1 Comparative Stability Analysis of DFIG-based Wind Farms and Conventional Synchronous Generators J. C. Muñoz, and C. A. Cañizares, Fellow, IEEE Abstract—This paper presents a comparative stability analysis of conventional synchronous generators and wind farms based on double feed induction generators (DFIG). Based on an appropriate DFIG wind generator model, PV curves, modal analysis and time domain simulations are used to study the effect on system stability of replacing conventional generation by DFIG-based wind generation on the IEEE 14-bus benchmark system, for both fixed power factor and voltage control operation. The results show that the oscillatory behavior associated with the dominant mode of the synchronous generator is improved when the DFIG-based wind turbine is connected to the system; this improvement in the damping ratios is more evident when the wind turbines are operated with terminal voltage control. Index Terms— Power system stability, Wind power generation, Synchronous generators. I. INTRODUCTION N OWDAYS, wind power energy is increasingly penetrating ele electrical grids. This penetration is mainly driven by policies, global warming concerns and better wind technologies. The control capabilities of these new technologies are continuously improving to satisfy grid code requirements, ensuring a safe operation under normal and fault conditions. Double feed induction generators (DFIGs) is one of the most commonly used technologies nowadays, as these offer advantages such as the decoupled control of active and reactive powers and maximum power tracking. These capabilities are possible due to the power electronic converters used in this type of generator. When the penetration of wind generation is high, it is important to keep these generators on line as much as possible during grid disturbances as per grid code requirements. Therefore, there is a significant interest in investigating the dynamic performance and characteristics of the system under high penetration of wind generation. Various studies have been carried out regarding modeling of DFIG for stability analysis. In [2]-[6], different models of DFIG-based wind generator farms are discussed and simulations are performed. The tuning of the parameters of the This work has been supported in part by MITACS and NSERC, Canada; and the Universidad de Los Andes, Merida-Venezuela. J.C. Muñoz and C. A. Cañizares are with the Department of Electrical and Computer Engineering, University of Waterloo, Waterloo, ON, Canada, N2L3G1 (jcmunozg@uwaterloo.ca, ccanizar@uwaterloo.ca). DFIG controllers is also addressed in various papers. Thus, in [11], a tuning method to optimise the parameters of the DFIG controllers is proposed to improve small-and large-disturbance stability performance. In [12], a methodology to tune damping controllers based on eigenvalue sensitivities is presented. Reference [13] studies the increase in system transient stability margins when DFIG generators are introduced instead of cage generators. A complete analysis of transient stability considering the point of connection of the DFIG at transmission, subtransmission and distribution levels is presented in [14]. In [15], the impact of the increased penetration of DFIG-based wind turbines on small and transient stability is assessed by replacing the DFIG by synchronous generators and evaluating the sensitivity of the eigenvalues with respect to inertia. This methodology identifies inter-area modes that are worsen, and electromechanical modes whose damping is increased by the penetration of DFIG based wind turbines. In [16], the steady state voltage stability of power systems with high penetration of wind turbines is studied using time-series ac power flow techniques. The methodology used in [16] incorporates resource and system assessment for wind power, unit commitment and economic dispatch; the historical data of loading and wind power output are time synchronized, and the worst operating point is identified as the point when wind generation feeds the largest portion of load. According to this paper, the voltage control capabilities of the DFIG wind turbines improve the voltage stability margin at distribution and transmission levels. Also, the eigenvalues trajectories as a function of the load for a power system containing DFIGs are computed in [17]. In this paper, the authors conclude that the DFIGs do not participate in the unstable modes associated with oscillatory instability; a sensitivity analysis of the eigenvalues with respect to the parameters of the active and reactive power controllers is also carried out. Finally, in [18], a four generator test system is used to study the effect of replacing one synchronous generator by a wind farm on the oscillation modes of the system, resulting in an increase of the stability of the observed modes when wind farms are connected. The present paper presents a comparative study of the effect on stability of DFIG-based wind turbines vis-a-vis conventional synchronous generators. PV curves are used for analyzing static load margins, and the effect on the damping ratio of the dominant mode of oscillation for the DFIG operating at fixed power factor and terminal voltage control. 