DESIGN NOTES GENERAL NOTES D1. GENERAL NOTES MASONRY NOTES LUMBER NOTES G1. M1: ALL STRUCTURAL MASONRY ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CSA STANDARD S304.1 "MASONRY DESIGN FOR BUILDINGS (LIMIT STATES DESIGN)". L1. ALL STRUCTURAL WOOD ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CSA STANDARD 086 "ENGINEERING DESIGN IN WOOD". (INCLUDING SUPPLEMENT CAN/CSA-086S1-05). M2. MASONRY CONSTRUCTION SHALL CONFORM TO CSA STANDARD A371. L2. STRUCTURAL LUMBER (EXCLUDING PRE-FABRICATED TRUSSES AND I-TYPE WOOD JOISTS): NO.2 S-P-F. M3. CONNECTORS SHALL CONFORM TO CSA STANDARD A370. L3. STUDS FOR WALLS: S-P-F STUD GRADE. M4. CONCRETE MASONRY UNITS SHALL BE TYPE H/15/A/M. L4. BRIDGING TO WOOD TRUSSES MUST BE CLEARLY INDICATED ON TRUSS ERECTION DRAWINGS AND BRACE POINTS MARKED ON RELEVANT TRUSS MEMBERS. M5. MORTAR SHALL BE TYPE S. L5. CHECK ALL DIMENSIONS SHOWN ON THE STRUCTURAL DRAWINGS WITH MECHANICAL, ELECTRICAL, AND/OR ANY OTHER RELATED DRAWINGS AND REPORT ANY INCONSISTENCIES TO THE ENGINEER BEFORE PROCEEDING WITH ANY WORK. M6. REFER TO TABLE FOR MASONRY SEISMIC REINFORCING. EXCEPT WHERE SPECIFIED OTHERWISE, NAILING SHALL CONFORM TO TABLES 9.23.3.4 AND 9.23.3.5 OF THE ONTARIO BUILDING CODE. M7. REFER TO ARCHITECTURAL ELEVATIONS FOR CONTROL JOINTS IN MASONRY. L6. G12. READ STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL OTHER CONTRACT DOCUMENTS. M10. GROUT BLOCKS SOLID TWO COURSES BELOW BEAM BEARING PLATES. WOOD TRUSSES AND ENGINEERED WOOD JOISTS SHALL CONFORM TO CSA STANDARD 086.1, INCLUDING SUPPLEMENT CAN/CSA-086S1, AND SHALL BE DESIGNED FOR THE LIVE AND DEAD LOADS INDICATED ON THE STRUCTURAL DRAWINGS. G13. SEE MECHANICAL, AND ELECTRICAL DRAWINGS FOR LOCATIONS OF OPENINGS, PITS, BASES, SUMPS, TRENCHES, SLEEVES, DEPRESSIONS, GROOVES AND CHAMFERS NOT INDICATED ON THE STRUCTURAL DRAWINGS. M11. PROVIDE 2-15M BARS IN CONTINUOUS BOND BEAMS AT FLOOR AND ROOF BEARING LEVELS. L7. M13. ALL CELLS IN MASONRY UNITS CONTAINING REINFORCING OR ANCHORS SHALL BE FILLED SOLID WITH GROUT. PLYWOOD, WAFERBOARD OR STRANDBOARD SHEATHING ATTACHED TO JOISTS, RAFTERS OR STUDS SHALL BE FASTENED WITH 2 " COMMON NAILS AT 150mm (6") CENTRES AT EDGES OF SHEATHING PANELS, AND 300mm (12") CENTRES ELSEWHERE UNLESS NOTED OTHERWISE. L8. NO STRUCTURAL MEMBERS SHALL BE NOTCHED UNLESS APPROVED BY THE STRUCTURAL ENGINEER. M18. CONTROL/EXPANSION JOINTS ABOVE OPENINGS IN WALLS WITH LINTELS SHALL BE OFFSET TO THE END OF THE LINTELS. PROVIDE A SLIP JOINT UNDER ONE END OF LINTEL. L9. BRACING OF WOOD TRUSSES SHALL BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE TRUSS PLATE INSTITUTE (BRACING WOOD TRUSSES: COMMENTARY - AND RECOMMENDATIONS). ANCHORAGE OF BRACING MEMBERS SHALL BE THE RESPONSIBILITY OF THE TRUSS MANUFACTURER. THE STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF THE 2006 ONTARIO BUILDING CODE. G2. D2. THE STRUCTURE HAS BEEN DESIGNED AS A BUILDING OF POST DISASTER IMPORTANCE IN ACCORDANCE WITH CLAUSE 4.1.2.1.3. D3. IMPORTANCE FACTORS G9. SPECIFIED LOAD IMPORTANCE FACTOR SNOW, Is 1.25 WIND, Iw 1.25 SEISMIC, Ie 1.50 G10. ULS G14. D4. LATERAL DESIGN LOADS WIND LOADS G15. STANDARD DETAILS THAT ARE PROVIDED WITH THESE PLANS ARE PROVIDED TO ILLUSTRATE A SPECIFIC DETAIL OR CONSTRUCTION CONCEPT. THEY WERE NOT DRAWN SPECIFICALLY FOR THIS PROJECT AND MAY SHOW BACKGROUND DETAILS THAT ARE NOT IDENTICAL TO THIS PROJECT. WHERE A DISCREPANCY EXISTS BETWEEN THE PLANS, DETAILS, SCHEDULES, TABLES AND/OR SPECIFICATIONS, THE MOST STRINGENT REQUIREMENT SHALL APPLY. ALL SUCH DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER PRIOR TO PROCEEDING WITH THE WORK. ALL WORK SHALL COMPLY WITH THE CURRENT ONTARIO BUILDING CODE AND ALL GOVERNING STANDARDS & REGULATIONS. CLARIFY WITH THE ENGINEER ANY QUERIES REGARDING INTERPRETATION OF THE DRAWINGS BEFORE PROCEEDING WITH ANY WORK. THE CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND SHALL REPORT ANY DISCREPANCY TO THE ENGINEER BEFORE PROCEEDING WITH ANY WORK. THE STRUCTURE HAS BEEN DESIGNED TO SAFELY RESIST THE 1 50 AVERAGE HOURLY WIND PRESSURE IN ACCORDANCE WITH THE 2006 ONTARIO BUILDING CODE. THE DESIGN PARAMETERS FOR THE WIND LOADS ARE AS NOTED BELOW: M19. STACK BOND SHALL NOT BE USED WITHOUT THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. M23. ALL MORTAR JOINTS IN CONCRETE BLOCK WORK SHALL BE TOOLED CONCAVE TYPE. L10. WOOD TRUSSES MUST BE DESIGNED FOR THE LOADS INDICATED ON THE DRAWINGS. USE OF LOADS OTHER THAN THOSE SPECIFIED MUST BE AUTHORIZED BY THE STRUCTURAL ENGINEER. LESS THAN 6mm NOR MORE THAN 20mm. L12. PROVIDE EDGE SUPPORT FOR SHEATHING CONSISTING OF NOT LESS THAN 38mmx38mm (2"x2") BLOCKING SECURELY NAILED BETWEEN FRAMING MEMBERS, OR TONGUE AND GROOVE EDGE JOINT. MORTAR & GROUT FOR UNIT MASONRY SHALL CONFORM TO THE REQUIREMENTS OF CSA STANDARD A179-M. L13. WOOD TRUSS CONNECTIONS TO SUPPORTING MEMBERS SHALL PROVIDE ADEQUATE RESISTANCE AGAINST UPLIFT FORCES AND SHALL PROVIDE LATERAL RESTRAINT TO THE SUPPORT. SUCH CONNECTIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. L14. TRUSSES MUST BE DESIGNED FOR THE BEARING LENGTH AVAILABLE ON WALLS, LINTELS AND BEAMS. L15. SUBMIT SHOP DRAWINGS OF ALL WOOD TRUSSES INDICATING DESIGN LOADS, BEARING LENGTHS, AND ARRANGEMENT OF WEBS. SHOP DRAWINGS MUST ALSO INCLUDE AN ERECTION DIAGRAM SHOWING LOCATION AND MARKS OF TRUSSES, SPACING, BRIDGING, BRACING, AND ANCHORAGE OF THE BRACING AND BRIDGING. LOADS MUST BE CLEARLY INDICATED ON THE ERECTION DRAWINGS INCLUDING SNOW ACCUMULATIONS AND CONCENTRATED LOADS FROM CONVENTIONAL FRAMING MEMBERS WHICH ARE SUPPORTED ON THE TRUSSES. ERECTION DRAWINGS MUST SHOW THE BEARING CONDITIONS FOR THE TRUSSES, INCLUDING METAL HANGERS WHERE REQUIRED. ALL SHOP DRAWINGS, INCLUDING ERECTION DIAGRAMS, MUST BE CERTIFIED BY A QUALIFIED PROFESSIONAL ENGINEER LICENSED IN THE PROVINCE OF ONTARIO. L16. CONNECTIONS OF WOOD TRUSSES TO ONE ANOTHER AND CONNECTIONS BETWEEN WOOD TRUSSES AND OTHER STRUCTURAL MEMBERS SUPPORTED BY THE TRUSSES ARE THE RESPONSIBILITY OF THE TRUSS MANUFACTURER AND SHALL BE CLEARLY DETAILED ON THE SHOP DRAWINGS. L17. WHERE TRUSSES ARE DESIGNED FOR UNBALANCED LOADING IN ACCORDANCE WITH OBC 4.1.6.2.