Energy-Saving Axial Fans - Unit Cooler - ebm

advertisement
Energy-saving axial fans
A solution specifically designed for unit cooler applications.
10-Position
rotary switch
The engineer’s choice
EC axial fans
New S1G305 series designed for unit cooler applications
Sickled blades (S-series) single inlet Ø 305
Highlights:
– Motor current limit
– Soft start
– Over-temperature protected electronics
– Locked rotor protection
Material: Blades and struts: PP plastic
Mounting position: Shaft horizontal with the harness in the 6 o'clock position
Condensate discharge holes: None
Direction of rotation: Clockwise, seen on rotor
Unit Cooler
The new S1G305 series uses 30% less power than typical unit cooler fans with PSC
motors. Specifically designed for unit cooler applications, the S1G305 fan series is
equipped with a very efficient electronically commuted, permanent magnet motor. Motor,
blade, power cable and three mounting options are integrated and available as a single
part number. The S1G305 fans are equally suited for both OEM and retrofit use.
Fan replacement or retrofit of walk-in evaporators is a breeze with the winning combination
of wide voltage range and rotary speed selection on the S1G305 series!
Standard Features
Voltage range
Frequency
Power input (1)
Speed
Current draw (1)
Max back pressure
Temperature range
Weight
» 835 CFM at 41 watts input power at free air
VAC
Hz
W
RPM
A
in. wg
°C
lbs
M1G055-DF
100...240
50/60
63
1590
M1G055-DF
100...240
50/60
70
1650
» Same performance operating on 50 or 60 Hz
» Maintains performance over wide voltage range (100-240 VAC)
» Efficient, small frame EC external rotor motor reduces power and mounting depth
Nominal Data
» Mounting depth only 2.86" (including mounting stud flange)
Type
Motor
» Integrated assembly reduces purchasing and manufacturing logistics
S1G305-DA02-07
» Multi-mount design provides three bolt-circles for choice of mounting
S1G305-DA02-10
(1) Nominal data at maximum load and 115 VAC.
» 12” diameter composite, aerodynamic blade is installed and balanced
(2)
0.90
0.30
-40...40
3.6
Single speed
0.98
0.35
-40...40
3.6
10-speed rotary switch
(2) Speed settings (rpm): 900, 1100, 1200, 1300, 1400, 1450, 1500, 1550, 1600, 1650
» Grounding protection Class II - no ground wire needed
» Protection Class IP54
S1G305-DA02-07 Performance Curve
» EMF P-2-1-075 compatible plug connection on 12” jacketed cable
S1G305-DA02-07 Performance Curve
0.45
Air performance measured on an
air chamber designed to meet ISO
AMCA210-99 and ISO 5801, with fan
installed as per ISO 5801 Installation
Category A but without protection
against accidental contact.
in. wg
» Allows use of existing fan guards
0.40
Options
0.35
» 10 position rotary switch for setting speed (P/N S1G305-DA02-10)
The fan was mounted in a square-edged
orifice to simulate worst case unit
cooler applications.
0.30
4
» Two speed
0.25
» Variable speed
0.20
The values given are valid under the
measuring conditions mentioned
and may vary accoring to the actual
installation situation.
3
For detailed information on the
measurement set-up, please contact
ebm-papst.
0.15
2
0.10
pfs
0.05
0.00
0
qV
1
100
200
300
400
500
600
700
800
1
Description
n
Pe
I(3)
rpm
W
A
A
1
1599
41.4
0.58
A
2
1596
48.2
0.67
A
3
1596
52.6
0.73
A
4
1595
57.2
0.80
A
5
A
6
A
7
A
8
A
9
A
10
A
11
A
12
A
13
A
14
A
15
A
16
(3) Current shown at 115 VAC
900
cfm
2
S1G305-DA02-07
Dimensions shown in millimeters (inches)
Notes
S1G305-DA02-10 performance curves for the 10 speed settings
S1G305-DA02-10 Performance Curves
in. wg
0.45
Air performance measured on an
air chamber designed to meet ISO
AMCA210-99 and ISO 5801, with fan
installed as per ISO 5801 Installation
Category A but without protection
against accidental contact.
Fan Speed Setting
0.40
1650rpm Step 10
1600rpm Step 9
1550rpm Step 8
0.35
1500rpm Step 7
1400rpm Step 5
1300rpm Step 4
1200rpm Step 3
0.25
dimensionally the same as the single
speed S1G305-DA02-07.
The values given are valid under the
measuring conditions mentioned
and may vary accoring to the actual
installation situation.
1100rpm Step 2
900rpm
shown without cover plate. Unit otherwise
The fan was mounted in a square-edged
orifice to simulate worst case unit
cooler applications.
1450rpm Step 6
0.30
View of rotary switch speed selector
Step 1
0.20
For detailed information on the
measurement set-up, please contact
ebm-papst.
0.15
0.10
pfs
0.05
0.00
0
qV
100
200
300
400
500
600
700
800
900
1000
cfm
Speed selector shown set to #7, equal to
1500 rpm.
3
4
S1G305 field replacement guide
Step-by-step visual instructions
The ebm-papst S1G305 unit cooler fan assembly
can be used to replace failed EC, PSC or shaded
pole inefficient motor/blade/mount assemblies
providing a quick repair and immediate energy
savings by upgrading to an EC motor.
Standard evaporator with motor,
blade and mounting fixture.
Scan here to see for yourself
how easy the S1G305 makes
replacing a broken or inefficient
fan assembly!
Or visit our YouTube channel at
https://www.youtube.com/
user/ebmpapstUSA
S1G305 field replacement guide
2
Remove existing fan, blade and
mount as complete assembly - no
disassembly required since these
parts will not be required.
3
Install the new preassembled
ebm-papst EC fan with existing
hardware.
1
Remove existing finger guard and
nuts for re-use.
5
4
Final installation re-using existing
fingerguards.
6
www.ebmpapst.us
Printed in the USA - 04/2016
ebm-papst Inc.
North America
100 Hyde Road
Farmington, CT 06034
Phone + 1 860-674-1515
Fax + 1 860-674-8536
sales@us.ebmpapst.com
© ebm-papst Inc. 2016.
ebm-papst Inc. reserves the right to change any specifications or data without notice