CD 0018 Directed to: Mayor Vanderheyden and Members of Council

advertisement
Municipality of Strathroy- Caradoc
Page 1 of 2
Staff Report #: CD 0018
Directed to:
Mayor Vanderheyden and Members of Council
Council Meeting Date:
December 15, 2014
Prepared
by:
Andrew Meyer, Community Development Manager
Brad Dausett, Roads Manager
Attachment(s):
Department:
Community & Cultural Services
Payback Calculation
Material Specifications
Subject:
LED Street Lighting Project
RECOMMENDATION
THAT: Council authorizes staff to negotiate with Entegrus Powerlines Inc. as project manager
to further develop a Request for Proposals for the implementation of the LED Street Lighting
Project, to be considered as part of the 2015 budget.
BACKGROUND
In 2014, the Municipality of Strathroy-Caradoc developed an Energy Consumption & Demand
Management Plan as part of its compliance with the Green Energy Act legislation. The plan
included a target of 5% reduction in energy consumption by 2020. In order to achieve this goal,
Council and staff have actively pursued opportunities to realize greater efficiencies within
operations to decrease energy demand.
Over the last several months, members of municipal staff have investigated the costs
associated with the retrofit of all existing street light fixtures with energy efficient Light Emitting
Diode (LED) technology. The Municipality of Strathroy-Caradoc currently owns and operates
an inventory of 1,992 street lights in the community of Strathroy, and 260 in the community of
Mount Brydges through Local Distribution Company (LDC) Entegrus Powerlines Inc. StrathroyCaradoc also owns and operates 90 additional street lights in the rural areas of the
municipality, which fall within LDC Hydro One territory.
CONSULTATION
Working with Entegrus, a complete audit of existing street lighting within Strathroy and Mount
Brydges was completed to assess potential savings through conversion to LED fixtures,
resulting in a conversion proposal that estimates a reduction of over 196 kW of connected
load, or a reduction of between 53.6% and 57.1% in energy consumption (taking into account
only the 2,252 fixtures located within Entegrus territory). See attached Payback Calculation for
more information. The fixtures located in Hydro One territory must also be included in any LED
upgrade proposal moving forward to ensure that a complete replacement program is achieved,
adding further reduction in overall energy consumption.
As part of their review, Entegrus has provided detailed specifications for the appropriate LED
lighting, with site-specific requirements based on factors such as desired luminosity, road
surface, pole placement, etc. See attached Material Specification for Roadway Luminaires for
1
more information.
FINANCIAL IMPLICATIONS
The proposal developed by Entegrus provided an outline of financial implications for the
fixtures located within Entegrus territory only. Before proceeding with the project, a complete
audit of fixtures for Hydro One territory must be added to the scope of work, and special areas
where specialized lighting is required (ie. decorative light standards in downtown Strathroy)
must also be completed.
Examining only the 2,252 fixtures in Entegrus territory, the proposal outlines a projected capital
cost for fixture replacement at $648,130, including a 10% Project Management Fee. The
proposal also estimates approximately $145,984.87 in annual energy savings, and a
$35,190.60 reduction in maintenance costs due to the longevity of LED roadside luminaires.
Based on these calculations, it is estimated that the cost of retrofitting the complete inventory
of street lighting in Entegrus territory would see a return on investment after only 3.5 years
(see attached Payback Calculation for more detail).
COMMENTS & NEXT STEPS
Based on the review above, it is recommended that the municipality engage Entegrus
Powerlines Inc. to further define the needs of the municipality in terms of street lighting in
Hydro One territory and areas requiring specialized lighting requirements. Once the
appropriate data is gathered, a project management agreement will be established with
Entegrus for Council review and approval. With a satisfactory agreement in place for project
management, Entegrus will proceed with a public Request for Proposals process in
compliance with the municipal Purchasing & Procurement Policy in order to determine an LED
fixture supplier and installation contractor.
