power line carrier coupling equipment for substations / switching

advertisement
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
POWER LINE CARRIER COUPLING EQUIPMENT
FOR SUBSTATIONS / SWITCHING STATIONS
1.
PURCHASER:
The Israel Electric Corporation Limited (IECo).
2.
NAME OF ITEM & PROJECT: Power line carrier coupling equipment for 161 kV
system.
3. LOCATION OF ITEM & PROJECT: IECo substations and switching stations.
4. SCOPE OF WORK:

Design, develop, manufacture, cooperate with others where necessary,
factory tests, supply all relevant electromechanical information necessary for
complete design for all purposes linked with proper operation as well as for
commissioning and maintenance, preserve, pack and furnish the Power line
Carrier Coupling Equipment (CE), delivery in Purchaser’s stores or sites,
test and verify equipment on site, provide technical guidance and
assistance, all in accordance with this Specification as detailed hereunder.

The coupling equipment system shall consist of Line Trap (LT), Coupling
Capacitor (CC), and associated accessories such as insulators (if any),
wiring, etc.

CE shall be installed on IECo substations/switching stations for
establishment of communication links operated over High Voltage Lines
(HVL) by Power Line Communication (PLC) technology.

CE shall be suitable for outdoor installation, and for connection to overhead
transmission line.

CE shall be complete with all accessories and appurtenances as specified
hereinafter.

CE shall be capable of withstanding electrical, mechanical and thermal
ratings of the specified systems.
All joints and connections shall be able to withstand the forces of expansion,
contraction, vibration, torsion, specified seismic requirements and
environmental conditions without damage, deformation, and malfunction.
Optimized arrangement is required to reduce installation space, installati on
time, provide ease operation, minimize maintenance and repair costs and
facilitate future additions and extensions.
- 1B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
4.1.
SPEC: STR-1377
ANNEXURE "B"
SCOPE OF SUPPLY / SERVICE:
The Contractor shall supply the following items:
4.1.1.
Item 1:
Power line carrier Coupling Equipment 161 kV, 2000 A, including: wide-band
Line Trap (LT) with inductance of 0.5 mH (defined at 100 kHz frequency),
high creepage distance Coupling Capacitor (CC) with 6000 pF rated
capacitance, isolators, accessories and appurtenances.
The rated frequency range (bandwidth) shall be 140 to 400 kHz.
Quantity:
2 units + 50% − 20%.
4.1.2.
Item 2:
Power line carrier Coupling Equipment 161 kV, 2000 A, including: wide-band
Line Trap (LT) with inductance of 1.0 mH (defined at 100 kHz frequency),
high creepage distance Coupling Capacitor (CC) with 6000 pF rated
capacitance, isolators, accessories and appurtenances.
The rated frequency range (bandwidth) shall be 87 to 500 kHz.
Quantity:
16 units + 50% − 20%.
4.1.3.
Item 3:
Power line carrier Coupling Equipment 161 kV, 2000 A, including: wide-band
Line Trap (LT) with inductance of 2.0 mH (defined at 100 kHz frequency),
high creepage distance Coupling Capacitor (CC) with 6000 pF rated
capacitance, isolators, accessories and appurtenances.
The rated frequency range (bandwidth) shall be 48 to 500 kHz.
Quantity:
11 units + 50% − 20%.
4.1.4.
Item 4:
Power line carrier Coupling Equipment 161 kV, 3150 A, including: wide-band
Line Trap (LT) with inductance of 0.5 mH (defined at 100 kHz frequency),
High creepage distance Coupling Capacitor (CC) with 6000 pF rated
capacitance, isolators, accessories and appurtenances.
The rated frequency range (bandwidth) shall be 140 to 400 kHz.
Quantity:
8 units + 50% − 20%.
4.1.5.
The quantities indicated above are not final. The IECo reserves the right to
purchase, during the Contract period, goods of a total value, which equals to
Contract value with deviation of plus 50% minus 20% with possibility to
alternate between items and quantities.
4.1.6.
In addition to the equipment the Contractor shall provide all technical data,
relevant drawings and other information as required in this Specification.
4.1.7.
All LT's(in items 1-4) can be mounted on the CC (preferred erection) or on
the insulators. In addition the Contractor shall provide the option for hanging
of 2000 A LT (items 1,2,3).
- 2B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
5.
TERMINAL POINTS & TERMINAL CONNECTION
5.1.
The Contractor is requested to propose the CE as a whole.
In case the Contractor has not in his production line one or more of the
required components, he can offer components manufactured by other
manufacturers.
The Contractor shall be responsible for the integration of all components
and will guarantee for the whole CE.
The list of subcontractors shall be approved by Purchaser.
5.2.
The Contractor shall use components and accessories manufactured in
Israel wherever possible.
5.3.
The Contractor shall be responsible for all equipment damage until time of
Purchaser equipment reception.
5.4.
The CE can be supplied only after approval of all type, special and routine
test reports.
6.
QUALITY ASSURANCE & QUALITY CONTROL
6.1.
General quality requirements
6.1.1.
In addition to the provisions of the General Conditions Annexure "A" "Contractor's Documentation" and Appendix N° 2 - "Procurement Quality
Requirements" the Contractor's Quality Assurance Program shall meet the
requirements described in ISO Standard 9001-2000.
6.1.2.
The Purchaser shall have the right to audit and comment on Contractor's
Quality Assurance System regardless of whether it was previously audited
by certifying agency or any other body.
6.1.3.
The Contractor shall be responsible for assuring that his subcontractor's
Quality Assurance/Quality Control Program, including their organizations,
procedures, personnel qualification etc., are approved and are consistent
with the specific requirements imposed by Purchaser in the Specification.