(8), ALL LOAD VALUES USED MUST BE CLEARLY INDICATED ON THE SHOP DRAWINGS. L18. WALL PLATES IN STUD WALLS SHALL CONFORM TO CLAUSE 9.23.11 OF THE ONTARIO BUILDING CODE. L22. PROVIDE WOOD NAILERS ON TOP FLANGE OF STEEL BEAMS WHERE REQUIRED. NAILER WIDTH SHALL M24. q50=0.32 kPa 1 50 HOURLY DESIGN WIND PRESSURE FOUNDATION NOTES Ce, Cg, Cp & Cpi HAVE BEEN CALCULATED IN ACCORDANCE WITH THE "USER'S GUIDE-NBC 2010 STRUCTURAL COMMENTARIES (PART 4 DIVISION B). M26. F2. FOOTINGS SHALL BE CARRIED DOWN TO UNDISTURBED SOIL OR COMPACTED ENGINEERED FILL HAVING A MINIMUM FACTORED BEARING RESISTANCE AT ULTIMATE LIMIT STATES OF 150 kPa AND AT SERVICEABILITY LIMIT STATES OF 60 kPa. M27. GROUT NOT PLACED WITHIN 1 DISCARDED. THE LINE OF SLOPE BETWEEN ADJACENT FOOTINGS OR EXCAVATIONS OR ALONG STEPPED FOOTINGS SHALL NOT EXCEED A RISE OF 7 IN A RUN OF 10. M31. PROVIDE MASONRY TIES TO BACKUP AT FIRST BED JOINT ABOVE TOP OF LINTELS. F15. PROVIDE TEMPORARY FROST PROTECTION, DURING CONSTRUCTION, FOR ALL FOOTINGS. M32. F16. FOUND EXTERIOR FOOTINGS AND OTHER FOOTINGS SUSCEPTIBLE TO DAMAGE RESULTING FROM FROST ACTION A MINIMUM 4'-0" (1200mm) BELOW FINISHED GRADE IF NOT NOTED TO BE FOUNDED LOWER. F17. PROTECT SOIL FROM FREEZING, ADJACENT TO AND BELOW ALL FOOTINGS. ALL MASONRY BEAMS AND LINTELS SHALL BE GROUTED SOLID WITH FINE GROUT IN ONE CONTINUOUS POUR OVER THE FULL HEIGHT AND LENGTH OF THE BEAM. GROUT SHALL CONFORM TO CSA STANDARD A179. REINFORCING BARS SHALL BE POSITIONED AND SECURELY HELD 6mm CLEAR ABOVE THE BOTTOM SURFACE OF THE FORMED CHANNEL IN THE LINTEL BLOCK UNIT. FOR BEAMS GREATER THAN ONE COURSE HIGH, FILL ALL FROGGED ENDS SOLID WITH GROUT AND ENSURE THAT NO VOIDS, GAPS OR AIR POCKETS ARE LEFT. F19. REMOVE ALL TOPSOIL AND ORGANIC MATERIAL FROM BUILDING SITE AND REPLACE WITH COMPACTED GRANULAR B. M33. ADHESIVE ANCHORS SHALL BE BONDED TO MASONRY ELEMENTS USING HILTI HY70 ADHESIVE (OR APPROVED EQUIVALENT) COMPLETE w/SCREEN TUBES WHERE REQUIRED, IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS. THIS STRUCTURE HAS BEEN DESIGNED USING THE INTERNAL PRESSURE COEFFICIENTS "C pi" FOR A CATEGORY 3 STRUCTURE. D5. F11. SEISMIC LOADS SEISMIC DESIGN CRITERIA, 2006 OBC ITEM 1 OBC REFERENCE PROJECT LOCATION: NORTHBROOK, ONTARIO N/A SEISMIC DATA: Sa(0.2)=0.276 S(0.2)=0.356 Sa(0.5)=0.153 S(0.5)=0.214 Sa(1.0)=0.076 S(1.0)=0.106 Sa(2.0)=0.024 S(2.0)=0.034 SOURCE: CANADIAN HAZARDS INFORMATION SERVICE. REFER TO GEOTECHNICAL REPORT. 2 F20. ALL FOOTINGS ARE CENTRED UNDER WALLS AND COLUMNS UNLESS NOTED OTHERWISE. F21. FIELD MEASUREMENTS OF FOUNDING ELEVATIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR IN CONSULTATION WITH THE GEOTECHNICAL ENGINEER. F23: REFER TO GEOTECHNICAL REPORT #T030815-A1 PREPARED BY INSPEC-SOL FOR SITE PREPARATION REQUIREMENTS & ADDITIONAL GEOTECHNICAL INFORMATION. PGA = 0.141 SITE CLASS: SITE CLASS D 3 4 5 SOURCE: INSPEC-SOL REPORT T030815-A1. IMPORTANCE FACTOR: POST DISASTER Ie = 1.5 (ULS) CLAUSE 4.1.8.5 TABLE 4.1.8.5 IeFaSa(0.2) SEISMIC HAZARD INDEX 0.534 CLAUSE 4.1.8.4.6 M35. PROVIDE BOND BEAM REINFORCED w/1-15M ABOVE & BELOW ALL OPENINGS UNLESS NOTED OTHERWISE. M36. UNLESS NOTED OTHERWISE, ALL LAP SPLICES IN MASONRY REINFORCEMENT TO BE CLASS "B". M37. PROVIDE HORIZONTAL JOINT REINFORCEMENT IN THE FIRST & SECOND BED JOINTS IMMEDIATELY ABOVE & BELOW WALL OPENINGS. EXTEND REINFORCEMENT NOT LESS THAN 600MM (24") PAST EACH SIDE OF THE OPENING, BUT DO NOT EXTEND THROUGH CONTROL JOINTS UNLESS NOTED OTHERWISE. 3 M39. 6 IeFvSa(1.0) 0.160 TABLE 4.1.8.6 IRREGULARITY REVIEW 7 8 9 10 11 12 TABLE 4.18.9 OBC N/A N/A N/A N/A N/A N/A N/A NO STRUCTURAL CONFIGURATION REGULAR CLAUSE 4.1.8.6 METHOD OF ANALYSIS EQUIVALENT STATIC FORCE PROCEDURE CLAUSE 4.1.8.7.(c) SEISMIC FORCE RESISTING SYSTEM: NORTH-SOUTH DIRECTION LIMITED DUCTILITY STEEL MOMENT FRAMES & NAILED WOOD-BASED PANEL SHEAR WALLS Rd=2.0 Ro=1.3 RdRo=2.6 TABLE 4.1.8.9 CSA S16-01 CLAUSE 27.4 CSA 086-01 MODERATELY DUCTILE MASONRY SHEAR WALLS & NAILED WOOD-BASED PANEL SHEAR WALLS Rd=2.0 Ro=1.5 RdRo=3.0 TABLE 4.1.8.9 CSA S304.1-04 CLAUSE 4.6.5 CSA 086-01 MOMENT RESISTING FRAMES CONVENTIONAL CONSTRUCTION Rd=1.5 Ro=1.3 RdRo=1.95 TABLE 4.1.8.9 CSA S16.1-01 CLAUSES 27.10.1 WOOD BASED PANEL DESIGNED NOT TO YIELD. CSA 086-09 CLAUSE 9.8 OBC 4.1.8.15 SEISMIC FORCE RESISTING SYSTEM: EAST-WEST DIRECTION SEISMIC FORCE RESISTING SYSTEM: UPPER ROOF - TRANSIT FACILITY N-S CLEANING BAY ADDITION SFRS DIAPHRAGM & CONNECTIONS: 13 C2. C8. 14 FOUNDATION SFRS Rd=1.0, Ro = 1.0 OBC 4.1.8.16 Fa = 1.29 TABLE 4.1.8.4.B 15 ACCELERATION BASED SITE COEFFICIENT 16 VELOCITY BASED SITE COEFFICIENT Fv = 1.4 HIGHER MODE FACTOR Mv = 1.0 17 CONCRETE SHALL BE MIXED, PLACED & CURED IN ACCORDANCE WITH CSA STANDARD A23.1 "CONCRETE MATERIALS AND METHODS OF CONCRETE CONSTRUCTION". THE MAXIMUM NOMINAL AGGREGATE SIZE FOR CONCRETE SHALL BE 20mm ( S1. ALL STRUCTURAL STEEL ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CSA STANDARD CAN/CSA-S16 "LIMIT STATES DESIGN OF STEEL STRUCTURES". S4. STRUCTURAL STEEL: CSA G40.21 300W (44W) EXCEPT W SECTIONS: CSA G40.21 350W (50W) HSS MEMBERS: CSA G40.21 350W (50W) CLASS C OR ASTM A500 GRADE C ANCHOR BOLTS: ASTM A307 CF SECTIONS: ASTM A570M GRADE 350W (50W) C14. REINFORCING STEEL SHALL CONFORM TO CSA STANDARD G30.18 GRADE 400 (GRADE 60). C15. REINFORCING WORK SHALL BE CARRIED OUT IN ACCORDANCE WITH CAN/CSA - A23.1, CSA W186 AND REINFORCING STEEL - MANUAL OF STANDARD PRACTICE. C16. UNLESS NOTED OTHERWISE, ALL LAP SPLICES IN CONCRETE REINFORCEMENT TO BE CLASS "B". C18. PROVIDE DOWELS TO WALLS AND COLUMNS SIMILAR IN NUMBER, SIZE, AND SPACING TO THE VERTICAL STEEL IN THE WALL OR COLUMN ABOVE UNLESS OTHERWISE NOTED OR SHOWN. C19. WELDING OF REINFORCEMENT SHALL CONFORM TO THE REQUIREMENTS OF CSA STANDARD W186. C20. HOOKS AND BENDS IN REINFORCEMENT SHALL BE AS DEFINED IN CSA STANDARD CAN/CSA-A23.1. C21. BAR LENGTHS INDICATED ON PLAN DO NOT INCLUDE LENGTH OF BENDS OR HOOKS. C22. PLACING DIAGRAMS FOR REINFORCING STEEL SHALL BE SUBMITTED IN TRIPLICATE FOR REVIEW BY THE ENGINEER PRIOR TO FABRICATION. C23. WELDED STEEL WIRE FABRIC: CSA G30.5 C24. WELDED WIRE MESH SHALL BE INSTALLED AND SECURELY SUPPORTED BY SPACERS CONFORMING TO CAN/CSA - A23.1 AT THE SPECIFIED ELEVATION BEFORE THE CONCRETE IS PLACED. PLACING THE REINFORCING AT THE BOTTOM OF THE SLAB AND LIFTING IT AS THE CONCRETE IS PLACED WILL NOT BE PERMITTED. S15. WELDING SHALL CONFORM TO THE REQUIREMENTS OF CSA STANDARD W59 AND CSA STANDARD S16. S23. THE FABRICATOR OR CONTRACTOR UNDERTAKING WELDING WORK SHALL BE CERTIFIED BY THE CANADIAN WELDING BUREAU AS BEING QUALIFIED UNDER REQUIREMENTS OF CSA STANDARD W-47.1, CERTIFICATION OF COMPANIES FOR FUSION WELDING OF STEEL STRUCTURES DIVISION 2.1. J = 1.0 