118 MY HOME Automation CONTENTS MY HOME – Automation General features. . . . . . . . . . . . . . . . . . . . . . . 60 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 84 General rules for installation . . . . . . . . . . . . . . . 94 Wiring diagrams. . . . . . . . . . . . . . . . . . . . . . 104 Automation MY HOME 119 GEnErAl fEAturEs introduction to the Automation system the MY HOME Automation system a programmable logic and are if it is not possible to achieve a Bus allows you to manage functions in connected in parallel with a system or if you want to expand a a simultaneous and integrated way 2-conductor Bus cable for sending pre-existing system without any to date, these functions have been information and with low voltage masonry work, the Automation performed with special and complex (27V d c ) electric power there are system can be expanded with special electrical devices such as: two types of devices in the system: wire/radio interfaces and radio lighting control controls, connected only to the control devices characterised by high installation flexibility Bus cable; control for shutters and/or electric actuators, connected both to curtains, fans, exhausters, etc Compared to the devices the Bus cable and to the 230V of a conventional electrical a c power line for managing the system, Automation devices connected load have an electronic circuit with Wire system Basic contact interface General control Touch control (SOFT TOUCH) Local Display Traditional device Power supply 230 Vac TV/SAT DIN module actuator TV/SAT automazione diffusione sonora IPTV DIN module dimmer actuator antifurto termoregolazione videocitofonia controllo TV/SAT automazione diffusione sonora antifurto termoregolazione videocitofonia controllo lan Shutters controllo carichi energia lan IPTV controllo carichi energia automazione luci diffusione tvcc sonora antifurto www termoregolazione irrigazione IPTV luci Light tvcc www irrigazione Shutters The MY HOME Automation system devices are IMQ certified, as they comply with the CEI EN 50428 standard “non-automatic control devices for fixed electrical home installations and similar uses”. 120 MY HOME Automation TV/SAT Shutter actuator IPTV control TV/SAT videocitofonia controllo n When the Automation system it is also possible to carry out special control device or by using the touch devices are configured properly, it functions - which can hardly be screen menu if the Automation is possible to manage the load as achieved with conventional electrical system is integrated with the 2 wire follows: systems sound system and temperature Control for a single load (lamp, these functions are called scenarios, control system, the scenario can also which consist of a set of simultaneous set up a room with background music controls used for arranging the room and with the required temperature shutters, etc ); Control for one or more load groups (for example, only the according to the user’s lifestyle shutters on the first floor, north An example of a scenario can be side, etc ); represented by the simultaneous activation of lights, shutters, etc , simultaneous management of all loads (for example, general which can be set by the user after deactivation of all lamps in the getting home by using one single house and/or closing of all rolling shutters) radio/wire interfaces Local control radio system Radio control SCS/ZigBee GATEWAY radio interface Touch Screen Radio remote control Basic actuator TV/SAT TV/SAT automazione IPTV TV/SAT controllo carichi energia IPTV diffusione sonora antifurto termoregolazione videocitofonia controllo lan controllo carichi energia IPTV luci tvcc www irrigazione IPTV luci Light tvcc Shutter actuator control www irrigazione Shutters Automation MY HOME 121 GEnErAl fEAturEs Control devices Control devices allow you to control is separated from the mechanical two types of keys and key covers can the state of the actuators, thus operating part so that one can be used: executing different functions: On, choose the type, number and size of 1 function key cover, one or two Off, timing, etc , which depend the control pushbuttons modules, to be used with the grey on the functioning mode that has the device can be modular, thus control key; been assigned to them through an meeting the different installation appropriate configuration requirements and different functions modules, to be used with the black the electronic part of these devices required by the user control key; 2 function key cover, one or two Upper pushbutton Lower pushbutton LED Control key Key cover 1 function 1 module Key cover 2 functions 1 module Control key Key cover 1 function 2 modules Control key Key cover 2 functions 2 modules The control with the single key cover can become integrated The double key cover (tilting) can become integrated with a traditional exchanging contact. with a traditional closing contact (pushbutton or switch). NOTE: control keys are supplied with the device as standard. 122 MY HOME Automation lowered controls speciAl control these devices are consist of two in addition to the standard functions lowered flush mounted modules it also enables performing all this reduces depth, leaving more the special functions, normally room inside the box for the housing performed by three different controls: of cables, or for basic modularity the special function control, the devices extended control, and the timer control lowered 2 Module control the special control features 4 the single and double load control pushbuttons and 2 green/red control stAtus indicAtors performs the same functions of the bicolour lEDs (in the liVinGliGHt All the controls feature lEDs, which previously released item the only and MÀtiX version) or 4 blue/red indicate their status (enabled or differences are: bicolour lEDs (AXOlutE version) disabled), and make them easier to find in the dark the intensity of the it has been lowered to reduce the selected load status signalling lED size inside the box; it features two green/red bicolour may be adjusted or turned off using lEDs (in the liVinGliGHt and the pushbutton on the control itself MÀtiX version), or 4 blue/red bicolour lEDs (AXOlutE version) Lowered 2 module control Special control Upper pushbutton more space available LED Lower pushbutton Automation MY HOME 123 GEnErAl fEAturEs Control devices: controls/key covers - quick matching guide aXolUTe Key-coVers WiThoUT silK-screen prinTing 1 ModUle 1 Function liVinglighT 2 ModUles 2 Functions 1 Function 2 Functions 1 ModUle 1 Function 2 ModUles 2 Functions 1 Function 2 Functions Controls for 3 independent loads Controls for 2 independent loads Special control conTrols H4651M2 L4651M2 AM5831M2 HD4915 HC4915 HS4915 HD4911 HC4911 HS4911 HD4915M2 HC4915/2 HS4915/2 HD4911M2 HC4911/2 HS4911/2 L4915N N4915LN NT4915N L4911N N4911N NT4911N L4915M2N N4915M2N NT4915M2LN L4911M2N N4911M2N NT4911M2N H4652/2 L4652/2 AM5832/2 HD4915 HC4915 HS4915 HD4911 HC4911 HS4911 HD4915M2 HC4915/2 HS4915/2 HD4911M2 HC4911/2 HS4911/2 L4915N N4915LN NT4915N L4911N N4911N NT4911N L4915M2N N4915M2N NT4915M2LN L4911M2N N4911M2N NT4911M2N H4652/3 L4652/3 AM5832/3 HD4915 HC4915 HS4915 HD4911 HC4911 HS4911 HD4915M2 HC4915/2 HS4915/2 HD4911M2 HC4911/2 HS4911/2 L4915N N4915LN NT4915N L4911N N4911N NT4911N L4915M2N N4915M2N NT4915M2LN L4911M2N N4911M2N NT4911M2N HD = WHITE, HC = TECH, HS = ANTHRACITE, L = ANTHRACITE, N = WHITE, NT = TECH aXolUTe Key-coVers WiTh silK-screen prinTing* 1 ModUle 1 Function 2 Functions liVinglighT 2 ModUles 1 Function 2 Functions 1 ModUle 1 Function 2 Functions 2 ModUles 1 Function 2 Functions Controls for 3 independent loads Controls for 2 independent loads Special control Controls H4651M2 L4651M2 AM5831M2 HD4915... HC4915... HS4915... HD4911... HC4911... HS4911... HD4915M2... HC4915/2... HS4915/2... HD4911M2... HC4911/2... HS4911/2... L4915... N4915... NT4915... L4911... N4915... NT4915... L4915M2... N4915M2... NT4915M2... L4911M2... N4915M2... NT4915M2... H4652/2 L4652/2 AM5832/2 HD4915... HC4915... HS4915... HD4911... HC4911... HS4911... HD4915M2... HC4915/2... HS4915/2... HD4911M2... HC4911/2... HS4911/2... L4915... N4915... NT4915... L4911... N4915... NT4915... L4915M2... N4915M2... NT4915M2... L4911M2... N4915M2... NT4915M2... HD4915... HC4915... HS4915... HD4911... HC4911... HS4911... HD4915M2... HC4915/2... HS4915/2... HD4911M2... HC4911/2... HS4911/2... L4915... N4915... NT4915... L4911... N4915... NT4915... L4915M2... N4915M2... NT4915M2... L4911M2... N4915M2... NT4915M2... H4652/3 AM5832/3 L4652/3 HD = WHITE, HC = TECH, HS = ANTHRACITE, L = ANTHRACITE, N = WHITE, NT = TECH * Complete the Key cover code with the letters corresponding to the required screen printing (see table). For the complete range of LIVINGLIGHT key covers see the “Catalogue” section. 124 MY HOME Automation selecTion of Key coVers WiTh silK- screen prinTing MàTiX 1 ModUle 1 Function AM5911 2 Functions AM5911 AM5911 AM5911 AM5911 2 ModUles AM5911 1 Function AM5911/2 AM5911/2 AM5911/2 aXolUTe MaTiX 2 Functions AM5911/2 AM5911/2 AM5911/2 MàTiX 1 Function AM5915... AM5915... AM5915... 2 Functions AM5911... AM5911... AM5911... 