Moving forward with the support of the Local Distribution Company will provide the expertise
and experience necessary to ensure that the municipality achieves the best possible outcome.
Entegrus brings to the project a vested interest in the long term viability of the system, and the
ability to assist the municipality in acquiring the maximum rebate funding through available
Ontario Power Authority incentives. With this in mind, the proposed 10% project management
fee is a responsible investment and reasonable for a project of this scope.
With Council approval to move forward, the LED Street Lighting Project would proceed in the
spring of 2015, and be accomplished over an 18 month period, with full completion achieved in
2016.
Staff will be available to answer questions regarding the report.
Prepared by:
Reviewed by:
Andrew Meyer
Community Development Manager
Ralph Coe
Chief Administrative Officer
2
Entegrus
Strathroy
LED Streetlighting Conversion Project
Simple Payback Calculation (Sep 2014)
Cobra Head Evaluation (HPS to LED)
Energy Cost per Kwh = $.169
Annual Operating Hours= 4,380
Existing System (HPS)
LED Option
..,
- ". ..
Total
Annual
Operating
Costs
Ql
t;
70
100
150
200
250
400
ti r:
"'C
0
0
0
95
130
190
250
300
465
0
1161
687
0
144
0
0.0
150.9
130.5
0.0
43.2
0.0
Totals:
1992
324.66
Initial Capita l Cost;
Annual Energy Savings;
Reduction in Maintenance Cost;
Re duction in Connected Load :
Simple Payback:
iii ~
:::l
1:
~
...
...
Ql
VI
"
0
$
s 111,837.03
s
$
$
s
96,720.92
32,010.60
-
$240,568.55
$0 .00
$20,317.50
$12,022.50
$0.00
$3,240.00
$0.00
$35,580.00
$
$
132,154.53
108,743.42
$
$
35,250 .60
s
s
LED
Syste m
Para me te rs
iii
~
:::l ...
"
Ql
~
~
30 LEO 350mA
30 LED 525mA
30 LEO 700mA
60 LED 525mA
60 LED 52SmA
96 LED 700mA
so
50
95
190
190
190
$276,148.55
$523,239 plus 10% Project Manageme nt fees ($76,640) =
$129,226.35
53.7%
$31,197.60
87.7%
53.6%
174.0 kW
3.59 Years
$575,563
0
1161
687
0
144
0
0.0
58.1
65.3
0.0
27.4
0.0
1992
150.7
...
"'
0
$
s
$
s
s
Tota l
Annual
Operating
Costs
42,896.40
48,227.96
20,217.84
$
$111,342.20
$0.00
$2,554.20
$1,511.40
$0.00
$316.80
$0 .00
$4,382.40
$
$ 234,522.00
$ 254,877.00
s
s
s
33,840.00
$523,239.00
Entegrus
Mt Brydges
LED Streetlighting Conversion Project
Simple Payback Calculation (Sep 2014)
Cobra Head Evaluation (HPS to lED)
Annual Operating Hours = 4,380
' nergy Cost per Kwh= $.16'
Existing System (HPS)
lED Option
Total
Annual
Operating
Costs
70
100
150
200
250
400
95
130
190
250
300
465
Totals:
0
178
79
0
0
3
0.0
23.1
15.0
0.0
0.0
1.4
260
39.545
Initial Capital Cost;
Annual Energy Savings;
Reduction in Maintenance Cost;
Reduction in Connected Load :
Simple Payback:
$
-
$ 17,146.42
$11,122.20
$
$
-
$ 1,033.68
$29,302.30
$0 .00
$3,115.00
$1,382.50
$0.00
$0.00
$67.50
$4,S6S.OO
LED
System
Parameters
Total
Capital
Cost
$ 20,261.42 30 LED 52SmA
so
so
$ 12,504.70 30 LED 700mA
60 LED 525mA
$
60 LED 525mA
$ 1,101.18 96 LED 700mA
95
190
190
190
$
-
$
30 LED 350mA
$33,867.30
$65,970 plus 10% Project Management fees ($515,608 $72,567
$16,758.52
57.2%
$3,993.00
87.5%
22.6 kW
57.1%
3.50 Years
$
-
0
178
79
0
0
3
0 .0
8.9
0.0
0 .0
0.6
$
$
-
$
260
17.0
7.5
421.20
$0.00
$391.60
$173.80
$0.00
$0.00
$6.60
$0
$35,956
$29,309
$0
$0
$705
$12,543.78
$572.00
$65,970.00
$ 6,576.71
$ 5,545.86
ENTEGRUS
MATERIAL SPECIFICATION
LIGHT EMITTING DIODE (l~D}
ROADWAY LUMINAIRES
This specification is for the evaluation and purchase of Light Emitting Diode (LED) roadway lighting
luminaires for mounting on mast arms attached to power utility poles or independent street-lighting
concrete, wood or aluminum poles. Applications shall include municipal standard local, collector, and arterial
roadways and intersections. Luminaires must meet the general requirements of this specification Part I and
demonstrate satisfactory energy and photometric performance as described in Part II.