TABLE 4.1.8.11 19 BASE SHEAR NORTH - SOUTH DIRECTION V=0.14W TABLE 4.1.8.11 20 BASE SHEAR EAST - WEST DIRECTION V=0.12W TABLE 4.1.8.11 C29. S24. UNLESS OTHERWISE SPECIFIED, SHOP PAINT AND SURFACE PREPARATION FOR PAINTING SHALL CONFORM TO CAN/CGSB - 85.10. S25. STEEL SURFACES IN CONTACT WITH CONNECTIONS DESIGNATED AS FRICTION TYPE, CONCRETE OR TOP SURFACES OF BEAMS CARRYING MASONRY, SHALL NOT BE PAINTED. S37. WHERE MOMENT CONNECTIONS ARE CALLED FOR BUT VALUES ARE NOT INDICATED, DESIGN CONNECTIONS FOR THE FULL MOMENT CAPACITY OF THE SMALLER MEMBER JOINED. S38. PROVIDE ALL ANCHOR BOLTS, CAST IN PLATES WITH ANCHORS, AND ANCHORS REQUIRED TO CONNECT STRUCTURAL STEEL TO CAST-IN-PLACE CONCRETE. S40. THE CONNECTIONS OF THE TENSION-ONLY BRACING & MOMENT CONNECTIONS SHALL BE DESIGNED TO SAFELY RESIST GRAVITY LOADS COMBINED WITH THE FACTORED SEISMIC LOADS INDICATED ON THIS PLAN & THE BUILDING ELEVATIONS. THE SEISMIC LOADS HAVE BEEN AMPLIFIED BY R d=1.5. AT SPLICES IN WELDED WIRE MESH, THE LENGTH OF OVERLAP MEASURED BETWEEN THE OUTERMOST CROSS WIRES OF EACH SHEET SHALL BE NOT LESS THAN ONE SPACING OF CROSS WIRES PLUS TWO INCHES (50mm). PLACE 200mm MINIMUM GRANULAR 'A' UNDER SLABS ON GRADE. COMPACT TO 100% STANDARD PROCTOR MAXIMUM DRY DENSITY. C33. CHAIRS, BOLSTERS, BAR SUPPORTS AND SPACERS FOR REINFORCING SHALL CONFORM TO CAN/CSA A23.1. C37. PROVIDE 2-15M AROUND ALL OPENINGS IN CONCRETE WALLS EXTENDING A MINIMUM OF 600mm (2'-0') BEYOND THE CORNERS OF THE OPENINGS. C38. PROVIDE VERTICAL CONTROL JOINTS AT 6096mm (10'-0") o.c. MAXIMUM IN WALLS HAVING OPENINGS AND AT 7620mm (25'-0") o.c. MAXIMUM FOR WALLS HAVING NO OPENINGS, OR OTHERWISE NOTED ON PLANS. TRUSS ABBREVATIONS SCHEDULE E.W.J. - ENGINEERED WOOD JOISTS DESIGNED BY OTHERS E.W.G.T. - ENGINEERED WOOD GIRDER TRUSS DESIGNED BY OTHERS E.W.H.T. ADHESIVE ANCHORS SHALL BE BONDED TO CONCRETE ELEMENTS USING HILTI HY150 INJECTION ADHESIVE (OR APPROVED EQUIVALENT) IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. L31. THE DESIGN OF THE LATERAL BRACING FOR PRE-FABRICATED ROOF TRUSS WEB MEMBERS AND ITS ANCHORAGE IS THE SOLE RESPONSIBILITY OF THE TRUSS SUPPLIER. SHOP DRAWINGS, STAMPED BY A PROFESSIONAL ENGINEER, INDICATING ALL LATERAL BRACING REQUIREMENTS SHALL BE SUBMITTED FOR REVIEW. AT THE ROOF TRUSS SUPPLIER'S DISCRETION, T-BRACING MAYBE USED AS AN ALTERNATIVE TO HORIZONTAL LATERAL WEB BRACING. L35. ALL LOAD BEARING WOOD STUD WALLS SHALL BE SHEATHED OR TEMPORARILY LATERALLY BRACED @ 2'-0" o.c. VERTICALLY PRIOR TO SUPPORTING ANY SUPERIMPOSED CONSTRUCTION LOADS. L37: STRUCTURAL COMPOSITE LUMBER (SCL) SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES: 2.0 E LVL LSL 1.7 E 2.0 E PSL L38. MODULUS BENDING SHEAR OF STRENGTH STRENGTH GRADE ELASTICITY MPa (psi) MPa (psi) MPa (psi) 13800 (2.0x106) COMPRESSIVE STRENGTH PERPENDICULAR TO GRAIN MPa (psi) 37.0 (5366) 3.70 (537) 9.40 (1363) 6 33.15 (4805) 5.15 (745) 11.05 (1600) 6 37.0 (5366) 3.70 (537) 9.40 (1363) 11720 (1.7x10 ) 13800 (2.0x10 ) FASTENERS FOR SIMPSON CONNECTORS SHALL CONFORM TO MANUFACTURER'S SPECIFICATIONS. NOTES 1. NAIL ROOF SHEATHING TO BLOCKING WITH 4.88 DIA. x 102mm Lg. NAILS AT 66mm MAX o.c. 2. NAIL WALL SHEATHING TO BLOCKING WITH 4.88 DIA. x 102mm Lg. NAILS AT 66mm MAX o.c. 3. 12.5 mm PLYWOOD SHEATHING NAILED TO VERTICAL SUPPORTS WITH 3.66 NAILS AT 100mm MAX. o.c. 4. NAIL WALL SHEATHING TO SILL PLATE WITH 4.88 DIA. x 102mm Lg. NAILS AT 66mm MAX o.c. 5. ANCHOR SILL TO TOP OF MASONRY WALL WITH 16 DIA. ANCHOR BOLTS x 500 Lg. AT 580 o.c. 6. REFER TO SHEAR BLOCKING SCHEDULE FOR FASTENING. 7. REFER TO SHEAR BLOCKING SCHEDULE FOR FASTENING. 8. ANCHOR SILL TO TOP OF MASONRY WALL WITH 16 DIA. ANCHOR BOLTS x 500 Lg. AT 580 o.c. - TYPICAL - ENGINEERED WOOD HIP TRUSS DESIGNED BY OTHERS E.W.M.T. - ENGINEERED WOOD MONO TRUSSES DESIGNED BY OTHERS E.W.T. C45. MULTIPLE PLY LAMINATED VENEER LUMBER (LVL) BEAMS SHALL BE FASTENED TOGETHER IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS. DO NOT CUT OR NOTCH. TYPE TABLE 4.1.8.11 BASE OVERTURNING REDUCTION FACTOR L30. PROVIDE MASONRY ANCHORS AT 1000mm (40") MAXIMUM o.c. ON ALL COLUMNS ADJACENT TO MASONRY. S22. 8 o.c. (2'-0") STAGGERED ON EACH SIDE OF BEAM WEB. STEEL NOTES "). CALCIUM CHLORIDE MUST NOT BE USED. C25. TYPE S BASED ON PROPORTION SPECIFICATIONS, OR 13.3 MPa BASED ON PROPERTY SPECIFICATIONS. ALL STRUCTURAL CONCRETE ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CSA STANDARD CAN/CSA A23.3 "DESIGN OF CONCRETE STRUCTURES". C11. TABLE 4.1.8.4.C 18 GROUT FOR UNIT MASONRY: CONCRETE NOTES C1. (1) VERTICAL STIFFNESS (2) MASS IRREGULARITY (3) VERTICAL GEOMETRY IRREGULARITY (4) INPLANE DISCONTINUITY IN V.L.F.R.E. (5) OUT OF PLANE OFFSETS (6) WEAK STOREY (7) TORSIONAL SENSITIVITY (8) NON-ORTHOGANAL HOURS AFTER WATER IS FIRST ADDED TO THE BATCH SHALL BE - ENGINEERED WOOD TRUSSES DESIGNED BY OTHERS PROPANE TANK BASE SLAB 3350 x 1300 x 200mm CONCRETE PAD WITH 10M @ 250 E.W. AT MID-DEPTH OF SLAB. PLACE SLAB ON 200mm MIN. GRANULAR 'A' COMPACTED TO 100% S.P.M.D.D. 12/08/30 FOUNDATION SCHEDULE ABBREVIATIONS MASONRY WALL MINIMUM SEISMIC REINFORCING CONCRETE COVER FOR REINFORCEMENT EXCEPT AS NOTED OTHERWISE = = = = = ANCHOR BOLT ADJUSTABLE ALTERNATE ARCHITECTURAL ANCHOR B BLDG. BM = = = = = BOTTOM BUILDING BEAM BASE OR BEARING PLATE BASEMENT = = = COL. = CONC. CONSTR. = = CONT. CENTRE TO CENTRE CENTRE LINE COLUMN CONCRETE CONSTRUCTION CONTINUOUS BSMT. C/C DET. DIAG. DIM. D.L. DWG. DWL. = = = = = = = DETAIL DIAGONAL DIAMETER DIMENSION DEAD LOAD DRAWING DOWEL EA. E.F. E.W. ELEV. E-W EXIST. EXP. J. EXT. = = = = = = = = EACH EACH FACE EACH WAY ELEVATION EAST - WEST EXISTING EXPANSION JOINT EXTERIOR F.F. FDN. FIN. FL. FTG. FT. = = = = = = FAR FACE FOUNDATION FINISHED FLOOR FOOTING FOOT, FEET PIER/PEDESTAL LSSJ LLV LLH = = = LONG SPAN STEEL JOIST LONG LEG VERTICAL LONG LEG HORIZONTAL kN kPa K = = = KILONEWTON KILOPASCAL KIP, KIPS MAX. MECH. MEZZ. = = = MAXIMUM MECHANICAL MEZZANINE MIN. MISC. ML mm = = = = MINIMUM MISCELLANEOUS MIDDLE LAYER MILLIMETRE N.F. N-S NTS = = = NEAR FACE NORTH - SOUTH NOT TO SCALE O.C. OPG. OWSJ O.F. = = = = ON CENTRES, CENTRE TO CENTRE OPENING OPEN WEB STEEL JOIST OUTSIDE FACE PART. PLF PSF PSI PROJ. = = = = = = PARTITION PLATE POUNDS PER LINEAL FOOT POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PROJECTION RAD. REF. REINF. REQ'D. REV. = = = = = RADIUS REFERENCE REINFORCING REQUIRED REVISION, REVISED SECT. SL. SPEC'S. STD. = = = = SECTION