TEST REPORT IEC 61643-1 / EN 61643-11 Surge

Test Report issued under the responsibility of:
TEST REPORT
IEC 61643-1 / EN 61643-11
Surge-protective devices connected to low-voltage power systems
Requirements and tests
Report Reference No. .................... :
5007032-1181-0008/147768-04
Date of issue..................................... :
16.01.2012
Total number of pages ......................
47
CB/CCA Testing Laboratory .......... :
Address ............................................ :
VDE Prüf- und Zertifizierungsinstitut GmbH
VDE Testing and Certification Institute
Merianstraße 28, 63069 Offenbach, Germany
Applicant’s name ............................ :
HAKEL spol. s.r.o.
Address ............................................ :
Bratri Stefanu 980, 500 03 HRADEC KRALOVE
Test specification:
Standard ........................................... :
IEC 61643-1:2005 (Second Edition) and/or
EN 61643-11:2002 + A11:2007
Test procedure ................................. :
CB/ CCA
Non-standard test method…………..:
N/A
Test Report Form No. .................... :
IECEN61643_1C
Test Report Form(s) Originator ........ :
OVE
Master TRF ...................................... :
Dated 2007-07
Copyright © 2007 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme
procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended
to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
If this Test Report Form is used by non-CCA members, the CIG logo and the reference to the CCA Procedure shall be
removed.
This report is not valid as a CCA Test Report unless signed by an approved CCA Testing Laboratory and
appended to a CCA Test Certificate issued by an NCB in accordance with CCA
Test item description ..................... :
Surge protective device
Trade Mark ....................................... :
Manufacturer .................................... :
HAKEL spol. s.r.o.
Model/Type reference....................... :
PIIIM-275; PIIIM-275 DS
Ratings ............................................. :
Uc = 275 V, Imax = 50 kA, In = 20 kA, Up ≤ 1,3 kV
Page 3 of 47
Report No.: 5007032-1181-0008/147768-04
Summary of testing:
Tests performed (name of test and test clause):
Testing location:
Test series 1 clause 7.2
P
VDE
Test series 8 clause 7.9.5.2 / 7.9.6
P
VDE
Test series 1, 2, 3, 5, 7, 8
P
IPH
Annex 1
Residual voltage, current-voltage oscillograms
IPH
Annex 2
Residual voltage, discharge current – residual voltage diagrams
IPH
Annex 4
Operating duty test, Preconditioning oscillograms
IPH
Annex 5
Operating duty test, current-voltage oscillograms
IPH
Summary of compliance with National Differences:
Copy of marking plate:
TRF No. IECEN61643_1C
Page 4 of 47
Report No.: 5007032-1181-0008/147768-04
Test item particulars .................................................. :
Number of ports:
One port / Two port
SPD design topology:
Voltage switching / Voltage limiting / Combination
SPD type (and test class):
Type 1 (I) / Type 2 (II) / Type 3 (III)
Location:
Indoor / Outdoor
Accessibility:
Accessible / Inaccessible
Mounting method:
Fixed / Portable
SPD Disconnector:
Internal / External / Both
Protection functions:
Thermal / Leakage current / Overcurrent
Overcurrent protection:
Specified / Not specified
Degree of protection (IP code):
IP20
Temperature range:
Normal / Extended
Required SPD-disconnectors:
Fuse-Link 500 V a.c. / 160 A gG (IEC 60269-2)
Possible test case verdicts:
- test case does not apply to the test object.................. : N/A
- test object does meet the requirement ....................... : P (Pass)
- test object does not meet the requirement ................. : F (Fail)
Testing .......................................................................... :
Date of receipt of test item ............................................ : 2011-04-05 - 2011-08-04
Date (s) of performance of tests ................................... : 2011-04-15 - 2011-08-05
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Note: This TRF includes EN Group Differences together with National Differences and Special National
Conditions, if any. All Differences are located in the Appendix to the main body of this TRF.
Throughout this report a comma (point) is used as the decimal separator.
This test report has to be read in conjunction with 5007032-1181-0008/147768-01.
General product information:
The suffix “DS” in the marking means that the SPD is provided with remote control contact.
TRF No. IECEN61643_1C
Page 5 of 47
Report No.: 5007032-1181-0008/147768-04
If not otherwise specified all tests have been carried out on three samples per test sequence.
Terminal tests have been carried out on three terminals of each construction used.
Impulse tests have been carried out according to chapters 7.1.1 to 7.1.4.
SPD Type 1 (Test class I):
I (kA)
Calculation of charge Q and specific energy W/R after operating duty test
acc. to 7.6.5 - test sequence 3 (measured values)
Q (As) within 10 ms
W/R (kJ/Ω)
0,1* Ipeak = _____
0,25* Ipeak = _____
0,5* Ipeak = _____
0,75* Ipeak = _____
1,0* Ipeak = _____
If a product covered by another international standard than IEC 61643 incorporates SPD technology the
requirements of the other international standard shall apply to those parts of the product not influenced by the
presence of the SPD technology.
Unless otherwise specified, a.c. values given in this report are r.m.s. values.
If not otherwise specified the tests have been performed in free air and at an ambient temperature
of (20 ± 15)°C.
If not otherwise specified, for all tests where a power supply at UC is required, the voltage
+0
tolerance for testing was /-5%.
If the SPD is supplied with integral cables, the full length of these cables forms part of the SPD under test,
except for the determination of the measured limiting voltage 7.5, where a lead length of 150 mm is
used.
SPD disconnectors have been selected and connected as required by the manufacturer, where applicable.
SPD disconnectors have been tested with the SPD during the sequence of type tests of 7.7 and 7.8.3,
except for RCDs, which are not tested during the operating duty test according to 7.7.1.
For SPDs having more than one mode of protection, for which the manufacturer declares a voltage protection
level, the tests have been performed on each mode, with the values chosen according to the manufacturer's
declaration, using new samples each time. For three phase devices in which the protective component
circuitry per given mode is identical, the testing may be performed on each of the three phases which fulfils
the three sample requirement.
If the manufacturer sets different requirements for the external SPD disconnector(s) depending upon the
prospective short-circuit current of the supply system, all relevant test sequences have been performed for
every combination of required SPD disconnector(s) and corresponding prospective short-circuit currents.
Remarks:
Test program: see page 6.
TRF No. IECEN61643_1C
Page 6 of 47
Report No.: 5007032-1181-0008/147768-04
Test program:
PIIIM-385 / PIIIM-385 DS
5007032-1181-0008/147768-02
PIIIM-440 / PIIIM-440 DS
5007032-1181-0008/147768-01
Samples
Samples
Samples
PIIIM-275 / PIIIM-275 DS
5007032-1181-0008/147768-04
PIIIM-320 / PIIIM-320 DS
5007032-1181-0008/147768-03
Test program and test samples
Seq.
