Test Report issued under the responsibility of: TEST REPORT IEC 61643-1 / EN 61643-11 Surge-protective devices connected to low-voltage power systems Requirements and tests Report Reference No. .................... : 5007032-1181-0008/147768-04 Date of issue..................................... : 16.01.2012 Total number of pages ...................... 47 CB/CCA Testing Laboratory .......... : Address ............................................ : VDE Prüf- und Zertifizierungsinstitut GmbH VDE Testing and Certification Institute Merianstraße 28, 63069 Offenbach, Germany Applicant’s name ............................ : HAKEL spol. s.r.o. Address ............................................ : Bratri Stefanu 980, 500 03 HRADEC KRALOVE Test specification: Standard ........................................... : IEC 61643-1:2005 (Second Edition) and/or EN 61643-11:2002 + A11:2007 Test procedure ................................. : CB/ CCA Non-standard test method…………..: N/A Test Report Form No. .................... : IECEN61643_1C Test Report Form(s) Originator ........ : OVE Master TRF ...................................... : Dated 2007-07 Copyright © 2007 IEC System for Conformity Testing and Certification of Electrical Equipment (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02. If this Test Report Form is used by non-CCA members, the CIG logo and the reference to the CCA Procedure shall be removed. This report is not valid as a CCA Test Report unless signed by an approved CCA Testing Laboratory and appended to a CCA Test Certificate issued by an NCB in accordance with CCA Test item description ..................... : Surge protective device Trade Mark ....................................... : Manufacturer .................................... : HAKEL spol. s.r.o. Model/Type reference....................... : PIIIM-275; PIIIM-275 DS Ratings ............................................. : Uc = 275 V, Imax = 50 kA, In = 20 kA, Up ≤ 1,3 kV Page 3 of 47 Report No.: 5007032-1181-0008/147768-04 Summary of testing: Tests performed (name of test and test clause): Testing location: Test series 1 clause 7.2 P VDE Test series 8 clause 7.9.5.2 / 7.9.6 P VDE Test series 1, 2, 3, 5, 7, 8 P IPH Annex 1 Residual voltage, current-voltage oscillograms IPH Annex 2 Residual voltage, discharge current – residual voltage diagrams IPH Annex 4 Operating duty test, Preconditioning oscillograms IPH Annex 5 Operating duty test, current-voltage oscillograms IPH Summary of compliance with National Differences: Copy of marking plate: TRF No. IECEN61643_1C Page 4 of 47 Report No.: 5007032-1181-0008/147768-04 Test item particulars .................................................. : Number of ports: One port / Two port SPD design topology: Voltage switching / Voltage limiting / Combination SPD type (and test class): Type 1 (I) / Type 2 (II) / Type 3 (III) Location: Indoor / Outdoor Accessibility: Accessible / Inaccessible Mounting method: Fixed / Portable SPD Disconnector: Internal / External / Both Protection functions: Thermal / Leakage current / Overcurrent Overcurrent protection: Specified / Not specified Degree of protection (IP code): IP20 Temperature range: Normal / Extended Required SPD-disconnectors: Fuse-Link 500 V a.c. / 160 A gG (IEC 60269-2) Possible test case verdicts: - test case does not apply to the test object.................. : N/A - test object does meet the requirement ....................... : P (Pass) - test object does not meet the requirement ................. : F (Fail) Testing .......................................................................... : Date of receipt of test item ............................................ : 2011-04-05 - 2011-08-04 Date (s) of performance of tests ................................... : 2011-04-15 - 2011-08-05 General remarks: The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(See Enclosure #)" refers to additional information appended to the report. "(See appended table)" refers to a table appended to the report. Note: This TRF includes EN Group Differences together with National Differences and Special National Conditions, if any. All Differences are located in the Appendix to the main body of this TRF. Throughout this report a comma (point) is used as the decimal separator. This test report has to be read in conjunction with 5007032-1181-0008/147768-01. General product information: The suffix “DS” in the marking means that the SPD is provided with remote control contact. TRF No. IECEN61643_1C Page 5 of 47 Report No.: 5007032-1181-0008/147768-04 If not otherwise specified all tests have been carried out on three samples per test sequence. Terminal tests have been carried out on three terminals of each construction used. Impulse tests have been carried out according to chapters 7.1.1 to 7.1.4. SPD Type 1 (Test class I): I (kA) Calculation of charge Q and specific energy W/R after operating duty test acc. to 7.6.5 - test sequence 3 (measured values) Q (As) within 10 ms W/R (kJ/Ω) 0,1* Ipeak = _____ 0,25* Ipeak = _____ 0,5* Ipeak = _____ 0,75* Ipeak = _____ 1,0* Ipeak = _____ If a product covered by another international standard than IEC 61643 incorporates SPD technology the requirements of the other international standard shall apply to those parts of the product not influenced by the presence of the SPD technology. Unless otherwise specified, a.c. values given in this report are r.m.s. values. If not otherwise specified the tests have been performed in free air and at an ambient temperature of (20 ± 15)°C. If not otherwise specified, for all tests where a power supply at UC is required, the voltage +0 tolerance for testing was /-5%. If the SPD is supplied with integral cables, the full length of these cables forms part of the SPD under test, except for the determination of the measured limiting voltage 7.5, where a lead length of 150 mm is used. SPD disconnectors have been selected and connected as required by the manufacturer, where applicable. SPD disconnectors have been tested with the SPD during the sequence of type tests of 7.7 and 7.8.3, except for RCDs, which are not tested during the operating duty test according to 7.7.1. For SPDs having more than one mode of protection, for which the manufacturer declares a voltage protection level, the tests have been performed on each mode, with the values chosen according to the manufacturer's declaration, using new samples each time. For three phase devices in which the protective component circuitry per given mode is identical, the testing may be performed on each of the three phases which fulfils the three sample requirement. If the manufacturer sets different requirements for the external SPD disconnector(s) depending upon the prospective short-circuit current of the supply system, all relevant test sequences have been performed for every combination of required SPD disconnector(s) and corresponding prospective short-circuit currents. Remarks: Test program: see page 6. TRF No. IECEN61643_1C Page 6 of 47 Report No.: 5007032-1181-0008/147768-04 Test program: PIIIM-385 / PIIIM-385 DS 5007032-1181-0008/147768-02 PIIIM-440 / PIIIM-440 DS 5007032-1181-0008/147768-01 Samples Samples Samples PIIIM-275 / PIIIM-275 DS 5007032-1181-0008/147768-04 PIIIM-320 / PIIIM-320 DS 5007032-1181-0008/147768-03 Test program and test samples Seq. Test discription Clause Identification and marking 6.1.1/ 6.1.2/ 7.2 Terminals and connections Testing for protection against direct contact Standby-Power consumption and residual current Samples 1.7 1.8 1.9 6.2.1/ 6.3/ 7.3 - - - - - - - - - 1.16 1.17 1.18 6.5.1/ 7.4 - - - - - - - - - 1.16 1.17 1.18 6.5.3/ 6.5.4/ 7.7.5 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 Protection level 6.2.2/ 7.5 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 Residual voltage 7.5.2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 Front of wave sparkover voltage 7.5.3 - - - - - - - - - - - - Limiting voltage with combination wave 7.5.4/ 7.5.5 - - - - - - - - - - - - Determination of the magnitude of the follow current 7.6.2 - - - - - - - - - - - - Operating duty test 6.2.6/ 7.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 Preconditioning 7.6.4/ 7.7.1 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 Class I and II operating duty test 6.2.3/ 6.2.4/ 7.6.5/7.6.6/ 7.7.1 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 Class III operating duty test 6.2.5/ 7.6.7/ 7.7.1 - - - - - - - - - - - - 4 Class I and II total discharge current 6.5.6/ 7.9.10 - - - - - - - - - - - - 5 Test of thermal stability 6.2.7/ 7.7.2 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6 Short-circuit withstand capability test 6.2.7/ 6.2.11/ 7.7.3 - - - - - - - - - TOV test 6.2.7/ 6.5.5/ 7.7.6 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 TOV test 6.2.7/ 6.5.5/ 7.7.4 - - - - - - - - - - - - Flexible cables and cords and their connection 7.9.1 - - - - - - - - - 6.3/ 6.5.1.1/ 7.9.2.1 - - Mechanical strength - Mechanical strength 6.3/ 6.5.1.1/ 7.9.2.2 - - - - - - - - - Insulation resistance 6.5.1.3/ 7.9.7 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 Dielectric withstand 6.2.10/ 7.9.8 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 Environment, IP code 6.4/ 6.5.1/ 7.9.9 - - - - - - - - - 8.10 8.11 8.12 8.10 8.11 8.12 1 2 3 7 8 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 5.10 5.11 5.12 6.1 6.2 6.3 6.4 6.5 6.6 7.10 7.11 7.12 8.10 8.11 8.12 - - - 8.10 8.11 8.12 Heat resitance 6.5.1.2/ 7.9.3 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 Air clearences and creepage distances outdoor 6.2.8/ 7.9.5.1 - - - - - - - - - Air clearences and creepage distances indoor 6.2.8/ 7.9.5.2 8.1 8.2 8.3 - - - - - - 8.10 8.11 8.12 Resistance to abnormal heat and fire 6.5.2/ 7.9.4 - - - - - - - - - 8.10 8.11 8.12 Tracking resistance 6.29/ 7.9.6 8.1 8.2 8.3 - - - - - - 8.10 8.11 8.12 - - - Additional test fort two-port SPDs and on one-port SPDs with seperate input/ output terminals 9 Percentage voltage regulation 6.6.1/ 7.8.1 - - - - - - - - - - - - Rated load current 6.6.2/ 7.8.2 - - - - - - - - - - - - Load side surge withstand 6.6.3/ 7.8.4 - - - - - - - - - - - - Overload behavior 6.6.4/ 7.8.5 - - - - - - - - - - - - Load side short-circuit withstand capability test 6.2.7/ 7.8.3 - - - - - - - - - - - - Status indicator operation 6.2.12 - - - - - - - - - P P P Isolation between seperate circuits 6.2.13 - - - - - - - - - P P P Additional checks and tests 10 TRF No. IECEN61643_1C Page 7 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 1 Clause 6.1.1/6.1.2 Requirement - Test Result Verdict HAKEL/ PIIIM-275 PIIIM-275 DS P 275 V P Identification and Marking Markings on the body or permanently attached to a) Manufacturer/Trade mark/Model number e) Maximum continuous operating voltage UC (for each mode) and rated frequency 50 / 60 Hz f) SPD test classification/type and discharge parameters for each mode of protection No. of modes 1 P Class I test / Type 1 IImp _____ kA N/A Class II test / Type 2 Imax 50 kA P _____ kV N/A 20 kA P h) Voltage protection level Up < 1,3 kV P j) Degree of protection if > IP20 IP _____ N/A l) Maximum overcurrent protection 160 A P _____ N/A a.c./d.c./both P indoor/outdoor P 1 P fixed/portable P _____ A N/A 60 kA P Indicating devices of external and internal disconnectors P _____ N/A Class III test / Type 3 UOC g) Nominal discharge current In for test class I / Type 1 and test class II / Type 2 SPDs (for each mode) o) Identification of terminals, if necessary q) Type of current Information provided by the manufacturer b) Location category c) Number of ports d) Method of mounting i) Rated load current IL, if required k) Short circuit withstand m) Indication of disconnector operation, if any n) position of normal use, if significant TRF No. IECEN61643_1C Page 8 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 1 Clause Requirement - Test Result Verdict p) Installation instructions (type of LV systems: TN, TT, IT etc , connections to LV systems and rated system voltages for which the SPD is designed, mechanical dimensions, lead lengths, etc..) TN TT ( L-N only) P _____ kJ/Ω N/A normal/extended P t) Follow current interrupting rating (except in case of voltage limiting SPDs) _____ A N/A u) External SPD disconnector requirements fuse link 160 A gG P r) Specific energy W/R for Type 1 SPDs (class I test) s) Temperature range v) Residual current (optional) w) Temporary overvoltage characteristic at UT x) Total discharge current ITotal for multipole SPDs (if declared by the manufacturer) N/A 334 V P ______ N/A Markings indelible and legible, not placed on screws and removable washers 7.2.2 6.5.3/6.5.4/ 7.7.5 P Test applied to markings not made by impressing, molding or engraving: 15s rubbing by hand with cotton soaked with - water - aliphatic solvent hexane P After test marking easily legible P Standby Power Consumption and Residual Current Test The SPD is connected to a voltage source at its maximum continuous operating voltage (UC) according the manufacturers instruction. The Apparent Power (Volt-Amperes) consumed by the SPD is measured. The current at the PE terminal is called the residual current.. Notes 1: If the manufacturer allows more than one configuration for the SPD installation, this test should be performed for every configuration. 