2 ModUles 1 Function AM5915/2... AM5915/2... AM5915/2... AM5911/2... AM5911/2... silK-screen prinTing descripTion DD DO NOT DISTURB BN STAIRCASE LIGHT MR MAKE THE ROOM AA OFF AB ON AC GEN AD ADN DIMMER BA AN LIGHT BB DN BELL BC EXHAUST FAN FN KEY BE TREBLE CLEF BF NURSE BG 1) ROOM BH ALARMS 2 FUNCTIONS 2 Functions AM5911/2... silK-screen prinTing 1 FUNCTION BD 1 ModUle liVinglighT AF AFN ON/OFF/GEN AG AGN ON/OFF AH AHN UP/DOWN AI AIN ON/OFF DIMMER BA 1) LIGHT BC 1) EXHAUST FAN BE 1) TREBLE CLEF BF 2) BFN ADN SOUND SYSTEM FUNCTION + - + UP - DOWN 1) Key cover not available for the MÀTIX series 2) Key cover not available for the 1 and 2 module AXOLUTE series, and for the 2 module MÀTIX, LIVINGLIGHT series Automation MY HOME 125 GEnErAl fEAturEs Control devices 2 module Soft Touch control two or three Module Axolute soft touch controls this device is capable of sending actuation and adjustment commands for the automation, sound system and video door entry system functions, with the simple touch of the control Axolute nighter, whice And white glAss controls Each zone corresponding to a key is the nighter and Whice control marked at the centre by a light blue this effect gives the user the feeling is a control where the traditional lED of activating the control using the pushbuttons are replaced by When the user moves a finger close, appropriate configurator it is possible capacitive sensors its intensity increases sensibly, and to select different intensity levels Moving the finger close to a sensor is remains so until the finger is moved the same as pressing a pushbutton away again the device can therefore be used to control single or group loads (e g lights and shutters), sound system, scenarios, and basic video door entry Nighter 3 module control system functions it’s produced in the versions with 3 and 4 flush mounted modules, with 6 and 8 keys respectively Whice 4 module control 126 MY HOME Automation infrAred controls ir receiver and new ir remote intended for 1 relay actuators for control: single loads, 2 relays actuators for With the receiver, the manual control double loads (shutter motor etc ), for can be complemented or replaced by the management of scenarios, as well a remote control, using the infrared as manage both sound systems and remote control unit, 3529 video door entry systems IR receiver to the remote control pushbuttons, it is possible to associate controls IR remote control MoVeMent And lighting sensors thanks to the new Green Comfort and wellbeing switch sensors and the lighting the new sensors also allow Management system sensors, it is increasing the level of comfort possible to manage, in a My Home of the users, with the automatic system, the lighting depending on switching on of the light when the presence of people, and the level entering the room, and the of natural light, ensuring: preservation of the desired Energy efficiency lighting level based on external With the new sensors it is possible conditions to eliminate energy waste through an intelligent management of the lights, ensuring the necessary lighting levels, at the right time and in the right place the various operating modes that can be set with the configuration enable the user to obtain different levels of energy efficiency Automation MY HOME 127 GEnErAl fEAturEs Control devices scenArio MAnAgeMent systeMs a certain level, and positioning some scenario that can be set using these devices can be used to create shutters for watching the television, the various integrated MY HOME particular and advanced comfort or reading a book, following the life systems is the activation of a certain situations called scenarios, for style of the user background music, the setting of the example, by activating some lights to Another example of an advanced temperature and the light level of the house, when entertaining friends Multimedia Touch Screen automazione Lighting/movement sensor diffusione sonora antifurto Scenario programmers MH200N Touch Screen TV/SAT Nighter & Whice control automazione 128 MY HOME Automation diffusione sonora antifurto termoregolazione videocitofonia controllo the described scenarios are managed 2 Din modules f420 scenario MH200n scenario programmer for from particular devices capable of module for saving 16 scenarios the creation and management of saving in the memory all the Controls for automation, sound system, advanced scenarios, also linked that define the scenario, and which temperature control, and video to time events, system status, and the user can recall simultaneously by door entry applications more pressing one single pushbutton the devices capable of saving and programming these functions are the following: automazione TV/SAT diffusione sonora antifurto termoregolazione videocitofonia controllo IPTV lan controllo carichi Special control energia luci tvcc Video Station (*) Scenario module F420 Soft Touch control Local display IPTV controllo carichi Protected scenario control with transponder (*) energia luci tvcc www irrigazione Scenario control NOTE (*): at the moment these devices cannot activate scenarios managed by the MH200N scenario programmer. Automation MY HOME 129 w GEnErAl fEAturEs Control devices control selection BAsed on the function to Be MAnAged Type of conTrol on/off lighTing and loads aXolUTe liVinglighT lighTing WiTh adJUsTMenT (diMMer) MàTiX aXolUTe liVinglighT MàTiX 2/3 module single and double load control (*) H4652/2 H4652/3 L4652/2 L4652/3 AM5832/2 AM5832/3 H4652/2 H4652/3 L4652/2 L4652/3 AM5832/2 AM5832/3 2 module special control (*) H4651M2 L4651M2 AM5831M2 H4651M2 L4651M2 AM5831M2 HD4563 HC4563 HS4563 L4563 N4563 NT4563 HD4654 HC4654 HS4654 L4654N N4654N NT4654N AM5834 Knob control Infrared receiver + IR remote control HD4654 HC4654 HS4654 L4654N N4654N NT4654N AM5834 Scenario control 2/3 module Soft Touch control HD4653M2 HD4653M3 HC4653/2 HC4653/3 HS4653/2 HS4653/3 HD4653M2 HD4653M3 HC4653/2 HC4653/3 HS4653/2 HS4653/3 3/4 module Nighter and Whice controls HD4657M3 HD4657M4 HC4657M3 HC4657M4 HS4657M3 HS4657M4 HD4657M3 HD4657M4 HC4657M3 HC4657M4 HS4657M3 HS4657M4 Touch Screen - Local display H4890 HW4890 LN4890 LN4890A AM5890 H4890 HW4890 LN4890 LN4890A AM5890 Green Switch control and PIR sensor HC4659 HC4658 HD4659 HD4658 HS4659 HS4658 H4648 H4649 L4659N L4658N N4659N N4658N NT4659N NT4658N LN4648 LN4649 AM5659 AM5658 HC4659 HC4658 HD4659 HD4658 HS4659 HS4658 L4659N L4658N N4659N N4658N NT4659N NT4658N AM5659 AM5658 Key card switches * To be completed with key cover 130 MY HOME Automation MANAGEMENT OF AUTOMATISMS (E.G. CURTAINS AND SHUTTERS) AXOLUTE LIVINGLIGHT SCENARIO MANAGEMENT USING F420 AND MH200N MàTIX AXOLUTE LIVINGLIGHT MàTIX H4652/2 H4652/3 L4652/2 L4652/3 AM5832/2 AM5832/3 H4651M2 L4651M2 AM5831M2 H4651M2 L4651M2 AM5831M2 HD4654 HC4654 HS4654 L4654N N4654N NT4654N AM5834 HD4654 HC4654 HS4654 L4654N N4654N NT4654N AM5834 HD4680 HC4680 HS4680 L4680 N4680 NT4680 HD4653M2 HD4653M3 HC4653/2 HC4653/3 HS4653/2 HS4653/3 HD4657M3 HD4657M4 HC4657M3 HC4657M4 HS4657M3 HS4657M4 H4890 HW4890 HC4891 HD4891 HS4891 LN4890 LN4890A L4891 N4891 NT4891 AM5890 HC4659 HC4658 HD4659 HD4658 HS4659 HS4658 H4648 H4649 L4659N L4658N N4659N N4658N NT4659N NT4658N LN4648 LN4649 AM5659 AM5658 HD4657M3 HD4657M4 HC4657M3 HC4657M4 HS4657M3 HS4657M4 H4890 HW4890 LN4890 LN4890A AM5890 Automation MY HOME 131 GEnErAl fEAturEs Actuator devices these devices execute direct controls flush-Mounting ActuAtor and control the connected load in the with 2 Modules same way as an electromechanical they are available with 1 and 2 relay interlocked relays: control for 1 single for this reason, they must be load (lamp or motor) or 1 double load connected to the Bus cable using the (motor for shutters) removable terminals as well as to the these actuators can be 230V a c supply line of the load advantageously used as a control there are different types of actuators: point, as they are provided with they can differ by shape, size, control pushbuttons at the front side installation features and by their operated by key covers Shutters up-down TV/SAT automazione diffusione sonora controlled power the range includes: Example of installation of a flush mounted actuator (with 2 interlocked relays) for the control of the shutters. flush mounted two module actuators; Basic modularity actuators with reduced profile; Din module actuators Upper pushbutton Lower pushbutton LED Control key Key cover 1 function 2 modules NOTE: the control keys are supplied with the device as standard. 132 MY HOME Automation Control key Key cover 2 functions 2 modules antifur BAsic Module ActuAtor Basic actuators are characterized by extremely compact dimensions: width = 40 5 mm, height = 40 5 mm, Example of installation in flush mounted box Side-by-side Basic items Box depth = 18 mm these dimensions allow the actuators to be installed in junction boxes or inside the load to be controlled (for example in the bowl of a chandelier, in the structure of a lampstand, etc ) it is also possible to place the control for two light points with their Basic actuators in a 503E box; the installation can otherwise be achieved with a 504E box or by finding new spaces for the BUS BUS Input for traditional devices Support Control positioning of the actuators new flush Mounted ActuAtor/control Flush mounted actuator/control this device is fitted with 2 independent relays for the management of: - 2 loads or 2 groups of loads, independent; - 1 single load (rolling shutter motor) the actuator may also be configured for the management of the connected load, whilst at the same time operating as a “control device” for the management of one or more remote actuators, with operating modes typical of control device item H/l4652/2 Light management “actuator” key cover Remote actuator “control” key cover Automation MY HOME 133 GEnErAl fEAturEs Actuator devices: controls/key covers quick matching guide aXolUTe Key-coVers WiThoUT silK-screen prinTing 2 ModUles 1 Function liVinglighT 1 ModUle 2 Functions 1 Function 2 Functions 2 ModUles 1 Function 1 ModUle 2 Functions 1 Function 2 Functions Dimmer actuator Actuator/control with 2 interlocked relays Actuator with 1 relay acTUaTors H4671/1 L4671/1 AM5851/1 HD4915M2 HC4915/2 HS4915/2 HD4911M2 HC4911/2 HS4911/2 H4671M2 L4671M2 AM5851M2 L4915M2N N4915M2N NT4915M2LN HD4911M2 HC4911/2 HS4911/2 H4678 L4678 HD4915M2 HC4915/2 HS4915/2 HD4915 HC4915 HS4915 L4911M2N N4911M2N NT4911M2N HD4911 HC4911 HS4911 HD4911M2 HC4911/2 HS4911/2 L4911M2N N4911M2N NT4911M2N L4915M2N N4915M2N NT4915M2LN L4915N N4915LN NT4915N L4911N N4911N NT4911N L4911M2N N4911M2N NT4911M2N HD = WHITE, HC = TECH, HS = ANTHRACITE, L = ANTHRACITE, N = WHITE, NT = TECH aXolUTe Key-coVers WiTh silK-screen prinTing* 2 ModUles 1 Function 2 Functions liVinglighT 1 ModUle 1 Function 2 Functions 2 ModUles 1 Function 2 Functions 1 ModUle 1 Function 2 Functions Dimmer actuator Actuator/control with 2 interlocked relays Actuator with 1 relay acTUaTors H4671/1 L4671/1 AM5851/1 HD4915M2... HC4915/2... HS4915/2... H4671/1 L4671/1 AM5851/1 H4678 L4678 HD4911M2... HC4911/2... HS4911/2... HD4911M2... HC4911/2... HS4911/2... HD4915M2... HC4915/2... HS4915/2... L4915M2 L4915M2 NT4915M2 HD4915... HC4915... HS4915... HD4911M2... HC4911/2... HS4911/2... HD = WHITE, HC = TECH, HS = ANTHRACITE, L = ANTHRACITE, N = WHITE, NT = TECH * Complete the Key cover code with the letters corresponding to the required screen printing (see table). 