6.1.4.
An Inspection & Test Plan, including witness points and hold points, shall be
mutually agreed between the Purchaser and the Contractor immediately
after awarding the contract. Any subsequent alteration to this program shall
require the Purchaser's agreement, prior to start of any work affected by
these alterations.
6.1.5.
When subcontracting part of the works, the Contractor shall submit copies of
his unpriced orders to the subcontractor.
- 3B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
6.1.6.
Test and inspection certificates as required in the Specification and the
applicable standards, shall be submitted immediately following their issue.
The certificates have to be original, signed by the Contractor, and contain
actual measured values.
The generation of certificates, including those generated by Subcontractors
and sub-Bidders, shall bear no extra cost to Purchaser.
6.1.7.
Manufacturing shall not commence prior to respective drawing approval by
the Purchaser.
6.1.8.
Changes in the Purchaser's approved design are normally unaccepted.
However, should such changes become necessary on an exceptional basis,
the Contractor shall obtain the Purchaser's approval prior to introducing any
change.
6.1.9.
Any equipment which does not conform to drawings, specifications or other
purchase order requirements which never the less are considered by the
Contractor as "acceptable as is" or "for repair", shall be submitted to the
Purchaser for approval, with their recommended dispositions. All such nonconformances shall be approved by the Purchaser, shall be documented
and a copy of the approval shall accompany each shipment.
6.1.10.
Source inspection, including inspection of local manufacturing, shall be
conducted by proficient, approved organizations or individuals, using
documented procedures. Any such independent inspector shall be subject to
Purchaser's approval.
6.1.11.
All materials used in the manufacture of the equipment shall conform to the
Specification, approved drawings and accepted standards.
6.1.12.
The Contractor shall notify the Purchaser, without any undue delay, of any
defect, failure, malfunction or incompatibility in the equipment, or in similar
types of equipment, which shall have appeared, or discovered in the course
of the period, extending from the execution of the contract of supply until
three years after the expiration of warranty, in as much as it affects, or may
affect the use, performance, qualities, lifetime or safety of the equipment.
The notification shall be in writing and shall specify the nature of the defect,
failure, malfunction or incompatibility, any ramifications, stemming therefrom
and any relevant corrective measures, adopted or recommended by the
Manufacturer.
6.1.13.
The Purchaser shall have the right to be present in the equipment
manufacturing process (at least two times during the manufacturing), as far
as in the routing and acceptance tests performance.
6.2.
Interchangeability
Power line carrier coupling equipment of the same type and ratings shall be
interchangeable both electrically and mechanically with each other, and
when so interchanged shall perform their function equally well in every
respect.
- 4B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
7.
STANDARDS & CODES
7.1.
Unless otherwise specified all equipment shall be designed, manufactured
and tested in accordance with the requirements of the latest relevant
published standards of the International Electrotechnical Commission (IEC)
or local standards of the Manufacturer's country as amended up to date.
7.2.
All aspects, test, etc, not covered by the above mentioned standards, shall
be executed according to the latest published issue of official or otherwise
approved standards of the Manufacturer's country.
7.3.
All relevant standards shall be stated by Bidder. In the event of a variance
between the general requirements of the standards and particular
requirements of this Specification, the Specification shall take precedence.
7.4.
If after issuing this Specification some of the mentioned standards are
updated, amended, withdrawn or replaced with another ones, the impact of
these changed on the Specification will be subjected to agreements between
the Contractor and the Purchaser.
7.5.
The following standards are applicable in the relevant parts to the individual
components of the coupling equipment:
7.5.1.
 IEC 60353
Line traps for a.c. power systems
7.5.3.
 IEC 60358-1
Coupling capacitors and capacitor dividers - Part 1:
General rules
7.5.4.
 IEC 60358-2
Coupling capacitors and capacitor dividers - Part 2:
AC or DC single-phase coupling capacitor
connected between line and ground for power line
carrier-frequency (PLC) application
7.5.5.
 IEC 60071
Insulation co-ordination.
7.5.6.
 IEC 60721/3-4
Classification of environmental conditions.
7.5.7.
 IEC 60815
Guide for the selection of insulators in respect of
polluted conditions.
7.5.8.
 IEC 61462
Composite insulators – Hollow insulators for use in
outdoor and indoor electrical equipment.
7.5.9.
 IEC 62155
Hollow pressurized and unpressurized ceramic and
glass insulators for use in electrical equipment with
rated voltages greater than 1000V.
7.5.10.
 IEEE Std. 693
Recommended practice for seismic design of
substations.
7.5.11.
 ISO 9001-2000
Quality management systems.
7.5.12.
 ISO 17025
General requirements for the competence of testing
and calibrating laboratories.
7.5.13.
 ASTM A 123
Standard specification for zing coating (hot-dip) on
iron and steel hardware.
7.5.2.
- 5B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
7.5.14.
 ASTM B 579
Standard specification for electrodeposited coatings
of tin-lead alloy (solder plate).
7.5.15.
 ASTM B 580
Standard specification for anodic oxide coatings on
aluminum.
8.
TECHNICAL DOCUMENTATION
8.1.
General
All data, nameplates and descriptive materials shall be in English or
Hebrew. Dimension and weights shall be shown in metric units. All
descriptive materials (lists, instruction books, etc.) should be numbered and
dated for easy identification and reference purposes. Indicate for all
requirements, number of drawing, catalogues or other documents.
During the tender process, IECo, on its own discretion, may ask to receive
additional technical documents relevant to the bidder’s proposal. The bidder
will be obliged to submit the documents according to a specified time.
8.2.