Test discription
Clause
Identification and marking
6.1.1/ 6.1.2/ 7.2
Terminals and connections
Testing for protection against direct contact
Standby-Power consumption and residual current
Samples
1.7
1.8
1.9
6.2.1/ 6.3/ 7.3
-
-
-
-
-
-
-
-
-
1.16 1.17 1.18
6.5.1/ 7.4
-
-
-
-
-
-
-
-
-
1.16 1.17 1.18
6.5.3/ 6.5.4/ 7.7.5
1.7
1.8
1.9
1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18
Protection level
6.2.2/ 7.5
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10 2.11 2.12
Residual voltage
7.5.2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10 2.11 2.12
Front of wave sparkover voltage
7.5.3
-
-
-
-
-
-
-
-
-
-
-
-
Limiting voltage with combination wave
7.5.4/ 7.5.5
-
-
-
-
-
-
-
-
-
-
-
-
Determination of the magnitude of the follow current
7.6.2
-
-
-
-
-
-
-
-
-
-
-
-
Operating duty test
6.2.6/ 7.6
3.7
3.8
3.9
3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18
Preconditioning
7.6.4/ 7.7.1
3.7
3.8
3.9
3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18
Class I and II operating duty test
6.2.3/ 6.2.4/
7.6.5/7.6.6/ 7.7.1
3.7
3.8
3.9
3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18
Class III operating duty test
6.2.5/ 7.6.7/ 7.7.1
-
-
-
-
-
-
-
-
-
-
-
-
4
Class I and II total discharge current
6.5.6/ 7.9.10
-
-
-
-
-
-
-
-
-
-
-
-
5
Test of thermal stability
6.2.7/ 7.7.2
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
6
Short-circuit withstand capability test
6.2.7/ 6.2.11/ 7.7.3
-
-
-
-
-
-
-
-
-
TOV test
6.2.7/ 6.5.5/ 7.7.6
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
TOV test
6.2.7/ 6.5.5/ 7.7.4
-
-
-
-
-
-
-
-
-
-
-
-
Flexible cables and cords and their connection
7.9.1
-
-
-
-
-
-
-
-
-
6.3/ 6.5.1.1/ 7.9.2.1
-
-
Mechanical strength
-
Mechanical strength
6.3/ 6.5.1.1/ 7.9.2.2
-
-
-
-
-
-
-
-
-
Insulation resistance
6.5.1.3/ 7.9.7
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
Dielectric withstand
6.2.10/ 7.9.8
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10 8.11 8.12
Environment, IP code
6.4/ 6.5.1/ 7.9.9
-
-
-
-
-
-
-
-
-
8.10 8.11 8.12
8.10 8.11 8.12
1
2
3
7
8
1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18
5.10 5.11 5.12
6.1
6.2
6.3
6.4
6.5
6.6
7.10 7.11 7.12
8.10 8.11 8.12
-
-
-
8.10 8.11 8.12
Heat resitance
6.5.1.2/ 7.9.3
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
Air clearences and creepage distances outdoor
6.2.8/ 7.9.5.1
-
-
-
-
-
-
-
-
-
Air clearences and creepage distances indoor
6.2.8/ 7.9.5.2
8.1
8.2
8.3
-
-
-
-
-
-
8.10 8.11 8.12
Resistance to abnormal heat and fire
6.5.2/ 7.9.4
-
-
-
-
-
-
-
-
-
8.10 8.11 8.12
Tracking resistance
6.29/ 7.9.6
8.1
8.2
8.3
-
-
-
-
-
-
8.10 8.11 8.12
-
-
-
Additional test fort two-port SPDs and on one-port SPDs with seperate input/ output terminals
9
Percentage voltage regulation
6.6.1/ 7.8.1
-
-
-
-
-
-
-
-
-
-
-
-
Rated load current
6.6.2/ 7.8.2
-
-
-
-
-
-
-
-
-
-
-
-
Load side surge withstand
6.6.3/ 7.8.4
-
-
-
-
-
-
-
-
-
-
-
-
Overload behavior
6.6.4/ 7.8.5
-
-
-
-
-
-
-
-
-
-
-
-
Load side short-circuit withstand capability test
6.2.7/ 7.8.3
-
-
-
-
-
-
-
-
-
-
-
-
Status indicator operation
6.2.12
-
-
-
-
-
-
-
-
-
P
P
P
Isolation between seperate circuits
6.2.13
-
-
-
-
-
-
-
-
-
P
P
P
Additional checks and tests
10
TRF No. IECEN61643_1C
Page 7 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 1
Clause
6.1.1/6.1.2
Requirement - Test
Result
Verdict
HAKEL/
PIIIM-275
PIIIM-275 DS
P
275 V
P
Identification and Marking
Markings on the body or permanently attached to
a) Manufacturer/Trade mark/Model number
e) Maximum continuous operating voltage UC
(for each mode) and rated frequency
50 / 60 Hz
f) SPD test classification/type and discharge
parameters for each mode of protection
No. of modes
1
P
Class I test / Type 1
IImp
_____ kA
N/A
Class II test / Type 2
Imax
50 kA
P
_____ kV
N/A
20 kA
P
h) Voltage protection level Up
< 1,3 kV
P
j)
Degree of protection if > IP20
IP _____
N/A
l)
Maximum overcurrent protection
160 A
P
_____
N/A
a.c./d.c./both
P
indoor/outdoor
P
1
P
fixed/portable
P
_____ A
N/A
60 kA
P
Indicating devices of
external and internal
disconnectors
P
_____
N/A
Class III test / Type 3 UOC
g) Nominal discharge current In for test class I / Type 1
and test class II / Type 2 SPDs (for each mode)
o) Identification of terminals, if necessary
q) Type of current
Information provided by the manufacturer
b) Location category
c) Number of ports
d) Method of mounting
i)
Rated load current IL, if required
k) Short circuit withstand
m) Indication of disconnector operation, if any
n) position of normal use, if significant
TRF No. IECEN61643_1C
Page 8 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 1
Clause
Requirement - Test
Result
Verdict
p) Installation instructions (type of LV systems: TN, TT,
IT etc , connections to LV systems and rated system
voltages for which the SPD is designed, mechanical
dimensions, lead lengths, etc..)
TN
TT ( L-N only)
P
_____ kJ/Ω
N/A
normal/extended
P
t) Follow current interrupting rating
(except in case of voltage limiting SPDs)
_____ A
N/A
u) External SPD disconnector requirements
fuse link 160 A gG
P
r) Specific energy W/R for Type 1 SPDs (class I test)
s) Temperature range
v) Residual current (optional)
w) Temporary overvoltage characteristic at UT
x) Total discharge current ITotal for multipole SPDs
(if declared by the manufacturer)
N/A
334 V
P
______
N/A
Markings indelible and legible, not placed on screws
and removable washers
7.2.2
6.5.3/6.5.4/
7.7.5
P
Test applied to markings not made by impressing,
molding or engraving:
15s rubbing by hand with cotton soaked with
- water
- aliphatic solvent hexane
P
After test marking easily legible
P
Standby Power Consumption and Residual Current
Test
The SPD is connected to a voltage source at its
maximum continuous operating voltage (UC) according
the manufacturers instruction. The Apparent Power
(Volt-Amperes) consumed by the SPD is measured.
The current at the PE terminal is called the residual
current..
Notes
1:
If the manufacturer allows more than one
configuration for the SPD installation, this test
should be performed for every configuration.
2:
The true r.m.s. current value is measured.
Remarks:
TRF No. IECEN61643_1C
UC = 275 V
PC = 0,90 VA
IPE = 3,28 mA
P
Page 9 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 2
Clause
6.2.2
7.5.
