Code of Practice 615 Issue 4 March 2015 Substation, Circuit and Plant Identification Contents 1 Scope 2 General 3 Definitions 4 Substation Names 5 GSP, BSP and Primary Substations, and Associated Networks 6 Distribution Networks 7 Pole Mounted Equipment 8 Circuit Labelling 9 Documents Referenced 10 Keywords Substations and Associated Appendices A to H Authorised for issue by the Technical Policy Panel © 2015 Electricity North West Limited All rights reserved The copyright of this document, which contains information of a proprietary nature, is vested in Electricity North West Limited. The contents of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced, either wholly or in part, in any way whatsoever. It may not be used by, or its contents divulged to, any other person whatsoever without the prior written permission of Electricity North West Limited. Electricity North West Limited. Registered in England & Wales. Registered No. 2366949. Registered Office: 304 Bridgewater Place, Birchwood Park, Warrington, WA3 6XG Amendment Summary Amendment No. Date 0 Brief Description and Amending Action Issue 1 10/12/99 CP615 - New Issue 1 Prepared by: DSD Issue 1 25/04/01 0 31/01/06 Authorised by: Clause 4.10 (c) added. Page E2 added – examples of 33kV teed transformers and feeders. Typographical error corrected on Page A1. Prepared by: DSD Issue 2 Authorised by: Detail added to labelling of LV distributor fuseways at section 6.8. Other revisions and clarifications. Rebadged United Utilities. Prepared by Peter Leather 0 02/03/07 Approved by the Technical Policy Panel and signed on its behalf by Simon Rushton: Issue 3 Merged with EPD601 Clarifications and other minor amendments. Prepared by Peter Leather 1 08/12/10 Approved by the Technical Policy Panel and signed on its behalf by Simon Rushton: Issue 3 Requirement to show highest voltage on substation nameplate removed (4.10). Numbering of ways of LV distribution fuseboards clarified (6.8.1). Additional requirement for marking the numbers of new link-boxes (6.8.5.1). Prepared by Peter Leather Approved by the Technical Policy Panel and signed on its behalf by Paul Whittaker. 0 12/03/15 Issue 4 Clarification for naming substations associated with generating sites added in section 4.11. New template applied. Prepared by Peter Twomey Approved by the Technical Policy Panel and signed on its behalf by Paul Whittaker. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page i of i SUBSTATION, CIRCUIT AND PLANT IDENTIFICATION 1. SCOPE 1.1 This Code of Practice (CP) describes the method of naming and labelling substations, circuits and plant that form part of the distribution network operated by Electricity North West Limited, hereinafter referred to as Electricity North West, and covers all voltages. 1.2 EPD601 – Substation, Plant and Circuit Identification and CP615, Issue 2 have been merged to form this current issue, which supersedes both the former documents. 2. GENERAL 2.1 Clear and unambiguous naming and labelling is a major factor in reducing human error switching incidents on the Electricity North West distribution Network (Network). 2.2 This CP applies to all substations, plant and apparatus comprising the Network. This CP is not intended to be retrospective, but where work is being done on the network, the opportunity shall be taken to make modifications that will apply this policy to existing substations, plant and apparatus. 2.3 It is recognised that there may be technical or operational reasons that make noncompliance with this CP desirable in some circumstances or that some unusual circuit arrangements are not adequately covered. In these cases the proposed arrangements shall be agreed, in writing, with the Network Planning Policy Manager, Network Strategy. 2.4 All substations, circuits and plant installed by third parties for adoption by Electricity North West shall be labelled in accordance with specific written instructions from Electricity North West in accordance with this CP. 2.5 All diagrams in the attached appendices are for illustrative purposes only. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 1 of 12 3. DEFINITIONS GSP Grid Supply Point (a substation shared with NGET, at which the Network is connected to that of NGET) BSP Bulk Supply Point (a substation, with 132kV to lower voltage transformers) NGET National Grid Electricity Transmission CEGB Central Electricity Generating Board Primary Substation 33kV to lower voltage substation Distribution Substation 11 or 6.6kV to 400/230V substation or 11kV to 6.6kV substation Network The electricity distribution network, owned and operated by Electricity North West. Switching Station Substation, as defined by the Electricity Safety, Quality and Continuity Regulations 2002, containing switchgear, but no power transformer MAMS Master Asset Management System PMT Pole-Mounted Transformer (not a substation within the definition of the Electricity Safety, Quality and Continuity Regulations 2002). 4. SUBSTATION NAMES 4.1 One name shall be selected and used through all stages of development. It should not be easily confused with others on the same network and should preferably assist in the location of the substation. 4.2 The name shall be allocated as soon as the site is fixed. The name, ten-figure grid reference and MAMS reference shall be added to a central index and used without variation from thereon. 4.3 The use of company names for substations shall be avoided, wherever there is a practicable alternative, which, nevertheless, provides sufficient indication of the location. 4.4 Where a substation is replaced at the same site, the existing site reference in MAMS shall continue to be used throughout. No new site record shall be created in such cases. However, an exception might arise in the case of a GSP and, in such circumstances, agreement shall be obtained from the Regional Control Manager, NGET as to how the transition will be managed. It might also be appropriate to inform and consult the System Development and Planning Manager, the Operations and Maintenance Strategy Manager and the Network Operations Centre Manager, NGET. 4.5 Where a substation comprises several adjacent but separate buildings and compounds, they shall all have the same name. For example, if in Anytown, there are on one site, or on a number of adjacent sites, 132kV sealing ends and disconnectors, 132/33kV transformers, 33kV switchgear, 33/11kV transformers, 11kV switchgear, an 11kV/LV transformer and a LV distribution fuseboard, all this equipment shall be regarded as forming parts of one substation, to be named Anytown BSP. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 2 of 12 4.6 The designation ‘GSP’ is reserved for substations shared with NGET. 4.7 A BSP substation name shall take the name of the area it serves which shall, where practicable, represent the localities of the associated primary substations. 4.8 A primary substation shall take the name of the locality it serves. 4.9 Subject to sub-section 4.3, a distribution substation shall take the name of the road or street in which it stands, or from which access is obtained. Additional substations in the same street shall be uniquely named; for this purpose, the addition of “Switching Station” shall not make sufficient difference. 4.10 Substation nameplates shall be in accordance with ES356 and shall contain the following information: 4.11 (a) Substation name with suffix GSP, BSP, Primary or Switching Station. No suffix is required for sites with HV/LV power transformers and no voltage above 11kV. (b) Substation MAMS number. A switching station or distribution substation that is dedicated to the connection of a generator shall have the relevant suffix from the table below to indicate the type of generation. Generation Biomass & energy crops (not CHP), Landfill* gas, sewage gas, biogas (not CHP) Hydro Large CHP (>=50MW) Medium CHP (>=5MW, <50MW) Mini CHP (<1MW) Offshore wind Onshore wind Other generation Photovoltaic Small CHP (>=1MW, <5MW) Tidal stream & wave power Suffix BIO GEN Hydro CHP CHP CHP OSWF WF GEN PV CHP Tidal 12/3/15 *Landfill not required if already in substation name 5. GSP, BSP AND PRIMARY SUBSTATIONS, AND ASSOCIATED NETWORKS (132kV & 33kV) The Table in Appendix A and drawings in Appendices B, C, D & E are associated with this section. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 3 of 12 5.1 132/33kV Open Type Switchgear In the case of open type 132/33kV switchgear the principles of CEGB Operation Memorandum No. 5, a copy of which is available in the electronic library, shall generally be followed. In this system each item of switchgear is allocated a code which must be displayed at the equipment and at each operating handle or control switch. Examples are described in the Table in Appendix A and are shown schematically in Appendices B & C. 5.2 132kV Open Type Busbars 132kV busbar numbering and nomenclature shall be based on CEGB Operation Memorandum No 5 and shall include the following: 5.2.1 Nominal busbar voltage eg 132kV; 5.2.2 Busbar designation (Main Busbar, Reserve Busbar, etc.); 5.2.3 Busbar section number (1, 2, 3, etc.), eg 132 kV Main Busbar 2; 5.2.4 Sections of busbars of the same nominal voltage and busbar designation shall be numbered consecutively from one end of the substation to the other. Main and reserve busbars shall have corresponding numbering. 