Technical documents to accompany the proposal
The Contractor should submit with the proposal the following documents
and information in four (4) copies, and four (4) compact discs in pdf. format
(dwg. format for drawings):
8.2.1.
Questionnaire: All Clauses.
8.2.2.
Quality Assurance related documentation, according to the Appendix No.1:
"PROCUREMENT QUALITY REQUIREMENTS" (spec. No: Q – APP – 02)
should be submitted for information. Particularly the following:
 Certification of Approval of the Quality Assurance System according to
the ISO 9001 Standard given by an Authorized Inspection Agency.
 A list of Quality Assurance Standards and Quality Assurance Manual.
 Design control procedures.
 Quality plan during manufacture.
 Acceptance test procedures for materials and sub-assembles.
 Non-conformance and corrective action procedures.
 Qualification of Subcontractor's Procedure.
 List of qualified suppliers of the most important parts and components.
 A preliminary Inspection and Test Plant (I&T plan).
- 6B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
8.2.3.
SPEC: STR-1377
ANNEXURE "B"
Drawings and tests
 Dimension drawings giving principal dimensions.
 Description of the principles of operating of the CE under various
operating conditions.
 Drawing of cross section of the CE.
 Description and drawing of insulator from Manufacturer.
 Drawing of line and earth terminals.
 Drawing of nameplate.
 Construction, mode of operation, mounting, connection arrangement and
checking of the CE.
 "Line trap impedance versus" frequency chart for each item.
 Type and special tests reports (authority, number and date) for offered
type of LT, including test circuit, instruments used and description of
method, calibration certificate.
 Type and special tests reports (authority, number and date) for offered
type of CC, including test circuit, instruments used and description of
method.
 Example of routine test report for offered type of CE, including test circuit,
instruments used and description of method.
 Reliability, availability, maintainability and safety (RAMS) report (Appendix
№ 3).
 Customer list for the last five years, with sum for each year (type, rated
voltage, rated discharge current, number of units, date of supply,
Purchaser).
 A list of recommended special tools and instruments necessary for
assembling of the CE.
 A list of recommended spare parts (including total quantities) for the
amount of CE indicated in this Specification.
 A list of all parts which could wear out after expiration of the warranty
period, after 5 years and 10 years of operating according to Manufacturer
or users experience.
 General instruction book for storage, erection, operating and maintaining.
 Recommendations for transport on roads and on site.
 Recommendations for prolonged (2-3 years) storage before erection,
taking into consideration the specific conditions under clause 9.
 Details of shock indicator.
8.2.4.
A proposal not including the documents mentioned above can be rejected.
- 7B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
8.2.5.
Contractor may be required to send his representative to discuss and/or
explain parts of his proposal with IECo's representatives.
8.2.6.
All the drawings and information submitted with the proposal shall be final
drawings and final information approved by the Bidder.
8.2.7.
Evaluation of bidder's technical proposal
 All requirements in this Specification indicated by the symbol  are
compulsory requirements. In case Bidder’s proposal will not comply
with one of the compulsory requirements, his offer will be disqualified.
 For evaluation purposes the Bidder is requested to fill in, in the sammary
of Data, the offered data and parameters against Purchaser’s required
values as well as in the absence thereof, in the free columns of the right
hand side. A definite answer (yes or no) or appropriate comments shall be
given to all other requirements.
8.3.
Technical documents after notification of award
8.3.1.
After notification of award, Contractor shall within 30 (thirty) days of the date
of award, submit to the Purchaser for approval four (4) sets of prints and
four (4) compact discs in pdf. format (dwg. format for drawings) covering the
following information:
 Outline drawing of CE including all necessary details for mounting such
as fixing holes, size and material of primary and earthling terminals,
weight, permissible static and dynamic forces.
 Line and earth terminals details (material, shape, cross-section).
 Description and Manufacturer's insulator drawing.
 Schematic and detailed wiring drawings.
 Technical catalogs of CE.
 Nameplate drawing with all data fulfilled.
 Bill of materials.
 Shipping assembly drawing with overall size and weight.
 Final list of all subcontractors and sub suppliers including name, address
and a copy of their Quality Assurance Certificate.
8.3.2.
After notification of award, Contractor shall within 60 (sixty)days of date of
award, submit to the Purchaser four (4) sets of prints of Quality Assurance
Manual including a full description of Contractor's Quality Assurance
program.
Contractor shall furnish the following Quality Control documentation:
 Inspection and Test Plan included in Contractor's Quality plan.
 Quality Control Procedures.
- 8B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
 Testing procedures as per applicable standards.
 Non-conformance's procedures.
 List of sub-suppliers of the most important parts and components.
8.3.3.
Purchaser reserves himself the right to require all necessary additional data,
descriptions, drawings, etc. that may contribute in completing information
supplied by Manufacturer about the equipment.
8.3.4.
If the prints are returned by the Purchaser and stamped "approved except
as noted", Contractor shall make corrections per Purchaser's marking and
shall resubmit required copies of the correct documents as stated above.
8.3.5.
Routine test reports shall be submitted for approval 1 (one) month before
delivery, in four (4) copies.
8.3.6.
The shipment cannot be realized before test approval.
8.3.7.
Commissioning program shall be supplied for approval in four (4) copies,
three (3) months before delivery.
8.3.8.
Contractor is free to supply any additional information considered necessary
for clarifying various aspects of erection, operation, maintaining, checking,
etc.
8.3.9.
All documents and drawings shall be provide with:
 Purchaser name.
 Project name.
 Unit serial number.
 Purchaser's order number.
 Specification number.
 Supplier's order number.
9.
TECHNICAL REQUIREMENTS
9.1.
Environmental considerations & service conditions
9.1.1.
