CIRCUIT BREAKERS Specifications Molded Case Circuit Breakers TD/TS series circuit breakers have built in thermal-magnetic trip units. Some models of the TD/TS series circuit breakers are UL Listed to be applied at up to 100% of their current rating. Because of the additional heat generated, the use of specificallydesigned enclosures and 90°C rated wire are required when using circuit breakers at 100% of their current rating. Markings on the circuit breaker indicate the minimum enclosure size and ventilation requirements. The 90°C wire size shall be based on UL 489. Circuit breakers with 100% rating can also be used in applications requiring only 80% continuous loading. Molded Case Circuit Breakers TD/TS Series TD125 Frame size 125AF Rated current ln A 15, 20, 30, 40, 50, 60, 80, 100, 125 V 600 3 Number of poles Rated operational voltage, Ue AC UL interupting rating AC 50/60Hz kA NU HU 120V 50 100 240V 50 100 480V 35 65 600V 10 14 UL 489 Reference standard Fixed thermal, fixed magnetic FTU Adjustable-thermal, fixed-magnetic Available breaker types FMU - AX - Auxiliary switch AL - Alarm switch SHT - Shunt trip UVT - Undervoltage trip Accessories EHU - Extended rotary handle FH - Flange handle PL, PHL - Locking devices (Removable, fixed) MIT - Mechanical interlock device Mechanical life Operations 4,000 Electrical life @600V AC Operations 4,000 Weight 3-pole lbs (kg) Basic dimension, Wx Hx D 3-Pole in (mm) www.franklin-controls.com | 1.800.962.3787 2.65lbs (1.2kg) 3.54 x 6.46 x 3.39in (90 x 164 x 86mm) CIRCUIT BREAKERS Specifications TS250 TS400 250AF 400AF TS800 800AF 150, 175, 200, 250 300, 400 500, 600, 800 3 3 3 600 600 600 NU HU NU HU NU HU - - - - - - 50 100 50 100 50 100 35 65 35 65 35 65 10 18 14 20 18 25 UL489 Fixed thermal, fixed magnetic, FTU Fixed thermal, fixed magnetic, FTU Fixed thermal, fixed magnetic, FTU Adjustable-thermal, fixed-magnetic, FMU Adjustable-thermal, fixed-magnetic, FMU Adjustable-thermal, fixed-magnetic, FMU Adjustable-thermal, Adjustable-magnetic (3 pole), ATU Adjustable-thermal, Adjustable-magnetic (3 pole), ATU Adjustable-thermal, Adjustable-magnetic (3 pole), ATU AX - Auxiliary switch AX - Auxiliary switch AX - Auxiliary switch AL - Alarm switch AL - Alarm switch AL - Alarm switch SHT - Shunt trip SHT - Shunt trip SHT - Shunt trip UVT - Undervoltage trip UVT - Undervoltage trip UVT - Undervoltage trip EHU - Extended rotary handle EHU - Extended rotary handle EHU - Extended rotary handle FH - Flange handle FH - Flange handle FH - Flange handle PL, PHL - Locking devices (removable, fixed) PL, PHL - Locking devices (removable, fixed) PL, PHL - Locking devices (removable, fixed) MIT - Mechanical interlock device MIT - Mechanical interlock device MIT - Mechanical interlock device 5,000 5,000 1,000 1,000 3,000 500 4.19lbs (1.9kg) 12.57lbs (5.7kg) 29.98lbs (13.6kg) 4.13 x 7.01 x 3.39in (105 x 178 x 86mm) 5.51 x 11.50 x 4.33in (140 x 292 x 110mm) 8.27 x 16.85 x 5.31in (210 x 428 x 135mm) CIRCUIT BREAKERS Ordering Information TD/TS Series Circuit Breakers (FTU) Frame Size 125AF 250AF 400AF Amp Rating UL Interrupting Rating (kA) 240V NU HU 480V NU HU 600V NU HU Magnetic Trip Setting NU Series (Normal Interrupting) 15A TD125HU FTU 125 15A TD125NU FTU 125 15A 20A TD125HU FTU 125 20A TD125NU FTU 125 20A 30A TD125HU FTU 125 30A TD125NU FTU 125 30A 40A TD125HU FTU 125 40A TD125NU FTU 125 40A TD125HU