134 MY HOME Automation HD4911... HC4911... HS4911... L4911M2 N4915M2 NT4915M2 L4911M2 N4915M2 NT4915M2 L4915M2 N4915M2 NT4915M2 L4911M2 N4915M2 NT4915M2 L4915... N4915... NT4915... L4911... N4915... NT4915... selecTion of Key coVers WiTh silK-screen prinTing MàTiX 2 ModUles 1 Function AM5911/2 aXolUTe MaTiX 1 ModUle 2 Functions 1 Function AM5911 AM5911 silK-screen prinTing DD DO NOT DISTURB BN STAIRCASE LIGHT MR MAKE THE ROOM AA OFF AB ON AC GEN AD ADN DIMMER BA AN LIGHT BB DN BELL BC BD MàTiX 2 ModUles 1 Function AM5915/2... 2 Functions 1 ModUle 1 Function AM5915... EXHAUST FAN FN KEY BE TREBLE CLEF BF NURSE BG 1) ROOM BH ALARMS 2 FUNCTIONS 2 Functions AM5911/2... AM5911/2... silK-screen prinTing descripTion 1 FUNCTION 2 Functions AM5911/2 AM5911/2 liVinglighT AM5911... AF AFN ON/OFF/GEN AG AGN ON/OFF AH AHN UP – DOWN AI AIN ON/OFF DIMMER BA 1) LIGHT BC 1) EXHAUST FAN BE 1) TREBLE CLEF BF 2) BFN ADN SOUND SYSTEM FUNCTION + - + UP - DOWN 1) Key cover not available for the MÀTIX series 2) Key cover not available for the 1 and 2 module AXOLUTE series, and for the 2 module MÀTIX, LIVINGLIGHT series Automation MY HOME 135 GEnErAl fEAturEs Actuator devices din Moduel ActuAtors these devices are suitable for cover so as to reduce the overall centralised installations in boards dimensions, thus allowing them to and switchboards (2 Din modules) be installed in raceways, junction Available in versions with 1, 2 and 4 boxes, false ceilings, boxes for rolling relays for controlling single loads or shutters, etc double loads (motor for shutters); With centralised installations, for these devices are also provided with example, Din switchboards E215/ , load control keys for carrying out an MultiBOX or with the innovative operational test installation solution MY HOME these actuators are characterised by flAtWAll*, the Din adapter and the having the advantage of removing front cover enable you to align the the rear Din adapter and the front profile of the adapter to that of the Switchboard installation example other Din modular devices DIN actuator for installation in switchboards Load connection terminals Load control pushbutton Example of installation inside a junction box Configurator housing Removable adapter for installation on DIN rail in switchboards Removable front cover 136 MY HOME Automation ActuAtors And diMMers 4 relay actuator in DIN module BMSW1003 with power line supply new actuators and dimmers, part of the lighting Management offer range, which, thanks to the power supply from the power line, provide Multi load dimmer actuator in DIN module with one output F416U1 control of the load connected even when no power is received from the Bus in this case, control is ensured using the keys found on the device itself in this case, control is ensured using the keys found on the device itself; they also absorb an extremely limited amount of current from the power supply of the Bus, and new ActuAtors therefore only have a marginal some devices of the Energy the exception of the management impact on the maximum number of Management offer may also be used of the shutters the connection with devices that may be installed on the in the automation system the power line enables zero crossing, Bus itself DIN actuators: which makes the devices compatible the catalogue offers actuators in two actuator devices capable with the new energy saving lamps the 1, 2, and 4 relay versions with of performing both energy (compact fluorescent and lED) independent outputs for lighting management and automation Flush mounted actuator: devices only; functions; one in the basic version Actuator conceived for installation the power supply enables zero and one fitted with an integrated in liVinGliGHt and AXOlutE flush crossing and allows them to current sensor for the measurement mounted supports, intended for be particularly suitable for the of the consumption of the controlled the automation and/or energy management of the new energy load (instantaneous consumption management functions saving lamps, such as compact and 2 energy totalizers that can be fluorescent lamps and lED lamps reset independently) there are also dimmers with 0/10 Configured in automation mode, they V output, and two new “multi load” enable performing all the operations dimmers with 1 or 2 outputs, which available on the Control devices, with can control any type of load (with the exception of compact fluorescent DIN actuator Flush mounted actuator and lED lamps), and which enable the user to install the dimmer on the system, postponing the selection of the lamp to a later date Automation MY HOME 137 GEnErAl fEAturEs Actuator devices ActuAtor selection BAsed on the function to Be MAnAged on/off lighTing and loads Type of acTUaTor aXolUTe liVinglighT Flush mounted 2 module (*) 1 relay actuator H4671/1 L4671/1 Flush mounted, 2 relays, 2 MODULES (*), actuator/control H4671M2 L4671M2 Flush mounted 2 MODULE (*) dimmer actuator Basic actuator 3475 Basic Actuator/Control 3476 1, 2, 4 relay DIN actuators F411/1N (1 relay) F411/2 (2 independent relays) F411/4 (4 independent relays with one common clamp) F411/1NC F411/2NC BMSW1001 BMSW1002 BMSW1003 DIN Dimmer actuators * To be completed with key cover 138 MY HOME Automation MàTiX AM5851/1 AM5851M2 LIGHTING WITH ADJUSTMENT (DIMMER) AXOLUTE LIVINGLIGHT MANAGEMENT OF AUTOMATISMS (E.G. CURTAINS AND SHUTTERS) MàTIX AXOLUTE H4671M2 H4678 LIVINGLIGHT LN4671M2 MàTIX AM5851M2 L4678 F411/1N (1 relay - e.g.to control a solenoid valve) -) F411/2 (2 relays - ex. for 230 Vac motors -) F411/4 (4 independent relays with one common clamp) F413N (for electronic ballasts and LED lamps) F414 (for 60 - 1000 VA resistive loads and ferromagnetic transformers) F415 (for 60 - 400 VA Electronic transformers) F416U1 F417U2 BMDI1001 Automation MY HOME 139 General features Actuator devices: selection of the actuators depending on the type of load The table allows identification of the actuator device depending on what it is to be used for, the electrical features of the load to be controlled and the installation features. Warning: Unless otherwise specified in the instruction leaflet, a 10 A thermal magnetic protection must be fitted on the power line to the actuators. Table of the loads Actuators Modules Power supply of the device Controllable loads Incandescent and halogen lamps LED lamps Linear fluorescent Compact lamps 1) fluorescent lamps - Electronic transformers 3) Ferromagnetic transformers 2) 3) Reducer motor for shutters 4) 2 A cosφ 0.5 460 VA @ 230 Vac 220 VA @ 110 Vac - 3475 3476 Basic BUS SCS 2A 460 W @ 230 Vac 220 W @ 110 Vac 40 W @ 230 Vac 20 W @ 110 Vac 1 lamp maximum F411/1N 2 DIN BUS SCS 10 A 2300 W @ 230 Vac 1100 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 500 W @ 230 Vac 4 A 4 A cosφ 0.5 250 W @ 110 Vac 920 W @ 230 Vac 920 VA @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 440 VA @ 110 Vac - F411/2 2 DIN BUS SCS 6A 1380 W @ 230 Vac 660 W @ 110 Vac 250 W @ 230 Vac 1 A 120 W @ 110 Vac 230 W @ 230 Vac 4 lamps maximum 110 W @ 230 Vac 250 W @ 230 Vac 1 A 2 A cosφ 0.5 120 W @ 110 Vac 230 W @ 230 Vac 460 VA @ 230 Vac 4 lamps maximum 110 W @ 230 Vac 220 VA @ 110 Vac 2A 460 W @ 230 Vac 220 W @ 110 Vac F411/4 2 DIN BUS SCS 2A 460 W @ 230 Vac 220 W @ 110 Vac 70 W @ 230 Vac 0.3 A 35 W @ 110 Vac 70 W @ 230 Vac 2 lamps maximum 35 W @ 110 Vac 70 W @ 230 Vac 0.3 A 35 W @ 110 Vac 70 W @ 230 Vac 2 lamps maximum 35 W @ 110 Vac 2 A cosφ 0.5 460 VA @ 230 Vac 220 VA @ 110 Vac 2A 460 W @ 230 Vac 220 W @ 110 Vac F413N 2 DIN BUS SCS - - - F414 4 DIN BUS SCS F415 4 DIN BUS SCS H/L4671/1 AM5851/1 2 flush BUS SCS mounting 40 W @ 230 Vac 20 W @ 110 Vac 1 lamp maximum 2A 460 W @ 230 Vac 5) 220 W @ 110 Vac 5) MAX. 10 ballast type T5, T8, compact or driver for LED - - 0.25 – 4.3A 60 – 1000 W @ 230 Vac - 50 Hz 0.25 – 3.5A 60 – 800 W @ 230 Vac - 60 Hz - - - 0.25 – 4.3A 60 – 1000 VA @ 230 Vac - 50 Hz 0.25 – 3.5A 60 – 800 VA @ 230 Vac - 60 Hz - - - - 0.25 – 1.7A 60 – 400 VA @ 230 Vac - 50 Hz 6A 1380 W @ 230 Vac 660 W @ 110 Vac 150 W @ 230 Vac 0.65 A 70 W @ 110 Vac 150 W @ 230 Vac 3 lamps maximum 70 W @ 110 Vac 150 W @ 230 Vac 0.65 A 2 A cosφ 0.5 70 W @ 110 Vac 150 W @ 230 Vac 460 VA @ 230 Vac 3 lamps maximum 70 W @ 110 Vac 220 VA @ 110 Vac - H/LN4671M2 2 flush BUS SCS AM5851M2 mounting 2A 460 W @ 230 Vac 220 W @ 110 Vac 70 W @ 230 Vac 0.3 A 35 W @ 110 Vac 70 W @ 230 Vac 2 lamps maximum 35 W @ 110 Vac 70 W @ 230 Vac 0.3 A 35 W @ 110 Vac 70 W @ 230 Vac 2 lamps maximum 35 W @ 110 Vac 2A 460 W @ 230 Vac 220 W @ 110 Vac F411/1NC 2 DIN BUS SCS 10 A 2300 W @ 230 Vac 1100 