5.2.5 In the case of substations where one section of one busbar is common to two sections of an associated busbar, the former shall bear the numbers of both corresponding sections of the latter, eg: 132kV Main Busbar 1; 132kV Main Busbar 2; 132kV Reserve Busbar 1/2. 5.2.6 The busbar section number shall be omitted in those cases where the busbar is a single busbar having no sectioning facilities, eg 132 kV Main Busbar. 5.2.7 In the case of a closed mesh type substation the corners of the mesh shall be numbered consecutively, anti-clockwise when viewed from above. 5.3 132kV Indoor Gas Insulated Switchgear (GIS) 5.3.1 The numbering convention for 132kV indoor gas insulated switchgear shall be based on CEGB Operation Memorandum No 5 and is shown in Appendix D. 5.3.2 A combined three-position disconnector and earthing switch shall be denoted by the suffix “ED”. 5.4 33/11/6.6kV Metalclad Busbar Designation 5.4.1 The 33kV busbar shall be taken as the reference point and sections of busbars lettered in order from left to right when facing the front of the switchgear. Provision shall be made in the lettering, for a further section to the left, only when this is a firm future requirement. 5.4.2 Bus-couplers shall be designated by the busbar identification, eg ‘Bus-coupler A’ 5.4.3 Bus-sections shall be designated by the two busbars connected eg ‘Bus-section A-B’. 5.4.4 Busbar interconnectors shall be designated by the two busbars interconnected e.g. ‘Interconnector A-B’ and are defined as a connection other than by busbar. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 4 of 12 5.4.5 Double busbars shall be designated ‘Main’ and ‘Reserve’ these terms being added where appropriate to the names of bus sections or interconnectors. 5.5 Transformer Designation 5.5.1 Transformer identification shall be by number using ‘GT1’, ‘GT2’ etc for transformers from 132kV to a lower voltage, ‘T11’, ‘T12’ etc for transformers from 33kV to a lower voltage and ‘Network T1’, ‘T11 Auxiliary’ etc. for transformers supplying 400/230V in primary substations. 5.5.2 Linking transformers, between 11kV and 6.6kV in the HV network, shall be numbered T21, T22 etc. 5.5.3 The number selected shall as far as possible reflect the section of busbar to which the transformer is connected, ie: GT1 on Section 1 or T11 on Section A; GT2 on Section 2 or T12 on Section B; GT3 on Section 3 or T13 on Section C. 5.5.4 Where it is not possible to apply the principles described in 5.5.3 then every effort shall be made to make the lower voltage side conform. 5.5.5 Where an additional transformer is connected to a section of busbar it is preferred that an odd-numbered transformer is connected to Section 1/A or Section 3/C busbars and an even-numbered transformer to Section 2/B or Section 4/D busbars etc. 5.5.6 Equipment directly associated with a transformer shall be given the transformer designation eg: T11 auxiliary transformer T11 Auxiliary; T11 fault throwing switch T11 Fault Thrower; GT1 neutral resistor GT1 NER. 5.5.7 Transformer cables shall not be crossed solely to maintain switchgear layouts. To avoid crossing cables it is preferable to maintain standard busbar nomenclature with nonstandard transformer designations. 5.6 Feeder Transformers 5.6.1 At the feeding end (or higher voltage end) the designation shall be by the remote substation name and the transformer designation. 5.6.2 For a teed circuit, the designation at the feeding end shall be the remote substation names, each, where applicable with its transformer designation, separated by ‘/’. Where both downstream sites have feeder transformers the transformers shall, where practical, have the same number. 5.6.3 At the transformer end, the transformer number and designation only are required (even if the circuit is teed). 5.6.4 The preference for selection of transformer numbers is described in sub-sections 5.5.3 to 5.5.7. 5.6.5 The use of circuit numbers in addition to names is permitted, as in the former Manchester Area, B567 etc,. The circuit number shall precede the name. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 5 of 12 5.7 Two-ended Circuits 5.7.1 A simple circuit shall be designated by the name of the remote substation. Where parallel circuits exist, they shall be distinguished by “No 1”, “No 2” etc added to the name, preferably following the rules for transformer number selection at the receiving end, ie circuit No 1 connected to Main Busbar 1 or Section A busbars, circuit No 2 connected to Main Busbar 2 or Section B busbars etc, where separate busbars exist. 5.7.2 The use of circuit numbers in addition to names, as in the former Manchester Area, B567 etc, is permitted. The circuit number shall precede the name. 5.8 Teed Circuits Teed circuits shall be labelled to identify the remote ends. Therefore for a three-ended circuit with substations A, B and C the labelling will be as follows: At end A B/C; At end B A/C; At end C A/B. Substations shall be in alphabetic order. 5.9 12/3/15 Spare Units Spare switch units shall be uniquely numbered within each substation and detail their designation, eg Spare No 1 to capped end. 5.10 Single Panel Switchboards and Busbar Cable-boxes 5.10.1 A single panel switchboard shall be labelled with the name of the substation or equipment connected to the cable box of the switch unit . 5.10.2 If the single panel switchboard includes an incoming earth switch then the switch shall be designated by the name of the feeding substation followed by a suffix ‘Earth Switch’ or ‘ES’. If a teed configuration exists the designation shall be as described in sub-sections 5.6 and 5.8 followed by the suffix ‘Earth Switch’ or ‘ES’. 5.10.3 A busbar cable box shall be designated by and labelled with the name of the remote substation or equipment connected to it. 5.11 Series Reactors A reactor connected as a busbar interconnector shall be labelled ‘Reactor A-B’ etc. Where a reactor is connected in series with a feeder or transformer the associated switchgear shall be labelled with the feeder or the transformer designation, the reactor itself being labelled ‘Reactor’ with the feeder or transformer designation added. 5.12 Relay/Control Panels Relay/Control panels shall be in the same order and preferably the same orientation as the associated switchgear. 5.13 Outgoing Circuit Names The rules for the selection of outgoing circuit names for 11/6.6kV circuits shall be in accordance with Section 6. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 6 of 12 6. DISTRIBUTION SUBSTATIONS AND ASSOCIATED NETWORK (11kV, 6.6kV & LV) Drawings in Appendices F & G are associated with this section. 6.1 Transformer Designation 6.1.1 The 11/6.6kV switch controlling a local network transformer shall be labelled ‘T1’, ‘T2’ etc. If the 11/6.6kV switch controls a consumer’s transformer it shall be labelled ‘Consumer T1’, ‘Consumer T2’ etc. 6.1.2 Where a transformer is feeding the network and a consumer it shall be labelled as a network transformer as described in clause 6.1.1. 6.1.3 Each transformer on a single site shall have a unique number, eg where a substation contains a network and consumer transformer they shall be uniquely identified, eg: Network T1; Consumer T2. 6.2 Feeder Transformers 6.2.1 At the feeding end (or higher voltage end) the designation shall be by the remote substation name and the transformer number. For a teed circuit, the designation at the feeding end shall be the remote substation names, with, where applicable, the transformer designation, separated by ‘/’. (See Appendix F.) 6.2.2 At the transformer end, the transformer number and designation only are required i.e. if the transformer feeds the network then it shall be labelled ‘Network T1’, or if the transformer feeds a consumer it shall be labelled ‘Consumer T1’. 6.2.3 If the transformer is connected locally to switchgear that includes an incoming earth switch then the switch shall be designated by the name of the feeding substation followed by the suffix ‘Earth Switch’ or ‘ES’. For a teed circuit, the designation shall be as described in sub-section 6.1.1, followed by the suffix ‘Earth Switch’ or ‘ES’. 6.3 HV Circuits 6.3.1 A simple circuit shall be designated by the name of the remote substation. Where parallel circuits exist, they shall be distinguished by “No 1”, “No 2” etc added to the name, preferably following the rules for transformer number selection at the end nearest to the source, eg feeder No 1 connected to Section A busbars, feeder No 2 connected to Section B busbars, where separate busbars exist. 