Requirement - Test
Voltage protection level Up
Measured limiting voltage
Result
PIIIM-275 DS
Measured limiting voltage does not exceed the
protection level specified by the manufacturer
P
SPDs tested acc. to class I and II perform 7.5.2
P
SPDs tested acc. to class I and II containing switching
components perform 7.5.3 in addition
N/A
SPDs tested acc. to class III perform 7.5.4 or 7.5.5
N/A
One port SPDs are tested unenergized
Two port SPDs are tested energized at UC
with a source having a nominal current ≥ 5 A
P
_____ V
_____ A
For a one-port SPD having terminals, the test is
performed without external disconnectors and the
measured limiting voltage is measured at the terminals.
For a one-port SPD having connecting leads, the
measured limiting voltage is measured with an external
lead length of 150 mm.
Measured limiting voltage = highest value measured
N/A
P
For a two-port SPD, and a one-port SPD having
separate load terminals, the measured limiting voltage
is measured at the load port or load terminals of the
SPD.
7.5.2
Verdict
N/A
1,155 kV
P
Residual voltage with 8/20 current impulse
Test with current impulses of
0,1 times In
_____kA / _____V
0,2 times In
_____kA / _____V
0,5 times In
_____kA / _____V
1,0 times In
20 kA / 1,155 kV
With one sequence of positive and one sequence of
negative polarity
P
P
Finally one impulse at Imax or Ipeak if Imax or Ipeak > In
with polarity that showed higher residual voltages during
previous tests
TRF No. IECEN61643_1C
50 kA / 1,750 kV
P
Page 10 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 2
Clause
Requirement - Test
Result
Time interval between impulses long enough for sample
to cool down to ambient
Verdict
P
Current -voltage oscillograms
see Annex 1
P
Discharge current - residual voltage diagram
showing peak values
see Annex 2
P
- Ipeak or In whichever is greater for class I test
_____ kV
N/A
- In for class II test
1,155 kV
P
Value for determination of the measured limiting voltage
= highest voltage on the curve corresponding to:
7.5.3
Front-of-wave sparkover voltage
The 1,2/50 voltage impulse is used. The generator
voltage is set to an open circuit output voltage of 6 kV
N/A
10 impulses applied to the SPD,
five of positive and five of negative polarity
N/A
Time interval between impulses long enough for sample
to cool down to ambient
N/A
If sparkover is not observed during any of the 10
impulses on the front of the wave, then the above
procedure is repeated, but with a generator open circuit
output voltage of 10 kV.
Voltage oscillograms
Value for determination of the Measured limiting voltage
is the maximum value of the sparkover voltages
recorded during the whole test sequence
7.5.4
N/A
see Annex 3
N/A
_____ kV
N/A
_____ V
N/A
Measured limiting voltage with combination wave
Sample energised at UC
For a.c. rated SPDs positive impulses are applied at
90°±10°el point and negative impulses at 270°±10°el
point of the sinusoidal voltage wave
N/A
Time interval between impulses long enough for sample
to cool down to ambient
N/A
TRF No. IECEN61643_1C
Page 11 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 2
Clause
Requirement - Test
Result
Verdict
Test with voltage settings of:
0,1 times UOC
_____ kV
____ V / ____ kA
0,2 times UOC
_____ kV
____ V / ____ kA
0,5 times UOC
_____ kV
____ V / ____ kA
1,0 times UOC
_____ kV
____ V / ____ kA
With four surges, two of positive and two of negative
polarity, applied at each setting
Current -voltage oscillograms
Value for determination of the Measured limiting voltage
= maximum peak voltage recorded
Remarks:
TRF No. IECEN61643_1C
N/A
N/A
see Annex 1
N/A
_____ V
N/A
Page 12 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3
Clause
6.2.6/7.6
Requirement - Test
Operating duty test
Result
Verdict
PIIIM-275 DS
Determination of the measured limiting voltage:
SPDs tested acc. to class I and II:
Residual voltage acc. to 7.5.2 at In only with
one positive and one negative impulse applied
20 kA / 1,120 kV
P
_____ kV
N/A
SPDs tested acc. to class I and II containing switching
components:
Sparkover voltage acc. to 7.5.3
All measured peak values (5 pos./ 5 neg.) below UP
SPDs tested acc. to class III:
_____ kV
Measured limiting voltage acc. to 7.5.4 or 7.5.5 at UOC
only with four surges (2 pos./ 2 neg.)
7.6.3
____ V / ____kA
N/A
275 V
P
Power frequency source for preconditioning:
Sample connected to power frequency source at UC
SPDs with follow current < 500 A:
Voltage at the SPD terminals does not fall below the
peak value of UC by more than 10% during flow of follow
current
P
SPDs with follow current > 500 A:
Power frequency voltage Uc with a prospective short
circuit current equal to the follow current interrupt rating
Ifi declared by the manufacturer in accordance with
Table 11, or 500 A, whichever is greater.
For SPDs connected between neutral and protective
earth only, the prospective short-circuit
current shall be at least 100 A.
Recovery voltage acc. to IEC 60947-1
7.6.4
_____ kA
cos phi = _____
N/A
γ = _____
N/A
fγ = _____ Hz
Class I and II preconditioning test
15 current impulses 8/20 of positive polarity in 3 groups
of 5 impulses, peak value equal to In or Ipeak, whichever
is greater, each impulse synchronized to the power
frequency, starting from 0°el the sync. angle is
increased in steps of 30°±5°,
time interval between the impulses 50s - 60s
time interval between the groups 25min - 30min
TRF No. IECEN61643_1C
20 kA
sync. 0°, 30°, 60°, 90°,
120°, 150°, 180°, 210°,
240°, 270°, 300°, 330°,
0°, 30°, 60°el
P
Page 13 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3
Clause
Requirement - Test
Current records show no sign of puncture or flashover
of the sample
7.6.7
Result
Verdict
see Annex 4
P
Class III preconditioning test
Power frequency source according to 7.6.3,
Combination wave generator adjusted to UOC
15 impulses of positive polarity in 3 groups of 5
impulses, peak value equal to UOC, each impulse
synchronized to the power frequency voltage at the
corresponding positive peak value
time interval between the impulses 50s - 60s
time interval between the groups 25min - 30min
Current records show no sign of puncture or flashover
of the sample
7.6.5
_____ kV
sync. 90°el
N/A
see Annex 4
P
Class I and II operating duty test
SPD energized at UC by a voltage source having a
nominal current capability of ≥ 5 A
275 V
30 A
Power frequency voltage remains applied for 30min
after each impulse to prove thermal stability
P
P
Test with current impulses of positive polarity initiated in
the corresponding positive peak value of the power
frequency voltage, one impulse for each value:
0,1 times Ipeak for class I test or Imax for class II test
5,0 kA
0,25 times Ipeak for class I test or Imax for class II test
12,5 kA
0,5 times Ipeak for class I test or Imax for class II test
25,0 kA
0,75 times Ipeak for class I test or Imax for class II test
37,5 kA
1,0 times Ipeak for class I test or Imax for class II test
50,0 kA
After each impulse cool down to ambient temperature
7.6.7
P
P
Class III operating duty test
SPD energized at UC by a voltage source having a
nominal current capability of ≥ 5 A
_____ V
_____ A
Power frequency voltage remains applied for 30min
after each impulse to prove thermal stability
TRF No. IECEN61643_1C
N/A
N/A
Page 14 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3
Clause
Requirement - Test
Result
Verdict
Test with impulses of positive polarity initiated in the
corresponding positive peak value of the power
frequency voltage:
0,1 times UOC
_____ kV
0,25 times UOC
_____ kV
0,5 times UOC
_____ kV
0,75 times UOC
_____ kV
1,0 times UOC
N/A
_____ kV
After each impulse cool down to ambient temperature
7.6.6
N/A
Pass criteria
After each impulse thermal stability
P
Any follow current is self extinguished
P
Voltage and current records and visual inspection show
no indication of puncture or flashover and no
mechanical damage of the sample
see Annex 5
P
No mechanical damage
P
One more impulse at In or UOC shall be applied to the
SPD whilst the SPD is energized at Uc by means of a
voltage source having a nominal current capability of at
least 5 A. After this impulse, UC remains applied and
thermal stability shall be achieved within 30 min.