SLAB SPECIFICATIONS STANDARD T TEMP TYP. = = = TOP TEMPERATURE TYPICAL MARK SIZE (mm) F1 370x370 HORIZ. = HORIZONTAL UL U/S U.N.O. = = = UPPER LAYER UNDERSIDE UNLESS NOTED OTHERWISE INT. I.F. = = INTERIOR INSIDE FACE VERT. = VERTICAL LLBB LL L.L. = = = LONG LEG BACK TO BACK LOWER LAYER LIVE LOAD W.W. w/ = = WELDED WIRE WITH 2000x2000 250 5-15M E.W. F3 480x580 8-15M 10M @ 250 2000x2000 250 5-15M E.W. 6-15M 10M @ 250 2000x2000 250 5-15M E.W. 480x400 MARK REINFORCEMENT MARK 190 CENTRE FOOTING UNDER STEEL COLUMN HORIZONTAL REINFORCING THICKNESS ENDS 240 1-20M 290 INTERMEDIATE 20M @ 1200mm o.c. 1-20M 1-20M + 1-15M @ 2400 mm o.c. MAX. + 1-15M IN BOND BEAM ABOVE & BELOW WINDOWS GROUT ALL CORES SOLID FULL HEIGHT GROUT CORES SOLID TO 1800mm ABOVE THE TOP OF THE FOUNDATION WALL SHEAR BLOCKING NAILS LOCATION (GRID LINE) 1-10M SPACING SIMPSON MODEL No. MAXIMUM SPACING A35 300 68 LINE 8 DETAIL SIZE 44 A35 390 45M 75 mm 75 mm 90 mm 55M 75 mm 75 mm 110 mm 25M & SMALLER 40 mm 40 mm 60 mm 30M 40 mm 45 mm 60 mm 35M 40 mm 55 mm 70 mm 45M 45 mm 70 mm 90 mm 55M 55 mm 85 mm 110 mm 25M & SMALLER 30 mm 40 mm 60 mm 1. HORIZONTAL REINFORCEMENT CONSISTS OF 2-WIRE TRUSS OR LADDER TYPE. 30M 30 mm 45 mm 60 mm 35M 35 mm 55 mm 70 mm 2. PROVIDE MINIMUM CLASS B LAP FOR JOINT REINFORCEMENT U.N.O. DETAIL REINFORCEMENT IN ACCORDANCE WITH CSA S304.1. 45M 45 mm 70 mm 90 mm 55M 55 mm 85 mm 110 mm 20M & SMALLER 20 mm 40 mm 60 mm 25M 25 mm 40 mm 60 mm 30M 30 mm 45 mm 60 mm 35M 35 mm 55 mm 70 mm 45M 45 mm 70 mm 90 mm 55M 55 mm 85 mm 110 mm 300 APPLICABLE IN SEPARATE PRICE CONFIGURATION ONLY 44 A35 300 LINE D 44 A35 300 LINE E 44 A35 300 LINE B 68 A35 300 140 mm 15M @ 800 190 mm 20M @ 1200 240 mm 2-15M @ 1200 290 mm 25M @ 1200 LINE G 68 A35 300 MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS SLUMP AT TIME 3 & POINT OF DISCHARGE 10M @ 1200 10M @ 1200 + 1-10M @ 2400 MAX. 10M @ 1200 + 1-15M @ 2400 MAX. 15M @ 1200 + 2-15M @ 2400 MAX. NOTES: 3. THIS TABLE APPLIES IN CASES WHERE THE SEISMIC HAZARD INDEX, I EFaSa(0.2), IS GREATER THAN OR EQUAL TO 0.35, BUT NOT MORE THAN 0.75. 4. THE REINFORCEMENT SHOWN HERE IS THE MINIMUM TO BE PROVIDED - REFER TO STRUCTURAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 5. PROVIDE A MINIMUM OF 2-15M CONTINUOUS IN A GROUT-FILLED BOND BEAM AT THE TOP AND BOTTOM OF ALL 290mm THICK WALL PANELS AND 1-15M CONTINUOUS FOR ALL OTHER WALL THICKNESSES, AND 1-15M VERTICAL CONTINUOUS AT ALL DISCONTINUOUS WALL ENDS AND CORNERS. SIZE BEARING REMARKS EXPOSURE CLASS L1 3-38x184 76mm ADD L 102x89x7.9 LLV GALV. AT MASONRY VENEER ADD L 89x89x6.4 GALV. AT MASONRY VENEER FOOTINGS / INTERIOR COLUMN PIERS 25 MPa N L2 2-38x184 38mm FOUNDATION WALLS / EXTERIOR COLUMN PIERS 25 MPa F-2 L3 2-38x184 76mm GRADE BEAMS 30 MPa F-2 L4 2-38x184 76mm 35 MPa C-1 L5 W200x27 220x7.9 PLATE L6 W200x27 220x7.9 PLATE PAVEMENTS, SIDEWALKS, NON-REINFORCED STAIR, CURBS AND GUTTERS. 32 MPa C-2 REINFORCED STAIRS AND SLABS 35 MPa C-1 COLUMNS AND BEAMS 30 MPa F-2 28 MPa N SLABS ON STEEL DECK 30 MPa N SUSPENDED GARAGE FLOORS 35 MPa C-1 GARAGE FLOOR SLABS ON GRADE2 32 MPa C-2 COLUMNS, WALLS & BEAMS 30 MPa N SUSPENDED CONCRETE STAIRS AND SLABS 30 MPa N HOUSEKEEPING PADS 35 MPa N 2 x 400mm Lg. @ 600mm o.c. L7 2- L 152x102x7.9 200mm L8 MB241 200mm L9 MB241 200mm L10 MB242 200mm CONNECT NORTH END TO STEEL COLUMN. FILL BLOCKS SOLID FULL HEIGHT BELOW BEARING AT SOUTH END NOTES: - PROVIDE MINIMUM 200mm BEARING FOR ALL LINTELS SUPPORTING MASONRY UNLESS NOTED OTHERWISE. - ALL LOOSE LINTELS SUPPORTING MASONRY VENEER TO BE GALVANIZED. 1. PROPORTION CAST IN PLACE CONCRETE IN ACCORDANCE WITH THE PROPERTIES GIVEN ABOVE, UNLESS NOTED OTHERWISE ON THE DRAWINGS. 5. BEAMS GREATER THAN ONE COURSE HIGH MUST BE LAID WITH 50% RUNNING BOND. DO NOT USE STACK BOND. 2. INTERIOR SLABS ON GRADE SHALL HAVE A MAXIMUM NOMINAL COARSE AGGREGATE SIZE OF 20mm AND A MINIMUM CEMENT CONTENT OF 320 kg PER CUBIC METRE. 6. GROUT BEAMS SOLID WITH FINE GROUT IN ONE CONTINUOUS POUR OVER THE FULL HEIGHT AND LENGTH OF THE BEAM. REINFORCING BARS & WIRES SHALL BE POSITIONED & SECURELY HELD AT THE COVER DISTANCES SPECIFIED. 3. THE SLUMP SPECIFIED ABOVE IS THE SLUMP SPECIFIED BEFORE THE ADDITION OF ANY SUPERPLASTICIZING ADMIXTURES. 7. FILL ALL VOIDS, INCLUDING FROGGED ENDS, SOLID WITH GROUT. ENSURE THAT NO VOIDS, GAPS OR AIR POCKETS ARE LEFT. 8. CLEAR DISTANCES ARE GIVEN IN mm. COLUMN SCHEDULE REMARKS POST SCHEDULE MARK SIZE P1 2-38x140 JACK STUDS + 2-38x140 CONT. STUDS P2 1-38x140 JACK STUD + 2-38x140 CONT. STUDS P3 2-38x89 JACK STUDS + 2-38x89 CONT. STUD P4 2-38x140 JACK STUDS + 2-38x140 CONT. STUDS P5 5-38x140 1-HDU5 BOTTOM P6 3-38x140 1-DTT2Z BOTTOM 2-LSTA15 STRAPS TOP P7 3-38x140 SIMPSON ACE4 TOP CB5-4.5 BOTTOM P8 2-38x140 JACK STUDS + 4-38x140 CONT. STUDS W460x74 220x20x480 BASE PLATE REFER TO BASE PLATE DETAIL CB2 W460x74 220x20x480 BASE PLATE ROOF SHEATHING FASTENING SCHEDULE NAIL SPACING (mm) REFER TO BASE PLATE DETAIL CB2 ZONE NAILS 38x89 BLOCKING AT PANEL EDGES OUTER BOUNDARIES OF ZONE PANEL EDGES ELSEWHERE A 64 100 300 REQUIRED B 100 150 300 REQUIRED REFER TO BASE PLATE DETAIL CB1 NOTES: 1. PROVIDE STEEL PLATE ON TOP OF ALL COLUMNS FLUSH WITH TOP OF STEEL BEAMS. 2. UNDERSIDE OF STEEL BASE PLATES 25mm ABOVE TOP OF CONCRETE PIER. HORIZONTAL MARK NOTES: 4. DO NOT SUBSTITUTE LARGER BAR SIZES IN PLACE OF THOSE SHOWN. DO NOT ADD MORE BARS THAN SPECIFIED. C3 VERTICAL CONCRETE SCHEDULE INTERIOR 3. MASONRY BEAMS SHALL EXTEND NOT LESS THAN 200mm BEYOND EDGES OF OPENING. W250x49 220x16x260 BASE PLATE HORIZONTAL 8. REFERENCE STANDARD: CSA S304.1 - 04 RETAINING WALLS AND RETAINING WALL FOOTINGS. 2. JOINT REINF. NOT SHOWN. REFER TO MASONRY WALL REINFORCEMENT NOTES, SPECIFICATIONS AND/OR DETAILS FOR JOINT REINFORCEMENT REQUIREMENTS. C2 VERTICAL 2. FOR CONCRETE ELEMENTS REQUIRING A FIRE RESISTANCE RATING, REFER TO APPLICABLE TABLE AND PROVIDE WHICHEVER COVER IS GREATER. LOCATION 1. IF MASONRY WALL ABOVE BEAM CONTAINS VERTICAL REINFORCEMENT, EXTEND VERTICAL BARS IN MASONRY BEAM. C1 75 mm 7. HORIZONTAL REINFORCING BARS SHALL BE PLACED IN FULLY GROUTED BOND BEAMS. NOTES: SIZE 75 mm 1. BASED ON CSA STANDARD A23.1-04 SLABS ON GRADE MARK 75 mm NOTES: LINTEL BLOCK 66 CLEAR 2-10M 35M & SMALLER WALL THICKNESS LINTEL SCHEDULE APPLICABLE IN BASE PRICE CONFIGURATION ONLY LINE 11 NON-LOAD BEARING WALLS N C-XL, C-1, C-2 A-1, A-2, A-3 6. PROVIDE A MINIMUM OF 1-15M IN CONTINUOUSLY GROUT-FILLED BLOCKS AT THE TOP, BOTTOM AND SIDES OF ALL OPENINGS EXCEEDING 1000mm IN WIDTH OR HEIGHT. EXTEND BARS A MINIMUM OF 610mm BEYOND EDGES OF OPENINGS. REMARKS STRETCHER 240 SLABS, WALLS, AND JOISTS LOAD BEARING WALLS & SHEAR WALLS F-1, F-2 S-1, S-2 FRAMING ANGLES REFER TO DETAIL 6.36 MB242 TOP AND FORMED SIDES OF FOOTINGS REMARKS SHEAR BLOCKING SCHEDULE 66 CLEAR 240 CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH BEAMS, GIRDERS, COLUMNS, AND PILES VERTICAL REINFORCING LINTEL BLOCK MB241 PLACE UNDERSIDE OF FOOTING NOT LESS THAN 1.5m BELOW FIN. GRADE. TOP OF CONCRETE PIER MIN. 150 ABOVE TOP OF CONCRETE SLAB. MASONRY SHEAR WALL SCHEDULE MASONRY BEAM SCHEDULE BEAM HEIGHT (mm) PLAIN CONC. 10M @ 250 LINE 1 BLOCK WIDTH (mm) 200 BAR SIZE REINF. 