6.3.2 The use of circuit numbers in addition to names, as in the former Manchester Area, F1234, L789 etc, is permitted. The circuit number shall precede the name. 6.4 Teed Circuits Teed circuits shall be labelled to identify the remote ends. Therefore for a four ended circuit with substations A, B, C and D the labelling will be as follows: CP615.doc At end A B/C/D; At end B A/C/D; At end C A/B/D; Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 7 of 12 At end D A/B/C. Substations shall be in alphabetic order. 6.5 12/3/15 Spare Units Spare switch units shall be uniquely numbered within each substation and detail their designation e.g. Spare No 1 to capped end. 6.6 Busbar Cable Boxes A busbar cable box shall be designated by and labelled with the name of the remote substation or equipment connected to it. 6.7 Multi-Switchgear Sites 6.7.1 On sites containing more than one non-extensible ring main unit or switchboard each unit or switchboard shall carry the substation name and be lettered in order from left to right when facing the front of the switchgear e.g. Unit A, Unit B. This is shown diagrammatically in Appendix G. 6.7.2 The number selected for any local transformer shall reflect the unit to which the transformer is connected, ie: Network T1 on Unit A; Network T2 on Unit B; Network T3 on Unit C. 6.7.3 Where additional transformer(s) are connected the principles of section 5.7 shall be followed. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 8 of 12 6.7.4 Switchgear interconnectors shall be designated by the unit they are connected to, ie: At Unit A ‘Interconnector A - B’; At Unit B ‘Interconnector B - A’; ‘Interconnector B - C’; ‘Interconnector C - B’. At Unit C 6.8 LV Distributor Ways 6.8.1 All 400/230V distributors, terminated at substation fuseboards, feeder pillars, including street pillars, and fuse-cabinets, shall be labelled with the following details: a) way number (minimum character height 10mm); b) circuit size, eg 3c 185 XC, 4w 0.1; c) fuse rating (as determined from CP331); and d) description, as sub-section 6.8.2 or 6.8.3, as appropriate. minimum character height 6mm Ways shall be numbered 1, 2, 3, etc. from left to right. The numbering shall include incoming transformer units (Where a transformer unit is mounted above the outgoing fuseways, it shall be way number 1.), any bus section ways and any separate way provided for the connection of a mobile generating set. Where a short length with increased conductor section is used immediately from a substation (and no significant amount of load is connected to it along its length), the circuit size shall be taken as that of the principal cross-section of the distributor. In accordance with CP331, sub-section 2.6, this is the size to be used in determining the fuse rating. 6.8.2 Interconnected Distributor An interconnected distributor shall be designated by the main route of the distributor (ie road name etc) and equipment at the point of interconnection, eg link box, feeder pillar or substation. (See Appendix H.) Where an equipment identification number is used, this number shall be included in the description. 6.8.3 Radial Distributor A radial distributor shall be designated by the route that the distributor takes and shall indicate, eg where practicable the side of the road the feeder takes - “Globe St (Odd Numbers)” - and, where appropriate, specific customer exit points - “Supermarket, East Mall, via Ground Floor”. 6.8.4 Spare Ways Spare ways shall be clearly identified within each substation and include detail of their designation, eg Spare No.1 - Caution - Shorted capped end. (See EPD283, sub-section 4.2.2.) 6.8.5 Link Boxes and Street Pillars CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 9 of 12 8/12/10 6.8.5.1 Each link box and free standing pillar (ie a pillar not comprising part of a substation) shall be given a unique number. Each link box number shall be indelibly and clearly marked on the bell-cover and each feeder pillar number on the inside and outside of the door. In addition, each newly installed link-box shall have its number indelibly and clearly marked on the fixed surround of the link-box, such that it may be easily read, with the bell-cover in position. This is particularly important, where link-boxes are in close proximity. 