Climatic conditions:
 Long periods without rain, alternating with high humidity as experienced
in coastal or desert areas in this country.
 Permissible ambient air temperature:
Maximum: +50 °C.
Minimum: -5 °C.
Average value over a period of 24 hours not exceeds: +35 °C.
- 9B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
 Permissible humidity:
Low relative/absolute humidity: 4/0.003 %//g/ m³.
High relative/absolute humidity: 100/36 %//g/ m³.
 Low/high air pressure: 70/106 KPa.
 Rain intensity: 15 mm/min.
 Keraunic level (thunderstorm):
Maximum keraunic level: 4 lightning / km² year
Minimum keraunic level: 0.1 lightning / km² year
 Direct and continuous solar radiation for long period. Heating effects of
solar radiation: 1120 W/m².
 Maximum wind velocity measured 10 m above ground (bare area) at 3
sec duration considering a 50 years mean return period: 44 m/sec.
9.1.2.
Environmental conditions:
 Environmental parameters according to IEC 60721, 3-4.
 Severe atmospheric and industrial air pollution, dust, salt spray and
sandstorms.
 Permissible altitude over the sea level: 1000 m.
 Water from sources other than rain: spraying water and water jets with
water velocity 15 m/sec.
 Chemically active substances according to IEC 60721, Table 4-4C3.
 Mechanically active substances according to IEC 60721, Table 5-4S3.
 Dust (suspension): 15 mg/ m³.
 Dust (sedimentation): 40 mg/ m³.
 Sand: 1000 mg/m³.
9.1.3.
Seismicity on the site
 The seismic design of the CE shall be based on the seismic qualification
requirements stated in IEEE Std. 693.
 The required seismic qualification level shall be: moderate level.
9.1.4.
Acceleration during transportation
Vibrations and shocks (non stationary vibrations including shocks). The
expected accelerations on the equipment transported on roads to be
considered:
 Longitudinal: 2g.
 Transversal: 1.2g.
 Vertical: 1.2g.
- 10B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
9.1.5.
SPEC: STR-1377
ANNEXURE "B"
Other requirements:
The CE shall be vermin and bird proof
9.1.6.
System data for all items:
9.1.6.1.
Rated system voltage (line to line) (kV)
161
9.1.6.2.
Highest system voltage (line to line) (kV)
170
9.1.6.3.
Highest system voltage (line to ground) (kV)
9.1.6.4.
Maximum phase to ground voltage in case of
earth fault………………...…(kV)
9.1.6.5.
Rated frequency……………….……(Hz)
91
9.1.6.6.
Range of frequency variation……...(Hz)
50.5 – 47.2
9.1.6.7.
System neutral …………….……………
effectively earthed
9.1.6.8.
Fault duration (three phase fault, sec)…
1
9.1.6.9.
Line auto - reclosing policy……………
9.1.6.10.
51.19
171
Tree-phase, one shots
Insulation level of the equipment to be protected:
Basic Insulation Level – BIL (1.2/50µsec) (kV
peak)
750
One minute withstand voltage (50Hz)
r.m.s)
529
(kV,
9.1.7.
Special requirements for environmental protection
9.1.7.1.
Due to the severe environmental conditions to which the equipment may be
subjected during its service life, the following requirements for its protection
form an integral part of the Specification and are in addition to the standard
design and protective measures which the Manufacturer would normally
invoke for these conditions:
9.1.7.2.
All aluminum components shall be fabricated from grades of aluminum
which show resistance to salt spray and moist conditions; e.g., Al-Mg base
alloys.
Al-Cu alloys are not acceptable. After fabrication, all aluminum components
shall be anodized according to ASTM B 580 Type A.
9.1.7.3.
All copper or copper alloy components shall be electrolytically tinned
according to ASTM B 579 Service Condition SC4.
9.1.7.4.
Bolts, nuts and washers as well as components such as springs, pins and
those for which a tight maintained dimensional tolerance is required shall be
made of stainless steel. The preferred stainless steel is an austenitic grade;
however, if physical requirements are overriding, other stainless steel
- 11B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
grades will be acceptable.
Austenitic grade will be subject to a solution quench. Prior to being placed
into service all stainless steel components will be cleaned and passivated.
9.1.7.5.
When dimensionally and functionally allowable, all structural support and
associated steelwork of the equipment shall be hot-dip galvanized according
to ASTM A 123. The thickness of the zinc shall be at least 100µm on
average, but the minimum thickness shall be not less than 90µm.
If dimensional or functional requirements do not allow hot-dip galvanizing,
steel parts will be electrolytically zinc plated to a minimum measured
thickness of 20µm.
9.1.7.6.
Components such as sleeves or bushings which may be fabricated having
an inner face of one metal and a supporting outer face of another, or
conductors which are used with connectors of a dissimilar metal are to have
their exposed interfaces protected against moisture.
9.1.7.7.
All exposed metal surfaces of the CE shall be coated according to
Manufacturer's standard. Include in your technical proposal the painting
standard you will use.
9.1.7.8.
All components shall successfully withstand in operation the climatic and
environmental conditions as defined under clause 9.1.1 and 9.1.2
9.1.7.9.
Manufacturer is requested to describe or indicate deviations (see
clause 15.2, Annexure "B") from above requirements. In case no deviations
are mentioned it will be understood that Manufacturer's offer entirely
complies with the above-mentioned requirements.
9.2.
Reliability, availability, maintainability (RAM)
The Bidder is requested to fill in the enclosed Appendix № 3 “Reliability,
availability, maintainability and safety” based on relevant information from
users. Bidder shall describe the system of relevant data collection from
users. This data is to establish the Contractor’s reliability statements.
9.3.
General Properties
9.3.1.
The line traps shell be wide-band and tuned.