8-15M MSW2 GAUGE GALVANIZED GENERAL 1000x1000 DEPTH (mm) 480x580 MSW1 = = = 10M @ 250 4-15M SIZE (mm) EXPOSURE CONDITION REMARKS F2 F4 GA. GALV. GEN. TIES (mm) VERT. REINF. EXPOSURE CLASS FOOTING EXTERIOR A.B. ADJ. ALT. ARCH. ANC. REMARKS REMARKS 12/08/30 CLASS "B" LAP SPLICE OR 2'-0" WHICHEVER IS GREATER - TYPICAL T NON-LOADBEARING MASONRY PARTITION CORNER BARS SAME SIZE AND SPACING AS HORIZ. REINFORCING CONCRETE SLAB ON GRADE 2-15M CONTINUOUS CORNER DOWELS SAME SIZE AND SPACING AS HORIZ. REINFORCING SAWCUT SLAB WITHIN 18 HOURS OF COMMENCEMENT OF POUR TO A DEPTH OF 1 4 OF THE SLAB THICKNESS KEY (WALLS ONLY) CONCRETE SLAB 100 FOOTING REINFORCEMENT (WHERE SPECIFIED) GREATER OF CLASS B LAP OR 610mm 1 2 MIN. 3.01 STEP FOOTINGS WHERE REQUIRED TO MAINTAIN MINIMUM FROST COVER OR TO MATCH LEVEL OF ADJACENT FOOTINGS. 200 3.04 STEPPING OF WALL FOOTING CORNER DETAIL 200 2T SLAB ON GRADE THICKENING UNDER NON-LOADBEARING PARTITIONS 3.07 1-10M NOSING 300 TYP. INTERSECTION DETAIL INTERSECTION DETAIL (POURED TOGETHER) (POURED SEPARATELY) HORIZONTAL REINFORCING JUNCTIONS IF TOP OF WALL IS EXPOSED, CARRY CHASE & SEALANT ACROSS TOP BOND BEAKER CONC. SLAB ON GRADE 300 TYP. (STRIP FOOTINGS AND WALLS) 3.11 SLAB ON GRADE SAWCUT DETAIL 13 ISOLATION JOINT ELASTOMERIC SEALANT WITH FOAM BACKER ROD IN FORMED CHASE ON ALL SIDES WHERE WALL IS EXPOSED TO SOIL OR MOISTURE NO LAPPING OF HORIZONTAL BARS IS PERMITTED AT CONTROL JOINT LOCATIONS BOND BREAKER t A t 5t 5t 2 MIN. 5t 1 FOUNDATION WALL 1 2 MIN. A 3.12 ELEVATION OF ADJACENT FOOTINGS & EXCAVATIONS 3.27 DISCONTINUE HORIZ. REBAR AT CONTROL JOINT BEVEL SIDES OF CHASE TO FACILITATE FORM REMOVAL TYPICAL SLAB DETAIL AT EXTERIOR DOORS 3.38 TYPICAL DETAIL AT INTERIOR DOOR THRESHOLDS REFER TO TABLE FOR REINF. REQUIREMENTS REINFORCED CONCRETE HOUSEKEEPING PAD CONCRETE FLOOR SLAB 1. PROVIDE VERTICAL CONTROL JOINTS AT 6096mm o.c. MAXIMUM IN WALLS HAVING OPENINGS AND AT 7620mm o.c. MAXIMUM FOR WALLS HAVING NO OPENINGS, OR OTHERWISE NOTED ON PLANS. 2. PROVIDE VERTICAL CONTROL JOINTS WITHIN 3658mm OF ALL CORNERS. 3. PROVIDE PVC WATERSTOPS AT ALL CONTROL JOINTS WHERE WATER TIGHTNESS IS REQUIRED. Sc 4 BARS PAD THICKNESS "t" REINFORCEMENT WALL THICKNESS T CHASE DEPTH A < 200mm 25mm OTHER T/8 6 BARS CROSS TIE (NOTE 1) sc WELDED LAP LENGTH AS REQUIRED TO DEVELOP BAR NOTE 1 STEEL COLUMN 50mm 152x152 MW18.7xMW18.7 WELDED WIRE MESH 100mm 10M @ 300mm o.c. EACH WAY 25mm NON-SHRINK GROUT 5. FIX LOCATIONS OF ALL CONTROL JOINTS WITH THE ARCHITECT/ENGINEER BEFORE CONSTRUCTION. BASE PLATE Sc 12 BARS 14 OR 16 BARS NOTE: REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR LOCATIONS & DIMENSIONS. (t Sc 3.39 10 BARS 8 BARS t CROSS TIE (NOTE 1) 4. DEPTH OF CHASE SHALL BE AS FOLLOWS: CL COLUMN FOOTINGS NOTE 1 Sc Sc TYPICAL DETAILS FOR HOUSEKEEPING PADS CONCRETE PIER 5.49 S204 3.31 NOTE 1 VERTICAL CONTROL JOINTS IN CONCRETE WALLS (OPTION #1) CIRCULAR COLUMNS 250mm) TENSION DEVELOPMENT LENGTH (ldh) FOR STD. HOOK 300 LAP MIN. NOTE 1 PROVIDE CLASS B LAP AT SPLICES U.N.O. FILL SOLID WITH MORTAR DOWELS TO MATCH VERT. REINF. PROVIDE CLASS "B" LAP SPLICE BUILDING PAPER CONCRETE FOOTING RAKE OUT MORTAR 19mm AND CAULK STOP GROUT 25mm FROM TOP -TYP. CORES CONTAINING STEEL ARE FILLED SOLIDLY WITH GROUT. VERTICAL CORES SHOULD PROVIDE A CONTINUOUS CAVITY FREE OF MORTAR DROPPINGS PLACE MORTAR ON CROSS WEBS ADJACENT TO CORES THAT WILL BE GROUTED REINFORCING HORIZONTAL REINF. SHOULD NOT BE CONT. THROUGH JOINT -TYP. SEE NOTE 4 > 16 BARS PLACE GROUT IN LIFTS NOT EXCEEDING 1500mm. GROUT SHOULD BE VIBRATED OR RODDED IN PLACE (OPTION #2) CIRCULAR COLUMNS (OPTION #3) NOTES: 1. ADD SINGLE CROSS TIES WHEN CLEAR DISTANCE BETWEEN BARS, "S c OF SUCCESSIVE TIES ENGAGING THE SAME LONGITUDINAL BAR SHALL BE ALTERNATED END FOR END. 2. CLEAR DISTANCE BETWEEN VERTICAL BARS SHALL BE NOT LESS THAN: a) 1.4 TIMES VERTICAL BAR DIAMETER. b) 1.4 TIMES THE MAXIMUM SIZE OF THE COARSE AGGREGATE. c) 30mm. 3. SEE COLUMN SCHEDULE FOR OTHER ARRANGEMENTS NOT SHOWN HERE. 4. PROVIDE FULL TIE FOR EVERY OTHER VERTICAL BAR. 5. PER REINFORCING STEEL MANUAL OF STANDARD PRACTICE BY RSIC (2004), TABLE 4. 4.01 MASONRY CONTROL JOINT 3.53 TYPICAL COLUMN FOUNDATION 4.02 REINFORCING MASONRY WALL GROUTING 3.57 ARRANGEMENT OF VERTICALS AND TIES IN COLUMNS 12/08/30 CL STEEL DECK HORIZONTAL JOINT REINFORCEMENT - TYPICAL VERTICAL REINFORCEMENT VERTICAL REINFORCEMENT BUTTER BOTH ENDS OF EACH UNIT TO ENSURE PROPER BONDAGE. SLUSHING OF HEAD JOINTS AFTER THE UNIT IS PLACED SHALL NOT BE PERMITTED STEEL BEAM 25 MIN. WALL INTERSECTION L 127x76x6.4 (LLV) x 200 Lg. @ 1800mm o.c. EACH SIDE VERT. REINF. MASONRY WALL BEAM BEARING OPENING GROUT SOLID TO U/S LINTEL 4.07 DETAIL OF LATERAL SUPPORT FOR MASONRY PARTITIONS VERT. REINF. WALL CORNER GROUT SOLID FULL HEIGHT TO U/S BEAM GROUT SOLID TO U/S LINTEL VERTICAL REINFORCEMENT HORIZONTAL JOINT REINF. END OF WALL UNIT BEING PLACED WALLS WITH SINGLE LAYER VERT. REINF. CONTINUOUS ANCHOR SET DOVETAIL INSERT ALTERNATE COURSES VERT. REINF. VERT. REINF. 4.17 VERT. REINFORCING IN GROUTED CORES U.N.O. HEAD JOINT CONSTRUCTION DETAIL 60 CLEAR RAKE BACK MORTAR & CAULK BOTH SIDES OPENINGS IN WALLS MASONRY WALLS ABUTTING CONCRETE NOTES: 25 CLEAR MINIMUM 1. PROVIDE PRE-FABRICATED CORNER & TEE SECTIONS FOR JOINT REINFORCEMENT. GROUT SOLID WITH FINE GROUT IN ACCORDANCE WITH CSA STANDARD A179 25 CLEAR 60 CLEAR 2. LAP SPLICES FOR VERTICAL REINFORCEMENT AND HORIZ. JOINT REINFORCEMENT SHALL BE CLASS "B" U.N.O. CONCRETE LINTEL BLOCK 38x8 FLAT @ 1000mm o.c. 3. PROVIDE DOWELS INTO FOUNDATION WALL OR CONCRETE FOOTING TO MATCH ALL VERTICAL BARS. WALLS WITH DOUBLE LAYER VERT. REINF. 50 5. VERTICAL REINFORCEMENT SHOWN SHALL BE AS FOLLOWS: 50 CLEAR TYPICAL WALL THICKNESS VERTICAL REINF. 