8/12/10 6.8.5.2 Each circuit of a link box shall be designated by a letter - A, B, C etc in a clockwise direction (when viewed from the top of the link box). Each circuit shall be lettered on the bell cover. The bell cover shall also be marked with (an) arrow(s) pointing to the kerb(s), or with a yellow triangle which corresponds to a yellow triangle on the side of the chamber. 6.8.5.3 Way labels may also be marked with the way letters. 6.8.5.4 Examples of marking for different street arrangements is shown in Figure 1 below. Footpath A B X3271 D C Footpath A Carriageway D Carriageway X3272 B C Footpath Footpath Carriageway Carriageway A B X3273 D C Footpath Carriageway Carriageway Figure 1 Examples of Link-box Markings 7. POLE-MOUNTED EQUIPMENT The drawing in Appendix G is associated with this section. 7.1 General Although this section applies primarily to 11/6.6kV equipment the general principles shall also be applied to 33kV equipment. 7.1.1 Circuits feeding overhead lines shall be designated as follows CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 10 of 12 7.1.1.1 Where the overhead line goes to a ground mounted substation this shall be used to identify the circuit, whether or not there are any PMTs connected to the line. 7.1.1.2 Where the overhead line does not go to a ground mounted substation the first pole mounted transformer on the line shall be used to identify the circuit. 7.1.1.3 Where the first pole mounted transformer is at or beyond the position of the first spur the overhead line shall be identified as a teed circuit, eg, where A is the first PMT on the main line and B is the first PMT on the spur line, the circuit would be identified as: A/B. 7.1.2 Where pole mounted switchgear is situated close to a substation it shall be named with the name of the substation, followed by the switchgear type. 7.1.3 All pole mounted equipment situated in one locality shall carry the same name and a suffix to identify the equipment type. The name should not be easily confused with other names on the system and should preferably assist in the location and identification of the equipment. 7.1.4 If more than one unit of the same switchgear is situated in the same locality then a suffix number shall be added. 7.1.5 Where equipment identification numbers are used in addition to the name this system can be continued in addition to the above standard. 7.1.6 Pole mounted equipment shall be identified by a suitable label, in accordance with ES400N1, fixed to the pole. 7.2 Pole Mounted Transformer A transformer name shall include the suffix ‘Transformer’ or ‘PMT’, eg Home Farm PMT. 7.3 Switchgear Types of pole-mounted switchgear shall be identified by the use of the appropriate abbreviations listed in Section 8. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 11 of 12 8. CIRCUIT LABELLING 8.1 Circuit labels shall state in full the circuit name. sufficient to enable the label to be clearly legible. The size of the lettering shall be The only permissible abbreviations are: For equipment descriptions: Air Break Switch Auto Recloser Auto Sectionalising Links Auxiliary Bottle End Bulk Supply Point Capped End Earthing Disconnector Earth Switch Feeder Pillar Fuses Gas Auto Recloser ABS AR ASL Aux BE BSP CE ED ES FP F GAR Gas Sectionaliser Gas Vacuum Recloser Grid Supply Point kilovolt Links Link Box Overhead Pole-Mounted Transformer Sectionaliser Substation Switching Station For descriptions: Avenue Buildings Close Cottage Cottages Court Crescent Drive East Estate Farm Garden(s) Generator Green Headquarters Higher Hospital House Industrial Ave Bldg Cl Cott Cotts Ct Cres Dr E Est Fm Gdn(s) Gen Grn HQ Hr Hosp Hs Ind Landlord Lane Lower North Number(s) Park Place Reservoir Road Saint South Square Street Station Terrace Village Walk West GSect Auto GVR GSP kV L LB O/H PMT Sect S/S Sw Stn locational L/Lord Ln Lr N No(s) Pk Pl Res Rd St S Sq St Stn Terr Vill Wa W 8.2 The circuit designations in MAMS etc. shall be character for character the same as the circuit designation. In situations where the number of characters available in MAMS is exceeded the circuit name can be abbreviated but shall still reflect the circuit name. 8.3 Circuit labels shall be attached to the plant prior to the commissioning of the circuits. 8.4 The labels shall generally be in accordance with ES356 and ES400N1, shall be easily legible, durable and securely fixed to the equipment. Self-adhesive labels, such as “Dymo” tape, shall not be used in place of permanent labels. