Current Transducer LF 1005

advertisement
Current Transducer LF 1005-S/SP16
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 1000 A
16097
Electrical data
Features
IPN
Primary nominal current rms
IPM
Primary current, measuring range @ ± 24 V
R M
Measuring resistance
with ± 15 V
with ± 24 V
ISN
K N
VC
IC
@ ± 1000 A max
@ ± 1200 A max
@ ± 1300 A max
@ ± 1000 A max
@ ± 1800 A max
@ ± 2100 A max
Secondary nominal current rms
Conversion ratio
Supply voltage (± 5 %)
Current consumption
1000
0 .. ± 2100
TA = 70°C TA = 85°C
RM minRM max RM minRM max
0
0
0
0
0
0
21
9
5
60.5
14
4
0
0
18
7
10 58.5
10 12
A
A
Ω
Ω
Ω
Ω
Ω
Ω
200
mA
1 : 5000
± 15 .. 24
V
28 (@ ± 24V) + IS mA
Accuracy - Dynamic performance data
XG
εL
IO
IOM
IOT
Overall accuracy @ IPN, TA = 25°C
± 0.4
Linearity error
< 0.1
Typ Max
Offset current @ IP = 0, TA = 25°C
± 0.4
Magnetic offset current @ IP = 0 and specified RM,
after an overload of 3 x IPN
± 0.2
Temperature variation of IO
- 10°C .. + 70°C
± 0.3 ± 0.4
- 40°C .. + 85°C
± 0.8
t r
di/dt
BW
Response time 1) to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (- 1 dB)
< 1
100
DC .. 150
%
%
mA
mA
mA
mA
µs
A/µs
kHz
General data
TA
TS
RS
m
Note:
Ambient operating temperature Ambient storage temperature
Secondary coil resistance @ TA = 70°C
@ TA = 85°C
Mass
Standards 1)
- 40 .. + 85
°C
- 50 .. + 90
°C
48
Ω
50
Ω
500
g
EN 50178: 1997
●● Closed loop (compensated)
current transducer using the Hall
effect
●● Isolated plastic case recognized
according to UL 94-V0.
Special features
●● IPM = 0 .. ± 2100 A
●● Connection to secondary circuit
on JST B 3P-VH connector.
Advantages
●●
●●
●●
●●
●●
●●
●●
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
●● Current overload capability.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial.
With a di/dt of 100 A/µs.
Page 1/3
090209/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer LF 1005-S/SP16
Isolation characteristics
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
Vw
Impulse withstand voltage 1.2/50 µs
dCp Creepage distance
dCI
Clearance distance CTI
Comparative Tracking Index (Group III a)
3
14.1
Min
17.4
16.6
175
kV
kV
mm
mm
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
●● Over voltage category OV 3
●● Pollution degree PD2
●● Non-uniform field
dCp, dCI, Vw
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
1600 V
1600 V
Reinforced isolation
800 V
800 V
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
090209/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions LF 1005-S/SP16 (in mm. 1 mm = 0.0394 inch)
Bottom view
Front view
Back view
Connection
Top view
Mechanical characteristics
●● General tolerance
●● Transducer fastening
Vertical position
Recommended fastening torque
or
Recommended fastening torque
Recommended fastening torque
●● Transducer fastening
Horizontal position
Recommended fastening torque
or
Recommended fastening torque
●● Primary through-hole
or
●● Connection of secondary
090209/8
Remarks
± 0.5 mm
2 holes Ø 5.3 mm
2 M5 steel screws
4 Nm or 2.96 Lb.-Ft.
4 holes Ø 4.2 mm
4 M4 steel screws
3.2 Nm or 2.37 Lb.-Ft.or
4 holes Ø 2.25 mm,
depth 10 mm
4 x PT KA30
screws long 10 mm
0.9 Nm or 0.66 Lb.-Ft.
●● IS is positive when IP flows in the direction of the arrow.
●● Temperature of the primary conductor should not exceed
100°C.
●● Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
4 holes Ø 5.3 mm
4 M5 steel screws
4 Nm or 2.96 Lb.-Ft.
4 holes Ø 2.25 mm,
depth 16 mm
4 x PT KA30
screws long 16 mm
1 Nm or 0.74 Lb.-Ft.
40.5 x 13 mm
Ø 38 mm
JST B 3P-VH
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 3/3
www.lem.com