FTU 125 50A TD125NU FTU 125 50A 60A TD125HU FTU 125 60A TD125NU FTU 125 60A 80A TD125HU FTU 125 80A TD125NU FTU 125 80A 100A TD125HU FTU 125 100A TD125NU FTU 125 100A 125A TD125HU FTU 125 125A TD125NU FTU 125 125A 150A TS250HU FTU 250 150A TS250NU FTU 250 150A TS250HU FTU 250 200A TS250NU FTU 250 200A 250A TS250HU FTU 250 250A TS250NU FTU 250 250A 300A TS400HU FTU 400 300A TS400NU FTU 400 300A TS400HU FTU 400 400A TS400NU FTU 400 400A TS800HU FTU 800 500A TS800NU FTU 800 500A TS800HU FTU 800 600A TS800NU FTU 800 600A TS800HU FTU 800 800A TS800NU FTU 800 800A 50A 200A 400A 50 50 50 100 100 100 35 35 35 65 65 65 10 10 14 14 18 20 10X 5-10X 5-10X 500A 800AF HU Series (High Interrupting) 600A 50 100 35 65 18 25 5-10X 800A TD/TS Series Circuit Breakers (FMU) Frame Size 125AF Amp Rating 400AF 480V NU HU 600V NU HU Magnetic Trip Setting NU Series (Normal Interrupting) TD125HU FMU 125 40A TD125NU FMU 125 40A 50A TD125HU FMU 125 50A TD125NU FMU 125 50A 60A TD125HU FMU 125 60A TD125NU FMU 125 60A TD125HU FMU 125 80A TD125NU FMU 125 80A 100A TD125HU FMU 125 100A TD125NU FMU 125 100A 125A TD125HU FMU 125 125A TD125NU FMU 125 125A 150A TS250HU FMU 250 160A TS250NU FMU 250 160A TS250HU FMU 250 200A TS250NU FMU 250 200A 250A TS250HU FMU 250 250A TS250NU FMU 250 250A 300A TS400HU FMU 400 300A TS400NU FMU 400 300A TS400HU FMU 400 400A TS400NU FMU 400 400A TS800HU FMU 800 500A TS800NU FMU 800 500A TS800HU FMU 800 600A TS800NU FMU 800 600A TS800HU FMU 800 800A TS800NU FMU 800 800A 200A 400A 50 50 50 100 100 100 35 35 35 65 65 65 10 10 14 14 18 20 10X 5-10X 5-10X 500A 800AF HU Series (High Interrupting) 40A 80A 250AF UL Interrupting Rating (kA) 240V NU HU 600A 50 100 35 65 18 25 5-10X 800A TD/TS Series Circuit Breakers (ATU) Frame Size Amp Rating UL Interrupting Rating (kA) 240V NU HU 480V NU HU 600V NU HU 50 35 10 Magnetic Trip Setting 400AF TS250NU ATU 250 160A TS250HU ATU 250 200A TS250NU ATU 250 200A 250A TS250HU ATU 250 250A TS250NU ATU 250 250A 300A TS400HU ATU 400 300A TS400NU ATU 400 300A TS400HU ATU 400 400A TS400NU ATU 400 400A TS800HU ATU 800 500A TS800NU ATU 800 500A TS800HU ATU 800 600A TS800NU ATU 800 600A TS800HU ATU 800 800A TS800NU ATU 800 800A 200A 400A 50 100 100 35 65 65 14 18 20 5-10X 5-10X 500A 800AF NU Series (Normal Interrupting) TS250HU ATU 250 160A 150A 250AF HU Series (High Interrupting) 600A 50 100 35 65 800A www.franklin-controls.com | 1.800.962.3787 18 25 5-10X CIRCUIT BREAKERS Technical Information Application Circuit Breakers for 400Hz Networks When circuit breakers are used at high frequencies, the breakers are required to be derated due to increased resistance of the copper sections resulting from the skin effect produced by eddy currents at 400Hz. • Standard production breakers can be used with alternating currents with frequencies other than 50/60Hz when appropriate derating coefficients should be applied. Thermal Magnetic Trip Thermal trip: From the data shown below, the tripping threshold of the thermal element (ln) decreases as the frequency increases because of the reduced conductivity of the materials and the increase of the associated thermal phenomena. Rated current (A) at 400Hz= K1x rated current (A) at 50/60Hz. Instantaneous trip: The magnetic threshold increases with the increase in frequency. Instantaneous current (A) AT 400Hz= 2x Instantaneous current (A) at 50/60Hz Thermal Magnetic Trip