International Conference on Electrical, Electronics, and Optimization Techniques (ICEEOT) - 2016 Reduction of Inrush Current for Transformer Using Sequential Switching Method Ketan Gohil Department of electrical engineering G.H.Patel college of engineering Anand, India gohilketan369@gmail.com Jatinkumar Patel Department of electrical engineering G.H.Patel college of engineering Anand, India jatinpatel@gcet.ac.in Chirag Parekh Plant coordinator Atlanta electricals Pvt. Ltd. Anand, India chirag.parekh@atlantaelectricals.com Abstract- Nowadays, solar power becomes one of the most suitable renewable energy source for power generation. In practice, inrush current is produced in grid connected transformer(s) during routine switching process of solar power plant. This inrush current effects to winding of transformer as well as produces harmonics and power quality issues. In this paper the calculation of inrush current and its effect on power system network is elaborated. Possible cost effective solution for reduction of inrush current by suitable techniques is discussed in this paper. In sequential switching technique, better suppression of inrush current and harmonics is obtained. Index terms—Modelling, Matlab, Transformer, Inrush current, solar power plant, switching method. I. INTRODUCTION A demand of electric power is increasing due to industrial and mankind growth rapidly. Therefore to fulfill the requirement of Electric power, apart from the conventional source of energy, the renewable source of energy is being more popular compared to other renewable sources of energy. Growth of solar power installation has been linearly increased and became key player for produce of electricity. Total installed capacity of solar power in India 5130 MW and Gujarat state is 1024.15 MW up to the till date [1]. Solar power plants are switched off at night due to some problems such as reverse power flow and reactive power compensation problem. Next day, at early morning, when solar plant is switched on in case of grid tide, due to switching effect, high value of inrush current is drawn by transformer due to instantaneous switching effects. Also transformer draws high amount of current when it converts its state from de-energized to energized state which measured as inrush current which should be mitigate effectively to overcome the power quality issues. Amount of inrush current is 8 to 10 times higher than rated current [2]. During starting, amount of high inrush current for several cycles has been fed to grid. But it slowly decreases and finally reaches at normal rated current which is shown in Fig. 1. 978-1-4673-9939-5/16/$31.00 ©2016 IEEE Fig.1. pattern of inrush current Electrical power is unable to generate during night time. As a result, solar power plant auxiliaries draw the certain amount of current and solar plant behaves like a load. Therefore, in uninstructed manner, plant(s) have been disconnected from main grid by power plant operators. Next day when plant is connected to grid through transformer high amount of magnetizing current (Im) drawn by the transformer due to residual flux of transformer. As a result, grid tied transformer of solar plant experiences the heavy amount of inrush current which becomes daily practice for solar power generation. To prevent from such an undesirable phenomenon, certain techniques has been developed, however rigorous research is required in this area. To reduce inrush current, different techniques such as series compensation techniques, virtual air gap techniques, asymmetric winding, pre fluxing, optimal losing, point on wave switching, ultra-low power frequency power source, bridge type inrush current limiter, grounding resistance at neutral point and sequential switching method are discussed in this paper. From above discussed methods, Sequential switching method is adopted to reduce the inrush current. A. Effects of inrush current. 1. Voltage distortion: when transformer impedance, smaller than the source impedance during energization of it, consider voltage drop will occurs due to inrush current event. Voltage distortion (0.1 pu to 0.9 pu) will affect the some sensitive load, industrial costumer, medical equipment etc. [3] [4]. 2. Harmonics: Due to inrush current, harmonics are generated with different orders and its magnitude indicated in Table I. Second order harmonics are dominant because its quarter wave symmetric in nature. Inrush current star in either positive direction or negative direction. [i.e. For supply of 50Hz frequency, freq. of second harmonics will be 50 x 2 = 100Hz.] [5]. TABLE I. HARMONICS CONTENT OF INRUSH CURRENT Harmonic order Fundamental DC 2nd 3rd Magnitude (%) 100% 40 to 60% 30 to 70% 30 to 50% 3. Stress on transformer winding: During inrush current in transformer, two main forces acts on winding. Radial force. Axial force. Radial force occurs during inrush current, which cause the increase the diameter of winding. It also forces during short circuit occurrence which is more damaging compared to inrush current. The axial force drives the winding towards ground which changes the dimensions and also able to damage the transformer winding [6] [7]. 