140 mm 15M 190 mm 20M 240 mm 2-15M 290 mm 2-15M WHERE LINTEL/BOND BEAM IS SINGLY REINFORCED, REINFORCING BAR SHALL BE CENTRED HORIZ. IN BLOCK STEEL COLUMN REFER TO CONCRETE BLOCK WALL SCHEDULE FOR REINFORCING 50x12.5 CHANNEL x 50mm Lg. WELDED TO COLUMN 12.5 4.14 TYPICAL LINTEL/BOND BEAM DETAIL 5.40 MASONRY WALL DETAILS UPPER BARS b HORIZONTAL JOINT REINF. 406 4. BARS SHOWN ARE TO BE PLACED IN ADDITION TO REINF. FOR WALLS SPECIFIED ELSEWHERE. 4.16 VERT. REINFORCING IN GROUTED CORES U.N.O. 4.29 MASONRY ANCHOR DETAIL TYPICAL CONCRETE BLOCK WALL REINFORCING DETAIL Rz LAY WIRES SIDE-BY-SIDE IN MORTAR JOINT LAP Mz Ry My Rx Mx STEEL COLUMN REFER TO COLUMN SCHEDULE FOR QUANTITY & SIZE OF ANCHOR BOLTS GROUT TRUSS OR LADDER TYPE HORIZ. JOINT REINFORCEMENT REMOVE CROSS WIRES WITHIN LAP SPLICE 25mm GROUT PAD BASE PLATE A307 ANCHOR BOLTS 50 MINIMUM CLEAR SPACING a (mm) MAXIMUM SEPARATION b (mm) 10M 25 94 475 15M 32 134 675 20M 39 150 820 25M 51 150 1320 30M 60 150 1565 BAR SIZE MINIMUM LAP SPLICE LENGTH (mm) MINIMUM LAP LENGTH (mm) SIDE WIRE DIAMETER (mm) KNURLED WIRE STANDARD 3.66 390 780 HEAVY- AND EXTRA HEAVY DUTY 4.76 390 780 TYPE REINFORCED CONCRETE PIER 5.56 ASTM A307 HEAVY HEX NUT TIES, REFER TO FOUNDATION SCHEDULE FOR SIZE & SPACING NOTES: NOTES: 3. ASSUMED IN-SITU GROUT STRENGTH: f'gr = 20 MPa 4. STEEL: CSA G30.18 GRADE 400 3. ASSUMED IN-SITU MORTAR STRENGTH: 5. FOR SPLICES IN MASONRY COLUMNS AND BEAMS WITHOUT STIRRUPS OR TIES, MULTIPLY MINIMUM LAP SPLICE LENGTHS BY 1.34 MINIMUM TENSION LAP SPLICE LENGTHS IN REINFORCED MASONRY 50 BURR THREADS AT TWO LOCATIONS BELOW NUT 2. FOR NON-STRUCTURALLY REINFORCED WALLS IN BUILDINGS HAVING A SEISMIC HAZARD INDEX IEFaSa(0.2) < 0.35, THE LAP LENGTHS MAY BE REDUCED TO 150mm AND 300mm FOR KNURLED AND SMOOTH/GALVANIZED WIRE, RESPECTIVELY 2. CLASS B LAP SPLICES 4.35 TYPICAL LOCAL AXIS MEMBER DIAGRAM VERTICAL REINFORCING REFER TO FOUNDATION SCHEDULE FOR SIZE & SPACING 1. THIS DETAIL APPLIES TO TRUSS OR LADDER TYPE HORIZONTAL JOINT REINFORCEMENT HAVING A MINIMUM YIELD STRENGTH OF 480 MPa (70 ksi) 1. ABOVE VALUES DO NOT APPLY TO EPOXY-COATED BARS 4-10M TIES @ 75mm o.c. f'gr = 10 MPa 4. STAGGER LAPS AT LEAST 750mm FROM COURSE TO COURSE 4.36 MINIMUM LAP SPLICE LENGTHS FOR JOINT REINFORCEMENT 5.49 TYPICAL COLUMN BASE PLATE ANCHORAGE DETAIL 12/08/30 PLYWOOD 2-PLY 30mm 35mm 30mm SEE PLAN FOR STUD SIZE & SPACING 2 PLY TOP PLATE WOOD TRUSSES (OR RAFTERS) 35mm REFER TO ARCH. FOR ROOF SLOPE SHEAR BLOCKING 75mm NAIL 75mm NAIL END POST. SEE SCHEDULE 38x89 60mm 3-PLY 38x140 60mm 30mm 2 PLY TOP PLATE TRUSS ANCHOR - TYPICAL AT ALL TRUSS BEARING POINTS SIMPSON HOLD DOWNS c/w BOLTS - SEE SCHEDULE TOP PLATE ANC. BOLTS. SEE SCHEDULE STUD WALL BOTTOM PLATE CRIPPLE STUDS WOOD STUDS REFER TO PLAN FOR SIZE & SPACING SHEATHING 35mm 30mm 125mm NAIL PROVIDE SIMPSON LS30 FRAMING ANGLE BOTTOM PLATE BOLTS 35mm 125mm NAIL 6.10 TYPICAL DETAIL AT ROOF TRUSSES 70 MIN. TYPICAL (RAFTERS SIMILAR) CONTINUOUS PLATE TO MATCH STUDS FOUNDATION WALL BUILT-UP WOOD POST WOOD SHEAR WALL SCHEDULE SPLICE (1 PLY ONLY) 38x89 80mm 4-PLY 38x140 80mm 35mm SIMPSON STRAP TIE SEE TABLE BELOW FOR SIZE 2-PLY S-P-F No.2 MARK STUDS SHEATHING 35mm HOLD DOWN ANCHOR 64mm NAILS @ 150mm o.c. 2-38x140 MIN. HDU4-SDS2.5 w/SSTB20 ANC. BOLT 64mm NAILS @ 75mm o.c. 3-38x140 MIN. HDU8-SDS2.5 w/SSTB28 ANC. BOLT 64mm NAILS @ 150mm o.c. 2-38x140 MIN. HDU4-SDS2.5 w/SSTB24 ANC. BOLT WSW3 WSW4 150mm NAIL 38x89 END POST SIZE BOTTOM PLATE BOLTS BUILT-UP WOOD BEAM JACK STUD(S) 35mm 35mm 120mm NAILING AT PANEL EDGES CONTINUOUS STUD(S) 120mm TOP PLATE SPLICE DETAIL TABLE 150mm NAIL 38x140 @ 400mm o.c. 12.5mm PLYWOOD WSW5 TOP PLATE SIZE GRADE SIMPSON CONNECTOR 2-38x89 S-P-F No. 2 MST48 STRAP TIE 2-38x140 S-P-F No. 2 MST60 STRAP TIE 1. PROVIDE MIN. 38x38 BLOCKING AT ALL PANEL EDGES. 2-38x184 S-P-F No. 2 HST5 STRAP TIE 2. SECURE SHEATHING WITH 64mm COMMON NAILS @ 300mm o.c. ALONG INTERMEDIATE FRAMING MEMBERS. MAXIMUM ROUGH OPENING 2540mm NOTE 1: MAXIMUM ROUGH OPENING SIZE FOR 38x89 STUD WALLS WITH BRICK VENEER SHALL BE 1800mm. NOTE 2: REFER TO PLAN FOR SIZE & NUMBER OF PLIES OF BUILT-UP WOOD MEMBERS NOTES: 3. ANCHOR BOLTS: ASTM A36 38x140 SPLICES SHALL BE MINIMUM 1800mm o.c. ONLY 1 PLY MAY BE SPLICED AT ANY SINGLE LOCATION 4. ANCHOR BOLTS SHALL HAVE A MINIMUM EDGE DISTANCE OF 70mm. SSTB ANCHOR BOLTS SHALL BE INSTALLED AS PER MANUFACTURER'S INSTRUCTIONS. 5. PROVIDE END POSTS & HOLD-DOWN ANCHORS AT ENDS OF WALL AND EACH SIDE OF ALL WINDOW & DOOR OPENINGS WITHIN SHEAR WALL. 6. END POST SIZE SHOWN IS MINIMUM. DRAWINGS MAY INDICATE LARGER POSTS. 6.04 6.24 NAILING FOR BUILT-UP COLUMNS 6.22 TYPICAL TOP PLATE SPLICE DETAIL 6.23 TYPICAL WOOD SHEAR WALL DETAIL TYPICAL WOOD LINTEL DETAIL 150 MAX. SHEAR BLOCKING NAILS 2 PLY 38x140 TOP PLATE SOLID WOOD BLOCKING TRUSSES OR RAFTERS LAP TOP PLATES. SECURE TOP PLY TO BOTTOM PLY w/5-89mm COMMON NAILS CUT OUT FOR VENTILATION 75 CAREFULLY DRILLED HOLES CONTINUOUS CONTINUOUS MAXIMUM ROUGH OPENING 2540mm WOOD STUDS REFER TO PLAN FOR SIZE & SPACING WALL STUDS JACK STUD(S) CONTINUOUS WOOD SILL SIZE & GRADE TO MATCH STUDS NOTE 1 BUILT-UP WOOD POST WALL TOP PLATE / NAILER FRAMING ANGLES STUD MAXIMUM HOLE DIAMETER 38x89 28mm 38x140 44mm SIMILAR AT CONCRETE & MASONRY WALLS CRIPPLE STUDS CORNER FRAMING CONTINUOUS STUD(S) 6.28 LAP TOP PLATES. SECURE TOP PLY TO BOTTOM PLY w/5-89mm COMMON NAILS ANCHOR BOLTS BOTTOM PLATE DRILLED HOLES IN INTERIOR LOAD BEARING STUD WALLS 6.36 TYPICAL SHEAR BLOCKING DETAIL TRUSSES @ 610 o.c. CONTINUOUS ROOF SHEATHING NAILS SHEAR BLOCKING BETWEEN TRUSSES / RAFTERS NOTE 1: SECURE SILL TO FIRST CONTINUOUS STUD OF BUILT-UP POST w/2-90mm SPIRAL NAILS. NOTE 2: MAXIMUM ROUGH OPENING SIZE FOR 38x89 STUD WALLS WITH BRICK VENEER SHALL BE 2050mm. NOTE 3: REFER TO PLAN FOR SIZE & NUMBER OF PLIES OF BUILT-UP WOOD MEMBERS CONTINUOUS SHEATHING 38x89 BRACING2 SETS PER PURLIN RUN 2 PLY 38x140 TOP PLATE FRAMING ANGLE SECURED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS TOP PLATE / NAILER WALL STUDS STUD WALL INTERSECTING WALL FRAMING ROOF SHEATHING 6.25 TYPICAL WOOD SILL DETAIL 6.26 6.34 PLAN AT PIGGYBACK BOTTOM CHORDS 6.37 TYPICAL SHEAR BLOCKING SECTION 12/08/30 8 7 6 5 4 3 2 1 EXTENT OF RIGID INSULATION 150mm CONCRETE PAD ON RIGID INSULATION OVER 200mm MIN. GRANULAR 'A' ON COMPACTED GRANULAR BACKFILL A PROVIDE 75mm RIGID INSULATION ALL AROUND COLUMN PIER FROM U/S OF SLAB DOWN 600mm - TYPICAL