P
Once thermal stability is achieved, either:
•
the current which flows through the test sample is
measured. Its resistive component (measured at
the crest of the sine wave) shall not exceed a value
of 1 mA.
P
or
•
the stand-by power consumption shall not be
greater than 20% above the value measured in
7.7.5
Following this complete test sequence and after the
sample has cooled down to near ambient temperature,
the measured limiting voltage test, which was made at
the beginning of the test sequence, shall be repeated.
TRF No. IECEN61643_1C
N/A
P
Page 15 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3
Clause
Requirement - Test
Result
Verdict
20 kA / 1,230 kV
P
_____ kV
N/A
SPDs tested acc. to class I and II:
Residual voltage acc. to 7.5.2 at In only with
one positive and one negative impulse applied
SPDs tested acc. to class I and II containing switching
components:
Sparkover voltage acc. to 7.5.3
All 10 measured peak values (5 pos./ 5 neg.) below UP
SPDs tested acc. to class III:
_____ kV
Measured limiting voltage acc. to 7.5.4 or 7.5.5 at UOC
only with four surges (2 pos./ 2 neg.)
7.7.1
____ V / ____kA
N/A
No SPD disconnector has operated during the test and
they are in working order after the test.
P
Values of measured limiting voltage test measured
before and after the test are below or equal to Up
P
Remarks:
TRF No. IECEN61643_1C
Page 16 of 47
Report No.: 5007032-1181-0008/147768-04
For TEST SEQUENCES 5, 6 and 7
Clause
6.2.7/7.7
Requirement - Test
Result
Verdict
SPD disconnectors and safety performance of
overstressed SPDs
SPD disconnector operation is indicated
P
SPD disconnectors tested with the SPD during the type
tests of 7.7 and 7.8.3, except for RCDs which are not
tested during operating duty test according to 7.7.1.
P
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 5
Clause
Requirement - Test
7.7.2
Test of thermal stability of SPDs
7.7.2.1
Temperature withstand test
7.7.2.2
Result
Verdict
PIIIM-275 DS
SPD kept in a heating cabinet at an ambient
temperature of (80 ± 5)°C for 24 h
P
No SPD disconnector has operated
P
Thermal stability test
This test is not performed on SPDs containing only
voltage switching components.
Any voltage switching component, which is connected in
series with a voltage limiting component, is shortcircuited by a copper wire with a diameter such that it
does not melt during the test.
N/A
N/A
For SPDs with different non-linear components
connected in parallel, this test is performed for every
current path of the SPD by disconnecting/interrupting all
the remaining current paths.
If components of the same type and parameters are
connected in parallel, they shall be tested as one
current path.
TRF No. IECEN61643_1C
N/A
Page 17 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 5
Clause
Requirement - Test
Result
P
Test for SPDs having no switching components in
series with other components - Procedure a)
Sample connected to a power frequency source with a
voltage high enough to drive a constant current, which is
increased by the following steps - 2 mA or 5 % of the
previously adjusted test current, whichever is greater with a tolerance of ± 10% :
Verdict
duration
2 mA r.m.s. or corresponding crest value
0,33 h
4 mA r.m.s. or corresponding crest value
0,33 h
6 mA r.m.s. or corresponding crest value
0,50 h
8 mA r.m.s. or corresponding crest value
0,83 h
10 mA r.m.s. or corresponding crest value
0,50 h
12 mA r.m.s. or corresponding crest value
0,67 h
14 mA r.m.s. or corresponding crest value
0,67 h
16 mA r.m.s. or corresponding crest value
0,27 h
______ mA r.m.s. or corresponding crest value
_____ h
______ mA r.m.s. or corresponding crest value
_____ h
P
Each step is maintained until thermal equilibrium is
reached - temperature variation < 2 K within 10 min
P
Surface temperature of the hottest spot and current
through the SPD are monitored continuously
P
Test interrupted if all non-linear components under test
are disconnected. The voltage is not increased further in
order to avoid any malfunction of the disconnector(s).
If the voltage across the SPD falls below Uc during the
test, the current regulation is discontinued and the
voltage is adjusted back to Uc (EN 61643-11 Ucs)
and maintained for a duration of 15 min. Continuous
current monitoring is no longer required.
Source short-circuit current capability does not limit the
current before any disconnector operates. The
maximum available current value does not exceed the
short circuit withstand capability declared by the
manufacturer.
TRF No. IECEN61643_1C
P
_____ V
_____ kA
cos phi = _____
N/A
Page 18 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 5
Clause
Requirement - Test
Result
N/A
Test for SPDs having switching components in
series with other components - Procedure b)
SPD energized with a power frequency source at UC
having a short-circuit current capability which does not
limit the current before any disconnector operates.
The maximum available current value does not exceed
the short-circuit withstand capability declared by the
manufacturer.
Verdict
_____ V
_____ kA
cos phi = _____
If no significant current flows - further testing acc to
Procedure a)
N/A
N/A
Pass criteria
Indoor SPDs:
max 46,2 K
Surface temperature always less than 120°K during test
and less than 80°K, 5min after disconnector operation
≤ 29,2 K after 5min
P
Outdoor SPDs:
No evidence of burning and no expulsion of solid
material
N/A
Accessible SPDs:
SPDs having an IP degree ≥ IP 2X - No live parts
accessible with standardised test finger applied with a
force of 5 N, except the ones which are accessible
when the SPD is fitted as in normal use
For disconnectors having operated there is clear
evidence of effective and permanent disconnection checked with power frequency voltage equal to UC
applied for 1min - current flow ≤ 0,5 mA r.m.s
TRF No. IECEN61643_1C
P
275 V
< 0,5 mA
P
Page 19 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 7
Clause
7.7.6
Requirement - Test
Test under TOVs caused by faults in the low
voltage system
If U C is greater or equal to U T there is no
requirement for testing.
7.7.6.1
Result
PIIIM-275 DS
_______
N/A
Test procedure:
New set of samples used and fitted as in normal use
according to the manufacturer's instructions.
The surge protective device is placed in a cuboid
wooden box whose sides are 500 mm ± 50 mm
away from the SPD external surfaces. The internal
surface of the box is covered with muslin paper or
cheese cloth. One of the box sides (not the bottom)
remains open in order that the supply cables can be
connected according to the manufacturer's
instructions.