4. Malfunctioning of protective relay: In actually to compute the highest value of inrush current should be very affected parameter in designing and to determine the setting of over current relay used in power transformer maloperation of relay is occurred. Due to malfunctioning of relays, circuit breakers operates for tripping which is undesirable [8]. B. Factors for inrush current 1. Switching angle: If applied voltage is zero value at that instant inrush current is maximum. Because if voltage is zero value at that time flux is maximum and hence, inrush current is maximum. Flux in transformer is given by following equation [9]. φ = (φr + φm) cos(α) −φm cos(ωt + α) (1) The flux value at different instant of switching is calculated using (1) and presented in Table II. Table. II seen that inrush current depends on two factors; residual flux and switching angle of voltage. If α=90; ϕ=2ϕm, for α= 0; ϕ=3ϕm. Therefore, voltage at zero crossing inrush current is maximum. TABLE II. VALUE OF THE FLUX AT DIFFERENT SWITCHING INSTANT Switching Angle Value of flux α = 0° ∅ = 3∅m α = 45° ∅ = 2.12∅m α = 90° ∅ = ∅m 2. Residual flux density: Transformer is made from ferromagnetic material. Hence, always residual flux will be present in it due to hysteresis effect which is the main cause of inrush current in windings. Which depends upon core material characteristics. Its extreme value considered for cold rolled and hot rolled material are 80% and 60% respectively of the core saturation value [10]. Value of residual flux in transformer is measured by de-energization instant of transformer. Residual flux measurement is used for calculate of suitable instant for energization of transformer [11]. Table III. shows residual flux in different rating of transformer. TABLE III. RESIDUAL FLUX OF DIFFERENT RATING OF TRANSFORMER Transformer capacity Residual flux 300 kVA 0.33 Wb 800 kVA 0.38 Wb 50 MVA 13 Wb 300 MVA 83 Wb 3. Series resistance: Line resistance between the sources and transformer is another factor of inrush current generation. Due to damping effect, series resistance between transformer and sources, not only decreases maximum preliminary inrush current but also increase its decay rate. Transformer near to generator usually have high inrush current because of the line resistance between generator side transformers and generator is minimum [10]. 4. Inrush under load: If transformer is energize with connected load, some value of load power factor affected by inrush current in transformer. If under heavy load and at unit power factor transformer is switched on, the maximum value of inrush current is low. Inrush current peak value is high for reduction of power factor [9]. 5. Source impedance: Inrush current is also defined by impedance of source of power system. If transformer primary winding and source impedance is same or impedance of source is more than impedance of transformer primary winding inrush current in that situation is maximum. The transformer inrush current causes momentary voltage sag due to the impedance between the energized transformer and the source [12]. 6. Size of transformer: The size of the transformer reproduces the inner transformer impedance of winding. The small transformer (< 1000 kVA) generates high inrush current for small duration (100 ms.). The high rated transformer (>1000 kVA) generates low inrush current for long duration in range of seconds [13]. Above factors are responsible for causes the inrush current. Main factors for reducing the inrush current are switching angle (α) and residual flux (ϕres) after designing of transformer. Inrush current value is high as compare to normal rated current, therefore harmonics at that instant is also high. Harmonics contents in inrush current waveform shown in Table I. II. METHODS FOR MITIGATE THE INRUSH CURRENT Several methods has been proposed by various authors to reduce inrush current in transformer in articles [14-29]. The methods elaborated here are developed in time frame chronologically which has shown in Fig.2. Most of the methods are able to mitigate inrush current effectively however sequential switching method is able to provide most effective solution compared to others which is simulated for power transformer used for distributed generator at large. Virtual air gap method Optimal closing method Series compensation method transformer, power-on angle of circuit breaker and calculation of residual flux. Inverter based series compensator using a currentmode control for reducing the inrush current during energization of transformer [17]. By using asymmetric winding the inrush current was minimizes based on increasing the inrush equivalent inductance by changing the value of internal film and external film in coil