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 500 W @ 230 Vac 4 A 4 A cosφ 0.5 250 W @ 110 Vac 920 W @ 230 Vac 920 VA @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 440 VA @ 110 Vac - F411/2NC 2 DIN BUS SCS 6A 1380 W @ 230 Vac 660 W @ 110 Vac - - - H/L4678 2 flush BUS SCS mounting 140 MY HOME 0.25 – 1.30 A 60 – 300 W @ 230 Vac - 50/60 Hz - Automation 0.65 A 150 W @ 230 Vac 70 W @ 110 Vac - 2 A cosφ 0.5 460 VA @ 230 Vac 220 VA @ 110 Vac 0.65 A 1 A cosφ 0.5 150 W @ 230 Vac 230 VA @ 230 Vac 70 W @ 110 Vac 110 Vac @ 110 Vac 0.25 – 1.3 A 60–300 VA @ 230 Vac50/60 Hz - - Table of the loads Actuators Modules Power supply of the device Controllable loads Incandescent and halogen lamps LED lamps Linear fluorescent lamps 1) Compact fluorescent lamps Electronic transformers 3) Ferromagnetic transformers 2) 3) Reducer motor for shutters 4) F522 1 DIN BUS SCS 10 A 2300 W @ 230 Vac 1100 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 4 A cosφ 0.5 920 VA @ 230 Vac 440 VA @ 110 Vac - F523 1 DIN BUS SCS 10 A 2300 W @ 230 Vac 1100 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 4 A cosφ 0.5 920 VA @ 230 Vac 440 VA @ 110 Vac - HD/HC/ HS/L/N/ NT4672N 2 flush BUS SCS mounting 10 A 2300 W @ 230 Vac 1100 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 500 W @ 230 Vac 4 A 250 W @ 110 Vac 920 W @ 230 Vac 10 lamps maximum 440 W @ 110 Vac 4 A cosφ 0,5 920 VA @ 230 Vac 440 VA @ 110 Vac - F416U1 6 DIN 100-240 Vac @ 50/60 Hz 4.3 A 40 – 1000 W @ 230 Vac 40 – 500 W @ 110 Vac - - 4.3 A 4.3 A 40 – 1000 W @ 230 Vac 40 – 1000 VA @ 230 Vac 40 – 500W@110Vac 40 – 500 VA @ 110 Vac F417U2 6 DIN 100-240 Vac @ 50/60 Hz 1.7 A 40 – 400 W @ 230 Vac 40 – 200 W @ 110 Vac - 1.7 A 1.7 A 40 – 400 W @ 230 Vac 40 – 400 W @ 230 Vac 40 – 200 W @ 110 Vac 20 – 200 W @ 110 Vac BMDI1001 6 DIN 100-240 Vac @ 50/60 Hz 4.3 A 1000 VA @ 230 Vac 500 VA @ 110 Vac - BMSW1001 4 DIN 100-240 Vac @ 50/60 Hz 16 A 3680 W @ 230 Vac 1760 W @ 110 Vac BMSW1002 4 DIN BMSW1003 6 DIN 4.3 A 1000 VA @ 230 Vac 500 VA @ 110 Vac 4.3 A 1000 VA @ 230 Vac 500 VA @ 110 Vac - - 2.1 A 4.3 A 5A 16 A 500 VA @ 230 Vac 10x(2x36 W) @ 230 Vac 1150 VA @ 230 Vac 3680 VA @ 230 Vac 250 VA @ 110 Vac 5x(2x36 W) @ 110 Vac 550 VA @ 110 Vac 1760 VA @ 110 Vac 16 A 3680 VA @ 230 Vac 1760 VA @ 110 Vac - 100-240 Vac @ 50/60 Hz 16 A 3680 W @ 230 Vac 1760 W @ 110 Vac 2.1 A 4.3 A 5A 16 A 500 VA @ 230 Vac 10x(2x36 W) @ 230 Vac 1150 VA @ 230 Vac 3680 VA @ 230 Vac 250 VA @ 110 Vac 5x(2x36 W) @ 110 Vac 550 VA @ 110 Vac 1760 VA @ 110 Vac 16 A 3680 VA @ 230 Vac 1760 VA @ 110 Vac - 100-240 Vac @ 50/60 Hz 16 A 3680 W @ 230 Vac 1760 W @ 110 Vac 2.1 A 4.3 A 5A 16 A 500 VA @ 230 Vac 10x(2x36 W) @ 230 Vac 1150 VA @ 230 Vac 3680 VA @ 230 Vac 250 VA @ 110 Vac 5x(2x36 W) @ 110 Vac 550 VA @ 110 Vac 1760 VA @ 110 Vac 16 A 3680 VA @ 230 Vac 1760 VA @ 110 Vac - Notes: 1) fluorescent lamps with corrected power factor, energy saving lamps, discharge lamps. 2) it is necessary to consider the efficiency of the transformer in order to calculate the effective power of the actuator load. For instance, if you connect a dimmer to a 100VA ferromagnetic transformer with efficiency 0.8, the effective power of the load will be 125VA. 3) the transformer must be loaded at its rated power and, in any case, never below 90% of that power. It is recommended to use one transformer rather than several transformers in parallel. For instance, it is preferred to use one 250VA transformer with 5 50W spotlights connected rather than 5 50VA transformers in parallel, each with a 50W spotlight. 4) the symbol shown of the actuators refers to a reducer motor for shutters. 5) only compatible with the selected lamps with Ballast 1/10 V. Automation MY HOME 141 GEnErAl fEAturEs interfaces contAct interfAce in din contAct interfAce in BAsic Module Module With this device it is possible to the essential feature of this connect traditional devices to the Bus, device, due to the reduced overall such as switches and pushbuttons, dimensions, is the rear-device thus extending the use of the Bus to installation mode As a result, it is traditional pre-existing systems possible to install the interface in a it is also possible to interface 503E box right behind the traditional thermostats, control devices, humidity devices (e g switch, pushbutton) or detectors, wind detectors etc behind electronic shallow devices (e g controls, detectors) it is also possible to interface thermostats, humidity detectors, wind detectors etc this installation solution simplifies the conversion of traditional electric systems into home DIN module contact interface automation systems, as it makes it possible to keep the existing flush mounted boxes, without the need for masonry work Basic module contact interface External devices 142 MY HOME Automation Prestige switch (reuse of historical devices) Wire Automation extension with ZigBee radio devices the wired automation system controlling the users from positions moving walls and with false ceiling described in the previous pages that cannot be reached by the Bus mounted Bus actuators, the radio can be expanded at any time by wiring the “wireless” connection controls are the ideal solution for extending the wiring or adding new among these devices and the wired installing flexible light points, easy to control devices ones is ensured by a special radio reposition in case of modification in However, this is not always easy interface connected to the Bus the arrangement of the offices, or the to do; in some buildings, either the integration between the two furniture historic and/or valuable buildings, technologies, radio and wired, for more information and for the the extension of the system entails enables therefore the installer to range of control devices see the unavoidable and costly interventions select each time the best solution specific radio system chapter of this on the building work that meets the requirements of guide these problems can be easily the customer, both in terms of resolved using the radio controls functionality, and in relation to the possiBle functions included in the ZigBee radio system homes shutter and rolling shutter range; being battery powered and this solution can also be extended, independent from the system wiring, with some advantages, to new lighting these devices give the possibility of buildings; for example in offices with scenario management Light control automation Radio control for the management of lights Shutter control Power supply SCS/Zigbee gateway TV/SAT 230 Vac TV/SAT Light actuator TV/SAT videocitofonia controllo lan controllo carichi automazione energia IPTV Shutter actuator IPTV TV/SAT termoregolazione IPTV diffusione sonora antifurto termoregolazione videocitofonia controllo lan controllo carichi energia luci tvcc www irrigazione IPTV luci Lights tvcc www irrigazione Radio Remote control for the management of scenarios Shutters Automation MY HOME 143 Configuration General concepts This chapter describes the general Actuator address - concepts for the “physical” and Physical Configuration “virtual” configuration of the MY The address of each actuator is positions (G1, G2 and G3) as they can HOME automation devices. For defined uniquely by assigning the belong to several different groups at each item, the “Technical Sheets” numeric configurators 1 to 9 in the same time. chapter describes the functions that positions A (Room) and PL (Light can be realised depending on the Point inside the Room). Example: The actuator configured with A = 1, PL = 3 configurators used. A maximum of 9 addresses can be and G = 4 is device 3 of room 1 belonging to group 4. defined for each room; a maximum of Actuators: 9 rooms can be defined in a system. address and type of The group of belonging is defined by control inserting a third numeric configurator To understand the addressing logical in the housing identified with G it is useful to define some terms (Group). which will occur frequently in this Some actuators have several G guide. Physical Configuration Room (A) Set of devices belonging to a logical area (in a home, for example, the ROOM 9 living room, the bedroom, etc.). Light Point (PL) Numeric identification of the single actuators inside the Room. A =9 PL = 1 A =9 PL = 2 A =9 PL = 1 A =9 PL = 2 A =9 PL = 2 A =9 PL = 9 Group (G) ROOM... Set of devices also belonging to different rooms but which must be controlled at the same time (e.g. the rolling shutters of the North side of the home, the lighting of the day ROOM 2 1–9 ROOM 1 A =1 PL = 1 A =1 PL = 1 A =1 PL = 2 A =1 PL = 9 A =1 PL = 2 A =0 PL = 9 GROUP 1 1–9 A = GR PL = 1 144 MY HOME Automation 1–9 GROUP 9 area, etc.). A =1 PL = 1 A =9 PL = 9 Actuator address - logical extension Virtual configuration For special applications such as A maximum of 16 addresses can be extended systems in houses or defined for each room(PL=0-15); service/industrial rooms, where the a maximum of 16 rooms can be use of many devices may exceed defined in a system. (A=0 -10). the configuration limits mentioned above, interface F422 can be used, configured in the “logical expansion” mode. This mode can make an extended system made up of several individual systems (see “General rules for installation” section). Virtual configuration ROOM 10 A = 10 PL = 0 A = 10 PL = 1 A = 10 PL = 0 A = 10 PL = 1 A = 10 PL = 1 A = 10 PL = 15 A = 10 PL = 15 ROOM ... ROOM 1 A =0 PL = 1 A =0 PL = 1 A =0 PL = 1 A =0 PL = 15 A =0 PL = 2 A =0 PL = 15 GROUP 1 1 – 15 A =0 PL = 2 GROUP 255 0 – 15 ROOM 0 A = GR PL = 1 1 – 255 Automation MY HOME 145 COnfiGurAtiOn General concepts controls: Address And type of control the control devices also have configurators with graphics which positions A and Pl to define the enable the device