The test sample is connected for a duration of
+5
tT = 5 s /-0% to a power frequency voltage of
+0
UT /-5% as given in Table B.1, or greater TOV-voltages
which the manufacturer has declared in accordance
with item w) of 6.6.1.
This voltage source shall be capable of delivering a
current either high enough to ensure that the
voltage at the SPD terminals does not fall below U T
- 5% during the test or at the declared short circuit
withstand of the SPD, whichever is lower.
Immediately following the application of U T a
voltage equal to U CS +0,-5 % with the same current
capability, is applied to the test sample for a period
of 30 min. The time interval between the test
periods shall be as short as possible and in any
case not exceed 100ms.
7.7.6.2
Verdict
P
front side
P
334 V
4000 A
P
253 V
4000 A
0 ms
P
Pass criteria:
The muslin paper or cheese cloth did not catch fire
during the test.
SPDs having an IP degree equal or greater than
IP20 do not have live parts accessible with the
standardized test finger applied with a force of 5 N
(see IEC 60529), except for those live parts which
were already accessible before the test when the
SPD is fitted as in normal use.
TRF No. IECEN61643_1C
P
P
Page 20 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 7
Clause
Requirement - Test
a)
Verdict
_____ mA
N/A
TOV failure mode :
If a disconnector has operated, there shall be clear
evidence of effective and permanent disconnection
by the device.
To check this, a power frequency voltage equal to
U C is applied for 1 min without current flow in
excess of 0,5 mA r.m.s.
b)
Result
TOV withstand mode :
The SPD has maintained thermal stability
during the application of UCS (following the application
of UT). The SPD is considered to be thermally stable if
the current flowing through it or its power dissipation
does not continue to increase during the total time of
application of UCS.
The test sample is then connected to UC. The
test transformer shall have a short circuit current
capability of at least 200 mA. The current, which flows
through the test sample, is measured.
Its resistive component (measured at the crest of the
sine wave) shall not exceed a value of 1 mA
or
P
P
the stand-by power consumption shall not increase
by more than 20 % of the value measured in 7.7.5.
_____
SPDs tested acc. to class I and II:
Residual voltage acc. to 7.5.2 at In only with
one positive and one negative impulse applied
20 kA / 1,23 kV
P
_____ kV
N/A
SPDs tested acc. to class I and II containing switching
components:
Sparkover voltage acc. to 7.5.3
Average of 10 measured peak values (5 pos./ 5 neg.)
SPDs tested acc. to class III:
_____ kV
Measured limiting voltage acc. to 7.5.4 or 7.5.5 at UOC
only with four surges (2 pos./ 2 neg.)
____ V / ____kA
N/A
Auxiliary circuits, like status indicators, are in
working order.
P
Visual inspection of the test sample shall reveal no
evidence of any damage.
P
Remarks:
TRF No. IECEN61643_1C
Page 21 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
Requirement - Test
7.9
Additional tests
6.5.1.3
7.9.7
Insulation resistance
This test is not applicable to SPDs having a metallic
enclosure connected to protective earth.
7.9.7.1
Additional entry holes for cables – if there are any – are
left open; if there are any knock-outs, one of them is
opened. Coverings and other parts, detachable without
tools, are removed and – if necessary – undergo the
same moisture treatment
Result
Verdict
PIIIM-275 DS
N/A
P
The moisture treatment is carried out in a humidity
cabinet with a relative humidity between 91% and 95%.
The air temperature is kept at all points, where the test
sample can be positioned, within ±1 K at a suitable
value T between 20 C and 30 C. Before putting the test
samples into the humidity cabinet, they have a
temperature between T and (T + 4 ) in C.
7.9.7.2
The test samples are kept in the humidity cabinet for 2
days (48 h).
P
After a delay period between 30 min and 60 min
following the humidity treatment, the insulation
resistance is measured 60 s after having applied a d.c.
voltage of 500 V
P
TRF No. IECEN61643_1C
Page 22 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
Requirement - Test
Result
Verdict
This measurement is carried out in the humidity cabinet
or in the room into which the specimens were brought to
reach the determined temperature, after having fixed
again the parts which might have been detached
a) between all interconnected live parts and the SPDs
body accessible to accidental contact
The expression "body" in the sense of this test means
–
all touchable metal parts and a metal foil on surfaces of
insulating material, which are touchable after installation as for
normal use,
–
the surface on which the SPD is mounted, if necessary, covered
with metal foil,
–
screws and other facilities for fastening the SPD on its support.
For these measurements, the metal foil is put on in such
a way, that perhaps existing casting mass is effectively
tested.
Protective components connected to PE may be
disconnected for this test.
P
b) between the live parts of the SPD main circuit and
live parts of auxiliary circuits, if there are any.
P
The insulation resistance being not lower than
5 MΩ for the measurements according to a),
> 5 MΩ
P
2 MΩ for the measurements according to b).
> 2 MΩ
P
6.2.10/7.9.8 Dielectric withstand
SPDs classified for outdoor use are tested between the
terminals with the internal parts removed. During this
test, the SPD is subjected to sprinkling according to 9.1
of IEC 60060-1.
N/A
SPDs category indoor are tested as indicated in a) and
b) of 7.9.7.2
P
TRF No. IECEN61643_1C
Page 23 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
Requirement - Test
Result
Verdict
SPDs are tested with an a.c. voltage according to
table 16, starting with not more than half the
required a.c. voltage, this voltage is increased to the full
value within 30 s which is then held for 1 min
test voltage
a) between all interconnected live parts and the SPDs
body accessible to accidental contact
2200 V
P
2200 V
P
The expression "body" in the sense of this test means
–
all touchable metal parts and a metal foil on surfaces of
insulating material, which are touchable after installation as for
normal use,
–
the surface on which the SPD is mounted, if necessary, covered
with metal foil,
–
screws and other facilities for fastening the SPD on its support.
For these measurements, the metal foil is put on in
such a way, that perhaps existing casting mass is
effectively tested.
b) between the live parts of the SPD main circuit and
live parts of auxiliary circuits, if there are any.
Arcing or puncturing do not occur, however, partial
discharges are accepted if the voltage change during
the discharge is less than 5%
Auxiliary circuits are tested according to IEC 60947-5-1
7.9.9
P
_____
N/A
IP 20
P
Resistance to ingress of solid objects and to
harmful ingress of water
Test carried out acc. to IEC 60529 to check the IP code
6.5.1.2
7.9.3
Heat resistance
7.9.3.1
For 1 h the SPD is kept in a heating cabinet at a
temperature of (100 ± 2)°C
P
Any sealing compound used in the internal assembly
does not flow out to any significant extent
P
After cooling, it is not possible to touch any live parts
when the test sample is mounted as for normal use
even if the standard test finger is applied with a force
not exceeding 5 N
The SPD is deemed to have passed the test even if the SPD
disconnector is open.
7.9.3.2
Outer parts of SPDs, consisting of insulating material,
are submitted to a ball thrust test by means of a tester
as shown on figure 11
TRF No. IECEN61643_1C
_____
P
P
Page 24 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
Requirement - Test
P
Parts of insulating material not necessary to retain
current carrying parts and parts of the earthing circuit in
position, even though they are in contact with them,
are tested at (70 ± 2) °C
N/A
The sample to be tested is fastened accordingly, its
surface being positioned horizontally; a steel ball having
a diameter of 5 mm is pressed against the surface with
a force of 20 N.
