLER PCM- Speicher 36° C SolarkollektorSOLAR anlage SYSTEM NT- Kühl-/Heizsystem HEATING / COOLING SYSTEM HEATING MODE LATENT 32°C HEAT STORAGE CHILLER Absorptionswärmepumpe bzw. Kä ltemaschine WärmeSpeicher AUX. Heizkessel BOILER Luftwärmetauscher 32°C PCM- 35°C Speicher SolarkollektorSOLAR anlage SYSTEM NT- Kühl-/Heizsystem HEATING / COOLING SYSTEM LATENT HEAT STORAGE Figure 2: Sketch of a solar heating and cooling system with absorption chiller (evaporator V, absorber/condenser A/C and generator G) and latent heat storage in cooling mode (top) and heating mode (bottom). 3. PILOT INSTALLATION Within the framework of the German “Solarthermie 2000plus” program, a pilot installation of the innovative solar heating and cooling system has been built. The installation serves simultaneously as field test project for a recently developed compact water/LiBr absorption chiller with 10 kW nominal capacity (Schweigler et al. 2002, Storkenmaier et al. 2003, Kühn et al. 2005). The chiller has been designed for chilled water supply/return temperature 15/18 °C and allows for utilization of rather moderate driving hot water temperature 85/75 °C when operated with open wet cooling tower. These conditions have been chosen as nominal data for the design of the chiller with a nominal chilled water capacity of 10 kW. When operated with higher driving hot water temperature of maximum 95 °C at the generator inlet the capacity increases to 160 % of its nominal value. The chiller exhibits a rather efficient part load behaviour with a COP above 0.7 throughout a wide capacity range. With respect to the solar cooling capacity of about 10 kW, a waste heat power of about 120 kWh is required in order to cover 50 % of the daily reject heat output of the chiller. The rest of the reject heat is directly transferred to the ambient by means of a dry air cooler, which operates with 36/40 °C cooling water temperature under peak load conditions, as given in Figure 2 (top). Therefore, the design of the latent heat storage will be based on 36/32 °C cooling water supply/return temperature. Apart from the solar cooling mode, during the heating season the system will serve for solarassisted heating. Assuming a solar insolation of 500 W/m2 for a duration of 6 hours again a heat storage capacity of about 120 kWh is required to absorb the solar gain of the 40 m2 solar collector field. The solar heat has to be stored above the return temperature of the building floor heating system, which is controlled in dependence of the ambient temperature. Under moderate winter heating conditions, the heating system return temperature typically ranges from 22 °C to 26 °C. Of course, phase transition of the PCM has to take place above this temperature level in order to accomplish heat transfer from the heat storage to the heating system. Supply of useful heat and cooling for conditioning of the office building (1000 m2, design heating demand: 42 W/m2) is provided by activated ceilings which receive chilled water from the evaporator of the absorption chiller during cooling mode and solar thermal heat during the solar heating season, respectively. 4. DEVELOPMENT OF THE LATENT HEAT STORAGE For the given application in a solar heating and cooling system, heat has to be stored in a very narrow temperature range in order to fulfil both tasks: support of the heat rejection of the chiller requires a phase change temperature below 32 °C and contribution to the heating of the building a phase change temperatures above 26 °C. Due to this limitation of the available temperature swing, the heat storage has been designed as a latent heat storage. According to its melting temperature in the range of 27 – 29 °C the salt hydrate calcium chloride hexahydrate (CaCl2•6H2O) has been chosen as phase change material (PCM), providing a heat capacity of about 150 J/g or 240 J/L between 26 °C and 32 °C. This value of the specific storage capacity comprises both sensible and latent heat. Of course the dominating portion is to be attributed to the latent part. For the comparison of the storage density of the latent heat storage to a conventional water heat storage, the specific heat of the liquid, i.e. water, and the temperature swing have to be taken into account. Given a temperature swing of 6 K only, a conventional water storage exhibits a storage density of 4.2 kJ/(kg K) x 6 K = 25 kJ/kg. Thus for the given application in the solar heating and cooling system, the latent heat storage allows for a reduction of the storage mass by a factor of about 6, requiring only about 10 % of the volume of a conventional water heat storage. Figure 3: Capillary tube heat exchanger for activation of the latent heat storage volume (left). 