FOR PIERS ON LINE A F1 F1 END OF MASONRY SHEAR WALL ABOVE FW7 200 20 CLEAR 10M TIES @ 225 FW7 4-15M VERT. DOWELLED INTO FOOTING 1200 CP3 B B CP3 FW3 310 MIRR. 1 S241 FW4 MIRR. SIM. F2 2 S241 3 MIRR. S241 SIM. BROOM FINISH FW4 F3 240 C S242 FACE OF VENEER ABOVE F4 C FW8 1-15M T&B x 1200 Lg. CENTERED IN SLAB - TYP. D 625 1:15 FW2 A 655 A CONCRETE PIER CP1 SAWCUTS - TYPICAL SAWCUT FW4 300 ISOLATION JOINT AROUND PIERS - TYPICAL SIM. CP2 B S242 FW1 CP2 420 20 CLEAR SAWCUT 430 FW5 10M TIES @ 250 4-15M VERT. DOWELLED INTO FOOTING 1200 625 A FW4 D S242 E CP1 SUMP PIT 655 150mm CONCRETE PAD ON 200mm MIN. GRANULAR 'A' OVER COMPACTED GRANULAR BACKFILL 600 SAWCUTS FW4 A S242 100mm CONCRETE SLAB ON GRADE 200mm MINIMUM GRANULAR 'A' COMPACTED TO 100% S.P.M.D.D. 300 CP2 SLAB THICKENING -TYPICAL CP1 FW1 DRAIN - TYP. 600 775 175mm CONCRETE SLAB ON GRADE 200mm MINIMUM GRANULAR 'A' COMPACTED TO 100% S.P.M.D.D. 775 1200 CP2 F2 F3 A F4 470 FW2 310 F 1 S241 2 S241 FW4 SIM. REFER TO ARCH DRAWINGS FOR FLOOR SLOPES IN TRUCK BAY AREA 3 S241 FW3 CONCRETE PIER CP2 FW8 WALL REINF. OMITTED FOR CLARITY 1:15 SAWCUTS CP3 G CP3 F1 F1 FW6 H NOTE A : 15M x 1200 Lg. 60mm CLEAR FROM TOP OF SLAB CENTRED ABOUT SAWCUT LOCATION. AT T-JOINTS IN SAWCUTS DO NOT OVERRUN CUT. G FW6 PROVIDE ISOLATION JOINT WHERE SLAB ABUTS BUILDING - TYPICAL ALL EXTERIOR PADS / RAMPS SAWCUTS 255 10M TIES @ 250 150mm CONCRETE PAD ON 200mm MIN. GRANULAR 'A' OVER COMPACTED GRANULAR BACKFILL 255 4-15M VERT. DOWELLED INTO FOOTING D S242 ISOLATION JOINT AROUND PIERS - TYPICAL 8 7 6 5 215 300 20 CLEAR 4 3 2 1 CONCRETE PIER CP3 WALL REINF. OMITTED FOR CLARITY 1:15 FOUNDATION PLAN 1:75 290 290 D 500 TOP OF PIER FLUSH WITH GARAGE FLOOR (HIGH POINT) LOWER TOP OF FOUNDATION WALL AT DOOR OPENING - TYPICAL 180 120 E E 300 E 300 D 180 MIRRORED LOWER TOP OF FOUNDATION WALL AT DOOR OPENING TOP OF PIER FLUSH WITH GARAGE FLOOR (HIGH POINT) MIRRORED TOP OF PIER FLUSH WITH GARAGE FLOOR (HIGH POINT) 290 180 80 5 120 10 7 300 8 OPENING FOR 200 200 GARAGE DOOR FOUNDATION PIER PLAN DETAIL REINF. OMITTED FOR CLARITY 1:15 1 S221 FOUNDATION PIER PLAN DETAIL REINF. OMITTED FOR CLARITY 1:15 2 S221 FOUNDATION PIER PLAN DETAIL REINF. OMITTED FOR CLARITY 1:15 3 S221 12/08/30 8 7 6 5 4 3 2 os s oc 1 1620 TYP. c os s s' oc c WSW4 os oc E.W.R.T. @ 600mm o.c. os s 128 P2 P6 L2 P2 128 P6 P1 P8 L8 c s os oc s' s os 2 WP GROUT MASONRY PIER BETWEEN OPENINGS SOLID & REINF. WITH 4-15M VERT. MSW1 WIND PRESSURE DIAGRAM P3 P3 D S243 P3 A S243 W410x39 C250x23 BELOW L4 E. W F W460x74 C250x23 BELOW 1 WP C3 240 CONC. BLOCK L7 P4 P5 SECURE w/SIMPSON HURRICANE TIE EACH END E.W.G.T. VALLEY JACKS OVER L10 ABOVE . .T .H W C S243 E. 2400 Mf =187 kNm E.W.M.T. @ 600mm o.c. 38x140 @ 600mm o.c. P2 P6 G P2 P6 P2 L2 P4 SECURE w/SIMPSON HCP2 P2 4 SLS r -1.41 0.79 -0.85 0.48 s -1.84 0.79 -1.10 0.48 c -2.31 0.79 -1.39 0.48 os -2.02 0.79 -1.21 0.48 oc -3.03 0.79 -1.82 0.48 s' -1.26 1.08 -0.76 0.65 -1.88 1.08 -1.13 0.65 -1.88 1.08 -1.13 0.65 SNOW DISTRIBUTIONS FOR GABLE ROOFS D S243 3. NEGATIVE VALUES INDICATE UPLIFT. 128 P7 3-2x6 MIN. UNDER E.W.H.T. 128 128 SECURE w/SIMPSON HURRICANE TIE - TYP. SNOW LOADS SHOWN INCLUDE IMPORTANCE FACTOR 2. ALL LOADS ARE UNFACTORED. G 3-38x184 128 3-38x184 P7 4.13 kPa 1. WOOD TRUSSES SHALL BE DESIGNED TO SAFELY RESIST THE WIND LOADS NOTED ABOVE IN COMBINATION WITH LOADS SPECIFIED IN THE 2006 OBC. L2 H CASE 2 P4 L2 310 P5 Mf =187 kNm WSW3 P4 2400 .H .T . L5 L8 P3 9 ULS 3.60 kPa L3 ZONE CASE 1 12 WIND PRESSURES (kPa) L3 1 C2 oc P3 E.W.R.T. @ 600mm o.c. 1 WP WP C1 c P3 MSW2 8 VALLEY JACKS OVER. DESIGN TRUSS FOR ADDITIONAL 0.23 kPa DEAD LOAD IN THIS REGION. SHEATHING SHALL BE CONTINUOUS OVER MAIN TRUSSES & BENEATH VALLEY JACKS. 1620 TYP. SECURE w/SIMPSON HURRICANE TIE - TYP. 38x89 @ 400 o.c. BELOW E.W.R.T. @ 600mm o.c. 38x140 @ 400mm o.c. ABOVE E.W.G.T. RIDGE E.W.G.T. VALLEY JACKS OVER E.W.M.T. @ 600mm o.c. L8 r E.W.R.T. @ 600mm o.c. WSW5 2 1 ROOF FRAMING PLAN 1:75 50 50 50 50 BASE PLATE ANCHOR BOLTS ANCHOR BOLTS b2/4 4.38 kPa b2 VARIES 2.44 kPa 12.7mm PLYWOOD OVER ALL EXTERIOR WOOD STUD WALLS TO BE 38x140 S-P-F STUD GRADE @ 400mm o.c. UNLESS NOTED OTHERWISE. ROOF RIDGE ROOF VALLEY ROOF VALLEY ROOF RIDGE CL ROOF VALLEY CL ROOF RIDGE 4.38 kPa BASE PLATE CL ROOF VALLEY 2.44 kPa 50 b1/2 SNOW DISTRIBUTIONS IN VALLEYS CASE 4 3 b2 VARIES 4 b2/4 5 4.38 kPa 6 6.31 kPa 7 SNOW DISTRIBUTIONS IN VALLEYS CASE 3 8 6.31 kPa b1/4 b1 VARIES 50 50 b1 VARIES 50 SNOW DISTRIBUTIONS IN VALLEYS CASE 3 STEEL COLUMN SNOW DISTRIBUTIONS IN VALLEYS CASE 4 STEEL COLUMN COLUMN BASE PLATE DETAIL CB1 REFER TO PLAN FOR COLUMN ORIENTATION 1:5 3.60 kPa + SNOW DISTRIBUTIONS 0.07 0.10 0.18 0.10 0.25 0.19 4.49 kPa + SNOW DISTRIBUTIONS os L3 T. L6 CONTINUOUS L9 . .H MSW2 E oc W 9 VALLEY JACKS OVER SNOW METAL ROOF PLYWOOD ROOF TRUSSES INSULATION MECH/ELECT CEILING TOTAL W 290 CONC. BLOCK F S243 s SECURE w/SIMPSON HURRICANE TIE EACH END P1 E. 240 CONC. BLOCK 240 CONC. BLOCK s os r L1 E. W E.W.G.T. C3 r c .T . .H C1 os s s s 2515 P4 VALLEY JACKS OVER 240 CONC. BLOCK W410x39 C250x23 BELOW + L 127x89x7.9 s SECURE w/SIMPSON HCP2 P5 C2 B P1 L1 E.W.M.T. @ 600mm o.c. E S243 B S243 310 8 D P1 L1 oc c ROOF DESIGN LOADS 1620 TYP. P1 W460x74 C250x23 BELOW + L 127x89x7.9 P. 3-2x6 MIN. UNDER E.W.H.T. 3-38x184 3-38x184 B C TY 20 16 P. TY 38x140 @ 600mm o.c. Mf =187 kNm r 128 A Mf =187 kNm r s D S243 P7 s 20 16 P7 190 c 1620 TYP. 1310 COLUMN BASE PLATE DETAIL CB2 REFER TO PLAN FOR COLUMN ORIENTATION 1:5 12/08/30 480 ISOLATION JOINT VENEER 430 CONCRETE SLAB ON GRADE ISOLATION JOINT 240 CONC. BLOCK CONCRETE SLAB ON GRADE COMPACTED GRANULAR "A" ISOLATION JOINT VENEER CONCRETE SLAB ON GRADE VENEER CONCRETE SLAB ON GRADE COMPACTED GRANULAR "A" COMPACTED GRANULAR "A" FIN. GRADE 150 MIN. 150 MIN. FIN. GRADE ISOLATION JOINT FIN. GRADE 150 MIN. COMPACTED GRANULAR "A" DOWELS TO MATCH VERT. REINF. IN MASONRY WALL 15M @ 300 x 1760 Lg. + 90 HOOK EACH END 15M @ 300 x 5250 Lg. 470 CONCRETE WALL 15M @ 300 VERT. E.F. COMPACTED GRANULAR BACKFILL COMPACTED GRANULAR BACKFILL 2-15M T&B 255 CONCRETE WALL 420 CONCRETE WALL 2-15M T&B 3-15M T&B 250 250 15M x 1570 Lg. @ 385 T&B 38x89 CONT. SHEAR KEY 1650 38x89 CONT. SHEAR KEY 1100 FOUNDATION WALL 1:15 ISOLATION JOINT CONCRETE SLAB ON GRADE COMPACTED GRANULAR "A" VENEER CONCRETE SLAB ON GRADE 15M @ 300 x 4680 Lg. HORIZ. EACH FACE CENTRED UNDER MASONRY SHEAR WALL FREE DRAINING COMPACTED GRANULAR BACKFILL 10M @ 250 VERT. E.F. 7-20M