2 , : Stator and rotor resistances; : Stator self-reactance; : Rotor self-reactance; : Mutual reactance; ω : Rotor speed. The wind turbine, generator shaft, and the gearbox is modeled in [19] as a lumped inertia ; therefore, the motion equation can be represented by: (5) Fig.1. DFIG overall scheme The presented studies are based on the IEEE 14-bus benchmark system. Thus, in this system, one of the synchronous generators is replaced by an aggregated DFIGbased wind turbine of equivalent size. Simulations are carried out using the Matlab-based toolbox (PSAT) [19], which includes power flow, optimal power flow, continuation power flow, small-disturbance stability and time domain simulation tools. The rest of this paper is organized as follows: Section II presents a brief description of the PSAT DFIG model and associated controls. In Section III the study methodologies used in this paper are briefly discussed. Section IV presents and discusses the obtained simulations results. Finally, in Section V the main conclusions of the present work are discussed. II. DFIG MODEL The overall scheme for a wind farm based on DFIG is depicted in Fig. 1. Thus, it is composed by two voltage fed PWM converters in back-to-back configuration. These converters allow the decoupled control of the active and reactive power flow between the DFIG and the ac network by adjusting the switching of the IGBTs. For this structure, the equations of the double feed induction generator in terms of the d and q axes and neglecting the stator and rotor flux transients can be written as [19]: •For the stator circuit: (1) where : Mechanical torque; : Electromagnetic torque. This simplification in the inertia is valid only if it is assumed that the controllers associated to the DFIG(s) are able to quickly minimize the shaft oscillations [19]. The electromagnetic torque is represented by: (6) Vector control schemes decouple the control of active and reactive power in the rotor. Thus, the active power P derived ω is from the wind turbine power-speed characteristic associated with the rotor current in the q axis as follows: ω (7) whereas the reactive power Q is associated with the rotor current in the d axis trough the following voltage control equation: (8) where : Actual terminal voltage; : Desired terminal voltage. This controller uses the current rotor speed to optimize the energy extracted from the wind. Furthermore, for rotor speeds greater than 1 p.u., the power is set to 1 p.u. and for rotor speeds lower than 0.5 p.u. the power is set to zero. The limits for the rotor currents are then computed in PSAT as follows: (9) (2) (10) •For the rotor circuit: where , , , 1 ω (3) 1 ω (4) : d and q axes stator voltages; : d and q axes stator currents; : d and q axes rotor currents; (11) (12) These limits are carefully selected to ensure a proper dynamic and steady state operation of the model. 3 Fig.3. DFIG Collector system (PSAT). loading level slowly changes. Here, the damping ratios are used to identify proximity to these bifurcations, which is defined for the i-th eigenvalue of the state matrix α σ ω as follows: γ Fig. 2. IEEE 14 bus system (PSAT). Four state variables can be identified in the DFIG model used , , , and β. Where β is the pitch angle. The in [19]: pitch angle control only operates for super-synchronous speeds, and for sub-synchronous speeds the pitch control is locked. For the speed ranges used here, this pitch angle is inactive and hence, not considered in this paper. It should be mentioned that the dynamics of the converter are fast and are neglected. Therefore, the converter is represented as a current source. The wind is modeled by using the Weibull distribution available in [19], with a shape factor equal to two, which results in a Rayleigh Distribution. III. STUDY METHODOLOGY The theoretical static load margin is computed in this paper by using PV curves. These curves are obtained in PSAT by means of continuation power flows; this method uses predictor-corrector steps to ensure convergence of the nonlinear algebraic equations that describe the power system, avoiding the singularity of the Jacobian matrix near the maximum loading point. The eigenvalues from the linearization of the differential algebraic equations that describe the dynamic operation of the power system are used to perform stability studies around the equilibrium points of the PV curves [20]. This paper focuses in small oscillatory phenomena, which can be