After 1 h, the steel ball is taken away from the sample;
by dipping it into cold water, the temperature of the
sample is reduced to ambient temperature within 10 s.
P
< 2 mm
P
Verification of air clearances and creepage
distances
The electrode spacing of spark gaps is not considered
for the determination of air clearances and creepage
distances
7.9.5.1
Verdict
Parts of insulating material necessary to retain current
carrying parts and parts of the earthing circuit in position
are tested in a heating cabinet at (125 ± 2)°C
The diameter of the ball indentation is measured and
does not exceed 2 mm
6.2.8/7.9.5
Result
N/A
SPDs category outdoor
Between live parts and earth, the air clearances and
creepage distances are not smaller than the values
indicated in table 14
UC = _____ V
____ ≤ CTI ≤ ____
required. _____ mm
measured ____ mm
TRF No. IECEN61643_1C
N/A
Page 25 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
7.9.5.2
Requirement - Test
Result
Verdict
SPDs category indoor
Air clearances and creepage distances are not smaller
than the values indicated in table 15:
required / measured
Air clearances in millimetres
3/>3
P
– screws and other means to fasten a covering,
having to be detached for mounting the SPD
____ / ____
N/A
– fastening surfaces (note 2)
____ / ____
N/A
6/>6
P
____ / ____
N/A
– bodies (note 1)
3/>3
P
– screws or other means for fastening the SPD
3/>3
P
3/>3
P
____ / ____
N/A
– screws or other means for fastening the SPD (note
2)
6/>6
P
– bodies (note 1)
3/>3
P
1) Between live parts of different polarity
2) Between live parts and
– screws or other means for fastening the SPD (note
2)
– bodies (notes 1 and 2)
3) Between the metal parts of the disconnector mechanism
and
Creepage distances in millimetres
4) Between live parts of different polarity
5) Between live parts and
– screws and other means to fasten a covering,
having to be detached for mounting the SPD
NOTE 1 – Definition see 7.9.7.2.
NOTE 2 – If clearances and creepage distances between live parts of
the device and the metallic screen or the surface on which the SPD is
mounted are dependant on the design of the SPD only, they cannot
be reduced when the SPD is mounted in the most unfavourable
position (even in a metallic enclosure), the values of lines 1 and 4 are
sufficient.
TRF No. IECEN61643_1C
Page 26 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
7.9.5.2.1
7.9.5.2.2
6.2.9/7.9.6
Requirement - Test
Result
The measurements are carried out without conductors
as well as with conductors of the greatest crosssectional area indicated by the manufacturer. Nuts and
screws with out-of-round heads are assumed to be in
the most unfavourable tightening position.
P
If metal parts are covered with self-hardening resin of a
least 2 mm thickness, or if they are covered with an
insulation, withstanding a test voltage according to
7.9.8, creepage distances and air clearances are not
necessary
N/A
Casting does not come over the rim of the deepening, it
sticks strongly to the walls of the cavity and the metal
parts in it
P
By examination and trial no possibility to detach the
casting mass without a tool
P
Tracking resistance
Test done on insulating materials necessary to retain
live parts in their position
P
Testing is not applicable in case of insulating materials
made out of ceramic, or if the creepage distances are at
least equal to double the values indicated in 7.9.5
N/A
Testing according to IEC 60112, solution A with a test
voltage of 175 V
6.5.2/7.9.4
Verdict
P
Resistance to abnormal heat and fire
The glow wire test is performed in accordance with
clauses 4 to 10 of IEC 60695-2-1/1
-
-
for external parts of SPDs made of insulating
material necessary to retain in position currentcarrying parts and parts of the protective circuit, by
the test made at a temperature of (850 ± 15)°C
for all other external parts made of insulating
material, by the test made at a temperature
of 650 °C ± 10 °C
P
850°C
P
P
For the purpose of this test, bases of surface-type SPDs are
considered as external parts.
The test is not made on parts of ceramic material.
If the insulating parts are made of the same material, the test is
carried out only on one of these parts, according to the appropriate
glow-wire test temperature.
The sample is positioned during the test in the most
unfavourable position of its intended use (with the
surface tested in a vertical position).
TRF No. IECEN61643_1C
P
Page 27 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8
Clause
Requirement - Test
Result
Verdict
The tip of the glow-wire is applied to the specified
surface of the test sample taking into account the
conditions of intended use under which a heated or
glowing element may come into contact with the sample
P
The sample is regarded as having passed the glow-wire
test if
–
–
there is no visible flame and no sustained glowing,
or if
P
flames and glowing parts on the sample extinguish
themselves within 30 s after the removal of the glowwire.
P
There is no ignition of the tissue paper or scorching of
the pinewood board
6.4
P
Environmental requirements
Outdoor SPDs contained in a weather shield of glass,
glazed ceramic or other acceptable material that is
resistant to UV radiation, corrosion, erosion and tracking
_____
Remarks:
TRF No. IECEN61643_1C
N/A
Page 28 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11 - EMC TEST SEQUENCE
Clause
Requirement - Test
Result
Verdict
APPENDIX
7.10
Electromagnetic compatibility
7.10.1
Electromagnetic immunity
SPDs either incorporating no electronic circuits or
incorporating electronic circuits in which all
components are passive (for example diodes,
resistors, capacitors, inductors, varistors and other
surge protective components) are not sensitive to
normal electromagnetic disturbances and therefore
no immunity tests are required.
The requirements for SPDs containing electronic
circuits are under consideration.
7.10.2
P
N/A
Electromagnetic emission
For SPDs not incorporating electronic circuits, or
incorporating electronic circuits that do not generate
fundamental frequencies greater than 9 kHz in
normal operation, electromagnetic disturbances can
only be generated during protective operations.
The duration of these disturbances is in the order of
microseconds to milliseconds.
The frequency, level and the consequences of these
emissions are considered as part of the normal
electromagnetic environment of low-voltage
installations. Therefore, the requirements for
electromagnetic emissions are deemed to be satisfied
and no verification is necessary.
The requirements for SPDs containing electronic
circuits generating fundamental frequencies greater
than 9 kHz are under consideration.
Remarks:
TRF No. IECEN61643_1C
N/A
N/A
Page 29 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11
Clause
Requirement - Test
Result
Verdict
APPENDIX
National Differences for Europe and/or Group Differences
7.7.2.2
Thermal stability test
Test for SPDs having no switching components in
series with other components - Procedure a)
If the voltage across the SPD falls below Ucs during the
test, the current regulation is discontinued and the
voltage is adjusted back to Uc (EN 61643-11 Ucs)
and maintained for a duration of 15 min. Continuous
current monitoring is no longer required.
Source short-circuit current capability does not limit the
current before any disconnector operates. The
maximum available current value does not exceed the
short circuit withstand capability declared by the
manufacturer.
_____ V
_____ kA
cos phi = _____
N/A
Test for SPDs having switching components in
series with other components - Procedure b)
SPD energized with a power frequency source at Ucs
having a short-circuit current capability which does not
limit the current before any disconnector operates.