2: The true r.m.s. current value is measured. Remarks: TRF No. IECEN61643_1C UC = 275 V PC = 0,90 VA IPE = 3,28 mA P Page 9 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 2 Clause 6.2.2 7.5. Requirement - Test Voltage protection level Up Measured limiting voltage Result PIIIM-275 DS Measured limiting voltage does not exceed the protection level specified by the manufacturer P SPDs tested acc. to class I and II perform 7.5.2 P SPDs tested acc. to class I and II containing switching components perform 7.5.3 in addition N/A SPDs tested acc. to class III perform 7.5.4 or 7.5.5 N/A One port SPDs are tested unenergized Two port SPDs are tested energized at UC with a source having a nominal current ≥ 5 A P _____ V _____ A For a one-port SPD having terminals, the test is performed without external disconnectors and the measured limiting voltage is measured at the terminals. For a one-port SPD having connecting leads, the measured limiting voltage is measured with an external lead length of 150 mm. Measured limiting voltage = highest value measured N/A P For a two-port SPD, and a one-port SPD having separate load terminals, the measured limiting voltage is measured at the load port or load terminals of the SPD. 7.5.2 Verdict N/A 1,155 kV P Residual voltage with 8/20 current impulse Test with current impulses of 0,1 times In _____kA / _____V 0,2 times In _____kA / _____V 0,5 times In _____kA / _____V 1,0 times In 20 kA / 1,155 kV With one sequence of positive and one sequence of negative polarity P P Finally one impulse at Imax or Ipeak if Imax or Ipeak > In with polarity that showed higher residual voltages during previous tests TRF No. IECEN61643_1C 50 kA / 1,750 kV P Page 10 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 2 Clause Requirement - Test Result Time interval between impulses long enough for sample to cool down to ambient Verdict P Current -voltage oscillograms see Annex 1 P Discharge current - residual voltage diagram showing peak values see Annex 2 P - Ipeak or In whichever is greater for class I test _____ kV N/A - In for class II test 1,155 kV P Value for determination of the measured limiting voltage = highest voltage on the curve corresponding to: 7.5.3 Front-of-wave sparkover voltage The 1,2/50 voltage impulse is used. The generator voltage is set to an open circuit output voltage of 6 kV N/A 10 impulses applied to the SPD, five of positive and five of negative polarity N/A Time interval between impulses long enough for sample to cool down to ambient N/A If sparkover is not observed during any of the 10 impulses on the front of the wave, then the above procedure is repeated, but with a generator open circuit output voltage of 10 kV. Voltage oscillograms Value for determination of the Measured limiting voltage is the maximum value of the sparkover voltages recorded during the whole test sequence 7.5.4 N/A see Annex 3 N/A _____ kV N/A _____ V N/A Measured limiting voltage with combination wave Sample energised at UC For a.c. rated SPDs positive impulses are applied at 90°±10°el point and negative impulses at 270°±10°el point of the sinusoidal voltage wave N/A Time interval between impulses long enough for sample to cool down to ambient N/A TRF No. IECEN61643_1C Page 11 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 2 Clause Requirement - Test Result Verdict Test with voltage settings of: 0,1 times UOC _____ kV ____ V / ____ kA 0,2 times UOC _____ kV ____ V / ____ kA 0,5 times UOC _____ kV ____ V / ____ kA 1,0 times UOC _____ kV ____ V / ____ kA With four surges, two of positive and two of negative polarity, applied at each setting Current -voltage oscillograms Value for determination of the Measured limiting voltage = maximum peak voltage recorded Remarks: TRF No. IECEN61643_1C N/A N/A see Annex 1 N/A _____ V N/A Page 12 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3 Clause 6.2.6/7.6 Requirement - Test Operating duty test Result Verdict PIIIM-275 DS Determination of the measured limiting voltage: SPDs tested acc. to class I and II: Residual voltage acc. to 7.5.2 at In only with one positive and one negative impulse applied 20 kA / 1,120 kV P _____ kV N/A SPDs tested acc. to class I and II containing switching components: Sparkover voltage acc. to 7.5.3 All measured peak values (5 pos./ 5 neg.) below UP SPDs tested acc. to class III: _____ kV Measured limiting voltage acc. to 7.5.4 or 7.5.5 at UOC only with four surges (2 pos./ 2 neg.) 7.6.3 ____ V / ____kA N/A 275 V P Power frequency source for preconditioning: Sample connected to power frequency source at UC SPDs with follow current < 500 A: Voltage at the SPD terminals does not fall below the peak value of UC by more than 10% during flow of follow current P SPDs with follow current > 500 A: Power frequency voltage Uc with a prospective short circuit current equal to the follow current interrupt rating Ifi declared by the manufacturer in accordance with Table 11, or 500 A, whichever is greater. For SPDs connected between neutral and protective earth only, the prospective short-circuit current shall be at least 100 A. Recovery voltage acc. to IEC 60947-1 7.6.4 _____ kA cos phi = _____ N/A γ = _____ N/A fγ = _____ Hz Class I and II preconditioning test 15 current impulses 8/20 of positive polarity in 3 groups of 5 impulses, peak value equal to In or Ipeak, whichever is greater, each impulse synchronized to the power frequency, starting from 0°el the sync. angle is increased in steps of 30°±5°, time interval between the impulses 50s - 60s time interval between the groups 25min - 30min TRF No. IECEN61643_1C 20 kA sync. 0°, 30°, 60°, 90°, 120°, 150°, 180°, 210°, 240°, 270°, 300°, 330°, 0°, 30°, 60°el P Page 13 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3 Clause Requirement - Test Current records show no sign of puncture or flashover of the sample 7.6.7 Result Verdict see Annex 4 P Class III preconditioning test Power frequency source according to 7.6.3, Combination wave generator adjusted to UOC 15 impulses of positive polarity in 3 groups of 5 impulses, peak value equal to UOC, each impulse synchronized to the power frequency voltage at the corresponding positive peak value time interval between the impulses 50s - 60s time interval between the groups 25min - 30min Current records show no sign of puncture or flashover of the sample 7.6.5 _____ kV sync. 90°el N/A see Annex 4 P Class I and II operating duty test SPD energized at UC by a voltage source having a nominal current capability of ≥ 5 A 275 V 30 A Power frequency voltage remains applied for 30min after each impulse to prove thermal stability P P Test with current impulses of positive polarity initiated in the corresponding positive peak value of the power frequency voltage, one impulse for each value: 0,1 times Ipeak for class I test or Imax for class II test 5,0 kA 0,25 times Ipeak for class I test or Imax for class II test 12,5 kA 0,5 times Ipeak for class I test or Imax for class II test 25,0 kA 0,75 times Ipeak for class I test or Imax for class II test 37,5 kA 1,0 times Ipeak for class I test or Imax for class II test 50,0 kA After each impulse cool down to ambient temperature 7.6.7 P P Class III operating duty test SPD energized at UC by a voltage source having a nominal current capability of ≥ 5 A _____ V _____ A Power frequency voltage remains applied for 30min after each impulse to prove thermal stability TRF No. IECEN61643_1C N/A N/A Page 14 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3 Clause Requirement - Test Result Verdict Test with impulses