120 kWh latent heat storage, formed by two 800 L storage tanks (right). Within the project a commercial capillary tube system commonly used for wall heating installations has been applied as heat exchanger in the latent heat storage. Because of the high storage density of the PCM and its low thermal conductivity, a distance between the capillaries of only a few centimeters had been chosen. To reach 120 kWh heat storage capacity, two storage modules with a volume of 800 L each have been designed and constructed. The capillary tube heat exchanger has been properly configured in order to fully activate the entire storage volume, as shown in Figure 3. The heat exchanger has finally been immersed in a Polyethylene tank and hermetically sealed in order to avoid uptake of humidity from the ambient air. For the sake of economics and in order to achieve a marketable design the heat storage prototype has been based on standard components. The cost of the PCM is about 0.37 Euro/kg, leading to total cost of the latent heat storage of about 4,000 Euro. Apart from pure economic aspects, operational issues are of major relevance for the feasibility of small scale solar heating and cooling installations. Here, the system with dry air cooler and latent heat storage offers substantial reduction of the maintenance effort and improved performance during the solar heating season. 40 40 inlet both 36 32 temperature [°C] temperature [°C] 36 outlet st. 1/2 28 storage temperature 1/2 storage temperature 1/2 28 outlet st. 1/2 24 24 20 00:00 32 03:00 06:00 09:00 20 00:00 12:00 inlet both 03:00 0 10 -2 8 -4 -6 storage 1 storage 2 -8 -10 00:00 03:00 06:00 09:00 12:00 6 4 2 0 00:00 12:00 03:00 06:00 09:00 12:00 time [h:min] 70 0 60 -10 storage 1 storage 2 -20 stored energy [kWh] stored energy [kWh] 09:00 storage 1 storage 2 Zeit [h:min] -30 -40 -50 -60 -70 00:00 06:00 time [h:min] power [kW] power [kW] time [h:min] 50 storage 1 storage 2 40 30 20 10 03:00 06:00 09:00 time [h:min] 12:00 0 00:00 03:00 06:00 09:00 12:00 time [h:min] Figure 4: Operational results of the two 800 L latent heat storage modules. Temperatures (top), power (center) and stored energy (bottom) during loading (right) and unloading (left) of the latent heat storage. 5. OPERATIONAL RESULTS At the beginning, the performance of the storage was determined in standalone tests. A total of 70 charge and discharge cycles were completed. The evaluation of the recorded data showed that the storage achieves the design storage capacity of 120 kWh. Figure 4 shows the temperature-time curves, the power and the stored energy of the two modules during loading and unloading. The internal storage temperatures (“storage 1”, “storage 2”) clearly show the effect of the latent heat in the temperature range of 27 – 29 °C where the PCM melts and solidifies, respectively. The measured power at charging with a supply temperature of 36 °C was 11 kW, which is better than the initial thermal design value of 10 kW. At discharge with a supply temperature of 22 °C the power was about 10 kW. During the 70 cycles, no degradation of the storage capacity was observed. After integration of the storage into the new system for solar heating and cooling at the ZAE Bayern in fall 2007, the performance of the system was monitored during operation. During the heating period 2007/2008 a significant increase of the solar gain due to the low temperatures in the system has been observed. Further on it has been proven that this storage temperature is sufficient for integration into the building heating system, allowing for substantial contribution to the overall heat supply throughout the heating period. In January e.g. the solar fraction for heating reached 23 %, rising to 74 % in March, as a consequence of increased solar gains and lower heating load of the building. In Figure 5 a typical day (10th Feb. 2008) for heating is shown. During daytime the heat demand is low, so first the solar collectors can heat the building directly and second the latent heat storage can be loaded. During nighttime the heat demand is higher and it can be seen, that the stored low temperature heat can be feed into the heating system. power [kW] 15 heat [kWh] unloading 14 loading unloading 140 13 120 12 11 100 10 9 8 6 80 stored heat 7 total heat demand 60 5 40 4 3 2 1 PCM storage output 0 0:00 2:00 4:00 solar heat directly used for heating 6:00 8:00 10:00 12:00 14:00 16:00 PCM storage output 20 time [hh:mm] 18:00 20:00 22:00 0 0:00 Figure 5: Typical day for heating (outside temperature: -2 °C to + 5 °C; 10 Feb. 2008). During loading about 80 kWh are stored. For solar cooling the system is designed to provide chilled water at 15/18 °C operated with moderate driving temperatures and dry air cooling even at high ambient temperatures. Below 26.3 °C ambient temperature the capacity of the dry air cooler is sufficient to completely cool the chiller. At increasing ambient temperatures more and more reject heat has to be stored in the latent heat storage. As shown in Figure 6 for the cooling season 2008 lasting from April to September, the latent heat storage had to support the dry air cooler only on 43 days. With minimum night time temperatures permanently below 20 °C, no limitations for the unloading of the latent heat storage have been experienced. ambient temperature / °C 35,0 2008 PCM storage supports dry air cooler 30,0 daytime 26,3 25,0 15,0 10,0 5,0 unloading PCM storage possible 20,0 nighttime minimum date / dd.mm. 09.09. 02.09. 26.08. 19.08. 12.08. 05.08. 29.07. 22.07. 15.07. 08.07. 01.07. 24.06. 17.06. 10.06. 03.06. 27.05. 20.05. 13.05. 06.05. 29.04. 22.04. 15.04. 