Part I-General Spedfication
References
The publications listed below form a part of this specification to the extent referenced . Publications
are referenced within the text by their basic designation only.
A.
American National Standards Institute (ANSI)
1. ANSI C136.2-2004 (R2009), American National Standard for Roadway and Area Lighting
Equipment- Luminaire Voltage Classification
2.
ANSI C136.3-2005, American National Standard for Roadway and Area Lighting EquipmentLuminaire Attachments
3.
ANSI C136.10-2006, American National Standard for Roadway Lighting Equipment- LockingType Photocontrol Devices and Mating Receptacle Physical and Electrical Interchangeability
and Testing
4.
ANSI C136.25-2009, American National Standard for Roadway and Area Lighting Equipment
- Ingress Protection (Resistance to Dust, Solid Objects and Moisture) for Luminaire
Enclosures
5.
ANSI C136.31-2001, American National Standard for Roadway Lighting Equipment Luminaire Vibration
B. American Society for Testing and Materials International (ASTM)
1. ASTM B117-97- Standard Practice for Operating Salt Spray (Fog) Apparatus
C.
Illuminating Engineering Society of North America (IESNA)
1.
DG-4-03, Design Guide for Roadway Lighting Maintenance (DG-4-11 is being voted on)
2.
LM-79-08, IESNA Approved Method for the Electrical and Photometric Measurements of
Solid-Sate Lighting Products
3.
LM-80-08, IESNA Approved Method for Measuring Lumen Maintenance of LED Light Sources
4.
RP-8-14, ANSI
5.
RP-16-05 and addenda, "Nomenclature and Definitions for Illuminating Engineering"
I
IESNA American National Standard Practice for Roadway Lighting
6. TM-15-11, "Luminaire Classification System for Outdoor Luminaires"
7. TM-21-11, «Projecting Long Term Lumen Maintenance of LED Light Sources»
D.
Institute of Electrical and Electronic Engineers {IEEE)
1.
ANSI/IEEE C62.41.2-2002 -IEEE Recommended Practice on Characterization of Surges in
low-Voltage (1000 V and less) AC Power Circuits
2.
ANSI/IEEE C62.45-2002 - IEEE Recommended Practice on Surge Testing for Equipment
Connected to low-Voltage (100 V or less) AC Power Circuits.
E.
National Electrical Manufacturers Association (NEMA)
1.
ANSI/N EMA/ANSLG C78.377-2008- American National Standard fo r the Chromaticity of
Solid State lighting Products
F.
Underwriters laboratories (Ul)
1.
UL 1449, Surge Protective Devices
2.
Ul1598, lum inaires
G. Canadian Standards Association
1.