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 12 of 12 8.5 Where there is a passageway or working space at the rear of extensible switchgear, labels shall be fitted on the rear as well as on the front of the equipment. 8.6 Similarly, where rear access to a ring-main unit is required for cable jointing or circuit testing, labels shall be fitted on the rear as well as on the front of the equipment. Where the manufacturer provides a facility for additional circuit labels, eg on cable boxes, this shall be used. 8.7 Where a circuit number is used in addition to the circuit name the name shall follow the number. 8.8 In the case of 400/230 V equipment, and where standard sized labels cannot be used, it is acceptable to use non-standard sizes. Minimum character sizes shall be as shown in 6.8.1. 9. DOCUMENTS REFERENCED CEGB Operation Memorandum No.5 ES356 - Notices & Nameplates ES400N1 - Notices & Nameplates – Overhead Lines CP331 - Protection of LV Underground and Overhead Distributors and HV Protection of Distribution Transformers - Network Diagrams CP625 10. KEYWORDS Name; Designation; Transformer; Feeder; Substation; Circuit; Plant; Distributor CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page 13 of 12 APPENDIX A *00 *01 *02 *03 *04 *05 *06 *07 *10 *11 *12 *13 *14 *15 *16 *20 *21 *24 *25 *26 *28 *60 *61 *66 *69 Bus Coupler Bus Coupler Circuit Breaker Bus Coupler Earthing Switch Bus Coupler Main Busbar Disconnector Bus Coupler Reserve Busbar Disconnector *30 *31 *34 *36 *W0 *W1 *W4 *W6 Static Series Compensator or Series Reactor Class Reactor Circuit Breaker Reactor Earthing Switch Main Busbar Selector Disconnector (1st Choice) 2nd Reactor Circuit Breaker where 2 per Reactor Reserve Busbar Selector Disconnector (1st Choice) Circuit Breaker Disconnector (Busbar side) Main Busbar Selector Disconnector (2nd Choice) Reactor Tie Busbar Disconnector or Reserve Busbar Selector Disconnector (2nd Choice) *40 *41 *44 *45 *46 *47 *48 *49 *R0 *R1 *R4 *R5 *R6 *R7 *R8 *R9 Reactor/Capacitor Circuit Breaker Reactor/Capacitor Earthing Switch Reactor/Capacitor Disconnector Reactor/Capacitor Switch Disconnector *50 *51 *53 *55 *K0 *K1 *K3 *K5 Reserve Bus Section Main Bus Section Transformer High Voltage Side Lines Switch Disconnector Line Earthing Switch By-Pass Disconnector Line Disconnector Main Busbar Selector Disconnector Circuit Breaker Reserve Busbar Selector Disconnector Circuit Breaker Disconnector (Busbar Side) Transformer Circuit Breaker Transformer Earthing Switch Transformer By-Pass Disconnector Transformer Disconnector Main Busbar Selector Disconnector Switch Disconnector Reserve Busbar Selector Disconnector Main Bus Section Circuit Breaker Main Bus Section Earthing Switch Main Bus Section Disconnector (No. 1 side) Switching Disconnector. Mesh Opening Corner Disconnector Main Bus Section Disconnector (No. 2 side) Reserve Bus Section Circuit Breaker Reserve Bus Section Earthing Switch Reserve Bus Section Disconnector (No. 1 side) Reserve Bus Section Disconnector (No. 2 side) 33/25 kV *L0 *L1 *L2 *L3 *L4 *L5 *L6 *L7 *H0 *H1 *H2 *H3 *H4 *H5 *H6 *S0 *S1 *S4 *S5 *S6 *S8 *P0 *P1 *P6 *P9 Static Shunt Compensator Open Type Switchgear Numbering & Nomenclature (excluding Metalclad) Title CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited 132kV Page A1 of 2 *80 *81 *83 *84 *85 *86 Generator Circuit Breaker (where 2 per generator, main busbar) Generator Transformer Earthing Switch By-Pass Disconnector Generator Transformer Disconnector Main Busbar Selector Disconnector Generator Circuit Breaker where 2 per generator (reserve Busbar) or Switch Disconnector Reserve Busbar Selector Disconnector Circuit Breaker Disconnector (Busbar Side) *90 *91 *92 *93 *94 *95 *96 *97 Generators Transformer Low Voltage Side Transformer Circuit Breaker Transformer Earthing Switch Transformer Disconnector Main Busbar Selector Disconnector Switch Disconnector Busbar Selector Disconnector *T6 *M0 *MI *M2 *M3 *M4 *M5 *M6 *M7 * Denotes a sequence number. + This is a departure from CEGB Operation Memorandum No.5 See appendices B, C & D for illustrations of both numbering & nomenclature. For further information see CEGB Operation Memorandum No.5. CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page A2 of 2 APPENDIX B CP615.doc Whitepool Grid Supply Point SGT 1 SGT 2 181 281 183 Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited (GSP) 283 121B 121A 180 221B 221A 280 132kV Main Busbar 1 132kV Main Busbar 2 104 