associated with Hopf Bifurcations (HB). These types of bifurcations are identified by the presence of a complex pair of eigenvalues crossing the imaginary axes of the complex plane when the σ √ σ ω (13) Moreover, by using participation factors, a better understanding of the states that influence the dominant or critical modes can be achieved [20]. Time domain simulations are also carried out using PSAT with the aim of studying the system dynamic behaviour under contingency (large-disturbance) operation. These simulations are based on the numerical integration of the differentialalgebraic equations that describe the dynamic operation of the system, and also allow to study the effect on all system variables of wind speed variations. IV. RESULTS The following three study cases are addressed here: • Case A corresponds to the IEEE 14-bus system with synchronous generators, as depicted in Fig. 2. This benchmark system, described in detail in [21], is comprised of two synchronous generators providing active and reactive power connected at Buses 1 and 2, and three synchronous condensers connected at Buses 3, 6 and 8. Automatic voltage regulators (AVR) Type II are incorporated in each machine. The model for the synchronous generator connected at Bus 1 is a 5th order model, and the models for the generator connected at Bus 2 and all the synchronous condensers are 6th order models. The system base load is 259 MW and 81.4 MVAR. In all simulations, the load are represented using exponential recovery dynamic models. • In Case B, the 60 MVA synchronous generator located at Bus 2 in Case A is replaced by an aggregated DFIG-based wind turbine of equivalent size and limits, operating at unity power factor. The corresponding collector system is shown in Fig. 3; two transformation stages are modeled: one from 480 V to 25 kV and the other one from 25kV to 69kV. Detailed data for the DFIG-based wind turbine, wind model and collector system can be found in the Appendix. • In Case C, the DFIG is assumed to operate under terminal voltage control. 4 Fig. 4. PV curves for normal operation. Fig. 5. PV curves for contingency operation. Normal and single contingency (Line 2-4 trip) operation are considered for each study case. A. Case A Figures 4 and 5 depict PV curves for normal and contingency operation respectively. Observe that the static load margin in this case under normal operating condition is 435 MW, while for contingency operation this margin is reduced to 391 MW. Moreover, HBs are identified for a loading level of 341 MW and 329 MW for normal and contingency operation, respectively. The participation factors associate the AVR of the generator connected at Bus 1 with this oscillatory instability, which has a frequency of 1.32 Hz for normal operating condition and 1.31 Hz for contingency operation. Time domain simulations for a Line 2-4 trip at 1s at a loading level of 332 MW is shown in Fig. 6. Notice from this figure the oscillatory instability predicted by the eigenvalue analysis. Fig. 6. Bus 14 voltage. B. Case B The static load margin for Case B under normal operation is depicted in Fig. 4. This margin is 424 MW, which is 2.53% lower than the static load margin for Case A. This reduction is mainly due to the DFIG unity power factor operation, which does not allow for the control of the terminal voltage. As it can be seen from Fig. 5, a similar observation can be made for the system under contingency conditions, where the static load margin becomes 382 MW, which represents a 2.30% reduction with respect to Case A for the same operating conditions. The eigenvalue analysis for Case B shows an important improvement in the dominant mode damping ratios associated with the generator connected at Bus 1. Indeed, for the same loading levels corresponding to the HBs in Case A (341 Mw and 329 MW), the damping ratios become 1.91% and 1.82% for normal and contingency operation, respectively, at similar frequencies as before. The participation factors do not link the DFIG state variables with the oscillatory modes, which is consistent with the observations reported in [17]. If the loading level is increased, an HB can be observed at a 386 MW total load level in normal operating condition. This corresponds to a 25% increase in the dynamic load margin with respect to Case A. Moreover, HBs are not observed for contingency conditions. The above eigenvalue discussion is consistent with the time domain simulations depicted in Fig. 6. Thus, observe that the oscillations in this case are completely damped after 25 s. C. Case C The DFIG-based wind turbine with terminal voltage control operation delivers the reactive power required to keep the voltage at terminals constant at 1.09 p.u. The limits for this reactive power are set so that they are similar to the replaced synchronous generator limits. As can be seen