of positive polarity initiated in the corresponding positive peak value of the power frequency voltage: 0,1 times UOC _____ kV 0,25 times UOC _____ kV 0,5 times UOC _____ kV 0,75 times UOC _____ kV 1,0 times UOC N/A _____ kV After each impulse cool down to ambient temperature 7.6.6 N/A Pass criteria After each impulse thermal stability P Any follow current is self extinguished P Voltage and current records and visual inspection show no indication of puncture or flashover and no mechanical damage of the sample see Annex 5 P No mechanical damage P One more impulse at In or UOC shall be applied to the SPD whilst the SPD is energized at Uc by means of a voltage source having a nominal current capability of at least 5 A. After this impulse, UC remains applied and thermal stability shall be achieved within 30 min. P Once thermal stability is achieved, either: • the current which flows through the test sample is measured. Its resistive component (measured at the crest of the sine wave) shall not exceed a value of 1 mA. P or • the stand-by power consumption shall not be greater than 20% above the value measured in 7.7.5 Following this complete test sequence and after the sample has cooled down to near ambient temperature, the measured limiting voltage test, which was made at the beginning of the test sequence, shall be repeated. TRF No. IECEN61643_1C N/A P Page 15 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 3 Clause Requirement - Test Result Verdict 20 kA / 1,230 kV P _____ kV N/A SPDs tested acc. to class I and II: Residual voltage acc. to 7.5.2 at In only with one positive and one negative impulse applied SPDs tested acc. to class I and II containing switching components: Sparkover voltage acc. to 7.5.3 All 10 measured peak values (5 pos./ 5 neg.) below UP SPDs tested acc. to class III: _____ kV Measured limiting voltage acc. to 7.5.4 or 7.5.5 at UOC only with four surges (2 pos./ 2 neg.) 7.7.1 ____ V / ____kA N/A No SPD disconnector has operated during the test and they are in working order after the test. P Values of measured limiting voltage test measured before and after the test are below or equal to Up P Remarks: TRF No. IECEN61643_1C Page 16 of 47 Report No.: 5007032-1181-0008/147768-04 For TEST SEQUENCES 5, 6 and 7 Clause 6.2.7/7.7 Requirement - Test Result Verdict SPD disconnectors and safety performance of overstressed SPDs SPD disconnector operation is indicated P SPD disconnectors tested with the SPD during the type tests of 7.7 and 7.8.3, except for RCDs which are not tested during operating duty test according to 7.7.1. P IEC 61643-1/EN 61643-11 - TEST SEQUENCE 5 Clause Requirement - Test 7.7.2 Test of thermal stability of SPDs 7.7.2.1 Temperature withstand test 7.7.2.2 Result Verdict PIIIM-275 DS SPD kept in a heating cabinet at an ambient temperature of (80 ± 5)°C for 24 h P No SPD disconnector has operated P Thermal stability test This test is not performed on SPDs containing only voltage switching components. Any voltage switching component, which is connected in series with a voltage limiting component, is shortcircuited by a copper wire with a diameter such that it does not melt during the test. N/A N/A For SPDs with different non-linear components connected in parallel, this test is performed for every current path of the SPD by disconnecting/interrupting all the remaining current paths. If components of the same type and parameters are connected in parallel, they shall be tested as one current path. TRF No. IECEN61643_1C N/A Page 17 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 5 Clause Requirement - Test Result P Test for SPDs having no switching components in series with other components - Procedure a) Sample connected to a power frequency source with a voltage high enough to drive a constant current, which is increased by the following steps - 2 mA or 5 % of the previously adjusted test current, whichever is greater with a tolerance of ± 10% : Verdict duration 2 mA r.m.s. or corresponding crest value 0,33 h 4 mA r.m.s. or corresponding crest value 0,33 h 6 mA r.m.s. or corresponding crest value 0,50 h 8 mA r.m.s. or corresponding crest value 0,83 h 10 mA r.m.s. or corresponding crest value 0,50 h 12 mA r.m.s. or corresponding crest value 0,67 h 14 mA r.m.s. or corresponding crest value 0,67 h 16 mA r.m.s. or corresponding crest value 0,27 h ______ mA r.m.s. or corresponding crest value _____ h ______ mA r.m.s. or corresponding crest value _____ h P Each step is maintained until thermal equilibrium is reached - temperature variation < 2 K within 10 min P Surface temperature of the hottest spot and current through the SPD are monitored continuously P Test interrupted if all non-linear components under test are disconnected. The voltage is not increased further in order to avoid any malfunction of the disconnector(s). If the voltage across the SPD falls below Uc during the test, the current regulation is discontinued and the voltage is adjusted back to Uc (EN 61643-11 Ucs) and maintained for a duration of 15 min. Continuous current monitoring is no longer required. Source short-circuit current capability does not limit the current before any disconnector operates. The maximum available current value does not exceed the short circuit withstand capability declared by the manufacturer. TRF No. IECEN61643_1C P _____ V _____ kA cos phi = _____ N/A Page 18 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 5 Clause Requirement - Test Result N/A Test for SPDs having switching components in series with other components - Procedure b) SPD energized with a power frequency source at UC having a short-circuit current capability which does not limit the current before any disconnector operates. The maximum available current value does not exceed the short-circuit withstand capability declared by the manufacturer. Verdict _____ V _____ kA cos phi = _____ If no significant current flows - further testing acc to Procedure a) N/A N/A Pass criteria Indoor SPDs: max 46,2 K Surface temperature always less than 120°K during test and less than 80°K, 5min after disconnector operation ≤ 29,2 K after 5min P Outdoor SPDs: No evidence of burning and no expulsion of solid material N/A Accessible SPDs: SPDs having an IP degree ≥ IP 2X - No live parts accessible with standardised test finger applied with a force of 5 N, except the ones which are accessible when the SPD is fitted as in normal use For disconnectors having operated there is clear evidence of effective and permanent disconnection checked with power frequency voltage equal to UC applied for 1min - current flow ≤ 0,5 mA r.m.s TRF No. IECEN61643_1C P 275 V < 0,5 mA P Page 19 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 7 Clause 7.7.6 Requirement - Test Test under TOVs caused by faults in the low voltage system If U C is greater or equal to U T there is no requirement for testing. 