0,0 Figure 6: Daytime maximum and nighttime minimum temperature during the cooling season 2008. Figure 7 shows typical temperature and capacity charts of the reject heat loop of the chiller during a hot day with 30 °C ambient air temperature. After a start-up phase the absorption chiller continuously provides at least 10 kW chilled water capacity which results in about 24 kW reject heat. At moderate ambient temperatures the dominating part of the heat rejection is accomplished via the dry air cooler, but during hot ambient conditions like here up to 50 % of the daily reject heat load is covered by the latent heat storage. During the nighttime the lower ambient temperatures suffice to regenerate the latent heat storage. Again the dry air cooler serves for the heat transfer to the ambient. 34 32 30 28 ambient temperature 26 24 unloading PCM storage Thunderstorm temperature / °C dry air cooler outlet 36 PCM storage outlet 22 20 2008 Aug 07/08 18 efficient unloading possible 16 chiller in operation 14 9:00 11:00 13:00 15:00 17:00 19:00 21:00 23:00 1:00 time / hh:mm 3:00 5:00 7:00 9:00 unloading PCM storage power / kW 24 20 reject heat chiller 16 12 heat dry air cooler 8 4 heat PCM storage dry air cooler 0 -4 2008 Aug 07/08 PCM storage -8 chiller in operation -12 9:00 11:00 13:00 15:00 17:00 19:00 21:00 23:00 1:00 time / hh:mm 3:00 5:00 7:00 9:00 Figure 7: Temperature and power performance of the reject heat loop during a hot day (max. 30 °C). This day about 34 % of the waste heat was stored. The storage has been for about 750 days in operation and has passed through about 400 loading-/unloading cycles without any problems up to now. 6. CONCLUSIONS By applying a low temperature latent heat storage together with a dry air cooler a substantial improvement of the design of a solar-driven absorption cooling system is accomplished: the reject heat of the sorption chiller is buffered by the heat storage and transferred to the ambient during periods of low ambient temperatures, e.g. night time or off-peak situations. Especially in low capacity applications, the use of a dry instead of a wet cooling tower substantially facilitates the introduction of absorption technology. During the heating season, the PCM storage facilitates low operating temperature of the solar collectors with a positive effect on the solar gain. For the latent heat storage the phase change material calcium chloride hexahydrate (CaCl2x6H2O) with phase transition, i.e. melting and solidification, in the temperature range of 27 to 29 °C is applied. Due to the limited temperature swing available for the given application, the latent heat storage provides a 10 times higher volumetric storage density in comparison to a conventional water heat storage. The latent heat storage provide a capacity of 10 kW and 120 kWh thermal storage content are in good agreement with the thermal design and thus prove the feasibility of the technical concept. It is now operating for about 750 days and 400 loading/unloading cycles without any problems. The latent heat storage supporting the heat rejection of the absorption chiller has been successfully tested. Operational results gained since fall 2007 confirm the general feasibility and the thermal design of the latent heat storage and the overall system. Analysis of system operation and performance will continue until end of 2009. ACKNOWLEDGMENTS The project is supported by funds of the German Federal Ministry of Environment (BMU) under contract number 0329605D. REFERENCES Furukawa, T. (1983): Study on characteristic Temperatures of Absorption Heat Pumps. 20th Japan Heat Transfer Conf. Proceedings, p. 508-510. Hellmann, H.-M., Schweigler, C., Ziegler, F. (1998): A simple method for modelling the operating characteristics of absorption chillers. Seminar Eurotherm, Nancy, France. 6.-7. 7. 1998. Kühn, A., Harm, M., Kohlenbach, P., Petersen, S., Schweigler, C., Ziegler, F.: Betriebsverhalten einer 10 kW Absorptionskälteanlage für die solare Kühlung. Ki Luft- und Kältetechnik, (41. Jahrgang) 7/2005, S. 263-266. Schweigler, C., Costa, A., Högenauer-Lego, M., Harm, M., Ziegler, F.: Absorptionskaltwassersatz zur solaren Kühlung mit 10 kW Kälteleistung. Ki Luft- und Kältetechnik, S. 201-205, 4/2002. Schweigler, C., Dantele, T., Kren, C., Ziegler, F., Clark, D., Fulachier, M.-H., Sahun, J.: Development of a direct-fired partly air-cooled double-effect absorption chiller. Proc. of the 29th International Congress of Refrigeration, Sydney, 19.-24. September 1999. Schweigler, C., Hiebler, S., Kren, C., Mehling, H.: Low temperature Heat Storage for Solar Heating and Cooling Applications. 1st International Conference Solar Air-Conditioning, Oct. 2005, Bad Staffelstein, Germany. Schweigler, C., Hiebler, S., Keil, C., Köbel, H., Kren, C., Mehling, H.: Low temperature Heat Storage for Solar Heating and Cooling Applications. ASHRAE Transactions, ASHRAE Winter-Meeting, Jan. 2007, Dallas, USA. Storkenmaier, F., Schweigler, C., Ziegler, F. (1999): Die charakteristische Gleichung von Sorptionskälteanlagen, Tagungsbericht der Deutschen Klima-Kälte-Tagung 1999, Berlin. Deutscher Kälte- und Klimatechnischer Verein, Stuttgart. Storkenmaier, F., Harm, M., Schweigler, C., Ziegler, F., Kohlenbach, P., Sengewald, T.: Small-capacity LiBr Absorption Chiller for Solar Cooling or Waste-Heat driven Cooling. Proc. of the 30th International Congress of Refrigeration, Sept. 2003, Washington, USA.