winding. [18]. In this method all three phases of transformer is energized at proper instant. If each phase of transformer is energized in sequential manner at suitable instant inrush current is reduce. In this method not required the residual flux calculation. Inrush current reduce by this method by using of zero crossing detector and knowledge about closing time of circuit breaker [19]. By using this method reduce the residual flux in core of transformer by applying voltage across tertiary winding before energization of transformer [20] [21]. In this method use the diode bridge technique for reduce the inrush current in primary grounded transformers. The advantages of this method are its simple circuit, easily implement to transformer [22]. By using sequential phase energization method each phase is energized in sequential manner with uses of neutral grounding resistance [24] [25]. In prefluxing inrush current reduction scheme reduce the remaining residual flux which remaining in transformer core at startup instant of transformer. Prefluxing equipment consist of capacitor, diode, and fuse. This method does not need measuring of the residual flux [26-29]. Asymmetrical winding III. SIMULATION FOR INRUSH CURRENT INDICES Point on wave switching method Ultra low frequency power source Transformer inrush currents are generates high magnitude amount harmonic rich currents at the instant of transformer energization. Inrush currents are categorized in three types [30]. Table IV shows the rating of transformer specially used for solar power plant. TABLE IV. PARAMETERS OF TRANSFORMER Bridge type Inrush current limiter Transformer Grounding resistance at neutral point Fig. 2. Methods of inrush current reduction A concept of virtual air gap method is use of virtual air gap which equal thickness differs in function of controllable limits changed to the alignment of magnetic circuit and the related control system. The AGW (air gap windings) current is either set to a definite value using a current sensor or external source, in the main magnetization winding of the magnetic circuit [14]. By using controlled switching or optimal closing method required the calculation of residual flux in core of transformer at deenergization instant. In this method to minimize the inrush current not required the independent pole circuit breaker but it required the calculation of residual flux of transformer [15] [16]. Series compensator technique is an inverter-based series compensator which is comprised of a single-phase inverter and series transformer. This technique is easy to implement because it does not requires information about the parameters of Secondary Rating of winding winding transformer 66 kV 20 MVA Freq. voltage Star-Star Prefluxing method Primary (Step up) 11 kV 50 Hz 1. Energization inrush current: During Energization of transformer, energized inrush current is result of re-energized transformer due to residual flux is can be zero or depending on de-energization time of transformer. 2. Recovery inrush current: Recovery inrush current is flow through transformer when supply voltage is restored after having been reduced by system disturbances. 3. Sympathetic inrush current: Sympathetic inrush current occurs in transformer when multiple transformers are connected in system and one of them is energized. Power transformer of 11/66 kV, 20MVA has been simulated for the given switching instant, normal inrush, recovery inrush and sympathetic inrush current difference has been achieved by suitable modelling in Matlab/ Simulink environment which are shown in Fig. 3(a), 3(b) and 3(c). Simulated results which reflects the difference between normal inrush current, recovery inrush current and sympathetic inrush currents of transformer are as shown in Fig. 4(a), 4(b) and 4(c). By analyzing the simulated result of energization inrush current in Fig. 4(a) show the inrush current peak is more than 1500A. Harmonics content and THD generated due to energization inrush current shown in Table V. TABLE. V. HARMONICS CONTENT AND THD OF ENERGIZATION INRUSH CURRENT Phase Phase R Phase Y Phase B THD 90.92% 111.69% 110.75% 2nd harmonics 63.93% 72.98% 73.49% 3rd harmonics 31.32% 52.85% 53.53% Fig. 3 (a). Matlab/Simulink based model of energization inrush current Fig. 4(a). Energization inrush current Recovery inrush current for 20MVA transformer are elaborated in 4(b). During starting (0 to 0.6 sec) is characterization of energization inrush current. For single phase fault (0.9 to 1.2 sec) has been achieved for rated power transformer. After recover the fault recovery inrush current is drawn by transformer after 1.2 sec as shown. Fig. 3(b). Matlab/Simulink based model of recovery inrush current Fig. 4(b). Recovery inrush current Fig.3(c). Matlab/Simulink based model of sympathetic inrush current Figure 4(c) indicates the waveform of transformer T1 current having energization inrush current and sympathetic inrush current (1 to 