7.7.6.1 Result PIIIM-275 DS _______ N/A Test procedure: New set of samples used and fitted as in normal use according to the manufacturer's instructions. The surge protective device is placed in a cuboid wooden box whose sides are 500 mm ± 50 mm away from the SPD external surfaces. The internal surface of the box is covered with muslin paper or cheese cloth. One of the box sides (not the bottom) remains open in order that the supply cables can be connected according to the manufacturer's instructions. The test sample is connected for a duration of +5 tT = 5 s /-0% to a power frequency voltage of +0 UT /-5% as given in Table B.1, or greater TOV-voltages which the manufacturer has declared in accordance with item w) of 6.6.1. This voltage source shall be capable of delivering a current either high enough to ensure that the voltage at the SPD terminals does not fall below U T - 5% during the test or at the declared short circuit withstand of the SPD, whichever is lower. Immediately following the application of U T a voltage equal to U CS +0,-5 % with the same current capability, is applied to the test sample for a period of 30 min. The time interval between the test periods shall be as short as possible and in any case not exceed 100ms. 7.7.6.2 Verdict P front side P 334 V 4000 A P 253 V 4000 A 0 ms P Pass criteria: The muslin paper or cheese cloth did not catch fire during the test. SPDs having an IP degree equal or greater than IP20 do not have live parts accessible with the standardized test finger applied with a force of 5 N (see IEC 60529), except for those live parts which were already accessible before the test when the SPD is fitted as in normal use. TRF No. IECEN61643_1C P P Page 20 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 7 Clause Requirement - Test a) Verdict _____ mA N/A TOV failure mode : If a disconnector has operated, there shall be clear evidence of effective and permanent disconnection by the device. To check this, a power frequency voltage equal to U C is applied for 1 min without current flow in excess of 0,5 mA r.m.s. b) Result TOV withstand mode : The SPD has maintained thermal stability during the application of UCS (following the application of UT). The SPD is considered to be thermally stable if the current flowing through it or its power dissipation does not continue to increase during the total time of application of UCS. The test sample is then connected to UC. The test transformer shall have a short circuit current capability of at least 200 mA. The current, which flows through the test sample, is measured. Its resistive component (measured at the crest of the sine wave) shall not exceed a value of 1 mA or P P the stand-by power consumption shall not increase by more than 20 % of the value measured in 7.7.5. _____ SPDs tested acc. to class I and II: Residual voltage acc. to 7.5.2 at In only with one positive and one negative impulse applied 20 kA / 1,23 kV P _____ kV N/A SPDs tested acc. to class I and II containing switching components: Sparkover voltage acc. to 7.5.3 Average of 10 measured peak values (5 pos./ 5 neg.) SPDs tested acc. to class III: _____ kV Measured limiting voltage acc. to 7.5.4 or 7.5.5 at UOC only with four surges (2 pos./ 2 neg.) ____ V / ____kA N/A Auxiliary circuits, like status indicators, are in working order. P Visual inspection of the test sample shall reveal no evidence of any damage. P Remarks: TRF No. IECEN61643_1C Page 21 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause Requirement - Test 7.9 Additional tests 6.5.1.3 7.9.7 Insulation resistance This test is not applicable to SPDs having a metallic enclosure connected to protective earth. 7.9.7.1 Additional entry holes for cables – if there are any – are left open; if there are any knock-outs, one of them is opened. Coverings and other parts, detachable without tools, are removed and – if necessary – undergo the same moisture treatment Result Verdict PIIIM-275 DS N/A P The moisture treatment is carried out in a humidity cabinet with a relative humidity between 91% and 95%. The air temperature is kept at all points, where the test sample can be positioned, within ±1 K at a suitable value T between 20 C and 30 C. Before putting the test samples into the humidity cabinet, they have a temperature between T and (T + 4 ) in C. 7.9.7.2 The test samples are kept in the humidity cabinet for 2 days (48 h). P After a delay period between 30 min and 60 min following the humidity treatment, the insulation resistance is measured 60 s after having applied a d.c. voltage of 500 V P TRF No. IECEN61643_1C Page 22 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause Requirement - Test Result Verdict This measurement is carried out in the humidity cabinet or in the room into which the specimens were brought to reach the determined temperature, after having fixed again the parts which might have been detached a) between all interconnected live parts and the SPDs body accessible to accidental contact The expression "body" in the sense of this test means – all touchable metal parts and a metal foil on surfaces of insulating material, which are touchable after installation as for normal use, – the surface on which the SPD is mounted, if necessary, covered with metal foil, – screws and other facilities for fastening the SPD on its support. For these measurements, the metal foil is put on in such a way, that perhaps existing casting mass is effectively tested. Protective components connected to PE may be disconnected for this test. P b) between the live parts of the SPD main circuit and live parts of auxiliary circuits, if there are any. P The insulation resistance being not lower than 5 MΩ for the measurements according to a), > 5 MΩ P 2 MΩ for the measurements according to b). > 2 MΩ P 6.2.10/7.9.8 Dielectric withstand SPDs classified for outdoor use are tested between the terminals with the internal parts removed. During this test, the SPD is subjected to sprinkling according to 9.1 of IEC 60060-1. N/A SPDs category indoor are tested as indicated in a) and b) of 7.9.7.2 P TRF No. IECEN61643_1C Page 23 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause Requirement - Test Result Verdict SPDs are tested with an a.c. voltage according to table 16, starting with not more than half the required a.c. voltage, this voltage is increased to the full value within 30 s which is then held for 1 min test voltage a) between all interconnected live parts and the SPDs body accessible to accidental contact 2200 V P 2200 V P The expression "body" in the sense of this test means – all touchable metal parts and a metal foil on surfaces of insulating material, which are touchable after installation as for normal use, – the surface on which the SPD is mounted, if necessary, covered with metal foil, – screws and other facilities for fastening the SPD on its support. For these measurements, the metal foil is put on in such a way, that perhaps existing casting mass is effectively tested. b) between the live