9.3.2.
The line traps shall mounted directly on capacitors (preferred erection) or on
the post isolators.
9.3.3.
The tuning elements and lightning arrestors of the line traps should be
mounted into the main coil and are easily replaceable without the need to
dismount of the line traps.
9.3.4.
Offeror shall propose the accessories for alternative suspend mounting of
the Line Trap.
- 12B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
9.4.
Electric data
9.4.1.
Rated voltage
( KV )………………………..
161 ©
9.4.2.
Rated frequency
( Hz )………………………..
50 ©
9.4.3.
Rated normal current at 45°c ( A )
9.4.3.1.
Item 1………………………………………
2000 ©
9.4.3.2.
Item 2………………………………………
2000 ©
9.4.3.3.
Item 3………………………………………
2000 ©
9.4.3.4.
Item 4………………………………………
3150 ©
9.4.4.
Rated insulation level (kVpeak/kVr.m.s.)…...
9.4.5.
Rated short-time thermal withstand current for 1 sec
( kA r.m.s. )
50 ©
9.4.6.
Rated peak dynamic withstand current ( kA peak )
128
9.4.7.
Arcing distance not less than ( mm )
1550
9.5.
Line Trap (LT)
9.5.1.
Inductance at 100 kHz (mH)
750/325
9.5.1.1.
Item 1……………………………………..
0.5 (mH) ©
9.5.1.2.
Item 2……………………………………..
1
(mH) ©
9.5.1.3.
Item 3……………………………………..
2
(mH) ©
9.5.1.4.
Item 4……………………………………..
0.5 (mH) ©
9.5.2.
The Offeror shall specify the LT inductance at 50 Hz and
1 kHz frequencies as well.
9.5.3.
Rated frequency range (kHz) ©
9.5.3.1.
Item 1……………………………………..
140 to 400 (KHz)
9.5.3.2.
Item 2……………………………………..
87 to 500 (KHz)
9.5.3.3.
Item 3……………………………………..
48 to 500 (KHz)
9.5.3.4.
Item 4……………………………………..
140 to 400 (KHz)
9.5.4.
Blocking action
9.5.5.
Minimum blocking resistance (Ohm)
9.5.6.
Minimum
blocking
bandwidth (Ohm)
wide band tuned
impedance
- 13B -
600 ©
within
frequency
600 ©
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
9.5.7.
SPEC: STR-1377
ANNEXURE "B"
The Offeror shall specify the following for LTs (items1-4):
9.5.8.1.
DC resistance at 20°C (Ohm)
9.5.8.2.
Quality factor at 100 (kHz)
9.5.8.3.
Tapping (incretion) losses, (dB)
9.5.8.4.
Total losses (DC resistance and eddy current
losses) at rated frequency current and 75°C (kW)
9.5.8.5.
Self resonant frequency (kHz)
9.5.8.6.
Self capacitance
9.5.8.
(pF)
The Offeror shall indicate Lightning arrestor specification
9.5.9.1.
Manufacturer
9.5.9.2.
Type designation
9.5.9.3.
Rated voltage (kV)
9.5.9.4.
Rated discharged current (kA)
9.5.10.
at least 30 ©
The Offeror shall indicate Tuning pack specification
9.5.10.1.
Manufacturer
9.5.10.2.
Type designation
9.5.10.3.
Rated impulse protective level (kV)
9.5.10.4.
Device values
9.6.
Coupling Capacitor (CC)
9.6.1.
Manufacturer
9.6.2.
Type designation
9.6.3.
The Offeror shall proposed capacitor according to IEC
60358-1, 60358-2 standards.
9.6.4.
Rated capacitance ( pF )
9.6.5.
Change in capacitance between -5°C to +45°C, less
than ( % )
9.6.6.
Arcing distance not less than ( mm)
9.6.7.
Substitute parallel loss impedance between Radio
Frequency (RF) bushing and ground at normal operating
conditions shall be equal or less than ( pF ):
6000 ±10% ©
9.6.8.
The Offeror shall specify Substitute series resistance at
carrier frequencies between 35 to 500 kHz measured
between HV terminal and RF terminal, (Ohm).
9.6.9.
The Offeror shall specify the Self resonant frequency
(kHz)
- 14B -
±2% ©
1550
100
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
9.7.
Design & construction
9.7.1.
General requirements
9.7.1.1.
The CE shall be suitable for outdoor installation, and for
connection to overhead transmission lines.
9.7.1.2.
The CE shall be capable of withstanding electrical,
mechanical and thermal ratings of the specified systems
9.7.1.3.
The CE shall be of proven design with established
service operation
9.7.1.4.
Field assembly of the CE should be done by bolting. Field
welding is not acceptable
9.7.1.5.
All electrical safety clearances shall conform to IEC
Recommendations as appropriate for the system
conditions described under subcl. 9.4
9.7.1.6.
The CE shall be without wheels and minimum four
mounting holes shall be provided on the base
9.7.1.7.
The Line trap shall be equipped with the bird barrier on
it's upper and bottom ends
9.7.2.
TERMINALS
9.7.2.1.
Aluminum terminal on the line side shall be provided.
The primary terminal shall be connected directly to the LT
without any intermediate connection
9.7.2.2.
Earth copper terminal marked with appropriate graphical
symbol shall be provided
9.7.2.3.
The earthling connections shall be designed to withstand
a short circuit current during 1 sec.
9.7.3.
INSULATOR
9.7.3.1.
The insulator shall be porcelain type. Other types of the
insulator (for example: composite type, porcelain
protected by silicon rubber coatings) may be acceptable
9.7.3.2.
Color of the insulator shall be Brown or grey.
9.7.3.3.
