Installation

advertisement
DC Outdoor Power Supply/Chargers
Installation Guide
Models Include:
WayPoint-3
- 2.5 amp @ 12VDC or 24VDC.
- 115/230VAC input.
WayPoint-5
- 4 amp @ 12VDC or 24VDC.
- 115/230VAC input.
WayPoint-7
- 6 amp @ 12VDC or 24VDC.
- 115VAC input.
WayPoint-7V
- 6 amp @ 12VDC or 24VDC.
- 230VAC input.
Rev. 080911DCPL
More than just power.™
Overview:
These Altronix High Current Outdoor Power Supply/Chargers provide 12VDC or 24VDC and are designed to be
conveniently located where power is required.
WayPoint-3
2.5 amp
WayPoint-5
4 amp
WayPoint-7
6 amp
WayPoint-7V 6 amp
12VDC or 24VDC
12VDC or 24VDC
12VDC or 24VDC
12VDC or 24VDC
SW1
CLOSED
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
OPEN
11
5V
In AC
pu /6
t C 0H
ur z
ren
23
tD
0V
raw
In AC
pu /5
t C 0H
ur z
ren
tD
raw
24
VD
C
C
VD
12
Altronix
Model
Number
To
ta
(P l ­O
ow ut
er) put
Cu
­Ou
rre
tp
nt
ut
Vo
lta
ge
WayPoint DC Reference Chart:
0.95 amp 0.6 amp
0.95 amp 0.6 amp
1.9 amp
N/A
N/A
0.95
Specifications:
• CE Compliant (except WayPoint-7/7V).
• AC and DC power LED indicators.
• Ease of installation saves time and
eliminates costly labor.
• Includes battery leads.
• NEMA 4/4X, IP66-11 Rated Outdoor Enclosure.
• Operating Ambient Temperature: -20º C to 50º C.
Enclosure Dimensions (H x W x D):
13.31” (338.074mm) x 11.31” (287.274mm) x
5.59” (141.986mm)
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction.
1. Remove back plane from enclosure prior to mounting (do not discard hardware).
2. Mark and drill desired inlets on the enclosure to facilitate wiring (Fig. 1, pg. 3).
3. Mount unit in desired location. Mark and drill holes to line up with the top and bottom holes of the enclosure flange.
Secure enclosure with appropriate fasteners (Fig. 5 & 5a, pg. 7 and Fig. 6, pg. 8).
4. Mount back plane to enclosure with hardware.
5. Set power switch to the OFF position (Fig. 2b, pg. 4, Fig. 3b, pg. 5, Fig. 4b, pg. 6).
6. Connect AC power (115VAC) to terminals marked [L & N], connect ground to terminal
marked [G] (Fig. 2-4, pgs. 4-6). Use 18 AWG or larger for all power connections (Battery, DC output).
7. Select the desired DC output voltage by setting SW1 to the appropriate position (Reference Chart above)
(Fig. 2a, pg. 4, Fig. 3a, pg. 5, Fig. 4a, pg. 6).
8. Set power switch to the ON position (Fig. 2b, pg. 4, Fig. 3b, pg. 5, Fig. 4b, pg. 6).
9. Measure output voltage at terminals marked [--- DC +] before connecting devices (Fig. 2c, pg. 4, Fig. 3c, pg. 5,
Fig. 4c, pg. 6). This helps avoid potential damage.
Note: Power supplies mounted in weatherproof enclosures should be derated by approximately
50% due to harsh environmental conditions.
10. Set power switch to the OFF position (Fig. 2b, pg. 4, Fig. 3b, pg. 5, Fig. 4b, pg. 6).
11. Connect devices to be powered to terminals marked [--- DC +] (Fig. 2c, pg. 4, Fig. 3c, pg. 5, Fig. 4c, pg. 6).
12. Connect optional stand-by battery to terminals marked [+ BAT --- ] battery leads included
(a separate enclosure is needed for batteries) (Fig. 2c, pg. 4, Fig. 3c, pg. 5, Fig. 4c, pg. 6).