to send the control addresses of the devices which with the various ways listed in the receive the control (actuators) table below for these positions there are numeric Mode for addressing the devices using the Physical Configuration Type of conTrol Mode for addressing the devices using the Virtual Configuration Type of conTrol conTrol deVice conTrol deVice configurator socket value of the configurator Configurable address Configuration Point-point A PL 1-9 1-9 Point-point A PL 0-10 0-15 Room A PL AMB 1-9 Room A PL AMB 0-10 Group A PL GR 1-9 Group A PL GR 1-255 General A PL GEN - General A PL GEN - 146 MY HOME Automation exAMples of configurAtion Point-point control Group control if the no 3 control is configured with if the no 7 control is configured identified with G = 1 (thus belonging A = 2 and Pl = 3, this device sends with A = Gr and Pl = 1, this device to group 1) the control to the actuator identified sends the control to the actuator with A = 2 and Pl = 3 poinT-poinT conTrol 2 1 4 3 A = 1 PL = 2 A = 1 PL = 1 groUp conTrols rooM conTrols A = 1 PL = 3 5 A = 2 PL = 1 7 6 A = AMB PL = 1 A = AMB PL = 2 general conTrols 8 A = GR PL = 1 9 A = GR PL = 2 A = GEN PL = – BUS actuators = Point-point control A = 1 PL = 1 G = 1 1 A = 1 PL = 2 G = 1 2 A = 1 PL = 3 G = 2 3 A = 2 PL = 1 G = 2 4 A = 2 PL = 2 G = 1 5 A = 2 PL = 3 G = 1 6 = Group control Automation MY HOME 147 COnfiGurAtiOn Addressing levels for a better understanding of the Example: control for a single load (lamp, fan, rolling shutter, etc.) concepts described in the previous rooM 1 page, the four addressing modes are rooM 2 described below the control devices (senders) can activate the actuators (receivers) with A = 1 PL = 1 the following modes A = 1 PL = 2 A = 1 PL = 3 A = 2 PL = 1 A = 2 PL = 2 A = 2 PL = 3 A = 2 PL = 1 A = 2 PL = 2 A = 2 PL = 3 point-point control TV/SAT TV/SAT Direct control to one actuator IPTV TV/SATIPTV IPTV TV/SAT TV/SAT IPTV IPTV identified by a “room number” and a “light point number” A = 1 PL = 1 A = 1 PL = 2 A = 1 PL = 3 Control device: A = n* Pl = n* Actuator: A = n* Pl = n* rooM control Direct control to all the actuators Example: control for all the lamps of a room identified by the same room number rooM 1 rooM 2 A = 1 PL = 1 A = 1 PL = 2 A = 1 PL = 3 A = 2 PL = 1 A = 2 PL = 2 A = 2 PL = 3 A = 1 PL = 1 A = 1 PL = 2 A = 1 PL = 3 A = 2 PL = 1 A = 2 PL = 2 A = 2 PL = 3 A = AMB PL = 1 n* = any numeric configurator from 1 to 9 148 MY HOME Automation A = AMB PL = 2 Control device: A = AMB Pl = n* Actuator: A = n* Pl = n* group control Direct control to all the actuators which perform particular functions even if they belong to different rooms and are identified by the same “group number” Example: control of all the lamps of a floor, on the North side of the building rooM 1 rooM 2 A = GR PL = 1 A = 1 PL = 1 A = 1 PL = 2 A = 1 PL = 3 A = 2 PL = 1 A = 2 PL = 2 A = 2 PL = 3 A =1 PL = 1 G =1 A =1 PL = 2 G =1 A =1 PL = 3 G =2 A =2 PL = 1 G =2 A =2 PL = 2 G =1 A =2 PL = 3 G =1 A = GR PL = 2 A = AMB PL = 1 Control device: A = Gr Pl = n* Actuator: A = n* Pl = n* A = AMB PL = 2 G = n* Automation MY HOME 149 COnfiGurAtiOn Addressing levels generAl control Direct control to all the system actuators Example: control of all the lamps of the building rooM 1 A = 1 PL = 1 rooM 2 A = 1 PL = 2 A = 1 PL = 3 A = 2 PL = 1 A = 2 PL = 2 A = 2 PL = 3 A = GR PL = 1 A = GR PL = 2 A =1 PL = 1 G =1 A =1 PL = 2 G =1 A =1 PL = 3 G =2 A =2 PL = 1 G =2 A =2 PL = 2 G =1 A = GEN PL = - A = AMB PL = 1 Control device: A = GEn Pl = / Actuator: A = n* 150 MY HOME Automation Pl = n* A = AMB PL = 2 G = n* n* = any numeric configurator from 1 to 9 A =2 PL = 3 G =1 Main operating modes The devices in the automation system The function performed, i.e. what the are flush mounted). The table below can perform different functions, such device must do, is defined by putting lists the various operating modes as a as setting the brightness, switching configurators into the housings function of the configurator and type lamps on/off or opening/closing marked with M of the control devices of key cover used in the device. rolling shutters. and completing the devices with keys and key covers (if the devices Control TABLE Key covers Configurator value (M) Function performed 1 function M M M Cyclical ON-OFF control Repeatedly pressing the relay actuators device key cover, ON and OFF controls will be sent in a cyclical way. M M With dimmer actuators, keep the pushbutton pressed to adjust the load power. M M M M M M M no configurator M M ON M SPE 1√4 M M M 1√4 M SPE 1√8 1√8 M 1√4 M SPE 1√8 1√8 M 1√4 M M SPE configurator ON OFF M 1√8 OFF M ON M 1√8 SLA O/I M configurator OFF M OFF M O/I M PUL M M M configurator PUL M O/I SLA SLA 1√8 M PUL M M SLA M PUL PUL M 2 FUNCTIONS Bistable controlMwith hold (UP-DOWN for rolling shutters) M UL Pressing the key cover (lower or Pupper) sends the UP-DOWN control to the rolling shutter motor. After the control has been sent, press the lower or upper key cover again, to stop the rolling shutter in the required position. M M M M M configurator ON M M M M M SPE M OFF M SPE 1√4 1√4 1√8 1√8 Monostable control (UP-DOWN for rolling shutters) The device sends an UP-DOWN control for a rolling shutter motor as long as the lower or upper key cover is pressed. When the key cover is released, the motor STOPS. M configurator ON M M M SLA M Monostable ON-OFF control (pushbutton) This mode can perform an ON/OFF control similar to the control of a traditional point-point pushbutton, thus intended just for one address. O/I M M 1√8 1√8 OFF control 1√8 1√8 When pressing the corresponding key cover, the device sends the OFF control. M OFF M O/I M OFF M M M ON M 1√8 ON1√4control M 1√8 SPE When pressing the corresponding key cover, the device sends the ON control. M M M ON M M 1√8 1√8 ON 1√8 M 1√8 1√8 ON/OFF control Used with relayMactuators, when the upper key cover is pressed the device sends an ON control; when the lower key cover is pressed the device sends an OFF control.With dimmer actuators, pressing the upper and lower key cover adjusts the load power. SLA M M OFF O/I M 1√8 configurator O/I M PUL M M M O/I SLA Automation MY HOME 151 Configuration Main operating modes Cen operating mode with the CEN configurator in the M AM5831M2, by pressing the T1 This particular mode is used to position. The key (upper or lower) of (upper) and T2 (lower) pushbuttons. manage scenario programmer the control device and the scenario For the correspondence between devices MH200N. to be activated are linked through the control keys and the scenarios to As described in the pages of this the TiMH200 program written to activate see the table: guide, the device can manage create the scenarios and then saving even complex scenarios activated them in the MH200N device. automatically after events in the For example, two independent system or manually by pressing a scenarios can be activated using key of a control device configured the special control H/L4651M2, Type of control Special control H/L4651M2 and AM5831M2 Configuration A=0–9; PL=0–9; M=CEN; LIV1/AUX=0; LIV2=0; SPE=0; I=0 Basic control for 2 independent loads H/L4652/2 and AM5832/2 A1=0–9; PL1=0–9; M1=CEN; A2=0; PL2=0; M2=0 Identification of scenario activation keys T1 T2 T1 T2 Basic control for 3 independent loads H/L4652/3 and AM5832/3 A1=0–9; PL1=0–9; M1=CEN; A2=0; PL2=0; M2=CEN T1 T2 A1=0–9; PL1=0–9; A2=0; PL2=0; A3=0; PL3=0; M=CEN T3 T4 T1 T2 T3 T4 T5 T6 M M M M Main actuator operating modes The actuators can be configured for the following operating modes: M 1√4 M 1√4 ON M SPE M SPE 1√8 1√8 1√8 1√8 M M ACTUATOR TABLE Configurator value (M) M M M 1√4 Function performed M SPE 1√8 1√8 1√8 1√8 Special functions This mode can perform special functions (OFF delayed, STOP timed) on the basis of the type of actuator used (single or double) and the numeric configurator inserted. configurator 1÷4 OFF M SLA M SLA M 1√8 Slave This mode can perform a control with two or more actuators. In practice the actuators with the SLA (Slave) configurator repeat the function performed by another actuator which acts as Master. The actuators must have the same addresses and must be of the same type (either all light actuators or all rolling shutter actuators). configurator SLA O/I M M PUL M PUL SLA PUL The device does not operate with the Room and General controls. configurator PUL M 152 MY HOME PUL Automation Examples of configuration the drawing shows a system for Group control receiving the control (one only, a the management of three lamps Group control 7 marked with A=Gr group or several room actuators) and and three shutters Each actuator is and Pl=1, controls actuators 1 and 2 from the configurators in position identified by three numbers: room marked with G=1 M to define the function (On/Off or number (A), device progressive General control On/DOWn) number (Pl for light actuators and the devices identified A=GEn and Pl1 and Pl2 for shutter actuators) Pl= - (no configurator) send a general control operAting Mode and Group (G) of belonging control to all the actuators, for the the configurator inserted in position defining the Addresses lights and for the shutters, in the M of each control device identifies Point-point control system the operating mode the O/i configurator specifies a lamp Control 1 (A = 1, Pl = 1) controls actuators 1 (A = 1, Pl = 1 and G = 1) NOTE: The actuators which manage the shutters, switching on control which is given in the same way control 2 (A = 1, unlike those for the lights, are configured in the same by pressing the upper key cover (On) Pl = 2) controls actuator 2 (A = 1, way in the two positions PL1 and PL2. and the lower key cover (Off) Room control the