parts of the SPD main circuit and live parts of auxiliary circuits, if there are any. Arcing or puncturing do not occur, however, partial discharges are accepted if the voltage change during the discharge is less than 5% Auxiliary circuits are tested according to IEC 60947-5-1 7.9.9 P _____ N/A IP 20 P Resistance to ingress of solid objects and to harmful ingress of water Test carried out acc. to IEC 60529 to check the IP code 6.5.1.2 7.9.3 Heat resistance 7.9.3.1 For 1 h the SPD is kept in a heating cabinet at a temperature of (100 ± 2)°C P Any sealing compound used in the internal assembly does not flow out to any significant extent P After cooling, it is not possible to touch any live parts when the test sample is mounted as for normal use even if the standard test finger is applied with a force not exceeding 5 N The SPD is deemed to have passed the test even if the SPD disconnector is open. 7.9.3.2 Outer parts of SPDs, consisting of insulating material, are submitted to a ball thrust test by means of a tester as shown on figure 11 TRF No. IECEN61643_1C _____ P P Page 24 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause Requirement - Test P Parts of insulating material not necessary to retain current carrying parts and parts of the earthing circuit in position, even though they are in contact with them, are tested at (70 ± 2) °C N/A The sample to be tested is fastened accordingly, its surface being positioned horizontally; a steel ball having a diameter of 5 mm is pressed against the surface with a force of 20 N. After 1 h, the steel ball is taken away from the sample; by dipping it into cold water, the temperature of the sample is reduced to ambient temperature within 10 s. P < 2 mm P Verification of air clearances and creepage distances The electrode spacing of spark gaps is not considered for the determination of air clearances and creepage distances 7.9.5.1 Verdict Parts of insulating material necessary to retain current carrying parts and parts of the earthing circuit in position are tested in a heating cabinet at (125 ± 2)°C The diameter of the ball indentation is measured and does not exceed 2 mm 6.2.8/7.9.5 Result N/A SPDs category outdoor Between live parts and earth, the air clearances and creepage distances are not smaller than the values indicated in table 14 UC = _____ V ____ ≤ CTI ≤ ____ required. _____ mm measured ____ mm TRF No. IECEN61643_1C N/A Page 25 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause 7.9.5.2 Requirement - Test Result Verdict SPDs category indoor Air clearances and creepage distances are not smaller than the values indicated in table 15: required / measured Air clearances in millimetres 3/>3 P – screws and other means to fasten a covering, having to be detached for mounting the SPD ____ / ____ N/A – fastening surfaces (note 2) ____ / ____ N/A 6/>6 P ____ / ____ N/A – bodies (note 1) 3/>3 P – screws or other means for fastening the SPD 3/>3 P 3/>3 P ____ / ____ N/A – screws or other means for fastening the SPD (note 2) 6/>6 P – bodies (note 1) 3/>3 P 1) Between live parts of different polarity 2) Between live parts and – screws or other means for fastening the SPD (note 2) – bodies (notes 1 and 2) 3) Between the metal parts of the disconnector mechanism and Creepage distances in millimetres 4) Between live parts of different polarity 5) Between live parts and – screws and other means to fasten a covering, having to be detached for mounting the SPD NOTE 1 – Definition see 7.9.7.2. NOTE 2 – If clearances and creepage distances between live parts of the device and the metallic screen or the surface on which the SPD is mounted are dependant on the design of the SPD only, they cannot be reduced when the SPD is mounted in the most unfavourable position (even in a metallic enclosure), the values of lines 1 and 4 are sufficient. TRF No. IECEN61643_1C Page 26 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause 7.9.5.2.1 7.9.5.2.2 6.2.9/7.9.6 Requirement - Test Result The measurements are carried out without conductors as well as with conductors of the greatest crosssectional area indicated by the manufacturer. Nuts and screws with out-of-round heads are assumed to be in the most unfavourable tightening position. P If metal parts are covered with self-hardening resin of a least 2 mm thickness, or if they are covered with an insulation, withstanding a test voltage according to 7.9.8, creepage distances and air clearances are not necessary N/A Casting does not come over the rim of the deepening, it sticks strongly to the walls of the cavity and the metal parts in it P By examination and trial no possibility to detach the casting mass without a tool P Tracking resistance Test done on insulating materials necessary to retain live parts in their position P Testing is not applicable in case of insulating materials made out of ceramic, or if the creepage distances are at least equal to double the values indicated in 7.9.5 N/A Testing according to IEC 60112, solution A with a test voltage of 175 V 6.5.2/7.9.4 Verdict P Resistance to abnormal heat and fire The glow wire test is performed in accordance with clauses 4 to 10 of IEC 60695-2-1/1 - - for external parts of SPDs made of insulating material necessary to retain in position currentcarrying parts and parts of the protective circuit, by the test made at a temperature of (850 ± 15)°C for all other external parts made of insulating material, by the test made at a temperature of 650 °C ± 10 °C P 850°C P P For the purpose of this test, bases of surface-type SPDs are considered as external parts. The test is not made on parts of ceramic material. If the insulating parts are made of the same material, the test is carried out only on one of these parts, according to the appropriate glow-wire test temperature. The sample is positioned during the test in the most unfavourable position of its intended use (with the surface tested in a vertical position). TRF No. IECEN61643_1C P Page 27 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - TEST SEQUENCE 8 Clause Requirement - Test Result Verdict The tip of the glow-wire is applied to the specified surface of the test sample taking into account the conditions of intended use under which a heated or glowing element may come into contact with the sample P The sample is regarded as having passed the glow-wire test if – – there is no visible flame and no sustained glowing, or if P flames and glowing parts on the sample extinguish themselves within 30 s after the removal of the glowwire. P There is no ignition of the tissue paper or scorching of the pinewood board 6.4 P Environmental requirements Outdoor SPDs contained in a weather shield of glass, glazed ceramic or other acceptable material that is resistant to UV radiation, corrosion, erosion and tracking _____ Remarks: TRF No. IECEN61643_1C N/A Page 28 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 - EMC TEST SEQUENCE Clause Requirement - Test Result Verdict APPENDIX 7.10 Electromagnetic compatibility 7.10.1 Electromagnetic immunity SPDs either incorporating no electronic circuits or incorporating electronic circuits in which all components are passive (for example diodes, resistors, capacitors, inductors, varistors and other surge protective components) are not sensitive to normal electromagnetic disturbances and therefore no immunity tests are required. The requirements for SPDs containing electronic circuits are under consideration. 