Power Systems Elliot Olsen Overview of Electric Utility System Definition of Primary Distribution Substations Feeder Configurations Primary Distribution Systems Protective Components Power Quality Underground vs. Pole Mounted Three stages: Generation, Transmission, Distribution Image Source: www.iaei.org Generation Coal, nuclear, renewable, etc. Output typically 50-1300 MVA @ 2-20 kV Generator step-up (GSU) transformer will increase voltage/decrease current to reduce losses during transmission Transmission Delivers energy from generators to distribution system Provides energy interchange among utilities Begins at a substation and includes everything up to the meter at customers’ premises. Divided into two areas: Primary: Distribution substation transformer Secondary: Distribution transformer customers’ meters distribution Image Source: www.osha.gov Transmission voltage (high) is stepped down to distribution voltage (low) Distribution power is output via feeders connected to distribution bus Substations are commonly constructed underground 7 Classes of primary voltages Class, kV Voltage, kV 2.5 2.4 5 4.16 8.66 7.2 15 12.47 13.2 13.8 25 22.9 24.94 34.5 34.5 50 46 15 kV is most common in the US Substation should be located near the center of the loads it serves N location min( Zi * di ) i 1 Typically a substation is between 1-30 miles from the furthest customer Loads should be supplied without undue voltage regulation and with standard equipment Substation design should allow for future expansion A substation failure or shutdown should not affect a large number of customers In an emergency, substations should be able to allow other substations to tie to them and vice versa Immediate output of a substation 3-Phase configured in 1 of 5 ways 4-Wire Y-connected, multi-grounded 4-Wire Y-connected, uni-grounded 3-Wire Y-connected, uni-grounded 3-Wire Δ-connected 3-Wire Y-connected, ungrounded Used in most distribution systems Substation is grounded via a 1 Ω impedance to limit fault currents Neutral is grounded at least 4 times every mile Second most popular configuration Popular in industrial settings Advantages of Y Greater feeder capacity ▪ Fewer substations are necessary ▪ Rural areas with long distances between consumers are easier to service Since the neutral wire is grounded at many points, voltage stresses on insulation is less Most devices used in existing Δ circuits can be reused Disadvantages of Y Higher phase-to-phase voltages only apply to the 3-phase main, not branches Harder to balance phases Fault currents are much higher in Y configurations Higher voltage and many grounds in a Y circuit may cause interference with communication circuits in parallel with power circuits Feeders are primarily designed by maximum voltage variation permissible at the farthest consumer The feeder has per unit impedance of Z and current I, meaning a voltage drop of IZ per unit length Voltage Regulation: Voltage at the receiving end of a line, with NoLoad and FullLoad conditions %VR 10% VR load | VL NoLoad | VL | | VL FullLoad FullLoad | | *100 +/- 5% of voltage source at the How to regulate the voltage? 1. Voltage regulators 2. Shunt capacitors 3. Choose a proper conductor ▪ If there is not significant loss in the line, other regulating methods may not be necessary Regulators maintain a constant voltage Image Source: Electrical Distribution Engineering, 3rd Ed. Used at substation and/or on feeders Voltage rise due to capacitors: VR IC X L Note: VR is not dependent on load However, low load will result in less voltage drop along the line, therefore, during low load times, capacitors are usually shut off Single-phase branch from a feeder main Each branch is again stepped down in secondary distribution for use by consumers Balancing Branch Loads Power systems work best when the loads on all three phases are equal Impedance and distance from substation are used to determine how to balance each phase N line _ impedance Z iL * d iL i 1 Economic Factors: Initial cost and upkeep Local government regulations Permissible voltage variations Mechanical feasibility Loads to be supplied Image Source: Electrical Distribution Engineering, 3rd Ed. 3 Possible configurations of distribution Radial Loop Primary Network Systems Feeders emanate radially from the substation Most commonly used configuration Typical in low-load-density areas Used where high reliability is important More protective devices are required to isolate faults along the feeder N.O. fuse N.O. N.O. Feeder conductors must be large enough to sustain entire load of loop Least common configuration Found only in downtown areas of large cities with high load densities Multiple interconnected substations Lightning Arrester: Limits surge voltages by providing a path to ground Also helps prevent equipment faults Image Source: www.osha.gov Image Source: www.lightningsource.com Similar to a circuit breaker… but they reclose Most SC faults are temporary and resolve themselves Tree branch shorts two phases, lines sway together in the wind, etc A recloser will open during a fault, then close to see if the fault went away Image Source: Brian Hayes, Flickr At initial fault detection, reclosers will open as quickly as possible Assumes a temporary fault will be cleared Subsequent openings will be delayed This allows persistent faults to be cleared by fuses downstream, which will isolate the fault to as few customers as possible IEEE 1100: “The concept of powering and grounding electronic equipment in a manner that is suitable for the operation of that equipment.” Factors degrading power quality: Grounding Surges Load Switching Harmonics And many more… The Power Quality pyramid reveals the most likely culprits of degraded power quality Image Source: Eaton, Power Distribution Systems Merits of overhead vs. underground lines Reliability ▪ Frequency of outages (# of power outages/year) ▪ Duration of outages (minutes/year a customer has no power) Cost Other factors Local perception Age of infrastructure Reliability 80% of faults in pole mounted systems are temporary faults Recall that temporary faults are caused by wind, tree branches, animals, etc. They do not occur in underground systems Source: Power Distribution Engineering Fundamentals Cost Installing underground systems is much more expensive than pole mounted Above ground, phase wires are insulated by air Insulation adds to costs of conductors, and more sophisticated equipment is needed Extra costs are usually offset by developers, who prefer aesthetics of underground systems Reliability Frequency of outages was 50% less for underground Duration of outages was 58% lower for overhead Cost 4 to 6 times more expensive to build new underground lines Cost to place existing overhead lines underground: $41 billion 125% rate increase ▪ 77% of SCE&G’s distribution system is overhead 1. 2. 3. 4. 5. 6. 7. J. Glover, M. Sarma, T. Overbye Power System Analysis & Design, 5th ed. Stamford, CT: CENGAGE Learning, 2012. A. Pansini Electrical Distribution Engineering, 3rd ed. Lilburn, GA: The Fairmont Press, 2007. J. Glover, “Electric Power Distribution,” Encyclopedia of Energy Technology and the Environment. New York: John Wiley & Sons, 1995. T. Gonen, Power Distribution Engineering. New York: Wiley, 1986. SCE&G, “Underground vs. Overhead Power Lines.” Eaton, “Power Distribution Systems.” 2011. M. Fard. (6 May 2011) “Lightning Arresters.” [Online]. Available: http://lightningsource.wordpress.com/