control devices are instead the configurators room control 8 (A=AMB, Pl=2) distinguished from the configurators position M instead specify a control controls actuators 4 and 5 marked in positions A and Pl which specify to manage the rolling shutters with A=2 the addresses of the actuators intended for actuators 4, 5 and 6 Pl = 2 and G = 1) etc poinT-poinT conTrol groUp rooM conTrols conTrols 1 2 3 4 A =1 PL = 1 M = O/I A =1 PL = 2 M = O/I A =1 PL = 3 M = O/I A =2 PL = 1 M = M 5 6 A =2 PL = 2 M = M A =3 PL = 1 M = M and M in general conTrols 7 8 9 A = GR PL = 1 M = O/I A = AMB PL = 2 M = M A = GEN PL = – M = O/I 10 A = GEN PL = – M = M BUS actuators 1 2 3 4 5 6 A = 1 PL = 1 G = 1 A = 1 PL = 2 G = 1 A = 1 PL = 3 G = 2 A = 2 PL = 1 G = 1 A = 2 PL = 2 G = 2 A = 3 PL = 1 G = 1 Automation MY HOME 153 GEnErAl rulEs fOr instAllAtiOn Maximum distances and absorptions this chapter outlines the details for for the purpose of the above availability of current according to ensuring a correct realisation of a MY calculations, refer to the tECHniCAl the length of the cable HOME automation system: DAtA shown in the technical sheets When setting up, please observe the selv classification chapter following rules: Maximum distances and When calculating the absorptions, it is also necessary to consider the absorptions Maximum number of devices which can be configured selV clAssificAtion the automation system is sElV 1 The connection between the power supply and the furthest away device must not be longer than 250m. Power supply Device Junction box (safety Extra low Voltage) classified due to the fact that it is powered using double safety insulation independent devices, not connected to the earth, and with maximum operating voltage of 27 Vdc, nonundulated, in accordance with CEi En 600065 it is therefore comparable to a sElV source as described in point 411 125 of CEi 64-8-4 the conformity to sElV classification is only guaranteed subject to full compliance with current installation regulations, and with the general rules for installation for each single 2 The total length of the connections must not be more than 500 metres (extended cable). device and cable making up the system recommended by Bticino MAxiMuM distAnces of the Bus cABle And ABsorptions the maximum number of devices that can be connected to the Bus depends on their total absorption and on the distance between the connection point and the power supply the power supply unit can deliver up to 1200 mA or 600 mA; ihence, the maximum number of devices will be determined by the sum of the absorptions of the single devices you need to install 154 MY HOME Automation Power supply Device Junction box 3 For optimum division of the currents on the BUS line power supply should be positioned in the middle. ON ON OFF OFF A A PRI E49 PRI: 220 – 240 V~ 185 – 175 mA 50/60 Hz SCS: 27 Vdc 600 mA B E46ADCN B SCS E49 1 1 2 2 C1 3 3 4 C2 4 5 1 5 1 C3 C4 2 2 C1 3 3 4 C2 4 5 5 C3 C4 With Power supply E46ADCn: With Power supply E49: A = 250 m max A = 250 m max B = 250 m max B = 250 m max A + B = 500 m Maximum current supplied from the power supply 1200 mA A + B = 500 m Maximum current supplied from the power supply 600 mA NOTE: If a UTP5 cable is used instead of a BUS L4669 cable, distances must halved. Automation MY HOME 155 GEnErAl rulEs fOr instAllAtiOn Maximum distances and absorptions MAxiMuM distAnces for the connection of ActuAtors Example of connection with F411/1N depending on the loAd N in order to manage some types of L loads correctly, it is necessary to observe the installation specifications for all actuators used fluorescent lamps: the length of the connecting cable between the 1 2 3 F411/1N 1 3 2 L N MIN 3 m C1 actuator and the load must not be less than 3m Do not connect more than 15 actuators controlling this type of lamp on the same line Metallic iodide and sodium- Warning: Refer to the technical data shown on the technical sheets for each actuator vapor lamps: in addition to the indications given for the fluorescent lamps, please pay attention to the operating instructions of these lamps (for example, avoid switching on when hot), do not connect dimmers to the same line of these lamps, keep the bus line and the power line of these lamps separated from each other (at least 1 metre) three-phase networks: when using three-phase networks, check the balance of the phases as well as Maximum distances for connecting the contact interface 50 m the quality of the network non-compliance of the above regulations may affect proper A PL1 PL2 M SPE operation of the devices PL1 MAxiMuM distAnce for interfAce interface (basic or Din module) and the traditional type device must not exceed 50 metres in length several pushbuttons may be connected to the interface inputs 156 MY HOME Automation C Prestige switch (reuse of historical devices) connecting the contAct the connection between the PL2 BUS ABSORPTIONs, SIZE AND DISSIPATIONS Item Description 3475 3476 3477 E46ADCN actuator control actuator contact interface power supply E49 F411/1N 1) F411/2 1) mini power supply 1-relay actuator 2-relay actuator F411/4 1) 4-relay actuator F412 1) F413N 1) F414 1-relay NC/NA actuator output 1 to 10 for ballast DIN dimmer F415 F522 F523 F420 F422 DIN dimmer actuator 16A with current sensor actuator 16A scenario module SCS/SCS interface F425 F426 F427 F428 F429 H/L4651M2 AM5831M2 memory module SCS/EIB interface OPEN KNX interface contact interface SCS/DALI interface special control H/L4652/2 AM5832/2 H/L4652/3 AM5832/3 H/L4671/1 AM5851/1 H/LN4671M2 AM5851M2 H/L4678 H/L4684 HD/HC/HS/L/N/NT4575SB HD/HC/HS/L/N/NT4607 HD/HC/HS/L/N/NT4607/4 HD/HC/HS/L/N/NT4610 HD/HC/HS/L/N/NT4611 HD/HC/HS/L/N/NT4672N HD/HC/HS/L/N/NT4680 BMSE1001 BMSE2001 BMSE2002 BMSE2003 BMSE2004 BMSE2005 F416U1 F417U2 BMDI1001 BMSW1001 BMSW1002 BMSW1003 control for 2 actuators control for 3 actuators 1-relay actuator control/actuator flush-mounting dimmer colour Touch Screen SB receiving radio interface protected control protected scenario control fixed IR detector swivel IR detector 16 A flush mounted 2 module actuator scenario control passive infrared ceiling sensor wide band wall/ceiling sensor narrow band wall/ceiling sensor two-way narrow band wall/ceiling sensor one-way narrow band wall/ceiling sensor double technology band wall/ceiling sensor dimmer actuator1000W TC dimmer actuator1000W 2x400 W TC dimmer actuator1000W 1/10 V 1-relay 230 Vac actuator 2-relay 230 Vac actuator 4-relay 230 Vac actuator Absorption from Bus (power supply 27 Vcc) 13 mA 13 mA 3.5 mA 22 mA 28 mA (single loads) 15.5 mA (interlock) 40 mA (single loads) 22 mA (interlock) 20 mA 30 mA 9 mA 9 mA 30 mA 10 mA 20 mA IN: 25 mA OUT: 2mA 5 mA 30 mA 9 mA 5 mA 6 mA for H4651M2 8.5 mA for L4651M2 and AM5831M2 9 mA 9 mA 16.5 mA 14 mA 9 mA 80 mA 33 mA 15 mA 12 mA 4.5 mA 4.5 mA 10 mA 9 mA 10 mA 12 mA 12 mA 12 mA 12 mA 17 mA 5 mA 5 mA 5 mA 5 mA 5 mA 5 mA Size Dissipation Dissipated power Max. load with max. load Basic module Basic module Basic module 8 DIN modules 2 DIN modules 2 DIN modules 2 DIN modules 11 W 6W 5.3 W 1.5 W 1.7 W 2 DIN modules 3.2 W 2 DIN modules 2 DIN modules 4 DIN modules 1.5 W 0.5 W 11W 5W 11 W 4 DIN modules 1 DIN module 1 DIN module 2 DIN modules 2 DIN modules 1.2 A 0.5 A 1000W 500W 400W 0.6 W 1W 2 DIN modules 6 DIN modules 6 DIN modules 2 DIN modules 6 DIN modules 2 flush-mounting mod. 2 flush-mounting mod. 3 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 3+3 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. 2 flush-mounting mod. l=75/p=40/h=20 l=115.86/p=69.6/h=91 l=115.86/p=69.6/h=92 l=115.86/p=69.6/h=93 l=115.86/p=69.6/h=94 l=115.86/p=69.6/h=95 6 DIN modules 6 DIN modules 6 DIN modules 4 DIN modules 4 DIN modules 6 DIN modules 0.1 W 0.2 W 0.9 W 3W 300 W 8W 8W 1000 W 2 X 400 W 1.2 W 1.7 W 2.8 W NOTE: 1) the power dissipated indicated is that corresponding to the device with all the relays loaded at the load maximum. If the load is less the dissipated power is less and may be calculated by means of the following formula: P[mW]=140+400*N+10*[I12+I22+...IN2] P: dissipated power in mW, N: no. of loaded relays IN: load current corresponding to the N relay. Install the items with greater dissipated power (in special power supplies and dimmers) in lower positions in the switchboard for easier heat dissipation. Do not place devices which dissipate a power greater than 5W side by side, but leave an empty module between them. Automation MY HOME 157 General rules for installation Maximum distances and absorptions If the absorption of the whole system PHYSICAL EXPANSION MODE Positions I3 and I4 shall be configured is less than 600 mA, the E49 compact Limit systems shall be applied to according to the configuration of power supply can be used. If the each bus in terms of absorption and the Automation devices in the two absorption is between 600 and 1200 maximum wiring distance, as shown systems connected to each other. mA, use the E46ADCN power supply. in the previous page. Therefore, it With reference to the picture, let us For extended systems with current is not possible to supply a system suppose, for example, that I3=2, I4=7: absorption over 1200 mA or 600 consisting of two or more buses with on the input bus (IN), the addresses mA powered by power supplies only one power supply unit E46ADCN of Automation devices No. 1 must E46ADCN and E49, it will be or E49, connected to each other by be between A=1 / PL=1 and A=2 / necessary to split the system into interfaces configured in “physical PL=6; several lines, each powered by its expansion” mode even if the number own power supply and connected and type of components connected addresses of Automation devices to each other using interface F422 