The insulator shall be provided with hydrophobic
coating.
The hydrophobic coating shall be suitable for the service
conditions mentioned above.
9.7.3.4.
The insulator shall be of the alternate sheds type or
normal sheds type permitting easy access for cleaning
to all surfaces.
- 15B -
©
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
9.7.3.5.
Heavy duty, high grade, high creepage path type,
insulator for outdoor and indoor installation, suitable for
the service conditions as described under sub clause 9.4
pollution zone III as defined by IEC 60815) shall be
provided.
In case the polymer type insulator is offered, the Bidder
shall submit all relevant test reports from the neutral
Laboratory authorized in accordance with ISO 17025
(e.g. KEMA), to prove that the offered polymer material
is suitable for the service conditions as described under
sub clause 9.4 above
9.7.3.6.
The insulator shall be only "wind formed" type, not drop
shaped type.
9.7.3.7.
The recommended dimensions and details of the
insulator are shown on the enclosed drawings (pages B17, B-18, B-19).
9.7.3.8.
The material used in attaching the flange to porcelain
insulator shall be such as to form a slanted circular zone
at the upper part of the flange and above it so as not to
permit water accumulation.
Any change in shape with aging of material in that zone
shall be unacceptable. Manufacturer is required to send
drawing and to give details about type of materials used
(bonding material, primer, final paint, etc.)
9.7.3.9.
Minimum phase to ground external creepage distance
(25 mm/kV):
4250
9.7.3.10.
Arcing distance not less than (mm) ……………
In case of lower values than 1063 mm the impulse and
power frequency test reports for offered insulators shall
be provided to prove that the insulation withstand
conditions are fulfilled.
1550
- 16B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
ALTERNATE-SHEDS TYPE INSULATOR
RECOMMENDED FOR
CC\ Insulators
S-S1
P1-P2
S1/P1
C
a
P.F.
Kd
Dm
l
L
C.F. (L/A)
ld1/ d1
ld2/ d2
Kd
Dm
l
=
=
=
L
A
P.F.
C.F.
=
=
=
=
> S1
≥ 15 mm
≥ 0.8
= mm
> 5°
> 0.7
=1
< 300 mm
= 25 mm/kV
= 4250 mm
≤4
Factor to increase the creepage distance
(De1+De2+2Di)/4
Minimum specific creepage distance per phase
(related to highest system voltage phase to phase)
Phase to ground external creepage distance
Arcing distance.
Profile factor (2P1+2P2+S)ld2
Creepage factor (L/A)
- 17B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
NORMAL-SHEDS TYPE INSULATOR
RECOMMENDED FOR
CC\ Insulators
S/P
C
a
P.F
Kd
Dm
l
L
C.F. (L/A)
ld/ d
Kd
Dm
l
=
=
=
L
A
P.F.
C.F.
=
=
=
=
≥ 0.8
= mm
> 5°
> 0.7
=1
< 300 mm
= 25 mm/kV
= 4250 mm
≤4
Factor to increase the creepage distance
(De +Di)/2
Minimum specific creepage distance per phase (related to highest system
voltage phase to phase)
Phase to ground external creepage distance
Arcing distance.
Profile factor (2P+S)ld
Creepage factor (L/A)
- 18B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
COMPOSITE INSULATOR
RECOMMENDED FOR
CC\ Insulators
S/P
C
a
Kd
Dm
l
L
L/A
ld/ d
Dti
Dte
Di
De
Kd
Dm
l
=
=
=
L
A
=
=
> 0.75 – 0.8
= mm
12°
=1
< 300 mm
= 25 mm/kV
= 4250 mm
< 4
mm
mm
mm
mm
Factor to increase the creepage distance
(De +Di)/2; for 300mm < Dm < 500mm, kd=1.1
Minimum specific creepage distance per phase (related to
highest system voltage phase to phase)
Phase to ground external creepage distance
Arcing distance
- 19B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
9.7.4.
Stresses on mounted equipment
9.7.4.1.
Guaranteed mean value of failing load (120% F) not less
than (N)
8000
9.7.4.2.
Service load (-40%F) (sum of all loads occurring
simultaneously in service: conductor pull, conductor
weight and wind, short-circuit excepted) in any direction
in space not less than: ( N ).........
2700
9.7.4.3.
Short-time load (F*) (sum of all loads occurring
simultaneously in case of short-circuit) in any direction
in space not less than ( N ):
6700
9.7.4.4.
Contractor shall indicate:
 Torsional strength (Nm)
 Testing load for 60 sec., applied to the midpoint of the
terminal, perpendicularly to the insulator axis (N)
 Recommended rope pull ( N )
 Wind load at wind velocity 44 m/sec
9.8.
Commissioning
9.8.1.
Contractor shall be responsible for the commissioning of all equipment
covered under his contract in case it will be requested by Purchaser.
9.8.2.
Contractor shall prepare and submit three months prior to the start of
commissioning, a Commissioning Program for approval by Purchaser.
9.8.3.
The Commissioning Program shall include indications for:
9.8.3.1.
Commissioning inspection to detect faults which have occurred during
transportation, storing or assembly at its final location
9.8.3.2.
Preparation for use and procedures to describe the activities required to
prepare systems for testing and operation.
9.8.3.3.
Checking of rated data, connection, loading etc. of the equipment and
necessary interface with the equipment supplied by others.
9.8.3.4.
Testing as detailed in tests on site program including:
 the test objective- test intent
 required performance data- prerequisites
 sequence of activities
 acceptance criteria
9.8.3.5.
Putting the equipment into service.
9.8.3.6.
Final check.
- 20B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
9.8.3.7.
The critical limits of each criteria for which the equipment should be drawn
out from service.