Note: When batteries are not used, a loss of AC will result in a loss of output voltage.
13. Set power switch to the ON position (Fig. 2b, pg. 4, Fig. 3b, pg. 5, Fig. 4b, pg. 6).
14. Upon completion of wiring, secure enclosure door with latches and optional lock.
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock.
This installation should be made by qualified service personnel and should conform to all local codes
and in accordance with the National Electrical Code.
- 2 -­
DC Outdoor
LED Diagnostics:
Red (DC)
ON
ON
OFF
OFF
Green (AC)
ON
OFF
ON
OFF
Power Supply Status
Normal operating condition.
Loss of AC. Stand-by battery supplying power.
No DC output. Short circuit or thermal overload condition.
No DC output. Loss of AC. Discharged or no battery present.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
Terminal Identification:
Terminal Legend
--- DC +
+ BAT –
Function/Description
WayPoint-3 12VDC or 24VDC @ 2.5 amp continuous supply current.
WayPoint-5 12VDC or 24VDC @ 4 amp continuous supply current.
WayPoint-7 12VDC or 24VDC @ 6 amp continuous supply current.
Stand-by battery connections. Maximum charge rate 500mA.
Fig. 1
Suggested Locations
for Wiring Inlets
Bottom of Enclosure
DC Outdoor
- 3 -­
Fig. 2 - WayPoint-3
Fig. 2a
OPEN - 24VDC
CLOSED - 12VDC
OPEN - 24VDC
CLOSED - 12VDC
Fig. 2b
AC DC
OFF
ON
OFF
ON
5A 250V
L
G
N
--- BAT +
--- DC +
CAUTION
HIGH VOLTAGE
Fig. 2c
--- BAT +
- 4 -­
--- DC +
DC Outdoor
Fig. 3 - WayPoint-5
Fig. 3a
OPEN - 24VDC
CLOSED - 12VDC
OPEN - 24VDC
CLOSED - 12VDC
Fig. 3b
AC DC
OFF
ON
OFF
ON
5A 250V
L
G
N
--- BAT +
--- DC +
CAUTION
HIGH VOLTAGE
Fig. 3c
--- BAT +
DC Outdoor
--- DC +
- 5 -­
Fig. 4 - WayPoint-7 and WayPoint-7V
Fig. 4a
OPEN - 24VDC
CLOSED - 12VDC
OPEN - 24VDC
CLOSED - 12VDC
Fig. 4b
AC DC
OFF
ON
OFF
ON
5A 250V
L
G
N
--- BAT +
--- DC +
CAUTION
120VAC
Fig. 4c
--- BAT +
- 6 -­
--- DC +
DC Outdoor
Wall Mount Installation
1- Place unit at desired location and secure with mounting screws
(not included) (Fig. 5 and Fig. 5a, pg. 7).
Fig. 5
Fig. 5a
DC Outdoor
- 7 -­
Enclosure Dimensions (H x W x D):
13.31” (338.074mm) x 11.31” (287.274mm) x 5.59” (141.986mm)
11.32” (287.528mm)
8.00” (203.2mm)
13.32”
(338.328mm)
1.61”
(40.894mm)
5.60”
(142.24mm)
3.96”
(100.584mm)
12.75”
(323.85mm)
12.00”
(304.8mm)
13.50”
(342.9mm)
PADLOCK LATCH ATTACHED
WITH RIVETS (Ø 0.375” (9.52mm) PADLOCK EYE).
Ø 0.32 (8.128mm) MOUNTING HOLE
TYP. 4 PLACES
10.75” (273.05mm)
10.00” (254mm)
8.25” (209.55mm)
10-32 X 0.375” (9.525mm)
BRASS INSERT (X4)
10.25”
(260.35mm)
10-32 X 0.25” (6.35mm)
BRASS INSERT (X2)
MEMBER
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIWayPointDC_PL
I07K
DC Outdoor
- 8 -­
STAINLESS STEEL PIANO HINGE
Fig. 6
Altronix is not responsible for any typographical errors.