Units TD and TS Series Performance Table at 400Hz Rated current (A) In at 400Hz Multiplier factors (K1, K2) MCCB MCCB Style K1 (Thermal trip units) K2 (Magnetic trip units) 15 0.8 2 20 0.8 2 30 0.8 2 40 0.8 2 0.8 2 0.8 2 50 TD125NU, TD125HU 60 FTU FMU 80 0.8 2 100 0.8 2 125 0.8 2 150 0.8 2 160 0.8 2 175 0.8 2 200 TS250NU, TS250HU 225 250 300 350 TS400NU,TS400HU FTU FMU ATU 0.8 2 0.8 2 0.8 2 0.8 2 0.8 2 2 400 0.8 500 0.8 2 600 0.8 2 0.8 2 0.8 2 700 TS800NU, TS800HU 800 *K1x multiplier factor of rated current (ln) K2-multiplier factor of instantaneous current due to the induced magnetic fields FTU-Fixed Thermal and magnetic trip unit FMUx-Adjustable thermal and fixed magnetic trip unit ATUx-Adjustable thermal and magnetic trip unit CIRCUIT BREAKERS BREAKER BO NEMA 3R Enclosed Circuit Breaker 125-800AF NEMA Rated Enclosed Breaker for Harsh Environments Simplified product range AF: 125, 250, 400, 800 Ampere range: 15A ~ 800A Superior technology results in high performance Cerus TD and TS circuit breakers provide superior performance in a compact package, with adjustable thermal trip settings and magnetic trip settings for ultimate flexibility Advanced arc quenching technology ensures excellent trip performance and long life Standardized internal accessories are interchangeable on all models and are field or factory installed Accessories mount on right or left side to simplify panel wiring Perfect for main disconnect applications Variable accessories Common use of electrical auxiliaries Motor operator Plug-in kit Terminals Communication module Cerus support & service Live tech support Made in USA Same day shipping 5 year warranty World class customer service www.franklin-controls.com | 1.800.962.3787 High Interrupting Capacity TS800HU TS400HU TS250HU TD125HU TS800NU TS400NU TS250NU TD125NU Rated current (A) 800A 400A 250A 125A CIRCUIT BREAKERS Ordering Information *Please refer to page 92 for Molded Case Circuit Breaker part numbers TD/TS Series Accessories Alarm & Auxiliary Switches Description Part Number Alarm Switch for TD/TS Series MCCB AL-TD/TS Auxiliary Switch for TD/TS Series MCCB AX-TD/TS Under Voltage Trip, UVT Control Voltage Part Number AC/DC 24V UVT-24V AC/DC 48V UVT-48V AC/DC 110~130V UVT-120V AC/DC 200~240V/DC 250V UVT-230V AC/DC 380~440v UVT-400V AC/DC 440~480v UVT-480V Shunt Trip, SHT Control Voltage DC 12V SHT-12VDC AC/DC 24V SHT-120V AC/DC 48V SHT-230V AC/DC 110~130V SHT-24V AC/DC 220~240V/DC250V SHT-48V AC/DC 380~500V SHT-480V Enclosures AF Part Number Part Number 125AF CER1-TD125CB-ENCL 250AF CER1-TS250CB-ENCL 400AF CER1-TS400CB-ENCL 800AF CER1-TS800CB-ENCL CIRCUIT BREAKERS Breaker Box Dimensions CER1-TD125CB-ENCL 7.283 5.300 4.143 MTG 9.623 MTG 12.923 FRONT VIEW SCALE 1/3 RIGHT VIEW SCALE 1/3 BACK VIEW SCALE 1/3 Ø1.750 KNOCKOUT (x2) Ø 1.125 KNOCKOUT (x2) BOTTOM VIEW SCALE 1/3 CER1-TS250CB-ENCL 5.300 12.240 8.000 MTG 23.850 16.000 MTG Ø .250 LOCKOUT FRONT VIEW SCALE 1/5 Ø 2.500 KNOCKOUT (x2) Ø1.500 KNOCKOUT (x2) BOTTOM VIEW SCALE 1/5 www.franklin-controls.com | 1.800.962.3787 RIGHT VIEW SCALE 1/5 BACK VIEW SCALE 1/5 CIRCUIT BREAKERS Breaker Box Dimensions CER1-TS400CB-ENCL 6 1/2 MTG. 8 3/4 3/8 THRU 25 MTG. 37 1/16 OD FRONT VIEW SCALE 1/3 RIGHT VIEW SCALE 1/3 BACK VIEW SCALE 1/3 11 11/16 OD BOTTOM VIEW SCALE 1/3 CER1-TS800CB-ENCL 16 109 16 10 MTG. 421 16 30 MTG. FRONT VIEW BOTTOM VIEW RIGHT VIEW BACK VIEW