9.8.4.
Changes and modifications to the Commissioning Program shall also be
approved by Purchaser.
9.8.5.
Commissioning results shall be witnessed by the Purchaser and
documented on forms to be agreed upon by the Contractor. The record shall
include other such as omissions or unsatisfactory test results.
9.8.6.
The Contractor shall maintain an up to date record of all inspections and
tests, which shall be handed over to Purchaser at the completion of the site
testing and commissioning.
9.8.7.
The Purchaser shall be responsible for connection and disconnection of the
equipment to and from system, including first energization, but with the
advice and technical assistance of the Contractor (if required).
9.8.8.
The Contractor shall be responsible for supplying commissioning personnel
with a good knowledge in all relevant operations prior and for
commissioning and will be requested to submit a list giving name,
experience and proposed duration on site.
9.8.9.
The Contractor shall be responsible for safety of personnel, ours or his own,
involved in commissioning and shall take all possible precautions and be
fully aware of dangers involved in testing. Contractor's personnel should
also be ensured against death, personal accident and health while in Israel
and be covered by Employers Liability Insurance applicable in their country
of origin.
9.8.10.
Major failure or damage to equipment will require either its return to the
factory or assignment of a special crew to carry out repairs.
9.8.11.
Commissioning personnel shall repair minor failure.
9.8.12.
All expensive (including transport to factory and return) in connection with
damages and repairs as described above shall be paid by Contractor.
9.8.13.
If supervision of erection or commissioning by Contractor is necessary it has
to be indicated.
9.8.14.
The validity of the warranty period shall be confirmed also in case that the
erection and commissioning will be performed by Purchaser without
Contractor supervision.
- 21B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
9.9.
Operation & maintenance
9.9.1.
General
9.9.1.1.
The CE shall be designed for live-washing (automatic and manual) taking
into account service conditions described under subcl. 9.4.
9.9.1.2.
A complete set of tools for maintenance and repair work (if applicable) shall
be provided together with relevant drawings or photos and full instructions
for use in English.
9.9.1.3.
Manufacturer shall ensure spare parts (if applicable) for the delivered
equipment for a period of life duration.
9.9.1.4.
Manufacture shall ensure training course for IEC erection and operating
people.
9.9.2.
Spare & renewal parts
9.9.2.1.
The Contractor shall indicate in the Proposal the life duration of the CE and
the normal replacement cycle.
9.9.2.2.
The Contractor shall include in its technical proposal a detailed list of spare
parts, recommended for:
 The short term: start-up, commissioning and until expiration of the
warranty period.
 The long term: spare parts for periods of 5 (five) and 10 (ten) years after
the end of the warranty period.
9.9.2.3.
The catalog and the lists shall include for each item:
 Item description and item designation.
 Likelihood that the part will be required for replacement during each
relevant period (short term, long term).
 Name of Contractor and Manufacturer.
 Necessary catalogue data for separate order.
 Optimal stocking level.
 If the supply is from the stock or by manufacturing after order.
 Lead time before supply (including transport time to Israel).
 Price.
9.9.2.4.
All Spare Parts shall be new and unused in all cases.
The Purchaser reserves the right to purchase said parts directly from the
Manufacturer or from another subcontractor.
The Contractor warrants that spare and renewal parts shall be available for
at least ten (10) years after supplying of the CE.
The Contractor guarantees that all the Spare Parts features will be
according to its catalogue and that the catalogue is periodically updated.
The Contractor shall give tree lists of recommended spare parts.
- 22B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
10.
TESTS & INSPECTIONS
10.1.
TESTS - GENERAL
10.1.1.
Contractor shall perform Production Tests to check the quality and uniformity
of the workmanship and materials used in the manufacture of the CE.
10.1.2.
Tests shall be carried out according to requirements further specified and 8
(eight) copies of the relevant test reports for the proposed type of equipment
shall be submitted to Purchaser with the proposal.
10.1.3.
8 (eight) weeks prior to the execution of the routine tests (also special tests)
the Contractor shall notify the Purchaser of the exact date of performing the
test.
10.1.4.
The Contractor shall submit test data to prove that the design has the
capability to meet all the ratings as specified in Annexure "B" as well as
relevant test reports.
10.1.5.
The Contractor shall prepare and submit an acceptance test plan according
to this Specification at least 8 (eight) weeks before the testing.
10.1.6.
The Purchaser can require carrying out the tests in the presence of the
Purchaser representatives.
10.1.7.
The Contractor shall submit a list of all tests to be performed on site, after
mounting of the equipment and during operation.
10.1.8.
The Contractor shall indicate permissible tolerance for each test value.
10.1.9.
Contractor shall submit with the test reports a list of all measuring
instruments including their accuracy class and type, test equipment and test
circuits, calibration certificate from authorized laboratory.
10.1.10.
The equipment can be delivered only after Purchaser's approval of all
relevant routine test reports.
10.2.
TYPE TESTS
10.2.1.
Type tests from a neutral Laboratory authorized in accordance with ISO
17025 (e.g. KEMA) performed for the offered type of the equipment
according to the provisions of the latest relevant issue of IEC
Recommendations shall be submitted to Purchaser in 8 (eight) copies with
the proposal (tender).
10.2.2.
Purchaser can require from Contractor to perform again type tests that are
not performed according to the requirements in this Specification.
- 23B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
10.3.
ROUTINE TESTS
10.3.1.
Contractor shall perform routine tests for all offered Items according to
provisions of the latest relevant issue of IEC Recommendations and submit
all relevant test reports as defined in Appendix №1 ©.
10.3.2.
Contractor shall submit the routine tests reports to Purchaser for approval in
8 (eight) copies one month prior to delivery.