CSA Standard C22.2 No. 250.0-08, luminaires (Tri-national standard with Ul-1598 and NMXJ-307/l-ANCE)
l,f:D l..uminaire ~
1) Housing
a) Cobra-H(!_ad _S_tyle
i)
The housing shall be of rugged, highly corrosion resistant, light weight die cast aluminum alloy.
ii)
The lumina ire housing shall be painted with a durable polyester powder coat. Castings shall be
pre-treated using a 5-stage iron phosphate system to assure adhesion. Colour is to be neutral
grey.
iii)
lumina ire components and applied finishes shall pass the 1000 hour salt test per ASTM 8117
standard.
iv) luminaires shall be horizontal mast arm mountable and allow for continuous adjustment in
the vertical plane of+ I- 3 deg. A four bolt hex head clamping assembly shall provide secure
attachment of the luminaire to the supporting mast arm. The assembly shall accommodate 1.25
to 2 inch pipe size mast arms.
v)
Where small metal machine screw fastening hardware is utilized in the luminaire assembly it
shall be of a material that is corrosion resistant and compatible with the housing material. The
hardware will have a Robertson or hex head drive. Flat or Philips head drives are not
acceptable.
vi) Internal system components, clamping assembly and terminal block shall be accessible without
the use of tools. Access doors shall be latched, swing down to the open position and be
mechanically secured to the main housing. Drivers and LED array modules must be mounted
internally, be modularly replaceable, and be easily accessible for replacement.
vii) The luminaire shall be CSA or cUL listed for wet locations. The LED optical module shall be sealed
and tested to IEC spec 529 to meet a rating of IP66 for particulate and moisture ingress.
Power supply I driver unit shall also be rated IEC IP66. The housing shall contain measures that
prevent the entry of birds.
viii) The outer exposed surface of the optical system shall be designed so that there will be no
adhesion of snow and minimal dirt collection that will block normal egress of light. The
system exterior shall also be easy to clean by hand. All light transmitting materials must
be high UV stabilized or glass so as not to discolour due to sunlight or high luminous flux
transmission over its expected operational life.
ix) The luminaire and all subcomponents are to be free of designated hazardous substances that
would otherwise prevent it from being disposed of in a normal regulated Ontario landfill site or
recycled without any special type of treatment or disassembly.
x) The luminaire shall operate within specifications for an operating ambient temperature range of
-40° C to + 40° C.
xi) Luminaire shall meet ANSI C136.31 (current version) for 3.0 G vibration for use on normal
roadways and bridges.
xii) The Vendor shall indicate the extent and nature of operational type testing for which the
lumina ire has been evaluated for the fo llowing:
(1) Ambient thermal cycl ing . (i.e . freeze - thaw)
(2) Ice formation and bu ild-up.
xiii) Each luminaire shall be safety certified to CSA C22.2 No. 250.0-08 or have an equivalent listing
from a recognized testing laboratory for the approved sale and use in Canada. Applicable labels
shall be applied inside each unit.
xiv) Each lumina ire shall have a label permanently fixed inside the unit that identifies the
manufacturer's essential product information including, date of manufacture, electrical
schematic diagram, and operating specifications.
2) Photometric; Performance
a) The lumina ire LED light source shall emit white to cool white light with a nominal CCT in the range
of 4000°K. Colour variation from the nominal luminaire rating over the operating life is to
observe tolerance ranges consistent with ANSI standard C78.377-2008 "Specifications for the
Chromaticity of Solid State Lighting" .
b) The luminaire zonal lumen distribution above goo vertical shall be zero as defined by IESNA
technical memorandum TM-15-11, "Luminaire Classification System (LCS) for Outdoor Luminaires".
c)
Colour Rendering Index (CRI) shall
be~
65 .
d) The luminaire shall be tested for photometric and electrical performance in accordance with the
IESNA LM-79-08 "Approved Method for the Electrical and Photometric Measurements of Solid
State Lighting Products". The test laboratory must hold National Voluntary Laboratory
Accreditation Program (NVLAP) accreditation for the IES LM-79 test procedure. For more
information, see ht~p:ffwwwl.eere .~fler:gy,gov/bu i ldings/ssl[t~_st_labs . html .
