SITOP UPS1600 Brochure 04/2013 24V DC Uninterruptible Power Supply – High-performance, communicative and integrated in TIA If a power failure occurs, not only the AC power goes out but also the 24 V DC supply and thus the complete automation system as well. Costly downtime and undefined system states can be the result. The new DC UPS modules prevent this scenario by providing reliable backup of the 24 volts for hours. They also offer new possibilities for diagnostics and system integration. The SITOP UPS1600 offers comprehensive functions, open communication via USB or Ethernet/Profinet and is the first UPS that is fully integrated in TIA. TheDCUPSmodulescomplement24Vpowersuppliesfrom SITOPforuninterruptedratedcurrentsupto20Afromthe UPS1100batterymodulesbasedonmaintenance-freegel cellbatteries.Viatheintegratedelectronics,theUPS1600 automaticallydetectsthetypeofbatteryandchargesitat theoptimal,temperature-controlledchargingcharacteristics.Theintelligentbatterymanagementsystemmonitorsall relevantdata,includingbatterymodulesconnectedin parallel.Thebatterystatusandvariousvalues,suchasthe voltage,currentorresidualcapacity,areoutputviathe Ethernet/Profinetinterface.Evenremotediagnosticsis possiblethankstoanintegratedwebserver. TheslimUPS1600DCUPSmodulefeaturesdynamicoverloadbehavior,whichcanbeusedtoactivateindustrialPCs, forexample.Thehighchargingcurrentquicklyrestoresthe bufferingcapacityfollowingapowerfailure.Andforusein stand-alonemode,theUPScanbeactivatedfrombattery withoutinputvoltage,forexample,tostartgenerators. The benefits at a glance •CompactDCUPSmodulesSITOPUPS160024VDC/10A and20Awithdigitalinputsandoutputs,optionallywith USBortwoEthernet/Profinetinterfaces •BatterymodulesSITOPUPS110024VDC/3.2Ahand 7Ahwithmaintenance-freegelcellbatteriesand integratedelectronics •Intelligentbatterymanagementwithautomatic detectionofbatterymodulesandselectionoftheoptimal,temperature-controlledchargingcharacteristics. Monitoringofoperationalreadiness,batteryfeed,age andchargelevel. •AlldiagnosticdataandalarmsavailableviaUSBand Ethernet/Profinet •Highdynamicoverloadcapacity:3timesratedcurrent for30msand1.5timesratedcurrentfor5sec.per minute •Highchargingcurrents •Startfrombatterymoduleswhenmainsvoltageis unavailable •Remotemonitoringwithintegratedwebserver •SITOPUPSManager(freesoftwaredownload)supports configurationandmonitoringwithPC-basedsystems •FullintegrationinTIA:Convenientengineeringinthe TIAPortal,S7functionblocksforintegrationinuser programsandWinCCfaceplates Answers for industry. SITOP UPS1600 – the first open... Whetheropenorsystem-integrated,thecommunicativeDCUPScanbeintegratedintoanyautomationsolution. FullyflexibledatacommunicationisperformedviaUSBorIndustrialEthernet/Profinet.Specialconfigurationand visualizationsoftwaremakesiteasytointegratetheDCUPSinbothPCandPLCbasedsystems.Youbenefitfromthe highperformanceoftheSITOPUPS1600inanycase. The advantages of the SITOP UPS1600: Integration in PC-based systems Open communication via Industrial Ethernet Control Control, configuration/ monitoring IndustrialPC IndustrialPC •Easyconfigurationandmonitoringvia SITOPUPSManager,runsonallcommon Windowssystems PC •Comprehensivediagnosticcapabilitiesusingthestatus oftheDCUPSandtheconnectedenergystorage •ConnectionviaUSBorEthernet IndustrialEthernet 24VDC •TargetedshutdownofmultiplePCs (master-slaveprinciple) •Closingofsoftwareapplications Energystoragelink SITOP UPS1600 SITOP UPS1100 •IntegratedOPCserver G_KT01_XX_00796 Power supply SITOP 24 V DC Uninterruptible power supply •Remotemonitoringviaintegratedwebserver, accesstodeviceconfigurationinformationand operatingdata,forexample,mains/buffermode, outputpower,chargingcurrentandbatterystatus SITOP UPS1600 in PC-based automation systems: ConfigurationandmonitoringisperformedviathePC software,SITOPUPSManager.Ifapowerfailureoccurs, the24VDCbufferandtheintegrationoftheDCUPSin IndustrialEthernetenablescontrolledshutdownof multiplePCsinmaster-slavemode. Remote monitoring via the web server: Theintegratedwebserverprovidesaccesstoallrelevant powersupplydata,ofcourse,onlywithappropriate identification. 