in Fig. 4, the static load margin for Case C under normal operating condition is 431 MW; this value is slightly lower than the Case A static load margin, but 1.6% greater than the margin observed for the DFIG operating at unity power factor. Moreover, in contingency operation, the static load margin for 5 TABLE I DOMINANT- MODE DAMPING AS A FUNCTION OF THE DFIG VOLTAGE CONTROLLER GAIN (NORMAL OPERATION CONDITION AT 341 MW LOADING) Dominant-mode Damping Ratio (%) 10 1.67 11 1.86 12 2.05 13 2.23 14 2.41 15* 2.59 16 2.76 17 2.92 18 3.08 19 3.24 20 3.39 * Base DFIG voltage controller gain Fig.7. DFIGs output power. TABLE II DOMINANT- MODE DAMPING AS A FUNCTION OF THE WIND POWER PENETRATION (NORMAL OPERATION CONDITION AT 341 MW LOADING) Wind Power Dominant-mode Penetration (MW) Damping Ratio (%) 5 0.89 10 1.14 15 1.39 20 1.64 25 1.88 30 2.12 35 2.36 40* 2.59 45 2.81 50 3.04 * Base synchronous generator power output Fig. 8. Wind speed. Fig. 9. Reactive power output. Case C becomes 387 MW, which is 1.3% greater than the corresponding margin for unity power factor operation. The normal and contingency operation dominant mode damping ratios for the same loading levels associated with the HBs in Case A are 2.59% and 2.50%, respectively. These values are roughly 74% greater than those obtained for the DFIG with unity power factor operation. As a result, oscillatory instabilities are not observed in Case C. Figure 6 further demonstrates the better damping response in this case by means of time domain simulations. Observe that oscillations are damped faster than in Case B. Figure 7 illustrates the power output variations associated with wind speed changes for the DFIG operating at terminal voltage control. The output power oscillation at 1s is mostly the result of the voltage drop when Line 2-4 is tripped; after this oscillation is damped, the output power is controlled to optimize the energy extracted from the wind speed shown in Fig. 8. Figure 9 depicts the DFIG reactive power support; notice that the reactive power changes to regulate the terminal voltage and thus increase system security. Results of a sensitivity study of the dominant-mode damping ratios with respect to the DFIG voltage controller gain can be seen in Table I. Observe that there is a linear correlation and the oscillatory mode damping ratios. between the gain This correlation suggests that by properly tuning the voltage controller gain, DFIGs equipped with voltage control 6 TABLE IV WIND MODEL PARAMETERS capabilities can properly damp the oscillatory modes, eliminating the occurrence of oscillatory instability associated with HBs. Table II shows the sensitivity of the dominant mode damping ratio with respect to the wind power penetration. These results suggest that as wind power penetration increases, the damping ratio of the dominant mode improves. For this study, the wind power output connected at Bus 2 was gradually increased from 5 MW to 50 MW at a 342 MW loading level. These wind power output levels range between 1.33 to 15% of the total system generated power. Wind model type Average wind speed vωA (m/s) Air density ρ(kg/m3) Filter time constant τ(s) Sample time for wind measurements Δt (s) Scale factor for Weibull distribution c Shape factor for Weibull distribution k Frequency step Δf (Hz) Weibull Distribution 14.50 1.225 4 0.1 20 2 0.2 TABLE IV COLLECTOR SYSTEM PARAMETERS IV. CONCLUSIONS A comparative stability analysis based on PV curves, modal analysis and time domain simulations of DFIG-based wind generators replacing synchronous generators has been carried out for the IEEE-14 bus system. The obtained results show that the oscillatory behaviour associated with the dominant mode of the synchronous generator is improved when the DFIG-based wind turbine is connected to the system, which is consistent with similar observations by other authors. This improvement in the damping ratio is more evident for DFIG wind turbines operating with terminal voltage control. Moreover, the static load margins are not significantly affected when the DFIG-based wind turbine with voltage control operation replaces an equivalent synchronous generator; the small differences could be accredited to the impedances of the collector system. However, when the DFIG is operated with unity power factor, static load margins are reduced; thus, negatively affecting the system security. First transformation stage Voltage ratio (kV/kV) 0.480/25 Resistance (p.u.) 0.00 Rectance (p.u.) 0.1 Fixed tap ratio (p.u./p.u.) 1.00 Second transformation stage Voltage ratio (kV/kV) 25/69 Resistance (p.u.) 0.00 Rectance (p.u.) 0.1 Fixed tap ratio (p.u./p.u.) 1.00 Transmission line Length of Line (km) 0* Resistance (p.u.) 0.035 Reactance (p.u.) 0.017 Susceptance (p.u.) 1e-3 * Zero indicates to PSAT that the line parameters are given in p.u. REFERENCES APPENDIX [1] TABLE III DFIG PARAMETERS Power rating Sn (MVA) Voltage rating Vn (kV) Frequency rating fn (Hz) Stator resistance Rs (p.u.) Stator reactance Xs (p.u.) Rotor resistance Rr (p.u.) Rotor reactance Xr (p.u.) Magnetization reactance Xm (p.u.) Initial constant Hm (kWs/kVA) Pitch control gain Kp (p.u.) Pitch control time constant Tp (s) Voltage control gain KV (p.u) Power control time constant Te (s) Rotor radius R (m) Number of poles p Number of Blades nb Gear box ratio ηGB Pmax (p.u.) Pmin (p.u.) Qmax (p.u.) Qmin (p.u.) 60.0 0.480 60.0 0.01 0.10 0.01 0.08 3.00 3.00 10 3 15 0.01 75 4 3 1/89 0.9 0.0 0.35 -0.219 V. Akhmatov, “Analysis of dynamic behavior of electric power systems with large amount of wind power,” Ph.D. dissertation, Technical Univ. Denmark, Lyngby, Denmark, 2003. [2] J. G. Slootweg, H. Polinder, and W.L. Kling, “Dynamic modeling of a wind turbine with doubly fed induction generator,” in Proc.2001 IEEE Power Eng. Soc. Summer Meeting, pp.644-649, Jul. 2001. [3] I. Erlich, J. Kretschmann, J. Fortmann, S. Mueller-Engelhardt, and H. Wrede, “Modeling of wind turbines based on doubly-fed induction generators for power system stability studies,” IEEE Trans. Power Syst., vol. 22, pp. 909-919, Aug. 2007. [4] “Dynamic Modeling of Doubly-Fed Induction Machine WindGenerators,” DIgSILENT GmbH, Germany, Aug. 2003. [Online]. Available: http//www.digsilent. de/images/Company/ news/DFIGRev1.pdf. [5] Y. Lei, A. Mullane, G. Lightbody, and R. Yacamini, “Modeling of the wind turbine with a doubly fed induction generator for grid integration studies,” IEEE Trans. Energy Convers., vol. 21, pp. 257–264, Mar. 2006. [6] L.M. Fernandez, F. Jurado, and J.R. Saenz, “Aggregated dynamic model for wind farms with doubly fed induction generator wind turbines,” Renewable Energy, vol.33, no.1, pp. 129-140, Jan. 2008, [Online]. Available: http// www.sciencedirect.com. [7] W. Qiao, “Dynamic Modeling and control of Doubly Fed Induction Generators Driven by Wind Turbines,” in Proc. 2009 IEEE/PES Power Systems Conference and Exposition, pp.1-7, Mar. 2009. [8] P. Ledesma, and J. Usaola, “Effect of Neglecting Stator Transients in Doubly Fed Induction Generators Models,” IEEE Trans. Energy Conv., vol. 19, pp. 459-461, Jun. 2004. [9] F. Mei and B. Pal, “Modal analysis of grid-connected doubly fed induction generators,” IEEE Trans. Energy Conv., vol. 22, pp. 728-736, Jun. 2007. [10] J.G. Slootweg, “Wind power: Modeling and Impact on Power System Dynamics,” Ph.D. dissertation, Delft University of Technology, Delft, Netherlands, 2003. 7 [11] F. Wu, X.-P. Zhang, K. Godfrey, and P. Ju, “Small signal stability analysis and optimal control of a wind turbine with doubly fed induction generator,” in Proc. 2007 IET Gener. Transm. Distrib., pp. 751-760, Sep. 2007. [12] L. Sigrist and L. Rouco, “Design of Damping Controllers for doubly Fed Induction Generators Using Eigenvalue Sensitivities,” in Proc. 2009 IEEE/PES Power Systems Conference and Exposition, pp. 1-7, Mar. 2009. [13] M. V. A. Nunes, J. A. P. Lopes, H. H. Zurn, U. H. Bezerra, and R. G. Almeida, “Influence of the variable-speed wind generators in transient stability margin of the conventional generators integrated in electrical grids,” IEEE Trans. Energy Conv., vol. 19, pp. 692, Dec. 2004. [14] Ch. Eping, J. Stenzel, M. Poller, and H. Muller, “Impact of Large Scale Wind Power on Power System Stability”. DIgSILENT GmbH, Germany, Apr. 2005. [Online]. Available: http//www.digsilent.de/ Consulting/Publications/PaperGlasgow_DIgSILENT.pdf. [15] D. Gautam, V. Vittal, and T. Harbour, “Impact of Increased Penetration of DFIG-Based Wind Turbine Generators on Transient and Small Signal Stability of Power Systems,” IEEE Trans. Power Syst., vol. 24, pp. 1426-1434, Aug. 2009. [16] E. Vittal, M. O’Malley, and A. Keane, “A Steady-State Voltage Stability Analysis of Power Systems With High Penetrations of Wind,” IEEE Trans. Power Syst., vol. 25, pp. 433-442, Aug. 2009. [17] H.A. Pulgar-Painemal and P.W. Sauer, “Power system modal analysis considering doubly-fed induction generators,” in Proc.2010 Bulk Power System Dynamics and Control (iREP) Symposium, pp. 1-7, Aug. 2010. [18] J.J. Sanchez-Gasca, N.W. Miller, and W.W. Price, “A modal analysis of a two-area system with significant wind power penetration,” in Proc. 2004 IEEE PES Power Systems Conf. Expo., pp. 1148-1152. [19] F. Milano, “PSAT, Matlab-based Power System Analysis Toolbox,” 2010, [Online]. Available: http:// www.power.uwaterloo.ca/~fmilano/. [20] A. Gomez-Exposito, A. J. Conejo, and C.A. Cañizares, “Electric Energy Systems: Analysis and Operation” ,vol. I. Boca Raton: CRC press, 2009, pp. 428-452. [21] S. K. M. Kodsi and C. A. Cañizares, “Modeling and simulation of IEEE 14 bus system with Facts controllers,” Tech. Rep., Univ. Waterloo, ON, Canada, [Online] Available: http://www.power.uwaterloo.ca., Mar.2003.