e) A copy of the manufacturer's LM-79 photometric report for each wattage, CCT, drive current, and
distribution type proposed shall be submitted for review.
f) The luminaire shall maintain a minimum of 70% of initial lumen output (L70) at 88,000 hours when
operated within specified operating parameters at an ambient temperature of 25°C. The
manufacturer shall indicate the expected number of operating hours to L70 at an ambient
g)
temperature of 25°C as calculated using procedures outlined in IES TM-21-11 (Projecting Long
Term Lumen Maintenance of LED Light Sources). The manufacturer shall provide a total assembled
luminaire system (LED package, housing, optical & electrical components) lumen depreciation
curve for each separate wattage, drive current and distribution type proposed .
The LED chip manufacturer shall have tested the lumen maintenance characteristics of the LED
chip in accordance with the guidelines of IESNA LM-80-08 "Approved Method for Lumen
Maintenance Testing of LED Light Sources". A copy of the manufacturer's LM - 80 reports shall
be submitted for review.
3) Electrical
a)
The Lumina ire shall contain a surge protection device (SPD) to protect all electrical and electronic
components from harmful line transient voltage surges as a result of utility line switching, lightning
strikes, or other electrical supply system disturbances. The SPD for luminaires to be wired at 120V
shall meet a 10 KA, 10 KV surge level and meet application and testing requirements per ANSI I IEEE
C.62.41.2 for Category C High operation and ANSI I IEEE C62.45. For luminaires to be wired at a
higher voltage (ie 240 or 347V) the SPD shall be rated for Category C Low.
b)
Utility supply wiring to the lumina ire shall terminate in a barrier-type terminal block secured to the
housing. The terminal block shall have wire grips suitable for No. 14 AWG to no. 6 AWG wire sizes.
All internal wiring shall be copper, 600V rated and insulated to lOST
c)
The Luminaire shall be available with or without a photoelectric control receptacle. If required,
the receptacle shall be a 3-prong twist lock type conforming to ANSI standard C136.10 and capable of
being adjustable directionally without tools.
d) The nominal operating voltage shall be 120 VAC +1- 10%, 60Hz.
e) The LED driver shall be designed to operate maintenance-free for a minimum of 100,000 hours at
25° C ambient.
f)
The LED driver shall have a power factor ~ 0.90.
g) The THO (current and voltage) induced into the AC supply line shall not exceed 20%.
h)
Luminaire driver electrical I electronic component devices shall comply with Industry Canada
ICES Interference Causing Equipment Standards for RF emissions.
i)
Drivers with switchable or dimmable drive current ratings are acceptable .
j)
It may be the intention of Entegrus to dim luminaires during night-time operating hours,
therefore it is desirable, but not mandatory, to have units with an optional dimming capability
should the town decide to include a dimming control system. Dimming control should either
be through a pre-programmed internal switching device, by a wireless control system, or a
combination of both. As an option, the manufacturer shall state its product's capability
for dimming, requirements to make its luminaire "dim-ready", what accessories would be
needed in the base luminaire unit, and what the capital cost adder would be.
4) Quality Assurance
a)
Before bulk purchase, Entegrus may request for inspection one or more standard- production-model
luminaire samples identical (including LED package) to product proposed to be installed. Owner
may request independent testing of sample luminaires to verify luminaire performance and
compliance with the specifications.
b) After in stallation, Entegrus may perform field measurements and/or send luminaires to an
independent laboratory for testing to confirm photometric performance.
5} Pack~gj[lg & Shipping
a) The luminaire shall be shipped as a single self-contained unit in its own boxed container. The
luminaire shall be fully assembled at the factory and not require any on site assembly. Each un it
shall include installation and ope rating instructions.