7.10.2 P N/A Electromagnetic emission For SPDs not incorporating electronic circuits, or incorporating electronic circuits that do not generate fundamental frequencies greater than 9 kHz in normal operation, electromagnetic disturbances can only be generated during protective operations. The duration of these disturbances is in the order of microseconds to milliseconds. The frequency, level and the consequences of these emissions are considered as part of the normal electromagnetic environment of low-voltage installations. Therefore, the requirements for electromagnetic emissions are deemed to be satisfied and no verification is necessary. The requirements for SPDs containing electronic circuits generating fundamental frequencies greater than 9 kHz are under consideration. Remarks: TRF No. IECEN61643_1C N/A N/A Page 29 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 Clause Requirement - Test Result Verdict APPENDIX National Differences for Europe and/or Group Differences 7.7.2.2 Thermal stability test Test for SPDs having no switching components in series with other components - Procedure a) If the voltage across the SPD falls below Ucs during the test, the current regulation is discontinued and the voltage is adjusted back to Uc (EN 61643-11 Ucs) and maintained for a duration of 15 min. Continuous current monitoring is no longer required. Source short-circuit current capability does not limit the current before any disconnector operates. The maximum available current value does not exceed the short circuit withstand capability declared by the manufacturer. _____ V _____ kA cos phi = _____ N/A Test for SPDs having switching components in series with other components - Procedure b) SPD energized with a power frequency source at Ucs having a short-circuit current capability which does not limit the current before any disconnector operates. The maximum available current value does not exceed the short-circuit withstand capability declared by the manufacturer. _____ V _____ kA cos phi = _____ N/A 6.2.11/7.7.3 Short circuit withstand capability a) Test of the declared short circuit withstand capability Power frequency source at Ucs, having a prospective shortcircuit current according to the declared shortcircuit withstand capability and power factor according to Table 11 b) Test at low short-circuit current Power frequency source at Ucs, having a prospective short-circuit current of five times the rated current of the maximum overcurrent protection (if declared by the manufacturer), and a power factor according to Table 11, shall be applied for 5 s ± 0,5 s. If no external overcurrent protection is required by the manufacturer, a prospective short-circuit current of 300 A is used. The test is carried out once with the shortcircuit initiated at 45 electrical degrees after the zero crossing of the voltage. TRF No. IECEN61643_1C _____ V _____ kA cos phi = _____ P _____ V 5 times max. overc. Prot. = _____ A P cos phi = _____ N/A Page 30 of 47 Report No.: 5007032-1181-0008/147768-04 IEC 61643-1/EN 61643-11 Clause 7.7.6 Requirement - Test Result Verdict Test under TOVs caused by faults in the low voltage system Only b) 7.8.5 TOV withstand mode is acceptable P Overload behaviour If a maximum overcurrent protection is specified by the manufacturer, the SPD is loaded for 1 h with a current equal to 1,6 times that maximum overcurrent protection. TRF No. IECEN61643_1C I = ______ A N/A Page 31 of 47 Report No.: 5007032-1181-0008/147768-04 Remarks: According to the manufacturers information the SPDs tested are designed for the following applications: Test(s) according to subclause SPD Type: Mode: Minimum U T for 5s: TOV values for 200ms designed to be connected to : (subclause 7.7.6.1) (subclause 7.7.4) 1,45*U O = 334 V - - - - - TN-systems with UO ≤ 230 V Connected L- (PE)N U C ≥ 1,1*U O Connected N-PE UC ≥ UO Connected L-L U C ≥ 1,1*√3*U O TT-systems with Uo ≤ 230 V Connected L-PE U C ≥ 1,1*U O √3*U O = _____ V 1200 V + U O = _____ V Connected L-N U C ≥ 1,1*U O 1,45*U O = 334 V - Connected N-PE UC ≥ UO - 1200 V - - - 1200 + U O = _____ V 1,45 U O = _____ V - - 1200 V - - Connected L-L U C ≥ 1,1*√3*U O IT-systems with Uo ≤ _____ V Connected L-PE U C ≥ 1,1*√3*U O Connected L-N U C ≥ 1,1*U O Connected N-PE UC ≥ UO Connected L-L U C ≥ 1,1*√3*U O TN, TT and IT-systems with Uo ≤ _____ V Connected L-PE U C ≥ 1,1*U O √3*U O = _____ V 1200 + U O = _____ V Connected L-(PE) N U C ≥ 1,1*U O 1,45*U O = _____ V - Connected N-PE UC ≥ UO - 1200 V - - __________ __________ Connected L-L U C ≥ 1,1*√3*U O Special applications, no public power supply ___________________________ TRF No. IECEN61643_1C Page 32 of 47 Report No.: 5007032-1181-0008/147768-04 Marking Reproduction: Photographs: Component list: Type HAKEL PIIIM-275 PIIIM-320 PIIIM-385 PIIIM-440 … … … … Varistor type SIOV-D40K275QK6 SIOV-D40K320QK6E3 SIOV-D40K385QK6E3 SIOV-D40K440QK6E3 TRF No. IECEN61643_1C Manufacturer Quantity EPCOS EPCOS EPCOS EPCOS 1 1 1 1 RMS-voltage [V] 275 320 385 440 Page 33 of 47 Report No.: 5007032-1181-0008/147768-04 Table 5 – Screw thread diameters and applied torques Nominal diameter of thread Torque mm I Nm II III Up to and including 2,8 0,2 0,4 0,4 Over 2,8 up to and including 3,0 0,25 0,5 0,5 Over 3,0 up to and including 3,2 0,3 0,6 0,6 Over 3,2 up to and including 3,6 0,4 0,8 0,8 Over 3,6 up to and including 4,1 0,7 1,2 1,2 Over 4,1 up to and including 4,7 0,8 1,8 1,8 Over 4,7 up to and including 5,3 0,8 2,0 2,0 Over 5,3 up to and including 6,0 1,2 2,5 3,0 Over 6,0 up to and including 8,0 2,5 3,5 6,0 Over 8,0 up to and including 10,0 – 4,0 10,0 Table 6 – Connectable cross-sections of copper conductors for screw-type terminals or screwless terminals Maximum continuous load current for two-port SPDs or one-port SPDs with separate input/output terminals1) Range of nominal cross-sections to be clamped (single conductor) A Up to and including 13 Above 13 up to and including 16 Above 16 up to and including 25 Above 25 up to and including 32 Above 32 up to and including 50 Above 50 up to and including 80 Above 80 up to and including 100 Above 100 up to and including 125 ISO – mm2 AWG – Terminal 1 to 2,5 1 to 4 1,5 to 6 2,5 to 10 4 to 16 10 to 25 16 to 35 25 to 50 18 to 14 18 to 12 16 to 10 14 to 8 12 to 6 8 to 3 6 to 2 4 to 1 1) It is required that, for current ratings up to and including 50 A, terminals be designed to clamp solid conductors as well as rigid stranded