10.3.3.
The equipment can be delivered only after approval of all routine test report.
10.4.
SPECIAL TESTS
10.4.1.
Contractor shall perform special tests for all offered Items and submit all
relevant test reports as defined in Appendix №1
10.4.2.
The equipment can be delivered only after approval of all special test
reports
10.5.
ACCEPTANCE TESTS
10.5.1.
In addition to the tests mentioned above Manufacturer shall perform the
acceptance tests (if applicable) and supply test reports accordingly.
10.6.
EQUIPMENT QUALIFICATION TO PROVE SEISMIC WITHSTAND
10.6.1.
The offered CE shall be analyzed to prove the seismic design.
The equipment shall be qualified according to IEEE Std 693
Required seismic qualification level – Moderate level.
10.6.2.
After performing the analysis the Contractor shall submit for approval the
calculations that demonstrate the anchorage requirements according to
IEEE Std 693
11.
PACKAGING & DELIVERY
11.1.
In addition to the provision of the General Conditions Annexure "A",
Contractor shall package all shipment in such manner as required to prevent
any damage to the equipment during prolonged storage (2-3 years) under
the climatic and environmental conditions described under clause 9.1.1 and
9.1.2
11.2.
Any components or accessories not included in the main shipment shall be
shipped by Air Mail, by Air Express or by Air Freight, at Contractor's
expense.
- 24B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
11.3.
The spare parts and special tools shall be packed separately and a detailed
packing list shall be sent.
11.4.
All components or accessories shipped dismantled for field assembly shall
be suitably tagged to show its identification. Tags shall be exceptionally
durable and security tied to items by wire or other approved methods
11.5.
Contractor shall include a Bill of Materials with a shipment to enable the
Purchaser to determine if all disassembled items have been received.
11.6.
Contractor shall submit prior to erection a detailed tabulation of all field
mounted items with at least the following information:
 Contractor's shop order number (if any).
 Number of items.
 Manufacturer and/or Supplier (if other than Contractor).
 Type or catalog number, if listed.
 Short description including service and on what device it is mounted.
 Shipping date.
 Shipping details.
11.7.
A three direction shock indicator calibrated for 10g acceleration nonresettable type shall be provided in each crate.
11.8.
Contractor shall supply 3 (three) months before the shipment of the
equipment 5 (five) sets of the complete Bill of Materials to enable checking
and identifying of the equipment upon receipt of the same.
11.9.
Each item shall be separately packed and the destination clearly marked.
11.10.
Each packing crate shall have a packing list and in addition shall be marked
with following information:
 Descriptive name(s) of equipment or supplies contained.
 Quantity packed in a crate.
 Serial numbers, if any, of the equipment contained.
 Contract (order) number.
 Contractor's name and address (city, state, and country).
 Gross weight of container.
 Complete destination marking.
 Indication in which position (horizontal or vertical) the equipment has to
be transported.
- 25B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
12.
STORAGE & HANDLING
12.1.
With regard to the shipment and handling of all equipment to be provided by
the Contractor to the Purchaser, Contractor shall be responsible for
ensuring that shipment and handling shall be wholly in the conformance with
Article B of IECo General Conditions for Equipment and Material Purchases
attached to this Specification as Annexure "A"
12.2.
Taking into account the specific climatic conditions described under clause
9.1 the Contractor shall indicate:
o The requirements for prolonged storage before erection.
o The maximum allowed storage time not energized without
equipment damage (months).
12.3.
All items should have their lifting, jacking and haulage points.
13.
NAMEPLATE / MARKING
13.1.
Each LT shall be provide with corrosion proof and clearly legible nameplate of
suitable material including the data indicated in IEC 60353-1 section four(4).
13.2.
Each CC shall be provide with corrosion proof and clearly legible nameplate
of suitable material including the data indicated in IEC 60358-1 cl.12.2 .
13.3.
In addition the following data shall be provided:
 Date of manufacture.
 Name and number of standard.
13.4.
The nameplate shall be subject to Purchaser's approval.
- 26B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
14.
SPEC: STR-1377
ANNEXURE "B"
NOTES
Progress Reports shall be submitted in accordance with General Conditions
Annexure "A".
- 27B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
SPEC: STR-1377
ANNEXURE "B"
15.
SPECIAL REQUIREMENTS
15.1.
COMMENTS BY MANUFACTURER ON ANNEXURE "B"
Name of Contractor: ___________________________________________
- 28B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
15.2.
SPEC: STR-1377
ANNEXURE "B"
DEVIATIONS FROM REQUIREMENTS
Name of Contractor: ____________________________________________
Contractor is requested to describe or indicate deviations of the equipment
and accessories from all requirements in this Specification.
In case no deviations are mentioned it will be understood that Contractor's
offer entirely complies with all requirements in this Specification.
- 29B -
THE ISRAEL ELECTRIC CORPORATION LTD.
ENGINEERING DIVISION
SUBSTATION PLANNING SECTOR
15.3.
SPEC: STR-1377
ANNEXURE "B"
CONFORMITY WITH PROPOSAL DOCUMENTS
Name of Contractor: ________________________________________
Contractor hereby certifies that he agrees to all provisions of the Proposal
Documents unless exceptions are specifically and clearly listed in the
Proposal and identified as Exceptions. Contractor printed terms and
conditions are not considered specific exceptions. Any exceptions, which
Contractor has taken, are listed on Page:
____________________________________________________________
Contractor hereby certifies that he agrees to all conditions of the cover letter
of THE ISRAEL ELECTRIC CORPORATION LIMITED, which accompanies
the Proposal Documents.
______________________
______________________________
Signature of Contractor
Date of Proposal
- 30B -