184 114 186 116 124 120 128 234 284 214 204 286 216 206 230 106 236 160 132kV Reserve Busbar 1 169 166 161A 105 161B 110 132kV Reserve Busbar 2 261B 261A 103 205 210 113 213 111 203 211 201 101 GT1 GT2 101 Page B1 of 1 Pendale 132kV Substation 1T1 103 105 2T3 * GT1 * GT2 2T4 Section A 104 106 101 113 1T4 132kV Main Busbar 1 132kV Reserve Busbar 1 2T1 1T3 1S4 1S0 111 Section B GT1 1S8 * GT1 * This is a departure from CEGB Op Memo 5. Figure 1 Examples of Switchgear Designations - Open-Type 132kV Switchgear APPENDIX C 132kV Main Busbar 2 204 206 132kV Reserve Busbar 2 205 Bredbury GSP 203 201 Hazel Grove Bredbury 101 113 Hazel Grove BSP 111 GT1 GT1 Earthing Transformer GT1 Indoor (Metalclad) 33kV Switchboard 33kV Figure 2 Examples of Switchgear Designations 132/33kV Transformer-Feeder CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page C 1 of 1 APPENDIX D CP615.doc 132kV Main Busbar 1 132kV Main Busbar 2 120 124 104 114 128 184 Issue 4 121A 131A 121B 12/03/15 PT CP615 © 2015 Electricity North West Limited 204 214 206 216 284 221A 221B 130 131B 106 116 186 132kV Reserve Busbar 1 166 161B 161A 101B 103 101A 261 111B 113 111A 281B 201B 181B 203 183 181A 280 210 205 Metal Switchgear Casing 281C 211C 201C 180 110 105 132kV Reserve Busbar 2 181C 111C 101C 169 286 211B 213 201A 281A 211A Feeder No. 2 Feeder No. 1 Page D1 of 1 GT1 SGT 1 Grid Supply Point (GSP) Figure 3 Examples of Switchgear Designations - 132kV GIS GT2 SGT2 APPENDIX E 132kV GT1 4.2 A ustin BSP Bus-Section GT1 Earthing Transformer GT1 NER GT1 Section A GT2 GT2 Earthing Transformer GT2 NER GT2 Section B A-B 33kV 33kV Commer No1 Bedford T11 T12 T14 Enfield T11 Commer No2 T14 T11 T12 No 1 No 2 4.1 A ustin BSP T11 Bus-Section A-B Section A T12 Section B 11kV Network T1 T14 T1 T11 Fault Thrower 5. Austin BSP Austin BSP No 1 Commer/ Daimler T11 Austin BSP No 2 Bedford Commer Bedford/ Daimler F T11 Daimler Enfield Bedford/ Commer Figure 4 Examples of Circuit Designation - 33kV Network CP615.doc Issue 4 12/03/15 PT © 2015 Electricity North West Limited CP615 Page E1 of 2 132kV GT1 Section A GT1 Ford BSP GT2 Bus Section A-B GT2 Section B 33kV 33kV Triumph/ Vauxhall Royce T12/ Norton T12 Morris/ Leyland T11/ Norton T11 T 11 Ford BSP/ Vauxhall T 11 Leyland 11kV T 11 Triumph T 12 T 11 33kV T 12 11kV Norton Ford BSP/ Leyland T11/ Norton T11 Morris T 12 Ford BSP/ Triumph T 12 33kV 11kV Royce Vauxhall 33kV Figure 5 Examples of Circuit Designation - 33kV Teed Circuits CP615.doc Issue 4 12/03/15 PT © 2015 Electricity North West Limited CP615 Page E2 of 2 APPENDIX F 33kV T12 T11 Nuttall (Primary) Bus-Section A-B T11 4. 11kV Close Ave T1 S e c ti o n A T12 Section B Wilson St No1 T1 Nuttall Primary No1 Wilson St No2 11kV Butcher Rd Giles Rd Nuttall Primary No2 Wilson St Nuttall Primary 11kV Nuttall Primary Close Ave T1 B u t c h T1 e r Mill St/ New Rd T1/ Oaks Rd Hope St T21 T1 3. Giles Rd John St Nuttall Primary Rd T1 T1 T21 New Rd T1 Close Ave John St Consumer T1 Giles Rd G T21 6.6kV Hope St M Mill St/ New Rd T1/ Butcher Rd T1 Ash Rd 2. Butcher Rd/ Oaks Rd/ New Rd T1 V O a k s 1. M i l l Smith Ave T1 T1St Rd to Ash Rd to Smith Ave Figure 6 Examples of Circuit Designation - HV Network CP615.doc Issue 4 12/03/15PT CP615 Page © 2015 Electricity North West Limited F1 of 1 APPENDIX G to Jones Paper Mill T2 James St S/S T1 M James St B James St A Consumer T2 Network T1 Interconnector B-A Interconnector A-B Walker St Benson Rd to Benson Rd to Walker St Figure 7 Example of 11kV Multi-Switchgear Site to Round St. Round St. Robson Lane Sw Stn Hillside Farm PMT/ Home Farm PMT Robson Lane GVR Located in close proximity to Robson Lane Switching Station Robson Lane ABS 100 Home Farm PMT 25 Hillside Farm PMT Row Lane SECT Figure 8 Example of 11kV Pole Mounted Equipment CP615.doc Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited Page G1 of 1 APPENDIX H CP615.doc John St. Fred St. Way 5 Way 4 Way 3 As subsection 6.8.3 Way 2 Way 1 Way 5 Way 4 Way 3 Way 2 Way 1 1 4c 0.3 OPEN High St to John St. S/S As subsection 6.8.3 4 3c 185 XC 400A John St. South / LB X3270 Charles St 1 X3270 4c 185 SAC 315A Ascot St./ LB X3270 Charles St Page H1 of 1 As subsection 6.8.3 Figure 9 Examples of LV Interconnector Labelling Way 5 Way 4 Way 3 Note: This diagram is for explanatory purposes only and does not comply with CP625. Port St. Way 2 Charles St. Link Box Way 1 Issue 4 12/03/15 PT CP615 © 2015 Electricity North West Limited 5 4c 0.3 400A John St North to Fred St. S/S