2 sec.) due to transformer T2 is energized. When transformer T2 is energized after 1 sec. it is observed that a value of sympathetic inrush is low as compare to energization inrush current in terms of magnitude. TABLE. VI. PEAK VOLTAGE INSTANT OF PHASE AT DIFFERENT FREQUENCY Frequency (Hz) 48.5 49.0 49.5 50.0 50.5 51.0 51.5 Peak voltage instant of Phase R (msec.) 5.150 5.100 5.050 5.000 4.950 4.900 4.854 Peak voltage instant of Phase Y (msec.) 12.016 11.900 11.783 11.666 11.550 11.433 11.326 Peak voltage instant of Phase B (msec.) 18.883 18.700 18.516 18.333 18.150 18.700 17.798 In Fig. 5 show that the Matlab/Simulink model of sequential switching method and in Fig. 6 show the waveform of current in transformer using sequential switching method. Simulation is carried out for 50Hz frequency and its phase R, Y, and B phase switching instant is 5 msec. 11.666 msec. and 18.333 msec. respectively. Fig. 4(c). Sympathetic inrush current IV. INRUSH CURRENT REDUCE BY SEQUENTIAL SWITCHING METHOD In this paper to reduce of transformer inrush current by using sequential switching method is described. In this method transformer each phase is energized at peak value of supply voltage of each phase. An instant of Peak value of supply voltage for each phase is different. For 50 Hz supply frequency switching instant of phase R, Y, B is calculated as follows, Therefore, 10 msec. time is required for half cycle (180° degree). 5 msec. is for 90° degree. For circuit breaker of phase RYB closing instant is, firstly assume that we supply phase R voltage at 90° (maximum) in 5 msec. Next phase Y is connected at 120° apart from phase R that means 90° + 120° = 210°. Time required for 0° to 210° is 11.666666 msec. After energization of phase Y next phase B is energized at 120° apart from phase Y. time required for 210°+120°=330°. Time duration for 0° to 330° is 18.3333333 msec. [19]. But in actual supply frequency is not remaining 50 Hz constant. For different frequency peak instant of voltage is different. Some different value of frequency and their switching instants are shown in Table VI. Table VI show that the peak voltage instant of three phase for different frequency. In proposed method, transformer must be energized at peak value of phase voltage. In actual it is possible by zero crossing detector such as IC TCA 785 and other zero crossing detector. But the limitation of zero crossing detector only use for particular value of frequency. Because, for different value of frequency peak instant of voltage is different. For example from Table V for 50 Hz frequency peak voltage instant of phase R, Y and B phase is 5 msec. , 11.666 msec. and 18.333 msec. respectively. Fig.5. Matlab simulation mode of sequential switching method Figure 6 show that inrush current is reduce by effectively by using sequential switching method for 11/66 kV, 20 MVA transformer. Fig. 6: Inrush current reduce by sequential switching method From Table VII show that the harmonics content after implementation of sequential switching method. TABLE VII. HARMONICS CONTENT AND THD AFTER IMPLEMENT OF SEQUENTIAL [11] Goran Petrović, Tomislav Kilić, Stanko Milun “Remanent flux measurement and optimal energization instant determination of power transformer” XVII IMEKO World Congress Metrology in the 3rd Millennium, Dubrovnik, Croatia, June 22 −27, 2003. [12] Lin, C.E., Cheng, C.L., Huang, C.L., and Yeh, J.C. “Investigation of magnetizing inrush current in transformers- Part I: Numerical simulation” IEEE Transactions on Power Delivery, Vol. 8, No. 1, pp. 246–254, January 1993. [13] Al-Khalifah A. K. and Al-Saadany E. F. "Investigation of magnetizing inrush current in a single-phase transformer" IEEE Conference on Power Engineering, 2006 Large Engineering Systems, pp. 165-171, July 26-28, 2006. V. Molcrette , J. L. Kotony, J. P. Swan and J. F. Brudny, "Reduction of inrush current insingle-phase transformer using virtual air gap technique" IEEE Trans.Magn. , vol. 34, pp.1192 -1194, 1998. J. Brunke, K. Frohlich, “Elimination of Transformer Inrush Currents by Controlled Switching-Part I: Theoretical considerations” IEEE Transactions on Power Delivery vol 16 no.2 April 2001. SWITCHING METHOD Phase R THD (%) 14.21 2nd order harmonics (%) 3rd order harmonics (%) Reduction of harmonics (%) 3.34 3.35 70.76 Y 24.92 6.35 2.11 86.77 B 37.52 2.99 2.92 73.23 V. CONCLUSION During switching of solar plant, produces inrush current in transformer effects the transformer winding, generates the harmonics and power quality issues. Different techniques to reduce the inrush current are discussed in this paper. Sequential switching method is used because it does not required calculation of residual flux and easy to implement in system. From simulation and analysis of inrush current it conclude that harmonics reduce in R, Y, and B phase are 71%, 87%, and 73% respectively References [14] [15] [16] J. Brunke, and K. Frohlich, “Elimination of Transformer Inrush Currents by Controlled Switching Part II: Application and performance considerations” IEEE Transactions on Power Delivery vol 16 no.2 April 2001. [17] Juei - Lung Shyu ," A Novel Control Strategy to Reduce Transformer Inrush Currents by Series Compensator ", IEEE PEDS 2005. [18] J. Chhen, T. Liang, C. Cheng, S. Chen, R. Lin and W. Yang, “Asymmetrical winding configuration to reduce inrush current with appropriate short-circuit current in transformer” IEE Proc.