to the system do not exceed the set No. 2 must be between A=2 / configured in “Physical expansion” maximum absorption (1200 mA). PL=8 to the address of the next on the output bus (OUT), the interface. mode. A/PL = 28 53 230 Vac F422 OUT OUT F422 OUT F422 I1 = – I2 = – I3 = 2 I4 = 7 MOD = 1 F422 C C IN IN IN 230 Vac 230 Vac A/PL = 11 26 158 MY HOME I1 = – I2 = – I3 = 5 I4 = 4 MOD = 1 Automation A/PL = 55 99 Installation rules When setting up the system, consider It is possible to use up to 4 the following recommendations: interfaces in series, which divide The buses, connected to the the system into 5 separate interface input and output, must be supplied with their own power sections. The F420 scenario module, the supply unit; additionally, the F425 memory module, and the system limits apply for each of devices that can be configured them, in terms of absorption and using the self-learning mode must maximum distance. be installed on the bus section Therefore, it is not possible to corresponding to their own supply a system consisting of local address. For example if the two or more buses with only one scenario module is configured power supply unit (E46ADCN or as A=0 (no configurator), PL=1, it E49) connected to each other will have to be placed on section by various interfaces configured 1 of the system. The energy in physical expansion mode management system central unit even if the number and type of F421 and the control panel N4682 components connected to the must be installed on the BUS with system do not exceed the set the highest addresses (system no. maximum absorption (1200 mA). 3 in the example). It is not possible to connect two interfaces in parallel to the same BUS Automation MY HOME 159 GEnErAl rulEs fOr instAllAtiOn Maximum number of devices which can be configured physicAlly configured single systeM A single system can manage up to 9 points (Pl), for a total of 81 addresses it is also possible to have several rooms (A) for each room, it will then to these addresses, any inclusion in devices with the same address be possible to manage up to 9 light one or more groups must be added A PL1 PL2 M SPE Power supply Shutter control Dimmer control 3 31 81 addresses MaX. Basic contact interface ON ON OFF OFF ART. 3477 PL1 PL2 C BUS cable 230 Vac DIN dimmer L 3 31 A PL1 PL2 M SPE ART. 3477 Flush-mounting actuator T5H 250V Basic actuator 0245 06 F414 50Hz 230V~ 60 1000V A ¤ A PL M G PL1 PL2 C VirtuAlly configured single systeM light points (Pl=0-15), for a total of rooms (A=0-10) for each room it will 175 addresses (the address A=0, Pl=0 then be possible to manage up to 16 is not permitted) Basic contact interface A PL1 PL2 M SPE Power supply Shutter control 3 31 175 addresses MaX. A single system can manage up to 11 Dimmer control 230 Vac Web server ON ON OFF OFF Extra power supply ART. 3477 PL1 PL2 C F453 Ethernet cross-over cable 230 Vac 3 31 A PL1 PL2 M SPE ART. 3477 Flush-mounting actuator T5H 250V Basic actuator 0245 06 F414 50Hz 230V~ 60 1000V A ¤ A PL M G PL1 PL2 Automation C 2 1 PRI: 220 – 240 V~ 175 – 165 mA 47/63 Hz SCS: 27 Vdc 600 mA BUS cable DIN dimmer L 160 MY HOME 1 Pc logical expansion of the addresses VirtuAlly configured extended systeM with one f422 interfAce in larger homes, or in the service using interface f422 configured in sector, there might be the need for the “logic expansion” mode: with Automation systems with a higher configurator n0 2 in position M, and number of functions than the above no 1 in i4 in this case, it is possible to create Power supply Basic contact interface A PL1 PL2 M SPE Shutter control 3 31 Fan control Dimmer control ON ON ON OFF OFF OFF Shutter control ART. 3477 PL1 PL2 C 230 Vac DIN actuator Power supply 0245 06 A PL1 PL2 M SPE 3 31 A PL1 PL2 M SPE 1 1 3 2 2 L N 3 AR T.F470/2 F414 50Hz 230V~ ART. 3477 60 1000V A ART. 3477 ¤ Interface F422 A PL M G PL1 PL2 C Flush-mounting actuator Basic actuator Basic contact interface Shutter control 3 31 A PL1 PL2 M SPE PL1 PL2 C Basic actuator DIN dimmer Dimmer control Fan control ON ON ON OFF OFF OFF I1 I2 I3 I4 M Shutter control =– =– =– =1 =2 ART. 3477 PL1 PL2 OUT OUT AR T.F422 IN C 230 Vac L 1 AUTOMATION SYSTEM NO. 1 (MAIN RISER) A PL1 PL2 M SPE 3 2 2 L N 3 AR T.F470/2 DIN actuator 3 31 T5H 250V 1 0245 06 3 31 A PL1 PL2 M SPE F414 50Hz 230V~ ART. 3477 60 1000V A ART. 3477 ¤ A PL M G PL1 PL2 Basic actuator C PL1 PL2 Flush-mounting actuator C DIN dimmer Basic actuator Web server 230 Vac Extra power supply Pc ETHERNET 174 addresses MaX. AUTOMATION SYSTEM NO. 2 (Local BUS) 3 31 T5H 250V L 349 addresses MaX. 175 addresses MaX. an extended Automation system PRI: 220 – 240 V~ 175 – 165 mA 47/63 Hz SCS: 27 Vdc 600 mA SCS AI SCS AV Ethernet Cross-over Cable Automation MY HOME 161 GEnErAl rulEs fOr instAllAtiOn logical expansion of the addresses VirtuAlly configured If you need to control and execute the centralised extended systeM with management of the system with Web Server, seVerAl f422 interfAces Touch screen and Energy Management Control if three or more systems (up to a Unit, these devices will have to be installed in the maximum of 9) must be combined, main riser. these must be connected by means of interfaces f422 with a common Main riser 166 addresses MaX. call “riser”, on which the control, LOCAL BUS activation and management (for 174 addresses MaX. Automation system No. 1 174 addresses MaX. bus, which from now on we will Automation system No. 2 example touch screen) devices can also be installed because they belong to the Automation system the riser cannot be made, for example, with a Burglar-alarm or 2 wire Video door I1 = I2 = I3 = I4 = M= – – – 1 2 OUT OUT ART.F422 Interface F422 IN entry system the f422 interfaces LOCAL BUS “logic expansion” mode, connecting configurator no 2 to the M position and configuring the address of position i4 with configurators from 1 to 9, as per the following diagram for each of the 9 systems there will be 174 configuration addresses address, as well as 166 addresses on the riser, for a total of 1732 addresses Warnings: = = = = = – – – 2 2 OUT OUT ART.F422 Interface F422 IN LOCAL BUS 174 addresses MaX. available, excluding the interface I1 I2 I3 I4 M Automation system No. 3 I1 I2 I3 I4 M = = = = = – – – 3 2 OUT OUT ART.F422 Interface F422 IN In the main riser it is possible to install control devices configured to send GROUP or GENERAL the single systems and in the same main riser. POINT-POINT controls generated inside each single system and on the main riser can reach the actuators situated in the whole system only if they are sent from the appropriately configured 174 addresses MaX. controls to some or all of the actuators situated in LOCAL BUS Automation system No. 4 I1 I2 I3 I4 M situated on the main riser or on one of the single 162 MY HOME Automation – – – 4 2 OUT OUT ART.F422 Interface F422 IN SPECIAL control device H/L4651M2, AM5831M2 systems (max 9) connected. = = = = = Automation system No. 9 addresses MaX.: 174x9+166 (Main riser) = 1732 are configured for operation in extended systeM with interfAce f422 And weB serVer special systems for which the using one or more Web servers f454 case the extended system is made up availability of more than 1739 and a lAn network which forms the of two or more systems for each of addresses is required can be made connection infrastructure which a maximum of 1739 addresses referring to the picture below, in this can be configured the centralised control of the functions is obtained through Personal Computer, LOCAL BUS Main riser OUT Control ART.F422 LOCAL BUS connecting directly to the Web server OUT Interface F422 IN fixed iP address and working on Web pages with preconfigured icons Automation system No. 2 OUT ART.F422 1 2 3 4 ART. F411/2 C1 C2 OUT Interface F422 IN Web Server F454 ETHERNET 1739 addresses MaX. Automation system No. 1 SYSTEM 1 SCS AI SCS AV BUS PC LOCAL BUS Main riser OUT Control ART.F422 OUT Interface F422 IN LOCAL BUS Automation system No. 2 OUT ART.F422 1 2 3 4 ART. F411/2 C1 C2 OUT Interface F422 IN Web Server F454 ETHERNET 1739 addresses MaX. Automation system No. 1 SYSTEM 2 SCS AI LAN network SCS AV BUS LOCAL BUS Control ART.F422 OUT Interface F422 IN Main riser LOCAL BUS Automation system No. 2 OUT ART.F422 1 2 3 4 ART. F411/2 C1 SYSTEM 3 OUT C2 OUT Interface F422 IN Web Server F454 ETHERNET 1739 addresses MaX. Automation system No. 1 SCS AI SCS AV BUS Automation MY HOME 163 Wiring diagrams Lighting management Diagram 1 SWITCHING ON/OFF OF 2 LAMPS FROM 4 LIGHT POINTS WITH GENERAL ON/OFF CONTROL 230 Vac N L L4671/1 ON E46ADCN OFF A PL M G1 G2 = = = = = L1 1 1 O/I – – L4671/1 ON OFF A PL M G1 G2 = = = = = BUS 230 Vac L4652/2 GEN BUS L4652/2 A = GEN PL1 = – M = O/I ON L2 1 2 O/I – – OFF ON ON OFF OFF A PL1 M1 A2 PL2 M = = = = = = To other devices 1 1 O/I 1 2 O/I Diagram 2 automatic switching on of the light with passive infrared ceiling sensor N L 3475 E46ADCN L L1 1 1 230 Vac ART. 3475 230V ˜ 2A cosϕ = 0,6 2A A PL M G = = = = 1 1 – – 230 Vac BUS BMSE1001 A PL M S T = = = = = 1 1 – 1 6 L4652/2 A1 = 1 PL1 = 1 M1 = O/I ON To other devices For other functions OFF The device controls the load with the address indicated in A and PL. When a movement is detected, if the lighting level is lower than the set level, the device switches the assigned load on, and keeps it on until the time set with the configurator connected to T expires. The PIR movement sensor sensitivity is set with the configurator connected to S. For correct operation the sensor Lighting set point must be defined (see procedure). If the user switches the light off manually with a control device, the movement sensor is disabled until a presence is detected, for a time set in T. 164 MY HOME