conductors; the use of flexible conductors is permitted. Nevertheless, it is permitted that terminals for conductors having cross-sections for 1 mm2 up to 6 mm2 be designed to clamp solid conductors only. Table 7 – Pulling forces (screw terminals) Cross-section of conductor accepted by the terminal Up to 4 Up to 6 Up to 10 Up to 16 Up to 50 50 60 80 90 100 mm2 Pull N TRF No. IECEN61643_1C Page 34 of 47 Report No.: 5007032-1181-0008/147768-04 Table 8 – Conductor dimensions Range of nominal cross-sections to be clamped Stranded conductor Number of wires Diameter of wires mm2 mm 1 to 2,5* 7 0,67 1 to 4* 7 0,85 1,5 to 6* 7 1,04 2,5 to 10 7 1,35 4 to 16 7 1,70 10 to 25 7 2,14 16 to 35 19 1,53 25 to 50 Under consideration Under consideration * If the terminal is intended to clamp solid conductors only (see note of table 6), the test is not made. Table 9 – Pulling force (screwless terminals) Cross-sectional area 0,5 0,75 1,0 1,5 2,5 4 6 10 16 25 35 30 30 35 40 50 60 80 90 100 135 190 mm2 Pull force N Table 11 – Prospective short-circuit current and power factor (lt. 898) Ip (kA)+5/-0% Ip ≤ 1,5 1,5 < Ip ≤ 3,0 3,0 < Ip ≤ 4,5 4,5 < Ip ≤ 6,0 6,0 < Ip ≤ 10,0 10,0 < Ip ≤ 20,0 20,0 < Ip ≤ 50,0 50,0 < Ip cosφ( +0/-0.05) 0,95 0,9 0,8 0,7 0,5 0,3 0,25 0,2 NOTE – Recovery voltage according to IEC 60947-1. Table 11x – Current factor k for overload behaviour TRF No. IECEN61643_1C Page 35 of 47 Report No.: 5007032-1181-0008/147768-04 Table 12 – Tightening requirements for clamping screws Nominal diameter of thread Torque mm Nm Up to and including 2,8 0,2 0,4 - Over 2,8 up to and including 3,0 0,25 0,5 - Over 3,0 up to and including 3,2 0,3 0,6 - Over 3,2 up to and including 3,6 0,4 0,8 - Over 3,6 up to and including 4,1 0,7 1,2 1,2 Over 4,1 up to and including 4,7 0,8 1,8 1,2 Over 4,7 up to and including 5,3 0,8 2,0 1,4 Table 13 – Fall distance for impact requirement Height of fall Parts of enclosures to be subjected to the impacts mm Ordinary accessory Other accessories 100 A and B A and B 150 C C 200 D D A: parts on the front surface, including parts which are recessed. B: parts which do not project more than 15 mm from the mounting surface (distance from the wall) after mounting as in normal use, with the exception of the above parts A. C: parts which project more than 15 mm and not more than 25 mm from the mounting surface (distance from the wall) after mounting as in normal use, with the exception of the above parts A. D: parts which project more than 25 mm from the mounting surface (distance from the wall) after mounting as in normal use, with the exception of the above parts A. Table 14 – Air clearances and creepage distances for SPDs category outdoor SPD maximum continuous operating voltage V Minimum air clearance in Up to 450 3 mm Creepage distance in mm for insulating materials with * CTI ≥ 600 400 ≤ CTI ≤ 600 6 7,5 450 – 600 5,5 12 15,5 600 – 1 200 8 20 25 1 200 – 1 500 10 30 40 * Other values are possible if the pollution degree is lower than 4 or a pollution test is performed. These values are based on IEC 60664-1 for heights up to 2 000 m above sea level, pollution degree 4 and inhomogeneous field conditions. Comparative Tracking Index (CTI) value according to IEC 60112, solution A. TRF No. IECEN61643_1C Page 36 of 47 Report No.: 5007032-1181-0008/147768-04 Table 15 – Air clearances and creepage distances for SPDs category indoor SPD continuous operating voltage Up to 100 V – 200 V – 450 V – 600 V 1 200 V – 100 V 200 V 450 V 600 V 1 200 V 1 500 V 1 2 3 5,5 8 12 – screws and other means to fasten a covering, having to be detached for mounting the SPD 1 2 3 5,5 8 12 – fastening surfaces (note 2) 2 4 6 11 16 24 – screws or other means for fastening the SPD (note 2) 2 4 6 11 16 24 – bodies (notes 1 and 2) 1 2 3 5,5 8 12 – bodies (note 1) 1 2 3 5,5 8 12 – screws or other means for fastening the SPD 1 2 3 5,5 8 12 1 2 3 5,5 8 12 1 2 3 5,5 8 12 – screws or other means for fastening the SPD (note 2) 2 4 6 11 16 24 – bodies (note 1) 1 2 3 5,5 8 12 Air clearances in millimetres 1) Between live parts of different polarity 2) Between live parts and 3) Between the metal parts of the disconnector mechanism and Creepage distances in millimetres 4) Between live parts of different polarity 5) Between live parts and – screws and other means to fasten a covering, having to be detached for mounting the SPD NOTE 1 – Definition see 7.9.7.2. NOTE 2 – If clearances and creepage distances between live parts of the device and the metallic screen or the surface on which the SPD is mounted are dependant on the design of the SPD only, they cannot be reduced when the SPD is mounted in the most unfavourable position (even in a metallic enclosure), the values of lines 1 and 4 are sufficient. Table 16 – Dielectric withstand SPD continuous operating voltage V TRF No. IECEN61643_1C AC test voltage kV Up to Uc = 100 1,1 Up to Uc = 200 1,7 Up to Uc = 450 2,2 Up to Uc = 600 3,3 Up to Uc = 1 200 4,2 Up to Uc = 1 500 5,8 Page 37 of 47 Report No.: 5007032-1181-0008/147768-04 Table B.1 – TOV test values Fig. B.1 – Test setting for operating duty test TRF No. IECEN61643_1C Page 38 of 47 Annex 1 Current – voltage oscillograms: 8/20 (positive polarity) Sample 2.1 (oscillogram 2112082) TRF No. IECEN61643_1C Report No.: 5007032-1181-0008/147768-04 Page 39 of 47 Sample 2.2 (oscillogram 2112084) TRF No. IECEN61643_1C Report No.: 5007032-1181-0008/147768-04 Page 40 of 47 Sample 2.3 (oscillogram 2112085) TRF No. IECEN61643_1C Report No.: 5007032-1181-0008/147768-04 Page 41 of 47 Report No.: 5007032-1181-0008/147768-04 Annex 2 Table of residual voltage at 1,0 times In (SPD contains only voltage limiting components) Sample 2.1 2.2 2.3 Oscillogram No.: 20 kA (pos. polarity) Ures [V] 1155 1135 1130 2112082/_084/_085 20 kA (neg. polarity) Ures [V] 1136 1140 1145 2112083/_117/_086 Annex 3 Sparcover voltage with 1,2/50 voltage impulse: Not Applicable TRF No. IECEN61643_1C Page 42 of 47 Report No.: 5007032-1181-0008/147768-04 Annex 4 Current records of preconditioning test Sample 3.7 (oscillogram 2113666) Picture at synchronisation with 60°, last shot of preconditioning test TRF No. IECEN61643_1C Page 43 of 47 Report No.: 5007032-1181-0008/147768-04 Sample 3.8 (oscillogram 2113671) Picture at synchronisation with 60°, last shot of preconditioning test TRF No. IECEN61643_1C Page 44 of 47 Report No.: 5007032-1181-0008/147768-04 Sample 3.9 (oscillogram 2113676) Picture at synchronisation with 60°, last shot of preconditioning test TRF No. IECEN61643_1C Page 45 of 47 Report No.: 5007032-1181-0008/147768-04 Annex 5 Voltage and current records of operating duty test: All pictures with 100% of Imax = 50kA, last shot of operating duty test Sample 3.7 (oscillogram 2113842) TRF No. IECEN61643_1C Page 46 of 47 Sample 3.8 (oscillogram 2113843) TRF No. IECEN61643_1C Report No.: 5007032-1181-0008/147768-04 Page 47 of 47 Sample 3.9 (oscillogram 2113860) TRF No. IECEN61643_1C Report No.: 5007032-1181-0008/147768-04