6}
Warranty
a) The manufacturer shall warrant the replacement of any component due to manufacturing
defect or failure of that component (including LED array and LED driver) for a period of 10
years from date of delivery. Alternatively, the manufacture may opt to repl ace the
entire luminaire at no cost to Entegrus.
PART II- LUMINAIRE PHOTOMETRIC AND ENERGY PERFORMANCE EVALUATION
A; Design Standards
1) It is of primary importance to Entegrus that LED roadway lighting equ ipment conforming to this
specification achieves significant energy usage reduction over the currently used High Pressure Sodium
roadway lighting systems while meeting or exceeding IESNA RP-8-14 Table 3 photometric performance for
luminance level, uniformity and glare control.
It is the intent of this specification to have Vendors, as part of the prequalification process, perform
lighting installation photometric and energy usage calculations for typical municipal roadways using
their selected product. Entegrus will evaluate to what extent the product can deliver the required energy
and lighting performance required for its roadways. Table A summarizes these typical example
roadways. Typical Sections 1 - 7 in Table 2 depict 7 typical municipal roadway geometries to be used
for evaluation purposes by the Vendor. The "typical" calculations will be used to evaluate the product's
suitability to light the roadways under the following three construction scenarios:
2)
a)
New Construction - Independent stand-alone street lighting system with optimized pole spacings and
luminaire selection . Fixed mounting heights and mast arm lengths shall be observed.
b)
New Construction- New street lighting luminaires installed onto new electric utility distribution
poles. Fixed mounting heights, and pole spacings shall be observed.
c)
Retrofit Programs- New street lighting luminaires for retrofit onto existing poles and mast arms . Fixed
mounting heights, pole spacings, and mast arm lengths shall be observed.
Design Restrictions
a)
In reference to the typica l roadway Figures 1- 7, it is not intended to deviate from the indicated
mou nting heights of 6.7 meters for cobra head style lum inaires due to a reluctance to change
from current construction and equipment standards. It is also not possible to change the
location of the poles as indicated relative to the edge of pavement as this is mandated by Entegrus to
avoid underground and surface utility location conflicts.
3)
Energy Usage
a)
4)
Vendors shall calculate the total energy input for a one kilometer section of straight street for
streets depicted in Typical Sections 1- 7
Light Loss Factors
a)
It is the responsibility of each manufacturer to provide a calculation of Lamp Lumen Depreciation (LLD)
for each photometric file used. LLD shall be based on actual lumen depreciation values reached at
87,600 hours at 25° C luminaire ambient and as proven by LM-80 back-up information and as
calculated using the procedures outlined in TM-21-11 as required under section C.4.
b)
For this evaluation, the LDD attributable to accumulation of ambient airborne particulates onto
the luminaire's exposed light emitting surfaces shall be 0.90. The LOO figure of 0.90 was derived
from Figure 2 in IESNA DG-4-03 corresponding to a 5 year exposure time and the "very clean" dirt
condition curve. It is Entegrus's intent to continue to clean the exterior of the light emitting shield
I refractors once every 5 years. Airborne particulate levels (PM 2.5) as recorded in 2009 by the
Ontario Ministry of the Environment did not exceed 150 micro grams per cubic meter in the
Southwestern Ontario area.
5) Installation Life
a)
It is Entegrus' s expectation that the in-service life of a typical LED luminaire installation will be 20 years.
This corresponds to an 87,600 hour on-time operating life based on 4380 hours of operation
annually.
6) Lighting Performance
a)
Lighting levels, uniformity ratios, and veiling luminance ratios are from the IESNA RP-8-14
Recommended Practice Table 3 and are required to be met for roadways depicted in Typical Sections 1
- 9 . These lighting requirements are indicated in Table 1.
b) The indicated lighting levels in Table 1 are those to be present at the end ofthe 20-year luminaire
useful life. They shall observe the 25 deg. C ambient operating temperature, the manufacturer's
light engine LLD and the 0.90 LDD attributable to accumulation of operating ambient particulates.