2 SITOP UPS1600 Configuration and monitoring with the SITOP UPS Manager: Thefreesoftwaretoolsupportseasyconfigurationofthe UPSinthePCsystemandalsovisualizationofthevarious statesoftheUPS,forexample,intheformoftrendcharts. Technicaldata DC USV modules Order numbers withoutinterface withUSBinterface with2Ethernet/Profinetinterfaces Input data RatedinputvoltageUinrated/range Connectionthresholdforbuffering InputcurrentIinrated Mains buffering Adjustablerangeusingarotarycodingswitch Behavioronrestorationofinputvoltageafter bufferingtime On/offcontrolcircuit(viaexternalfloatingNOcontact) Startfrombatteryduringmissinginputvoltage (viaexternalfloatingNOcontact) Energy storage Connectablebatteries Output data Outputvoltageinnormaloperation Outputvoltageinbufferingmode Output+Bat/-Batinnormaloperation End-of-chargevoltage Ratedoutputcurrent •Powerboostfor30ms •ExtraPowerfor5s/min Chargingcurrent Efficiencyonnormaloperationandloadedbattery Protection and monitoring Polarityreversalprotection Overload/short-circuitprotection Signaling Normaloperation/Bufferingmode Chargingstatus(over85%charged) Alarm(notreadyforbuffering) Batterystatus PROFINETInterface Ethernet General details Radiointerferencelevel(EN55022)/noiseimmunity Protectionclass Degreeofprotection(EN60529) Ambienttemperatureduringoperation (naturalconvection) Transport/storagetemperature Dimensions(WxHxD)inmm Weightapprox. Installation Approvals SITOP UPS1600 24 V DC/ 10 A SITOP UPS1600 24 V DC/ 20 A 6EP4134-3AB00-0AY0 6EP4134-3AB00-1AY0 6EP4134-3AB00-2AY0 6EP4136-3AB00-0AY0 6EP4136-3AB00-1AY0 6EP4136-3AB00-2AY0 24 V DC/21...29V 22.5VDC±3%(factorysetting),adjustable: 21V,21.5V,22V,22.5V,23V,24V,25VDCorviasoftware. approx.14Aduring approx.25Aduring max.chargecurrent(3A) max.chargecurrent(4A) 0.5min,1min,2min,5min,10min,20min, max.bufferingtimeorviasoftware InterruptionofUoutfor5sfortheautomaticrestartofPCsoroptionallyno interruption byopeningthecircuitthebuffermodeisterminated byclosingthecircuitthebuffermodeisstarted –codedSiemenstypesSITOPUPS1100(max.6viaEnergyStorageLink) –uncodedSiemenstypes6EP1935-6M… –othermanufacturers RatedinputvoltageUinlessapprox.0.2V 27VDC(noload);24V(50%batteryratedcurrent); 22VDC(100%batteryratecurrent);18.5VDC(exhaustivedischargeprotection) I-Uchargingcharacteristic (firstrapidchargingcurrent,thenconstantvoltageforchargeretention) automatictemperature-managedadjustmentwithbatterymodules SITOPUPS1100 0 ... 10 A 0 ... 20 A 30A 60A 15A 30A max.3A max.4A automaticadjustmentwithUPS1100; automaticadjustmentwithUPS1100; otherwiseselectable otherwiseselectable 0.3A,0.8A,3A 0.8A,1.75A,4A >=95% >=95% againstreversaloninputvoltageUinandagainstbatteries yes,restartinnormaloperation LED1(O.K./BAT)green/yellowandfloatingchangeovercontact1 LED2(BAT.>85%)greenandfloatingchangeovercontact3 LED3(Alarm)redandfloatingchangeovercontact2 LED4(BAT.FAULT))redandfloatingchangeovercontact2:Batteriedefect, yellow:selectedbuffertimenotensured,yellowflashing:overtemperature LED5(SF)greenandLED6(RUN) LED7(P1)green/yellowandLED8(P2)green/yellow,LinkandActivity ClassB/NoiseimmunitytoEN61000-6-2 ClassIII(ext.circuitandpower-supplyunit: SELVinaccordancewithEN60950required) IP20 -25...+70°C(Deratingfrom+60°C) -40...