-Electr. Power Appl., Vol.152, No.3, May 2005. [19] F. Ali Asghar and K. P. Basu, "Reduction of three phase transformer magnetizing inrush current by use of point on wave switching ", IEEE Student Conference on Research and Development, Malaysia, pp368-370, Nov. 16-18 2009. B. Kovan, F. de Leon, D. Czarkowski, Z. Zabar, and L. Birenbaum, “Mitigation of inrush currents in network transformers by reducing the residual flux with an ultra-low-frequency power source,” IEEE Trans. Power Del., vol. 26, no. 3, pp. 1563–1570, Jul. 2011. [1] http://pib.nic.in/newsite/PrintRelease.aspx?relid=134497. [2] Hemchandra Madhusudan Shertukde “distributed photovoltaic grid transformer” CRC publication book, 2014. [3] Seo, HC & Kim, CH 2008, “The analysis of power quality effects from the transformer inrush current: A case study of the Jeju power station, Koria”, Power and energy society general meeting-conversion and delivery of electrical energy in the 21st century 2008, IEEE, PA Pittsburgh, pp. 1-6, 20-24 July 2008. [4] M. Nagpal, T. G. Martinich, A. Moshref, K. Morison, and P. Kundur,"Assessing and limiting impact of transformer inrush current on power quality," IEEE Transactions on Power Delivery, vol. 21, pp. 890-896, 2006. [5] Al-Khalifah A. K. and Al-Saadany E. F. "Investigation of magnetizing inrush current in a single-phase transformer" IEEE Conference on Power Engineering, 2006 Large Engineering Systems, pp. 165-171, July 26-28, 2006. [21] D. P. Balachandran, K. R. Sreerama and V. P. Shimnamol, "Transformer Inrush Current Redution by Power Frequency Low Voltage Signal Injection to the Tertiary Winding" IEEE conf Powertech “07, pp.1953 -1958, 2007. [6] Neves, W, Fernandes, D, Baltar, F, Rosentino, A, Saraiva, E, Delaiba, A, Guimaraes, R, Lynce, M & de Oliveira, J 2011, “A comparative investigation of electromechanical stress on transformers caused by inrush and short-circuited currents”, International conference on electrical power quality and utilisation (EPQU), 2011, Libson, 17-19 October 2011. [22] Seyed Majid Madania, Mehrdad Rostamia, G.B. Gharehpetianb, Reza Hagh Maram “Improved bridge type inrush current limiter for primary grounded transformers” Electric Power Systems Research , vol.95, pp. 1– 8, feb.2013. [23] Faiz, J., Ebrahimi, B.M., Abu-Elhaija, W. “Computation of static and dynamic axial and radial forces on power transformer windings due to inrush and short circuit currents” Applied Electrical Engineering and Computing Technologies (AEECT), 2011 IEEE Conference, Jordan, 2011. Yu Cui, Sami G. Abdulsalam, Shiuming Chen, Wilsun Xu, “A Sequential Phase Energization Technique for Transformer Inrush Current Reduction— Part I: Simulation and Experimental Results” IEEE transactions on power delivery, vol. 20, no. 2, April 2005. [24] Fahrudin Mekic, Ramsis Girgis, Zoran Gajic, Ed teNyenhuis “Power Transformer Characteristics and Their Effect on Protective Relays” 33rd Western Protective Relay Conference, October 17-19, 2006. Yu Cui, Sami G. Abdulsalam, Shiuming Chen, Wilsun Xu, “A Sequential Phase Energization Technique for Transformer Inrush Current Reduction—Part II: Theoretical Analysis and Design Guide” IEEE transactions on power delivery, vol. 20, no. 2, April 2005. [25] D.I.Taylor, N.Fischer, J. D. Law, and B. K. Johnson, “Using LabVIEW to measure transformer residual flux for inrush current reduction,” presented at the North Amer. Power Symp., Starkville, MS, Oct. 4–6, 2009. [26] Douglas I. Taylor, Joseph D. Law, Brian K. Johnson, and Normann Fischer, “Single phase transformer inrush current reduction using prefluxing” IEEE Transactions On Power Delivery, Vol. 27, No. 1, January 2012. [7] [8] [9] Y.G. paithankar and S.R. bhide “fundamental of power system protection” PHI Pvt. Ltd, 2003. [10] S.V.kulkarni and S.A.kharpade “Transformer engineering design and practice” MARCEL DEKKER, INC. 2004. [20] [27] Douglos I. taylor “system apparatus, and method for reducing inrush current in a three phase transformer” united states patent, patent no. US 8,878,391 B2, date: nov, 4, 2014. [28] V. Oiring de Castro Cezar, L-L. Rouve, J-L. Coulomb, F-X. Zgainski, O. Chadebec, and B. Caillault “Elimination of inrush current using a new prefluxing method. Application to a single-phase transformer”IEEE, 2014. [29] Vaddeboina, V, Taylor, G & Proudfoot, C 2012, “Switching large transformers on weak transmission netroks – A real time case study”, Universities power engineering conference 2012, 47th international conference, , IEEE, London, pp. 1-6, 4-7 September 2012.