(Refer to Item 4 above)
c)
Photometric calculations shall recognize only photopic lumens and will not incorporate any
mesopic multiplier factor. Calculations shall observe current IESNA calculation and
measurement methods.
B; Required Submittals for Each Luminair~-~
1) Product cut-sheets
a)
Shall indicate a complete and unique catalogue number for each product submitted
b) All components of catalogue numbers shall be identifiable as options and explained
c)
Lumina ire input current, LED drive current, and nominal Correlated Color Temperature (CCT) shall
be clearly indicated.
d) Shall include complete specifications for LED light source(s), including make/model#
2)
e)
Shall include complete specifications for LED driver(s), including make/model#
f)
Shall include complete specifications for any integral controls, including make/model#
g)
Shall include documentation supporting claims of luminaire recyclability
Luminaire photometric report per IES LM-79 including
a)
Name of independent test laboratory
i)
The test laboratory must hold National Voluntary Laboratory Accreditation Program (NVLAP)
accreditation for the IES LM-79 test procedure. For more information, see
ht!Qjf~'!"JW1 . eere.en~rgy.govf~!Jjlf:!ings/ssl/test_La_!:!~bJrn l .
b)
Report number
c)
Date
d) Complete luminaire catalogue number, consistent with submitted product cut-sheet
3)
e)
Description of luminaire, LED light source, and LED driver(s)
f)
Photometry
g)
Colorimetry
Computer-generated point-by-point photometric analysis of maintained light levels as per Table A.
a)
Calculations shall be for maintained values, i.e. Light Loss Factor (LLF) < 1.0, where LLF
i)
=LLD x LDD
Lamp Lumen Depreciation (LLD); determined by the process outlined in Para . 4 of the Design
Standards section.
ii)
Luminaire Dirt Depreciation (LDD) = 0.90, as per IES DG-4-03 for an enclosed and gasketed
roadway lumina ire installed in an environment with airborne particulate matter less than 150
3
~g/m and cleaned every five years.
b) Calculation/measurement points shall be as per IES RP-8-14 Figure A4
4)
Documentation supporting claims of expected L70 useful life, as per Appendix B
a)
Provide IES LM-80 report from manufacturer of LED chip used in lumina ire
b)
Provide ISTMT report
c)
Provide TM-21-11 computed charts illustrating interpolation between TMP curves from LM-80 data
for lumen maintenance at TMP from ISTMT report
i)
TMP interpolation is only valid for same drive current
5)
Written product warranty per section C; below.
6)
Safety certification and file number per the CEC. Recognized Testing Laboratories include: CSA
(Canadian Standards Association), ETL (Edison Testing Laboratory), and UL (Underwriters Laboratory).
1) Provide a written ten-year warranty covering material, workmanship, and fixture finish. Finish warranty
shall include warranty against failure or substantial deterioration such as blistering, cracking, peeling,
chalking, or excessive fading.
2)
Provide a written ten-year replacement material warranty for defective or non-starting LED source
assemblies (Light engines) . Light engine failure will be defined as the fa ilure of ~ 15% of the individual
LED chips.
3)
Provide
a written ten -year replacement material warranty on all drivers (power supplies).
4) Warranty period shall begin on date of receipt of material from the supplier. The suppl ier will provide
Entegrus with appropriate signed warranty certificates.
Vendor .Ev~l u~tion~
Vendors shall be required to tabulate energy and photometric calculation results in table 2 for each roadway. If the indicated
lighting requirements cannot be met by the proposed luminaire for the given parameters, the Vendor shall indicate the best
that could be achieved. The vendor shall also calculate the maximum achievable spacing for each Typical Section. This
will be used to develop optimized spacings for new construction applications.
Table 1
Example Roadways to be evaluated
Roadway
type
Pedestrian
Conflict
Luminance
cd/m 2
Uniformity
Avg/Min
Uniformity
Max/Min
Veiling
Luminance
Ratio
(min)
(max)
(max)
Lv max/Lavg
Typical
Section
No.