Automation diAgrAM 3 switching on And off of one lAMp And rolling shutter control using An ActuAtor control 230 Vac N L L1 A1 PL1 M1 A2 PL2 M2 E46ADCN = = = = = = 1 1 1 2 O/I N A PL M G1 G2 M L2 = = = = = L2 1 2 O/I – – ON OFF L4671/1 L4671M2(*) 230 Vac BUS To other devices *Complete the device with key covers as per the drawing: ON Shutter control Light control OFF diAgrAM 4 wire systeM extension with rAdio control to MAnAge two lAMps 230 V ac N L F411/1N E46ADCN 1 2 3 F411/1N C1 A PL M G1 G2 G3 = = = = = = 1 1 – – – – F411/1N L1 1 2 3 F411/1N C1 A PL M G1 G2 G3 = = = = = = 1 2 – – – – L2 To other devices of the Wire Automation system 230 Vac L4578 (*) L4597N A = 9 PL = 8 M = – A =1 PL1 = 1 PL2 = 2 Note: Replacing actuator F411/1N with actuator dimmer F414 and F414/127 the lamp brightness can be adjusted as well Note (*): assign an address not used for other Automation devices. The interface can manage up to 36 radio control devices. Automation MY HOME 165 Wiring diagrams Management of different loads Diagram 5 SWITCHING-ON control for bathroom light and fan with delayed SWITCHING-OFF 230 Vac N L M Bathroom light F411/1N 1 2 3 F411/1N E46ADCN C1 A PL M G1 G2 G3 = = = = = = F411/1N 3 1 2 – – – 1 2 3 F411/1N C1 A PL M G1 G2 G3 = = = = = = Bathroom fan 3 1 SLA – – – 230 Vac BUS L4652/2 The ON control turns on the light and the fan at the same time. The OFF control turns off the light whereas the fan turns off after 2 minutes (configurator in M=2 of the Master actuator) To other devices A = 3 PL = 1 M = O/I ON OFF Diagram 6 motor control in direct current for motorised curtains (example 24 V d.c.) 24 Vdc M + + F411/2 1 2 3 4 ART. F411/2 C1 E46ADCN A PL1 PL2 G M = = = = = 3 1 1 – – C2 F411/2 1 2 3 4 ART. F411/2 C1 A PL1 PL2 G M = = = = = 3 1 1 – SLA C2 230 Vac BUS 230 Vac To other devices L4652/2 It is possible to use direct current motors with other features (12 - 24 - 48 V d.c.) by replacing the compatible power supply unit with the features of the motor (voltage and current), thus verifying the absorptions of the motor with the actuator relay capacity (F411/2). 166 MY HOME Automation A = 3 PL = 1 M = For other functions Window and shutter management Diagram 7 motor control in alternated current for rolling shutters, curtains or motorised shutters 230 Vac N N L L1-N = clockwise rotation L2-N = anticlockwise rotation M1 L1 F411/2 M = AC motor with 2 windings 1 2 3 4 ART. F411/2 E46ADCN C1 A PL1 PL2 G M = = = = = N L2 M2 L1 F411/2 2 1 1 – – 1 2 3 4 ART. F411/2 C2 C1 A PL1 PL2 G M = = = = = 2 2 2 – – N L2 L1 F411/2 1 2 3 4 ART. F411/2 C2 C1 230 Vac M3 A PL1 PL2 G M = = = = = L2 2 3 3 – – C2 BUS L4652/3 A PL1 A2 PL2 A3 PL3 M = = = = = = = 2 1 2 2 2 3 To other devices L4652/2 GEN A = GEN PL = – M = Diagram 8 motor control in alternated current for opening/closing motorised shutters M1 230 Vac N L Ap C ˜ M2 Ch Ap C F411/4 1 2 3 4 5 E46ADCN ART. F411/4 C1 C2 C3 C4 ˜ Ch A PL1 PL2 PL3 PL4 M = = = = = = 2 1 1 1 1 1 230 Vac M1 = motor controlling the internal rabbet shutter M2 = motor controlling the external rabbet shutter PL1 and PL2 = contacts: must be interlocked to each other and must always be fitted to the internal rabbet shutter PL3 and PL4 = contacts: must be interlocked to each other and must always be fitted to the external rabbet shutter BUS L4652/2 To other devices For other functions A = 2 PL = 1 M = Automation MY HOME 167 Wiring diagrams Management of dimmer lamps Diagram 9 SWITCHING ON AND OFF AND brightness ADJUSTMENT OF fluorescent lamps By means of the “ballast” N N L L 230 Vac + F413 Ballast A PL1 M G 1 2 NC 3 4 - + 0-10V N L - + = = = = 2 1 – – ART. F413N C1 E46ADCN 230 Vac To other devices BUS L4652/2 A1 = 2 PL1 = 1 M1 = O/I For other functions ON OFF Diagram 10 SWITCHING ON AND OFF AND brightness ADJUSTMENT OF incandescence lamps, halogen and ferromagnetic transformers N L DIN dimmer actuator E46ADCN Incandescence lamps, halogen and ferromagnetic transformer L T5H 250V 230 Vac 0245 06 F414 230V~ 50Hz ¤ 60 1000VA A PL M G 230 Vac A PL M G = = = = 1 2 – – To other devices BUS L4652/2 A1 = 1 PL1 = 2 M1 = O/I 168 MY HOME Automation ON OFF For other functions Lighting and shutter management Diagram 11 LIGHTING AND SHUTTER MANAGEMENT SYSTEM – 100 M2 HOME The following pages give a Functions performed by the system: description of an Automation Light general control. system used for lighting and Shutters general control. shutter management in a home of Control of light points in each approximately 100 m2, consisting of living room, kitchen, two bedrooms Dimmer light control point in the living room and the bedrooms. room. Central control using the Touch Screen installed in the living room. Recalling of scenarios with Local Control of shutters in each room. Display in the two bedrooms. and two bathrooms. Distribution components in the single rooms Hall Corridor KITCHEN LIVING ROOM BATHROOM 1 ROOM 1 ROOM 2 ITEM 1 lighting general control (1) 1 shutter general control (2) 1 ceiling light point controlled by flush mounted actuator (3) 1 control (4) for the corridor light point 2 ceiling light points controlled by flush mounted actuator and 8 other points (4 - 6 - 7 - 9 - 13 - 22 - 28) 1 ceiling light point controlled from one point (7) and by a 1 relay actuator in the DIN module (*) 1 motorised shutter controlled from 1 point (8) and by a 2 relay actuator in the DIN module (*) 1 wall light point controlled from 1 point (11) with light intensity adjustment and by 1 dimmer actuator in DIN module (*) 1 ceiling light point controlled from two points (9 - 11) and by a 1 relay actuator in the DIN module (*) 1 motorised shutter controlled from 1 point (10) and by a 2 relay actuator in the DIN module (*) 1 Touch Screen (12) 1 ceiling light point controlled from one point (13) and by a 1 relay actuator in the DIN module (*) 1 motorised shutter controlled from 1 point (14) and by a 2 relay actuator in the DIN module (*) 1 ceiling light point controlled from 3 points (16 - 17 - 18) with light intensity adjustment and by 1 dimmer actuator in DIN module (*) 1 motorised shutter controlled from 1 point (15) and by a 2 relay actuator in the DIN module (*) 1 wall light point controlled from 1 point (17) 1 wall light point controlled from 1 point (18) and by a 2 relay actuator in the DIN module (*) 1 control (20) for the Corridor Light Point 1 Local Display (19) 1 ceiling light point controlled from 3 points (22 - 23 - 24) with light intensity adjustment and by 1 dimmer actuator in DIN module (*) 1 motorised shutter controlled from 1 point (21) and by a 2 relay actuator in the DIN module (*) 1 wall light point controlled from 1 point (23) 1 wall light point controlled from 1 point (24) and by a 2 relay actuator in the DIN module (*) 1 control (26) for the Corridor Light Point 1 Local Display (25) H4652/2 H4652/2 H4671/1 H4652/2 H4671/1 H4652/2 F411/1N H4652/2 F411/2 H4652/2 F415 H4652/2 F411/1N H4652/2 F411/2 H4890 H4652/2 F411/1N H4652/2 F411/2 H4652/2 F415 H4652/2 F411/2 H4652/2 H4652/2 F411/2 H4652/2 HS4891 H4652/2 F415 H4652/2 F411/2 H4652/2 H4652/2 F411/2 H4652/2 HC4685 NOTE: All the controls must be completed with support, cover plate and key covers for the desired civil series. These can be found in the BTicino General Installation catalogue. For this specific example products of the AXOLUTE civil series have been used. NOTE (*): All the actuators in DIN module are installed on the 54 module home automation panel in the hall. Home automation panel DIN MODULES 1 SCS power supply 12 DIN actuators 8 24 Home automation panel DIN MODULES 3 DIN dimmer 1 scenario module 12 2 Total 46 Automation MY HOME 169 WirinG DiAGrAMs lighting and shutter management HALL CORRIDOR KITCHEN L N F420 F411/1N A1 = – PL = 1 E46ADCN H4671/1 A1 = 1 PL = 1 M1 = O/I ON ART.F420 H4671/1 OFF ON OFF A = 3 PL = 1 ART.F411/1 A1 = 2 PL = 1 M1 = O/I 5 3 230 Vac H4652/2 ON GEN H4652/2 A1 = GEN M = O/I H4652/2 A = GEN M = OFF OFF 1 2 H4652/2 A1 = 2 PL1 = 1 M = O/I ON ON OFF 4 H4652/2 A1 = 2 PL1 = 1 M = O/I 6 ON ON OFF OFF A1 PL1 M1 A2 PL2 M2 7 = = = = = = ROOM 2 L N M F415 L ART.F415 F411/2 A = 8 PL = 1 1 2 3 4 1 2 3 4 ART.F411/2 H4652/2 ON OFF 26 H4652/2 A = 2 PL1 = 1 M = O/I 25 A = PL1 = M = FUN = H4652/2 – 1 4 1 NOTE: for the configuration of bathroom 2 refer to bathroom 1, configuring for all the devices room A=6 170 MY HOME Automation ON OFF 24 ON OFF A1 PL1 M1 A2 PL2 M2 F411/2 A = 8 PL1 = 2 PL2 = 3 1 2 3 4 1 2 3 4 ART.F411/2 H4652/2 = = = = = = 8 3 O/I 8 1 O/I ON OFF 23 ON OFF A1 PL1 M1 A2 PL2 M2 A = 8 PL1 = 4 PL2 = 4 H4652/2 = = = = = = 8 2 O/I 8 1 O/I ON OFF 22 H4652/2 A = 8 PL1 = 1 M1 = O/I A = 8 PL1 = 4 M1 = 21 3 1 O/I 2 1 O/I KITCHEN LIVING ROOM BATHROOM L N M M F411/2 1 2 3 4 1 2 3 4 ART.F411/2 F411/1N A = 3 PL1 = 2 PL2 = 2 ART.F411/1 H4652/2 F415 A = 4 PL = 1 ART.F415 H4652/2 A1 = 3 PL1 = 2 M = 8 ON ON OFF OFF A1 PL1 M1 A2 PL2 M2 9 F411/2 A = 4 PL = 2 L 4 1 O/I 2 1 O/I 1 2 3 4 ART.F411/2 A1 PL1 M1 A2 PL2 M2 ON ON OFF OFF 11 10 ART.F411/1 H4890 H4652/2 A1 = 4 PL1 = 3 M = F411/1N A = 4 PL1 = 3 PL2 = 3 1 2 3 4 H4652/2 = = = = = = M = = = = = = 4 2 O/I 4 1 O/I F411/2 A = 5 PL = 1 1 2 3 4 1 2 3 4 ART.F411/2 H4652/2 ON ON OFF OFF 13 12 A1 PL1 M1 A2 PL2 M2 A = 5 PL1 = 2 PL2 = 2 H4652/2 = = = = = = 5 1 O/I 2 1 O/I A1 = 5 PL1 = 2 M = 14 ROOM 1 L N M F415 F411/2 A = 7 PL = 1 L ART.F415 1 2 3 4 ART.F411/2 H4652/2 ON OFF 20 HS4891 A1 = 2 PL1 = 1 M = O/I 19 A = PL1 = M = FUN = F411/2 A = 7 PL1 = 2 PL2 = 3 1 2 3 4 H4652/2 – 1 4 1 ON OFF 18 ON OFF A1 PL1 M1 A2 PL2 M2 1 2 3 4 1 2 3 4 ART.F411/2 H4652/2 = = = = = = 7 3 O/I 7 1 O/I ON ON OFF 17 OFF A1 PL1 M1 A2 PL2 M2 A = 7 PL1 = 4 PL2 = 4 H4652/2 = = = = = = 7 2 O/I 7 1 O/I ON OFF 16 H4652/2 A = 7 PL1 = 4 M1 = A = 7 PL1 = 1 M1 = O/I 15 Automation MY HOME 171