T&B 10M @ 250 VERT. E.F. 255 CONCRETE WALL VENEER FIN. GRADE FREE DRAINING COMPACTED GRANULAR BACKFILL COMPACTED GRANULAR BACKFILL 15M @ 300 HORIZ. E.F. 240 CONCRETE WALL FW4 1:15 COMPACTED GRANULAR "A" 150 MIN. COMPACTED GRANULAR BACKFILL FOUNDATION WALL FREE DRAINING COMPACTED GRANULAR BACKFILL COMPACTED GRANULAR BACKFILL 15M @ 300 HORIZ. E.F. 10M @ 250 VERT. E.F. 255 CONCRETE WALL FIN. GRADE 15M @ 300 HORIZ. E.F. 10M @ 250 VERT. E.F. 255 CONCRETE WALL 20M x 2520 Lg. @ 400 T&B 38x89 CONT. SHEAR KEY 2600 FOUNDATION WALL AT SHEAR WALL DRAINAGE TILE 755 1:15 FW5 250 250 400 1200 MINIMUM COMPACTED GRANULAR BACKFILL 38x89 CONT. SHEAR KEY CONCRETE SLAB ON GRADE COMPACTED GRANULAR "A" DOWELS TO MATCH VERT. REINF. IN MASONRY WALL COMPACTED GRANULAR BACKFILL DRAINAGE TILE ISOLATION JOINT CONCRETE PAD 20 CL. FW3 1:15 ISOLATION JOINT COMPACTED GRANULAR BACKFILL 950 FOUNDATION WALL FW2 1:15 VENEER DRAINAGE TILE 455 FOUNDATION WALL FW1 DOWELS TO MATCH VERT. REINF. IN MASONRY WALL 38x89 CONT. SHEAR KEY DRAINAGE TILE 755 FOUNDATION WALL 1:15 FW6 250 DRAINAGE TILE FREE DRAINING COMPACTED GRANULAR BACKFILL COMPACTED GRANULAR BACKFILL 240 CONCRETE WALL 5-15M x 5730 Lg.T&B FREE DRAINING COMPACTED GRANULAR BACKFILL 200 1200 MINIMUM DOWELS TO MATCH VERT. REINF. IN MASONRY WALL 150 MIN. COMPACTED GRANULAR BACKFILL 200 FREE DRAINING COMPACTED GRANULAR BACKFILL 38x89 CONT. SHEAR KEY DRAINAGE TILE 1100 FOUNDATION WALL 1:15 FW7 FOUNDATION WALL 1:15 FW8 12/08/30 1200 MIN. 460 38x38 SHEAR KEY 300 REFER TO ARCH DWG. 10M @ 230 VARIES 200mm TO 300mm 15M @ 230 BETWEEN TRENCH AND SAWCUT 60 CLEAR ISOLATION JOINT SAWCUT STAINLESS STEEL DOWELS @ 300mm o.c. 75 100mm RIGID INSULATION (DOW SM OR EQUIVALENT) FIN. GRADE (OR SIDEWALK) 1-15M 60 CLEAR 300 SAWCUT 600 30 CL. 450 2-10M 175 300 150 60 CL. 75 CLEAR 4-10M E.W. 750 DOWEL SHALL BE COATED TO PREVENT BOND 15M @ 230 4-15M CONT. 450 650 75mm RIGID INSULATION 450 175 COMPACTED GRANULAR BACKFILL 650 SUMP PIT SECTION 1:15 SECTION AT TRENCH A S242 1:15 B S242 SECTION THROUGH CONCRETE PAD AT EAST ENTRANCE 1:15 725 2360 C S242 725 CL FLAGPOLE CL FLAGPOLE SIGN SUPPORT WALL VENEER LEDGE 300 300 15M NOSING 860 460 300 60 CLEAR E S242 CONCRETE FOOTING BELOW 4210 150 750 PLAN VIEW OF SIGN BASE INSTALL ANCHOR BOLTS FOR FLAGPOLES AS PER POLE SUPPLIER'S SPECIFICATIONS 1:20 SECTION AT EDGE OF EXTERIOR CONCRETE PAD TOP OF SIGN D S242 1200 MAX. 1:15 40 CL. 260 CONC. WALL 10M @460 VERT. E.F. 610 PROVIDE DOVETAIL ANCHOR SLOTS FOR VENEER TIES @ 600mm o.c. DOVETAIL TIES TO CSA A370 40 CL. 100 10M @ 400 HORIZ. E.F. 100 300 LAP 150 FIN. GRADE 15M @ 400 HORIZ. E.F. COMPACTED GRANULAR BACKFILL 380 380 3730 1500 MIN. 15M @ 230 FROM PIT TO NEAREST SAWCUT REFER TO ARCH. FOR GRATING & FRAME COMPACTED GRANULAR BACKFILL 15M @ 500 VERT. E.F. PLAIN CONC. FOOTING SECTION THROUGH SIGN BASE 1:15 E S242 12/08/30 D VALLEY JACK TRUSSES 4 1310 HANGERS EACH END 38x184 CONTINUOUS + 38x184 BLOCKING BETWEEN TRUSSES 1 ROOF JOISTS 2 38x140 @ 600mm o.c. MAX. NAILED TO END VERTICAL OF EACH TRUSS w/76mm NAILS @ 200mm o.c. PLYWOOD SHEATHING 38 E BLOCKING BETWEEN TRUSSES 38x89 38x89 @ 400mm o.c. CEILING JOISTS HOLD DOWN ANCHORS 3 L 89x89x6.4 HANGERS @ 1450mm o.c. MAX. 5 PLYWOOD 102mm BEARING FOR TRUSS 4 8 SHEAR BLOCKING SECURED TO TOP PLATE COPE HANGER AT CHANNEL & WELD SHEATHING 1:15 PROVIDE LATERAL SUPPORT TO TOP OF MASONRY SIMILAR TO DETAIL 4.07 WHERE MASONRY ABUTS U/S OF CHANNEL SECTION 1:15 B S243 SECTION 1:15 C S243 SECTION 1:15 D S243 INVERTED JOIST HANGER 38x140 MIN. TOP CHORD OUTRIGGERS 127 PROVIDE LATERAL SUPPORT TO TOP OF MASONRY SIMILAR TO DETAIL 4.07 WHERE MASONRY ABUTS U/S OF CHANNEL VALLEY JACK TRUSSES 38x89 @ 400mm o.c. STUD WALL TIGHT TO INSIDE FACE OF GABLE END TRUSS BLOCKING BETWEEN OUTRIGGERS REFER TO ARCH. FOR ROOF SLOPE 212 A S243 TOP PLATE STUD WALL L 76x76x4.9 HANGERS @ 1450mm o.c. MAX. 127 TRUSS ANCHOR - TYPICAL AT ALL TRUSS BEARING POINTS HOLD-DOWN ANCHORS - TYPICAL ALL TRUSSES STEEL L OVER OPENINGS, SECURE TO CHANNEL CONNECT TO STEEL COLUMN EACH END SECTION WOOD TRUSS (OR RAFTERS) 237 EXTEND WEB STIFFENER @ EACH HANGER 2-38x140 SILL CENTRED ON WALL AT HEEL TYP. ALL TRUSSES PLYWOOD 64mm NAILS @ 50mm o.c. 38x89 BLOCKING AT EACH BRACE DROPPED TOP-CHORD GABLE END TRUSS INVERTED JOIST HANGER PLYWOOD SHEATHING 6 SHEAR BLOCKING BETWEEN TRUSSES 2-38x140 SILL SHEATHING STUD WALL 38x89 BRACE @ 600mm o.c. SIMPSON GBC GABLE BRACE CONNECTOR 7 2-15M CONT. VERT. REINF. FILL TOP 2 COURSES SOLID WITH GROUT SECTION AT GABLE ENDS 1:15 CONC. BLOCK WALL E S243 SECTION 1:15 F S243 12/08/30 11 10 9 7.5 11 10 9 7.5 6 9 FW4 4 S251 MIRR. SIM. F4 F4 2 S241 F3 D C SAWCUT W460x74 C250x23 BELOW + L 127x89x7.9 C1 C2 200 VALLEY JACKS OVER 200 F S243 11 L8 E F4 F4 . W E. F3 C3 4 S251 FW4 SIM. REFER TO ARCH DRAWINGS FOR FLOOR SLOPES IN TRUCK BAY AREA 2 S241 C3 C1 W410x39 C250x23 BELOW W460x74 C250x23 BELOW C2 Mf =187 kNm 2400 SAWCUTS 200 TOP OF PIER FLUSH WITH GARAGE FLOOR (HIGH POINT) 310 5 S251 80 8 W410x39 C250x23 BELOW F 310 F 10 LOWER TOP OF FOUNDATION WALL AT DOOR OPENING Mf =187 kNm D E 300 E .T .H 10 180 A 625 A FW4 E.W.R.T. @ 600mm o.c. MSW2 655 CP2 SAWCUT MIRRORED B S242 FW1 240 CONC. BLOCK RIDGE C S243 CP2 SUMP PIT 1:15 NOTE A : 15M x 1200 Lg. 60mm CLEAR FROM TOP OF SLAB CENTRED ABOUT SAWCUT LOCATION. AT T-JOINTS IN SAWCUTS DO NOT OVERRUN CUT. 500 OPENING FOR GARAGE DOOR 11 10 9 7.5 11 10 9 7.5 6 FOUNDATION PIER PLAN DETAIL REINF. OMITTED FOR CLARITY FOUNDATION PLAN ROOF FRAMING PLAN 1:75 oc 1620 TYP. oc 1620 TYP. c 4 S521 E.W.G.T. SIM. 600 SAWCUTS A S242 REINF. OMITTED FOR CLARITY MSW2 VALLEY JACKS OVER CP2 FOUNDATION PIER PLAN DETAIL 290 CONC. BLOCK E.W.M.T. @ 600mm o.c. FW1 DRAIN - TYP. 600 775 L8 A 175mm CONCRETE SLAB ON GRADE 200mm MINIMUM GRANULAR 'A' COMPACTED TO 100% S.P.M.D.D. 775 150mm CONCRETE PAD ON 200mm MIN. GRANULAR 'A' OVER COMPACTED GRANULAR BACKFILL 240 CONC. BLOCK L8 655 A CP2 FW4 D W410x39 C250x23 BELOW + L 127x89x7.9 E 625 FW4 . .T D C3 W410x39 C250x23 BELOW + L 127x89x7.9 .H W E. 1-15M T&B x 1200 Lg. CENTERED IN SLAB - TYP. 8 C3 L9 C 180 MIRR. 300 5 S251 310 310 MIRR. LOWER TOP OF FOUNDATION WALL AT DOOR OPENING - TYPICAL 120 B S243 MIRRORED TOP OF PIER FLUSH WITH GARAGE FLOOR (HIGH POINT) c os os s s 12.7mm PLYWOOD OVER os s os s s' 1:15 5 S521 1:75 oc c r s r r s s os s r r P. TY oc c 20 16 20 16 P. TY os s s s os r s oc s s os os r c oc s os s' s os 1620 TYP. c c oc 1620 TYP. WIND PRESSURE DIAGRAM 12/08/30