The maximum available current value does not exceed
the short-circuit withstand capability declared by the
manufacturer.
_____ V
_____ kA
cos phi = _____
N/A
6.2.11/7.7.3 Short circuit withstand capability
a) Test of the declared short circuit withstand capability
Power frequency source at Ucs, having a prospective
shortcircuit current according to the declared shortcircuit withstand capability and power factor according
to Table 11
b) Test at low short-circuit current
Power frequency source at Ucs, having a prospective
short-circuit current of five times the rated current of the
maximum overcurrent protection (if declared by the
manufacturer),
and a power factor according to Table 11, shall be
applied for 5 s ± 0,5 s.
If no external overcurrent protection is required by the
manufacturer, a prospective short-circuit current of 300
A is used. The test is carried out once with the shortcircuit initiated at 45 electrical degrees after the zero
crossing of the voltage.
TRF No. IECEN61643_1C
_____ V
_____ kA
cos phi = _____
P
_____ V
5 times
max. overc. Prot.
= _____ A
P
cos phi = _____
N/A
Page 30 of 47
Report No.: 5007032-1181-0008/147768-04
IEC 61643-1/EN 61643-11
Clause
7.7.6
Requirement - Test
Result
Verdict
Test under TOVs caused by faults in the low
voltage system
Only
b)
7.8.5
TOV withstand mode is acceptable
P
Overload behaviour
If a maximum overcurrent protection is specified by the
manufacturer, the SPD is loaded for 1 h with a current
equal to 1,6 times that maximum overcurrent
protection.
TRF No. IECEN61643_1C
I = ______ A
N/A
Page 31 of 47
Report No.: 5007032-1181-0008/147768-04
Remarks:
According to the manufacturers information the SPDs tested are designed for the following applications:
Test(s) according to subclause
SPD Type:
Mode:
Minimum U T for 5s:
TOV values for 200ms
designed to be connected to :
(subclause 7.7.6.1)
(subclause 7.7.4)
1,45*U O = 334 V
-
-
-
-
-
TN-systems with UO ≤ 230 V
Connected L- (PE)N
U C ≥ 1,1*U O
Connected N-PE
UC ≥ UO
Connected L-L
U C ≥ 1,1*√3*U O
TT-systems with Uo ≤ 230 V
Connected L-PE
U C ≥ 1,1*U O
√3*U O = _____ V
1200 V + U O = _____ V
Connected L-N
U C ≥ 1,1*U O
1,45*U O = 334 V
-
Connected N-PE
UC ≥ UO
-
1200 V
-
-
-
1200 + U O = _____ V
1,45 U O = _____ V
-
-
1200 V
-
-
Connected L-L
U C ≥ 1,1*√3*U O
IT-systems with Uo ≤ _____ V
Connected L-PE
U C ≥ 1,1*√3*U O
Connected L-N
U C ≥ 1,1*U O
Connected N-PE
UC ≥ UO
Connected L-L
U C ≥ 1,1*√3*U O
TN, TT and IT-systems
with Uo ≤ _____ V
Connected L-PE
U C ≥ 1,1*U O
√3*U O = _____ V
1200 + U O = _____ V
Connected L-(PE) N
U C ≥ 1,1*U O
1,45*U O = _____ V
-
Connected N-PE
UC ≥ UO
-
1200 V
-
-
__________
__________
Connected L-L
U C ≥ 1,1*√3*U O
Special applications,
no public power supply
___________________________
TRF No. IECEN61643_1C
Page 32 of 47
Report No.: 5007032-1181-0008/147768-04
Marking Reproduction:
Photographs:
Component list:
Type HAKEL
PIIIM-275
PIIIM-320
PIIIM-385
PIIIM-440
…
…
…
…
Varistor type
SIOV-D40K275QK6
SIOV-D40K320QK6E3
SIOV-D40K385QK6E3
SIOV-D40K440QK6E3
TRF No. IECEN61643_1C
Manufacturer
Quantity
EPCOS
EPCOS
EPCOS
EPCOS
1
1
1
1
RMS-voltage
[V]
275
320
385
440
Page 33 of 47
Report No.: 5007032-1181-0008/147768-04
Table 5 – Screw thread diameters and applied torques
Nominal diameter of thread
Torque
mm
I
Nm
II
III
Up to and including 2,8
0,2
0,4
0,4
Over 2,8 up to and including 3,0
0,25
0,5
0,5
Over 3,0 up to and including 3,2
0,3
0,6
0,6
Over 3,2 up to and including 3,6
0,4
0,8
0,8
Over 3,6 up to and including 4,1
0,7
1,2
1,2
Over 4,1 up to and including 4,7
0,8
1,8
1,8
Over 4,7 up to and including 5,3
0,8
2,0
2,0
Over 5,3 up to and including 6,0
1,2
2,5
3,0
Over 6,0 up to and including 8,0
2,5
3,5
6,0
Over 8,0 up to and including 10,0
–
4,0
10,0
Table 6 – Connectable cross-sections of copper conductors for
screw-type terminals or screwless terminals
Maximum continuous load current for
two-port SPDs or one-port SPDs with separate
input/output terminals1)
Range of nominal cross-sections to be clamped
(single conductor)
A
Up to and including 13
Above 13
up to and including 16
Above 16
up to and including 25
Above 25
up to and including 32
Above 32
up to and including 50
Above 50
up to and including 80
Above 80
up to and including 100
Above 100 up to and including 125
ISO – mm2
AWG – Terminal
1 to 2,5
1 to 4
1,5 to 6
2,5 to 10
4 to 16
10 to 25
16 to 35
25 to 50
18 to 14
18 to 12
16 to 10
14 to 8
12 to 6
8 to 3
6 to 2
4 to 1
1) It is required that, for current ratings up to and including 50 A, terminals be designed to clamp solid conductors as well
as rigid stranded conductors; the use of flexible conductors is permitted.
Nevertheless, it is permitted that terminals for conductors having cross-sections for 1 mm2 up to 6 mm2 be designed to
clamp solid conductors only.
Table 7 – Pulling forces (screw terminals)
Cross-section of conductor
accepted by the terminal
Up to 4
Up to 6
Up to 10
Up to 16
Up to 50
50
60
80
90
100
mm2
Pull
N
TRF No. IECEN61643_1C
Page 34 of 47
Report No.: 5007032-1181-0008/147768-04
Table 8 – Conductor dimensions
Range of nominal cross-sections
to be clamped
Stranded conductor
Number of wires
Diameter of wires
mm2
mm
1 to 2,5*
7
0,67
1 to 4*
7
0,85
1,5 to 6*
7
1,04
2,5 to 10
7
1,35
4 to 16
7
1,70
10 to 25
7
2,14
16 to 35
19
1,53
25 to 50
Under consideration
Under consideration
* If the terminal is intended to clamp solid conductors only (see note of table 6), the
test is not made.