+85°C 50x125x125 0.4kgwithoutinterface,0.42kgwithUSB, 0.45kgwithEthernet/PROFINETinterfaces SnapsontoDINrailDINEN50022-35x15/7.5 CE,cULus,C-Tick;KCC;GL,ABS,ATEX SITOP UPS1600 3 Technicaldata Battery modules SITOP UPS1100 24 V DC, 3.2 Ah SITOP UPS1100 24 V DC, 7 Ah For SITOP UPS1600 10 A 10 A and 20 A Ordernumber 6EP4133-0GB00-0AY0 6EP4134-0GB00-0AY0 Recommendedend-of-chargevoltage (automaticsettingfromSITOPUPS1600): 26.4…27.3VDC(>+20°C),27.3…29.0VDC(<+20°C) Chargingcurrent max.0.8A Ratedoutputvoltage 24VDC,22...27.0VDC(noload) Ratedoutputcurrent 15A 30A Integralbatteryfuse 15A/32V 30A/32V Signaling LEDgreen:batteryok.,greenflashing:defectorwarning, off:batteryoff,nocommunication Degreeofprotection(EN60529) IP00 Ambienttemperature -10…+50°C Transport/storagetemperature -40…+85°C Servicelife(whencapacityfallsto50%oforiginal capacity),dependingonbatterytemperature,approx. +20°C:4years+30°C:2years,+40°C:1year,+50°C:0.5years Installation Standardrailorwallmounting Wallmounting Dimensions(WxHxD)inmm 190x169x79.5 186x186x110.5 Weightapprox. 3.8kg 6.1kg Certifications CE,cULus,C-Tick;KCC;GL,ABS,ATEX max.1.75A Buffer times Loadcurrent... 1A 2.6h 5.4h 2A 1h 2.6h 3A 39.3min 1.6h 4A 27.1min 1.2h 6A 17.5min 41min 8A 12.1min 28.6min 10A 9min 21.8min 12A ² 17.3min 14A ² 16A ² 20A 4 SITOP UPS1600 15.1min 12.5min ² 9.1min ...and system-integrated DC UPS System integration in TIA Control SIMATICS7- 300/400/ 1200/1500, Step7 Operation and Monitoring PanelPC/PC SIMATICHMI, WinCC Engineering PCWinCC, SCADA- System PG/PC, TIAPortal, Step7 PROFINET 24VDC Power supply SITOP SITOP UPS1600 SITOP UPS1100 Engineering in the TIA Portal: TheintegrationoftheDCUPSintoProfinetissimpleand reliable. G_KT01_XX_00797 Energystoragelink 24 V DC Uninterruptible power supply SITOP UPS1600 in Totally Integrated Automation: EngineeringissimpleviatheTIAPortal.Ifapowerfailure occurs,the24VDCbufferandtheintegrationofthe DCUPSinProfinetenablesthePLCstobebroughttoa definedstateindependentofoneanother.Thefunction blocksofSIMATICS7-300,400,1200and1500are availableforthis.Thecomprehensivediagnosticdataof thepowersupplycanbevisualizedbyvariousdevices, forexample,viaUPSfaceplates. Engineering in the TIA Portal: TheUPSconfigurationisalsoeasytoperform,because theconfigurationdataofUPS1600andUPS1100are storedintheTIAPortal. Advantages of the SITOP UPS1600: System integration •FullintegrationinTIAsavestimeandmoneyin planningandoperation •ConvenientengineeringofSITOPDCUPSin theTIAPortal •Fastselectionofproductsandnetwork integrationinProfinet •Comprehensivedeviceconfiguration •Comprehensivediagnosticcapabilitiesusing thepowersupplystatus •EasyintegrationinSTEP7userprogramswith functionblocksforS7-300/400/1200/1500(free download) •FastintegrationintheHMIwith“UPSfaceplates”for SIMATICPanelsandSIMATICWinCC(freedownload) Faceplates for diagnostics in WinCC: MonitoringisquicklyprovidedwithprefabricatedSITOP UPS1600faceplates.AllrelevantdataoftheDCUPSand thebatterycanbeseenataglance.Alarmmessages,for example,ifbufferreadinessisnotavailable,arealso generated,whichsavesadditionalprogrammingwork. SITOP UPS1600 5 Additional information MoreinformationonSITOPDCUPS: www.siemens.com/sitop-ups Informationmaterialfordownload: www.siemens.com/sitop-infomaterial TheSITOPSelectionToolforselectingtheappropriate powersupply: www.siemens.com/sitop-selection-tool Operatinginstructionsasdownload: www.siemens.com/sitop/manuals CAxdata(2D,3D,circuitdiagrammacro)asdownload: www.siemens.com/sitop-cax ElectronicorderingviatheInternetwiththeIndustryMall: www.siemens.com/industrymall Yourpersonalcontactpartnerislistedat: www.siemens.com/automation/partner SiemensAG IndustrySector IndustryAutomation P.O.Box4848 90026NUREMBERG GERMANY www.siemens.com/automation Subjecttochangewithoutpriotnotice OrderNo.6ZB5341-0AQ02-0AA0 MP.R1.SC.0000.77.3.20/Dispo10001 BR04132.0SB6En PrintedinGermany ©SiemensAG2013 Theinformationprovidedinthisbrochurecontainsmerelygeneral descriptionsorcharacteristicsofperformancewhichincaseofactual usedonotalwaysapplyasdescribedorwhichmaychangeasaresult offurtherdevelopmentoftheproducts.Anobligationtoprovidethe respectivecharacteristicsshallonlyexistifexpresslyagreedinthe termsofcontract. Allproductdesignationsmaybetrademarksorproductnamesof SiemensAGorsuppliercompanieswhoseusebythirdpartiesfortheir ownpurposescouldviolatetherightsoftheowners.