Local
Low
0.3
6.0
10.0
0.4
1
Local
Low
0.3
6.0
10.0
0.4
2
Collector
Low
0.4
4.0
8.0
0.4
3
Collector
Medium
0.6
3.5
6.0
0.4
4
Major
Low
0.6
3.5
6.0
0.3
5
Major
Low
0.6
3.5
6.0
0.3
6
Major
Medium
0.9
3.0
5.0
0.3
7
Table 2
Date:
Sample Roadway Calculation Summary
Vendor:
Typical Section 1 Cobra Head Style- Local Low: 2 Lane- 3.6m Lane width,
0 ne s ·d
.
7 3 m MH 1 2 m set b ac k 2 4 m arm
1 e f IXe d 55 m spacmg,
Manufacturer Total Unit Total System
Photometric Performance- Luminance
& Model
Input Watts Input watts LAverage
Uniformity
Uniformity
Veiling
1 KM Road cd/sq. m
Lavg/Lmin
Lmax/Lmin Luminance
Typical Section 2 Cobra Head Style - Local Low : 2 Lane- 3.6 m lane width,
Two-side (Staggered) I fixed 91 m spacingI 7 3m MH I 1 2 m setback I 24m arm
Manufacturer Total Unit Total System
Photometric Performance - Luminance
Uniformity Uniformity
Input Watts Input watts LAverage
Veiling
& Model
Lavg/Lmin
Lmax/Lmin Luminance
1 KM Road cd/sq. m
Typical Section 3 Cobra Head Style -Collector Low: 2 Lane- 3.6 m lane width, with
1m bike lane. One side fixed 40 m spacings, 7 3m MH, 18m setback, 2.4 m arm
Manufacturer Total Unit Total System
Photometric Performance- Luminance
& Model
Input Watts Input watts LAverage
Uniformity Uniformity
Veiling
1 KM Road cd/sq. m
Lavg/Lmin
Lmax/Lmin Luminance
4 CobrLHead Style- Collector Medium: 2 Lane- 3.6 m lane width, with
Centre turn lane, two sided (Staggered), fixed 4S m spacing, 7.3 m MH, 1.8 m setback,
24m arm
Manufacturer Total Unit Total System
Photometric Performance- Luminance
Input Watts Input watts LAverage
& Model
Uniformity Uniformity
Veiling
1 KM Road cd/sa. m I Law/Lmin
Lmax/Lmin Luminance
T~Section
Typical Section 5 Cobra Head Style- Major low: 2 Lane- 4.2 m lane w idth with diagonal parking
both sides, two sided (Staggered), fixed 42 m spacing, 7.6 m MH, 0.5 m setback, 1.2 m arm
Manufacturer Total Unit Total System
Photometric Performance- Luminance
& Model
Input Watts lnputwatts LAverage
Veiling
Uniformity Uniformity
1 KM Road cd/sq. m
Luminance
Lavg/Lmin
Lmax/Lmin
Typical Section 6 Cobra Head Style - Major Low· 4 Lane - 3 6 m lane width I
Two sided (Staggered), fixed 70 m spacing, 7.6 m MH 1.8 m setback 1.8 m arm
Manufacturer Total Unit Total System
Photometric Performance - Luminance
& Model
Input Watts Input watts LAverage Uniformity Uniformity
Veiling
1 KM Road cd/sq . m Lavg/Lmin Lmax/Lmin Luminance
Typical Section 7 Cobra Head Style - Major Medium: 4 Lane- 3.6 m lane width, with 2.5 m
Median strip, two sided (opposite), fixed 40 m spacing, 7.3 m MH, 1.2 m setback, 2.4 m arm
Manufacturer
Total Total System
& Model
Unit
Input watts
Input 1 KM Road
Photometric Performance- Luminance
Watts
LAverage Uniformity Uniformity
Veiling
cd/sq . m Lavg/Lmin Lmax/Lmin Luminance
Download