Table 9 – Pulling force (screwless terminals)
Cross-sectional area
0,5
0,75
1,0
1,5
2,5
4
6
10
16
25
35
30
30
35
40
50
60
80
90
100
135
190
mm2
Pull force
N
Table 11 – Prospective short-circuit current and power factor (lt. 898)
Ip (kA)+5/-0%
Ip ≤ 1,5
1,5 < Ip ≤ 3,0
3,0 < Ip ≤ 4,5
4,5 < Ip ≤ 6,0
6,0 < Ip ≤ 10,0
10,0 < Ip ≤ 20,0
20,0 < Ip ≤ 50,0
50,0 < Ip
cosφ( +0/-0.05)
0,95
0,9
0,8
0,7
0,5
0,3
0,25
0,2
NOTE – Recovery voltage according to IEC 60947-1.
Table 11x – Current factor k for overload behaviour
TRF No. IECEN61643_1C
Page 35 of 47
Report No.: 5007032-1181-0008/147768-04
Table 12 – Tightening requirements for clamping screws
Nominal diameter of thread
Torque
mm
Nm
Up to and including 2,8
0,2
0,4
-
Over 2,8 up to and including 3,0
0,25
0,5
-
Over 3,0 up to and including 3,2
0,3
0,6
-
Over 3,2 up to and including 3,6
0,4
0,8
-
Over 3,6 up to and including 4,1
0,7
1,2
1,2
Over 4,1 up to and including 4,7
0,8
1,8
1,2
Over 4,7 up to and including 5,3
0,8
2,0
1,4
Table 13 – Fall distance for impact requirement
Height of fall
Parts of enclosures to be subjected to the impacts
mm
Ordinary accessory
Other accessories
100
A and B
A and B
150
C
C
200
D
D
A: parts on the front surface, including parts which are recessed.
B: parts which do not project more than 15 mm from the mounting surface (distance from the
wall) after mounting as in normal use, with the exception of the above parts A.
C: parts which project more than 15 mm and not more than 25 mm from the mounting surface
(distance from the wall) after mounting as in normal use, with the exception of the above parts A.
D: parts which project more than 25 mm from the mounting surface (distance from the wall)
after mounting as in normal use, with the exception of the above parts A.
Table 14 – Air clearances and creepage distances for SPDs category outdoor
SPD maximum continuous
operating voltage
V
Minimum air clearance in
Up to 450
3
mm
Creepage distance in mm for
insulating materials with *
CTI ≥ 600
400 ≤ CTI ≤ 600
6
7,5
450 – 600
5,5
12
15,5
600 – 1 200
8
20
25
1 200 – 1 500
10
30
40
* Other values are possible if the pollution degree is lower than 4 or a pollution test is performed.
These values are based on IEC 60664-1 for heights up to 2 000 m above sea level, pollution degree 4 and
inhomogeneous field conditions. Comparative Tracking Index (CTI) value according to IEC 60112, solution A.
TRF No. IECEN61643_1C
Page 36 of 47
Report No.: 5007032-1181-0008/147768-04
Table 15 – Air clearances and creepage distances for SPDs category indoor
SPD continuous operating voltage
Up to
100 V –
200 V –
450 V –
600 V
1 200 V –
100 V
200 V
450 V
600 V
1 200 V
1 500 V
1
2
3
5,5
8
12
– screws and other means to fasten a
covering, having to be detached for
mounting the SPD
1
2
3
5,5
8
12
– fastening surfaces (note 2)
2
4
6
11
16
24
– screws or other means for fastening
the SPD (note 2)
2
4
6
11
16
24
– bodies (notes 1 and 2)
1
2
3
5,5
8
12
– bodies (note 1)
1
2
3
5,5
8
12
– screws or other means for fastening
the SPD
1
2
3
5,5
8
12
1
2
3
5,5
8
12
1
2
3
5,5
8
12
– screws or other means for fastening
the SPD (note 2)
2
4
6
11
16
24
– bodies (note 1)
1
2
3
5,5
8
12
Air clearances in millimetres
1) Between live parts of different polarity
2) Between live parts and
3) Between the metal parts of the disconnector
mechanism and
Creepage distances in millimetres
4) Between live parts of different polarity
5) Between live parts and
– screws and other means to fasten a
covering, having to be detached for
mounting the SPD
NOTE 1 – Definition see 7.9.7.2.
NOTE 2 – If clearances and creepage distances between live parts of the device and the metallic screen or the surface on
which the SPD is mounted are dependant on the design of the SPD only, they cannot be reduced when the SPD is mounted
in the most unfavourable position (even in a metallic enclosure), the values of lines 1 and 4 are sufficient.
Table 16 – Dielectric withstand
SPD continuous operating voltage
V
TRF No. IECEN61643_1C
AC test voltage
kV
Up to Uc = 100
1,1
Up to Uc = 200
1,7
Up to Uc = 450
2,2
Up to Uc = 600
3,3
Up to Uc = 1 200
4,2
Up to Uc = 1 500
5,8
Page 37 of 47
Report No.: 5007032-1181-0008/147768-04
Table B.1 – TOV test values
Fig. B.1 – Test setting for operating duty test
TRF No. IECEN61643_1C
Page 38 of 47
Annex 1
Current – voltage oscillograms: 8/20 (positive polarity)
Sample 2.1 (oscillogram 2112082)
TRF No. IECEN61643_1C
Report No.: 5007032-1181-0008/147768-04
Page 39 of 47
Sample 2.2 (oscillogram 2112084)
TRF No. IECEN61643_1C
Report No.: 5007032-1181-0008/147768-04
Page 40 of 47
Sample 2.3 (oscillogram 2112085)
TRF No. IECEN61643_1C
Report No.: 5007032-1181-0008/147768-04
Page 41 of 47
Report No.: 5007032-1181-0008/147768-04
Annex 2
Table of residual voltage at 1,0 times In (SPD contains only voltage limiting components)
Sample
2.1
2.2
2.3
Oscillogram No.:
20 kA (pos. polarity) Ures [V]
1155
1135
1130
2112082/_084/_085
20 kA (neg. polarity) Ures [V]
1136
1140
1145
2112083/_117/_086
Annex 3
Sparcover voltage with 1,2/50 voltage impulse: Not Applicable
TRF No. IECEN61643_1C
Page 42 of 47
Report No.: 5007032-1181-0008/147768-04
Annex 4
Current records of preconditioning test
Sample 3.7 (oscillogram 2113666)
Picture at synchronisation with 60°, last shot of preconditioning test
TRF No. IECEN61643_1C
Page 43 of 47
Report No.: 5007032-1181-0008/147768-04
Sample 3.8 (oscillogram 2113671)
Picture at synchronisation with 60°, last shot of preconditioning test
TRF No. IECEN61643_1C
Page 44 of 47
Report No.: 5007032-1181-0008/147768-04
Sample 3.9 (oscillogram 2113676)
Picture at synchronisation with 60°, last shot of preconditioning test
TRF No. IECEN61643_1C
Page 45 of 47
Report No.: 5007032-1181-0008/147768-04
Annex 5
Voltage and current records of operating duty test:
All pictures with 100% of Imax = 50kA, last shot of operating duty test
Sample 3.7 (oscillogram 2113842)
TRF No. IECEN61643_1C
Page 46 of 47
Sample 3.8 (oscillogram 2113843)
TRF No. IECEN61643_1C
Report No.: 5007032-1181-0008/147768-04
Page 47 of 47
Sample 3.9 (oscillogram 2113860)
TRF No. IECEN61643_1C
Report No.: 5007032-1181-0008/147768-04